EXTERIOR MOISTURE CREATES INDOOR HUMIDITY, DEWPOINT & BIOAEROSOL INCREASES IN HEALTHY BUILDINGS
|
|
- Paul Spencer
- 7 years ago
- Views:
Transcription
1 EXTERIOR MOISTURE CREATES INDOOR HUMIDITY, DEWPOINT & BIOAEROSOL INCREASES IN HEALTHY BUILDINGS TJ Ryan 1, LW Whitehead 2, TH Connor 2 and KD Burau 2 1 School of Health Sciences, Ohio University, Athens, OH, USA 2 School of Public Health, University of Texas-Houston Health Sciences Center, Houston, TX, USA ABSTRACT Indoor environmental parameters and bioaerosols were studied in relation to exterior moisture events in healthy buildings. Significant differences between both relative humidity and dewpoint were observed when paired samples from wet and dry climatological conditions were compared (p<0.001). Relative humidity averaged almost 20 percent (7.2 scale points) higher indoors following rainfall. Bioaerosols determined during these climatological conditions were observed to remain elevated up to three days following heavy rainfall periods in building locations exhibiting increased humidity. Results indicate that heavy rainfalls can produce sustained indoor bioaerosol increases in healthy buildings. HVAC systems cannot control such high level, short-lived exterior moisture. These findings are discussed relative to HVAC system limitations, and bioaerosol concentration implications, in hot and humid climates. INDEX TERMS Indoor Air Quality, Bioaerosols, Relative Humidity, Moisture, Dewpoint INTRODUCTION The problematic role of fungal growth generating office or other non-industrial indoor air quality (IAQ) issues has been widely reported (Croft et al. 1986; Burge 1990; Harrison et al. 1992; Flannigan and Miller 1994; Crawford and Filip 1998; Hodgson et al. 1998; Ryan et al. 1998; Samimi 1998). Sick Building Syndrome (SBS) symptoms have been causally associated with Penicillium chrysogenum (Meyer et al. 1998), while others have found a significant correlation between increased Penicillium prevalence and SBS in school buildings involved in IAQ complaints (Cooley et al. 1998). There is therefore clear justification for increased attention to total bioaerosol concentrations when investigating certain IAQ complaints. The American Society of Heating, Refrigeration, and Air Conditioning Engineers (ASHRAE) has long recognized the role that outdoor to indoor vapor pressure differential plays in high humidity climates. Accordingly, it is currently recommended that moisture load attributable to diffusion through the building envelope be considered in the control of indoor air temperature and humidity (ASHRAE 1993). Control of relative humidity within ASHRAE acceptable ranges is dependent on thermal insulation, vapor barriers, proper sizing of the air conditioning system, and the use of reheat. In most applications climatological data averages Contact author ryant@ohio.edu 782
2 based on 2160 hours of winter data or 2928 hours of summer data are utilized to design HVAC systems to adequately control indoor air for the purposes of comfort and the reduction of mold and mildew (ASHRAE 1991). The impact of considerable exterior moisture events (such as heavy rainfall) on these operational goals appears to have been unappreciated. This project specifically studied the importance these relatively short duration events have on interior environmental measures and bioaerosol concentrations. METHODS Thirty (30) healthy buildings served by conventional HVAC systems employing reheat air conditioning for humidity control were selected for study. Indoor sampling locations were selected to maximize potential differences among both the environmental measures and bioaerosols collected at those locations. Specifically, paired samples, from a potentially moist site ("Wet") and a typically dry location ("Dry"), were collected from all facilities twice, during meteorologically defined Low (rain) and Hi (no rain) sampling periods (n=120). Hi periods were defined as all days of 0.1 inches or less of precipitation subsequent to at least a consecutive three day (72 hour) period of 0.1 inches or less of precipitation (i.e., dry periods began three days after the most recent rainfall of 0.1 inches or less). Low periods were defined as any 60 hour period commencing 12 hours following at least 0.5 inches of precipitation, inclusive (i.e., hours after the beginning of rainfall exceeding 0.5 inches in a 24 hour period). Actual on-site rainfall was verified with instruments atop one of the study buildings, as later confirmed from U.S. National Weather Service data. Environmental factors of room relative humidity (RH), and room temperature, were recorded for all areas; dewpoints were calculated from this data for all sample locations using standard formulae (NWS 1997). Temperature and relative humidity were assessed both indoors and outdoors. Accuracy of the direct reading probe was compared to a calibrated recording hygrometer, with readings within 2% of scale taken as acceptable. Culturable bioaerosol samples were collected with single stage impactor samplers. Five minute samples were collected indoors (sampled air volume m 3 ). Air was impacted into plastic petri plates containing 27 ml of media. Trypticase Soy Agar (TSA) was utilized for mesophilic fungi and total bacteria enumeration, and Inhibitory Mold Agar (IMA) was used for fungi enumeration. Three minute bioaerosol samples were also collected from outdoor locations each day facilities were sampled. Plates were grown out in fluorescent light at a room temperature of 22ºC (71ºF) in a standard microbiological laboratory. Plate counts were determined by the positive hole method (Andersen 1958). Counts were related to volume of air sampled in order to report colony forming units per cubic meter air sampled (CFU/m 3 ). Environmental measures of relative humidity and dewpoint were compared across climatological condition and building sampling location dichotomies using ANOVA. Tukey confidence intervals were computed to ensure acceptable overall significance levels when making a priori pairwise multiple comparisons. Descriptive point estimates and measures of variability for these bioaerosols were computed by climatological condition and location. 783
3 RESULTS Sampling was conducted over a 6 week period in the fall of 1997 (November 3 - December 16, 1997). A two-way ANOVA was performed on data for climatological conditions by sampling location within the building (Table 1). Results reveal that climatological category (Hi/Low) was the major cause for the differences in environmental parameters (p values ranged from < ), as opposed to sampling location category (Wet/Dry) results. Tukey s pairwise confidence intervals confirmed the importance that climatological category had in determining the differences seen. On average there was a 19% elevation (7.2% absolute scale difference) of mean relative humidity during climatological Low conditions compared with Hi conditions (two sample t-test, α=.05). Table 1. Two-way ANOVA: Climatological Conditions (Hi/Low) by Location (Wet/Dry) Relative Humidity Dewpoint P value Mean 95% CI P value Mean 95% CI Hi/Low <0.001 <0.001 Hi Hi Low Low Tukey s 95% CI: Tukey s 95% CI: Wet/Dry Wet Wet Dry Dry Tukey s 95% CI: Tukey s 95% CI: Significant Difference (α=0.05) Indoor environmental data from this period showed distinct differences between relative humidity and dewpoint according to climatological condition. Differences between climatological Hi/-- and Low/-- data were highly significant (p<0.001) for both relative humidity and dewpoint (two-tailed two sample t-test). Visible condensation problems at floor or wall surfaces were not seen owning to the high dry bulb temperatures of the indoor air and massive masonry construction of most of the facilities. Results of culturable bioaerosols are shown in Table 2. Significant differences (p=0.030) were indicated between Hi/Dry (GM=252 CFU/m 3 ) and Low/Wet (GM=494 CFU/m 3 ) conditions for mesophilic fungi and bacteria when means of the logs were tested (two-tailed two sample t-test). Differences for indoor fungi grown on IMA between Hi/Dry (GM=106 CFU/m 3 ) and Low/Wet (GM=235 CFU/m 3 ) were significant as well (p=0.020). 784
4 Table 2. Bioaerosol Results by Climate Condition and Sampling Location Condition/ Location mean CFU/m 3 median CFU/m 3 SD A GM B CFU/ m 3 GSD C Mesophilic Fungi and Bacteria ( TSA) Hi/Dry (n=30) * 2.3 Low/Wet (n=30) * IMA Grown Fungi Hi/Dry (n=30) Low/Wet (n=30) * Significant difference (p=0.030) Significant difference (p=0.020) A Standard Deviation B Geometric Mean C Geometric Standard Deviation Outdoor bioaerosol data were collected on all days that indoor bioaerosols were sampled. There were no significant differences between the means of logs of either outdoor IMA grown fungi (Hi and Low GM = 863 and 773 CFU/m 3, respectively; p=0.910) or outdoor mesophilic fungi and bacteria (Hi and Low GM = 1,176 and 941 CFU/m 3, respectively; p=0.770), by weather condition (α=0.05; data not presented). DISCUSSION ANOVA results definitively indicate that exterior rainfall events can result in moisture loading indoors. This finding is challenging to any notion that HVAC engineering setpoints are capable of maintaining precise interior relative humidity within tightly defined ranges in the hot and humid Gulf Coast region of the U.S. With indoor temperatures in non-industrial or office buildings typically maintained about 70 F (21 C), any significant elevation of the indoor dewpoint could bring temperature and dewpoint values close enough to result in localized condensation at surfaces. Those events, in turn, could potentially account for the microbial blooms found in this study. Results demonstrate that in office building occupancies interior relative humidity and bioaerosol concentrations vary in conjunction with exterior climatological events. It is rational to believe that increased indoor bioaerosol levels of the magnitude seen in this study, especially if caused by a toxigenic or highly allergenic microbial species, could be responsible for instances of SBS or Building Related Illness (BRI) (e.g., Legionnaires' Disease) under certain circumstances. While the indoor bioaerosol blooms seen in this study might conceivably be attributed to the introduction of outside air into the facilities, there were no significant differences between outdoor air concentrations of either mesophilic fungi and bacteria, or selective fungi, by weather condition. Furthermore, because of the low replacement air used in the facilities while in reheat configuration (typically less than 15%) and the relatively energy efficient windows and other openings present, mechanical introduction of outside contamination is not 785
5 believed to contribute to the concentration increases seen. It is most likely that the bioaerosol increases are due to interior microbial growth precipitated by increases in total interior moisture resulting from exterior moisture intrusion. CONCLUSIONS & IMPLICATIONS In the absence of IAQ complaints in any of the study buildings, they could be characterized as healthy. Results indicate that routinely encountered, short-lived climatological moisture events produce sustained indoor humidity and bioaerosol increases immediately following such events in healthy buildings. This study could be faulted for not characterizing the genera of bacteria and fungi detected. Given the ANOVA results the findings are significant enough to warrant further research on the ecological balance of the contaminants found. Conventional HVAC systems relying on variable air dampers or reheat air conditioning to limit indoor humidity may be unable to completely control interior moisture under exterior moisture loading conditions normally encountered in hot and humid climates. REFERENCES Andersen, AA New sampler for the collection, sizing, and enumeration of viable airborne particles. J Bacteriol 76, pp ASHRAE ASHRAE Handbook Applications, pp Atlanta: American Society of Heating, Refrigerating, and Air-Conditioning Engineers, Inc. AS HRAE ASHRAE Handbook Fundamentals, pp Atlanta: American Society of Heating, Refrigerating, and Air-Conditioning Engineers, Inc. Burge, HA Bioaerosols: prevalence and health effects in the indoor environment. J Allergy Clin Immunol 86(5), pp Coo ley JD, Wong WC, Jumper CA, et al Correlation between the prevalence of certain fungi and sick building syndrome. Occup Environ Med 55, pp Crawford GN, and Filip, G Hidden mold and concealed moisture sources. [abstract]. In: Abstracts. American Industrial Hygiene Conference and Exposition; 1998 May 9-15; Atlanta, Georgia. Fairfax (VA): American Industrial Hygiene Association, p. 41. Cro ft WA, Jarvis BB, and Yatawara, CS Airborne outbreak of tricothecene toxicosis. Atmos Environ 20(3), pp Flannigan B, and Miller JD Health implications of fungi in indoor environments - an overview. In: Samson RA, Flannigan B, editors. Health implications of fungi in indoor environments. Air Quality Monographs. Vol. 2. Amsterdam: Elsevier, pp Gravesen S Identification and prevalence of culturable mesophilic microfungi in house dust from 100 Danish homes. Allergy 33, pp Harrison J, Pickering CAC, Faragher EB, et al An investigation of the relationship between microbial and particulate indoor air pollution and the sick building syndrome. Resp Med 86, pp Hodgson MJ, Morey P, Leung W-Y, et al Building-associated pulmonary disease from exposure to Stachybotrys chartarum and Aspergillus versicolor. J Occup Environ Med 40(3), pp Meyer HW, Larsen FO, Jacobi HH, et al Sick building syndrome: Association of symptoms with serum IgE specific to fungi. Inflamm Res 47(suppl I), pp. S9-S10. National Weather Service, El Paso, Texas Moisture Conversions: Dewpoint and Wet- bulb from Relative Humidity. A vailable from: Accessed: November 14,
6 Reynolds SJ, Streifel AJ, and McJilton CE Elevated airborne concentrations of fungi in residential and office environments. Am Ind Hyg Assoc J 51(11), pp Ryan TJ, Eason T, and Stenvall H Unusual microbial contamination of a university rare book collection. [abstract]. In: Abstracts. American Industrial Hygiene Conference and Exposition; 1998 May 9-15; Atlanta, Georgia. Fairfax (VA): American Industrial Hygiene Association, p. 22. Samimi B Prevalence of Aspergillus versicolor in residential and commercial buildings with a history of water intrusion. In: Abstracts. American Industrial Hygiene Conference and Exposition; 1998 May 9-15; Atlanta, Georgia. Fairfax (VA): American Industrial Hygiene Association, p
Liabilities of Vented Crawl Spaces, Their Impacts on Indoor Air Quality in Southeastern U.S. Homes and One Intervention Strategy
Liabilities of Vented Crawl Spaces, Their Impacts on Indoor Air Quality in Southeastern U.S. Homes and One Intervention Strategy Jonathan Coulter 1 ABSTRACT This paper documents the influences vented crawl
More informationLiabilities of Vented Crawl Spaces And Their Impacts on Indoor Air Quality in Southeastern U.S. Homes
Liabilities of Vented Crawl Spaces And Their Impacts on Indoor Air Quality in Southeastern U.S. Homes Jonathan Coulter, Bruce Davis, Cyrus Dastur, Melissa Malkin-Weber and Tracy Dixon Advanced Energy,
More informationTuula Putus, M.D. Professor in Occupational Health Care and Occupational Medicine, University of Turku, Finland
Tuula Putus, M.D. Professor in Occupational Health Care and Occupational Medicine, University of Turku, Finland The concepts sick buildings and SBS (sick building syndrome) were introduced in the 70 ies
More informationMeasurements of Airborne Fungal and Endotoxin Levels in Water-Damaged Buildings
Measurements of Airborne Fungal and Endotoxin Levels in Water-Damaged Buildings Stella Manchun Tsai Chin S. Yang, Ph.D. Michael S. Crandall Member ASHRAE Member ASHRAE ABSTRACT Airborne fungi are often
More informationMicrobial Air Quality in a 50-year-old Middle School
Microbial Air Quality in a 50-year-old Middle School Benjamin Borgo and Mina Mostafavi * Biology Department, Skyline College, San Bruno CA August 2007 Accepted for publication Society for the Advancement
More informationHow To Interpret Laboratory Results for Airborne Fungal (Mould) Samples
How To Interpret Laboratory Results for Airborne Fungal (Mould) Samples By Jackson Kung u, PhD Mold & Bacteria Consulting Laboratories (MBL) Inc. 1020 Brevik Place, Unit 1A, Mississauga, ON L4W 4N7 Phone:
More informationCourse Agenda. Mold in Commercial Buildings: Overview of Mold Contamination in Buildings. Overview of Mold Contamination in Buildings
1 Course Agenda What is Mold What to look for Mold in Commercial Buildings: What you should know and look for Presented by David Krause, PhD, MSPH, CIH How to respond to a mold problem Why is mold considered
More informationFungal Assessment. Smith Recreation Community Centre 1019 Hwy 2A, Smith, Alberta
Top Q A DIVISION OF TOP QUALITY INSPECTIONS INC. Fungal Assessment Smith Recreation Community Centre 1019 Hwy 2A, Smith, Alberta 2012 P. O. B o x 8 3 0 2 4, E d m o n t o n, A B T 5 T 6 S 1 P h o n e :
More informationMolds and mildew are fungi that grow
Appendix C: Moisture, Mold and Mildew Molds and mildew are fungi that grow on the surfaces of objects, within pores, and in deteriorated materials. They can cause discoloration and odor problems, deteriorate
More informationCauses and Prevention of Symptom Complaints in Office Buildings: Distilling the Experience of Indoor Environment Quality Investigators
Causes and Prevention of Symptom Complaints in Office Buildings: Distilling the Experience of Indoor Environment Quality Investigators Mark J. Mendell, Richard C. Diamond, William J. Fisk Environmental
More informationVenice Library Humidity Study. for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205. Report April 13, 2015
for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205 Report April 13, 2015 Moses & Associates, Inc. 2209 NW 40 th Terrace, Suite A Gainesville, FL 32605 FL License EB-0003097
More informationMinimizing Indoor Mold Problems through Management of Moisture in Building Systems
Minimizing Indoor Mold Problems through Management of Moisture in Building Systems Position Document Approved by ASHRAE Board of Directors June 30, 2005 AMERICAN SOCIETY OF HEATING, REFRIGERATING AND AIR-CONDITIONING
More informationMEASURING THE EFFICACY OF MOLD REMEDIATION ON CONTAMINATED DUCTWORK
MEASURING THE EFFICACY OF MOLD REMEDIATION ON CONTAMINATED DUCTWORK JD Krause 1,2* and YY Hammad 1 1 College of Public Health, University of South Florida, Tampa, FL, USA 2 Indoor Air Solutions, Tampa,
More informationBiological Contamination in the HVAC System
Biological Contamination in the HVAC System by Chin S. Yang, Ph.D. P & K Microbiology Services, Inc. Cherry Hill, New Jersey The heating, ventilating, and air-conditioning system (HVAC) in a building is
More informationMOLD ASSESSMENT. Charles A. Bernazzani Elementary School 701 Furnace Brook Parkway Quincy, Massachusetts
MOLD ASSESSMENT Charles A. Bernazzani Elementary School 701 Furnace Brook Parkway Quincy, Massachusetts Prepared by: Massachusetts Department of Public Health Bureau of Environmental Health Indoor Air
More informationCHAPTER 3. BUILDING THERMAL LOAD ESTIMATION
CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION 3.1 Purpose of Thermal Load Estimation 3.2 Heating Load versus Cooling Load 3.3 Critical Conditions for Design 3.4 Manual versus Computer Calculations 3.5 Heating
More information49 th Annual Convention Society of Wood Science and Technology Newport Beach, California June 25, 2006
Remediation of Fungal Growth on Wood and Wood-based Building Materials: Challenges to the Forest Products Industry by Stephen L. Quarles University of California Cooperative Extension Richmond Field Station,
More informationTO TEST OR. NOT TO TEST Redefining the Role of Third-party Consultants CLEANING & RESTORATION A PUBLICATION OF THE RESTORATION INDUSTRY ASSOCIATION
CR & CLEANING & RESTORATION May 2014 Vol. 51 No. 4 $9.00 A PUBLICATION OF THE RESTORATION INDUSTRY ASSOCIATION TO TEST OR NOT TO TEST Redefining the Role of Third-party Consultants Underdog Leadership
More informationIEQ-15 Air Distribution System
AIM OF CREDIT To encourage and recognise the design and maintenance of air distribution systems that minimise the risk of particulate and microbial contamination to the internal air supply. CREDIT CRITERIA
More information9/16/2014. Michelle Peninger, BSMT, CIC Inova Health System
Michelle Peninger, BSMT, CIC Inova Health System Houston, Texas June 9, 2001 1 Tropical Storm Allison June 9, 2001 Memorial Hermann Hospital flooded Evacuated over 500 patients in 36 hours Loss of all
More informationAir- and Dustborne Mycoflora in Houses Free of Water Damage and Fungal Growth
APPLIED AND ENVIRONMENTAL MICROBIOLOGY, Nov. 2004, p. 6394 6400 Vol. 70, No. 11 0099-2240/04/$08.00 0 DOI: 10.1128/AEM.70.11.6394 6400.2004 Copyright 2004, American Society for Microbiology. All Rights
More informationWhole House Dehumidification for Occupant Comfort and Energy Savings
Downloaded from www.rsrews.com. Since 1968, RS Andrews has proudly served Atlanta's Heating, Air Conditioning & Plumbing Needs. Whole House Dehumidification for Occupant Comfort Energy Savings June 2009
More informationMold Management Plan Operations & Maintenance
Document #: SAFETY_015 Revision Date: October 4, 2010 Mold Management Plan Operations & Maintenance Developed by: Environmental Health & Safety Approved by: Associate VP of Facilities & Campus Services
More informationStachybotrys chartarum a mold that may be found in water-damaged homes
Stachybotrys chartarum a mold that may be found in water-damaged homes November 2000 Environmental Health Investigations Branch California Department of Health Services Stachybotrys chartarum ecology Stachybotrys
More informationResidential HVAC System Sizing
Residential HVAC System Sizing William P. Goss University of Massachusetts, Amherst, Massachusetts, USA Corresponding email: goss@acad.umass.edu SUMMARY Heating, ventilating and air-conditioning (HVAC)
More informationHVAC Costs. Reducing Building. Building owners are caught between two powerful forces the need to lower energy costs. By Stephen J.
Reducing Building HVAC Costs of site rec By Stephen J. Pargeter Building owners are caught between two powerful forces the need to lower energy costs and the need to meet or exceed outdoor air ventilation
More informationFacts Regarding Mold on Wood Structural Building Components
Facts Regarding Mold on Wood Structural Building Components Issues involving mold on building materials, whether during construction or in completed and occupied structures, have gained considerable media
More informationInfrastructure & Cities Sector
Technical Article Infrastructure & Cities Sector Building Technologies Division Zug (Switzerland), October 18, 2011 Saving Energy in a Data Center A Leap of Faith? New guidelines from ASHRAE (American
More informationIAQ - indoor ventilation Air contaminants Molds Requirements for growth Health effects Mold prevention - moisture EH&S mold checks & removal
Indoor Air Quality & Mold Class Spring 2012 Building Monitors Meeting Presentation Agenda IAQ - indoor ventilation Air contaminants Molds Requirements for growth Health effects Mold prevention - moisture
More informationOverview. Objective. Purpose. Hypothesis. Procedure
Detection of Indoor borne Fungal Contamination Through Examination of Building Heating, Ventilating and Conditioning (HVAC) s Hernando Perez, PhD, MPH Assistant Professor Department of Environmental and
More informationKEY ELEMENTS IN PREVENTING AND MITIGATING MOLD CLAIMS
KEY ELEMENTS IN PREVENTING AND MITIGATING MOLD CLAIMS By Jerome E. Spear, CSP, CIH Effective January 1, 2005, consultants who prepare mold management plans for buildings located in Texas must be licensed
More informationMoisture Control. It s The Dew Point. Stupid! Its not the humidity.
Moisture Control Its not the humidity. It s The Dew Point Stupid! Mike Schell EpiphanyTec Inc. Santa Barbara, CA mschell@epiphanytec.com 805 687-3175 Matching great technology to market need! Topics SHR
More informationHospital Application Guide. Cost-effective climate control for hospitals
Hospital Application Guide Cost-effective climate control for hospitals Munters is the world leader in dehumidification Munters is the largest manufacturer of dehumidifiers in the world. Since developing
More informationMold Questions and Answers Questions and Answers on Stachybotrys chartarum and other molds
Questions and Answers on Stachybotrys chartarum and other molds Questions and Answers 1. I heard about "toxic molds" that grow in homes and other buildings. Should I be concerned about a serious health
More informationENVIRONMENTAL MONITORING
ENVIRONMENTAL MONITORING Assessment and verification of the adequacy of the aseptic compounding environment is essential. Environmental monitoring programs are designed to promptly identify potential sources
More informationEnvironmental Monitoring
Environmental Monitoring Purpose of Environmental Monitoring Critical process within the pharmaceutical and biotechnology industries. Determines the microbial and particulate content of cleanroom air and
More informationBUREAU OF ENVIRONMENTAL HEALTH Emergency Response/Indoor Air Quality Program
BUREAU OF ENVIRONMENTAL HEALTH Emergency Response/Indoor Air Quality Program Use of Moisture Measuring Devices in Evaluating Water Damage in Buildings July 2007 The evaluation of mold colonization of building
More informationRegulations & Guidelines
Regulations & Guidelines Short History of Mold Standards Leviticus 13: 47-50, 14: 39-47 Initial assessment by priest; follow-up visit in 7 days If mold spreads to walls, tear out contaminated stones and
More informationMoisture and Mould Damage in Norwegian Houses
Moisture and Mould Damage in rwegian Houses Jonas Holme, Cand Scient, Research Scientist, PhD-fellow, SINTEF Building and Infrastructure, rway; jonas.holme@sintef.no and www.sintef.no/byggforsk Stig Geving,
More informationMold Remediation Practices
Lorman Educational Services Mold Remediation Practices Presented by: A. James Partridge, PE James Partridge Consulting, LLC 925 South Adams Road Birmingham MI 48009-7039 248.645.1465 voice 248.645.1590
More informationIndoor air quality monitoring made easy
Indoor air quality monitoring made easy with the Fluke 985 Particle Counter Application Note Introduction Energy savings is top of facilities owners agenda. HVAC system tends to be the largest contributor
More informationIndoor Air Quality- What You Need to Know
Indoor Air Quality- What You Need to Know Overview Indoor air quality (IAQ) concerns present ever-mounting problems to facility managers and health and safety personnel. From toxic mold to carbon dioxide
More informationConstruction Indoor Air Quality Management Plans for LEED. Matt Gregg, PE, LEED AP
Construction Indoor Air Quality Management Plans for LEED Matt Gregg, PE, LEED AP Agenda What is a Construction IAQ Management Plan? What are the LEED Requirements? What is the Mechanical Contractor s
More informationThe Facts About Mold. Operation Outreach
The Facts About Mold Operation Outreach Mold/IAQ Resources from AIHA More AIHA Operation Outreach Brochures: Do I Work In a Sick Building? Guidelines for Selecting an Indoor Air Quality Consultant Is Air
More informationPolyMaster Foam Insulation and Resistance to Mold PM Mold Statement RetroFoam is naturally resistant to mold growth, and does not contain cellulose or other fiber which will sustain mold growth. RetroFoam
More informationCadmus Environmental. 713.252.8549 Wendy@CadmusEnvironmental.com. Mold Inspection Report. Mold Inspection Report Example Page 1 of 12
Cadmus Environmental 713.252.8549 Wendy@CadmusEnvironmental.com Mold Inspection Report Mold Inspection Report Example Page 1 of 12 Background Information A mold inspection and assessment was conducted
More informationNIOSH Interim Recommendations for the Cleaning and Remediation of Flood-Contaminated HVAC Systems: A Guide for Building Owners and Managers
NIOSH Interim Recommendations for the Cleaning and Remediation of Flood-Contaminated HVAC Systems: A Guide for Building Owners and Managers Introduction During flooding, systems for heating, ventilating,
More informationIndoor Air Quality Issues for Hotels
Indoor Air Quality Issues for Hotels Chai chen Chao DEA 670 Spring, 2000 Thermal Control Relative Humidity Winter Temperature Summer Temperature 30% 68.5 F - 76.0 F 74.0 F - 80.0 F 40% 68.5 F - 75.5 F
More informationSEMI-QUANTITATIVE MOLD EXPOSURE INDEX PREDICTS BUILDING-RELATED RESPIRATORY SYMPTOMS
SEMI-QUANTITATIVE MOLD EXPOSURE INDEX PREDICTS BUILDING-RELATED RESPIRATORY SYMPTOMS JH Park *, PL Schleiff, MD Attfield, JM Cox-Ganser, K Kreiss National Institute for Occupational Safety and Health,
More informationAnswers to Your Questions from the Webinar
2008 Desert Aire and USA Swimming. Used by permission. Desert Aire & USA Swimming - Aquatics Webinar - Answers to Your Questions Answers to Your Questions from the Webinar Thank you for your interest in
More informationComponents HVAC General Standards HVAC Guidelines HVAC System Selection Life Cycle Cost Analysis
Components HVAC General System Selection Life Cycle Cost Analysis Outdoor Air Design Values Indoor Air Design Values Outdoor Air Ventilation Welding Ventilation Temperature Control Systems Ductwork HVAC
More informationNYU Safety Policy Manual
NYU Safety Policy Manual Page 1 of 6 Subject: Mold Prevention, Assessment, and Remediation Program Policy No. 167 ISSUE DATE REPLACES ORIGINATOR APPLICATION NYU Washington Square Campus PURPOSE The purpose
More informationTHE EFFECTS OF CLEANING ON CONCENTRATIONS OF SURFACE DUST AND AIRBORNE PARTICLES
THE EFFECTS OF CLEANING ON CONCENTRATIONS OF SURFACE DUST AND AIRBORNE PARTICLES E Pesonen-Leinonen Dept. of Agricultural Engineering and Household Technology, University of Helsinki, Finland ABSTRACT
More informationMicrobiological Events After a Fire in a High-rise Building
Indoor Air 1993, 3: 354-360 Copyright Ii': Munksgaard 1993 Primed in Denmark all rights l"cscrvcd Indoor Air ISSN 0905-6947 Microbiological Events After a Fire in a High-rise Building Philip R. Morey p
More informationINVESTIGATION OF INDOOR AIR QUALITY PROBLEMS IN UNIVERSITY OFFICES WITH A QUESTIONNAIRE
INVESTIGATION OF INDOOR AIR QUALITY PROBLEMS IN UNIVERSITY OFFICES WITH A QUESTIONNAIRE Maneerat Ongwandee a, Namphung Dungkokkruad b a Faculty of Engineering, Mahasarakham University, Mahasarakham 44150,
More informationUNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01
GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per
More informationNatatorium Building Enclosure Deterioration Due to Moisture Migration
Buildings 2012, 2, 534-541; doi:10.3390/buildings2040534 OPEN ACCESS buildings ISSN 2075-5309 www.mdpi.com/journal/buildings/ Case Study Natatorium Building Enclosure Deterioration Due to Moisture Migration
More informationCertificate of Mold Analysis
, Tel: (954) 384-4446 Fax: (954) 384-4838 Toll Free: 800-427-0550 AIHA Lab ID # 163230 Prepared for: Phone Number: (800) 427-0550 Fax Number: (555) 555-5555 Email Address: Test Location: prolabinc@gmail.com
More informationCarson Dorn, Inc. December 18, 2012. Patrick Holmes Associate Manager Juneau I, LLC 645 G Street, Suite 100-604 Anchorage, AK 99501. Dear Mr.
Carson Dorn, Inc. 712 West 12th Street Juneau, Alaska 9981 December 18, 212 Patrick Holmes Associate Manager Juneau I, LLC 645 G Street, Suite 1-64 Anchorage, AK 9951 Dear Mr. Holmes, The renovation of
More informationWebinar Questions and Answers. Mold and Moisture Control in Schools: Potential Health Effects and Safe Clean-Up Practices
Webinar Questions and Answers Mold and Moisture Control in Schools: Potential Health Effects and Safe Clean-Up Practices Q: If a school wanted to set up a preventive program for mold and moisture, what
More informationJoseph Laquatra Cornell University
Joseph Laquatra Cornell University Animals get displaced during floods May enter homes If there is standing water in the home: Turn off power from a dry location if possible Don t turn power off or use
More informationTHE IC Y N E N E AD V A N T A G E
THE IC Y N E N E AD V A N T A G E APP L I C A T I O N CA S E ST U D Y : CO M M E R C I A L BUILDING IN S U L A T I O N Condensation Control with ICYNENE LD-C-50 Synopsis: Icynene solved the condensation
More informationEvaluation of Microbial Growth and Survival on Construction materials treated with Anabec NewBuild 30
Evaluation of Microbial Growth and Survival on Construction materials treated with Anabec NewBuild 30 Absar Alum, Ph.D. Department of Civil and Environmental Engineering Arizona State University Tempe,
More informationMold prevention makes sense...
Mold prevention makes sense... MOLD-RAM makes it easy. The trusted chemistry found in MOLD-RAM delivers long-term surface mold and mildew prevention. Use it with confidence on wood, wallboard, concrete
More informationPEOSH. Indoor Air Quality Training for Asthma-Friendly Schools Part I PEOSH Indoor Air Quality Standard Overview. Eric Weren, MSIH
PEOSH Indoor Air Quality Training for Asthma-Friendly Schools Part I PEOSH Indoor Air Quality Standard Overview Eric Weren, MSIH Public Employees Occupational Safety and Health Unit IAQ Asthma-Friendly
More informationHousing Fact Sheets. Moisture Condensation at the Windows
Moisture Condensation at the Windows Housing Fact Sheets This fact sheet discusses the causes of and remedies for wintertime condensation problems that occur on windows, glass, and other glazing materials
More informationPERCENT OUTDOOR AIR (%OA) CALCULATION AND ITS USE
PERCENT OUTDOOR AIR (%OA) CALCULATION AND ITS USE APPLICATION NOTE TI-138 TSI s IAQ-CALC TM Indoor Air Quality Meter and TH-CALC TM Thermohygrometer calculate Percent Outdoor Air (%OA). In order to take
More informationLack of humidity control during the long construction period of this custom home resulted in staining and mushroom growth on the oak beams
Note: This document has been divided into several sections in order to suit the limitations of the website. The Disclaimer located on page one of the OAA Mould Control Practice Guide applies to each section
More informationCertificate of Mold Analysis
CHICAGO INSPECTION AGENCY 815 N SCHOOL ST PROSPECT HEIGHTS, IL 60070 Certificate of Mold Analysis Prepared for: CHICAGO INSPECTION AGENCY Phone Number: (847) 459-9387 Fax Number: (847) 459-9443 Project
More informationFIELD TESTING SERVICES
FIELD TESTING SERVICES Chris Leach Director of Testing Baton Rouge, Louisiana Destin, Florida Scott Leach David Nichols Field Testing Representative Field Testing Representative 17485 Opportunity Avenue
More informationEnvironmental Monitoring of Clean Rooms
Environmental Monitoring of Raul Duarte President DDK Scientific, Corp. Copyright DDK Scientific, Corp. 2008, 2009, DDK Scientific, Corp. Proprietary A manufacturing facility for pharmaceutical products
More informationComparison of Analytical Methods for Evaluating Mold in Carpet Dust
Comparison of Analytical Methods for Evaluating Mold in Carpet Dust R. Rottersman, MS, CIH & G. Crawford, CIH Boelter & Yates, Inc. Park Ridge, IL P. Fallah, PhD EMLab San Diego, CA Carpet & Indoor Mold
More informationHETA 86-421-1956 NIOSH INVESTIGATORS: Charles Bryant, M.S., C.I.H.
This Health Hazard Evaluation (HHE) report and any recommendations made herein are for the specific facility evaluated and may not be universally applicable. Any recommendations made are not to to be considered
More informationWhy Measure Carbon Dioxide Inside Buildings? By Rich Prill, Washington State University Extension Energy Program
Why Measure Carbon Dioxide Inside Buildings? By Rich Prill, Indoor air quality Workers and students spend about half their waking hours at work or school. Therefore, maintaining adequate indoor air quality
More informationOld Dominion University Mold Management Plan
OFFICE OF ENVIRONMENTAL HEALTH AND SAFETY 5255 Hampton Blvd. Spong Hall, suite 2501 Norfolk, Virginia 23529 Phone: (757) 683-4495 Fax: (757) 683-6025 Occupational Safety & Health Environmental Health Laboratory
More informationTHE IC Y N E N E AD V A N T A G E
THE IC Y N E N E AD V A N T A G E APP L I C A T I O N CA S E ST U D Y : Insulating a Metal Building for Air Sealing/ Energy Efficiency Synopsis: Twice as effective at air sealing versus conventional insulation
More informationSpecifications for Removal and Replacement of Water Damaged/Mold Impacted Materials
Specifications for Removal and Replacement of Water Damaged/Mold Impacted Materials Park Potomac Place 12500 Park Potomac Avenue Potomac, Maryland 20854 KEM Project # 21703 Prepared for: Park Potomac Place
More informationMold, Mildew, Fungi What s the Difference? Mold: The Good, the Bad and the Ugly
CEILING SYSTEMS Mold is receiving more attention within the construction industry than ever before. One reason is that it is becoming an increasingly visible subject in the media. Another is an increased
More informationNew Protocol for the Assessment and Remediation of Indoor Mold Growth
New Protocol for the Assessment and Remediation of Indoor Mold Growth Ed Light 1,*, Roger Gay 1 and James Bailey 1 1 Building Dynamics, LLC, Ashton MD (USA) *Corresponding email: ELight@building-dynamics.com
More informationGuidelines for Mold Remediation (Removal)
Guidelines for Mold Remediation (Removal) Indoor mold growth, water damage, or musty odors should be addressed quickly. Removing mold growth and correcting the underlying cause of water accumulation can
More informationSpecification. Indoor Air Quality Management
GREENGUARD Environmental Institute 2211 Newmarket Parkway, Suite 110 Marietta, GA 30067 1.800.427.9681 Specification Indoor Air Quality Management This Master Specification section is intended for use
More informationCONDENSATION. Section Break (Next Page)
CONDENSATION Elimination of condensation on or within walls and floors is as important as reducing the heat loss through the wall or floor. In addition to the moisture damage caused to buildings by condensation,
More informationA COMPARISON OF SAMPLING METHODS FOR DETECTING FUNGAL CONTAMINANTS IN CARPETS. Joe C. Spurgeon Daniel W. Bridge Marshall E. Krotenberg.
A COMPARISON OF SAMPLING METHODS FOR DETECTING FUNGAL CONTAMINANTS IN CARPETS Joe C. Spurgeon Daniel W. Bridge Marshall E. Krotenberg January, 2006 ( 2 ABSTRACT The purpose of the current study was to
More informationRadford University. Indoor Air Quality Management Plan
Radford University Indoor Air Quality Management Plan Spring 2015 Introduction Concerns with Indoor Air Quality (IAQ) have increased since energy conservation measures were instituted in office buildings
More informationCritical for healthy indoor air quality.
feeling clammy? basement mold? Critical for healthy indoor air quality. property damage? musty odors? dust mites? Indoor air quality issues? High moisture levels can result in physical discomfort, increased
More information*Trademark of The Dow Chemical Company A business unit of The Dow Chemical Company and its subsidiaries Copyright 2003 The Dow Chemical Company.
Dow Chemical is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned on completion of this program will be reported to CES Records for AIA members.
More informationImpact of Infiltration on Heating and Cooling Loads in U.S. Office Buildings
Impact of Infiltration on Heating and Cooling Loads in U.S. Office Buildings 1 Steven J. Emmerich, 1 Andrew K. Persily, and 2 Timothy P. McDowell 1 Building and Fire Research Laboratory, National Institute
More informationInnovent LASER Packaged Fresh Air Conditioning Units
LASER Latent And Sensible Energy Reduction Latent And Sensible Energy Reduction For Outside Air Innovent LASER Packaged Fresh Air Conditioning Units Innovent LASER units provide both sensible and latent
More informationWATER DAMAGE INVESTIGATION. Massachusetts Department of Public Utilities 1 South Station Boston, Massachusetts
WATER DAMAGE INVESTIGATION Massachusetts Department of Public Utilities 1 South Station Boston, Massachusetts Prepared by: Massachusetts Department of Public Health Bureau of Environmental Health Indoor
More informationMold and mold spores
Mold and mold spores Mold and mold spores are everywhere around us and have always been a part of our environment. The air we breath is a virtual jungle of fungal spores. We routine encounter mold spores
More informationSafety Policy Manual Policy No. 112
Policy: Mold Prevention, Assessment and Remediation Program Page 1 of 9 APPLICATION NYU Langone Medical Center (NYULMC) POLICY SUMMARY NYULMC is committed to protecting employees, patients, and visitors
More informationElement D Services Heating, Ventilating, and Air Conditioning
Load Calculation Criteria PART 1 - GENERAL 1.01 OVERVIEW A. This section includes requirements for calculating HVAC cooling and heating loads. B. Load calculations must be performed in accordance with
More informationHow To Prevent And Manage A Flood And Mold
Flood Response and Mold Prevention Program Prepared by the Berea College Department of Environmental Health and Safety Revised May 2010 Contents I. Introduction II. III. IV. Flood and Mold Hazards Roles
More informationControlling Condensation On CWP Insulation BY ED LIGHT, MEMBER ASHRAE; JAMES BAILEY, P.E., MEMBER ASHRAE; AND ROGER GAY
This article was published in ASHRAE Journal, Decemeber 2014. Copyright 2014 ASHRAE. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically or in paper form without
More informationDehumidification Frequently Asked Questions
Dehumidification Basics Why do you want to keep indoor Rh between 30-60%? ASHRAE recommends keeping the relative humidity in a home between 30-60% to limit the effects of many unwanted conditions and harmful
More informationCENTER FOR ENVIRONMENTAL HEALTH Emergency Response/Indoor Air Quality Program
CENTER FOR ENVIRONMENTAL HEALTH Emergency Response/Indoor Air Quality Program Guidance Concerning Remediation and Prevention of Mold Growth and Water Damage in Public Schools/Buildings to Maintain Air
More informationGenett Group, Inc. Genett Group, Inc. Anti Microbial Technology. Hospitality Schools Hospitals Construction Remediator Assessor
Genett Group, Inc. 1515 FEDERAL HIGHWAY BOCA RATON, FL 33432 561 392 6176 Genettgroup.com Hospitality Schools Hospitals Construction Remediator Assessor Anti Microbial Technology Clean Room Antiseptic
More informationE-mail: m-skaria@tamu.edu. http://primera.tamu.edu/kcchome/faculty/ms.htm. Moisture Challenges & Solutions: Proactive Construction Strategies
E-mail: m-skaria@tamu.edu http://primera.tamu.edu/kcchome/faculty/ms.htm Moisture Challenges & Solutions: Proactive Construction Strategies 62 nd Annual Convention of the International Builders Show Orange
More informationMold Response and Remediation Plan
1.0 Policy Statement The University of New Haven has developed a mold response and remediation plan in accordance with best practices set forth by the Environmental Protection Agency (EPA), Occupational
More informationResidential HVAC Load Sizing Training October 14, 2015. David Kaiser Green Code Plan Reviewer
Residential HVAC Load Sizing Training October 14, 2015 David Kaiser Green Code Plan Reviewer DCRA - Green Building Division Regulations of green codes including: Green Building Act Green Construction Code
More information