Standard Specification K105 Water Reticulation
|
|
|
- Milo Ryan
- 9 years ago
- Views:
Transcription
1 Standard Specification K105 Water Reticulation INDEX K105.1 SCOPE OF WORK 3 K105.2 STANDARDS 3 K105.3 MATERIALS 3 K Pipes and Fittings 3 K Storage and Handling 4 K Bedding and Haunching 4 K Backfill 4 K Concrete 4 K Valves, Hydrants and Covers 5 K105.4 EXCAVATION 5 K General 5 K Trenching 6 K Dewatering 6 K Storage and Disposal of Material 6 K105.5 LOCATION OF PIPES, VALVES, HYDRANTS ETC 6 K105.6 CONNECTION TO EXISTING MAINS 6 K105.7 PIPE LAYING, JOINTING AND BACKFILLING 6 K Trench Foundation 6 K Bedding 7 K Laying 7 K Jointing 7 K Haunching 7 K Backfilling 7 K Cutting of Pipes 7 K Cables in Common Trench 8 K Property Connections 8 K Ends of Pipework 8
2 K105.8 VALVES AND HYDRANTS 8 K105.9 THRUST AND ANCHOR BLOCKS 8 K INDICATOR POSTS 8 K INSPECTIONS 9 K TESTING 9 K Cost of Testing 9 K Testing of Bedding, Haunching and Backfill Material 9 K Pipeline Inspection and Testing 9
3 K105.1 SCOPE OF WORK This section includes the supply of materials, equipment, labour and services necessary for the construction of water reticulation. This specification is the same as the Metropolitan Standard Specification Part 5 JUNE 1995 Water Reticulation except for the items written in bold and italic. K105.2 STANDARDS The following Australian Standards and Standard Drawings are referred to: Australian Standards AS 3578 AS 3579 AS 4087 AS 3725 AS AS 2638 AS 2280 AS 2033 AS 2032 AS 1724 AS 1718 AS 1646 AS 1628 AS 2977 AS 1460 AS 1432 AS 1289 Standard Drawings MSD 1-01 MSD 5-01 MSD 5-02 MSD 5-03 MSD 6-02 MSD 6-03 MSD 6-04 MSD 6-06 K105.3 MATERIALS Cast Iron Non-Return Valves for General Purposes Cast Iron Wedge Gate Valves for General Purposes Metallic Flanges for Waterworks Purposes Loads on Buried Concrete Pipes National Plumbing and Drainage Code - Water Supply Cast Iron Sluice Valves for Waterworks Purposes Ductile Iron Pressure Pipes and Fittings Installation of Polyethylene Pipe Systems Code of Practice for Installation of UPVC Pipe Systems Grey Cast Iron Pressure Pipes and Fittings with Bolted Gland Joints Copper Alloy Screw Down Pattern Taps Rubber Ring Joints for Water Supply Sewerage and Drainage Purposes Copper Alloy Gate Valve and Non-Return Valves for use in Water UPVC Pipes and Fittings for Pressure Applications-Compatible with Cast Iron Fittings Fittings for use with Polyethylene Pipes Copper Tubes for Plumbing, Gasfitting and Drainage Applications Methods for Testing Soils for Engineering Purposes Service locations (urban subdivisions) Fire hydrant, sluice and scour valve installation details Property connection details - water Thrust block details DICL pipe - installation details UPVC pipe - installation details Copper and polyethylene pipe - installation details Anchor Blocks K Pipes and Fittings Pipes and fittings shall comply with the relevant Australian Standards and type of pipes used in the Contract shall be as shown on the Drawings unless otherwise approved by the Superintendent. Fittings for polyethylene pipework shall be brass of a type approved by the Superintendent. 3 of 9
4 K Storage and Handling Materials shall be stored and handled in such a manner necessary to prevent their damage and deterioration. The Contractor shall employ adequate means to safely handle pipes, fittings and other materials. K Bedding and Haunching Pipe bedding and haunching material will depend on the type of pipe installed as shown in the Standard Drawings MSD 6-01 to MSD It shall be clean sand, gravel or crushed rock, free from organic matter and clay lumps and conform with the grading given in Table K Pipe bedding material shall also have a sand equivalent of at least 60. Table K AS Sieve (mm) Percentage Passing By Mass Where referred to on the Standard Drawings alternative bedding material may be fine crushed rock in accordance with Clause K (c). K Backfill (a) Select Fill Select Fill shall comply with the requirements of AS 3725, Section 4, generally being sands or gravels or sand and gravel mixtures with fines of low plasticity obtained from excavation of the pipe trench or elsewhere with a particle size not greater than 75 mm. (b) Ordinary Fill Shall comply with the requirements of AS 3725, Section 4, being material obtained from excavation of the pipe trench or elsewhere and containing not more than 20 per cent by mass of stones with a size between 75 mm and 150 mm and none larger than 150 mm. (c) Fine Crushed Rock Fine crushed rock shall be material complying with the requirements of aggregate used for basecourse construction in accordance with the DIER specification R40 Pavement base and subbase. K Concrete Concrete for minor concrete structures shall be in accordance with the DIER specification R81, Minor Concrete Structures. 4 of 9
5 K Valves, Hydrants and Covers (a) Sluice Valves Sluice valves shall be fitted with a C.I. cap and comply with AS Cast Iron Sluice Valves for Waterworks Purposes. They are to be class 16 resilient seated and powder coated. They shall have non-rising spindles forged from high tension bronze with inside screw thread. Spindle nuts shall be gun metal. Valves shall open with an anti-clockwise rotation. (b) Gate Valves Gate valves shall comply with AS 1628, Copper Alloy Gate Valves for General Purposes or AS Cast Iron Wedge Gate Valves for General Purposes and shall have a nonrising stem and hand wheel. (c) Fire Hydrants Hydrant risers shall be 100 mm diameter powder coated. Hydrant is to be spring loaded bayonet type, powder coated. (d) Non-return and Air Valves Valves shall be from an approved manufacturer and comply where applicable with AS Cast Iron Non-Return Valves for General Purposes or AS Copper Alloy Gate Valve and Non-Return Valves for use in Water. (e) Property Connections Water property connections to be fitted with gate valve to AS1628 and approved dual check valve, install in a jumbo size PVC meter box, (meter not required except for commercial properties). Refer to MSD 5-02A. (f) Valve and Hydrant Covers Valve and hydrant covers shall be to the requirements of the Superintendent. (g) Pressure Relief and Reducing Valves Pressure relief and reducing valves shall be subject to the approval of the Superintendent. (h) Fastenings All bolts, nuts and washers to be galvanized. All fastenings to be lagged in Denso tape and shall be subject to the approval of the Superintendent. K105.4 EXCAVATION K General Prior to excavation the Contractor shall note all existing surface features and locate all underground services. 5 of 9
6 K Trenching Trenches shall be excavated to the lines and levels shown on the Drawings with allowance being made for bedding. The dimensions of the trench shall comply with the relevant Standard Drawing. The Contractor shall excavate such chambers or recesses as are necessary to enable joints to be made, and shall trim the trench bottom so as to give even bedding to the pipe. The cost of such excavation will be deemed to be included in the schedule rate for laying and jointing. The base of the excavated trench shall be trimmed neat and uniform for its full length. Boulders, roots and any other hard objects in the bottom of the trench shall be removed, soft areas in the bottom of the trench shall be taken out and filled to grade level with approved bedding material and compacted. At any time the length of open trench shall not be more than 120 metres. The Contractor shall maintain all trenches in a safe condition for protection of people and property. The Contractor shall notify the Department of Tasmania - Development and Resources of any excavation over 1.5m deep and be responsible for carrying out the instructions of its officers. K Dewatering During the progress of drainage works, the Contractor shall provide for effective diversion and disposal of surface and ground water and shall be responsible for all damage to any portion of the works or surrounding properties due to inadequate drainage diversion of dewatering equipment. K Storage and Disposal of Material Excavated material not required or not suitable for the works shall be removed from the site. No excavated material shall be placed against any fence or wall without the written consent of the owner and the approval of the Superintendent. Material shall be placed a minimum of 1.0 m clear of the edge of the trench. Excavated materials which are to be reused shall be stockpiled separately on site. K105.5 LOCATION OF PIPES, VALVES, HYDRANTS ETC All pipes, valves, hydrants etc. shall be located as shown on the Drawings unless otherwise approved by the Superintendent. K105.6 CONNECTION TO EXISTING MAINS Arrangements shall be made with the Kingborough Council for connection to existing mains. K105.7 PIPE LAYING, JOINTING AND BACKFILLING K Trench Foundation The trench foundation shall be finished to the approval of the Superintendent prior to placing of the bedding material. 6 of 9
7 K Bedding Bedding shall be compacted bedding material complying with Clause and placed in accordance with the relevant Standard Drawing. Compaction shall be to 95 per cent standard compaction in accordance with AS K Laying All pipes shall be laid straight and shall be free from dirt and foreign matter and in good condition and laid with manufacturing works visible. Pipes and fittings shall be laid with all branches, valves, fireplugs, bends and closer pipes in the positions shown on the Drawings or as directed. Detector tape shall be laid 200mm above all pipes. All DICL pipes are to have plastic sleeving unless otherwise directed by the Superintendent. K Jointing Jointing of pipes shall be in accordance with the manufacturers' specifications. K Haunching Haunching shall be material complying with Clause K placed in accordance with the relevant Standard Drawing. Material shall be well tamped to the satisfaction of the Superintendent. K Backfilling Backfilling material shall be as shown on the relevant Standard Drawing and shall be compacted in layers not exceeding 150 mm thick when compacted. The degree of compaction shall depend on the location of the trench. For trenches clear of trafficked areas the layers shall be compacted to a minimum density of 95 per cent standard compaction in accordance with AS For trenches under trafficked areas the layers shall be compacted to comply with the pavement requirements as shown in Table K Pavement Layer Sub-grade Sub-base Base Table K Characteristic Density in accordance with AS % standard compaction 95% modified compaction 98% modified compaction The ground surface shall be reinstated to its original condition or as shown on the Drawings and to the satisfaction of the Superintendent. K Cutting of Pipes Where pipes are cut the ends shall be left neat and regular. 7 of 9
8 K Cables in Common Trench Where services are laid in a common trench the trench size, depth and backfill shall be in accordance with requirements of the relevant authority. K Property Connections Property connection points for house connections shall be laid in accordance with the Standard Drawings and located as shown on the Drawings. K Ends of Pipework The open ends of all pipework shall be kept covered to prevent dirt, stones and other debris from entering. K105.8 VALVES AND HYDRANTS Valves, air valves, hydrants and covers shall be installed as shown on the Drawings. K105.9 THRUST AND ANCHOR BLOCKS The Contractor shall construct thrust and anchor blocks as required at bends, tees, dead ends and valves. The concrete shall conform to DIER specification R81 Minor Concrete Structures. Thrust and anchor blocks shall be seated onto solid ground against which the thrust is to be taken and anchor blocks shall extend into the trench wall for a depth of 150 mm as shown in the Standard Drawings unless otherwise directed by the Superintendent. K INDICATOR POSTS The Contractor shall supply and erect approved reinforced concrete indicator posts for all sluice valves, gate valves, air valves, scour valves and hydrants. Indicator posts shall be in accordance with the Standard Drawings and be set vertically against the property line (or elsewhere as directed) so that a line from the centre of the post to the fittings to be indicated is at right angles to the principal face of the post. Posts shall be painted with two coats of approved paint. Sluice valve posts shall be painted blue and fire plug posts shall be yellow. Posts shall be marked with the designating letters 'S.V.' (indicating sluice valve) or 'F.P.' (indicating fire plug) and figures denoting the distance in metres from the indicator post to the fitting shall be indicated. Figures and letters shall be neatly painted with approved black and red paint respectively and shall be correctly proportioned and not less than 75 mm high. In addition the kerb shall be marked and painted with the appropriate colours and letters and a two-way blue reflective raised pavement marker is to be fixed in the centre of the roadway adjacent to hydrants as per IMEA Fire Hydrant Guidelines. 8 of 9
9 K INSPECTIONS K105 - WATER RETICULATION AUGUST 2011 Unless otherwise required by the Superintendent inspections shall be arranged at the following stages of the work: (a) (b) (c) (d) (e) (f) Completion of trench excavation prior to placement of bedding material. Completion of pipe laying prior to any backfilling. Stages of backfilling. Testing of pipelines. Completion of work at Practical Completion. Final inspection after Defects Liability Period. Twenty four (24) hours notice is required for any of the above inspections. Work shall not proceed unless each stage of work has been inspected and passed by the Superintendent. K TESTING K Cost of Testing All tests required by the Superintendent shall be at the Contractor's expense. K Testing of Bedding, Haunching and Backfill Material The Superintendent may request a sample of bedding or backfill material to be taken and tested by registered N.A.T.A. testing laboratory in order to determine whether the material complies with this specification. Any material which is found not to comply with the requirements shall not be used for bedding or backfill. K Pipeline Inspection and Testing (a) Flushing The pipeline shall be flushed clean prior to testing. (b) Pipeline Testing All lines shall be tested in the presence of the Superintendent to a pressure of 1,500 kpa in accordance with the appropriate Australian Standard. Each line shall be tested after it has been laid and jointed and sufficient filling has been placed over the centre of each pipe to hold it in position except at the joints. No line shall be tested less than forty eight (48) hours after construction of all thrust blocks and anchors. The Contractor shall provide a 20 mm tapping and ferrule tap or other suitable approved means for connecting the line to be tested. Such tapping shall be provided, where directed, for each section of water main to be separately tested. 9 of 9
SPECIFICATION FOR PIPE SUBSOIL DRAIN CONSTRUCTION
SPECIFICATION FOR PIPE SUBSOIL DRAIN CONSTRUCTION 1. SCOPE Pipe subsoil drains shall be constructed in accordance with this specification and in conformity with the lines, grades and cross-sections shown
EXHIBIT "A. Technical Specifications for Water and Sewer Service Lines
EXHIBIT "A Technical Specifications for Water and Sewer Service Lines Water and Sewer Line Bedding and Backfill: Drawings show cross-section of trench, pipe laid on top of 6" min. bedding material, bedding
3. Contractor shall ensure that all permits are obtained prior to any construction. Contractor shall be responsible for all utility fees.
The following shall serve as the minimum requirements for contractors performing work in relation to the Authority s potable water and sanitary sewer system(s), appurtenances and service connections. General:
A. Contractor shall furnish, to the Engineer, all materials certifications available from the manufacturer for all required materials.
PART 1 GENERAL 1.1 SCOPE A. This item shall include the work necessary for the installation of storm sewer line construction. B. Reference Section 3800 Trenching and Backfill and the General Conditions,
The Manitoba Water Services Board SECTION 022180 Standard Construction Specifications PIPE EXCAVATION, BEDDING AND BACKFILL Page 1 of 11
Page 1 of 11 Part 1 General 1.1 DESCRIPTION OF WORK.1 The work described herein shall consist of the excavation of trenches (or excavation of tunnels); the supply and placing of bedding and backfill materials;
SECTION 15 AIR RELEASE VALVE ASSEMBLIES. 15-1 General
SECTION 15 AIR RELEASE VALVE ASSEMBLIES 15-1.01 Scope 15-1 General This section describes the requirements for furnishing and installing Air Release Valve Assemblies of the size and type shown on the plans,
SECTION 55 PIPE FOR STORM DRAINS AND CULVERTS (FAA D-701)
SECTION 55 PIPE FOR STORM DRAINS AND CULVERTS (FAA D-701) 55-1 GENERAL The Contractor shall perform all work required by the plans for construction of pipe for storm drains, precast polymer trench drains
The work of this Section includes furnishing and installing Reinforced Concrete Pressure Pipe as shown on the Drawings and as specified.
Section 33 0200- Page 1 of 4 PART 1 - GENERAL 1.1 DESCRIPTION OF WORK The work of this Section includes furnishing and installing Reinforced Concrete Pressure Pipe as shown on the Drawings and as specified.
LS 2540 SEWER LATERALS AND INSPECTION TEES
LS 2540 SEWER LATERALS AND INSPECTION TEES A. Summary B. Submittals C. Site Information D. Sewer Pipe and Fittings E. Lateral Locations F. Lateral Installation G. Inspection Tee Installation H. Removal
Beacon Hill Sewer District Standard Specifications
Beacon Hill Sewer District Standard Specifications Residential Gravity Side Sewer Including Design Criteria and Standard Construction Drawings Residential Gravity Side Sewer Design Criteria 1. Provisions
DESIGN AND CONSTRUCTION GUIDELINES AND STANDARDS DIVISION 33 UTILITIES 33 00 00 SITE UTILITIES
SECTION INCLUDES Domestic Water Fire Water Service Water Well Sanitary Sewer Storm Drains Foundation Drainage RELATED SECTIONS 03 30 00 Concrete 21 00 00 Fire Suppression - Sprinklers 22 00 00 Plumbing
SECTION LS 2530 SANITARY SEWERS. A. General: Submit the following in accordance with The General Conditions.
SECTION LS 2530 SANITARY SEWERS PART 1 GENERAL 1.1 SUBMITTALS A. General: Submit the following in accordance with The General Conditions. 1. Product data for drainage piping specialties. 2. Shop drawings
SUBDRAINS AND FOOTING DRAIN COLLECTORS. A. Construct subdrains, subdrain cleanouts and outlets, and footing drain collectors.
SUBDRAINS AND FOOTING DRAIN COLLECTORS PART 1 - GENERAL 1.01 SECTION INCLUDES A. Subdrains B. Subdrain Cleanouts and Outlets C. Footing Drain Collectors D. Storm Sewer Service and Connections 1.02 DESCRIPTION
SECTION 31 20 00 EARTH MOVING
SECTION 31 20 00 PART 1 - GENERAL 1.01 DESCRIPTION A. This Section describes the requirements for excavating, filling, and grading for earthwork at Parking Structure, new exit stair and as required to
Section 2100-Trenching and Tunneling
SECTION 5200 - STORM SEWER PART 1 - GENERAL 1.01 SCOPE: This Section covers installation of storm sewer mains and culverts. Topics include permits and fees, trench widths, pipe laying, bedding, initial
SECTION 02530 STORM DRAINAGE STRUCTURES. 1. Trench excavation, backfill, and compaction; Section 02250.
02530-1 of 5 SECTION 02530 STORM DRAINAGE STRUCTURES 02530.01 GENERAL A. Description Storm drainage structure construction shall include, but not necessarily be limited to, furnishing and installing or
AIR RELEASE, CLEANOUT, AND SEWER MANHOLES
AIR RELEASE, CLEANOUT, AND SEWER MANHOLES **From Hartford IM BLDG(10) DESCRIPTION. This work shall consist of the construction of air release, cleanout, and sanitary sewer manholes; and the furnishing
TS 813 GROUNDING AND BONDING TTD 813.001 TRAFFIC SIGNAL INSTALLATION AND CONTROLLER CABINET GROUNDING SYSTEM TTD 813.005 CONTROLLER CABINET GROUNDING
TORONTO TRANSPORTATION January 2012 TS 813 GROUNDING AND BONDING TABLE OF CONTENTS 1. DRAWINGS TTD 813.001 TRAFFIC SIGNAL INSTALLATION AND CONTROLLER CABINET GROUNDING SYSTEM TTD 813.005 CONTROLLER CABINET
STANDARD SPECIFICATIONS SECTION 02512 CLEANING AND LINING WATER MAINS
STANDARD SPECIFICATIONS SECTION 02512 CLEANING AND LINING WATER MAINS PART 1 GENERAL 1.1 DESCRIPTION A. Section includes requirements for cleaning and lining existing cast iron and ductile iron water mains
SECTION 33 11 00.15 DUCTILE IRON PIPE AND FITTINGS
SECTION 33 11 00.15 DUCTILE IRON PIPE AND FITTINGS PART 1: GENERAL 1.01 COORDINATION OF WORK Connection to existing pipelines may require shutdown of AW facilities. Closely coordinate construction work
SECTION 02400 - STORM DRAIN SYSTEM
SECTION 02400 - STORM DRAIN SYSTEM CONTENTS: Part 1 - General... 1 1.01 Work Included... 1 1.02 Related Requirements... 1 1.03 Reference Standards... 1 1.04 Quality Assurance... 1 1.05 Measurement And
WATER MAIN CONSTRUCTION TECHNIQUES DEPARTMENT OF PUBLIC WORKS WATER & WASTEWATER DIVISION
WATER MAIN CONSTRUCTION TECHNIQUES Overview Water Main - Materials Specifications Installation Future? Water Main Materials Material Types There are various material types used for water mains, these include:
SECTION 15105 DUCTILE IRON PIPE AND FITTINGS
SECTION 15105 DUCTILE IRON PIPE AND FITTINGS PART 1 GENERAL.01 COORDINATION OF WORK Connection to existing pipelines may require shutdown of Owner facilities. Closely coordinate construction work and connections
SECTION 02630 STORM DRAINAGE SYSTEM
SECTION 02630 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes specifications for storm drainage systems including modifications and connections to existing storm drainage systems. 1.02 REFERENCE
CONTENTS. Yale University Design Standards. Underground Electrical Duct Bank. A. Summary. B. System Design and Performance Requirements
16600 Underground Electrical Duct Bank This document provides design standards only, and is not intended for use, in whole or in part, as a specification. Do not copy this information verbatim in specifications
TG 105 ALLOWABLE PIPE SIZE, CLASS AND MATERIALS FOR WATER MAINS TECHNICAL GUIDELINE. Manager Asset Management SOUTH AUSTRALIAN WATER CORPORATION
TG 105 SOUTH AUSTRALIAN WATER CORPORATION TECHNICAL GUIDELINE ALLOWABLE PIPE SIZE, CLASS AND MATERIALS FOR WATER MAINS Issued by: Manager Asset Management Issue Date: SA WATER 2007 This document is copyright
CONCRETE SEGMENTAL RETAINING WALL SYSTEM
CONCRETE SEGMENTAL RETAINING WALL SYSTEM PART 1: GENERAL SPECIFICATIONS 1.01 Work Included A. Work shall consist of furnishing and constructing a Rockwood Classic 8 with PCS unit segmental retaining wall
08003-1 WATER SERVICE 2
08003_Mar08_2011.pdf Page 1 of 7 INDEX Page 08003-1 WATER SERVICE 2 1.1 Pipe 2 1.1.1 Copper 2 1.1.2 Polyethylene 2 1.2 Valves and Fittings 2 1.2.1 Main Stops 3 1.2.2 Curb Stops 3 1.2.3 Curb Box 3 1.2.4
SECTION 33 12 19 FIRE HYDRANTS
SECTION 33 12 19 FIRE HYDRANTS PART 1: GENERAL 1.01 SCOPE A. Fire hydrants. B. Adjustment of fire hydrants and gate valves. 1.02 SUBMITTALS A. Conform to requirements of Section 01 33 00 - Submittals.
DIVISION 2 - SEWERAGE AND DRAINAGE SECTION 02720 - STORM DRAIN SYSTEMS PART 1 - GENERAL
DIVISION 2 - SEWERAGE AND DRAINAGE SECTION 02720 - STORM DRAIN SYSTEMS PART 1 - GENERAL 1.01 DESCRIPTION A. Furnish and install all storm drains, including manholes, inlets, service lines and other appurtenant
SECTION 02732 BUILDING SEWERS. B. Connection of building sanitary drainage system to municipal sewers.
SECTION 02732 BUILDING SEWERS PART 1 GENERAL 1.01 SECTION INCLUDES A. Lateral piping, fittings, and accessories. B. Connection of building sanitary drainage system to municipal sewers. 1.02 REGULATORY
SIERRA LAKES COUNTY WATER DISTRICT P.O. Box 1039, Soda Springs, CA 95728-1039 (7300 Short Road, Serene Lakes)
SIERRA LAKES COUNTY WATER DISTRICT P.O. Box 1039, Soda Springs, CA 95728-1039 (7300 Short Road, Serene Lakes) Maintenance Office Administrative Office Billing Office 530-426-7802 530-426-7800 916-332-4872
Section C-1 Pipes and Fittings
Section C-1 Pipes and Fittings C1.00 Work Included The work under this Division of the Specifications shall include all labor, materials, and equipment necessary to furnish and install all piping, pipelines,
EXCAVATION AND PILING NEAR SEWERS, STORMWATER DRAINS AND WATER MAINS
NMP 1.4 EXCAVATION AND PILING NEAR SEWERS, STORMWATER DRAINS AND WATER MAINS Index Purpose... 2 Application... 2 Referral Agency... 2 Associated Requirements... 2 Referenced Standards...2 Definitions...
SPECIFICATION FOR CONSTRUCTION OF UNBOUND GRANULAR PAVEMENT LAYERS
TNZ B/02:2005 SPECIFICATION FOR CONSTRUCTION OF UNBOUND 1. SCOPE This specification shall apply to the construction of unbound granular pavement layers. The term pavement layer shall apply to any layer
PART 5 : WASTEWATER DRAINAGE
Authorised by : City Waters Unit Manager Page 1 of 15 PART 5 : WASTEWATER DRAINAGE 5.1 INTRODUCTION This Manual sets out the basic design principles for drainage of wastewater. While some construction
State of Illinois Department Of Transportation CONSTRUCTION INSPECTOR S CHECKLIST FOR STORM SEWERS
State of Illinois Department Of Transportation CONSTRUCTION INSPECTOR S CHECKLIST FOR STORM SEWERS While its use is not required, this checklist has been prepared to provide the field inspector a summary
Section 2 Specification 2.18 Concrete and/or Corrugated Steel Storm Sewer TABLE OF CONTENTS
TABLE OF CONTENTS 2.18 CONCRETE AND/OR CORRUGATED STEEL STORM SEWER... 1 2.18.1 GENERAL... 1 2.18.2 MATERIALS... 1 2.18.2.1 Storm Sewer Pipe... 1 2.18.2.2 Cement Mortar... 1 2.18.2.3 Granular Materials...
Civil. 2. City of Seattle Supplement to the Specification for Road, Bridge and Municipal Construction, most current addition.
Design Guide Basis of Design This section applies to the design and installation of earthwork and backfill. Design Criteria No stockpiling of excavation materials is allowed unless the Geotechnical Engineer
STANDARD SPECIFICATIONS FOR PRIVATE BUILDING SEWER LINES IN PUBLIC RIGHT-OF-WAY
STANDARD SPECIFICATIONS FOR PRIVATE BUILDING SEWER LINES IN PUBLIC RIGHT-OF-WAY Approved and adopted as Official Document Number 800576 this 10th day of December, 1980 Donald R. Boyd, P.E., Director Water
SECTION 02150 REMOVAL OR ABANDONMENT OF EXISTING UTILITIES AND UNDERGROUND STRUCTURES. 1. Trench excavation, backfill, and compaction; Section 02250.
02150-1 of 6 SECTION 02150 REMOVAL OR ABANDONMENT OF EXISTING 02150.01 GENERAL A. Description Removal or abandonment of existing utilities and underground structures shall include, but not necessarily
505.3.6 For a building with a crawl space, see Figure 10. 505-1
505 WATER SERVICE INSTALLATION 505.1 DEFINITION A service line is comprised of the piping and related appurtenances including the connection installed from the Des Moines Water Works water main to the
MDWASD 8/1999 SECTION 02315 TRENCHING AND BACKFILLING FOR PIPING SYSTEMS
PART 1 - GENERAL 1.01 WORK INCLUDED SECTION 02315 TRENCHING AND BACKFILLING FOR PIPING SYSTEMS A. The work included under this Section consists of excavating, backfilling and compaction as required for
C. Section 014510 TESTING LABORATORY SERVICE.
SECTION 014500 QUALITY CONTROL PART 1 GENERAL 1.01 RELATED REQUIREMENTS A. Drawings and General Provisions of Contract, including General and Special Conditions and other Division 1 Specification Sections,
SECTION 02401 - SANITARY SEWER PIPE
PART 1 - GENERAL 1.1 DESCRIPTION A. The WORK under this Section includes providing all labor, materials, tools and equipment necessary for furnishing and installing sanitary sewer pipe, in accordance with
APPLICATION PROCEDURES FOR PLACEMENT OF UNDERGROUND WATER AND SEWER PIPELINES IN THE VICINITY OF TRANSPORTATION FACILITIES UNDER THE
APPLICATION PROCEDURES FOR PLACEMENT OF UNDERGROUND WATER AND SEWER PIPELINES IN THE VICINITY OF TRANSPORTATION FACILITIES UNDER THE JURISDICTION OF ALBERTA TRANSPORTATION 1.0 Application Procedures 2.0
SECTION 33 41 13 PUBLIC STORM UTILITY DRAINAGE PIPING
SECTION 33 41 13 PUBLIC STORM PART 1 - GENERAL 1.01 SECTION INCLUDES A. Storm drainage piping, fittings, and accessories at proposed station areas and locations other than under and immediately adjacent
Standard Specification for the Laying of Sewer Lines and Appurtenances in the Hurunui District
Standard Specification for the Laying of Sewer Lines and Appurtenances in the Hurunui District 1. SCOPE OF WORK This Specification applies to the laying of sewer pipes and all associated appurtenances
9.00 THE USE OF HUNTER LAND DRAINAGE PERFORATED PIPES. Hunter Underground Systems
9.00 THE USE OF HUNTER LAND DRAINAGE PERFORATED PIPES Hunter Underground Systems 9.01 General 9.02 Surface water Drainage 9.03 Groundwater Drainage 9.04 Dispersal of Septic Tank Effluent 9.01 The use of
SECTION 6 SANITARY SEWER MAIN 6.01 SCOPE
6.01 SCOPE The work covered by this section of the specifications consists of the furnishing of all plant, labor, materials, equipment and supervision and performing all operations involved in the construction
How To Safely Dig For Natural Gas
PNG DIAL B4-U-DIG book_final_nu 5/1/05 3:24 PM Page 2 Phoenix Natural Gas,197 Airport Road West, Belfast BT3 9ED. Tel. 08454 55 55 55. www.phoenix-natural-gas.com PNG DIAL B4-U-DIG book_final_nu 5/1/05
1.3.2 Method of construction and restoration of existing water service connections. This shall include:
1.0 GENERAL 1.1 DESCRIPTION: This specification shall cover the rehabilitation of existing water lines using the GRUNDOCRACK PIPE BURSTING SYSTEM. Pipe bursting is a system by which the pneumatic bursting
Wastewater Capital Projects Management Standard Construction Specification
CITY AND COUNTY OF DENVER ENGINEERING DIVISION Wastewater Capital Projects Management Standard Construction Specification 10.1 Precast Concrete Pipe 10.1.1 General This section covers material requirements,
CONCRETE SEGMENTAL RETAINING WALL SYSTEM
CONCRETE SEGMENTAL RETAINING WALL SYSTEM PART 1: GENERAL SPECIFICATIONS 1.01 Work Included A. Work shall consist of furnishing and constructing a Rockwood Vintage TM unit segmental retaining wall (SRW)
SECTION 02720 SANITARY SEWER AND STORM DRAIN SYSTEMS
SECTION 02720 SANITARY SEWER AND STORM DRAIN SYSTEMS PART 1 GENERAL 1.01 SECTION INCLUDES A. The requirements for pipe material and installation in sewer and drainage collection systems. All materials
32-02.05 Precast Manhole Sections and Castings. These items shall conform to Section 31, "Storm Drain Installation," of these Standard Provisions.
SECTION 32: SANITARY SEWER INSTALLATION 32-01 SCOPE. The Work shall consist of furnishing and installing sewer mains, manholes, laterals, cleanout fittings and appurtenances; and testing, flushing and
BOQ for Plumbing, Sanitary Works
BOQ for Plumbing, Sanitary Works Page 1 of 6 Sr.No Item Description Quantity Unit Rate Amount (Rs.) 1 SANITARY FIXTURES Providing & Fixing star white colour vitreous china wall mounted wc with 1a heavy
San Antonio Water System Standard Specifications for Construction ITEM NO. 854 SANITARY SEWER LATERALS
San Antonio Water System Standard Specifications for Construction ITEM NO. 854 SANITARY SEWER LATERALS 854.1 DESCRIPTION: This item shall govern sanitary sewer laterals installed in accordance with these
Model Specification 509 DRISCOPLEX 4200 and DRISCOPLEX 4300 Gravity Flow Sanitary Sewer
Model Specification 509 DRISCOPLEX 4200 and DRISCOPLEX 4300 Gravity Flow Sanitary Sewer The user may choose to adopt part or all of this Model Specification; however, the user should ensure that all parts
Developer s/consultants Field Services Guidelines
Developer s/consultants Field Services Guidelines 2007 Engineering and Works Department DEVELOPER S/CONSULTANT S FIELD SERVICES GUIDELINES Fourth Electronic Edition February 2007 STATEMENT OF COMPLETION
CW 3110 SUB-GRADE, SUB-BASE AND BASE COURSE CONSTRUCTION TABLE OF CONTENTS
December 2014 CW 3110 SUB-GRADE, SUB-BASE AND BASE COURSE CONSTRUCTION TABLE OF CONTENTS 1. DESCRIPTION... 1 1.1 General... 1 1.2 Definitions... 1 1.3 Referenced Standard Construction Specifications...
STANDARD SPECIFICATIONS SECTION 03461 PRECAST REINFORCED CONCRETE MANHOLES AND MANHOLE BASES. 1. Structure Earthwork: 02200
STANDARD SPECIFICATIONS SECTION 03461 PRECAST REINFORCED CONCRETE MANHOLES AND MANHOLE BASES PART 1 - GENERAL A. Description This section includes materials, testing, and installation of precast concrete
EFFECTIVE FEBRUARY 2014. note: drainage permit required to call for a dampproof inspection
EFFECTIVE FEBRUARY 2014 note: drainage permit required to call for a dampproof inspection 1. ROOF DRAINS/DECK DRAINS (INTERIOR ) All roof and deck drains within the perimeter of the building shall be APPROVED
SANITARY SEWER SERVICE CONNECTION INSTRUCTIONS
1 SANITARY SEWER SERVICE CONNECTION INSTRUCTIONS TABLE OF CONTENTS I. Introduction II. General Information and Requirements A. Applying for Sewer connection B. Excavation C. Cutting Concrete and Asphalt
Gas Meter Clearances and Service Installation Requirements
March 2015 Gas Meter Clearances and Service Installation Requirements Builder/Owner/Developer Requirements Call PSE s Customer Construction Services 1-888-321-7779 or visit PSE.com/CustomerConstruction
SECTION 33 11 00.11 POLYVINYL CHLORIDE (PVC) PIPE
SECTION 33 11 00.11 POLYVINYL CHLORIDE (PVC) PIPE PART 1: GENERAL 1.01 SECTION INCLUDES PVC pressure pipe and fabricated fittings in nominal sizes 4-inches through 12-inches with cast iron pipe equivalent
All work shall comply with applicable codes and ordinances. Work shall comply with the BOCA National Plumbing Code, latest edition.
DIVISION 15 MECHANICAL SECTION 15100 - PLUMBING PART 1 - GENERAL SCOPE Plumbing work includes all domestic water, gas, and sanitary sewer systems as shown on plans. Also all fixtures and equipment which
SECTION 15056 DUCTILE-IRON PIPE AND FITTINGS
SECTION 15056 PART 1 GENERAL 1.01 DESCRIPTION This section includes materials and installation of ductile-iron pipe and fittings for potable and recycled water systems. A written request to use Ductile
Construction Specification for Concrete Curb and Concrete Curb and Gutter
Engineering & Construction Services Division Standard Specifications for Road Works TS 3.50 April 2015 for Concrete Curb and Table of Contents TS 3.50.01 SCOPE... 3 TS 3.50.02 REFERENCES... 3 TS 3.50.03
WATER SERVICES ASSOCIATION OF AUSTRALIA WATER SUPPLY CODE OF AUSTRALIA
WATER SERVICES ASSOCIATION OF AUSTRALIA WATER SUPPLY CODE OF AUSTRALIA WSA 03 2011 Water Supply Code of Australia WSA 03 2011 Third Edition Version 3.1 Previous edition WSA 03: 2002-2.3 CONTENTS PREFACE
CHAPTER 6 - SANITARY SEWER
CHAPTER 6 - SANITARY SEWER 6.1 GENERAL This section covers the requirements for PVC plastic sewer pipe materials and installation in sanitary sewer construction. 6.2 PIPE PVC gravity sewer pipe and fittings
Technical Solution Sheet 5.03 5: Cold Water Plumbing
5: Cold Water Plumbing Drawings of Typical Water and Fire Services, Pipe Materials and Private Service AIM The aim of this technical solution is to inform practitioners on the typical requirements for
Division 2 Section 32 14 13.19 Section 02795
Note: The text must be edited to suit specific project requirements. It should be reviewed by a qualified civil or geotechnical engineer, or landscape architect familiar with the site conditions. Edit
SECTION 02110 - ASBESTOS CEMENT PIPE REPAIRS, DEMOLITION, AND DISPOSAL
SECTION 02110 - ASBESTOS CEMENT PIPE REPAIRS, DEMOLITION, AND DISPOSAL PART 1 - GENERAL 1.1 WORK INCLUDED IN THIS SECTION A. The WORK of this Section includes the repair, demolition, and disposal of asbestos
Dimensional and Structural Data for Elliptical Pipes. PD 26 rev D 21/09/05
Dimensional and Structural Data for Elliptical Pipes 21/09/05 Page 1 of 15 1. Foreword This document details a method for the structural design of Stanton Bonna Elliptical pipes for the common conditions
SECTION 33 31 00.11 GRAVITY SANITARY SEWERS
SECTION 33 31 00.11 GRAVITY SANITARY SEWERS PART 1: GENERAL 1.01 SCOPE A. Gravity sanitary sewers and appurtenances. 1.02 SUBMITTALS A. Conform to requirements of Section 01 33 00 Submittals. B. Submit
SECTION 4Aggegate Subbase
The contractor shall moist-cure the completed Lime Treated Subbase for a minimum of days before allowing any traffic on the compacted surface. The contractor shall be responsible for repairing any damages
CONSTRUCTION OF SEWER RISING MAINS
STS403 Hunter Water Corporation A.B.N. 46 228 513 446 Standard Technical Specification for: CONSTRUCTION OF SEWER RISING MAINS This Standard Technical Specification was developed by Hunter Water to be
SECTION 02845 GUARDRAILS
SECTION 02845 GUARDRAILS PART 1 - GENERAL 1.01 SCOPE OF WORK A. Furnish all labor, materials, equipment and incidentals necessary and repair, replace or install all types of guardrails as specified herein
Exhibit A. Rules and Regulations for House Connections and Sewer Extensions
The purpose of this application example is to provide assistance to small and medium sized rural communities in the drafting of documents necessary for the efficient operation of water, wastewater, and
SECTION 33 05 16.13 PRECAST CONCRETE UTILITY STRUCTURES
SECTION 33 05 16.13 PRECAST CONCRETE PART 1 - GENERAL 1.01 SECTION INCLUDES A. This item shall consist of the construction of both sanitary and storm sewer precast concrete manholes in accordance with
3", 4", 6" & 8" Model H Series Alarm Check Valve Installation and Maintenance Guide
", ", " & " Model H Series Alarm Check Valve Installation and Maintenance Guide 077 AIRPARK DRIVE STANDISH, MICHIGAN PHONE 99-- 00-2-0 FAX 99--92 www.globesprinkler.com OCTOBER 2 C- BULLETIN A.C.V.I.M.,
ITS specification Jointing chambers and pull pits (ITS-02-02)
ITS specification Jointing chambers and pull pits (ITS-02-02) NZ Transport Agency Effective from September 2011 Copyright information This publication is copyright NZ Transport Agency (NZTA). Material
Prepare a drainage system layout and specification notes for a low- rise building.
STUDENT MATERIALS Prepare a drainage system layout and specification notes for a low- Outcome 1 - rise building. In this outcome you will study the technology of below and above ground drainage systems.
50AI01oe 02/15. Labko GRP cesspools. Instructions for installation, operation and maintenance
02/15 Labko GRP cesspools Instructions for installation, operation and maintenance Reliable solutions Wastewater treatment systems Contents 1 LABKO CESSPOOLS... 3 1.1 GENERAL... 3 1.2 IMPORTANT TO KNOW
STANDARD SPECIFICATIONS SECTION 02701 INSTALLATION OF GRAVITY SEWER PIPELINES. 1. Trenching, Backfilling and Compacting: 02223
STANDARD SPECIFICATIONS SECTION 02701 INSTALLATION OF GRAVITY SEWER PIPELINES PART 1 - GENERAL A. Description This section describes the installation of gravity sewer pipelines fabricated of vitrified
CAST IRON THE BASICS. Heatline - Cast Iron Radiators SMOOTH FLAT FILE TO REMOVE ANY SWARF. ONE TIME. ASSEMBLY. JOINTS SHOULD BE TIGHTENED.
CAST IRON THE BASICS 1. DO NOT LIFT ON YOUR OWN. 2. ONLY LIFT THE RADIATOR VERTICALLY. 3. DO NOT LIFT MORE THAN 8/10 SECTIONS AT ANY ONE TIME. 4. POSITION THE RADIATOR BEFORE FINAL ASSEMBLY. 5. THIS PRODUCT
Subcontractors Typical Sample - Groundworks Priced Bill of Quantities. Labour & Plant Groundworks. Ref Description Quantity Units Rate Sub Total
Subcontractors Typical Sample - Groundworks Priced Bill of Quantities Labour & Plant Groundworks Ref Description Quantity Units Rate Sub Total Excavating trenches; to receive pipes not exceeding 200 nominal
COATING & WRAPPING OF UNDERGROUND PIPING
CONSTRUCTION STANDARD SPECIFICATION DOCUMENT NO :SEC-PJ-000-SPC-PI-008 TOTAL PAGES : 8 Page 1 of 8 CONTENTS 1. SCOPE 2. DEFINITION 3. CODES AND STANDARDS 4. MATERIALS Page 2 of 8 1. SCOPE This specification
MY ACCOUNT. HOW IT WORKS FOR YOU.
ECTRICAL CONDUIT POLYETHYLENE PIPE GAS PIPE HYDRANT RISER GEBERIT BITUMEN COMMUNICATIONS RUBBER RING UNIVERSAL COUPLINGS FERRULE BEND TPFNR FER IN SEWERMAIN ELECTROFUSION MPVC CONCRETE FLANGE BLUE STRIPE
DESCRIPTION OF WORK:
DEPARTMENT OF PUBLIC WORKS COUNTY OF HENRICO P.O. BOX 27032 RICHMOND, VIRGINIA 23273 PERMIT NO. One (1) copy of application and four (4) copies of plans are hereby made to the Director of Public Works
MS-3/2009 HDPE (High Density Polyethylene) Pipe and Fittings Specification for Buried Potable Water
MS-3/2009 HDPE (High Density Polyethylene) Pipe and Fittings Specification for Buried Potable Water 105 Decker Court, Suite 825, Irving, TX 75062 P: 469-499-1044 F: 469-499-1063 www.plasticpipe.org HDPE
APPLICATION FOR DEMOLITION & RIGHT-OF OF-WAY PERMIT
APPLICATION FOR DEMOLITION & RIGHT-OF OF-WAY PERMIT City of Swartz Creek 8083 Civic Drive Swartz Creek, MI 48473 810-635-4464 Fee Received: $ Date: / / Receipt No: Demolition Permit (including Right of
PLUMBING MAINTENANCE WORK FOR TOILETS IN HEAD OFFICE, SUPPLYCO ESTIMATE
Sl.No. PLUMBING MAINTENANCE WORK FOR TOILETS IN HEAD OFFICE, SUPPLYCO ESTIMATE Description of item Qty Unit Rate Amount 1 Demolishing tile work/cement concrete/( carefully taking out the closet and other
AWWA Small Systems Pipe Repair Checklist, as published in July 2008 Opflow Question of the Month
, as published in July 2008 Opflow Question of the Month Thanks to: Mike Grahek, Los Angeles Department of Water, Los Angeles, California Ahmad Havivian, Black & Veatch, Gaithersburg, Maryland David Kroon,
Gas Meter Clearances and Service Installation Requirements
March 2016 Gas Meter Clearances and Service Installation Requirements Builder/Owner/Developer Requirements Call PSE's Customer Construction Services 1 888 321 7779 or visit PSE.com/CustomerConstruction
SUMMARY OF PUBLIC WORK STANDARD SPECIFICATION REVISIONS 2016
SUMMARY OF PUBLIC WORK STANDARD SPECIFICATION REVISIONS 2016 102.5 Bid Deposits The City of Madison bid deposit form is required for all bids unless a Biennial Bid Bond is on file or check deposit is used.
Underground Piping for Private Hydrants & Sprinkler Supply Line
ORANGE COUNTYFIRE AUTHORITY Planning & Development Services Section 1 Fire Authority Road, Bldg. A, Irvine, CA 92602 714-573-6100 www.ocfa.org Underground Piping for Private Hydrants & Sprinkler Supply
Permeable Pavement Construction Guide
Permeable Pavement Construction Guide Permeable pavement at Olympic Park, Waitakere Final Construction result What are permeable pavements? Permeable pavements are hard surface paving systems that reduce