Control Panels. Single-phase electric panels for submersible pumps QSM - QPC - QPCS - QSC - QSCS

Size: px
Start display at page:

Download "Control Panels. Single-phase electric panels for submersible pumps QSM - QPC - QPCS - QSC - QSCS"

Transcription

1 Control Panels Single-phase electric panels for submersible pumps QSM - QPC - QPCS - QSC - QSCS Electric panels for surface or submergible pumps QM - QTD - Q3A - Q3D - Q3Y - Q3I - Q3SF Electric panels for drainage pumps QDR - QDR2 - QDRM - QDRMC - QDRM2 - QDRMC2 - QGMC - QYR - QYR2 - QXR20 Auxiliary electric panels and accessories QCL5 - QCL10 - QCLP10 - KSL - DPF - VR - SCA

2 QSM Series Single-phase electric panels for the protection and control of a 4 single-phase borehole pump. Main switch for manual control Supply voltage: 1 x V ±5% Frequency: 50 Hz Power: 0.25 to 1.1 kw Direct motor starting Protection: IP43 Ambient temperature: -5 to +40 C (limit specified by EN standard ) Maximum relative humidity: 50% at +40 C provided that no condensation occurs (limit specified by EN standard ) Wall mounted Plastic enclosure Built-in capacitor Thermal protection inside panel Special versions available on request QSM PF version with overvoltage protection (lightning protector) For proper electric panel-electric pump selection, make sure that the Ampere input of the motor falls within the rated current range shown in the table. 518

3 QSM SERIES MODEL RATED RATED RATED CAPACITOR DIMENSIONS WEIGHT VOLTAGE POWER CURRENT 450V A B C V kw HP A uf mm mm mm Kg QSM ,25 0,33 2,6 12, ,45 QSM ,3 0,5 3, ,45 QSM ,55 0,5 4, ,45 QSM ,5 1 6, ,45 QSM ,1 1,5 8, ,45 CB-QSM-en_c_te 519

4 QPC Series Single-phase electric panels for the protection and control of a 4 single-phase borehole pump. Main switch for manual control Supply voltage: 1 x 230 V ±10% Frequency: 50 Hz Power: 0.25 to 2.2 kw Direct motor starting Protection: IP54 Ambient temperature: -5 to +40 C (limit specified by EN standard ) Maximum relative humidity: 50% at +40 C provided that no condensation occurs (limit specified by EN standard ) Wall-mounted using supplied brackets Plastic enclosure Built-in capacitor Main switch with thermal protector (manual reset) and power ON indicator light Optional accessories DPF single-phase module for overvoltage protection (lightning protector) For proper electric panel-electric pump selection, make sure that the Ampere input of the motor falls within the rated current range shown in the table. 520

5 QPC SERIES PANEL TYPE RATED RATED RATED DIMENSIONS WEIGHT VOLTAGE POWER CURRENT A B C V kw HP A mm mm mm Kg QPC/02 1 x 230 V ± 10 % 0,25 0, ,1 QPC/03 1 x 230 V ± 10 % 0,3 0, ,1 QPC/05 1 x 230 V ± 10 % 0,55 0, ,1 QPC/0 1 x 230 V ± 10 % 0, ,1 QPC/11 1 x 230 V ± 10 % 1,1 1, ,1 QPC/15 1 x 230 V ± 10 % 1, ,1 QPC/22 1 x 230 V ± 10 % 2, ,2 CAPACITOR F/450V 12, CB-QPC_a_te 521

6 QPCS Series Single-phase electric panels for the protection and control of a 4 single-phase borehole pump. Automatic control through an external contactor Supply voltage: 1 x 230 V ±10% Frequency: 50 Hz Power: 0.25 to 2.2 kw Low voltage auxiliary circuit 12 Vac Direct motor starting Protection: IP54 Ambient temperature: -5 to +40 C (limit specified by EN standard ) Maximum relative humidity: 50% at +40 C provided that no condensation occurs (limit specified by EN standard ) Wall-mounted using supplied brackets Plastic enclosure with see-through cover Built-in capacitor Main switch with thermal protector (manual reset) and power ON indicator light Power, pump running and dry running level indicator lights Overvoltage protection Dry running control through probes, float switch or minimum pressure switch Optional accessories Kit n 3 electrodes (probes) without cable Float switch Pressure switch For proper electric panel-electric pump selection, make sure that the Ampere input of the motor falls within the rated current range shown in the table. 522

7 QPCS SERIES PANEL TYPE RATED RATED RATED DIMENSIONS WEIGHT VOLTAGE POWER CURRENT A B C V kw HP A mm mm mm Kg QPCS/02 1 x 230 V ± 10 % 0,25 0, ,3 QPCS/03 1 x 230 V ± 10 % 0,3 0, ,3 QPCS/05 1 x 230 V ± 10 % 0,55 0, ,3 QPCS/0 1 x 230 V ± 10 % 0, ,3 QPCS/11 1 x 230 V ± 10 % 1,1 1, ,3 QPCS/15 1 x 230 V ± 10 % 1, ,3 QPCS/22 1 x 230 V ± 10 % 2, ,3 CAPACITOR F/450V 12, CB-QPCS_a_te 523

8 QSC Series Protection and control of a single-phase submersible electric pump for 4 wells. Main switch for manual control. Supply voltage: 1 x 230 V ±10%. Frequency: 50 Hz. Power: 0,25 to 4 kw. Direct motor start. Protection class: IP55. Ambient temperature: -5 to +40 C (according to EN ). Maximum relative humidity: 50% at +40 C, provided that no condensation occurs (according to EN ). Wall mounted. Plastic enclosure. Incorporated capacitor. Main switch with manual-reset thermal protection. Optional accessories DPF single-phase module for overvoltage protection (lightning protector). For proper electric panel-electric pump selection, make sure that the Ampere input of the motor falls within the rated current range shown in the table. 524

9 QSC SERIES MODEL RATED RATED RATED DIMENSIONS WEIGHT VOLTAGE POWER CURRENT A B C V kw HP A mm mm mm Kg QSC/02 1 x 230 V ± 10 % 0,25 0,33 2, , QSC/03 1 x 230 V ± 10 % 0,3 0,5 4 6, , QSC/05 1 x 230 V ± 10 % 0,55 0,5 4 6, , QSC/0 1 x 230 V ± 10 % 0, , , QSC/11 1 x 230 V ± 10 % 1,1 1,5 6, , QSC/15 1 x 230 V ± 10 % 1, , QSC/22 1 x 230 V ± 10 % 2, , QSC/40 1 x 230 V ± 10 % 4 5, CAPACITOR μf/450v 12, CB-QSC-en_d_te 525

10 QSCS Series Protection and control of a single-phase submersible electric pump for 4 wells. Automatic control through an external enable contact Supply voltage: 1 x 230 V ±10% Frequency: 50 Hz Power: 0,25 to 2,2 kw Direct motor start Protection class: IP55 Ambient temperature: -5 to +40 C (according to EN ) Maximum relative humidity: 50% at +40 C, provided that no condensation occurs (according to EN ) Wall mounted Plastic enclosure Incorporated capacitor Main switch with manual-reset thermal protection Dry running control with float or minimum pressure switch (available separately) Optional accessories DPF single-phase module for overvoltage protection (lightning protector) KSL series 24 V level kit Probe module for protection against dry running (set of three electrodes included in the supply) For proper electric panel-electric pump selection, make sure that the Ampere input of the motor falls within the rated current range shown in the table. 526

11 QSCS SERIES MODEL RATED RATED RATED DIMENSIONS WEIGHT VOLTAGE POWER CURRENT A B C V kw HP A mm mm mm Kg QSCS/02 1 x 230 V ± 10 % 0,25 0,33 2, , QSCS/03 1 x 230 V ± 10 % 0,3 0,5 4 6, , QSCS/05 1 x 230 V ± 10 % 0,55 0,5 4 6, , QSCS/0 1 x 230 V ± 10 % 0, , , QSCS/11 1 x 230 V ± 10 % 1,1 1,5 6, , QSCS/15 1 x 230 V ± 10 % 1, , QSCS/22 1 x 230 V ± 10 % 2, , CAPACITOR μf/450v 12, CB-QSCS-en_b_te 52

12 QM Series Single-phase electric panels for the protection and control of a 4 single-phase surface pump. Control through an external contactor Supply voltage: 1 x 230 V ±10% Frequency: 50/60 Hz Power: 0.25 to 2.2 kw Direct motor starting Protection: IP54 Ambient temperature: -5 to +40 C (limit specified by EN standard ) Maximum relative humidity: 50% at +40 C provided that no condensation occurs (limit specified by EN standard ) Wall mounted Metal enclosure Ready for installation of dry-running control with float or pressure switch (available separately) Power and thermal overload indicator lights Optional accessories VR1 single-phase varistor module for overvoltage protection (lightning protector) SLD series 24V level kit. Probe module for protection against dry running (set of three electrodes included in the supply) For proper electric panel-electric pump selection, make sure that the Ampere input of the motor falls within the rated current range shown in the table. 528

13 QM SERIES PANEL TYPE RATED RATED RATED DIMENSIONS WEIGHT VOLTAGE POWER CURRENT A B C V kw HP A mm mm mm Kg QM/02 1 x 230 V ± 10 % 0,25 0,33 1 1, ,8 QM/03 1 x 230 V ± 10 % 0,3 0,5 1,6 2, ,8 QM/05 1 x 230 V ± 10 % 0,55 0,5 2, ,8 QM/0 1 x 230 V ± 10 % 0, , ,8 QM/15 1 x 230 V ± 10 % 1,5 2 6, ,8 QM/22 1 x 230 V ± 10 % 2, ,8 CB-QM_b_te 529

14 QTD Series Three-phase electric panels for the protection and control of a 4 three-phase surface or submersible pump. Control through an external contactor Supply voltage: 3 x 400 V ±10% Frequency: 50/60 Hz Power: 0.25 to 9.2 kw Direct motor starting Overload protection Protection: IP54 Ambient temperature: -5 to +40 C (limit specified by EN standard ) Maximum relative humidity: 50% at +40 C provided that no condensation occurs (limit specified by EN standard ) Wall mounted Metal enclosure Ready for installation of dry-running control with float or pressure switch (available separately) Power and thermal overload indicator lights Optional accessories VR3 three-phase module for overvoltage protection (lightning protector) Selection For proper electric panel-electric pump selection, make sure that the Ampere input of the motor falls within the rated current range shown in the table SLD series 24V level kit. Probe module for protection against dry running (set of three electrodes included in the supply) For proper electric panel-electric pump selection, make sure that the Ampere input of the motor falls within the rated current range shown in the table. 530

15 QTD SERIES PANEL TYPE RATED RATED RATED DIMENSIONS WEIGHT VOLTAGE POWER CURRENT A B C V kw HP A mm mm mm Kg QTD/ x 400 V ± 10 % 0,25-0,3 0,33-0,50 0, ,8 QTD/ x 400 V ± 10 % 0,3-0,55 0,55-0,5 1 1, ,8 QTD/ x 400 V ± 10 % 0,55-0,5 0,5-1 1,6 2, ,8 QTD/ x 400 V ± 10 % 0,5-1, , ,8 QTD/ x 400 V ±10 % 1,5-2, , ,8 QTD/ x 400 V ± 10 % 2, ,5 6, ,8 QTD/ x 400 V ± 10 % 4-,5 5, ,8 QTD/ x 400 V ± 10 %,5-9, , ,8 CB-QTD_c_te 531

16 Q3A Series Three-phase electric panels for the protection and control of a 4 three-phase surface or submersible pump. Manual control through A-0-M switch Automatic control through an external contactor Supply voltage: 3 x 400 V ±10% Frequency: 50/60 Hz Low voltage auxiliary circuit 24 Vac Power: 4 to 315 kw Autotransformer starting Overload protection Protection: IP54 Ambient temperature: -5 to +40 C (limit specified by EN standard ) Maximum relative humidity: 50% at +40 C provided that no condensation occurs (limit specified by EN standard ) Wall mounted Metal enclosure Power - pump running - thermal overload - dry running indicator lights Ready for installation of dry-running control with float or pressure switch (available separately) Electronic protection module with electrodes can be fitted Optional accessories SLD series 24V level kit: Probe module for protection against dry running (set of three electrodes included in the supply) Float switch Pressure switch VR3/SCA3 three-phase module for overvoltage protection (lightning protector) For proper electric panel-electric pump selection, make sure that the Ampere input of the motor falls within the rated current range shown in the table. 532

17 Q3A SERIES A C 500 V 300 A L1-L2 L2-L3 L3-L B M 0 A MODEL RATED RATED RATED DIMENSIONS WEIGHT VOLTAGE POWER CURRENT A B C V kw HP A mm mm mm Kg Q3A/ x 400 V ± 10 % 4-,5 5, Q3A/ x 400 V ± 10 %,5-9, , Q3A/ x 400 V ± 10 % 9, , Q3A/ x 400 V ± 10 % Q3A/ x 400 V ± 10 % 15-18, Q3A/ x 400 V ± 10 % 18, Q3A/ x 400 V ± 10 % Q3A/ x 400 V ± 10 % Q3A/ x 400 V ± 10 % p 1300p 300p 90 Q3A/ x 400 V ± 10 % p 1500p 300p 120 Q3A/ x 400 V ± 10 % p 1500p 300p 120 Q3A/ x 400 V ± 10 % p 100p 400p 150 Q3A/ x 400 V ± 10 % p 1900p 400p 150 Q3A/ x 400 V ± 10 % p 1900p 400p 200 Q3A/ x 400 V ± 10 % p 1900p 400p 200 Q3A/ x 400 V ± 10 % p 1900p 400p 230 Q3A/ x 400 V ± 10 % p 1900p 400p 230 Q3A/ x 400 V ± 10 % p 1900p 400p 250 Dimensions note : P indicates floor mounted control panel. CB-Q3A-en_c_te 533

18 Q3D Series Three-phase electric panels for the protection and control of a 4 three-phase surface or submersible pump. Manual control through A-0-M switch Automatic control through an external contactor Supply voltage: 3 x 400 V ±10% Frequency: 50/60 Hz Low voltage auxiliary circuit 24 Vac Power: 0.25 to 3 kw Direct starting Overload protection Protection: IP54 Ambient temperature: -5 to +40 C (limit specified by EN standard ) Maximum relative humidity: 50% at +40 C provided that no condensation occurs (limit specified by EN standard ) Wall mounted Metal enclosure Power - pump running - thermal overload - dry running indicator lights Ready for installation of dry-running control with float or pressure switch (available separately) Electronic protection module with electrodes can be fitted Optional accessories SLD series 24V level kit: Probe module for protection against dry running (set of three electrodes included in the supply) Float switch Pressure switch VR3/SCA3 three-phase module for overvoltage protection (lightning protector) For proper electric panel-electric pump selection, make sure that the Ampere input of the motor falls within the rated current range shown in the table. 534

19 Q3D SERIES A C 500 V 300 A L1-L2 L2-L3 L3-L B M 0 A PANEL TYPE RATED RATED RATED DIMENSIONS WEIGHT VOLTAGE POWER CURRENT A B C V kw HP A mm mm mm Kg Q3D/ x 400 V ± 10 % 0,25-0,3 0,33-0,50 0, Q3D/ x 400 V ± 10 % 0,3-0,55 0,5-0,5 1 1, Q3D/ x 400 V ± 10 % 0,55-0,5 0,5-1 1,6 2, Q3D/ x 400 V ± 10 % 0,5-1, , Q3D/ x 400 V ± 10 % 1,5-2, , Q3D/ x 400 V ± 10 % 2, ,5 6, Q3D/ x 400 V ± 10 % 4-,5 5, Q3D/ x 400 V ± 10 %,5-9, , Q3D/ x 400 V ± 10 % 9, , Q3D/ x 400 V ± 10 % Q3D/ x 400 V ± 10 % 15-18, Q3D/ x 400 V ± 10 % 18, Q3D/ x 400 V ± 10 % Q3D/ x 400 V ± 10 % CB-Q3D_a_te 535

20 Q3Y Series Three-phase electric panels for the protection and control of a 4 three-phase surface or submersible pump. Manual control through A-0-M switch Automatic control through an external contactor Supply voltage: 3 x 400 V ±10% Frequency: 50/60 Hz Low voltage auxiliary circuit 24 Vac Power: 4 to 315 kw Star-delta starting Overload protection Protection: IP54 Ambient temperature: -5 to +40 C (limit specified by EN standard ) Maximum relative humidity: 50% at +40 C provided that no condensation occurs (limit specified by EN standard ) Wall mounted Metal enclosure Power - pump running - thermal overload - dry running indicator lights Ready for installation of dry-running control with float or pressure switch (available separately). Electronic protection module with electrodes can be fitted Optional accessories SLD series 24V level kit: Probe module for protection against dry running (set of three electrodes included in the supply) Float switch Pressure switch VR3/SCA3 three-phase module for overvoltage protection (lightning protector) For proper electric panel-electric pump selection, make sure that the Ampere input of the motor falls within the rated current range shown in the table. 536

21 Q3Y SERIES A C 500 V 300 A L1-L2 L2-L3 L3-L B M 0 A MODEL RATED RATED RATED DIMENSIONS WEIGHT VOLTAGE POWER CURRENT A B C V kw HP A mm mm mm Kg Q3Y/ x 400 V ± 10 % 4-,5 5, Q3Y/ x 400 V ± 10 %,5-9, , Q3Y/ x 400 V ± 10 % 9, , Q3Y/ x 400 V ± 10 % Q3Y/ x 400 V ± 10 % 15-18, Q3Y/ x 400 V ± 10 % 18, Q3Y/ x 400 V ± 10 % Q3Y/ x 400 V ± 10 % Q3Y/ x 400 V ± 10 % Q3Y/ x 400 V ± 10 % Q3Y/ x 400 V ± 10 % p 1300p 300p 109 Q3Y/ x 400 V ± 10 % p 1300p 300p 109 Q3Y/ x 400 V ± 10 % p 1500p 300p 120 Q3Y/ x 400 V ± 10 % p 100p 400p 130 Q3Y/ x 400 V ± 10 % p 100p 400p 130 Q3Y/ x 400 V ± 10 % p 1900p 400p 140 Q3Y/ x 400 V ± 10 % p 1900p 400p 180 Q3Y/ x 400 V ± 10 % p 1900p 400p 180 Dimensions note : P indicates floor mounted control panel. CB-Q3Y-en_c_te 53

22 Q3I Series Three-phase electric panels for the protection and control of a 4 three-phase surface or submersible pump. Manual control through A-0-M switch Automatic control through an external contactor Supply voltage: 3 x 400 V ±10% Frequency: 50/60 Hz Low voltage auxiliary circuit 24 Vac Power: 4 to 315 kw Impedance starting Overload protection Protection: IP54 Ambient temperature: -5 to +40 C (limit specified by EN standard ) Maximum relative humidity: 50% at +40 C provided that no condensation occurs (limit specified by EN standard ) Wall mounted Metal enclosure Power - pump running - thermal overload - dry running indicator lights Ready for installation of dry-running control with float or pressure switch (available separately) Electronic protection module with electrodes can be fitted Optional accessories SLD series 24V level kit: Probe module for protection against dry running (set of three electrodes included in the supply) Float switch Pressure switch VR3/SCA3 three-phase module for overvoltage protection (lightning protector) For proper electric panel-electric pump selection, make sure that the Ampere input of the motor falls within the rated current range shown in the table. 538

23 Q3I SERIES A C 500 V 300 A L1-L2 L2-L3 L3-L B M 0 A MODEL RATED RATED RATED DIMENSIONS WEIGHT VOLTAGE POWER CURRENT A B C V kw HP A mm mm mm Kg Q3I/ x 400 V ± 10 % 4-,5 5, Q3I/ x 400 V ± 10 %,5-9, , Q3I/ x 400 V ± 10 % 9, , Q3I/ x 400 V ± 10 % Q3I/ x 400 V ± 10 % 15-18, Q3I/ x 400 V ± 10 % 18, Q3I/ x 400 V ± 10 % Q3I/ x 400 V ± 10 % Q3I/ x 400 V ± 10 % Q3I/ x 400 V ± 10 % p 1300p 300p 100 Q3I/ x 400 V ± 10 % p 1300p 300p 100 Q3I/ x 400 V ± 10 % p 1500p 300p 100 Q3I/ x 400 V ± 10 % p 100p 400p 100 Q3I/ x 400 V ± 10 % p 100p 400p 150 Q3I/ x 400 V ± 10 % p 100p 400p 150 Q3I/ x 400 V ± 10 % p 1900p 400p 160 Q3I/ x 400 V ± 10 % p 1900p 400p 180 Q3I/ x 400 V ± 10 % p 1900p 400p 200 Dimensions note : P indicates floor mounted control panel. CB-Q3I-en_c_te 539

24 Q3SF Series Three-phase electric panels for the protection and control of a 4 three-phase surface or submersible pump. Manual control through A-0-M switch Automatic control through an external contactor Supply voltage: 3 x 400 V ±10% Frequency: 50/60 Hz Low voltage auxiliary circuit 24 Vac Power: 5.5 to 110 kw Soft start with torque control Protection: IP54 Ambient temperature: -5 to +40 C (limit specified by EN standard ) Maximum relative humidity: 50% at +40 C provided that no condensation occurs (limit specified by EN standard ) Wall mounted Metal enclosure Dry running indicator light Power-running-failure indicator LEDs on starter keypanel 0-1 selector switch for activation of bypass contactor Ready for installation of dry-running control with float or pressure switch (available separately) Electronic protection module with electrodes can be fitted Static starter for gradual starting and stopping featuring keypanel with liquid crystal display Optional accessories SLD series 24V level kit: Probe module for protection against dry running (set of three electrodes included in the supply) Float switch Pressure switch VR3/SCA3 three-phase module for overvoltage protection (lightning protector) For proper electric panel-electric pump selection, make sure that the Ampere input of the motor falls within the rated current range shown in the table. 540

25 Q3SF SERIES PANEL TYPE RATED RATED RATED DIMENSIONS WEIGHT VOLTAGE POWER CURRENT A B C V kw HP A mm mm mm Kg Q3SF 5 3 x 400 V ± 10 % 5,5 -,5,5-10 8, Q3SF x 400 V ± 10 % 9, , Q3SF x 400 V ± 10 % 18, Q3SF x 400 V ± 10 % Q3SF 30 3 x 400 V ± 10 % Q3SF x 400 V ± 10 % Q3SF x 400 V ± 10 % Q3SF x 400 V ± 10 % Q3SF 50 3 x 400 V ± 10 % p 100p 400p 120 Q3SF x 400 V ± 10 % p 100p 400p 120 Q3SF x 400 V ± 10 % p 100p 400p 120 Dimensions note : P indicates floor mounted control panel. CB-Q3SF_b_te 541

26 QDR Series Three-phase electric panels for the protection and control of a three-phase drainage pump. Automatic control through electromechanical floats Supply voltage: 3 x 400 V ±10% Frequency: 50/60 Hz Power: 0.36 to 9.2 kw Direct motor starting Protection: IP54 Ambient temperature: -5 to +40 C (limit specified by EN standard ) Maximum relative humidity: 50% at +40 C provided that no condensation occurs (limit specified by EN standard ) Wall mounted Metal enclosure Power, thermal overload, high level indicator lights Alarm reset button /TS version with stator thermal protection circuit /WD version with water control probe in oil bath and stator thermal protection Optional accessories Audible or visual signalling device, 12 Vdc 0.3 A max. (inside the electric panel there are two connection terminals) for high-level alarm VR3 three-phase module for overvoltage protection (lightning protector) For proper electric panel-electric pump selection, make sure that the Ampere input of the motor falls within the rated current range shown in the table. 542

27 QDR SERIES MODEL RATED RATED RATED DIMENSIONS WEIGHT VOLTAGE POWER CURRENT A B C V kw HP A mm mm mm Kg QDR/03 3 x 400 V ± 10 % 0,3 0,5 0, ,1 QDR/05 3 x 400 V ± 10 % 0,55 0,5 1 1, ,1 QDR/0 3 x 400 V ± 10 % 0,5 1 1,6 2, ,1 QDR/15 3 x 400 V ± 10 % 1,1 1,5 1,5 2 2, ,1 QDR/22 3 x 400 V ± 10 % 2, , ,1 QDR/40 3 x 400 V ± 10 % ,5 6, ,1 QDR/5 3 x 400 V ± 10 % 5,5,5, ,1 QDR/0/TS 3 x 400 V ± 10 % 0,5 1 1,6 2, ,5 QDR/15/TS 3 x 400 V ± 10 % 1,5 2 2, ,5 QDR/22/TS 3 x 400 V ± 10 % 2, , ,5 QDR/0/WD 3 x 400 V ± 10 % 0,5 1 1,6 2, QDR/15/WD 3 x 400 V ± 10 % 1,5 2 2, QDR/22/WD 3 x 400 V ± 10 % 2, , The /WD option also includes the /TS option. CB-QDR-en_c_te 543

28 QDR2 Series Three-phase electric panels for the protection and control of two three-phase drainage pumps. Automatic control through electromechanical floats Supply voltage: 3 x 400 V ±10% Frequency: 50/60 Hz Power: 0.3 to 9.2 kw Direct motor starting Protection: IP54 Ambient temperature: -5 to +40 C (limit specified by EN standard ) Maximum relative humidity: 50% at +40 C provided that no condensation occurs (limit specified by EN standard ) Wall mounted Metal enclosure Electronic board with power, overload, high-level alarm, pump on/off indicator lights Alarm reset button /TS version with stator thermal protection circuit /WD version with water control probe in oil bath and stator thermal protection Optional accessories Audible or visual signalling device, 12 Vdc 0.3 A max. (inside the electric panel there are two connection terminals) for high-level alarm VR3 three-phase module for overvoltage protection (lightning protector) Signal relay board kit (power, aut/man, on/off, overload, high level) For proper electric panel-electric pump selection, make sure that the Ampere input of the motor falls within the rated current range shown in the table. 544

29 QDR2 SERIES MODEL RATED RATED RATED DIMENSIONS WEIGHT VOLTAGE POWER CURRENT A B C V kw HP A mm mm mm Kg QDR2/03 3 x 400 V ± 10 % 0,3 0,5 0, ,4 QDR2/05 3 x 400 V ± 10 % 0,55 0,5 1 1, ,4 QDR2/0 3 x 400 V ± 10 % 0,5 1 1,6 2, ,4 QDR2/15 3 x 400 V ± 10 % 1,1 1,5 1,5 2 2, ,4 QDR2/22 3 x 400 V ± 10 % 2, , ,4 QDR2/40 3 x 400 V ± 10 % ,5 6, ,4 QDR2/5 3 x 400 V ± 10 % 5,5,5, ,4 QDR2/92 3 x 400 V ± 10 % 9,2 12, QDR2/0/TS 3 x 400 V ± 10 % 0,5 1 1,6 2, QDR2/15/TS 3 x 400 V ± 10 % 1,1 1,5 1,5 2 2, QDR2/22/TS 3 x 400 V ± 10 % 2, , QDR2/0/WD 3 x 400 V ± 10 % 0,5 1 1,6 2, QDR2/15/WD 3 x 400 V ± 10 % 1,1 1,5 1,5 2 2, QDR2/22/WD 3 x 400 V ± 10 % 2, , The /WD option also includes the /TS option. CB-QDR2-en_b_te 545

30 QDRM Series Single-phase electric panels for the protection and control of a single-phase drainage pump. Automatic control through electromechanical floats Supply voltage: 1 x 230 V ±10% Frequency: 50/60 Hz Power: 0.25 to 2.2 kw Direct motor starting Protection: IP54 Ambient temperature: -5 to +40 C (limit specified by EN standard ) Maximum relative humidity: 50% at +40 C provided that no condensation occurs (limit specified by EN standard ) Wall mounted Metal enclosure Power, thermal overload, high level indicator lights Alarm reset button Optional accessories Audible or visual signalling device, 12 Vdc 0.3 A max. (inside the electric panel there are two connection terminals) for high-level alarm VR1 single-phase module for overvoltage protection (lightning protector) For proper electric panel-electric pump selection, make sure that the Ampere input of the motor falls within the rated current range shown in the table. 546

31 QDRM SERIES MODEL RATED RATED RATED DIMENSIONS WEIGHT VOLTAGE POWER CURRENT A B C V kw HP A mm mm mm Kg QDRM/02 1 x 230 V ± 10 % 0,25 0,33 1 1, ,2 QDRM/03 1 x 230 V ± 10 % 0,3 0,5 1,6 2, ,2 QDRM/05 1 x 230 V ± 10 % 0,55 0,5 2, ,2 QDRM/0 1 x 230 V ± 10 % 0, , ,2 QDRM/15 1 x 230 V ± 10 % 1,1 1,5 1,5 2 6, ,2 QDRM/22 1 x 230 V ± 10 % 2, ,1 CB-QDRM-en_c_te 54

32 QDRMC Series Single-phase electric panels for the protection and control of a single-phase drainage pump with external capacitor. Automatic control through electromechanical floats Supply voltage: 1 x 230 V ±10% Frequency: 50/60 Hz Power: 0.5 to 2.2 kw Direct motor starting Protection: IP54 Ambient temperature: -5 to +40 C (limit specified by EN standard ) Maximum relative humidity: 50% at +40 C provided that no condensation occurs (limit specified by EN standard ) Wall mounted Plastic enclosure Power, thermal overload, high level indicator lights Alarm reset button Run and start capacitor in panel/ts version with stator thermal protection circuit/wd version with water control probe in oil bath and stator thermal protection Optional accessories Audible or visual signalling device, 12 Vdc 0.3 A max. (inside the electric panel there are two connection terminals) for high-level alarm VR1 single-phase module for overvoltage protection (lightning protector) For proper electric panel-electric pump selection, make sure that the Ampere input of the motor falls within the rated current range shown in the table. 548

33 QDRMC SERIES MODEL RATED RATED RATED DIMENSIONS WEIGHT C Cs VOLTAGE POWER CURRENT A B C V kw HP A mm mm mm Kg uf uf QDRMC/0 1 x 230 V ± 10 % 0, , , QDRMC/15 1 x 230 V ± 10 % 1,5 2 6, , QDRMC/22 1 x 230 V ± 10 % 2, , QDRMC/0/TS 1 x 230 V ± 10 % 0, , , QDRMC/15/TS 1 x 230 V ± 10 % 1,5 2 6, , QDRMC/22/TS 1 x 230 V ± 10 % 2, , QDRMC/0/WD 1 x 230 V ± 10 % 0, , QDRMC/15/WD 1 x 230 V ± 10 % 1,5 2 6, QDRMC/22/WD 1 x 230 V ± 10 % 2, QDRMC/15/TS/GL 1 x 230 V ± 10 % 1,5 2 6, C= Run capacitor; Cs= Start capacitor CB-QDRMC-en_e_te 549

34 QDRM2 Series Single-phase electric panels for the protection and control of two single-phase drainage pumps. Automatic control through electromechanical floats Supply voltage: 1 x 230 V ±10% Frequency: 50/60 Hz Power: 0.25 to 2.2 kw Direct motor starting Protection: IP54 Ambient temperature: -5 to +40 C (limit specified by EN standard ) Maximum relative humidity: 50% at +40 C provided that no condensation occurs (limit specified by EN standard ) Wall mounted Metal enclosure Electronic board with power, overload, high-level alarm, pump on/off indicator lights Alarm reset button Optional accessories Audible or visual signalling device, 12 Vdc 0.3 A max. (inside the electric panel there are two connection terminals) for high-level alarm VR1 single-phase module for overvoltage protection (lightning protector) Signal relay board kit (power, aut/man, on/off, overload, high level) For proper electric panel-electric pump selection, make sure that the Ampere input of the motor falls within the rated current range shown in the table. 550

35 QDRM2 SERIES PANEL TYPE RATED RATED RATED DIMENSIONS WEIGHT VOLTAGE POWER CURRENT A B C V kw HP A mm mm mm Kg QDRM2/02 1 x 230 V ± 10 % 0,25 0,33 1 1, ,4 QDRM2/03 1 x 230 V ± 10 % 0,3 0,5 1,6 2, ,4 QDRM2/05 1 x 230 V ± 10 % 0,55 0,5 2, ,4 QDRM2/0 1 x 230 V ± 10 % 0, , ,4 QDRM2/15 1 x 230 V ± 10 % 1,1 1,5 1,5 2 6, ,4 QDRM2/22 1 x 230 V ± 10 % 2, ,4 CB-QDRM2_a_te 551

36 QDRMC2 Series Single-phase electric panels for the protection and control of two single-phase drainage pumps with external capacitor. Automatic control through electromechanical floats Supply voltage: 1 x 230 V ±10% Frequency: 50/60 Hz Power: 0.5 to 2.2 kw Direct motor starting Protection: IP54 Ambient temperature: -5 to +40 C (limit specified by EN standard ) Maximum relative humidity: 50% at +40 C provided that no condensation occurs (limit specified by EN standard ) Wall mounted Plastic enclosure Electronic board with power, overload, high-level alarm, pump on/off indicator lights Alarm reset button Run and start capacitor in panel /TS version with stator thermal protection circuit /WD version with water control probe in oil bath and stator thermal protection Optional accessories Audible or visual signalling device, 12 Vdc 0.3 A max. (inside the electric panel there are two connection terminals) for high-level alarm VR1 single-phase module for overvoltage protection (lightning protector) Signal relay board kit (power, aut/man, on/off, overload, high level) For proper electric panel-electric pump selection, make sure that the Ampere input of the motor falls within the rated current range shown in the table. 552

37 QDRMC2 SERIES MODEL RATED RATED RATED DIMENSIONS WEIGHT C Cs VOLTAGE POWER CURRENT A B C V kw HP A mm mm mm Kg uf uf QDRMC2/0 1 x 230 V ± 10 % 0, , , QDRMC2/15 1 x 230 V ± 10 % 1,5 2 6, , QDRMC2/22 1 x 230 V ± 10 % 2, , QDRMC2/0/TS 1 x 230 V ± 10 % 0, , QDRMC2/15/TS 1 x 230 V ± 10 % 1,5 2 6, QDRMC2/22/TS 1 x 230 V ± 10 % 2, QDRMC2/0/WD 1 x 230 V ± 10 % 0, , QDRMC2/15/WD 1 x 230 V ± 10 % 1,5 2 6, QDRMC2/22/WD 1 x 230 V ± 10 % 2, QDRMC2/15/TS/GL 1 x 230 V ± 10 % 1,5 2 6, C = Run capacitor; Cs = Start capacitor. CB-QDRMC2-en_d_te 553

38 QGMC Series Single-phase electric panels for the protection and control of a single-phase drainage pump with external capacitor. Automatic control through external contact Supply voltage: 1 x 230 V ±10% Frequency: 50 Hz Power: 0.5 to 2.2 kw Direct motor starting Protection: IP55 Ambient temperature: -5 to +40 C (limit specified by EN standard ) Maximum relative humidity: 50% at +40 C provided that no condensation occurs (limit specified by EN standard ) Wall mounted Plastic enclosure Built-in run capacitor Built-in start capacitor Built-in starter Main switch with thermal protection For proper electric panel-electric pump selection, make sure that the Ampere input of the motor falls within the rated current range shown in the table. 554

39 QGMC SERIES PANEL TYPE RATED RATED RATED DIMENSIONS WEIGHT C Cs VOLTAGE POWER CURRENT A B C V kw HP A mm mm mm Kg F F QGMC/0 1 x 230 V ± 10 % 0, , QGMC/15 1 x 230 V ± 10 % 1,5 2 6, QGMC/22 1 x 230 V ± ±10 % 2, C = Run capacitor; Cs = Start capacitor. CB-QGMC_a_te 555

40 QYR Series Three-phase electric panels for the protection and control of a three-phase drainage pump with star-delta starting. VR3 (for QDR) three-phase module for overvoltage protection (lightning protector) Automatic control through electromechanical floats Supply voltage: 3 x 400 V ±10% Frequency: 50/60 Hz Power: 3 to 5 kw Star-delta starting Protection: IP54 Ambient temperature: -5 to +40 C (limit specified by EN standard ) Maximum relative humidity: 50% at +40 C provided that no condensation occurs (limit specified by EN standard ) Wall mounted Metal enclosure Power, thermal overload, high level indicator lights Alarm reset button /TS version with stator thermal protection circuit /WD version with water control probe in oil bath and stator thermal protection Optional accessories Audible or visual signalling device, 12 Vdc 0.3 A max. (inside the electric panel there are two connection terminals) for high-level alarm For proper electric panel-electric pump selection, make sure that the Ampere input of the motor falls within the rated current range shown in the table. 556

41 QYR SERIES MODEL RATED RATED RATED DIMENSIONS WEIGHT VOLTAGE POWER CURRENT A B C V kw HP A mm mm mm Kg QYR/40 3 x 400 V ± 10 % ,5 6, QYR/5 3 x 400 V ± 10 % 5,5, QYR/92 3 x 400 V ± 10 % 9,2 12, QYR/110 3 x 400 V ± 10 % QYR/150 3 x 400 V ± 10 % QYR/185 3 x 400 V ± 10 % 18, QYR/220 3 x 400 V ± 10 % QYR/300 3 x 400 V ± 10 % QYR/30 3 x 400 V ± 10 % QYR/450 3 x 400 V ± 10 % QYR/550 3 x 400 V ± 10 % QYR/50 3 x 400 V ± 10 % p 1300p 300p 0 QYR/22/TS 3 x 400 V ± 10 % 2, , QYR/40/TS 3 x 400 V ± 10 % ,5 6, QYR/5/TS 3 x 400 V ± 10 % 5,5,5, QYR/92/TS 3 x 400 V ± 10 % 9,2 12, QYR/110/TS 3 x 400 V ± 10 % QYR/150/TS 3 x 400 V ± 10 % QYR/185/TS 3 x 400 V ± 10 % 18, QYR/220/TS 3 x 400 V ± 10 % QYR/300/TS 3 x 400 V ± 10 % QYR/30/TS 3 x 400 V ± 10 % QYR/450/TS 3 x 400 V ± 10 % QYR/550/TS 3 x 400 V ± 10 % QYR/50/TS 3 x 400 V ± 10 % p 1300p 300p 0 QYR/40/WD 3 x 400 V ± 10 % ,5 6, QYR/5/WD 3 x 400 V ± 10 % 5,5,5, QYR/92/WD 3 x 400 V ± 10 % 9,2 12, QYR/110/WD 3 x 400 V ± 10 % QYR/150/WD 3 x 400 V ± 10 % QYR/185/WD 3 x 400 V ± 10 % 18, QYR/220/WD 3 x 400 V ± 10 % QYR/300/WD 3 x 400 V ± 10 % QYR/30/WD 3 x 400 V ± 10 % QYR/450/WD 3 x 400 V ± 10 % QYR/550/WD 3 x 400 V ± 10 % QYR/50/WD 3 x 400 V ± 10 % p 1300p 300p 1 Dimensions: p = floor-standing cabinet. CB-QYR-en_e_te 55

42 QYR2 Series Three-phase electric panels for the protection and control of two three-phase drainage pumps with star-delta starting. Automatic control through electromechanical floats Supply voltage: 3 x 400 V ±10% Frequency: 50/60 Hz Power: 3 to 5 kw Star-delta starting Protection: IP54 Ambient temperature: -5 to +40 C (limit specified by EN standard ) Maximum relative humidity: 50% at +40 C provided that no condensation occurs (limit specified by EN standard ) Wall mounted Metal enclosure Electronic board with power, overload, high-level alarm, pump on/off indicator lights Alarm reset button /TS version with stator thermal protection circuit /WD version with water control probe in oil bath and stator thermal protection Optional accessories Audible or visual signalling device, 12 Vdc 0.3 A max. (inside the electric panel there are two connection terminals) for high-level alarm VR3 three-phase module for overvoltage protection (lightning protector) Signal relay board kit (power, aut/man, on/off, overload, high level) For proper electric panel-electric pump selection, make sure that the Ampere input of the motor falls within the rated current range shown in the table. 558

43 QYR2 SERIES MODEL RATED RATED RATED DIMENSIONS WEIGHT VOLTAGE POWER CURRENT A B C V kw HP A mm mm mm Kg QYR2/40 3 x 400 V ± 10 % ,5 6, QYR2/5 3 x 400 V ± 10 % 5,5,5, QYR2/92 3 x 400 V ± 10 % 9,2 12, QYR2/110 3 x 400 V ± 10 % QYR2/150 3 x 400 V ± 10 % QYR2/185 3 x 400 V ± 10 % 18, QYR2/220 3 x 400 V ± 10 % QYR2/300 3 x 400 V ± 10 % QYR2/30 3 x 400 V ± 10 % p 1300p 300p 92 QYR2/450 3 x 400 V ± 10 % p 100p 300p 125 QYR2/550 3 x 400 V ± 10 % p 100p 300p 125 QYR2/50 3 x 400 V ± 10 % p 1900p 300p 148 QYR2/22/TS 3 x 400 V ± 10 % 2, , QYR2/40/TS 3 x 400 V ± 10 % ,5 6, QYR2/5/TS 3 x 400 V ± 10 % 5,5,5, QYR2/92/TS 3 x 400 V ± 10 % 9,2 12, QYR2/110/TS 3 x 400 V ± 10 % QYR2/150/TS 3 x 400 V ± 10 % QYR2/185/TS 3 x 400 V ± 10 % 18, QYR2/220/TS 3 x 400 V ± 10 % QYR2/300/TS 3 x 400 V ± 10 % QYR2/30/TS 3 x 400 V ± 10 % p 1300p 300p 92 QYR2/450/TS 3 x 400 V ± 10 % p 100p 300p 125 QYR2/550/TS 3 x 400 V ± 10 % p 100p 300p 125 QYR2/50/TS 3 x 400 V ± 10 % p 1900p 300p 148 QYR2/40/WD 3 x 400 V ± 10 % ,5 6, QYR2/5/WD 3 x 400 V ± 10 % 5,5,5, QYR2/92/WD 3 x 400 V ± 10 % 9,2 12, QYR2/110/WD 3 x 400 V ± 10 % QYR2/150/WD 3 x 400 V ± 10 % QYR2/185/WD 3 x 400 V ± 10 % 18, QYR2/220/WD 3 x 400 V ± 10 % QYR2/300/WD 3 x 400 V ± 10 % QYR2/30/WD 3 x 400 V ± 10 % p 1300p 300p 92 QYR2/450/WD 3 x 400 V ± 10 % p 100p 300p 125 QYR2/550/WD 3 x 400 V ± 10 % p 100p 300p 125 QYR2/50/WD 3 x 400 V ± 10 % p 1900p 300p 148 Dimensions: p = floor-standing cabinet. CB-QYR2-en_b_te 559

44 QXR20 Series Protection and control of two single-phase drainage pumps. Automatic control through electromechanical floats Power supply voltage: 1 x 230 V ±10% Frequency: 50/60 Hz Power: 0,25 to 1,5 kw Direct motor start Protection class: IP55 Ambient temperature: -5 to +40 C (according to EN ) Maximum relative humidity: 50% at +40 C, provided that no condensation occurs (according to EN ) Wall mounted Plastic enclosure Electronic board with power, thermal overload, acustic alarm of high level, pump, start/stop indicator LEDs Alarm silencing button Cyclic exchange starting pumps Aut-0-Man selector (1 for each pump) One pump is controlled by the closing of internal contact that is inside the control card Optional accessories Signal relay board kit (power, auto man, start/stop, thermal overload, high level) For proper electric panel-electric pump selection, make sure that the Ampere input of the motor falls within the rated current range shown in the table. 560

45 QXR20 SERIES MODEL RATED RATED RATED DIMENSIONS WEIGHT VOLTAGE POWER CURRENT A B C V kw HP A mm mm mm Kg QXR20 1 x 230 V ± 10 % 0,25 1,5 0, ,5 CB-QXR20-en_a_te 561

46 QCL5 Series Level control panel. Accessory for electric pump control panels, suitable for tank filling or drainage applications or for activation of sound or visual alarms. Automatic control through probes Power supply: 1 x 230 V ±10% o 1 x 24 V ±10% Frequency: 50/60 Hz Voltage to probes: 15 Vac at 0.5 ma max. Switch contact: 48 Vac at 3 A max. (250 W max.) Protection: IP55 Ambient temperature: -5 to +40 C (limit specified by EN standard ) Maximum relative humidity: 50% at +40 C provided that no condensation occurs (limit specified by EN standard ) Wall mounted Plastic enclosure Electrodes suitable for water at a maximum temperature of 40 C Set of three electrodes included in supply Optional accessories Drop cable with circular cross-section For connecting electrodes to the panel, the following cross-sections are recommended: PANEL TYPE m CABLE CROSS SECTION mm , , , ,5 400 > 4,0 CB-CASEL_a_te Three-pole cables can be used for short lengths. Otherwise, one-pole cables placed at suitable distances from each other should be used to prevent the capacitive effect of the cable from interfering with the proper operation of the electronic module. For proper electric panel-electric pump selection, make sure that the Ampere input of the motor falls within the rated current range shown in the table. 562

47 QCL5 SERIES PANEL TYPE POWER INPUT CONTACTS DIMENSIONS WEIGHT TENSION FREQUENCY POWER PANEL TYPE DELIVERY A x B x C V Hz W V A mm Kg QCL5/24 1 x 24 50/60 2 QCL5/230 1 x /60 2 NO-C-NC x 130 x 60 0,5 CB-QCL5_a_te 563

48 QCL10 Series Level control panel. Accessory for electric pump control panels, suitable for tank filling or drainage applications or for activation of sound or visual alarms. Automatic control through probes Power supply: 1 x 230 V ±10% o 1 x 24 V ±10% Frequency: 50/60 Hz Voltage to probes: 15 Vac at 0.5 ma max. Protection: IP55 Ambient temperature: -5 to +40 C (limit specified by EN standard ) Maximum relative humidity: 50% at +40 C provided that no condensation occurs (limit specified by EN standard ) Wall mounted Plastic enclosure Electrodes suitable for water at a maximum temperature of 40 C Set of three electrodes included in supply Optional accessories Drop cable with circular cross-section For connecting electrodes to the panel, the following cross-sections are recommended: PANEL TYPE m CABLE CROSS SECTION mm , , , ,5 400 > 4,0 CB-CASEL_a_te Three-pole cables can be used for short lengths. Otherwise, one-pole cables placed at suitable distances from each other should be used to prevent the capacitive effect of the cable from interfering with the proper operation of the electronic module. For proper electric panel-electric pump selection, make sure that the Ampere input of the motor falls within the rated current range shown in the table. 564

49 QCL10 SERIES PANEL TYPE POWER INPUT CONTACTOR DIMENSIONS WEIGHT MAIN SECONDARY CLASS DELIVERY A x B x C V V V A mm Kg QCL10/24 1x230 50/60 Hz 1x 24 50/60 Hz QCL10/230 1x230 50/60 Hz - AC x 10 x CB-QCL10_a_te 565

50 QCLP10 Series Level control panel. Accessory for electric pump control panels, suitable for tank filling or drainage applications or for activation of sound or visual alarms. Automatic control through probes Power input: 1 x 230 V ±10% o 1 x 24 V ±10% Frequency: 50/60 Hz Voltage to probes: 15 Vac at 0.5 ma max. Protection: IP55 Ambient temperature: -5 to +40 C (limit specified by EN standard ) Maximum relative humidity: 50% at +40 C provided that no condensation occurs (limit specified by EN standard ) Wall mounted Plastic enclosure with clear door enabling access to the magnetothermal switch Electrodes suitable for water at a maximum temperature of 40 C Set of three electrodes included in supply Optional accessories Drop cable with circular cross-section For connecting electrodes to the panel, the following cross-sections are recommended: PANEL TYPE m CABLE CROSS SECTION mm , , , ,5 400 > 4,0 CB-CASEL_a_te Three-pole cables can be used for short lengths. Otherwise, one-pole cables placed at suitable distances from each other should be used to prevent the capacitive effect of the cable from interfering with the proper operation of the electronic module. For proper electric panel-electric pump selection, make sure that the Ampere input of the motor falls within the rated current range shown in the table. 566

51 QCLP10 SERIES PANEL TYPE POWER INPUT CONTACTOR MAGNETOTHERMAL DIMENSIONS WEIGHT MAIN SECONDARY CLASS DELIVERY SWITCH A x B x C V V V A mm Kg QCLP10/24 1x230 50/60 Hz 1x 24 50/60 Hz AC C 10A Icn 6 KA 10 x 10 x 100 1,5 QCLP10/230 1x230 50/60 Hz - CB-QCLP10_a_te 56

52 KSL Series Accessory for electric panels. Electronic module for use of probes as protection against dry running Supply voltage: 1 x 24 V ±10% for model SLD/24 Frequency: 50/60 Hz Absorbed power: 3,5 VA max Voltage to probes:,5 V AC at 0,4 ma max Switch contact 24 V AC at 5 A max (250 W max) Designed for installation on Lowara electric panels featuring DIN bar Electrodes suitable for water at a maximum temperature of 60 C Optional accessories Module made of plastic material with DIN bar attachment Cables with quick plug-in connectors Set of three electrodes included in the supply Electrodes with nylon 6 body, stainless steel sensitive element brass washer and nitrile rubber seal Optional accessories Drop cable with circular cross section. For connection of the electrodes to the panel we recommend the following cross sections: PANEL TYPE CABLE CROSS SECTION m mm , , , ,5 400 > 4,0 CB-CASEL_a_te Three-pole cables can be used for short lenghts. Otherwise we recommend the use of unipolar cables placed at suitable distance from each other to prevent the capacitive effect of the cable from interfering with the proper operation of the electronic module. TYPE POWER SUPPLY CONTACT DIMENSIONS WEIGHT PANELS MAIN POWER TYPE RANGE A x B x C V VA V~ A mm Kg KIT KSL/24 1x24 50/60 Hz 3,5 N0-C-NC x 36 x 60 0,5 QSCS-QM-QTD-Q3D-Q3Y- Q3A-Q3I-Q3SF CB-SLD-en_b_te For proper electric panel-electric pump selection, make sure that the Ampere input of the motor falls within the rated current range shown in the table. 568

53 DPF, VR, SCA3 Series Lightining protection. Accessory for electric panels. DPF SERIES Varistor for overvoltage protection of single-phase lines. To be connected between the phase and neutral conductor Operating voltage: 460 V AC Maximum varistor voltage: 50 V with 100 A peak current VR SERIES SCA3 SERIES Lightning arresters for overvoltage protection of three-phase lines. To be connected between the phases and the heart conductor Operating voltage: 500 V AC. Maximum varistor voltage: 2,5 kw with 40 ka peak current. Designed for installation on Lowara electric panels featuring DIN bar Varistors for overvoltage protection of three-phase lines To be connected between the phases (VR3 model) Operating voltage: 460 V AC Maximum varistor voltage: 50 V with 100 A peak current Designed for installation on Lowara electric panels featuring DIN bar DPF KIT VR1 KIT VR3 KIT SCA 3 TYPE VOLTAGE V 1 x x x x /60 Hz 50/60 Hz 50/60 Hz 50/60 Hz PANELS QSM - QSC - QSCS - QPC QM - QDRM - QDRM2 - QDRMC - QDRMC2 QTD - QDR - QDR2 - Q3D Q3Y-Q3A-Q3I-Q3SF-Q3D CB-VR-en_c_te For proper electric panel-electric pump selection, make sure that the Ampere input of the motor falls within the rated current range shown in the table. 569

LC/LCD ranges level controllers

LC/LCD ranges level controllers GRUNDFOS WASTEWATER LC/LCD ranges level controllers 18 Grundfos Sololifts > Grundfos LC/LCD controllers Keeping a close eye on liquid levels Reliable level controllers from Grundfos Grundfos offers a choice

More information

Quick Connect. quick - simple - efficient. www.g-mw.de

Quick Connect. quick - simple - efficient. www.g-mw.de Quick Connect quick - simple - efficient www.g-mw.de Phone: +49 9103 7129-0 Fax: +49 9103 7129-207 Innovative connection technology to plug three single-phase current transformers to multifunctional power

More information

PSR The compact range Description

PSR The compact range Description Description The PSR range is the most compact of all the ABB softstarter ranges, thereby making it possible to fit many devices into the same enclosure. The system concept with Manual Motor Starters provides

More information

Thyristor-controlled power supplies and battery chargers

Thyristor-controlled power supplies and battery chargers Thyristor-controlled power supplies and battery chargers Input voltage: 115 / 230 VAC, single phase, 50 / 60 Hz or 208 / 400 / 480 VAC, three phases, 50 / 60 Hz Output voltage: 12 / 24 / 48 / 60 / 72 /

More information

Series description: Wilo-Drain TC 40

Series description: Wilo-Drain TC 40 Series description: Wilo-Drain TC 40 H[m] Wilo-Drain TC 40 10 8 6 4 2 TC 40/8 TC 40/10 0 0 2 4 6 8 10 12 14 Q[m³/h] Design Submersible sewage pump Application Pumping heavily contaminated fluids for House/site

More information

Products and solutions for lifting systems

Products and solutions for lifting systems Products and solutions for lifting systems 100% electricity www.lovatoelectric.com Tra dition and Innovation LOVATO Electric S.p.A. - Bergamo - Italy Since 1922 The first LOVATO Electric headquarters founded

More information

HERZ-Thermal Actuators

HERZ-Thermal Actuators HERZ-Thermal Actuators Data Sheet 7708-7990, Issue 1011 Dimensions in mm 1 7710 00 1 7710 01 1 7711 18 1 7710 80 1 7710 81 1 7711 80 1 7711 81 1 7990 00 1 7980 00 1 7708 11 1 7708 10 1 7708 23 1 7709 01

More information

VLT Series 3500 Adjustable Frequency Drive Instruction Manual

VLT Series 3500 Adjustable Frequency Drive Instruction Manual Adjustable Frequency Drive Instruction Manual VLT Series 3500 Instruction Manual 175R5237 - Document Version 5.00 This manual applies to all VLT Series 3502-3800 Adjustable Frequency Drives with software

More information

2CP. Twin-impeller pumps PERFORMANCE RANGE INSTALLATION AND USE APPLICATION LIMITS OPTIONALS AVAILABLE ON REQUEST CONSTRUCTION AND SAFETY STANDARDS

2CP. Twin-impeller pumps PERFORMANCE RANGE INSTALLATION AND USE APPLICATION LIMITS OPTIONALS AVAILABLE ON REQUEST CONSTRUCTION AND SAFETY STANDARDS 2CP Twin-impeller pumps PERFORMANCE RANGE Flow rate up to 40 l/min (27 m³/h) Head up to 112 m APPLICATION LIMITS Manometric suction lift up to 7 m Liquid temperature between -10 C and +90 C Ambient temperature

More information

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller Overview/Modes of Operation Bulletin 150 Smart Motor Controller The SMC-3 is a compact, simple to use, solid-state motor controller designed to operate 3-phase motors. It features a built-in overload relay

More information

Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated. Ordering information

Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated. Ordering information Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated Ordering information Connection technique Description Description Rated operational current Screw terminals 3 pole AC

More information

Technical catalogue. Modular DIN rail components Installation contactors

Technical catalogue. Modular DIN rail components Installation contactors Technical catalogue Modular DIN rail components Installation contactors Installation Contactors Overview... ESB Installation Contactors 0 A / AC-/AC-7a ESB0...4 4 A / AC-/AC-7a ESB4...5 40 A / AC-/AC-7a

More information

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous Safety relay for monitoring E-STOP pushbuttons. Approvals Unit features Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous 1 auxiliary contact (N/C), instantaneous Safe separation of

More information

BETA Switching. Switching Devices. 5TT5 8 Insta contactors, AC technology. Overview

BETA Switching. Switching Devices. 5TT5 8 Insta contactors, AC technology. Overview BETA Switching Siemens AG 200 5TT5 Insta contactors, AC technology Overview The 5TT5 Insta contactors are equipped with an AC magnetic system and are ideal for use under harsh conditions. The auxiliary

More information

Technical data UNIBLOCK UBSF 180 625

Technical data UNIBLOCK UBSF 180 625 Data TECHNICL DT Technical data UNIBLOCK UBSF 80 6 Output data Type UBSF 80 UBSF 0 UBSF 00 UBSF 6 Output power 80 kv 0 kv 00 kv 6 kv Output voltage 80/77 V 0/ V 0/ V 0/ V Output current 7 8 66 80 Power

More information

ABB i-bus KNX Fan Coil Actuator, MDRC FCA/S 1.1M, 2CDG 110 084 R0011

ABB i-bus KNX Fan Coil Actuator, MDRC FCA/S 1.1M, 2CDG 110 084 R0011 , 2CDG 110 084 R0011 2CDC 071 112 F0008 The Fan Coil Actuator is a modular installation device (MDRC) in pro M design. It is intended for installation in the distribution board on 35 mm mounting rails.

More information

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com Product description Wide rated operational voltage 208 600 V AC Wide rated control supply voltage 100 250 V, 50/60 Hz Rated operational current 18 to 370 A Wide ambient temperature range, -25 to +60 ºC

More information

Electronic overload relay EF19 and EF45

Electronic overload relay EF19 and EF45 Data sheet Electronic overload relay EF19 and EF45 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays. Motor

More information

Mini Motor Contactor J7KNA Main contactor Accessories Approved Standards Standard Guide No (US,C) Ordering Information tage Model Number Legend gear

Mini Motor Contactor J7KNA Main contactor Accessories Approved Standards Standard Guide No (US,C) Ordering Information tage Model Number Legend gear Mini Motor Contactor J7KNA ) Main contactor AC & DC operated Integrated auxiliary contacts Screw fixing and snap fitting (35 mm DIN-rail) Range from 4 to 5.5 (AC 3, 380/415V) 4 -main pole version (4 AC

More information

Conlift1, Conlift2, Conlift2 ph+

Conlift1, Conlift2, Conlift2 ph+ GRUNDFOS DATA BOOKLET Conlift1, Conlift2, Conlift2 ph+ Small lifting stations 50 Hz CONLIFT1, CONLIFT2, CONLIFT2 ph+ Table of contents 1. Product overview 3 Conlift for condensate applications 3 Applications

More information

Installation Contactors. Technical Catalogue. Type ESB. abb. ABB STOTZ-KONTAKT GmbH 1 2CDC 103002 C0201

Installation Contactors. Technical Catalogue. Type ESB. abb. ABB STOTZ-KONTAKT GmbH 1 2CDC 103002 C0201 Technical Catalogue Installation Contactors Type ESB abb ABB STOTZ-KONTAKT GmbH 1 CDC 10300 C001 ABB STOTZ-KONTAKT GmbH CDC 10300 C001 Low Voltage Products and Systems We ensure safety and comfort for

More information

AuCom s IMS2 soft starters are a total motor starting solution, combining highlevel functionality with ease of use:

AuCom s IMS2 soft starters are a total motor starting solution, combining highlevel functionality with ease of use: AuCom s IMS2 soft starters are a total motor starting solution, combining highlevel functionality with ease of use: advanced soft start and soft stop control protection functions that operate even when

More information

SURGE PROTECTIVE DEVICES

SURGE PROTECTIVE DEVICES SURGE PROTECTIVE DEVICES 1. INTRODUCTION In order to ensure safety of people, protection of equipment and, to a certain extent, continuity of supply, insulation co-ordination aims at reducing the likelihood

More information

Single-phase (220...240 V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable

Single-phase (220...240 V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable Features 70.11 70.31 70.41 Electronic voltage monitoring relays for single and three-phase applications Multifunctional types, providing the flexibility of monitoring Undervoltage, Overvoltage, Window

More information

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw 4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and

More information

33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application

33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application 33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application Features Compliant with the IEEE802.3at Standard -40 to +60 C Temperature Range Diagnostic LEDs Full Protection

More information

Products and solutions for machine builders (OEM) 100% electricity

Products and solutions for machine builders (OEM) 100% electricity Products and solutions for machine builders (OEM) 100% electricity www.lovatoelectric.com Tra dition and innovation LOVATO Electric S.p.A. - Bergamo - Italy Since 1922 The first LOVATO Electric headquarters

More information

..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark...

..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark... ..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark... TIME MARK CORPORATION 11440 EAST PINE STREET TULSA, OK 74116 USA tel 918 438-1220 fax 918 437-7584 www.time-mark.com

More information

ADS8 IP54 Direct-On-Line Starter Technical Focus. Replaces ADS7 Rated up to 9kW

ADS8 IP54 Direct-On-Line Starter Technical Focus. Replaces ADS7 Rated up to 9kW ADS8 IP54 Direct-On-Line Starter Technical Focus Replaces ADS7 Rated up to 9kW New ADS8 Motor Starter The new ADS8 range of motor starters replaces the successful ADS7 range which was introduced 20 years

More information

Number 1 in efficiency

Number 1 in efficiency PowerXL DE1 Variable Speed Starter www.eaton.eu/de1 Number 1 in efficiency The easiest way of variable motor speed NEW Variation DE11 The new device category! The PowerXL DE1 Variable Speed Starter Why

More information

Electronic overload relay EF65, EF96 and EF146

Electronic overload relay EF65, EF96 and EF146 Data sheet Electronic overload relay EF65, EF96 and EF146 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays.

More information

REVIEWED BY CAPITAL PROJECTS MANAGER (DAN REDDY) GENERAL MANAGER EQUIPMENT ENGINEERING & ASSET MANAGEMENT (HAMILTON NXUMALO)

REVIEWED BY CAPITAL PROJECTS MANAGER (DAN REDDY) GENERAL MANAGER EQUIPMENT ENGINEERING & ASSET MANAGEMENT (HAMILTON NXUMALO) SA Port Operations DOCUMENT TYPE: REFERENCE EEAM-Q-014 (ORIGINAL SPECIFICATION HE8.2.3 Ver5) REVISION 0 SPECIFICATION TITLE: SPECIFICATION FOR ELECTRICAL MOTORS AND GENERATORS PAGE 0 of 07 COMPILED BY

More information

JNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410

JNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410 The INTEG is an Ethernet I/O (digital, analog) device that monitors and controls a small set of process signals. functions as both basic I/O for integration with another application or system AND as a

More information

Power Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1

Power Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1 Power Supply Unit, Primary Switched, Narrow Design MINI POWER provides: Extra narrow design with widths of 22.5 mm, 45 mm, and 67.5 mm (0.886, 1.772, and 2.657 in.) Global use due to a wide-range input

More information

PS1800 Centrifugal Pumping Systems

PS1800 Centrifugal Pumping Systems PS1 Centrifugal Pumping Systems General Data and Sizing Tables The curve show the performance range of 4 models at 1Wp solar array - irradiation of 6kWh/m² on a tilted surface - ambient temperature 3 C

More information

Electric Rotary Actuator - On/Off or programmable control actuator

Electric Rotary Actuator - On/Off or programmable control actuator Electric Rotary Actuator - On/Off or programmable control actuator Direct mounting on quarter-turn valves Manual override standard Corrosion resistant Adjustable limit switches Multi-voltage version Type

More information

Example of use: Fuse for a solenoid valve. If the fuse is defective, no information is sent to the electronic component.

Example of use: Fuse for a solenoid valve. If the fuse is defective, no information is sent to the electronic component. Overview Switch and button modules The dimensions of the switch and button modules are adapted to the electronic components in the integral housing. The modules are equipped with the universal clip-on

More information

Heating, air-conditioning, cooling

Heating, air-conditioning, cooling Series description Design High efficiency, single stage, low pressure, inline centrifugal pump Supplied with EC motor and electronic duty adaptation Available in glanded construction, mechanical shaft

More information

Fluid Level Gauge Fluid Level Sensor Temperature Switch FSA / FSK / TS

Fluid Level Gauge Fluid Level Sensor Temperature Switch FSA / FSK / TS Fluid Level Gauge Fluid Level Sensor Temperature Switch FSA / FSK / TS up to size 381; to PN 0.5; to T = 80 C 1. Description 1.1. General FSA fluid level gauges, FSK fluid level sensors and TS temperature

More information

IDEAL INDUSTRIES, INC. TECHNICAL MANUAL MODELS: 61-763 61-765

IDEAL INDUSTRIES, INC. TECHNICAL MANUAL MODELS: 61-763 61-765 IDEAL INDUSTRIES, INC. TECHNICAL MANUAL MODELS: 61-763 61-765 The Service Information provides the following information: Precautions and safety information Specifications Performance test procedure Calibration

More information

Series description: Wilo-Star-Z

Series description: Wilo-Star-Z H[m] Series description: Wilo-Star-Z 4 3 Wilo-Star-Z Star-Z 2/5 2/4 2 1 Star St ar- Z1 5T Design Glandless circulation pump with threaded connection Application Potable water circulation systems in industry

More information

Vario-Series Accessories

Vario-Series Accessories Accessories and spare parts for GMW analogue panel meters and controllers Current Transformers pages 2-9 Shunt Resistors 10-11 Voltage Dividers 12 Power supply for indicator/controllers 13 Blanking Plates

More information

Centro-Matic Automatic Lubrication Systems System Controls

Centro-Matic Automatic Lubrication Systems System Controls Selecting the right controls for your automated lubrication system is one of the last steps in the design process. Several different models may be chosen to control power-operated pumps, depending on the

More information

Frequency Converter Fv

Frequency Converter Fv 2 Bosch Rexroth AG Electric Drives and Controls Documentation Brake chopper with up to 30 kw continuous braking power Easy to operate and service (detachable fan, LCD operating panel with copy function)

More information

Technical Data. back-up time in minutes 100% load 6 7 0 5 6 0 5 0 50% load 15 18 0 15 16 0 15 0

Technical Data. back-up time in minutes 100% load 6 7 0 5 6 0 5 0 50% load 15 18 0 15 16 0 15 0 The protectoq is a On-Line double conversion UPS-system according to IEC / EN 62040-3 (VFI-SS-111) with sinus wave output voltage in each operation mode, LCDindication, RS232 interface, USB-connection,

More information

XFE. The cost effective starter for all AC induction motors from 4A 2800A The choice for small to medium industrial applications

XFE. The cost effective starter for all AC induction motors from 4A 2800A The choice for small to medium industrial applications The cost effective starter for all AC induction motors from 4A 2800A The choice for small to medium industrial applications The XFE Soft Starter range provides a combination of competitive prices, flexible

More information

IntesisBox KNX LG Air Conditioning

IntesisBox KNX LG Air Conditioning IntesisBox KNX LG Air Conditioning Gateway for integration of LG Air Conditioners with KNX control systems. 1. Main Features Direct connection to KNX TP-1 (EIB) bus. Direct connection to LG outdoor unit

More information

3-phase, bidirectional energy meter

3-phase, bidirectional energy meter Data sheet www.sbc-support.com 3-phase, bidirectional energy meter with S0 pulse output Bidirectional energy meter with S0-interface. The S0 interface is a hardware interface for the transmission of measured

More information

Products and solutions for pumping, irrigation and piping

Products and solutions for pumping, irrigation and piping Products and solutions for pumping, irrigation and piping 100% electricity www.lovatoelectric.com Tra dition and Innovation LOVATO Electric S.p.A. - Bergamo - Italy Since 1922 The first LOVATO Electric

More information

Control Devices Catalogue. Control Devices. Preferred and Standard Products

Control Devices Catalogue. Control Devices. Preferred and Standard Products Control Devices Catalogue Control Devices Preferred and Standard Products KOP.J Timer Electronic 22.5 mm Characteristics Mounting KOP.J 22.5 mm mono or multifunction high immunity to interference surface

More information

Power Thyristor TS3 (SP) 3ph. Installation Guide

Power Thyristor TS3 (SP) 3ph. Installation Guide Power Thyristor TS3 (SP) 3ph Installation Guide L1 L2 L3 TS3 (SP) 3ph Contents: 1. General Discription 2. Set up of power thyristor TS3 (SP) 3ph 3. Installation 4. Meaning of terminal connectors 5. Description

More information

Electronic, Digital and Mechanical Vibration Switches

Electronic, Digital and Mechanical Vibration Switches PT500 Electro-Mechanical Vibration Switch Introduction The PT500 is an economical solution that provides basic vibration protection for rotating reciprocating machines. The PT500 uses an inertia sensitive

More information

Model: DC-A2IO Advanced HVAC Controller

Model: DC-A2IO Advanced HVAC Controller Model: DC-A2IO Advanced HVAC Controller Job Name: Schedule Reference: Date: DC-A2IO Advanced HVAC Controller Package PAC-IF01 M-Net Adapter AL2-14MR-D α2 Simple Application Controller Accessories AL2-2DA

More information

Power Supplies 3. SDN-P DIN Rail Series

Power Supplies 3. SDN-P DIN Rail Series SDN-P DIN Rail Series The SDN DIN Rail power supplies provide industry leading performance. Sag Immunity, transient suppression and noise tolerant, the SDN series ensures compatibility in demanding applications.

More information

NIVOCONT CONDUCTIVE LEVEL SWITCHES LEVEL SWITCHES

NIVOCONT CONDUCTIVE LEVEL SWITCHES LEVEL SWITCHES NIVOCONT CONDUCTIVE LEVEL SWITCHES O U R P R O F E S S I O N I S Y O U R L E V E L LEVEL SWITCHES APPLICATION Level switches, based on the conductivity principle, can be applied to liquids with conductivity

More information

APPENDIX A PIN-OUT OF RJ12 / RJ45 CONNECTORS. RJ12 connectors

APPENDIX A PIN-OUT OF RJ12 / RJ45 CONNECTORS. RJ12 connectors APPENDIX APPENDIX A PIN-OUT OF RJ12 / RJ45 CONNECTORS RJ12 connectors Pin # 1 Signal Name Not Used 2 +TR Description + Data Line 3 +R Remote OFF Required or Remote OFF control 4 -TR 5 Not Used 6 RTN -

More information

VIBRATION MONITORING OF FANS INSTALLED IN ROAD TUNNELS

VIBRATION MONITORING OF FANS INSTALLED IN ROAD TUNNELS VIBRATION MONITORING OF FANS INSTALLED IN ROAD TUNNELS CEMB SPA Via Risorgimento, 9 Mandello del Lario (Lc), Italy stm@cemb.com www.cemb.com INSTRUMENT FOR MONITORING VIBRATIONS OF FANS INSTALLED IN ROAD

More information

How To Drive A Compact Serie 1

How To Drive A Compact Serie 1 Electric lifting cylinder Compact Series Table of Contents Glossary... 2 Compact serie SR 1... 4 Dimension SR 1... 5 Compact Serie SR 1SP... 6 Dimension SR 1SP... 7 Compact Serie SR 5... 8 Dimension SR

More information

LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification

LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification 08/17/12 Rev2 LTR Series General Specification 700 VA to 2.1 KVA 1.0 General LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA General Specification This specification describes the features and

More information

MICROSENS. Central 48 V DC Power Supplies for PoE-Components. Description. Features

MICROSENS. Central 48 V DC Power Supplies for PoE-Components. Description. Features Central 48 V DC Power Supplies for PoE-Components MICROSENS Description Active network equipment which is supporting the Power-over-Ethernet functions, typically requires a powerful 48 V DC power supply.

More information

Manual motor starter MS116

Manual motor starter MS116 Data sheet Manual motor starter MS116 Manual motor starters are electromechanical devices for motor and circuit protection. These devices offer local motor disconnect means, manual ON/ OFF control, and

More information

HEAT MONITORING AND CONTROL INSTRUMENTS FOR TRANSFORMERS MB 103 TEMPERATURE CONTROL UNIT PT 100 TEMPERATURE SENSOR

HEAT MONITORING AND CONTROL INSTRUMENTS FOR TRANSFORMERS MB 103 TEMPERATURE CONTROL UNIT PT 100 TEMPERATURE SENSOR HEAT MONITORING AND CONTROL INSTRUMENTS FOR TRANSFORMERS MB 103 TEMPERATURE CONTROL UNIT PT 100 TEMPERATURE SENSOR 2 MB 103 TRANSFORMER TEMPERATURE CONTROL UNIT WITH CONTROL SIGNAL Recent approval of new

More information

DLW 8. POWER RATING 1500 rpm/50 Hz 1800 rpm/60 Hz Prime 7.5 kva, 6 kw 9.1 kva, 7.3 kw Standby 8.5 kva, 6.8 kw 10.1 kva, 8.1 kw

DLW 8. POWER RATING 1500 rpm/50 Hz 1800 rpm/60 Hz Prime 7.5 kva, 6 kw 9.1 kva, 7.3 kw Standby 8.5 kva, 6.8 kw 10.1 kva, 8.1 kw DLW 8 POWER RATING 1500 rpm/50 Hz 1800 rpm/60 Hz Prime 7.5 kva, 6 kw 9.1 kva, 7.3 kw Standby 8.5 kva, 6.8 kw 10.1 kva, 8.1 kw Generator set consisting of engine and alternator mounted on a fabricated steel

More information

How To Control A Power Supply With A Mini Transmitter And Switch (Power Supply)

How To Control A Power Supply With A Mini Transmitter And Switch (Power Supply) transmitter (2 wire) / switch for continuous or On/Off Control Indication, monitoring, transmitting and continuous or On/Off control in one device Output signal 4...20 ma, 2-wire for continuous control

More information

40.3. Control Relays and Timers

40.3. Control Relays and Timers .3 Contents EASY500/700/800 Intelligent Relays........ EASY/MFD Expansion Modules............ MFD Intelligent Relays................... EASY/MFD Communication Modules....... EASY/MFD Power Supplies, Accessories

More information

SMS 4 / SMS 5 safety mat Product information

SMS 4 / SMS 5 safety mat Product information SMS 4 / SMS 5 safety mat Product information SMS 4 / SMS 5 safety mats Safety mats are used for the protection of man on machinery and plants with hazardous movements. Typical fields of application are,

More information

32:(5#5$7,1* 4833#USP283#+] 4;33#USP293#+] 3ULPH 10.4 kva, 8.3 kw 12.9 kva, 10.3 kw 6WDQGE\ 11.3 kva, 9 kw 14.4 kva, 11.5 kw

32:(5#5$7,1* 4833#USP283#+] 4;33#USP293#+] 3ULPH 10.4 kva, 8.3 kw 12.9 kva, 10.3 kw 6WDQGE\ 11.3 kva, 9 kw 14.4 kva, 11.5 kw ,QGXVWULDO#*HQHUDWRU 32:(5#5$7,1* 4833#USP283#+] 4;33#USP293#+] 3ULPH 10.4 kva, 8.3 kw 12.9 kva, 10.3 kw 6WDQGE\ 11.3 kva, 9 kw 14.4 kva, 11.5 kw Generator set consisting of engine and alternator mounted

More information

Operating Manual for the Electronic Built-in Interval Timer. Micro II (Countdown Timer)

Operating Manual for the Electronic Built-in Interval Timer. Micro II (Countdown Timer) Operating Manual for the Electronic Built-in Interval Timer Micro II (Countdown Timer) Note: This document has been designed for our OEM customers. They can use it as supporting material when creating

More information

PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES

PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES BUSHING WITH PLUG CONNECTION WITH OUTER CONE PPS CHARACTERISTICS The PPS bushing can be used as a fixed section for the entry of medium

More information

E-STOP relays, safety gate monitors

E-STOP relays, safety gate monitors Unit features Safety features Gertebild ][Bildunterschrift_NOT_Sch.tuer_Licht Safety relay for monitoring E-STOP pushbuttons, safety gates and light beam devices Approvals Gertemerkmale Positive-guided

More information

APC. DIN Rail Control Panel Mounting Uninterruptible Power Supply. Catalog

APC. DIN Rail Control Panel Mounting Uninterruptible Power Supply. Catalog APC DIN Rail Control Panel Mounting Uninterruptible Power Supply Catalog 2014 Contents Introduction, description... 4 Specifications...5 References....6 Dimensions...7 Wiring diagrams....8 Product reference

More information

Actuator-Sensor-Interface

Actuator-Sensor-Interface Selection and ordering data Design Order No. Price Pack 3RX9 307-0AA00 3RX9 307-1AA00 4FD5 213-0AA10-1A 3RX9 305-1AA00 3RX9 306-1AA00 Single output IP 65 current 2.4 A Rated input voltage DC 24 V current

More information

Digital inductive conductivity transmitter

Digital inductive conductivity transmitter Digital inductive conductivity transmitter Optimal solution for conductivity measurements in difficult fluids (polluted, dirty,...) PEEK/PPA version for CIP applications Large range of process connections

More information

R4D0-FB-IA* FieldBarrier. Features. Assembly. Function. Connection IN + - S OUT ... ... Spur 2. Spur 1. Zone 1. Zone 0

R4D0-FB-IA* FieldBarrier. Features. Assembly. Function. Connection IN + - S OUT ... ... Spur 2. Spur 1. Zone 1. Zone 0 FieldBarrier Features Assembly 8... 12 outputs Ex ia IIC, FISCO and Entity Advanced fault isolation and diagnostics at the spur FieldBarrier in Zone 1/Div. 2 Instruments in Zone 0...1/Div. 1 For FOUNDATION

More information

Electronic Control Devices The European Product Catalogue 2007

Electronic Control Devices The European Product Catalogue 2007 FX07 Field Controller (1/4) FX07 Field Controller Display Model Dimensions in mm (inches) The FX07 is a terminal unit controller in the Facility Explorer range of products. The controller is designed specifically

More information

Max primary circuit temperature 90ºC Max primary circuit temp. 90ºC Max secondary circuit temperature 45ºC Max secondary circuit temp.

Max primary circuit temperature 90ºC Max primary circuit temp. 90ºC Max secondary circuit temperature 45ºC Max secondary circuit temp. EGLISH 1 Product description exchanger equipped with an electronic control unit and circulation pump for the primary circuit. All Aqua-Mex variants can be ordered with an interior coil of either titanium

More information

Maximum Demand Control

Maximum Demand Control Maximum Demand Control There are three terms that appear on the majority of electric company bills: Active energy consumption (kwh) Reactive energy consumption (kvarh) Maximum Demand Traditionally, utility

More information

3753 en - 04.2004/b VE/B - VE/RG Va V riable speed drives

3753 en - 04.2004/b VE/B - VE/RG Va V riable speed drives 3753 en 04.2004/b Variable speed drives LEROYSOMER's drives provide SPEED VARIATION for a DC motor, SIMPLY and ECONOMICALLY from a singlephase power supply. CMStype technology is used. These products conform

More information

Analogue Input, 4-fold, MDRC AE/S 4.1, GH Q605 0054 R0001

Analogue Input, 4-fold, MDRC AE/S 4.1, GH Q605 0054 R0001 Analogue Input, -fold, MDRC, GH Q605 005 R0001 The analogue input is a DIN rail mounted device for insertion in the distribution board. It is connected to the EIB via the bus connecting terminal supplied.

More information

E-STOP relays, safety gate monitors

E-STOP relays, safety gate monitors Unit features Safety features gang engertebild ][Bildunterschrift_NOT_Sch.tuer_Licht Safety relay for monitoring E-STOP pushbuttons, safety gates and light beam devices Approvals Gertemerkmale Positive-guided

More information

Bulletin 150 SMC Flex Smart Motor Controller Specifications

Bulletin 150 SMC Flex Smart Motor Controller Specifications Specifications Specifications Standard Features Optional Features Installation Setup Communications Power Wiring Control Wiring Keypad Software Starting and Stopping Modes Protection and Diagnostics Metering

More information

Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points

Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points Features SELV Compliant No Detection Passive Injector Gigabit Compatible Full Protection

More information

SPEED CONTROL SYSTEM

SPEED CONTROL SYSTEM SPEED CONTROL SYSTEM INDEX SPEED CONTROL MOTOR FEATURES 144 6W ( 70mm) 153 10W ( 70mm) 155 15W ( 80mm) 157 25W ( 80mm) 159 40W ( 90mm) 161 SPEED CONTROL W ( 90mm) 163 90W ( 90mm) 165 120W ( 90mm) 168 180W

More information

TECHNICAL SPECIFICATION FOR PROJECTION WELDING MACHINE (Qty. 2 Nos.)

TECHNICAL SPECIFICATION FOR PROJECTION WELDING MACHINE (Qty. 2 Nos.) TECHNICAL SPECIFICATION FOR PROJECTION WELDING MACHINE (Qty. 2 Nos.) 1. Requirement: Two (02) Nos. DC Type, 3 phase, 3 wire Projection Welding Machine is required for welding of ventilation M.S. / Stainless

More information

Thermistor motor protection

Thermistor motor protection Thermistor motor protection CM-E Range Thermistor motor protection Thermistor motor protection relays Benefits and advantages Selection table Operating principle and fields of application for thermistor

More information

Power factor correction and harmonic filtering. Rectimat 2 Automatic capacitor banks. Catalogue. Building a New Electric World

Power factor correction and harmonic filtering. Rectimat 2 Automatic capacitor banks. Catalogue. Building a New Electric World Catalogue 2002 Automatic capacitor banks Building a New Electric World 0Contents Power factor correction 2 Power factor equipment selection guide 3 General technical data 4 Capacitors and banks 50 z 6

More information

A project to optimise quality and energy efficiency must include metering

A project to optimise quality and energy efficiency must include metering EMDX 3 : Energy Metering A project to optimise quality and energy efficiency must include metering Metering upstream identifies the critical points and ensures optimum targeting of the actions to be taken,

More information

Stroom voor elke toepassing

Stroom voor elke toepassing ELECTRICITY: ALWAYS & EVERYWHERE With VICTRON Phoenix MultiPlus and a HONDA Generator An intelligent combination with endless possibilities! Electrical appliances that increase on board comfort, such as

More information

Défumair XR. ventilation and cmv. fire grade - label CE. smoke-extraction fan extraction casing for kitchen at F400-120. advantages.

Défumair XR. ventilation and cmv. fire grade - label CE. smoke-extraction fan extraction casing for kitchen at F400-120. advantages. Défumair XR smoke-extraction fan extraction casing for kitchen at F400-120 Personalisation : - Phonic insulation version by insulated double-skin panels through 25 mm glass wool, class M1. advantages Originally

More information

I STAR COMPUTER CO., LTD

I STAR COMPUTER CO., LTD I STAR COMPUTER CO., LTD Mini Redundant Power Supply 300W+300W for IPC-Computer Model No. TC-300R8 Table of content 1. Introduction...1 2. Specification 2.1 Input Voltage...1 2.2 DC Output...1 2.3 PS-ON

More information

Series 8146/5-V37 and Series 8150/5-V37

Series 8146/5-V37 and Series 8150/5-V37 www.stahl.de > Clear assignment safe technology easy installation > Intelligent structure only one rotary actuator for frequency-controlled drives ) 20 ms leading auxiliary contact for safe motor disconnection

More information

UPS UNINTERRUPTIBLE POWER SUPPLY GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES

UPS UNINTERRUPTIBLE POWER SUPPLY GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES UNINTERRUPTIBLE POWER SUPPLY GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES INDEX General characteristics page 4 Modular page 12 Conventional page 32 Line-interactive page 44 Communication

More information

SICONT Limit Switches Type 3SE3 upto 500 VAC, 600 VDC, 10A

SICONT Limit Switches Type 3SE3 upto 500 VAC, 600 VDC, 10A s SICONT Limit Switches Type 3SE3 upto 500 VAC, 600 VDC, 10A Introduction The technical and descriptive information on the function, construction and selection of the new types of 3SE3 limit switches is

More information

Product and Applications Description. Application Programs. Example of Operation. GAMMA instabus Technical Product-Information.

Product and Applications Description. Application Programs. Example of Operation. GAMMA instabus Technical Product-Information. Product and Applications Description The power supply units N 125/x2 can supply DC 24 V power from an additional pair of terminals (yellowwhite). This DC 24 V output voltage can be used to power e.g. an

More information

Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start 0225592. * see variants. Applications.

Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start 0225592. * see variants. Applications. Safety Technique SAFEMASTER Emergency Stop Module BG 5924, IP 5924 Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start 0225592 BG 5924 IP 5924 Product Description

More information

Art.S001-S002 SOLAR MODULE WITH DELIVERY AND RETURN CONNECTIONS

Art.S001-S002 SOLAR MODULE WITH DELIVERY AND RETURN CONNECTIONS Art.S001-S002 SOLAR MODULE WITH DELIVERY AND RETURN CONNECTIONS Technical Information sheet 0001/07/Rev01 ENG FUNCTION Series S001 and S002 circulation units are applied to the primary circuit of solar

More information

Digital Pressure Measuring Instrument MDR480

Digital Pressure Measuring Instrument MDR480 Description The digital panel instrument MDR480 is designed to measure, display, and monitor pressures in industrial applications. The instrument is panel mounted with a front frame dimension of 96 mm

More information

AUTOMATIC TRANSFER SWITCH. Changeover Type from 250A to 2500A

AUTOMATIC TRANSFER SWITCH. Changeover Type from 250A to 2500A AUTOMATIC TRANSFER SWITCH Changeover Type from 250A to 2500A Table of Contents Preamble 1.1 Theoretical base 1.2 Selection the size of automatic transfer switch 1.3 Automatic transfer switch components

More information

RM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC

RM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC Characteristics multifunction control relay RM17-TE - range 183..528 V AC Complementary Reset time Maximum switching voltage Minimum switching current Maximum switching current [Us] rated supply voltage

More information

ETZGAR CONVEYOR COMPANY Controls Section v12.05

ETZGAR CONVEYOR COMPANY Controls Section v12.05 Section 7 Controls Page Description 7-1 Controls Index 7-2 Motor Data, Enclosure Rating and Abbreviations 7-3 Controls Safety Guidelines 7-4 Fixed Speed Controls Packages 7-5 Three Phase AC Variable Speed

More information