13HPD SPLIT SYSTEM HEAT PUMP WITH DRY NITROGEN HOLDING CHARGE INSTALLATION / START UP INSTRUCTIONS
|
|
|
- Juliet Shelton
- 9 years ago
- Views:
Transcription
1 13HPD SPLIT SYSTEM HET PUMP WITH DRY NITROGEN HOLDING HRGE INSTLLTION / STRT UP INSTRUTIONS These instructions must be read and understood completely before attempting installation. TLE OF ONTENTS Shipping and Packing List General Unit Dimensions Torque Requirements Typical Unit Parts rrangement Operating Gauge Set and Service Valves Recovering Refrigerant from Existing System New Outdoor Unit Placement Replacement Line Set razing onnections Removing Existing Metering Device and Flushing Line Set and Indoor oil Installing Indoor Metering Device Leak Test Line Set and Indoor oil Evacuating Line Set, Indoor oil and Outdoor Unit. 14 Electrical onnections Servicing Outdoor Unit Delivered Void of Nitrogen harge Unit Start up and Weigh In harging Optimizing System harge System Operation Defrost System Maintenance Start Up and Performance hecklist NOTIE TO INSTLLER This unit is factory charged with dry nitrogen. The unit is intended for installation in existing HF 22 systems. arefully follow all installation procedures. WRNING Installation or repairs made by unqualified persons can result in hazards to you and others. Installation MUST conform with local building codes or, in the absence of local codes, with the National Electrical ode NFP 70/NSI or current edition and anadian Electrical ode Part 1 S UTION Improper selection of a matching indoor unit and a matching metering device, improper installation, adjustment, alteration, service or maintenance may void the warranty. The qualified installer or agency must use factory authorized kits or accessories when modifying this products. Refer to the individual instructions packaged with the kits or accessories when installing. NOTE These instructions are intended as a general guide and do not supersede national, state or local codes in any way. These instructions must be left with the property owner. 11/ Page 1
2 Shipping and Packing List heck the unit for shipping damage. If damaged, contact the last shipping carrier. 1 ssembled outdoor unit General The 13HPD heat pump, which will also be referred to in this instruction as the outdoor unit, uses HF 22 refrigerant. This outdoor unit is intended as a replacement outdoor component for use in residential systems which include an existing indoor coil which is functioning properly. It is NOT intended for new installations. shipped from the factory with nitrogen holding charge that must be purged from the unit; designed for use with HF 22 refrigerant only; designed for use in systems that use check / thermal expansion valve (TXV). See the 13HPD product specification sheet for approved check / expansion valve match ups and application information. Important The heat pump must have properly matched system components including indoor unit and refrigerant metering device. Mismatched equipment may have an impact on the operation, performance, reliability, and warranty of the heat pump system. Unit Dimensions inches (mm) OUTDOOR OIL FN Discharge ir OMPRESSOR VPOR ND LIQUID LINE ONNETIONS SIDE VIEW SIDE VIEW Model Number 13HPD /4 (616) 33 1/4 (845) 13HPD /4 (616) 33 1/4 (845) 13HPD /4 (616) 29 1/4 (743) 13HPD /4 (616) 33 1/4 (845) 13HPD /4 (616) 33 1/4 (845) 13HPD /4 (718) 37 (940) 13HPD /4 (819) 37 (940) /10 Page 2
3 Typical Unit Parts rrangement ONTROL OX PITOR (12) DEFROST THERMOSTT (S6) MUFFLER GROUND LUG DEFROST ONTROL (M1) HEK / EXPNSION VLVE LIQUID LINE I FLOW FILTER DRIER TRUE SUTION PORT REVERSING VLVE (L1) RNKSE HETER (HR1) ( 042, 048, 60 UNITS ONLY) SINGLE POLE ONTTOR (K 1) HIGH PRESSURE SWITH (S4) ( 018 UNIT ONLY) LIQUID LINE SERVIE PORT VPOR LINE SERVIE PORT Torque Requirements When servicing or repairing heating, ventilating and air conditioning components, ensure the fasteners are appropriately tightened. Table 1 lists torque values for fasteners. Table 1. Torque Requirements Parts Recommended Torque Service valve cap 8 ft. lb. 11 NM Sheet metal screws 16 in. lb. 2 NM Machine screws #10 28 in. lb. 3 NM ompressor bolts 90 in. lb. 10 NM Gauge port seal cap 8 ft. lb. 11 NM Operating Gauge Set and Service Valves USING MNIFOLD GUGE SET When checking the system charge, only use a manifold gauge set that features low loss anti blow back fittings. OPERTING SERVIE VLVES The liquid and vapor line service valves are used for Figure 1. Typical Unit Parts rrangement removing refrigerant, flushing, leak testing, evacuating, checking charge and charging. Each valve is equipped with a service port which has a factory installed valve core. Figure 2 provides information on accessing and operating both angle and ball service valves. IMPORTNT To prevent stripping of the various caps used, the appropriately sized wrench should be used and fitted snugly over the cap before tightening. IMPORTNT Only use llen wrenches of sufficient hardness (50Rc Rockwell Harness Scale minimum). Fully insert the wrench into the valve stem recess. Service valve stems are factory torqued (from 9 ft lbs for small valves, to 25 ft lbs for large valves) to prevent refrigerant loss during shipping and handling. Using an llen wrench rated at less than 50Rc risks rounding or breaking off the wrench, or stripping the valve stem recess. Page 3 13HPD SERIES
4 Operating ngle Type Service Valve: 1. Remove stem cap with an appropriately sized wrench. 2. Use a service wrench with a hex head extension (3/16" for liquid line valve sizes and 5/16" for vapor line valve sizes) to back the stem out counterclockwise as far as it will go. SERVIE PORT P SERVIE PORT ORE (VLVE STEM SHOWN OPEN) INSERT HEX WRENH HERE (VLVE STEM SHOWN LOSED) INSERT HEX WRENH HERE TO INDOOR UNIT STEM P TO OUTDOOR UNIT NGLE TYPE SERVIE VLVE (K SETED OPENED) When service valve is OPEN, the service port is open to line set, indoor and outdoor unit. Operating all Type Service Valve: 1. Remove stem cap with an appropriately sized wrench. 2. Use an appropriately sized wrenched to open. To open valve, rotate stem counterclockwise 90. To close rotate stem clockwise 90. TO OPEN ROTTE STEM OUNTERLOKWISE 90. TO LOSE ROTTE STEM LOKWISE 90. SERVIE PORT SERVIE PORT ORE SERVIE PORT P TO OUTDOOR UNIT TO INDOOR UNIT LL (SHOWN LOSED) VLVE STEM STEM P NGLE TYPE SERVIE VLVE (FRONT SETED LOSED) WHEN SERVIE VLVE IS LOSED, THE SERVIE PORT IS OPEN TO THE LINE SET ND INDOOR UNIT. To ccess Service Port: service port cap protects the service port core from contamination and serves as the primary leak seal. 1. Remove service port cap with an appropriately sized wrench. 2. onnect gauge set to service port. 3. When testing is completed, replace service port cap and tighten as follows: With torque wrench: Finger tighten and torque cap per table 1. Without torque wrench: Finger tighten and use an appropriately sized wrench to turn an additional 1/6 turn clockwise /6 TURN Reinstall Stem ap: Stem cap protects the valve stem from damage and serves as the primary seal. Replace the stem cap and tighten as follows: With Torque Wrench: Finger tighten and then torque cap per table 1. Without Torque Wrench: Finger tighten and use an appropriately sized wrench to turn an additional 1/12 turn clockwise. 1/12 TURN NOTE label with specific torque requirements may be affixed to the stem cap. If the label is present, use the specified torque. Figure 2. ngle and all Service Valves /10 Page 4
5 Recovering Refrigerant from Existing System IMPORTNT The lean ir ct of 1990 bans the intentional venting of refrigerant (Fs, HFs ND HFs) as of July 1, pproved methods of recovery, recycling or reclaiming must be followed. Fines and/or incarceration may be levied for noncompliance. REOVERING REFRIGERNT FROM SYSTEM DISONNET POWER Disconnect all power to the existing outdoor unit at the service disconnect switch or main fuse box/breaker panel. 1 2 SERVIE DISONNET SWITH ONNET MNIFOLD GUGE SET onnect a gauge set, clean recovery cylinder and a recovery machine to the service ports of the existing unit. Use the instructions provided with the recovery machine to make the connections. REOVERY MHINE MNIFOLD GUGES LOW HIGH 3 Page 5 LEN REOVERY YLINDER OUTDOOR UNIT METHOD 1: Use this method if the existing outdoor unit is not equipped with shut off valves, or if the unit is not operational and you plan to use the existing refrigerant to flush the system. Remove all refrigerant from the existing system. heck gauges after shutdown to confirm that the entire system is completely void of refrigerant. METHOD 2: Use this method if the existing outdoor unit is equipped with manual shut off valves, and you plan to use new refrigerant to flush the system. The following devices could prevent full system charge recovery into the outdoor unit: Outdoor unit s high or low pressure switches (if applicable) when tripped can cycle the compressor OFF. ompressor can stop pumping due to tripped internal pressure relief valve. REOVERING REFRIGERNT Remove existing refrigerant using one of the following procedures: IMPORTNT Some system configurations may contain higher than normal refrigerant charge due to either large internal coil volumes, and/or long line sets. ompressor has internal vacuum protection that is designed to unload the scrolls (compressor stops pumping) when the pressure ratio meets a certain value or when the suction pressure is as high as 20 psig. (ompressor suction pressures should never be allowed to go into a vacuum. Prolonged operation at low suction pressures will result in overheating of the scrolls and permanent damage to the scroll tips, drive bearings and internal seals.) Once the compressor cannot pump down to a lower pressure due to one of the above system conditions, shut off the vapor valve. Turn OFF the main power to unit and use a recovery machine to recover any refrigerant left in the indoor coil and line set. Perform the following task: Start the existing system in the cooling mode and close the liquid line valve. Use the compressor to pump as much of the existing HF 22 refrigerant into the outdoor unit until the outdoor system is full. Turn the outdoor unit main power OFF and use a recovery machine to remove the remaining refrigerant from the system. NOTE It may be necessary to bypass the low pressure switches (if equipped) to ensure complete refrigerant evacuation. When the low side system pressures reach 0 psig, close the vapor line valve. D heck gauges after shutdown to confirm that the valves are not allowing refrigerant to flow back into the low side of the system. Figure 3. Refrigerant Recovery 13HPD SERIES
6 New Outdoor Unit Placement Remove existing outdoor unit prior to placement of new outdoor unit. See Unit Dimensions on page 2 for sizing mounting slab, platforms or supports. Refer to figure 4 for mandatory installation clearance requirements. LERNE ON LL SIDES INHES (MILLIMETERS) MINIMUM LERNE OVE UNIT 6 (152) ESS PNEL 12 (305) 36 (914) 30 (762) LINE SET ONNETIONS NOTES: learance to one of the other three sides must be 36 inches (914mm). learance to one of the remaining two sides may be 12 inches (305mm) and the final side may be 6 inches (152mm). 48 (1219) MINIMUM LERNE ETWEEN TWO UNITS 24 (610) DETIL Install unit away from windows. DETIL If unit coil cannot be mounted away from prevailing winter winds, a wind barrier should be constructed. Size barrier at least the same height and width as outdoor unit. Mount barrier 24 inches (610 mm) from the sides of the unit in the direction of prevailing winds as illustrated. INLET IR Figure 4. Installation learances Two 90 elbows installed in line set will reduce line set vibration. PREVILING WINTER WINDS WIND RRIER INLET IR INLET IR DETIL These units operate under a wide range of weather conditions; therefore, several factors must be considered when positioning the outdoor unit. The unit must be positioned to give adequate clearances for sufficient airflow and servicing. Install unit level or, if on a slope, maintain slope tolerance of 2 degrees (or 2 inches per 5 feet [50 mm per 1.5 m]) away from building structure. Install the unit high enough above the ground or roof to allow adequate drainage of defrost water and prevent ice or snow build up. In heavy snow areas, do not locate the unit where drifting will occur. The unit base should be elevated above the depth of average snows. Stand off kits are available for order using either catalog numbers 94J45 (4 each) or 30K79 (20 each). When installed in areas where low ambient temperatures exist, locate unit so winter prevailing winds do not blow directly onto outdoor unit. Locate unit away from overhanging roof lines which would allow water or ice to drop on, or in front of, coil or unto unit. STRUTURE DISHRGE IR INLET IR MOUNTING SL MUST SLOPE WY FROM UILDING. Figure 5. Placement, Slab Mounting and Wind arrier GROUND LEVEL Page /10
7 UTION Physical contact with metal edges and corners while applying excessive force or rapid motion can result in personal injury. e aware of, and use caution when working near these areas during installation or while servicing this equipment. POSITIONING ONSIDERTIONS UTION In order to avoid injury, take proper precaution when lifting heavy objects. onsider the following when positioning the unit: Some localities are adopting sound ordinances based on the unit s sound level registered from the adjacent property, not from the installation property. Install the unit as far as possible from the property line. When possible, do not install the unit directly outside a window. Glass has a very high level of sound transmission. For proper placement of unit in relation to a window see the provided illustration in figure 5. PLING OUTDOOR UNIT ON SL When installing a unit at grade level, the top of the slab should be high enough above the grade so that water from higher ground would not collect around the unit as illustrated in figure 5. Slab may be level or have a slope tolerance away from the building of not more than two degrees, or 2 inches per 5 feet (51 mm per 1524 mm) as illustrated in figure 5. INSTLLING OUTDOOR UNIT ON ROOF Install the unit at a minimum of 4 inches (102 mm) above the surface of the roof. Ensure the weight of the unit is properly distributed over roof joists and rafters. Redwood or steel supports are recommended. Refer to figure 5, detail c, for rooftop wind barrier considerations. Model 13HPD HPD HPD HPD HPD HPD Field onnections NOTIE Roof Damage! This system contains both refrigerant and oil. Some rubber roofing material may absorb oil and cause the rubber to swell when it comes into contact with oil. The rubber will then bubble and could cause leaks. Protect the roof surface to avoid exposure to refrigerant and oil during service and installation. Failure to follow this notice could result in damage to roof surface. Replacement Line Set Table 2. Refrigerant Line Set Inches (mm) Recommended Line Set This section provides information on new installation or replacement of existing line set. If a new or replacement line set is not required, then proceed to razing onnections on page 8. REFRIGERNT LINE SET Field refrigerant piping consists of liquid and suction lines from the outdoor unit (braze connections) to the indoor unit coil (flare or braze connections). If replacing line set, use brazed, non flare line set, or field fabricated refrigerant lines as listed in table 2. Existing line set should meet size requirements listed in table 2. NOTE When installing refrigerant lines longer than 50 feet, contact technical support for assistance. To obtain the correct information from manufacturer, be sure to communicate the following points: Model (13HPD) and size of unit (e.g. 060). Line set diameters for the unit being installed as listed in table 2 and total length of installation. Number of elbows and if there is a rise or drop of the piping. Liquid Line Vapor Line Liquid Line Vapor Line Line Sets 3/8 in. (10 mm) 3/4 in. (19 mm) 3/8 in. (10 mm) 3/4 in. (19 mm) 3/8 in. (10 mm) 7/8 in. (22 mm) 3/8 in. (10 mm) 7/8 in. (22 mm) 13HPD /8 in. (10 mm) 1 1/8 in. (29 mm) 3/8 in. (10 mm) 1 1/8 in. (29 mm) Field fabricated brazed, non flare. Page 7 13HPD SERIES
8 razing onnections Use the procedures outline in figures 6 and 7 for brazing line set connections to service valves. WRNING When using a high pressure gas such as dry nitrogen to pressurize a refrigeration or air conditioning system, use a regulator that can control the pressure down to 1 or 2 psig (6.9 to 13.8 kpa). WRNING Danger of fire. leeding the refrigerant charge from only the high side may result in pressurization of the low side shell and suction tubing. pplication of a brazing torch to a pressurized system may result in ignition of the refrigerant and oil mixture heck the high and low pressures before applying heat. IMPORTNT llow braze joint to cool before removing the wet rag from the service valve. Temperatures above 250ºF can damage valve seals. IMPORTNT Use silver alloy brazing rods with 5% minimum silver alloy for copper to copper brazing. Use 45% minimum alloy for copper to brass and copper to steel brazing. WRNING Danger of fire. leeding the refrigerant charge from only the high side may result in pressurization of the low side shell and suction tubing. pplication of a brazing torch to a pressurized system may result in ignition of the refrigerant and oil mixture heck the high and low pressures before applying heat. UTION razing alloys and flux contain materials which are hazardous to your health. void breathing vapors or fumes from brazing operations. Perform operations only in well ventilated areas. Wear gloves and protective goggles or face shield to protect against burns. Wash hands with soap and water after handling brazing alloys and flux. Page /10
9 1 2 vapor UT ND DEUR ut ends of the refrigerant lines square (free from nicks or dents) and debur the ends. The pipe must remain round. Do not crimp end of the line. P ND ORE REMOVL Remove service cap and core from both the and liquid line service ports. UT ND DEUR OPPER TUE STU REDUER SERVIE VLVE ONNETION LINE SET SIZE MTHES SERVIE VLVE ONNETION SERVIE PORT P SERVIE PORT ORE LIQUID LINE SERVIE VLVE SERVIE PORT ORE SUTION / VPOR LINE SERVIE VLVE SERVIE PORT P 3 TTH THE MNIFOLD GUGE SET FOR RZING LINE SETS TO LIQUID ND SUTION / VPOR LINE SERVIE VLVES Flow regulated nitrogen (at 1 to 2 psig) through the low side refrigeration gauge set into the liquid line service port valve, and out of the suction / vapor line service port valve. REFRIGERNT LINE LINE SET SIZE IS SMLLER THN ONNETION onnect gauge set low pressure side to liquid line service valve (service port). onnect gauge set center port to bottle of nitrogen with regulator. Remove Schrader valve in suction / vapor line service port to allow nitrogen to escape. DO NOT RIMP SERVIE VLVE ONNETOR WHEN PIPE IS SMLLER THN ONNETION LOW TTH GUGES HIGH USE REGULTOR TO FLOW NITROGEN T 1 TO 2 PSIG. SUTION / VPOR SERVIE PORT MUST E OPEN TO LLOW EXIT POINT FOR NITROGEN VPOR LINE SUTION / VPOR LINE SERVIE VLVE INDOOR UNIT OUTDOOR UNIT LIQUID LINE LIQUID LINE SERVIE VLVE WHEN RZING LINE SET TO SERVIE VLVES, POINT FLME WY FROM SERVIE VLVE. NITROGEN Figure 6. razing Procedures Page 9 13HPD SERIES
10 4 saturated WRP SERVIE VLVES To help protect service valve seals during brazing, wrap a saturated cloth around service valve bodies and copper tube stub. Use another cloth underneath the valve body to protect the base paint. 5 FLOW NITROGEN Flow regulated nitrogen (at 1 to 2 psig) through the refrigeration gauge set into the valve stem port connection on the liquid service valve and out of the suction / vapor valve stem port. See steps 3, 3 and 3 on manifold gauge set connections. 6 RZE LINE SET Wrap both service valves with a saturated cloth as illustrated here before brazing to line set. LIQUID LINE SERVIE VLVE WHEN RZING LINE SET TO SERVIE VLVES, POINT FLME WY FROM SERVIE VLVE. IMPORTNT llow braze joint to cool. pply additional saturated cloths to help cool brazed joint. Do not remove wet rag until piping has cooled. Temperatures above 250ºF will damage valve seals. STURTED LOTH LIQUID LINE WRNING 1. FIRE, PERSONL INJURY, OR PROPERTY DMGE will result if you do not wrap a wet cloth around both liquid and suction line service valve bodies and copper tube stub while brazing in the line set! The braze, when complete, must be quenched with water to absorb any residual heat. 2. Do not open service valves until refrigerant lines and indoor coil have been leak tested and evacuated. Refer to procedures provided in this supplement. SUTION / VPOR LINE SERVIE VLVE WHEN RZING LINE SET TO SERVIE VLVES, POINT FLME WY FROM SERVIE VLVE. SUTION / VPOR LINE STURTED LOTH 7 PREPRTION FOR NEXT STEP fter all connections have been brazed, disconnect manifold gauge set from service ports. pply saturated rags to both services valves to cool piping. Once piping is cool, remove all wet cloths. Figure 7. razing Procedures (continued) /10 Page 10
11 Removing Existing Metering Device and Flushing Line Set and Indoor oil Flushing is recommended if existing indoor coil and line set are to be used. Otherwise proceed to Installing Indoor Metering Device on page TYPIL EXISTING FIXED ORIFIE REMOVL PROEDURE (UNSED OIL SHOWN) OR DISTRIUTOR TUES LIQUID LINE ORIFIE HOUSING TEFLON RING FIXED ORIFIE 1 TYPIL EXISTING EXPNSION VLVE REMOVL PROEDURE (UNSED OIL SHOWN) TWO PIEE PTH PLTE (UNSED OIL ONLY) DISTRIUTOR TUES LIQUID LINE ORIFIE HOUSING STU END HEK EXPNSION VLVE TEFLON RING RSS NUT TEFLON RING SENSING LINE DISTRIUTOR SSEMLY REMOVE ND DISRD WHITE TEFLON SEL (IF PRESENT) LIQUID LINE SSEMLY (INLUDES STRINER) Page 11 DISTRIUTOR SSEMLY EQULIZER LINE LIQUID LINE SSEMLY WITH RSS NUT On fully cased coils, remove the coil access and plumbing panels. Remove any shipping clamps holding the liquid line and distributor assembly. MLE EQULIZER LINE FITTING Using two wrenches, disconnect liquid line from liquid line orifice housing. Take care not to twist or damage distributor tubes during this pro- SENSING UL VPOR LINE LIQUID LINE cess. D Remove and discard fixed orifice, valve stem assembly if present and Teflon washer as illustrated above. On fully cased coils, remove the coil access and plumbing panels. Remove any shipping clamps holding the liquid line and distributor E Use a field provided fitting to temporarily reconnect the liquid line to the indoor unit s liquid line orifice housing. assembly. Disconnect the equalizer line from the check expansion valve equalizer line fitting on the vapor line. 2 ONNET GUGES ND EQUIPMENT FOR D Remove the vapor line sensing bulb. FLUSHING PROEDURE E Disconnect the liquid line from the check expansion valve at the liquid line assembly. INVERTED YLINDER GUGE F Disconnect the check expansion valve from the liquid line orifice ONTINS LEN MNIFOLD LIQUID HF 22 TO E housing. Take care not to twist or damage distributor tubes during this USED FOR FLUSHING. process. G Remove and discard check expansion valve and the two Teflon rings. 1 LOW HIGH H Use a field provided fitting to temporary reconnect the liquid line to the VPOR LINE NEW indoor unit s liquid line orifice housing. SERVIE VLVE OUTDOOR 3 UNIT FLUSHING LINE SET OPENED LOSED The line set and indoor unit coil must be flushed with at least the EXISTING same amount of clean refrigerant that previously charged the INDOOR system. heck the charge in the flushing cylinder before UNIT proceeding. LIQUID LINE SERVIE VLVE D VPOR LIQUID TNK RETURN INLET DISHRGE REOVERY REOVERY MHINE YLINDER Inverted cylinder with clean refrigerant to the vapor service valve. gauge set (low side) to the liquid line valve. gauge set center port to inlet on the recovery machine with an empty recovery tank to the gauge set. D onnect recovery tank to recovery machine per machine instructions. Figure 8. Removing Metering Device and Flushing D Set the recovery machine for liquid recovery and start the recovery machine. Open the gauge set valves to allow the recovery machine to pull a vacuum on the existing system line set and indoor unit coil. Invert the cylinder of clean refrigerant and open its valve to allow liquid refrigerant to flow into the system through the vapor line valve. llow the refrigerant to pass from the cylinder and through the line set and the indoor unit coil before it enters the recovery machine. fter all of the liquid refrigerant has been recovered, switch the recovery machine to vapor recovery so that all of the vapor is recovered. llow the recovery machine to pull the system down to zero. lose the valve on the inverted drum and the gauge set valves. Pump the remaining refrigerant out of the recovery machine and turn the machine off. 13HPD SERIES
12 Installing New Indoor Metering Device This outdoor unit is designed for use in existing HF 22 systems that use check / thermal expansion valve metering device (purchased separately) at the indoor coil. See the 13HPD product specification sheet for approved expansion valve kit match ups. The expansion valve unit can be installed internal or external to the indoor coil. INDOOR HEK EXPNSION VLVE INSTLLTION TWO PIEE PTH PLTE (UNSED OIL ONLY) DISTRIUTOR TUES DISTRIUTOR SSEMLY MLE EQULIZER LINE FITTING (SEE EQULIZER LINE INSTLLTION FOR FURTHER DETILS) (Uncased oil Shown) LIQUID LINE ORIFIE HOUSING STU END TEFLON RING EQULIZER LINE HEK EXPNSION VLVE VPOR LINE Sensing bulb insulation is required if mounted external to the coil casing. sensing bulb installation for bulb positioning. EQULIZER LINE INSTLLTION TEFLON RING LIQUID LINE SSEMLY WITH RSS NUT SENSING LINE LIQUID LINE Remove and discard either the flare seal cap or flare nut with copper flare seal bonnet from the equalizer line port on the vapor line as illustrated in the figure below. D E ttach the vapor line sensing bulb in the proper orientation as illustrated to the right using the clamp and screws provided. NOTE onfirm proper thermal contact between vapor line and expansion bulb before insulating the sensing bulb once installed. Remove the field provided fitting that temporarily reconnected the liquid line to the indoor unit s distributor assembly. Install one of the provided Teflon rings around the stubbed end of the expansion valve and lightly lubricate the connector threads and expose surface of the Teflon ring with refrigerant oil. ttach the stubbed end of the expansion valve to the liquid line orifice housing. Finger tighten and use an appropriately sized wrench to turn an additional 1/2 turn clockwise as illustrated in the figure above, or 20 ft lb. Place the remaining Teflon washer around the other end of the expansion valve. Lightly lubricate connector threads and expose surface of the Teflon ring with refrigerant oil. ttach the liquid line assembly to the expansion valve. Finger tighten and use an appropriately sized wrench to turn an additional 1/2 turn clockwise as illustrated in the figure above or 20 ft lb. SENSING UL INSTLLTION onnect the equalizer line from the expansion valve to the equalizer vapor port on the vapor line. Finger tighten the flare nut plus 1/8 turn (7 ft lbs) as illustrated below. VPOR LINE UL 12 UL 1/2 Turn ON LINES SMLLER THN 7/8", MOUNT SENSING UL T EITHER THE 3 OR 9 O LOK POSITION /8 Turn FLRE SEL P OR FLRE NUT OPPER FLRE SEL ONNET VPOR LINE 12 ON 7/8" ND LRGER LINES, MOUNT SENSING UL T EITHER THE 4 OR 8 O LOK POSITION. NEVER MOUNT ON OTTOM OF LINE. MLE RSS EQULIZER LINE FITTING UL UL VPOR LINE NOTE NEVER MOUNT SENSING UL ON OTTOM OF LINE. Figure 9. Installing Indoor heck Expansion Valve Page /10
13 Leak Test Line Set and Indoor oil fter completing the leak testing of the line set and indoor coil as outlined in figure 10, proceed to Evacuating Line Set and Indoor oil on page 14. IMPORTNT The Environmental Protection gency (EP) prohibits the intentional venting of HF refrigerants during maintenance, service, repair and disposal of appliance. pproved methods of recovery, recycling or reclaiming must be followed. 1ONNET GUGE SET onnect an HF 22 manifold gauge set high pressure hose to the vapor valve service port. NOTE Normally, the high pressure hose is connected to the liquid line port. However, connecting it to the vapor port better protects the manifold gauge set from high pressure damage. With both manifold valves closed, connect the cylinder of HF 22 refrigerant to the center port of the manifold gauge set. NOTE Later in the procedure, the HF 22 container will be replaced by the nitrogen container. IMPORTNT Leak detector must be capable of sensing HF refrigerant. WRNING Refrigerant can be harmful if it is inhaled. Refrigerant must be used and recovered responsibly. Failure to follow this warning may result in personal injury or death. LOW HIGH MNIFOLD GUGE SET TO VPOR SERVIE VLVE OUTDOOR UNIT HF 22 2 TEST FOR LEKS D E F NITROGEN fter the line set has been connected to the indoor and outdoor units, check the line set connections and indoor unit for leaks. Use the following procedure to test for leaks: With both manifold valves closed, connect the cylinder of HF 22 refrigerant to the center port of the manifold gauge set. Open the valve on the HF 22 cylinder (vapor only). Open the high pressure side of the manifold to weigh in a trace amount of HF 22 into the line set and indoor unit. trace amount is a maximum of two ounces (57 g) refrigerant or three pounds (31 kpa) pressure. lose the valve on the HF 22 cylinder and the valve on the high pressure side of the manifold gauge set. Disconnect the HF 22 cylinder. onnect a cylinder of dry nitrogen with a pressure regulating valve to the center port of the manifold gauge set. djust dry nitrogen pressure to 150 psig (1034 kpa). Open the valve on the high side of the manifold gauge set in order to pressurize the line set and the indoor unit. fter a few minutes, open one of the service valve ports and verify that the refrigerant added to the system earlier is measurable with a leak detector. fter leak testing disconnect gauges from service ports. DIGITL SLE Figure 10. Leak Test Page 13 13HPD SERIES
14 Evacuating Line Set, Indoor oil and Outdoor Unit (System) 1 ONNET GUGE SET NOTE Remove cores from service valves (if not already done). onnect low side of manifold gauge set with 1/4 SE in line tee to vapor line service valve onnect high side of manifold gauge set to liquid line service valve onnect micron gauge available connector on the 1/4 SE in line tee. onnect the vacuum pump (with vacuum gauge) to the center port of the manifold gauge set. The center port line will be used later for both the HF 22 and nitrogen containers. OUTDOOR UNIT /4 SE TEE WITH SWIVEL OUPLER 500 MIRON GUGE LOW MNIFOLD GUGE SET TO VPOR SERVIE VLVE HIGH NITROGEN HF 22 VUUM PUMP TO LIQUID LINE SERVIE VLVE 2EVUTE THE SYSTEM REOMMEND MINIMUM 3/8" HOSE Open the liquid and vapor line service valves (counterclockwise) to release the factory nitrogen charge (contained in outdoor unit) into the system. Open both manifold valves and start the vacuum pump. Evacuate the line set, indoor unit and outdoor unit to an absolute pressure of 23,000 microns (29.01 inches of mercury). NOTE During the early stages of evacuation, it is desirable to close the manifold gauge valve at least once. rapid rise in pressure indicates a relatively large leak. If this occurs, repeat the leak testing procedure. NOTE The term absolute pressure means the total actual pressure within a given volume or system, above the absolute zero of pressure. bsolute pressure in a vacuum is equal to atmospheric pressure minus vacuum pressure. D When the absolute pressure reaches 23,000 microns (29.01 inches of mercury), perform the following: E F G H lose manifold gauge valves lose valve on vacuum pump Turn off vacuum pump Disconnect manifold gauge center port hose from vacuum pump ttach manifold center port hose to a dry nitrogen cylinder with pressure regulator set to 150 psig (1034 kpa) and purge the hose. Open manifold gauge valves to break the vacuum in the line set and indoor unit. lose manifold gauge valves. Shut off the dry nitrogen cylinder and remove the manifold gauge hose from the cylinder. Open the manifold gauge valves to release the dry nitrogen from the line set and indoor unit. Reconnect the manifold gauge to the vacuum pump, turn the pump on, and continue to evacuate the line set and indoor unit until the absolute pressure does not rise above 500 microns (29.9 inches of mercury) within a 20 minute period after shutting off the vacuum pump and closing the manifold gauge valves. When the absolute pressure requirement above has been met, disconnect the manifold hose from the vacuum pump and connect it to an upright cylinder of HF 22 refrigerant. Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line set and indoor unit. 1/6 TURN Perform the following: lose manifold gauge valves Shut off HF 22 cylinder Reinstall service valve cores by removing manifold hose from service valve. Quickly install cores with core 9 3 tool while maintaining a positive system pressure Replace stem caps and secure finger tight, then tighten an additional one sixth (1/6) of a turn as illustrated. 6 D Figure 11. Evacuating System /10 Page 14
15 WRNING Danger of Equipment Damage. void deep vacuum operation. Do not use compressors to evacuate a system. Extremely low vacuums can cause internal arcing and compressor failure. Damage caused by deep vacuum operation will void warranty. UTION razing alloys and flux contain materials which are hazardous to your health. void breathing vapors or fumes from brazing operations. Perform operations only in well ventilated areas. Wear gloves and protective goggles or face shield to protect against burns. Wash hands with soap and water after handling brazing alloys and flux. Evacuating the system of non condensables is critical for proper operation of the unit. Non condensables are defined as any gas that will not condense under SIZE IRUIT ND INSTLL DISONNET SWITH Refer to the unit nameplate for minimum circuit ampacity, and maximum fuse or circuit breaker (HR per NE). Install power wiring and properly sized disconnect switch. MIN FUSE OX/ REKER PNEL SERVIE DISONNET SWITH temperatures and pressures present during operation of an air conditioning system. Non condensables and water suction combine with refrigerant to produce substances that corrode copper piping and compressor parts. IMPORTNT Use a thermocouple or thermistor electronic vacuum gauge that is calibrated in microns. Use an instrument capable of accurately measuring down to 50 microns. Electrical onnections In the U.S.., wiring must conform with current local codes and the current National Electric ode (NE). In anada, wiring must conform with current local codes and the current anadian Electrical ode (E). Refer to the furnace or air handler installation instructions for additional wiring application diagrams and refer to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size. 24V TRNSFORMER Use the transformer provided with the furnace or air handler for low-voltage control power (24V 40 V minimum) Figure 12 illustrates typical outdoor unit wiring diagrams for the 13HPD heat pumps. HEK EXISTING ROOM THERMOSTT Ensure that existing room thermostat is installed on an inside wall approximately in the center of the conditioned area and 5 feet (1.5m) from the floor. It should not be installed on an outside wall or where it can be affected by sunlight or drafts. THERMOSTT 5 FEET (1.5M) NOTE Units are approved for use only with copper conductors. Ground unit at disconnect switch or to an earth ground. NOTE 24V, lass II circuit connections are made in the control panel. WRNING Electric Shock Hazard. an cause injury or death. Line voltage is present at all components on units with single-pole contactors, even when unit is not in operation! Unit may have multiple power supplies. Disconnect all remote electric power supplies before opening access panel. Unit must be grounded in accordance with national and local codes. Page 15 13HPD SERIES
16 Refer to the furnace or blower coil installation instructions for additional wiring application diagrams and refer to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size. 1. Install line voltage power supply to unit from a properly sized disconnect switch. 2. Ground unit at unit disconnect switch or to an earth ground. NOTE To facilitate conduit, a hole is provided in the bottom of the control box. onnect conduit to the control box using a proper conduit fitting. NOTE Units are approved for use only with copper conductors. 24V, lass II circuit connections are made in the low voltage junction box (see figure 12). NOTE complete unit wiring diagram is located inside the unit control box cover. NOTE For proper voltages, select thermostat wire gauge per the following chart: Wire run length WG # Insulation type less than 100 (30m) 18 color coded, temperature more than 100 (30m) 16 rating 35 º minimum 3. Install room thermostat (ordered separately) on an inside wall approximately in the center of the conditioned area and 5 feet (1.5 m) from the floor. It should not be installed on an outside wall or where it can be effected by sunlight, drafts or vibrations. 4. Install low voltage wiring from outdoor to indoor unit and from thermostat to indoor unit (see figure 12). THERMOSTT R W1 E G O Y1 POWER OMMON FIRST STGE UXILIRY HET INDOOR LOWER INDOOR UNIT R W1 W2 W3 G REVERSING VLVE OMPRESSOR POWER OMMON FIRST STGE UXILIRY HET (SOME ONNETIONS MY NOT PPLY. REFER TO SPEIFI THERMOSTT ND INDOOR UNIT.) HET PUMP WITH IR HNDER ND ELETRI HET OUTDOOR UNIT Figure 12. Typical Low Voltage onnections R W1 L O Y1 Page /10
17 IMPORTNT rankcase heater (if applicable) should be energized 24 hours before unit start up to prevent compressor damage as a result of slugging. Servicing Outdoor Unit Delivered Void of Nitrogen harge If the outdoor unit is void of factory nitrogen charge, clean the system using the procedure described below. 1. Use nitrogen to repressurize system and check for leaks. 2. Evacuate the system using evacuating procedure provided in this instruction. 3. Use nitrogen to break the vacuum and install a new filter drier in the system. 4. Evacuate the system again using evacuating procedure provided in this instruction. 5. Weigh in refrigerant using procedure outlined under Unit Start Up and Weigh In harging. Figure 13. Typical Unit Wiring Diagram 6. Monitor the system to determine the amount of moisture remaining in the oil. It may be necessary to replace the filter drier several times to achieve the required dryness level. If system dryness is not verified, the compressor will fail in the future. Unit Start Up and Weigh In harging 1. heck that fan rotates freely. 2. Inspect all factory and field installed wiring for loose connections. 3. fter evacuation of the outdoor unit, line set, and indoor unit are complete, close the manifold gauge set valves. Disconnect vacuum pump from center hose of gauge set. 4. onnect the center hose of the gauge set to a cylinder of HF 22 and purge the hose. Then, place the cylinder upside down on a scale (see figure 14). 5. Open the high side manifold gauge valve and weigh in liquid refrigerant. Refer to unit nameplate to determine correct weigh in charge (see figure 15) 6. lose manifold gauge valves. Page 17 13HPD SERIES
18 GUGE SET ONNETIONS FOR TESTING ND HRGING MNIFOLD GUGE SET LOW HIGH NOTE Refrigerant tank should be turned right side up to deliver vapor during charge optimizing procedure. OUTDOOR UNIT REFRIGERNT TNK HRGE IN LIQUID PHSE DIGITL SLE TRUE SUTION PORT ONNETION INSIDE OUTDOOR UNIT D TEMPERTURE SENSOR TO LIQUID LINE SERVIE VLVE TEMPERTURE SENSOR (LIQUID LINE) lose manifold gauge set valves and connect the center hose to a cylinder of HF 22. Set for liquid phase charging. onnect the manifold gauge set s low pressure side to the true suction port. onnect the manifold gauge set s high pressure side to the liquid line service port. DPosition temperature sensor on liquid line near liquid line service port. Figure 14. Gauge Set onnections for Initial Weigh WEIGH IN HRGING DD MOUNT OF HF 22 REFRIGERNT S SPEIFIED ON UNIT NMEPLTE DJUST MOUNT FOR VRITION IN LINE SET LENGTH S LISTED ELOW + = TOTL HRGE Refrigerant harge per Line Set Length Liquid Line Ounces per 5 feet (g per 1.5 m) Set Diameter adjust from 15 feet (4.6 m) line set* 3/8" (9.5 mm) 3 ounce per 5 (85 g per 1.5 m) NOTE *If line length is greater than 15 ft. (4.6 m), add this amount. If line length is less than 15 ft. (4.6 m), subtract this amount. Figure 15. Gauge Set harge Setup and Weigh In Page /10
19 Optimizing System harge This section outlines procedures for optimizing the system charge. NOTE Gauge set should be connected as illustrate in figure 14; however, refrigerant tank should be turned right side up to deliver refrigerant gas during charge optimizing procedure. 1. heck voltage supply at the disconnect switch. The voltage must be within the range listed on the unit s nameplate. If not, do not start the equipment until you have consulted with the power company and the voltage condition has been corrected. 2. Move the low side manifold gauge hose from the vapor line service valve to the true suction port (see figure 1 in the unit installation instruction). Make sure the refrigerant cylinder is right side up so that it will deliver gas during the charge optimizing procedure. 3. Set the thermostat for a cooling demand. Turn on power to the indoor unit and close the outdoor unit disconnect switch to start the unit. 4. llow unit to run for five minutes to allow pressures to stabilize. IRFLOW Temp. of air entering indoor coil ºF DT Wet bulb ºF º DRY UL Dry bulb T Drop 19º air flow ll temperatures are expressed in ºF air flow INDOOR OIL 64º WET UL 72º DRY UL 5. heck and adjust indoor airflow using procedures provided below for heating mode and figure 16 for cooling mode. 6. Use either approach or subcooling method (see figures 17 and 18 for optimizing system charge. djust charge as necessary. 7. lose gauge set valves and disconnect gauge set. 8. Replace the stem and service port caps and tighten as specified in Operating Service Valves on page Recheck voltage while the unit is running. Power must be within range shown on the nameplate. HETING MODE INDOOR IRFLOW HEK lower airflow (FM) may be calculated by energizing electric heat and measuring: temperature rise between the return air and supply air temperatures at the indoor coil blower unit, voltage supplied to the unit, amperage being drawn by the heat elements. Then, apply the measurements taken in following formula to determine FM: FM = mperage x Volts x x Temperature Rise (F) 1. Determine the desired DTMeasure entering air temperature using dry bulb () and wet bulb (). DT is the intersecting value of and in the table (see triangle). 2. Find temperature drop across coilmeasure the coil s dry bulb entering and leaving air temperatures ( and ). Temperature Drop Formula: (T Drop ) = minus. 3. Determine if fan needs adjustmentif the difference between the measured T Drop and the desired DT (T Drop DT) is within +3º, no adjustment is needed. See examples: ssume DT = 15 and temp. = 72º, these temperatures would necessitate stated actions: º T Drop DT = ºF TION 53º = 4 Increase the airflow 58º = 1 (within +3º range) no change 62º = 5 Decrease the airflow 4. djust the fan speedsee indoor unit instructions to increase/decrease fan speed. hanging air flow affects all temperatures; recheck temperatures to confirm that the temperature drop and DT are within +3º. Figure 16. ooling Mode Indoor irflow heck Page 19 13HPD SERIES
20 Outdoor mbient Temperature is 65ºF (18.3º) or ELOW LOK OUTDOOR OIL: [sometimes necessary with lower temperatures] Use cardboard or plastic sheet to restrict the airflow through the outdoor coil to achieve pressures from psig ( kpa). Higher pressures are needed to check charge. lock equal sections of air intake panels and move coverings sideways until the liquid pressure is in the above noted ranges. 1. onfirm proper airflow across coil using figure ompare unit pressures with table 3, Normal Operating Pressures. 3. Set thermostat to call for heat (must have a cooling load between 70-80ºF (21 26º). 4. onnect gauge set. 5. Measure outdoor ambient temperature. 6. When heat demand is satisfied, set thermostat to call for cooling. 7. llow temperatures and pressures to stabilize. NOTE If necessary, block outdoor coil to maintain psig. 8. Record liquid line temperature (Position temperature sensor on liquid line near liquid line service port.): LIQº = 9. Measure liquid line pressure and use the value to determine saturation temperature: STº = 10. Subtract to determine subcooling (Sº): STº LIQº = Sº 11. ompare results with table below. 12. If value is greater than shown, remove refrigerant; if less than shown, add refrigerant. 13. If refrigerant is added or removed, retest using approach method. Sº (Subcooling) Values (F:+/ 1.0 [: +/ 0.6 ]) Model F ( )* 6 (3.3) 11 (6) 8 (4.4) 6 (3.3) 6 (3.3) 4 (2.2) 9 (5) NOTE For best results, use the same electronic thermometer to check both outdoor-ambient and liquid-line temperatures. *F: + / 1.0 ; : + / 0.5 Figure 17. HF 22 Subcooling TXV harge Outdoor mbient Temperature 66ºF (18.9º) or OVE. 1. onfirm proper airflow across coil using figure ompare unit pressures with table 3, Normal Operating Pressures. 3. onnect gauge set. 4. When heat demand is satisfied, set thermostat to call for cooling. 5. llow temperatures and pressures to stabilize. 6. Record outdoor ambient temperature: Mº = 7. Record line temperature: LIQº = 8. Subtract to determine approach (PPº): LIQº Mº = PPº 9. ompare results with table below. 10. If value is greater than shown (high approach), add refrigerant; if less than shown (liquid temperature too close to ambient temperature, low approach), remove refrigerant. 11. If refrigerant is added or removed, retest to confirm that unit is properly charged. PPº (pproach) Values(F:+/ 1.0 [: +/ 0.6 ]) Model F ( )* 7 (3.9) 8 (4.4) 9 (5) 13 (7.2) 7 (3.9) 9 (5) 7 (3.9) NOTE For best results, use the same electronic thermometer to check both outdoor-ambient and liquid-line temperatures. *F: + / 1.0 ; : + / 0.5 Figure 18. HF 22 pproach TXV harge /10 Page 20
21 Table 3. Normal Operating Pressure Liquid +10 and Vapor +5 PSIG* IMPORTNT Minor variations in these pressures may be expected due to differences in installations. Significant differences could mean that the system is not properly charged or that a problem exists with some component in the system. Model 13HPD HPD HPD HPD HPD HPD HPD 060 Temp. F ()** Liquid / Vapor Liquid / Vapor Liquid / Vapor Liquid / Vapor Liquid / Vapor Liquid / Vapor Liquid / Vapor ooling 65 (18) 141 / / / / / / / (24) 163 / / / / / / / (29) 191 / / / / / / / (35) 222 / / / / / / / (41) 256 / / / / / / / (45) 296 / / / / / / / 81 Heating 50(10) 192 / / / / / / / (4) 180 / / / / / / / ( 1) 172 / / / / / / / ( 7) 164 / / / / / / / 34 *These are most popular match up pressures. Indoor match up, indoor air quality, and indoor load cause pressures to vary. **Temperature of the air entering the outside coil. System Operation The outdoor unit and indoor blower cycle on demand from the room thermostat. When the thermostat blower switch is in the ON position, the indoor blower operates continuously. LIQUID LINE I FLOW FILTER DRIER The pre installed liquid line bi flow filter drier as illustrated in figure 1 is approved for use with HF 22 only. Do not replace liquid line filter drier with component designed for use with HF 410. EMERGENY HET FUNTION (ROOM THERMOSTT) n emergency heat function is designed into some room thermostats. When the room thermostat is placed in the emergency heat position, the outdoor unit is disabled and only the backup heat source is used to provide heat. Typically the thermostat will have an LED or will indicate on the display the system is in the emergency heat mode to remind the homeowner that he is operating in the emergency heat mode. Emergency heat is usually used during an outdoor shutdown, but it should also be used following a power outage if power has been off for over an hour and the outdoor temperature is below 50 F (10 ). System should be left in the emergency heat mode at least six hours to allow the crankcase heater sufficient time to prevent compressor slugging. HIGH PRESSURE SWITH (S4) ( 018 MODEL ONLY) S4 is standard on the 13HPD 018 model and an option on all other models. S4 is a manual re set switch located on the liquid line. When liquid line pressure rises above the factory setting of psi, the switch opens and shuts off the compressor. MNUL RESET UTTON Figure 19. High Pressure Switch (S4) Manual Reset Defrost System The 13HPD defrost system includes two major components, a defrost control (M1) and defrost thermostat switch (S6). Page 21 13HPD SERIES
22 DEFROST ONTROL (M1) The defrost control includes the combined functions of a time/temperature defrost control, defrost relay, diagnostic LEDs and terminal strip for field wiring connections as illustrated in figure 20. FIELD SELET TIMING PINS TEST PINS OMPRESSOR DELY PINS REVERSING VLVE S87 LOW PRESSURE SWITH (OPTIONL) DEFROST THERMOSTT S4 HIGH PRESSURE SWITH (OPTIONL) DIGNOSTI LEDS 24V TERMINL STRIP ONNETIONS Figure 20. Defrost ontrol (M1) The defrost control provides automatic switching from normal heating operation to defrost mode and back. During compressor cycle (call for defrost), the control accumulates compressor run times at 30-, 60-, or 90-minute field adjustable intervals. If the defrost thermostat is closed when the selected compressor run time interval ends, the defrost relay is energized and defrost begins. NOTE The 30-second OFF cycle is not functional when jumpering the TEST pins. P1 Defrost Temperature Termination and Test Jumper Each timing pin selection provides a different accumulated compressor run time period for one defrost cycle. This time period must occur before a defrost cycle is initiated. 60 P DEFULT TEST Figure 21. P1 Jumper onfigurations The defrost control selections are: 30, 60, and 90 F (10, 21, 32 and 38 ). The jumper termination pin is factory set at 90 F (10 ). If the temperature jumper is not installed, the default termination temperature is 90 F (32 ). The maximum defrost period is 14 minutes and cannot be adjusted. P5 ompressor 30 Second Delay The defrost control has a field selectable delay to reduce occasional sounds that may occur while the unit is cycling in and out of the defrost mode. The compressor will be cycled off for 30 seconds going in and out of the defrost mode when the compressor delay jumper is removed. Test Option (P1) TEST option is provided for troubleshooting. The TEST mode may be started any time the unit is in the heating mode and the defrost thermostat is closed or jumpered. If the jumper is in the TEST position at power-up, the control will ignore the test pins. When the jumper is placed across the TEST pins for two seconds, the control will enter the defrost mode. If the jumper is removed before an additional 5 second period has elapsed (7 seconds total), the unit will remain in defrost mode until the defrost thermostat opens or 14 minutes have passed. If the jumper is not removed until after the additional 5 second period has elapsed, the defrost will terminate and the test option will not function again until the jumper is removed and re applied. Time Delay ypass The timed-off delay is five minutes long. The delay helps to protect the compressor from short-cycling in case the power to the unit is interrupted or a pressure switch opens. The delay is bypassed by placing the timer select jumper across the P1 TEST pins for 0.5 seconds as illustrated in figure 21. DS1 and DS2 Diagnostic LEDs The defrost control uses two LEDs (DS1 and DS2) for diagnostics. The LEDs flash a specific sequence according to the condition. Table 4. DS1 and DS2 LED odes Defrost ontrol (M1) Diagnostic LED Mode Green LED (DS2) Red LED (DS1) No power to control OFF OFF Normal operation / power Simultaneous Slow FLSH to control nti-short cycle lockout lternating Slow FLSH Low pressure switch fault OFF Slow FLSH (Optional) Low pressure switch OFF ON lockout (Optional) High pressure switch fault Slow FLSH OFF (Optional) High pressure switch lockout (Optional) ON OFF Page /10
23 DEFROST THERMOSTT SWITH (S6) The defrost thermostat as illustrated in figure 1 is located on the liquid line between the TXV and the distributor. When defrost thermostat senses 42 F (5.5 ) or cooler, the thermostat contacts close and send a signal to the defrost control to start the defrost timing. It also terminates defrost when the liquid line warms up to 70 F (21 ). Table 5. Defrost ontrol Inputs, Outputs and onfigurable Settings ontrol Location ontrol Label or Description Purpose Function P1 TEST Test Mode See Test Mode on page 22 for further details. P1 30, 60, 90 W1 Defrost Temperature Termination (Jumper) Pins 24V Thermostat Input / Output The defrost control as illustrated in figure 20 has valid selections which are: 30, 60, and 90 F ( 1, 16 and 32 ). The shunt termination pin is factory set at 50 F (10 ). If the temperature shunt is not installed, the default termination temperature is 90 F (32 ). 24V input/output from indoor thermostat to indoor unit. 24V ommon 24V common P2 L Thermostat Service Light Thermostat service light connection. R 24V 24V O Thermostat Input Reversing valve solenoid. Y1 Thermostat Input ontrols the operation of the unit. P5 DELY Delay Mode The defrost control has a field selectable delay to reduce occasional sounds that may occur while the unit is cycling in and out of the defrost mode. When a jumper is installed on the DELY pins, the compressor will be cycled off for 30 seconds going in and out of the defrost mode. Units are shipped with jumper installed on DELY pins. NOTE The 30 second off cycle is NOT functional when jumpering the TEST pins on P1. P6 TST, PS DF,, R, O, Y1 Factory Test onnectors Factory Use Only. DS1 DS2 RED LED GREEN LED Diagnostic LED Valid states for defrost control s two LEDs are OFF, ON and FLSHING which indicate diagnostics conditions that are described in table 4. FN TWO ONNETORS ondenser Fan Operation These two connections provide power for the condenser fan. O OUT O OUT 24V output 24V output connection for reversing valve. LO PS LO PS Low Pressure Switch Not Used. DF DF Defrost Thermostat Defrost thermostat connection points. Y1 OUT Y1 OUT 24V ommon Output 24V common output, switched for enabling compressor contactor. HS PS HS PS High Pressure Switch (Optional) Not Used. L L Service Light Output output 24V service light output. 24V 24V 24V output Not Used. Page 23 13HPD SERIES
24 Maintenance Outdoor Unit 1. lean and inspect outdoor coil (may be flushed with a water hose). Ensure power is off before cleaning. 2. Outdoor unit fan motor is pre lubricated and sealed. No further lubrication is needed. 3. Visually inspect all connecting lines, joints and coils for evidence of oil leaks. 4. heck all wiring for loose connections. 5. heck for correct voltage at unit (unit operating). 6. heck amp draw on outdoor fan motor. Motor Nameplate: ctual:. 7. Inspect drain holes in coil compartment base and clean if necessary. NOTE - If insufficient heating or cooling occurs, the unit should be gauged and refrigerant charge should be checked. Outdoor oil It may be necessary to flush the outdoor coil more frequently if it is exposed to substances which are corrosive or which block airflow across the coil (e.g., pet urine, cottonwood seeds, fertilizers, fluids that may contain high levels of corrosive chemicals such as salts) Outdoor oil The outdoor coil may be flushed with a water hose. Outdoor oil (Sea oast) Moist air in ocean locations can carry salt, which is corrosive to most metal. Units that are located near the ocean require frequent inspections and maintenance. These inspections will determine the necessary need to wash the unit including the outdoor coil. onsult your installing contractor for proper intervals/procedures for your geographic area or service contract. Indoor Unit 1. lean or change filters. 2. Some blower motors are prelubricated and permanently sealed. No more lubrication is needed. 3. djust blower speed for cooling. Measure the pressure drop over the coil to determine the correct blower FM. Refer to the unit information service manual for pressure drop tables and procedure. 4. elt Drive lowers heck belt for wear and proper tension. 5. heck all wiring for loose connections. 6. heck for correct voltage at unit. (blower operating) 7. heck amp draw on blower motor. Motor Nameplate: ctual:. Indoor oil 1. lean coil if necessary. 2. heck connecting lines, joints and coil for evidence of oil leaks. 3. heck condensate line and clean if necessary. Start Up and Performance hecklist Job Name Job no. Date Job Location ity State Installer ity State Unit Model No. Serial No. Service Technician Nameplate Voltage Rated Load mpacity ompressor Outdoor Fan Maximum Fuse or ircuit reaker Electrical onnections Tight? Indoor Filter clean? Supply Voltage (Unit Off) Indoor lower RPM S.P. Drop Over Indoor (Dry) Outdoor oil Entering ir Temp. Discharge Pressure Vapor Pressure Refrigerant harge hecked? Refrigerant Lines: Leak hecked? Properly Insulated? Outdoor Fan hecked? Service Valves: Fully Opened? aps Tight? Thermostat Voltage With ompressor Operating alibrated? Properly Set? Level? /10 Page 24
INSTALLATION INSTRUCTIONS
2008 Lennox Industries Inc. Dallas, Texas, USA INSTALLATION INSTRUCTIONS Merit Series13ACD Units RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE WARNING Improper installation, adjustment, alteration, service
INSTALLATION INSTRUCTIONS Fan Coil Replacement Coil Kit EBX & EBXX
Fan Coil Replacement Coil Kit EBX & EBXX These instructions must be read and understood completely before attempting installation. These instructions covers the installation of replacement coil kit into
INSTALLATION INSTRUCTIONS
2011 Lennox Industries Inc. Dallas, Texas, US INSTLLTION INSTRUTIONS Elite Series X13 Units ONDENSING UNITS 506635 01 09/11 Supersedes 07/11 Litho U.S.. RETIN THESE INSTRUTIONS FOR FUTURE REFERENE These
INSTALLATION INSTRUCTIONS
2010 Lennox Industries Inc. Dallas, Texas, US INSTLLTION INSTRUTIONS Elite Series X16 Units IR ONDITIONER 506637 01 11/10 Supersedes 506101 01 Litho U.S.. RETIN THESE INSTRUTIONS FOR FUTURE REFERENE These
INSTALLATION INSTRUCTIONS
2011 Lennox Industries Inc. Dallas, Texas, USA INSTALLATION INSTRUCTIONS Dave Lennox Signature Collection XP17 System HEAT PUMPS 506586 01 06/11 Supersedes 05/11 Litho U.S.A. RETAIN THESE INSTRUCTIONS
INSTALLATION INSTRUCTIONS
2011 Lennox Industries Inc. Dallas, Texas, USA INSTALLATION INSTRUCTIONS Elite Series XP14 Units RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE These instructions are intended as a general guide and do
INSTALLATION INSTRUCTIONS
2012 Lennox Industries Inc. Dallas, Texas, USA THIS MANUAL MUST BE LEFT WITH THE HOMEOWNER FOR FUTURE REFERENCE The State of California has determined that this product may contain or produce a chemical
INSTALLATION INSTRUCTIONS
2010 Lennox Industries Inc. Dallas, Texas, USA INSTALLATION INSTRUCTIONS Dave Lennox Signature Collection XC17 Units AIR CONDITIONER 04/10 Supersedes 506498 01 Litho U.S.A. RETAIN THESE INSTRUCTIONS FOR
10ACC WARNING WARNING. Service Literature 10ACC SERIES UNITS
Service Literature ACC SERIES UNITS ACC Corp. 0201 L1 Revised 08 2004 The ACC is a residential split-system condensing unit available in sizes ranging from 1 1/2 to 5 tons. Condensing coil size, circuiting
Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)
Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) I. Demonstrate safety skills in typical HVACR work situations to NATE Core Installer Knowledge Areas for Technician Excellence for Safety
INSTALLATION INSTRUCTIONS
201 Lennox Industries Inc. Dallas, Texas, US INSTLLTION INSTRUCTIONS Elite Series XC14 Units IR CONDITIONER 506636 01 07/11 Supersedes 11/10 Litho U.S.. RETIN THESE INSTRUCTIONS FOR FUTURE REFERENCE These
Recharge Procedure for Telemark TVP-2000 and TVP-3500
Recharge Procedure for Telemark TVP-2000 and TVP-3500 Required items: 1.) Refrigeration service manifold. 2.) Charge recovery system. 3.) Dry nitrogen gas. If a high pressure cylinder is used, a pressure
Model No. XP13 018 XP13 024 XP13 030 XP13 036 XP13 037 XP13 042 XP13 048 XP13 060 Data Nominal Tonnage 1.5 2 2.5 3 3+ 3.5 4 5 Connections (sweat)
Service Literature Corp. 0528 L10 Revised 05 2008 XP13 SERIES UNITS XP13 The XP13 is a high efficiency residential split system heat pump unit, which features a scroll compressor and R 410A refrigerant.
INSTALLATION AND MAINTENANCE INSTRUCTIONS 4AC16LT SERIES. Split System Air Conditioner. Save these instructions for future reference WARNING
INSTALLATION AND MAINTENANCE INSTRUCTIONS 4AC16LT SERIES Split System Air Conditioner Save these instructions for future reference WARNING The equipment covered in this manual is to be installed by trained
Your safety and the safety of others are very important.
NATURAL GAS TO PROPANE CONVERSION KIT 090 INSTALLATION INSTRUCTIONS FOR ALTITUDES 0 -,00 FT. ONLY PROPANE CONVERSION KIT SAFETY... INSTALLATION REQUIREMENTS... Tools and Parts... LP Gas Requirements...
INSTALLATION INSTRUCTION
INSTALLATION INSTRUCTION OUTDOOR SPLIT-SYSTEM AIR CONDITIONER MODELS: 10, 12, 13 AND 14 SEER 1 PHASE - 1.5 TO 5 TONS TABLE OF CONTENTS GENERAL INFORMATION.................... 2 INSPECTION..............................
Installer s Guide 18-AH39D1-13
18-AH39D1-13 Cased Aluminum "Convertible" Coils 4TXCA018BC3HC** 4TXCA024BC3HC** 4TXCB025BC3HC** 4TXCB026BC3HC** 4TXCB031BC3HC** 4TXCB032BC3HC** ALL phases of this installation must comply with NATIONAL,
SSB*H4. Service Literature. SSB*H4 Commercial Air Conditioner
Service Literature Corp. 0628 L5 Revised 07 2010 SSB*H4 Commercial Air Conditioner SSB*H4 The SSB*H4 is a high efficiency commercial split system condensing unit, which features a two stage scroll compressor
Service Facts. WARNING: HAZARDOUS VOLTAGE - DISCONNECT POWER and DISCHARGE 4TTM3-SF-1. Split System Cooling 4TTM3018-4TTM3060
4TTM3-SF-1 Service Facts Split System Cooling 4TTM3018-4TTM3060! CAUTION UNIT CONTAINS R-410A REFRIGERANT! R-410A OPERATING PRESSURE EXCEEDS THE LIMIT OF R-22. PROPER SERVICE EQUIPMENT IS REQUIRED. FAILURE
Installation Instructions
CNPVU CNRVU Uncased Coils Upflow - Downflow Heating - Cooling Installation Instructions NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS...
Refrigerant Changeover Guidelines R-22 to R-407C. Leading the Industry with Environmentally Responsible Refrigerant Solutions
Refrigerant Changeover Guidelines R-22 to R-407C Leading the Industry with Environmentally Responsible Refrigerant Solutions Emerson Climate CFC Technologies, Inc. does not advocate the HCFC wholesale
BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS
BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS PLEASE READ COMPLETE INSTRUCTIONS BEFORE YOU BEGIN LEAVE INSTALLATION INSTRUCTIONS AND USER'S GUIDE WITH OWNER ALL ELECTRIC WIRING AND PLUMBING MUST BE DONE
COMPRESSOR REPLACEMENT PROCEDURE
COMPRESSOR REPLACEMENT PROCEDURE Bard Manufacturing Company Bryan, Ohio 43506 Since 1914...Moving ahead just as planned Manual No.: 2100-003E Supersedes 2100-003D File: Volume I, Tab 1 Date: 06-25-02 Copyright
4AC13/14 SPLIT SYSTEM AIR CONDITIONER INSTALLATION / START-UP INSTRUCTIONS /HOMEOWNERS INFORMATION MANUAL
4AC13/14 SPLIT SYSTEM AIR CONDITIONER INSTALLATION / START-UP INSTRUCTIONS /HOMEOWNERS INFORMATION MANUAL These instructions must be read and understood completely before attempting installation. TABLE
Oil and Coolant Circulating Heating System. Model - OCSM
Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine
Installation and Troubleshooting Instructions for Electric Tankless Residential Water Heaters.
Model Number: Serial Number: Information Manual Installation and Troubleshooting Instructions for Electric Tankless Residential Water Heaters. ATTENTION: IF YOU ARE NOT A LICENSED PLUMBER OR A LICENSED
INSTALLATION INSTRUCTIONS R 410A Split System Air Conditioner N4A3, C4A3, H4A3, T4A3, NXA6, CXA6, HXA6, TXA6
N4A3, 4A3, H4A3, T4A3, NXA6, XA6, HXA6, TXA6 These instructions must be read and understood completely before attempting installation. DANGER, WARNING, AUTION, and NOTE The signal words DANGER, WARNING,
UHIR Series. Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater. Owner s Manual
UHIR Series Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater Owner s Manual This manual covers installation, maintenance and repair parts. Read carefully before attempting to
Refrigerant Changeover Guidelines R-22 to R-407C. Leading the Industry with Environmentally Responsible Refrigerant Solutions
Refrigerant Changeover Guidelines R-22 to R-407C Leading the Industry with Environmentally Responsible Refrigerant Solutions Copeland does not CFC advocate the wholesale changeover of HCFC HCFC refrigerants
Evaluate, Clean, and Tune Guidance
Evaluate, Clean, and Tune Guidance The Evaluate, Clean and Tune (ECT) process serves three essential purposes in the Weatherization Assistance Program (WAP). The first is to evaluate the existing system
Chromalox. Installation, Operation. Portable Industrial Unit Blower Air Heater Type DRA RENEWAL PARTS IDENTIFICATION
Chromalox Installation, Operation RENEWAL PARTS IDENTIFICATION Portable Industrial Unit Blower Air Type DRA and DIVISION SALES REFERENCE DATE SECTION (Supersedes P-) PF-) NOVEMBER, 00 DRA PF- -0-00 Specifications
INSTALLATION INSTRUCTIONS
2008 Lennox Industries Inc. Dallas, Texas, USA WARNING Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and
Thermwire. Selection Guide. Freeze Protection Heating Cable. Thermwire -Wrap. Pre-Assembled. Thermwire-Comp. Thermwire-Melt.
Thermwire Freeze Protection Heating Cable Selection Guide Pipe Freeze Protection Heating Cable Pre-Assembled Pipe Freeze Protection Heating Cable with Attached Cord & Plug Thermwire-Comp Refrigeration
Cleaning Instructions, Pilot Replacement and Valve Change. Model No.: 233010 Natural Gas
Cleaning Instructions, Pilot Replacement and Valve Change Model No.: 233010 Natural Gas 8mm open-end wrench 9mm open-end wrench 10mm open-end wrench 12mm open-end wrench 13mm open-end wrench Phillips screw
Evaporator Coil Installation Instructions
Part # 96654008 July 2010 Evaporator Coil Installation Instructions A-Coil Page 4 Multi-position A-Coil Page 4-7 Slab Coil Page 5 Horizontal A-Coil Top Connection Page 5 Horizontal A-Coil Side Connection
SPLIT SYSTEM OUTDOOR UNIT
SPLIT SYSTEM OUTDOOR UNIT CKL, CKF, CPKF SERIES INSTALLATION & OPERATING INSTRUCTIONS 2-2 Goodman Manufacturing Company, L.P. San Felipe, Suite, Houston, TX 776 www.goodmanmfg.com -or- www.amana-hac.com
Refrigeration System Installation & Operation Manual
Refrigeration System Installation & Operation Manual Manitowoc Foodservice Walk-In Division 2915 Tennessee Avenue North P.O. Box 550 Parsons, TN 38363 Phone: 800-225-9916 www.manitowocfsusa.com 550001058-3
TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW52AL AW64AL AW52AL 387030095 AW64AL 0.8180.463.0 07/05
TECHNICAL DATA & SERVICE MANUAL INDOOR UNIT: AW52AL AW64AL SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. AW52AL 387030095 AW64AL 387030096 0.8180.463.0 07/05 IMPORTANT! Please read before installation
INSTALLATION INSTRUCTIONS & HOME OWNERS MANUAL EEMAX ELECTRIC TANKLESS WATER HEATERS IMPORTANT SAFETY INFORMATION
INSTALLATION INSTRUCTIONS & HOME OWNERS MANUAL EEMAX ELECTRIC TANKLESS WATER HEATERS IMPORTANT SAFETY INFORMATION When installing or using any high voltage electrical appliance, basic safety precautions
Test Code: 8297 / Version 1
Blueprint HVAC Maintenance Technology PA Test Code: 8297 / Version 1 Copyright 2014. All Rights Reserved. General Assessment Information HVAC Maintenance Technology PA Blueprint Contents General Assessment
A/C refrigerant system, overview
Page 1 of 19 87-18 A/C refrigerant system, overview A/C refrigerant system, identification Typical A/C refrigerant system with expansion valve and receiver drier 1 - Evaporator 2 - Expansion valve 3 -
COMPRESSOR REPLACEMENT PROCEDURE
R-22 and R-410A COMPRESSOR REPLACEMENT PROCEDURE Bard Manufacturing Company, Inc. Bryan, Ohio 43506 Since 1914...Moving ahead just as planned Manual No.: 2100-003F Supersedes 2100-003E File: Volume I,
USER S, MAINTENANCE and SERVICE INFORMATION MANUAL
CONTENTS SAFETY INFORMATION................ 2 FOR YOUR SAFETY....................... 2 SYSTEM OPERATION.................. 2 THERMOSTATS........................... 2 INTERMITTENT IGNITION DEVICE...........
SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS
SECTION 15750 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for roof mounted, self-contained units, with electric cooling, and electric or reverse refrigeration cycle (heat pump) heating
Cleaning Instructions for Burner, Pilot Assembly, and Emitter Screen. Series: 150000 200605 LP Gas
Cleaning Instructions for Burner, Pilot Assembly, and Emitter Screen Series: 150000 200605 LP Gas Tools needed Bottle brush Non-abrasive scouring pad Small utility brush Heavy-duty pipe cleaners Air hose
Air Conditioner Water Heater - A Product of HotSpot Energy LLC
Air Conditioner Water Heater - A Product of HotSpot Energy LLC PLEASE READ THIS BEFORE YOU INSTALL THE UNIT 1. This air conditioner must be installed and/or repaired by a qualified technician. If you perform
How To Install An Evaporator Coil
EVAPORATOR COIL INSTALLATION INSTRUCTIONS EVAPORATOR COIL SAFETY... INSTALLATION REQUIREMENTS... Tools and Parts... System Requirements... Location Requirements... Drain Requirements... INSTALLATION INSTRUCTIONS...
It will be available soon as an 8.5 X 11 paperback. For easier navigation through the e book, use the table of contents.
The System Evaluation Manual and Chiller Evaluation Manual have been revised and combined into this new book; the Air Conditioning and Refrigeration System Evaluation Guide. It will be available soon as
Why and How we Use Capacity Control
Why and How we Use Capacity Control On refrigeration and air conditioning applications where the load may vary over a wide range, due to lighting, occupancy, product loading, ambient weather variations,
Installation Instructions
VentilAire IV Whole-House Fresh Air Supply System Installation Instructions 914228 Flat Roof Kit 914229 Sloped Roof Kit 5" x 11' Class I Insulated Flexible Duct Plastic Clamps (2) Metal Clamps (2) Ceiling
Service manual. Website: www.andico.com.au CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.
Website: www.andico.com.au Service manual CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL. - ONLY FOR AUTHORISED SERVICE PERSONNEL. MODELS: MPK1-09CR-QB8 MPK1-12ER-QB6
Ductless Split Air Conditioner
Ductless Split Air Conditioner Installation Manual Indoor HSU09VHG(DB)-W HSU12VHG(DB)-W HSU18VHH(DB)-W HSU24VHG(DB)-W Outdoor HSU09VHG(DB)-G HSU12VHG(DB)-G HSU18VHH(DB)-G HSU24VHG(DB)-G Table of Contents
Cooling system components, removing and installing
Engine BHW Cooling system components, removing and installing Page 1 / 24 19-1 Cooling system components, removing and installing Warning! When doing any repair work, especially in the engine compartment,
4AC13/14 SPLIT SYSTEM AIR CONDITIONER INSTALLATION / STARTUP INSTRUCTIONS /HOMEOWNERS INFORMATION MANUAL
4AC13/14 SPLIT SYSTEM AIR CONDITIONER INSTALLATION / STARTUP INSTRUCTIONS /HOMEOWNERS INFORMATION MANUAL These instructions must be read and understood completely before attempting installation. TABLE
HEAT PUMP FREQUENTLY ASKED QUESTIONS HEAT PUMP OUTDOOR UNIT ICED-UP DURING COLD WEATHER:
HEAT PUMP FREQUENTLY ASKED QUESTIONS HEAT PUMP OUTDOOR UNIT ICED-UP DURING COLD WEATHER: It is normal for a heat pump to have a build up of white frost on the outside coil during cold damp weather. The
DESIGN STANDARDS SECTION 23 60 00
PART 1 - GENERAL 1.01 Work included: A. Piping, tubing and fittings. B. Piping specialties. C. Special duty valves. D. Refrigerants. E. Chillers. F. Refrigerant monitors. 1.02 General requirements: A.
TECHNICAL SUPPORT MANUAL 3 Phase Air Conditioner Component R2A3**GHR
3 Phase Air Conditioner Component R2A3**GHR DANGER, WARNING, CAUTION, and NOTE The signal words DANGER, WARNING, CAU- TION, and NOTE are used to identify levels of hazard seriousness. The signal word DANGER
WON0502-B INSTALLATION INSTRUCTIONS FOR ELECTRIC FURNACES. Bulletin 30-34 / March 2013
Bulletin 30-34 / March 2013 INSTALLATION INSTRUCTIONS FOR ELECTRIC FURNACES General The information on the following pages is to provide the installer the necessary information to properly install the
Geyser-R Heat pump water heater Installation manual
Geyser-R Heat pump water heater Installation manual 1 Version 2.9 SAFETY INFORMATION Please read carefully to prevent serious accidents or injury. The Geyser-R Heat Pump Water Heater must be installed
Cooling system components, removing and installing
Page 1 of 34 19-1 Cooling system components, removing and installing WARNING! The cooling system is pressurized when the engine is warm. When opening the expansion tank, wear gloves and other appropriate
CARING FOR YOUR WATER HEATER
http://waterheatertimer.org/troubleshoot-rheem-tankless-water-heater.html Water Heater Inspections CARING FOR YOUR WATER HEATER Venting System (Direct Vent Only) The venting system should be inspected
Evaporator Coil. Installation Instructions GENERAL
IM-HAC-0966540-12 December 2013 Evaporator Coil Installation Instructions TABLE OF CONTENTS PAGE General... 1 Vertical... 2 Horizontal... 2 Multi-Position... 3-5 Metering Device... 6 Condensate Drain...
Ducoterra Radiant Heating Panel Installation Manual
Ducoterra Radiant Heating Panel Installation Manual 1. Introduction Your new radiant heating panels are designed to heat living and working spaces rapidly and efficiently by radiant heating. Like the sun,
Table V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm.
Table V Troubleshooting Checklist for Refrigeration Systems TROUBLE POSSIBLE CAUSE CORRECTIVE MEASURE High condensing pressure. Low condensing pressure. Air or non-condensable gas in system. Inlet water
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2
Refrigerant Charging Unit ICOGD. 020AH1000 Operating Manual. FR.8.2.4-09 İ-COLD 12.03.2014 Rev. 00
E Refrigerant Charging Unit ICOGD 020AH1000 Operating Manual FR.8.2.4-09 İ-COLD 12.03.2014 Rev. 00 Contents Technical Specifications... 20 Safety... 21 A/C System... 22 Components... 23 Control Panel...
ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013
ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013 READ CAREFULLY These instructions are intended to cover good practices in
Refrigerant Changeover Guidelines HCFC R-22 to HFC R-404A/R-507. Leading the Industry with Environmentally Responsible Refrigerant Solutions
Refrigerant Changeover Guidelines HCFC R-22 to HFC R-404A/R-507 Leading the Industry with Environmentally Responsible Refrigerant Solutions Copeland does not advocate the wholesale changeover of HCFCs
Cooktop Low-Profile Ventilation Hoods
INSTALLATION GUIDE Cooktop Low-Profile Ventilation Hoods Contents Wolf Cooktop Low-Profile Ventilation Hoods........ 3 Cooktop Low-Profile Hood Specifications.......... 4 Cooktop Low-Profile Hood Installation............
NITROUS TRANSFER PUMP INSTRUCTIONS
NITROUS TRANSFER PUMP INSTRUCTIONS SAFETY TIPS Never directly inhale nitrous oxide. When inhaled in large quantities, nitrous oxide can cause respiratory ailments or in extreme cases, death by suffocation.
Reverse Cycle Inverter Split System Air Conditioner
Reverse Cycle Inverter Split System Air Conditioner Model Number TAC-09CHSA/JAI5 INSTALLATION MANUAL Contents 03 Warranty Details 04 Welcome 05 General Safety Instructions 06 Product Overview 07 Selecting
SL280UHV SERIES GAS FURNACE WARNING
2010 Lennox Industries Inc. Dallas, Texas, USA 506677 01 11/2010 Supersedes 506409 01 SL280UHV SERIES GAS FURNACE Litho U.S.A. FIRE OR EXPLOSION HAZARD. Failure to follow safety warnings exactly could
EVANS ELECTRONIC TEMPERATURE CONTROL TROUBLESHOOTING GUIDE for systems equipped with electric coolant valve and external PC board.
EVANS ELECTRONIC TEMPERATURE CONTROL TROUBLESHOOTING GUIDE for systems equipped with electric coolant valve and external PC board. This Troubleshooting Guide covers the electric coolant valve and control
15GAL STEEL OIL DRAIN WITH 110V PUMP
15GAL STEEL OIL DRAIN WITH 110V PUMP OWNER S MANUAL WARNING: Read carefully and understand all ASSEMBLY AND OPERATION INSTRUCTIONS before operating. Failure to follow the safety rules and other basic safety
WHAT YOU DON T KNOW ABOUT ACCUMULATORS CAN KILL YOU!
WHAT YOU DON T KNOW ABOUT ACCUMULATORS CAN KILL YOU! Atlanta (Monroe) GA 770-267-3787 [email protected] www.gpmhydraulic.com What You Don t Know About Hydraulic Accumulators Can Kill You TABLE OF CONTENTS
UV100A Ultraviolet Air Treatment System
UV100A Ultraviolet Air Treatment System INSTALLATION INSTRUCTIONS APPLICATION When installed in forced air heating and cooling systems, the UV100A Ultraviolet Air Treatment System kills airborne microorganism
OHIO MEDICAL CORPORATION. Medical Gas Panel. Installation and Maintenance Manual
OHIO MEDICAL CORPORATION Medical Gas Panel Installation and Maintenance Manual P/N 255105 (Rev.5) 08/2005 P/N 255105 (Rev.5) 08/2005 PAGE 2 OHIO MEDICAL CORPORATION PAGE 3 1.0 User Responsibilities The
36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve
Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE. DESCRIPTION
Please keep this manual for f uture reference.
GAS WATER/AGUA Congratulations! You've just purchased a new Marey Portable tankless water heater and will soon begin to enjoy the benefits of going tankless. Take the time to thoroughly read and understand
SBC90. Abrasive Blast Cabinet Assembly & Operating Instructions
SBC90 Abrasive Blast Cabinet Assembly & Operating Instructions READ ALL INSTRUCTIONS AND WARNINGS BEFORE USING THIS PRODUCT. SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE. This manual provides important
ATS Overhead Table Shelf System INSTRUCTION MANUAL
ATS Overhead Table Shelf System INSTRUCTION MANUAL ATS Overhead Table Shelf System Instruction Manual Warranty Newport Corporation warrants this product to be free of defects in material and workmanship
XL PREMIUM OIL COOLER KIT
-J05 REV. 0-0-0 XL PREMIUM OIL COOLER KIT GENERAL Kit Number 0008 Models For model fitment information, see the P&A Retail Catalog or the Parts and Accessories section of www.harley-davidson.com (English
Explosion-Proof Electric Unit Heaters
Type FX4 FX4 Explosion-Proof Electric Air Heaters FX4 heaters are UL listed and/or CSA certified for use in hazardous locations. They are designed for dry indoor industrial applications such as oil refineries,
MAC-120HE-01 Air-Cooled Chiller
MAC-120HE-01 Air-Cooled Chiller 10 Ton / 120,000 BTUH Air-Cooled Chiller 208/230-1-50/60 1 HVAC Guide Specifications Air-Cooled Liquid Chiller Nominal Size: 10 Tons Multiaqua Model Number: MAC-120HE-01
DANGER DANGER. General Information. Safety Is Your Responsibility. Ordering Parts. Contact Information
Safety Safety Is Your Responsibility DANGER To avoid personal injury or death, carefully read and understand all instructions pertaining to the Anthony Liftgates product. Do not attempt to install, operate,
Dehumidifier Users manual. For Models: DH45S DH65S
Dehumidifier Users manual For Models: DH45S DH65S 950-0062-revD Jan. 9 2007 FORWARD The appearance of the units that you purchase might be slightly different from the ones described in the Manual, but
3. SEISCO PARTS & SERVICE REMOVAL AND REPAIR GUIDE
4 3. SEISCO PARTS & SERVICE REMOVAL AND REPAIR GUIDE A. Changing the Control Board B. Replacing a Heating Element C. Thermistor Replacement D. High Limit Switch Replacement E. Level Detector Replacement
Split-type Air-Conditioner INSTALLATION MANUAL CONTENTS FOR INSTALLER MXZ-3A30NA MXZ-4A36NA ATTENTION. English. Français. Español
Split-type Air-Conditioner MXZ-3A30NA MXZ-4A36NA INSTALLATION MANUAL Refer to the installation manual of each indoor unit for indoor unit installation. English Français Español ATTENTION This manual mentions
Ceiling Mount Air Handler Manual
www.surna.com 303.993.5271 Ceiling Mount Air Handler Manual Models: CMAH12, CMAH18, CMAH24, CMAH30, CMAH36, CMAH48, CMAH60 Revised: September 2014 Table of Contents Warranty Information 4 Limited Warranty
COOLING SYSTEM Section Page
5 COOLING SYSTEM Section Page 5.1 COOLANT PRE-HEATER... 5-3 5.2 COOLANT PUMP NON-EGR ENGINE... 5-7 5.3 COOLANT PUMP EGR ENGINE... 5-13 5.4 FRONT CONNECTOR HOUSING NON-EGR ENGINE... 5-17 5.5 FRONT CONNECTOR
543-0032-00, 943-0032-00. User s Manual
543-0032-00, 943-0032-00 User s Manual 1 Comfort Alert Diagnostics Faster Service And Improved Accuracy The Comfort Alert diagnostics module is a breakthrough innovation for troubleshooting heat pump and
http://waterheatertimer.org/troubleshoot-rheem-tankless-water-heater.html
http://waterheatertimer.org/troubleshoot-rheem-tankless-water-heater.html TECHNICAL SERVICE DEPARTMENT Removal, Cleaning, & Reinstallation of the Burner Assembly For models 74 & GT199 Required tools -
SunMaxx Solar Filling Station Operating Instructions
SunMaxx Solar Filling Operating Instructions Content 1. Declaration of conformity... 2 2. Introduction... 2 3. Transportation and unpacking... 4 4. Mounting and commissioning... 5 5. End of operation...
TABLE OF CONTENTS. SECTION 1 General Information: Pg 2 Description of Operation
GTRDD SERIES HEATLESS DRYER INSTALLATION, OPERATION & MAINTENANCE MANUAL TABLE OF CONTENTS SECTION 1 General Information: Pg 2 Description of Operation SECTION 2 Safety Instructions: Pg 3 Installation
Packaged Terminal Air Conditioner Wall Sleeve Installation
Installation & Maintenance Data IM 1196 Group: PTAC Part Number: 910141799 Date: October 2013 Packaged Terminal Air Conditioner Installation x 42" PGAN with Top-Mounted Hydronic Heat Note: Installation
SYLLABUS For BASIC TRADE COURSE (360 Hours) On REFRIGERATION AND AIR CONDITIONING
SYLLABUS For BASIC TRADE COURSE (360 Hours) On REFRIGERATION AND AIR CONDITIONING INDEX 1. Introduction 3 2. Objectives 3 3. Employment Opportunity 4 4. Course Structure 4 5. Entry Qualification 4 6. List
CDS TROUBLESHOOTING SECTION I. VACUUM. 1.0. Weak vacuum at wand. Gauge reads normal (10hg to 14hg)
CDS TROUBLESHOOTING SECTION I. VACUUM 1.0. Weak vacuum at wand. Gauge reads normal (10hg to 14hg) 1.1. Clogged hoses or wand tube. Disconnect hoses and carefully check for an obstruction. 1.2. Excessive
Installation Guide. 5 Series 15 W. Undercounter/Freestanding Nugget Ice Machine
Installation Guide 5 Series 15 W. Undercounter/Freestanding Nugget Ice Machine Table of Contents Warnings & Important Safety Instructions 3 Dimensions (Professional) 5 Dimensions (Custom Panel) 6 Specifications
CEILING CASSETTE FAN COIL UNIT
CEILING CASSETTE FAN COIL UNIT Operation and Installation Manual MHCFC4W-04, 08, 12, 16 Four way ceiling cassette fan coil unit Please read this manual before using the fan coil unit. Installation and
M SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A
Bulletin 20-20.2 / July 2012 M SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A ➀ ➁ ➂ Model Number Key M 2430 C L 1 - A - ➀ Unit Type M=Modular Nominal Capacity 2430=24000 to 30000
