CRITICALITY IN A CASCADING FAILURE BLACKOUT MODEL
|
|
|
- Crystal Barrett
- 9 years ago
- Views:
Transcription
1 15th Power Systems Computation Conference, Liège Belgium August 2005 CRITICALITY IN A CASCADING FAILURE BLACKOUT MODEL Dusko P. Nedic (1) Ian Dobson (2) Daniel S. Kirschen (1) Benjamin A. Carreras (3) Vickie E. Lynch (3) (1) School of Electrical & Electronic Engineering (2) ECE Dept., Univ. of Wisconsin (3) Oak Ridge National Lab The University of Manchester, UK Madison WI USA Oak Ridge TN USA [email protected] [email protected] [email protected] Abstract We verify and examine criticality in a 1000 bus network with an AC blackout model that represents many of the interactions that occur in cascading failure. At the critical loading there is a sharp rise in the mean blackout size and a power law probability distribution of blackout size that indicates a significant risk of large blackouts. Keywords: reliability, security, risk, power law 1 INTRODUCTION Cascading failure is the main mechanism of large blackouts. Failures successively weaken the system and make further failures more likely so that a blackout can propagate to disable large portions of the electric power transmission infrastructure upon which modern society depends. Here the term failure refers to power system components being removed from service by a variety of means, including action or malfunction of the protection system, automatic or manual controls, and physical breakdown. There are many different types of interactions by which failures can propagate during the course of a blackout. For example, a transmission line tripping can cause a transient, the overloading of other lines, the operation or misoperation of relays, reactive power problems, or can contribute to system instabilities or operator stress. However, for all these types of interaction, the risk of cascading failure generally becomes more severe as overall system loading increases. But exactly how does cascading failure become more likely as loading increases? Previous work suggests that a cascading failure does not gradually and uniformly become more likely; instead there is a transition point at which its likelihood sharply increases. This transition point has some of the properties of a critical transition or a phase transition in statistical physics. That is, there is a critical loading at which the probability of large blackouts and the mean blackout size start to rise quickly and at which the probability distribution of blackout sizes has a power law dependence [1, 9, 5, 13]. The significance of the power law in the probability distribution of blackout size is that it implies a substantial risk of large blackouts near the critical loading [2]. (For example, a power law dependence with exponent 1 implies that blackout probability is inversely proportional to blackout size. Then, if blackout cost is proportional to blackout size, the blackout risk, which is the product of blackout size and blackout probability, remains constant so that the risk of large blackouts is comparable to that of small blackouts.) The power law is also consistent with the observed frequency of large blackouts in North America [3]. It is important to verify and compare criticality in a variety of power system blackout models to find out the extent to which it is a phenomenon universally associated with cascading failure of power systems. Models of cascading failure in power systems are described in [14, 12, 1, 10, 5, 13]. We investigate criticality in a sizable network with a fairly detailed blackout model and measure blackout size by energy unserved. At a given loading level, initial outages are chosen randomly and the consequences of each initial outage are simulated to estimate the distribution of blackout size. Gradually increasing the loading yields estimates of the probability distribution of blackout size at each loading. The mean blackout size is also computed at each loading. Blackouts are traditionally analyzed after the blackout by a detailed investigation of the particular sequence of failures. This is good engineering practice and very useful for finding and correcting weaknesses in the power system. We take a different and complementary approach and seek to analyze the overall probability and risk of blackouts from a global perspective. An analogy can highlight this bulk systems approach and the role of phase transitions: If we seek to find out how close a beaker of water is to boiling, we do not compute in detail the vast number of individual molecule movements and collisions according to Newton s deterministic laws. A bulk statistical approach using a thermometer works well and we know that the phase transition of boiling water occurs at 100 degrees Celsius. The analogy suggests that to manage the risk of blackouts, we first need to confirm, understand and detect the criticality phase transition in blackout risk that seems to occur as power systems become more stressed. 2 POWER SYSTEM BLACKOUT MODEL The AC power blackout model developed at the University of Manchester represents a range of interactions, including cascade and sympathetic tripping of transmission lines, heuristic representation of generator instability, under-frequency load shedding, post-contingency redispatch of active and reactive resources, and emergency load shedding to prevent a complete system blackout caused by a voltage collapse. The amount of time re- 15th PSCC, Liege, August 2005 Session 1, Paper 4, Page 1
2 quired for restoration is assumed to depend on the amount of load to be reconnected. The Manchester model used in this paper was designed to provide a realistic representation of the behavior of a power system when subjected to disturbances [14, 12]. For example, the Manchester model represents various adjustments that are made by automatic control systems and operators when trying to return the system to a stable operating condition. It also incorporates mechanisms that can amplify a relatively benign initial disturbance and cause a cascading outage. Initialize System State Simulate Random Outages Simulate Generator Instability Simulate Sympathetic Trippings Restore Load Generation Balance Yes Run Power Flow Converged? Yes Simulate Cascade Trippings Any Tripping? No No Compute Energy Not Served Shed some load Figure 1: Cascading failure power system model. Because it is impossible to predict the nature or the location of the initiating fault or failure, the model relies on a state sampling Monte Carlo simulation of the behavior of the system. Simulations start from a normal system state that can be varied to study the resilience of the system under various conditions. As Figure 1 illustrates, the system is returned to this normal state at the beginning of each trial. For each trial, an initial disturbance is created by simulating random outages of system components. This is achieved by generating a random number between 0 and 1 for each component in the system. If the random number is below the probability of outage over the period considered for the component under consideration, this component is taken out of service. Otherwise, it is assumed to remain in service. This approach generates a new system state with either no outage, a single outage or, occasionally, multiple independent outages. Some of the faults that these simulated outages represent can cause generators to go unstable. A simple procedure has been implemented to identify circumstances under which one or more generators might be disconnected because of transient instability caused by the initiating failures [14]. If this procedure determines that a generator would go unstable following the initiating fault, it is disconnected from the system. It has been recognized that malfunctions in the protection system are an important contributing factor in major blackouts [16, 15]. Hidden failures in the protection system cause intact equipment to be unnecessarily disconnected following a fault on a neighboring component. These sympathetic failures have the potential to transform a routine outage into a major incident. Because it is impossible to know which protection device might malfunction, a probabilistic approach has been adopted. The component affected by the initiating failure is assumed to be at the centre of a vulnerability region that contains all the components that might be tripped by a malfunction of the protection system in response to the initiating failure. Sympathetic trippings are then simulated when a random number generated for each component in the vulnerability region turns out to be larger than the assumed probability of protection malfunction. The initiating failure and the possible subsequent generator instabilities and sympathetic trippings may cause an imbalance between load and generation. Such an imbalance would cause a change in frequency that triggers under-frequency load shedding or generation outages due to overspeed. Once the load/generation balance has been restored, a power flow is run taking into consideration all the changes to the base case triggered by the initiating failure. If this power flow does not converge, this is taken as an indication that the system would suffer from a voltage collapse if the operator did not take action. The model assumes that the operator has enough time and understanding of the situation to implement load shedding in an attempt to arrest this voltage collapse. Rather than use an optimal power flow to determine the minimum amount of load to be shed, the model sheds load in blocks of 5% in the area with the worst mismatches until convergence is achieved. If shedding load in one area is not sufficient, further dis- 15th PSCC, Liege, August 2005 Session 1, Paper 4, Page 2
3 connections are made in neighboring areas. If convergence is not achieved after a certain number of load shedding steps, it is assumed that a complete system blackout has occurred. Once the power flow has converged, the power flow in each branch is checked against its emergency rating. If this rating is exceeded, the branch is assumed to have tripped. The power flow is recalculated and further load shedding implemented if needed to achieve convergence. If this trial resulted in the outage of one or more components and if these outages caused the disconnection of some load, the energy not served is then computed and recorded. Going from the load disconnected to the energy not served requires a model of the restoration process. The model that was adopted [11] assumes a fixed time during which the operators take stock of the situation, get organized and then reconnect the load at a constant rate. With this model all complete system blackouts result in the same amount of energy not served. The Manchester model has been exhaustively tested on a 53-bus system [14] and on the large power system used in this paper [12]. 3 RESULTS The test case represents a large European power system and has 1000 busses, 1800 transmission lines and transformers, and 150 generating units. The base case for the studies is derived from a snapshot of the output of the state estimator running at the control center that manages this system. The base case load has an active power demand of 33 GW and a reactive power demand of 2.5 GVAr. The Manchester model was run with randomized initial outages at a series of load levels starting from 1.20 times base case load and ending at 2.00 times base case load. Figure 2: Expected energy not served as a function of the loading factor with respect to the base case. There is a sharp increase in blackout size at the critical loading of 1.94 times the base case loading. Probability Figure 3: Probability distribution of expected energy not served at the critical loading of 1.94 times the base case loading. Note the log-log scale; a straight line on this plot indicates a power law relation. The straight line slope of approximately 1.2 indicates that the blackout probability is proportional to (EENS) The sharp rise in expected energy unserved in Figure 2 suggests a critical loading at 1.94 times the base case loading. The corresponding probability distribution (probability density function) obtained by binning the data for loadings at the critical loading is shown in Figure 3. (The bins are chosen to require a minimum number of points per bin. The probability density estimated in each bin is then the fraction of points in the bin divided by the bin width.) The probability distribution at critical loading in Figure 3 shows evidence of a power law region over almost 3 decades of expected energy not served. The exponent of the power law relationship is approximately 1.2. We also process the data at the critical loading in a different way to get another estimate of the power law exponent. The relative frequency of blackouts exceeding a given expected energy not served gives an estimate of the complementary cumulative distribution function as shown in Figure 4. This complementary cumulative distribution function shows a power law region of slope approximately 0.5, and, since a cumulative distribution function is the integral of a probability distribution function, this corresponds to a power law in the (non-cumulative) probability distribution function of exponent 1.5. Both methods give a power law exponent for the probability distribution function between 1 and 2. Both the sharp rise in average blackout size and the power law in the probability distribution of expected energy unserved near loading 1.94 are evidence of criticality. 15th PSCC, Liege, August 2005 Session 1, Paper 4, Page 3
4 1-cumulative distribution function E Figure 4: Probability that blackout exceeds a given expected energy not served (complementary cumulative probability distribution) at the critical loading of 1.94 times the base case loading. The straight line slope of approximately 0.5 indicates that the blackout probability is proportional to (EENS) Probability Figure 5: Probability distributions of expected energy not served for four loadings below the critical loading, namely 1.20, 1.47, 1.63 and 1.84 times the base case loading. Probability Figure 6: Probability distributions of expected energy not served for four loadings above the critical loading, namely 1.95, 1.98, 1.99 and 2.00 times the base case loading. Loadings below the critical loading show a similar power law behavior in Figure 4 except that there seems to be a tendency for the power law to extend to lower maximum values of blackout size. A sample of loadings above the critical loading yield the probability distributions of Figure 6. Figure 6 shows an overall approximate power law behavior together with peaks at which blackouts are concentrated at particular sizes. These results have some uncertainty due to noise in the data and the peaks show some sensitivity to the precise loading level. 4 COMPARISON WITH OTHER MODELS 4.1 Abstract cascading failure model The power system results can be compared to the corresponding results from the idealized CASCADE model of cascading failure [9]. Here CASCADE has 1000 identical components randomly loaded. An initial disturbance adds load d to each component and causes some components to fail by exceeding their loading limit. Failure of a component causes a load increase p for all the other components. As components fail, the system becomes more loaded and cascading failure of further components becomes likely. The model is simple enough that there is an analytic formula for the probability distribution of the number of failed components. CASCADE is an abstract model with a minimum representation of cascading failure and it has no power systems modeling. However, it can be used to help understand cascading failure in more complicated models. 15th PSCC, Liege, August 2005 Session 1, Paper 4, Page 4
5 Figure 7: Mean number of failed components as a function of average initial loading L in CASCADE model. There is a sharp increase at the critical loading L=0.8. There is saturation with all 1000 components failed at loading L=0.96. Figure 8: Probability of more than 500 components failed as a function of loading L in CASCADE model. There is a sharp increase at the critical loading L=0.8. We increase the average initial loading L to obtain the results shown in Figures 7 and 8 (parameters are d=p=0.0004/(2-2l) and more modeling details are given in [9]). The critical loading occurs near L = 0.8 as is seen by the change in gradient in both the mean number of components failed in Figure 7 and the probability of more than 500 components failing in Figure 8. The probability distribution of the number of failed components at criticality is shown in Figure 9 and the exponent of the power law region is approximately 1.4. Branching process models that approximate CASCADE show similar results [7]. For single-type branching processes it is known analytically that the exponent of the power law region is 1.5. Figure 9: Probability distribution of number of failed components near criticality in CASCADE model. 4.2 Power system blackout models The OPA power system blackout model [1] represents transmission lines, loads and generators with the usual DC load flow assumptions. Starting from a solved base case, blackouts are initiated by random line outages. Whenever a line is outaged, the generation and load is redispatched using standard linear programming methods. The cost function is weighted to ensure that load shedding (blackout) is avoided where possible. If any lines were overloaded during the optimization, then these lines are outaged with a fixed probability. The process of redispatch and testing for outages is iterated until there are no more outages. (This describes OPA with a fixed network; OPA can also represent the complex dynamics of load increase and network upgrade [4].) The hidden failure power system blackout model [5] has a similar level of modeling detail as OPA for cascading line outages but also models in detail hidden failures of relays by increasing the probability of failure of loaded lines exposed by adjacent line trips. Probabilities of blackout are determined using importance sampling. Both OPA [1] and the hidden failure model [5] show a change in gradient as overall system load is increased, although the effect is less clear-cut in the case of the hidden failure model. Some approximate power law exponents obtained at criticality for all the models discussed in this paper are shown in Table 1. model exponent test case reference Manchester -1.2, bus this paper OPA -1.2, -1.6 tree 382 [1], [4] Hidden failure -1.6 WSCC179 [5] CASCADE [9] Branching [7] Table 1: Approximate power law exponents at criticality for several cascading failure models. 15th PSCC, Liege, August 2005 Session 1, Paper 4, Page 5
6 4.3 Further discussion of criticality In complex systems and statistical physics, a critical point for a type-2 phase transition is characterized by a discontinuity of the gradient in some measured quantity. (For example, for the Manchester model results in section 3 this measured quantity is mean blackout size as measured by expected energy not served, and for the CASCADE model in section 4 the measured quantity is the mean number of failed components or the probability of the number of failures exceeding half the components.) (There are other types of transition possible: type-1 phase transitions have a discontinuity in the measured quantity at the phase transition.) At the critical point, fluctuations of the measured quantity can be of any size and their correlation length becomes of the order of the system size. In terms of blackouts, this means that a range of blackout sizes up to the system size are possible and that an initial failure can possibly propagate to black out most of the power system. A consequence of criticality is that the probability distribution of the fluctuations or the blackout size has a power tail. CASCADE and especially OPA show complicated critical transition behavior [1]. The parameter values for the CASCADE results in section 4.1 correspond to a small initial disturbance; this gives qualitatively similar results to power system cascading failures with a few initial line outages. In CASCADE, the mean number of failures can fail to detect the criticality at other parameter values. The loading at which an initial failure can with positive probability propagate to failure of the entire system is called the percolation threshold. A measure for criticality that corresponds more exactly to a percolation threshold is the probability of a large fraction of components failing and this measure was illustrated for the CASCADE model in section 4.1. The results in section 4.1 show that for the parameter values chosen, the mean number of failures detects criticality very similarly to the probability of a large fraction of components failing. 5 DISCUSSION AND CONCLUSIONS The main conclusion is that the Manchester model of cascading failure on a 1000 bus power system test case shows evidence of a critical loading at which there is a sharp rise in mean blackout size and a power law in the probability distribution of blackout size. In addition to being another and needed verification of the criticality phenomenon for cascading blackout risk, this is an advance upon previous results because of the variety of cascading failure interactions represented in the Manchester model and because of the test case size and realism. The details of the observed criticality are broadly consistent with previous results. For example, the Manchester model on the 1000 bus test case gives an approximate power law exponent of 1.2 or 1.5 at criticality and observed NERC data and power system and abstract models of cascading failure also give power law exponents between 1 and 2 [3, 1, 4, 2, 5, 8, 9]. There is some uncertainty in obtaining precise values of the power law exponent for any of the real or simulated power system data and considerable idealization in applying the more abstract models of cascading failure, so a more accurate comparison of the exponents is not feasible at present. More quantitative statistical estimation would be desirable. The importance of the critical loading is that it defines a reference point for increasing risk of cascading failure. Monitoring the proximity to the critical loading will allow the risk of large, cascading failure blackouts to be assessed. In terms of the temperature analogy discussed in the introduction, determining the proximity to the critical loading is akin to measuring temperature to determine the proximity to boiling. The emerging methods to make these bulk statistical measurements include the correlated sampling Monte Carlo methods in [12] and the measurement of average propagation of failures in a branching process approximation suggested in [8]. Although there is a substantial risk of large blackouts near criticality, it cannot be assumed based on the present knowledge about blackout risk that power system operation near criticality is necessarily undesirable; there are also substantial economic benefits in maximizing the use of the power transmission system that will also have to be considered in a comprehensive risk analysis. A key part of such a risk analysis is obtaining the probability distribution of blackout size from simulations or measurements and criticality plays an important role in the form of the probability distribution. Such a comprehensive risk analysis of blackouts of all sizes is an overall research goal and the work in this paper confirming criticality with a fairly detailed model in a 1000 bus test case contributes to this goal. ACKNOWLEDGMENTS Part of this research was coordinated by the Consortium for Electric Reliability Technology Solutions and funded by the Office of Electric Transmission and Distribution, Transmission Reliability Program of the U.S. Department of Energy under contract and Interagency Agreement DE-A1099EE35075 with the National Science Foundation. Part of this research has been carried out at Oak Ridge National Laboratory, managed by UT-Battelle LLC, for the U.S. Department of Energy under contract number DE-AC05-00OR I. Dobson gratefully acknowledges support in part from NSF grant ECS This paper is an account of work sponsored in part by the Power Systems Engineering Research Center (PSERC). 15th PSCC, Liege, August 2005 Session 1, Paper 4, Page 6
7 REFERENCES [1] B.A. Carreras, V.E. Lynch, I. Dobson, D.E. Newman, Critical points and transitions in an electric power transmission model for cascading failure blackouts, Chaos, vol. 12, no. 4, 2002, pp [2] B.A. Carreras, V.E. Lynch, I. Dobson, D.E. Newman, Blackout mitigation assessment in power transmission systems, 36th Hawaii International Conference on System Sciences, Hawaii, USA January [3] B.A. Carreras, D.E. Newman, I. Dobson, A.B. Poole, Evidence for self organized criticality in electric power system blackouts, IEEE Trans. Circuits and Systems I, vol. 51, no. 9, Sept 2004, pp [4] B.A. Carreras, V.E. Lynch, I. Dobson, D.E. Newman, Complex dynamics of blackouts in power transmission systems, Chaos, vol. 14, no. 3, 2004, pp [5] J. Chen, J.S. Thorp, I. Dobson, Cascading dynamics and mitigation assessment in power system disturbances via a hidden failure model, International Journal Electrical Power and Energy Systems, vol. 27, no. 4, May 2005, pp [6] I. Dobson, B.A. Carreras, V. Lynch, D.E. Newman, Complex systems analysis of series of blackouts: cascading failure, criticality, and self-organization, Bulk Power System Dynamics and Control VI, Aug. 2004, Cortina d Ampezzo, Italy. [7] I. Dobson, B.A. Carreras, D.E. Newman, A branching process approximation to cascading load-dependent system failure, 37th Hawaii Intl. Conference on System Sciences, Hawaii, USA [8] I. Dobson, B.A. Carreras, D.E. Newman, A criticality approach to monitoring cascading failure risk and failure propagation in transmission systems, Electricity Transmission in Deregulated Markets, conf. at Carnegie Mellon University, Pittsburgh PA USA Dec [9] I. Dobson, B.A. Carreras, D.E. Newman, A loadingdependent model of probabilistic cascading failure, Probability in the Engineering and Informational Sciences, vol. 19, no. 1, 2005, pp [10] R.C. Hardiman, M.T. Kumbale, Y.V. Makarov, An advanced tool for analyzing multiple cascading failures, 8th Intl. Conf. Probability Methods Applied to Power Systems, Ames Iowa USA Sept [11] D.S. Kirschen, K.R.W. Bell, D.P. Nedic, D. Jayaweera, R.N. Allan, Computing the value of security, IEE Proceedings Generation, Transmission and Distribution, Vol. 150, No. 6, Nov 2003, pp [12] D.S. Kirschen, D. Jayaweera, D.P. Nedic, R.N. Allan, A probabilistic indicator of system stress, IEEE Trans. Power Systems, vol. 19, no. 3, August 2004, pp [13] H. Liao, J. Apt, S. Talukdar, Phase transitions in the probability of cascading failures, Electricity Transmission in Deregulated Markets, conference at Carnegie Mellon University, Pittsburgh PA USA Dec [14] M.A. Rios, D.S. Kirschen, D. Jayaweera, D.P. Nedic, R.N. Allan, Value of security: modeling timedependent phenomena and weather conditions, IEEE Trans. Power Systems, vol. 17, no. 3, August 2002, pp [15] D.P. Nedic, D.S. Kirschen, Discovering mechanisms of disturbance development, Bulk Power System Dynamics and Control VI, August 2004, Cortina d Ampezzo, Italy. [16] S. Tamronglak, S.H. Horowitz, A.G. Phadke, J.S. Thorp, Anatomy of power systems blackouts: preventive relaying strategies, IEEE Trans. Power Delivery, vol. 11, no. 2, April 1995, pp th PSCC, Liege, August 2005 Session 1, Paper 4, Page 7
Risk of Large Cascading Blackouts
Risk of Large Cascading Blackouts EUCI Transmission Reliability Conference Washington DC, October 2006 Ian Dobson ECE Department University of Wisconsin joint work with Ben Carreras, Oak Ridge National
Value of Security Assessment - Extensions and Applications
Value of Security Assessment - Extensions and Applications A thesis submitted to the University of Manchester Institute of Science and Technology for the degree of Doctor of Philosophy 2003 Dilan Supun
REQUIREMENTS FOR A REAL-TIME RISK MONITORING TOOL TO REDUCE TRANSMISSION GRID NUCLEAR PLANT VULNERABILITIES
REQUIREMENTS FOR A REAL-TIME RISK MONITORING TOOL TO REDUCE TRANSMISSION GRID NUCLEAR PLANT VULNERABILITIES M. D. Muhlheim, 1 L. C. Markel, 2 F. J. Rahn, 3 and B. P. Singh 4 1 Oak Ridge National Laboratory,
Engineering innovation
Eaton's Electrical Engineering Services & Systems Solutions Focus Seamless Solutions for Reliable, Efficient and Safe Power Systems Engineering innovation Progressive solutions for today s power systems
Chapter 5. System security and ancillary services
Chapter 5. System security and ancillary services 1 Introduction Markets for electrical energy can function only if they are supported by the infrastructure of a power system. System should continue to
Optimal Replacement of Underground Distribution Cables
1 Optimal Replacement of Underground Distribution Cables Jeremy A. Bloom, Member, IEEE, Charles Feinstein, and Peter Morris Abstract This paper presents a general decision model that enables utilities
Benchmarking and Validation of Cascading Failure Analysis Tools
preprint; to appear in IEEE Transactions on Power Systems in 2016 1 Benchmarking and Validation of Cascading Failure Analysis Tools IEEE Working Group on Understanding, Prediction, Mitigation and Restoration
Cancellation of Load-Regulation in Low Drop-Out Regulators
Cancellation of Load-Regulation in Low Drop-Out Regulators Rajeev K. Dokania, Student Member, IEE and Gabriel A. Rincόn-Mora, Senior Member, IEEE Georgia Tech Analog Consortium Georgia Institute of Technology
Cumulative Diagrams: An Example
Cumulative Diagrams: An Example Consider Figure 1 in which the functions (t) and (t) denote, respectively, the demand rate and the service rate (or capacity ) over time at the runway system of an airport
Power Systems Engineering Research Center
Power Systems Engineering Research Center PSERC Background Paper What is Reactive Power? Peter W. Sauer Department of Electrical and Computer Engineering University of Illinois at Urbana-Champaign September
Power System review W I L L I A M V. T O R R E A P R I L 1 0, 2 0 1 3
Power System review W I L L I A M V. T O R R E A P R I L 1 0, 2 0 1 3 Basics of Power systems Network topology Transmission and Distribution Load and Resource Balance Economic Dispatch Steady State System
Nuclear Power Plant Electrical Power Supply System Requirements
1 Nuclear Power Plant Electrical Power Supply System Requirements Željko Jurković, Krško NPP, [email protected] Abstract Various regulations and standards require from electrical power system of the
SINGLE-SUPPLY OPERATION OF OPERATIONAL AMPLIFIERS
SINGLE-SUPPLY OPERATION OF OPERATIONAL AMPLIFIERS One of the most common applications questions on operational amplifiers concerns operation from a single supply voltage. Can the model OPAxyz be operated
Maximum Likelihood Estimation of ADC Parameters from Sine Wave Test Data. László Balogh, Balázs Fodor, Attila Sárhegyi, and István Kollár
Maximum Lielihood Estimation of ADC Parameters from Sine Wave Test Data László Balogh, Balázs Fodor, Attila Sárhegyi, and István Kollár Dept. of Measurement and Information Systems Budapest University
MOSFET DEVICE MODELING FOR ANALOG CIRCUITS DESIGN
MOSFET DEVICE MODELING FOR ANALOG CIRCUITS DESIGN Student name: Truong, Long Giang Student #: 970304580 Course: ECE1352F 1. INTRODUCTION The technological trend towards deep sub-micrometer dimensions,
NUCLEAR MAGNETIC RESONANCE. Advanced Laboratory, Physics 407, University of Wisconsin Madison, Wisconsin 53706
(revised 4/21/03) NUCLEAR MAGNETIC RESONANCE Advanced Laboratory, Physics 407, University of Wisconsin Madison, Wisconsin 53706 Abstract This experiment studies the Nuclear Magnetic Resonance of protons
Survey of Harmonics Measurements in Electrical Distribution Systems
Survey of Harmonics Measurements in Electrical Distribution Systems Leon M. Tolbert, Member, IEEE Oak Ridge National Laboratory* P.O. Box 28, Bldg Oak Ridge, TN 3783-6334 Alexandria, VA 2235-3862 Phone:
Email: [email protected]. 2Azerbaijan Shahid Madani University. This paper is extracted from the M.Sc. Thesis
Introduce an Optimal Pricing Strategy Using the Parameter of "Contingency Analysis" Neplan Software in the Power Market Case Study (Azerbaijan Electricity Network) ABSTRACT Jalil Modabe 1, Navid Taghizadegan
Effect of Remote Back-Up Protection System Failure on the Optimum Routine Test Time Interval of Power System Protection
Effect of Remote Back-Up Protection System Failure on the Optimum Routine Test Time Interval of Power System Protection Y. Damchi* and J. Sadeh* (C.A.) Abstract: Appropriate operation of protection system
Effect of Remote Back-Up Protection System Failure on the Optimum Routine Test Time Interval of Power System Protection
Effect of Remote Back-Up Protection System Failure on the Optimum Routine Test Time Interval of Power System Protection Y. Damchi* and J. Sadeh* (C.A.) Abstract: Appropriate operation of protection system
LAB 7 MOSFET CHARACTERISTICS AND APPLICATIONS
LAB 7 MOSFET CHARACTERISTICS AND APPLICATIONS Objective In this experiment you will study the i-v characteristics of an MOS transistor. You will use the MOSFET as a variable resistor and as a switch. BACKGROUND
Characterizing Digital Cameras with the Photon Transfer Curve
Characterizing Digital Cameras with the Photon Transfer Curve By: David Gardner Summit Imaging (All rights reserved) Introduction Purchasing a camera for high performance imaging applications is frequently
Alberta Reliability Standard Cyber Security Configuration Change Management and Vulnerability Assessments CIP-010-AB-1
A. Introduction 1. Title: 2. Number: 3. Purpose: To prevent and detect unauthorized changes to BES cyber systems by specifying configuration change management and vulnerability assessment requirements
EXTREME EVENTS PHASE 2
Public Interest Energy Research (PIER) Program FINAL PROJECT REPORT EXTREME EVENTS PHASE 2 Prepared for: Prepared by: California Energy Commission Pacific Northwest National Laboratory MARCH 2011 CEC-MR-08-03
Generic Reliability Evaluation Method for Industrial Grids with Variable Frequency Drives
Energy and Power Engineering, 2013, 5, 83-88 doi:10.4236/epe.2013.54b016 Published Online July 2013 (http://www.scirp.org/journal/epe) Generic Reliability Evaluation Method for Industrial Grids with Variable
CHARACTERISTICS OF DEEP GPS SIGNAL FADING DUE TO IONOSPHERIC SCINTILLATION FOR AVIATION RECEIVER DESIGN
CHARACTERISTICS OF DEEP GPS SIGNAL FADING DUE TO IONOSPHERIC SCINTILLATION FOR AVIATION RECEIVER DESIGN Jiwon Seo, Todd Walter, Tsung-Yu Chiou, and Per Enge Stanford University ABSTRACT Aircraft navigation
Hybrid processing of SCADA and synchronized phasor measurements for tracking network state
IEEE PES General Meeting, Denver, USA, July 2015 1 Hybrid processing of SCADA and synchronized phasor measurements for tracking network state Boris Alcaide-Moreno Claudio Fuerte-Esquivel Universidad Michoacana
TA Kahraman Yumak ELK412 - Distribution of Electrical Energy Lab. Notes v1.0 2013 Spring web.itu.edu.tr/yumakk. Distance Protection
Distance Protection Announcement: You are not supposed to prepare a pre-report. But there will be an oral examination, so you are strongly advised to study this note regarding to the pre-study questions
Appendix A: Science Practices for AP Physics 1 and 2
Appendix A: Science Practices for AP Physics 1 and 2 Science Practice 1: The student can use representations and models to communicate scientific phenomena and solve scientific problems. The real world
Matching Investment Strategies in General Insurance Is it Worth It? Aim of Presentation. Background 34TH ANNUAL GIRO CONVENTION
Matching Investment Strategies in General Insurance Is it Worth It? 34TH ANNUAL GIRO CONVENTION CELTIC MANOR RESORT, NEWPORT, WALES Aim of Presentation To answer a key question: What are the benefit of
Chapter 11 Monte Carlo Simulation
Chapter 11 Monte Carlo Simulation 11.1 Introduction The basic idea of simulation is to build an experimental device, or simulator, that will act like (simulate) the system of interest in certain important
Calculation of Voltage Sag Indices for Distribution Networks
Calculation of Voltage Sag Indices for Distribution Networks Juan A. Martinez-Velasco, Member, IEEE, Jacinto Martin-Arnedo, Nonmember Abstract This paper is presenting the main results of a work aimed
Transistor Amplifiers
Physics 3330 Experiment #7 Fall 1999 Transistor Amplifiers Purpose The aim of this experiment is to develop a bipolar transistor amplifier with a voltage gain of minus 25. The amplifier must accept input
A Practical Guide to Dielectric Testing
Chroma Systems Solutions, Inc. A Practical Guide to Dielectric Testing 19032 Series Electrical Safety Analyzer & 19050 Series Hipot Tester AC/DC/IR/SCAN Keywords: Dielectric tests, insulation resistance
Developing an Agent-based Backup Protection System for Transmission Networks
Power Systems and Communications Infrastructures for the Future, Beijing, September 2002 Developing an Agent-based Backup Protection System for Transmission Networks X. R. Wang* Member IEEE, K. M. Hopkinson**
Bipolar Transistor Amplifiers
Physics 3330 Experiment #7 Fall 2005 Bipolar Transistor Amplifiers Purpose The aim of this experiment is to construct a bipolar transistor amplifier with a voltage gain of minus 25. The amplifier must
A New Method for Estimating Maximum Power Transfer and Voltage Stability Margins to Mitigate the Risk of Voltage Collapse
A New Method for Estimating Maximum Power Transfer and Voltage Stability Margins to Mitigate the Risk of Voltage Collapse Bernie Lesieutre Dan Molzahn University of Wisconsin-Madison PSERC Webinar, October
Synchronized real time data: a new foundation for the Electric Power Grid.
Synchronized real time data: a new foundation for the Electric Power Grid. Pat Kennedy and Chuck Wells Conjecture: Synchronized GPS based data time stamping, high data sampling rates, phasor measurements
Big Ideas in Mathematics
Big Ideas in Mathematics which are important to all mathematics learning. (Adapted from the NCTM Curriculum Focal Points, 2006) The Mathematics Big Ideas are organized using the PA Mathematics Standards
Step Response of RC Circuits
Step Response of RC Circuits 1. OBJECTIVES...2 2. REFERENCE...2 3. CIRCUITS...2 4. COMPONENTS AND SPECIFICATIONS...3 QUANTITY...3 DESCRIPTION...3 COMMENTS...3 5. DISCUSSION...3 5.1 SOURCE RESISTANCE...3
BJT Characteristics and Amplifiers
BJT Characteristics and Amplifiers Matthew Beckler [email protected] EE2002 Lab Section 003 April 2, 2006 Abstract As a basic component in amplifier design, the properties of the Bipolar Junction Transistor
Overload Protection in a Dual-Corded Data Center Environment
Overload Protection in a Dual-Corded Data Center Environment White Paper 206 Revision 0 by Neil Rasmussen Executive summary In a dual-corded environment, the loss of power on one path will cause the load
EVALUATION OF VOLTAGE STABILITY INDICES BY USING MONTE CARLO SIMULATION
Proceedings of the 4th IASME / WSEAS International Conference on ENERGY & ENVIRONMENT (EE'9) EVALUATION OF VOLTAGE STABILITY INDICES BY USING MONTE CARLO SIMULATION T. RATNIYOMCHAI & T. KULWORAWANICHPONG
Reactive Power and Importance to Bulk Power System OAK RIDGE NATIONAL LABORATORY ENGINEERING SCIENCE & TECHNOLOGY DIVISION
Reactive Power and Importance to Bulk Power System OAK RIDGE NATIONAL LABORATORY ENGINEERING SCIENCE & TECHNOLOGY DIVISION Outline What is Reactive Power and where does it come from? Why is it important?
Modeling and Analysis of DC Link Bus Capacitor and Inductor Heating Effect on AC Drives (Part I)
00-00-//$0.00 (c) IEEE IEEE Industry Application Society Annual Meeting New Orleans, Louisiana, October -, Modeling and Analysis of DC Link Bus Capacitor and Inductor Heating Effect on AC Drives (Part
Market Simulators for Conjoint Analysis
Chapter 10 Market Simulators for Conjoint Analysis The market simulator is usually considered the most important tool resulting from a conjoint analysis project. The simulator is used to convert raw conjoint
Asset Management Business Update
Asset Management Business Update Improvements through Asset Management Mark Davis, Director, Asset Management & AW October 29, 2008 1 From Maintenance to Asset Management Maintain the System -Initial Focus
WINDING RESISTANCE TESTING
WINDING RESISTANCE TESTING WINDING RESISTANCE TEST SET, MODEL WRT-100 ADWEL INTERNATIONAL LTD. 60 Ironside Crescent, Unit 9 Scarborough, Ontario, Canada M1X 1G4 Telephone: (416) 321-1988 Fax: (416) 321-1991
Measurement with Ratios
Grade 6 Mathematics, Quarter 2, Unit 2.1 Measurement with Ratios Overview Number of instructional days: 15 (1 day = 45 minutes) Content to be learned Use ratio reasoning to solve real-world and mathematical
Assessment of power swing blocking functions of line protective relays for a near scenario of the Uruguayan system
Assessment of power swing blocking functions of line protective relays for a near scenario of the Uruguayan system C. Sena, R. Franco, A. Giusto. Instituto de Ingeniería Eléctrica Facultad de Ingeniería
Single Phase UPS Management, Maintenance, and Lifecycle
Single Phase UPS Management, Maintenance, and Lifecycle White Paper 210 Revision 0 by Justin Solis Executive summary How long will my battery last? and what is the best practice for maintaining my UPS?
Scholars Research Library
Available online at www.scholarsresearchlibrary.com Scholars Research Library Archives of Applied Science Research, 2010, 2 (2):380-387 (http://scholarsresearchlibrary.com/archive.html) ISSN 0975-508X
School of Engineering Department of Electrical and Computer Engineering
1 School of Engineering Department of Electrical and Computer Engineering 332:223 Principles of Electrical Engineering I Laboratory Experiment #4 Title: Operational Amplifiers 1 Introduction Objectives
Extreme Events in the Atmosphere
Cover Extreme Events in the Atmosphere Basic concepts Academic year 2013-2014 ICTP Trieste - Italy Dario B. Giaiotti and Fulvio Stel 1 Outline of the lecture Definition of extreme weather event. It is
Simulation and Lean Six Sigma
Hilary Emmett, 22 August 2007 Improve the quality of your critical business decisions Agenda Simulation and Lean Six Sigma What is Monte Carlo Simulation? Loan Process Example Inventory Optimization Example
Chapter 9 Monté Carlo Simulation
MGS 3100 Business Analysis Chapter 9 Monté Carlo What Is? A model/process used to duplicate or mimic the real system Types of Models Physical simulation Computer simulation When to Use (Computer) Models?
Section A. Index. Section A. Planning, Budgeting and Forecasting Section A.2 Forecasting techniques... 1. Page 1 of 11. EduPristine CMA - Part I
Index Section A. Planning, Budgeting and Forecasting Section A.2 Forecasting techniques... 1 EduPristine CMA - Part I Page 1 of 11 Section A. Planning, Budgeting and Forecasting Section A.2 Forecasting
Analysis of Internet Topologies
Analysis of Internet Topologies Ljiljana Trajković [email protected] Communication Networks Laboratory http://www.ensc.sfu.ca/cnl School of Engineering Science Simon Fraser University, Vancouver, British
Title : Analog Circuit for Sound Localization Applications
Title : Analog Circuit for Sound Localization Applications Author s Name : Saurabh Kumar Tiwary Brett Diamond Andrea Okerholm Contact Author : Saurabh Kumar Tiwary A-51 Amberson Plaza 5030 Center Avenue
Basic Electronics Prof. Dr. Chitralekha Mahanta Department of Electronics and Communication Engineering Indian Institute of Technology, Guwahati
Basic Electronics Prof. Dr. Chitralekha Mahanta Department of Electronics and Communication Engineering Indian Institute of Technology, Guwahati Module: 2 Bipolar Junction Transistors Lecture-2 Transistor
A Robustness Simulation Method of Project Schedule based on the Monte Carlo Method
Send Orders for Reprints to [email protected] 254 The Open Cybernetics & Systemics Journal, 2014, 8, 254-258 Open Access A Robustness Simulation Method of Project Schedule based on the Monte Carlo
Optical Fibres. Introduction. Safety precautions. For your safety. For the safety of the apparatus
Please do not remove this manual from from the lab. It is available at www.cm.ph.bham.ac.uk/y2lab Optics Introduction Optical fibres are widely used for transmitting data at high speeds. In this experiment,
A Compact Linac for Proton Therapy Based on a Dielectric Wall Accelerator
UCRL-CONF-236077 A Compact Linac for Proton Therapy Based on a Dielectric Wall Accelerator G. J. Caporaso, T. R. Mackie, S. Sampayan, Y. -J. Chen, D. Blackfield, J. Harris, S. Hawkins, C. Holmes, S. Nelson,
PTC Thermistor: Time Interval to Trip Study
PTC Thermistor: Time Interval to Trip Study by by David C. C. Wilson Owner Owner // Principal Principal Consultant Consultant Wilson Consulting Services, LLC April 5, 5, 5 Page 1-19 Table of Contents Description
Analysis of Internet Topologies: A Historical View
Analysis of Internet Topologies: A Historical View Mohamadreza Najiminaini, Laxmi Subedi, and Ljiljana Trajković Communication Networks Laboratory http://www.ensc.sfu.ca/cnl Simon Fraser University Vancouver,
Use and Application of Output Limiting Amplifiers (HFA1115, HFA1130, HFA1135)
Use and Application of Output Limiting Amplifiers (HFA111, HFA110, HFA11) Application Note November 1996 AN96 Introduction Amplifiers with internal voltage clamps, also known as limiting amplifiers, have
GigaSPEED X10D Solution How
SYSTIMAX Solutions GigaSPEED X10D Solution How White Paper June 2009 www.commscope.com Contents Modal Decomposition Modeling and the Revolutionary 1 SYSTIMAX GigaSPEED X10D Performance MDM An Introduction
itesla Project Innovative Tools for Electrical System Security within Large Areas
itesla Project Innovative Tools for Electrical System Security within Large Areas Samir ISSAD RTE France [email protected] PSCC 2014 Panel Session 22/08/2014 Advanced data-driven modeling techniques
CORRELATION ANALYSIS
CORRELATION ANALYSIS Learning Objectives Understand how correlation can be used to demonstrate a relationship between two factors. Know how to perform a correlation analysis and calculate the coefficient
ENTSO-E Network Code on Emergency and Restoration
ENTSO-E Network Code on Emergency and Restoration Notice 25 March 2015 This Network Code represents ENTSO-E s final proposals in line with the ACER Framework Guidelines on Electricity System Operation
Measuring Electric Phenomena: the Ammeter and Voltmeter
Measuring Electric Phenomena: the Ammeter and Voltmeter 1 Objectives 1. To understand the use and operation of the Ammeter and Voltmeter in a simple direct current circuit, and 2. To verify Ohm s Law for
MATH 140 Lab 4: Probability and the Standard Normal Distribution
MATH 140 Lab 4: Probability and the Standard Normal Distribution Problem 1. Flipping a Coin Problem In this problem, we want to simualte the process of flipping a fair coin 1000 times. Note that the outcomes
Signpost the Future: Simultaneous Robust and Design Optimization of a Knee Bolster
Signpost the Future: Simultaneous Robust and Design Optimization of a Knee Bolster Tayeb Zeguer Jaguar Land Rover W/1/012, Engineering Centre, Abbey Road, Coventry, Warwickshire, CV3 4LF [email protected]
Current and Temperature Ratings
Document 361-1 Current and Temperature Ratings Introduction This application note describes: How to interpret Coilcraft inductor current and temperature ratings Our current ratings measurement method and
CIP 010 1 Cyber Security Configuration Change Management and Vulnerability Assessments
CIP 010 1 Cyber Security Configuration Change Management and Vulnerability Assessments A. Introduction 1. Title: Cyber Security Configuration Change Management and Vulnerability Assessments 2. Number:
An introduction to Value-at-Risk Learning Curve September 2003
An introduction to Value-at-Risk Learning Curve September 2003 Value-at-Risk The introduction of Value-at-Risk (VaR) as an accepted methodology for quantifying market risk is part of the evolution of risk
Positive Feedback and Oscillators
Physics 3330 Experiment #6 Fall 1999 Positive Feedback and Oscillators Purpose In this experiment we will study how spontaneous oscillations may be caused by positive feedback. You will construct an active
Neuro-Dynamic Programming An Overview
1 Neuro-Dynamic Programming An Overview Dimitri Bertsekas Dept. of Electrical Engineering and Computer Science M.I.T. September 2006 2 BELLMAN AND THE DUAL CURSES Dynamic Programming (DP) is very broadly
ANCILLARY SERVICES SUPPLIED TO THE GRID: THE CASE OF THISVI CCGT POWER PLANT (GREECE)
Claudio Cavandoli, Alessandro Crippa EDISON S.p.A., Engineering Department ANCILLARY SERVICES SUPPLIED TO THE GRID: THE CASE OF THISVI CCGT POWER PLANT (GREECE) 1 ANCILLARY SERVICES SUPPLIED TO THE GRID:
COMMISSION STAFF WORKING DOCUMENT EXECUTIVE SUMMARY OF THE IMPACT ASSESSMENT. Accompanying the document
EUROPEAN COMMISSION Brussels, XXX SWD(2014) 18 /2 COMMISSION STAFF WORKING DOCUMENT EXECUTIVE SUMMARY OF THE IMPACT ASSESSMENT Accompanying the document Proposal for a Decision of the European Parliament
Optimization of Asset Management in High Voltage Substation Based on Equipment Monitoring and Power System Operation
Optimization of Asset Management in High Voltage Substation Based on Monitoring and Power System Operation Yotaro Suzui, Hiroi Kojima, Naoi Hayaawa, Fumihiro Endo, Hitoshi Oubo Nagoya University Furo-cho,
Software Project Scheduling under Uncertainties
Copyright Notice: Materials published by Intaver Institute Inc. may not be published elsewhere without prior written consent of Intaver Institute Inc. Requests for permission to reproduce published materials
Switch Mode Power Supply Topologies
Switch Mode Power Supply Topologies The Buck Converter 2008 Microchip Technology Incorporated. All Rights Reserved. WebSeminar Title Slide 1 Welcome to this Web seminar on Switch Mode Power Supply Topologies.
Preliminary Feasibility Assessment For. The Rio Tinto Alcan to BCH Transfer Limit of 460 MW. With 50% Series Compensation on Both KMO KIT lines
Preliminary Feasibility Assessment For The Rio Tinto Alcan to BCH Transfer Limit of 460 MW With 50% Series Compensation on Both KMO KIT lines Report : ASP2010-T001 July 2010 Asset Strategy & Planning,
Probabilistic Risk Assessment Methodology for Criteria Calculation Versus the Standard (Deterministic) Methodology
Probabilistic Risk Assessment Methodology for Criteria Calculation Versus the Standard (Deterministic) Methodology State of Idaho Department of Environmental Quality March 2014 Background The equation
This document should be reviewed at least every two years.
1.0 Change Control Version Date Modification Author(s) Reviews and Approvals by Issue 1 06 August 2007 Initial Document Philip J. Tatro David Wright Issue 2 29 February Removed Confidential from Philip