Models FL3110/FL3111. UV/IR and UV only Flame Detectors. Instruction Manual 09/10
|
|
|
- Willa Walton
- 9 years ago
- Views:
Transcription
1 Models FL3110/FL3111 UV/IR and UV only Flame Detectors The information and technical data disclosed in this document may be used and disseminated only for the purposes and to the extent specifically authorized in writing by General Monitors. Instruction Manual 09/10 General Monitors reserves the right to change published specifications and designs without prior notice. Part No. Revision MANFL3110/11-EU G/09-10
2 Warranty Statement General Monitors warrants the Models FL3110/3111 to be free from defects in workmanship or material under normal use and service within two years from the date of shipment. General Monitors will repair or replace without charge any such equipment found to be defective during the warranty period. Full determination of the nature of, and responsibility for, defective or damaged equipment will be made by General Monitors personnel. Defective or damaged equipment must be shipped to General Monitors plant or representative from which the original shipment was made. In all cases this warranty is limited to the cost of the equipment supplied by General Monitors. The customer will assume all liability for the misuse of this equipment by its employees or other personnel. The customer will assume all liability for the misuse of this equipment by its employees or other personnel. All warranties are contingent upon proper use in the application for which the product was intended and do not cover products which have been modified or repaired without General Monitors approval or which have been subjected to neglect, accident, improper installation or application, or on which the original identification marks have been removed or altered. Except for the express warranty stated above, General Monitors disclaims all warranties with regard to the products sold, including all implied warranties of merchantability and fitness and the express warranties stated herein are in lieu of all obligations or liabilities on the part of General Monitors for damages including, but not limited to, consequential damages arising out of, or in connection with, the performance of the product. Warnings WARNING - Installation and Maintenance must be carried out by suitably skilled and competent personnel only. i
3
4 Table of Contents Page Warranty Statement... i Warnings... i E C Declaration of Conformity in accordance with EC & ATEX Directives... ii Table of Contents... iii 1.0 Introduction General Description Principle of Operation Specifications System Specifications Mechanical Specifications Electrical Specifications Environmental Specifications Modbus RTU Protocol Installation Upon Receipt of Your Equipment Choosing Detector Locations Detector Installation Interconnecting Cable Guidelines Installation Instructions Terminal Connections User Selectable Options Factory Default Settings Maintenance General Maintenance Cleaning the Lenses/Light Rod Sensitivity Check Storage Trouble Shooting Trouble Shooting Chart Spares & Accessories Spare Parts Test Lamps iii
5 7.0 Modbus Serial Communications Baud Rate Data Format Modbus Read Status Protocol (Query/Response) Modbus Write Command Protocol (Query/Response) Exception Responses and Exception Codes FL3110 Command Register Locations FL3110 Operational Mode Command Register Details Customer Satisfaction Questionnaire iv
6 Table of Figures Figure 2 Spectral Response of UV and IR Detectors... 3 Figure 3A-1 FL3110 Horizontal Field of View Figure 3A-2 FL3110 Vertical Field of View Figure 3A-3 FL3111 Horizontal Field of View Figure 3A-4 FL3111 Vertical Field of View Figure 3-B Outline Drawing Figure 3-C Base Assembly with Terminal Block Figure 3-D Strip Length Figure 3-E Relay Outputs Figure 3-F Field Loop Outputs Figure 3-G Front Cap Assembly v
7 1.0 Introduction 1.1 General Description Fire is a phenomenon of combustion. Combustion is the continuous chemical reaction of a reducing agent (fuel) and an oxidizing agent (oxygen, etc.) with the evolution of thermal energy (heat). Fire is usually manifested in heat (IR), smoke, light (visible), and flame (UV). Flame is the gaseous region of a fire where vigorous combustion chain reactions take place. These reactions emit radiation covering the Infrared, Ultraviolet and the Visible Spectral Regions. The General Monitors Model FL3110 is an Ultraviolet/Infrared (UV/IR) Flame Detector. It detects the Ultraviolet and Infrared spectral regions of the flame to produce a system which is highly immune to false alarms caused by lightning, arc-welding, hot objects, and other sources of radiation. The Model FL3111 is an Ultraviolet (UV) flame detector. It only responds to UV and has been optimised for speed of response. The Models FL3110 and FL3111 features include: Compact unitised design. Continuous optical path monitoring. Wide field of view. High false alarm immunity. 0-20mA, Relays, Field Loop and Modbus RTU RS-485 serial communications output versions. Visual indicators. Stainless Steel body with integral mounting bracket. Rated for continuous 90 C operation. 1
8 1.2 Principle of Operation UV Detector FL3111 The Model FL3111 is a Flame Detector, which contains an ultraviolet phototube that responds to Ultra-Violet (UV) radiation in the 185 to 260 nanometer region (Figure 2). When radiation from a flame reaches the cathode plate within the UV detector tube, electrons are ejected from the cathode plate. These electrons are accelerated towards the positively charged anode of the tube. They collide with molecules of an ionisable gas, with which the tube is filled. This emits more electrons and produces an avalanche condition. More electrons are released which creates a momentary electron flow from the cathode to the anode. This momentary current (pulse) recurs at a rate proportional to the intensity of the UV radiation. The Flame Detectors process these UV signals with a microcomputer and, depending on the version, produces the following outputs: 0 to 20 milliampere signal. Immediate WARN relay contacts. Time delayed ALARM relay contacts. FAULT relay contacts. RS-485 MODBUS RTU serial communications ports. (See Sections 2 & 3 for more information on detector outputs) 2
9 Ultraviolet Region Visible Region Infrared Region Relative Energy UV Detector's Spectral Sensitivity Sun's Radiation Reaching the Earth IR Detector's Spectral Sensitivity 185nm 260nm 4.35um Wavelength Figure 2 Spectral Response of UV and IR Detectors UV/IR Flame Detector FL3110 The Model FL3110 is a discriminating UV/IR Detector, which makes use of an ultraviolet radiation sensitive phototube in addition to an infrared detector (see figure 2). This combination provides a flame detection system, which is highly immune to false alarms. The UV portion of the detector, as described in UV Detector, is combined with an infrared detector, which reacts to changes in the intensity of infrared radiation. By sensing very specific wavelengths in both the UV and IR spectra and then processing these signals with a microcomputer, a very high degree of discrimination is achieved. Incorporated in the IR circuitry is a flicker discrimination circuit. This permits the detector to ignore steady IR sources such as hot objects. The inherent flickering of flame provides the necessary modulation to activate the IR circuit. Since a flame is a copious source of both ultraviolet and infrared radiation, discrimination is provided when both UV and IR emissions are detected. If only UV is detected, as in the case of arc welding, no alarm is given. If only IR is detected, such as a large modulating hot object, no alarm is given. However, if both conditions are met in the correct combination and intensity, as determined by an algorithm in the microcomputer, a fire is identified and the alarm outputs are activated. 3
10 COPM Circuitry A self-testing feature called Continuous Optical Path Monitoring (COPM) checks the optical path, the detector(s), and the related electronic circuitry once every minute. If foreign material impairs the optical path of the UV detector tube (both Models FL3110 and FL3111) or infrared detector (Model FL3110 only) for two consecutive checks, the unit will indicate FAULT. The optical FAULT outputs are, depending on the version, a 2.0 ma signal or deenergizing of the FAULT relay. The FAULT status is available via the RS-485 serial communications port. (see Section 3-6 Terminal Connections). After a COPM FAULT, a COPM check is performed every ten seconds until the obstruction is removed. Then the COPM check will resume checking once per minute check. WARNING Dirty or partially blocked windows can significantly reduce the detector s field of view and detection distance. NOTE: Since the optical path is checked once per minute and it requires two check failures to produce a FAULT, it may take up to two minutes for the unit to detect an obstruction. Alarm Test The Model FL3110 and FL3111 Flame Detector s have a built-in Alarm Test feature. This test may be activated via the serial communications port (see Section 3-6 Terminal Connections). The Flame Detectors will immediately go into WARN and then into time delayed ALARM. After two to ten seconds the Flame Detectors will activate the ALARM. A latching WARN and/or ALARM will remain latched until reset. Visual Indicators Two light emitting diodes (LEDs) are visible through the IR window. LEDs are provided for a visual indication that corresponds with the detector s outputs. The following blinking sequence indicates the operating condition: Timeout (10 seconds when the unit is first powered) Green and red LEDs blinking alternately. Ready Green LED that flashes off 1 second, every 5 seconds. WARNING Slow blinking red LED. ALARM Fast blinking red LED. COPM FAULT Slow blinking green LED. Low Voltage FAULT Fast blinking green LED. 4
11 2.0 Specifications 2.1 System Specifications Certification*: EExed IIC T4 T135-40ºC to +90ºC (-40ºF to +194ºF) EExed IIC T5 T100-40ºC to +75ºC (-40ºF to +167ºF) IP66/67 FL3110 only: Bureau Veritas Rules for the Classification of Steel Ships EN54-10:2002 (4-20mA only, Relays and Relays + EOL versions) IR Detector centre wavelength: 4.35 microns UV Detector Pass Band: 185 to 260 nanometres Typical Alarm Activation Response Times*: FL3110< 3 50 ft. (15.2m) FL3111< 1 50 ft. (15.2m) Minimum Detector Response Times: FL3110< 500 ms. FL3111< 100 ms. Field of View*: (Figure 3-A) FL maximum conical FL maximum conical Sensitivity: 50 feet (15.2m); Maximum distance for a 1 square foot (.092m 2 ) gasoline fire to be reliably detected. Maximum Cable Parameters: 4-20mA Output Signal 9000 feet (2750 m), maximum 50 Ohms loop, with maximum 250 Ohms input impedance of readout unit. Remote power supply 3000 feet (930 m), maximum 20 Ohms loop and 24 VDC minimum. (See Section 3-4 Terminal Connections) Approvals: ATEX & CE Mark FL3110 only: Bureau Veritas Warranty: Two Years * NOTE: 1. Response Times and Field of View data have been derived by testing the Models FL3110 /FL3111 Flame Detectors with a 1 square foot gasoline fire. One cup of unleaded gasoline on top of a one inch layer of water was ignited for each test. These are typical values and different results may occur depending on the variation of each fire. 2. To meet the directional dependence requirements of EN the horizontal viewing angle must not exceed ±30. 5
12 2.2 Mechanical Specifications Enclosure material Material: Stainless Steel 316 Colour: Natural Dimensions: Diameter 3.3 in (8.4 cm) Length 5.4 in (13.7 cm) Weight 5lbs (2.3 kg) Cable Entries: 2 x M Electrical Specifications Supply voltage range: Nominal supply voltage: Maximum supply current: Maximum output signal 24 VDC: Output signal range: FAULT signal: COPM fault signal: Ready signal: WARN signal: ALARM signal: 20 to 36 VDC 24VDC 150mA 600 Ohms 0 to 20mA 0 to 0.2mA 2.0mA ± 0.2 ma 4.0 ± 0.2 ma 16.0 ± 0.2 ma 20.0 ± 0.2 ma Relay Contact Ratings: 1A 30VRMS/42.2 VPK, Resistive. RS-485 Serial Communications Port: Modbus RTU Protocol 128 units MAX. (247 units with repeaters) Baud Rate: 2400, 4800, 9600 or RFI/EMI Protection Complies with EN50270, Type 2 Status Indicator: Two LEDs indicate status, fault conditions. 6
13 2.4 Environmental Specifications Operating temperature range: -40 C to 90 C -40 F to 194 F Storage temperature range: -40 C to 90 C -40 F to 194 F Humidity range: 0 to 100% RH non-condensing 2.5 Modbus RTU Protocol For detailed information on data format, read commands, write commands, register details, and register locations refer to the Serial Communications section in this manual. 7
14 3.0 Installation WARNING - Installation and Maintenance must be carried out by suitably skilled and competent personnel only. 3.1 Upon Receipt of Your Equipment All items shipped by General Monitors are packed in shock absorbing containers which affords a considerable degree of protection against physical damage. When received, the contents should be carefully removed and checked against the enclosed packing slip. All subsequent correspondence with General Monitors must specify the equipment part number and serial number. 3.2 Choosing Detector Locations Several variables are involved in selecting the locations in which to install detectors to ensure proper flame detection. There are no hard and fast rules defining the optimum location. There are some general suggestions that should be considered in regard to particular conditions at the site where the unit(s) is being installed: Detector Field of View Each Model FL3110 and FL3111 Flame Detector have a maximum cone of vision of 120º. This Cone has its vertex at the center of the detector (see figure 3A-1, 3A-2, and 3A-3). Optical Sensitivity Range The distance at which the detector will respond to a flame is a function of the intensity of that flame. The maximum distance is 50 feet (15.2m) for a gasoline fire with a surface area of 1 square foot (0.92m 2 ). 8
15 Environmental Factors 1. Mounting should be as free from shock and vibration as possible and convenient for visual inspection and cleaning. 2. Detectors mounted in dirty atmospheric conditions will require more frequent inspection, cleaning, and sensitivity checking. 3. Observe the ambient temperature range for the specific model (see section 2-4 Environmental Specifications). For outdoor installations or other areas exposed to intense, direct solar radiation, the detector may reach temperatures well above specifications. For this condition, a cover for shade may be required to bring the detector temperature within specifications. As with any cover or object nearby, make sure the field-of-view of the detector is not obstructed. 4. Avoid conditions of ice build up on the optical detector windows: complete icing over of the detector windows can result in fault conditions. 5. Mount away from possible sources of electrical noise. 6. A constant UV source detected by the unit will cause the FL3110 unit to go into FAULT after 9-10 minutes of exposure. Source must be removed or detector repositioned. (UV detectors can pick-up arc welding up to 2-3 miles away). 7. Users should be aware that any UV detector may be triggered by other sources of EMI, for instance X-rays, sunlight, reflected sunlight, Gamma rays, lightning, arc welding, industrial lighting, fluorescent lighting, etc., and due regard should be paid to the possible presence of such radiation. 3.3 Detector Installation The Model FL3110/3111 Detectors should be mounted tilting downwards so that dust/moisture will not accumulate on the windows. (The detector(s) should be mounted in locations which will avoid either people or objects from obscuring the detector s Cone of Vision.) Cable glands and stopping plugs should be installed with the o-rings supplied with the flame detector. It is recommended to fit boots over cable glands to prevent water ingress at the cable-to-gland junction. Mounting hardware should be used as shown in figure 3-B. The overall dimensions of the detector and mounting hardware is also shown. 9
16 3.4 Interconnecting Cable Guidelines The flame detector requires an interconnecting cable with an overall screen (shield) and armour. Cables to BS5308 Part 2, Type 2 or equivalent are suitable. Interconnecting cables should be segregated from power and other noisy cables. Avoid proximity to cables associated with radio transmitters, welders, switched mode power supplies, inverters, battery chargers, ignition systems, generators, switch gear, arc lights and other high frequency or high power switching process equipment. In general, maintain a separation of at least 1m between instrument and other cables. Greater separation is required where long parallel cable runs are unavoidable. Avoid running instrument cable trenches close to lightning conductors earthing pits. Complete all cable insulation tests before connecting the cable at either end. General Monitors do not recommend the use of cable shoes or crimps on any junction box or housing wiring terminals. Poor crimping can cause bad connection when unit experiences temperature variations. We therefore recommend that it is good practice to just terminate the cable. 3.5 Installation Instructions FL3110/3111 Cable Termination The flame detector should be installed in accordance with the certification documents and the relevant regulations of the country concerned. Ensure that approved Exe cable glands are used and installed according to the manufacturer s instructions. The cable armour must be terminated in the gland to ensure a positive electrical connection. The cable screens (drain wires) must not be connected electrically to the electronic circuitry of the flame detector. Connect Safety Earth to the chassis grounding screw available on the rear exterior of the base assembly. This Safety Earth wire should have a wire gauge of at least 22 AWG (0.33mm 2 ) and be no longer than 3 meters in length Cable Termination in Safe Area The cable armour must be connected to Safety Earth. The cable screens (drain wire) and power supply return (OV) must be connected to Instrument Earth. The power supply or power distribution system employed should meet the requirements of EN /2 and EN
17 FL3110 Horizontal Field of View ft 40 ft ft ft 10 ft ft FL % Horizontal FL % Horizontal FL % Horizontal Figure 3A-1 FL3110 Horizontal Field of View FL3110 Vertical Field of View ft 40 ft ft 20 ft ft ft FL % Vertical FL % Vertical FL % Vertical Figure 3A-2 FL3110 Vertical Field of View 11
18 FL3111 Horizontial Field of View ft 40 ft ft ft 10 ft ft FL % Horizontal FL % Horizontal FL % Horizontal Figure 3A-3 FL3111 Horizontal Field of View FL3111 Vertical Field of View ft 40 ft 30 ft 20 ft 10 ft ft FL % Vertical FL % Vertical -15 FL % Vertical Figure 3A-4 FL3111 Vertical Field of View 12
19 Figure 3-B Outline Drawing 13
20 Figure 3-C Base Assembly with Terminal Block 3.6 Terminal Connections The Terminal Block is located on the Base Assembly (See figure 3-C) and accepts 12 AWG (3.31 mm 2 ) to 22 AWG (0.33 mm 2 ) stranded or solid core wire. Each wire should be stripped as shown in figure 3-D. Figure 3-D Strip Length Four of the six positions on the terminal block have functions which depend on the FL3110/3111 version selected. The remaining two positions are reserved for the power connections. Figure 3-C outlines the terminal block connections by version. On both this and the following pages is a description and specification for each of the signals shown in figure 3-C. 14
21 POWER INPUTS +B and 0V These are the power connections. The supply voltage range is 20 to 36 VDC at the detector (low voltage is detected at 18.5 VDC). The following maximum cable lengths apply for a +24VDC supply (maximum 20 ohm loop): ANALOGUE OUTPUT 4 20mA AWG mm 2 FEET METRES 14 AWG AWG AWG AWG AWG The 4 to 20mA output is a current signal that corresponds to the following specification: FAULT signal: COPM Fault signal: Ready signal: WARN signal: ALARM signal: Output Load Max.: 0 to 0.2mA 2.0 ± 0.2mA 4.0 ± 0.2mA 16.0 ± 0.2mA 20.0 ± 0.2mA 600 ohms For interfacing with 250 ohm input impedance devices, the following maximum cable lengths apply (maximum 50 ohm loop): AWG mm 2 FEET METRES 14 AWG AWG AWG AWG AWG COMMUNICATIONS OUTPUTS DATA 1A DATA 1B DATA 2A DATA 2B These are the connections for the RS-485 serial communications ports 1 & 2. The RS-485 connection is used to either query the unit s status or to configure the unit. See Section 7 for detailed information on Modbus RTU protocol. 15
22 RELAY OUTPUT (Figure 3-E) A1 ALM Description: This connection is the WARN relay contact. The WARN output is immediate and can be normally energised or normally de-energised, latching or non-latching. WARN relay contact rating is 30VRMS/42.2VPK Resistive. A2 ALM Description: This connection is the ALARM relay contact. The ALARM output is time delayed for 2, 4, 8 or 10 seconds. The ALARM output can be normally energised or normally de-energised, latching or non-latching. ALARM relay contact rating is 30VRMS/42.2VPK Resistive. FAULT Description: This connection is the FAULT relay contact. The FAULT output configuration is normally energised and non-latching. This is the standard output configuration and it cannot be changed. The FAULT circuit will be activated during the time-out function, a low power or loss of power condition, and during a failed COPM check. During these conditions the FAULT relay will de-energise and the analogue output signal will drop to 0 ma (2mA for COPM Faults) for the duration of the FAULT. FAULT relay contact rating is 30VRMS/42.2VPK Resistive. COMM Description: This is the common connection of the WARN, ALARM and FAULT relay contacts. Figure 3-E Relay Outputs 16
23 FIELD LOOP OUTPUTS (Figure 3 F) LP+ and LP- Description: These are the field loop connections to a fire card such as General Monitors IN042. The FAULT relay, when energised, inserts a 5600ohms, 2Watt End-Of-Line resistor across these connections. The ALARM relay, when energised, inserts a 560ohms, 2Watt resistor across the End-Of- Line resistor. The WARN relay has no effect. For a description of relay functionality refer to the section RELAY OUTPUTS above. Figure 3-F Field Loop Outputs RESET All versions may be reset by interrupting the power supply for a minimum of two seconds. Versions with serial communications can also be reset by using the Remote Reset command. Refer to section 7 for details. SAFETY EARTH This connects the FL3110/3111 enclosure to Safety Earth. An alternative connection is available on the rear exterior of the base assembly. The Safety Earth wire should have a wire gauge of at least 22 AWG (0.33mm 2 ) and be no longer than 3 meters in length. WARNING: Under no condition should the retaining strap screws be used for Safety Earth purposes 3.7 User Selectable Options All user selectable option settings on the Model FL3110/3111 are held in EEPROM. It is recommended the option settings be specified when ordering. Versions with serial communications capabilities can be (re)programmed via the communications port(s). Refer to section 7 for details. Other versions can be (re)programmed with the Program Card accessory if necessary. PROGRAM CARD ACCESSORY The Program Card is a small module with a DIP switch which can be read by the FL3110/3111 microprocessor. DIP switch positions 5 to 8 select the options being programmed, such as Sensitivity and Alarm-time-delay, Relay or Return to Factory Default settings. DIP switch positions 1 to 4 determine the actual parameter settings. Refer to the following tables for details: 17
24 SENSITIVITY and ALARM-TIME-DELAY Options Sensitivity (%) Alarm-time-delay (sec) DIP OFF OFF ON ON 2 OFF ON OFF ON 3 OFF OFF ON 4 OFF ON OFF 5 OFF OFF OFF OFF OFF OFF OFF 6 OFF OFF OFF OFF OFF OFF OFF 7 ON ON ON ON ON ON ON 8 ON ON ON ON ON ON ON WARN and ALARM Relay Options WARN (1) Relay ALARM (2) Relay DIP LA NL EN DE LA NL EN DE 1 ON OFF 2 ON OFF 3 ON OFF 4 ON OFF 5 OFF OFF OFF OFF OFF OFF OFF OFF 6 OFF OFF OFF OFF OFF OFF OFF OFF 7 OFF OFF OFF OFF OFF OFF OFF OFF 8 ON ON ON ON ON ON ON ON LA = Latching EN = Energised NL = Non Latching DE = De-Energised The above options have been represented pictorially on the label attached to the Program Card Return to FACTORY DEFAULT settings DIP Default 5 ON 6 ON 7 OFF 8 ON DIP switch positions 1 to 4 are not relevant here 18
25 WARNING: During the following steps proper anti-static procedures must be observed. Failure to do so may permanently damage the FL3110/3111 electronic circuits and void the warranty. To (re)program, remove the detector from the Base Assembly, disconnect the fly-lead and disconnect the retainer strap at the rear of the Base only. 1. Refer to figure 3-G and remove the five screws securing the front cap assembly to the enclosure. 2. Remove the front cap assembly. 3. Disconnect the fly-lead connector from the power supply board. 4. Insert the Program Card with the required DIP switch settings into connector J3 on the microprocessor board. 5. Apply +24VDC to connector J3 pins 1 and 2, as shown in the figure, for a minimum of five seconds. This step allows the microprocessor to read the DIP switch settings on the Program Card. 6. Disconnect the +24VDC power supply. If more programming is required, adjust the DIP switch settings and re-apply +24VDC for a minimum of five seconds. Steps 4 to 6 may be repeated as required. When programming is completed, remove the +24VDC power supply and the Program Card. 7. Inspect the o-ring on the front cap assembly for damage and the flame path surfaces for contamination. If necessary replace or clean and re-apply a suitable grease to the o-ring and flame path surfaces. 8. Reconnect the fly-lead connector to the power supply board. Insert the front cap assembly into the enclosure, ensuring the o-ring does not snag and secure with the five screws. Inspect the o-ring on the Base assembly for damage and the corresponding surfaces for contamination. If necessary clean or replace and re-apply a suitable grease to the o-ring and corresponding surfaces. Reconnect the retainer strap at the rear of the Base assembly and reconnect the fly-leads as shown in figure 3-C. Mount the detector on the Base assembly ensuring the o-ring does not snag. 3.8 Factory Default Settings Return to Factory Default settings only affects FL3110/3111 versions with serial communications capabilities. It provides a mechanism to restore the communications parameters, should they be unknown or corrupted. The Factory Default settings are: Parameter Setting Address 1 (Decimal) Baud Rate Data Format 8-N-1 Refer to section 7 for details 19
26 Figure 3-G Front Cap Assembly 20
27 4.0 Maintenance WARNING Installation and Maintenance must be carried out by suitably skilled and competent personnel only. 4.1 General Maintenance Once correctly installed, the unit requires very little maintenance other than regular sensitivity checks and cleaning of the lenses, light rod and reflector. General Monitors recommends that a schedule be established and adhered to. Warning: Disconnect or inhibit external devices, such as automatic extinguishing or fire suppression systems before performing any maintenance. 4.2 Cleaning the Lenses/Light Rod A clean, soft, lint-free cloth, tissue or cotton swab should be used to apply the cleaning solution. Do not touch the lenses with fingers. a) Wet the lenses with the solution. b) Rub with a dry, unsoiled cloth until clean. c) Completely dry the lenses. d) Repeat steps a, b and c for the reflector and light rod. NOTE: The removal of particulate matter and any film build-up on the lenses, lightrod and reflector is necessary to ensure proper sensitivity of the system. It is recommended that the lens and reflector be cleaned at least every 30 days or more often if the detector is located in a particularly dirty environment. Warning: A dirty or partially blocked lens can significantly reduce the detector s field of view and detection distance DO NOT USE A COMMERCIAL GLASS CLEANER OTHER THAN INDUSTRIAL STRENGTH WINDEX with Ammonia D : The UV lens material is quartz, the IR lens material is sapphire. The cleaning solution should be General Monitors P/N (Industrial Strength Windex with Ammonia D). 21
28 4.3 Sensitivity Check To verify that each detector is functioning correctly, a General Monitors Test Lamp and/or the ALARM TEST function should be used. For the Model FL3110 (UV/IR) the General Monitors Model TL103 Test Lamp is recommended. For the Model FL3111 (UV only) the General Monitors Model TL100 Test Lamp is recommended. Alarm Test The Models FL3110 and FL3111 Flame Detectors have a built-in Alarm Test feature. The user can test the alarm outputs of the Flame Detector by activating the Alarm Test feature via serial communications. The Flame Detector will immediately go into WARN and then into the time delayed ALARM. After two to ten seconds the Flame Detector will reset the non-latching WARN and/or ALARM. A latching WARN and or/ ALARM will remain latched until manually reset. If the Flame Detector does not respond to the sources, it will output a FAULT condition and will retest every ten seconds, as in the COPM FAULT case. See section 6, Spares & Accessories for details on test lamps. 4.4 Storage These Flame Detectors should be stored in a clean, dry area and within the temperature and humidity ranges quoted in Section 2-4 Environmental Specifications. 22
29 5.0 Trouble Shooting WARNING - Installation and Maintenance must be carried out by suitably skilled and competent personnel only. 5.1 Trouble Shooting Chart This section is intended to be a guide in correcting problems which may arise in the field. This section is not all-inclusive, and General Monitors should be contacted for assistance if the corrective actions listed do not eliminate the problem. If equipment or qualified personnel required for various tests are not available it is recommended that the defective unit be returned to General Monitors for repair. A complete written description of the problem should be included. Be sure to inhibit or disconnect external alarm wiring before making any checks which might send the unit into alarm, if an alarm condition will create problems. NOTE: If the equipment is under warranty, any repairs performed by persons other than General Monitors authorised personnel may void the warranty. Please read the warranty statement carefully. PROBLEM POSSIBLE CAUSE CORRECTIVE ACTION No output signal and green No DC Power to the Unit Be sure the +24 VDC is applied LED in IR window is off. with the correct polarity. No output signal and green LED in IR window is rapidly blinking. 2mA signal and green LED in IR window is slowly blinking. Constant 8mA signal with no known radiation to detector (FL3110 only). Constant 12mA signal with no known radiation to detector (FL3110 only). Constant 16mA or 20mA signal (WARN or ALARM) with no known radiation at detector (FL3111 only). Low voltage FAULT (voltage at unit less than +18VDC). COPM FAULT, dirty or obscured optical path (UV or IR window) Background IR radiation at detector. Background UV radiation at detector. Background UV radiation at detector. Be sure that the unit is powered with at least +20VDC under load. Clean UV and IR window and source light rod. Cover IR portion of FL3110 for ten seconds to determine if there is background IR. If there is, remove IR Radiation source or change FL3110 location. If there is no background IR, replace IR detector in FL3110. Cover UV portion of FL3110 for ten seconds to determine if there is background UV. If there is, remove UV radiation source or change FL3110 location. If there is no background UV, replace UV detector tube in FL3110. Cover UV portion of FL3111 for ten seconds to determine if there is background UV. If there is, remove UV radiation source or change FL3111 location. If there is no background UV, replace UV detector tube in FL
30 6.0 Spares & Accessories 6.1 Spare Parts When ordering Spare Parts and/or Accessories please contact your nearest General Monitors Representative or General Monitors directly and give the following information. DESCRIPTION PART NR Instruction Manual MANFL3110/11 UV Source UV Detector IR Detector TL100 Test Lamp TL100 Test Lamp 110V Charger Lamp, IR Source Program Card High Vacuum Grease, 150g Tube TL105 UV/IR Test Lamp TL FL3110 TL105 UV/IR Test Lamp TL FL3111 Window Cleaning Solution Test Lamps TL100 UV Test Lamp The General Monitors TL100 Test Lamp is a portable, rechargeable source of ultra-violet radiation, specifically designed to use in testing UV flame detection systems. It emits a wide band of radiation and specifically covers the 185 to 260 nanometer region which corresponds with the response of most ultraviolet flame detectors. The test lamp is CSA certified intrinsically safe for Class I, Division 1, Groups C and D and therefore does not require an explosion-proof housing. To avoid damaging exposure to ultraviolet radiation, the TL100 provides a Power On indicator so that direct viewing is not necessary. Insert the charging plug into the receptacle. Complete recharging takes a minimum of fourteen hours. TL100 Operating Instructions The TL100 has two intensity levels, LO and HI, indicated on the rocker switch label. With the switch in the HI position, the Test Lamp is capable of activating General Monitors UV flame detection systems at distance up to 40 feet (12 meters) from the detector. The LO switch will activate the system at distances up to 20 feet (6 meters). To operate the Test Lamp switch, aim it directly at the detector to be tested and activate the desired intensity level. The ON LED (green) should light, indicating Power On and the Low Battery (red) should remain off, indicating a sufficient charge for normal operation. The response of the system will depend on the distance from the detector, as well as the sensitivity and /or time-delay settings at the control module. If the system is operating normally, it will respond immediately upon activating the TL100. If the TL100 remains ON for the time period set by the Time Delay adjustment, the flame detector and the control module will go into ALARM. If the low battery LED (red) is illuminated, the batteries are nearing discharge, however there is a built-in battery reserve of approximately 15 minutes. It is recommended that the batteries be charged as soon as possible after this period. Do not allow the unit to remain in a discharged state. 24
31 NOTE - Recharging the TL100 must be done in a non-hazardous area. Recharging the batteries is required whenever the Low Battery LED (red) is illuminated. Plug the charger into a suitable outlet and insert the charging plug into the charging receptacle located on the back end of the Test Lamp. Fourteen to sixteen hours are required for a complete charge: although overcharging for up to twenty-four hours is tolerable, it will reduce battery life and is not recommended. If the TL100 is not used for an extended period of time, it is recommended that it be charged bimonthly to prevent excessive discharge. Batteries may be recharged an average of 500 times. TL103 UV/IR Test Lamp The General Monitors TL103 Test Lamp is a battery operated, rechargeable, test source specifically designed to test General Monitors UV, UV/IR, and Digital Frequency IR Flame Detection Systems. It consists of a high-energy broad band radiation source which emits sufficient energy in both the Ultraviolet and Infrared spectra to activate UV and/or IR detectors. To simulate a fire, the test lamp automatically flashes at one of three DIP switch selectable rates. The Model TL103, rated explosion-proof, is CSA certified for use in Class I, Division 1, Groups C and D areas. The test lamp operates on internal lead-acid batteries which, when fully charged, will operate continuously for 25 to 30 minutes. An internal circuit will prevent operation when the batteries are low. TL103 Operating Instructions It is always important to start a series of TL103 checks with a fully charged unit. Stand within 20 feet (FL3110/3111) or within 35 feet (FL3111) of the unit to be tested and aim the TL103 squarely into the detector face. Shaking the lamp from side to side or up and down will increase the simulation of flame flicker, and improve the response of the flame detector to the lamp. If the system is operating normally, the detector will go into a WARNING condition after a few flashes of the Test Lamp. If the lamp remains ON for the timedelayed period of the DIP switch setting, the detector will go into ALARM. To conserve charge, do not operate the Test Lamp longer than is necessary to test each detector. When the battery level drops below the level required maintaining the proper intensity of the lamp, an internal low voltage circuit will shut the lamp off until the batteries have been recharged. TL103 Recharging Instructions Insert the charging plug into the receptacle. Complete recharging takes a minimum of fourteen hours. A schedule should be established and followed. WARNING: Replace the knurled plug after charging is complete. Charging must be carried out in a non-hazardous area. The charging receptacle is located inside the housing adjacent to the ON button. To gain access, it is necessary to unscrew the gnarled plug from the body of the unit. The plug is secured to the ON button by a safety strap to keep it from being lost. It is recommended that the TL103 be kept on charge when not in use to prevent excessive battery discharge. The batteries may be charged an average of 500 times and the battery pack is replaceable. TL105 UV/IR Test Lamp Please refer to the TL105 Test Lamp manual for operating instructions 25
32 7.0 Modbus Serial Communications 7.1 Baud Rate The Baud Rate is a selectable setting via the Modbus Communications Interface. The selectable baud rates are 19200, 9600, 4800 or 2400 bits per second. 7.2 Data Format The Data Format is a selectable setting via the Modbus Communications Interface. The selectable data formats are as follows: Data Bits Parity Stop Bit Format 8 None 1 8-N-1 8 Even 1 8-E-1 8 Odd 1 8-O-1 8 None 2 8-N Modbus Read Status Protocol (Query/Response) Modbus Read Query Message Byte Modbus Range Referenced to FL3110/ st Slave 1-247* (Decimal) ID (Address 2 nd Function Code 03 Read Holding Registers 3 rd Register Address Hi** 00 Not Used 4 th Register Address Lo** 00-FF (Hex) Command Registers 5 th No. of Registers Hi 00 Not Used 6 th No. of Registers Lo 01 No. of 16 Bit Registers 7 th CRC Lo 00-FF (Hex) CRC Lo Byte 8 th CRC Hi 00-FF (Hex) CRC Hi Byte * Note: Address 0 is reserved for broadcast mode and will not be supported at this time. ** Note: Register Address can be a maximum of 9999 Address Locations ( E) 26
33 7.3.2 Modbus Read Response Message Byte Modbus Range Referenced to FL3110/ st Slave Address 1-247* (Decimal) ID (Address) 2 nd Function Code 03 Read Holding Registers 3 rd Byte Count 02 No. of Data Bytes 4 th Data Hi 00-FF (Hex) Hi Byte Status Data 5 th Data Lo 00-FF (Hex) Lo Byte Status Data 6 th CRC Lo 00-FF (Hex) CRC Lo Byte 7 th CRC Hi 00-FF (Hex) CRC Hi Byte * Note: Address 0 is reserved for broadcast mode and will not be supported at this time 7.4 Modbus Write Command Protocol (Query/Response) Modbus Write Query Message Byte Modbus Range Referenced to FL3110/ st Slave Address 1-247* (Decimal) ID (Address) 2 nd Function Code 06 Preset Single Register 3 rd Register Address Hi** 00 Not used 4 th Register Address Lo** 00-FF (Hex) Command Registers 5 th Preset Data Hi 00-FF (Hex) Hi Byte Command Data 6 th Preset Data Lo 00-FF (Hex) Lo Byte Command Data 7 th CRC Lo 00-FF (Hex) CRC Lo Byte 8 th CRC Hi 00-FF (Hex) CRC Hi Byte * Note: Address 0 is reserved for broadcast mode and will not be supported at this time. ** Note: Register Address can be a maximum of 9999 Address Locations ( E) Modbus Write Response Message Byte Modbus Range Referenced to FL3110/ st Slave Address 1-247* (Decimal) ID (Address) 2 nd Function Code 06 Preset Single Register 3 rd Register Address Hi **00 Not used 4 th Register Address Lo**00-FF (Hex) Command Register 5 th Preset Data Hi 00-FF (Hex) Hi Byte Command Data 6 th Preset Data Lo 00-FF (Hex) Lo Byte Command Data 7 th CRC Lo 00-FF (Hex) CRC Lo Byte 8 th CRC Hi 00-FF (Hex) CRC Hi Byte * Note: Address 0 is reserved for broadcast mode and will not be supported at this time. ** Note: Register Address can be a maximum of 9999 Address Locations ( E) 27
34 7.4.3 Function Codes Supported Function Code 03 (Read Holding Registers) will be used to read status from the slave unit. Function Code 06 (Preset Single Register) will be used to write a command to the slave unit. 7.5 Exception Responses and Exception Codes In a normal exchange, the master device sends a query to the FL3110/3111. The FL3110/3111 receives the query and returns a normal response to the master. If a communications error occurs, the FL3110/3111 will return an exception response Exception Responses Byte Modbus Range Referenced to FL3110/ st Slave Address 1-247* (Decimal) ID (Address) 2 nd Function Code 83 or 86 (Hex) MSB is set with Function Code 3 rd Exception Code (Hex) Appropriate Exception Code (See below) 4 th CRC Lo 00-FF (Hex) CRC Lo Byte 5 th CRC Hi 00-FF (Hex) CRC Hi Byte Function Code Field: In a normal response, the FL3110/3111 echoes the function code of the original query in the function code field of the response. All the Function Codes have a most-significant bit (MSB) of zero (0). In an exception response, the FL3110/3111 sets the MSB of the function code to a one (1). With the function code s MSB set, the master can recognise the exception response and can process the data field for the exception code from the FL3110/3111 response message. Exception Code Field: In a normal response, the FL3110/3111 returns data and status in the data field, which was requested in the query from the master. In an exception response, the FL3110/3111 returns an exception code in the data field, which describes the FL3110/3111 condition that caused the exception. On the following page is a list of exception codes that are supported by the FL3110/3111: 28
35 Code Name Description 01 Illegal Function The function code in the query is not an allowable action for the FL3110/ Illegal Command The command register address received in Register Address query is not an allowable command address for the FL3110/ Illegal Data Value A value contained in the query data field is not an allowable value for the FL3110/ Slave Device Failure An unrecoverable error occurred while the FL3110/3111 was attempting to perform the requested action. 05 Acknowledge The FL3110/3111 has accepted the request and is processing it, but a long duration of time will be required to do so. This response is returned to prevent a timeout error from occurring in the master. 06 Device Busy The FL3110/3111 is engaged in processing a long-duration program command. The master should retransmit the message later when the slave is free. 29
36 7.6 FL3110/3111 Command Register Locations Operational Mode Commands R indicates Read Only Access R/W indicates Read/Write Access Master Reg I/O Refer to Parameter Function Type Scale Access Addr Addr Section Analogue 4-20mA Current Output Value 16-Bit R Mode Indicates Fire Status Mode Value (0-11) R Status/Error Indicates error Bit 8-Bit R Only or IR Only (FL3110 only) UV/IR Only Indicates Detection of UV Value (1,2,3) R Model Type Identifies the Model FL311x Value (311x) R (x=0 or 1 to indicate Model) Software Rev Indicates the SW Revision ASCII 2-Char R COPM Fault UV/IR COPM Fault Bit 8-Bit R Not Used Options Indicates Unit Options Bit 8-Bit R/W Address Unit Address Value (1-247) R/W Not Used 000A Baud Rate Indicates present Baud Rate Value (0-3) R/W 000B (2400, 4800, 9600, 19200) Data Format Indicates Data Format Value (0-3) R/W 000C (8-N-1, 8-E-1, 8-O-1, 8-N-2) UV Indicates No. of UV Signal Value 8-Bit R 000D Sig Count Pulses within 500 ms IR Indicates No. of IR Signal Value 8-Bit R 000E Sig Count Pulses within 500ms UV Fault Indicates Total No. of UV Value 8-Bit R 000F Total COPM Faults IR Indicates Total No. of IR Value 8-Bit R Fault Total COPM Faults Remote Reset Remotely Resets the Alarm Bit 1-Bit R/W & Warn Condition Remote Alarm Remotely Activates Alarm Bit 1-Bit R/W Test Test Clear COPM Clears Window/Detector Bit 1-Bit R/W Faults COPM Fault Counters 30
37 7.7 FL3110/3111 Operational Mode Command Register Details Analogue A read returns a value, which is proportional to the 0 20mA output current. The current is based on a 16-bit value. The master scaling is Decimal which corresponds to the FL3110/3111 scaling which is 0 20mA Mode A read returns the fire status mode of the FL3110/3111. Mode Decimal Value Powerup Delay 1 Warn Non-latching Only 2 Warn & Alarm Non-Latching 3 Warn Latching Only 4 Alarm Latching Only 5 Warn & Alarm Latching 6 Ready State (No Fire) 7 Alarm Test 10 COPM Fault Detected Status/Error A read returns the errors that are occurring at the present time which are indicated by bit position. Byte Function Bit Position Low EPROM Checksum 8 EEPROM Checksum 7 RAM Test 6 Low (24V) Voltage Check 5 UV COPM 4 IR COPM (FL3110 only) 3 Not Used 2 Not Used 1 High Reset line shorted 8 UV 10 Minute 7 Not Used
38 7.7.4 UV/IR Only A read indicates the detection of UV only or IR only. UV Only Detected = 01 (Lo Data Byte) IR Only Detected = 02 (Lo Data Byte) (FL3110 only) High Data Byte Not Used Model Type A read returns the Decimal Value 311x which identifies the unit by model number. Model Version Decimal Value FL3110 UV/IR 3110 FL3111 UV Only Software Rev A read returns the software revision of the FL3110/3111 in 2 ASCII characters (Usually a blank and then a letter revision ex. A, B, C etc) COPM Fault A read returns the type of Continuous Optical Path Monitoring (COPM) Fault, which is a UV COPM Fault or IR COPM Fault. The UV COPM Fault and/or IR COPM Fault indicates either that the window is dirty and needs to be cleaned or there is a hardware problem with the detection circuitry or sensor. UV COPM Fault = 02 (Lo Data Byte) IR COPM Fault = 04 (Lo Data Byte) (FL3110 only) High Data Byte Not Used. 32
39 7.7.8 Options A read returns the status of the settings for the Detector Sensitivity, Relay Delay, Relay Latching/Non-Latching and Relay Energised/Non-Energised features from EEPROM. A write command changes the settings for the EEPROM. Exception: If an EEPROM write error occurs, then the Exception Code 04 (Slave Device Failure) is returned. These Functions operate on the Low Data Byte. Function Bit Position Conditions Access Warn Energised 8 (MSB) 1 = Energised Read/Write 0 = Non-Energised Alarm Energised 7 1 = Energised Read/Write 0 = Non-Energised Warn Latched 6 1 = Latched Read/Write 0 = Non-Latched Alarm Latched 5 1 = Latched Read/Write 0 = Non-Latched (Time Delay in Seconds) Alarm Time Delay Read/Write Alarm Time Delay Read/Write (Sensitivity %) Sensitivity Read/Write Sensitivity 1 1 (LSB) Read/Write High Data Byte Not Used Address A read returns the address of the FL3110/3111. A write changes the address to the requested address. The range of the address is 1 to 247 (01 to F7 Hex). After the address has been changed to the slave unit, the Modbus communications will cease because the address has changed; therefore the master will have to change its query address to the slave s new address in order to restart the communications. Exception: If an EEPROM write error occurs, then the Exception Code 04 (Slave Device Failure) is returned. 33
40 Baud Rate A read returns the Baud Rate of the FL3110/3111 whereas a write changes the Baud Rate that is requested baud. After the baud rate has been changed to the addressed unit, the Modbus communications will cease because the baud rate has changed; therefore the master will have to change its baud rate to the slave s new baud rate in order to restart the communications. These Functions operate on the Low Data Byte Baud Rate Low Data Byte Access Read/Write Read/Write Read/Write Read/Write High Data Byte Not Used Exception: If an illegal data value is entered which is not listed above, then the Exception Code 03 (Illegal Data Value) is returned. Exception: If an EEPROM write error occurs, then the Exception Code 04 (Slave Device Failure) is returned Data Format A read returns the data format of the FL3110/3111. A write changes the data format to the requested data format. After the data format has been changed to the addressed unit, the Modbus communications may cease or start producing comm errors because the data format has changed, therefore the master will have to change its data format to the slave s new data format in order to restart or provide proper communications. These Functions operate on the Low Data Byte. Data Parity Stop Format Low Data Byte Access 8 None 1 8-N-1 00 Read/Write 8 Even 1 8-E-1 01 Read/Write 8 Odd 1 8-O-1 02 Read/Write 8 None 2 8-N-2 03 Read/Write High Data Byte Not Used Exception: If an EEPROM write error occurs, then the Exception Code 04 (Slave Device Failure) is returned UV COPM Fault Total A read indicates the Total Number of UV Channel Window or Sensor COPM Faults that occurred in the slave device. This fault is usually caused by a dirty Window or faulty Sensor or Circuitry. The maximum count is 255 after which the counter will roll over to zero and begin counting again. 34
41 IR COPM Fault Total A read indicates the Total Number of IR Channel Window or Sensor COPM Faults that occurred in the slave device. This fault is usually caused by a dirty Window or a faulty Sensor or Circuitry. The maximum count is 255 after which the counter will roll over to zero and begin counting again. (FL3110 only) UV Signal Count A read indicates the number of UV Signal Counts that have occurred within 500ms which is the time required to detect a fire in the UV spectrum IR Signal Count A read indicates the number of IR Signal Counts that have occurred within 500 ms which is the time required to detect in the IR spectrum. (FL3110 only) Remote Reset Writing a (1) to the bit activates the Remote Reset function that resets the Alarm and Warn Conditions. The function is active momentarily and will reset automatically after being used. Function Bit (LSB) Access Enable 1 Read/Write Disable 0 Read/Write Remote Alarm Test Writing a (1) to the bit activates the Remote Alarm Test function that activates the Warn and Alarm relay turn-on along with the analogue current status. Once the Alarm Test is complete the function should be disabled by writing a zero to Remote Alarm Test and then resetting the Alarm and Warn relays by writing a (1) to the Remote Reset (referenced above). Function Bit (LSB) Access Enable 1 Read/Write Disable 0 Read/Write Clear COPM Faults A write to enable the bit activates the Clear COPM Faults function that resets all of the COPM faults. The bit and enable function is active momentarily and will reset to disable and zero after being used. Function Bit (LSB) Access Enable 1 Read/Write Disable 0 Read/Write 35
42 Attention Field Operations: Customer Satisfaction Questionnaire Models FL3110/3111 We would appreciate your help in assessing and thus improving the quality of our Equipment and Service and would therefore be grateful if you would complete the Questionnaire below and return it to: General Monitors Ireland Ltd, Ballybrit Business Park, Galway, Republic of Ireland. Thank you for your assistance Client Client Order No. General Monitors Sales Order No. Was the equipment the correct option? Are sensors correct type and range? Is mechanical assembly good? (everything proper fit and tight) Did you receive the necessary accessories to commission the equipment? Has the equipment been commissioned? Any problems encountered during commissioning? Is the equipment functioning correctly at present? (Please tick appropriate box) Yes No If you have answered NO to any of the above, please provide further details overleaf. Thank you. Completed by: Date: 36
FlameGard 5 UV/IR. Ultraviolet/Infrared Flame Detector
FlameGard 5 UV/IR Ultraviolet/Infrared Flame Detector The information and technical data disclosed in this document may be used and disseminated only for the purposes and to the extent specifically authorized
FIRERAY 2000 Installation Guide
FIRERAY 2000 Installation Guide Features Range 33ft to 330 ft. 24Vdc operation Selectable alarm thresholds Low current consumption Ground level electronics Manual or Automatic reset System Description
FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 10
TECHNICAL SPECIFICATIONS Page 1 of 10 FIRE DETECTION AND ALARM SYSTEM Scope Furnish a complete 24V DC conventional, electrically supervised, zone annunciated, fire detection and alarm system as specified
GENERATOR START CONTROL MODULE - MINI (2 Wire to 3 Wire)
FEATURES & APPLICATIONS Inexpensive 2 wire to 3 wire start controller for electric start high speed gas generators. Optimized for use with Outback Invertors. Supports three types of 3 wire generator control
RI-215A Operator s Manual. Part Number: 71-0045RK Revision 0 Released: 10/3/05
RI-215A Operator s Manual Part Number: 71-0045RK Revision 0 Released: 10/3/05 Warranty RKI Instruments, Inc., warrants gas alarm equipment sold by us to be free from defects in materials and workmanship,
Triple Waveband Infra-Red Flame Detection
Minerva S200PLUS Ex ia Intrinsically Safe & Ex d Flameproof Solar Blind Flame Detectors Triple Waveband Infra-Red Flame Detection Key Features Unrivalled black body rejection over a wide range of source
Manual for Fire Suppression & Methane Detection System
Manual for Fire Suppression & Methane Detection System Fogmaker North America Post address: 150 Gordon Dr Exton, PA 19341 Delivery address: 150 Gordon Dr Exton, PA 19341 Tel: 610-265-3610 Fax: 610-265-8327
Advantium 2 Plus Alarm
ADI 9510-B Advantium 2 Plus Alarm INSTALLATION AND OPERATING INSTRUCTIONS Carefully Read These Instructions Before Operating Carefully Read These Controls Corporation of America 1501 Harpers Road Virginia
TYPE 65UV5-1004 CEX Integrated Flame Scanner with Internal Flame Relay and Analog Output
133-683 JUNE 28, 2006 TYPE 65UV5-1004 CEX Integrated Flame Scanner with Internal Flame Relay and Analog Output DESCRIPTION APPLICATION The Fireye 65UV5-1004 flame scanner is a microprocessor based flame
SOLAR ELECTRIC MODULE ES-124 & ES-62T Owners Manual and Installation Guide
SOLAR ELECTRIC MODULE ES-124 & ES-62T Owners Manual and Installation Guide circuit. Reverse connection will damage the module and may result in fire. CAUTIONS Solar electric modules produce DC electricity
LS1024B / LS2024B/ LS3024B. Solar Charge Controller USER MANUAL
EPSOLAR LS1024B / LS2024B/ LS3024B Solar Charge Controller USER MANUAL Thank you very much for selecting our product! This manual offers important information and suggestions with respect to installation,
Operation and Installation Manual
Operation and Installation Manual RCM-10 Remote Control Monitor and RSM-10 Remote Status Monitor for the CNA-100 & CNA-200 Automations Revision 1.1 9/98 WARRANTY INFORMATION The RCM-10 Remote Control
MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE
DESCRIPTION MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE DESCRIPTION The SST Model 5010 Two Channel Smoke/Fire Detection Module provides two independent detection input channels for the NOVA-5000
EX-TECH SAS CP/PB 150 EXPLOSIONPROOF MANUAL CALL POINT/ PUSH BOTTON TECHNICAL MANUAL
PRODUCT NAME: CP/PB -150- EXPLOSION-PROOF-MANUAL CALL POINT/ PUSH BOTTON DOC NO.: EX-TECH SAS-12-CP-PB150-TM REV01 EXPLOSION-PROOF MANUAL CALL POINT/ PUSH BOTTON II 2GD EPL Gb, Db Ex d IIC T6, IP66 Ex
Detector transparent with Color Inserts. FAA 500 TR P Trim Ring transparent with Color Inserts. FCA 500 / FCA 500 E Detector Bases
Detector Color Detector transparent with Color Inserts FAA 500 TR W Trim Ring FAA 500 TR P Trim Ring transparent with Color Inserts FAA 500 BB Ceiling Mount Back Box FCA 500 / FCA 500 E Detector Bases
Model TL105. Test Lamp for Flame Detection
Model TL105 Test Lamp for Flame Detection The information and technical data disclosed in this document may be used and disseminated only for the purposes and to the extent specifically authorized in writing
T7560A,B,C Digital Wall Module
T7560A,B,C Digital Wall Module HONEYWELL EXCEL 5000 OPEN SYSTEM BEFORE INSTALLATION All wiring must comply with local electrical codes and ordinances or as specified on installation wiring diagrams. Digital
AXIS T81B22 DC 30W Midspan
INSTALLATION GUIDE AXIS T81B22 DC 30W Midspan ENGLISH About this Document This document includes instructions for installing AXIS T81B22 on your network. Previous experience of networking will be beneficial
MCR1900 Media Converter 19-Slot Chassis
MCR1900 Media Converter 19-Slot Chassis Installation Guide Part #5500304-11 Copyright Statement This document must not be reproduced in any way whatsoever, either printed or electronically, without the
Infrarot-Bewegungsmelder IP44
Infrarot-Bewegungsmelder IP44 infrared motion sensors IP44 ODA (weiß) slim ODA (schwarz) slim 95174 96000 ODA (weiß) ODA (schwarz) 95175 96001 Betriebsanleitung User s Manual User s Manual infrared motion
RGC-IR Remote Gas Calibrator for IR400
Remote Gas Calibrator for IR400 The information and technical data disclosed in this document may be used and disseminated only for the purposes and to the extent specifically authorized in writing by
SDX Submersible Depth Transmitter User Manual
SDX Submersible Depth Transmitter User Manual January 2011 USER INFORMATION Stevens makes no warranty as to the information furnished in these instructions and the reader assumes all risk in the use thereof.
Mobile Data Power Model: MDP-25
Mobile Data Power Model: MDP-25 Topic Section Features... 2 Operational Features Summary... 2 Back-up Battery Power Internal Charger Voltage Spike Protection RF Noise Filtering Warning of Imminent Loss
D7050/D7050TH. Installation Instructions. Multiplex Photoelectric Smoke Detectors
D7050/D7050TH EN Installation Instructions Multiplex Photoelectric Smoke Detectors D7050/D7050TH Installation Instructions.0 Description Notices These instructions cover the installation of the D7050/D7050TH
Operating Instructions
Important information: These instructions contain safety information, read and follow them carefully. Dialight will not accept any responsibility for injury, damage or loss which may occur due to incorrect
How to Select a Flame Detector
How to Select a Flame Detector Process and plant engineers in the oil and gas industry and a wide range of other hazardous process and manufacturing industries require continuous flame monitoring equipment
ALL WEATHER W-SERIES QUARTZ TUBE ELECTRIC INFRARED RADIANT HEATER INSTALLATION USE & CARE MANUAL
ALL WEATHER W-SERIES QUARTZ TUBE ELECTRIC INFRARED RADIANT HEATER TABLE OF CONTENTS: INSTALLATION USE & CARE MANUAL IMPORTANT INFORMATION Assembly Instructions 2 Wiring Instructions 2 Outdoor Installation
ATS Overhead Table Shelf System INSTRUCTION MANUAL
ATS Overhead Table Shelf System INSTRUCTION MANUAL ATS Overhead Table Shelf System Instruction Manual Warranty Newport Corporation warrants this product to be free of defects in material and workmanship
12 Volt 30 Amp Digital Solar Charge Controller
12 Volt 30 Amp Digital Solar Charge Controller User s Manual WARNING Read carefully and understand all INSTRUCTIONS before operating. Failure to follow the safety rules and other basic safety precautions
CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems
CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems EN Security System CM705B CM705B - Universal Expander Module The CM705B universal expander provides a cost effective way
TIG INVERTER INSTRUCTION MANUAL
TIG INVERTER INSTRUCTION MANUAL Contents Warning General Description Block Diagram Main Parameters Circuit Diagram Installation and Operation Caution Maintenance Spare Parts List Troubleshooting 3 4 4
Short Range Wireless Switch System Handheld 8 Installation and Operations Guide
Phone: (866) 701-1146 Fax: (425) 216-7558 www.remotecontroltech.com Short Range Wireless Switch System Handheld 8 Installation and Operations Guide Introduction... 2 Before Installation... 2 Receiver Installation...
DTW Works Master Specification Version 2006
Issued 2006/08/01 Section 13852 Multiplex Fire Alarm System Page 1 of 10 PART 1 GENERAL 1.1 RELATED WORK.1 Section 01330 Submittal Procedures..2 Section 01780 Closeout Procedures..3 Section 01810 Commissioning..4
JNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410
The INTEG is an Ethernet I/O (digital, analog) device that monitors and controls a small set of process signals. functions as both basic I/O for integration with another application or system AND as a
Comfort Control Relay Panel (CCRP)
CCRP9 "Commitment to Innovation" OPERATION & INSTALLATION GUIDE FOR Comfort Control Panel (CCRP) Off-Peak System Control 9 Pole CCRP 4 Pole CCRP (Applicable to Software Version 14.0-14.9) "Manufactured
Modular I/O System Analog and Digital Interface Modules
OPERATING INSTRUCTIONS Modular I/O System Analog and Digital Interface Modules Installation Operation Maintenance Document Information Document ID Title: Operating Instructions Modular I/O System Part
User Manual for CH-PFC76810
AA Portable Power Corp www.batteryspace.com, Email: [email protected] User Manual for CH-PFC76810 1. Overview The CH-PFC76810 charger is suitable for charging lithium ion battery packs such as those
Portable Solar Kits Owner s Manual
powered by Portable Solar Kits Owner s Manual Veuillez visiter gpelectric.com pour la version française de ce manuel de l utilisateur Visite gpelectric.com para la versión en español de este manual del
Solar Power Systems Models: PVS220W-24 and PVS220W-48 Installation Manual
Solar Power Systems Models: PVS220W-24 and PVS220W-48 Installation Manual 255379 Rev. D0 1015 Printed in U.S.A. Copyright 2015 Federal Signal Corporation Limited Warranty The Alerting and Notification
User s Manual Before using the inverter, you need to read and save the safety instructions.
User s Manual Before using the inverter, you need to read and save the safety instructions. STI SERIES (STI200, STI300, STI500, STI700, STI1000) Power Frequency Pure Sine Wave Inverter The information
HP UPS R1500 Generation 3
HP UPS R1500 Generation 3 Installation Instructions Part Number 650952-001 NOTE: The rating label on the device provides the class (A or B) of the equipment. Class B devices have a Federal Communications
Digital echo-charge. Owner s Manual. Xantrex Digital echo-charge Battery Charger
Digital echo-charge Owner s Manual Xantrex Digital echo-charge Battery Charger Thank you for purchasing a Xantrex Digital echo-charge. Xantrex Technology Inc. takes pride in manufacturing quality products
R4D0-FB-IA* FieldBarrier. Features. Assembly. Function. Connection IN + - S OUT ... ... Spur 2. Spur 1. Zone 1. Zone 0
FieldBarrier Features Assembly 8... 12 outputs Ex ia IIC, FISCO and Entity Advanced fault isolation and diagnostics at the spur FieldBarrier in Zone 1/Div. 2 Instruments in Zone 0...1/Div. 1 For FOUNDATION
Installation and Operation Back-UPS 1250, 1300, 1500
Installation and Operation Back-UPS 1250, 1300, 1500 Inventory bu001a Safety and General Information This unit is intended for indoor use only. Do not operate this unit in direct sunlight, in contact with
INSTRUCTION MANUAL MODEL PCD-88
INSTRUCTION MANUAL MODEL PCD-88 CLOSED CAPTION DECODER LINK ELECTRONICS, INC. 2137 Rust Avenue Cape Girardeau, Missouri 63703 Phone: 573-334-4433 Fax: 573-334-9255 e-mail: sales @ linkelectronics.com website:
FLUORESCENT UV- RING LIGHT OPERATING INSTRUCTION
FLUORESCENT UV- RING LIGHT OPERATING INSTRUCTION Caution! UV-radiation of this device is in the range of UV-A (320-400 nm). Direct exposure to eyes shall therefore be avoided. UV protection glasses shall
GreenWay Solar LED Path and Trail Lighting System. Installation and Owner s Manual
GreenWay Solar LED Path and Trail Lighting System Installation and Owner s Manual Important Notes and Warnings This installation and instruction manual provides installation, operation, and maintenance
OPERATING INSTRUCTIONS Model ST-888 DTMF ANI/ENI Display Decoder
P R O D U C T G R O U P OPERATING INSTRUCTIONS Model ST-888 DTMF ANI/ENI Display Decoder Manual # 600-0901 November 30, 1999 Rev. D - 99068 DESCRIPTION The ST-888 Mobilecall Display Decoder is a desktop
DSM155 Digital LED Light Meter User s Manual DSM155
DSM155 Digital LED Light Meter User s Manual DSM155 CONTENTS TABLE OF CONTENTS......3 LIMITED WARRANTY AND LIMITATION OF LIABILITY......3 Out of Box....3 Accessories....3 Safety Information....3 Certification....5
Clear Glass Sensor. Ordering Information E3S-CR67/62. Optimum Sensor for Detecting Transparent Glass and Plastic Bottles
Clear Glass Sensor Optimum Sensor for Detecting Transparent Glass and Plastic Bottles E3S-CR67/62 Retroreflective Sensor smoothly detects 5-mm gaps. Detects transparent bottles that have a lens effect.
PL-1, Pocket Logger 11-0135B
PL-1, Pocket Logger 1 PL-1... 2 2 Wiring... 3 2.1.1 Single Innovate Device Relay Wiring Instructions... 3 3 Mounting... 4 4 Connecting the PL-1 to the MTS serial chain... 4 5 Recording... 5 6 LogWorks...
Original instructions Tina 3A/Aps Adaptor unit
Original instructions Tina 3A/Aps Adaptor unit ABB Jokab Safety Varlabergsvägen 11, SE-434 39 Kungsbacka, Sweden www.abb.com/jokabsafety Read and understand this document Please read and understand this
BARDIC. 4 & 8 Zone Fire Panels Zircon range. Data, installation, operation and maintenance. by Honeywell
Data, installation, operation and maintenance 4 & 8 Zone Fire Panels Zircon range BARDIC by Honeywell LED flashing LED Continuous FAULT DISABLE/TEST Power General Fault Sounder Fault/ Disable System Fault
CB200 1 8 Zone Conventional Control Panel
CB200 1 8 Zone Conventional Control Panel > features Built-in detector removal indication facility From 1 to 8 zones 4 Alarm circuits on 4-8 zone panels Conforms to the requirements of EN54-2 User-friendly
Ground Resistance Clamp-On Tester
User s Manual Ground Resistance Clamp-On Tester MODEL 382357 Warranty EXTECH INSTRUMENTS CORPORATION (a FLIR company) warrants the basic instrument to be free of defects in parts and workmanship for one
AUTOMATIC BEST BATTERY SELECTOR INSTALLATION & OPERATION BBS-1600 BBS-1600E
AUTOMATIC BEST BATTERY SELECTOR INSTALLATION & OPERATION BBS-1600 BBS-1600E SENS part no: 101314 Document revision: F DCN No. 106811 Date 8/3/15 1840 Industrial Circle Longmont, CO 80501 Fax: (303) 678-7504
LDG DTS-4/4R Desktop Coaxial Switch / Remote
LDG DTS-4/4R Desktop Coaxial Switch / Remote LDG Electronics 1445 Parran Road, PO Box 48 St. Leonard MD 20685-2903 USA Phone: 410-586-2177 Fax: 410-586-8475 [email protected] www.ldgelectronics.com
Automatic Transfer Switch FT-10 Network Control Communications Module (CCM-T) Kit 541 0811
Instruction Sheet 1-2003 Automatic Transfer Switch FT-10 Network Control Communications Module (CCM-T) Kit 541 0811 PURPOSE OF KIT A CCM-T is used to monitor and control an automatic transfer switch. The
Smarthome SELECT Bluetooth Wireless Stereo Audio Receiver and Amplifier INTRODUCTION
Smarthome SELECT Bluetooth Wireless Stereo Audio Receiver and Amplifier INTRODUCTION The Smarthome SELECT Bluetooth Wireless Stereo Audio Receiver and Amplifier is a multi-functional compact device. It
Wireless Indoor/ Outdoor Thermometer
Wireless Indoor/ Outdoor Thermometer Owner s Manual Please read before using this equipment. ˆ Contents FCC Information... 3 FCC Declaration of Conformity... 5 Preparation... 5 Installing Batteries...
3500/93 System Display
3500/93 System Display Bently Nevada* Asset Condition Monitoring Description The 3500/93 System Display is designed to meet the requirements of American Petroleum Institute (API) Standard 670 and provide
Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF
Daker DK 1, 2, 3 kva Manuel d installation Installation manual Part. LE05334AC-07/13-01 GF Daker DK 1, 2, 3 kva Index 1 Introduction 24 2 Conditions of use 24 3 LCD Panel 25 4 Installation 28 5 UPS communicator
User Manual. English. APC Smart-UPS SC. 1000/1500 VA 110/120/230 Vac. 2U Tower/Rack-Mount Uninterruptible Power Supply
User Manual English APC Smart-UPS SC 1000/1500 VA 110/120/230 Vac 2U Tower/Rack-Mount Uninterruptible Power Supply 990-1851C, 10/2005 Introduction The APC Uninterruptible Power Supply (UPS) is designed
Solar Home System. User Manual. AEH-SHS01-10W2L Solar Home System 2 Lamps
Solar Home System User Manual AEHSHS0110W2L Solar Home System 2 Lamps All rights reserved Specifications subject to change without prior notice 2 Dear Customer, Thank you for purchasing Schneider Electric
Explosion proof enclosures
1 of 7 Explosion proof enclosures DE8 C 2 of 7 The Ex d enclosures are rugged and designed for harsh environment like: Oil and gas industry Chemical industry Pharmaceutical industry Agribusiness Without
Water Leak Detection System
Water Leak Detection System Installation and Operating Manual 505-334-5865 ph 505-334-5867 fax www.rodisystems.com email:[email protected] 936 Highway 516 Aztec, NM 87410-2828 Manual Revisions and Copyright
Motion Detector 360 Degrees 5420/360. Installation Instructions REGISTERED DESIGN REGISTERED PATENT
Motion Detector 360 Degrees 5420/360 Installation Instructions REGISTERED DESIGN REGISTERED PATENT Installation Instructions The Infra-red Monitor Motion Detector from Clipsal provides high performance
Flame detection across the spectrum. Range Brochure
talentum Flame detection across the spectrum Range Brochure Talentum - Why use our Flame Detectors... Talentum Flame Detectors are ideal for applications where fast acting and accurate detection of fire
Radiant Temperature Sensor TY7321
AB-5361-U Specifications/Instructions Radiant Temperature TY7321 General TY7321 Radiant Temperature s are designed to measure infrared radiation from perimeter windows and walls and provide a proportional
User s manual FLIR VP50/VP52 Non-contact AC voltage detector
User s manual FLIR VP50/VP52 Non-contact AC voltage detector User s manual FLIR VP50/VP52 #T559851; r. AD/ 9134/9134; en-us Table of contents 1 Disclaimers... 1 1.1 Copyright... 1 1.2 Quality assurance...
TC-9102 Series Surface Mount Temperature Controllers
TC-9102 Series Surface Mount Temperature Controllers General Description & Applications The TC-9102 Series Temperature Controller offers a versatile solution for a wide variety of applications that may
How To Use A Power Supply Unit (Upu)
BRAVER UPS (Uninterruptible Power System) User s Manual Safety CAUTION! This UPS utilizes voltages that may be hazardous. Do not attempt to disassemble the unit. The unit contains no user replaceable parts.
Owner s Manual & Safety Instructions
Owner s Manual & Safety Instructions Save This Manual Keep this manual for the safety warnings and precautions, assembly, operating, inspection, maintenance and cleaning procedures. Write the product s
Ground Resistance Clamp On Tester
USER MANUAL Ground Resistance Clamp On Tester MODEL 382357 Introduction Congratulations on your purchase of Extech s 382357 Ground Resistance Tester. This Clamp on device allows the user to measure ground
12 Volt 30 Amp Digital Solar Charge Controller Installation & Operation Manual
12 Volt 30 Amp Digital Solar Charge Controller Installation & Operation Manual This 30Amp charge controller is designed to protect your 12Volt Lead-acid or Gel-cell battery from being overcharge by solar
SHUTTER REMOTE USER MANUAL UNIVERSAL WIRED & IR RS-UWIR100 COMPATIBLE WITH MOST DSLR CAMERAS
SHUTTER REMOTE UNIVERSAL WIRED & IR SHUTTER REMOTE RS-UWIR00 COMPATIBLE WITH MOST DSLR CAMERAS USER MANUAL THANK YOU FOR CHOOSING ZIV. The Ziv Shutter Remote RS-UWIR00 can trigger the shutter on most DSLR
Duct Humidity Transmitter
SDC-H Duct Humidity Transmitter Features Replaceable sensor element Humidity measurement for air ducts Minimum and maximum value memory 0 0V, 0 0mA or 0V, 4 0mA measuring signals selectable with jumpers
Zlinx Wireless I/O. Peer-to-Peer and Modbus I/O B&B ELECTRONICS PRODUCT INFORMATION
Modular, Customizable Wire Replacement 128 / 256 Bit AES Encryption Software Selectable RF Transmit Power Software Selectable Over-the-air Data Rate Modbus ASCII /RTU Compatible Wide Operating Temperature
StructureScan HD Module. Installation Guide ENGLISH. www.bandg.com www.simrad-yachting.com www.lowrance.com
StructureScan HD Module Installation Guide ENGLISH www.bandg.com www.simrad-yachting.com www.lowrance.com Disclaimer As Navico is continuously improving this product, we retain the right to make changes
Instruction Manual. T3111 T3111L T3111P T3111Ex
www.cometsystem.cz Instruction Manual T3111 T3111L T3111P T3111Ex Programmable transmitter of temperature, relative humidity and other calculated humidity values with external probe and 4-20 ma outputs
USER MANUAL Stand Alone Power Supply PSQ 2909 / PSQ 3909 / PSQ 4909 PSQ 2920 / PSQ 3920 / PSQ 4920
USER MANUAL Stand Alone Power Supply PSQ 2909 / PSQ 3909 / PSQ 4909 PSQ 2920 / PSQ 3920 / PSQ 4920 [This page intentionally left blank] Warning for Your Protection 1. Read these instructions. 2. Keep these
Portable Bluetooth Speaker. Quick Start Guide. Model: BTS201
Portable Bluetooth Speaker Quick Start Guide Model: BTS201 Disclaimer All the information, design and specifications contained in this manual were correct at the time of publication. However, as the product
User s Manual AURORA 1.2K/2.2K
User s Manual AURORA 1.2K/2.2K Uninterruptible Power System Safety CAUTION This UPS utilizes voltages that may be hazardous. Do not attempt to disassemble the unit. The unit contains no user serviceable
Installation and Operation Manual. Digital Remote Meter for Monitoring System Performance. Version: RM-1
REMOTE METER TM Installation and Operation Manual. Digital Remote Meter for Monitoring System Performance. Version: RM-1 1098 Washington Crossing Road Washington Crossing, PA 18977 USA www.morningstarcorp.com
Amps Per Bank. Total Output. Battery System. Model Name. 6 amps 12 amps 10 amps 20 amps 30 amps 40 amps 15 amps 30 amps 45 amps
Model Name Total Output Amps Per Bank Battery System Pro XL Dual Pro XL Pro SE Dual Pro SE Three Bank Pro SE Four Bank Pro SE Pro Charger Dual Pro Charger Three Bank Pro Charger 6 amps 12 amps 10 amps
Mobile 3G. Cellular Signal Booster 460102. Need help? www.wilsonelectronics.com Tech Support 866-294-1660 Mon.- Fri. Hours: 7 am to 6 pm MST
Mobile 3G Cellular Signal Booster 460102 Need help? www.wilsonelectronics.com Tech Support 866-294-1660 THE ALUMINUM CASING OF YOUR SIGNAL BOOSTER!! WILL ADJUST TO THE TEMPERATURE OF ITS ENVIRONMENT, BUT
How To Use The Visifault Visual Fault Locator
VisiFault Visual Fault Locator Instruction Sheet The VisiFault Visual Fault Locator (VFL) is a visible light source that helps you trace optical fibers, check fiber continuity, and find faults such as
Temp. & humidity Transmitter Instructions
Temp. & humidity Transmitter Instructions AQ3485/AQ3485Y www.aosong.com 1 Product Overview AQ3485/ AQ3485Y outdoor network temperature and humidity transmitter is accurate measurement of relative humidity
Master Time Clock MTC-200 MTC-400 MTC-600. Users Manual
Master Time Clock MTC-200 MTC-400 MTC-600 Users Manual Toll Free (888)713-0373 Phone (972)987-4408 FAX (877)720-9291 www.midwest-time.com [email protected] TABLE OF CONTENTS TOPIC PAGE GENERAL DESCRIPTION
Back-UPS Pro 1300/1500 Installation and Operation
Back-UPS Pro 1300/1500 Installation and Operation Inventory Safety Do not install the Back-UPS in direct sunlight, in excessive heat, humidity, or in contact with fluids. Connect the battery bu059a bu058a
User's Guide. Integrating Sound Level Datalogger. Model 407780. Introduction
User's Guide 99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com Back to the Extech 407780 Product Page Integrating Sound Level Datalogger
PSC POWER STAR LiFE TM
PSC POWER STAR LiFE TM Operation Manual Version 3.0 Copyright 2012 Professional Sound Corp 28085 Smyth Drive, Valencia, CA 91355 USA CE RoHS Printed in the U.S.A. Thank you for purchasing your new PSC
Charge Regulator SCR 12 Marine
Charge Regulator SCR 12 Marine Manual Many thanks for purchasing a superwind product. The SCR 12 Marine is a charge regulator of highest quality and will perfectly and reliably charge your batteries for
3 WATT LED SPOTLIGHT Model No. SLM - 3801
3 WATT LED SPOTLIGHT Model No. SLM - 3801 OWNER'S MANUAL Customer Service Tel: 1-800-268-3319 Superex Canada Ltd, Toronto,M2H 3B8 Made in China Table of Contents A). Important Safety Instructions B). Charging
VLT Series 300 Watt True Sine Wave Inverter
VLT Series 300 Watt True Sine Wave Inverter PURE SINE WAVE INVERTER I ON 0 OFF REMOTE CONTROL AC OUTPUT POWER STATUS Vout Vin Models VLT12-300 VLT24-300 300 Watt VLT Series Inverter - 1 - TABLE OF CONTENTS
OUTPUT CABLE CONNECTIONS:
Tender Plus: Models: 12V1.25A and 6V1.25A The Tender Plus 12 Volt, 1.25 Amp 6 Volt, 1.25 Amp GENERAL DESCRIPTION: The Tender Plus battery charger is a desktop, portable, linear power converter that has
E-PDD Duct Smoke Detector Installation Sheet
E-PDD Duct Smoke Installation Sheet Operation The duct smoke detector's primary purpose is to provide early warning of an impending fire and shut down the HVAC unit in order to prevent smoke from circulating
Tina 2A/B Adaptor unit
Original instructions Tina 2A/B Adaptor unit ABB Jokab Safety Varlabergsvägen 11, SE-434 39 Kungsbacka, Sweden www.abb.com/jokabsafety Read and understand this document Please read and understand this
Operation Manual for Users
Operation Manual for Users Model No.: FLTAMFMRCD!!!!!!!!!! ATTENTION!!!!!!!!!! THE RESET BUTTON MUST BE PRESSED TO ENSURE PROPER OPERATION. SEE INSTRUCTION MANUAL Table of Contents Table of Contents ---------------------------------------------------------------------------------------------
FOSTCDR. Industrial Serial to Multimode Fiber Optic Converter PRODUCT INFORMATION B&B ELECTRONICS. Specifications Serial Technology
FOSTCDR pn 8684R1 FOSTCDR-0812ds page 1/5 Industrial Serial to Multimode Fiber Optic Converter Data Rates up to 115.2 kbps 2.5 Mile (4 km) Range 10 to 30 VDC Input Voltage Wide Operating Temperature 2000V