PRC Review & Update. Phil O Donnell, WECC Manager Operations & Planning Audits
|
|
|
- Kelly Barton
- 9 years ago
- Views:
Transcription
1 PRC Review & Update Phil O Donnell, WECC Manager Operations & Planning Audits
2 2 PRC Quick Review of the Requirements The extra things you need to do Version 1 Version 2 Transition Notes System Monitoring Encouraging more than minimum Unresolved Maintenance Issues
3 3 All For One and One For All PRC Transmission and Generation Protection System Maintenance and Testing PRC Implementation and Documentation of Underfrequency Load Shedding Equipment Maintenance Program PRC Undervoltage Load Shedding System Maintenance and Testing PRC Special Protection System Maintenance and Testing PRC PRC PRC PRC PRC-005-2
4 4 PRC Requirements R1-R5 Definitions: Some in NERC Glossary some in the Standard Tables must be followed as a requirement Attachment A must be followed as a requirement for performance based maintenance.
5 5 Requirement 1 Each Transmission Owner, Generator Owner, and Distribution Provider shall establish a Protection System Maintenance Program (PSMP) for its Protection Systems
6 6 Requirement Identify which maintenance method (time-based, performance-based per PRC-005 Attachment A, or a combination) is used to address each Protection System Component Type.
7 7 Requirement 1 Except of course for batteries: All batteries associated with the station DC supply Component Type of a Protection System shall be included in a time-based program. Should I have a time based program For batteries?
8 8 Requirement Include the applicable monitored Component attributes applied to each Protection System Component Type consistent with the maintenance intervals specified in Tables 1-1 through 1-5, Table 2, and Table 3 where monitoring is used to extend the maintenance intervals beyond those specified for unmonitored Protection System Components.
9 9 Requirement Translation Are you using any type of monitoring to determine the maintenance or testing interval? If Yes: Then the verification of the monitoring capability must be specified in your program!
10 10 Requirement 2 Each Transmission Owner, Generator Owner, and Distribution Provider that uses performance-based maintenance intervals in its PSMP shall follow the procedure established in PRC-005 Attachment A to establish and maintain its performancebased intervals. If you do not use performance-based maintenance R2 is not applicable.
11 11 Attachment A To establish a performance based program: Five (5) steps which should be considered as requirements for compliance purposes To maintain a performance based program: Four (4) additional steps should be considered as annual requirements for compliance purposes. One (1) additional step if program does not work.
12 12 Requirement 3 Each Transmission Owner, Generator Owner, and Distribution Provider that utilizes time based maintenance program(s) shall maintain its Protection System Components that are included within the time-based maintenance program in accordance with the minimum maintenance activities and maximum maintenance intervals prescribed within Tables 1-1 through 1-5, Table 2, and Table 3.
13 13 Requirement 3 Audit must include verification that the specified maintenance tasks have been done. If monitoring is used, Audit must include verification of alarming capability per Table 2
14 14 Requirement 4 Each Transmission Owner, Generator Owner, and Distribution Provider that utilizes performance-based maintenance program(s) in accordance with Requirement R2 shall implement and follow its PSMP for its Protection System Components that are included within the performance-based program(s).
15 15 Unresolved Maintenance Issue Unresolved Maintenance Issue A deficiency identified during a maintenance activity that causes the component to not meet the intended performance, cannot be corrected during the maintenance interval, and requires follow-up corrective action. The maintenance interval is the interval specified in the tables (or per performance based plan)
16 16 Unresolved Maintenance Issue An unmonitored non-microprocessor relay was last maintained 5 years ago. During a scheduled calibration test the technician could not calibrate the device to within specification. Is this an Unresolved Maintenance Issue (Ref: Table 1-1)
17 17 Requirement 5 Each Transmission Owner, Generator Owner, and Distribution Provider shall demonstrate efforts to correct identified Unresolved Maintenance Issues. Entities should be tracking UMI as of April 1, Evidence of efforts to correct the UMI may be requested for those outstanding on April 1, 2015.
18 18 Do the right thing! What If your program specifies maintenance activities to be performed that are not listed in the tables and you fail to perform those activities? NO penalty for trying to do more!
19 19 The Tables Table 1-1 Protective Relay s Table 1-2 Communications Systems Table 1-3 Sensing Devices Table 1-4 (a-f) DC Supply Table 1-5 Control Circuitry Table 2 Alarming Paths Table 3 Distributed UFLS and UVLS Systems Attachment A Criteria for a Performance Based Protection System Maintenance Program.
20 20 The (1-4) Tables Table 1-4a DC Supply (VLA Batteries) Table 1-4b DC Supply (VRLA Batteries) Table 1-4c DC Supply (NiCad Batteries) Table 1-4d DC Supply (non- Battery Table 1-4e DC Supply for SPS, non-distributed UFLS, and non-distributed UVLS systems Table 1-4f Exclusions for Protection System Station dc Supply Monitoring Devices and Systems
21 21
22 22 Beware! Read the Table Carefully Table 1-3: Component Type - Voltage and Current Sensing Devices Providing Inputs to Protective Relays Component Attribute Voltage and Current Sensing devices connected to microprocessor relays with AC measurements are continuously verified by comparison of sensing input value, as measured by the microprocessor relay, to an independent ac measurement source, with alarming for unacceptable error or failure Maximum Maintenance Interval No periodic maintenance specified Maintenance Activities None.
23 23 Beware! Read the Table Carefully Table 3: Maintenance Activities and Intervals for distributed UFLS and distributed UVLS Systems Component Attribute Voltage and/or current sensing devices associated with UFLS or UVLS systems. Maximum Maintenance Interval 12 calendar years Maintenance Activities Verify that current and/or voltage signal values are provided to the protective relays.
24 24 Protection System Monitoring PRC allows Implementation of Protection System Monitoring to alter the interval for specified tests in the tables. Monitoring capability must be as specified in the tables. Monitoring System itself must be maintained as specified in Table 2
25 25 An Alarming Fact! For monitoring to have any impact on maintenance interval it must have associated alarms. The Alarm Path itself must have testing performed (12 year interval) unless. The Alarm Path itself is monitored.
26 26 Monitoring and Version 1 For PRC-005 version 1, an entity may use monitoring to satisfy testing requirements under the following conditions: The entity has described what is monitored within its program, and has specified continuous as the established interval for that testing. Monitoring must be applied per the attributes listed in the tables in PRC If monitoring is used as a basis to establish maintenance intervals, the monitoring processes and systems must be maintained as specified in PRC Table 2. In no case may monitoring be used as a basis to extend maintenance intervals beyond what would be allowed for the same component in PRC
27 27 Transition Notes Can continue to use PRC and other Legacy Standards during implementation period for version 2. After you complete all maintenance tasks specified in the tables for a component that component has been transitioned to version 2. You must keep all records associated with your version 1 program until you have performed two maintenance activities under version 2 OR you have been audited.
28 28 Transition Notes PRC was effective April 1, The first compliance date is April 1, Must have a PSMP (TBM, PBM or both). Current plan may be used to become compliant with PRC Must be compliant with R1, R2 & R5
29 29 Transition Notes PRC R3 and R4: Phased Implementation Implementation based on maximum intervals Applies to both time based and performance based programs. PRC-005 Implementation Plan
30 30 Transition Notes Auditors will check on status of transition from Version 1 to Version 2. Failure to meet the implementation goals specified in the implementation plan would be considered as a possible violation of R3 or R4.
31 31 Contact Information Phil O Donnell, Manager Operations and Planning Audits and Investigations [email protected]
CIP 010 1 Cyber Security Configuration Change Management and Vulnerability Assessments
CIP 010 1 Cyber Security Configuration Change Management and Vulnerability Assessments A. Introduction 1. Title: Cyber Security Configuration Change Management and Vulnerability Assessments 2. Number:
CIP-010-2 Cyber Security Configuration Change Management and Vulnerability Assessments
CIP-010-2 Cyber Security Configuration Change Management and Vulnerability Assessments A. Introduction 1. Title: Cyber Security Configuration Change Management and Vulnerability Assessments 2. Number:
CIP-003-5 Cyber Security Security Management Controls
A. Introduction 1. Title: Cyber Security Security Management Controls 2. Number: CIP-003-5 3. Purpose: To specify consistent and sustainable security management controls that establish responsibility and
Re: NERC Notice of Penalty regarding Pacific Gas and Electric Company FERC Docket No. NP10-_-000
f April 28, 2010 Ms. Kimberly Bose Secretary Federal Energy Regulatory Commission 888 First Street, N.E. Washington, D.C. 20426 Re: NERC Notice of Penalty regarding Pacific Gas and Electric Company FERC
Summary of CIP Version 5 Standards
Summary of CIP Version 5 Standards In Version 5 of the Critical Infrastructure Protection ( CIP ) Reliability Standards ( CIP Version 5 Standards ), the existing versions of CIP-002 through CIP-009 have
Midwest Reliability Organization Procedure For NERC PRC-012
Midwest Reliability Organization Procedure For NERC PRC-012 A. Introduction The following procedure developed by the MRO Protective Relay Subcommittee (PRS) and Transmission Assessment Subcommittee (TAS)
CIP-005-5 Cyber Security Electronic Security Perimeter(s)
A. Introduction 1. Title: Cyber Security Electronic Security Perimeter(s) 2. Number: CIP-005-5 3. Purpose: To manage electronic access to BES Cyber Systems by specifying a controlled Electronic Security
Asset Management Business Update
Asset Management Business Update Improvements through Asset Management Mark Davis, Director, Asset Management & AW October 29, 2008 1 From Maintenance to Asset Management Maintain the System -Initial Focus
MOBILE DC POWER SYSTEMS FOR SUBSTATION APPLICATIONS
MOBILE DC POWER SYSTEMS FOR SUBSTATION APPLICATIONS Gary P. Guagliardi Director Sales & Marketing HindlePower, Inc. Easton, PA Introduction This paper explores the use of mobile DC power systems for three
ISO 9001:2000 AUDIT CHECKLIST
ISO 9001:2000 AUDIT CHECKLIST No. Question Proc. Ref. Comments 4 Quality Management System 4.1 General Requirements 1 Has the organization established, documented, implemented and maintained a quality
AUDITOR GUIDELINES. Responsibilities Supporting Inputs. Receive AAA, Sign and return to IMS with audit report. Document Review required?
1 Overview of Audit Process The flow chart below shows the overall process for auditors carrying out audits for IMS International. Stages within this process are detailed further in this document. Scheme
CAN/ULC-S561-03 Installation and Services for Fire Signal Receiving Centres and Systems- Ottawa 2013
CAN/ULC-S561-03 Installation and Services for Fire Signal Receiving Centres and Systems- Ottawa 2013 Alan Cavers, Engineering Manager Underwriters Laboratories of Canada Dec. 2013 Copyright 1995-2007 Underwriters'
When this standard has received ballot approval, the text boxes will be moved to the Guidelines and Technical Basis section of the Standard.
CIP-002-5 Cyber Security BES Cyber System Categorization When this standard has received ballot approval, the text boxes will be moved to the Guidelines and Technical Basis section of the Standard. A.
Alarm Systems Using Wireless or Other Transmission Technology as a Single Path of Communication. Purpose. References. Description of Code Reference
TOWN OF BRIGHTON Office of the Fire Marshal 2300 Elmwood Avenue Rochester, New York 14618 (585) 784-5220 Office (585) 784-5207 Fax Alarm Systems Using Wireless or Other Transmission Technology as a Single
3. Purpose: To improve the reliability of the Bulk Electric System by requiring the reporting of events by Responsible Entities.
A. Introduction 1. Title: Event Reporting 2. Number: EOP-004-2 3. Purpose: To improve the reliability of the Bulk Electric System by requiring the reporting of events by Responsible Entities. 4. Applicability:
Alberta Reliability Standard Cyber Security Configuration Change Management and Vulnerability Assessments CIP-010-AB-1
A. Introduction 1. Title: 2. Number: 3. Purpose: To prevent and detect unauthorized changes to BES cyber systems by specifying configuration change management and vulnerability assessment requirements
ADMO. Maintenance management solution for protection systems supporting NERC PRC-005 requirements
ADMO Maintenance management solution for protection systems supporting NERC PRC-005 requirements Keeping track with ADMO The challenge Proper functioning of the protection system with all its individual
ISO 9001 (2000) QUALITY MANAGEMENT SYSTEM ASSESSMENT REPORT SUPPLIER/ SUBCONTRACTOR
Page 1 of 20 ISO 9001 (2000) QUALITY MANAGEMENT SYSTEM ASSESSMENT REPORT SUPPLIER/ SUBCONTRACTOR SUPPLIER/ SUBCONTRACTOR NAME: ADDRESS: CITY AND STATE: ZIP CODE: SUPPLIER/MANUFACTURER NO PHONE: DIVISION:
NERC Cyber Security Standards
SANS January, 2008 Stan Johnson Manager of Situation Awareness and Infrastructure Security [email protected] 609-452-8060 Agenda History and Status of Applicable Entities Definitions High Level of
GROUND DETECTION CIRCUITS FOR STATIONARY APPLICATIONS (IN PLAIN DOWN TO EARTH LANGUAGE)
GROUND DETECTION CIRCUITS FOR STATIONARY APPLICATIONS (IN PLAIN DOWN TO EARTH LANGUAGE) Matthew Theriault Designer Hindle Power Inc. Easton, PA SCOPE AND PURPOSE OF THE PAPER Why do we bother to monitor
Alberta Reliability Standard Cyber Security Personnel & Training CIP-004-AB-5.1
Alberta Reliability Stard A. Introduction 1. Title: 2. Number: 3. Purpose: To minimize the risk against compromise that could lead to misoperation or instability in the bulk electric system from individuals
1.1 ANNUAL PREVENTIVE MAINTENANCE VISIT
Maintenance Service - 1 - Lead Acid Battery Frame On-Site Warranty Statement of Work 1.0 Executive Summary Lead Acid Battery Frame On-Site Warranty Service Service Table of Contents 1.0 Executive Summary
FA-300 Series. LCD Fire Alarm Control Panel. User Guide. LT-954 Rev. 0.1 February 2013. FA-300 SERIES Fire Alarm Control Panel
ABC DEF GHI JKL MNO PQR STU YZ WXY FA-300 Series LCD Fire Alarm Control Panel Advanced Life Safety Solutions System Normal 10:36AM WED 2003-10-01 SYSTEM RESET A.C. ON ALARM SUPV TRBL CPU FAIL SIGNAL SILENCE
TOTAL QUALITY MANAGEMENT II QUALITY AUDIT
TOTAL QUALITY MANAGEMENT II Chapter 13: QUALITY AUDIT Dr. Shyamal Gomes Introduction: The term audit was defined in the 16th Century as the official examination of the accounts with verification by reference
Understanding Fire Alarm Requirements & Inspections. Presented By Bill Conroy Technical Sales For Briscoe Protective Systems Inc
Understanding Fire Alarm Requirements & Inspections Presented By Bill Conroy Technical Sales For Briscoe Protective Systems Inc Introduction Fire Alarm Requirements are structured through a system of codes.
Nuclear Power Plant Electrical Power Supply System Requirements
1 Nuclear Power Plant Electrical Power Supply System Requirements Željko Jurković, Krško NPP, [email protected] Abstract Various regulations and standards require from electrical power system of the
DNV GL Assessment Checklist ISO 9001:2015
DNV GL Assessment Checklist ISO 9001:2015 Rev 0 - December 2015 4 Context of the Organization No. Question Proc. Ref. Comments 4.1 Understanding the Organization and its context 1 Has the organization
Kommunikationszubehör für USV PROTECT C. / C. R / 1. / 1.M Communication accessory for UPS PROTECT C. / C. R / 1. / 1.M
Kommunikationszubehör für USV PROTECT C. / C. R /. /.M Communication accessory for UPS PROTECT C. / C. R /. /.M Einsteckkarte pot.-freie Kontakte Slotcard potential - free contacts AEG Power Solutions
ISO 9001:2000 Gap Analysis Checklist
ISO 9001:2000 Gap Analysis Checklist Type: Assessor: ISO 9001 REQUIREMENTS STATUS ACTION/COMMENTS 4 Quality Management System 4.1 General Requirements Processes needed for the quality management system
Quality Management System Manual
Effective Date: 03/08/2011 Page: 1 of 17 Quality Management System Manual Thomas C. West Eric Weagle Stephen Oliver President ISO Management General Manager Representative Effective Date: 03/08/2011 Page:
A. Introduction. B. Requirements. Standard PER-005-1 System Personnel Training
A. Introduction 1. Title: System Personnel Training 2. Number: PER-005-1 3. Purpose: To ensure that System Operators performing real-time, reliability-related tasks on the North American Bulk Electric
Alberta Reliability Standard Cyber Security Physical Security of BES Cyber Systems CIP-006-AB-5
Alberta Reliability Stard Final Proposed Draft Version 2.0 September 9, 2014 A. Introduction 1. Title: 2. Number: 3. Purpose: To manage physical access to BES cyber systems by specifying a physical security
Alarm Management. July 2012 / White paper. Make the most of your energy SM
Alarm Management July 2012 / White paper Make the most of your energy SM Summary Executive summary... p 1 Introduction... p 2 Control room management best practices today... p 4 Alarm management requirements...
Cyber Security Standards Update: Version 5
Cyber Security Standards Update: Version 5 January 17, 2013 Scott Mix, CISSP CIP Technical Manager Agenda Version 5 Impact Levels Format Features 2 RELIABILITY ACCOUNTABILITY CIP Standards Version 5 CIP
Fuld Skolerapport for Hunderupskolen, i Odense kommune, for skoleår 2013/2014 for klassetrin(ene) 7. med reference Tilsvarende klassetrin i kommunen
Side 1 af 43 Side 2 af 43 Side 3 af 43 Side 4 af 43 Side 5 af 43 Side 6 af 43 Side 7 af 43 Side 8 af 43 Side 9 af 43 Side 10 af 43 Side 11 af 43 Side 12 af 43 Side 13 af 43 Side 14 af 43 Side 15 af 43
Fuld Skolerapport for Søhusskolen, i Odense kommune, for skoleår 2013/2014 for klassetrin(ene) 9. med reference Tilsvarende klassetrin i kommunen
Side 1 af 41 Side 2 af 41 Side 3 af 41 Side 4 af 41 Side 5 af 41 Side 6 af 41 Side 7 af 41 Side 8 af 41 Side 9 af 41 Side 10 af 41 Side 11 af 41 Side 12 af 41 Side 13 af 41 Side 14 af 41 Side 15 af 41
DC UPS. RTB.e 50-1000 A. IMB.e/ITB.e 5-200 kva. E2001.e/E3001.e 5-200 kva. Input voltage: 110/125/220 Vdc. 115/120/230 Vac, 1-phase (IMB.
Oil & Gas Energy Catalogue DC UPS RTB.e 50-1000 A 3 phase rectifier battery chargers voltage: 400 Vac, 3-phase, 50/60 Hz voltage: 24/48/110/220 Vdc RMB.e/RCB.e 50-100-150 A 1 and 3 phase compact rectifier
Alberta Reliability Standard Cyber Security Security Management Controls CIP-003-AB-5
A. Introduction 1. Title: 2. Number: 3. Purpose: To specify consistent and sustainable security management controls that establish responsibility and accountability to protect BES cyber systems against
Office of the Register of Wills Baltimore County, Maryland
Audit Report Office of the Register of Wills Baltimore County, Maryland April 2002 This report and any related follow-up correspondence are available to the public. Alternate formats may also be requested
ISO 9001 : 2008 QUALITY MANAGEMENT SYSTEM AUDIT CHECK LIST INTRODUCTION
INTRODUCTION What auditors should look for: the items listed in these headings that the ISO requirement is met that the requirement is met in the manner described in the organization's documentation Page
Weather Direct Displays show Lost Forecast (blank boxes in the picture icons)
Weather Direct Displays show Lost Forecast (blank boxes in the picture icons) Many routine events can cause a Lost Forecast situation. Examples include: Power outage Change batteries Internet down in your
INSPECTION AND TESTING FORM
INSPECTION AND TESTING FORM SERVICE ORGANIZATION PROPERTY NAME (USER) DATE: 08-04-15 TIME: 8:00 Name: Siemens Industries Inc. Name: Kcvtcs Madisonville Tech, School Bldg. Address: 2700 Stanley Gault Pkwy
MISO Annual Compliance Program Update
MISO Annual Compliance Program Update Corporate Governance & Strategic Planning Committee April 2013 Presented by Lori A. Spence 0 Table of Contents TOPIC SLIDES General Board Obligations 2 Board Compliance
Standard CIP 004 3a Cyber Security Personnel and Training
A. Introduction 1. Title: Cyber Security Personnel & Training 2. Number: CIP-004-3a 3. Purpose: Standard CIP-004-3 requires that personnel having authorized cyber or authorized unescorted physical access
Connecting your Victron product to a computer with VE Configure
Connecting your Victron product to a computer with VE Configure www.victronenergy.com VE configure II is a program used to configure settings/options on a Multi or Quattro. It is necessary to know several
SNMP Web Management. User s Manual For SNMP Web Card/Box
SNMP Web Management User s Manual For SNMP Web Card/Box Management Software for Off-Grid Inverter Version: 1.2 Table of Contents 1. Overview... 1 1.1 Introduction... 1 1.2 Features... 1 1.3 Overlook...
ISO 9001:2008 Clause 8.2.2 PR018 Internal Audit Procedure
ISO 9001:2008 Clause 8.2.2 PR018 Internal Audit Procedure Strode Park Foundation Page 1 of 9 Approvals The signatures below certify that this procedure has been reviewed and accepted, and demonstrates
Achieving Operational Efficiencies through On-Line Substation Monitoring. Vince Polsoni Powerstream Inc. Manager Station Sustainment EDIST 2016
Achieving Operational Efficiencies through On-Line Substation Monitoring Vince Polsoni Powerstream Inc. Manager Station Sustainment EDIST 2016 1 Agenda Maintenance Monitoring Equipment CMMS Data Historian
Programming Logic controllers
Programming Logic controllers Programmable Logic Controller (PLC) is a microprocessor based system that uses programmable memory to store instructions and implement functions such as logic, sequencing,
AGRI-ALERT 128 TOUCH AGRI-ALERT 800EZE ALARM SYSTEMS
AGRI-ALERT 128 TOUCH AGRI-ALERT 800EZE ALARM SYSTEMS AGRI-ALERT ALARM SYSTEMS Peace of Mind Agri-Alert is a complete alarm system for monitoring temperature, power, feed and watering systems, burglary,
OBOA 2009 Huntsville, ON Overview of ULC Standards Affecting Building Occupancy Alan Cavers Area Manager Fire & Security Systems Group
OBOA 2009 Huntsville, ON Overview of ULC Standards Affecting Building Occupancy Alan Cavers Area Manager Fire & Security Systems Group Course Title: Rev Date Agenda Introduction to Underwriters Laboratories
GSM ATT Modules Simply effective remote control
GSM ATT Modules Simply effective remote control To control electrical loads via mobile phone The benefits Remote management of electrical devices is an increasingly widespread requirement in residential
DIALER SPECIFICATION VERBATIM MODULAR SERIES VSS
DIALER SPECIFICATION VERBATIM MODULAR SERIES VSS 1. Description and Phone Number Dialing: The dialer shall be a solid state component capable of dialing up to 16 telephone numbers, each up to 60 digits
Central Station Interface with Fire Alarm and the Relevant Codes & Standards
Central Station Interface with Fire Alarm and the Relevant Codes & Standards By: Kim Caron Director of Business Development Communication Paths History Panel Testing Requirements ULC Listed Station requirements
GUIDE TO IMPLEMENTING A REGULATORY FOOD SAFETY AUDITOR SYSTEM
GUIDE TO IMPLEMENTING A REGULATORY FOOD SAFETY AUDITOR SYSTEM FEBRUARY 2016 2 Contents Introduction... 4 Scope and objectives... 5 Scope... 5 Objectives... 5 Responsibilities... 5 The role of the licensee
Temperature & Humidity SMS Alert Controller
Temperature & Humidity Alert Controller METERS 3 simple steps starting the unit: Insert the SIM card Plug in the sensors connectors Connect the AC power cord. Specifications: AC 90~260V Auto Select Internal
Mixing Sodium and Lead Battery Technologies in Telecom Applications
Mixing Sodium and Lead Battery Technologies in Telecom Applications Paul Smith Shanon Kolasienski Technical Marketing Manager Application Engineer GE Critical Power GE Energy Storage Plano, TX 75074 Schenectady,
PK-01. Standalone door control module. SATEL sp. z o.o. ul. Schuberta 79 80-172 Gdańsk POLAND tel. + 48 58 320 94 00
Standalone door control module PK-01 Firmware version 1.00 pk-01_en 06/12 SATEL sp. z o.o. ul. Schuberta 79 80-172 Gdańsk POLAND tel. + 48 58 320 94 00 [email protected] www.satel.eu WARNINGS Read carefully
A Consumer Guide to Purchasing a Burglar Alarm System and Understanding False Alarms
A Consumer Guide to Purchasing a Burglar Alarm System and Understanding False Alarms Produced by the False Alarm Reduction Association (FARA) May not be reproduced without the expressed, written consent
White Paper. Why Cellular as a Single Transmission Path meets the Requirements of NFPA 72. The Gradual Demise of POTS
White Paper Why Cellular as a Single Transmission Path meets the Requirements of NFPA 72 The purpose of this white paper is to provide documentation supporting the use of cellular as a single communication
INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT
INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT FIRE EXTINGUISHERS,SPRINKLER SYSTEMS AND FIRE ALARMS Attachment #1 Inspection of Fire Extinguishers Fire Extinguishers must be tested according
AUDITING A BCP PLAN. Thomas Bronack Auditing a BCP Plan presentation Page: 1
AUDITING A BCP PLAN Thomas Bronack Auditing a BCP Plan presentation Page: 1 What are the Objectives of a Good BCP Plan Protect employees Restore critical business processes or functions to minimize the
Entity Name ( Acronym) NCRnnnnn Risk Assessment Questionnaire
Entity Name ( Acronym) NCRnnnnn Risk Assessment Questionnaire Upcoming Audit Date: March 16, 2015 Upcoming Audit Type: O&P Audit Start of Audit Period: March 16, 2012 Date Submitted: Table of Contents
ATTACHMENT G. Network Operating Agreement
ATTACHMENT G Network Operating Agreement 1. PURPOSE OF NETWORK OPERATING AGREEMENT The purpose of this Agreement is to identify contractual requirements related to Network Integration Transmission Service
Chapter 8 ALARM SYSTEMS. [HISTORY: Adopted 5-18-2004 by the Annual Town Meeting, Art. 27. Amendments noted where applicable.] GENERAL REFERENCES
Chapter 8 ALARM SYSTEMS [HISTORY: Adopted 5-18-2004 by the Annual Town Meeting, Art. 27. Amendments noted where applicable.] Noise -- See Ch. 40. GENERAL REFERENCES ~ 8-1. Title and purpose. A. This bylaw
Fire Alarm Trainee Log Book
Fire Alarm Trainee Log Book this page is intentionally left blank canadian fire alarm association l association canadienne d alarme incendie PREFACE This training record document was developed by the Canadian
Risks and Controls for VAR-001-4 and EOP-004-2. Richard Shiflett Ruchi Ankleshwaria
Risks and Controls for VAR-001-4 and EOP-004-2 Richard Shiflett Ruchi Ankleshwaria 2 Introductions Richard Shiflett Compliance Risk Engineer Joined WECC in February 2014 11 years experience with Bureau
Generation Interconnection Feasibility Study Report-Web Version. PJM Generation Interconnection Request Queue Position Z1-055
Generation Interconnection Feasibility Study Report-Web Version For PJM Generation Interconnection Request Queue Position Z1-055 South Bend Generation Project March 2014 PJM Interconnection 2014. All rights
Module 15: Nonconformance And Corrective And Preventive Action
Module 15: Nonconformance And Corrective And Preventive Action Guidance...15-2 Figure 15-1: Root Cause Diagram...15-3 Tools and Forms...15-6 Tool 15-1: Corrective & Preventive Action Worksheet...15-6 Tool
Loop Start or Ground Start?
Fire Alarm Notebook by Dean K. Wilson. P.E. Page 1 Loop Start or Ground Start? by Dean K. Wilson, P.E. Question: The new telephone system installed in our office building has telephone voice mail. To signal
EP 95 00 30 03 SP RAILCORP NETWORK MANAGEMENT PLAN CHAPTER 2 - CUSTOMER INSTALLATION SAFETY. Authorised by: Neal Hook Chief Engineer Electrical
Engineering Standard Electrical RAILCORP NETWORK MANAGEMENT PLAN CHAPTER 2 - CUSTOMER INSTALLATION SAFETY Owner: Approved by: Chief Engineer, Electrical Neal Hook Chief Engineer Electrical Authorised by:
Audit Report AS/NZS ISO 9001:2008. RRW and Co Pty Ltd trading as National On Site Training
Audit Report AS/NZS ISO 9001:2008 RRW and Co Pty Ltd trading as National On Site Training AUDIT D E T A I L S Invoice Reference Number Certificate Number Review Date/s Review Time Hours S12627 158 10 th
ISO-9001:2000 Quality Management Systems
ISO-9001:2000 Quality Management Systems REQUIREMENTS 10/10/2003 ISO-9001:2000 Requirements 1 Process Based Approach C U S MANAGEMENT RESPONSIBILITY RESOURCE MANAGEMENT C U S T O M Requirements PRODUCT
3 Terms and definitions 3.5 client organization whose management system is being audited for certification purposes
3 Terms and definitions 3.4 third-party certification audit audit carried out by an auditing organization independent of the client and the user, for the purpose of certifying the client's management system
Master/Local Control Center Procedure No. 13 (M/LCC 13) Communications Between the ISO and Local Control Centers
Master/LCC Procedure No. 13 - Communications Master/Local Control Center Procedure No. 13 (M/LCC 13) Communications 1. References... 2 2. Background... 3 3. Responsibilities... 3 4. Procedure... 4 4.1
ERCOT Design and Implementation of Internal Controls and benefits for NERC CMEP/RAI
ERCOT Design and Implementation of Internal Controls and benefits for NERC CMEP/RAI Matt Mereness, ERCOT Compliance Director August 2015 Anfield Summit Outline of discussion ERCOT Background Business Case
221.01 PURPOSE AND GENERAL POLICY...221-1 221.02 DEFINITIONS...221-1. 221.03 ALARM PERMITS...221-1 (1) Permit Fees...221-2
TABLE OF CONTENTS ALARMS ORDINANCE 221.01 PURPOSE AND GENERAL POLICY...221-1 221.02 DEFINITIONS...221-1 221.03 ALARM PERMITS...221-1 (1) Permit Fees...221-2 221.04 CENTRAL ANSWERING STATION ALARM...221-2
SMS GSM Alarm Messenger
SMS GSM Alarm Messenger Data Logging Alarm Input Relay Output Voice Temperature Humidity Analog Input Capture and Send Data via SMS Report triggered alarm via SMS Output triggered via SMS Auto pick up
UNCONTROLLED COPY FOR REFERENCE ONLY
CLOVER MACHINE AND MFG. 800 MATHEW ST. #101 SANTA CLARA, CA 95050 727-3380 727-7015 fax REVISION: DATE: PAGE 1 OF 45 QUALITY POLICY MANUAL DISTRIBUTION LIST: President Purchasing Manager Vice President
COMMUNICATIONS SYSTEMS ANALYST 2 2168
COMMUNICATIONS SYSTEMS ANALYST 2 2168 GENERAL DESCRIPTION OF CLASS The COMMUNICATIONS SYSTEMS ANALYST 2 employs an extensive knowledge of electronics theory and practice while performing highly scientific
SPECIFICATION COG-2007
Cleco Power LLC SPECIFICATION COG-2007 FOR PARALLEL OPPERATION OF CUSTOMER-OWNED GENERATION ON CLECO S ELECTRICAL SYSTEM Revised: March 7, 2014 CONTENTS ITEM NO. TITLE PAGE NO. 1.0 Scope 3 2.0 Policy On
REPUBLIC OF. Marine Notice THE MARSHALL ISLANDS No. 2-011-18 OFFICE OF THE MARITIME ADMINISTRATOR Rev. 8/06
REPUBLIC OF Marine Notice THE MARSHALL ISLANDS No. 2-011-18 OFFICE OF THE MARITIME ADMINISTRATOR Rev. 8/06 TO: SUBJECT: ALL SHIPOWNERS, OPERATORS, MASTERS AND OFFICERS OF MERCHANT SHIPS, AND RECOGNIZED
D. Infrared scanning reports with pictures printed in a final report with any deficiencies and actions taken to rectify.
SECTION 263354 STATIC UPS TESTING AND COMMISSIONING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes 1. System start-up services. 2. Battery charging. 3. Load bank testing. 4. Battery load testing. 5.
ORDINANCE NO. 1072. The City Council of the City of Los Banos does ordain as follows:
ORDINANCE NO. 1072 AN ORDINANCE OF THE CITY COUNCIL OF THE CITY OF LOS BANOS ADDING CHAPTER 14B, ALARMS AND ALARM SYSTEMS, TO THE LOS BANOS MUNICIPAL CODE Recitals The City Council of the City of Los Banos
NABL accreditation is a formal recognition of the technical competence of a medical testing laboratory
NABL accreditation is a formal recognition of the technical competence of a medical testing laboratory Third party assessment NABL has Mutual Recognition Arrangement with APLAC and ILAC NABL accredited
PRV Outreach MediPASS Enrollment Overrides (Via Fax or E-mail Only)
PRV Outreach MediPASS Enrollment Overrides (Via Fax or E-mail Only) Purpose: The purpose of this procedure is to accept MediPASS enrollment overrides from MediPASS providers via fax or email who have enrollment
Configuring H.323 over Port Network Address Translation (PNAT) for Avaya IP Endpoints using the Avaya SG200 Security Gateway - Issue 1.
Configuring H.323 over Port Network Address Translation (PNAT) for Avaya IP Endpoints using the Avaya SG200 Security Gateway - Issue 1.0 Abstract These Application Notes describe how to configure the Avaya
Standard CIP 003 1 Cyber Security Security Management Controls
A. Introduction 1. Title: Cyber Security Security Management Controls 2. Number: CIP-003-1 3. Purpose: Standard CIP-003 requires that Responsible Entities have minimum security management controls in place
INTERNATIONAL STANDARD ON AUDITING 610 USING THE WORK OF INTERNAL AUDITORS CONTENTS
INTERNATIONAL STANDARD ON 610 USING THE WORK OF INTERNAL AUDITORS (Effective for audits of financial statements for periods beginning on or after December 15, 2009) CONTENTS Paragraph Introduction Scope
Displayport Extender via 2 multimode fibers LC Duplex Connector Extends Displayport Link up to 200 meters
Description Displayport combines the audio and video through an interface. It supports high resolution displays and multiple displays with a single cable, and increases the efficiency and bandwidth of
TESTING, INSPECTION, AND MAINTENANCE FREQUENCIES FOR FIRE DETECTION AND ALARM SYSTEMS
TESTING, INSPECTION, AND MAINTENANCE FREQUENCIES FOR FIRE DETECTION AND ALARM SYSTEMS The following information regarding testing frequencies for fire detection and alarm systems. All of the following