Business Case for Battery Monitoring
|
|
|
- Claud Griffin
- 9 years ago
- Views:
Transcription
1 WHITE PAPER Business Case for Battery Monitoring Why condition-based monitoring allows you to predict and preempt issues versus risk and react TONY CAMPITELLI VP Marketing, Canara, Inc. June, 2013
2 Table of Contents Introduction 3 Overview 3 Canara s Data Center Customers 3 Battery Failure 4 Battery Preventative Maintenance 6 Extending Life of the Battery Asset 6 The Effect of Ripple Current on Battery Life 8 UPS (Uninterruptible Power Systems) 8 Initial Load Testing 10 Return on Investment 11 Conclusion 12 Table of Figures/Tables Figure 1: UPS System Failure is the #1 cause of data center outages 3 Figure 2: Battery Failure caused by Sudden Impedance/Resistance Rise 5 Table 1: Benefits of battery replacement on condition versus time 7 Figure 3: Typical UPS topology 8 Figure 4: Inverter Output Sine wave 9 Figure 5: Rectification of AC voltage producing AC ripple 9 Figure 6: Load test illustrating battery failure 10 CANARA PAGE 02
3 INTRODUCTION Overview In today s data reliant environment, no element can be overlooked in support of total uptime and maximizing your assets. Canara is a full-service solutions provider serving global markets with turnkey battery backup systems and predictive monitoring and maintenance services to ensure against systems failure. The battery industry veterans who founded Canara realize that multiple vendors and patched together systems put service level agreements at risk and shorten the life of the battery asset investment significantly. That is why Canara created one superior solution for the entire battery lifecycle and united all the critical elements into one seamless package. Our turnkey solution combines best in class VRLA batteries, easy-to-access cabinets, professional installation in our factory environment or in the field, integration of battery monitoring hardware, remote monitoring, weekly reporting and data analysis, and regular preventive and corrective maintenance to help our customers achieve 100% uptime. Does it work? BUSINESS CASE FOR BATTERY MONITORING WHITE PAPER While UPS failure is the #1 cause of Data Center outages, Canara customers have never experienced an unexpected battery failure since the Canara Solution provides complete system visibility to predict and preempt UPS & battery failure and avoid the #1 cause of data center outages. Furthermore, Canara customers realize up to 35% extended ROI on their battery investment with our conditionsbased predictive monitoring and maintenance program. Equipment Failure 5% Other 5% Generator Failure 10% UPS System Failure 29% Weather Related 12% Water, Heat or CRAC Failure 15% Accidental / Human Error 24% Figure 1: UPS System Failure is the #1 cause of data center outages 1
4 Canara s Data Center Customers Canara s customer base of over 100 organizations is rapidly evolving as the integrated, modular solutions approach is adopted by a range of specifying engineers, end users, market conditions and sensible business models. The core business is compromised of the world s leading data centers and enterprise organizations including Charles Schwab, Cologix, CSC, Digital Realty Trust, Equinix, Fidelity Investments, RagingWire, Sabey, Savvis and Qwest (both CenturyLink companies), Server Farm Realty and ViaWest. Battery Failure One failure in a single battery string can have disastrous and costly consequences from both an impact to negative corporate image to the cost of a customer load loss. Even in a 2N environment one weak battery in each string can and has caused UPS load loss. UPS load loss failures are primarily caused by due to weak or failed batteries as they are called upon to carry the load. Furthermore, batteries can fail in as little as a few days making quarterly or semiannual maintenance visits ineffective. Sudden Impedance/Resistance Rise (SIRR) in a Stationary Battery is indicated by an exponential rise of internal resistance over a period of a few days to 1-2 weeks. SIRR, which can occur at anytime in the serviceable life of a battery, is a common form of battery failure (from our experience, about 15% of battery failures are due to SIRR). A SIRR battery jar (if not replaced) can cause an open circuit, jeopardizing the integrity and reliability of the entire UPS, DC Plant, Switchgear or Generator Start battery systems. In the worst case, a failed open jar can even explode under load conditions, jeopardizing integrity of surrounding equipment and most importantly life safety. The following graph shows a battery failure that happened within a few days as illustrated by the sudden resistance rise and corresponding drop in voltage. (A) Unit Voltage trending reveals sudden voltage drop (D) Replacement Unit Voltage is tracked for proper charging (C) (B) Unit Ohmic trending reveals sudden Ohmic rise (typically 1-2 weeks earlier than voltage drop) (E) Replacement Unit Ohmic trending is tracked to ensure exposure is eliminated Figure 2: Battery Failure caused by Sudden Impedance/Resistance Rise CANARA PAGE 04
5 CANARA SOLUTION With the installation of a comprehensive Battery Monitoring System and Canara s patented trending battery management software, battery trends can be predicted in advance thereby eliminating the risk of an SIRR as noted above and subsequent UPS load loss. A stepped solution: A) Stationary battery monitor data on unit voltage measurements is gathered and then embedded and trended in our monitoring system which detects voltage drop in an individual battery unit which our NOC and site personnel can see clearly from any web browser. In this case, you can see that this happened in a matter of days. B) Stationary battery monitor data on same unit s ohmic measurements is gathered and then embedded and trended in our monitoring system which confirms that the battery (or interconnect torque/sulfation) requires conditions based maintenance. BUSINESS CASE FOR BATTERY MONITORING WHITE PAPER C) Right away, our (or our partners ) field technicians are dispatched to verify with a handheld testing unit and visual/physical inspection and replace the unit prior to it compromising the strings ability to carry a load in a discharge event. This is the critical intervention period to perform conditions-based pre-emptive maintenance. D) The replacement unit is watched carefully to ensure its voltage charge trend is normal and the new battery is integrating with the string properly. E) The replacement unit is watched carefully to ensure also that its ohmic trend is within expected range to ensure that the risk exposure has been completely eliminated. Note: The above steps are possible with any major brand of battery monitor (Alber, Btech, Cellwatch, Canara), however the Canara monitor also measures and trends the internal temperature of each battery and ripple voltage/current at each battery point to provide much deeper insight into the condition. In this case, two additional trend graphs per battery unit are provided visually to assist onsite personnel and our Monitoring Operation Center staff in judgment calls of how and how urgent to take action.
6 Battery Preventative Maintenance Following IEEE it is recommended that, if possible, the following inspections be done under normal float conditions and that measurements and observations should be recorded for future comparisons: MONTHLY Overall float voltage measured at the battery terminals Charger output current and voltage Ambient temperature Visual individual cell/unit condition check to include - Cell/unit integrity for evidence of corrosion at terminals, connections racks, or cabinet - General appearance and cleanliness of the battery, the battery rack or cabinet, and battery area, including accessibility - Cover integrity and check for cracks in cell/unit or leakage of electrolyte Excessive jar/cover distortion DC float current (per string) QUARTERLY Cell/unit internal ohmic values Temperature of the negative terminal of each cell/unit of the battery Voltage of each cell/unit The reliability of any UPS system can be compromised if this program recommended by IEEE is compromised or omitted. CANARA SOLUTION With the installation of a comprehensive stationary Battery Monitoring System these parameters (minus the visual inspections) are measured four times per day, thus allowing you to reduce your time-based Preventative Maintenance scope to once annually and migrate to a continuous Preventative Maintenance schedule based on actual need. CANARA PAGE 06
7 Extending Life of the Battery Asset Without access to comprehensive battery data over the lifecycle of the asset including initial load test results, initial and trended ohmic values (from multiple daily reads), temperature history, voltage, battery discharge events, depth of discharge, number of individual battery replacements within a string, etc. it is very difficult to determine when to replace an individual battery and more importantly when to replace an entire battery string. Since this data is not available from quarterly battery maintenance inspections, a standard industry practice has been to perform time-based replacements vs. needs based replacements. The net result of this legacy approach is that many battery strings are replaced pre-maturely and capital costs are not fully realized through amortization over the true effective life of the string. For example, the following table from a recent data center battery replacement project involving 10 UPS modules underscores the value of a data based replacement program using empirical data and analysis vs. a time based program. Using a time-based replacement model of four (4) years would have, in the cases of UPS 1 & 2, exposed the site to a load-loss risk (UPS downtime) with strings lasting only 26 & 22 months respectively, while strings 3 & 4 clearly show the benefit of maximizing the capital cost of the investment out past six years, as in the case of UPS 5-9. Note that these are all batteries are at different locations but for the same customer and the same make and model. BUSINESS CASE FOR BATTERY MONITORING WHITE PAPER UPS Battery Count Type Location Date Code Actual Replacement Age (Years) Benefits vs. standard 4-year replacement interval C&D NJ 11/1/ Avoided risk to connected load C&D NJ 3/1/ Avoided risk to connected load C&D NJ 9/1/ Extended life by 4 months C&D NJ 9/5/ Extended life by 4 months C&D LA 11/15/ Extended life by over 2 years C&D LA 10/15/ Extended life by over 2 years C&D LA 10/15/ Extended life by over 2 years C&D LA 11/15/ Extended life by over 2 years C&D LA 11/15/ Extended life by over 2 years C&D LA 11/1/ Extended life by over 1 year Table 1: Benefits of battery replacement on condition versus time CANARA SOLUTION Combining a stationary Battery Monitoring System with Canara s cloud-based Monitoring Service allows us to collect several key characteristics of a battery string to actually predict the number of years/months of expected remaining service life to each individual string in your infrastructure. This critical asset management function offered by Canara, takes the guesswork out of the equation as strings are replaced upon condition and not time. This method also ensures replacements happen on a planned budget cycle so you can avoid any budget surprises. Our proprietary algorithms for calculating remaining service life include characteristics of temperature history, average ohmic measurement/trend, number of discharges, depth of discharges, battery model/make, UPS Load %, and several other factors.
8 The Effect of Ripple Current on Battery Life One of the growing concerns in the industry today is how excess AC ripple can shorten the service life of batteries. An additional concern is, as UPS capacitors start weakening, they can explode and cause collateral damage to the UPS as well as load loss. One of the major parameters that affect the service life of battery systems is ripple voltage and current. UPS systems place the highest levels of ripple on batteries due to the noisy nature of the rectification and inversion process of UPS systems. Other system types such as Telecom equipment produce low levels of ripple. However, the presence of excessive ripple, particularly in a Telecom or any 48VDC environment, may be an indication of a system malfunctioning. In order to understand the nature of ripple generation, a brief tutorial is presented below on the difference between UPS and DC power systems: UPS (Uninterruptible Power Systems) UPS systems provide uninterrupted AC power for computer networks or servers. The UPS rectifier converts the Utility AC voltage to a DC voltage to charge the batteries and also feed the inverter. The inverter feeds an AC electrical load. See Figure 3. AC POWER FROM UTILITY + _ RECTIFIER DC POWER (BUS) _ + INVERTER AC POWER TO ELECTRICAL LOAD BATTERY SYSTEM Figure 3: Typical UPS topology Figure 4: Inverter Output Sine wave Figure 4 illustrates how the output of a UPS system is a regenerated AC sine wave derived from a square wave (filtered). The Insulated Gate Bipolar Transistors (IGBT) turns on and off reproducing the sine wave. AC capacitors smooth out the sine wave. CANARA PAGE 08
9 Figure 5 illustrates where AC ripple occurs as a by product of the rectification process, when converting AC voltage to DC voltage. AC ripple are the filtered remnants of the AC waveform riding over the top of the DC output voltage passing through a DC capacitor network. Figure 5: Rectification of AC voltage producing AC ripple The presence of AC ripple voltage leads to shallow discharge cycles producing hydrogen gas, sulfation on the battery plates and heat within the cell due to exothermic electrochemical reactions. As AC ripple voltage increases, AC ripple current rises. An increase of AC ripple current also adds to the internal heat generated inside the battery. Ultimately, excessive ripple current leads to excessive gassing, heat and dry-out, consequently diminishing the service life of the battery. BUSINESS CASE FOR BATTERY MONITORING WHITE PAPER Excessive AC ripple voltage can also be indicative of failing capacitors that can potentially explode and cause collateral damage to personnel, UPS equipment and UPS load loss. CANARA SOLUTION Canara provides the only solution that monitors the ripple so you can successfully prevent harmful levels of ripple voltage and current, from damaging your system s electronics and/or battery system. Initial Load Testing The best way to commission or perform a periodic test of a battery string is to perform an IEEE 1188 compliant load bank test, and gather key data from the battery monitoring system (see Figure 6 below), which performs a rapid scan of each individual battery s voltage. It is important to have Monitoring Services platform that ensures each battery monitoring system is prepared to correctly detect discharge and enter rapid scan mode to collect this critical data. With this data you can then perform a complete analysis of the resulting data and provide a detailed report of which batteries pass/fail the load testing. This ensures that weak batteries are removed from the string immediately for better warranty claim and longer life string performance.
10 In addition, this baseline data is used to monitor and predict future trends such as the ohmic rise of each individual battery and the overall trend of the battery string. Each battery is manufactured with a slightly different base ohmic value so using a generic baseline will either lead to batteries being replaced to soon or replaced too late. Further, following having accurate baseline data allows you to follow IEEE 1188, which recommends replacing batteries that reach between a 30-50% ohmic rise above their initial baseline. As illustrated in the chart below, a 10 minute load test performed at 740KW on a 1,000kVA UPS shows battery unit 74 failing the initial load test by ending at 7.71V. Figure 6: Load test illustrating battery failure CANARA SOLUTION The best way to commission or perform a periodic test of a battery string is to perform an IEEE 1188 compliant load bank test, and gather key data from the battery monitoring system, which performs a rapid scan of each individual battery s voltage. This data is then stored and analyzed in our Monitoring Services platform and an IEEE compliant load test report is generated for the customer. CANARA PAGE 10
11 Return on Investment The following ROI had been prepared based upon existing customer infrastructure in the U.S. end of 2012 and current operational costs. Canara ROI Analysis Number of UPS / Battery systems 7 Total Number of Strings 21 Total batteries per String 40 Total number of batteries to be monitored 5,880 Battery Cost $1,764,000 Battery Installation $176,400 Canara Hardware & Labor $715,406 TOTAL $2,655,806 BUSINESS CASE FOR BATTERY MONITORING WHITE PAPER 12-YEAR COSTS Non Monitored $18,778,375 Canara $14,215,982 Difference $4,562,393 Avg Savings Year $380,199 ASSUMPTIONS Model is based on 12 years, the estimated life of the UPS Non-monitored batteries replaced every 4.00 years Canara batteries replaced every 5.40 years Number of preventative maintenance visits per year with non-monitored system is 4 Number of preventative maintenance visits per year with Canara is 1
12 The ROI is achieved through savings and increased efficiency in the following areas: Reducing Preventative Maintenance Visits: Maintenance visits can be reduced from 4 to 1 per year since the Battery Monitoring system provides daily visibility into the state of health of each battery and reduces the need for costly and time consuming hand-held testing. Decreased costs associated with battery spot replacements: With visibility into each battery spot replacements can be planned in advanced and timed with pre-scheduled PM or service visits, multiple batteries can be replaced at the same time, and work can be planned in advanced so that overtime is not incurred at the site. Extending the battery life: Capital investment is optimized and batteries are replaced on an as needed basis vs. a time based (e.g. every 4 years) model. On average, battery life can be extended by 6-24 months when a Battery Monitoring Systems and Monitoring Services are deployed. Ensuring Warranty Replacements: In order to successfully claim a warranty replacement, manufacturers require batteries to be operated and be maintained within specifications. Since Canara maintains the entire data history for these systems, we are able to certify the battery history against the manufacturers specifications thus ensuring successful replacement. BUSINESS CASE FOR BATTERY MONITORING WHITE PAPER Conclusion Cloud-based monitoring coupled with predictive trending and maintenance is critical to achieving uptime; monitoring hardware alone is not enough. If you are not actively monitoring every day you are at risk of becoming an outage statistic. In fact, most organizations incur significant outage costs with an average cost just over US $500K 1. If this business case took into account the average outage cost, then the ROI would be less than 3 years. So if you re interested in: Extending battery life Reducing costs for maintenance Managing assets and accurately forecasting maintenance and string replacements Protecting your systems from thermal runaway Identifying potential UPS problems Knowing about problems before they happen Then give Canara a call or visit our website to learn how you can get the most out of your battery backup systems. 1 Ponemon Institute, Calculating the Cost of Data Center Outages, sponsored by Emerson Network Power, February 1, NORTH AMERICA 181 Third Street, Suite 150 San Rafael, CA TEL TOLL FREE FAX EMEA Festival House, Jessop Avenue Cheltenham, Glouscestershire GL50 3SH +44 (0) TEL CHINA Building 18, Area B, No. 1 Disheng North Street Yizhuang Economic and Technological Development Zone Beijing, China TEL FAX ONLINE [email protected] 2013 Canara Inc. All rights reserved. Canara and the Canara logo are trademarks of Canara. All other trademarks are the property of their respective owners V5
Executive Summary. Technical Description
Executive Summary The Cellwatch system is built using modules. The majority of the system is constructed with Data Collection Modules (DCMs). The DCMs are optically linked to Control Units (CUs) that in
Emergency Power System Services Industrial UPS, Batteries, Chargers, Inverters and Static Switches
Emergency Power System Services Industrial UPS, Batteries, Chargers, Inverters and Static Switches Downtime Is Not An Option The industrial uninterruptible power supply (UPS) is the foundation of your
1.1 ANNUAL PREVENTIVE MAINTENANCE VISIT
Maintenance Service - 1 - Lead Acid Battery Frame On-Site Warranty Statement of Work 1.0 Executive Summary Lead Acid Battery Frame On-Site Warranty Service Service Table of Contents 1.0 Executive Summary
Charger Output AC Ripple Voltage and the affect on VRLA batteries
TECHNICAL BULLETIN 41-2131 Charger Output AC Ripple Voltage and the affect on VRLA batteries Please Note: The information in this technical bulletin was developed for C&D Dynasty 12 Volt VRLA products.
Effects of AC Ripple Current on VRLA Battery Life. A Technical Note from the Experts in Business-Critical Continuity
Effects of AC Ripple Current on VRLA Battery Life A Technical Note from the Experts in Business-Critical Continuity Introduction Given the importance of battery life to UPS system users and the fact that
DC GROUND FAULT DETECTION PROVIDED FOR UNINTERRUPTIBLE POWER SUPPLIES
DC GROUND FAULT DETECTION PROVIDED FOR UNINTERRUPTIBLE POWER SUPPLIES Edward P. Rafter, P. E. Principal Tier IV Consulting Group Lee s Summit, Missouri 64064 INTRODUCTION There are concerns among owners
THE PROPER CHARGING OF STATIONARY LEAD-ACID BATTERIES. (YOUR BATTERY IS ONLY AS GOOD AS HOW YOU CHARGE IT.)
THE PROPER CHARGING OF STATIONARY LEAD-ACID BATTERIES. (YOUR BATTERY IS ONLY AS GOOD AS HOW YOU CHARGE IT.) J. Allen Byrne Engineering, Training and Tech Support Manager Interstate PowerCare, a Division
Constant Voltage Charger Selection for VRLA Batteries
TECHNICAL BULLETIN 41-2129 Constant Voltage Charger Selection for VRLA Batteries Please Note: The information in this technical bulletin was developed for C&D Dynasty 12 Volt VRLA products. While much
APPLICATION NOTE TESTING PV MICRO INVERTERS USING A FOUR QUADRANT CAPABLE PROGRAMMABLE AC POWER SOURCE FOR GRID SIMULATION. Abstract.
TESTING PV MICRO INVERTERS USING A FOUR QUADRANT CAPABLE PROGRAMMABLE AC POWER SOURCE FOR GRID SIMULATION Abstract This application note describes the four quadrant mode of operation of a linear AC Power
SMA SERVICE FOR PV POWER PLANTS
SMA SERVICE FOR PV POWER PLANTS EN Successful Projects with Sunny Central System Solutions SMA SERVICE Top Performance and Maximum Yields One thing is certain: PV power plants are investments in the future.
D. Infrared scanning reports with pictures printed in a final report with any deficiencies and actions taken to rectify.
SECTION 263354 STATIC UPS TESTING AND COMMISSIONING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes 1. System start-up services. 2. Battery charging. 3. Load bank testing. 4. Battery load testing. 5.
OHMIC MEASUREMENTS: THE HISTORY AND THE FACTS
OHMIC MEASUREMENTS: THE HISTORY AND THE FACTS Glenn Albér, President Albércorp Boca Raton, FL INTRODUCTION Internal battery ohmic measurements have been a hot topic amongst battery users and battery manufacturers
LEAD ACID BATTERY working LIFETIME STUDY
LEAD ACID BATTERY working LIFETIME STUDY Valve Regulated Lead Acid (VRLA) Batteries Overview The most common type of battery used on UPS systems and for backup of telecommunications systems. VRLA batteries
Line Reactors and AC Drives
Line Reactors and AC Drives Rockwell Automation Mequon Wisconsin Quite often, line and load reactors are installed on AC drives without a solid understanding of why or what the positive and negative consequences
Understand Hybrid Generator Battery Systems
Understand Hybrid Generator Battery Systems For off-grid applications powered by diesel generators, move to cyclic operation to save costs Telecommunications operators in Africa, India and other developing
Single Phase UPS Management, Maintenance, and Lifecycle
Single Phase UPS Management, Maintenance, and Lifecycle White Paper 210 Revision 0 by Justin Solis Executive summary How long will my battery last? and what is the best practice for maintaining my UPS?
Neve V-Series Console Restoration Technical Brief
Neve V-Series Console Restoration Technical Brief by Gregory G. Davis October 2004 2004 Audio Engineering Services LLC All Rights Reserved Unauthorized duplication or re-transmission by any means without
Enterprise Remote Monitoring
Enterprise Remote Monitoring Alarm Management, Predictive Maintenance, Advanced Network Security Services For Business-Critical Continuity Can You Really Afford Not To Know? Loss of productivity and the
Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager
Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager Introduction There is a growing trend in the UPS industry to create a highly efficient, more lightweight and smaller UPS
CHAPTER 5 PHOTOVOLTAIC SYSTEM DESIGN
CHAPTER 5 PHOTOVOLTAIC SYSTEM DESIGN 5.1 Introduction So far in the development of this research, the focus has been to estimate the available insolation at a particular location on the earth s surface
Solar Wind Microhydro Water Pumping Inverters Batteries Professional system design and installation
Solar Wind Microhydro Water Pumping Inverters Batteries Professional system design and installation BATTERY CHARGING GUIDELINES FOR GLOBAL/DAVIDSON TUBULAR PLATE BATTERIES Introduction Your Global/Davidson
The Different Types of UPS Systems
Systems White Paper 1 Revision 6 by Neil Rasmussen Contents Click on a section to jump to it > Executive summary There is much confusion in the marketplace about the different types of UPS systems and
UNINTERRUPTIBLE POWER SUPPLIES >9900AUPS UNINTERRUPTIBLE POWER SUPPLIES
UNINTERRUPTIBLE POWER SUPPLIES 9900A >9900AUPS UNINTERRUPTIBLE POWER SUPPLIES 9900A The 9900A UPS system uses the most advanced IGBT in both the converter and inverter with Digital Signal Processor (DSP)
Liebert GXT MT+ CX UPS, 1000VA - 3000VA Intelligent, Reliable UPS Protection. AC Power for Business-Critical Continuity
Liebert GXT MT+ CX UPS, 1000VA - 3000VA Intelligent, Reliable UPS Protection AC Power for Business-Critical Continuity Liebert GXT MT+ CX UPS, 1000VA -3000VA Intelligent, Reliable UPS Protection Liebert
"Charging Lithium-Ion Batteries: Not All Charging Systems Are Created Equal"
"Charging Lithium-Ion Batteries: Not All Charging Systems Are Created Equal" By Scott Dearborn Principal Applications Engineer Microchip Technology Inc. 2355 West Chandler Blvd Chandler, AZ 85224 www.microchip.com
Capacitors Age and Capacitors Have an End of Life. A White Paper from the Experts in Business-Critical Continuity TM
Capacitors Age and Capacitors Have an End of Life A White Paper from the Experts in Business-Critical Continuity TM Executive Summary This white paper discusses large DC aluminum electrolytic and AC polymeric
Battery Monitoring Systems
Cellwatch is a state of the art family of battery monitoring solutions that help prevent unplanned outages on critical power backup systems. Cellwatch was a pioneer in its ability to monitor batteries
EXCERPT - THE DATA CENTER BATTERY DILEMMA
Consulting Associates, Inc. Page 1 EXCERPT - THE DATA CENTER BATTERY DILEMMA Developed by Marco W. Migliaro, PE, Life Fellow IEEE Visit: stationarybatterytraining.com esaconsulting.com Copyright 2014 by
UPS Applications and VRLA Battery Sizing
TECHNICAL BULLETIN 41-7334 UPS Applications and VRLA Battery Sizing 41-7334/0213/CD www.cdtechno.com The uninterruptable power system (UPS) is used to protect critical equipment and processes from the
KACO-monitoring. onlinecomponents.com. Integrated monitoring available. Monitor up to 32 inverters per prolog. Reliable and accurate data
KACO-monitoring watchdog insight prolog Integrated monitoring available Monitor up to 32 inverters per prolog Reliable and accurate data Email alarms to maximize uptime Historical, current and production
10 Year VRLA Battery Periodic Maintenance Instructions
TECHNICAL BULLETIN 41-7546 Valve Regulated Lead Acid Battery 20 to 200 ampere-hours capacity 10 Year VRLA Battery Periodic Maintenance Instructions 41-7546/0213/CD www.cdtechno.com General Information
LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification
08/17/12 Rev2 LTR Series General Specification 700 VA to 2.1 KVA 1.0 General LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA General Specification This specification describes the features and
CONSTRUCTING A VARIABLE POWER SUPPLY UNIT
CONSTRUCTING A VARIABLE POWER SUPPLY UNIT Building a power supply is a good way to put into practice many of the ideas we have been studying about electrical power so far. Most often, power supplies are
Variable Frequency Drives - a Comparison of VSI versus LCI Systems
Variable Frequency Drives - a Comparison of VSI versus LCI Systems Introduction TMEIC is a leader in the innovative design and manufacture of large ac variable f requency drive systems. TMEIC has been
REPORT ON THE LONG TERM RESULTS OF BATTERY CAPACITY RECOVERY PROCESSES FOR VRLA CELLS
REPORT ON THE LONG TERM RESULTS OF BATTERY CAPACITY RECOVERY PROCESSES FOR VRLA CELLS Peter J. DeMar Founder Battery Research and Testing, Inc. ABSTRACT It is well understood that premature capacity loss
Battery Technology for Data Centers and Network Rooms: Lead-Acid Battery Options
Battery Technology for Data Centers and Network Rooms: Lead-Acid Battery Options By Stephen McCluer White Paper #30 Revision 11 Executive Summary The lead-acid battery is the predominant choice for Uninterruptible
Top 12 Questions to Consider When Choosing UPS Systems for Network/Server Applications
W H I T E P A P E R Top 12 Questions to Consider When Choosing UPS Systems for Network/Server Applications Executive Summary One of the fundamental decisions in the design of data centers, server rooms
GROUND DETECTION CIRCUITS FOR STATIONARY APPLICATIONS (IN PLAIN DOWN TO EARTH LANGUAGE)
GROUND DETECTION CIRCUITS FOR STATIONARY APPLICATIONS (IN PLAIN DOWN TO EARTH LANGUAGE) Matthew Theriault Designer Hindle Power Inc. Easton, PA SCOPE AND PURPOSE OF THE PAPER Why do we bother to monitor
Power Supplies. 1.0 Power Supply Basics. www.learnabout-electronics.org. Module
Module 1 www.learnabout-electronics.org Power Supplies 1.0 Power Supply Basics What you ll learn in Module 1 Section 1.0 Power Supply Basics. Basic functions of a power supply. Safety aspects of working
Power Quality For The Digital Age INVERTING SOLAR POWER A N E N V IRONME N TA L P OT E N T I A L S W HI T E PA PER. www.ep2000.com 800.500.
Power Quality For The Digital Age INVERTING SOLAR POWER A N E N V IRONME N TA L P OT E N T I A L S W HI T E PA PER Introduction Heat in the System The modern facility has been revolutionized by advancements
2. Add the following definitions to 3.3 General Definitions and renumber 3.3 as required:
NFPA 72-2013 National Fire Alarm and Signaling Code TIA Log No. 1188 Reference: Various Sections on Battery Comment Closing Date: June 19, 2015 Submitter: Herbert Hurst, Savannah River Nuclear Solutions,
The Different Types of UPS Systems
White Paper 1 Revision 7 by Neil Rasmussen > Executive summary There is much confusion in the marketplace about the different types of UPS systems and their characteristics. Each of these UPS types is
Advanced Fuel Cells A Reliable and Green Solution to Reduce Operating Expenses of Telecommunication Networks
Advanced Fuel Cells A Reliable and Green Solution to Reduce Operating Expenses of Telecommunication Networks White Paper Anil K. Trehan, Vice President, Energy Solutions CommScope, Inc. May 28, 2013 Contents
On-line PD Monitoring Makes Good Business Sense
On-line PD Monitoring Makes Good Business Sense An essential tool for asset managers to ensure reliable operation, improve maintenance efficiency and to extend the life of their electrical assets. Executive
MoniUPS Software and Service. with an expert
MoniUPS Software and Service Monitor your UPS with an expert A service expert at your fingertips innovative remote monitoring System MoniUPS for critical applications MoniUPS is the innovative remote monitoring
UNDERSTANDING POWER FACTOR AND INPUT CURRENT HARMONICS IN SWITCHED MODE POWER SUPPLIES
UNDERSTANDING POWER FACTOR AND INPUT CURRENT HARMONICS IN SWITCHED MODE POWER SUPPLIES WHITE PAPER: TW0062 36 Newburgh Road Hackettstown, NJ 07840 Feb 2009 Alan Gobbi About the Author Alan Gobbi Alan Gobbi
Overcoming the Causes of Data Center Outages
Overcoming the Causes of Data Center Outages Executive Summary A data center s main function should be to provide constant uptime for the mission-critical applications it houses. However, unplanned outages
Automatic taper of charge rate for superior battery life through good equalization of cells and low water use rate.
*00151* FEATURES Automatic taper of charge rate for superior battery life through good equalization of cells and low water use rate. Silicon diodes with inherent surge protection operated at a conservative
BATTERY CHARGING GUIDELINES FOR 6-VOLT DEEP CYCLE BATTERIES
BATTERY CHARGING GUIDELINES FOR 6-VOLT DEEP CYCLE BATTERIES Introduction Your 6-volt deep cycle battery set has been specially formulated for long cycle life and has particular voltage and specific gravity
Condition Monitoring of equipment to improve quality of supply to customers by averting failures
Condition Monitoring of equipment to improve quality of supply to customers by averting failures Author & presenter: Patrick O Halloran BTECH Manager Technology Services at City Power Johannesburg Abstract
HyPM Fuel Cell Power Modules
HyPM Fuel Cell Power Modules HyPM XR Fuel Cell Power Module for stationary and backup power applications HyPM HD Fuel Cell Power Module for mobility applications Purpose-built to deliver the best in performance
If you accidentally get battery acid on your skin, flush it with lots of water
RV Battery Savvy To properly maintain and extend the life of your RV batteries you need to have a basic understanding of what a battery is and how it works. Batteries used in RVs are lead acid batteries.
The full wave rectifier consists of two diodes and a resister as shown in Figure
The Full-Wave Rectifier The full wave rectifier consists of two diodes and a resister as shown in Figure The transformer has a centre-tapped secondary winding. This secondary winding has a lead attached
Distributed Power, Renewables, Stored Energy and the Grid Blinkless Synchronous Inverter System
Distributed Power, Renewables, Stored Energy and the Grid Blinkless Synchronous Inverter Go Electric Inc. www.goelectricinc.com 1 Distributed Power, Renewables, Stored Energy and the Grid Blinkless Synchronous
875 Dearborn Drive Columbus, Ohio 43085 Tel: (614) 846-7500 Fax: (614) 885-3990
Selection and Sizing of Batteries for UPS Backup 875 Dearborn Drive Columbus, Ohio 43085 Tel: (614) 846-7500 Fax: (614) 885-3990 Selection and Sizing of Batteries for UPS Backup Abstract Introduction Battery
Battery Technology for Data Centers and Network Rooms: Ventilation of Lead-Acid Batteries
Battery Technology for Data Centers and Network Rooms: Ventilation of Lead-Acid White Paper 34 Revision 3 by Stephen McCluer > Executive summary Lead-acid batteries are the most widely used method of energy
High Efficiency Battery Charger using Power Components [1]
application note TPB:101 High Efficiency Battery Charger using Power Components [1] Marco Panizza Senior Applications Engineer July 2006 Contents Page Introduction 1 A Unique Converter 1 Control Scheme
LABORATORY 10 TIME AVERAGES, RMS VALUES AND THE BRIDGE RECTIFIER. Bridge Rectifier
LABORATORY 10 TIME AVERAGES, RMS VALUES AND THE BRIDGE RECTIFIER Full-wave Rectification: Bridge Rectifier For many electronic circuits, DC supply voltages are required but only AC voltages are available.
A Solar Powered Cellular Base Station
Technical Whitepaper SolarConnect Energy management solution for Base Stations A Solar Powered Cellular Base Station Many people in emerging markets like India live in rural areas with limited access to
Ametek Prestolite Power AC power / Charger / Battery terms
Ametek Prestolite Power AC power / Charger / Battery terms Basic Values: Voltage: The potential difference at the battery (DC) or at the charger input (AC) measured in Volts. Current: The rate of flow
Liebert NXC from 10 to 200 kva
Liebert NXC from 10 to 200 kva Emerson Network Power, a division of Emerson, is a global company that provides a unique combination of industry expertise, technology, and resources to make the future of
The Different Types of UPS Systems
The Different Types of UPS Systems By Neil Rasmussen White Paper #1 Revision 5 Executive Summary There is much confusion in the marketplace about the different types of UPS systems and their characteristics.
POWER. Your Partners in Availability POWER
Your Partners in Availability The Service Arm for All Liebert Products We have the industry-leading technical expertise, top onsite response times and the most sophisticated parts logistics in the industry.
Harmonics in your electrical system
Harmonics in your electrical system What they are, how they can be harmful, and what to do about them Abstract Harmonic currents, generated by non-linear electronic loads, increase power system heat losses
User s Manual AURORA 1.2K/2.2K
User s Manual AURORA 1.2K/2.2K Uninterruptible Power System Safety CAUTION This UPS utilizes voltages that may be hazardous. Do not attempt to disassemble the unit. The unit contains no user serviceable
The Effect of Regular, Skilled Preventive Maintenance on Critical Power System Reliability
The Effect of Regular, Skilled Preventive Maintenance on Critical Power System Reliability A White Paper from the Experts in Business-Critical Continuity TM Executive Summary Emerson Network Power has
Data Center Precision Cooling: The Need For A Higher Level Of Service Expertise. A White Paper from the Experts in Business-Critical Continuity
Data Center Precision Cooling: The Need For A Higher Level Of Service Expertise A White Paper from the Experts in Business-Critical Continuity Executive Summary Today s data centers are changing rapidly,
Equipment Performance Monitoring
Equipment Performance Monitoring Web-based equipment monitoring cuts costs and increases equipment uptime This document explains the process of how AMS Performance Monitor operates to enable organizations
VICOR WHITE PAPER. The Sine Amplitude Converter Topology Provides Superior Efficiency and Power Density in Intermediate Bus Architecture Applications
The Sine Amplitude Converter Topology Provides Superior Efficiency and Power Density in Intermediate Bus Architecture Applications Maurizio Salato, Applications Engineering, Vicor Corporation Contents
Offshore Platform Powered With New Electrical Motor Drive System
Offshore Platform Powered With New Electrical Motor Drive System Authors: Jan O. Lamell, M.Sc E.E. ABB Automation Technologies Presenters: Thomas Johansson, M.Sc E.E. ABB Automation Technologies Timothy
Maximizing UPS Availability
Maximizing UPS Availability A comparative assessment of UPS designs and deployment configurations for the highavailability data center By Chris Loeffler Product Manager, BladeUPS & Data Center Applications
Mixing Sodium and Lead Battery Technologies in Telecom Applications
Mixing Sodium and Lead Battery Technologies in Telecom Applications Paul Smith Shanon Kolasienski Technical Marketing Manager Application Engineer GE Critical Power GE Energy Storage Plano, TX 75074 Schenectady,
Cormant-CS Infrastructure Management versus Active Patching Solution
Cormant-CS Infrastructure Management versus Active Patching Solution Paul Goodison, CEO Cormant, Inc. Michael Salvador, Technical Solutions Manager-Data Centers This document provides a brief overview
Brochure Introducing HVDC
Brochure Introducing HVDC ABB and HVDC The world s first commercial high-voltage direct current (HVDC) link, situated between the Swedish mainland and the island Gotland, was delivered by ABB already in
EssPro Energy Storage Grid Substation The power to control energy
EssPro Energy Storage Grid Substation The power to control energy EssPro Grid gives you the power to control energy helping to keep smart grids in balance Maximizing the value and performance of energy
The Prescient Data Center Manager
May/June 2009 The Prescient Data Center Manager www.missioncriticalmagazine.com PRESCIENT The Data Center Manager How to predict standby battery life BY DAVID BROWN Today s modern UPS systems employ cutting
CATALYST Frequently Asked Questions
CATALYST Frequently Asked Questions Q: What is the CATALYST Efficiency Enhancing Controller (EEC)? A: The CATALYST is a retrofit technology for single-zone, constant-volume, roof top packaged HVAC systems.
The Quest for Energy Efficiency. A White Paper from the experts in Business-Critical Continuity
The Quest for Energy Efficiency A White Paper from the experts in Business-Critical Continuity Abstract One of the most widely discussed issues throughout the world today is the rapidly increasing price
Fast Charging Facts Enhancing use of electric lift trucks, AGVs, and other motive electric vehicles
Fast Charging Facts Enhancing use of electric lift trucks, AGVs, and other motive electric vehicles Nasser Kutkut, Ph.D. PowerDesigners USA, LLC Madison, WI Introduction Fast charging of industrial batteries
Philosophy of Topology and Components Selection for Cost and Performance in Automotive Converters.
Philosophy of Topology and Components Selection for Cost and Performance in Automotive Converters. Alexander Isurin ( [email protected] ) Alexander Cook ([email protected] ) Vanner inc. USA Abstract- This
A Practical Guide to Free Energy Devices
A Practical Guide to Free Energy Devices Device Patent No 29: Last updated: 7th October 2008 Author: Patrick J. Kelly This is a slightly reworded copy of this patent application which shows a method of
ABB PSPS Erich Steinmann; Generator control-2013
ABB PSPS Erich Steinmann; Generator control-2013 GENERATOR CONTROL THE MODULAR SOLUTION FOR GENERATORS To make sure that power is efficiently converted into electric energy, it is necessary to supervise
Modular architecture for high power UPS systems. A White Paper from the experts in Business-Critical Continuity
Modular architecture for high power UPS systems A White Paper from the experts in Business-Critical Continuity Abstract Today, more than ever before, energy efficiency and cost-savings are among the top
CUSTOMER EXPERIENCE CENTER
v CUSTOMER EXPERIENCE CENTER ABOUT THE CUSTOMER EXPERIENCE CENTER MAKE YOUR DATA CENTER AS DYNAMIC AS YOUR BUSINESS Emerson Network Power continuously strives to provide the best solutions by working collaboratively
Managing Cooling Capacity & Redundancy In Data Centers Today
Managing Cooling Capacity & Redundancy In Data Centers Today About AdaptivCOOL 15+ Years Thermal & Airflow Expertise Global Presence U.S., India, Japan, China Standards & Compliances: ISO 9001:2008 RoHS
The High Performance Floormount Indoor Package Cooling Solution. Precision Cooling for Business-Critical Continuity
Liebert HPF The High Performance Floormount Indoor Package Cooling Solution Precision Cooling for Business-Critical Continuity We re Emerson Network Power, backed by Emerson, a global company that brings
Statement Of Work. Data Center Thermography Assessment. Service. Professional Services. Table of Contents. 1.0 Executive Summary
Statement Of Work Professional Services Data Center Thermography Assessment Data Center Thermography Assessment Service 1.0 Executive Summary Table of Contents 1.0 Executive Summary 2.0 Features & Benefits
Working definitions of terms: Commercial vs. Industrial UPS Systems:
The Essential Differences Between Commercial & Industrial UPS Systems Page 1 of 8 Working definitions of terms: Commercial vs. Industrial UPS Systems: On-Line, Uninterruptible Power Systems (abbreviated:
Deep Dive on Microgrid Technologies
March 2015 Deep Dive on Microgrid Technologies 2 3 7 7 share: In the wake of Superstorm Sandy, a microgrid kept the lights on for more than for the more than 60,000 residents of Co-Op City in the northeastern
Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency
A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency
DIODE CIRCUITS LABORATORY. Fig. 8.1a Fig 8.1b
DIODE CIRCUITS LABORATORY A solid state diode consists of a junction of either dissimilar semiconductors (pn junction diode) or a metal and a semiconductor (Schottky barrier diode). Regardless of the type,
APC Smart-UPS RT. GUIDE SPECIFICATIONS FOR 3000VA, 5000VA and 6000 VA Smart-UPS RT 230VAC Uninterruptible Power Supply
APC Smart-UPS RT GUIDE SPECIFICATIONS FOR 3000VA, 5000VA and 6000 VA Smart-UPS RT 230VAC Uninterruptible Power Supply PART 1 - GENERAL 1.1 SUMMARY A. This specification describes the operation and functionality
Table Of Contents 6 6 6 7 7 8 8 9-11 12 12-13 14 15 16 17 18 19 20-21 22 22 23 24 24 24
USER S GUIDE Table Of Contents Package Contents Accessories: Sold Separately Product Specifications Intended Use Compatibility ResMed Device Warning Battery Pack Run Times Power Backup Usage Getting Started