Battery Technology for Data Centers and Network Rooms: Ventilation of Lead-Acid Batteries
|
|
|
- Jesse Douglas
- 9 years ago
- Views:
Transcription
1 Battery Technology for Data Centers and Network Rooms: Ventilation of Lead-Acid White Paper 34 Revision 3 by Stephen McCluer > Executive summary Lead-acid batteries are the most widely used method of energy reserve. Ventilation systems must address health and safety as well as performance of the battery and other equipment in a room. Valve regulated lead acid (VRLA) batteries and modular battery cartridges (MBC) do not require special battery rooms and are suitable for use in an office environment. Air changes designed for human occupancy normally exceed the requirements for VRLA and MBC ventilation. Vented (flooded) batteries, which release hydrogen gas continuously, require a dedicated battery room with ventilation separate from the rest of the building. This paper summarizes some of the factors and U.S. codes to consider when selecting and sizing a ventilation system for a facility in which stationary batteries are installed. Contents Click on a section to jump to it Introduction 2 Terminology 2 Environmental design considerations Conclusion 7 Resources 8 4 by Schneider Electric White Papers are now part of the Schneider Electric white paper library produced by Schneider Electric s Data Center Science Center [email protected]
2 Introduction The main objectives of any ventilation system are management of environmental air temperature, humidity and air quality. In a data center, or any facility in which electrical equipment and battery systems are installed, the ventilation system must address: Health safety - the air must be free of pollutants that could be toxic, corrosive, poisonous, or carcinogenic Fire safety - the system must prevent and safely remove the accumulation of gasses or aerosols that could be flammable or explosive. Equipment reliability and safety - the system must provide an environment that optimizes the performance of equipment (including both batteries and electronic equipment) and maximizes their life expectancy Human comfort Stationary lead-acid batteries are the most widely used method of energy storage for information technology rooms (data centers, network rooms). Selecting and sizing ventilation for battery systems must balance and trade off many variables. These could include different battery technologies, installation methods, operating modes, and failure modes. Terminology Battery technologies are described in detail in other white papers (see the Resources and References section at the end of this paper). The following brief overview describes different lead-acid battery technologies and how they would interact with a ventilation system. Battery types Vented lead acid batteries are commonly called flooded or wet cell batteries because of their conspicuous use of liquid electrolyte. As the name implies, this type of battery vents hydrogen continuously during normal float operation. The electrolyte is sulfuric acid diluted in water. Vented batteries are usually installed on open racks in dedicated battery rooms that have dedicated ventilation systems to prevent mixing with ventilation systems for the rest of the building Valve regulated lead acid (VRLA) batteries are the most widely used battery type because of their high power density and ease of use. VRLA batteries are considered to be sealed because they normally do not allow for the addition or loss of liquid. A vented battery can give off sixty times more gas than a VRLA battery in normal use. The term VRLA derives from the use of safety valves that allow pressure to be released when a fault condition causes internal gas to build up faster than it can be recombined. VRLA batteries can be mounted on open racks (rarely), or in cabinets (most common). Small power systems (such as single-phase UPS systems) integrate VRLA batteries inside their own enclosures. VRLA batteries can use the ventilation provided for human occupancy. Modular battery cartridges (MBC) are actually strings of VRLA batteries packaged into cartridges that can be swiftly plugged into a power system that has the appropriate mating connections. MBCs are designed for use in a data center, network room or office environment and can use the ventilation provided for human occupancy. Modes of operation All battery types work on the principle of chemical reactions between positive and negative plates. Because they have different technologies, they have different considerations for ventilation under the same operating mode. Schneider Electric Data Center Science Center White Paper 34 Rev 3 2
3 Storage stored lead-acid batteries create no heat. High ambient temperatures will shorten the storage life of all lead-acid batteries. o Vented (flooded) Vented battery units would normally be stored with shipping plugs installed, in which case they release no gas. With shipping plugs removed, vented battery units can give off minor amounts of hydrogen and oxygen due to normal evaporation of water (depending upon the amount of ambient heat and air humidity).. o VLRA and MBC create no off-gassing unless stored in extreme heat Normal mode in back-up applications the batteries are kept at a constant state of maximum potential (called float voltage) in order to ensure maximum power reserve. The constant presence of voltage causes batteries to continuously create hydrogen and oxygen. Optimum ambient temperature is defined by the battery manufacturer, but usually ranges from 20 C to 25 C (68-77 F). Higher room temperatures increase off gassing and shorten battery life. When float charged at the manufacturer s recommended voltage and room temperature, a battery can generate heat roughly in the magnitude of 0.1% of the full load operating power of the batteries. o Vented (flooded) some of the hydrogen gas is released into the room. Flooded lead acid batteries can vent approximately 60 times more hydrogen than comparably rated VRLA batteries. o VRLA and MBC hydrogen recombines under pressure with oxygen into water inside the battery. Gas can only escape when internal pressure exceeds the rating of the pressure valve. Discharge batteries vent little or no gas during a discharge. High ambient temperature will cause more chemical reaction and longer run times, whereas low ambient temperature does the opposite. The battery generates little heat. However, the power electronics supported by the battery might run slightly hotter during a discharge. o Vented (flooded) little or no gas vented during discharge. o VRLA and MBC little or no gas vented during discharge. Recharge higher charging voltage following a discharge causes the battery to heat up and release some measure of hydrogen gas. More voltage means more gas release. o Vented (flooded) release the most hydrogen into a room during recharge. o VRLA and MBC release little or no gas until the battery is recharged to approximately 80% of its capacity. VRLA is vulnerable to overheating if voltage and/or ambient temperature exceed recommended levels, so normal charging regimen of any UPS is to reduce the charging rate during the last 20% of its charging. Failure mode a rare but serious battery failure mechanism in lead acid batteries is a condition known as thermal runaway. Thermal runaway is preventable. o Vented (flooded) flooded batteries are largely immune to thermal runaway, but it is not impossible. o VRLA and MBC only a tiny percentage of VRLA battery systems ever experience thermal runaway. It is most likely to occur on inexpensive systems without appropriate protective circuits. This condition can be triggered by a cell failure, improper float voltage settings, charger failure, high ambient temperature around the batteries, excess charger capacity, or a combination of these conditions. Charger over-voltage is the most common cause. In thermal runaway heat generates inside the battery faster than it can be dissipated. The safety valves open and the battery vents hydrogen until temperature and/or voltage are reduced, or else the battery melts or dries out. A well-designed UPS system will have circuits to detect battery overtemperature and/or excess float current. Corrective action to prevent thermal runaway is to reduce charger voltage or to shut down a failed charger. Schneider Electric Data Center Science Center White Paper 34 Rev 3 3
4 Hazardous gasses One should consult the material safety data sheets provided with the battery for complete details of hazardous materials. In general, battery installations could potentially be exposed to the following types of gasses to some degree: Explosive gas is hydrogen (H 2 ), which can be emitted by all lead-acid batteries. o Vented (flooded) continuously release small amounts of hydrogen. o VRLA and MBC recombine the hydrogen to form water inside the battery and release hydrogen only when overheated and/or overcharged. Toxic gas emissions are miniscule, but can include arsine and hydrogen sulfide. These gasses appear only during severe failure events such as thermal runaway, and are not always present during such events. Aerosols and corrosive vapor that can be emitted during a severe venting event include electrolyte vapor. Reports of problems associated with aerosols are rare. Long term consequences are usually limited to equipment reliability. Aerosols generally pose little personnel risk unless inhaled or in contact with eyes. Environmental design considerations Most building and fire codes have separate articles specifically for batteries in order to distinguish battery rooms from classified (hazardous) locations. For example, the NFPA-1 Fire Code specifically exempts rooms or structures containing stationary lead-acid batteries from being classified as Class H, Division 1 occupancy. The International Fire Code states, shall be permitted in the same room as the equipment that they support. Special fire or explosion-proof equipment should not be required. Link to resource White Paper 31 Battery Technology for Data Centers and Network Rooms: U.S. Fire Safety Codes Related to Lead-Acid Link to resource White Paper 32 Battery Technology in Data Centers and Network Rooms: Environmental Regulations Vented (flooded) lead-acid battery requirements Because they continuously vent hydrogen gas, vented batteries are usually installed in dedicated battery rooms. They are sometimes co-located with the UPS, chargers, or other electronic equipment with which they are associated, although this practice is not recommended. Dedicated flooded battery rooms must be physically separated from other areas, avoid localized heat sources, and have doors and partitions designed to meet the required fire resistance rating for the application. For more information on battery safety codes and environmental regulations see White Paper 31, Battery Technology for Data Centers and Network Rooms: U.S. Fire Safety Codes Related to Lead-Acid and White Paper 32, Battery Technology for Data Centers and Network Rooms: Environmental Regulations. VRLA (sealed) battery and MBC requirements VRLA batteries and modular battery cartridges can be used in the same room as the equipment they support. If the room has controlled access (i.e., accessible only by trained and authorized personnel), the batteries can be installed in open racks; otherwise the batteries should be in cabinets with lockable doors. Rooms and cabinets should be designed to prevent the accumulation of hydrogen as described below. Ventilation The requirements of a ventilation system must be coordinated with the requirements of a fire prevention and suppression system. Schneider Electric Data Center Science Center White Paper 34 Rev 3 4
5 Cleanliness of Air all battery manufacturers and all best practices recommend that batteries be clean. o Vented (flooded) vented batteries are more vulnerable than VRLA batteries to build-up of oils and dust. In rare situations, accumulation of watersoluble salts in fine particles can accumulate on equipment surfaces where they can lead to increased corrosion levels, surface leakage, and potential arcing problems, particularly when the relative humidity is above 40%. In most cases, coarse-mode particles do not cause surface leakage or corrosion unless the dust is metallic (and therefore conductive) or contains large amounts of chloride. Typically, medium efficiency filters are recommended to filter outside air supply for rooms with vented batteries. o VRLA and MBC filters for rooms with electronic equipment, where VRLA batteries and MBC are often used, will typically have an ASHRAE Standard 52 dust spot efficiency between 30 to 60 percent - far in excess of the battery s requirements. Air Changes o Vented (flooded) ASHRAE and NFPA-111 recommend a minimum of two air changes per hour to remove gases generated by vented batteries during charging or caused by equipment malfunction. o VRLA and MBC sealed or valve regulated batteries are typically used in occupied environments. The National Electric Code (NEC) and NFPA-75 define specific requirements for ventilation under raised floors or above ceilings for information technology (IT) equipment rooms. Special rules apply if the space is used to re-circulate computer room/computer area environmental air. In order to qualify as an IT space, air in the under-floor area cannot be shared with non-it spaces. No additional air changes are required because of the presence of VRLA batteries or modular battery cartridges. Hydrogen accumulation in any space, hydrogen should not be allowed to accumulate to greater than two percent concentration of the total air volume in the space. Most regulations stipulate a maximum concentration of only one percent. The lower explosive level of hydrogen [i.e. the point at which hydrogen can combust] is four percent. (By comparison, the natural concentration of hydrogen in the atmosphere is 0.01%). Battery manufacturers should be able to provide exact gassing rate, charging voltage and charging currents for the type of battery installed. (Note that gassing rates can vary significantly depending upon voltage applied to the battery, temperature, and atmospheric pressure.) o Vented (flooded) the Institute of Electrical and Electronics Engineers (IEEE) provides formulae for calculating the maximum hydrogen evolution in vented (flooded) batteries when precise information is known about the battery and charger characteristics. Codes generally consider the worst case to be equalize charge. o VRLA and MBC VRLA batteries and MBC do not vent unless they are forced into a failure mode. Contact the supplier for the gassing rate of a particular model. Since most UPS systems designed specifically for use with VRLA batteries do not feature an equalize mode, the worst case is recharge following discharge. IEEE Std 1635/ASHRAE 21, Guideline for Ventilation of Stationary Battery Installations, provides formulae for calculating hydrogen hazards. When precise data is not practical or possible, fire codes require continuous ventilation at a rate not less than one cubic foot per minute per square foot of floor area for a VRLA battery system, or per square foot of the entire room for a vented battery system. Tables 1 and 2 give some rough comparisons for UPS systems rated 80 kw and 40 kw respectively, [Note that these tables are representational only and should not be substituted for actual calculations for any given site.] Anecdotal evidence suggests that in a completely sealed room with Schneider Electric Data Center Science Center White Paper 34 Rev 3 5
6 VRLA batteries, the time required for hydrogen to accumulate to a hazardous level can be many days or weeks. Table 1 Ventilation requirements for a typical 80 kw UPS battery system Vented (flooded) VRLA MBC Necessary ventilation air flow 12 cubic meters / hr 1.2 cubic meters / hr 1.2 cubic meters / hr Outdoor (fresh) air requirements for office space per person 36 cubic meters / hr 36 cubic meters / hr 36 cubic meters / hr Ratio 3 to 1 30 to 1 30 to 1 Special ventilation required Yes No No Table 2 Ventilation requirements for a typical 400 kw UPS battery system Vented (flooded) VRLA MBC Necessary ventilation air flow 60 cubic meters / hr 6 cubic meters / hr 6 cubic meters / hr Outdoor (fresh) air requirements for office space per person 36 cubic meters / hr 36 cubic meters / hr 36 cubic meters / hr Ratio 0.6 to 1 6 to 1 6 to 1 Special ventilation required Yes No No The NEC Handbook says that mechanical ventilation is not required for enclosures of battery systems. Convection ventilation is permitted. Hydrogen disperses rapidly and requires little air movement to prevent accumulations. Unrestricted natural air movement in the vicinity of the battery, together with normal air changes for occupied spaces or heat removal, will normally suffice. If the space is confined, mechanical ventilation may be required in the vicinity of the battery. Hydrogen is lighter than air and will tend to concentrate at ceiling-level, so some form of ventilation should be provided at the upper portion of the structure. Ventilation can be a fan, roof ridge vent, or louvered area. Temperature while all batteries will operate within a fairly wide temperature range, the life expectancy of a battery can be severely shortened at high temperatures. For example, continuous operation at 33 C (91 F) would cut the life expectancy of a VRLA battery by ½ and a vented battery by about ¼. The optimum temperature for air around a stationary battery is C ( F). [Note: this includes the air inside a battery cabinet, which may be warmer than the rest of the room.] Schneider Electric Data Center Science Center White Paper 34 Rev 3 6
7 Vented cells VRLA & MBC Table 3 Effect of temperature on battery life Design temperature Reduction in battery life from heat above design temperature Other effects of heat 25 C (77 F) 25 C (77 F) 2.5 % per C (1.8 F) 5 % per C (1.8 F) More frequent watering and maintenance Venting & dry-out Bulging, cracking Humidity - battery environments should be kept dry and free of static electricity. The optimum relative humidity is in the range of 35% to 55%. Battery placement - open racks for flooded and VRLA batteries allow heat to dissipate into the room. VRLA batteries in a cabinet should allow airflow around each battery container to allow removal of heat by convection or fan cooling. Avoid placing battery racks and/or cabinets near heat-generating sources. Monitoring & instrumentation where mechanical ventilation is used, monitors are recommended to detect and sound an audible alarm upon loss of air movement, fan failure and/or closure of fire/smoke dampers. Any alarm system should be monitored twenty-four hours per day. Alarm functions and use of automatic controls (such as switching to backup ventilation methods or disconnecting the battery) will depend upon operator availability, component redundancy, battery charging cycle duration and frequency, and ventilation dilution rate margins. Local codes usually do not require hydrogen and other gas detectors to be installed in dedicated battery rooms. If used, hydrogen detectors should be set to alarm at a maximum of two percent concentration. Requirements are typically vague about the quantity and placement of sensors. Careful consideration must be given to where pockets are likely to form. Nuisance alarms can be generated if the sensor is too close to battery vents. Schneider Electric Data Center Science Center White Paper 34 Rev 3 7
8 Conclusion Ventilation systems for stationary batteries must address human health and safety, fire safety, equipment reliability/ safety, and human comfort. Vented (flooded) batteries should be installed in dedicated battery rooms, but may share the same room as the equipment they support (such as a UPS system). VRLA batteries and modular battery cartridges can be used in an office environment. The amount of heat generated by a battery system is insignificant compared to the total IT system. However, batteries need cool, clean air for optimum performance and long life. Vented batteries must have a dedicated ventilation system that exhausts to the outside and prevents circulation of air in other parts of the building. For VRLA and MBC systems, the ventilation required for human occupancy is normally sufficient to remove heat and gases that might be generated. A minimum of two room air changes per hour and a temperature in the range of C (68 75 F) are recommended. The ventilation system must prevent the accumulation of hydrogen pockets in greater than 1 2% concentration. For vented batteries, it is recommended to enlist the services of an engineering firm experienced in battery room design, including ventilation, fire protection, hazardous material reporting and disposal, and spill control. For VLRA and MBC battery systems, the ventilation requirements for human occupancy and electronic equipment operation in a data center or network room well exceed the requirements for the batteries. No additional engineering should be necessary for VRLA battery ventilation. About the author Stephen McCluer is a Senior Manager for external codes and standards at Schneider Electric. He has 30 years of experience in the power protection industry, and is a member of NFPA, ICC, IAEI, ASHRAE, The Green Grid, BICSI, and the IEEE Standards Council. He serves on a number of committees within those organizations, is a frequent speaker at industry conferences, and authors technical papers and articles on power quality topics. He served on a task group to rewrite the requirements for information technology equipment in the 2011 National Electrical Code, and is one of the authors of the joint IEEE/ASHRAE Guide for battery ventilation. Schneider Electric Data Center Science Center White Paper 34 Rev 3 8
9 Resources Click on icon to link to resource Battery Technology for Data Centers and Network Rooms: Battery Options White Paper 30 Battery Technology for Data Centers and Network Rooms: U.S. Fire Safety Codes Related to Lead-Acid White Paper 31 Battery Technology for Data Centers and Network Rooms: Environmental Regulations White Paper 32 Battery Technology for Data Centers and Network Rooms: Site Planning White Paper 33 Battery Technology for Data Centers and Network Rooms: VRLA Reliability and Safety White Paper 34 White Paper Library whitepapers.apc.com TradeOff Tools tools.apc.com Schneider Electric Data Center Science Center White Paper 34 Rev 3 9
10 References 1. NFPA 1, Fire Code, National Fire Protection Association, Chapter International Fire Code, Article 608, International Code Council, Inc. 3. IEEE P1184, IEEE Guide for for Uninterruptible Power Supply Systems [Draft 09/2001], para and , Institute of Electrical and Electronics Engineers 4. IEEE P1188, IEEE Recommended Practice for Maintenance, Testing & Replacement of Valve Regulated Lead-Acid for Stationary Applications [Balloted 10/2002], paragraphs c and e.(2) 5. IEEE P450, IEEE Recommended Practice for Maintenance, Testing & Replacement of Vented Lead-Acid for Stationary Applications, paragraphs b and e 6. ATIS T1E1.5, Battery Rooms and Enclosures Standard, paragraph ANSI/ASHRAE Standard 62, Ventilation for Acceptable Indoor Air Quality, Table 2.1, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. 8. NFPA 111, Standard on Stored Electrical Energy, Emergency and Standby Power Systems, ed., para NFPA 70, National Electric Code 2002, Article 645, National Fire Protection Association 10. NFPA 75, Standard for the Protection of Electronic Computer/Data Processing Equipment, 1999, National Fire Protection Association 11. IEEE 1635/ASHRAE 21, Guide for Ventilation of Battery Installations, Joint publication of the Institute of Electrical and Electronics Engineers and the American Society of Heating, Refrigeration, and Air-conditioning Engineers (Publish late 2012) 12. NFPA 1, Fire Code, Chapter 52, National Fire Protection Association 13. NFPA 70HB11, NEC2011 Handbook, National Fire Protection Association Contact us For feedback and comments about the content of this white paper: Data Center Science Center [email protected] If you are a customer and have questions specific to your data center project: Contact your Schneider Electric representative at Schneider Electric Data Center Science Center White Paper 34 Rev 3 10
Battery Technology for Data Centers and Network Rooms: Lead-Acid Battery Options
Battery Technology for Data Centers and Network Rooms: Lead-Acid Battery Options By Stephen McCluer White Paper #30 Revision 11 Executive Summary The lead-acid battery is the predominant choice for Uninterruptible
Battery Technology for Data Centers and Network Rooms: Fire Safety Codes USA
Battery Technology for Data Centers and Network Rooms: Fire Safety Codes USA By Stephen McCluer White Paper #31 Revision 6 Executive Summary Fire safety regulations and their application to UPS battery
THE PROPER CHARGING OF STATIONARY LEAD-ACID BATTERIES. (YOUR BATTERY IS ONLY AS GOOD AS HOW YOU CHARGE IT.)
THE PROPER CHARGING OF STATIONARY LEAD-ACID BATTERIES. (YOUR BATTERY IS ONLY AS GOOD AS HOW YOU CHARGE IT.) J. Allen Byrne Engineering, Training and Tech Support Manager Interstate PowerCare, a Division
Stationary Storage Battery Systems
ORANGE COUNTY FIRE AUTHORITY Planning & Development Services Section 1 Fire Authority Road, Building A Irvine, CA 92602 714-573-6100 www.ocfa.org Stationary Storage Battery Systems Guideline G-10 Date:
Containment Requirements
Introduction: Building and fire codes are developed by associations for adoption by federal, state and local authorities having jurisdiction. The local municipalities often make amendments or changes to
How To Use A Power Supply Unit (Upu)
BRAVER UPS (Uninterruptible Power System) User s Manual Safety CAUTION! This UPS utilizes voltages that may be hazardous. Do not attempt to disassemble the unit. The unit contains no user replaceable parts.
Single Phase UPS Management, Maintenance, and Lifecycle
Single Phase UPS Management, Maintenance, and Lifecycle White Paper 210 Revision 0 by Justin Solis Executive summary How long will my battery last? and what is the best practice for maintaining my UPS?
875 Dearborn Drive Columbus, Ohio 43085 Tel: (614) 846-7500 Fax: (614) 885-3990
Selection and Sizing of Batteries for UPS Backup 875 Dearborn Drive Columbus, Ohio 43085 Tel: (614) 846-7500 Fax: (614) 885-3990 Selection and Sizing of Batteries for UPS Backup Abstract Introduction Battery
LEAD ACID BATTERY working LIFETIME STUDY
LEAD ACID BATTERY working LIFETIME STUDY Valve Regulated Lead Acid (VRLA) Batteries Overview The most common type of battery used on UPS systems and for backup of telecommunications systems. VRLA batteries
Batteries and inverters
Batteries and other energy storage devices store energy so that it can be used when needed. In a stand-alone power system, the energy stored in batteries can be used when energy demand exceeds the output
User s Manual AURORA 1.2K/2.2K
User s Manual AURORA 1.2K/2.2K Uninterruptible Power System Safety CAUTION This UPS utilizes voltages that may be hazardous. Do not attempt to disassemble the unit. The unit contains no user serviceable
Temperature Compensated Charging of Lead Acid Batteries
Technical Note Batteries 512-0101-01-01 Rev 1 Temperature Compensated Charging of Lead Acid Batteries Introduction To ensure optimum charging of lead acid batteries, the charge voltages should be adjusted
Requirements for Hydrogen Storage and Use
Requirements for Hydrogen Storage and Use I. INTRODUCTION Fire and Life-Safety Group (FLS) The following is a summary of the fire and building code requirements for the storage and use of hydrogen. These
MOBILE DC POWER SYSTEMS FOR SUBSTATION APPLICATIONS
MOBILE DC POWER SYSTEMS FOR SUBSTATION APPLICATIONS Gary P. Guagliardi Director Sales & Marketing HindlePower, Inc. Easton, PA Introduction This paper explores the use of mobile DC power systems for three
400 Amp Rechargeable Jump Start System RAC-HP082
400 Amp Rechargeable Jump Start System RAC-HP082 MAINTENANCE Always inspect the tool before use to ensure the cables are in good condition and the clamps are clean and free from corrosion. Keep clean by
ELECTRICAL EMERGENCY SYSTEM PLAN REVIEW OVERVIEW OF CODE REQUIREMENTS
ELECTRICAL EMERGENCY SYSTEM PLAN REVIEW What to Look for during Plan Review OVERVIEW OF CODE REQUIREMENTS First determine the type of emergency power system; is the system designed for Emergency or Legally
USER S MANUAL. MaxPower 400-600 UPS. Uninterruptible Power System 28-2MAXPO0018
USER S MANUAL MaxPower 400-600 UPS Uninterruptible Power System 28-2MAXPO0018 IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions for models MaxPower 400 and
LEAD CRYSTAL. User Manual. Valve-regulated lead-crystal batteries Energy storage Cells
Engineering Production Sales LEAD CRYSTAL Valve-regulated lead-crystal batteries Energy storage Cells User Manual www.axcom-battery-technology.de [email protected] Chapter 1: 1. Introduction
10 Year VRLA Battery Periodic Maintenance Instructions
TECHNICAL BULLETIN 41-7546 Valve Regulated Lead Acid Battery 20 to 200 ampere-hours capacity 10 Year VRLA Battery Periodic Maintenance Instructions 41-7546/0213/CD www.cdtechno.com General Information
White Paper. Best Practices for Gas Monitoring in the Commercial Kitchen
White Paper Best Practices for Gas Monitoring in the Commercial Kitchen Enhancing Kitchen Safety through Strategic Gas Monitoring Overview Commercial kitchens are one of the most hazardous commercial building
Substations. Design Guide. January, 2010 Doc 11737_00
Substations Design Guide January, 2010 Doc 11737_00 VESDA by Xtralis Substations Design Guide Preface Xtralis has produced this Design Guide as a reference, to be consulted when designing VESDA fire protection
Mechanical Systems Competency 1.20
Competency 1.20 Mechanical systems personnel shall demonstrate a working level knowledge of the safety and health fundamentals of mechanical systems and/or components. 1. Supporting Knowledge and Skills
How To Calculate Total Cooling Requirements For Data Center
Calculating Total Cooling Requirements for Data Centers White Paper 25 Revision 3 by Neil Rasmussen > Executive summary This document describes how to estimate heat output from information technology (IT)
Fume Hood Questions and Answers
Fume Hood Questions and Answers 1. When should I use a fume hood? Use a chemical fume hood anytime your work involves: Chemicals with a National Fire Protection Association (NFPA) Health rating of 3 or
Canadian Regulatory Compliance for Stationary Battery Systems North American Update
Canadian Regulatory Compliance for Stationary Battery Systems North American Update ComplianceKnowledgeCenter.com What is Compliance? In general: compliance means conforming to a rule, such as: a specification,
5/3/2010. Article 500 address the requirements for hazardous locations: Wiring Equipment
Two Documents are used for the Classification of Combustible Dusts and Hazardous Locations: NFPA 499-Recommended Practices for the Classification of Combustible Dusts and Hazardous Locations for Electrical
Battery Handbook. By: RON SMITH
Battery Handbook By: RON SMITH Information compiled from the Battery Charger Handbook and the Battery Handbook written by Alvin G. Graham, Chief Engineer, Ratelco Electronics Inc. Introduction The purpose
Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF
Daker DK 1, 2, 3 kva Manuel d installation Installation manual Part. LE05334AC-07/13-01 GF Daker DK 1, 2, 3 kva Index 1 Introduction 24 2 Conditions of use 24 3 LCD Panel 25 4 Installation 28 5 UPS communicator
Element D Services Heating, Ventilating, and Air Conditioning
PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer
EXPLOSIVE ATMOSPHERES - CLASSIFICATION OF HAZARDOUS AREAS (ZONING) AND SELECTION OF EQUIPMENT
EXPLOSIVE ATMOSPHERES - CLASSIFICATION OF HAZARDOUS AREAS (ZONING) AND SELECTION OF EQUIPMENT OVERVIEW ASSESSING THE RISK RELATIONSHIP BETWEEN FIRES AND EXPLOSIONS CLASSIFYING HAZARDOUS AREAS INTO ZONES
Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal
Ontario Fire Code SECTION 5.13 DIP TANKS Illustrated Commentary Office of the Ontario Fire Marshal Dip Tanks Illustrated Commentary 1 5.13.1. Location 5.13.1.1. Dip tank operations involving flammable
Height w/o Terminals (in)
EaglePicher Technologies, LLC Commercial Power P.O. Box 47 Joplin, MO 6482 (417) 623-8 [email protected] Carefree Sealed Lead Acid (SLA) MSDS EaglePicher s Carefree lead acid batteries are
HVAC Code Requirements
one and two family dwellings? Answer: SECTION 2001: GENERAL 2001.1 Air supply. Fuel-burning equipment shall be provided with a supply of air for fuel combustion, draft hood dilution and ventilation of
MISSION CRITICAL FACILITIES DESIGN UPS BATTERY ROOM ENVIRONMENT CRITICAL DESIGN CONSIDERATIONS
MISSION CRITICAL FACILITIES DESIGN UPS BATTERY ROOM ENVIRONMENT CRITICAL DESIGN CONSIDERATIONS Allen Wood Vice President Data Center Division Engineering Design Group INTRODUCTION It can be very effectively
Frequently Asked Questions Generators
Frequently Asked Questions Generators Fuel Related How much fuel do the generators use during normal operation? At exercise? The generator fuel consumption is given in each of the product knowledge books
If you accidentally get battery acid on your skin, flush it with lots of water
RV Battery Savvy To properly maintain and extend the life of your RV batteries you need to have a basic understanding of what a battery is and how it works. Batteries used in RVs are lead acid batteries.
Application Requirement
Hazardous Gas Monitors Sensor Selection Overview Safety Monitoring (LEL) Toxic Limit Detection (PEL) Leak Detection Personal Safety Application Requirement Exposure Assessment (TWA) Ambient Air Quality
Ethanol Vehicle and Infrastructure Codes and Standards Citations
Ethanol Vehicle and Infrastructure Codes and Standards Citations This document lists codes and standards typically used for U.S. ethanol vehicle and infrastructure projects. To determine which codes and
Carefree Sealed Lead Acid (SLA) MSDS
EaglePicher Technologies, LLC Commercial Power P.O. Box 47 Joplin, MO 6482 (417) 623-8 [email protected] Carefree Sealed Lead Acid (SLA) MSDS EaglePicher s Carefree lead acid batteries are
Natural Gas Emergencies
Natural Gas Emergencies Purpose To protect the personnel within the department, and citizens from the hazards involved in a natural gas emergency. The Incident Commander is to use his/her best judgment
IMO. 8 June 1998 *** I:\CIRC\MSC\848.WPD INTERNATIONAL MARITIME ORGANIZATION 4 ALBERT EMBANKMENT LONDON SE1 7SR
INTERNATIONAL MARITIME ORGANIZATION 4 ALBERT EMBANKMENT LONDON SE1 7SR E Telephone: 0171-735 7611 Fax: 0171-587 3210 Telex: 23588 IMOLDN G IMO Ref. T4/4.03 MSC/Circ.848 8 June 1998 REVISED GUIDELINES FOR
EARLY WARNING OF FIRE AND HYDROGEN GAS THREATS IN BATTERY SPACES
EARLY WARNING OF FIRE AND HYDROGEN GAS THREATS IN BATTERY SPACES Steven Joseph, Director of Market Development Thomas Stilwell, Regional Sales Executive Xtralis, Inc. Norwell, MA 02061 INTRODUCTION The
SPECIAL APPLICATIONS
Page 1 SPECIAL APPLICATIONS The protection of microelectronics clean rooms using aspirating smoke detection systems requires special consideration. The physical configuration of the room(s) and the direction
Glossary of Heating, Ventilation and Air Conditioning Terms
Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment
SL280UHV SERIES GAS FURNACE WARNING
2010 Lennox Industries Inc. Dallas, Texas, USA 506677 01 11/2010 Supersedes 506409 01 SL280UHV SERIES GAS FURNACE Litho U.S.A. FIRE OR EXPLOSION HAZARD. Failure to follow safety warnings exactly could
ALVERNIA UNIVERSITY OSHA REGULATION: 29 CFR 1910.252 WELDING, CUTTING, AND BRAZING ( HOT WORK ) SECTION: 3600
OSHA REGULATION: 9 CFR 90.5 WELDING, CUTTING, AND BRAZING ( HOT WORK ) A. POLICY. This procedure follows requirements set forth in 9 CFR 90.5.. This policy applies to all Hot Work operations being done
BC-5000 OPERATIONS MANUAL BATTERY CAPACITY TESTER COFKO LLC.
BC-5000 BATTERY CAPACITY TESTER OPERATIONS MANUAL COFKO LLC. COPYRIGHT 2010 1 UNPACKING As you unpack your new BC-5000 battery capacity tester, inspect the tester for signs of shipping damage. If shipping
A Code Review for Emergency Generators and Indoor Use of Portable Generators
A Code Review for Emergency Generators and Indoor Use of Portable Generators By: the Fire and Life-Safety Group (FLS) Fire Code requires that emergency generators be stationary generators. Therefore, a
Ammonia Detection System Codes and Design Specifications
Ammonia Detection System Codes and Design Specifications December 28, 2015 Revision 5 920 N Trade Winds Pkwy Columbia, MO 65201 Ammonia detection system codes and design specifications Following is a discussion
Outline. Background. NFPA 820 Applicability to Wastewater Treatment Facilities. Hazardous Area Classifications. Treatment Plant Area Classifications
Outline Background NFPA 820 Applicability to Wastewater Treatment Facilities Hazardous Area Classifications Treatment Plant Area Classifications Locations of Concern Background NFPA 820 Standard for fire
Installation Instructions for Alarm Module Kit A043F059
Instruction Sheet 07-2013 Installation Instructions for Alarm Module Kit A043F059 1 Introduction The information contained within is based on information available at the time of going to print. In line
New York City Fire Code & Energy Storage Systems
New York City Fire Code & Energy Storage Systems Winnie Lei on behalf of Tamara Saakian, P.E. Director of Engineering & Technology Management Technology Management Unit Bureau of Fire Prevention Fire Department
Data Bulletin. Mounting Variable Frequency Drives in Electrical Enclosures Thermal Concerns OVERVIEW WHY VARIABLE FREQUENCY DRIVES THERMAL MANAGEMENT?
Data Bulletin April 2001 Raleigh, NC, USA Mounting Variable Frequency Drives in Electrical Enclosures Thermal Concerns OVERVIEW Variable frequency drives are available from manufacturers as enclosed engineered
Managing Heat Stress in Poultry
Managing Heat Stress in Poultry Amy E. Halls, Monogastric Nutritionist Shur-Gain, Nutreco Canada Inc. Heat stress has several serious and economical effects on poultry. In broilers and turkeys, it can
Spray Booth Guideline
Department of Development Service 135 North D Street, Perris CA. 92570 Phone: (951) 443-1029 Fax: (951) 943-3293 PURPOSE The intent of this guideline is to provide the information necessary to ensure that
Cooling Strategies for IT Wiring Closets and Small Rooms
Cooling Strategies for IT Wiring Closets and Small Rooms White Paper 68 Revision 1 by Neil Rasmussen and Brian Standley > Executive summary Cooling for IT wiring closets is rarely planned and typically
CHARGING METHODS. Methods of Charging the Valve Regulated (Sealed) Lead-Acid Battery. 19 Valve Regulated (Sealed) Lead-Acid Batteries
CHARGNG METHODS Methods of Charging the alve Regulated (Sealed) Lead-Acid Battery For charging the alve Regulated (Sealed) lead-acid battery, a well-matched charger should be used because the capacity
THREE. Heating and Cooling
THREE Heating and Cooling 17 Condensation Drain Line The line that drains condensed moisture away from your heating and/or cooling unit needs periodic maintenance. If your unit is located in the attic,
Improving Rack Cooling Performance Using Airflow Management Blanking Panels
Improving Rack Cooling Performance Using Airflow Management Blanking Panels White Paper 44 Revision 4 by Neil Rasmussen > Executive summary Unused vertical space in open frame racks and rack enclosures
Effects of AC Ripple Current on VRLA Battery Life. A Technical Note from the Experts in Business-Critical Continuity
Effects of AC Ripple Current on VRLA Battery Life A Technical Note from the Experts in Business-Critical Continuity Introduction Given the importance of battery life to UPS system users and the fact that
A GUIDE TO SELECTING YOUR INDUSTRIAL OVEN
A GUIDE TO SELECTING YOUR INDUSTRIAL OVEN Application 1 The first step in selecting an industrial oven is defining the required heat application that your oven will be used for. Heat processing is extensively
BATTERY CHARGING GUIDELINES FOR 6-VOLT DEEP CYCLE BATTERIES
BATTERY CHARGING GUIDELINES FOR 6-VOLT DEEP CYCLE BATTERIES Introduction Your 6-volt deep cycle battery set has been specially formulated for long cycle life and has particular voltage and specific gravity
heating 3 & cooling heating and cooling 2010 PulteGroup, Inc. All Rights Reserved.
3 & cooling 17 heating 2010 PulteGroup, Inc. All Rights Reserved. condensation The line that drains condensed moisture away from your heating and/or cooling unit needs periodic maintenance. Air conditioning
OPERATION MANUAL. Total Heat Exchanger HRV (Heat Reclaim Ventilation) (Ceiling mounted duct type)
OPERATION MANUAL (Ceiling mounted duct type) VAM50FB VAM500FB VAM650FB VAM800FB VAM000FB VAM500FB VAM000FB 8 7 6 9 5 7 5 0 6 8 6 9 0 5 5 7 7 6 7 A A B B 5 6 5 6 7 VAM50F VAM800F VAM500F VAM500F VAM000F
TELEDYNE BATTERY PRODUCTS. INSTRUCTIONS FOR CONTINUED AIRWORTHINESS and COMPONENT MAINTENANCE MANUAL. For
TELEDYNE BATTERY PRODUCTS INSTRUCTIONS FOR CONTINUED AIRWORTHINESS and COMPONENT MAINTENANCE MANUAL For TSO-C173/C173a Authorized (GILL ) 7000 Series LT Valve-Regulated Lead-Acid Aircraft Batteries REFER
3000W Power Inverter
3000W Power Inverter OWNER S MANUAL Model number-4573000 TO REDUCE THE RISK OF INJURY, USER MUST READ AND UNDERSTAND THIS INSTRUCTIONAL MANUAL. THIS MANUAL CONTAINS IMPORTANT INFORMATION REGARDING THE
LEVEL 3 DATA CENTER ASSESSMENT
Nationwide Services Corporate Headquarters 410 Forest Street Marlborough, MA 01752 USA Tel: 800-342-5332 Fax: 508-303-0579 www.eecnet.com LEVEL 3 DATA CENTER ASSESSMENT Submitted by: Electronic Environments
State of the Art Energy Efficient Data Centre Air Conditioning
- White Paper - State of the Art Energy Efficient Data Centre Air Conditioning - Dynamic Free Cooling - Release 2, April 2008 Contents ABSTRACT... 3 1. WHY DO I NEED AN ENERGY EFFICIENT COOLING SYSTEM...
Practical Guidelines for Electrical Area Classification in Combustion Turbine-Generator Power Plants
Practical Guidelines for Electrical Area Classification in Combustion Turbine-Generator Power Plants Ram K. Saini, P.E. Principal Engineer, Chuck Emma, P.E. Principal Engineer, Burns and Roe Enterprises,
Solar Wind Microhydro Water Pumping Inverters Batteries Professional system design and installation
Solar Wind Microhydro Water Pumping Inverters Batteries Professional system design and installation BATTERY CHARGING GUIDELINES FOR GLOBAL/DAVIDSON TUBULAR PLATE BATTERIES Introduction Your Global/Davidson
Dear Neuton Owner, This is a helpful hint to guide you in getting the most out of your NEUTON Battery and Charger.
Battery-Powered Mower NEUTON 24-Volt Charger Instructions Booklet Dear Neuton Owner, In order for you to get the most out of your Neuton Mower, we recently reviewed and revised our battery-charging instructions.
DRAFT REGULATORY GUIDE DG-1154 (Proposed Revision 2 of Regulatory Guide 1.128, dated October 1978)
U.S. NUCLEAR REGULATORY COMMISSION October 2006 OFFICE OF NUCLEAR REGULATORY RESEARCH Division 1 DRAFT REGULATORY GUIDE Contact: W.S. Raughley (301) 415-7577 DRAFT REGULATORY GUIDE DG-1154 (Proposed Revision
Flammable Liquids 29 CFR 1910.106
Flammable Liquids 29 CFR 1910.106 OSHA s Directorate of Training and Education These materials were developed by OSHA s Directorate of Training and Education and are intended to assist employers, workers,
HealthandSafetyOntario.ca. Introduction. Storage Containers. Storing Flammable Liquids
Flammable Liquids Storage Introduction This guideline is designed to help you store flammable liquids safely. It is based on the requirements of the Ontario Fire Code, Part 4, and of the Regulations for
Data Centre Services. JT Rue Des Pres Data Centre Facility Product Description
JT Rue Des Pres Data Centre Facility Product Description JT s Data Centre Hosting Service provides a secure computer room environment with protected and backup power, security and bandwidth. Data Centre
Height w/o Terminals (in)
EaglePicher Technologies, LLC Commercial Power P.O. Box 47 Joplin, MO 6482 (417) 623-8 [email protected] Carefree Sealed Lead Acid (SLA) MSDS EaglePicher s Carefree lead acid batteries are
User s Manual Before using the inverter, you need to read and save the safety instructions.
User s Manual Before using the inverter, you need to read and save the safety instructions. STI SERIES (STI200, STI300, STI500, STI700, STI1000) Power Frequency Pure Sine Wave Inverter The information
HVAC Processes. Lecture 7
HVAC Processes Lecture 7 Targets of Lecture General understanding about HVAC systems: Typical HVAC processes Air handling units, fan coil units, exhaust fans Typical plumbing systems Transfer pumps, sump
Subpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715,
4658.4500 PLUMBING SYSTEMS; NEW CONSTRUCTION. Subpart 1. Installation. All plumbing systems must be installed and tested according to this chapter and chapter 4715, the Minnesota Plumbing Code. Subp. 2.
SMOKE DETECTOR INSTALLATION PROGRAM The Burlington Ordinance Perspective
SMOKE DETECTOR INSTALLATION PROGRAM The Burlington Ordinance Perspective The National Fire Alarm Code, NFPA 72, sets the minimum requirements of performance, selection, use and location of automatic detection
Operating Instructions Split System Air Conditioner
Operating Instructions Split System Air Conditioner Model No. Indoor Unit Type Indoor Unit Type Nominal Capacity 26 36 F2 Low Silhouette Ducted S-26PF2U6 S-36PF2U6 Connectable outdoor unit lineup This
Manual for Fire Suppression & Methane Detection System
Manual for Fire Suppression & Methane Detection System Fogmaker North America Post address: 150 Gordon Dr Exton, PA 19341 Delivery address: 150 Gordon Dr Exton, PA 19341 Tel: 610-265-3610 Fax: 610-265-8327
EKOS Cart. Instructions for Use
EKOS Cart Instructions for Use EKOS Corporation 11911 North Creek Parkway South Bothell, WA 98011 USA (425) 415-3100 (tel) (425) 415-3102 (fax) [email protected] (e-mail) - 1-4913-002 REV E Intended Use
PROCEDURES PREVENTION OF ACCIDENTAL IGNITION
Page No: 1 of 7 6.0 PURPOSE (192.751) All possible precautions shall be exercised to prevent the accidental escape and ignition of gas. Whenever possible, potential sources of ignition should be eliminated
Wet vs Sealed Batteries A detailed explanation of the differences between charging "Wet" Batteries and charging "Sealed" Batteries.
Service Bulletins & Tips February 2006 Volume 3, Issue 1 In this issue: Wet vs Sealed Batteries A detailed explanation of the differences between charging "Wet" Batteries and charging "Sealed" Batteries.
Components HVAC General Standards HVAC Guidelines HVAC System Selection Life Cycle Cost Analysis
Components HVAC General System Selection Life Cycle Cost Analysis Outdoor Air Design Values Indoor Air Design Values Outdoor Air Ventilation Welding Ventilation Temperature Control Systems Ductwork HVAC
Compressed Gas Cylinder Safety
Compressed Gas Cylinder Safety I. Background. Due to the nature of gas cylinders, special storage and handling precautions are necessary. The hazards associated with compressed gases include oxygen displacement,
10 tips for getting more reliability from your air-conditioning system [reliability]
10 tips for getting more reliability from your air-conditioning system [reliability] A guide for installers, specifiers, contractors and architects February 2010 10 tips for getting more reliability from
VRLA BATTERIES AUGUST
CHARGNG METHODS Methods of Charging the alve-regulated Lead-Acid Battery For charging the valve-regulated lead-acid battery, a well-matched charger should be used because the capacity or life of the battery
2. Add the following definitions to 3.3 General Definitions and renumber 3.3 as required:
NFPA 72-2013 National Fire Alarm and Signaling Code TIA Log No. 1188 Reference: Various Sections on Battery Comment Closing Date: June 19, 2015 Submitter: Herbert Hurst, Savannah River Nuclear Solutions,
Tel.X Ni-Cd battery. The compact maintenance-free solution for telecom networks
Tel.X Ni-Cd battery The compact maintenance-free solution for telecom networks Tel.X, delivering high-energy performance in a compact maintenance-free package Tel.X: guaranteed power continuity for remote
Data Centre Services. JT First Tower Lane Data Centre Facility Product Description
JT First Tower Lane Data Centre Facility Product Description JT s Data Centre Hosting Service provides a secure computer room enviroment with protected incoming power supplies, state-of-the-art security
ICC CODE CORNER 2012 IFC Code & Commentary
SECTION 908 EMERGENCY ALARM SYSTEMS 908.1 Group H occupancies. Emergency alarms for the detection and notification of an emergency condition in Group H occupancies shall be provided as required in Chapter
12. Inspection and Maintenance
12. and Maintenance Mandatory Be sure to inspect the inverter regularly and periodically to prevent it from breaking down because of the environment of use, such as temperature, humidity, dust and vibration,
Electrical Classification
Electrical Classification Using NFPA 70 and NFPA 499 to Classify Hazardous Locations Electrical classifications are established in accordance with the National Electrical Code, NFPA 70, also referred to
USER S, MAINTENANCE and SERVICE INFORMATION MANUAL
CONTENTS SAFETY INFORMATION................ 2 FOR YOUR SAFETY....................... 2 SYSTEM OPERATION.................. 2 THERMOSTATS........................... 2 INTERMITTENT IGNITION DEVICE...........
Guardian Fire Safety Solutions FIRE RISK CONTROL IN WELDING FUME EXTRACTION SYSTEMS
Guardian Fire Safety Solutions FIRE RISK CONTROL IN WELDING FUME EXTRACTION SYSTEMS Guardian Fire Safety Solutions FIRE RISK CONTROL IN WELDING FUME EXTRACTION SYSTEMS DO YOU CONTROL THE RISK OF FIRE AT
TYPICAL FIRE SAFETY INSPECTION VIOLATIONS
TYPICAL FIRE SAFETY INSPECTION VIOLATIONS The following is a list of typical violations often found by inspectors and a generic solution. You can use this list to improve the safety of your facility, to
Data Center Precision Cooling: The Need For A Higher Level Of Service Expertise. A White Paper from the Experts in Business-Critical Continuity
Data Center Precision Cooling: The Need For A Higher Level Of Service Expertise A White Paper from the Experts in Business-Critical Continuity Executive Summary Today s data centers are changing rapidly,
Understand Hybrid Generator Battery Systems
Understand Hybrid Generator Battery Systems For off-grid applications powered by diesel generators, move to cyclic operation to save costs Telecommunications operators in Africa, India and other developing