1 = 13.8 kv. 1 = 69 kv

Size: px
Start display at page:

Download "1 = 13.8 kv. 1 = 69 kv"

Transcription

1 EP 306 GENERATION, TRANSMISSION AN ISTRIBUTION Chapter (1) Representation of Power Systems (1) Three parts of a single phase electric system are designated A,B and C are connected to each other through transformer as shown in fig. The transformer are rate as follows; A-B 100,00 KVA, KV leakage reactance 10 % B-C 100,00 KVA, KV,leakage reactance 8% If the ase in circuit B is chosen as 100,00 KVA, 138 KV, find the per unit impedance of the 300Ω resistive load in circuit C referred to circuit C,B and A. raw the impedance diagram neglecting magnetizing current transformer resistance and impedance. etermine the voltage regulation if the voltage at the load is 66KV with the assumption that the voltage input to circuit A remain constant. Base voltage for circuit A 138 x kv Base voltage for circuit C 138 x 1 69 kv Base voltage for circuit C (BasekV) 1000 Base kva Ω 100, Per-unit impedance of load in circuit C 0.63 p.u Base impedance of circuit B 1400Ω 100,000 Impedance of load referred to circuit B 300 x 100Ω 100 Per- unit impedance of load in circuit B o.63 p.u Base impedance of circuit A 19Ω 100,00 Impedance of load referred to circuit A 300 x x 0.1 1Ω

2 1 Per-unit impedance of load in circuit A 0.63 p.u Voltage at load jo p.u jo Load current jo p.u jo Voltage input (1.5 + jo) (jo.1 +jo.08) jo p.u Voltage regulation 3.97% () A300,00 KVA 13.8 KV 3Ǿ generator has a su transient reactance of 15%. The generator supplies two motors over a transmission line having transformer at oth ends as shown on the line diagram of fig. The motor have rated inputs of 00,00 and 100,00 KVA, oth 1.5KV with X 0 % 3Ǿ. Transformer T 1 is rated 35,000 KVA, 13. Δ 115 Υ KV with leakage reactance of 10%. Transformer T is composed of 3 single phase transformer each rated 100,00 KVA, KV with leakage reactance of 1%. Series reactance of the transmission line is 80Ω. raw the reactance diagram with all reactance marked in per-unit. Select the generator rating as ase in generator circuit. 3 rating of T 3x 100,00 300,00 kva Line to line ration x kv A ase of 300,00 kva, 13.8 KV In transmission line, 13.8 x kv 13.

3 1. 5 In motor circuit, 10 x kv ase kv X P.U Z given x ( ase kv (given) (new) ) x ase kva ase kva (new) (given) Transformer, T 1 X 0.1 x ( ) x p.u T X 0.1 x ( ) x p.u The ase impedance of transmission line 480Ω Reactance of line p.u Reactance of motor 1 0. x ( ) x 0.8 p.u Reactance of motor 0. x ( ) x p.u (3) A generator rated 100 MVA, 13.kV with X 0 % is connected through a Δ-Υ transformer to a transmission line whose series reactance is 40Ω. The ase chosen for calculation is 00 MVA, 115KV in transmission line. etermine the generator and transformer reactance in-per unit for reactance diagram (a) if the transformer is a 3 unit rated 13.8Δ - 10Υ kv, 100MVA with X8% and () if the transformer is composed of three single phase each rated 13.8kV 69kV, 35,000 kva. Also determine the per- unit reactance of the transmission line on the chosen ase.

4 Base 00MVA, 115kV in transmission line Base voltage for generator circuit 115 x 10 (a) For generator, p.u.z j0.x( For transformer p.u.z (H.T) j0.08 x ( ) x j0.174 p.u 13.5 kv 13.8 For transformer p.u.z (L.T) j0.08 x ( 13.5 j0.174 p.u () 3 rating of Δ Υ Transformer 3 x 35,000 kva 00 ) x j0.4 p.u ) x Δ 69 x 3 Υ 13.8 Base voltage for generator circuit 115 x 13.8 kv For generator, p.u z j0. x ( ) x j0.395 p.u For transformer p.u z (H.T) jo.08 x ( ) x j p.u For transformer p.u z (L.T) jo.08 x ( ) x j0.164 p.u ase kv 100 Base impedance for transmission line ase kva p.u z of transformer line Ω j0.605 p.u

5 (4) A 15,000 KVA 8.5 three phase generator has a su-transient reactance of 0%.It is connected through a Δ Υ transformer to a high voltage transmission lion having a total series reactance of 70 ohms. At the load circuit of the line is a Υ Υ step down transformer. Both transformers ank are composed of single phase transformer connected for three phase operation. Each of the three transformers composing each.bank is rated 6,667 KVA, KV with a reactance of 10%. The load represented as impedance is drawing 10,000 KVA at 1.5KV and 80% power factor lagging. raw a positive sequence diagram showing all impedances in per-unit. Chose a ase of 10,000 KVA, 1.5KV in the load circuit. etermine the voltage at the terminals of the generator. Choose ase 10,000 kva, 1.5 kv of the load circuit Base kv for line x kw Base kv for generator 15 x kv For generator, p.u z x ( ) x p.u For transformer T 1 p.u z 10 10, x ( ) x p.u For Transformer T p.u z , x ( ) x p.u Basic impedance of transmission line 156.5Ω 100,00 p.u z For transmission line 70 o.o448 p.u 156.5

6 j0.096 j j0.096 j j1 Eg p.u voltage 1 p.u 1.5 p.u z j0.6 1 p.u I 0.8+ jo.6 1 generator terminal voltage j0.6 (j0.37) p.u (5) The one line diagram of an unloaded power system in fig. reactance of the two section of transmission line are shown on the diagram. The generator and transformers are rated as follows; Generator (1) ; 0,000 kva, 6.9 kv, X 0.15 p.u () ; 10,000 kva, 6.9 kv, X 0.15 p.u (3) ; 30,000 kva, 13.8 kv, X 0.15 p.u Transformer (T 1 ) ; 5,000 kva, 6.9 Δ 115 Υ kv, X 10% (T ) ; 1,500 kva, 6.9 Δ 115 Υ kv, X 10% (T 3 ) ; single phase unit each rated 10,000 kva 7.5 kv, X 10% raw the impedance diagram with all reactance marked in per unit and with letters to indicate point corresponding to the one line diagram, choose a ase of 30,000kVA, 6.9 kv in the circuit of generator (1)

7 1 A 0MVA 6.9KV X 0.5 5MVA V X 10% 5MVA 6.9 Y X 10% B J100Ω 100MVA 6.9KV X 0.15 C 115YKV 6.9KV 1MVA X 10% E Y MVA 3 75Y MVA Y13.8KV X 0.15 kv 3 rating of T 3 3x10 MVA 30 MVA Line to line voltage ratio 3 x 75 V 1-3 x 7.5 V 1-8 KV Choose a ase of 30 MVA, 6.9 kv 115 Base kv for transmission line 6.9 x 115 kv Base kv for generator () 115 x 6.9 kv 115 Base kv for generator (3) kv 3 75 For generator (1), p.u z j0.15 x ( ) j0.5 p.u For generator (), p.u z j0.15 x ( ) j0.5 p.u For generator (3), p.u z j0.1 x ( ) j0.16 p.u For Transformer T j0.1 x ( ) j0.1 p.u For Transformer T j0.1 x ( ) j0.5 p.u For Transformer T 3 j0.1 x ( ) j0.18 p.u Base impedance of transmission line ( ase kv ) 1000 ase kva

8 (115) Ω j100 For j100ω line p.u z j 0.7 p.u For j80ω line p.u z j j p.u (6) raw the impedance diagram for the power system shown in fig;. Mark impedances in per- unit- neglect resistance and use a ase of 50,000 kva, 138 kv in the 40 Ω line. The rating of the generators, motors and transformers are, Generator (1), 0,000 kva, 13. kv, x 15% Generator (), 0,000 kva, 13. kv, x 15% Synchronous motor (3) 30,000 kva, 6.9kV, X 0% Three phase Υ Υ transformer 0,000 kva, 13.8V Υ kv, X 10% Three phase Υ Δ transformer 15,000 kva, 6.9 Δ Υ kv, X 10% All transformer are connected to step up the voltage of the generator to transmission line voltage.

9 Choose a ase of 50MVA, 138kV in the 40Ω line 13.8 ase kv for the generator (1) and () kV ase kv for synchronous motor kV ase kv for the Y-Y transformer kV ase kv for the Y-Δ transformer kV for the generator (1) and () p.uz J for synchronous motor p.uz J for 3, Y-Y transformer p.uz J J0.343 p.u 0 50 J0.333 p.u J0.5 p.u for 3, Y-Δ transformer p.uz J J0.333 p.u 15 for 40 Ω line p.uz J J p.u ( 138) for 0 Ω line p.uz J 0 50 J p.u ( 138)

10 Chapter () Series impedance of transmission lines (7) One circuit of a single phase transmission line is composed of three solid 0.5 cm radius wires. The return circuit is composed of two 0.5 cm radius wires. The arrangement of conductors is shown in fig. Find the inductance of the complete line in henrys per meter (and in milli- henrys per mile). L x s 10 3 aa 7 ln a ac m s aa cc r x 0.5 x 10 - a c c a 6m ac ca 1m s m a c cc ca c m m n ad d cd ad e 4m cd 15m ae d ce 177 m m m L x x 10-7 ln ae e ce x 10-7 H/m For cord Y, s dd eede de ee r de ed 6m ed

11 s m m L y x 10-7 ln s L L x + L y x 10-7 H/m m 8.71 x 10-7 H/m (8) A three phase doule circuit line is composed of 300,000 (mil 6/7 ACSR ostrich conductors arranged as shown in Fig. Find the 60 Hz inductive reactance in ohms per mile per phase. ( s 0.09 ) Phase C (c -c ) Phase A (a -a ) Phase B ( - ) L 7 meq 10 ln H/m s Phase A, a-a B, - C, c-c P n.m AB aa a a a 10.1 ft d a 1.9 a 10.1 P AB

12 P n. m BC c c c 10.1 ft c c c 1.9 c P 4 BC P n m CA. caac a c ca c a 0 ac a c 18 P CA c dc P meq 16.1 For phase A, SA sd a s 0.09 d a-a P P P AB BC CA a SA For phase B, SB sd d SB For phase B, d c-c SC 3 Seq L 10 ln H/m P meq Seq ln x 10-7 H/m/P X l πfl π x 60 x 6.13 x 10-7 x Ω/mi/P

13 (9) A single phase 60 Hz power line is supported on a horizontal cross arm. Spacing etween conductors is.5m. A telephone line is supported on a horizontal cross arm 1.8m directly power line with a spacing of 1.0m etween the centers of its conductors. Find the mutual inductance etween the power line and telephone circuits and the 60 Hz voltage per kilometer induced in the telephone line if the current in the power line is 150A. φa φ ue to I a, flux leakage ψ ad c ac d ue to I a, ue to I, ψ ψ cd ( ) 7 I a ln +.51m + ( ) 1.95m cd I a 10 7 d I a.51 ln ln 1.95 Since I a and I are 180 out of phase, the total flux (due to oth I a and I ) 7.51 ψ cd ( total ) 4 10 I a ln 1.95 ψ cd Mutual inductance, M I a ln I a x 10-7 H/m 60 Hz telephone circuit V/km for 150A V cd πf MI a π x 60 x x 10-7 x 150 x V/km ad ac

14 (10) Find the GRM of each of the unconventional conductors shown in Fig: in terms of the radius of the individual strands. Solution; (a) aa cc dd r a ad c cd da dc a c r ac ca d d 8 r s GMR (0.7788r) (r) ( 8r) 1.78r () (c) aa cc dd r a ad c cd da dc a c r ac ca r r 3 r s GMR (0.7788r) (r) ( 3r) 1.69r aa cc r a c a c r ac ca 4r GMR ( r ) (r) (4r) r

15 (d) a f c d e aa cc dd ee ff r a a c c cd dc de ed ef fe fa af f f d d df fd r ac ca ae ea ce ec 4r ad da (4r) (r) 1r c c cf fc r r 3 r GMR (0.7788r) (r) (4r) ( 1r) ( 3r).1r (11) A three phase 60 Hz line has flat horizontal spacing. The conductors has a GRM of with 10m etween adjacent conductors. etermine the inductive reactance per phase in ohms per kilometer. What is the name of this conductor? s m m m 1.6m Inductance per phase, L x 10-7 ln x ln x 10-6 H/m 1.37 x 10-3 H/km Inductive reactance πfl π x 60 x 1.37 x Ω/km m s

16 (1) Calculate the inductive reactance in ohm per kilometer of a undle 60 Hz three phase line having three ACSR Rail conductors per undle with 45cm etween conductors of the undle. The spacing etween undle center is 9, 9 and 18 ( s ) 45cm, s s sd m m m XL π x x ln x 10-4 Ω/m 0.38 Ω/km (13) A 60Hz three phase line composed of an ASCR Bluejay conductor per phase has flat horizontal spacing of 11m etween adjacent conductors. Compare the inductive reactance in ohm per kilometer per phase of this line that of a line using a two conductor undle of ASCR 6/7 conductors having the same total cross sectional area of aluminium as the single phase conductor line and 11m spacing measured from the center of the undles. The spacing etween conductors in the undle is 40cm.( s ) s For 30 lines, eq m Inductive reactance, XL π x 60 x x 10-7 ln x 10-4 Ω/m 0.57 Ω/km For undle, 10 conductor, s m m 11m

17 X L π x 60 x x ln x 10-4 Ω/m 0.38 Ω/km 0.57 Compare with two condition, horizontal conductor 1.39 times of two undle conductors. (14) Six conductors of ASCR rake constitute a 60Hz doule circuit three phase line arranged in Fig. The vertical spacing however is 14 the longer horizontal distance is 3 and the short horizontal distance are 5. Find the inductance per phase per mile and the six inductive reactance in ohm per mile. ( s ) Solution; Phase A, a-a B, - C, c-c For P AB a a a a P AB For P BC c c c c 1.4 P BC P CA For ca c a 8

18 ca c a P CA P meq.97 For phase A, d 4 P P P AB BC CA SA s a a d a-a SA For phase B, SB sd d SB For phase C, SC sdc c d c-c d a-a SC Seq L 10 ln H/m P meq Seq ln x 10-7 H/m XL πfl π x 60 x 5.99 x 10-7 Ω/m/Ph.56 x 10-4 x Ω/m/phase

19 Chapter (3) Capacitance of Transmission Line (15) Find the capacitive reactance for 1 mi of the line as shown in Fig. If the length of the line is 175 mi and the normal operating voltage is 0kV, find the capacitive reactance to neutral for the entire length of the line, the charging current per mi and the total charging megavolt-amperes. (r ) eq , r X a X d log d πk Cn F/m to neutral eq ln( ) r 1 π x 10-1 F/m 4.8 ln( ) x 10-1 x 1609 F/mi 1 1 XC πfc x 10-1 x x 10 6 Ω/mi Xa x 10 6 Xd log d log x 10 6 Xc Xa + Xd x 10 6 Ω/mi to neutral For 175 mi, Xc 1066Ω to neutral 175 I chg πf C an V an π x 60 x x x 10-1 x A/mi For 175 mi, I chg x A Reactive power, Q 3 Vl I chg 3 x 0 x 10 3 x Mvars

20 (16) Find the 60Hz capacitive susceptance to neutral per mile per phase of the doule circuit line in ostrich. ( r ) r AB a a aa a a a 1.5 a AB 14.8 BC AB 14.8 CA eq 16.1 AB BC CA SA rd a a d a-a SA SB rd SC rd c c Seq 3 SA SB SC πk C n eq ln( ) s π ln( )

21 x F/m x x 1609 F/mi 1 1 B C πfc X C 1 πfc π x 60 x x x x 10-5 mho/mi to neutral (17) A three phase 60 Hz transmission line has its conductor arrange in a triangular formation so that two of the distances etween conductors are 5 and third is 4. The conductors are ASCR. Osprey. etermine the capacitance to neutral in microfarad per mile and the capacitive reactance to neutral in ohm-mile. If the line is 150mi long find the capacitance to neutral and capacitive reactance of the line. ( in) k 8.85 x r πk C an F/m meq ln r meq π C n x 10-8 F/mi to neutral 9.7 ln Xc πfc n π kω - mi to neutral For 150 mi, C n x 10-8 x μf to neutral X Cn Ω

22 (18) Calculate the capacitive reactance in ohm kilometer of a undle 60 Hz, 30 line having three ACSR Rail conductors per undle with 45cm etween conductors of the undle. The spacing etween undle centers is 9,9 and 18m.( 1.165in)k 8.85 x cm 45cm 45cm 9m 9m 1.165in r m 4 πk C an meq ln S meq m rd m s 1 π C an ln x 10-1 F/m 1 Xc πfc n π x 10 6 Ω km/p (19) A 60 Hz 30 line composed of one ACSR Bluejay conductor per phase has flat horizontal spacing of11m etween adjacent conductors. Compare the capacitive reactance in ohm kilometer per phase of this line with that of a line using a two conductor undle of ACSR 6/7 conductors having the same total cross sectional area of aluminum as the single conductor line and the 11m spacing measured etween undles. The spacing etween conductors in the undle is 40cm. ( 1.59 in) k 8.85 x in

23 r 0.016m 1 d 40cm 0.4m eq m rd m s 1 πk π C n eq ln ln 0.08 S x F/m to neutral x F/km to neutral 1 X cn πfc n 46 l kω- km to neutral For same total cross-sectional area Finch, r 1 1 πk π C n eq ln ln r x 10-9 F/km to neutral 1 X cn kω- km to neutral πfc n X cn (single conductor) > X cn (undled conductor) (0) Six conductors of ACSR rake constitute a 60 Hz doule circuit three phase line arranged as shown in Fig. The vertical spacing, however, is 14ft the longer horizontal distance is 3 Hz and the short horizontal distance are 5 ft. Find the capacitive reactance to neutral in ohm-miles and the charging current per mile per phase and per conductor at 138 kv. ( ) X c?, I chg?

24 πk C n ln Phase A, a-a B, - C, c-c eq S For phase A, Radius, r rd SA a a d a a SA SA For phase B, d SC 3 SB S For P AB SA SB SC a a a P BC P AB 1.4 ca 8ft c a ca 5 ft c a P 4 CA P eq 4 P P P AB BC CA.97 1 π C n 19.7 x 10-1 F/m.97 ln X c πfc n π x 10 6 Ω-mi to neutral

25 I chg πf V an C an π x 60 x A/mi 3 x 19.7 x 10-1 x 1609 Chapter (4) Sag Calculations and Some Features of Lighters of Lightning Protections (1) A transmission line conductor at a river crossing is supported from two towers at heights of 150 and 300 aove water level. The horizontal distance etween the towers is If the tension in the conductor is 460 l and the conductor weights l/ft, find the clearance etween the conductor and the water at a point midway etween the towers. Assume Paraolic configuration. y 1 150ft, y 300ft, l 1100ft, T 460 l, W c l/ft h y - y ft Th x 1 l- Wl ft Th x l+ Wl

26 ft x 1 + x x ft Wx d 1 ½ T ft Wx ½ T ft WX d T 460 From point B, Δd d d Clearance y - Δd () An overhead line has the following data. Span length 160m, conductor diameter 0.95cm, weight per unit length of the conductor 0.65 kg/m. Ultimate stress 450 kg/cm, wind pressure 40 kg/cm of projected area. Factor of safety is 5. Calculate the sag. Solution 1 160cm, diameter 0.95cm, Wc 0.65Kg /m, muximun stress 450Kg/cm, W wind 40 Kg / cm, S.F 5, Sag, d? max imum stress S.F working stress 450 Working stress 850 Kg / cm 5 πd π 0.95 Working tension kg 4 4 W wind 40kg/cm 0.95 cm 38kg/cm 0.38kg/m W Wv + Wn kg / m 1 WL d 3.998m T 60.5 (3) A transmission line conductor having a diameter of 19.5mm weights 0.85kg/m. The span is 75m. The wind pressure is 39 kg/m of projected area with ice coating of 13mm. The ultimate strength of the conductor is 8000kg. Calculate the maximum sag if the factor of safety is and ice weights 910 kg/m 3.

27 Solution iameter 195mm, Wc 0.85 kg/m, L 75m, wind Pressure 39mm Mun strength 8,00kg, Max sag d?, p.f, ice weight 910kg/m 3 overall diameter dia + L cm Projected area per wire length ( )m 1m m wind load 39kg /m 10 - m 1.775kg/m The area of section of ice [ π ( r + t) π r ] m Ice load 910kg/ m m kg/ m W ( Wc + W ) + W Working stress Max sag, d ice wind ( ) + (1.775).717kg / m max imumstree s.f WL T 6.41m.717(75/ ) kg (4) Consider an insulator made up of three porcelain disks as in Fig. Let the capacitance from the insulator hardware to the line conductor e considered negligile. Let the capacitive susceptances at a given frequency have the values shown in Fig. The lines in Fig represent metal. Find the proportion of voltage across disk.

28 Let V 1-4 E and V 1- V I 1-9Bv I 3Bv I -3 I 1- + I 9Bv + 3Bv 18V I 3 1Bv 4 V -3 V 9B 9B V 1-3 V 1- + V 3 v + V V I 3 V 1-3 B V B BV 3 3 But, I 3-4 I -3 + I 3 1BV + I 3 V 3-4 9B V 1-4 E BV BV BV V V 3 91 B V E V E 0.39E 7 V 1- V 0.39E V V E 0.319E V 3-4 V 0.39E 0.44E 7 7 V 1-4 E

29 (5) Find the proportion of voltage on each disk of the 3 disk suspension insulator shown in Fig. Let V 1-4 E and V 1- V I 1-9 BV I 3 BV I B V -4 B (V V 1- ) B (E-V) BE BV I -3 I 1- + I I 9BV + 3 BV (BE + BV) 13BV BE 13BV BE 13V E V -3 8B 9 13V E V E V 1-3 V 1- + V -3 V V E 44BV BE I 3 BV 1-3 B 9 9 I 3 B V 3-4 B (V 1-4 V 1-3 ) V E B (E - ) 9 10BV EV 9

30 I 3-4 I -3 + I 3 I 3 44BV BE 10BV EV (13VV BE) + ( ) - ( ) BV 1EV 9 I BV 1EV 1 183V 1E V 3-4 E 9B 9 9B 81 81E + 30E 381V 381 E V 3.43 V 111 V V V V V V V 9.14 % 3.43V 13V 3.43V 30.9 % 93.43V 183V 1(3.43V) 39.9 % V (6) Find the unstressed length at -0 F a 400,000 cmil copper conductor in a span etween two supports 400ft apart and of equal height. The maximum tension in conductor is to e 6500l. The weight of the conductor is 1.5l per ft and of its ice load 0.75l per ft. The wind load, with ice present, is 1.0l per ft. Take the modulus of elasticity to e 15,000,000 l per sq-in use short paraolic formula. Unstressed length, L u? (at 0 F) A 400,000 mil 400,000 4 π 10-6 in L 400ft T 6500 l W e 1.5 l/ft W ice 0.75 l/ft W wind 1.0 l/ft E 15,000,000 l/in T Stretch L ( ) AE W ( π 400, h v W + W ( ).361 l/ft 6 )

31 1 WL P L [1 + ( ) ] 6 T L u P Stretch 400, (at -0 F) 7. The unstressed length at 3 F of a 450,000 cmil copper conductor is 600 ft. The supports are at equal height and are 600 ft apart. Find the temperature at which the conductor has a sag of 14 ft, with no ice and no wind. The weight of conductor is 39 l/ft. Take the characteristics of copper cale to e as W c 1.39 l/ft, E l/in, α 0.000,0095 use the paraolic formula. Solution; L u1 600 (3 F) A450,000 cmil 450,000 4 π 10-6 in L W c 1.39 l/ft, t? E l/in 0.000, Wl d T L u P stretch lt Stretch AE 1 WL P L [1+ ( ) ] 6 T d T T l P 600 [1 + ( ) ] stretch π , L u L u L u1 [1 + (t t 1 )] [ ,0095 (t -3)] t 96.1 F

32 8. At a river crossing an overhead transmission line has a span of 560 m with the two supports of lowest conductor at 15 m and 95 m aove the water level. The weight of the conductor is kg/m. If the tension is adjusted to 100 kg, determine the clearance of the conductors aove the water level at a point 15 m the ase of the higher tower. Solution; p d p p 1 d y d 1 y 1 x 1 x x 15 m 560 m L 560 m, y 95 m, y 1 15 m, w0.394 kg/m,t100kg h y -y m Th x 1 L m wl Th x L m wl x x m Wx 0.394(715) d m T 100 Wx d m T 100 Δd d d m clearance y - Δd m

33 9. An overhead transmission line at a river crossing is supported from two towers at heights of 40 m and 90 m aove water level the horizontal distance etween the towers eing 400 m. If the maximum allowale tension is 000 kg, find clearance etween the conductor and water level at a point midway etween the towers. Weight of the conductor is 1 kg/m. Solution; B d p y d A y 1 d 1 x 1 x d x 15 m L y 1 40m, y 90 m, u400 m, T 000 kg, w1 kg/m h y y m Th x m wl Th x l m wl x1 + x x 50 m wx d m T 000 Δd d d m clearance y - Δd m

34 30. In fig: let there e 4 disks, the capacitive susceptance of the two connectors across each disk eing 10 B. The susceptance of each metal connector to ground is 4 B. Find the ratio of the voltage across the ottom disk to the voltage from line to ground. V4 5? V1 5 V 1- V I 1-10 BV I 1 4 BV I -3 I 1- + I 14BV I 3 7 V -3 V 10B 5 1 V 1-3 V 1- + V -3 V 5 I V 13 4B 5 48 V I 3-4 V+ 14BV V BV 118 V 3-4 V V 1-4 V + V

35 38 4 I 3 V BV I 4-5 I I 3 + BV BV 50 V 4-5 V V BV 13 V V V Where V1 5 V1 4 + V4 5 38V V 500 By TU(MawLaMyaing) yanaungoo@gmail.com

PowerWorld Transmission Line Parameter Calculator

PowerWorld Transmission Line Parameter Calculator PowerWorld Transmission Line Parameter Calculator Introduction The PowerWorld Transmission Line Parameter Calculator is a tool designed to compute characteristic line parameters given the type of the conductor

More information

Modeling of Transmission Lines

Modeling of Transmission Lines Modeling of Transmission Lines Electric Power Transmission The electric energy produced at generating stations is transported over high-voltage transmission lines to utilization points. The trend toward

More information

EEL303: Power Engineering I - Tutorial 4

EEL303: Power Engineering I - Tutorial 4 1. Determine the voltage at the generating station and the efficiency of the following system (Figure 1): Both transformers have ratio of 2kV/11kV. The resistance on LV side of both Figure 1: transformers

More information

Visa Smart Debit/Credit Certificate Authority Public Keys

Visa Smart Debit/Credit Certificate Authority Public Keys CHIP AND NEW TECHNOLOGIES Visa Smart Debit/Credit Certificate Authority Public Keys Overview The EMV standard calls for the use of Public Key technology for offline authentication, for aspects of online

More information

EDEXCEL NATIONAL CERTIFICATE/DIPLOMA UNIT 5 - ELECTRICAL AND ELECTRONIC PRINCIPLES NQF LEVEL 3 OUTCOME 4 - ALTERNATING CURRENT

EDEXCEL NATIONAL CERTIFICATE/DIPLOMA UNIT 5 - ELECTRICAL AND ELECTRONIC PRINCIPLES NQF LEVEL 3 OUTCOME 4 - ALTERNATING CURRENT EDEXCEL NATIONAL CERTIFICATE/DIPLOMA UNIT 5 - ELECTRICAL AND ELECTRONIC PRINCIPLES NQF LEVEL 3 OUTCOME 4 - ALTERNATING CURRENT 4 Understand single-phase alternating current (ac) theory Single phase AC

More information

Estimating Line-Flow Limits

Estimating Line-Flow Limits Estimating Line-Flow Limits University of Wisconsin-Madison May 1, 2013 Specifying reasonable line-flow limits requires two quantities: the surge impedance loading for the line and an estimate of the line

More information

PowerWorld Transmission Line Parameter Calculator Version 2

PowerWorld Transmission Line Parameter Calculator Version 2 PowerWorld Transmission Line Parameter Calculator Version 2 Introduction The PowerWorld Transmission Line Parameter Calculator (TransLineCalc) is a tool designed to compute characteristic line parameters

More information

Chapter 11. Inductors ISU EE. C.Y. Lee

Chapter 11. Inductors ISU EE. C.Y. Lee Chapter 11 Inductors Objectives Describe the basic structure and characteristics of an inductor Discuss various types of inductors Analyze series inductors Analyze parallel inductors Analyze inductive

More information

6 ELECTRICAL PARAMETERS

6 ELECTRICAL PARAMETERS 6 ELECTRICAL PARAMETERS For power, low voltage and medium voltage cables, cross section nominal areas are calculated in taking into account several parameters as: permissible current carrying capacities

More information

DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION

DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION ÿþ üûúùø öõöôùóùõò CT Dimensioning DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION Application note GER3973 1 CT Dimensioning ÿþ üûúùø öõöôùóùõò GER-3973 Application note ÿþ üûúùø öõöôùóùõò

More information

45. The peak value of an alternating current in a 1500-W device is 5.4 A. What is the rms voltage across?

45. The peak value of an alternating current in a 1500-W device is 5.4 A. What is the rms voltage across? PHYS Practice Problems hapters 8- hapter 8. 45. The peak value of an alternating current in a 5-W device is 5.4 A. What is the rms voltage across? The power and current can be used to find the peak voltage,

More information

EARTHING SYSTEM CALCULATION

EARTHING SYSTEM CALCULATION BAZIAN STEAL FACTORY S/S 132/11kV, 1x30/40MVA EARTHING SYSTEM CALCULATION Kurdistan Region Sulaimani May 2011 Bazian Steal Factory S/S 132/11kV, 1x30/40 MVA Contents: 1. Introduction... 3 2. List of references

More information

ASCII CODES WITH GREEK CHARACTERS

ASCII CODES WITH GREEK CHARACTERS ASCII CODES WITH GREEK CHARACTERS Dec Hex Char Description 0 0 NUL (Null) 1 1 SOH (Start of Header) 2 2 STX (Start of Text) 3 3 ETX (End of Text) 4 4 EOT (End of Transmission) 5 5 ENQ (Enquiry) 6 6 ACK

More information

AC Generators. Basic Generator

AC Generators. Basic Generator AC Generators Basic Generator A basic generator consists of a magnetic field, an armature, slip rings, brushes and a resistive load. The magnetic field is usually an electromagnet. An armature is any number

More information

Understanding Power Factor and How it Affects Your Electric Bill. Presented by Scott Peele PE

Understanding Power Factor and How it Affects Your Electric Bill. Presented by Scott Peele PE Understanding Power Factor and How it Affects Your Electric Bill Presented by Scott Peele PE Understanding Power Factor Definitions kva, kvar, kw, Apparent Power vs. True Power Calculations Measurements

More information

Impedance Matching and Matching Networks. Valentin Todorow, December, 2009

Impedance Matching and Matching Networks. Valentin Todorow, December, 2009 Impedance Matching and Matching Networks Valentin Todorow, December, 2009 RF for Plasma Processing - Definition of RF What is RF? The IEEE Standard Dictionary of Electrical and Electronics Terms defines

More information

CHAPTER 2 EXAMPLES AND TABLES

CHAPTER 2 EXAMPLES AND TABLES CHAPTER 2 EXAMPLES AND TABLES COMMENTARY AT 210.20(A) EXCEPTION An overcurrent device that supplies continuous and noncontinuous loads must have a rating that is not less than the sum of 100 percent of

More information

Application Note. So You Need to Measure Some Inductors?

Application Note. So You Need to Measure Some Inductors? So You Need to Measure Some nductors? Take a look at the 1910 nductance Analyzer. Although specifically designed for production testing of inductors and coils, in addition to measuring inductance (L),

More information

Measurement of Capacitance

Measurement of Capacitance Measurement of Capacitance Pre-Lab Questions Page Name: Class: Roster Number: Instructor:. A capacitor is used to store. 2. What is the SI unit for capacitance? 3. A capacitor basically consists of two

More information

Radial Distribution Test Feeders

Radial Distribution Test Feeders Radial Distribution Test Feeders Distribution System Analysis Subcommittee Report Abstract: Many computer programs are available for the analysis of radial distribution feeders. In 1992 a paper was published

More information

EDS 02-0027 11KV TRIPLEX CABLE

EDS 02-0027 11KV TRIPLEX CABLE THIS IS AN UNCONTROLLED DOCUMENT, THE READER MUST CONFIRM ITS VALIDITY BEFORE USE Document Number: EDS 02-0027 ENGINEERING DESIGN STANDARD EDS 02-0027 11KV TRIPLEX CABLE Network(s): EPN, LPN, SPN Summary:

More information

Contactless Power Transfer : Inductive charging of EV

Contactless Power Transfer : Inductive charging of EV Contactless Power Transfer : Inductive charging of EV 7-12-2010 P.Bauer Delft University of Technology Challenge the future EV have to be charged December 7, 2010 2 2 Chicken and egg problem December 7,

More information

Basic Wire Antennas. Part II: Loops and Verticals

Basic Wire Antennas. Part II: Loops and Verticals Basic Wire Antennas Part II: Loops and Verticals A loop antenna is composed of a single loop of wire, greater than a half wavelength long. The loop does not have to be any particular shape. RF power can

More information

Critical thin-film processes such as deposition and etching take place in a vacuum

Critical thin-film processes such as deposition and etching take place in a vacuum WHITEPAPER INTRODUCING POWER SUPPLIES AND PLASMA Critical thin-film processes such as deposition and etching take place in a vacuum SYSTEMS chamber in the presence of a plasma. A plasma is an electrically

More information

SYNCHRONOUS MACHINES

SYNCHRONOUS MACHINES SYNCHRONOUS MACHINES The geometry of a synchronous machine is quite similar to that of the induction machine. The stator core and windings of a three-phase synchronous machine are practically identical

More information

Synchronous generators are built in large units, their rating ranging from tens to hundreds of megawatts.

Synchronous generators are built in large units, their rating ranging from tens to hundreds of megawatts. II. Synchronous Generators Synchronous machines are principally used as alternating current (AC) generators. They supply the electric power used by all sectors of modern societies: industrial, commercial,

More information

NO LOAD & BLOCK ROTOR TEST ON THREE PHASE INDUCTION MOTOR

NO LOAD & BLOCK ROTOR TEST ON THREE PHASE INDUCTION MOTOR INDEX NO. : M-142 TECHNICAL MANUAL FOR NO LOAD & BLOCK ROTOR TEST ON THREE PHASE INDUCTION MOTOR Manufactured by : PREMIER TRADING CORPORATION (An ISO 9001:2000 Certified Company) 212/1, Mansarover Civil

More information

Chapter 24. Three-Phase Voltage Generation

Chapter 24. Three-Phase Voltage Generation Chapter 24 Three-Phase Systems Three-Phase Voltage Generation Three-phase generators Three sets of windings and produce three ac voltages Windings are placed 120 apart Voltages are three identical sinusoidal

More information

EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID

EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID Tension (kv) Impedance (Ohms) EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID frequency (Hz) Simon DESCHANVRES Yannick VERNAY RTE, CNER, Substations Department t (ms) EMTP-RV Users Group

More information

Power Technology Issue 104. Modeling of Two-Winding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E

Power Technology Issue 104. Modeling of Two-Winding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E SIEMENS Siemens Energy, Inc. Power Technology Issue 104 Modeling of TwoWinding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E Carlos GrandeMoran, Ph.D. Principal Consultant

More information

Lecture Notes ELE A6

Lecture Notes ELE A6 ecture Notes EE A6 Ramadan El-Shatshat Three Phase circuits 9/12/2006 EE A6 Three-phase Circuits 1 Three-phase Circuits 9/12/2006 EE A6 Three-phase Circuits 2 Advantages of Three-phase Circuits Smooth

More information

Coupling Effect in Substation Ground Measurements

Coupling Effect in Substation Ground Measurements SERBIAN JOURNAL OF ELECTRICAL ENGINEERING Vol. 9, No. 3, October 2012, 315-324 UDK: 621.316.13.011.2 DOI: 10.2298/SJEE1203315F Coupling Effect in Substation Ground Measurements Alex Farber 1, Boris Katz

More information

ATTACHMENT F. Electric Utility Contact Information Utility Name. For Office Use Only

ATTACHMENT F. Electric Utility Contact Information Utility Name. For Office Use Only ATTACHMENT F CATEGORY 2 GENERATOR INTERCONNECTION APPLICATION FOR ALL PROJECTS WITH AGGREGATE GENERATOR OUTPUT OF MORE THAN 20 KW BUT LESS THAN OR EQUAL TO 150 KW Also Serves as Application for Category

More information

BALANCED THREE-PHASE AC CIRCUIT

BALANCED THREE-PHASE AC CIRCUIT BAANCED THREE-PHASE AC CRCUT Balanced Three-Phase oltage Sources Delta Connection Star Connection Balanced 3-hase oad Delta Connection Star Connection Power in a Balanced Phase Circuit ntroduction Three

More information

Chapter 12: Three Phase Circuits

Chapter 12: Three Phase Circuits Chapter 12: Three Phase Circuits 12.1 What Is a Three Phase Circuit? 12.2 Balance Three Phase Voltages 12.3 Balance Three Phase Y to Y Connection 12.4 Other Balance Three Phase Connections 12.5 Power in

More information

EMDX3 Multifunction meter Cat No. 146 69 ModbusTable LGR EN v1.01.xls

EMDX3 Multifunction meter Cat No. 146 69 ModbusTable LGR EN v1.01.xls GENERAL MODBUS TABLE ORGANIZATION Starting of the Starting of the Group s Group s System Version (Release) System Version (Build) Group Name (Text) Group Code Group Complexity Group Version 50512 C550

More information

Basic Electrical Technology Dr. L. Umanand Department of Electrical Engineering Indian Institute of Science, Bangalore. Lecture - 33 3 phase System 4

Basic Electrical Technology Dr. L. Umanand Department of Electrical Engineering Indian Institute of Science, Bangalore. Lecture - 33 3 phase System 4 Basic Electrical Technology Dr. L. Umanand Department of Electrical Engineering Indian Institute of Science, Bangalore Lecture - 33 3 phase System 4 Hello everybody. So, in the last class we have been

More information

Voltage Loss Formula s

Voltage Loss Formula s www.litz-wire.com HM Wire International Inc. Phone: 330-244-8501 Fax: 330-244-8561 Voltage Loss Formula s www.hmwire.com Voltage loss in a wire is synonymous to pressure loss in a pipe. Electric current

More information

Apprentice Telecommunications Technician Test (CTT) Study Guide

Apprentice Telecommunications Technician Test (CTT) Study Guide Apprentice Telecommunications Technician Test (CTT) Study Guide 1 05/2014 Study Guide for Pacific Gas & Electric Company Apprentice Telecommunications Technician Qualifying Test (CTT) About the Test The

More information

Aircraft Electrical System

Aircraft Electrical System Chapter 9 Aircraft Electrical System Introduction The satisfactory performance of any modern aircraft depends to a very great degree on the continuing reliability of electrical systems and subsystems.

More information

Electron S.R.L. A29 ELECTRICAL POWER SYSTEM TRAINERS. Production Transmission Distribution

Electron S.R.L. A29 ELECTRICAL POWER SYSTEM TRAINERS. Production Transmission Distribution lectron S..L. Design Production & Trading of ducational quipment A29 LCTICAL POW SYSTM TAINS Production Transmission Distribution FAX 9065 980 - -mail: electron@electron.it Web: www.electron.it ev 02 Specifications

More information

Induction Motor Theory

Induction Motor Theory PDHonline Course E176 (3 PDH) Induction Motor Theory Instructor: Jerry R. Bednarczyk, P.E. 2012 PDH Online PDH Center 5272 Meadow Estates Drive Fairfax, VA 22030-6658 Phone & Fax: 703-988-0088 www.pdhonline.org

More information

Full representation of the real transformer

Full representation of the real transformer TRASFORMERS EQVALET CRCT OF TWO-WDG TRASFORMER TR- Dots show the points of higher potential. There are applied following conventions of arrow directions: -for primary circuit -the passive sign convention

More information

High Voltage Systems. Today. The history of cables

High Voltage Systems. Today. The history of cables High Voltage Cables High Voltage Systems Today Prysmian Cables and Systems B.V. is part of the Prysmian Group, a leading player in the industry of high-technology cables and systems for energy and telecommunications,

More information

2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated?

2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated? Extra Questions - 2 1. A straight length of wire moves through a uniform magnetic field. The e.m.f. produced across the ends of the wire will be maximum if it moves: a) along the lines of magnetic flux

More information

DHANALAKSHMI COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING EE2302 - ELECTRICAL MACHINES II UNIT-I SYNCHRONOUS GENERATOR

DHANALAKSHMI COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING EE2302 - ELECTRICAL MACHINES II UNIT-I SYNCHRONOUS GENERATOR 1 DHANALAKSHMI COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Constructional details Types of rotors EE2302 - ELECTRICAL MACHINES II UNIT-I SYNCHRONOUS GENERATOR PART A 1.

More information

Module Title: Electrotechnology for Mech L7

Module Title: Electrotechnology for Mech L7 CORK INSTITUTE OF TECHNOLOGY INSTITIÚID TEICNEOLAÍOCHTA CHORCAÍ Autumn Examinations 2012 Module Title: Electrotechnology for Mech L7 Module Code: ELEC7007 School: School of Mechanical, Electrical and Process

More information

TRANSFORMER: THREE PHASE

TRANSFORMER: THREE PHASE CONTENTS Transformer : Three Phase 1211 C H A P T E R 33 Learning Objectives Three-phase Transformers Three-phase Transformer Connections Star/Star or Y/Y Connection Delta-Delta or Connection Wye/Delta

More information

Single and Three Phase Transformer Testing Using Static Motor Circuit Analysis Techniques

Single and Three Phase Transformer Testing Using Static Motor Circuit Analysis Techniques Single and Three Phase Transformer Testing Using Static Motor Circuit Analysis Techniques Howard W. Penrose, Ph.D On behalf of ALL-TEST Pro, LLC Old Saybrook, CT Introduction Field and shop testing of

More information

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application g Digital Energy ITI Instrument Transformer Basic Technical Information and Application Table of Contents DEFINITIONS AND FUNCTIONS CONSTRUCTION FEATURES MAGNETIC CIRCUITS RATING AND RATIO CURRENT TRANSFORMER

More information

Three phase circuits

Three phase circuits Three phase circuits THREE PHASE CIRCUITS THREE-PHASE ADVANTAGES 1. The horsepower rating of three-phase motors and the kva rating of three-phase transformers are 150% greater than single-phase motors

More information

www.mathsbox.org.uk Displacement (x) Velocity (v) Acceleration (a) x = f(t) differentiate v = dx Acceleration Velocity (v) Displacement x

www.mathsbox.org.uk Displacement (x) Velocity (v) Acceleration (a) x = f(t) differentiate v = dx Acceleration Velocity (v) Displacement x Mechanics 2 : Revision Notes 1. Kinematics and variable acceleration Displacement (x) Velocity (v) Acceleration (a) x = f(t) differentiate v = dx differentiate a = dv = d2 x dt dt dt 2 Acceleration Velocity

More information

How To Understand And Understand The Theory Of Electricity

How To Understand And Understand The Theory Of Electricity DIRECT CURRENT AND ALTERNATING CURRENT SYSTEMS N. Rajkumar, Research Fellow, Energy Systems Group, City University Northampton Square, London EC1V 0HB, UK Keywords: Electrical energy, direct current, alternating

More information

Chapter 11 Balanced Three-Phase Circuits

Chapter 11 Balanced Three-Phase Circuits Chapter 11 Balanced Three-Phase Circuits 11.1-2 Three-Phase Systems 11.3 Analysis of the Y-Y Circuit 11.4 Analysis of the Y- Circuit 11.5 Power Calculations in Balanced Three-Phase Circuits 11.6 Measuring

More information

Power Technology Issue 106. Modeling of Three-Winding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E

Power Technology Issue 106. Modeling of Three-Winding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E SIEMENS Siemens Energy, Inc. Power Technology Issue 106 Modeling of Three-Winding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E Carlos Grande-Moran, Ph.D. Principal

More information

Introduction. Three-phase induction motors are the most common and frequently encountered machines in industry

Introduction. Three-phase induction motors are the most common and frequently encountered machines in industry Induction Motors Introduction Three-phase induction motors are the most common and frequently encountered machines in industry - simple design, rugged, low-price, easy maintenance - wide range of power

More information

Bill is the author of 15 papers and lectures on transmission lines and other power system topics.

Bill is the author of 15 papers and lectures on transmission lines and other power system topics. Transmission Lines Electricity s Highway This talk starts with an explanation of Surge Impedance Loading and demonstrates how it is used for transmission line work. The St. Clair Curve widely used in transmission

More information

PacifiCorp Original Sheet No. 476 FERC Electric Tariff, Substitute 6 th Rev Volume No. 11 APPENDIX 2 TO SGIP

PacifiCorp Original Sheet No. 476 FERC Electric Tariff, Substitute 6 th Rev Volume No. 11 APPENDIX 2 TO SGIP PacifiCorp Original Sheet No. 476 APPENDIX 2 TO SGIP SMALL GENERATOR INTERCONNECTION REQUEST (Application Form) Transmission Provider: Designated Contact Person: Address: Telephone Number: An Interconnection

More information

Circuits with inductors and alternating currents. Chapter 20 #45, 46, 47, 49

Circuits with inductors and alternating currents. Chapter 20 #45, 46, 47, 49 Circuits with inductors and alternating currents Chapter 20 #45, 46, 47, 49 RL circuits Ch. 20 (last section) Symbol for inductor looks like a spring. An inductor is a circuit element that has a large

More information

DS 600. A contact free flux gate based current measurement sensor 600A rms

DS 600. A contact free flux gate based current measurement sensor 600A rms DS 600 A contact free flux gate based current measurement sensor 600A rms DS 600 is member of the small housing sensor family. The family includes a 200A and a 600A version. 600A rms - 900A peak Maximum

More information

Prepared By: Sheilani Binti Shaari Department of Electrical Engineering/PKB

Prepared By: Sheilani Binti Shaari Department of Electrical Engineering/PKB Prepared By: Sheilani Binti Shaari Department of Electrical Engineering/ Course Learning Outcome (CLO) Upon completion of this course, students should be able to: Apply the principles of three phase systems,

More information

Static Analysis of Power Systems. Lennart Söder and Mehrdad Ghandhari

Static Analysis of Power Systems. Lennart Söder and Mehrdad Ghandhari Static Analysis of Power Systems Lennart Söder and Mehrdad Ghandhari Electric Power Systems Royal Institute of Technology August 200 ii Contents Introduction 2 Power system design 3 2. The development

More information

CHAPTER VIII LINE PLANT SYSTEM COMMUNICATION THROUGH RE CABLE

CHAPTER VIII LINE PLANT SYSTEM COMMUNICATION THROUGH RE CABLE CHAPTER VIII LINE PLANT SYSTEM COMMUNICATION THROUGH RE CABLE 8.1 SYSTEM 8.1.1 Armoured, screened underground cables are used for control communication in electrified areas to limit induction effect. 8.2

More information

IV. Three-Phase Induction Machines. Induction Machines

IV. Three-Phase Induction Machines. Induction Machines IV. Three-Phase Induction Machines Induction Machines 1 2 3 4 5 6 7 8 9 10 11 12 13 Example 1: A 480V, 60 Hz, 6-pole, three-phase, delta-connected induction motor has the following parameters: R 1 =0.461

More information

Vrieswijk, T & Srinivasan,A Amerongen,NL, 25 januari 2012

Vrieswijk, T & Srinivasan,A Amerongen,NL, 25 januari 2012 Theory Current Transformers Vrieswijk, T & Srinivasan,A Amerongen,NL, 25 januari 2012 Theory Current Transformers 25 januari 2012 Topics - Theory of current transformers (CTs) - Equivalent Circuit for

More information

Chapter 15, example problems:

Chapter 15, example problems: Chapter, example problems: (.0) Ultrasound imaging. (Frequenc > 0,000 Hz) v = 00 m/s. λ 00 m/s /.0 mm =.0 0 6 Hz. (Smaller wave length implies larger frequenc, since their product,

More information

Physics 3330 Experiment #2 Fall 1999. DC techniques, dividers, and bridges R 2 =(1-S)R P R 1 =SR P. R P =10kΩ 10-turn pot.

Physics 3330 Experiment #2 Fall 1999. DC techniques, dividers, and bridges R 2 =(1-S)R P R 1 =SR P. R P =10kΩ 10-turn pot. Physics 3330 Experiment #2 Fall 1999 DC techniques, dividers, and bridges Purpose You will gain a familiarity with the circuit board and work with a variety of DC techniques, including voltage dividers,

More information

V.A PJM Design and Application of Overhead Transmission Lines 69kV and Above

V.A PJM Design and Application of Overhead Transmission Lines 69kV and Above V.A PJM Design and Application of Overhead Transmission Lines 69kV and Above These design criteria have been established to assure acceptable reliability of the bulk transmission system facilities. These

More information

CONFLEX ELECTRIC CABLE

CONFLEX ELECTRIC CABLE CONFLEX ELECTRIC CABLE CONFLEX - 0.6/1kV Flexible VSD/EMC Cables Applications WW VSD/EMC cables are manufactured for use where electrical interference distorts signal transmission in electric motors. Standard

More information

Tutorial One: Calculation of leakage inductance of transformer using FEM. 31.5 MVA, 132 kv/33kv, Y/, Ampere-turns: 135024, No.

Tutorial One: Calculation of leakage inductance of transformer using FEM. 31.5 MVA, 132 kv/33kv, Y/, Ampere-turns: 135024, No. Tutorial One: Calculation of leakage inductance of transformer using FEM Consider a transformer with the following rating: 31.5 MVA, 132 kv/33kv, Y/, Ampere-turns: 135024, No. of HV turns = 980 Although

More information

STANDARDS. Site-Specific Loss Adjustments PUBLIC

STANDARDS. Site-Specific Loss Adjustments PUBLIC STANDARDS PUBLIC MDP_STD_0005 Site-Specific Loss Adjustments Requirements for Adjustment of Meter Readings for Site-Specific Losses in the IESO-Administered Market Issue 4.0 This standard provides the

More information

AC Power. by Prof. Dr. Osman SEVAİOĞLU Electrical and Electronics Engineering Department

AC Power. by Prof. Dr. Osman SEVAİOĞLU Electrical and Electronics Engineering Department by Prof. Dr. Osman SEVAİOĞLU Electrical and Electronics Engineering Department EE 209 Fundamentals of Electrical and Electronics Engineering, Prof. Dr. O. SEVAİOĞLU, Page 1 Voltage Waveform Consider the

More information

Physics 1114: Unit 6 Homework: Answers

Physics 1114: Unit 6 Homework: Answers Physics 1114: Unit 6 Homework: Answers Problem set 1 1. A rod 4.2 m long and 0.50 cm 2 in cross-sectional area is stretched 0.20 cm under a tension of 12,000 N. a) The stress is the Force (1.2 10 4 N)

More information

Mathematical Modeling and Dynamic Simulation of a Class of Drive Systems with Permanent Magnet Synchronous Motors

Mathematical Modeling and Dynamic Simulation of a Class of Drive Systems with Permanent Magnet Synchronous Motors Applied and Computational Mechanics 3 (2009) 331 338 Mathematical Modeling and Dynamic Simulation of a Class of Drive Systems with Permanent Magnet Synchronous Motors M. Mikhov a, a Faculty of Automatics,

More information

Chapter 3 AUTOMATIC VOLTAGE CONTROL

Chapter 3 AUTOMATIC VOLTAGE CONTROL Chapter 3 AUTOMATIC VOLTAGE CONTROL . INTRODUCTION TO EXCITATION SYSTEM The basic function of an excitation system is to provide necessary direct current to the field winding of the synchronous generator.

More information

GUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables

GUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables Engineering Department SEPTEMBER, 2007 GUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables General Requirements This section applies to all public and private utilities,

More information

Effective: September 10, 2006 Vermont Attachment 1 to Rule 5.500 Public Service Board Page 1 of 6

Effective: September 10, 2006 Vermont Attachment 1 to Rule 5.500 Public Service Board Page 1 of 6 Public Service Board Page 1 of 6 STANDARD APPLICATION FOR INTERCONNECTION OF GENERATION RESOURCES IN PARALLEL TO THE ELECTRIC SYSTEM OF: (Interconnecting Utility) Preamble and Instructions: An owner of

More information

Estimating AC Mitigation Requirements for Pipelines Installed in High Voltage AC Corridors: Fault Conditions

Estimating AC Mitigation Requirements for Pipelines Installed in High Voltage AC Corridors: Fault Conditions Estimating AC Mitigation Requirements for Pipelines Installed in High Voltage AC Corridors: Fault Conditions R. D. Southey, Eng. W. Ruan, Ph.D. F. P. Dawalibi, Eng., Ph.D. S. Fortin, Ph.D. Safe Engineering

More information

Direction of current flow through conductor. Fig. 1 Magnetic field generated by current flow

Direction of current flow through conductor. Fig. 1 Magnetic field generated by current flow ingle Conductor Cable Copper heathed Cable heath Currents ingle conductor cables present certain application considerations that do not arise in multiconductor cable installations. These considerations

More information

GENERATOR SELECTION. a. Three phase - 120/208V, 3 phase, 4W wye; 277/408, 3 phase, 4W wye; * 120/240V 3 phase, 4W Delta

GENERATOR SELECTION. a. Three phase - 120/208V, 3 phase, 4W wye; 277/408, 3 phase, 4W wye; * 120/240V 3 phase, 4W Delta GENERATOR SELECTION Generators must be sized to handle their load based on the continuous KW, kilowatt load, and KVA, kilovoltamp load, and the worst case starting load KW + KVA. They must be derated for

More information

Gulf Cable & Electrical Ind. Co.

Gulf Cable & Electrical Ind. Co. CONTENTS INTRODUCTION PRODUCT RANGE I PRODUCT DATA TABLES XLPE INSULATED 600/1000V CABLES Two Core Cables CU/XLPE/PVC/LC/PVC/SWA/PVC 1 Three Core Cables CU/XLPE/PVC/LC/PVC/SWA/PVC 2 Four Core Cables CU/XLPE/PVC/LC/PVC/SWA/PVC

More information

CROSS REFERENCE. Cross Reference Index 110-122. Cast ID Number 110-111 Connector ID Number 111 Engine ID Number 112-122. 2015 Ford Motor Company 109

CROSS REFERENCE. Cross Reference Index 110-122. Cast ID Number 110-111 Connector ID Number 111 Engine ID Number 112-122. 2015 Ford Motor Company 109 CROSS REFERENCE Cross Reference Index 110-122 Cast ID Number 110-111 Connector ID Number 111 112-122 2015 Ford Motor Company 109 CROSS REFERENCE Cast ID Number Cast ID Ford Service # MC Part # Part Type

More information

SERVER CERTIFICATES OF THE VETUMA SERVICE

SERVER CERTIFICATES OF THE VETUMA SERVICE Page 1 Version: 3.4, 19.12.2014 SERVER CERTIFICATES OF THE VETUMA SERVICE 1 (18) Page 2 Version: 3.4, 19.12.2014 Table of Contents 1. Introduction... 3 2. Test Environment... 3 2.1 Vetuma test environment...

More information

1 Introduction. 2 The Symmetrical Component Transformation. J.L. Kirtley Jr.

1 Introduction. 2 The Symmetrical Component Transformation. J.L. Kirtley Jr. Massachusetts Institute of Technology Department of Electrical Engineering and Computer Science 6.06 Introduction to Power Systems Class Notes Chapter 4 Introduction To Symmetrical Components J.L. Kirtley

More information

Objectives 200 CHAPTER 4 RESISTANCE

Objectives 200 CHAPTER 4 RESISTANCE Objectives Explain the differences among conductors, insulators, and semiconductors. Define electrical resistance. Solve problems using resistance, voltage, and current. Describe a material that obeys

More information

Transformer circuit calculations

Transformer circuit calculations Transformer circuit calculations This worksheet and all related files are licensed under the Creative Commons Attribution License, version 1.0. To view a copy of this license, visit http://creativecommons.org/licenses/by/1.0/,

More information

BASIC ELECTRONICS AC CIRCUIT ANALYSIS. December 2011

BASIC ELECTRONICS AC CIRCUIT ANALYSIS. December 2011 AM 5-202 BASIC ELECTRONICS AC CIRCUIT ANALYSIS December 2011 DISTRIBUTION RESTRICTION: Approved for Pubic Release. Distribution is unlimited. DEPARTMENT OF THE ARMY MILITARY AUXILIARY RADIO SYSTEM FORT

More information

Current and Temperature Ratings

Current and Temperature Ratings Document 361-1 Current and Temperature Ratings Introduction This application note describes: How to interpret Coilcraft inductor current and temperature ratings Our current ratings measurement method and

More information

Power measurement in balanced 3 phase circuits and power factor improvement. 1 Power in Single Phase Circuits. Experiment no 1

Power measurement in balanced 3 phase circuits and power factor improvement. 1 Power in Single Phase Circuits. Experiment no 1 Experiment no 1 Power measurement in balanced 3 phase circuits and power factor improvement 1 Power in Single Phase Circuits Let v = m cos(ωt) = cos(ωt) is the voltage applied to a R-L circuit and i =

More information

The common ratio in (ii) is called the scaled-factor. An example of two similar triangles is shown in Figure 47.1. Figure 47.1

The common ratio in (ii) is called the scaled-factor. An example of two similar triangles is shown in Figure 47.1. Figure 47.1 47 Similar Triangles An overhead projector forms an image on the screen which has the same shape as the image on the transparency but with the size altered. Two figures that have the same shape but not

More information

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw 4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and

More information

Candidate Number. General Certificate of Education Advanced Level Examination June 2012

Candidate Number. General Certificate of Education Advanced Level Examination June 2012 entre Number andidate Number Surname Other Names andidate Signature General ertificate of Education dvanced Level Examination June 212 Physics PHY4/1 Unit 4 Fields and Further Mechanics Section Monday

More information

Mutual Inductance and Transformers F3 3. r L = ω o

Mutual Inductance and Transformers F3 3. r L = ω o utual Inductance and Transformers F3 1 utual Inductance & Transformers If a current, i 1, flows in a coil or circuit then it produces a magnetic field. Some of the magnetic flux may link a second coil

More information

Request for Payment Instructions Wholesale Distribution Access Tariff (WDAT) Attachment I - GIP

Request for Payment Instructions Wholesale Distribution Access Tariff (WDAT) Attachment I - GIP Grid Interconnection & Contract Development Request for Payment Instructions Wholesale Distribution Access Tariff (WDAT) Attachment I - GIP Submittal Instructions Prior to submitting your application and

More information

Candidate Number. General Certificate of Education Advanced Level Examination June 2014

Candidate Number. General Certificate of Education Advanced Level Examination June 2014 entre Number andidate Number Surname Other Names andidate Signature General ertificate of Education dvanced Level Examination June 214 Physics PHY4/1 Unit 4 Fields and Further Mechanics Section Wednesday

More information

Ohm's Law and Circuits

Ohm's Law and Circuits 2. Conductance, Insulators and Resistance A. A conductor in electricity is a material that allows electrons to flow through it easily. Metals, in general, are good conductors. Why? The property of conductance

More information

KNOW YOUR OPTIONS: 230 KV POWER CABLES

KNOW YOUR OPTIONS: 230 KV POWER CABLES KNOW YOUR OPTIONS: 230 KV POWER CABLES 71 CONDUCTOR MATERIAL AND SIZE Conductor material is a matter of both customer preference and required current carrying capacity At 230 kv, copper is most common

More information

Short Circuit Current Calculations

Short Circuit Current Calculations Introduction Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective devices based on these sections mandate that

More information

PI734D - Technical Data Sheet

PI734D - Technical Data Sheet PI734D - Technical Data Sheet PI734D SPECIFICATIONS & OPTIONS STANDARDS Newage Stamford industrial generators meet the requirements of BS EN 60034 and the relevant sections of other national and international

More information

Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer

Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer A Short Circuit analysis is used to determine the magnitude of short

More information