1 Humidification in pear storage Phase 1 Jan Verschoor, M. Sc. Report no. 1040
2 Colophon Title Author(s) AFSG number ISBN-number Publication date Confidential OPD code Approved by Humidification in pear storage - phase1 Jan Verschoor, M. Sc April 2009 No OPD code H.L.M.M. Maas, M. Sc. Agrotechnology and Food Sciences Group P.O. Box 17 NL-6700 AA Wageningen Tel: +31 (0) [email protected] Internet: Agrotechnology and Food Innovations b.v. All rights reserved. No part of this publication may be reproduced, stored in a retrieval system of any nature, or transmitted, in any form or by any means, electronic, mechanical, photocopying, recording or otherwise, without the prior permission of the publisher. The publisher does not accept any liability for inaccuracies in this report. The quality management system of Agrotechnology and Food Innovations b.v. has been certified by SGS International Certification Services EESV on the basis of ISO 9001:
3 Table of Contents 1 Introduction Context Goals 2 Test design 2.1 Humidity installation and test rooms 2.2 Quality assessments Quality determinations 2.3 Statistics 3 Results and discussion 3.1 Execution of test 3.2 Humidification and fluid discharge RH measurements during the waiting period Course of humidification and water discharge during CA conditioning Ice formation 3.3 Weight loss stacking crates during storage 3.4 Quality evaluations Conclusions Hardness Base color Weakness score Sugar content External and internal abnormalities 5 Points to note and recommendations Acknowledgements Agrotechnology and Food Innovations b.v., part of Wageningen UR 3
4 1 Introduction 1.1 Context Contronics wishes to gain more insight into the operation of its in-house humidification system for pear storage. This is to aid the promotion of the implementation of its humidification techniques in the fruit sector. Contronics is interested in an independent opinion from Wageningen UR about the functioning of its system. 1.2 Goals The goal of this project is to experimentally determine 1) what the effect of humidification is on the quality of pears during CA storage and 2) if the installed humidification equipment functions as it is designed to function. 4 Agrotechnology and Food Innovations b.v., part of Wageningen UR
5 2 Test design 2.1 Humidification installation and test rooms This practical test was performed in two test rooms at Fruitmasters Veiling B.V., Geldermalsen, that were as identical as possible in terms of technical layout and product batch : one without humidification, one with Contronics humidification, see Illustration 1. This humidification installation consists of an ultrasonic humidifier HU-25 placed outside the storage room with a yield of 0 to 1.2 kg per hour with a DZR-43 RH control that is placed in a gas-tight casing with its own circulation to and from the storage room without disturbing the CA regime (% O 2 and CO 2 ). All this was connected to an existing supply pipe using a T-section, where the supply to the room is placed through a pipe with a smaller diameter in the supply line. This means that there are no additional passages required in the room wall and maintenance can safely take place without disturbing the room climate. Water provision is controlled by a connection to a water pipe via a filter module with a storage vat. Control of the ultrasonic humidifier in the module takes place on the basis of measuring the relative humidity of the air sucked in by the RH sensor/control unit. [RH: Relative Humidity] Illustration 1 Set up of Contronics humidification installation in this test. Left the closed module when in use, right a view of the opened module 1) gas-tight system cabinet 2) water filter unit 3) filtered water storage vat 4) combined supply room air /discharge humidified air 5) RH sensor/control DRZ-43 6) Ultrasonic humidifier HU-25 7) collection vat for measuring melt water from evaporator in the room (part of the regular room installation) Agrotechnology and Food Innovations b.v., part of Wageningen UR 5
6 The RH value of the incoming air in the module is continuously monitored, and the ultrasonic unit is controlled on the basis of this measured value. The outgoing humidified gas flow was guided through a small pipe in the middle, just under the evaporator in front of the curtain; see Illustration 2. A B Illustration 2 A) RH sensor/controller unit on the humidification module B) Outlet nozzle for the humidified air (in an empty room, in a filled room the bins touch the curtain) The control room was not equipped with this humidification installation. Both rooms were intended for CA storage of Conference pears until February. The pears are stored in wooden storage bins of about 450 kg, without a plastic cover sheet or sleeve. The Conference pears in both rooms were mostly from the same source. Twelve inventory bins were taken from this source, and after weighing these were placed back in the test rooms in the positions described in Illustration 3 to be able to determine the loss of moisture during the storage period. Both rooms were conditioned according to the standard protocol for CA conditioning, including a 21-day waiting period before starting to reduce the oxygen content. The final oxygen content was 3%, % CO 2 <1% %. The water emission through the evaporator of the cooling installation was monitored during the storage period as well as any possible ice accumulation. Side view test room ver Evaporator inlet point Contronics humidification Circulation direction Top view rest room storage 9 Evaporator storage 8 rear/ high rij 1 row 1 storage rij 2 ks front/low left middle/ middle left rear/ high left row 2 storage 6 rij 3 row 3 storage 5 middle/ middle inlet nozzle Contronics rij 4 circulation direction row 4 door storage 4 rij 5 row 5 storage 3 rij 6 right front/low right middle/ middle right rear/ high right row 6 storage 2 front/low rij row 7 storage 1 stack 1 stack 2 stack 3 stack 4 stack 5 stack 6 stack 7 stack 8 stack 9 stack 1 stack 2 stack 3 stack 4 stack 5 stack 6 stack 7 stack 8 stack 9 Illustration 3 Side and top view of the configuration of the humidification installation in the storage room. The position of the sample crates monitored for moisture loss and quality are indicated in green; these positions were identical to those in the control room. 6 Agrotechnology and Food Innovations b.v., part of Wageningen UR
7 2.2 Quality Assessments In addition to the monitoring of fluid loss described above, the quality of the fruit was also followed. Per object/position in the room two samples of 20 fruits were continually assessed for quality. This was done during the stocking and after the storage of the pears. In addition, the quality at the end of the chain is simulated (display life) after storage at a higher temperature. This is performed at 18 C and 75% RH. At the time of stocking for the test, the display life period was 7 days, after storage, a period of 5 days was adhered to due to the usual quicker ripening after storage Quality determinations When stocking the pears in the storage rooms, sample crates were marked at specific positions. These crates were weighed during storage and again during room opening to determine the weight loss at various positions in the test rooms. In addition, during storage and removal, samples of 40 fruits were collected from the various objects, from which the following quality measurements were taken immediately and after a display period at 18 C: Hardness The firmness of the pears (kg/cm 2 ) is measured using an automated penetrometer (Fruit Texture Analyzer, Güss, South Africa) equipped with a pear plunger. Base color The color determination of the green base color is performed by scoring individual fruits using a color chart suitable for pears, and from this calculate a lot-average. This color chart has a score of 1 to 5 in 0.5 increments, where green is a low score and yellow is a high score. Weakness score The weakness score indicates the degree of "weak necks" of a lot, a quality problem in Conference pears associated with fluid loss. See clarification below. Sugar content The total content of dissolved substance is determined using a digital refractometer in Brix. This is generally used as a convenient measurement for the sugar content. A representative selection per fruit is ground into a mixed sample per object from which the sugar content is determined in duplicate. External and internal abnormalities Clarification of weakness score: By giving a score by fruit on the basis of wrinkling that is or is not present according to the table below, an average weakness score by lot can be determined. The score goes from 0 (no single problem) to 4 (all fruits seriously weak) Agrotechnology and Food Innovations b.v., part of Wageningen UR 7
8 Score description 0 OK 1 Wrinkles at bending 2 First wrinkles visible Explanation Visually no wrinkles can be observed, neck feels stiff at light attempt to bend it, still no wrinkling visible Visually no wrinkles observable, at light attempt to bend using the thumb, the neck bends and a slight wrinkling becomes visible When examined closely, small wrinkles are visible 3 4 Slight wrinkles Clear wrinkles Wrinkles in the neck are clearly visible without doubt Wrinkles in the neck are clearly pronounced 2.3 Statistics To be able to determine whether differences in weight loss and quality parameters between pears stored with or without Contronics humidification are statistically reliable has been statistically tested using a Student T-test (p<0.05). 8 Agrotechnology and Food Innovations b.v., part of Wageningen UR
9 3 Results and discussion 3.1 Execution of test The tests were performed in two adjacent pear rooms. Room 116 was equipped with Contronics humidification, room 118 was the control room. Stocking was in week 37. In both rooms, pears of the same origin (10791) formed the bulk, the stacking crates for fluid loss and quality determinations were taken from this origin. Six stacking crates were marked and weighed per room during stocking according to the schedule in Illustration 3. In addition, samples for quality determination at harvesting were taken. Both rooms were opened in February: the control room on February 3, the room with the humidification on February 13. This ten-day difference is in practice quite acceptable. Experience has taught that for a storage duration of 175 days this ten days difference does not have a major impact on measured fluid loss and quality progress. 3.2 Humidification and fluid discharge The humidification installation was activated in the test room upon stocking. During the entire period the installation ran without problems and functioned without malfunctions. During the beginning period an original RH controller was replaced by the type mentioned in the description among other reasons to make logging of data possible. During intermediary measurements an injection of 0.6 liter per hour was determined. During the entire period, the humidifier functioned practically continuously at maximum with an RH of the incoming air at 94 96%, which concurs with incidental measurements in the room RH measurements during the waiting period Through the placement of calibrated RH sensors at the relatively most unfavorable location in the room, an attempt was made to obtain a picture of the effect of the Contronics humidification installation in the waiting period. The test was performed after the pears had already been cooled well for at least a week. In each room, a logger was placed on the lowest but one crate to the left by the door (about 1 meter high), on the pears. At this position, the vapor pressure deficit, the driving force for dehumidification, is usually the highest. Agrotechnology and Food Innovations b.v., part of Wageningen UR 9
10 Effect o R R (%) Contronics control r Illustration 4 RH in the test rooms during the waiting period. RH in the room with the Contronics humidification installation is an average of 95.5% versus 86% in the control room without humidification. As shown in Illustration 4, the RH at this unfavorable position with humidification is significantly higher than without: resp and 86% RH. The temperature at this position at that moment was C. The higher air humidity in the humidified room ensures a lower vapor pressure deficit, and thus less fluid loss. In this case, 0.22 and 0.67 g/m 3 resp., a substantial difference Course of humidification and water discharge during CA conditioning By collecting the melt water from the evaporators and measuring it regularly, the quantity of water that leaves the room this way was recorded for both rooms. The quantity of water actually injected was determined halfway through the test by Contronics to be 0.6 liter per hour. The quantity of fluid is also expressed on the basis of 150 ton pears per room in % of the product weight in the room, see Illustration Agrotechnology and Food Innovations b.v., part of Wageningen UR
11 liter Cumulat water water water Contronics injecti Contronics water - injecti Contronics % 1.0% 0.8% 0.6% 0.4% 0.2% 0.0% % Cumulat water water water Contronics injecti Contronics water - injecti Contronics Illustration 5 The cumulative course of the water discharge through the cooler in the control room and the room with Contronics humidification. Left in liters, right in %. The quantity of injected water and the difference water measurement injection is also shown. The water discharge of the control room is lower than in the room with the humidification, resp and 2.86 liter per ton per month. In the humidified room however, water is brought in by the humidification installation, which almost completely compensates for the fluid loss through the evaporator. Ultimately the net balance in the room with the humidification then comes to liter per ton per month. Given that fluid also leaves the room through control actions, and that the fruit takes up fluid as well, the actual balance will not be negative, otherwise an increasing ice formation would have been visible but the fluid loss through the evaporator does seem to be almost completely compensated by the humidification. In the beginning period (first 3 weeks) there did seem to be a limited improvement present by applying a larger capacity evaporator, but the continuous maximum humidification has in this case therefore led to a very tight result. A larger humidification capacity would be able to work favorably on a further inhibition of the fluid loss particularly in the waiting period Ice formation From the end of October, there was a slight growth of ice crystals under/in front of the inlet nozzle of the humidification in the room with the humidification installation. This was particularly noticeable on a stacking crate that protruded somewhat above the normal stacking height immediately behind the inlet nozzle. During the test, the ice formation remained limited to this position. It concerned a light powdery ice layer and did not create a problem. This could possibly be completely prevented by positioning the inlet nozzle somewhat higher and/or level stacking, so the chance of the saturated air blowing directly against the pears and freezing against them is decreased. However, given experiences with other humidification systems where there was sometimes an issue with serious ice formation over the entire room, this is an exceptionally good result. Agrotechnology and Food Innovations b.v., part of Wageningen UR 11
12 3.3 Weight loss stacking crates during storage Fluid loss is by far the most significant cause of weight loss in pear storage. Below are the results of the weight losses of the individual stacking crates. 2.5% 2.0% 1.5% % 1.0% control Contronics 0.5% 0.0% r l / h g / midd / l control % Contronics 0.34% 0.56% 0.34% 0.88% 1.94% 1.88% in On average, the weight loss was 1.91% in the control room compared to 0.99% in the humidified room; this is a statistically reliable difference. For both rooms, the position of the crates in the room to the left or right did not give a statistically reliable difference. This indicates that the room climate across the width of the room was not interrupted by, for example, unequal functioning evaporators in the rooms. In the humidified room, the position of the stacking crates in the length/height of the room did make a difference: the low crates close to the door (front/low) provided a statistically reliable higher weight loss than those in the middle (middle/middle) or at the rear (rear/high), which remained the same. This distribution concurs with the findings from a previous study into the humidification of pears as part of the Kwalicon project, see Illustration 6. It is obvious that the bulk of the room load profits from the humidification. 12 Agrotechnology and Food Innovations b.v., part of Wageningen UR
13 A B C Illustration 6 Global distribution of a pear room by temperature zones with A as coldest and C as warmest location in the room, this relates to the local fluid loss. In this test, the humidification resulted in a significant limitation of the fluid loss in zone A and B, such that the majority of the room load gained an advantage from this humidification. 3.4 Quality evaluations The quality of the pears was evaluated at the end of the storage period upon room opening and after a display period of 5 days. As a check to see whether the samples were homogenous enough to be able to generate reliable pronouncements, the weight of the flesh of individual fruits was determined for the various samples. This appeared to be 288 g with a standard deviation of 54 g. The differences between the treated samples and the control were statistically not significant. For the remaining quality parameters, within the rooms there did not appear to be a statistically reliable difference between the samples to the left or right from the room, so that the results of these have always been displayed as an average. Agrotechnology and Food Innovations b.v., part of Wageningen UR 13
14 3.4.1 Hardness Hard Conference ( control Contronics control / idd / midd / l / h g idd e / midd e / l a Contronics The firmness after storage is on average 5.9 (control) and 6.2 kg/cm 2 (Contronics). This difference is still correctly statistically significant. After display, the pears are significantly soft but the difference has become relatively greater, and clearly statistically reliable. It concerns a relatively small difference in hardness, which is not found in many other experiments with humidification. Given the limited character of this experiment it goes too far to place an emphasis on this effect. 14 Agrotechnology and Food Innovations b.v., part of Wageningen UR
15 3.4.2 Base color Base color Conference at stocking and after storage with and without humidification Color (1 = Green. 5 = Yellow) control Contronics Rear / high Middle / middle Front / low Rear / high Middle / middle Front / low At room opening After display control Contronics The base color was excellent at room opening and still very acceptable after display. The differences found were not statistically different Weakness score 18 C - 75% R control Contronics At room opening After display control Contronics Agrotechnology and Food Innovations b.v., part of Wageningen UR 15
16 The weakness score is a practical indication for weak necks. A lot with a weakness score greater than about 1 is considered in the trade as being of lower quality. Here also, the weakness score is determined after display to obtain an impression of the behavior later in the chain. The weakness score after storage is an average 0.56 (Control) and 0.30 (Contronics). After display, these values are respectively 2.85 and 1.26 and all these differences are statistically reliable. The humidification has therefore provided a positive effect immediately at room opening that also continues to work during the display phase. The expectation is that in terms of fluid loss this effect can be commercially greater for lower quality pears or in case of longer storage duration Sugar content The sugar content at storage was an average 13.6 Brix. After storage this was an average 14.9 Brix, the increase can be explained by starch conversion after the harvest. There were no statistically relevant differences found between the humidified/control, the positions in the room and the moment of the evaluation. This was also not expected External and internal abnormalities The sample pears were of excellent quality, there were no abnormalities encountered. 16 Agrotechnology and Food Innovations b.v., part of Wageningen UR
17 4 Conclusions 1. In this test in test rooms of unpackaged Conference pears, the Contronics humidification installation functioned technically excellently during the stocking and storage period: a. No significant malfunctions b. No interruption of the conditioning in regard to the control room c. No problems with ice formation d. Excellent compensation of the water discharge through the evaporator 2. Humidification provided a significant reliable reduction of the weight loss of the bulk of the stacking crates in the room compared to the control room (average respectively 1.0 and 1.9 %.) The effect locally under the evaporator however was limited, but this only concerned a small part of the room load. 3. Humidification resulted in a significant reliable reduction of the degree of "weak necks in the pears, even in the most unfavorable position under the evaporator. This effect was more noticeable after 5 days of display at 18 C. 4. The quality of the pears used in this test was excellent. The firmness was statistically reliably higher (0.2 kg/cm 2 ) in the humidified room. This last effect had not been this clearly observed previously in other humidification/packaging tests, so not too much significance should be attached to this slight difference. Base color and sugar content were not measurably influenced. 5. The fact that the unit functioned well technically together with a clearly measurable quality advantage, indicates that humidification using this Contronics humidification is a practical tool to utilize in the storage of unpackaged pears. Agrotechnology and Food Innovations b.v., part of Wageningen UR 17
18 5 Points to note and recommendations To limit the fluid loss of Conference during storage even further, increasing the capacity of the ultrasonic unit can be considered. This would be of interest especially during the stocking period. With the humidification installation utilized, the upper limit (overdosing, increasing ice formation) was not (quite) reached, so that control actions were not needed. However when increasing the capacity of the ultrasonic unit this will begin to play a role. The RHs measured currently in the module (94-96%) are a useful target if overdosing leads to undesirable ice formation. Achieving a better effect at the "worst location" in the room is also attainable by a further RH increase. Linking (registration of) the humidification system with the CA/temperature control/adjustment system can increase the appeal of using the system. It is important to pay sufficient attention to the leak-tightness of the humidification module. 18 Agrotechnology and Food Innovations b.v., part of Wageningen UR
19 Acknowledgements Practical tests such as performed here are only possible with the cooperation of the room manager. Therefore the cold-storage manager at Fruitmasters Veiling B.V., Mr. Harry Beelen, must be thanked for his active thinking and cooperation during the test. Agrotechnology and Food Innovations b.v., part of Wageningen UR 19
THE HUMIDITY/MOISTURE HANDBOOK
THE HUMIDITY/MOISTURE HANDBOOK Table of Contents Introduction... 3 Relative Humidity... 3 Partial Pressure... 4 Saturation Pressure (Ps)... 5 Other Absolute Moisture Scales... 8 % Moisture by Volume (%M
Summary of Recent International Transportation Trials
Summary of Recent International Transportation Trials 1. Introduction Conditions of international transport, if poorly controlled, can lead to substantial deterioration in the quality and safety of food
Chapter 19 Purging Air from Piping and Vessels in Hydrocarbon Service
BP Lower 48 Onshore Operations Safety Manual Page 4.19 1 Chapter 19 Purging Air from Piping and Vessels in Hydrocarbon Service I. General Requirements A. After motor vehicle accidents and underground excavation
International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS
International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES
Help. Help Software Tutorial. Building a load sizing project with an ME Series Humidifier
Help Help Software Tutorial Building a load sizing project with an ME Series Humidifier 502-B 18 Aug 2015 Help Tutorials provide step-by-step examples of complete load sizing projects and browser projects
Climate chamber with illumination
KBWF series (E5.2) Climate chambers with illumination Climate chamber with illumination The BINDER climate chamber with illumination of the KBW series achieves homogeneous light distribution with its natural
Total Heat Versus Sensible Heat Evaporator Selection Methods & Application
Total Heat Versus Sensible Heat Evaporator Selection Methods & Application Scope The purpose of this paper is to provide specifying engineers, purchasers and users of evaporators in industrial refrigeration
Online Infrared Flue Gas Analyzer Gasboard 3000
Online Infrared Flue Gas Analyzer Gasboard 3000 O 2 CO CO2 SO 2 NO NO x Use of measurement methods Proprietary Infrared NDIR Detectors - Micro-flow in ppm range: CO, NO, SO2, CO2 - Dual beam in % volume
Basic Hydraulics and Pneumatics
Basic Hydraulics and Pneumatics Module 1: Introduction to Pneumatics PREPARED BY IAT Curriculum Unit March 2011 Institute of Applied Technology, 2011 ATM 1122 Basic Hydraulics and Pneumatics Module 1:
PERMEABILITY TEST. To determine the coefficient of permeability of a soil using constant head method.
PERMEABILITY TEST A. CONSTANT HEAD OBJECTIVE To determine the coefficient of permeability of a soil using constant head method. need and Scope The knowledge of this property is much useful in solving problems
How do I measure the amount of water vapor in the air?
How do I measure the amount of water vapor in the air? Materials 2 Centigrade Thermometers Gauze Fan Rubber Band Tape Overview Water vapor is a very important gas in the atmosphere and can influence many
APC APPLICATION NOTE #92
#92 Best Practices for Designing Data Centers with the InfraStruXure InRow RC By John Niemann Abstract The InfraStruXure InRow RC is designed to provide cooling at the row and rack level of a data center
HVAC: Cool Thermal Storage
HVAC: Cool Thermal Storage Thermal storage systems offer building owners the potential for substantial operating cost savings by using offpeak electricity to produce chilled water or ice for use in cooling
TheFinancialEdge. Configuration Guide for General Ledger
TheFinancialEdge Configuration Guide for General Ledger 071012 2012 Blackbaud, Inc. This publication, or any part thereof, may not be reproduced or transmitted in any form or by any means, electronic,
PROCEDURE FOR FRESH APPLE AND PEAR EXPORTS FROM SOUTH AFRICA TO MEXICO. Responsibility: Service Manager: Special Shipments Name: Initial:
Page 1 of 10 Rev: 0 1. Reference 1.1 This procedure refers to the cold treatment of fruit flies and Eastern fruit moth in apples and pears, as prescribed by the Secretariat of Agriculture, Cattle and Rural
Density and Refractometry
Density and Refractometry BRIX - Sugar Determination By Density and Refractometry Introduction There are a lot of different sugars, e.g. sucrose, malt sugar, glucose, HFCS. Strictly speaking of Brix,only
Heating oven with mechanical convection
FD series 53 Drying ovens / Heating ovens Heating oven with mechanical convection A BINDER FD series heating oven is always used when fast drying and sterilization is required. Thanks to its fully homogeneous
High Capacity Hot Air Dryer
High Capacity Hot Air Dryer MADE IN AUSTRIA autumn 2015 www.zimmer-austria.com page 1 Hot air dryer type: Compact HC The modular construction of the high efficiency and powerful hot air nozzle dryer is
TECHNICAL SPECIFICATION. StirLIN-1 Economy Liquid Nitrogen System
TECHNICAL SPECIFICATION StirLIN-1 Economy Liquid Nitrogen System Reference 80 8120_01 Issue Date August 1, 2015 1. INTRODUCTION Since more than sixty years Stirling Cryogenics has designed and manufactured
USER INSTRUCTIONS FOR 10 LITRE PORTABLE DEHUMIDIFIER MODEL NO. DHMD102
USER INSTRUCTIONS FOR 10 LITRE PORTABLE DEHUMIDIFIER MODEL NO. DHMD102 THANK YOU FOR CHOOSING YOUR NEW DEHUMIDIFIER. BEFORE USING THE UNIT READ THESE INSTRUCTIONS FULLY AND RETAIN THEM FOR FUTURE REFERENCE
Marine after-treatment from STT Emtec AB
Marine after-treatment from STT Emtec AB For Your Vessel and the Environment SCR Technology How it works The selective catalytic reduction of nitrous oxides (NOx) by nitrogen compounds such as urea solutions
US Environmental Protection Agency Office of Pesticide Programs
US Environmental Protection Agency Office of Pesticide Programs Office of Pesticide Programs Microbiology Laboratory Environmental Science Center, Ft. Meade, MD Standard Operating Procedure for Monitoring
Energy Efficient Operations and Maintenance Strategies for Boilers
Energy Efficient Operations and Maintenance Strategies for Boilers Large, complex and widely used, industrial boilers are major consumers of fuel. Proper operations and maintenance (O&M) procedures must
Principles of Rice Drying How does rice dry?
Principles of Rice Drying James F. Thompson June 30, 1998 How does rice dry? Rice gains or loses moisture based on its moisture and the humidity of the air around it. If the humidity is low, high moisture
Technical Specifications for West Campus Data Center HVAC System
Technical Specifications for West Campus Data Center HVAC System I. Mechanical Systems Requirements A. HVAC Primary Data Centers, Automation HVAC is to be provided on a 24 hours per day, 365 days per year
Engineering Recommendation on: Accumulators Revised 6-17-99 Issued January 10, 1979 Page 1 of 7
Issued January 10, 1979 Page 1 of 7 Accumulators have long been recognized by the industry as an effective means of maintaining good system balance by storing excess refrigerant as the condenser or evaporator
Marine after-treatment from STT Emtec AB
Marine after-treatment from STT Emtec AB For Your Vessel and the Environment Recommended by Volvo Penta 16 15 5 6 10 8 13 2 14 12 3 4 7 9 11 1 1. SCR Catalyst 2. Injection nozzle 3. Mixer unit 4. Diagnostic
2A.1 Features of Chiller Control Components... 104. 2A.3 Chilled-Water Supply Temperature Control... 107. 2A.4 Cooling-Water Supply Control...
Appendix 2A: Chiller Control Principles... 104 2A.1 Features of Chiller Control Components... 104 2A.2 Start-up and Shutdown... 105 2A.2.1 Start-up...105 2A.2.2 Shutdown...106 2A.3 Chilled-Water Supply
A/C refrigerant system, overview
Page 1 of 19 87-18 A/C refrigerant system, overview A/C refrigerant system, identification Typical A/C refrigerant system with expansion valve and receiver drier 1 - Evaporator 2 - Expansion valve 3 -
Instruction Manual HI 96800 Refractometer for Refractive Index and Brix Measurements
Instruction Manual HI 96800 Refractometer for Refractive Index and Brix Measurements www.hannainst.com 1 Dear Customer, Thank you for choosing a Hanna Instruments product. Please read this instruction
Infrastructure & Cities Sector
Technical Article Infrastructure & Cities Sector Building Technologies Division Zug (Switzerland), October 18, 2011 Saving Energy in a Data Center A Leap of Faith? New guidelines from ASHRAE (American
Pneumatic control loops save water and energy with fixed-bed filters
Pneumatic control loops save water and energy with fixed-bed filters Dr. Wolfgang Rieger, Festo AG & Co. KG, 73734 Esslingen Published in Industrial Valves 2010/2011 Vulkan-Verlag GmbH, Essen/Germany Contact:
Design of Cold Storage Structure For Thousand Tonne Potatoes
International Journal of Agriculture and Food Science Technology. ISSN 2249-3050 Volume 5, Number 3 (2014), pp. 171-178 Research India Publications http://www.ripublication.com Design of Cold Storage Structure
Read Naturally, Inc. Version: 05 February 2016. Saint Paul, Minnesota
USER GUIDE Version: 05 February 2016 Read Naturally, Inc. Saint Paul, Minnesota Phone: 800.788.4085/651.452.4085 Website: www.readnaturally.com Email: [email protected] Copyright 2011 2016 Read Naturally,
Siebel Professional Services Automation Guide
Siebel Professional Services Automation Guide Version 7.7 November 2004 Siebel Systems, Inc., 2207 Bridgepointe Parkway, San Mateo, CA 94404 Copyright 2004 Siebel Systems, Inc. All rights reserved. Printed
Minnesota Comprehensive Assessments-Series III
Not for student use. Minnesota Comprehensive Assessments-Series III Science Item Sampler Script Grade 8 S ARE NOT SECURE TEST MATERIALS. THIS ITEM SAMPLER SCRIPT MAY BE COPIED OR DUPLICATED. MINNESOTA
HVAC air curtains. Type InduAir
Air Conditioning Cooling Heating Ventilation HVAC air curtains Type InduAir The Energy Saving air curtain for Industrial Applications InduAir The solid, self-supporting housing of the energy saving air
Material test chamber with mechanical convection
FP series 400 Material test chambers Material test chamber with mechanical convection A BINDER material test chamber with mechanical convection of the FP series provides reliably short drying times and
QFP910. Water detector. Building Technologies. CE1N2732en 2016-03-01. Synco living
2 732 Synco living Water detector QFP910 Wireless radio sensor to record water puddles RF communication based on KNX standard (868 MHz unidirectional) Battery operation with standard 1.5 V batteries Use
EXPLANATION OF WEATHER ELEMENTS AND VARIABLES FOR THE DAVIS VANTAGE PRO 2 MIDSTREAM WEATHER STATION
EXPLANATION OF WEATHER ELEMENTS AND VARIABLES FOR THE DAVIS VANTAGE PRO 2 MIDSTREAM WEATHER STATION The Weather Envoy consists of two parts: the Davis Vantage Pro 2 Integrated Sensor Suite (ISS) and the
[4] SA1.2 The student demonstrates an understanding of the processes of science by observing,
Frost Depth Levels Overview: In this lesson, students explore the active layer above permafrost and begin a long-term investigation of frost depth. (NOTE: This lesson requires a frost tube in your community.
THE USE OF A CORIOLIS FLOW METER FOR MEASURING MOLASSES PRODUCTION IN A SUGAR MILL. ABSTRACT
THE USE OF A CORIOLIS FLOW METER FOR MEASURING MOLASSES PRODUCTION IN A SUGAR MILL. P. W. Rein 1, D. J. Muzzell 2, and N. Dolan 2 1 Audubon Sugar Institute, LSU AgCenter, St. Gabriel, LA, 2 Raceland Raw
Temperature Rise Calculation Software Tutorial. In Accordance with the Calculation Method to IEC 60890
Temperature Rise Calculation Software Tutorial In Accordance with the Calculation Method to IEC 60890 Temperature Rise Calculation Software (TRCS) Rockwell Automation All rights reserved. No parts of this
THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS.
THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS. NOT ALL CODES ARE POSSIBLE ON ANY INDIVIDUAL UNIT. IF THE ALARM APPLIES
Absolute and relative humidity Precise and comfort air-conditioning
Absolute and relative humidity Precise and comfort air-conditioning Trends and best practices in data centers Compiled by: CONTEG Date: 30. 3. 2010 Version: 1.11 EN 2013 CONTEG. All rights reserved. No
INJECTION MOLDING PROCESSING GUIDE Polymer
FOAMAZOL Chemical Foaming Agents INJECTION MOLDING PROCESSING GUIDE Polymer Foaming Agent INJECTION MOLDING WITH CHEMICAL FOAMING AGENTS Introduction The injection molding of structural foam molded parts
Technical Manual. FAN COIL CONTROLLER COOLING or HEATING ANALOG or PWM Art. 119914 631001A
COOLING or HEATING ANALOG or PWM Art. 119914 631001A TOTAL AUTOMATION GENERAL TRADING CO. LLC SUITE NO.506, LE SOLARIUM OFFICE TOWER, SILICON OASIS, DUBAI. UAE. Tel. +971 4 392 6860, Fax. +971 4 392 6850
Effects of Cage Stocking Density on Feeding Behaviors of Group-Housed Laying Hens
Animal Industry Report AS 651 ASL R2018 2005 Effects of Cage Stocking Density on Feeding Behaviors of Group-Housed Laying Hens R. N. Cook Iowa State University Hongwei Xin Iowa State University, [email protected]
Walnut Drying Design and Operation. Selecting Dryer Type. Tray Drying Before 1920. Don Osias Jim Thompson
Walnut Drying Design and Operation Don Osias Jim Thompson Selecting Dryer Type Tray Drying Before 1920 1 Stack Dryer Energy efficient High capital cost Pothole For small lots High labor cost Hopper-bottom
AN INDUSTRIAL APPLICATION OF THE SMED METHODOLOGY AND OTHER LEAN PRODUCTION TOOLS
Integrity, Reliability and Failure of Mechanical Systems Paper Ref: 3927 AN INDUSTRIAL APPLICATION OF THE SMED METHODOLOGY AND OTHER LEAN PRODUCTION TOOLS Eric Costa 1(*), Rui Sousa 1, Sara Bragança 1,
floater imports DF169 ECO AIR COOLER EVAPORATIVE AIR COOLER WITH IONIZER USER S MANUAL
floater imports DF169 ECO AIR COOLER EVAPORATIVE AIR COOLER WITH IONIZER USER S MANUAL WHAT IS AN ECO AIR COOLER? The ECO AIR COOLER uses evaporative cooling to provide an airflow that is cooler than the
1 Introduction The Scientific Method (1 of 20) 1 Introduction Observations and Measurements Qualitative, Quantitative, Inferences (2 of 20)
The Scientific Method (1 of 20) This is an attempt to state how scientists do science. It is necessarily artificial. Here are MY five steps: Make observations the leaves on my plant are turning yellow
VTS³ and VCS³ Stress Screening Systems. More Power for Maximum Quality Assurance
VTS³ and VCS³ Stress Screening Systems More Power for Maximum Quality Assurance Tailor-made for your product: Our proven testing methods Thermal and climatic conditions can affect the production, storage
EVALUATION OF GEOTHERMAL ENERGY AS HEAT SOURCE OF DISTRICT HEATING SYSTEMS IN TIANJIN, CHINA
EVALUATION OF GEOTHERMAL ENERGY AS HEAT SOURCE OF DISTRICT HEATING SYSTEMS IN TIANJIN, CHINA Jingyu Zhang, Xiaoti Jiang, Jun Zhou, and Jiangxiong Song Tianjin University, North China Municipal Engineering
Chapter 12 - Liquids and Solids
Chapter 12 - Liquids and Solids 12-1 Liquids I. Properties of Liquids and the Kinetic Molecular Theory A. Fluids 1. Substances that can flow and therefore take the shape of their container B. Relative
Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MN12CES / MN10CESWW
Portable Air Conditioner OWNER S MANUAL Read these instructions before use 8 Model: MN12CES / MN10CESWW Voltage rating: 120V~60Hz Power rating : 1100W (MN12CES) Power rating : 900W (MN10CESWW) Customer
BD150 INDUSTRIAL DEHUMIDIFIER USER MANUAL
BD150 INDUSTRIAL DEHUMIDIFIER USER MANUAL Drawing : - TPC337 Issue : - 2 Date : - 24/01/12 UNPACKING Thank you for deciding to purchase an EIPL Industrial dehumidifier. Like the many tens of thousands
The Basic Principles of Sieve Analysis
The Basic Principles of Sieve Analysis Introduction Many natural and manufactured materials occur in a disperse form, which means that they consist of differently shaped and sized particles. The particle
Operating Instructions & Maintenance Guidelines for Precision Vaporizers
Operating Instructions & Maintenance Guidelines for Precision Vaporizers This page intentionally blank. Examination and Preparation for Use We want you to be completely satisfied with your vaporizer. Please
Environmental Data Center Management and Monitoring
2013 Raritan Inc. Table of Contents Introduction Page 3 Sensor Design Considerations Page 3 Temperature and Humidity Sensors Page 4 Airflow Sensor Page 6 Differential Air Pressure Sensor Page 6 Water Sensor
Make Your Own SNOWBREEZE AC For Rs.1500 ($30) Can be converted into an energy saving and humidified room heater in winter
Make Your Own SNOWBREEZE AC For Rs.1500 ($30) Can be converted into an energy saving and humidified room heater in winter You can now assemble Snowbreeze, a mild air conditioner in your house with materials
Best Practices for Wire-free Environmental Monitoring in the Data Center
White Paper 11800 Ridge Parkway Broomfiled, CO 80021 1-800-638-2638 http://www.42u.com [email protected] Best Practices for Wire-free Environmental Monitoring in the Data Center Introduction Monitoring for
Gravimetric determination of pipette errors
Gravimetric determination of pipette errors In chemical measurements (for instance in titrimetric analysis) it is very important to precisely measure amount of liquid, the measurement is performed with
Implementing Oracle Time Management (US) Release 11.i (A77087-01)
Implementing Oracle Time Management (US) Release 11.i (A77087-01) Implementing Oracle Time Management, Release 11.i (A77087-01) Copyright Oracle Corporation 1999 Primary Author: Joycelyn Smith. Contributing
Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MM14CCS. Voltage rating: 115V~60Hz Power rating : 1400W
Portable Air Conditioner OWNER S MANUAL Read these instructions before use Model: MM14CCS Customer Support : 1-800-474-2147 Voltage rating: 115V~60Hz Power rating : 1400W For product inquiries or support
FAQs. Conserve package. Gateway... 2 Range Extender... 3 Smart Plug... 3 Thermostat... 4 Website... 7 App and Mobile Devices... 7
FAQs Conserve package Gateway... 2 Range Extender... 3 Smart Plug... 3 Thermostat... 4 Website... 7 App and Mobile Devices... 7 FAQs Gateway Can I have someone install my system for me? If you are concerned
Mold Alert... Operation Manual P0270
Mold Alert... Operation Manual P0270 introduction Congratulations on your purchase of the P0270 Mold Alert! Mold is as old as the Earth and it s everywhere. Under the right set of conditions, it can actually
Marine after-treatment from STT Emtec AB
Marine after-treatment from STT Emtec AB For Your Vessel and the Environment 6 7 8 1 11 1 10 9 1. Pick up. Flow direction valve. Filters. Cooler. Condensate trap 6. Flow meter 7. EGR-valve 8. Secondary
Three-years operation experience of a ground source heat pump system in Northern Greece
Energy and Buildings 39 (2007) 328 334 www.elsevier.com/locate/enbuild Three-years operation experience of a ground source heat pump system in Northern Greece A. Michopoulos, D. Bozis, P. Kikidis, K. Papakostas,
Head Loss in Pipe Flow ME 123: Mechanical Engineering Laboratory II: Fluids
Head Loss in Pipe Flow ME 123: Mechanical Engineering Laboratory II: Fluids Dr. J. M. Meyers Dr. D. G. Fletcher Dr. Y. Dubief 1. Introduction Last lab you investigated flow loss in a pipe due to the roughness
Instruction Manual. T3111 T3111L T3111P T3111Ex
www.cometsystem.cz Instruction Manual T3111 T3111L T3111P T3111Ex Programmable transmitter of temperature, relative humidity and other calculated humidity values with external probe and 4-20 ma outputs
Seeing by Degrees: Programming Visualization From Sensor Networks
Seeing by Degrees: Programming Visualization From Sensor Networks Da-Wei Huang Michael Bobker Daniel Harris Engineer, Building Manager, Building Director of Control Control Technology Strategy Development
Redefining Spray Technology
Redefining Spray Technology Macrospray Single-Point Nozzles Macrospray Spider Nozzles Macrospray nozzle technology Improved performance, lower cost Macrospray nozzle technology from Parker Hannifin s Gas
User Guide. Temperature and Humidity Datalogger. Model 42280
User Guide Temperature and Humidity Datalogger Model 42280 Introduction Congratulations on your purchase of the Extech 42280 Thermometer and Relative Humidity Datalogger. The 42280 is a wall-mount, tripod
Commercial refrigeration has been in the environmental. Refrigerant. as a. Basics Considerations PART 1:
PART 1: CO 2 Commercial refrigeration has been in the environmental spotlight for more than a decade, especially as leakage studies have revealed the true effects of hydrofluorocarbon (HFC) emissions.
Petrel TIPS&TRICKS from SCM
Petrel TIPS&TRICKS from SCM Knowledge Worth Sharing Histograms and SGS Modeling Histograms are used daily for interpretation, quality control, and modeling in Petrel. This TIPS&TRICKS document briefly
DEF Q&A. A. SCR is a technology that uses a urea based diesel exhaust fluid (DEF) and a
Selective Catalytic Reduction (SCR) Q. What is Selective Catalytic Reduction (SCR)? A. SCR is a technology that uses a urea based diesel exhaust fluid (DEF) and a catalytic converter to significantly reduce
Power consumption (kw)
OS Series Series description LIT OS systems are applied to wastewater disinfection. The models of this series were developed on base of high-efficiency low-pressure amalgam lamps and have all components
NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES
NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES 8.1 INTRODUCTION Testing, adjusting, and balancing of HVAC systems can best be accomplished by following a series of systematic procedures. The NEBB TAB
Portable Evaporative Air Cooler. OWNER S MANUAL Read and save these instructions before use. Model: CL30XC
Portable Evaporative Air Cooler OWNER S MANUAL Read and save these instructions before use Model: CL30XC Power rating: 250 Watts Voltage rating: 230 Volt, 50Hz Made in P.R.C. QUICK START GUIDE Fill with
USER MANUAL HRV CONSTRUCTO 2.0ES* HRV CONSTRUCTO 1.5ES* * THESE PRODUCTS EARNED THE ENERGY STAR BY MEETING STRICT ENERGY EFFICIENCY
USER MANUAL RESIDENTIAL USE ONLY VB0175 HRV CONSTRUCTO 2.0ES* HRV CONSTRUCTO 1.5ES* * THESE PRODUCTS EARNED THE ENERGY STAR BY MEETING STRICT ENERGY EFFICIENCY GUIDELINES SET BY NATURAL RESOURCES CANADA
Please read this owner s Manual carefully before operating the unit. - Cooling - Heating - Dehumidifying - Fan
Please read this owner s Manual carefully before operating the unit. - Cooling - Heating - Dehumidifying - Fan TABLE OF CONTENTS INTRODUCTION 2 IMPORTANT SAFEGUARDS...2 PACKAGE CONTAINS..2 NAMES OF PARTS.3
NITROUS TRANSFER PUMP INSTRUCTIONS
NITROUS TRANSFER PUMP INSTRUCTIONS SAFETY TIPS Never directly inhale nitrous oxide. When inhaled in large quantities, nitrous oxide can cause respiratory ailments or in extreme cases, death by suffocation.
Why and How we Use Capacity Control
Why and How we Use Capacity Control On refrigeration and air conditioning applications where the load may vary over a wide range, due to lighting, occupancy, product loading, ambient weather variations,
Safe Dry Goods Storage
FOOD PROTECTION CONNECTION 1 HOUR SAN Safe Dry Goods Storage by Melissa Vaccaro, MS, CHO Not too long ago a consumer brought an open pouch of hot chocolate into our office for testing. She claimed there
UTZ Certified Certification Protocol
Version 3.0 (previous version 2.0 February 2010) Copies of this document are available for free in electronic format on the UTZ Certified Training Center website: http://www.utzcertified-trainingcenter.com
Signature and ISX CM870 Fuel System
Signature and ISX CM870 Fuel System Cummins Ontario Training Center HPI-TP Fuel System Heavy Duty High Pressure Injection - Time Pressure Fuel System The fuel system developed for the Signature and ISX
Systems Thinking and Modeling Climate Change Amy Pallant, Hee-Sun Lee, and Sarah Pryputniewicz
Systems Thinking and Modeling Climate Change Amy Pallant, Hee-Sun Lee, and Sarah Pryputniewicz You know the effects of the proverbial butterfly flapping its wings. But what about an automobile driver?
50AI01oe 02/15. Labko GRP cesspools. Instructions for installation, operation and maintenance
02/15 Labko GRP cesspools Instructions for installation, operation and maintenance Reliable solutions Wastewater treatment systems Contents 1 LABKO CESSPOOLS... 3 1.1 GENERAL... 3 1.2 IMPORTANT TO KNOW
Stack Sampling Stack sampling or source sampling
Stack Monitoring Stack Sampling Stack sampling or source sampling may be defined as a method of collecting representative samples of pollutant laden air/gases at the place of origin of pollutants to determine
Warehouse Management MICROSOFT BUSINESS SOLUTIONS AXAPTA
Warehouse Management MICROSOFT BUSINESS SOLUTIONS AXAPTA Microsoft Business Solutions Axapta Warehouse gives you the flexibility and control you need to optimise your entire warehouse management cycle
Overview. Introduction Cooling Tower Basics Principles of Operation Types of Cooling Towers Common Applications Design Considerations
Stephen Lowe ASHRAE Hampton Roads Chapter Past President AECOM Design Mechanical Engineering Discipline Manager, Virginia Beach Division Professional Engineer Commonwealth of Virginia, NCEES BSME University
CoolTeg Plus Chilled Water (CW) version: AC-TCW
version: 12-04-2013 CONTEG DATASHEET TARGETED COOLING CoolTeg Plus Chilled Water (CW) version: AC-TCW CONTEG, spol. s r.o. Czech Republic Headquarters: Na Vítězné pláni 1719/4 140 00 Prague 4 Tel.: +420
39HQ Airovision Air Handling Units
39HQ Airovision Air Handling Units Mounting instructions CONTENTS 1 - TRANSPORT AND LIFTING INSTRUCTIONS... 3 1.1 - General... 3 1.2 - Transport and storage... 3 1.3 - Roof edge protection during transport
The new Audi TT Coupé. Life Cycle Assessment
The new Audi TT Coupé Life Cycle Assessment Content Foreword Life cycle assessment what s involved Life cycle assessment the boundaries Life cycle assessment the effect categories Lightweight construction
Benefits of Cold Aisle Containment During Cooling Failure
Benefits of Cold Aisle Containment During Cooling Failure Introduction Data centers are mission-critical facilities that require constant operation because they are at the core of the customer-business