Prefabricated Power and Cooling Modules for Data Centers
|
|
|
- Estella Evans
- 9 years ago
- Views:
Transcription
1 Prefabricated Power and Cooling Modules for Data Centers White Paper 163 Revision 2 by Dennis Bouley and Wendy Torell Executive summary Standardized, pre-assembled and integrated data center facility power and cooling modules are at least 60% faster to deploy, and provide a first cost savings of 13% or more compared to traditional data center power and cooling infrastructure. Facility modules, also referred to in the data center industry as containerized power and cooling plants, allow data center designers to shift their thinking from a customized construction mentality to a standardized site integration mentality. This white paper compares the cost of both scenarios, presents the advantages and disadvantages of each, and identifies which environments can best leverage the facility module approach. by Schneider Electric White Papers are now part of the Schneider Electric white paper library produced by Schneider Electric s Data Center Science Center [email protected]
2 Introduction When data center stakeholders are faced with the challenge of deploying new data center power and cooling infrastructure (i.e., chillers, pumps, CRACS, CRAHS, UPS, PDUs, switchgear, transformers etc.), is it better for them to convert an existing room within the building (if this is at all an option) or to construct an extension to house additional power and cooling equipment? Or is it more cost effective and technically feasible to source the power and cooling from a series of prefabricated facility modules? Prefabricated facility modules are pre-engineered, pre-assembled / integrated, and pre-tested data center physical infrastructure systems (i.e., power and cooling) that are delivered as standardized plug-in modules to a data center site. This contrasts with the traditional approach of provisioning physical infrastructure for a data center with unique one-time engineering, and all assembly, installation, and integration occurring at the construction site. The benefits of prefabricated facility modules include cost savings, time savings, simplified planning, improved reliability, improved agility, higher efficiency, and a higher level of vendor accountability. Deployment of prefabricated facility modules results in a savings of 60% in deployment speed and 13% or more in first cost when compared to a traditional build out of the same infrastructure (see Figures 1 and 6). Cost savings are even more dramatic (30% or more) when the traditional data center is overbuilt in capacity and provisioned upfront with typical power and cooling systems and controls. Traditional 12.2 m by 2.4 m (40 ft by 8 ft) ISO shipping containers are the most recognizable form of facility module. However, prefabricated facility modules can also be built on a skid or delivered as multiple form factor modular buildings. For this reason, this paper will use the term prefabricated facility modules and not containers when describing the various modular solutions. This paper provides data center professionals with the information needed to justify a business case for data center facility power and cooling modules. Upfront cost of standardized vs. customized Prefabricated facility modules are faster and less costly to deploy than a same physical infrastructure traditional approach for a number of reasons. Figure 1 compares the first cost of these two approaches using identical design and deploy framework or apples to apples. Cooling: $1.75/watt Power: $1.90/watt First cost savings First cost savings: 13% Cooling: $2.00/watt Power: $2.20/watt Figure 1 First cost differences between the traditional and the prefabricated facility module approach Design / Installation Hardware / Software Installation Design Hardware / Software Prefabricated facility modules Traditional facility Schneider Electric Data Center Science Center Rev 2 2
3 Definition of Traditional In this paper, the traditional approach has the same physical infrastructure components and sizing as in the power and cooling facility modules. The key difference is that the traditional approach is built out in a building (sometimes called stick built ). This involves custom engineering and significant onsite work compared to standardized preengineered modules. The costs used in this analysis represent street prices and come from actual projects from design / build firms and component manufacturers, as well as industry averages and rules of thumb. The analysis is based on the following assumptions: 500 kw power and cooling capacity Packaged chiller with economizer mode St. Louis, MO, USA costs of labor with suburban office park site conditions No core & shell cost savings included No white space infrastructure included (air distribution, power distribution units, racks) Identical physical infrastructure for both the facility module and traditional approaches in order to ensure fair comparison of material costs Facility power and cooling modules offer substantial savings (a difference of $3.65 vs. $4.20/watt first cost) because they offer a standardized means for building and installing the data center physical infrastructure. The standardization of components enables dramatic economies of scale in the production, delivery, and installation of data center power and cooling capacity. The traditional approach, on the other hand, is highly customized with the majority of the work being performed on site. Disparate components from multiple vendors are custom engineered into one unique facility. As can be seen in Figure 1, although the materials or system cost is higher for the prefabricated facility modules, the net savings in first cost is 13% because of the significant savings in design and installation costs, The following sections provide a description of each category in Figure 1 to illustrate why prefabricated facility modules are less costly. Hardware / software costs The "hardware / software cost includes the mechanical and electrical room physical infrastructure hardware (switchgear, UPS, panel boards, heat exchanger, air-cooled chiller, pumps, filters, lighting, security and fire suppression) as well as the, management and controls system). These system costs are about 40% higher for prefabricated facility modules, because of the cost of the additional materials (such as the container shell) and the cost of pre-assembling / integrating the hardware, software, and controls together. Design costs The prefabricated facility modules are designed in a research and development area, are tested, and then released to manufacturing. Once in manufacturing, the design is stamped out and shipped to the end user. In the traditional approach, multiple parties play a role in developing the design. Numerous meetings are held as electrical contractors, mechanical contractors, designers, end users, facilities departments, IT departments, and executives are all involved. Design points are argued back and forth, politics plays a significant role, and decisions often have to be made serially. Design costs include two types of costs: equipment selection & layout, and site plan design/engineering. In the case of prefabricated facility modules, the equipment selection and layout is already done in the factory (rolled into system cost), and site plan design/engineering is reduced by over 80% compared to the traditional build because site layout and planning becomes much simpler and will generally involve 4 trades structural engineer, civil engineer, electrical engineer, and an architectural review, In traditional data center builds, site plan design/engineering can be 5% of the total project expense. Schneider Electric Data Center Science Center Rev 2 3
4 Installation costs Installation costs include all work performed in the field to assemble, integrate, and commission the system for operation. Specifically, this includes: Systems project management The cost to oversee the project is significantly less for a modular facility (approximately 60%) based on the decreased complexity of the project and having a single vendor for the entire physical infrastructure to manage. Site prep and site project management This expense includes steps like digging trenches for pipes and electrical conduits, grading and laying concrete pads, and other general site expenses. This type of work must happen regardless of the approach taken, and therefore the cost is approximately the same. Power & cooling system installation Hardware installation includes the expense of unpackaging components, taking inventory, laying out and assembling components, making inter-connections between components and starting the system up. For modular facilities, many of these tasks are eliminated (work consists only of placing the modules on cement slabs, wiring the modules up to existing building switchboards, plumbing for the cooling, and starting up the systems), resulting in installation cost savings of more than 50%. In addition, since field work is more costly and time consuming than comparable work in the factory, prefabricated facility modules offer substantial savings. For example, a worker on the assembly line in the factory who installs a pre-engineered standard set of electrical wire in a module costs less than the combination of an electrical engineer and electrician in the field who are tasked with building a one off electrical design for that particular project. Another related expense savings (not factored into the analysis of Figure 1) is associated with the shipping. It is significantly less expensive to ship a pre-assembled module compared to shipping the individual parts and pieces of a traditional field-assembled system. Simpler, consolidated shipping also results in less shipping damage, which can be an added expense and an unwelcome time delay. Management / controls installation and programming In a traditional data center, installation and programming of the management software and controls system can be a significant expense ($0.30/watt or more) and includes the cost to integrate the management system dashboard/interface with the power and cooling infrastructure and to tune the controls of the system to achieve desired performance (i.e. controlling cooling set points for optimal energy economizer mode hours and energy consumption). For many custom data centers, this is an end goal that is never achieved because of the complexities in controlling the system. For modular facilities, this expense is brought primarily into the factory, where programming and optimization of software and controls are standardized so onsite work is nearly eliminated and operating performance of the data center improves. Commissioning Commissioning involves documenting and validating the result of the data center's design / build process. The detailed steps of commissioning varies from data center to data center, but often includes steps like factory witness testing, quality assurance & quality control, start-up, functional testing, and integrated systems testing. For modular facilities, steps like factory witness testing and quality assurance is often viewed as unnecessary since it is a standardized, pre-designed, pre-integrated, and pre-tested complete system. This results in a savings of around 25%. Although not illustrated in the Figure 1 analysis, another key cost benefit of the facility module approach is the reduction or elimination of on-site brick & mortar facility construction to house the physical infrastructure. Not only is this costly (on the order of $ $1,614 per m 2 or $100-$150 per ft 2 ), it is disruptive to normal facility operations (see Figure 2 and Figure 3). Schneider Electric Data Center Science Center Rev 2 4
5 Figure 2 Traditional approach for expanding existing data center Figure 3 Raised floor installation for brick and mortar data center With prefabricated facility modules, the construction work is less invasive and less complex as no core and shell needs to be built and field installation is significantly reduced. Figure 4 illustrates a facility module being placed on-site on a cement pad with a crane. Once in place, electrical power is connected to the main switchgear, to the cooling facility module, and to the IT space, and chilled water piping is connected to the air handlers in the IT space). Schneider Electric Data Center Science Center Rev 2 5
6 Figure 4 Installation of preassembled, preengineered data center power module In a scenario where facility power and cooling modules will be supporting the data center, much of the traditional up-front design and construction management burden shifts from the data center owner / end user to the solution provider, as Figure 5 illustrates (note a designbuild firm could perform all of these tasks in the traditional case). The manufacturer designs and then stamps and repeats data center power and cooling modules for multiple customers. The data center power and cooling physical infrastructure becomes part of the manufacturing supply chain instead of an on-site custom build. This has a significant impact on the installation expense. In a traditional approach, the owner / end user is responsible for either developing the design, assembling the components of the solution, engaging the various vendors for equipment acquisition, or for hiring and managing contractors to perform this work. In contrast, since facility power and cooling modules are pre-built in the factory, the owner / end user avoids time consuming tasks (no need to chase down the individual pieces of equipment needed, one or few delivery schedules to manage, very few, if any, construction contractors to interface with). For help on comparing the cost tradeoffs between prefabricated and traditional data centers, use Schneider Electric s TradeOff Tool, Prefabricated vs. Traditional Data Center Cost Calculator. Traditional Approach Conception Prefabricated Facility Modules Begin Conception Figure 5 In the traditional approach, the data center owner is burdened with either performing or contracting out much of the planning and solution assembly work Schematic design Design development Construction documents Bidding / negotiation for parts Acquisition of components Construction / Operations installation Data Center Life Cycle Schematic design Design development Construction documents Bidding / negotiation for parts Acquisition of components Manufacturing / installation Operations Solution Provider Management Responsibility Data Center Owner Management Responsibility Decommissioning End Decommissioning Schneider Electric Data Center Science Center Rev 2 6
7 Further cost savings of facility modules The above analysis focused on capital cost, but there are further savings when operating expense is considered. Maintenance costs The potential exists to reduce facility module maintenance costs. Even though maintenance must now be done in a tighter space, the end user would save by contracting for one stop shop facility module maintenance. Rather than having to write up an assortment of terms and conditions with different vendors, only one contract could be drawn up to support the one or two big box prefabricated facility modules. In such a scenario, one organization would be held accountable for the proper function of the facility module. This is a simplified approach as the data center owner no longer has to preoccupy himself with trying to track down which organization is responsible for resolving a mishap. In a traditional data center, many of the parts and pieces (plumbing, electrical, power system, cooling system, and racks) are supported by different suppliers and finger pointing is a common occurrence. The cost savings could also extend to software / management upgrades. Instead of custom written code for a large assortment or products, the data center facility power and cooling modules could make available to the customer one set of standard firmware upgrades. Energy costs Traditional mechanical and electrical rooms consume more energy than comparable power and cooling prefabricated facility modules. Energy savings exists primarily because the preengineered design of the modules allows for better integration of power and cooling system controls (this advantage is especially pronounced when it comes to the coordination of the cooling system controls). Consider the example of controls for a chiller plant. The programming required to properly coordinate chillers, cooling towers, pumps and valves, for example, is extensive. Adding economizer modes increases the complexity. In fact, often times, economizer modes are disabled in designs because of this complexity, which results in added energy expense. The American Society of Heating, Refrigerating and Air-conditioning Engineers (ASHRAE) publishes standards for Coefficient of Performance (COP) for chiller plants. A higher COP indicates a better overall system performance. Although the individual parts that make up the chiller plant may achieve the published standards, most chiller plants achieve a much lower COP. This is a symptom of problems encountered when attempting to integrate the controls of the various components involved. The ineffectiveness of custom designed / integrated controls implemented in the field often means significantly less time operating in economizer mode and higher energy consumption overall. The PUE of a facility module is predictable because the equipment has been extensively pre-tested using standard components and the controls have been coordinated ahead of time. The complexity of the controls makes it difficult to predict Power Usage Effectiveness (PUE) within a traditional setting. The PUE of a facility module is predictable, however, because the equipment has been extensively pre-tested using standard components and the controls have been coordinated ahead of time. Consider the PUE of a traditional 1 MW data center located in St. Louis, Missouri, USA at 50% load with an average density of 6 kw per rack, raised floor, chillers, variable frequency drives (VFD), water control, and economizers. In such a data center a PUE of about 1.75 would be typical. Comparable prefabricated module configurations have been tested and analyzed and a measured PUE of 1.4 or better is expected. That difference translates into an electrical bill reduction of 20%. Schneider Electric Data Center Science Center Rev 2 7
8 Additional facility module benefits Beyond the cost advantages of prefabricated facility modules, data center owners have additional reasons for pursuing the facility module approach: Predictable efficiency The facility module approach allows the consumer to specify and for the manufacturer to publish expected efficiencies based on real measurements of the design. This predictability is attractive for businesses with a focus on energy efficiency initiatives. Portability If portability represents a high value, then the prefabricated facility modules may make some sense. Consider the example of a business that needs to deploy data center power and cooling but whose lease runs out in 18 months. If their lease is not renewed, they can physically move their data center physical infrastructure (power and cooling) investment with them instead of leaving it behind. Other financial benefits From an accounting standpoint, prefabricated facility modules could be classified as equipment as opposed to being designated as a building. This would likely offer tax, insurance and financing benefits. Obviously, tax law, insurance policies, and purchase/leasing contracts vary from place to place and from region to region. So this potentially substantial benefit should first be verified before assuming it exists for your given circumstances. Hedge against uncertainty Prefabricated facility modules are a viable option if a high degree of uncertainty exists regarding future growth. The flexibility of scaling and rightsizing helps to minimize risk. Speed of deployment Traditional data centers can take up to two years, from concept to commissioning, for delivery. Speed of implementation is oftentimes critical to a business. Cost of time is important to organizations that place a high value on early delivery (e.g., companies who want to be first to market with new products). Data centers built with prefabricated facility modules can be deployed in less than half the time from concept to commissioning (see Figure 6). Time to Deployment Estimates (in weeks) Design & Engineering % time savings Factory Production 4 32 Figure 6 Comparison of deployment time estimates (modular vs. traditional) Construction Testing End of traditional timeline Installation 6 End of modular timeline 25 Commission Modular Weeks Traditional Schneider Electric Data Center Science Center Rev 2 8
9 Simplified training The facility module approach allows the training of the staff to be greatly simplified since the modules are standardized with a system-level interface. This also means there is less risk to the data center operation when transitions in staff occur. Facility module drawbacks If prefabricated facility modules offer flexibility, shorter time of deployment, and cost advantages, then why aren t prefabricated facility modules a solution for everyone? Consider some of the challenges that prefabricated facility modules can present: Distance between the prefabricated facility modules and the internal data center In cases where outdoor facility power and cooling modules supply an indoor data center, distance is an important factor. If the indoor data center is located next to an outdoor perimeter wall or a roof, expense to connect the data center to the prefabricated facility modules is minimized. However, if the data center is located deep within the building, the cost of running cable and piping (breaking through multiple walls, floors, and/or ceilings) could quickly become prohibitive. Physical risks Prefabricated facility modules can be exposed to outside elements such as severe weather, malicious intent, vehicle traffic (if placed in parking lot), and animal / insect infestation. Risks for a particular site should be assessed before choosing to deploy prefabricated facility modules. Arrangements for power provisioning and network connectivity When prefabricated facility modules are installed, arrangements for additional power distribution (additional breakers / switchgear) and fiber connections need to be established. Restrictive form factor Prefabricated facility modules are big chunks of power and cooling capacity and, although mobile, they do present some challenges when it comes to relocation. The blocks are heavy and may be too heavy to place on the roof of a building. The 40 foot by 8 foot (12.2 m by 2.4 m) dimensions of a typical shipping container means that data center owners who experience growth may be confined by width, height, and length restrictions unless they have enough ground space to add more prefabricated facility modules. Human ergonomics Prefabricated facility modules are designed for remote operations and are less human friendly than traditional brick and mortar data centers. Space inside is very limited (for maintenance personnel for example) and airflow is geared towards equipment and not for the comfort of humans. Serviceability Service personnel who work in traditional data centers are accustomed to access to the front and back of equipment in a protected indoor environment. Some facility power and cooling modules, on the other hand, have doors located on the outside which are the means by which service people can access the back of the equipment. When these doors are open, the physical infrastructure equipment is exposed to heat, moisture, dust, cold and other potentially harmful outdoor elements. Local code compliance Since prefabricated facility modules present a new technology, local municipalities may not yet have established guidelines for restrictions on modules. Inconsistencies could exist regarding how different municipalities classify power, cooling, and IT modules. Local codes impact the level of module engineering and customization required to secure Authority Having Jurisdiction (AHJ) approvals. Transportation The Transportation Security Administration (TSA) stipulates width (11.6 feet, 3.5 meters) and length limitations in the United States in order for truck and train loads to pass over curved roads, under bridges, and through tunnels. Outside of North America, Schneider Electric Data Center Science Center Rev 2 9
10 roads can be even smaller, further restricting the mobility of containers. Non-standard wide loads require special permits and in some cases escorts which increases the cost of transporting the prefabricated facility modules. Table 1 summarizes the differences between a traditional data center build out and prefabricated facility modules across various factors. (Note that the cells with a checkmark indicate the best performer for each factor.) Table 1 Summary comparison of traditional and prefabricated facility module approaches Factor Traditional data center build out Prefabricated facility module Time to deploy 12 to 24 months represents a typical timeframe Can be designed, delivered, installed, and operational within 8 months or less Cost to deploy Regulatory roadblocks Security Installation Tax implications Reliability High up front capital cost with extensive field assembly, installation, and integration Regulatory approvals on an ad-hoc basis for the various steps of the infrastructure layout. This approach often results in delays that impact the initiation of downstream construction. The end user is responsible for securing approvals. Physical security is enhanced when assets are located deep within the building, away from the outside perimeter From a physical infrastructure perspective, a retrofit can be more complex and more invasive than a build out of a new data center. Infrastructure components need to be installed individually, started up individually and then commissioned. Recognized as permanent part of the building The solution is assembled on site from various parts and pieces provided by multiple vendors. This increases the need for coordination and therefore, creates more chances for human error. Allows data center to be built out in large kw building blocks of pre-manufactured power and cooling capacity Data center owners who choose to install prefabricated facility modules should check with local authorities prior to installation. Permitting processes may vary greatly across different geographies. Location of physical infrastructure assets outside of the building increases exposure to outside physical security and weather threats Specialized equipment (such as a crane) is needed to maneuver 20 and 40 foot pre-configured prefabricated facility modules. A docking station needs to be configured for connection to building pipes and electrical. Started up as one integrated unit. Reported as temporary structure which can be more attractive from a tax perspective (see Schneider-Electric White Paper 115, Accounting and Tax Benefits of Modular, Portable Data Center Infrastructure) More predictable performance because components are prewired and are factory acceptance tested before shipping. Smaller modules reduce risks of human error: If a failure occurs, the entire data center doesn t go down. Efficiency Carbon footprint Serviceability Existing structures often limit the electrical efficiencies that can be achieved through optimized power and cooling distribution; complex custom configured controls often result in suboptimal cooling operation, reducing efficiency Construction materials utilized are high in carbon emissions. Brick, insulation and concrete are all carbon emission intensive materials. Concrete is often used for floors, walls and ceilings. Traditional data centers have more room for service people to maneuver. All servicing is protected from any harsh weather elements. Prefabricated facility modules can utilize standard modular internal components and can be specified to a target PUE. Steel and aluminum produce about half the carbon emissions of concrete. Concrete is only used to pour a support pad. Significantly less concrete is needed for prefabricated facility modules as opposed to a comparable building shell data center. Servicing is more limited with facility modules because of space constraints. In some cases equipment can only be accessed by opening a door from the outside and exposing equipment to outside elements (heat, moisture, cold). Schneider Electric Data Center Science Center Rev 2 10
11 Types of prefabricated facility modules Schneider Electric classifies prefabricated facility modules based on three attributes that, together, define the majority of prefabricated modular data centers. These three attributes are: Functional block Form factor Configuration Functional block The functions of a data center can be broken down into three major categories the power plant, the cooling plant, and the IT space. Prefabricated data center modules sometimes provide multiple functions (referred to as all-in-one configurations), but often they provide one function of the data center Form factor This refers to the type of structure, size, and shape. The form of a particular solution impacts the transportability of it, the placement of it, and its location (inside vs. outside on the ground vs. on a rooftop). The three general forms of prefabricated data center modules are; ISO container, enclosure, and skid-mounted. Configuration There are several ways the functional blocks can be implemented in a data center. These approaches fall under three main categories: Semi-prefabricated A data center comprised of a combination of prefabricated functional blocks and traditional stick built systems Fully prefabricated A data center comprised completely of prefabricated IT, power, and cooling modules All-in-one A data center that is self-contained in a single enclosure, with IT, power, and cooling systems For more information on the types of prefabricated facility modules, see White Paper 165, Types of Prefabricated Modular Data Centers. Applications of data center facility modules The following is a list of some typical facility module applications: Colocation facilities seeking faster, cheaper ways to step and repeat computer power and support systems for their customers Prefabricated facility modules provide colos with a solution to cost effectively upsize and downsize in large kw modular building blocks when demand for their services fluctuates as a result of market conditions. Data centers that are out of power and cooling capacity or out of physical space The prefabricated facility modules can quickly add cooling and power capacity so that additional servers can be placed into existing racks, creating a higher density per rack, which can now be handled by the supplemental power and cooling. New facilities with tight time constraints Cost of time is important to organizations that place a high value on early delivery (e.g., companies who want to be first to market with new products). Data center operators in leased facilities If a business has a lease, they may not want to pour money into a fixed asset that they would have to leave behind. If their lease is not renewed, modules can physically move with them. Schneider Electric Data Center Science Center Rev 2 11
12 IT departments whose staff is willing to manage power and cooling Not relying on the stretched resources of corporate facility departments can leverage prefabricated facility modules to control their own chilled water supply. Data center facilities saddled with existing infrastructure characterized by poor PUE These facilities may only be marginally improved within the constraints of their existing physical plant. Adding prefabricated facility modules provides an alternative to help solve problems inherent to the inefficient data center design they may have inherited. An organization with vacant space For example, an empty warehouse space can populate the space with a series of pre-packaged modules. They leverage utilization of the space and avoid the delays and construction costs of building a new brick and mortar wing. Schneider Electric Data Center Science Center Rev 2 12
13 Conclusion The introduction of facility power and cooling modules presents an alternative to the traditional craft industry approach of designing and building data centers. New economic realities make it no longer possible to bear the brunt of heavy upfront costs and extended construction times for building a traditional data center. The availability of pre-engineered prefabricated facility modules allows the planning cycle to switch from an onsite construction focus to onsite integration of pre-manufactured, pre-tested blocks of power and cooling. The result of this change in focus is a lower cost, and faster delivery solution. The ideal applications for prefabricated facility modules are as follows: 1. A new data center seeking faster, cheaper ways to step and repeat computer power and support systems (especially when load growth is uncertain). 2. An organization with vacant space (i.e. warehouse space) that can be leveraged for a more quickly-deployed new data center without the expense of brick and mortar construction. 3. Existing data centers that are constrained by space and power / cooling capacity. Prefabricated facility modules can power and cool traditional data center IT rooms that are out of power and cooling capacity. They can also be used to power and cool IT modules (containers of IT equipment). Among leading edge corporations, a migration from brick and mortar to facility module parks will take place. Cloud computing business models will also accelerate the deployment of rapid facility module provisioning. About the authors Dennis Bouley is a Senior Research Analyst at Schneider Electric's Data Center Science Center. He holds bachelor s degrees in journalism and French from the University of Rhode Island and holds the Certificat Annuel from the Sorbonne in Paris, France. He has published multiple articles in global journals focused on data center IT and physical infra-structure environments and has authored several white papers for The Green Grid. Wendy Torell is a Senior Research Analyst at Schneider Electric s Data Center Science Center. She consults with clients on availability science approaches and design practices to optimize the availability of their data center environments. She received her Bachelors of Mechanical Engineering degree from Union College in Schenectady, NY and her MBA from University of Rhode Island. Wendy is an ASQ Certified Reliability Engineer. Schneider Electric Data Center Science Center Rev 2 13
14 Resources Accounting and Tax Benefits of Modular, Portable Data Center Infrastructure White Paper 115 Economizer Modes of Data Center Cooling Systems White Paper 132 Data Center Projects: Growth Model White Paper 143 TCO Analysis of a Traditional Data Center vs. a Scalable, Prefabricated Data Center White Paper 164 Types of Prefabricated Modular Data Centers White Paper 165 Browse all white papers whitepapers.apc.com Data Center Capital Cost Calculator TradeOff Tool 4 Data Center Design Planning Calculator TradeOff Tool 8 Prefabricated vs. Traditional Data Center Cost Calculator TradeOff Tool 17 Browse all TradeOff Tools tools.apc.com Contact us For feedback and comments about the content of this white paper: Data Center Science Center [email protected] If you are a customer and have questions specific to your data center project: Contact your Schneider Electric representative at Schneider Electric. All rights reserved. Schneider Electric Data Center Science Center Rev 2 14
Types of Prefabricated Modular Data Centers
Types of Prefabricated Modular Data Centers White Paper 165 Revision 0 by Wendy Torell Executive summary Data center systems or subsystems that are preassembled in a factory are often described with terms
The Pros and Cons of Modular Systems
The Pros and Cons of Modular Systems Kevin Brown, Vice President Global Data Center Offer Schneider Electric Schneider Electric 1 Foundational BUSINESS OVERVIEW Rev 2 Desired characteristics of pre-fabricated
Comparing Data Center Power Distribution Architectures
Comparing Data Center Power Distribution Architectures White Paper 129 Revision 3 by Neil Rasmussen and Wendy Torell Executive summary Significant improvements in efficiency, power density, power monitoring,
Data Center Solutions - The Containerized Evolution
Data Center Solutions - The Containerized Evolution Power IT Cooling 7 th Green Connected World Tsikogias Thanassis Data Centers Solutions Architect, IT Business Athens 2015 1 We are the global specialist
Datacenter Efficiency
EXECUTIVE STRATEGY BRIEF Operating highly-efficient datacenters is imperative as more consumers and companies move to a cloud computing environment. With high energy costs and pressure to reduce carbon
Avoiding Costs from Oversizing Data Center and Network Room Infrastructure
Avoiding Costs from Oversizing Data Center and Network Room Infrastructure White Paper 37 Revision 7 by Neil Rasmussen > Executive summary The physical infrastructure of data centers and network rooms
European Code of Conduct for Data Centre. Presentation of the Awards 2016
European Code of Conduct for Data Centre Presentation of the Awards 2016 Paolo Bertoldi European Commission DG JRC Institute for Energy and Transport 1 The Code of Conduct for Data Centre Results European
Simplifying Data Center Design/Build
Simplifying Data Center Design/Build A new approach to deliver speed, cost, and performance (availability, efficiency, scalability) Eduard Bodor Data Center Business Development Manager for Central and
Data Center Consolidation Trends & Solutions. Bob Miller Vice President, Global Solutions Sales Emerson Network Power / Liebert
Data Center Consolidation Trends & Solutions Bob Miller Vice President, Global Solutions Sales Emerson Network Power / Liebert Agenda Traditional Data Centers Drivers of a Changing Environment Alternate
Types of Electrical Meters in Data Centers
Types of Electrical Meters in Data Centers White Paper 172 Revision 1 by David Kidd and Wendy Torell > Executive summary There are several different types of meters that can be designed into a data center,
S c h n e i d e r E l e c t r i c BUSINESS IMPACT. Jack Hack Enterprise System Engineer 19 November 2015
S c h n e i d e r E l e c t r i c BUSINESS IMPACT Datacenter means business - create the bridge between IT en Facilities. Jack Hack Enterprise System Engineer 19 November 2015 1 Your ability to compete
Creating Order from Chaos in Data Centers and Server Rooms
Creating from in Data Centers and Server Rooms White Paper 119 Revision 1 by Dennis Bouley > Executive summary Data center professionals can rid themselves of messy racks, sub-standard under floor air
Guidance for Calculation of Efficiency (PUE) in Data Centers
Guidance for Calculation of Efficiency (PUE) in Data Centers White Paper 158 Revision 3 by Victor Avelar Executive summary Before data center infrastructure efficiency can be benchmarked using PUE or other
Specification of Modular Data Center Architecture
Specification of Modular Data Center Architecture White Paper 160 Revision 1 by Neil Rasmussen > Executive summary There is a growing consensus that conventional legacy data center design will be superseded
Guidance for Calculation of Efficiency (PUE) in Data Centers
Guidance for Calculation of Efficiency (PUE) in Data Centers White Paper 158 Revision 1 by Victor Avelar > Executive summary Before data center infrastructure efficiency can be benchmarked using PUE or
Data Center Technology: Physical Infrastructure
Data Center Technology: Physical Infrastructure IT Trends Affecting New Technologies and Energy Efficiency Imperatives in the Data Center Hisham Elzahhar Regional Enterprise & System Manager, Schneider
IBM Portable Modular Data Center Overview for Critical Facilities Round Table
Brian Canney Global Services Executive, IBM GTS Site and Facilities Services April 2011 IBM Portable Modular Data Center Overview for Critical Facilities Round Table 2009 IBM Corporation Key messages Containers
How Row-based Data Center Cooling Works
How Row-based Data Center Cooling Works White Paper 208 Revision 0 by Paul Lin and Victor Avelar Executive summary Row-based data center cooling is normally regarded as a cold air supply architecture that
How To Calculate Total Cooling Requirements For Data Center
Calculating Total Cooling Requirements for Data Centers White Paper 25 Revision 3 by Neil Rasmussen > Executive summary This document describes how to estimate heat output from information technology (IT)
AisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings
WH I TE PAPE R AisleLok Modular Containment vs. : A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings By Bruce Long, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies,
Overload Protection in a Dual-Corded Data Center Environment
Overload Protection in a Dual-Corded Data Center Environment White Paper 206 Revision 0 by Neil Rasmussen Executive summary In a dual-corded environment, the loss of power on one path will cause the load
Traditional Data Centers
Data Centers 2 Lectrus is a leading electrical systems integrator and custom metal enclosure manufacturer. We build fully integrated modules for power distribution, power generation, cooling and IT equipment
Modular Data Centre. Flexible, scalable high performance modular data centre solutions. Data Centre Solutions...energy efficient by design
Data Centre Solutions...energy efficient by design Modular Data Centre Flexible, scalable high performance modular data centre solutions Creating an effective workspace environment The Modular Data Centre
Data Center Colocation Build vs. Buy
Data Center Colocation Build vs. Buy Comparing the total cost of ownership of building your own data center vs. buying third-party colocation services Executive Summary As businesses grow, the need for
POD S in Data Centres. The Frame Group Pty Ltd
Presented by: Greg Goode The Frame Group Pty Ltd DATA Centres? POD SOLUTIONS REFERRED TO AS: Cells Modular Rooms High Density Zones Portable Modular Data Centres (Containers) Multiple Interpretations Varied
Automation's Modular Containerized Datacenter Solutions
SAFE Automation's Modular Containerized Datacenter Solutions Automation's SAFE (Secure, Autonomous, Flexible, Efficient) Modular Containerized Datacenter offers a fast, flexible and efficient solution
Statement Of Work Professional Services
Statement Of Work Professional Services Data Center Electrical Efficiency Assessment Data Center Electrical Efficiency Assessment Service 1.0 Executive Summary Table of Contents 1.0 Executive Summary 2.0
A Scalable, Reconfigurable, and Efficient Data Center Power Distribution Architecture
A Scalable, Reconfigurable, and Efficient Data Center Power Distribution Architecture White Paper 129 Revision 1 by Neil Rasmussen > Executive summary Significant improvements in efficiency, power density,
abstract about the GREEn GRiD
Guidelines for Energy-Efficient Datacenters february 16, 2007 white paper 1 Abstract In this paper, The Green Grid provides a framework for improving the energy efficiency of both new and existing datacenters.
Cannon T4 Modular Data Centres. For Outside Deployment & Challenging Environments
Cannon T4 Modular Data Centres For Outside Deployment & Challenging Environments A high performance, full specification Data Centre, up to Tier 4* resilience, instantly deployable A highly secure Data
Data Center & IT Infrastructure Optimization. Trends & Best Practices. Mickey Iqbal - IBM Distinguished Engineer. IBM Global Technology Services
Data Center & IT Infrastructure Optimization Trends & Best Practices Mickey Iqbal - IBM Distinguished Engineer IBM Global Technology Services IT Organizations are Challenged by a Set of Operational Issues
ASSESSING THE COST: MODULAR VERSUS TRADITIONAL BUILD SUPPORTED BY
ASSESSING THE COST: MODULAR VERSUS TRADITIONAL BUILD SUPPORTED BY 2 Synopsis Within the data centre industry, the subject of modular data centres continues to be a source of widespread debate, disagreement
Engineered Material Handling. Overhead Bridge Cranes and Gantry Cranes
TM Engineered Material Handling Overhead Bridge Overhead and Gantry Bridge Cranes and Gantry Cranes Custom Engineered Crane Systems Gantry Cranes EMH builds a complete range of gantry cranes including
How To Improve Energy Efficiency In Data Center Management
A White Paper from the Experts in Business-Critical Continuity TM Data Center Users Group Special Report Energy efficiency and capacity concerns increase Fall 2012 Survey Results Executive Summary The
Dealing with Thermal Issues in Data Center Universal Aisle Containment
Dealing with Thermal Issues in Data Center Universal Aisle Containment Daniele Tordin BICSI RCDD Technical System Engineer - Panduit Europe [email protected] AGENDA Business Drivers Challenges
OPERATOR - FACILITY ADDRESS - DATE
. Facility Criteria (RFP).0 Location Characteristics Criteria Requirements 1 Ownership and Management: Please identify the owner(s) and managers of the property and indicate if there is on-site management.
Modular Systems wind portfolio overview Power Collection and Grid Connection products
Modular Systems wind portfolio overview Power Collection and Grid Connection products Slide 1 Modular Systems wind portfolio Wind power - definition A wind turbine is a device that converts kinetic energy
Avoiding Costs from Oversizing Data Center and Network Room Infrastructure
Avoiding Costs from Oversizing Data Center and Network Room Infrastructure White Paper 37 Revision 6 by Neil Rasmussen > Executive summary The physical and power infrastructure of data centers and network
A Scalable, Reconfigurable, and Efficient Data Center Power Distribution Architecture
A Scalable, Reconfigurable, and Efficient Data Center Power Distribution Architecture By Neil Rasmussen White Paper #129 Executive Summary Significant improvements in efficiency, power density, power monitoring,
A new way to do data centers.
A new way to do data centers. Get your business up to digital speed. Keep pace with prefabricated data center solutions. Your business is ready for a new data center or an upgrade. But is your data center
La modularidad a nivel de Data Centers integrales. Arturo Maqueo Business Development Manager Mexico y Centro America
La modularidad a nivel de Data Centers integrales Arturo Maqueo Business Development Manager Mexico y Centro America Dashboard Our approach to simplify DC transformation A Focus for Schneider Electric
Cooling Strategies for IT Wiring Closets and Small Rooms
Cooling Strategies for IT Wiring Closets and Small Rooms White Paper 68 Revision 1 by Neil Rasmussen and Brian Standley > Executive summary Cooling for IT wiring closets is rarely planned and typically
Data Center Rack Level Cooling Utilizing Water-Cooled, Passive Rear Door Heat Exchangers (RDHx) as a Cost Effective Alternative to CRAH Air Cooling
Data Center Rack Level Cooling Utilizing Water-Cooled, Passive Rear Door Heat Exchangers (RDHx) as a Cost Effective Alternative to CRAH Air Cooling Joshua Grimshaw Director of Engineering, Nova Corporation
Classification of Data Center Infrastructure Management (DCIM) Tools
Classification of Infrastructure Management (DCIM) Tools White Paper 104 Revision 3 by Kevin Brown Dennis Bouley > Executive summary Data centers today lack a formal system for classifying infrastructure
Data Center Projects: Project Management
Project Management White Paper 141 Revision 1 by Neil Rasmussen and Suzanne Niles > Executive summary In data center design/build projects, flaws in project management and coordination are a common but
Creating Order from Chaos in Data Centers and Server Rooms
Creating from in Data Centers and Server Rooms By Dennis Bouley White Paper #119 Executive Summary Data center professionals can rid themselves of messy racks, sub-standard under floor air distribution,
Enterprise Data Centres
Enterprise Data Centres 09/12/2014 MAR0064 Cannon Data Campus s Pre-Engineered, factory built modules and systems combine to produce a high performance, efficient, Data Centre Campus. s White Space, Mechanical
Energy Efficiency in New and Existing Data Centers-Where the Opportunities May Lie
Energy Efficiency in New and Existing Data Centers-Where the Opportunities May Lie Mukesh Khattar, Energy Director, Oracle National Energy Efficiency Technology Summit, Sep. 26, 2012, Portland, OR Agenda
Questions to be responded to by the firm submitting the application. Why do you think this project should receive an award? How does it demonstrate:
Questions to be responded to by the firm submitting the application Why do you think this project should receive an award? How does it demonstrate: innovation, quality, and professional excellence transparency
GHG Protocol Product Life Cycle Accounting and Reporting Standard ICT Sector Guidance. Chapter 8: 8 Guide for assessing GHG emissions of Data Centers
GHG Protocol Product Life Cycle Accounting and Reporting Standard ICT Sector Guidance Chapter : Guide for assessing GHG emissions of Data Centers DRAFT March 0 Table of Contents GHG Protocol ICT Sector
Determining Total Cost of Ownership for Data Center and Network Room Infrastructure
Determining Total Cost of Ownership for Data Center and Network Room Infrastructure White Paper #6 Revision 3 Executive Summary An improved method for measuring Total Cost of Ownership of data center and
Cooling Small Server Rooms Can Be. - Jim Magallanes Computer Room Uptime: www.cruptime.com Uptime Racks: www.uptimeracks.com
Cooling Small Server Rooms Can Be Inexpensive, Efficient and Easy - Jim Magallanes Computer Room Uptime: www.cruptime.com Uptime Racks: www.uptimeracks.com Server Rooms Description & Heat Problem Trends
Energy Efficiency Opportunities in Federal High Performance Computing Data Centers
Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory
Data Center Lifecycle and Energy Efficiency
Data Center Lifecycle and Energy Efficiency Lifecycle infrastructure management, power management, thermal management, and simulation solutions enable data center modernization. White Paper October 2014
Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings
WHITE PAPER Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings By Lars Strong, P.E., Upsite Technologies, Inc. Kenneth G. Brill, Upsite Technologies, Inc. 505.798.0200
AIR-SITE GROUP. White Paper. Green Equipment Room Practices
AIR-SITE GROUP White Paper Green Equipment Room Practices www.air-site.com Common practices to build a green equipment room 1 Introduction Air-Site (www.air-site.com) is a leading international provider
Guidelines for Specification of Data Center Power Density
Guidelines for Specification of Data Center Power Density White Paper 120 Revision 1 by Neil Rasmussen > Executive summary Conventional methods for specifying data center density are ambiguous and misleading.
Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001
Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001 Presented by: Liberty Engineering, LLP 1609 Connecticut Avenue
APC APPLICATION NOTE #112
#112 Best Practices for Deploying the InfraStruXure InRow SC By David Roden Abstract The InfraStruXure InRow SC (ACSC100 and ACSC101) is a self-contained air conditioner for server rooms and wiring closets.
BRUNS-PAK Presents MARK S. EVANKO, Principal
BRUNS-PAK Presents MARK S. EVANKO, Principal Data Centers of the Future and the Impact of High Density Computing on Facility Infrastructures - Trends, Air-Flow, Green/LEED, Cost, and Schedule Considerations
High-Efficiency AC Power Distribution for Data Centers
High-Efficiency AC Power Distribution for Data Centers White Paper 128 Revision 2 by Neil Rasmussen > Executive summary The use of 240 volt power distribution for data centers saves floor space, simplifies
Implementing Energy Efficient Data Centers
Implementing Energy Efficient Data Centers By Neil Rasmussen White Paper #114 Executive Summary Electricity usage costs have become an increasing fraction of the total cost of ownership (TCO) for data
Data Centre Solutions energy efficient by design
Data Centre Solutions energy efficient by design Mobile & Modular Data Centre Solutions Agile, Scalable, High Performance Mobile and Modular DC solutions Flexible, scalable high performance mobile & modular
Recommendations for Measuring and Reporting Overall Data Center Efficiency
Recommendations for Measuring and Reporting Overall Data Center Efficiency Version 2 Measuring PUE for Data Centers 17 May 2011 Table of Contents 1 Introduction... 1 1.1 Purpose Recommendations for Measuring
SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT
SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION A. The Work specified in this Section consists of designing, furnishing and installing factory-assembled
TELUS Quebec Intelligent Internet Data Center, Canada
Further information Skanska AB www.skanska.com Contact Noel Morrin, SVP Sustainability & Green Support [email protected] TELUS Quebec Intelligent Internet Data Center, Canada Case Study 105 Aspects
Overview of Green Energy Strategies and Techniques for Modern Data Centers
Overview of Green Energy Strategies and Techniques for Modern Data Centers Introduction Data centers ensure the operation of critical business IT equipment including servers, networking and storage devices.
How to estimate the cost of installing an Electrical Distribution Center (EDC)
How to estimate the cost of installing an Electrical Distribution Center (EDC) Candidate Number 0112233 June 2012 Table of Contents 1) Introduction 3 2) Types and Methods of Measurement 3 5 3) Specific
Classification of Data Center Operations Technology (OT) Management Tools
Classification of Data Center Operations Technology (OT) Management Tools White Paper 104 Revision 0 by Kevin Brown Dennis Bouley > Executive summary Data centers today lack a formal system for classifying
Data Center Industry Leaders Reach Agreement on Guiding Principles for Energy Efficiency Metrics
On January 13, 2010, 7x24 Exchange Chairman Robert Cassiliano and Vice President David Schirmacher met in Washington, DC with representatives from the EPA, the DOE and 7 leading industry organizations
Increasing Data Center Efficiency by Using Improved High Density Power Distribution
Increasing Data Center Efficiency by Using Improved High Density Power Distribution By Neil Rasmussen White Paper #128 Executive Summary A new approach to power distribution for high density server installations
Modular Chiller Plants for data centers. Downtime isn t acceptable
Modular Chiller Plants for data centers Downtime isn t acceptable Reducing risk with Quick Start A direct solution to your most important challenge uptime. At Johnson Controls we protect our customers
EMC DURHAM CLOUD DATA CENTER
EMC DURHAM CLOUD DATA CENTER Energy efficient design and construction EMC IT was hard at work reducing operational costs, increasing IT agility, and preparing for a dynamic future in the cloud when it
CANNON T4 MODULAR DATA CENTRE HALLS
CANNON T4 MODULAR DATA CENTRE HALLS Halve up-front investment, use a Modular fit out approach Highly efficient, Low PUE, Scalable system with reduced Capex and Opex Turnkey solutions available complete,
Statement of Work. 3.0 Details of Service Pre Start-up. - 1 - Cooling Start-up Service. Installation Service. Table of Contents. 1.0 Executive Summary
Installation Service Statement of Work - 1 - Cooling Start-up Service Cooling Start-up Service Service 1.0 Executive Summary Table of Contents 1.0 Executive Summary 2.0 Features & Benefits 3.0 Details
Case Study Nottingham Trent University
Data Centre Solutions...energy efficient by design Case Study Nottingham Trent University Nottingham Trent University deploys Modular Data Centre Technology (MDC) Designed & Manufactured by Workspace Technology
Data Center Business Overview:
Data Center Business Overview: How Trends impact your Datacenter Strategy Anna Conan Global Data Center strategy deployment VP Foundational BUSINESS OVERVIEW Rev 4a The energy dilemma is here to stay Continued
Data Center Trend: Distributed Power in the White Space
Data Center Trend: Distributed Power in the White Space By Jason Anderson Product Line Manager Eaton Executive summary Cloud computing vendors and colocation data centers make every effort to maximize
Power and Cooling Guidelines for Deploying IT in Colocation Data Centers
Power and Cooling Guidelines for Deploying IT in Colocation Data Centers White Paper 173 Revision 0 by Paul Lin and Victor Avelar Executive summary Some prospective colocation data center tenants view
Top 5 Trends in Data Center Energy Efficiency
Top 5 Trends in Data Center Energy Efficiency By Todd Boucher, Principal Leading Edge Design Group 603.632.4507 @ledesigngroup Copyright 2012 Leading Edge Design Group www.ledesigngroup.com 1 In 2007,
Enabling an agile Data Centre in a (Fr)agile market
Enabling an agile Data Centre in a (Fr)agile market Phil Dodsworth Director, Data Centre Solutions 2008 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without
A Blueprint for a Smarter Data Center Data Center Services helps you respond to change
Bret W. Lehman, PE GTS Site and Facilities Services March 25, 2011 A Blueprint for a Smarter Data Center Data Center Services helps you respond to change 2011 IBM Corporation Change is accelerating IT
Frequently Asked Questions Generators
Frequently Asked Questions Generators Fuel Related How much fuel do the generators use during normal operation? At exercise? The generator fuel consumption is given in each of the product knowledge books
Data Center Components Overview
Data Center Components Overview Power Power Outside Transformer Takes grid power and transforms it from 113KV to 480V Utility (grid) power Supply of high voltage power to the Data Center Electrical Room
Data Center Projects: Project Management
Data Center Projects: Project Management White Paper 141 Revision 1 by Neil Rasmussen and Suzanne Niles > Executive summary In data center design/build projects, flaws in project management and coordination
Unified Physical Infrastructure (UPI) Strategies for Thermal Management
Unified Physical Infrastructure (UPI) Strategies for Thermal Management The Importance of Air Sealing Grommets to Improving Smart www.panduit.com WP-04 August 2008 Introduction One of the core issues affecting
HVAC For Schools How to purchase an HVAC system that meets your school s unique requirements and stays within your budget
A PRIMER Educational HVAC For Schools How to purchase an HVAC system that meets your school s unique requirements and stays within your budget Contents: Introduction: The best HVAC system is durable, reliable
Calculating Space and Power Density Requirements for Data Centers
Calculating Space and Power Density Requirements for Data Centers White Paper 155 Revision 0 by Neil Rasmussen Executive summary The historic method of specifying data center power density using a single
The Next Generation APC by Schneider Electric InfraStruxure
The Next Generation APC by Schneider Electric InfraStruxure Data Centre physical infrastructure architecture Data Centres and Networks Introducing the Next Generation InfraStruxure The data centre architecture
Design Best Practices for Data Centers
Tuesday, 22 September 2009 Design Best Practices for Data Centers Written by Mark Welte Tuesday, 22 September 2009 The data center industry is going through revolutionary changes, due to changing market
100 Locust Avenue, Berkeley Heights, New Jersey P R O P E R T Y O F F E R I N G
100 Locust Avenue, Berkeley Heights, New Jersey P R O P E R T Y O F F E R I N G The Opportunity Jones Lang LaSalle, Inc. (the Broker ) is please to offer the fee simple interest in 100 Locust Avenue (the