Enhancing ESP Efficiency for High Resistivity Fly Ash by Reducing the Flue Gas Temperature
|
|
|
- Corey Dorsey
- 9 years ago
- Views:
Transcription
1 406 Enhancing ESP Efficiency for High Resistivity Fly Ash by Reducing the Flue Gas Temperature Andreas Bäck (Alstom Power Sweden AB P.O. Box 1233 SE , Växjö, 0BAbstract: the resistivity of fly ash after coal-fired boilers varies with the flue gas temperature. the normal esp operating temperature of around 150 is typically near the maximum resistivity of the ash. for low sulphur coals the resistivity will sharply decrease if the flue gas temperature at the esp inlet is reduced to about 100 or less. this will mean that a significantly smaller esp can be built for a given efficiency. already in the early 1970 s esps were built at the liddell power station in australia purposely designed to operate at low temperature to reduce the fly ash resistivity. the full-scale design at liddell was based on pilot testing at other locations in order to verify the low temperature approach. despite successful implementation at liddell the experiences did not result in much follow-up of low temperature esp operation. the concept was revived in japan in the 1990 s, resulting in several installations working at temperatures below 100 these units have a considerably reduced esp size, and the energy recovered upstream the esp is used to re-heat the flue gas after the desulphurisation system. the low temperature esp operation is now well proven and a viable alternative when burning low sulphur coals. 9BKeywords: Electrostatic precipitator, ESP, power plant, coal, fly ash, sulphur, resistivity, back-corona, temperature, migration velocity 1B1 INTRODUCTION AND BACKGROUND Globally, the largest application for industrial particulate collection is after coal-fired boilers. In principle there are two practical alternatives of equipment to collect the fly ash, namely electrostatic precipitators (ESPs) or fabric filters (FFs). The choice between these two options is affected by the coal that will be fired in the boiler. For coal that generates fly ash that has high resistivity an ESP cannot be operated at a high specific power input since a high current passing through the ash layer on the collecting electrodes will induce backionisation (back-corona). Due to the low current density required to reduce the back-corona the ESP size will have to be larger to meet a given emission level. A fabric filter is not at all affected by the resistivity of the fly ash and often becomes an attractive option for such type of coals. The phenomenon of back-corona and the strategies to avoid it is traditionally an area of great interest in the field of electrostatic precipitation. The resistivity of fly ash depends strongly on the temperature of the flue gas. The exact functional relationship depends on fly ash composition, sulphur content of the coal, flue gas moisture content, etc. It may look like the curve shown in Fig. 1 for a typical high resistivity fly ash. The curve in Fig. 1 shows a measurement performed in the laboratory on collected fly ash, and is considered to be roughly representative of the situation inside the ESP during operation. Typically the maximum fly ash resistivity occurs between , which is close to the operating temperature of most ESPs after coal-fired boilers. The decrease in resistivity with increasing temperature above the peak is a volume property of the ash that occurs for any semiconductor or insulator material. The decrease in resistivity for lower temperature, on the other hand, is a surface effect due to condensation of mainly moisture and SO 3 on the individual ash particles. Fig. 1 Dust resistivity as function of temperature (Australian fly ash) In the 1960 s it was thought that an effective way to overcome resistivity problems in electrostatic precipitators would be to place it upstream the air preheater, letting the ESP operate at a temperature of Under such operating conditions it was envisioned that all problems associated with high resistivity fly ash would vanish [1]. This would result in lower cost ESPs despite the higher actual gas flow and other complications associated with high temperatures. Consequently a large number of these hot-side ESPs were built between the late 1960 s and early 1980 s, mainly in the USA. However, this approach turned out as a failure for the majority of the installations due to unexpected
2 Enhancing ESP Efficiency for High Resistivity Fly Ash by Reducing the Flue Gas Temperature 407 long term effects in the dust layer. This so called sodium depletion phenomenon caused back-corona to re-occur after some time of operation at the elevated temperatures [2]. Thus the design of new hot-side ESPs was discontinued. Today most of the existing installations have been converted to ordinary units with the ESPs located after the air preheater at gas temperatures of around 150. The other obvious choice to solve the high resistivity problem, namely to go for lower flue gas temperatures, did not at all receive the same amount of interest as the hot-side ESPs. Possibly this was due to fear for corrosion issues when coming closer to the acid dew point, as well as doubts regarding the design of the air preheater. Despite the lack of attention for the use of a low temperature approach for improved ESP performance it came into use in at least one major installation during the 1970 s. This interesting and important plant was the Liddell power station in Australia, arguably the first installation to utilize low flue gas temperature to reduce fly ash resistivity problems in the ESP. The Liddell plant consists of four 500 MWe boilers and each boiler was equipped with five ESPs. Three of these five ESPs, treating about 80% of the flue gas, were designed to operate at temperatures down to 90, while the two other would operate between 160 and 220. Successful performance guarantee testing of particulate emission was carried out for the low sulphur design coal in Despite the success at Liddell no organized effort was really made by ESP vendors or utilities to pursue a similar approach for many years. However, one example in these intermediate years was the Ensted power plant in Denmark (630 MWe). Originally designed for low to medium resistivity ash from West-Canadian coals the ESP experienced emission problems after a switch to low sulphur coals from Australia in the early 1980 s. Based on the experiences from Liddell, the solution employed was to decrease the flue gas temperature to the ESP, together with the newly introduced feature of Semipulse (Intermittent Energization) [3]. It was possible to operate the air preheater in such a way that the flue gas temperature was lowered to about 105 on a continuous basis, which gave a significant performance improvement compared to the design temperature of 130. The plant was operated in the low temperature mode for more than 10 years with no operational problems or corrosion issues. Renewed interest in low temperature ESP operation came in the mid-1990 s when Mitsubishi Heavy Industries (MHI) promoted the low temperature approach via pilot studies, and subsequently supplied a full scale ESP for a 1000 MWe plant in Japan [4,5]. This installation uses a separate non-leakage gas-gas heater (GGH) after the ordinary Ljungstrom air preheater to reduce the temperature to below 100. The energy recovered is used to reheat the flue gases downstream the wet flue gas desulphurisation unit to avoid a wet stack and visible plume. As in the Liddell case the ESP was sized much smaller than would have been the case at ordinary ESP operating temperatures, where resistivity would be very high for the low sulphur coals fired. After MHI s first installation at the plant Haranomachi several ESP installations operating at similar temperatures after coal-fired boilers have been built. Notable plants include Tachibanawan, Tomatoh, Maizuru, and the most recent installation Tosoh Nanyo, commissioned in early The total installed coal fired capacity using the low temperature ESP approach is to date well above MW. All of these new installations are located in Japan, and use the concept of an extra gas-gas heater before the ESP. New plants are currently in the planning stage. In the following sections the implementation of the low temperature approach at the three sites Liddell, Ensted and Tosoh Nanyo is described in some detail. It is hoped that this will serve as useful examples, showing the potential of low temperature ESP operation. In the last section some general conclusions are presented. 2B2 BASIC THEORY The basic formula describing ESP performance is the Deutsch equation, giving the outlet dust concentration, C out, as function of the inlet concentration (C in ), gas flow (Q) and precipitator collecting area (A): C out = C in exp[-ω A/Q]. The parameter ω has the dimension of m/s, and is referred to as the particle migration velocity (in the electric field). It can indeed be interpreted as the average velocity at which the dust particles travel towards the collecting plates, but may also be seen simply as a performance parameter for the ESP for the conditions at hand. The quantity A/Q that multiply ω is called the specific collecting area (SCA), which is the ESP size in m 2 of collecting area per m 3 of flue gas per second. Thus the ESP size (for given actual gas flow and emission limit) is directly proportional to 1/ω. The migration velocity, ω, is a complicated function of a large number of variables, including particle size distribution, ash composition, precipitator current and voltage, flue gas temperature, actual gas flow, ESP geometry, etc. The migration velocity is also dependent on the sulphur content in the coal, which in addition is a critical parameter for the feasibility of operating an ESP at low temperature. Depending on the moisture and temperature of the flue gas, and the SO 2 to SO 3 conversion rate in the system a maximum sulphur content (e.g. 0.8%) must be specified to avoid acid condensation and corrosion. It should be clear that the Deutsch equation is a highly idealized formula. Among other things it assumes the same ω- value for each particle, independent of its size, and includes no non-ideal effects like rapping losses or dust re-entrainment. In fact, the real precipitation process is so complex that purely theoretical models of the ESP operation have never been really successful. Electrostatic precipitation is therefore an experimental science, where prediction models must be based
3 408 on empirical experience in conjunction with theoretical considerations. One way to somewhat compensate for the dependence of ω on the particle size and make it less dependent on the SCA value is to use the modified Deutsch equation, also known as the Matts-Öhnfeldt equation [6]: C out = C in exp[-(ω k A/Q) k ]. Here k is an ad hoc parameter to compensate for a finite particle size distribution of the dust. For fly ash it has turned out that a k-value of around 0.5 is suitable to get a robust equation for size predictions and performance evaluations. Since this paper only concerns coal fired boilers the modified migration velocity, ω k, will be used throughout as the relevant ESP performance parameter. A k-value of 0.5 is then implied in the modified Deutsch equation. In this paper the focus will be on ω k as a function of flue gas temperature. When discussing the dependence of a multivariable function like ω k of only one single parameter all other variables would ideally be kept constant. This is however not theoretically possible due to internal temperature related dependencies among the variables themselves. Another comparison philosophy, which is possibly more relevant, is to optimize the ESP operation for each new test condition (temperature). However, it is very difficult to know that optimized performance is indeed achieved, and all parameters may not be practically possible to adjust. In the test descriptions below an attempt is made to explain briefly how other parameters were treated while investigating different flue gas temperatures. 3B3 RESULTS OF LOW TEMPERATURE ESP OPERA- TION IN AUSTRALIA In 1966 Fläkt (now Alstom) and the Electricity Commission of New South Wales (which later adopted the trading name Pacific Power) performed pilot testing to prepare the ESP specifications for the upcoming Liddell power plant. The tests were carried out using an Alstom three-field pilot ESP connected to a slipstream after boiler #4 at the Pyrmont power station in Sydney, Australia. The boiler was a 50 MWe pulverized coal boiler manufactured by International Combustion in For the tests 5000 tons of Bayswater coal, which was considered as a main fuel source for Liddell, had been excavated and transported to site. The flue gas temperature of the slipstream could be cooled by means of a heat exchanger, or heated using electrical heaters or by extracting flue gas upstream the economizer. A temperature range from about 90 up to 280 was achieved during the course of the test campaign. The ESP performance for the difficult low sulphur Bayswater coal was found to be strongly temperature dependent. This is illustrated in Fig. 2, where relative migration velocities for the temperature range have been plotted. During the testing at Pyrmont the pilot ESP was mostly run at a voltage close to the sparking threshold and continuous charging was used (the Semipulse concept was not developed until about 15 years later). The gas velocity through the pilot ESP was kept constant at about 0.55 m/s, and the boiler was running stable close to maximum load. Fig. 2 Relative migration velocity for the pilot ESP tests at Pyrmont as function of temperature (fly ash from Bayswater coal) As can be seen in Fig. 2, ω k at 90 is almost twice as high as compared to e.g For the design of an ESP this would translate in the first approximation to a corresponding reduction of the ESP size to half. If also the reduced actual gas flow at the lower temperature is considered one would arrive at a further reduced ESP size. The pilot study at Pyrmont, was made available to all prospective tenders for the MW Liddell project. The contract for all four boilers went to Combustion Engineering, while Fläkt (Alstom) received the ESP portion. Unit #1 was placed into service in 1971, and the other units came on line in the following two years. The ESP design and ductwork at Liddell was rather special, with the intention of using the low temperature from the secondary air preheaters (SAPH) to obtain enhanced ESP performance. The flue gas from the primary air preheaters (PAPH), on the other hand had a high temperature, and went into two separate ESP casings. The general ESP layout at Liddell is shown in Fig. 3. Fig. 3 Schematic picture of the ESP layout at Liddell (one boiler). The crossed squares represent damper locations
4 Enhancing ESP Efficiency for High Resistivity Fly Ash by Reducing the Flue Gas Temperature 409 The flue gas passing the secondary air preheater constitutes about 80% by weight of the total gas flow, and enters the ESP (casings B-D) at a temperature of The rest of the gas, which goes through the primary air preheaters, is treated in the two outer ESP casings (A and E), at a nominal temperature of 175. All five ESPs have three electrical fields, but the SCA of the low temperature casings B-D was designed significantly lower than that of casings A and E. This was based on the pilot test results at Pyrmont. The results from the performance guarantee tests at Liddell confirmed the temperature trend seen at Pyrmont. Fig. 4 shows the relative migration velocity for the low temperature ESPs versus the high temperature ESPs at Liddell. This figure is based on the guarantee tests for unit #2 in May Fig. 4 Measured relative migration velocities during the performance testing at Liddell #2 for the cold and hot ESP casings The Liddell measurements indicate an increase in migration velocity of about 70% if the flue gas temperature is decreased from 160 to 90. This is a somewhat smaller improvement factor than what was seen at Pyrmont. Part of the difference is of course that a pilot investigation is not the same as a full-scale test. Another reason could be that the gas velocity inside the low temperature ESP casings at Liddell was somewhat high, whereas the Pyrmont tests were designed to have equal gas velocity independent of temperature. In addition the much larger and more modern boiler at Liddell likely played a role. Anyhow the performance increase at low temperature is significant, and it is somewhat surprising that utilities and suppliers did not pursue this opportunity in many years to come. to the supplier of the ESP, Fläkt (Alstom), for advice on mitigations to increase fuel flexibility while still maintaining the legislated particulate emission level. The primary solution became to decrease the flue gas temperature to about 105, which was possible due to a conservatively sized Ljungstrom air preheater. This approach allowed firing of a wide range of difficult low sulphur coals with high resistivity ash, which had not been possible at the original design temperature. In 1984 a major test campaign took place, where different approaches were tested in order to minimize the particulate emission. Among other things this led to an early successful demonstrations of Semipulse (intermittent energization), using the first generation of microprocessor ESP controllers (EPIC) [3]. Special interest was also paid to the effect of flue gas temperature on the ESP performance. The ESP performance was monitored by a data acquisition system with continuous storage of over 300 variables. The dust emission in particular was measured by opacity meters, which had been thoroughly calibrated by gravimetric sampling. During the test campaign low sulphur Ulan coal from Australia was fired. The fly ash from this coal is well known for being extremely difficult to collect in a precipitator due to its high resistivity. During the temperature tests the plant personnel increased the flue gas temperature from the nominal 105 up to about 130, while keeping the boiler load constant at 620 MW. At about 130 the emission levels were typically so high that the temperature had to be brought back to 105 after some time due to environmental concerns. One temperature test is shown in Fig. 5. As can be seen, the east ESP casing performed better than the west, which is probably due to the lower pulsing frequency in the Semipulse settings (charging ratio 1:9 in the east casing compared to 1:5 in the west). For optimum performance higher charging ratios should likely have been used, especially for the high temperature. This was however not done. 4B4 IMPROVEMENT OF ESP EFFICIENCY AT REDUCED FLUE GAS TEMPERATURE IN DENMARK Unit #3 at the Ensted power plant (owned by DONG Energy) was commissioned in 1979 and is the second largest boiler in Denmark, at a rating of 630 MWe. The unit utilizes two separate five-field ESP casings for particulate collection. The SCA had been determined for handling low to medium resistivity fly ash from West-Canadian and Polish coals, but due to market availability alternative coal supplies had to be considered shortly after commissioning. The plant then turned Fig. 5 ESP performance (relative migration velocity) during a temperature excursion. The points shown in the graph represent about 4 hours and 45 minutes of data logging
5 410 Each point in Fig. 5 represents one sampled value, with a four minute averaging time. The figure shows two hours of stable operation at 105, after which comes an increase to 130 during about 45 minutes where the temperature then was kept for two hours. The emission peaks due to rapping in the last field resulted in an increase of outlet particulate with about a factor of three during the corresponding four-minute average. Thus the rapping peaks also decreased in proportion to the base line emission when operating at a lower temperature. The corresponding data points during rapping are however not shown in Fig. 5 (five points in both east and west casings). The data in Fig. 5 show an even more pronounced temperature trend than what was seen at the Liddell plant. This makes sense, since the Ulan coal at Ensted generates even higher resistivity fly ash than the Bayswater coal fired at Liddell. The performance enhancement for the Ulan coal is as high as a factor of two for the moderate temperature difference of 105 versus 130. In the mid-1980 s Alstom erected and commissioned an ESP pilot at the Ensted plant. The pilot, which treated a slipstream from boiler #3, was further developed in the 1990 s, comprising a total of three two-field ESPs. In view of the re-emerging interest for low temperature ESP operation some testing of the temperature dependence was performed at this pilot in In the following years additional pilot tests at other sites, e.g. at the Saijo power plant in Japan, were also carried out, paying special interest to operating temperatures around 100. During the pilot testing at Ensted in 1994 the three ESPs were connected in series, for a total of six electrical fields. The temperature could be varied between approximately 120 and 150. For the low sulphur South African coal fired in the boiler during the testing a clear temperature trend for the ESP collection efficiency could be seen even for this interval. As for the previous cases a prediction model used by Alstom for ESP sizing was found to correlate very favourably with the experimental data. The theoretical model could then be employed to estimate the efficiency at temperatures also below 100. This is demonstrated in Fig. 6. Fig. 6 Pilot results at Ensted 1994 for South African coal. The prediction model is the standard Alstom ESP sizing program The pilot tests at Ensted also support the temperature trend seen in the other examples above. The increase in migration velocity for the South African coal is predicted to be similar to that measured for Bayswater coal. 5B5 LOW-LOW TEMPERATURE ESP AT THE TOSOH NANYO COMPLEX IN JAPAN The ESP after unit #6 boiler at the Tosoh Corporation Nanyo complex in Shunan city is the most recent of the new generation of low temperature ESPs in Japan. These are often referred to as colder side ESP or low-low temperature ESP (LLT-ESP), operating at typical flue gas temperatures of The unit, which was commissioned in March 2008, consists of a 220 MWe pulverized coal boiler supplied by IHI Corporation, followed by the LLT-ESP and a limestone scrubber. The ESP, shown in Fig. 7, was supplied by Alstom and has two parallel gas passes (A and B) and four electrical fields in the direction of gas flow. Fig. 7 View of the #6 low-low temperature ESP at Tosoh Nanyo The reduction of flue gas temperature to below 100 is accomplished by a tubular non-leakage gas-gas heater upstream the ESP, which re-heats the saturated flue gas exiting the scrubber. In this way there will be no visible plume at the exit of the stack, and a wet stack is avoided. Shortly after the commissioning dust measurements of the ESP was carried out. The main purpose was to calibrate the optical dust meters and to prepare for the upcoming performance tests. The testing took place during three days while the boiler was operating at about 210 MW load, firing a 50-50% mix of Indonesian and Chinese coal. This was not the most difficult fuel out of the contract specification from an ESP perspective, but some Chinese coal types are known to give very fine fly ash [7], which could present a complication.
6 Enhancing ESP Efficiency for High Resistivity Fly Ash by Reducing the Flue Gas Temperature 411 During the test campaign the flue gas temperature in the ESP was kept at The gravimetrical testing and on-line dust monitoring showed emissions well below the designed emission of 30 mg/nm 3. In fact, during the measurements the power input to the ESP had to be reduced to give higher emission that did not fall under the measurement precision of the gravimetrical sampling. The emissions at maximum power input could then be estimated by extrapolating the calibrated dust monitoring curve downwards. This method led to an estimated outlet of around 4 mg/nm 3. At the lowest point of the calibration curve the gravimetrical sampling gave an emission of 6.7 mg/nm 3 (at about half the power consumption compared to maximum input). Alternatively the power consumption of the ESP could be further reduced to less than 1/10 of the maximum, while still staying below the design emission. This was done during the gravimetrical sampling to obtain the highest point of the calibration curve. Fig. 8 shows the outlet signal from the A- pass of the ESP at two different power input levels. Optical particle count per minute Increase of power input to ESP Gravimetric measurement no mg/nm3 (17:15-17:40) 0 18:00:00 18:10:00 18:20:00 18:30:00 Time Rapping Fig. 8 On-line signal after gas pass A. The emission is seen to decrease when the power input to the ESP is increased In Fig. 8 one can also see the impact of collecting electrode rapping. During four minutes fields 1 through 4 are being rapped sequentially, and a peak in emission can be observed. The emission peak is however very moderate, corresponding to less than 7 mg/nm 3. In summary the low-low temperature ESP at Tosoh Nanyo performed very satisfactory. Since the unit is operating continuously at temperatures below 100 the emission at higher temperatures can only be estimated using prediction rules. Given the fly ash characteristics and flue gas composition for the present operating conditions the temperature dependence will be less pronounced than e.g. for the difficult Australian coals described above. The present fly ash at Tosoh Nanyo could be classified as being of medium resistivity (at ordinary ESP temperatures) and will become low resistive in the low-low temperature regime. It is interesting to see that outlet emissions in the 5 mg/nm 3 range can be readily achieved by an ESP, and that the emission peaks associated with rapping are relatively small. This could indicate that low temperature operation enhance the agglomeration properties of the dust so that rapping losses are reduced. 6B6 DISCUSSION AND CONCLUSIONS As shown by the examples in this paper a very significant performance improvement can be achieved for an ESP by reducing the flue gas temperature. This is valid for a wide range of low sulphur coals, and with proper design and operation the potential risks like corrosion and clogging can be avoided. For specifications containing coals that generate fly ash of very high resistivity the ESP size can be reduced to less than half, if the design temperature is lowered from e.g. 150 down to below 100. The decrease of flue gas temperature can be achieved either by an increased size Ljungstrom air preheater, or by addition of an extra gas-gas heater upstream the ESP. The second approach uses the recovered energy in the GGH to reheat the flue gas exiting the limestone scrubber. This concept has been used for several large plants in Japan during more than a decade. For future development the path using merely an upsized Ljungstrom air heater could have more potential in terms of plant efficiency and savings in capital cost. Different approaches to effectively utilize the recovered energy to increase the plant net efficiency are possible. In future scenarios it may also be possible to use the low-grade heat in various CO 2 capture technologies. 7BACKNOWLEDGEMENTS The author wishes to thank the people at the Ensted plant for the excellent cooperation over the years, and in particular for reviewing the section about the Ensted investigations in this paper. Also the help from personnel at the Tosoh Corporation during the measurements on the Tosoh Nanyo ESP is gratefully acknowledged. 8BREFERENCES 1. Walker A.B.; Hot-side precipitators. APCA journal, Vol. 25, 143, Bickelhaupt R.E.; An interpretation of the deteriorative performance of hot-side precipitators. APCA journal, Vol. 30, 882, Porle K., Karlsson R., Kirkegaard B.; Long-term experience with pulsed energization of ESP s at a Danish power station. The 6th Symposium on the Transfer and Utilization of Particulate Control Technology, New Orleans, USA, Tanaka T., Fujishima H.; Development of advanced dust collecting system for coal-fired power plant. ICESP V, Washington D. C., USA, Fujishima H., Tsuchiya Y., Onishi S. Colder side electrostatic precipitator of advanced flue gas treatment system for coal fired boiler. ICESP VII, Kyongju, Korea Matts S., Öhnfeldt P-O. Efficient gas cleaning with the SF electrostatic precipitator. Fläkt Review, Vol. 6/7, 105, 1963/1964.
7 Lillieblad L., Johansson T., Porle K.; Electrostatic precipitator performance with Chinese coals. ICESP X, Cairns, Australia 2006.
TRIAL CHEMICAL CLEANING OF FOULED APH BASKETS
TRIAL CHEMICAL CLEANING OF FOULED APH BASKETS Dr. Abhay Kumar Sahay, AGM(CC OS) Bijay Manjul, AGM( Operation) Kahalgaon Boiler has three inputs Steam generator 1. WATER 2. COAL 3. AIR Burner Air preheater
Long-Term Demonstration of CO2 Recovery from the Flue Gas of a Coal-Fired Power Station
Long-Term Demonstration of CO2 Recovery from the Flue Gas of a Coal-Fired Power Station MASAKI IIJIMA* 1 SHOJIRO IWASAKI* 1 SHINYA KISHIMOTO* 1 TORU TAKASHINA* 2 SUSUMU OKINO* 2 There is now a growing
MILLIKEN CLEAN COAL TECHNOLOGY DEMONSTRATION PROJECT UNIT 2 ELECTROSTATIC PRECIPITATOR PERFORMANCE TEST RESULTS BEFORE AND AFTER MODIFICATION
MILLIKEN CLEAN COAL TECHNOLOGY DEMONSTRATION PROJECT UNIT 2 ELECTROSTATIC PRECIPITATOR PERFORMANCE TEST RESULTS BEFORE AND AFTER MODIFICATION Prepared by: CONSOL Inc. Research & Development 4000 Brownsville
Assessing the Changes Required by the Industrial Boiler MACT Regulations
Technical Paper MS-17 Assessing the Changes Required by the Industrial Boiler MACT Regulations Authors: A.L. LeClair L.M. McDermitt Babcock & Wilcox Power Generation Group, Inc. Barberton, Ohio, U.S.A
Phoenix Process Engineering, Inc. Project Experience Helping Clients Achieve MACT Compliance
Phoenix Process Engineering, Inc. Project Experience Helping Clients Achieve MACT Compliance The Boiler MACT, 40 CFR 63, Subpart DDDDD, was vacated in 2007 by the U.S Court of Appeals and the 2004 rule
Improving the Thermal Efficiency of Coal-Fired Power Plants: A Data Mining Approach
Paper 1805-2014 Improving the Thermal Efficiency of Coal-Fired Power Plants: A Data Mining Approach Thanrawee Phurithititanapong and Jongsawas Chongwatpol NIDA Business School, National Institute of Development
Natural Gas Conversions of Existing Coal-Fired Boilers
White Paper MS-14 Natural Gas Conversions of Existing Coal-Fired s Authors: F.J. Binkiewicz Jr., P.E. R.J. Kleisley B.E. McMahon J.E. Monacelli D.A. Roth D.K. Wong Babcock & Wilcox Power Generation Group,
GAS HEATING IN COMMERCIAL PREMISES
ENERGY EFFICIENCY OFFICES GAS HEATING IN COMMERCIAL PREMISES www.energia.ie www.energia.ie Typically, energy reductions of 10% or more can be made easily through maintenance and low cost improvements.
CoalGen 2010 Pre-Air Heater Control of SO3 and Related Condensables
CoalGen 2010 Pre-Air Heater Control of SO3 and Related Condensables Charles A. Lockert, Breen Energy Solutions, 104 Broadway Street, Carnegie, PA 15106 Greg Filippelli, P.E. and Marty Dillon, ADA Environmental
10 Nuclear Power Reactors Figure 10.1
10 Nuclear Power Reactors Figure 10.1 89 10.1 What is a Nuclear Power Station? The purpose of a power station is to generate electricity safely reliably and economically. Figure 10.1 is the schematic of
Guidelines on AIR POLLUTION CONTROL for. Joss Paper Burning at Chinese Temples, Crematoria and Similar Places
Guidelines on AIR POLLUTION CONTROL for Joss Paper Burning at Chinese Temples, Crematoria and Similar Places CONTENTS 1 Introduction 2 Major Considerations 3 Best Available Technology for Control of Air
Multi-pollutant control solutions for coal based power plants
Multi-pollutant control solutions for coal based power plants By Luca Mancuso and Hans Janssen Content SOx control Wet Scrubbers Open towers Dual Flow Tray Technology Semi-Dry SDA CFB Scrubbers Dust control
Biomass Boiler House Best Practices. Irene Coyle & Fernando Preto CanmetENERGY
Biomass Boiler House Best Practices Irene Coyle & Fernando Preto CanmetENERGY Growing the Margins London, Ontario March 2010 The Biomass & Renewables Group of Industrial Innovation Group (IIG) of CanmetENERGY
2nd IEA Oxyfuel Combustion Conference
2nd IEA Oxyfuel Combustion Conference Oxyfuel Combustion with Hitachi's DST - Burner at Vattenfall's 30Wth Pilot Plant at Schwarze Pumpe S. Rehfeldt, F.-P. Schiffer, P. Weckes, C. Bergins, K.-D. Tigges
Description of Thermal Oxidizers
Description of Thermal Oxidizers NESTEC, Inc. is a full service equipment supplier specializing in solutions for plant emission problems. The benefit in working with NESTEC, Inc. is we bring 25+ years
Thermo Scientific Arke SO 3 System. increased sensitivity. greater value
Thermo Scientific Arke SO 3 System increased sensitivity greater value Technology That Meets the Challenge The Thermo Scientific Arke SO 3 System, with built-in SO 3 generator, uses an advanced Quantum
University of Iowa Power Plant
University of Iowa Power Plant Contents Purpose... 2 History... 3 Cogeneration... 6 Boilers... 7 Environmental Impact... 10 Steam Turbine Generators... 12 Modernization... 14 Biomass Fuel Initiative...
Development and Operating Results of Low SO2 to SO3 Conversion Rate Catalyst for DeNOx Application
Development and Operating Results of Low SO2 to SO3 Conversion Rate Catalyst for DeNOx Application By Isato Morita Yoshinori Nagai Dr. Yasuyoshi Kato Babcock-Hitachi K.K., Japan Dr.Howard N. Franklin Hitachi
MHI s Energy Efficient Flue Gas CO 2 Capture Technology and Large Scale CCS Demonstration Test at Coal-fired Power Plants in USA
MHI s Energy Efficient Flue Gas CO 2 Capture Technology and Large Scale CCS Demonstration Test at Coal-fired Power Plants in USA 26 MASAKI IIJIMA *1 TATSUTO NAGAYASU *2 TAKASHI KAMIJYO *3 SHINSUKE NAKATANI
OROT RABIN POWER STATION UNITS 1-4. 4 x 350 MW
ISRAEL ELECTRIC OROT RABIN POWER STATION UNITS 1-4 4 x 350 MW COAL BOILER CONVERSION TO LOW NO X NATURAL GAS AND COAL FIRING BY PRIMARY AND SECONDARY MEASURES INSTALLATION Replacing the Burner Management
Bill Maxwell, U.S. Environmental Protection Agency, OAQPS (C439-01)
TO: Bill Maxwell, U.S. Environmental Protection Agency, OAQPS (C439-01) FROM: Jeffrey Cole, RTI International DATE: December 2003 SUBJECT: Methodology for Estimating Cost and Emissions Impact for Coal-
Application Note 12: TrendView Recorders Continuous Emissions Monitoring
Application Note 12: TrendView Recorders Continuous Emissions Monitoring Continuous Emissions Monitoring (often abbreviated to CEM) is the term commonly used to describe instantaneous or real-time environmental
Sulfur Tail Gas Thermal Oxidizer Systems By Peter Pickard
Sulfur Tail Gas Thermal Oxidizer Systems By Peter Pickard Introduction SRU s (Sulfur Recovery Units) are critical pieces of equipment in refineries and gas plants. SRUs remove sulfur compounds from certain
1.3 Properties of Coal
1.3 Properties of Classification is classified into three major types namely anthracite, bituminous, and lignite. However there is no clear demarcation between them and coal is also further classified
Continuous flow direct water heating for potable hot water
Continuous flow direct water heating for potable hot water An independently produced White Paper for Rinnai UK 2013 www.rinnaiuk.com In the 35 years since direct hot water systems entered the UK commercial
Well Positioned for the Future
Dominion Generation Virginia City Hybrid Energy Center Well Positioned for the Future The Coal Institute July 13, 2015 Rick Boyd Manager of Fuel Origination & Operations 1 Dominion Profile Operating Segments
SMPS: Present Application & Future Investigation
SMPS: Present Application & Future Investigation Gary J. Grieco, PE Air Consulting Associates, LLC Morris Plains, NJ Abstract This paper discusses Switch Mode Power Supply for improved energization of
Technique of Monitoring Dioxins in Flue Gas from MSW Incinerators using Dioxin Precursor Analyzer
Technique of Monitoring Dioxins in Flue Gas from MSW Incinerators using Dioxin Precursor Analyzer Hideki Nagano*, Kunio Miyazawa**, Yoshinori Yomura***, Toshihiko Iwasaki****, Takashi Yokoyama***** and
Experimental Study on Super-heated Steam Drying of Lignite
Advanced Materials Research Vols. 347-353 (2012) pp 3077-3082 Online available since 2011/Oct/07 at www.scientific.net (2012) Trans Tech Publications, Switzerland doi:10.4028/www.scientific.net/amr.347-353.3077
SO 3 -Monitoring in Flue Gas of a Power Plant Application & Results
of a Power Plant Application & Results : Introduction - SO 3 / H 2 SO4 - The SO 3 Challenge : Spectral evaluation - Components to be monitored - Calibration : Analyzer Setup : Field Test Results : Benefits
Increasing Natural Gas Boiler Efficiency by Capturing Waste Energy from Flue Gas
Increasing Natural Gas Boiler Efficiency by Capturing Waste Energy from Flue Gas Mark Schiffhauer, ATSI Engineering Services Cameron Veitch, Combustion and Energy Systems Scott Larsen, New York State Energy
Energy Efficient Operations and Maintenance Strategies for Boilers
Energy Efficient Operations and Maintenance Strategies for Boilers Large, complex and widely used, industrial boilers are major consumers of fuel. Proper operations and maintenance (O&M) procedures must
1.0 What Are the Purpose and Applicability of Performance Specification 11?
While we have taken steps to ensure the accuracy of this Internet version of the document, it is not the official version. Please refer to the official version in the FR publication, which appears on the
SNOX flue gas treatment for boilers burning high-sulphur fuels
SNOX flue gas treatment for boilers burning high-sulphur fuels SNOX flue gas treatment for boilers burning high-sulphur fuels 1 / 18 Summary The processing of more and more high-sulphur crude oil makes
Condensing Economizers Workshop Enbridge Gas, Toronto. MENEX Boiler Plant Heat Recovery Technologies. Prepared by: Jozo Martinovic, M A Sc, P Eng
Condensing Economizers Workshop Enbridge Gas, Toronto MENEX Boiler Plant Heat Recovery Technologies Prepared by: Jozo Martinovic, M A Sc, P Eng MENEX Innovative Solutions May 15, 2008 MENEX INC. 683 Louis
ELECTRODE BOILERS VAPOR POWER INTERNATIONAL
ELECTRODE BOILERS WITH JET-FLO Technology VAPOR POWER INTERNATIONAL ELECTRODE boilers The Electrode Steam Boiler with Jet-Flo technology consists of an insulated pressure vessel and is fully enclosed in
CONTENTS. ZVU Engineering a.s., Member of ZVU Group, WASTE HEAT BOILERS Page 2
WASTE HEAT BOILERS CONTENTS 1 INTRODUCTION... 3 2 CONCEPTION OF WASTE HEAT BOILERS... 4 2.1 Complex Solution...4 2.2 Kind of Heat Exchange...5 2.3 Heat Recovery Units and Their Usage...5 2.4 Materials
Evaluation Of Hybrid Air- Cooled Flash/Binary Power Cycle
INL/CON-05-00740 PREPRINT Evaluation Of Hybrid Air- Cooled Flash/Binary Power Cycle Geothermal Resources Council Annual Meeting Greg Mines October 2005 This is a preprint of a paper intended for publication
Drying of Woody Biomass. Process Engineering / GEA Barr-Rosin
Drying of Woody Biomass BioPro Expo & Marketplace / Atlanta, GA / March 14-16, 2011 Drying of Woody Biomass Conventional Direct Fired Dryer Technology Proprietary work of the Copyright Owner Issues with
HYBRID WAY EAF OFF GAS HEAT RECOVERY -ECORECS- MASANARI YAMAZAKI*1, YASUHIRO SATO*2, RYUTARO SEKI*3
HYBRID WAY EAF OFF GAS HEAT RECOVERY -ECORECS- BY MASANARI YAMAZAKI*1, YASUHIRO SATO*2, RYUTARO SEKI*3 SYNOPSIS JP Steel Plantech Co. has developed Hybrid system for EAF off-gas heat recovery, with EAF
S300 Series Dust Monitors
S301 DustGuard S303 Trend Monitor S304 Emission Monitor S305 Stack Monitor Intrinsically Safe (ATEX) Dust Monitors Split Architecture (Remote)Models Data Logging Software S300 Series Dust Monitors Dust
Increasing Power Plant efficiency for safe wet stack Operation
Increasing Power Plant efficiency for safe wet stack Operation Albert de Kreij Albert de Kreij joined Hadek Protective Systems in 1989. He has been closely involved in a number of projects with the use
Overview of Integrated Coal Gasification Combined-cycle Technology Using Low-rank Coal
19 Overview of Integrated Coal Gasification Combined-cycle Technology Using Low-rank Coal TAKAO HASHIMOTO *1 KOICHI SAKAMOTO *2 YOSHIKI YAMAGUCHI *3 KOJI OURA *4 KENICHI ARIMA *5 TAKESHI SUZUKI *6 Mitsubishi
Making Coal Use Compatible with Measures to Counter Global Warming
Making Use Compatible with Measures to Counter Global Warming The J-POWER Group is one of the biggest coal users in Japan, consuming approximately 2 million tons of coal per year at eight coal-fired power
SRS: THE STANDARDIZED REPOWERING SOLUTION FOR 300MW STEAM POWER PLANTS IN RUSSIA. Matthias Fränkle Siemens Power Generation (PG), Germany
SRS: THE STANDARDIZED REPOWERING SOLUTION FOR 300MW STEAM POWER PLANTS IN RUSSIA Matthias Fränkle Siemens Power Generation (PG), Germany Page 1 of 11 1 Introduction Deregulation and competition are further
CLEAN ENERGY PROJECT ANALYSIS WITH RETSCREEN SOFTWARE
Training Module SPEAKER S NOTES CLEAN ENERGY PROJECT ANALYSIS WITH RETSCREEN SOFTWARE CLEAN ENERGY PROJECT ANALYSIS COURSE This document provides a transcription of the oral presentation (Voice & Slides)
voestalpine Stahl, Linz, Austria Maximized Emission Reduction Of Sintering SIMETAL CIS MEROS plant Metals Technologies
voestalpine Stahl, Linz, Austria Maximized Emission Reduction Of Sintering SIMETAL CIS MEROS plant Metals Technologies 1 Meeting future environmental demands now! The challenge: Requirements placed on
Performance of the Boiler and To Improving the Boiler Efficiency Using Cfd Modeling
IOSR Journal of Mechanical and Civil Engineering (IOSR-JMCE) e-issn: 2278-1684,p-ISSN: 2320-334X, Volume 8, Issue 6 (Sep. - Oct. 2013), PP 25-29 Performance of the Boiler and To Improving the Boiler Efficiency
Improving Energy Efficiency through Biomass Drying
Improving Energy Efficiency through Biomass Drying Gilbert McCoy, Senior Energy Systems Engineer Northwest CHP Technical Assistance Partnership International District Energy Association Woody Biomass CHP
Chapter 3.5: Fans and Blowers
Part I: Objective type questions and answers Chapter 3.5: Fans and Blowers 1. The parameter used by ASME to define fans, blowers and compressors is a) Fan ration b) Specific ratio c) Blade ratio d) Twist
Waste to Energy in Düsseldorf. for a clean city.
Waste to Energy in Düsseldorf for a clean city. Waste Management in Düsseldorf. Düsseldorf s public utilities company known as Stadtwerke Düsseldorf operates a waste to energy plant (WtE) that has been
Heat-Pipe Heat Exchanger
Heat-Pipe Heat Exchanger Heat Pipe Heat Exchanger For air-air 1 Heat Pipe Heat Exchanger Heat exchanger, which transfers the heat from one medium to another, is the most common thermal equipment in various
NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES
NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES 8.1 INTRODUCTION Testing, adjusting, and balancing of HVAC systems can best be accomplished by following a series of systematic procedures. The NEBB TAB
Comparison of selected plasma technologies
Comparison of selected plasma technologies PREPARED BY PLASTEP PARTNER #11 INSTITUTE OF NUCLEAR CHEMISTRY AND TECHNOLOGY Working group Dr. Andrzej Pawelec Mrs. Sylwia Witman-Zając Mrs. Agnieszka Molenda
Sixth Annual Conference on Carbon Capture & Sequestration
Sixth Annual Conference on Carbon Capture & Sequestration Session Title: Retrofitting of Existing Coal-Fired Plants MHI s Post Combustion CO 2 Recovery Process for Coal Fired Power Stations: Requirement
Roadmap Performance Target Best technology Capability
Sulfur Dioxide Control Technologies In Electric Power Plants CCTR Basic Facts File #5 Brian H. Bowen, Marty W. Irwin The Energy Center at Discovery Park Purdue University CCTR, Potter Center, 500 Central
6 CONSIDERATION OF ALTERNATIVES
6 CONSIDERATION OF ALTERNATIVES 6.1.1 Schedule 4 of the Town and Country Planning (Environmental Impact Assessment) (Scotland) Regulations 2011 sets out the information for inclusion in Environmental Statements
F ox W hi t e Paper. Reduce Energy Costs and Enhance Emissions Monitoring Systems
F ox W hi t e Paper Reduce Energy Costs and Enhance Emissions Monitoring Systems A Technical White Paper from Fox Thermal Instruments Rich Cada, VP Sales & Marketing, Fox Thermal Instruments, Inc. 399
EFFICIENT ENERGY SUPPLY (ELECTRICITY AND DISTRICT HEAT) FOR THE CITY OF LINZ
Parallel session Producing more with less: Efficiency in Power Generation EFFICIENT ENERGY SUPPLY (ELECTRICITY AND DISTRICT HEAT) FOR THE CITY OF LINZ Johann Gimmelsberger Linz Strom GmbH EFFICIENT ENERGY
Design and Test Operation Performance of 1,500 C Class Gas Turbine Combined-Cycle Power Plant:
31 Design and Test Operation Performance of 1,500 C Class Gas Turbine Combined-Cycle Power Plant: Construction of Group 1 of the Tokyo Electric Power Company s Kawasaki Thermal Power Station KIYOSHI KAWAKAMI
Automatic Back-Flushing Filter AutoFilt RF9.
Automatic Back-Flushing Filter AutoFilt RF9. AutoFilt RF9 Clearing the Way. The Challenge: In response to the Tier III standard which will come into effect in 2016, the International Maritime Organization
Developments and trends shaping the future for Waste-to- Energy technology suppliers
Developments and trends shaping the future for Waste-to- Energy technology suppliers 21 st October 2015 Copenhagen, Denmark Edmund Fleck ESWET President 2 Contents 1. About ESWET 2. Introduction 3. Modern
Experience with co-combustion of biomass and waste in coal-fired power plants
Experience with co-combustion of biomass and waste in coal-fired power plants Topsøe Catalysis Forum August 2009 Bo Sander, DONG Energy Power, Denmark GENERATION - HCASA DONG Energy Power in Europe Power
Optimization of Water - Cooled Chiller Cooling Tower Combinations
Optimization of Water - Cooled Chiller Cooling Tower Combinations by: James W. Furlong & Frank T. Morrison Baltimore Aircoil Company The warm water leaving the chilled water coils is pumped to the evaporator
Assessment of Solar-Coal Hybrid Electricity Power Generating Systems 13
Journal of Energy and Power Engineering 6 (2012) 12-19 D DAVID PUBLISHING Assessment of Solar-Coal Hybrid Electricity Power Generating Systems Moses Tunde Oladiran 1, Cheddi Kiravu 1 and Ovid Augustus
IAPWS Certified Research Need - ICRN
IAPWS Certified Research Need - ICRN ICRN 23 Dew Point for Flue Gas of Power-Plant Exhaust The IAPWS Working Group Industrial Requirements and Solutions has examined the published work in the area of dew-point
HOW TO SELECT A LOW VOLUME (L.V ) BOILER
HOW TO SELECT A LOW VOLUME (L.V ) BOILER FREQUENTLY ASKED QUESTIONS OR COMMENTS ON BOILERS Dear Potential Customer: Low Volume Operator Exempt boilers have been marketed in Ontario to eliminate the requirement
It s time for H.E.R.O. Energy Saving Strategy for. Tunnel & Shuttle Kilns
Energy Saving Strategy for Tunnel & Shuttle Kilns SANITARY WARE 1 Introduction The application of the Kyoto protocol and the effects of the recent energy crisis, have highlighted just how important it
Optimization Design for Sulfur Dioxide Flow Monitoring Apparatus in Thermal Power Plants Hao-wei Hu 1, a, Xue Yang 1, b and Xiao-wei Song 1, c
International Conference on Information Sciences, Machinery, Materials and Energy (ICISMME 2015) Optimization Design for Sulfur Dioxide Flow Monitoring Apparatus in Thermal Power Plants Hao-wei Hu 1, a,
Experimental Evaluation Of The Frost Formation
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Experimental Evaluation Of The Frost Formation Yusuke Tashiro Mitsubishi
Recover Heat from Boiler Blowdown Water
Prepared for California Energy Commission (CEC) Prepared By: Southern California Gas Company (A Sempra Energy Utility) E3M Inc. May 2012 i Disclaimer The CEC and its contractor, Southern California Gas
Carbon Capture. Investment for the Future
Carbon Capture Investment for the Future Doosan Carbon Capture Technologies Oxyfuel 160KWt at Doosan ERTF* ERTF Oxyfuel Conversion 40MWt OxyCoal TM Burner at Doosan CCTF Full Power Plant Demo Expected
Beware of Exaggerated Claims and Uncertified Manufacturers Ratings Regarding Commercial Boiler Efficiency
Beware of Exaggerated Claims and Uncertified Manufacturers Ratings Regarding Commercial Boiler Efficiency For many years competent professional HVAC engineers have been aware of exaggerated or deceptive
ELECTRICAL ENERGY REDUCTION IN REFRIGERATION AND AIR CONDITIONING Ken Landymore, Director of Operations, Smartcool Systems Inc.
ELECTRICAL ENERGY REDUCTION IN REFRIGERATION AND AIR CONDITIONING Ken Landymore, Director of Operations, Smartcool Systems Inc. 1. INTRODUCTION In the coming decades, actions to limit greenhouse gas emissions
THE PSYCHROMETRIC CHART AND ITS USE
Service Application Manual SAM Chapter 630-16 Section 3A THE PSYCHROMETRIC CHART AND ITS USE Psychrometry is an impressive word which is defined as the measurement of the moisture content of air. In broader
Success Case of Co-firing of Biomass and Coal
Success Case of Co-firing of Biomass and Coal Luca Rigoni Thermal Services Boiler 29/05/2012 Index of Contents Introduction Biomass Fuels Categories Options for Biomass Firing Alstom success case: Fiddlers
Gas-Fired Power HIGHLIGHTS
Gas-Fired Power HIGHLIGHTS PROCESS AND TECHNOLOGY STATUS Approximately 21% of the world s electricity production is based on natural gas. The global gas-fired generation capacity amounts to 1168 GW e (2007).
Iron Powder Cores for Switchmode Power Supply Inductors. by: Jim Cox
HOME APPLICATION NOTES Iron Powder Cores for Switchmode Power Supply Inductors by: Jim Cox Purpose: The purpose of this application note is to cover the properties of iron powder as a magnetic core material
THE THERMAL FLOW METER, A GAS METER FOR ENERGY MEASUREMENT
THE THERMAL FLOW METER, A GAS METER FOR ENERGY MEASUREMENT Kazuto Otakane, Tokyo Gas Co., Ltd Katsuhito Sakai, Tokyo Gas Co., Ltd Minoru Seto, Tokyo Gas Co., Ltd 1. INTRODUCTION Tokyo Gas s new gas meter,
Continuous Emissions Monitoring - Program 77
Program Description Program Overview Coal-fired power plants are in increased need of robust, accurate, and certifiable continuous emissions monitors (CEMs) for mercury, particulate matter (PM), acid gases,
PRE-QUALIFICATION ANNOUNCEMENT
Warsaw March 9, 2011 PRE-QUALIFICATION ANNOUNCEMENT The contracting authority 00-526 Warsaw, ul. Krucza 24/26, Poland Website: www.elektrowniapolnoc.pl Contact person: Mr. Marek Obuchowicz E-mail: [email protected]
SULFUR RECOVERY UNIT. Thermal Oxidizer
SULFUR RECOVERY UNIT Thermal Oxidizer BURNERS FLARES INCINERATORS PARTS & SERVICE SULFUR RECOVERY UNIT Thermal Oxidizer Tail Gas Thermal Oxidizer designed and built to GOST-R requirements. Zeeco can meet
Development of Coal Gasification System for Producing Chemical Synthesis Source Gas
27 Development of Coal Gasification System for Producing Chemical Synthesis Source Gas TAKAO HASHIMOTO *1 KOICHI SAKAMOTO *1 KATSUHIRO OTA *2 TAKASHI IWAHASHI *3 YUUICHIROU KITAGAWA *4 KATSUHIKO YOKOHAMA
Committed to make a better world
Committed to make a better world 1. Higher Availability & Reliability 2. Highest Plant efficiency 3. Lower Heat Rate 4. Minimum Auxiliary Power Consumption 5. Minimum Emission of Pollutants Committed to
Circuit breaker panel. Power supply for condensing unit. Power supply for furnace. Air handler (Furnace)
UNIT OBJECTIVES Describe the concept of year-round air conditioning List three typical year-round air conditioning system types List the five ways to condition the air Determine airflow for a cooling system
Design of heat exchangers
Design of heat exchangers Exchanger Design Methodology The problem of heat exchanger design is complex and multidisciplinary. The major design considerations for a new heat exchanger include: process/design
Site Identification No.: 197809AAO Application No.: 15030051
Project Summary for a Construction Permit Application from Midwest Generation for a Natural Gas Conversion Project for the Joliet Electric Generating Station Joliet, Illinois Site Identification No.: 197809AAO
gasnetworks.ie Methodology for forecasting gas demand
gasnetworks.ie Methodology for forecasting gas demand 1 Contents 1 Introduction 2 1.1 Scope of the report 3 1.2 Use and publication of the forecasts 4 1.3 Structure of the document 5 2 Conceptual background
POLLUTED EMISSION TREATMENTS FROM INCINERATOR GASES
POLLUTED EMISSION TREATMENTS FROM INCINERATOR GASES Ecole Nationale Supérieure de Chimie Avenue du Général Leclerc, Campus de Beaulieu 35700 Rennes, France Tel 33 (0)2 23 23 80 02 Fax 33 (0)2 23 23 81
OPPORTUNITIES FOR HEAT RATE REDUCTIONS IN EXISTING COAL- FIRED POWER PLANTS: A STRATEGY TO REDUCE CARBON CAPTURE COSTS
CONFERENCE PROCEEDINGS OPPORTUNITIES FOR HEAT RATE REDUCTIONS IN EXISTING COAL- FIRED POWER PLANTS: A STRATEGY TO REDUCE CARBON CAPTURE COSTS by Edward K. Levy, Nenad Sarunac, and Carlos Romero Energy
Boiler Calculations. Helsinki University of Technology Department of Mechanical Engineering. Sebastian Teir, Antto Kulla
Helsinki University of Technology Department of Mechanical Engineering Energy Engineering and Environmental Protection Publications Steam Boiler Technology ebook Espoo 2002 Boiler Calculations Sebastian
PROCESS PARTICLE COUNTER (PPC) SENSOR/CONTROLLER FOR OPTIMIZING POWER RECOVERY EXPANDER AND GAS TURBINE PERFORMANCE
PROCESS PARTICLE COUNTER (PPC) SENSOR/CONTROLLER FOR OPTIMIZING POWER RECOVERY EXPANDER AND GAS TURBINE PERFORMANCE APPLICATIONS NOTE FOR MEASUREMENTS AT THE ENTRANCE AND EXIT OF A THIRD STAGE SEPARATOR
BOILER TUNE-UP GUIDE FOR NATURAL GAS AND LIGHT FUEL OIL OPERATION GREG HARRELL, PH.D., P.E.
ENERGY MANAGEMENT SERVICES Greg Harrell, Ph.D., P.E. 341 Willocks Drive Jefferson City, Tennessee 37760 Telephone: (865) 719-0173 Email: [email protected] BOILER TUNE-UP GUIDE FOR NATURAL GAS AND
BOILER OPERATORS HANDBOOK
BOILER OPERATORS HANDBOOK prepared by National Industrial Fuel Efficiency Service Ltd. Graham & Trotman First published in 1959 as the New Stoker's Manual and in 1969 as The Boiler Operators Handbook This
The soot and scale problems
Dr. Albrecht Kaupp Page 1 The soot and scale problems Issue Soot and scale do not only increase energy consumption but are as well a major cause of tube failure. Learning Objectives Understanding the implications
Experimental study on atmospheric pollutant emissions from heating systems, in Italy
Experimental study on atmospheric pollutant emissions from heating systems, in Italy Promoted by the Italian Ministry for the Environment, in coperation with : The Lombardy Region, the Piedmont Region,