CONSTRUCTIBILITY REVIEWS: CASE STUDY OF BID DOCUMENT ERRORS AND OMISSIONS
|
|
|
- Elisabeth Goodwin
- 10 years ago
- Views:
Transcription
1 BY: KEN PRUETT, PROJECT MANAGER, PINNACLEONE The specific objective of a Constructibility Review should be to minimize or eliminate potential change orders and delay claims during construction by ensuring that the Construction Documents are fully coordinated, complete, and buildable. While accomplishing that primary objective, a constructibility review should also seek to eliminate the redundancy in quality control reviews being performed by different entities involved in the project such as architects, peer reviewers, and permitting agencies. Formal constructibility review programs have been conducted on enormous public works programs such as the Los Angeles County USC Medical Center and the Los Angeles Unified School District s school bond program as well as many other programs across the nation. For a large public works program with construction cost of over $500 million, a 2 to 5% reduction in construction costs through a comprehensive constructibility review can result in millions of dollars in savings for what are relatively minor costs associated with conducting the reviews. Any project whether small or large stands to benefit by a properly conducted constructibility review by reducing the occurrence and extent of change orders, claims, schedule delays, or simply by preserving a better relationship between owner, construction manager, contractor, and architect. This article describes some particular recurring construction document errors and omissions or trends that were encountered on projects that instituted a formal review process. The Los Angeles Unified School District (LAUSD) embarked on a program in 2000 to construct over 150 new schools with a combined hard construction cost of $1.5 billion through a voter-approved bond proposition. The program was completing its design phase and transitioning into the plan check/permit phase. The District recognized the need to conduct constructibility reviews at the conclusion of the design phase mitigate contract change exposure. The Contract Documents were being produced with subjective and arbitrary notes such as The Architect assumes no responsibility for the completeness of the plans for bid purposes Provide trap and vent as required. Provide condensate pumps if necessary Contractor to provide fire and smoke dampers as needed at all rated wall penetrations If phased construction is required by the District, the District will allow a 30-day time extension for the contract Copyright 2004 by the Construction Management Association of America page 1
2 A unique constructibility Program was adopted by the LAUSD to address the potential contract change order exposure. Constructibility management tools were developed and utilized on the LAUSD program including comprehensive constructibility checklists, dedicated in-house review teams, constructibility audits as construction was on-going or complete, and a detailed scope of work for all review participants. A constructibility team was mobilized and over the span of a year was successful in reviewing all of the design packages prior to submission to the permitting agency. The team discovered literally thousands of errors, omissions, conflicts and ambiguities in the contract documents which were noted and, as verified by a back-check system, incorporated into the contract documents. It is estimated that the as a result of catching the problems prior to contracting, that the District received at least a 10 to 1 pay back on the cost of the constructibility review team. This paper discusses some of the lessons learned from that program and makes several recommendations that can easily be adopted to future public works construction programs. Constructibility Defined Again, the specific objective of a constructibility review program is to minimize the occurrence and scope of potential change orders and schedule delays during construction by ensuring that ALL the construction documents are fully coordinated, complete, and buildable. When saying ALL Construction Documents, it is indicating that the scope of the review cannot be limited to a review of the Contract Documents provided by the architect. Traditionally, owners provide integral portions of the Contract Documents such as survey, as-built, geotechnical, hazardous material, environmental, and other preconstruction documentation. Often times constructibility reviews are conducted on behalf of an owner and erroneously exclude the owner-furnished bid package elements. All elements that make up the contract documents need to be concurrently reviewed - drawings, as-built conditions, specifications, geotechnical reports, environmental documents, site topographic and utility surveys, etc. We use the term buildable to help define and limit the scope of the constructibility review to a review of those elements which make a design buildable. This is important in order to eliminate the document review redundancies that can occur. In the case of the LAUSD projects, the jurisdictional review agency, Division of the State Architect, looks for code-related errors and omissions in the construction documents and would often outsource the reviews to design engineering firms. Or an owner may conduct independent peer reviews by engineering or architectural firms to validate design and engineering assumptions. We were careful to focus our efforts not on the code or engineering aspects of the documents, but the portions of the documents that really make it buildable for a contractors and subcontractors. Typical questions while conducting the review include: Are there a sufficient number of wall sections/elevations, Are there a sufficient number of details, Copyright 2004 by the Construction Management Association of America page 2
3 Is sufficient information provided in the sections/elevations/ details, Are the plans, sections, elevations, and details coordinated between architectural, structural, civil/site, and MEP drawings? These questions are indicative of the type of questions that should be asked and answered when validating whether documents are buildable. Constructibility Review Methodology The methodology or approach to conducting a constructibility review should be consistent with the goals of the review. As stated above, the focus should be to concurrently review all documents and focus on their buildability. The right personnel and tools are necessary to effectively execute the review. The approach adopted for the LAUSD program was to establish multi-disciplinary review teams with constructionexperienced personnel, create and provide the reviewers with comprehensive constructibility management tools, conduct constructibility audits on projects under construction or completed to ascertain and prevent recurring bid document errors, and conduct site visits to verify site topographic, utility, easement, surrounding public utility, and other existing conditions. Multi-Disciplinary Reviews: The success of a constructibility review lies in the quality of the personnel assigned to participate in the constructibility review. Individuals with direct construction field experience should be selected to perform constructibility reviews. The initial Program, Design, and Peer reviews are typically done by architects and engineers and are viewed from a designer s perspective while the constructibility review team views the documents through a builder perspecitve. Wouldn t it be great to get the grouchy old field superintendent who declares on every project this is the worst set of drawings I ve ever seen!, to review and comment on the documents during the design phase? It may be difficult to corral that individual from the field and have them sit down in an office to conduct a constructibility review but those types of people who have to deal with the end result of bid document errors and omissions and lack of coordination are perfect candidates for review team members. Constructibility Management Tools: The review team needs to have management tools that act as a guide to finding missing or uncoordinated contract document information, including a detailed constructibility scope of work. The LAUSD program was unique because of the large number of projects that were under construction or in design at any one time. It afforded us the opportunity to examine where previous bid document errors and omissions occurred and then apply that knowledge to the review of projects that were currently in design. We were able to continually build upon a lesson learned database of specific problem areas. The detailed constructibility scope of work defined areas to be reviewed in the documents and assigned multidisciplinary team members responsible for there completion. In practice, each reviewer was responsible for catching comments such as see structural or provided by others and then verifying that the design does in fact address the comment in the structural documents or that some other discipline, owner-furnished product, or utility agency is the by others. Copyright 2004 by the Construction Management Association of America page 3
4 Constructibility Audits: The purpose of a constructibility audit is to identify typical or frequently repeating errors or omissions that have resulted in changes orders on completed or under construction projects. The audit should be the genesis of any lessons learned database which is ultimately used to prevent design mistakes from continuing to occur on future projects. At LAUSD it became apparent after conducting only a limited number of constructibility audits that there were obvious trends in the errors and omissions in the contract documents. Lack of information about existing site conditions, coordination of MEP systems within the useable plenum space, and weaknesses between the coordination of civil, utility and site plumbing information were some of the trends revealed. These lessons learned were added to the constructibility checklists established at the beginning of the constructibility program. Interviews with site personnel superintendents, inspectors, and contractors also helped to formulate the lessons learned database. All this information was fed back to the reviewers conducting the constructibility reviews so that there was a continual improvement in the quality and thoroughness of the reviews. Site Visits: Site visits are an integral part of the review whether it is a remodel, addition, or new construction. Many projects start off wrong simply because no one has checked the site information which is customarily derived early in the project phase and by the owner. The individual on the review team that is reviewing the civil portion of the bid documents is likely the most appropriate person to visit the site on a new construction project. For the LAUSD program, the civil reviewer visited the site with topographic and utility survey and all site plan (architectural, plumbing, electrical) information in hand. The civil reviewer would verify that the conditions existing on site were as depicted on the documents. The architectural, structural, MEP, and civil reviewers all may need to visit the site as a part of their reviews for additions projects. The site visit ended up being one of the most revealing and beneficial aspects of the LAUSD constructibility review program. Constructibility Review Results (Lessons Learned) Performance Type of Drawings/Specifications: Most of the designs relied on performance type of drawings and specifications to represent certain systems. Precast panels and precast support systems, fire sprinkler systems, and shoring systems were examples of where a designer may specify these systems in a performance manner and place the design-build responsibility on the contractor. Although this seems to be standard practice within the design industry, gaps in the scope of work occur if they are not properly specified. For instance, if no fire sprinkler systems drawings are included or at best a schematic of a fire sprinkler riser line is provided, then it is likely that the bid documents fail to address the installation of power or signal to the fire sprinkler flow switches since the switched would not be shown on the drawings. Coordination with Geotechnical Recommendations: Blanket statements about compliance with recommendations made in the referenced geotechnical reports in the structural general notes where often found to be in conflict with the information provided in the earthwork specifications or structural drawings. The geotechnical reports would often address several options or flatly made no reference to conditions Copyright 2004 by the Construction Management Association of America page 4
5 shown on the drawings (i.e. allowable shoring systems). The result was a potential conflict between the geotechnical, earthwork, or structural systems which were unclear at the time of bid or were subjective and left the least expensive, and often less desirable, option to the contractor. Subjective Notes: If you want to get an earful, ask that grouchy old field superintendent how he feels about drawings riddled with subjective phrases such as in an approved manner or as needed. Field supervisors and inspectors struggle with the final acceptance of components shown to be installed in an approved manner. Referencing specific WIC or other industry standards can often mitigate disputes that arise from these subjective comments. Unaddressed Site Conditions: Again, maybe the most important part of the constructibility review. Site conditions can change dramatically from the time a project owner conducts a site survey or an architect initially visits the site to the time of bid. The documents reviewed on the LAUSD program consistently did a very poor job of illustrating the complete picture on site. Projects that involved additions or modifications to existing facilities suffer in particular from unaddressed site conditions. Close attention needs to be paid to new construction integrating with existing construction. If new raceways are shown indicated intruding into existing areas, hazardous material mitigation, plenum space conflicts, or available panelboard space for new circuits need to be addressed. Numerous times when new electrical or systems panelboards were to be added to existing electrical, mechanical, or LAN rooms, the rooms lacked the physical space to install the new panels. This portion of the review can not be stressed enough. Other Issues: Other common errors and omissions consistently discovered in the audits or the reviews were failure to provide enough useable plenum space. Project budget concerns resulted in reduced floor to floor heights while at the same time aesthetic design considerations increase ceiling heights. These two factors limit plenum space with the inevitable impact to ductwork, cable trays, and ceiling-mounted equipment. Horizontal control (civil) information needs to provide benchmarks and centerlines and have sufficient dimensional information to locate all major building and site features outside of easements and right-of-ways. Site plans also need to consider adequate offsets to adjacent properties to prevent undermining of neighboring properties. Electrical documents need to consider all miscellaneous power requirements carbon monoxide sensors, high water level alarms, irrigation controllers, automatic overhead doors, and miscellaneous mechanical equipment. Owner-furnished kitchen or medical equipment needs to clearly define where the owner s furnishing scope stops and the contractor s installation scope begins. Summary The constructibility review should never target only the bid documents provided by the designer. Although the bulk of the documents bid will be produced by the architect/engineer, the effect of owner-furnished, utility agency, or environmental documentation needs to be concurrently reviewed. Copyright 2004 by the Construction Management Association of America page 5
6 The most qualified constructibility reviewers are those individuals that have dealt with the by-product of bid document errors and omissions in the field. Superintendents, inspectors, or managers who have been involved in resolving unclear construction conditions or settling change orders and claims have an excellent background that can be applied in the up front constructibility reviews. Their knowledge combined with some form of a constructibility checklist that is derived from audits of previous projects and changes are necessary for a comprehensive and successful constructibility review. The checking or backchecking for incorporation of the constructibility comments by the designer has not been mentioned but is a natural activity to follow the constructibility review. Several meetings with the architect/engineer subsequent to the review may be necessary to resolve all of the comments. Consensus on whether to incorporate or not apply each constructibility comment should be reached by the project team. The timing of the review needs to be considered as well. A review should occur when enough detailed information is available to conduct a constructibility review. The 50% construction document stage and after the submittal of the 100% construction documents to the jurisdictional review agency are good milestone dates to conduct reviews. Not as much information is available at the 50% construction document stage so the review should be pared to match the level of information provided. The constructibility review, when conducted properly and focused on those issues that affect buildability, will pay for itself. It can be difficult to quantify in dollars what the review has saved an owner since the stage of construction that the error is discovered has the biggest impact on its cost. However, you need only uncover a few of the major and recurring issues listed above to realize its value. Copyright 2004 by the Construction Management Association of America page 6
ELECTRICAL CONTRACTORS THE UNIVERSITY OF TENNESSEE KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1
KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1 PART 1 - GENERAL 1.01 RELATED DOCUMENTS: SECTION 16050 A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1
LOUISIANA DEPARTMENT OF TRANSPORTATION AND DEVELOPMENT CONSTRUCTION PLANS QUALITY CONTROL / QUALITY ASSURANCE MANUAL
LOUISIANA DEPARTMENT OF TRANSPORTATION AND DEVELOPMENT CONSTRUCTION PLANS QUALITY CONTROL / QUALITY ASSURANCE MANUAL August 2008 TABLE OF CONTENTS Section 1 - Introduction... 3 1.1 Defining Plan Quality...
OPEN ITEMS LIST - CONSTRUCTION Project Name: East Central Middle School - Jackson County CLA#: 11003
OPEN ITEMS LIST - CONSTRUCTION Project Name: East Central Middle School - Jackson County CLA#: 11003 No. Discipline Sent to Name Item Date Noted Date Resolved How item was resolved Electrical Contractor
Exhibit C: Scope of Work and Schedule of Deliverables
Exhibit C: Scope of Work and Schedule of Deliverables Project Scope of Work Phases: A City Hall Envelope Renovations B City Hall Skylight Replacement C City Hall Chiller Replacement D City Hall Annex Plaza
Assistant Project Management - Training Program A 3-year Program Beginning strategy places the new employee into a three-year program that provides
Assistant Project Management - Training Program A 3-year Program Beginning strategy places the new employee into a three-year program that provides for experience in the Construction Company's three areas
Document Comparison. AIA Documents A134 2009 and A131CMc 2003
Document Comparison AIA Documents A134 2009 and A131CMc 2003 AIA Document A134 2009 is in the right-hand column. Corresponding sections of AIA Document A131 CMc 2003 are in the left-hand column. Sections
ISSUE BRIEF. Understanding the Hospital Planning, Design, and Construction Process. Introduction. Background. Phase 1: Project Definition and Planning
Understanding the Hospital Planning, Design, and Construction Process Introduction California s acute care hospitals are an essential health care resource that serve a wide range of patients during times
Electrical. This section applies to the design and installation of building power distribution systems.
Basis of Design This section applies to the design and installation of building power distribution systems. Design Criteria This section contains the architectural, structural and mechanical provisions
Design Development Quality Management Phase Checklist Project Phase Checklist Series
Best Practices Design Checklist Project Phase Checklist Series Contributed by Micheal J. Lough, AIA, Principal, Integral Consulting The AIA collects and disseminates Best Practices as a service to AIA
2012 BIM Guidelines and Standards (Rev. 00) University at Albany
A. Building Information Modeling (BIM) Guidelines: The Office of AECM will require the submission of BIM modeling files as part of an electronic file submission to the AECM project manager as requested
Fire Alarm Systems Certification
Fire Alarm Systems Certification The skills and knowledge listed under each task are suggestive of those involved in that task, but are not intended to constitute an exhaustive listing. 2.1 Submittal Preparation
EXHIBIT "A" RESPONSIBILITIES AND SERVICES OF ARCHITECT TABLE OF CONTENTS
EXHIBIT "A" RESPONSIBILITIES AND SERVICES OF ARCHITECT TABLE OF CONTENTS A. SCOPE OF PROJECT... 1 B. BASIC SERVICES... 1 C. PRE-DESIGN AND START-UP SERVICES... 4 D. SCHEMATIC DESIGN PHASE... 7 E. DESIGN
City of La Vernia 102 E. Chihuahua Street, La Vernia, Texas 78121 Phone: (830)779-4541 Fax: (830) 253-1198 cityoflavernia@lavernia-tx.
[email protected] Commercial New/Remodel Building Requirements This document is not meant to modify any Federal or State laws or City Ordinances. It is intended to be informative and to be
Notes. Score. 1 Basic Services 1.1. A few instances; could have been more proactive
Jacobs Contract performance Tracking spreadsheet = Excellent 2 = Meets performance standards 1 = Improvement needed 0= Unsatisfactory Report for the time period: Annual report 210 Total average score 2.86
School Construction Projects
The process of educating young people seems to be continually developing. New insights regarding how students most effectively receive retain and gain understanding of information and principles affect
Marketing Subcontractor Services
Marketing Subcontractor Services Part I Winning That Big Contract is More Than Just Low Bid Today By Greg Hoyle, Consultant Fails Management Institute Often subcontractors come to our consultants and say,
TRANSFERRING RISKS IN CONSTRUCTION CONTRACTS
TRANSFERRING RISKS IN CONSTRUCTION CONTRACTS Bryan S. Shapiro, QC I. INTRODUCTION Risk and conflict are inherent characteristics of the construction industry. Conflict usually results from the allocation
SECTION 17400 ACCESS CONTROL SYSTEM. CONDITIONS OF THE CONTRACT AND DIVISION 1, as applicable, apply to this Section.
SECTION 17400 ACCESS CONTROL SYSTEM CONDITIONS OF THE CONTRACT AND DIVISION 1, as applicable, apply to this Section. PART 1 - GENERAL 1.1 RELATED WORK A. 16060 Grounding and Bonding B. 16070 Electrical
Project Implementation Guide for CT, PET/CT, X-Ray, and Nuclear Systems
GE Healthcare Project Implementation Guide for CT, PET/CT, X-Ray, and Nuclear Systems Working together to get your new technology online so you can begin providing patient care. Table of Contents Table
Revised Work Scope Dated April 23 rd, 2015
Revised Work Scope Dated April 23 rd, 2015 2.4 SCOPE OF SERVICES The following combines the Scope of Services included in RFQ No. 671 dated March 12, 2015 and the Invitation to Interview letter dated March
Schematic Design: Quality Management Phase Checklist Project Phase Checklist Series
Best Practices : Project Phase Series Contributed by Micheal J. Lough, AIA, Principal, Integral Consulting The AIA collects and disseminates Best Practices as a service to AIA members without endorsement
REQUEST FOR PROPOSALS (RFP) - Construction Management Services. Germantown School District Office
REQUEST FOR PROPOSALS (RFP) - Construction Management Services From: Germantown School District Project: Germantown School District Addition & Renovations to Rockfield Elementary School N132 W18473 Rockfield
Corrected Form: Revised Attachment 7B Cost Proposal Distribution Exhibits A1 and A2 Attached
ADDENDUM #1 RFP: 500 16 Design Build Maintenance & Operations Complex The following changes to the Request for Proposal and clarifications are provided based on questions received and must be added/considered
All substantial design decisions and budget confirmation shall be resolved for the College to approve the Design Development Submittal.
2.02 DESIGN DEVELOPMENT PHASE GENERAL The Architect shall prepare the Design Development Documents from the approved Schematic Design. The Design Development Documents shall consist of drawings and other
The use of BIM in plumbing projects creates deeper project knowledge, delivers a more robust product, and can reduce total project costs.
BIM for plumbing design The use of BIM in plumbing projects creates deeper project knowledge, delivers a more robust product, and can reduce total project costs. BY JUNCHENG (JAMES) YANG, PE, CPD, LEED
2301.1 Scope: Communications and Electronic Systems addressed in this section include:
Chapter 23 COMMUNICATIONS / ELECTRONIC SYSTEMS SECTION 2301 - GENERAL 2301.1 Scope: Communications and Electronic Systems addressed in this section include: 1. Fire Alarm System 2. Telecommunication and
Energy Design Resources Commissioning Plan Outline Template
IMPORTANT NOTICE: This sample document is provided for instructional purposes only. CCC is not rendering advice concerning any commission project or practices. This document is neither approved nor intended
Request for Qualifications 2015-162
Kitsap County Human Services Department Request for Qualifications 2015-162 Architectural and Project Management Services - Kitsap County Work Release Facility Remodel Response Deadline: November 17, 2015
REQUEST FOR QUALIFICATIONS ARCHITECTURAL DESIGN SERVICES FOR A FIRE STATION
Architectural Design Services RFQ October 30, 2015 Shoreline Fire Station & Headquarters Modifications REQUEST FOR QUALIFICATIONS ARCHITECTURAL DESIGN SERVICES FOR A FIRE STATION A. Purpose of Request:
DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS
DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS NOTICE TO BIDDERS BID FORM INSTRUCTIONS TO BIDDERS CONTRACTOR S BID FOR PUBLIC WORK - FORM 96 MINORITY AND WOMEN S BUSINESS ENTERPRISE PARTICIPATION
Fire Alarm System Plans Submittal Guidelines For New and Existing Systems
Fire Alarm System Plans Submittal Guidelines For New and Existing Systems SCOPE The Temecula Fire Prevention Bureau (TFPB) has established the following requirements for the submittal of all fire alarms,
A Guide to Renovation and Repair Contract Warranties
A Guide to Renovation and Repair Contract Warranties By Gerald A. Dalrymple, PE A fter being retained to review the merits of several major disputes involving the scope of warranties in renovation and
Checklist 26: How Owners Can Avoid Litigation on Construction Projects
Checklist 26: How Owners Can Avoid Litigation on Construction Projects While it is impossible to completely avoid litigation on construction projects, certain steps can be taken to minimize the potential
Sample Company SECTION 019113 GENERAL COMMISSIONING REQUIREMENTS PART 1 GENERAL 1.1 SUMMARY AND CONTRACT RESPONSIBILITIES
SECTION 019113 GENERAL COMMISSIONING REQUIREMENTS PART 1 GENERAL 1.1 SUMMARY AND CONTRACT RESPONSIBILITIES A. The Owner will contract separately and directly for the majority of the commissioning work
REQUEST FOR QUALIFICATIONS RFQ NO. 001-09
REQUEST FOR QUALIFICATIONS RFQ NO. 001-09 COAST COMMUNITY COLLEGE DISTRICT Facilities & Planning Department 1370 Adams Avenue, Costa Mesa, CA 92626 Telephone (714) 438-4673 Fax (714) 438-4893 The is inviting
Request for Proposal East Tower Nursing Unit and Infrastructure Upgrade Grossmont Hospital
Request for Proposal East Tower Nursing Unit and Infrastructure Upgrade Grossmont Hospital June 21, 2007 The Grossmont Healthcare District (GHD) will accept proposals for Architectural and Engineering
HERNANDO COUNTY FIRE ALARM GUIDELINES
HERNANDO COUNTY FIRE ALARM GUIDELINES To be used for all commercial building fire alarm system plan review. The procedures set forth in this document are the minimum requirements necessary to ensure a
NECESSITY OF SCHOOL CONSTRUCTION STAGE III DESIGN REVIEWS
NECESSITY OF SCHOOL CONSTRUCTION STAGE III DESIGN REVIEWS Rhode Island Department of Education School Building Authority 255 Westminster Street, Providence, RI 02909 Telephone (401)222-4600 Website: www.ride.ri.gov
FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January, 2011
Office of the Fire Marshal 1.0 PERMITS FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January, 2011 1.1 To acquire an installation
The Pennsylvania State University ------------- Physical Security Office. Intrusion Alarm. Performance Specification
The Pennsylvania State University ------------- Physical Security Office Intrusion Alarm Performance Specification By PHYSICAL SECURITY OFFICE Group (Access Controls & Electronic Security Programs) and
MTA UNIVERSAL STATION PEDESTRIAN BRIDGE Los Angeles, CA. Project Manual and Specification 100% PE SUBMITTAL TABLE OF CONTENTS
Los Angeles, CA Project Manual and Specification DIVISION 1 GENERAL CONDITIONS 01 01 10 STATEMENT OF WORK 01 11 00 SUMMARY OF THE WORK 01 14 05 METRO (OWNER) - DIRECTED STOPPAGES 01 20 00 PRICE AND PAYMENT
TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST
TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST In order to provide a comprehensive plan review in a timely manner, and to insure the design and installation of fire alarm systems
Document B105 TM. Standard Form of Agreement Between Owner and Architect for a Residential or Small Commercial Project
Document B105 TM 2007 Standard Form of Agreement Between Owner and Architect for a Residential or Small Commercial Project AGREEMENT made as of the day of in the year (In words, indicate day, month and
Checklist top portion completed and *Note* initialed. Owner s Authorization signed by both owner and agent
FOR OFFICE USE ONLY: File No. Associated concurrent applications: Pre-application review checklist for tenant improvements/additions/change of use/change of major occupancy/reconstruction/renovations/repair
Solar Panel Installations
Solar Panel Installations Page 1 of 6 SINGLE-FAMILY RESIDENTIAL CHECKLIST City of Hayward Development Services Department Revised: 7-09-15 PERMIT REQUIREMENTS Permits are required for all solar panel installations.
Building Permit Application
Building Permit Application Administrative Use Only PARENT PERMIT NUMBER (Required if part of another project) PERMITTEE: PERMITTEE ADDRESS: E-MAIL ADDRESS: ARCHITECT/ENGINEER: PHONE: PHONE: ARCHITECT/ENGINEER
How To Get Construction Procurement Services
Construction Procurement William C. Charvat, AIA, CSI Excerpt from The Architect s Handbook of Professional Practice, 13th edition 2000 The procurement of construction services brings together the team
City of Columbus Department of Building and Zoning Services
City of Columbus Department of Building and Zoning Services Introduction This manual is designed to provide you, the contractor, owner or design professional with a step-by-step guide to our process, beginning
REQUEST FOR PROPOSAL MECHANICAL, ELECTRICAL, PLUMBING ENGINEERING SERVICES VARIOUS BUILDING RENOVATIONS AND NEW CONSTRUCTION
REQUEST FOR PROPOSAL For MECHANICAL, ELECTRICAL, PLUMBING ENGINEERING SERVICES For VARIOUS BUILDING RENOVATIONS AND NEW CONSTRUCTION CITY OF ROCHESTER November 2009 TABLE OF CONTENTS GENERAL INFORMATION
Water Damage During Construction
Allianz Global Corporate & Specialty Americas Water Damage During Construction May 2012 A Contractor s Loss Prevention Guide Water damage losses are a major cause of loss during construction and represent
Finance and Administration Department 907 Billy Mitchell Blvd. P: (210) 228-1022 Fire Alarm Permit Application
PERMIT FEE: $ Finance and Administration Department 907 Billy Mitchell Blvd. P: (210) 228-1022 Fire Alarm Permit Application PAYMENT TYPE: Check Credit Card Charge to Job #: (Please complete all of the
SAMPLE. CONTRACT FOR PROFESSIONAL SERVICES: Lump Sum by Phase. Federal Identification (I.D.) Number
Lump Sum A/E R 12/16/13 STATE OF MICHIGAN DEPARTMENT OF TECHNOLOGY, MANAGEMENT AND BUDGET This contract authorizes the professional services contractor to provide professional services. (Authority: 1984
Form C: Application for Construction Insurance
Form C: Application for Construction Insurance Broker Information: Broker: BFL CANADA Insurance Services Inc. Contact: Address: 200, 1177 West Hastings Street, Vancouver, BC, V6E 2K3 Phone Number: 604-669-9600
This request for qualifications seeks the following type of service providers:
ANNOUNCEMENT REQUEST FOR STATEMENT OF QUALIFICATIONS NOTICE SAN FRANCISCO UNIFIED SCHOOL DISTRICT FACILITIES DESIGN AND CONSTRUCTION ARCHITECTURAL SERVICES The San Francisco Unified School District Facilities,
Commissioning of Fire Protection and Life Safety Systems. Presented by: Charles Kilfoil Bechtel National Waste Treatment Plant Richland WA
Commissioning of Fire Protection and Life Safety Systems Presented by: Charles Kilfoil Bechtel National Waste Treatment Plant Richland WA Fire Protection Engineering s role in sustainability through Commissioning
SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM
SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM ENGINEERING SPECIFICATION INTELLIGENT REPORTING FIRE DETECTION SYSTEM PART 1 GENERAL 1.1 DESCRIPTION A. This specification includes the furnishing,
MISCELLANEOUS ELECTRICAL JOBS REQUIRING PERMITS
MISCELLANEOUS ELECTRICAL JOBS REQUIRING PERMITS 01. SAFETY INSPECTION of service equipment at FPL Power Source 02. Construction GFI power outlets (Temp Pole for Construction) 03. 90 day temporary power
Original Document 10/16/07 Revised 01/30/09 2 nd Revision 01-23-12 3 rd Revision- 12/18/14
North Collier Fire Control & Rescue District Greater Naples Fire Rescue District Immokalee Fire Control & Rescue District 2800 North Horseshoe Drive Naples, Florida 34104 SYSTEM REHABILITATION PLAN CHECKLIST
Construction Practice Group
Advising and counseling our clients through every phase of even the most complex construction matters is what differentiates the lawyers in Gould & Ratner s construction practice. As a group, they possess
Flood Risk Considerations
CHECKLIST FOR MITIGATING OR AVOIDING FLOOD DAMAGE It may not seem the case, but individuals are not powerless in influencing their potential exposure to catastrophes, such as floods. Property owners have
ST. MONICA FOOD PANTRY HOUSTON, TEXAS
PROJECT MANUAL FOR ST. MONICA FOOD PANTRY HOUSTON, TEXAS OWNER: ST. MONICA CATHOLIC CHURCH 8421 W. MONTGOMERY ROAD HOUSTON, TEXAS 77088 ARCHITECT: C SIX ARCHITECTURE, LLC 4606 F.M. 1960 WEST, STE 400 HOUSTON,
SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS
SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS I. APPLICATION AND DEFINITIONS 1.01 Authorization for Standards 1.02 Application of Standards 1.03 Definitions
Request for Qualifications & Proposal. Architectural Team. Lake County School District R-1. On-Call Services. For
Request for Qualifications & Proposal Architectural Team For Lake County School District R-1 On-Call Services Provided by: Submittal Deadline: April 23, 2015 Time: 5:00 PM 1.0 Introduction On behalf of
Construction Management Services Delmar School District RFP No. DSD16001-CONSTR_MAN
Construction Management Services Delmar School District RFP No. DSD16001-CONSTR_MAN The Delmar School District (DSD) is seeking the professional services of a Construction Management (CM) firm for the
PROJECT REQUIREMENT, PR 20 VIRTUAL DESIGN & CONSTRUCTION (VDC), BUILDING INFORMATION MODEL (BIM)
PROJECT REQUIREMENT, PR 20 VIRTUAL DESIGN & CONSTRUCTION (VDC), BUILDING INFORMATION MODEL (BIM) A. GENERAL: 1. Summary: Design/Builder will employ VDC and BIM tools to facilitate the construction, coordination,
SECTION 28 05 00 COMMON WORK RESULTS FOR ELECTRONIC SAFETY AND SECURITY
SECTION 28 05 00 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specifications Sections, apply
A Guide to Hiring a Custom Home Builder
A Guide to Hiring a Custom Home Builder A Guide to Hiring a Custom Home Builder Copyright 2013 Published by Christian Gladu Design 2721 NW Nordic Avenue Bend, OR 97701 All rights reserved. Except as permitted
Element D Services Plumbing
Medical Vacuum and Gas PART 1 - GENERAL 1.01 OVERVIEW A. This section addresses medical vacuum, waste anesthetic gas disposal, compressed air, oxygen, nitrous oxide, nitrogen and carbon dioxide systems.
REQUEST FOR PROPOSAL CONSTRUCTION MANAGEMENT SERVICES
REQUEST FOR PROPOSAL CONSTRUCTION MANAGEMENT SERVICES Big Rapids Public Schools Building Program 2005 OWNER Big Rapids Public Schools 21034 15-Mile Road Big Rapids, Michigan 49307 PHONE: (231) 796-2627
Water Leak 1: Intrusion Policy
Water Leak 1: Intrusion Policy {Non-Casualty) 1. Determine Source of Leak Roof Leak- 11 See roof leak" Pressured Pipe leak- 11 See pressured pipe leak" Water Intrusion- See 11 see Water Intrusion leak"
TLHAMATSI AFRICA PROJECTS CONSTRUCTION MANAGEMENT PRESENTATION. PRESENTED BY: BAKANG MOENG [email protected]
TLHAMATSI AFRICA PROJECTS CONSTRUCTION MANAGEMENT PRESENTATION PRESENTED BY: BAKANG MOENG [email protected] CONSTRUCTION MANAGEMENT - DEFINED Act of managing the construction process Contractual arrangement
GUIDELINES FOR AUGUST 1995
GUIDELINES FOR ELECTRICAL ENGINEERING SERVICES AUGUST 1995 PUBLISHED BY: PROFESSIONAL ENGINEERS AND GEOSCIENTISTS OF NEWFOUNDLAND & LABRADOR (PEGNL) P.O. Box 21207, St. John's, NL A1A 5B2 Telephone: (709)
Invitation to Bid FIRE ALARM & DETECTION SYSTEM
Invitation to Bid FIRE ALARM & DETECTION SYSTEM Responses to an Invitation to Bid will be received by the Purchasing Supervisor, Sumner County Board of Education, 1500 Airport Road, Gallatin, TN 37066
Aurora Mall. Aurora (Denver), Colorado
is the largest superregional mall in the city of Aurora, and it s only getting bigger and better. The mall is currently undergoing a significant interior and exterior renovation, scheduled for completion
SAN FRANCISCO UNIFIED SCHOOL DISTRICT 2011 PROPOSITION A BOND PROGRAM Paul Revere School Modernization and Interim Housing ADDENDUM NO.
SAN FRANCISCO UNIFIED SCHOOL DISTRICT 2011 PROPOSITION A BOND PROGRAM Paul Revere School Modernization and Interim Housing ADDENDUM NO. 1 PROJECT: Paul Revere School DATE: March 25, 2015 Modernization
EXAM GUIDE. Construction Documents & Services
RE EXAM GUIDE Construction Documents & 2 Knowledge / 3 5 Choice Answers 15 16 Sample Passing Solution 18 Sample Failing Solution 19 20 Copyright 2015 This document, effective August 2015, supersedes all
You & Your Architect A GUIDE FOR A SUCCESSFUL PARTNERSHIP.
A GUIDE FOR A SUCCESSFUL PARTNERSHIP. YOU AND YOUR ARCHITECT Architecture isn t only for museums, corporations, and the very wealthy. Whether you are remodeling a kitchen, creating your dream home, or
Mechanical Contractor Pre-Qualification Packet. SPSC N180 Computer Data Room Phase II. Project No. CP 159313. Notice No. Notice 13-11.
Mechanical Contractor Pre-Qualification Packet SPSC N180 Computer Data Room Phase II Project No. CP 159313 Notice No. Notice 13-11 Issued by Department of Facilities Management Delivery address: Research
Building Commissioning 17900-1
SECTION 17900 BUILDING COMMISSIONING PART 1 - GENERAL 1.01 WORK DESCRIPTION: A. General: 1. The Commissioning process is a joint team effort to ensure that all mechanical equipment, controls, and systems
FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval.
Polk School District Specifications for the New Fire Alarm in the Existing Building Eastside Elementary School FIRE ALARM SYSTEM 1.01 SUBMITTALS A. Shop drawings shall be submitted as follows: 1. Manufacturer's
CITY OF YORBA LINDA P.O. BOX 87014 CALIFORNIA 92885-8714
CITY OF YORBA LINDA P.O. BOX 87014 CALIFORNIA 92885-8714 BUILDING DIVISION (714) 961-7120 Single Family Residential New Construction, Additions & Alterations Submittal Requirements Required agency approvals
NORTH COLONIE CENTRAL SCHOOL DISTRICT 91 FIDDLERS LANE LATHAM, NEW YORK 12110-5349 INVITATION FOR CONSTRUCTION MANAGEMENT PROPOSALS
NORTH COLONIE CENTRAL SCHOOL DISTRICT 91 FIDDLERS LANE LATHAM, NEW YORK 12110-5349 INVITATION FOR CONSTRUCTION MANAGEMENT PROPOSALS The North Colonie Central School District invites your firm to submit
LONG INTERNATIONAL. Long International, Inc. 10029 Whistling Elk Drive Littleton, CO 80127-6109 (303) 972-2443 Fax: (303) 972-6980
LONG INTERNATIONAL Long International, Inc. 10029 Whistling Elk Drive Littleton, CO 80127-6109 (303) 972-2443 Fax: (303) 972-6980 www.long-intl.com Construction Claims Prevention Richard J. Long, P.E.
Los Angeles Unified School District Maintenance and Operations. COMMUNITY INITIATED PROJECTS: A Manual for Complex Project Managers
Los Angeles Unified School District Maintenance and Operations COMMUNITY INITIATED PROJECTS: A Manual for Complex Project Managers Los Angeles Unified School District 333 South Beaudry Ave. Los Angeles,
Guide Specification SECTION 23 08 00 - COMMISSIONING OF HVAC PART 1 - GENERAL 1.1 SUMMARY
SECTION 23 08 00 - COMMISSIONING OF HVAC PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. HVAC Commissioning description. 2. HVAC Commissioning responsibilities. 1.2 REFERENCES A. American Society
Development Services Guidelines
Dear Customer/Developer: Balcones Heights 3300 Hillcrest San Antonio, Texas 78201 210-735-9148 ext 246 Fax: 210-735-9409 Development Services Guidelines Welcome to the City of Balcones Heights, we look
PRIME CONSULTANT SERVICES
GUIDELINES FOR Professional Engineers providing PRIME CONSULTANT SERVICES 1.0 INTRODUCTION 1.1 PURPOSE OF GUIDELINES The "Guidelines for Professional Engineers providing Prime Consultant Services" have
Attachment 5 Electrical Engineering
A. Phase 1, Preliminary Design: The CONSULTANT shall: Attachment 5 Electrical Engineering 1. Ascertain the requirements for each project through a meeting with the Capital Projects Division Manager or
Health Chapter 420-5-22 ALABAMA STATE BOARD OF HEALTH ALABAMA DEPARTMENT OF PUBLIC HEALTH ADMINISTRATIVE CODE
Health Chapter 420-5-22 ALABAMA STATE BOARD OF HEALTH ALABAMA DEPARTMENT OF PUBLIC HEALTH ADMINISTRATIVE CODE CHAPTER 420-5-22 SUBMISSION OF PLANS AND SPECIFICATIONS FOR HEALTH CARE FACILITIES TABLE OF