PUBLICATION 280 Manufacturing Specification For Reinforced Concrete Pipe
|
|
|
- Byron Greene
- 10 years ago
- Views:
Transcription
1 Commonwealth of Pennsylvania Department of Transportation Bureau of Construction & Materials PUBLICATION 280 Manufacturing Specification For Reinforced Concrete Pipe Pennsylvania Installation Direct Design (PAIDD) May 2009 Edition
2 TABLE OF CONTENT MANUFACTURING SPECIFICATION FOR DIRECT DESIGN OF BURIED PRECAST CONCRETE PIPE PUBLICATION SCOPE REFERENCED DOCUMENTS DEFINITIONS CLASSIFICATIONS BASIS OF ACCEPTANCE MATERIALS DESIGN REINFORCEMENT JOINTS MANUFACTURE PHYSICAL REQUIREMENTS PERMISSIBLE VARIATIONS WORKMANSHIP, FINISH, AND APPEARANCE REPAIRS INSPECTION REJECTION MARKING APPENDIX A - DESIGN TABLES & PROOF LOAD TABLES APPENDIX B REPAIR PROCEDURES FOR REINFORCED CONCRETE PIPE APPENDIX C QUALITY CONTROL PLAN GUIDELINES FOR RC PIPE PRODUCTION JOINT WELDING SPECIFICATION (WPS) DIMENSIONAL REVIEW FOR CONCRETE PIPE (POST-POUR FORM)... 71
3 Manufacturing Specification For Direct Design of Buried Precast Concrete Pipe Using Pennsylvania Installation Direct Design (PAIDD) 1. SCOPE 1.1. This Specification covers reinforced concrete pipe intended to be used for the conveyance of sewage, industrial wastes, and storm water, and for the construction of culverts This Specification covers the manufacture and acceptance of precast concrete pipe designed to conform to the Department design requirements Manufacturers are required to submit a plant Quality Control plan and concrete mix design(s) to the Structural Materials Engineer, MTD, for review and approval. NOTE: This specification is a manufacturing and purchase specification and the manufacturer must be listed in BULLETIN REFERENCED DOCUMENTS 2.1. AASHTO Standards: M 6 M 31 M 32 M 55 M 80 M 85 M 148 M 221 M 225 M 240 M 262 M 295 Fine Aggregate for Portland Cement Concrete Deformed and Plain Billet-Steel Bars for Concrete Reinforcement Cold Drawn Steel Wire for Concrete Welded Steel Wire Fabric for Concrete Reinforcement Coarse Aggregate for Portland Cement Concrete Portland Cement Liquid Membrane Forming compounds for Curing Concrete Welded Deformed Steel Wire Fabric for Concrete Reinforcement Deformed Steel Wire for concrete Reinforcement Blended Hydraulic Cements Terms Relating to Concrete Pipe and Related Products Fly Ash and Raw or Calcined Natural Pozzolan for use as a Mineral Admixture in Portland Cement Concrete 1
4 T 22 T 280 Pub 145 Compressive Strength of Cylindrical Concrete Specimens Testing Concrete Pipe, Sections, or Tile Inspection of Prestressed/Precast Concrete Products & Concrete Products & Concrete Pipe 3. DEFINITIONS 3.1. For definitions of terms relating to concrete pipe, see AASHTO M Group of Pipe Sections: Each day s production run of pipe sections of a single concrete strength or structural design for the Department Lot of Pipe Sections: The total of the number of groups of pipe sections of a single concrete strength and structural design produced for the Department (max 100 pieces). A Lot shall be all pipe dates equal to or prior to Test Specimen date, except when manufacturing is performed for special design pipes requiring reduced sized test specimens (Sec. 7.2) and/or for extended delivery schedules where the pipe lot cannot be fabricated entirely prior to initial delivery to the project Running Average: The average concrete compressive strength of all groups of pipe sections of a single concrete strength produced for the Department, generally determined as each lot is tested Proof Load: The load carried by a pipe subjected to a three-edge bearing test, expressed in pounds per linear foot per foot of inside diameter. This proof load reflects the field service load condition for live and dead load Proof Test Load: 3.2. Abbreviations: Tree-edge bearing test load extrapolated from design requirement to produce a 0.01 crack. AASHTO PAIDD BD-XXX American Association of State Highway and Transportation Officials Pennsylvania Installation Direct Design Bridge Design Drawing (e.g. BD-636) 2
5 RC-XX Road Construction Drawing (e.g. RC-30) PTM-XXX Pennsylvania Test Method (e.g. PTM 606) PDM4 PENNDOT Design Manual Part 4 MTD Materials and Testing Division 4. Classifications 4.1. Pipe manufactured in accordance with the classification and specifications in BD Basis of Acceptance 5.1. Unless otherwise designated by the Department at the time of, or before placing an order, separate alternative bases of acceptance are permitted as follows: Unless otherwise specified acceptance on the Basis of Plant Load-Bearing Tests, Material Tests, and Inspection of Manufactured Pipe for Visual Defects and Imperfections Acceptability of the pipe in all diameters and classes produced in accordance with PAIDD Design Date, conformance to this Specification and inspection of manufactured pipe for defects Acceptance on the Basis of Material Tests and Inspection of manufactured Pipe for Defects and Imperfections-Acceptance of pipe shall be on the basis of concrete compression tests, materials tests, conformance to the PAIDD Design Date, conformance to this Specification and inspection of manufactured pipe for defects When mutually agreed in writing by Department and the manufacturer, a certification may be made the basis of acceptance of the concrete pipe. This certification shall consist of a statement by the manufacturer that the concrete pipe conforms to the Manufacturing Design Data and to this Specification, and that the concrete and materials have been sampled and tested and conform to this specification The Department may select and have applied the basis of acceptance in either Section 5.1.1, 5.1.2, or Age of Acceptance: Pipe shall be considered ready for acceptance when it conforms to the requirements as indicated by the specified tests. 6. Materials 6.1. All material suppliers must be listed in the appropriate Bulletin 14 or Reinforced Concrete: 3
6 The reinforced concrete shall consist of cementitious materials, mineral aggregates, admixtures if used, and water, in which steel has been embedded in such a manner that the steel and concrete act together Cementitious Material: Cement: Cement shall conform to the requirements for Portland cement AASHTO Specification M 85 or shall be Portland Blast-Furnace Slag Cement or Portland-Pozzolan Cement conforming to the requirements of AASHTO Specification M 240, except that the Pozzolan constituent in the Type IP Portland Pozzolan cement shall be Fly Ash and shall not exceed 25% by weight Fly Ash or Pozzolan: Fly Ash or Pozzolan shall conform to the requirements of AASHTO Specification M 194, Class F or Class C Allowable Combinations of Cementitious Materials: The combination of cementitious materials used in the concrete shall be one of the following: Portland Cement only Portland Blast Furnace Slag Cement only Portland Pozzolan Cement only A combination of Portland Cement and Fly Ash or Pozzolan, wherein the proportion of Fly Ash is between 5 and 25% by weight of total cementitious material (Portland Cement plus Fly Ash) Aggregates: Aggregates shall conform to the requirements of Publication 408, Section 703 (Class A) except that the requirement for gradation shall not apply Admixtures: Admixtures may be used unless prohibited by the Department Steel Reinforcement: Reinforcement shall consist of wire conforming to AASHTO specification M 32 or AASHTO Specification M 55, or of wire fabric conforming to AASHTO Specification M 55, or AASHTO M 31 Specification. 4
7 7. Design 7.1. Design Tables: The diameter, wall thickness, compressive strength and reinforcement shall be as prescribed in APPENDIX A, or as provided by the PAIDD program in Section Footnotes: 7.2. Special Designs: Footnotes in APPENDIX A, are intended to be amplifications of tabulated requirements and are to be considered applicable and binding as if they were contained in the body of the specification The manufacturer may request approval by the Department for special designs when diameters and installation depths are beyond those provided in the Design Tables, Section Special designs shall be based on PAIDD, and the Design Specifications in PDM4. Special designs shall include copies of any output produced by the PAIDD program The fabricator shall submit to the Department, MTD, Chief Structural Materials Engineer, proof of the adequacy of the proposed special design. Such proof may comprise the submission of properly certified proof load tests already made, which are found by the Department to be adequate or, if such proof load tests are not available or acceptable, the fabricator may be required to perform proof load tests to demonstrate the correctness and adequacy of the proposed design Such pipe must meet all of the test and performance requirements specified by the Department in accordance with Section When the PAIDD program is used for special design pipe, submit one copy of the computer output to the Chief Structural Materials Engineer for review and approval. Show input data and design results. Include shop drawings of the proposed pipe cross section and reinforcement layouts in sufficient detail to provide inspection. Include the following details at a minimum: State Route, Section and County; minimum concrete strength; steel areas and maximum spacing; steel yield strength ; reinforcement cover and tolerances; wall thickness and tolerances; joint details; weight per lineal foot of pipe; maximum fill height and proof load Area In this specification, when the word area is not described by adjectives, such as crosssection or single wire, it shall be understood to be the cross-sectional area of reinforcement per unit lengths of pipe. 5
8 8. Reinforcement 8.1. Circumferential Reinforcement: A line of circumferential reinforcement for any given total area may be composed of two layers for pipe with wall thicknesses of less than 7 in. or three layers for pipe with wall thickness of 7 in. or greater. The layers shall not be separated by more than the thickness of one longitudinal plus ¼. The multiple layers shall be fastened together to form a single rigid cage. If the multiple layers of a cage contain circumferential splices, the individual layers shall be rotated so that the splices are staggered. All other specification requirements such as laps, welds, and tolerances of placement in the wall of the pipe, etc. shall apply to this method of fabricating a line of reinforcement. The design shall be based on the centroid of the layers Where one line of circular reinforcement is used, it shall be placed from 35 to 50% of the wall thickness from the inner surface of the pie, except that for wall thicknesses less than 2-1/2 in. the protective cover of the concrete over all reinforcement, each line shall be reinforcement in the wall of the pipe shall be 3/ In pipe having two lines of circular reinforcement, each line shall be so placed that the protective covering of concrete over all reinforcement in the wall of the pipe shall be 1 in Elliptical reinforcement shall be permitted for Elliptical pipe and quadrant reinforcement only In pipe having elliptical reinforcement with wall thicknesses 2-1/2 in. or greater, the reinforcement in the wall of the pipe shall be so placed that the protective covering of concrete over the circumferential reinforcement shall be 1 in. from the inner surface of the pipe at the vertical diameter and 1 in. from the outer surface of the pipe at the horizontal diameter The location of the reinforcement shall be subject to the permissible variations in dimensions given in Requirements for placement and protective covering of the concrete from the inner or outer surface of the pipe do not apply to that portion of a cage which is flared so as to extend into the bell or reduced in diameter so as to extend into the spigot. Reinforcement shall not be exposed on the mating side surface of the joints The spacing center to center of circumferential reinforcement in a cage shall not exceed 4 in. for pipe up to and including pipe having a 4 in. wall thickness nor exceed the wall thickness for larger pipe, and shall in no case exceed 6 in Where the wall reinforcement does not extend into the joint, the maximum longitudinal distance to the last circumferential from the inside shoulder of the bell or the shoulder of the spigot shall be 3 in., except that if this distance exceeds one-half the wall thickness, the pipe wall shall contain at least a total reinforcement area of the minimum specified area per linear foot times the 6
9 laying length of the pipe section. The minimum cover on the last circumferential near the spigot shoulder shall be 1/2 in Where reinforcement is in the bell or spigot the minimum end cover on the last circumferential shall be 1/2 in. in bell or 1/4 in. in the spigot The continuity of the circumferential reinforcing steel shall not be destroyed during the manufacture of the pipe, except that when agreed upon by the Department, lift eyes or holes may be provided in each pipe for the purpose of handling Form or create lift eyes or holes in accordance with the fabrication method approved by the Chief Structural Materials Engineer. Test by sounding, 10% of each lot of cured pipe around the lift hole. If any rejections are found, test 100% of each lot; reject for Department use all pipe having evidence of damage. Remove any reinforcement within the lift hole exposed during the manufacturing process Welds, Splices and Development of circumferential / Reinforcement Where pipe are not marked to show a specific orientation in the ground, any weld to, or splice, of a circumferential shall be considered to be at the point of the maximum flexural stress Where Pipe are marked to show a specific orientation in the ground, any weld to, or splice, of a circumferential shall be considered to be at a distance determined by the orientation angle closer to the point of maximum flexural stress than the marking indicates Notation A wa = Actual Steel area of the individual circumferential wire, square inches. A wr = Steel area required for the individual circumferential wire for flexure (a) at the splice, for splices, or (b) at the point of maximum moment, for quadrant mat reinforcement, square inches. d b = D i = Diameter of reinforcing wire or bar, inches Inside diameter of pipe, in. F w = Embedded weld factor, See Section h = Overall thickness of member (wall thickness), in. L d = Development length of reinforcing wire or bar, in. 7
10 I e = P t = f y = f c = t b = θ = S p = Total additional arc length beyond calculated arc lengths requiring stirrups, in. Pull test strength of wire or bar at break, pounds. Design yield strength of reinforcement, lbs./in2 Design compressive strength of concrete, lbs./in2 Clear cover over reinforcement, in. Orientation angle, deg. Spacing of circumferential reinforcement, in. V u = Factored shear force, lbs. V c = Nominal shear strength of the concrete cross section, lbs/ft Welds Manual welding of reinforcing steel shall be performed using either shielded metal arc welding (SMAW), gas metal arc welding (GMAW), or flux cored arc welding processes (FCAW). Welder and procedure qualification must be performed in accordance with AWS D1.4 for butt splices of circumferentials. For welding limited solely to lapped splicing of circumferentials (single or double flare-v groove welds), procedure qualification testing shall be limited to demonstration that the tensile requirements of and will be met for production welds. Inspection, sampling and testing for procedure qualification must be coordinated through the MTD, Structural Materials Section Submit a weld procedure specification (WPS) to the Chief Structural Materials Engineer, MTD, for approval, (see Appendix D). For Procedure qualification of lapped circumferentials, not less than three samples will be tested for each diameter of wire. Where the WPS is submitted for a range of wire sizes, procedure qualification will be performed on each of the minimum and maximum wire diameters shown. The procedure qualification testing will be considered acceptable when a 90 Percent Within Limits (PWL) is achieved For butt splices of circumferentials or where welds are made to circumferentials, pull tests of representative specimens of the circumferential across the finished weld shall demonstrate a strength of not less than 1.1 times the design yield strength of the circumferential except as provided in
11 At the option of the fabricator a more detailed analysis may be made and the requirements of this section used in lieu of For butt splices of circumferentials or where welds are made to circumferentials, pull tests, Pv of representative specimens of the circumferential across the finished weld shall demonstrate a strength of not less than Pt = 1.1 Awr f (1) y or not less than Pt = 0. 5 Awr f (2) y whichever is greater The overall performance and acceptance of the welds in section shall be accepted subject to section external load crushing Strength Lapped Splices of circumferential Reinforcement Where lapped circumferentials are spliced by spot welding. They shall be lapped not less than 2 inches. Pull tests of representative specimens shall develop not less than 0.9 times design yield strength of the circumferential At the option of the fabricator a more detailed analysis may be made and the requirements of this section used in lieu of Where lapped circumferentials are spliced by welding, they shall be lapped no less than 2 in. Pull tests, Pt, of representative specimens shall develop not less than Pt = F Awr f (3) W y or not less than the strength required by equation (2), whichever is the greater The embedded weld factor, Fw, relates the pull test strength of the non-embedded splice specimens to the strength of the splice embedded in the concrete of the pipe wall. (a) If the pull test breaks is in the wire, Fw shall be taken as
12 (b) If the pull test break is in the weld, Fw shall be taken as If lapped splices or circumferentials consisting of deformed bars, deformed wire or welded deformed wire fabric are not welded, they shall be lapped not less than L d, where: 0.03 d b Ld = f ' A A or not less than c f y wa wr (4) d b f f y ' c (5) whichever is greater If lapped splices of circumferentials consisting of welded, smooth wire fabric are not welded, the overlap measured between the outermost longitudinals on each side of the splice shall be no less than the spacing of the longitudinals plus1 inch, or L d, where: L d = 0.27 A s p wr f f y ' c (6) whichever is greater At the option of the fabricator a more detailed analysis may be made and the following exception to the requirements of may be applied. If the area of circumferential reinforcement is at least twice that required for flexure, the first requirement of Section shall not apply. The overlap measured between the outermost longitudinals on each side of the splice shall be not less than that required by equation (6), or 1 inch, whichever is greater Alternative splice designs that differ from section may be submitted to the Department for approval Development of Quadrant Mat Reinforcement 10
13 Circumferential quadrant mat reinforcement shall consist of welded wire fabric with 8 inch maximum cross wire spacing. When quadrant mat reinforcement is used, the area of the main cage shall be no less than 25% of the area required at the point of maximum moment. The quadrant mats shall extend at least 45 degrees each side of the point of maximum moment At the option of the fabricator a more detailed analysis may be made and the requirements of Sections and used in lieu of When circumferential quadrant mat reinforcement consists of welded smooth wire fabric the following requirements shall apply: The outermost longitudinals on each end of the circumferentials shall be embedded in accordance with the following requirements: (a) (b) Past the point where the quadrant reinforcement is no longer required by the orientation angle, plus the greater of 12 circumferential wire diameters or ¾ of the wall thickness of the pipe, and Past the point of maximum flexural stress by the orientation angle, plus the development length, L d, required by Equation (6) The mat shall contain no less than 2 longitudinals at a distance 1 inch greater than that determined by the orientation angle from either side of the point requiring the maximum flexural reinforcement The point of embedment of the outermost longitudinals of the mat shall be at least a distance determined by the orientation angle past the point where the continuing reinforcement is no less that double the area required for flexure When circumferential quadrant mat reinforcement consists of deformed bars, deformed wire or welded deformed wire fabric the following requirements shall apply: Circumferentials shall extend past the point where they are no longer required by the orientation angle, plus the greater of 12 wire diameters of 3/4 of the wall thickness of the pipe Circumferentials shall extend either side of the point of maximum flexural stress not less than the orientation angle, 11
14 plus the development length, Ld, required by Equation (4) or (5) Circumferentials shall extend at least a distance determined by the orientation angle past the point where the continuing reinforcement is no less than double the area required for flexure Stirrup Reinforcement: The number of lines of stirrups shall be sufficient to include the distance determined by calculation where Vu is less than Vc plus the distance lθ as determined by formula (7). The required number of lines of stirrups shall be equally distributed on each side of the point of maximum moment, as per PAIDD. πθ lθ = ( D i + 2tb )+ h (7) Stirrups used for radial tension When stirrups are used to resist radial tension, they shall be anchored around each circumferential of the inside cage to develop the resistance of the stirrup, and they shall also be anchored around the outside cage or embedded sufficiently in the compression side to develop the required resistance of the stirrup. If continuous prefabricated stirrup mats are used, the stirrups need to be sufficiently anchored in the compression zone of the concrete cross section so as to develop the full tensile strength of the stirrup wire. Continuous stirrup loop lengths equivalent to at least 70% of the wall thickness may be considered to provide adequate anchorage Stirrups used for diagonal tension When stirrups are not required for radial tension but required for shear (diagonal tension); their longitudinal spacing shall be such that they are anchored at either each or every other tension circumferential. Such spacing shall not exceed 6 inches. If prefabricated stirrup mats are used, they shall be placed inside the inner cage with loops directed toward the outer cage Anchorage systems that differ from those shown in Figures 1 and 2, and their corresponding anchorage design stresses, must be submitted to the Department, MTD, for proof of adequacy. For Bulletin 15 approval, submit independent Quality Control data for prefabricated loop type stirrup mats to verify a minimum of 65,000 psi anchorage strength is developed, as determined by appropriate tests that simulate the behavior of the stirrup in the pipe. 12
15 8.3. Longitudinal reinforcement: Each line of circumferential reinforcement shall be assembled into a cage that shall contain sufficient longitudinal bars or members, extending the length of the pipe, to maintain the reinforcement rigidly in shape and in correct position within the form. The exposure of the ends of longitudinals, stirrups, or spacers that have been used to position the cages during the placement of the concrete shall not be a cause for rejection Joint Reinforcement: For pipe 36 in. and larger in diameter, either the bell or spigot shall contain circumferential reinforcement. This reinforcement shall be an extension of a wall cage, or may be a separate cage of at least the area per foot of that specified for the outer cage or one-half of that specified for single cage wall reinforcement, whichever is less Where bells or spigots require reinforcement, the maximum end cover on the last circumferential shall be one-half the length of the joint or 3 in., whichever is less. 9. JOINTS 9.1. The joints shall be of such design and the ends of the concrete pipe sections so formed that when the sections are laid together they will make a continuous line of pipe with a smooth interior free from appreciable irregularities in the flow line, all compatible with the permissible variations given in Section
16 14
17 15
18 10. MANUFACTURE Mixture: The aggregates shall be sized, graded, proportioned, and mixed in a batch mixer with such proportions of cement and water as will produce a homogeneous concrete mixture of such quality that the pipe will conform to the test and design requirements of this specification. All concrete shall have a water-cement ratio not exceeding All pipe manufactured under the provisions of this specification shall contain a minimum of 470 lb. of cement/yd 3 of concrete unless mix designs with a lower cement content demonstrate that the quality and performance of the pipe meet the requirements of this specification Bin Scales: Curing: Bin Scales used in proportioning cement and aggregates must be verified annually to their accuracy within ± 2% of the required weight by an acceptable certified calibration agency. Pipe shall be subjected to any one of the methods of curing described in 10.2 to , or to any other method or combination of methods approved by the purchaser that will give satisfactory results. The pipe shall be cured for a sufficient length of time so that the specified proof load is obtained when acceptance is based on 5.1.1, or so that the concrete will develop the specified compressive strength at 28 days, or less when acceptance is based on or Steam Curing Pipe may be placed in a curing chamber, free of outside drafts, and cured in a moist atmosphere maintained by the injection of steam for such time and such temperature as approved in the Quality Control Plan and needed to enable the pipe to meet the strength requirements. The curing chamber shall be so constructed as to allow full circulation of steam around the entire pipe Water Curing: Concrete pipe may be water-cured by covering with water saturated material or by a system of perforated pipes, mechanical sprinklers, porous hose, or by any other approved method that will keep the pipe moist during the approved curing period The fabricator may, at his option, combine the methods described in to provided the required concrete compressive strength is attained. 16
19 A sealing membrane conforming to the requirements of AASHTO M 148 may be applied and should be left intact until the strength requirements are met. The concrete at the time of application shall be 10 o F above the atmospheric temperature. All surfaces shall be kept moist prior to the application of the compounds and shall be damp when the compound is applied. 11. PHYSICAL REQUIREMENTS Test Specimens: 1% of each lot for testing tests shall be furnished without charge by the fabricator and shall be selected at random by the Department and shall be pipe that would not otherwise be rejected under this specification. The selection shall be made at the point or points designated by the purchaser when placing the order Tests for Extended Delivery Schedules: For extended project deliveries, the lot will be accepted as follows: Perform a preliminary three-edge bearing test on a section in accordance with Section Each successive production date comprising the reduced lot will be accepted on the basis of compressive strength testing in accordance with Section (2), Acceptance Testing External Load Crushing Strength: The load to produce a 0.01 in. crack, as determined by the three-edge bearing method described in AASHTO T 280, shall be not less than the proof load provided in Appendix A, or by PAIDD for each respective pipe design. Lots for which the pipe have been tested in accordance with this specification and that meet the proof load requirements given in shall be accepted for use Retests of Pipe Not Meeting the External Load Crushing Strength Requirements Pipe shall be considered as meeting the strength requirements when all test specimens conform to the strength requirements, the fabricator shall be allowed to retest two additional specimens for each specimen that failed, and the pipe shall be acceptable only when all of the retest specimens meet the strength requirements When acceptance is on the basis of 5.1.1, test pipe by the three-edge bearing method in accordance with AASHTO T 280, as modified herein. Accept any test specimens which meet the 0.01 in. crack proof-load requirement without exceeding a in. crack width under test load and which are otherwise free from defects as listed in section 16. Verify that in. crack limit with a feeler gauge conforming to the requirements shown in AASHTO T 280, except having a gauge thickness of in. 17
20 The lot shall be tested to the specified design proof-load requirement as outlined below: Fabricator loads pipe at uniform rate. As 0.01 crack load is approached, look for crack 0.01 or greater Crack 0.01 or greater before proof is reached Test 2 more units. For lot to pass, both units must pass the proof load test. No crack 0.01 and greater than 12 in length Lot passes three-edge bearing test. 18
21 11.4. Concrete Test Requirements: Compressive Strength: (1) Quality Control Testing: Compressive tests, or monitoring the design concrete strength, may be made on either standard rodded concrete cylinders or cylinders compacted and cured in a like manner as the pipe, or on cores drilled from the wall of the pipe. Cylinders and cores shall be tested in accordance the PTM 604 and AASHTO T24, respectively. The design will be considered satisfactory when at least 90% of the strength tests show strengths greater than the required minimum specification strength. Cylinders may be kept in a moist temperature controlled condition to develop 28-day strengths. (2) Acceptance Testing: When compressive strength testing is performed for the purpose of accepting pipe lots in accordance with section and 11.2, perform compressive strength testing in accordance with PTM 604 and AASHTO T24, respectively. The compressive strength test must meet or exceed the design requirement. Specimen results which deviate from each other by 1,000 psi or more are considered invalid. If the concrete consistency is too stiff for compaction by rodding or internal vibrations, the following alternative method may be use: (1) Bolt a cylinder mold to the top of a vibrating table, or to the actual concrete pipe form being used to produce the pipe. (2) Place wetcast concrete in the cylinder mold in three equal lifts, and drycast or packerhead concrete in accordance with AASHTO T (3) Place a cylindrical hammer on the surface of each lift with the hammer to be 1/4 inch less in diameter than the inside diameter of the mold and of a weight to create a pressure of psi on the surface of the concrete. (4) External vibration shall be applied on each lift with a frequency of at least 800 vibrations per minute, and continued until cement paste begins to ooze up around the bottom edge of the hammer. If cores are cut from the wall of the pipe and tested they shall be cut and tested in accordance with the requirements of AASHTO T 280. The compressive strength of each core tested shall be equal to or greater than the design strength of the concrete. 19
22 Requirements: Pipe shall be considered as meeting the strength requirements when all test specimens conform to the strength requirements. Should any of the test specimens fail to meet the strength requirements, the fabricator shall be allowed a retest on two additional specimens for each specimen that failed, and the pipe shall be acceptable only when all of the retest specimens meet the strength requirements. When the cores cut from a section of pipe successfully meet the strength requirement, the core holes shall be plugged and sealed by the fabricator in an approved manner such that the pipe section will meet all of the requirements of this specification. Pipe sections so sealed shall be considered as satisfactory for use Absorption Test Requirements of Concrete: Test Equipment: The absorption of a sample from the wall of the pipe, as determined in accordance with AASHTO T 280, shall not exceed 9 percent of the dry mass. Each sample shall be a piece broken from the wall, or a core drilled from the wall, shall have a minimum area of 9 in 2. as measured on one surface of the pipe wall, and shall be free of visible cracks. When the initial absorption sample, from a pipe fails to conform to this specification the fabricator shall be allowed a retest on two additional samples from the same pipe for each sample that failed. The pipe shall be acceptable only when all of the retest samples meet the absorption requirements. Absorption test requirements of concrete may be waived by the Department. Every fabricator furnishing pipe under this specification shall furnish all facilities and personnel necessary to carry out the tests described in AASHTO T PERMISSIBLE VARIATIONS Internal Diameter: The internal diameter of round 12 to 24 in. pipe shall vary not more the ± 1.5% from the design diameter. The internal diameter of round 27 in. and larger pipe shall not vary by more than ± 1% from the design diameter or ± 3/8 in., whichever is greater. The internal dimensions of elliptical pipe shall not vary more than +2% from the internal dimensions shown in Fig Wall Thickness: The design wall thickness, or specified wall thickness, shall not vary by more than ± 5% or 3/16 in., whichever is greater. A specified wall thickness more than required in the design is not cause for rejection. Pipe having localized variations 20
23 in wall thickness exceeding those specified above shall be accepted if the proof load strength and minimum steel cover requirements are met Length of Two Opposite Sides: Variations in the laying length of two opposite sides of the pipe shall not be more than ¼ in. for all sizes through 24 in. internal diameter, and not more than 1/8 in./ft. for all sizes larger with a maximum of 3/4 in. for 90 in. internal diameter or larger, except where beveled end pipe for laying on curves is specified by the Department Length of Pipe: The under run in length of a section of pipe shall not be more than 1/8 in./ft. with a maximum of ½ in. in any length of pipe. Regardless of the underrun or overrun in any section of the pipe, the end cover requirements of Section 8 and 12 shall apply Position of Area of Reinforcement: Position: The maximum variation in the position of the reinforcement shall be ± 10% of the wall thickness or ± 2 in., whichever is greater. Pipe having variations in the position of the reinforcement exceeding those specified above shall be accepted if the three-edge-bearing strength requirements obtained on a representative specimen are met. In no case, however, shall the cover over any reinforcement be less than ¼ in. as measured to the end of the spigot or ½ in. as measured to any other surface. The preceding minimum cover limitations do not apply to mating surfaces of non-rubber gasket joints, here reinforcement shall not be exposed on the side mating surface of the joints. If convoluted reinforcement is used, the convoluted circumferential end wire may be at the end surface of the joint providing the alternate convolutions have at least 1 in. cover from the end surface of the joint Area of Reinforcement: Reinforcement will be considered as meeting the design requirements if the area, computed on the basis of nominal area of the wire or bars used, equals or exceeds the requirements of 7.1 or 7.2. Actual area of the reinforcing used may vary from the nominal area according to permissible variations of the standard specifications for the reinforcing. 13. WORKMANSHIP, FINISH, AND APPEARANCE Pipe shall be substantially free of fractures and surface roughness. The ends of the pipe shall be normal to the walls and center line of the pipe, within the limits of variations given in 12.3 and
24 14. REPAIRS Pipe may be repaired, if necessary, because of imperfections in manufacture or damage during handling and will be acceptable if, in the opinion of the Department, the repairs are sound and properly finished and cured and the repaired pipe conforms to the requirements of this standard. Repair procedures for RC pipes are described in Appendix B. 15. INSPECTION The quality of materials, the process of manufacture, and the finished pipe may be subject to inspection and approval by an inspector employed by the Department. The following criteria has been developed to assign certification demerits or deviations to fabricators found to have certified and delivered pipe to Department projects not meeting the Specifications. Fabricators who accumulate three or more substantiated complaints during any continuous twelve month period will lose their certification status and may result in removal from Bulletin 15. Fabricators will earn an additional certification credit over and above the base allowance of three deviations for each 100 certified deliveries to Department projects. To earn certification credits, fabricators will be required to submit actual copies of Form CS-4171 s for verification. The following general guidelines were developed to establish the relative weight of each deviation applied toward a fabricator s certification status. Based on the actual number of pipe affected, however, partial deviations may be considered cumulative. Incident Type # deviations Diameter, out of tolerance 1 Joint dimensions, out-of-tolerance, unacceptable fit 1 Length of opposite sides, skewed sections 1 Wall thickness, out-of-tolerance 1 Unapproved repairs, unacceptable repairs (cosmetic) ½ Unapproved repairs, unacceptable repairs (structural) 1 Reinforcement not removed from lift holes ½ Through wall cracking, exceeding the depth of the joint 1 Cracking wide AND 12 long 1 Insufficient reinforcement cover 1 Open texture and/or honeycombing 1 Improper marking, structurally adequate ½ Improper marking, structurally deficient 1 Improperly substituted, structurally adequate ½ Improperly substituted, structurally deficient 1 Improperly certified, minor ½ Improperly certified, major 1 Non-Bulletin 14/15 materials used in production 1 Quality Control records missing/incomplete 1 22
25 16. REJECTION Pipe shall be subject to rejection on account of failure to conform to any of the specification requirements. Individual sections of pipe may be rejected because of any of the following: Fractures or cracks passing through the wall, except for a single end crack that does not exceed the depth of the joint Defects that indicate proportioning, mixing, and molding not in compliance with 10.1, or surface defects indicating honey-combed or open texture that would adversely affect the function of the pipe Damaged or cracked ends, where such damage would prevent making a satisfactory joint Any continuous crack having an unloaded surface width of in. or more and extending for a length of 12 in. or more, regardless of position in the wall of the pipe. Any continuous crack having an unloaded surface width of in. will be accepted. Verify the in. crack limit with a feeler gauge conforming to the requirements of AASHTO T 280, except having a gauge thickness of in. 17. MARKING The following information shall be legibly marked on the inside barrel of each section of pipe The pipe designation shall be indicated as follows: PA d t/s Max Min Or PA d t/sh Max Min Where: d = designated pipe internal diameter, inches t = installation type [A = state heavy duty, B = Standard duty] S = standard installation SH = shoring trench box installation Max = Maximum fill height, feet Min + Minimum fill height, feet Example: 24 pipe with a 3 wall thickness on a state highway with 15 of embankment fill where heavy duty pipe is required. This pipe could also be used for shoring condition and receive two markings as indicated below. PA 24 A/ S 15 2 PA 24 A/SH
26 When dual markings are used, the lot must be tested for the greater proof load required for either the standard or shoring/trench box installation, as applicable The date of manufacture The name or trademark of the fabricator, and Identification of plant American Concrete Pipe Association (ACPA) Q-Cast or National Precast Concrete Association (NPCA) stamp One end of each section of pipe with Elliptical or Quadrant reinforcement shall be clearly marked with the word TOP, during the process of manufacturing or immediately thereafter, on the inside and the outside of opposite walls along the minor axis of the Elliptical reinforcing or along the vertical axis for Quadrant reinforcing Markings shall be indented on the pipe section or painted thereon with waterproof paint. 24
27 SPAN RISE Approximate Equivalent Rise, in. Span, in. Round Size, in Figure 3: Cross-Sectional Shape of Elliptical Pipe 25
28 APPENDIX A - DESIGN TABLES & PROOF LOAD TABLES NOTES: 1. Fabricate concrete pipe per this Publication, Pennsylvania Installation Direct Design Manufacturing Specification 2. Test concrete pipes in accordance with this publication, Proof Test Load Include a 1.43 factor of safety for field cracking. Testing to Ultimate is not required. 3. The design values shown in this publication make the assumption that the excavation, backfill and construction methods in the RC standards and publication 408 are used. 4. Elliptical reinforcement is not permitted, except for quadrant reinforcement and for reinforcement of elliptical pipe. 5. Smooth welded wire fabric is used in the design of the steel areas for concrete pipe; the use of deformed wire fabric or deformed wire is also permitted. 6. Use design tables given in this publication to determine steel area; use PAIDD software for designs not covered by these tables. 7. Steel areas shown are in in 2 /ft. INSTRUCTIONS: Use PAIDD computer program to perform pipe designs for fill height and concrete strengths not shown in the designs tables, or as indicated by double asterisks (**). 26
29 DEFINITIONS: DIA TYPE A STANDARD INSTALLATION = INSIDE DIAMETER OF THE CONCRETE PIPE IN INCHES. = HEAVY DUTY CONCRETE PIPE EMBANKMENT INSTALLATION DESIGN. (APPROX. 100 YEARS LIFE) TYPE A SHORING/TRENCH BOX INSTALLATION = HEAVY DUTY CONCRETE PIPE TRENCH BOX OR SHORING INSTALLATION DESIGN. (APPROX. 100 YEARS LIFE) TYPE B STANDARD INSTALLATION = STANDARD DUTY CONCRETE PIPE EMBANKMENT INSTALLATION DESIGN. (APPROX. 50 YEARS LIFE) TYPE B SHORING/ TRENCH BOX INSTALLATION = STANDARD DUTY CONCRETE PIPE TRENCH BOX OR SHORING INSTALLATION DESIGN. (APPROX. 50 YEARS LIFE) PROOF TEST LOAD = THREE EDGE BEARING TEST TO A LOAD EXTRAPOLATED FROM DESIGN REQUIREMENT TO PRODUCE A 0.01 CRACK. PROOF LOAD = THE LOAD CARRIED BY A PIPE SUBJECTED TO A THREE EDGE BEARING TEST, EXPRESSED IN POUNDS PER LINEAR FOOT OF INSIDE DIAMETER. THE PROOF LOAD REFLECTS THE FIELD SERVICE LOAD CONDITION FOR BOTH LIVE AND DEAD LOADS H fy = DESIGN FILL HEIGHT. = SPECIFIED YIELD STRENGTH OF REINFORCEMENT. f c = SPECIFIED COMPRESSIVE STRENGTH OF CONCRETE. 27
30 ITEM TRENCH BOX/SHORING STANDARD INSTALLATION INSTALLATION TYPE A TYPE B TYPE A TYPE B INSTALLATION TYPE PA I DD PA I DD PA I DD PA I DD HAUNCH COMPACTION 95% MIN. 95% MIN. 60% MIN. 60% MIN. SOIL WEIGHT 140 lbs./ft lbs./ft lbs./ft lbs./ft 3 LIVE LOAD HS 25 HS 25 HS 25 HS 25 Fy 65,000 psi 65,000 psi 65,000 psi 65,000 psi f c MIN. 4,000 psi MIN. 4,000 psi MIN. 4,000 psi MIN. 4,000 psi CONCRETE COVER 1 OVER STEEL 1 OVER STEEL 1 OVER STEEL 1 OVER STEEL LOAD FACTORS: TYPE A TYPE B TYPE A TYPE B DEAD LOAD & EARTH LOAD FACTOR (SHEAR & MOMENT) DEAD LOAD FACTOR (THRUST): REINFORCEMENT DESIGN CONCRETE COMPRESSION LIVE LOAD FACTOR (SHEAR & MOMENT) LIVE LOAD FACTOR (THRUST) INTERNAL PRESSURE LOAD FACTORS (THRUST) IMPACT (TO MAX. 8 HEIGHT) 40[ H]>10% 40[ H]>10% 40[ H]>10% 40[ H]>10% STRENGTH REDUCTION ( φ FACTORS): TYPE A TYPE B TYPE A TYPE B FLEXURE RADIAL TENSION DIAGONAL TENSION CRACK CONTROL FACTOR ORIENTATION ANGLE ± 10 O ± 10 O ± 10 O ± 10 O MATERIAL & PROCESS FACTOR: TYPE A TYPE B TYPE A TYPE B RADIAL TENSION DIAGONAL TENSION EMBANKMENT ARCHING FACTORS: VAF (VERTICAL) HAF (HORIZONTAL) SEE TABLE C BD-636 SEE TABLE C BD
31 TYPE A STANDARD INSTALLATION STEEL AREAS (in. 2 / ft.) FILL HEIGHT (ft.) Dia. Wall Thick f c (psi) H< <H<2 2 <H<3 3 <H<7 7 <H< H> / / / / / / / / / / / / / / / NOTES: 1) INDICATES SAME STEEL AREA AS SHOWN FOR THE LESSER CONCRETE STRENGTH. 2) INDICATES A SPECIAL DESIGN IS REQUIRED. USE PAIDD SOFTWARE. 3) ELLIPTICAL REINFORCING IS NOT ALLOWED, EXCEPT FOR QUADRANT REINFORCEMENT AND FOR REINFORCEMENT OF ELLIPTICAL PIPE. 4) FOR DOUBLE CIRCULAR STEEL REINFORCED PIPE, TWO AREAS ARE SHOWN. THE GREATER AREA IS FOR THE INNER CAGE STEEL AND LESSER AREA IS FOR OUTER CAGE STEEL. 5) SUBSTITUTION OF PIPES UNDER FILLS OF 3-0 OR LESS IS PERMITTED ONLY WITH DESIGNER APPROVAL. 6) USE PAIDD SOFTWARE ONLY FOR PIPE DESIGNS NOT PROVIDED BY BD-636M. 7) STEEL AREAS SPECIFIED IN THE FILL HEIGHT / STEEL AREA TABLES ARE TO BE ACHIEVED USING ONE LAYER OF REINFORCEMENT FOR EACH CAGE. TWO LAYERS MAY BE SUBSTITUTED FOR ONE LAYER, PROVIDED THE SUM OF THE STEEL AREAS OF THE 2 LAYERS IS EQUAL TO THE AREAS OF STEEL FOR THE SINGLE LAYER CAGE. WHEN SUBSTITUTING, SPACING OF REINFORCEMENT IS TO REMAIN THE SAME. DESIGNING FOR 2 LAYERS OF REINFORCEMENT AND PROVIDING ONE LAYER OF REINFORCEMENT OF EQUIVALENT AREA IS NOT PERMITTED. DESIGN TABLES AND PROOF TEST LOAD TABLE FOR CIRCULAR PIPES 29
32 - TYPE A SHORING/TRENCH BOX INSTALLATION TYPE A STANDARD INSTALLATION STEEL AREAS ( in. 2 / ft.) FILL HEIGHT (ft.) Dia. Wall Thick f c (psi) H< <H<2 2 <H<3 3 <H<7 7 <H< H > 40 NOTES: / / / / / / ) INDICATES SAME STEEL AREA AS SHOWN FOR THE LESSER CONCRETE STRENGTH. 2) INDICATES A SPECIAL DESIGN IS REQUIRED. USE PAIDD SOFTWARE. 3) ELLIPTICAL REINFORCING IS NOT ALLOWED, EXCEPT FOR QUADRANT REINFORCEMENT AND FOR REINFORCEMENT OF ELLIPTICAL PIPE. 4) FOR DOUBLE CIRCULAR STEEL REINFORCED PIPE, TWO AREAS ARE SHOWN. THE GREATER AREA IS FOR THE INNER CAGE STEEL AND LESSER AREA IS FOR OUTER CAGE STEEL. 5) SUBSTITUTION OF PIPES UNDER FILLS OF 3-0 OR LESS IS PERMITTED ONLY WITH DESIGNER APPROVAL. 6) USE PAIDD SOFTWARE ONLY FOR PIPE DESIGNS NOT PROVIDED BY BD-636M. 7) STEEL AREAS SPECIFIED IN THE FILL HEIGHT / STEEL AREA TABLES ARE TO BE ACHIEVED USING ONE LAYER OF REINFORCEMENT FOR EACH CAGE. TWO LAYERS MAY BE SUBSTITUTED FOR ONE LAYER, PROVIDED THE SUM OF THE STEEL AREAS OF THE 2 LAYERS IS EQUAL TO THE AREA OF STEEL FOR THE SINGLE LAYER CAGE. WHEN SUBSTITUTING, SPACING OF REINFORCEMENT IS TO REMAIN THE SAME. DESIGNING FOR 2 LAYERS OF REINFORCEMENT AND PROVIDING ONE LAYER OF REINFORCEMENT OF EQUIVALENT AREA IS NOT PERMITTED. DESIGN TABLE FOR CIRCULAR PIPES - TYPE A STANDARD INSTALLATION 30
33 TYPE A STANDARD INSTALLATION STEEL AREAS ( in. 2 / ft.) Fill Height (ft.) Dia. Wall Thick f c (psi) H< <H<2 2 <H<3 3 <H<7 7 <H< H > / / / / / / NOTES: 1) INDICATES SAME STEEL AREA AS SHOWN FOR THE LESSER CONCRETE STRENGTH. 2) INDICATES A SPECIAL DESIGN IS REQUIRED. USE PAIDD SOFTWARE. 3) ELLIPTICAL REINFORCING IS NOT ALLOWED, EXCEPT FOR QUADRANT REINFORCEMENT AND FOR REINFORCEMENT OF ELLIPTICAL PIPE. 4) FOR DOUBLE CIRCULAR STEEL REINFORCED PIPE, TWO AREAS ARE SHOWN. THE GREATER AREA IS FOR THE INNER CAGE STEEL AND LESSER AREA IS FOR OUTER CAGE STEEL. 5) SUBSTITUTION OF PIPES UNDER FILLS OF 3-0 OR LESS IS PERMITTED ONLY WITH DESIGNER APPROVAL. 6) USE PAIDD SOFTWARE ONLY FOR PIPE DESIGNS NOT PROVIDED BY BD-636M. 7) STEEL AREAS SPECIFIED IN THE FILL HEIGHT / STEEL AREA TABLES ARE TO BE ACHIEVED USING ONE LAYER OF REINFORCEMENT FOR EACH CAGE. TWO LAYERS MAY BE SUBSTITUTED FOR ONE LAYER, PROVIDED THE SUM OF THE STEEL AREAS OF THE 2 LAYERS IS EQUAL TO THE AREAS OF STEEL FOR THE SINGLE LAYER CAGE. WHEN SUBSTITUTING, SPACING OF REINFORCEMENT IS TO REMAIN THE SAME. DESIGNING FOR 2 LAYERS OF REINFORCEMENT AND PROVIDING ONE LAYER OF REINFORCEMENT OF EQUIVALENT AREA IS NOT PERMITTED. DESIGN TABLES TABLE FOR CIRCULAR PIPES 31
34 - TYPE A STANDARD INSTALLATION TYPE A STANDARD INSTALLATION STEEL AREAS (in. 2 / ft.) Fill Height (ft.) Dia. Wall Thick f c (psi) H< <H<2 2 <H<3 3 <H<7 7 <H< H> / / / / / / NOTES: 1) INDICATES SAME STEEL AREA AS SHOWN FOR THE LESSER CONCRETE STRENGTH. 2) INDICATES A SPECIAL DESIGN IS REQUIRED. USE PAIDD SOFTWARE. 3) ELLIPTICAL REINFORCING IS NOT ALLOWED, EXCEPT FOR QUADRANT REINFORCEMENT AND FOR REINFORCEMENT OF ELLIPTICAL PIPE. 4) FOR DOUBLE CIRCULAR STEEL REINFORCED PIPE, TWO AREAS ARE SHOWN. THE GREATER AREA IS FOR THE INNER CAGE STEEL AND LESSER AREA IS FOR OUTER CAGE STEEL. 5) SUBSTITUTION OF PIPES UNDER FILLS OF 3-0 OR LESS IS PERMITTED ONLY WITH DESIGNER APPROVAL. 6) USE PAIDD SOFTWARE ONLY FOR PIPE DESIGNS NOT PROVIDED BY BD-636M. 7) STEEL AREAS SPECIFIED IN THE FILL HEIGHT / STEEL AREA TABLES ARE TO BE ACHIEVED USING ONE LAYER OF REINFORCEMENT FOR EACH CAGE. TWO LAYERS MAY BE SUBSTITUTED FOR ONE LAYER, PROVIDED THE SUM OF THE STEEL AREAS OF THE 2 LAYERS IS EQUAL TO THE AREAS OF STEEL FOR THE SINGLE LAYER CAGE. WHEN SUBSTITUTING, SPACING OF REINFORCEMENT IS TO REMAIN THE SAME. 32
35 DESIGNING FOR 2 LAYERS OF REINFORCEMENT AND PROVIDING ONE LAYER OF REINFORCEMENT OF EQUIVALENT AREA IS NOT PERMITTED. DESIGN TABLE FOR CIRCULAR PIPES TYPE A STANDARD INSTALLATION TYPE A STANDARD INSTALLATION STEEL AREAS ( in. 2 / ft.) Fill Height (ft.) Dia. Wall Thick f c (psi) H< <H<2 2 <H<3 3 <H<7 7 <H< H > / / / / NOTES: 1) INDICATES SAME STEEL AREA AS SHOWN FOR THE LESSER CONCRETE STRENGTH. 2) INDICATES A SPECIAL DESIGN IS REQUIRED. USE PAIDD SOFTWARE. 3) ELLIPTICAL REINFORCING IS NOT ALLOWED, EXCEPT FOR QUADRANT REINFORCEMENT AND FOR REINFORCEMENT OF ELLIPTICAL PIPE. 4) FOR DOUBLE CIRCULAR STEEL REINFORCED PIPE, TWO AREAS ARE SHOWN. THE GREATER AREA IS FOR THE INNER CAGE STEEL AND LESSER AREA IS FOR OUTER CAGE STEEL. 5) SUBSTITUTION OF PIPES UNDER FILLS OF 3-0 OR LESS IS PERMITTED ONLY WITH DESIGNER APPROVAL. 6) USE PAIDD SOFTWARE ONLY FOR PIPE DESIGNS NOT PROVIDED BY BD-636M. 7) STEEL AREAS SPECIFIED IN THE FILL HEIGHT / STEEL AREA TABLES ARE TO BE ACHIEVED USING ONE LAYER OF REINFORCEMENT FOR EACH CAGE. TWO LAYERS MAY BE SUBSTITUTED FOR ONE LAYER, PROVIDED THE SUM OF THE STEEL AREAS OF THE 2 LAYERS IS EQUAL TO THE AREAS OF STEEL FOR THE SINGLE LAYER CAGE. WHEN SUBSTITUTING, SPACING OF REINFORCEMENT IS TO REMAIN THE SAME. DESIGNING FOR 2 LAYERS OF REINFORCEMENT AND PROVIDING ONE LAYER OF REINFORCEMENT OF EQUIVALENT AREA IS NOT PERMITTED. DESIGN TABLE FOR CIRCULAR PIPES 33
36 - TYPE A STANDARD INSTALLATION TYPE A STANDARD INSTALLATION FILL HEIGHT (FT.) PROOF TEST LOAD (lb./lf/ft. OF DIAMETER) DIA (in.) 1.0 H < H < 2 2 H < 3 3 H < 7 7 H < H< H < H < H < H < H < H < H < H < H < H < NOTE: THESE PROOF LOADS INCLUDE A FACTOR OF SAFETY OF 1.43 FOR FIELD CRACK CONTROL. LEGEND: = FOR INFORMATION ONLY. PROOF LOAD TEST MUST BE PERFORMED TO THE MAXIMUM PROOF TEST LOAD FOR THE RANGE OF ITEM NUMBER. NOTES: 1) ELLIPTICAL REINFORCING IS NOT ALLOWED, EXCEPT FOR QUADRANT REINFORCEMENT AND FOR REINFORCEMENT OF ELLIPTICAL PIPE. 2) FOR DOUBLE CIRCULAR STEEL REINFORCED PIPE, TWO AREAS ARE SHOWN. THE GREATER AREA IS FOR THE INNER CAGE STEEL AND LESSER AREA IS FOR OUTER CAGE STEEL. 3) FOR PIPE SIZES GREATER THAN 48 DIAMETER, USE TYPE A STANDARD INSTALLATION DESIGN TABLES. 4) H = DESIGN FILL HEIGHT, FT. 5) SUBSTITUTION OF PIPES UNDER FILLS OF 3-0 OR LESS IS PERMITTED ONLY WITH DESIGNER APPROVAL. 6) USE PAIDD SOFTWARE ONLY FOR PIPE DESIGNS NOT PROVIDED BY BD-636M. 7) STEEL AREAS SPECIFIED IN THE FILL HEIGHT / STEEL AREA TABLES ARE TO BE ACHIEVED USING ONE LAYER OF REINFORCEMENT FOR EACH CAGE. TWO LAYERS MAY BE SUBSTITUTED FOR ONE LAYER, PROVIDED THE SUM OF THE STEEL AREAS OF THE 2 LAYERS IS EQUAL TO THE AREA OF STEEL FOR THE SINGLE LAYER CAGE. WHEN SUBSTITUTING, SPACING OF REINFORCEMENT IS TO REMAIN THE SAME. 34
37 DESIGNING FOR 2 LAYERS OF REINFORCEMENT AND PROVIDING ONE LAYER OF REINFORCEMENT OF EQUIVALENT AREA IS NOT PERMITTED. PROOF TEST LOAD TABLE FOR CIRCULAR PIPES - TYPE A STANDARD INSTALLATION TYPE A STANDARD INSTALLATION FILL HEIGHT (FT.) PROOF TEST LOAD (lb./lf/ft. OF DIAMETER) DIA (in.) 1.0 H < H < 2 2 H < 3 3 H < 7 7 H < H < H < H < H < H < H < H < H < H < H < H < NOTE: THESE PROOF LOADS INCLUDE A FACTOR OF SAFETY OF 1.43 FOR FIELD CRACK CONTROL. LEGEND: = FOR INFORMATION ONLY. PROOF LOAD TEST MUST BE PERFORMED TO THE MAXIMUM PROOF TEST LOAD FOR THE RANGE OF ITEM NUMBER. NOTES: 1) ELLIPTICAL REINFORCING IS NOT ALLOWED, EXCEPT FOR QUADRANT REINFORCEMENT AND FOR REINFORCEMENT OF ELLIPTICAL PIPE. 2) FOR DOUBLE CIRCULAR STEEL REINFORCED PIPE, TWO AREAS ARE SHOWN. THE GREATER AREA IS FOR THE INNER CAGE STEEL AND LESSER AREA IS FOR OUTER CAGE STEEL. 3) FOR PIPE SIZES GREATER THAN 48 DIAMETER, USE TYPE A STANDARD INSTALLATION DESIGN TABLES. 4) H = DESIGN FILL HEIGHT, FT. 5) SUBSTITUTION OF PIPES UNDER FILLS OF 3-0 OR LESS IS PERMITTED ONLY WITH DESIGNER APPROVAL. 6) USE PAIDD SOFTWARE ONLY FOR PIPE DESIGNS NOT PROVIDED BY BD-636M. 7) STEEL AREAS SPECIFIED IN THE FILL HEIGHT / STEEL AREA TABLES ARE TO BE ACHIEVED USING ONE LAYER OF REINFORCEMENT FOR EACH CAGE. TWO LAYERS MAY BE SUBSTITUTED FOR ONE LAYER, PROVIDED THE SUM OF THE STEEL AREAS OF THE 2 LAYERS IS EQUAL TO THE AREA OF STEEL FOR THE 35
38 SINGLE LAYER CAGE. WHEN SUBSTITUTING, SPACING OF REINFORCEMENT IS TO REMAIN THE SAME. DESIGNING FOR 2 LAYERS OF REINFORCEMENT AND PROVIDING ONE LAYER OF REINFORCEMENT OF EQUIVALENT AREA IS NOT PERMITTED. PROOF TEST LOAD TABLE FOR CIRCULAR PIPES - TYPE A STANDARD INSTALLATION 36
39 TYPE B STANDARD INSTALLATION STEEL AREAS ( in. 2 / ft.) FILL HEIGHT (ft.) Dia. Wall Thick f c (psi) H< <H<2 2 <H<3 3 <H<7 7 <H< H> / / / / / / / / / / / / / / / / / ) INDICATES SAME STEEL AREA AS SHOWN FOR THE LESSER CONCRETE STRENGTH. 2) INDICATES A SPECIAL DESIGN IS REQUIRED. USE PAIDD SOFTWARE. 3) ELLIPTICAL REINFORCING IS NOT ALLOWED, EXCEPT FOR QUADRANT REINFORCEMENT AND FOR REINFORCEMENT OF ELLIPTICAL PIPE. 4) FOR DOUBLE CIRCULAR STEEL REINFORCED PIPE, TWO AREAS ARE SHOWN. THE GREATER AREA IS FOR THE INNER CAGE STEEL AND LESSER AREA IS FOR OUTER CAGE STEEL. 5) FOR PIPE SIZES GREATER THAN 48 DIAMETER, USE TYPE A STANDARD INSTALLATION DESIGN TABLES 6) H = DESIGN FILL HEIGHT, FT. 7) SUBSTITUTION OF PIPES UNDER FILLS OF 3-0 OR LESS IS PERMITTED ONLY WITH DESIGNER APPROVAL. 8) USE PAIDD SOFTWARE ONLY FOR PIPE DESIGNS NOT PROVIDED BY BD-636M. 9) STEEL AREAS SPECIFIED IN THE FILL HEIGHT / STEEL AREA TABLES ARE TO BE ACHIEVED USING ONE LAYER OF REINFORCEMENT FOR EACH CAGE. TWO LAYERS MAY BE SUBSTITUTED FOR ONE LAYER, PROVIDED THE SUM OF THE STEEL AREAS OF THE 2 LAYERS IS EQUAL TO THE AREAS OF STEEL FOR THE SINGLE LAYER CAGE. WHEN SUBSTITUTING, SPACING OF REINFORCEMENT IS TO REMAIN THE SAME. DESIGNING FOR 2 LAYERS OF REINFORCEMENT AND PROVIDING ONE LAYER OF REINFORCEMENT OF EQUIVALENT AREA IS NOT PERMITTED. DESIGN TABLE FOR CIRCULAR PIPES 37
40 - TYPE B STANDARD INSTALLATION 38
41 TYPE B STANDARD INSTALLATION FILL HEIGHT (FT.) PROOF TEST LOAD (lb./lf/ft. OF DIAMETER) DIA (in.) 1.0 H < H < 2 2 H < 3 3 H < 7 7 H < H < H < H < H < H < H < H < H < H < H < H < NOTE: THESE PROOF LOADS INCLUDE A FACTOR OF SAFETY OF 1.43 FOR FIELD CRACK CONTROL. LEGEND: = FOR INFORMATION ONLY. PROOF LOAD TEST MUST BE PERFORMED TO THE MAXIMUM PROOF TEST LOAD FOR THE RANGE OF ITEM NUMBER. NOTES: 8) ELLIPTICAL REINFORCING IS NOT ALLOWED, EXCEPT FOR QUADRANT REINFORCEMENT AND FOR REINFORCEMENT OF ELLIPTICAL PIPE. 9) FOR DOUBLE CIRCULAR STEEL REINFORCED PIPE, TWO AREAS ARE SHOWN. THE GREATER AREA IS FOR THE INNER CAGE STEEL AND LESSER AREA IS FOR OUTER CAGE STEEL. 10) FOR PIPE SIZES GREATER THAN 48 DIAMETER, USE TYPE B STANDARD INSTALLATION DESIGN TABLES. 11) H = DESIGN FILL HEIGHT, FT. 12) SUBSTITUTION OF PIPES UNDER FILLS OF 3-0 OR LESS IS PERMITTED ONLY WITH DESIGNER APPROVAL. 13) USE PAIDD SOFTWARE ONLY FOR PIPE DESIGNS NOT PROVIDED BY BD-636M. 14) STEEL AREAS SPECIFIED IN THE FILL HEIGHT / STEEL AREA TABLES ARE TO BE ACHIEVED USING ONE LAYER OF REINFORCEMENT FOR EACH CAGE. TWO LAYERS MAY BE SUBSTITUTED FOR ONE LAYER, PROVIDED THE SUM OF THE STEEL AREAS OF THE 2 LAYERS IS EQUAL TO THE AREA OF STEEL FOR THE SINGLE LAYER CAGE. WHEN SUBSTITUTING, SPACING OF REINFORCEMENT IS TO REMAIN THE SAME. DESIGNING FOR 2 LAYERS OF REINFORCEMENT AND PROVIDING ONE LAYER OF REINFORCEMENT OF EQUIVALENT AREA IS NOT PERMITTED. PROOF TEST LOAD TABLE FOR CIRCULAR PIPES - TYPE B STANDARD INSTALLATION 39
42 TYPE B SHORING/TRENCH BOX INSTALLATION Fill Height/Steel Areas Dia. Wall Thick. f c (psi) H< H<2 2 H<3 3 H<7 7 H< ¾ ¼ ½ ¼ ¾ ½ ¾ ¼ ½ 4000 ** ¼ 4000 ** ¾ 4000 ** ½ 4000 ** NOTES: NO SHORING IS REQUIRED NO SHORING IS REQUIRED 1. *INDICATES SAME STEEL AREA AS SHOWN FOR THE LESSER CONCRETE STRENGTH. 2. **INDICATES A SPECIAL DESIGN IS REQUIRED. USE PAIDD SOFTWARE. 3. ELLIPTICAL REINFORCING IS NOT ALLOWED, EXCEPT FOR QUADRANT REINFORCEMENT AND REINFORCEMENT OF ELLIPTICAL PIPE. 4. FOR DOUBLE CIRCULAR STEEL REINFORCED PIPE, TWO AREAS ARE SHOWN. THE GREATER AREA IS FOR INNER CAGE STEEL AND LESSER AREA IS FOR OUTER CAGE STEEL. 5. FOR PIPE DIAMETERS GREATER THAN 48, USE TYPE A SHORING / TRENCH BOX DESIGN TABLES. 6. FOR FILL HEIGHTS GREATER THAN INDICATED, USE THE PAIDD PROGRAM. 7. H = DESIGN FILL HEIGHT, FT. 8. SUBSTITUTION OF PIPES UNDER FILLS OF 3 0 OR LESS IS PERMITTED ONLY WITH DESIGNER APPROVAL. 9. USE PAIDD SOFTWARE ONLY FOR PIPE DESIGNS NOT PROVIDED BY PUB STEEL AREAS SPECIFIED IN THE FILL HEIGHT / STEEL AREA TABLES ARE TO BE ACHIEVED USING ONE LAYER OF REINFORCEMENT FOR EACH CAGE. TWO LAYERS MAY BE SUBSTITUTED FOR ONE LAYER, PROVIDED THE SUM OF THE STEEL AREAS OF THE 2 LAYERS IS EQUAL TO THE AREA OF STEEL FOR THE SINGLE LAYER CAGE. WHEN SUBSTITUTING, SPACING OF REINFORCEMENT IS TO REMAIN THE SAME. DESIGNING FOR 2 LAYERS OF THE REINFORCEMENT AND PROVIDING ONE LAVER OF REINFORCEMENT OF EQUIVALENT AREA IS NOT PERMITTED. DESIGN TABLE FOR CIRCULAR PIPES - TYPE B SHORING/TRENCH BOX INSTALLATION 40
43 TYPE B SHORING / TRENCH BOX INSTALLATION Fill Height / Steel Areas Dia. Wall Thick. f c (psi) H< H<2 2 H<3 3 H<7 7 H< ** ¾ 4000 ** ** ** ¾ 4000 ** ** ½ 4000 ** ** ¼ 4000 ** ** ** ** ¾ 4000 ** ** NOTES: 1) * INDICATES SAME STEEL AREA AS SHOWN FOR THE LESSER CONCRETE STRENGTH. 2) **INDICATES A SPECIAL DESIGN IS REQUIRED. USE PAIDD SOFTWARE. 3) ELLIPTICAL REINFORCING IS NOT ALLOWED, EXCEPT FOR QUADRANT REINFORCEMENT AND REINFORCEMENT OF ELLIPTICAL PIPE. 4) FOR DOUBLE CIRCULAR STEEL REINFORCED PIPE, TWO AREAS ARE SHOWN. THE GREATER AREA IS FOR THE INNER CAGE STEEL AND LESSER AREA IS FOR OUTER CAGE STEEL. 5) FOR PIPE DIAMETERS GREATER THAN 48, USE TYPE A SHORING/TRENCH BOX DESIGN TABLES. 6) FOR FILL HEIGHTS GREATER THAN INDICATED, USE THE PAIDD PROGRAM. 7) H = DESIGN FILL HEIGHT, FT. 8) SUBSTITUTION OF PIPES UNDER FILLS OF 3-0 OR LESS IS PERMITTED ONLY WITH DESIGNER APPROVAL. 9) USE PAIDD SOFTWARE ONLY FOR PIPE DESIGNS NOT PROVIDED BY PUB ) STEEL AREAS SPECIFIED IN THE FILL HEIGHT / STEEL AREA TABLES ARE TO BE ACHIEVED USING ONE LAYER OF REINFORCEMENT FOR EACH CAGE. TWO LAYERS MAY BE SUBSTITUTED FOR ONE LAYER, PROVIDED THE SUM OF THE STEEL AREAS OF THE 2 LAYERS IS EQUAL TO THE AREA OF STEEL FOR THE SINGLE LAYER CAGE. WHEN SUBSTITUTING, SPACING OF REINFORCEMENT IS TO REMAIN THE SAME. DESIGNING FOR 2 LAYERS OF REINFORCEMENT AND PROVIDING ONE LAYER OF REINFORCEMENT OF EQUIVALENT AREA IS NOT PERMITTED. DESIGN TABLE FOR CIRCULAR PIPES - TYPE B SHORING/TRENCH BOX INSTALLATION 41
44 FILL DIA. TYPE B SHORING / TRENCH BOX INSTALLATION FILL HEIGHT / PROOF TEST LOAD ( LBS/LF/FT.OF DIAMETER) 1.5 H<2 2 H<3 3 H<7 7 H<10 10 H<15 15 H<20 20 H< NOTE: THESE PROOF LOADS INCLUDE A 1.43 SAFETY FACTOR FOR FIELD CRACK CONTROL. NOTES: 1) * INDICATES SAME STEEL AREA AS SHOWN FOR THE LESSER CONCRETE STRENGTH. 2) * INDICATES A SPECIAL DESIGN IS REQUIRED. USE PAIDD SOFTWARE 3) * ELLIPTICAL REINFORCING IS NOT ALLOWED, EXCEPT FOR QUADRANT REINFORCEMENT AND REINFORCEMENT OF ELLIPTICAL PIPE. 4) FOR DOUBLE CIRCULAR STEEL REINFORCEMENT PIPE, TWO AREAS ARE SHOWN. THE GREATER AREA IS FOR THE INNER CAGE STEEL AND LESSER AREA IS FOR OUTER CAGE STEEL. 5) FOR PIPE DIAMETERS GREATER THAN 48, USE TYPE A SHORING/TRENCH BOX DESIGN TABLES. 6) FOR FILL HEIGHTS GREATER THAN INDICATED, USE THE PAIDD PROGRAM. 7) H = DESIGN FILL HEIGHT, FT. 8) SUBSTITUTION OF PIPES UNDER FILLS OF 3-0 OR LESS IS PERMITTED ONLY WITH DESIGNER APPROVAL. 9) USE PAIDD SOFTWARE ONLY FOR PIPE DESIGNS NOT PROVIDED BY PUB ) STEEL AREAS SPECIFIED IN THE FILL HEIGHT/STEEL AREA TABLES ARE TO BE ACHIEVED USING ONE LAYER OF THE REINFORCEMENT FOR EACH CAGE. TWO LAYERS MAY BE SUBSTITUTED FOR ONE LAYER, PROVIDED THE SUM OF THE STEEL AREAS OF THE 2 LAYERS IS EQUAL TO THE AREA OF STEEL FOR THE SINGLE LAYER CAGE, WHEN SUBSTITUTING, SPACING OF REINFORCEMENT AND PROVIDING ONE LAYER OF REMAIN THE SAME. DESIGNING FOR 2 LAYERS OF REINFORCEMENT AND PROVIDING ONE LAYER OF REINFORCEMENT OF EQUIVALENT AREA IS NOT PERMITTED. = FOR. INFORMATION ONLY PROOF LOAD TEST MUST BE PERFORMED TO THE MAXIMUM PROOF TEST LOAD FOR THE RANGE OF ITEM NUMBER. PROOF TEST LOAD TABLE FOR CIRCULAR PIPES - TYPE B SHORING/TRENCH BOX INSTALLATION 42
45 TYPE A SHORING/TRENCH BOX Fill Height/Steel Area Dia. Wall f c Thick. (psi) H H<2 2 H<3 3 H<7 7 H< ¾ ¼ ½ ¼ ¾ ½ ¾ ¼ ½ 4000 ** ¼ 4000 ** ¾ 4000 ** ½ 4000 ** ** ¾ 4000 ** ** ** ¾ 4000 ** ** ½ 4000 ** ** ¼ 4000 ** ** NOTES: 1) * INDICATES SAME STEEL AREA AS SHOWN FOR THE LESSER CONCRETE STRENTH. 2) ** INDICATES A SPECIAL DESIGN IS REQUIRED. USE PAIDD SOFTWARE. 3) ELLIPTICAL REINFORCING IS NOT ALLOWED, EXCEPT FOR QUADRANT REINFORCEMENT AND REINFORCEMENT OF ELLIPTICAL PIPE. 4) FOR DOUBLE CIRCULAR STEEL REINFORCED PIPE, TWO AREAS ARE SHOWN. THE GREATER AREA IS FOR THE INNER CAGE STEEL AND LESSER AREA IS FOR OUTER CAGE STEEL. 5) FOR PIPE DIAMETERS GREATER THAN 48, USE TYPE A SHORING/TRENCH BOX DESIGN TABLES 6) FOR FILL HEIGHTS GREATER THAN INDICATED, USE THE PAIDD PROGRAM. 7) H = DESIGN FILL HEIGHT, FT. 8) SUBSTITUTION OF PIPES UNDER FILLS OF 3-0 OR LESS IS PERMITTED ONLY WITH DESIGNER APPROVAL. 9) USE PAIDD SOFTWARE ONLY FOR PIPE DESIGNS NOT PROVIDED BY PUB ) STEEL AREAS SPECIFIED IN THE FILL HEIGHT/STEEL AREA TABLES ARE TO BE ACHIEVED USING ONE LAYER OF THE REINFORCEMENT FOR EACH CAGE. TWO LAYERS MAY BE SUBSTITUTED FOR ONE LAYER, PROVIDED THE SUM OF THE STEEL AREAS OF THE 2 LAYERS IS EQUAL TO THE AREA OF STEEL FOR THE SINGLE LAYER CAGE, WHEN SUBSTITUTING, SPACING OF REINFORCEMENT AND PROVIDING ONE LAYER OF REMAIN THE SAME. DESIGNING FOR 2 LAYERS OF REINFORCEMENT AND PROVIDING ONE LAYER OF REINFORCEMENT OF EQUIVALENT AREA IS NOT PERMITTED. NO SHORING IS REQUIRED NO SHORING IS REQUIRED DESIGN TABLE FOR CIRCULAR PIPES 43
46 - TYPE A SHORING/TRENCH BOX INSTALLATION TYPE A SHORING/TRENCH BOX Fill Height/Steel Areas Dia. Wall f c Thick. (psi) H< H<2 2 H<3 3 H<7 7 H< ** ** ¾ 4000 ** ** ½ 4000 ** ** ¼ 4000 ** ** ** ** ¾ 4000 ** ** ½ 4000 ** ** ¼ 4000 ** ** ** ** ** ** 5000 ** * * * * 0.76 ** * * * * ¾ 4000 ** ** ½ 4000 ** ** ** ** 5000 ** * * * * 0.86 ** * * * * ¼ 4000 ** ** NOTES: 1) * INDICATES SAME STEEL AREA AS SHOWN FOR THE LESSER CONCRETE STRENGTH. 2) ** INDICATES A SPECIAL DESIGN IS REQUIRED. USE PAIDD SOFTWARE. 3) ELLIPTICAL REINFORCING IS NOT ALLOWED, EXCEPT FOR QUADRANT REINFORCEMENT AND REINFORCEMENT OF ELLIPTICAL PIPE. 4) FOR DOUBLE CIRCULAR STEEL REINFORCED PIPE, TWO AREAS ARE SHOWN. THE GREATER AREA IS FOR INNER CAGE STEEL AND LESSER AREA IS FOR OUTER CAGE STEEL. 5) FOR PIPE DIAMETERS GREATER THAN 48, USE TYPE A SHORING/TRENCH BOX DESIGN TABLES. 6) FOR FILL HEIGHTS GREATER THAN INDICATED, USE THE PAIDD PROGRAM. 7) H = DESIGN FILL HEIGHT, FT. 8) SUBSTITUTION OF PIPES UNDER FILLS OF 3-0 OR LESS IS PERMITTED ONLY WITH DESIGNER APPROVAL. 9) USE PAIDD SOFTWARE ONLY FOR PIPE DESIGNS NOT PROVIDED BY BD ) STEEL AREAS SPECIFIED IN THE FILL HEIGHT / STEEL AREAS TABLES ARE TO BE ACHIEVED USING ONE LAYER OF REINFORCEMENT FOR EACH CAGE. TWO LAYERS MAY BE SUBSTITUTED FOR ONE LAYER, PROVIDED THE SUM OF THE STEEL AREAS OF THE 2 LAYERS IS EQUAL TO THE AREA OF STEEL FOR THE SINGLE LAYER CAGE. WHEN SUBSTITUTING, SPACING OF REINFORCEMENT IS TO REMAIN THE SAME. DESIGNING FOR 2 LAYERS OF REINFORCEMENT AND PROVIDING ONE LAYER OF REINFORCEMENT OF EQUIVALENT AREA IS NOT PERMITTED. 44
47 DESIGN TABLE FOR CIRCULAR PIPES - TYPE A SHORING/TRENCH BOX INSTALLATION 45
48 TYPE A SHORING / TRENCH BOX Fill Height / Steel Areas Dia. Wall f c Thick. (psi) H< H<2 2 H<3 3 H<7 7 H< ** ** ** ** 6000 ** * * * * 0.90 ** * * * * ¾ 4000 ** ** ** ** 5000 ** * * * * 0.82 ** * * * * ½ 4000 ** ** ** ** 6000 ** * * * * 1.01 ** * * * * ¼ 4000 ** ** ** ** 5000 ** * * * * 0.94 ** * * * * ** ** ** ** ** ** 5000 ** * * * 0.88 ** ** * * * 0.30 ** 96 9 ¾ 4000 ** ** ** ** 6000 ** * * * * 0.95 ** * * * * ½ 4000 ** ** ** ** ** ** 5000 ** * * * 0.97 ** ** * * * 0.33 ** ¼ 4000 ** ** ** ** ** ** 5000 ** * * * 0.83 ** ** * * * 0.30 ** NOTES 1) * INDICATES SAME STEEL AREA AS SHOWN FOR THE LESSER CONCRETE STRENGTH. 2) ** INDICATES A SPECIAL DESIGN IS REQUIRED. USE PAIDD SOFTWARE. 3) ELLIPTICAL REINFORCING IS NOT ALLOWED, EXCEPT FOR QUADRANT REINFORCEMENT AND REINFORCEMENT OF ELLIPTICAL PIPE. 4) FOR DOUBLE CIRCULAR STEEL REINFORCED PIPE, TWO AREAS ARE SHOWN. THE GREATER AREA IS FOR THE INNER CAGE STEEL AND LESSER AREA IS FOR OUTER CAGE STEEL. 5) FOR PIPE DIAMETERS GREATER THAN 48, USE TYPE A SHORTING/TRENCH BOX DESIGN TABLES. 6) FOR FILL HEIGHTS GREATER THAN INDICATED, USE THE PAIDD PROGRAM. 7) H = DESIGN FILL HEIGHT, FT. 8) SUBSTITUTION OF PIPES UNDER FILLS OF 3-0 OR LESS IS PERMITTED ONLY WITH DESIGNER APPROVAL. 9) USE PAIDD SOFTWARE ONLY FOR PIPE DESIGNS NOT PROVIDED BY BD ) STEEL AREAS SPECIFIED IN THE FILL HEIGHT/STEEL AREA TABLES ARE TO BE ACHIEVED USING ONE LAYER OF REINFORCEMENT FOR EACH CAGE. TWO LAYERS MAY BE SUBSTITUTED FOR ONE LAYER OF REINFORCEMENT FOR EACH CAGE. TWO LAYERS MAY BE SUBSTITUTED FOR ONE LAYER, PROVIDED THE SUM OF THE STEEL AREAS OF THE 2 LAYERS IS EQUAL TO THE AREA OF STEEL FOR THE SINGLE LAYER CAGE. WHEN SUBSTITUTING, SPACING OF REINFORCEMENT IS TO REMAIN THE SAME. DESIGNING FOR THE 2 LAYERS OF REINFORCEMENT AND PROVIDING ONE OF REINFORCEMENT OF EQUIVALENT AREA IS NOT PERMITTED. DESIGN TABLE FOR CIRCULAR PIPES - TYPE A SHORING/TRENCH BOX INSTALLATION 46
49 47
50 TYPE A SHORING/TRENCH BOX Fill Height/Steel Areas Dia. Wall Thick. f c H< H<2 2 H<3 3 H<7 7 H ** *** ** ** * ** 6000 ** * * * 1.00 ** * * * ¾ 4000 ** ** ** ** 5000 ** * * * 0.93 ** * * * ½ 4000 ** *** ** ** * ** * * * 1.11 ** * * * ¼ 4000 ** ** ** ** 5000 ** * * * 1.06 ** * * * ** 0.75 ** *** ** ** 0.29 ** * ** 5000 ** * 0.72 * ** ** * 0.30 * ** 6000 ** * * * 1.22 ** * * * ¾ 4000 ** ** ** ** 6000 ** * * * 1.07 ** * * * 0.38 NOTES: 1) * INDICATES SAME STEEL AREA AS SHOWN FOR THE LESSER CONCRETE STRENGTH. 2) ** INDICATES A SPECIAL DESIGN IS REQUIRED. USE PAIDD SOFTWARE. 3) ELLIPTICAL REINFORCING IS NOT ALLOWED, EXCEPT FOR QUADRANT REINFORCEMENT AND REINFORCEMENT OF ELLIPTICAL PIPE. 4) FOR DOUBLE CIRCULAR STEEL REINFORCED PIPE, TWO AREAS ARE SHOWN. THE GREATER AREA IS FOR THE INNER CAGE STEEL AND LESSER AREA IS FOR OUTER CAGE STEEL. 5) FOR PIPE DIAMETERS GREATER THAN INDICATED, USE TYPE A SHORING/TRENCH BOX DESIGN TABLES. 6) FOR FILL HEIGHTS GREATER THAN INDICATED, USE THE PAIDD PROGRAM. 7) H = DESIGN FILL HEIGHT, FT. 8) SUBSTITUTION OF PIPES UNDER FILLS OF 3-0 OR LESS IS PERMITTED ONLY WITH DESIGNER APPROVAL. 9) USE PAIDD SOFTWARE ONLY FOR PIPE DESIGNS NOT PROVIDED BY PUB ) STEEL AREAS SPECIFIED IN THE FILL HEIGHT/STEEL AREA TABLES ARE TO BE ACHIEVED USING ONE LAYER OF REINFORCEMENT FOR EACH CAGE. TWO LAYERS MAY BE SUBSTITUTED FOR ONE LAYER PROVIDED THE SUM OF THE STEEL AREAS OF THE 2 LAYERS IS EQUAL TO THE AREA OF STEEL FOR THE SAME SINGLE LAYER CAGE. WHEN SUBSTITUTING, SPACING FOR REINFORCEMENT IS TO REMAIN THE SAME DESIGNING FOR 2 LAYERS OF REINFORCEMENT AND PROVIDING ONE LAYER OF REINFORCEMENT OF EQUIVALENT AREA IS NOT PERMITTED. - FOR INFORMATION ONLY, PROOF LOAD TEST MUST BE PERFORMED TO THE MAXIMUM PROOF TEST LOAD FOR THE RANGE OF ITEM NUMBER. DESIGN TABLE FOR CIRCULAR PIPES -TYPE A SHORING/TRENCH BOX INSTALLATION 48
51 TYPE A SHORING/TRENCH BOX INSTALLATION FILL HEIGHT/PROOF TEST LOAD (lbs/lf/ft. OF DIAMETER) DIA. 1.5 H<2 2 H<3 3 H<7 7 H<10 10 H<15 15 H<20 20 H< NOTE: THESE PROOF LOADS INCLUDE A 1.43 SAFETY FACTOR FOR FIELD CRACK CONTROL. PROOF TEST LOAD TABLE FOR CIRCULAR PIPES - TYPE A SHORING/TRENCH BOX INSTALLATION (SEE NOTES, PAGE 43) 49
52 Eguivalent Round Rise /Span TYPE A SHORING/TRENCH BOX VERTICAL ELLIPTICAL PIPE Fill Height / Steel Areas Wall Thick. f c (psi) H<1.5 5 H<2 2 H<3 3 H<7 7 H< x29 4 ½ 4000 ** ** x ** ** x38 5 ½ 4000 ** ** x ** ** ** ** 5000 ** * * * * * * 0.30 ** * * * * * * x48 6 ½ 4000 ** ** ** ** 5000 ** * * * * * * 0.34 * * * * * * x ** ** ** ** 5000 ** * * * * * * 0.39 ** * * * * * * x58 7 ½ 4000 ** ** ** ** ** ** 5000 ** * * * * * ** * * * * * x ** ** ** ** ** ** 5000 ** * * * * * ** * * * * * x68 8 ½ 4000 ** ** ** ** ** ** 5000 ** * * * * * 0.45 ** ** * * * * * 0.20 ** 6000 ** * * * * * * 0.53 ** * * * * * * x ** ** ** ** ** ** 5000 ** * * * * * 0.48 ** ** * * * * * 0.21 ** 6000 ** * * * * * * 0.56 ** * * * * * * x77 9 ½ 4000 ** ** ** ** ** ** 5000 ** * * * * * 0.52 ** ** * * * * * 0.23 ** 6000 ** * * * * * * 0.61 ** * * * * * * x82 9 ¾ 4000 ** ** ** ** ** ** ** ** 5000 ** * * * * ** ** * * * * ** 6000 ** * * * * * * 0.73 ** * * * * * * x ** * ** ** ** * ** ** 5000 ** * * * * ** ** * * * * ** 6000 ** * * * * * * 0.86 ** * * * * * * x92 10 ½ 4000 ** ** ** ** ** ** ** ** 5000 ** * * * * 0.57 ** ** ** * * * * 0.25 ** ** 6000 ** * * * * * 0.69 ** ** * * * * * 0.30 ** x ** * ** ** ** * ** ** 5000 ** * * * * 0.61 ** ** ** * * * * 0.27 ** ** 6000 ** * * * * * 0.76 ** ** * * * * * 0.32 ** DESIGN TABLE FOR VERTICAL ELLIPTICAL PIPES - TYPE A SHORING / TRENCH BOX INSTALLATION (SEE NOTES, NEXT PAGE) - 50
53 PROOF TEST LOAD TABLE FOR VERTICAL ELLIPTICAL PIPE TYPE A SHORING TRENCH BOX INSTALLATION ( lbs/lf/ft. of DIAMETER) FILL HEIGHT / PROOF TEST LOADS Equivalent Rise 1.5 H<2 2 H<3 3 H 7 7<H 10 10<H 15 15<H 20 20<H 25 Round / Span 36 14x x x x x x x x x x x x x x x NOTES: 1) * INDICATES SAME STEEL AREA AS SHOWN FOR THE LESSER CONCRETE STRENGTH. 2) ** INDICATES A SPECIAL DESIGN IS REQUIRED. USE PAIDD SOFTWARE. 3) ELLIPTICAL REINFORCING IS NOT ALLOWED, EXCEPT FOR QUADRANT REINFORCEMENT AND ELLIPTICAL PIPE. 4) FOR DOUBLE CIRCULAR STEEL REINFORCED PIPE. TWO AREAS ARE SHOWN. THE GRATER AREA IS FOR INNER CAGE STEEL AND LESSER AREA IS FOR OUTER CAGE STEEL. 5) *** INDICATES A SHEAR CONTROL HAS BEEN REACHED. USE PAIDD SOFTWARE FOR SPECIAL DESIGN. 6) H = DESIGN FILL HEIGHT, FT. 7) SUBSTITUTION OF PIPES UNDER FILLS OF 3-0 OR LESS IS PERMITTED ONLY WITH DESIGNER APPROVAL. 8) FOR DESIGN OF A TYPE A STANDARD ELLIPTICAL PIPE FOLLOW THESE STEPS: a) SELECT THE LARGER DIMENSION OF SPAN OR RISE FROM ELLIPTICAL PIPE SIZES SHOWN IN THE TYPE A SHORING/TRENCH BOX TABLE FOR ELLIPTICAL PIPES. I.E. RISE DIMENSION FOR VERTICAL ELLIPTICAL SPAN DIMENSION FOR HORIZONTAL ELLIPTICAL. b) GO TO TYPE A STANDARD INSTALLATION TABLES FOR CIRCULAR PIPES. c) USE THE RISE DIMENSION FOR VERTICAL ELLIPTICAL DESIGNS OR THE SPAN DIMENSION FOR THE HORIZONTAL ELLIPTICAL DESIGNS AS THE DIAMETER IN THE TYPE A STANDARD INSTALLATION TABLES FOR CIRCULAR PIPE. ( IF THE SELECTED DIAMETER IS NOT AVAILABLE IN THE TYPE A STANDARD INSTALLATION TABLES FOR CIRCULAR PIPE, USE THE NEXT LARGER AVAILABLE DIAMETER IN THE TYPE A STANDARD INSTALLATION TABLES FOR CIRCULAR PIPE TO DETERMINE THE STEEL AREAS.) d) FOR THE SELECTED DIAMETER, WALL THICKNESS, DESIGN FILL HEIGHT AND CONCRETE STRENGTH, DETERMINE THE AREA OF STEEL REQUIRED FOR THE INNER CAGE OF THE PIPE IN THE TYPE A STANDARD INSTALLATION TABLES FOR CIRCULAR PIPES. USE THIS AREA FOR EACH, INNER AND OUTER, CAGE FOR THE ELLIPTICAL PIPE DESIGN 9) USE PAIDD SOFTWARE ONLY FOR PIPE DESIGNS NOT PROVIDED BY PUB ) STEEL AREAS SPECIFIED IN THE HEIGHT/STEEL AREA TO BE ACHIEVED USING ONE LAYER OF REINFORCEMENT FOR EACH CAGE. TWO LAYERS MAY BE SUBSTITUTED FOR ONE LAYER PROVIDED THE SUM OF THE STEEL AREAS OF THE 2 LAYERS EQUAL TO THE AREA OF REMAIN THE SAME. DEIGNING FOR 2 LAYERS OF REINFORCEMENT AND PROVIDING ONE LAYER OF REINFORCEMENT OF EQUIVALENT AREA IS NOT PERMITTED. PROOF TEST LOAD TABLE FOR VERTICAL PIPES - TYPE A SHORING / TRENCH BOX INSTALLATION 51
54 TYPE A SHORING/TRENCH BOX HORIZONTAL ELLIPTICAL PIPE Equivalent Wall f c Fill Height/Steel Areas Rise/Span Round Thick. (psi) H< H<2 2 H<3 3 H<7 7 H< x23 2 ¾ 4000 ** x30 3 ¼ 4000 ** x34 3 ½ 4000 ** x38 3 ¾ 4000 ** ** x42 3 ¾ 4000 ** ** x45 4 ½ 4000 ** ** x ** ** x60 5 ½ 4000 ** ** x ** ** x76 6 ½ 4000 ** ** ** ** 5000 ** * * * 0.81 ** * * * x ** ** ** ** 5000 ** * * * 0.94 ** * * * x91 7 ½ 4000 ** ** ** ** 6000 ** * * * 1.03 ** * * * x ** ** ** ** ** ** 5000 ** * * 0.98 ** ** * * 0.98 ** 6000 ** * * * 1.16 ** * * * x106 8 ½ 4000 ** ** ** ** ** ** 6000 ** * * 1.07 ** ** * * 1.07 ** 90 72x ** ** ** ** ** ** 96 77x121 9 ½ 4000 ** 1.06 ** ** ** ** 1.06 ** ** ** 5000 ** * 1.04 ** ** ** * 1.04 ** ** 7000 ** * * 1.31 ** ** * * 1.31 ** x128 9 ¾ 5000 ** ** *** ** ** *** 6000 ** * * 1.52 *** ** * * 1.52 *** x ** 1.32 ** ** *** ** 1.32 ** ** *** 6000 ** * 1.33 ** *** ** * 1.33 ** *** x ½ 5000 ** 1.43 ** ** *** ** 1.43 ** ** *** 6000 ** * 1.44 ** *** ** * 1.44 ** *** x ** ** ** ** *** ** ** ** ** *** DESIGN TABLE FOR HORIZONTAL ELLIPTICAL PIPES -TYPE A SHORING/TRENCH BOX INSTALLATION (SEE NOTES, NEXT PAGE) 52
55 PROOF TEST LOAD TABLE FOR HORIZONTAL ELLIPTICAL PIPE TYPE A SHORING TRENCH BOX INSTALLATION ( lbs/lf/ft. of DIAMETER) FILL HEIGHT / PROOF TEST LOADS Equivalent Round Rise / Span 1.5 H<2 2 H<3 3 H<7 7 H<10 10 H<15 15 H<20 20 H< x x x x x x x x x x x x x x x x x x x x NOTES: 1) * INDICATES SAME STEEL AREA AS SHOWN FOR THE LESSER CONCRETE STRENGTH. 2) ** INDICATES A SPECIAL DESIGN IS REQUIRED. USE PAIDD SOFTWARE. 3) ELLIPTICAL REINFORCING IS NOT ALLOWED, EXCEPT FOR QUADRANT REINFORCEMENT AND REINFORCEMENT OF ELLIPTICAL PIPE. 4) FOR DOUBLE CIRCULAR STEEL REINFORCED PIPE, TWO AREAS ARE SHOWN. THE GREATER AREA IS FOR INNER CAGE STEEL AND LESSER AREA IS FOR OUTER CAGE STEEL. 5) *** INDICATES A SHEAR CONTROL HAS BEEN REACHED. USE PAIDD SOFTWARE FOR SPECIAL DESIGN. 6) H = DESIGN FILL HEIGHT, FT. 7) SUBSTITUTION OF PIPES UNDER FILLS OF 3-0 OR LESS IS PERMITTED ONLY WITH DESIGNER APPROVAL. 8) FOR DESIGN OF A TYPE A STANDARD ELLIPTICAL PIPE FOLLOW THESE STEPS: (a) SELECT THE LARGER DIMENSION OF SPAN OR RISE FROM ELLIPTICAL PIPE SIZE SHOWN IN THE TYPE A SHORING/TRENCH BOX TABLE FOR ELLIPTICAL PIPES. (I.E. RISE DIMENSION FOR VERTICAL ELLIPTICAL SPAN DIMENSION FOR HORIZONTAL ELLIPTICAL) (b) (c) GO TO TYPE A STANDARD INSTALLATION TABLES FOR CIRCULAR PIPES. USE THE RISE DIMENSION FOR VERTICAL ELLIPTICAL DESIGNS OF THE SPAN DIMENSION FOR THE HORIZONTAL ELLIPTICAL DESIGNS AS THE DIAMETER IN THE TYPE A STANDARD INSTALLATION TABLES FOR CIRCULAR PIPE. ( IF THE SELECTED DIAMETER IS NOT AVAILABLE IN THE TYPE A STANDARD INSTALLATION TABLES FOR CIRCULAR PIPE, USE THE NEXT LARGER AVAILABLE DIAMETER IN THE TYPE A STANDARD INSTALLATION TABLES FOR CIRCULAR PIPE TO DETERMINE THE STEEL AREA. ) (d) FOR THE SELECTED DIAMETER, WALL THICKNESS, DESIGN FILL HEIGHT AND CONCRETE STRENGTH, DETERMINE THE AREA OF STEEL REQUIRED FOR THE INNER CAGE OF THE PIPE IN THE TYPE A STANDARD INSTALLATION TABLES FOR CIRCULAR PIPES. USE THIS AREA FOR EACH, INNER AND OUTER, CAGE FOR THE ELLIPTICAL PIPE DESIGN. 9) USE PAIDD SOFTWARE ONLY FOR PIPE DESIGNS NOT PROVIDED BY PUB ) STEEL AREAS SPECIFIED IN THE FILL HEIGHT / STEEL AREA TABLES ARE TO BE ACHIEVED USING ONE LAYER OF REINFORCEMENT FOR EACH CAGE. TWO LAYERS MAY BE SUBSTITUTED FOR ONE LAYER, PROVIDED THE SUM OF THE STEEL AREAS OF THE 2 LAYERS IS EQUAL TO THE AREA OF STEEL FOR THE SINGLE LAYER CAGE. WHEN SUBSTITUTION, SPACING OF THE REINFORCEMENT IS TO REINFORCEMENT OF EQUIVALENT AREA IS NOT PERMITTED. PROOF TEST LOAD TABLE FOR HORIZONTAL ELLIPTICAL PIPES -TYPE A SHORING / TRENCH BOX INSTALLATION 53
56 TYPE B SHORING/TRENCH BOX VERTICAL ELLIPTICAL PIPE Fill Height / Steel Areas Equivalent Round Rise /Span Wall Thick. f c (psi) H< H<2 2 H<3 3 H<7 7 H< x29 4 ½ 4000 ** ** x ** ** x38 5 ½ 4000 ** ** x ** ** x48 6 ½ 4000 ** ** x ** ** ** ** 5000 ** * * * * * * 0.61 ** * * * * * * x58 7 ½ 4000 ** ** ** ** 6000 ** * * * * * * 0.74 ** * * * * * * x ** ** ** ** 6000 ** * * * * * * 0.71 ** * * * * * * x68 8 ½ 4000 ** ** ** ** ** ** 5000 ** * * * * * 0.63 ** ** * * * * * 0.32 ** 6000 ** * * * * * * 0.81 ** * * * * * * x ** ** ** ** ** ** 5000 ** * * * * * 0.71 * ** * * * * * 0.36 * x77 9 ½ 4000 ** ** ** ** ** ** 5000 ** * * * * * 0.83 * ** * * * * * 0.42 * x82 9 ¾ 4000 ** ** ** ** ** ** 6000 ** * * * * * 0.53 ** ** * * * * * 0.42 ** x ** ** ** ** ** ** ** ** 5000 ** * * * * 0.72 * ** ** * * * * 0.36 * ** x92 10 ½ 4000 ** ** ** ** ** ** ** ** 5000 ** * * * * 0.80 * ** ** * * * * 0.40 * ** x ** ** ** ** ** ** ** ** 5000 ** * * * * 0.90 * ** ** * * * * 0.45 * ** DESIGN TABLE FOR VERTICAL ELLIPTICAL PIPES - TYPE B SHORING/TRENCH BOX INSTALLATION (SEE NOTES, NEXT PAGE) 54
57 PROOF TEST LOAD TABLE FOR VERTICAL ELLIPTICAL PIPE TYPE B SHORING TRENCH-BOX INSTALLATION (lbs/lf/ft. of DIAMETER) FILL HEIGHT/PROOF TEST LOADS Equivalent Round Rise /Span 1.5 H<2 2 H<3 3 H<7 7 H H<15 15 H<20 20 H< x x x x x x x x x x x x x x x NOTES: 1) * INDICATES SAME STEEL AREA AS SHOWN FOR THE LESSER CONCRETE STRENGTH. 2) ** INDICATES A SPECIAL DESIGN IS REQUIRED. USE PAIDD SOFTWARE. 3) ELLIPTICAL REINFORCING IS NOT ALLOWED, EXCEPT FOR QUADRANT REINFORCEMENT AND REINFORCEMENT OF ELLIPTICAL PIPE. 4) FOR DOUBLE CIRCULAR STEEL REINFORCED PIPE, TWO AREAS SHOWN. THE GREATER AREA IS FOR INNER CAGE STEEL AND LESSER AREA IS FOR OUTER CAGE STEEL. 5) *** INDICATES A SHEAR CONTROL HAS BEEN REACHED. USE PAIDD SOFTWARE FOR SPECIAL DESIGN. 6) H = DESIGN FILL HEIGHT, FT. 7) SUBSTITUTION OF PIPES UNDER FILLS OF 3-0 OR LESS IS PERMITTED ONLY WITH DESIGNER APPROVAL. 8) FOR DESIGN OF A TYPE A STANDARD ELLIPTICAL PIPE FOLLOW THESE STEPS: (a) SELECT THE LARGER DIMENSION OF SPAN OR RISE FROM ELLIPTICAL PIPE SIZES SHOWN IN THE TYPE A SHORING/TRENCH BOX TABLE FOR ELLIPTICAL PIPES. (I.E. RISE DIMENSION FOR VERTICAL ELLIPTICAL SPAN DIMENSION FOR HORIZONTAL ELLIPTICAL) (b) GO TO TYPE A STANDARD INSTALLATION TABLES FOR CIRCULAR PIPES. (c) USE THE RISE DIMENSION FOR VERTICAL ELLIPTICAL DESIGNS OR THE SPAN DIMENSION FOR THE HORIZONTAL ELLIPTICAL DESIGNS AS THE DIAMETER IN THE TYPE A STANDARD INSTALLATION TABLES FOR CIRCULAR PIPE. [ IF THE SELECTED DIAMETER IS NOT AVAILABLE IN THE TYPE A STANDARD INSTALLATION TABLES FOR CIRCULAR PIPE, USE THE NEXT LARGER AVAILABLE DIAMETER IN THE TYPE A STANDARD INSTALLATION TABLES FOR CIRCULAR PIPE TO DETERMINE THE STEEL AREA.] (d) FOR THE SELECTED DIAMETER, WALL THICKNESS, DESIGN FILL HEIGHT AND CONCRETE STRENGTH, DETERMINE THE AREA OF STEEL REQUIRED FOR THE INNER CAGE OF THE PIPE IN THE TYPE A STANDARD INSTALLATION TABLES FOR CIRCULAR PIPES. USE THIS AREA FOR EACH, INNER AND OUTER, CAGE FOR THE ELLIPTICAL PIPE DESIGN. 9) USE PAIDD SOFTWARE ONLY FOR PIPE DESIGNS NOT PROVIDED BY PUB ) STEEL AREAS SPECIFIED IN THE FILL HEIGHT/STEEL AREA TABLES ARE TO BE ACHIEVED USING ONE LAYER OF REINFORCEMENT FOR EACH CAGE. TWO LAYERS MAY BE SUBSTITUTED FOR ONE LAYER, PROVIDED THE SUM OF THE STEEL AREAS IS EQUAL TO THE AREA OF STEEL FOR THE SINGLE LAYER CAGE. WHEN SUBSTITUTING, SPACING OF REINFORCEMENT IS TO REMAIN THE SAME. DESIGNING FOR 2 LAYERS OF REINFORCEMENT AND PROVIDING ONE LAYER OF REINFORCEMENT OF EQUIVALENT AREA IS NOT PERMITTED. PROOF TEST LOAD TABLE FOR VERTICAL ELLIPTICAL PIPES 55
58 - TYPE B SHORING/TRENCH BOX INSTALLATION 56
59 TYPE B SHORING/TRENCH BOX HORIZONTAL Fill Height/Steel Areas Equivalent Round Rise / Span Wall Thick. f c H< H<2 2 H<3 3 H<7 7 H x23 2 ¾ 4000 ** x30 3 ¼ 4000 ** x34 3 ½ 4000 ** x38 3 ¾ 4000 ** ** x42 3 ¾ 4000 ** ** x45 4 ½ 4000 ** ** x ** ** x60 5 ½ 4000 ** ** x ** ** x76 6 ½ 4000 ** ** x ** ** x91 7 ½ 4000 ** ** x ** ** ** ** ** ** 5000 ** * * 0.93 ** ** * * 0.93 ** 6000 ** * * * 1.10 ** * * * x106 8 ½ 4000 ** ** ** ** ** ** 5000 ** * * 1.08 ** ** * * 1.08 ** 90 72x ** ** ** ** ** ** 6000 ** * * 1.14 ** ** * * 1.14 ** 96 77x121 9 ½ 4000 ** ** ** ** ** ** 6000 ** * * 1.30 ** ** * * 1.30 ** x128 9 ¾ 5000 ** ** ** ** ** ** x ** ** *** ** ** *** x ½ 5000 ** ** *** ** ** *** x ** ** ** ** *** ** ** ** ** *** DESIGN TABLE FOR HORIZONTAL ELLIPTICAL PIPES -TYPE B SHORING/TRENCH BOX INSTALLATION 57
60 PROOF TEST LOAD TABLE FOR HORIZONTAL ELLIPTICAL PIPE TYPE B SHORING TRENCH-BOX INSTALLATION(lbs/LF/FT. of DIAMETER) FILL HEIGHT / PROOF TEST LOADS Equivalent Round Rise /Span 1.5 H<2 2 H<3 3 H<7 7 H<10 10 H<15 15 H<20 20 H< x x x x x x x x x x x x x x x x x x x x NOTES: 1) * INDICATES SAME STEEL AREA AS SHOWN FOR THE LESSER CONCRETE STRENGTH. 2) ** INDICATES A SPECIAL DESIGN IS REQUIRED. USE PAIDD SOFTWARE. 3) ELLIPTICAL REINFORCING IS NOT ALLOWED, EXCEPT FOR QUADRANT REINFORCEMENT AND REINFORCEMENT OF ELLIPTICAL PIPE. 4) FOR DOUBLE CIRCULAR STEEL REINFORCED PIPE, TWO AREAS ARE SHOWN. THE GREATER AREA IS FOR INNER CAGE STEEL AND LESSER AREA IS FOR OUTER CAGE STEEL. 5) *** INDICATES A SHEAR CONTROL HAS BEEN REACHED. USE PAIDD SOFTWARE FOR SPECIAL DESIGN. 6) H = DESIGN FILL HEIGHT, FT. 7) SUBSTITUTION OF PIPE UNDER FILLS OF 3-0 OR LESS IS PERMITTED ONLY WITH DESIGNER APPROVAL. 8) FOR DESIGN OF A TYPE A STANDARD ELLIPTICAL PIPE FOLLOW STEPS: a) SELECT THE LARGER DIMENSION OF SPAN OR RISE FROM ELLIPTICAL PIPE SIZES SHOWN IN THE TYPE A SHORING/TRENCH BOX TABLE FOR ELLIPTICAL PIPES (I.E. RISE DIMENSION FOR VERTICAL ELLIPTICAL SPAN DIMENSION FOR HORIZONTAL ELLIPTICAL) b) GO TO TYPE A STANDARD INSTALLATION TABLES FOR CIRCULAR PIPES. c) USE THE RISE DIMENSION FOR VERTICAL ELLIPTICAL DESIGNS OR THE SPAN DIMENSION FOR THE HORIZONTAL ELLIPTICAL DESIGNS AS THE DIAMETER IN THE TYPE A STANDARD INSTALLATION TABLES FOR CIRCULAR PIPE. ( IF THE SELECTED DIAMETER IS NOT AVAILABLE IN THE TYPE A STANDARD INSTALLATION TABLES FOR CIRCULAR PIPE, USE THE NEXT LARGER AVAILABLE DIAMETER IN THE TYPE A STANDARD INSTALLATION TABLES FOR CIRCULAR PIPE TO DETERMINE THE STEEL AREA.) d) FOR THE SELECTED DIAMETER, WALL THICKNESS, DESIGN FILL HEIGHT AND CONCRETE STRENGTH, DETERMINE THE AREAS OF STEEL REQUIRED FOR THE INNER CAGE OF THE PIPE IN THE TYPE A STANDARD INSTALLATION TABLES FOR CIRCULAR PIPES. USE THIS AREA FOR EACH, INNER AND OUTER, CAGE FOR THE ELLIPTICAL PIPE DESIGN. 9) USE PAIDD SOFTWARE ONLY FOR PIPE DESIGNS NOT PROVIDED BY PUB ) STEEL AREAS SPECIFIED IN THE FILL HEIGHT/STEEL AREA TABLES ARE TO BE ACHIEVED USING ONE LAYER OF REINFORCEMENT FOR EACH CAGE. TWO LAYERS MAY BE SUBSTITUTED FOR ONE LAYER, PROVIDED THE SUM OF THE STEEL AREAS OF THE 2 LAYERS IS EQUAL TO THE AREA OF STEEL FOR THE SINGLE LAYER CAGE. WHEN SUBSTITUTING, SPACING OF REINFORCEMENT IS TO REMAIN THE SAME. DESIGNING FOR 2 LAYERS OF REINFORCEMENT AND PROVIDING ONE LAYER OF REINFORCEMENT OF EQUIVALENT AREA IS NOT PERMITTED. PROOF TEST LOAD TABLE FOR HORIZONTAL ELLIPTICAL PIPES 58
61 - TYPE B SHORING/TRENCH BOX INSTALLATION 59
62 Equivalent Round TYPE A STANDARD INSTALLATION HORIZONTAL ELLIPTICAL PIPE H<1.5 ft. Rise/span Wall Thick. f c (psi) Steel Area (in. 2 ) Proof Test Lbs/ft/ft 18 14x / x / x / x / x / x / x x / x x / x x / x x / x x / x / x x / x Equivalent Round Rise/span TYPE B STANDARD INSTALLATION HORIZONTAL ELLIPTICAL PIPE H<1.5 ft. Wall Thick. f c (psi) Steel Area (in. 2 ) 18 14x / x / x / x / x / x / x x / x x / x x / x x / x x / x / x x / x NOTES: 1) INDICATES A SPECIAL DESIGN IS REQUIRED. USE PAIDD SOFTWARE. 2) ELLIPTICAL REINFORCING IS NOT ALLOWED, EXCEPT FOR QUADRANT REINFORCEMENT AND REINFORCEMENT OF ELLIPTICAL PIPE. 3) FOR DOUBLE CIRCULAR STEEL REINFORCED PIPE, TWO AREAS ARE SHOWN. THE GREATER AREA IS FOR THE INNER CAGE STEEL AND LESSER AREA IS FOR OUTER CAGE. 4) H = DESIGN FILL HEIGHT, mm. 5) SUBSTITUTION OF PIPES UNDER FILLS OF 1000mm OR LESS IS PERMITTED ONLY WITH DESIGNER APPROVAL. 6) FOR DESIGN OF A TYPE A STANDARD ELLIPTICAL PIPE FOLLOW THESE STEPS: a) SELECT THE LARGER DIMENSION OF SPAN OR RISE FROM ELLIPTICAL PIPE SIZES SHOWN IN THE TYPE A SHORING/TRENCH BOX TABLE FOR ELLIPTICAL PIPES. Proof Test Lbs/ft/ft (I.E. RISE DIMENSION FOR VERTICAL ELLIPTICAL SPAN DIMENSION FOR HORIZONTAL ELLIPTICAL) b) GO TO TYPE A STANDARD INSTALLATION TABLES FOR CIRCULAR PIPES. c) USE THE RISE DIMENSION FOR VERTICAL ELLIPTICAL DESIGNS OR THE SPAN DIMENSION FOR THE HORIZONTAL ELLIPTICAL DESIGNS AS THE DIAMETER IN THE TYPE A STANDARD INSTALLATION TABLES FOR CIRCULAR PIPE. [ IF THE SELECTED DIAMETER IS NOT AVAILABLE IN THE TYPE A STANDARD INSTALLATION TABLES FOR CIRCULAR PIPE, USE THE NEXT LARGER AVAILABLE DIAMETER IN THE TYPE A STANDARD INSTALLATION TABLES FOR CIRCULAR PIPE TO DETERMINE THE STEEL AREA. ] d) FOR THE SELECTED DIAMETER, WALL THICKNESS, DESIGN FILL HEIGHT AND CONCRETE STRENGTH, DETERMINE THE AREA OF STEEL REQUIRED FOR THE INNER CAGE OF THE PIPE IN THE TYPE A STANDARD INSTALLATION TABLES FOR CIRCULAR PIPES. USE THIS AREA FOR EACH, INNER AND OUTER, CAGE FOR THE ELLIPTICAL PIPE DESIGN. 7) USE PAIDD SOFTWARE ONLY FOR PIPE DESIGNS NOT PROVIDED BY BD 636M. 8) STEEL AREAS SPECIFIED IN THE FILL HEIGHT / STEEL AREA TABLES ARE TO BE ACHIEVED USING ONE LAYER OF REINFORCEMENT FOR EACH CAGE. TWO LAYERS MAY BE SUBSTITUTED FOR ONE LAYER, PROVIDED THE SUM OF THE STEEL AREAS OF THE 2 LAYERS IS EQUAL TO THE AREA OF STEEL FOR THE SINGLE LAYER CAGE. WHEN SUBSTITUTING, SPACING OF REINFORCEMENT IS TO REMAIN THE SAME. DESIGNING FOR 2 LAYERS OF REINFORCEMENT LAYER OF REINFORCEMENT OF EQUIVALENT AREA IS NOT PERMITTED. DESIGN TABLES FOR HORIZONTAL ELLIPTICAL PIPE - STANDARD INSTALLATION TYPE A/TYPE B
63 APPENDIX B REPAIR PROCEDURES FOR REINFORCED CONCRETE PIPE 1. Spalls: 1.1. End Spalls Occasional spalls or chips on the spigots, bell, tongue or groove which are no greater than ½ the depth of the joint in the longitudinal direction shall not be cause for rejection, provided the total length of spalls on the pipe end is not more than 10% of the total circumference. These spalls must be repaired using a Bulletin 15 approved repair material Spalls, other than damaged pope ends Repairs to the inner barrel will only be permitted within the acceptable limits at the male and female ends of the joint as described above and as follows: Spalling to the inner barrel which does not reveal the reinforcement with 1.5 times the joint depth from the end of the pipe may be repaired in accordance with the cosmetic repair procedure identified at the end of this appendix Minor spalls less than 2 from the edge of the lift hole may be repaired in accordance with the cosmetic repair procedures described at the end of this appendix. The aggregate fractured surface need not be obtained. Reinforcing steel may be visible prior to completing the repair. Minor spalls developed at the lift hole during installation may be repaired at the same time the lift hole is plugged. 61
64 Spalling on the outer barrel which does not expose the reinforcement may be repaired in accordance with the cosmetic repair procedure described at the end of this appendix. Spalling on the outer barrel which reveals the reinforcement must be repaired in accordance with the structural repair procedure described at the end of this appendix. 2. Cracks: 2.1. Through wall cracks: Any pipe section exhibiting a through wall crack shall be rejected, except that a single end crack that does not exceed the depth of the joint will be permitted. Pipe sections rejected for cracks may not be repaired Non-through wall cracks. Untested pieces, prior to installation. Any untested sections of pipe, other than the test specimen which was tested by the three edge bearing method, within an approved lot and which exhibit nonthrough wall crack(s) having a surface width of less than will be accepted. Sections exhibiting non-through wall cracks greater than or equal to in width and 12 or more in length will be rejected. 62
65 2.3. Non-through wall cracks, tested pieces, prior to installation. The test section for each approved lot will be accepted under the conditions of 2.2 provided the crack, under the prescribed test load, did not exceed a surface width of Plastic tear cracks Occasionally, concrete pipe develop tear cracks at their surface during initial manufacturing/handling, prior to curing, when tensile stresses exceed the concrete strength. These cracks are predominantly located along the shoulder of the spigot joint where the pipe transitions to full wall depth, although minor cracking located on the outer barrel may occur less frequently. Cracks eligible for repair must meet the following criteria: circumferential spigot tears less than 15% of the circumference of the pipe outer-barrel wall tears less than 12 in length crack depth does not extend beyond the pipe reinforcement (after V-grooving) 63
66 Prepare the crack for repair by v-grooving along the length of the crack. Complete the repair with a Bulletin 15 approved concrete repair material (non-cosmetic), listed in Bulletin 15 which develops the minimum design strength of the pipe. 3. Manufacturing Defects and Processes 3.1. Honeycombing and other mixture defects Any section exhibiting honeycombing or mixture defects that expose the reinforcing cage will be rejected. Any section exhibiting minor surface texture defects encountered on the mating surfaces of the joint can be accepted if the surface can be completely closed with a cement slurry Cage shadow Some manufacturing processes may reveal the reinforcing cage even though the section has sufficient cover. If the inspector is concerned about insufficient cover, The Structural materials Engineer should be contacted for further review Exposed end tips The presence of exposed longitudinal end tips of the reinforcing cage at the pipe ends or spacers on the pipe wall shall not be cause for rejection. 64
67 4. General: Note: Any repairs required beyond the scope of this appendix may be submitted to the Structural Materials Engineer for evaluation on a case-by-case basis. Such repair proposals should include a photograph or sketch of the affected are and a detailed repair proposal. The QC inspector must document additional information in the plant book when pipe sections are rejected. The date of manufacture, lot number, size, quantity and reason for rejection must be included. Rejected pipe or pipe requiring repair should be clearly marked with a colored keel or crayon in a location to prevent the defective pipe from mistakenly being shipped. Repairs to pipe should be performed in a workmanlike fashion, properly finished, cured and sound. Structural repairs must be witnessed by the Department inspector. Repair Procedures Minor chips and spalls less than 1 deep Areas to be repaired must be clean, sound and free of contaminants. Provide and aggregate fractured surface with a minimum surface profile of 1/8. Saturate the repair surface with clean water to provide an SSD condition. Use (1) a thoroughly mixed Bulletin 15 Material in accordance with the manufacturer s recommendation, or (2) a mortar mix. Cure (1) the Bulletin 15 material in accordance with the manufacturer s recommendations, or (2) the mortar mix a minimum of 24 hours in accordance with the approved quality control plan. Structural Repair Procedure Broken Joints or large barrel spalls where the reinforcement is exposed. Area: 1 to 6 depth range, maximum 120 square inches surface area. Area to be repaired must be clean, sound and free of contaminants. Make a 3/4 deep vertical surface along the perimeter of the damaged area. Remove concrete a minimum of 1 beyond all exposed reinforcement. Provide an aggregate fractured surface with a minimum surface profile of 1/8. Drill and insert 3/8 diameter steel pins on 4 centers for damaged areas with depths greater than 3. Clean the repair surface and apply an approved epoxy bonding or concrete bonding agent in accordance with the manufacturer s instructions. This item may be deleted if the Bulletin 15 repair product contains a bonding agent. Fill the area with (1) a thoroughly mixed Bulletin 15 material and add 3/8 coarse aggregate to the mix in accordance with the manufacturer s recommendations, or (2) the approved concrete mix design. ** Cure (1) the Bulletin 15 material in accordance with the manufacturer s recommendations, or (2) the approved concrete mix design a minimum of 24 hours in accordance with the approved quality control plan. 65
68 The repaired area will be evaluated by the Plant s Quality Control Personnel by applying a moderate blow with a 16oz. hammer at several locations of the repaired area. ** (2) is applicable only for wet cast pipe General Notes: The damaged area may not exceed a length of 12 in any direction. The total surface area repaired may not exceed 200 square inches. The patching operation and the duration of the curing cycle are to be performed in a minimum 40 o F environment. 66
69 APPENDIX C QUALITY CONTROL PLAN GUIDELINES FOR RC PIPE Note: The Quality Control Plan must be developed using these requirements as a guide. Amplification of how the manufacturer controls their process, using these criteria to meet specifications is required. I. Materials Minimum Frequency QC Pg # A. Cement - Certification from Bulletin 15 source B. Reinforcement - Certification from Bulletin 15 source C. Aggregates - Approved Bulletin 14 sources with in plant or Quarry gradation result D. Admixtures - Certification from Bulletin 15 source II. Prepour Inspection A. Rings Dimensions - Measure 25% monthly Clean - Review 10% daily B. Forms Dimensions - Measure 25% monthly Clean - Review 10% daily Lift Hole - Identify fabrication method C. Reinforcement Wire Size/Area - Measure 10% and record daily Cage Diameter - Measure 10% and record daily Welding - Verify WPS machine parameters, document daily Spacer Position - Check 10% daily III. Concrete Mix A. Batch Mass (Weight) - Record 2 batch masses (weights) each shift. B. Cylinders/Cores - Cast cylinders each day or core 3 pipe sections weekly to monitor concrete strength each mix design IV. Curing Define curing method; indicate curing temperature and duration of curing period. Describe the procedure for recording the curing cycle. V. Post pour Inspection A. Wall Thickness - Measure 10% and record daily B. Internal diameter - Measure 10% and record daily 67
70 C. Length of two opposite sides - Measure 10% and record daily D. Length of Pipe - Measure 10% and record daily E. Appearance - Review 10% daily F. Position of Reinforcement - One core weekly or measure nondestructively VI. Calibration maintain calibration certifications on file A. Cylinder compression machine - Start of season B. Admixture dispensers - Start of season C. Three edge bearing machine - Start of season D. Scale check - Start of season VII. Patching A. Outside surface - Patch before curing pipe, if possible B. Inside surface, ends - Use approved patching material and cure in accordance with the manufacturer s recommendations. VIII. Documentation A. Straight-Line Analysis Charts - Plot compressive strength B. Certification Shipping Form - Form CS-4171 C. Quality Control Procedures - Record test results, post pour measurements, etc. D. Material Certifications -Maintain on file IX. Submit an Organizational Chart, Illustrating a Quality Control Department operating and reporting to Management independent from production. 68
71 Bureau of Construction & Materials Structural Materials Section (reproduce locally) Production Joint Welding Procedure Specification/ Procedure Qualification Record : RC Pipe only WPS No: Date Issued: Revision No: Revision Date: 1. Fabricator Prepared by: 2. Wire Material Specification: Wire Size or range (in.) 3. Welding process: check one SMAW FCAW GMAW (transfer mode: ) 4. Shielding Gas Gas Flow Rate 5. Position(s) of welding 6. Filler metal specification 7. Filler metal classification 8. Single or multiple pass 9. Polarity : check one AC DC (negative) DC (positive) 10. Electrode extension (electrical stickout) 11. Preheat and Interpass temperature: Per AWS D1.4 based on bar size and carbon equivalency Pass No. Elect. Size Welding Process Variables Amperes Voltage Joint Detail Show relevant dimensions and AWS symbols Minimum Weld Length, L: in. (2 x wire diameter, minimum) This procedure may vary due to fabrication sequence, fit-up, pass size, etc. within the Limitation of Variables. Authorized Company Signature: Additional Shop Notes: For PaDOT use only Test Results (See MTD Lab No. A attached) (3 tensile specimens required for each size or for each max./min. diameter if WPS submitted for a range. All results must PASS) 69
72 Bureau of Construction & Materials Structural Materials Section (reproduce locally) Production Joint Welding Procedure Specification/ Procedure Qualification Record : RC Pipe only WPS No: Date Issued: Revision No: Revision Date: 1. Fabricator Any Plant Prepared by: John Doe 2. Wire Material Specification: A185 Wire Size or range (in.)_ through_0.250 inch_ 3. Welding process: check one SMAW FCAW GMAW (transfer mode: ) 4. Shielding Gas NA Gas Flow Rate NA 5. Position(s) of welding Flat/Horizontal 6. Filler metal specification A Filler metal classification E Single or multiple pass single 9. Polarity : check one AC DC (negative) DC (positive) 10. Electrode extension (electrical stickout) NA 11. Preheat and Interpass temperature: Per AWS D1.4 based on bar size and carbon equivalency Pass No. Elect. Size Welding Process Variables Amperes Voltage Joint Detail Show relevant dimensions and AWS symbols 1 1/ Minimum Weld Length, L: 1/2 in. (2 x wire diameter, minimum) Authorized Company Signature: John Smith Additional Shop Notes: For PENNDOT use only Test Results (See MTD Lab No. A _ attached) (3 tensile specimens required for each size or for each max./min. diameter if WPS submitted for a range. All results must PASS) 70
73 04/03 Dimensional Review for Reinforced Concrete Pipe Fabricator Name: Plant Job ID ECMS # State Project # SR Sec. County S- Concrete Pipe Type: Circular Manufacture Date: Properly Repaired: Elliptical Date of Post-Pour Check: Quantity Made DIA D DIA L Paid Wall Thick D1 (in.) L1 (in.) Marking (W) in. Inner Cage Steel (in.) 2/Linear Ft. Required Outer Cage Required Remarks And/or Waivers: 71
DMS - 7310 REINFORCED CONCRETE PIPE AND MACHINE-MADE PRECAST CONCRETE BOX CULVERT FABRICATION AND PLANT QUALIFICATION
DMS - 7310 REINFORCED CONCRETE PIPE AND MACHINE-MADE PRECAST CONCRETE BOX CULVERT FABRICATION EFFECTIVE DATE: APRIL 2012 7310.1. Description. This specification will govern for the fabrication of machine-made
PRE INSTALLATION MANUAL
REINFORCED CONCRETE PIPE PRE INSTALLATION INSPECTION & REPAIR MANUAL Kentucky Transportation Cabinet Kentucky Department of Highways Division of Materials 1227 Wilkinson Boulevard Frankfort, KY 40601 (502)
Wastewater Capital Projects Management Standard Construction Specification
CITY AND COUNTY OF DENVER ENGINEERING DIVISION Wastewater Capital Projects Management Standard Construction Specification 10.1 Precast Concrete Pipe 10.1.1 General This section covers material requirements,
C. Section 014510 TESTING LABORATORY SERVICE.
SECTION 014500 QUALITY CONTROL PART 1 GENERAL 1.01 RELATED REQUIREMENTS A. Drawings and General Provisions of Contract, including General and Special Conditions and other Division 1 Specification Sections,
State of Illinois Department Of Transportation CONSTRUCTION INSPECTOR S CHECKLIST FOR STORM SEWERS
State of Illinois Department Of Transportation CONSTRUCTION INSPECTOR S CHECKLIST FOR STORM SEWERS While its use is not required, this checklist has been prepared to provide the field inspector a summary
SECTION 55 PIPE FOR STORM DRAINS AND CULVERTS (FAA D-701)
SECTION 55 PIPE FOR STORM DRAINS AND CULVERTS (FAA D-701) 55-1 GENERAL The Contractor shall perform all work required by the plans for construction of pipe for storm drains, precast polymer trench drains
DIVISION 4300 STORM DRAINAGE
DIVISION 4300 STORM DRAINAGE SECTION 4305 STORM SEWER PART 1 - GENERAL 1.01 SCOPE This section covers the construction of storm sewers for the collection and transport of stormwater runoff. 1.02 REFERENCES
SECTION 15076 CEMENT-MORTAR LINED AND COATED STEEL PIPE
SECTION 15076 CEMENT-MORTAR LINED AND COATED (CML&C) STEEL PIPE PART 1 GENERAL 1.01 DESCRIPTION This section designates the requirements for steel pipe fabrication, test in shop, installation of steel
SECTION 36 - CAST-IN-PLACE CONCRETE PIPE (CIPCP) TABLE OF CONTENTS
SECTION 36 - CAST-IN-PLACE CONCRETE PIPE (CIPCP) TABLE OF CONTENTS Section Page 36-1 GENERAL... 36.1 36-2 PIPEMAKING EQUIPMENT... 36.1 36-3 TRENCH EXCAVATION... 36.1 36-4 SPECIAL FOUNDATION TREATMENT...
SECTION 33 05 16.13 PRECAST CONCRETE UTILITY STRUCTURES
SECTION 33 05 16.13 PRECAST CONCRETE PART 1 - GENERAL 1.01 SECTION INCLUDES A. This item shall consist of the construction of both sanitary and storm sewer precast concrete manholes in accordance with
TECHNICAL SPECIFICATION SERIES 8000 PRECAST CONCRETE
TECHNICAL SPECIFICATION SERIES 8000 PRECAST CONCRETE TECHNICAL SPECIFICATION PART 8000 - PRECAST CONCRETE TABLE OF CONTENTS Item Number Page 8100 PRECAST CONCRETE CONSTRUCTION - GENERAL 8-3 8101 General
Section 2100-Trenching and Tunneling
SECTION 5200 - STORM SEWER PART 1 - GENERAL 1.01 SCOPE: This Section covers installation of storm sewer mains and culverts. Topics include permits and fees, trench widths, pipe laying, bedding, initial
Detailing of Reinforcment in Concrete Structures
Chapter 8 Detailing of Reinforcment in Concrete Structures 8.1 Scope Provisions of Sec. 8.1 and 8.2 of Chapter 8 shall apply for detailing of reinforcement in reinforced concrete members, in general. For
STATE OF OHIO DEPARTMENT OF TRANSPORTATION SUPPLEMENTAL SPECIFICATION 888 PORTLAND CEMENT CONCRETE PAVEMENT USING QC/QA.
STATE OF OHIO DEPARTMENT OF TRANSPORTATION SUPPLEMENTAL SPECIFICATION 888 PORTLAND CEMENT CONCRETE PAVEMENT USING QC/QA October 21, 2011 888.01 General 888.02 Materials 888.03 Concrete Proportioning 888.04
Guide Specification Precast Concrete Products
Guide Specification Precast Concrete Products This specificaton should be used only by qualified professionals who are competent to evaluate the significance and limiations of the specification and who
SECTION 02612 NONREINFORCED CONCRETE SEWER PIPE
SECTION 02612 PART 1 GENERAL 1.1 SUMMARY A. Section Includes: Furnishing and installing nonreinforced concrete sewer pipe. Provide concrete sewer pipe less than 12 inches in diameter, and in other sizes
Inspection Manual for Precast Concrete Pipe and Structures
Inspection Manual for Precast Concrete Pipe and Structures May 2014 Table of Contents Chapter One Precast Concrete Pipe and Structures Certified Precast Concrete Producer.. 1-1 Materials Material Testing
Georgia Department of Transportation. Office of Materials and Research. Standard Operating Procedure (SOP) 19
Laboratory SOP 19 Revised July 1, 2003 Georgia Department of Transportation Office of Materials and Research Standard Operating Procedure (SOP) 19 This Standard Operating Procedure provides a means whereby
IHSS-N1 WELDED HONEYCOMB CORE SPECIFICATION. Generated: Sergiy Papyshev Engineering. Approved: Don Prysi Manufacturing. Approved: Merzuk Ramic Quality
IHSS-N1 WELDED HONEYCOMB CORE SPECIFICATION Generated: Sergiy Papyshev Engineering Approved: Don Prysi Manufacturing Approved: Merzuk Ramic Quality Approved: Steven Barnett Administrative DATE DATE DATE
725-R-599 PIPE LINING. (Revised 05-01-12) SECTION 725, BEGIN LINE 1, INSERT AS FOLLOWS: SECTION 725 SLIP LINING OF EXISTING PIPE
PIPE LINING (Revised 05-01-12) The Standard Specifications are revised as follows: SECTION 725, DELETE LINES 1 THRU 317. SECTION 725, BEGIN LINE 1, INSERT AS FOLLOWS: SECTION 725 SLIP LINING OF EXISTING
Photographs: Acceptable, Unacceptable, and Unacceptably Repaired Precast Concrete Products
Photographs: Acceptable, Unacceptable, and Unacceptably Repaired Precast Concrete Products A Visual Aid For: Bureau of Materials and Physical Research s (BMPR) Policy Memorandum, Quality Control/Quality
GUIDE SPECIFICATIONS FOR PRECAST CONCRETE PRODUCTS
GUIDE SPECIFICATIONS FOR PRECAST CONCRETE PRODUCTS PART 1 - GENERAL 1.1 SECTION INCLUDES A. This specification covers the materials for and manufacture of precast reinforced concrete units produced in
SPECIFICATIONS FOR PRECAST MODULAR BLOCK RETAINING WALL SYSTEM (revised 11/5/13)
Page 1 of 7 STONE STRONG SYSTEMS SPECIFICATIONS FOR PRECAST MODULAR BLOCK RETAINING WALL SYSTEM (revised ) PART 1: GENERAL 1.01 Description A. Work includes furnishing and installing precast modular blocks
SECTION 03400 PRECAST CONCRETE STRUCTURES
SECTION 03400 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes specifications for precast concrete structures, including fabrication and erection. 1.02 REFERENCE STANDARDS A. American Society for
SECTION 1 GENERAL REQUIREMENTS
Page 1 of 6 SECTION 1 GENERAL REQUIREMENTS 1. SCOPE OF WORK: The work to be performed under the provisions of these documents and the contract based thereon includes furnishing all labor, equipment, materials,
SECTION 724 PIPE CULVERTS
SECTION 724 PIPE CULVERTS 724.1 Description. This work shall consist of providing pipe or pipe arch of the diameter or shape designated, laid upon a firm bed and backfilled as specified. Where appropriate
Section 02702 SEWER PIPE INSTALLATION AND TESTING
PART 1 - GENERAL Section 02702 SEWER PIPE INSTALLATION AND TESTING 1-1. SCOPE. This section covers the installation and testing of all sewer pipe furnished under the following specification sections: Concrete
SUPPLEMENTAL TECHNICAL SPECIFICATIONS BI-DIRECTIONAL STATIC LOAD TESTING OF DRILLED SHAFTS
July 14, 2015 1.0 GENERAL BI-DIRECTIONAL STATIC LOAD TESTING OF DRILLED SHAFTS This work shall consist of furnishing all materials, equipment, labor, and incidentals necessary for conducting bi-directional
NAPCA BULLETIN 18-99 APPLICATION PROCEDURES FOR CONCRETE WEIGHT COATING APPLIED BY THE COMPRESSION METHOD TO STEEL PIPE
NAPCA BULLETIN 18-99 APPLICATION PROCEDURES FOR CONCRETE WEIGHT COATING APPLIED BY THE COMPRESSION METHOD TO STEEL PIPE GENERAL a. These specifications may be used in whole or in part by any party without
SECTION 02630 STORM DRAINAGE SYSTEM
SECTION 02630 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes specifications for storm drainage systems including modifications and connections to existing storm drainage systems. 1.02 REFERENCE
DIVISION 2 - SEWERAGE AND DRAINAGE SECTION 02720 - STORM DRAIN SYSTEMS PART 1 - GENERAL
DIVISION 2 - SEWERAGE AND DRAINAGE SECTION 02720 - STORM DRAIN SYSTEMS PART 1 - GENERAL 1.01 DESCRIPTION A. Furnish and install all storm drains, including manholes, inlets, service lines and other appurtenant
1997 Uniform Administrative Code Amendment for Earthen Material and Straw Bale Structures Tucson/Pima County, Arizona
for Earthen Material and Straw Bale Structures SECTION 70 - GENERAL "APPENDIX CHAPTER 7 - EARTHEN MATERIAL STRUCTURES 70. Purpose. The purpose of this chapter is to establish minimum standards of safety
CCU Engineering Specifications. Section 003300 PRECAST CONCRETE PRODUCTS
CCU Engineering Specifications Section 003300 Effective Date: Nov. 1st, 2011 Page 1 of 5 PRECAST CONCRETE PRODUCTS PART 1 - GENERAL The following specification is intended for use for the design, selection
Design and Construction of Cantilevered Reinforced Concrete Structures
Buildings Department Practice Note for Authorized Persons, Registered Structural Engineers and Registered Geotechnical Engineers APP-68 Design and Construction of Cantilevered Reinforced Concrete Structures
High Strain Dynamic Load Testing of Drilled Shafts
Supplemental Technical Specification for High Strain Dynamic Load Testing of Drilled Shafts SCDOT Designation: SC-M-712 (9/15) September 3, 2015 1.0 GENERAL This work shall consist of performing high-strain
The work of this Section includes furnishing and installing Reinforced Concrete Pressure Pipe as shown on the Drawings and as specified.
Section 33 0200- Page 1 of 4 PART 1 - GENERAL 1.1 DESCRIPTION OF WORK The work of this Section includes furnishing and installing Reinforced Concrete Pressure Pipe as shown on the Drawings and as specified.
MATERIALS DIVISION MEMORANDUM
MATERIALS DIVISION MEMORANDUM GENERAL SUBJECT: Precast Concrete SPECIFIC SUBJECT: Quality Control Plan Review Check list; Approved list Nos. 26 and 34; Precast Repair Manual NUMBER: MD 286-06 DATE: December
SECTION 08000 STORM DRAINAGE TABLE OF CONTENTS
SECTION 08000 STORM DRAINAGE 08010 DESIGN A. Location B. Sizing TABLE OF CONTENTS 08020 MATERIALS A. Pipe Materials B. Structure Materials C. Installation D. Inlets and Outlets 08030 INSPECTIONS AND TESTING
SECTION 02720 SANITARY SEWER AND STORM DRAIN SYSTEMS
SECTION 02720 SANITARY SEWER AND STORM DRAIN SYSTEMS PART 1 GENERAL 1.01 SECTION INCLUDES A. The requirements for pipe material and installation in sewer and drainage collection systems. All materials
Construction Specifications for Keyhole Pavement Coring and Reinstatement
F I N A L Construction Specifications for Keyhole Pavement Coring and Reinstatement Gas Technology Institute 1700 S. Mount Prospect Rd. Des Plaines, Illinois 60018 www.gastechnology.org Version 13 October
June 2007 CHAPTER 7 - CULVERTS 7.0 CHAPTER 7 - CULVERTS 7.1 GENERAL
7.0 7.1 GENERAL For the purpose of this manual, culverts are defined as structures that are completely surrounded by soil and located below the surface of the roadway parallel to the general direction
CONCRETE SEGMENTAL RETAINING WALL SYSTEM
CONCRETE SEGMENTAL RETAINING WALL SYSTEM PART 1: GENERAL SPECIFICATIONS 1.01 Work Included A. Work shall consist of furnishing and constructing a Rockwood Classic 8 with PCS unit segmental retaining wall
SECTION 02400 - STORM DRAIN SYSTEM
SECTION 02400 - STORM DRAIN SYSTEM CONTENTS: Part 1 - General... 1 1.01 Work Included... 1 1.02 Related Requirements... 1 1.03 Reference Standards... 1 1.04 Quality Assurance... 1 1.05 Measurement And
Draft Table of Contents. Building Code Requirements for Structural Concrete and Commentary ACI 318-14
Draft Table of Contents Building Code Requirements for Structural Concrete and Commentary ACI 318-14 BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE (ACI 318 14) Chapter 1 General 1.1 Scope of ACI 318
SPECIFICATION FOR PIPE SUBSOIL DRAIN CONSTRUCTION
SPECIFICATION FOR PIPE SUBSOIL DRAIN CONSTRUCTION 1. SCOPE Pipe subsoil drains shall be constructed in accordance with this specification and in conformity with the lines, grades and cross-sections shown
INDEX. Sec. No. Items Page Nos.
INDEX Sec. No. Items Page Nos. 1. Types of Pipe............... MSSP- 2 2. Concrete Pipe............... MSSP- 2 thru MSSP-3 3. ABS and PVC Truss Pipe............... MSSP- 3 4. ABS and PVC Solid Wall Pipe...............
Report on. Wind Resistance of Signs supported by. Glass Fiber Reinforced Concrete (GFRC) Pillars
Report on Wind Resistance of Signs supported by Glass Fiber Reinforced Concrete (GFRC) Pillars Prepared for US Sign and Fabrication Corporation January, 2006 SUMMARY This study found the attachment of
Bethel Township Municipal Authority (BTMA) RESIDENTIAL SEWER CONNECTION MANUAL
155 E. Front Street (rear) Lititz, PA 17543 Phone (717) 625-1930 Fax (717) 625-1931 Bethel Township Municipal Authority (BTMA) RESIDENTIAL SEWER CONNECTION MANUAL CONSTRUCTION SPECIFICATIONS AND DETAILS
738-B-297 POLYMERIC CONCRETE BRIDGE DECK OVERLAY. (Adopted 02-20-14)
POLYMERIC CONCRETE BRIDGE DECK OVERLAY (Adopted 02-20-14) Description The polymeric concrete bridge deck overlay shall consist of an epoxy polymer that acts together with special aggregate to form an overlay
Reproduced with the permission of the American Welding Society (AWS), Miami, Florida - 09/15/2011. 7. Stud Welding
7. Stud Welding 7.1 Scope Section 7 contains general requirements for welding steel studs to steel (see 7.2.7 and 1.2.2 for approved steels). In addition, it stipulates specific requirements for the following:
Technical Notes 3B - Brick Masonry Section Properties May 1993
Technical Notes 3B - Brick Masonry Section Properties May 1993 Abstract: This Technical Notes is a design aid for the Building Code Requirements for Masonry Structures (ACI 530/ASCE 5/TMS 402-92) and Specifications
AIR RELEASE, CLEANOUT, AND SEWER MANHOLES
AIR RELEASE, CLEANOUT, AND SEWER MANHOLES **From Hartford IM BLDG(10) DESCRIPTION. This work shall consist of the construction of air release, cleanout, and sanitary sewer manholes; and the furnishing
Tension Development and Lap Splice Lengths of Reinforcing Bars under ACI 318-02
ENGINEERING DATA REPORT NUMBER 51 Tension Development and Lap Splice Lengths of Reinforcing Bars under ACI 318-02 A SERVICE OF THE CONCRETE REINFORCING STEEL INSTITUTE Introduction Section 1.2.1 in the
APPENDIX K PIPE INSPECTION
APPENDIX K PIPE INSPECTION **Virginia Test Method 123** Post Installation Inspection of Buried Storm Drain Pipe and Pipe Culverts June 25, 2010 SCOPE For all roadway projects that are constructed by private
Activity 2.3b Engineering Problem Solving Answer Key
Activity.3b Engineering roblem Solving Answer Key 1. A force of 00 lbs pushes against a rectangular plate that is 1 ft. by ft. Determine the lb lb pressure in and that the plate exerts on the ground due
CONCRETE SEGMENTAL RETAINING WALL SYSTEM
CONCRETE SEGMENTAL RETAINING WALL SYSTEM PART 1: GENERAL SPECIFICATIONS 1.01 Work Included A. Work shall consist of furnishing and constructing a Rockwood Vintage TM unit segmental retaining wall (SRW)
Specification Guidelines: Allan Block Modular Retaining Wall Systems
Specification Guidelines: Allan Block Modular Retaining Wall Systems The following specifications provide Allan Block Corporation's typical requirements and recommendations. At the engineer of record's
METHOD OF STATEMENT FOR STATIC LOADING TEST
Compression Test, METHOD OF STATEMENT FOR STATIC LOADING TEST Tension Test and Lateral Test According to the American Standards ASTM D1143 07, ASTM D3689 07, ASTM D3966 07 and Euro Codes EC7 Table of Contents
Transport and Main Roads Specifications MRTS25 Steel Reinforced Precast Concrete Pipes
Technical Specification Transport and Main Roads Specifications MRTS25 Steel Reinforced Precast Concrete Pipes September 2014 Copyright http://creativecommons.org/licenses/by/3.0/au/ State of Queensland
EXPANDED POLYSTYRENE (EPS) INSULATION BOARD SPECIFICATIONS
EXPANDED POLYSTYRENE (EPS) INSULATION BOARD SPECIFICATIONS 1. SCOPE 1.1 This specification covers the type, physical properties and dimensions of Expanded Polystyrene Insulation Board intended for use
Construction Specification for Concrete Curb and Concrete Curb and Gutter
Engineering & Construction Services Division Standard Specifications for Road Works TS 3.50 April 2015 for Concrete Curb and Table of Contents TS 3.50.01 SCOPE... 3 TS 3.50.02 REFERENCES... 3 TS 3.50.03
TECHNICAL NOTE Culvert Sliplining and Lining of Casings with HPPipe
TECHNICAL NOTE Culvert Sliplining and Lining of Casings with HPPipe TN 5.14 February 2010 Introduction It may be at times necessary, in an aging infrastructure, to rehabilitate drainage and sanitary lines
DESIGN OF SLABS. 3) Based on support or boundary condition: Simply supported, Cantilever slab,
DESIGN OF SLABS Dr. G. P. Chandradhara Professor of Civil Engineering S. J. College of Engineering Mysore 1. GENERAL A slab is a flat two dimensional planar structural element having thickness small compared
Lab 1 Concrete Proportioning, Mixing, and Testing
Lab 1 Concrete Proportioning, Mixing, and Testing Supplemental Lab manual Objectives Concepts Background Experimental Procedure Report Requirements Discussion Prepared By Mutlu Ozer Objectives Students
Acceptance Codes APPENDIX - A. Acceptance Criteria
1111 Receipt of a satisfactory Test Report from WSDOT Materials Laboratory is required indicating the lot (or lots) or batch of material meets the requirement of the specifications under which it is listed.
Proper use of the Rebound Hammer Updated to reflect the changes to ASTM C805
CEMEX USA - Technical Bulletin 2.1 Proper use of the Rebound Hammer Updated to reflect the changes to ASTM C805 The Rebound Hammer has been around since the late 1940 s and today is a commonly used method
MINIMUM QUALITY CONTROL PLAN FOR FIELD PLACEMENT OF LATEX MODIFIED MORTAR OR CONCRETE WEARING SURFACE
CS-1042 (8-13) www.dot.state.pa.us MINIMUM QUALITY CONTROL PLAN FOR FIELD PLACEMENT OF LATEX MODIFIED MORTAR OR CONCRETE WEARING SURFACE State Route (SR) Section County ECMS# Prime/Sub Contractor Latex
Commonwealth of Pennsylvania PA Test Method No. 632 Department of Transportation October 2013 5 Pages LABORATORY TESTING SECTION. Method of Test for
Commonwealth of Pennsylvania PA Test Method No. 632 Department of Transportation 5 Pages LABORATORY TESTING SECTION Method of Test for TIME OF SETTING OF CONCRETE MIXTURES BY PENETRATION RESISTANCE 1.
Field Welding Inspection Guide
Field Welding Inspection Guide Assistance in interpretation of any specification or questions concerning field welding issues can be obtained from the Office of Materials Management, Structural Welding
MeltonStone Cast Stone Product Specifications
MeltonStone Cast Stone Product Specifications Section 04-72-00-04 Architectural Cast Stone This specification encompasses basic requirements for Cast Stone, a refined architectural concrete building unit
SECTION 02845 GUARDRAILS
SECTION 02845 GUARDRAILS PART 1 - GENERAL 1.01 SCOPE OF WORK A. Furnish all labor, materials, equipment and incidentals necessary and repair, replace or install all types of guardrails as specified herein
No allowance will be made for classification of different types of material encountered.
PROJECT : Repair/ Maintenance of Flood Control and Drainage Structures Along Butuan City Cagayan de Oro City Iligan City Road LOCATION : San Antonio, Jasaan, Misamis Oriental SUBJECT : General Notes and
SECTION 33 41 00 REINFORCED CONCRETE PIPE. A. The following is a list of SPECIFICATIONS, which may be related to this section:
SECTION 33 41 00 REINFORCED CONCRETE PIPE PART 1 GENERAL 1.01 SECTION INCLUDES A. This section includes construction of reinforced concrete pipe for storm drainage, culverts, and sanitary sewer, including
Collapse of Underground Storm Water Detention System
Collapse of Underground Storm Water Detention System No. 16 March 2008 Shopping malls have large roof areas and large paved areas for parking. In many cases, during heavy rainfall, the drainage from these
San Antonio Water System Standard Specifications for Construction ITEM NO. 1100 SLIP-LINING SANITARY SEWERS
ITEM NO. 1100 SLIP-LINING SANITARY SEWERS 1100.1 DESCRIPTION: This item shall consist of slip-lining sanitary sewer pipe, which is accomplished by pulling or pushing liner pipe into existing sewers by
SECTION 4Aggegate Subbase
The contractor shall moist-cure the completed Lime Treated Subbase for a minimum of days before allowing any traffic on the compacted surface. The contractor shall be responsible for repairing any damages
PCI BIG BEAM COMPETITION
PCI BIG BEAM COMPETITION Official Rules for the PCI Engineering Design Competition Academic Year 2015-16 PROGRAM The PCI Student Education Committee is inviting entries from students to participate in
LEGACY REPORT. www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council. *Corrected March 2014
ICC-ES Legacy Report PFC-3700* Issued October 2003 www.icc-es.org (00) 423-57 (52) 99-0543 A Subsidiary of the International Code Council Legacy report on the 1997 Uniform Building Code and the 2000 International
PRECAST CONCRETE BOX CULVERTS
PRECAST CONCRETE BOX CULVERTS OUTLINE Introduction Applications Manufacturing Methods Design Procedures & Joints Installation Quality Summary INTRODUCTION Four-sided culverts are typically referred to
STANDARD REQUIREMENTS FOR BONDING OR MECHANICAL ATTACHMENT OF INSULATION PANELS AND MECHANICAL ATTACHMENT OF ANCHOR AND/OR BASE SHEETS TO SUBSTRATES
ROOFING APPLICATION STANDARD (RAS) No. 117 STANDARD REQUIREMENTS FOR BONDING OR MECHANICAL ATTACHMENT OF INSULATION PANELS AND MECHANICAL ATTACHMENT OF ANCHOR AND/OR BASE SHEETS TO SUBSTRATES Scope 1.1.
SUBDRAINS AND FOOTING DRAIN COLLECTORS. A. Construct subdrains, subdrain cleanouts and outlets, and footing drain collectors.
SUBDRAINS AND FOOTING DRAIN COLLECTORS PART 1 - GENERAL 1.01 SECTION INCLUDES A. Subdrains B. Subdrain Cleanouts and Outlets C. Footing Drain Collectors D. Storm Sewer Service and Connections 1.02 DESCRIPTION
Chapter 36 - STRAW BALE CONSTRUCTION SECTION 3601 - PURPOSE. SECTION 3602 - SCOPE. SECTION 3603 - DEFINITIONS.
Austin City Code - Volume II TITLE 25 LAND DEVELOPMENT\CHAPTER 25-12 TECHNICAL CODES\ARTICLE 1: UNIFORM BUILDING CODE\25-12-3 LOCAL AMENDMENTS TO THE BUILDING CODE Chapter 36 - STRAW BALE CONSTRUCTION
Prequalification Requirements For Precast Concrete Drainage Products
Prequalification Requirements For Precast Concrete Drainage Products June 2010 Rev. 9, June 2010 Prequalification Requirements For Precast Concrete Drainage Products August 1998; Rev. 1, June 1999; Rev.
Section 402. STORM SEWERS
402.02 Section 402. STORM SEWERS 402.01. Description. This work consists of constructing storm sewers of the size and class required, including excavation, bedding, and backfill. 402.02. Materials. Provide
Diameter. Swift Lift Round Recess Plug. Note: The diameter of the narrow recess plug is the same as the diameter of the round recess plug.
P-5 The P-5 is hot forged from carbon steel. The formed head provis spherical seating that the Lifting Eye engages, while a disc-shaped foot is embedd in the concrete. Due to its being a forged part, the
SPECIAL INSPECTION AND TESTING AGREEMENT INTERNATIONAL BUILDING CODE
Community Development Permit Services SPECIAL INSPECTION AND TESTING AGREEMENT INTERNATIONAL BUILDING CODE PROJECT NAME PROJECT ADDRESS PERMIT NUMBER CITY RECEIVED STAMP AND INITIALS Instructions: BEFORE
SEDIMENT/STORMWATER MANAGEMENT BASIN CONSTRUCTION CHECKLIST
SEDIMENT/STORMWATER MANAGEMENT BASIN CONSTRUCTION CHECKLIST For permanent structures per Delaware SCS Pond Code 378 and Delaware Sediment and Stormwater Regulations KEY PROJECT INFORMATION Item meets standard
CONTRACT SPECIFICATIONS - SEISMIC ISOLATION BEARINGS
CONTRACT SPECIFICATIONS - SEISMIC ISOLATION BEARINGS 1.0 DESIGN 1.1 Scope of Work 1.1.1 This work shall consist of furnishing Isolation Bearings and installing Isolation Bearing Assemblies at the locations
PVC PIPE PERFORMANCE FACTORS
PVC PIPE PERFORMANCE FACTORS PVC pipe, like all flexible pipe products, is very dependent on the surrounding soil for its structural capacity, in addition, the pipe material must have sufficient inherent
SEISMIC DESIGN. Various building codes consider the following categories for the analysis and design for earthquake loading:
SEISMIC DESIGN Various building codes consider the following categories for the analysis and design for earthquake loading: 1. Seismic Performance Category (SPC), varies from A to E, depending on how the
Division 4 Section 047200 Concrete Masonry Specifications
Cast Stone Specification This specification encompasses basic requirements for Cast Stone, as manufactured by Building Products Corp, 494 North 33 rd Street East St. Louis, Il 618-874-6282, 800-427-6282,
SECTION 6 SANITARY SEWER MAIN 6.01 SCOPE
6.01 SCOPE The work covered by this section of the specifications consists of the furnishing of all plant, labor, materials, equipment and supervision and performing all operations involved in the construction
Basics of Reinforced Concrete Design
Basics of Reinforced Concrete Design Presented by: Ronald Thornton, P.E. Define several terms related to reinforced concrete design Learn the basic theory behind structural analysis and reinforced concrete
City of Tucson and Pima County Arizona Building Code Appendix Chapter 72 Straw-Bale Structures
City of Tucson and Pima County Arizona Building Code Appendix Chapter 72 Straw-Bale Structures SECTION 7201 - PURPOSE The purpose of this appendix chapter is to establish minimum prescriptive standards
SECTION 33 41 13 PUBLIC STORM UTILITY DRAINAGE PIPING
SECTION 33 41 13 PUBLIC STORM PART 1 - GENERAL 1.01 SECTION INCLUDES A. Storm drainage piping, fittings, and accessories at proposed station areas and locations other than under and immediately adjacent
UX-30 PERFORMANCE TESTING SUMMARY REPORT Revision 0
UX-30 PERFORMANCE TESTING SUMMARY REPORT Revision 0 Prepared By: Patrick L. Paquin, EnergySolutions Date Reviewed By: Mirza I. Baig, EnergySolutions Date Approved By: Thomas F. Dougherty, Columbiana Hi
WATERPROOFING FOR CONCRETE STRUCTURES
MANUAL OF CONTRACT DOCUMENTS FOR ROAD WORKS VOLUME 1 SPECIFICATION FOR ROAD WORKS SERIES 2000 WATERPROOFING FOR CONCRETE STRUCTURES Contents Clause Title Page 2001 General 2 2002 Protection of Bridge Deck
PTS HELICAL PIERS INSTALLATION SPECIFICATIONS NOTICE
FORM A PTS HELICAL PIERS INSTALLATION SPECIFICATIONS NOTICE The following suggested specifications are written as a guide to assist the specifier in writing his own specifications. Specific circumstances
Reinforced Concrete Design
FALL 2013 C C Reinforced Concrete Design CIVL 4135 ii 1 Chapter 1. Introduction 1.1. Reading Assignment Chapter 1 Sections 1.1 through 1.8 of text. 1.2. Introduction In the design and analysis of reinforced