1 Tunnelling and Underground Space Technology 22 (2007) Tunnelling and Underground Space Technology incorporating Trenchless Technology Research CFD simulation and optimization of the ventilation for subway side-platform Feng-Dong Yuan *, Shi-Jun You School of Environment Science and Technology, Tianjin University, No. 72, Weijin Road, Nankai District, Tianjin , China Received 27 May 2006; received in revised form 23 September 2006; accepted 19 October 2006 Available online 5 December 2006 Abstract To obtain the velocity and temperature field of subway station and the optimized ventilation mode of subway side-platform station, this paper takes the evaluation and optimization of the ventilation for subway side-platform station as main line, builds three dimensional models of original and optimization design of the existed and rebuilt station. And using the two-equation turbulence model as its physics model, the thesis makes computational fluid dynamics (CFD) simulation to subway side-platform station with the boundary conditions collected for simulation computation through field measurement. It is found that the two-equation turbulence model can be used to predict velocity field and temperature field at the station under some reasonable presumptions in the investigation and study. At last, an optimization ventilation mode of subway side-platform station was put forward. Ó 2006 Elsevier Ltd. All rights reserved. Keywords: Ventilation; CFD simulation; k-e model; Subway; Side-platform 1. Introduction Computational fluid dynamics (CFD) software is commonly used to simulate fluid flows, particularly in complex environments (Chow and Li, 1999; Zhang et al., 2006; Moureh and Flick, 2003). CFD is capable of simulating a wide variety of fluid problems (Gan and Riffat, 2004; Somarathne et al., 2005; Papakonstantinou et al., 2000; Karimipanah and Awbi, 2002). CFD models can be realistically modeled without investing in more costly experimental method (Betta et al., 2004; Allocca et al., 2003; Moureh and Flick, 2003). So CFD is now a popular design tool for engineers from different disciplines for pursuing an optimum design due to the high cost, complexity, and limited information obtained from experimental methods (Li and Chow, 2003; Vardy et al., 2003; Katolidoy and Jicha, 2003). Tunnel ventilation system design can be developed in depth from the predictions of various parameters, such * Corresponding author. Tel.: ; fax: address: [email protected] (F.-D. Yuan). as vehicle emission dispersion, visibility, air velocity, etc. (Li and Chow, 2003; Yau et al., 2003; Gehrke et al., 2003). Earlier CFD simulations of tunnel ventilation system mainly focus on emergency situation as fire condition (Modic, 2003; Carvel et al., 2001; Casale, 2003). Many scientists and research workers (Waterson and Lavedrine, 2003; Sigl and Rieker, 2000; Gao et al., 2004; Tajadura et al., 2006) have done much work on this. This paper studied the performance of CFD simulation on subway environment control system which has not been studied by other paper or research report. It is essential to calculate and simulate the different designs before the construction begins, since the investment in subway s construction is huge and the subway should run up for a few decade years. The ventilation of subway is crucial that the passengers should have fresh and high quality air (Lowndes et al., 2004; Luo and Roux, 2004). Then if emergency occurred that the well-designed ventilation system can save many people s life and belongings (Chow and Li, 1999; Modic, 2003; Carvel et al., 2001). The characteristics of emergency situation have been well investigated, but there have been /$ - see front matter Ó 2006 Elsevier Ltd. All rights reserved. doi: /j.tust

2 F.-D. Yuan, S.-J. You / Tunnelling and Underground Space Technology 22 (2007) few studies in air distribution of side-platform in normal conditions. The development of large capacity and high speed computer and computational fluid dynamics technology makes it possible to use CFD technology to predict the air distribution and optimize the design project of subway ventilation system. Based on the human-oriented design intention in subway ventilation system, this study simulated and analyzed the ventilation system of existent station and original design of rebuilt stations of Tianjin subway in China with the professional software AIRPAK, and then found the optimum ventilation project for the ventilation and structure of rebuilt stations. 2. Ventilation system Tianjin Metro, the secondly-built subway in China, will be rebuilt to meet the demand of urban development and expected to be available for Beijing 2008 Olympic Games. The existent subway has eight stations, with a total length of km and a km average interval. For sake of saving the cost of engineering, the existent subway will continue to run and the stations will be rebuilt in the rebuilding Line 1 of Tianjin subway. Although different existent stations of Tianjin Metro have different structures and geometries, the Southwest Station is the most typical one. So the Southwest Station model was used to simulate and analyze in the study. Its geometry model is shown in Fig The structure and original ventilation mode of existent station The subway has two run-lines. The structure of Southwest Station is, length width height = 74.4 m(l) 18.7 m(w) 4.4 m(h), which is a typical side-platform station. Each side has only one passageway (length height = 6.4 m(l) 2.9 m(h)). The middle of station is the space for passengers to wait for the vehicle. The platform mechanical ventilation is realized with two jet openings located at each end of station and the supply air jets towards train and track. There is no mechanical exhaust system at the station and air is removed mechanically by tunnel fans and naturally by the exits of the station The design structure and ventilation of rebuilt station The predicted passenger flow volume increase greatly and the dimension of the original station is too small, so in the rebuilding design, the structure of subway station is changed to, (length width height = 132 m(l) m(w) 4.65 m(h)), and each side has two passageways. The design volume flow of Southwest Station is m 3 /h. For most existent stations, the platform height is only 2.9 m, which is too low to set ceiling ducts. So in the original design, there are two grille vents at each end of the platform to supply fresh air along the platform length direction and two grille vents to jet air breadthways towards trains. The design velocity of each lengthways grille vent is 5.54 m/s. For each breadthways vent, it is 5.28 m/s. Under the platform, 80 grille vents of the same velocity (4.62 m/s, 40 for each platform of the station) are responsible for exhaust. 3. CFD simulation and optimization The application of CFD simulation in the indoor environment is based on conversation equations of energy, mass and momentum of incompressible air. The study Fig. 1. The location of test section and the layout of measuring points.

3 476 F.-D. Yuan, S.-J. You / Tunnelling and Underground Space Technology 22 (2007) adopted a turbulence energy model that is the two-equation turbulence model advanced by Launder and Spalding. And it integrated the governing equation on the capital control volumes and discretized in the definite grids, at last simulated and computed with the AIRPAK software Preceding simplifications and presumptions Because of mechanical ventilation and the existence of train-driven piston wind, the turbulence on platform is transient and complex. Unless some simplifications and presumptions are made, the mathematics model of threedimensional flow is not expressed and the result is divergent. While ensuring the reliability of the computation results, some preceding simplifications and presumptions have to be taken. (1) The period of maximum air velocity is paid attention to in the transient process. Apparently the maximum air velocity is reached at the period when train stops at or starts away from the station (Yau et al., 2003; Gehrke et al., 2003), so the period the simulation concerns about the best period of time for simulation is from the point when at the section of x = 0.0 m (Fig. 1) and the air velocity begin to change under piston-effect to the point when train totally stops at the station (defined as a pulling-in cycle ). (2) Though the pulling-in cycle is a transient process, it is simplified to a steady process. (3) Because the process is presumed to a steady process, the transient velocity of test sections, which was tested in Southwest Station in pulling-in cycle, is presumed to the time-averaged velocity of test sections. (4) The volume flow driven into the station by pulling-in train is determined by such factors as BR (blocking ratio, the ratio of train cross-section area to tunnel cross-section area), the length of the train and the resistance of station etc. For existent and new stations, BRs are almost the same. Although the length of the latter train doubles that of the former which may increase the piston flow volume, the resistance of latter is greater than that of the former which may counteract this increase. So it is presumed that the piston flow volume is same for both existent and new station and that the volume flow through the passenger exits is also same. Based on this presumption, the results of the field measurements at the existent station can be used as velocity boundary conditions to predict velocity filed of new station Original conditions To obtain the boundary conditions for computation and simulation, such as the air velocity and temperature of enclosure, measures were done by times at Southwest Station. All data are recorded during a complete pulling-in cycle. The air velocities were measured by the multichannel anemonmaster hotwire anemoscope and infrared thermometer is used to measure the temperature of the walls of the station which are taken as the constant temperature thermal conditions in the simulation Temperatures of enclosure Divide the platform into five segments and select some typical test positions. The distributing temperature of enclosure is shown in Table 1. It can be seen from Table 1 that all temperatures of enclosure are between 23 C and 25 C, there is little difference in all test positions, and the average temperature is 24 C. So all temperatures of subway station s walls is 24 C in CFD computation and simulation Time-averaged air velocity above the platform Fig. 1 is the location of test section and the layout of measuring points. The data measured include 12 transient velocities in each section (A H in Fig. 1), which were deal with section s time-averaged velocities in the period, 12 point s velocities of passageway, which is used to acquire the average flow, and the velocities of each end of station, which is used to acquire the average piston flow volume. Fig. 2 is the lengthways velocities measured of platform sections, V max is the maximum air velocity, V min is the minimum air velocity and V ave is the average air velocity. Fig. 2 shows that the maximum air velocity is at the passageway. At the passageway the change of air velocity is about 2.25 m/s, which is the maximum and indicates that the passageway is the position effected most by the piston wind effect, and the air velocity of section D and E after the passageway is almost the same, which indicates that the piston wind can hardly effect the air velocity after the passageway. Table 1 Distributing temperature of enclosure Test positions Station walls Platform Top Railway ground Lateral wall Ground Temperature ( C) when x = 12.8 m Temperature ( C) when x = 25.6 m Temperature ( C) when x = 38.4 m Temperature ( C) when x = 51.2 m

4 F.-D. Yuan, S.-J. You / Tunnelling and Underground Space Technology 22 (2007) station in CFD simulation is shown in Table 2. Additionally, the Tianjin Metro is out of run during the measuring time, so the heat load is not typical and is difficult to be determined so that the distributing temperature was not simulated in this study. Referred to the feasibility research report of No. 3 design institute of China s ministry of railway and the measured data in Southwest Station, the boundary conditions of new station in CFD simulation of the existent station is shown in Table Solution process Fig. 2. Measured lengthways velocities at platform sections. In addition, because of the movement of train, the velocity cannot be measured in section U of Fig. 1, the air velocity of section U was computed in CFD simulation Boundary conditions of simulation Through analyzing the boundary data measured at the Southwest Station, the boundary conditions of the existent Method of solution The governing equations to calculate original variables, such as velocity and temperature etc., can be shown (Moureh and Flick, 2003). o ðq/þþdivðq~u/þ ¼divðCgrad/ÞþS ot ð1þ where / is common variable and denotes (u,v,w,t), ~u is velocity vector, q is density, C is dissipation function, S is the source item. u is air velocity of direction X, v and w are air velocities of direction Y and Z, respectively, and T is air temperature. Eq. (1) is integrated on the spatial control volumes, and through discretizing in the definite grids Table 2 Boundary condition of existent stations in CFD simulation Sections Section G Section U (estimated) Section H Passageway of the trainstopping side:exit1 Passageway of the non-train stopping side:exit2 Air velocity (m/s) Air flow (m 3 /s) The exit of train F Table 3 Boundary condition of rebuilt stations in CFD simulation (a) Heat load Persons Lamps (on the top of platform) Heat load 44 kw/ person Advertisement lamps (lateral wall of platform) Heat emitted from train 13 W/m 2 15 kw/station 320 kw (acceleration) and 200 kw (heat from applying brake) (b) Air velocity Supply air (lengthways) Supply air (breadthways) Under the platform vents Air velocity (m/s) (c) Boundary conditions of air velocity Boundary conditions of air velocity (m/s) (d) Temperature Temperature ( C) The entrance of train The exit of train Passageway of the train-stopping side Train walls (expert for excluding top and bottom of train) Outdoor air (summer) Supply air (summer) Passageway of the non-train-stopping side Tunnel air Enclosure walls

5 478 F.-D. Yuan, S.-J. You / Tunnelling and Underground Space Technology 22 (2007) Table 4 Settlement of existent station ventilation CFD simulation Variable Pressure Kinetic k e Discretization Body force weighted Second order upwind Second order upwind Second order upwind Relaxation coefficient Solution Pressure AMG a Kinetic AMG k AMG e AMG Cycle type V-type Flexible Flexible Flexible a AMG is algebra multi-grid. Table 5 Settlement of new station ventilation CFD simulation Variable Pressure Temperature Kinetic k e Discretization Body force weighted Second order upwind First order upwind First order upwind First order upwind Relaxation coefficient Solution Pressure AMG Temperature AMG Kinetic AMG k AMG e AMG Cycle type V-type Flexible Flexible Flexible Flexible a p / ¼ X a nb / nb þ b ð2þ nb In Eq. (2), nb denotes neighbor grids; a p and a nb are the coefficients of / and / nb, respectively, b is the source item. (2) Tables 4 and 5 shows solution, cycle type and convergence criterion and relaxation coefficient in CFD simulation of the existent station ventilation and the new station Simulation and discussion Used the boundary conditions measured in Southwest Station, the air velocity of subway side-platform station was simulated in AIRPAK. Fig. 3 is the air velocity comparison of simulation and measurement in section A E, which shows that the two-equation model and the preceding simplifications are acceptable in predicting flow at the station. Although the computed velocity at section C and Fig. 3. Air velocity of section A E simulation and measurement. E is not equal to the values of the field measurement, whose error is about m/s, the differences are acceptable and the overall variance trend of the velocity along the platform tallies with the measurement. The simulation result of air velocity of 1.7 m height above platform of existent station can be seen in Fig. 4. Fig. 4 shows that the majority of piston winds pour out from the passageway and the air velocity of the zone after the passageway is lower, which is below 0.4 m/s. The maximum air velocity at 1.7 m height above platform is the passageway of the train-stopping side, which is about 1.89 m/s. The simulation results indicate that it is applicable to use two-equation turbulence model to predict time-averaged flow and temperature distribution at subway station so the veracity is reliable. Fig. 5 is the simulation result, which is the original design of air velocity at 1.7 m height above platform of new station. It is shown from Fig. 5 that at the training-stopping side of platform the supply air does not reach the zone between the two exits, which is for the passenger to wait for the train, and pour out from the passageway because of the leakage of passageway. The air velocity between two passageways, which is below 0.4 m/s, is a little low so that the Dead Zone is formed. The simulation also shows that the maximum velocity exists at the exits, which agrees with the references and experience. Fig. 6 is the temperature distribution at 1.7 m height above platform of the new station, which is used to simulate for original design ventilation mode. It shows that the temperature distribution is imbalanced for the leakage of exits at the training-stop side of platform, and at each end of platform, the temperature should be approximately between 24 C and 26 C while the temperature is between 32 C and34 C because the heat away from the train can not be cooled and removed by the cold supply air in time, even at the x = 61 m point, the temperature reaches above 40 C, which makes people feel uncomfortable. The simulation result of temperature and air velocity of original design at the lengthways center section is shown in

6 F.-D. Yuan, S.-J. You / Tunnelling and Underground Space Technology 22 (2007) Fig. 4. Simulation result of air velocity at 1.7 m height above platform of existent station. Fig. 5. Simulation result of air velocity at 1.7 m height above platform of new station (original design). Fig. 6. Simulation result of temperature at 1.7 m height above platform of new station (original design). Fig. 7, which shows that the distribution of temperature and air velocity is not balanceable and the zone between two exits is Dead Zone. From the simulation of original design, the following can be seen: (1) The ventilation mode that the feasibility research report design for the side-platform station of subway makes the distribution of temperature and air velocity unbalanced, so the passengers will feel uncomfortable at the middle of platform.

7 480 F.-D. Yuan, S.-J. You / Tunnelling and Underground Space Technology 22 (2007) Fig. 7. Simulation result of temperature and air velocity at the lengthways center section (original design). (2) The air velocity is too high at some position of platform and the passengers feel easily the change of air velocity, whose scope is between 0.4 m/s and 2.5 m/s, and feel uncomfortable when they go to exits from the middle of platform. (3) The efficiency of ventilation is not as good as expectation and the supply air from jet fans cannot reach the middle of platform adequately and part of them will flow away from the passageways. Because of the unbalanced distribution of temperature and air velocity, original design s ventilation mode was optimized. The exhaust vents are as same as that of original ones. The flow of supplied air remains the same and under the platform there are tubes of supplied fresh air. Also there are some vertical tubes fetched out by platform. As a result, the air is supplied widthways and reasonably the flow of supplied air is delivered in balance, which eliminates the unbalanced distribution of temperature and air velocity on the platform. On the other hand the breadthways supplied air prevents the heat brought by train from diffusing onto the platform, and the heat can be vented in time from the exhaust vents under the platform. At the same time the fresh air from the breadthways vents passes through the passengers, takes away heat and humidity, and the efficiency of ventilation is quite satisfactory. To validate the optimization ventilation mode, the simulation adopted the same boundary conditions and set up with original design s CFD simulation. The simulation results are showed in Figs. 8 and 9. Fig. 8 is the air velocity distribution at 1.7 m height above platform of new station, which is simulated for optimization design ventilation mode. It shows that the distribution of air velocity is good enough and balanced. The breadthways supplied air makes the Dead Zone disappeared, and the maximum air velocity is only about 1.67 m/s at 1.7 m height above platform of new station, which makes it difficult for passengers to feel windy. Fig. 9 is the simulation result of temperature and air velocity of original design at the lengthways center section, which shows that the Dead Zone disappears at the lengthways center section. And the breadthways supplied air prevents the heat, which is from the air conditioning condenser and the friction produced by train-stopping, from diffusing to the platform, so the temperature is about below 28 C. Compared with the ventilation mode in original design, the optimization ventilation mode has several advantages as follows: (1) The supply air is delivered to every zone in a balanced way and the distribution of temperature and air velocity of side-platform is also balanced. (2) The air velocity is balanced and the maximum is only about 1.67 m/s. Fig. 8. Simulation result of air velocity at 1.7 m height above platform of new station (optimization design).

8 F.-D. Yuan, S.-J. You / Tunnelling and Underground Space Technology 22 (2007) Fig. 9. Simulation result of temperature and air velocity at the lengthways center section (optimization design). (3) The supplied air removes the heat of platform better and the whole platform s temperature is lower than that of the original design, which can lower temperature standard and can decrease the flow of supply air to save energy. (4) The supplied air from breadthways vents also well prevents the hot contaminated train-driven air from spreading onto the platform, and on the other hand the fresh air from the breadthways vents passes through the passengers, takes away heat and humidity, collects and is exhausted by the under-platform vents. (5) The ventilation efficiency is quite satisfactory. 4. Conclusions The following can be concluded from this study: The air flow in platform of subway is a complex threedimensional transient turbulence. Simplification of the air flow to steady process and presumption of the transient velocity to the time-averaged velocity are applicable to simulate the distribution of temperature and air velocity of subway platform in the pulling-in cycle. It is applicable to use two-equation turbulence model to predict time-averaged velocity and temperature distribution at subway station. The simulation results are influenced greatly by the boundary conditions such as boundary velocity and temperature. The optimization ventilation mode has more advantages than the original design s. The breadthways ventilation is suggested when the height of platform is too low to have ceiling ducts. It makes the distribution of temperature and air velocity balanced. Before a design is accepted it is very necessary to evaluate and optimize it by such techniques as CFD, etc. It will help a lot to build a reliable, effective and economical system. Acknowledgement This project was supported by the funding generated by the Tianjin Municipal Science and Technology Commission of China (Project No: ). References Allocca, C., Chen, Q.Y., Glicksman, L.R., Design analysis of singlesided natural ventilation. Energy and Buildings 35, Betta, V., Cascetta, F., Labruna, P., Palombo, A., A numerical approach for air velocity predictions in front of exhaust flange slot openings. Building and Environment 39, Carvel, R.O., Beard, A.N., Jowitt, P.W., The influence of longitudinal ventilation systems on fires in tunnels. Tunnelling and Underground Space Technology 16, Casale, E., The automation of the aeraulic response in the case of a fire in a tunnel-first concrete answers. In: Proceedings of Claiming the Underground Space, pp Chow, W.K., Li, J.S.M., Safety requirement and regulations reviews on ventilation and fire for tunnels in the Hong Kong Special Administration Region. Tunnelling and Underground Space Technology 14, Gan, G.H., Riffat, S.B., CFD modelling of air flow and thermal performance of an atrium integrated with photovoltaics. Building and Environment 39, Gao, P.Z., Liu, S.L., Chow, W.K., Fong, N.K., Large eddy simulations for studying tunnel smoke ventilation. Tunnelling and Underground Space Technology 19, Gehrke, P.J., Stacev, C.H.B., Agnew, N.D., Rail tunnel temperature stratification and implications for train and tunnel ventilation design. In: Proceedings of 11th International Symposium on Aerodynamics and Ventilation of Vehicle Tunnels, pp Karimipanah, T., Awbi, H.B., Theoretical and experimental investigation of impinging jet ventilation and comparison with wall displacement ventilation. Building and Environment 37, Katolidoy, J., Jicha, M., Eulerian-Lagrangian model for traffic dynamics and its impact on operational ventilation of road tunnel. In: Proceedings of 11th International Symposium on Aerodynamics and Ventilation of Vehicle Tunnels, pp Li, J.S.M., Chow, W.K., Numerical studies on performance evaluation of tunnel ventilation safety systems. Tunnelling and Underground Space Technology 18, Lowndes, Ian S., Crossley, Amanda J., Yang, Zhi Yuan, The ventilation and climate modeling of rapid development tunnel drivages. Tunnelling and Underground Space Technology 19, Luo, S., Roux, B., Modeling of the HESCO nozzle diffuser used in IEA Annex-20 experiment test room. Building and Environment 39, Modic, J., Fire simulation in road tunnels. Tunnelling and Underground Space Technology 18, Moureh, J., Flick, D., Wall air-jet characteristics and airflow patterns within a slot ventilated enclosure. International Journal of Thermal Sciences 42, Papakonstantinou, K.A., Kiranoudis, C.T., Markatos, N.C., Computational analysis of thermal comfort: the case of the archaeological museum of Athens. Applied Mathematical Modelling 24,

9 482 F.-D. Yuan, S.-J. You / Tunnelling and Underground Space Technology 22 (2007) Sigl, O., Rieker, K., NATM tunnelling in Singapore old alluviumdesign assumptions and construction experience. In: International Conference on Tunnels and Underground Structures. pp Somarathne, S., Seymour, M., Kolokotroni, M., Dynamic thermal CFD simulation of a typical office by efficient transient solution methods. Building and Environment 40, Tajadura, R.B., Carlos, S.M., Eduardo, B.M., Influence of the slope in the ventilation semi-transversal system of an urban tunnel. Tunnelling and Underground Space Technology 21, Vardy, A.E., Mori, E., Yokota, M., Nakahori, I., Model-based predictive control of road tunnel portal emissions. In: Proceedings of Claiming the Underground Space, pp Waterson, N.P., Lavedrine, J., Evaluation of a simplified model for the design of ventilation systems in tunnel networks. In: Proceedings of 11th International Symposium on Aerodynamics and Ventilation of Vehicle Tunnels, pp Yau, R., Cheng, V., Lau, K.P., Lai, F., Design and analysis of tunnel ventilation system for the extension of an existing railway tunnel in Hong Kong. In: Proceedings of 11th International Symposium on Aerodynamics and Ventilation of Vehicle Tunnels, pp Zhang, Lin, Feng, Jiang, Chow, T.T., Tsang, C.F., Lu, W.Z., CFD analysis of ventilation effectiveness in a public transport interchange. Building and Environment 41,

INITIAL ASSESSMENT OF THE IMPACT OF JET FLAME HAZARD FROM HYDROGEN CARS IN ROAD TUNNELS AND THE IMPLICATION ON HYDROGEN CAR DESIGN

INITIAL ASSESSMENT OF THE IMPACT OF JET FLAME HAZARD FROM HYDROGEN CARS IN ROAD TUNNELS AND THE IMPLICATION ON HYDROGEN CAR DESIGN INITIAL ASSESSMENT OF THE IMPACT OF JET FLAME HAZARD FROM HYDROGEN CARS IN ROAD TUNNELS AND THE IMPLICATION ON HYDROGEN CAR DESIGN Wu, Y Department of Chemical and Process Engineering, University of Sheffield,

More information

CFD Grows Up! Martin W. Liddament Ventilation, Energy and Environmental Technology (VEETECH Ltd) What is Computational Fluid Dynamics?

CFD Grows Up! Martin W. Liddament Ventilation, Energy and Environmental Technology (VEETECH Ltd) What is Computational Fluid Dynamics? CIBSE/ASHRAE Meeting CFD Grows Up! Martin W. Liddament Ventilation, Energy and Environmental Technology (VEETECH Ltd) 10 th December 2003 What is Computational Fluid Dynamics? CFD is a numerical means

More information

CFD AND MULTI-ZONE MODELLING OF FOG FORMATION RISK IN A NATURALLY VENTILATED INDUSTRIAL BUILDING

CFD AND MULTI-ZONE MODELLING OF FOG FORMATION RISK IN A NATURALLY VENTILATED INDUSTRIAL BUILDING 2000 Elsevier Science Ltd. All rights reserved., Air Distribution in Rooms, (ROOMVENT 2000) Editor: H.B. Awbi 767 CFD AND MULTI-ZONE MODELLING OF FOG FORMATION RISK IN A NATURALLY VENTILATED INDUSTRIAL

More information

Eco Pelmet Modelling and Assessment. CFD Based Study. Report Number 610.14351-R1D1. 13 January 2015

Eco Pelmet Modelling and Assessment. CFD Based Study. Report Number 610.14351-R1D1. 13 January 2015 EcoPelmet Pty Ltd c/- Geoff Hesford Engineering 45 Market Street FREMANTLE WA 6160 Version: Page 2 PREPARED BY: ABN 29 001 584 612 2 Lincoln Street Lane Cove NSW 2066 Australia (PO Box 176 Lane Cove NSW

More information

CFD STUDY OF TEMPERATURE AND SMOKE DISTRIBUTION IN A RAILWAY TUNNEL WITH NATURAL VENTILATION SYSTEM

CFD STUDY OF TEMPERATURE AND SMOKE DISTRIBUTION IN A RAILWAY TUNNEL WITH NATURAL VENTILATION SYSTEM CFD STUDY OF TEMPERATURE AND SMOKE DISTRIBUTION IN A RAILWAY TUNNEL WITH NATURAL VENTILATION SYSTEM J. Schabacker, M. Bettelini, Ch. Rudin HBI Haerter AG Thunstrasse 9, P.O. Box, 3000 Bern, Switzerland

More information

CFD SIMULATION OF SDHW STORAGE TANK WITH AND WITHOUT HEATER

CFD SIMULATION OF SDHW STORAGE TANK WITH AND WITHOUT HEATER International Journal of Advancements in Research & Technology, Volume 1, Issue2, July-2012 1 CFD SIMULATION OF SDHW STORAGE TANK WITH AND WITHOUT HEATER ABSTRACT (1) Mr. Mainak Bhaumik M.E. (Thermal Engg.)

More information

CFD Based Air Flow and Contamination Modeling of Subway Stations

CFD Based Air Flow and Contamination Modeling of Subway Stations CFD Based Air Flow and Contamination Modeling of Subway Stations Greg Byrne Center for Nonlinear Science, Georgia Institute of Technology Fernando Camelli Center for Computational Fluid Dynamics, George

More information

Thermal environment in indoor spaces with under-floor air distribution systems: 1. Impact of design parameters (1522-RP)

Thermal environment in indoor spaces with under-floor air distribution systems: 1. Impact of design parameters (1522-RP) Lee, K.S., Xue, G., Jiang, Z., and Chen, Q. 0. Thermal environment in indoor spaces with under-floor air distribution systems:. Impact of design parameters (5-RP), HVAC&R Research, 8(6), 8 9. Thermal environment

More information

BAFFLES AS A MEANS OF STATION PROTECTION FROM HIGH AIR VELOCITIES - COMPARISON OF ANALYTICAL AND FIELD MEASUREMENTS RESULTS

BAFFLES AS A MEANS OF STATION PROTECTION FROM HIGH AIR VELOCITIES - COMPARISON OF ANALYTICAL AND FIELD MEASUREMENTS RESULTS - 289 - BAFFLES AS A MEANS OF STATION PROTECTION FROM HIGH AIR VELOCITIES - COMPARISON OF ANALYTICAL AND FIELD MEASUREMENTS RESULTS Maevski Igor, PhD, PE Jacobs Engineering, USA ABSTRACT Draught relief

More information

CAN DEMAND CONTROLLED VENTILATION REPLACE SPACE HEATING IN OFFICE BUILDINGS WITH LOW HEATING DEMAND?

CAN DEMAND CONTROLLED VENTILATION REPLACE SPACE HEATING IN OFFICE BUILDINGS WITH LOW HEATING DEMAND? Topic B3: Control of indoor environment CAN DEMAND CONTROLLED VENTILATION REPLACE SPACE HEATING IN OFFICE BUILDINGS WITH LOW HEATING DEMAND? Axel CABLE 1,*, Mads MYSEN 1,2, Kari THUNSHELLE 1 1 SINTEF,

More information

Air distribution effectiveness with stratified air distribution systems

Air distribution effectiveness with stratified air distribution systems Lee, K.S., Jiang, Z., and Chen, Q. 2009 Air distribution effectiveness with stratified air distribution systems, ASHRAE Transactions, 115(2). Air distribution effectiveness with stratified air distribution

More information

CALCULATION AND ASSESSING NATURAL VENTILATION IN A SINGLE OPENING OFFICE ROOM WITH DIFFERENT WINDOWS IN THE REGIME OF HOT SUMMER AND COLD WINTER

CALCULATION AND ASSESSING NATURAL VENTILATION IN A SINGLE OPENING OFFICE ROOM WITH DIFFERENT WINDOWS IN THE REGIME OF HOT SUMMER AND COLD WINTER CALCULATION AND ASSESSING NATURAL VENTILATION IN A SINGLE OPENING OFFICE ROOM WITH DIFFERENT WINDOWS IN THE REGIME OF HOT SUMMER AND COLD WINTER Fang Ruan 1,2, Nianping Li 1,*, Jibo Long 1,2 1 College

More information

NUMERICAL ANALYSIS OF THE EFFECTS OF WIND ON BUILDING STRUCTURES

NUMERICAL ANALYSIS OF THE EFFECTS OF WIND ON BUILDING STRUCTURES Vol. XX 2012 No. 4 28 34 J. ŠIMIČEK O. HUBOVÁ NUMERICAL ANALYSIS OF THE EFFECTS OF WIND ON BUILDING STRUCTURES Jozef ŠIMIČEK email: [email protected] Research field: Statics and Dynamics Fluids mechanics

More information

Development of Ventilation Strategy in Diesel Engine Power Plant by Using CFD Modelling

Development of Ventilation Strategy in Diesel Engine Power Plant by Using CFD Modelling Development of Ventilation Strategy in Diesel Engine Power Plant by Using CFD Modelling Panu Mustakallio and Risto Kosonen Halton Oy, Haltonintie 1-3, 47400 Kausala, Finland E-mail: [email protected]

More information

Using Computational Fluid Dynamics (CFD) for improving cooling system efficiency for Data centers

Using Computational Fluid Dynamics (CFD) for improving cooling system efficiency for Data centers Data Centre Best Practises Workshop Using Computational Fluid Dynamics (CFD) for improving cooling system efficiency for Data centers Shishir Gupta 17 th March 2009 You are Here Introduction to CFD Data

More information

Computational Fluid Dynamic Investigation of Liquid Rack Cooling in Data Centres

Computational Fluid Dynamic Investigation of Liquid Rack Cooling in Data Centres School of something School of Mechanical Engineering FACULTY OF OTHER ENGINEERING Computational Fluid Dynamic Investigation of Liquid Rack Cooling in Data Centres A. Almoli 1, A. Thompson 1, N. Kapur 1,

More information

Flow in data racks. 1 Aim/Motivation. 3 Data rack modification. 2 Current state. EPJ Web of Conferences 67, 02070 (2014)

Flow in data racks. 1 Aim/Motivation. 3 Data rack modification. 2 Current state. EPJ Web of Conferences 67, 02070 (2014) EPJ Web of Conferences 67, 02070 (2014) DOI: 10.1051/ epjconf/20146702070 C Owned by the authors, published by EDP Sciences, 2014 Flow in data racks Lukáš Manoch 1,a, Jan Matěcha 1,b, Jan Novotný 1,c,JiříNožička

More information

INTERNATIONAL JOURNAL OF MECHANICAL ENGINEERING AND TECHNOLOGY (IJMET)

INTERNATIONAL JOURNAL OF MECHANICAL ENGINEERING AND TECHNOLOGY (IJMET) INTERNATIONAL JOURNAL OF MECHANICAL ENGINEERING AND TECHNOLOGY (IJMET) Proceedings of the 2 nd International Conference on Current Trends in Engineering and Management ICCTEM -2014 ISSN 0976 6340 (Print)

More information

Mechanical and Natural Ventilation

Mechanical and Natural Ventilation BBSE3006: Air Conditioning and Refrigeration II http://www.hku.hk/bse/bbse3006/ Mechanical and Natural Ventilation Dr. Sam C. M. Hui Department of Mechanical Engineering The University of Hong Kong E-mail:

More information

Validation of CFD Simulations for Natural Ventilation

Validation of CFD Simulations for Natural Ventilation Jiang, Y., Allocca, C., and Chen, Q. 4. Validation of CFD simulations for natural ventilation, International Journal of Ventilation, (4), 359-37. Validation of CFD Simulations for Natural Ventilation Yi

More information

DESIGN OF NATURAL VENTILATION WITH CFD CHAPTER SEVEN. Qingyan Chen. difficult to understand and model, even for simple

DESIGN OF NATURAL VENTILATION WITH CFD CHAPTER SEVEN. Qingyan Chen. difficult to understand and model, even for simple CHAPTER SEVEN L. Glicksman and J. Lin (eds), Sustainable Urban Housing in China, 116-123 2006 Springer. Printed in the Netherlands. DESIGN OF NATURAL VENTILATION WITH CFD Qingyan Chen INTRODUCTION As the

More information

Problem Statement In order to satisfy production and storage requirements, small and medium-scale industrial

Problem Statement In order to satisfy production and storage requirements, small and medium-scale industrial Problem Statement In order to satisfy production and storage requirements, small and medium-scale industrial facilities commonly occupy spaces with ceilings ranging between twenty and thirty feet in height.

More information

Yijun Gao, Wei Wu, Zongwei Han, Xianting Li *

Yijun Gao, Wei Wu, Zongwei Han, Xianting Li * Study on the performance of air conditioning system combining heat pipe and vapor compression based on ground source energy-bus for commercial buildings in north China Yijun Gao, Wei Wu, Zongwei Han, Xianting

More information

MODELLING COUPLED HEAT AND AIR FLOW: PING-PONG VS ONIONS

MODELLING COUPLED HEAT AND AIR FLOW: PING-PONG VS ONIONS MODELLING COUPLED HEAT AND AIR FLOW: PING-PONG VS ONIONS Jan Hensen University of Strathclyde Energy Systems Research Unit 75 Montrose Street, GLASGOW G1 1XJ, Scotland Email: [email protected] SYNOPSIS

More information

HEAT TRANSFER ANALYSIS IN A 3D SQUARE CHANNEL LAMINAR FLOW WITH USING BAFFLES 1 Vikram Bishnoi

HEAT TRANSFER ANALYSIS IN A 3D SQUARE CHANNEL LAMINAR FLOW WITH USING BAFFLES 1 Vikram Bishnoi HEAT TRANSFER ANALYSIS IN A 3D SQUARE CHANNEL LAMINAR FLOW WITH USING BAFFLES 1 Vikram Bishnoi 2 Rajesh Dudi 1 Scholar and 2 Assistant Professor,Department of Mechanical Engineering, OITM, Hisar (Haryana)

More information

How To Model With Cfd Using Phoenics

How To Model With Cfd Using Phoenics The Use and Application of CFD in the Air Conditioning and Fire Protection Industry AIRAH NSW February 2008 The Use and Application of CFD in the Air Conditioning and Fire Protection Industry An Introduction

More information

ASSESSMENT OF MODELING SLATTED FLOOR AS POROUS MEDIA IN LIVESTOCK BUILDINGS IN TWO VENTILATION SYSTEMS. Inge Lehmanns Gade 10, 8000, Aarhus C, Denmark

ASSESSMENT OF MODELING SLATTED FLOOR AS POROUS MEDIA IN LIVESTOCK BUILDINGS IN TWO VENTILATION SYSTEMS. Inge Lehmanns Gade 10, 8000, Aarhus C, Denmark ASSESSMENT OF MODELING SLATTED FLOOR AS POROUS MEDIA IN LIVESTOCK BUILDINGS IN TWO VENTILATION SYSTEMS Li Rong 1, Bjarne Bjerg 2, Guoqiang Zhang 1 1 Department of Engineering, Aarhus University Inge Lehmanns

More information

CFD MODELLING FOR SWIRL DIFFUSER AND ITS IMPLICATIONS ON AIR CHANGE EFFECTIVENESS ASSESSMENT TO GREEN STAR'S IEQ-2

CFD MODELLING FOR SWIRL DIFFUSER AND ITS IMPLICATIONS ON AIR CHANGE EFFECTIVENESS ASSESSMENT TO GREEN STAR'S IEQ-2 CFD MODELLING FOR SWIRL DIFFUSER AND ITS IMPLICATIONS ON AIR CHANGE EFFECTIVENESS ASSESSMENT TO GREEN STAR'S IEQ-2 Eddy Rusly 1 and Mirek Piechowski 2 1,2 Meinhardt (VIC), Melbourne, Australia ABSTRACT

More information

CFD ANALYSIS CHALLENGES IN BUILDING SIMULATION FOR SIMBUILD2004 CONFERENCE. Ferdinand Schmid and Galen Burrell Architectural Energy Corporation

CFD ANALYSIS CHALLENGES IN BUILDING SIMULATION FOR SIMBUILD2004 CONFERENCE. Ferdinand Schmid and Galen Burrell Architectural Energy Corporation CFD ANALYSIS CHALLENGES IN BUILDING SIMULATION FOR SIMBUILD2004 CONFERENCE Ferdinand Schmid and Galen Burrell Architectural Energy Corporation ABSTRACT This paper discusses the capabilities and challenges

More information

DESIGN AND FLOW VELOCITY SIMULATION OF DIFFUSER AUGMENTED WIND TURBINE USING CFD

DESIGN AND FLOW VELOCITY SIMULATION OF DIFFUSER AUGMENTED WIND TURBINE USING CFD Journal of Engineering Science and Technology Vol. 8, No. 4 (2013) 372-384 School of Engineering, Taylor s University DESIGN AND FLOW VELOCITY SIMULATION OF DIFFUSER AUGMENTED WIND TURBINE USING CFD T.

More information

THERMAL STRATIFICATION IN A HOT WATER TANK ESTABLISHED BY HEAT LOSS FROM THE TANK

THERMAL STRATIFICATION IN A HOT WATER TANK ESTABLISHED BY HEAT LOSS FROM THE TANK THERMAL STRATIFICATION IN A HOT WATER TANK ESTABLISHED BY HEAT LOSS FROM THE TANK J. Fan and S. Furbo Abstract Department of Civil Engineering, Technical University of Denmark, Brovej, Building 118, DK-28

More information

NUMERICAL INVESTIGATION OF HEAT AND MASS TRANSFER IN A REFRIGERATED TRUCK COMPARTMENT

NUMERICAL INVESTIGATION OF HEAT AND MASS TRANSFER IN A REFRIGERATED TRUCK COMPARTMENT NUMERICAL INVESTIGATION OF HEAT AND MASS TRANSFER IN A REFRIGERATED TRUCK COMPARTMENT T. LAFAYE DE MICHEAUX (a), V. SARTRE (a)*, A. STUMPF (b), J. BONJOUR (a) (a) Université de Lyon, CNRS INSA-Lyon, CETHIL,

More information

Ravi Kumar Singh*, K. B. Sahu**, Thakur Debasis Mishra***

Ravi Kumar Singh*, K. B. Sahu**, Thakur Debasis Mishra*** Ravi Kumar Singh, K. B. Sahu, Thakur Debasis Mishra / International Journal of Engineering Research and Applications (IJERA) ISSN: 48-96 www.ijera.com Vol. 3, Issue 3, May-Jun 3, pp.766-77 Analysis of

More information

EVALUATION OF PHOENICS CFD FIRE MODEL AGAINST ROOM CORNER FIRE EXPERIMENTS

EVALUATION OF PHOENICS CFD FIRE MODEL AGAINST ROOM CORNER FIRE EXPERIMENTS EVALUATION OF PHOENICS CFD FIRE MODEL AGAINST ROOM CORNER FIRE EXPERIMENTS Yunlong Liu and Vivek Apte CSIRO Fire Science and Technology Laboratory PO Box 31 North Ryde, NSW 167, Australia TEL:+61 2 949

More information

Rate of Heating Analysis of Data Centers during Power Shutdown

Rate of Heating Analysis of Data Centers during Power Shutdown 2011. American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Transactions, Volume 117, Part 1. For personal use only. Additional reproduction,

More information

CFD Beyond the Whitespace. Datacentres Central & Eastern Europe

CFD Beyond the Whitespace. Datacentres Central & Eastern Europe CFD Beyond the Whitespace Datacentres Central & Eastern Europe September 2013 CONTENTS 1.0 Introduction 2.0 What is CFD? How it Works CFD in Data Centres 3.0 CFD Outside the White Space Case Study 4.0

More information

Experimental Evaluation of the Discharge Coefficient of a Centre-Pivot Roof Window

Experimental Evaluation of the Discharge Coefficient of a Centre-Pivot Roof Window Experimental Evaluation of the Discharge Coefficient of a Centre-Pivot Roof Window Ahsan Iqbal #1, Alireza Afshari #2, Per Heiselberg *3, Anders Høj **4 # Energy and Environment, Danish Building Research

More information

Use of Computational Fluid Dynamics for Calculating Flow Rates Through Perforated Tiles in Raised-Floor Data Centers

Use of Computational Fluid Dynamics for Calculating Flow Rates Through Perforated Tiles in Raised-Floor Data Centers This article appeared in the International Journal of Heating, Ventilation, Air-Conditioning, and Refrigeration Research, Volume 9, Number 2, April 2003, pp. 153-166. Use of Computational Fluid Dynamics

More information

IPACK2005-73273 DISTRIBUTED LEAKAGE FLOW IN RAISED-FLOOR DATA CENTERS

IPACK2005-73273 DISTRIBUTED LEAKAGE FLOW IN RAISED-FLOOR DATA CENTERS Proceedings of IPACK5 ASME InterPACK '5 July 17-, San Francisco, California, USA IPACK5-7373 DISTRIBUTED LEAKAGE FLOW IN RAISED-FLOOR DATA CENTERS Amir Radmehr Innovative Research, Inc. Plymouth, MN, USA

More information

SINGLE TRAIN PASSING THROUGH A TUNNEL

SINGLE TRAIN PASSING THROUGH A TUNNEL European Conference on Computational Fluid Dynamics ECCOMAS CFD 2006 P. Wesseling, E. Oñate, J. Périaux (Eds) TU Delft, The Netherlands, 2006 SINGLE TRAIN PASSING THROUGH A TUNNEL Jakub Novák* *Skoda Research,

More information

RAISED-FLOOR DATA CENTER: PERFORATED TILE FLOW RATES FOR VARIOUS TILE LAYOUTS

RAISED-FLOOR DATA CENTER: PERFORATED TILE FLOW RATES FOR VARIOUS TILE LAYOUTS Paper Presented at ITHERM 2004 Ninth Intersociety Conference on Thermal and Thermomechanical Phenomena in Electronic Systems June 1-4, Las Vegas, NV RAISED-FLOOR DATA CENTER: PERFORATED TILE FLOW RATES

More information

Methods for Effective Room Air Distribution. Dan Int-Hout Chief Engineer, Krueger Richardson, Texas

Methods for Effective Room Air Distribution. Dan Int-Hout Chief Engineer, Krueger Richardson, Texas Methods for Effective Room Air Distribution Dan Int-Hout Chief Engineer, Krueger Richardson, Texas Agenda Overview LEED issues and Update Perimeter Acoustics Thermal Comfort IAQ / Standard 62.1 Update

More information

COOKING THE ROOF CFD BEYOND THE WHITE SPACE

COOKING THE ROOF CFD BEYOND THE WHITE SPACE COOKING THE ROOF CFD BEYOND THE WHITE SPACE Alex Nock 20 November 2013 CONTENTS 1. Introduction» Introduction to RED» Modeling in Data Centres 1. What is CFD» How it works» CFD in Data Centres 3. Cooking

More information

SPECIAL APPLICATIONS

SPECIAL APPLICATIONS Page 1 SPECIAL APPLICATIONS The protection of microelectronics clean rooms using aspirating smoke detection systems requires special consideration. The physical configuration of the room(s) and the direction

More information

Performance Estimation of Water Thermal Energy Storage Tank by Using Simplified Simulation

Performance Estimation of Water Thermal Energy Storage Tank by Using Simplified Simulation Performance Estimation of Water Thermal Energy Storage Tank by Using Simplified Simulation M. Kubota, K. Sagara, T. Yamanaka, H. Kotani Division of Global Architecture, Graduate School of Engineering,

More information

Natural Convection. Buoyancy force

Natural Convection. Buoyancy force Natural Convection In natural convection, the fluid motion occurs by natural means such as buoyancy. Since the fluid velocity associated with natural convection is relatively low, the heat transfer coefficient

More information

E N G I N E E R I N G E X C E L L E N C E. Tunnel ventilation

E N G I N E E R I N G E X C E L L E N C E. Tunnel ventilation E N G I N E E R I N G E X C E L L E N C E Tunnel ventilation n Tunnel ventilation know-how Ventilation is a key element of electro-mechanical equipment and is crucial to the safety of tunnel operation.

More information

THE CFD SIMULATION OF THE FLOW AROUND THE AIRCRAFT USING OPENFOAM AND ANSA

THE CFD SIMULATION OF THE FLOW AROUND THE AIRCRAFT USING OPENFOAM AND ANSA THE CFD SIMULATION OF THE FLOW AROUND THE AIRCRAFT USING OPENFOAM AND ANSA Adam Kosík Evektor s.r.o., Czech Republic KEYWORDS CFD simulation, mesh generation, OpenFOAM, ANSA ABSTRACT In this paper we describe

More information

CFD Application on Food Industry; Energy Saving on the Bread Oven

CFD Application on Food Industry; Energy Saving on the Bread Oven Middle-East Journal of Scientific Research 13 (8): 1095-1100, 2013 ISSN 1990-9233 IDOSI Publications, 2013 DOI: 10.5829/idosi.mejsr.2013.13.8.548 CFD Application on Food Industry; Energy Saving on the

More information

2013 Code_Saturne User Group Meeting. EDF R&D Chatou, France. 9 th April 2013

2013 Code_Saturne User Group Meeting. EDF R&D Chatou, France. 9 th April 2013 2013 Code_Saturne User Group Meeting EDF R&D Chatou, France 9 th April 2013 Thermal Comfort in Train Passenger Cars Contact For further information please contact: Brian ANGEL Director RENUDA France [email protected]

More information

International Journal of Food Engineering

International Journal of Food Engineering International Journal of Food Engineering Volume 6, Issue 1 2010 Article 13 Numerical Simulation of Oscillating Heat Pipe Heat Exchanger Benyin Chai, Shandong University Min Shao, Shandong Academy of Sciences

More information

TWO-DIMENSIONAL FINITE ELEMENT ANALYSIS OF FORCED CONVECTION FLOW AND HEAT TRANSFER IN A LAMINAR CHANNEL FLOW

TWO-DIMENSIONAL FINITE ELEMENT ANALYSIS OF FORCED CONVECTION FLOW AND HEAT TRANSFER IN A LAMINAR CHANNEL FLOW TWO-DIMENSIONAL FINITE ELEMENT ANALYSIS OF FORCED CONVECTION FLOW AND HEAT TRANSFER IN A LAMINAR CHANNEL FLOW Rajesh Khatri 1, 1 M.Tech Scholar, Department of Mechanical Engineering, S.A.T.I., vidisha

More information

HANDOUT CLIMATIC WIND TUNNEL MAHLE BEHR GMBH & CO. KG STATUS: FEBRUARY 2014

HANDOUT CLIMATIC WIND TUNNEL MAHLE BEHR GMBH & CO. KG STATUS: FEBRUARY 2014 HANDOUT CLIMATIC WIND TUNNEL MAHLE BEHR GMBH & CO. KG STATUS: FEBRUARY 2014 CLIMATIC WIND TUNNEL FOR CAR, VAN AND TRUCK Location 70469 Stuttgart-Feuerbach, Germany Size Test section (L x W x H) 13 x 8.8

More information

Full scale tunnel fire tests of VID Fire-Kill Low Pressure Water Mist Tunnel Fire Protection System in Runehamar test tunnel, spring 2009

Full scale tunnel fire tests of VID Fire-Kill Low Pressure Water Mist Tunnel Fire Protection System in Runehamar test tunnel, spring 2009 Full scale tunnel fire tests of VID Fire-Kill Low Pressure Water Mist Tunnel Fire Protection System in Runehamar test tunnel, spring 2009 By Carsten Palle, VID Fire-Fill, www.vid.eu Presented at ISTSS

More information

Kan behovsstyrt ventilasjon erstatte lokal varme? Axel Cablé, SINTEF Seminar 19.11.13

Kan behovsstyrt ventilasjon erstatte lokal varme? Axel Cablé, SINTEF Seminar 19.11.13 Kan behovsstyrt ventilasjon erstatte lokal varme? Axel Cablé, SINTEF Seminar 19.11.13 1 Kan behovsstyrt ventilasjon erstatte lokal varme? Principles Challenges VABAT Project 2 Principles Increased envelope

More information

Challenges for Use of Fixed Fire Suppression Systems in Road Tunnel Fire Protection

Challenges for Use of Fixed Fire Suppression Systems in Road Tunnel Fire Protection Challenges for Use of Fixed Fire Suppression Systems in Road Tunnel Fire Protection Z. G. Liu *, A. Kashef, G. Lougheed, and A. K. Kim Fire Research Program, Institute for Research in Construction National

More information

AIR DISTRIBUTION FOR COMFORT AND IAQ

AIR DISTRIBUTION FOR COMFORT AND IAQ AIR DISTRIBUTION FOR COMFORT AND IAQ Heating Piping and Air Conditioning March 1998 Dan Int-Hout Chief Engineer KRUEGER EXCELLENCE IN AIR DISTRIBUTION Modern environmentally controlled spaces consume significant

More information

CFD Applications of PHOENICS on Building Environment and Fire Safety Design

CFD Applications of PHOENICS on Building Environment and Fire Safety Design CFD Applications of PHOENICS on Building Environment and Fire Safety Design Dr. Qian Wang, Kenneth Ma & Micael Lundqvist Ove Arup Pty Ltd Level 10, 201 Kent Street, Sydney, NSW 2000, Australia PO Box 76,

More information

Displacement ventilation

Displacement ventilation General The displacement ventilation principle is the oldest form of ventilation and can be achieved without the use of fans. Air movement occurs by means of the density differences between supply air

More information

Integrated Personalized Ventilation for Minimizing Cross Infection

Integrated Personalized Ventilation for Minimizing Cross Infection Integrated Personalized Ventilation for Minimizing Cross Infection by Peter V. Nielsen Peter V. Nielsen, Aalborg University [email protected] 1 Personalized Ventilation Melikow et al. Peter V. Nielsen,

More information

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES

More information

Andrea Basti* Italian National Institute of Nuclear Physics (INFN) Gran Sasso National Laboratory (LNGS) *Research Grant Holder

Andrea Basti* Italian National Institute of Nuclear Physics (INFN) Gran Sasso National Laboratory (LNGS) *Research Grant Holder Evaluation of the possibility to use waterscreen for people evacuation from the Gran Sasso National Laboratory inside the Gran Sasso highway tunnel in case of fire The case of The Gran Sasso National Laboratory

More information

SMOKE HAZARD ASSESSMENT USING COMPUTATIONAL FLUID DYNAMICS (CFD) MODELLING

SMOKE HAZARD ASSESSMENT USING COMPUTATIONAL FLUID DYNAMICS (CFD) MODELLING SMOKE HAZARD ASSESSMENT USING COMPUTATIONAL FLUID DYNAMICS (CFD) MODELLING Baldev S Kandola and Mark Morris AEA Consultancy Services (SRD), Thomson House, Risley, Warrington, Cheshire WA3 6AT Fire is a

More information

Piotr Tofiło a,*, Marek Konecki b, Jerzy Gałaj c, Waldemar Jaskółowski d, Norbert Tuśnio e, Marcin Cisek f

Piotr Tofiło a,*, Marek Konecki b, Jerzy Gałaj c, Waldemar Jaskółowski d, Norbert Tuśnio e, Marcin Cisek f Available online at www.sciencedirect.com Procedia Engineering 57 (2013 ) 1156 1165 11th International Conference on Modern Building Materials, Structures and Techniques, MBMST 2013 Expert System for Building

More information

Computational Fluid Dynamics or Wind Tunnel Modeling?

Computational Fluid Dynamics or Wind Tunnel Modeling? Computational Fluid Dynamics or Wind Tunnel Modeling? J.D. McAlpine, Envirometrics, Inc. CFD holds great promise for replacing the wind tunnel in coming years as the science behind CFD improves and computers

More information

Energy Efficient HVAC-system and Building Design

Energy Efficient HVAC-system and Building Design Energy Efficient HVAC-system and Building Design Maija Virta 1, Harri Itkonen 1, Panu Mustakallio 1, Risto Kosonen 1 1 Halton Oy, Finland Corresponding email: [email protected] SUMMARY This paper

More information

A NODAL MODEL FOR DISPLACEMENT VENTILATION AND CHILLED CEILING SYSTEMS IN OFFICE SPACES

A NODAL MODEL FOR DISPLACEMENT VENTILATION AND CHILLED CEILING SYSTEMS IN OFFICE SPACES A NODAL MODEL FOR DISPLACEMENT VENTILATION AND CHILLED CEILING SYSTEMS IN OFFICE SPACES Simon J. Rees and Philip Haves School of Mechanical & Aerospace Engineering, Oklahoma State University, Stillwater,

More information

P. Lu, Sh. Huang and K. Jiang

P. Lu, Sh. Huang and K. Jiang 416 Rev. Adv. Mater. Sci. 33 (2013) 416-422 P. Lu, Sh. Huang and K. Jiang NUMERICAL ANALYSIS FOR THREE-DIMENSIONAL BULK METAL FORMING PROCESSES WITH ARBITRARILY SHAPED DIES USING THE RIGID/VISCO-PLASTIC

More information

CHAPTER 4 CFD ANALYSIS OF THE MIXER

CHAPTER 4 CFD ANALYSIS OF THE MIXER 98 CHAPTER 4 CFD ANALYSIS OF THE MIXER This section presents CFD results for the venturi-jet mixer and compares the predicted mixing pattern with the present experimental results and correlation results

More information

Principles of Ventilation. Patrick N. Breysse, PhD, CIH Peter S.J. Lees, PhD, CIH Johns Hopkins University

Principles of Ventilation. Patrick N. Breysse, PhD, CIH Peter S.J. Lees, PhD, CIH Johns Hopkins University This work is licensed under a Creative Commons Attribution-NonCommercial-ShareAlike License. Your use of this material constitutes acceptance of that license and the conditions of use of materials on this

More information

AN EFFECT OF GRID QUALITY ON THE RESULTS OF NUMERICAL SIMULATIONS OF THE FLUID FLOW FIELD IN AN AGITATED VESSEL

AN EFFECT OF GRID QUALITY ON THE RESULTS OF NUMERICAL SIMULATIONS OF THE FLUID FLOW FIELD IN AN AGITATED VESSEL 14 th European Conference on Mixing Warszawa, 10-13 September 2012 AN EFFECT OF GRID QUALITY ON THE RESULTS OF NUMERICAL SIMULATIONS OF THE FLUID FLOW FIELD IN AN AGITATED VESSEL Joanna Karcz, Lukasz Kacperski

More information

Supporting document to NORSOK Standard C-004, Edition 2, May 2013, Section 5.4 Hot air flow

Supporting document to NORSOK Standard C-004, Edition 2, May 2013, Section 5.4 Hot air flow 1 of 9 Supporting document to NORSOK Standard C-004, Edition 2, May 2013, Section 5.4 Hot air flow A method utilizing Computational Fluid Dynamics (CFD) codes for determination of acceptable risk level

More information

SBi 2013:12. Use of perforated acoustic panels as supply air diffusers in diffuse ceiling ventilation systems

SBi 2013:12. Use of perforated acoustic panels as supply air diffusers in diffuse ceiling ventilation systems SBi 2013:12 Use of perforated acoustic panels as supply air diffusers in diffuse ceiling ventilation systems Use of perforated acoustic panels as supply air diffusers in diffuse ceiling ventilation systems

More information

Effect of design parameters on temperature rise of windings of dry type electrical transformer

Effect of design parameters on temperature rise of windings of dry type electrical transformer Effect of design parameters on temperature rise of windings of dry type electrical transformer Vikas Kumar a, *, T. Vijay Kumar b, K.B. Dora c a Centre for Development of Advanced Computing, Pune University

More information

EFA PSBP. Natural Ventilation Strategy. Introduction. 1.1 Relevant legislation. 1.1.1 The Building Regulations 2010

EFA PSBP. Natural Ventilation Strategy. Introduction. 1.1 Relevant legislation. 1.1.1 The Building Regulations 2010 EFA PSBP Natural Ventilation Strategy Introduction The Baseline Designs Project will provide scheme design details for a number of Primary and Secondary School Exemplars. For the purposes of setting a

More information

Open Access Numerical Analysis on Mutual Influences in Urban Subway Double-Hole Parallel Tunneling

Open Access Numerical Analysis on Mutual Influences in Urban Subway Double-Hole Parallel Tunneling Send Orders for Reprints to [email protected] The Open Construction and Building Technology Journal, 2014, 8, 455-462 455 Open Access Numerical Analysis on Mutual Influences in Urban Subway Double-Hole

More information

AMCA International. Investigation of the Impact of Building Entrance Air Curtain on Whole Building Energy Use AIR MOVEMENT AND CONTROL

AMCA International. Investigation of the Impact of Building Entrance Air Curtain on Whole Building Energy Use AIR MOVEMENT AND CONTROL AMCA International Investigation of the Impact of Building Entrance Air Curtain on Whole Building Energy Use AIR MOVEMENT AND CONTROL ASSOCIATION INTERNATIONAL, INC. The International Authority on Air

More information

Adaptive strategies for office spaces in the UK climate

Adaptive strategies for office spaces in the UK climate International Conference Passive and Low Energy Cooling 631 Adaptive strategies for office spaces in the UK climate I. Gallou Environment & Energy Studies Programme, Architectural Association Graduate

More information

Influence of fire source locations on the actuation of wet-type sprinklers in an office fire

Influence of fire source locations on the actuation of wet-type sprinklers in an office fire Influence of fire source locations on the actuation of wet-type sprinklers in an office fire Ko-Jen Chen 1 Chun-Ta Tzeng 2 Chi-ming Lai 3 Abstract An experiment is conducted on a full-scale model office

More information

Keywords: Heat transfer enhancement; staggered arrangement; Triangular Prism, Reynolds Number. 1. Introduction

Keywords: Heat transfer enhancement; staggered arrangement; Triangular Prism, Reynolds Number. 1. Introduction Heat transfer augmentation in rectangular channel using four triangular prisms arrange in staggered manner Manoj Kumar 1, Sunil Dhingra 2, Gurjeet Singh 3 1 Student, 2,3 Assistant Professor 1.2 Department

More information

Essam E. Khalil [email protected]

Essam E. Khalil khalile1@asme.org AIR-CONDITIONING SYSTEMS DEVELOPMENTS IN HOSPITALS: COMFORT, AIR QUALITY, AND ENERGY UTILIZATION Essam E. Khalil [email protected] PROFESSOR OF MECHANICAL ENGINEERING, CAIRO UNIVERSITY, EGYPT Abstract

More information

Investigations of a Long-Distance 1000 MW Heat Transport System with APROS Simulation Software

Investigations of a Long-Distance 1000 MW Heat Transport System with APROS Simulation Software th International Conference on Structural Mechanics in Reactor Technology (SMiRT ) Espoo, Finland, August 9-4, 9 SMiRT -Division 3, Paper 56 Investigations of a Long-Distance MW Heat Transport System with

More information

Impacts of Perforated Tile Open Areas on Airflow Uniformity and Air Management Performance in a Modular Data Center

Impacts of Perforated Tile Open Areas on Airflow Uniformity and Air Management Performance in a Modular Data Center Impacts of Perforated Tile Open Areas on Airflow Uniformity and Air Management Performance in a Modular Data Center Sang-Woo Ham 1, Hye-Won Dong 1, Jae-Weon Jeong 1,* 1 Division of Architectural Engineering,

More information

Tomasz STELMACH. WindSim Annual User Meeting 16 June 2011

Tomasz STELMACH. WindSim Annual User Meeting 16 June 2011 Developments of PHOENICS as CFD engine for WindSim Tomasz STELMACH Ltd, UK [email protected] WindSim Annual User Meeting 16 June 2011 Topics of presentation 1. - who we are, what we do 2. PHOENICS 3. GCV -

More information

Comparison of Heat Transfer between a Helical and Straight Tube Heat Exchanger

Comparison of Heat Transfer between a Helical and Straight Tube Heat Exchanger International Journal of Engineering Research and Technology. ISSN 0974-3154 Volume 6, Number 1 (2013), pp. 33-40 International Research Publication House http://www.irphouse.com Comparison of Heat Transfer

More information

Opening the Bonnet. Prof Darren Woolf WYSINWYG 1

Opening the Bonnet. Prof Darren Woolf WYSINWYG 1 Opening the Bonnet Prof Darren Woolf WYSINWYG 1 WYSINWYG What You See Is NOT What You Get: Looking inside the Pandora s Box Prof Darren Woolf WYSINWYG 2 WYSIWYG implies a user interface that allows the

More information

Element D Services Heating, Ventilating, and Air Conditioning

Element D Services Heating, Ventilating, and Air Conditioning PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer

More information

O.F.Wind Wind Site Assessment Simulation in complex terrain based on OpenFOAM. Darmstadt, 27.06.2012

O.F.Wind Wind Site Assessment Simulation in complex terrain based on OpenFOAM. Darmstadt, 27.06.2012 O.F.Wind Wind Site Assessment Simulation in complex terrain based on OpenFOAM Darmstadt, 27.06.2012 Michael Ehlen IB Fischer CFD+engineering GmbH Lipowskystr. 12 81373 München Tel. 089/74118743 Fax 089/74118749

More information

Design of heat exchangers

Design of heat exchangers Design of heat exchangers Exchanger Design Methodology The problem of heat exchanger design is complex and multidisciplinary. The major design considerations for a new heat exchanger include: process/design

More information

Under sill units. Type FSL-B-ZAS

Under sill units. Type FSL-B-ZAS .1 X X testregistrierung Under sill units Type, heat recovery Centrifugal fan Adaptive heat recovery damper HYGIENISCH GETESTET V DI 022 Tested to VDI 022 Secondary air unit for supply air and extract

More information

NUCLEAR ENERGY RESEARCH INITIATIVE

NUCLEAR ENERGY RESEARCH INITIATIVE NUCLEAR ENERGY RESEARCH INITIATIVE Experimental and CFD Analysis of Advanced Convective Cooling Systems PI: Victor M. Ugaz and Yassin A. Hassan, Texas Engineering Experiment Station Collaborators: None

More information

Ultrasonic Detection Algorithm Research on the Damage Depth of Concrete after Fire Jiangtao Yu 1,a, Yuan Liu 1,b, Zhoudao Lu 1,c, Peng Zhao 2,d

Ultrasonic Detection Algorithm Research on the Damage Depth of Concrete after Fire Jiangtao Yu 1,a, Yuan Liu 1,b, Zhoudao Lu 1,c, Peng Zhao 2,d Advanced Materials Research Vols. 368-373 (2012) pp 2229-2234 Online available since 2011/Oct/24 at www.scientific.net (2012) Trans Tech Publications, Switzerland doi:10.4028/www.scientific.net/amr.368-373.2229

More information

Dr.A.K.Shaik Dawood. N.V.Kamalesh. Department of Mechanical Engineering, Associate Professor, Karpagam University, Coimbatore 641202, India.

Dr.A.K.Shaik Dawood. N.V.Kamalesh. Department of Mechanical Engineering, Associate Professor, Karpagam University, Coimbatore 641202, India. CFD Analysis of cooling channels in built-in motorized high speed spindle K.MadhanMuthuGanesh Department of Mechanical Engineering, Research scholar, PSG College of Technology, Coimbatore 641107, India.

More information

Thermal Mass Availability for Cooling Data Centers during Power Shutdown

Thermal Mass Availability for Cooling Data Centers during Power Shutdown 2010 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Transactions (2010, vol 116, part 2). For personal use only. Additional reproduction,

More information

Energy and Buildings

Energy and Buildings Energy and Buildings 42 (2010) 1120 1128 Contents lists available at ScienceDirect Energy and Buildings journal homepage: www.elsevier.com/locate/enbuild Localized air-conditioning with occupancy control

More information