CSP1-L Cable and Line Differential Protection System Performance and functional outline
|
|
|
- Alexina George
- 10 years ago
- Views:
Transcription
1 SYSTEM LINE CSP1-L Cable and Line Differential Protection System Performance and functional outline SCADA RS 232 Operation and display via Notebook Operation and display via CMP1 CAN-BUS FO FO RS 232 (in preparation) CAN-BUS Operation and display via CMP1 Data, FO Data, FO CSP1-L Cable and Line Differential Protection CSP1-L Cable and Line Differential Protection
2 2 LF CSP1-L E
3 Contents 1 Outline and Applications CSP1-L digital, phase-selective differential protection Scope of capacity and functions Design Protection functions Controlling and Monitoring Measuring functions Statistical measuring values Data recording Event recorder Fault recorder Disturbance recorder (optional) CMP Operating the CMP Operating elements of the CMP Functions of the operating elements Programming & Parameter Setting SYSTEM-LINE-SOFT Scope of functions and performance Technical Data Auxiliary voltage Voltage supply CMP Voltage supply CSP Measuring inputs Current inputs Voltage inputs (optional in CSP1-L) Measuring precision Function and signal inputs Outputs Power outputs Signal relays Communication interfaces Standards General regulations High-voltage tests (EN [11.94]) EMC Emission test I EMC Emission test II Mechanical stress Climatic stress Dimensions and weights Order Form...27 LF CSP1-L E 3
4 1 Outline and Applications The top-quality digital protection and control sytems of the»system LINE«fulfil all demands and requirements for protection and control at medium-voltage level. The differential protection systems at both ends of the objects to be protected each consist of two separate devices, i.e. the base unit CSP1-L and the operating and display unit CMP1 Protection requirements CSP1-B Busbar protection CSP1-L Line/cable differential protection SYSTEM LINE Figure 1.1: Range of SYSTEM-LINE devices CSP1-F Feeder management Functionality In the CSP1-L, which is capable of working selfsuffiently, all protection functions are integrated. The base unit is installed into the low-voltage niche (mounted on mounting plate). The wide-range power part permits connection of all aux. voltage e- quipment commonly used in MV systems. Ÿ One device for all switchgears and applications The compact operating and display unit CMP1 is decentralilzed and installed in the front door of the circuit breaker panel. The simple, menu-guided operation, the large display with illuminated background as well as the ergonomically designed surface ensure fast and comprehensive information of the operating personnel at all times. A single bus/line replaces the conventional cable tree. The line differential protection system CSP1-L is a fast, phase-selective cable and line differential protection system. SCADA Development work focussed primarily on the following goals: RS 232 Operation and display via Notebook User-friendly operation, Flexibility, Ease of integration into switchboards, Freely selectable functions, Large range of applications and Standardized communication. FO RS 232 (in preparation) CAN-BUS Operation and display via CMP1 Ÿ Cost optimization at the medium-voltage level SYSTEM 1 SYSTEM 2 CMP1-2 CMP1-2 Data, FO Data, FO CSP1-L FO )2 CSP1-L CSP1-L Cable and Line Differential Protection Figure 1.2: Block diagramm Cable/Line Figure 1.3: CSP1-L Cable and Line Differential Protection System 4 LF CSP1-L E
5 2 CSP1-L digital, phase-selective differential protection The base module CSP1-L, which is capable of working self-sufficiently, comprises the complete protection technology. DIP-SWITCHES DIGITAL INPUTS AUX.VOLTAGE SUPPLY LEDs CURRENT INPUTS SIGNAL RELAY CONTROL OUTPUTS Figure 2.1: CSP1-L 2.1 Scope of capacity and functions The base unit CSP1-L features the following special characteristics: Compact design in robust aluminium/plastic housing in accordance with protection class IP50, Wide-range power part, Wide range of protection and control functions, Flexible management of inputs and outputs, Power outputs directly driving the circuit breaker, Communication with host computers via VDEW-interface with fibre optic conductor (optional) (as per IEC ), Various communication interfaces: CAN-Bus, RS232 for parameter setting, Highly efficient fault recording function (optional), Comprehensive self-monitoring and No maintenance required. LF CSP1-L E 5
6 RS 232 SUBSTATION CONTROL SYSTEM MASTER SYSTEM Notebook CAN-BUS )2 CMP1-2 PARTNER DEVICE CSP1-L Cable and Line Differential Protection System RS 232 optional Display Communication &$1%86 Supervision Statistics Disturbance recorder FO CSP1-L PARTNER DEVICE Signal/indication Measurement Protection Input Output MEDIUM VOLTAGE PANEL Figure 2.2: CSP1-L as Line Differential Protection System 2.2 Design The compact CSP1-L incorporates all components required for: Measured value recording and evaluation, Signal and command output, Entry and evaluation of binary signals, Data transmission and storage and Aux. voltage supply. The housing of the CSP1-L is a very robust, extruded a- luminium/plastic profile which meets the exacting requirements set by environmental influences such as vibration, shock, EMV, etc. The upper circuit board tightly seals the housing, and at the same time serves as connection level. Mounted on this conductor plate are all external connections for the transformers and the control inputs and outputs. Below the cover of this conductor plate are the internal current and voltage transformers, opto-couplers and relays. The housing is designed in such a manner that the protection class IP50 is achieved for the electronics. All external connections, except the measuring transformer and control outputs, are screw- or plug-type. This facilitates fast installation. Connection cables can be prefabricated in advance. The base unit CSP1-L is supplied with the currents embossed by the main current transformers and the analogous input signals provided by the voltage transfomers via separate input transformers. These input signals are galvanically decoupled, analogously filtered and finally transmitted to the analog/digital converter. The CSP1-L is equipped with a 24-Bit signal processor for the protection functions and a high-power 16-Bit controller for processing the control and communication functions. Thanks to the digital signal processing, the influences of higher frequency compensation processes and DC components are suppressed. 6 LF CSP1-L E
7 Figure 2.3: Connection diagramm LF CSP1-L E 7
8 2.3 Protection functions The combined protection and control system CSP1-L is equipped with a great number of protection functions which cover nearly all protection tasks in the mediumvoltage range. All protection functions are fully accessible to the operator and can be activated as desired. Parameter setting of the protection functions can either be done via the operating and display unit CMP1 or by means of PC/Laptop via the»system LINE SOFT«. There are four parameter sets available for each protection function. The protection parameter can be changed as follows: By parameter setting, by means of a digital input signal or by means of data protocol as per IEC (VDEW). For the purpose of integrating external protection devices into the monitoring and control process, the CSP1-L is equipped with manifold functions. No. Protection functions ANSI CSP1-L 1 Phase-selective line differential protection 87L 9 2 Overcurrent time protection non-directional* Short-circuit direction non-directional Earthfault protection non-directional* 50/51G 9 5 Overload protection with thermal image* Programmable protection logics (function/blocking/trip block) 9 7 Tripping circuit supervision 9 8 CB failure protection 50/62BF 9 9 Backward interlocking* 9 Table 2.1: Outline of the protection functions of the CSP1-L *= available as from software version 2.0 Specific features of the line differential protection system Stabilization against transformer saturation in case of internal and external faults and continunous transformer closing rush (transformer at the line end outside the protected range). Multiple algorithm for stabilization in case of transient processes. Protected range (length of line) up to 2 km (860 nm) or up to approx. 25 km (1300 nm). Tripping time: <25 ms LWL data coupling of the stations with bi-directional data transmission of status information, pre-processed measuring values and parameter balancing. Automatic synchronization of the measured value comparison. Continuous supervision of the FO data transmission. Continuous determination of running time of the device-device communication. Tripping for the line differential protection depends on the set parameters and takes place either after confirmation by the counter-station (2 out of 2) or immediately after detection on one side (1 out of 2). In each case the CBs are tripped in both stations by an intertripping command transmitted via FO. The devices of both stations are operated as independent slaves at the host interface. 2.4 Controlling and Monitoring For controlling and monitoring tasks the CSP1-L -System is equipped with the following functions: Graphic display of the status of the switching devices. Direct selection of the circuit breaker. Interlocking of the CB. Protocolling of switching actions and changes in switch positions. 8 LF CSP1-L E
9 The switching device positions are recorded via two opto-decoupled inputs each for»off«and»on«on the CSP1-L. The position signals of the various switching devices (up to 3) are shown on the LC graphic display of the CMP1 in the form of a single-line. Fault and differential positions are indicated by a dotted switching symbol in centre position. The single line diagram is pre-set at the factory in accordance with customer requirements. It can be easily adjusted to specific applications thanks to a configuration software. In addition to status recording it is possible to record, protocol and transmit external protection signals, monitoring messages, external control commands and interlocking functions with varying functionalities via the freely adjustable inputs. Q0 Q9 Q8 Figure 2.4: Example Feeder Configuration In addition to the functional assignments, it is also possible to set parameters for rebouncing time and signal logics for each input. By means of potential-free signal relays it is possible to transmit binary signals for protection and monitoring (e.g. CB failure, backward interlocking). CB = Circuit Breaker No. Control functions CSP1-L 1 Number of controllable switching devices 1 2 Number of recordable switching devices displayable on the graphic display 3 3 Number of power outputs for changing the switch position (coil selection) of circuit breakers 2 4 Number of signal relays 6 5 Number of digital inputs with freely settable parameters 8 6 Command output with defined output and extra running times 9 No. Supervision functions CSP1-L 7 Disturbance/diff. position 9 8 CB removed 9 9 Spring tensioned 9 10 Programmable feeder interlocking 9 Table 2.1: Outline of control and supervision functions of the CSP1-L LF CSP1-L E 9
10 2.5 Measuring functions In addition to the recorded measuring values current and voltage, further measuring values such as active and reactive power etc. are calculated and displayed as primary values. The measured values can be called up cyclically and transmitted via the CMP1, a laptop or a PC, or via communication with the host computer. The measuring error rate is < 1% in the operating range and up to 40 x I N < 3%. No. Measuring functions CSP1-L 1 Phase currents IL1, IL2, IL3 9 2 Earth current I E 9 3 Differential current 9 4 Stabilising current 9 5 Harm. stabilisation factor 9 6 Thermal capacity 9 7 Time up to overload tripping 9 Table 2.2: Outline of measuring functions of the CSP1-L 2.6 Statistical measuring values In addition to measuring value recording, the CSP1-L offers statistical functions. Maximum und average value as well as counting functions can be called up via the CSP1-L. The maximum and average values can be called up via a variable time window. The counting functions such as operating hours or switching cycle counter are resettable. No. Statistical data CSP1-L 1 Max. current value 9 2 Mean current value 9 3 Number of operating cycles per switching device 9 4 Sum total of switched short-circuit currents 9 5 Operating data 9 6 Max. differential current 9 7 Mean differential current 9 8 Max. stabilisation current 9 9 Mean stabilisation current 9 Table 2.3: Statistical data (available as from software version 2.0) 10 LF CSP1-L E
11 2.7 Data recording The CSP1-L offers various protocolling and recording methods for events, fault values and fault records, which are stored in the CSP1-L and can be called up via the CMP1, a PC or the communication interface. This way, the operator has all data for fault analysis and fault elimination locally at his disposal Event recorder The event recorder protocols and stores the last 50 e- vents in the CSP1-L. The recorded messages are filed with running number and real time stamp, safe against device failure, in a non-volatile memory. Each event is stored with date, time, cause, event and information with a resolution of 1 ms. This includes all messages which are related to protection, control, the configurable inputs, parameter setting and internal system supervision of the device. In case of a fault, the protection messages are additionally marked with a clear and definite failure case number Fault recorder The fault recorder stores the last 5 faults failure-safe in the CSP1-L in accordance with the failure case number. In addition to the triggering event, all effective measuring values as stored and displayed as primary values. In case of damage, this permits evaluation and analysis at a later date by means of the protection messages stored in the event recorder Disturbance recorder (optional) The analogous and digital information is stored in the disturbance recorder for the purpose of evaluating mains interferences. Up to 8 digitalized measuring values (phase currents, earth current, conductor voltages, residual voltage) are recorded. Simultaneously, binary input and output signals can be recorded. The maximum recording time amounts to 10 s, with a prerunning and extra running time being adjustable. The measured values are recorded in the form of momentary values. LF CSP1-L E 11
12 3 CMP1 The CMP1 is easy to operate and ergonomically designed. The CMP1 is installed in the front door of the medium-voltage compartment as separate operating and control unit. It informs the operating personnel about the momentary status of the feeder and controls the circuit breaker connected to the CSP1-L. A single cable establishes the connection to the base unit CSP1-L and thus replaces the conventional cable tree. This cable can be easily laid jointly with the aux. voltage supply. The large LC-graphic display permits: Display of a freely configurable single line diagram. Display of switch positions, measuring values and operating instructions. Protocolling of events with real-time stamp. Protocolling of interference events with effective values. Comprehensive commissioning support and manifold testing possibilities. 3.1 Operating the CMP1-2 Parameter setting can be effected via the CMP1. All entries are made via the foil keyboard. Check-backs and status indications are shown on the large graphic display with illuminated background. The display shows switch positions graphically, messages as texts and parameters or measured values in table form. Figure 3.1: CMP1-2 The most significant features of the CMP1 include: Flat, compact design, Wide-range voltage supply, Large LC graphic display with illuminated background (128 x 240 Pixel), Foil keyboard as per protection class IP54, Multi-coloured function keys for menu guidance, Two key switches for fixing the various switching authorizations, 11 multi-coloured LEDs (8 freely configurable), Two RS232 interfaces for parameter setting and readout of data via PC. 12 LF CSP1-L E
13 3.2 Operating elements of the CMP1-2 Direct selection Status LEDs RS232 interface LED assignment Switch over: Local/Remote Direct selection Switch over: Parameter setting/ Control Navigation, Save Reset Figure 3.2: Operating elements of the CMP1 3.3 Functions of the operating elements Main menu Display LED assignment Single line Up/Down Switch over: Local/Remote Switch over: Parameter setting/ Control R.H.: Select menu point Move cursor to the right L.H.: Reverse Move cursor to the left Reset e.g. LEDs Scrolling/changing values + = more/- = less Mode 2 following changes: Starting storing otherwise select menu point (like R.H.) Acknowledge popup-messages Figure 3.3: Functions of the operating elements LF CSP1-L E 13
14 3.4 Programming & Parameter Setting There are 4 complete parameter sets available for the protection functions. Thus it is possible to select, set parameters and switch over between four protection parameter sets. There is always one of the four parameter sets active or in operation. Each parameter set can be edited in the background and stored at the end without influencing the actively operating protection and control functions. A changed parameter set, even if only one single parameter has been changed, will only become active upon confirmation of the storing function (acknowledgement). The fundamental parameter set serves to fix the basic configuration of the device such as rated feeder data, control times, configuration of the inputs and outputs and communication. Locally, parameter setting of the CSP1-L can be effected menu-guided via the operating surface of the CMP1 or by means of a PC via the serial interface. 14 LF CSP1-L E
15 4 SYSTEM-LINE-SOFT 4.1 Scope of functions and performance Operating and evaluation programme/functions The software for setting the parameters of the CSP1-L via PC and interface is still in preparation. The»System-Line-Soft«permits evaluation and parameter setting of the CSP1 family of devices. It will work on any PC with the operating systems Windows 95/98 or Windows NT. Communication takes place via the RS232 interface or via the internal CAN-BUS. It permits operation by the use of the mouse (Windows surface) and has a user-guided window technology. The»System-Line-Soft«is easy to instal and is available in different languages. Available for all devices of the»system Line«, Setting of parameters for all device-specific data, Window technology with operating and status line, Menu-guided plausibility checks, Comprehensive help functions, Readout, readin, comparison with the device possible, Archiving, editing such as copying or erasing data sets, Logbook function, Readout of messages, Cyclic readout of measured values, Further processing of measured values (recording, displaying), Controlling possible with single line diagram display, Query to inputs and outputs, Commissioning support (e.g. diff- und stability values in case of DIFF), fundtional support as well as VDEW-Test, Evaluation of fault records, curve-type illustration, editability, additional information such as Trigger, Initiation of test fault records and Time synchronization from the PC. RS 232 CAN-BUS RS 232 (in Vorbereitung) Figure 4.1: Connection example CSP1-L/CMP1-PC via RS 232 LAPTOP LF CSP1-L E 15
16 Figure 4.2: Display event recorder Figure 4.3: Display fault recorder 16 LF CSP1-L E
17 Figure 4.4: Read out of the digital inputs Figure 4.5: Parameter setting LF CSP1-L E 17
18 5 Technical Data 5.1 Auxiliary voltage Voltage supply CMP1 Voltage ranges Power consumption in idle state Max. power consumption V DC 5 W 10 W V AC 5 VA 10 VA Frequency range f = Hz Voltage supply CSP1 Voltage ranges Power consumption in idle state Max. power consumption V DC 14 W 26 W V AC 14 VA 26 VA Frequency range f = Hz Fixed aux. voltages (EN ): DC AC 24 V, 48 V, 60 V, 110 V, 220 V 24 V, 100 V, 110 V, 230 V The power supply part furthermore covers the following commonly used aux. voltages (among others in the UK) with limited tolerance ranges: 240 V AC with the tolerance range -20% / +15% 254 V AC with the tolerance range -20% / +10% The permissible voltage deviations refer to the fixed rated aux. voltages. Buffering of the aux. voltage supply: = 50 ms at Uemin. In case of aux. voltage failure functioning of the device is ensured for at least 50 ms. The fuse for the aux. voltage supply (230) must be dimension min. 4 A, lag. 18 LF CSP1-L E
19 5.2 Measuring inputs Current inputs Quantity: Measuring method: Rated currents: 3 phase currents + 1 summing current (for earth, e.g. cable-type CT) conventional transformers (other sensors in preparation) 1 A and 5 A Connections per current input: 3 (1S1(1 A), 1S2(5 A), 1S3) Measuring range: Power consumption in the power path: Thermal load capacity: Rated peak short-circuit current: x I N (AC) phase currents x I N (AS) summing current = 0.1 VA at I = I N 250 x I N (dynamic half period of sinus oscillation) Rated short-term current 100 x I N (for 1 s) Permanent load capacity: 4 x I N Voltage inputs (optional in CSP1-L) Quantity: 3 x phase voltage (P-P, P-N) + 1 x residual voltage Measuring method: Rated voltages: conventional transformers (other sensors in preparation) 100, 110 V AC Connections per voltage input: 2 (1A1, 1A2) Measuring range: Thermal load capacity: V AC 2 x U N permanent load capacity Power consumption: = 0.1 VA at U = 230 V Rated frequencies: 50 Hz; 60 Hz (parameter adjustable) LF CSP1-L E 19
20 5.2.3 Measuring precision Current (at rated frequency): x I N < 1% of I N x I N < 3% of Measured value Frequency influence: < 2% / Hz Voltage in relation to rated voltage (at rated frequency): V < 2% V...< 1% Frequency influence: < 2% / Hz Frequency: Hz < 0.05% Power: P N < 2% 5.3 Function and signal inputs Opto-decoupler inputs Quantity: Input voltage range: 14 (CSP1-F1) 22 (CSP1-F3) 26 (CSP1-F5) 14 (CSP1-L) V DC V AC Threshold value recognition: low set range: U on = 8.5 V DC /8.5 V AC (50/60 Hz) (code plug plugged in) U off = 5.5 V DC /4.5 V AC (50/60 Hz) high set range: U on = 35 V DC /35 V AC (50/60 Hz) (code plug open) U off = 20 V DC /19 V AC (50/60 Hz) Input current: < 2 ma DC (depending on input voltage) < 2 ma AC (depending on input voltage) Adjustable rebouncing time: ms per dig. input (1 ms pitch) 20 LF CSP1-L E
21 5.4 Outputs Power outputs Maximum load: motor drive: 500 W DC UH = 24 V, I = 22 A DC for t = 30 s (Is = 1.5*I, t = 100 ms) UH = 60 V, I = 5 A DC for t = 30 s (Is = 1.5*I, t = 100 ms) Operating current tripping coil (CB): Number of outputs: Operating current tripping coil OL: Motor drive OM: 300 W DC for t = 150 ms 2 (CSP1-F1) 2 (CSP1-F3) 3 (CSP1-F5) 2 (CSP1-L) - (CSP1-F1) 2 (CSP1-F3) 4 (CSP1-F5) The following data apply for the outputs OM and OL: Low supply voltage range power circuit (range L) Switching voltage: V DC Permissible permanent current: 24 A continiously Rated peak connection current: 40 A (1 s) Current resistance: Shut-down power: short-circuit resistant 24 A with load shedding measures (idle current circuit) High supply voltage range power circuit (range H): Switching voltage: V DC Permissible permanent current: 15 A continiously Rated peak connection current: 30 A (1 s) Current resistance: Shut-down power: short-circuit resistant 24 A with load shedding measures (idle current circuit) LF CSP1-L E 21
22 5.4.2 Signal relays Number: Switching voltage: 6 CSP1-F1/F3/L, 10 CSP1-F5 250 V AC 220 V DC, ohmic load Imax. = 0.2 A inductive load Imax. = 0.1 A L/R < 50 ms 24 V DC inductive load Imax. = 5 A Switching power: Min. switching load: Max rated current: Switching current: Insulation: Contact material: Contact service life: ohmic 1250 VA AC or 120 W DC, respectively inductive 500 VA AC or 75 W DC, respectively 18 V/2 ma 5 A (16 ms): 20 A 4 kv AgNi + Au mechanical: 100 x 10^6 operating cycle 22 LF CSP1-L E
23 5.5 Communication interfaces RS232 X9 (PC interface) Parameter setting locally by means of PC Galvanically seperated via opto-coupler (2.5 kv). Transmission rate: 9600, Baud (adjustable) 9-pole SUB-D bushing CAN BUS 1 X10 X11 System interface to the CMP1 CAN Specification V2.0 part B (extended frame) Siemens 80C167C on chip CAN Module Galvanically separated via opto-coupler (2.5 kv). 9-pole SUB-D bushing FO Interfaces (optional) CSP1-F1,3,5 X7/X7 Optic fibre conductor connection as per IEC (RxD/TxD) (VDEW recommendation) Setting of slave No.(0-255) Via 8-pol. DIP switch on the CSP1 or parameter setting CMP1 Wave length nm Fibre type 62,5 (core diameter)/125 µm (sleeve diameter) (Multimode/multi-gradient fibre) 2 fibres (transmitting/receiving) Plug type BFOC 2.5 (ST ) max. dampening 8 db max. cable length 2 km CSP1-L Wave length 1300 nm 9/125 µm Monomode fibre (ST ) max. dampening 7 db max. length 20 km LF CSP1-L E 23
24 5.6 Standards General regulations Generic standard DIN EN [02.96] DIN EN [03.93] Product standard DIN EN [11.94] BS 142 DIN EN [04.98] High-voltage tests (EN [11.94]) Voltage test IEC [01.77] DIN EN [04.98] All electric circuits against other electric circuits and touchable surfaces. 2.5 kv (eff.)/50 Hz, 1 min. Peak-voltage test IEC [01.77] 5 kv/0.5 J, 1.2/50 µs High-frequency test DIN EN [05.91] Class 3 Within a electric circuit Electric circuit against earth Electric circuit against electric circuit 1 kv/2 s 2.5 kv/2 s 2.5 kv/2 s EMC Emission test I Disturbance resistance against fast transient disturbance values (Burst) DIN IEC Current supply, mains inputs [10.93] DIN EN [03.96] Other in- and outputs Class 4 Disturbance resistance against the discharge of electricity DIN EN Air discharge [05.97] DIN EN [03.96] Contact discharge Class 3 Disturbance resistance against peak voltages DIN EN [09.96] Within an electric circuit Class 4 Electric circuit against earth Disturbance resistance high-frequency electromagnetic fields DIN EN [08.97] Class 3 ±4 kv, 2.5 khz ±2 kv, 5 khz 8 kv 6 kv 2 kv 4 kv 10 V/m Disturbance resistance against cable-conducted disturbance values induced by high-frequency fields DIN ENV [04.96] 10 V/m Class 3 24 LF CSP1-L E
25 Disturbance resistance against magnetic fields with energy-technological frequencies DIN EN [05.94] Class 5 continuous 3 sec. 100 A/m 1000 A/m EMC Emission test II Measuring of radio interference voltage DIN EN [10.97] Measuring of radio interference radiation DIN EN [10.97] Limit value Class B Limit value Class B Mechanical stress Vibration tests DIN EN [05.96] Class 1 Vibration test for proper functioning Continuous vibration testing 0,035 mm, 0,5 gn, 1 run-through in each direction 1,0 gn, 20 run through in each direction Shock and continuous shock tests DIN EN Shock test for proper functioning [05.96] Shock test for resistance Class 1 Continuous shock test 5 gn, 11 ms, 3 Impulses in each direction 15 gn, 11 ms, 3 Impulses in each direction 10 gn, 16 ms, 1000 Impulses in each direction Climatic stress Climatic stress Temperature range for storage/ in case of emergency (max. 2h) the device must be in operation. Temperature range during operation -25 o C o C -10 o C o C Humidity stress DIN DIN IEC [12.86] Class F over 56 days at 40 C and 95% relative humidity LF CSP1-L E 25
26 5.6.7 Dimensions and weights Basic unit CSP1 Display unit CMP1 Weight: Basic unit CSP1-F Basic unit CSP1-L Display unit CMP1 W 368 mm H 264 mm D 155 mm W 307 mm H 246 mm D 55 mm approx. 8 kg approx. 7 kg 2.2 kg 26 LF CSP1-L E
27 6 Order Form Cable- and line differential protection (Base unit) CSP1- Differential protection; phase selective current measuring Single unit for each line-end via optical communication L2 Cable- and wire differential protection system LS existing of: 2 St. CSP1-L2 + 2 St. CMP1-2 + CAN-connecting cable Type key like CSP1-L2 Protection options Standard type differential protection 1 Transformer technology Conventional 1 A and 5 A, 100/110 V AC Auxiliary voltage supply; power circuit DC V DC V Communication interface without Protocol IEC Protocol IEC , fibre optic (FH-ST plug-type connector; 820 nm 62.5/125 µm) Protocol Profibus Optical interface to remote station (L2- und LS-Typ) (FH-ST connecting cable) range up to 2 km; 820 nm 62.5/125 µm range up to 20 km; 1300 nm 9/125 µm Language English German Options PC-card for local disturbance recording C L H 00 V1 V3 P1 1 2 E G K on request on request Cable- and line differential protection(indication and operation unit) CMP1- Frontplate IP 54; key switches LCD- Display without control functions 2 Interface RS CAN-Bus, fixed wired 2 User identification (Logo) Standard 0 LF CSP1-L E 27
28 This Manual undergoes continuous further development and is subject to changes. We reserve the right to include such changes in future editions of the manual, without prior notice. Status: 06/99 28 LF CSP1-L E
29
30 Woodward SEG GmbH & Co. KG Krefelder Weg 47 D Kempen (Germany) Postfach (P.O.Box) D Kempen (Germany) Phone: +49 (0) Internet Homepage Documentation Sales Phone: +49 (0) Telefax: +49 (0) [email protected] Service Phone: +49 (0) Telefax: +49 (0) [email protected]
TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY
TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY 2 TRACTION NETWORK MONITORING AND PROTECTION SYSTEM Traction network monitoring and protection system,
Quick Connect. quick - simple - efficient. www.g-mw.de
Quick Connect quick - simple - efficient www.g-mw.de Phone: +49 9103 7129-0 Fax: +49 9103 7129-207 Innovative connection technology to plug three single-phase current transformers to multifunctional power
Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact
Data sheet Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact The CT-AHD.12 is an electronic time relay with OFF-delay. It is from the CT-D range. With their MDRC profile and a width of only
38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A
38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit EMR Electromechanical Relays
MasterINTERFACE 39 Series - Relay interface modules
MasterINTERFACE 39 Series - Relay interface modules Common features Space saving 6.2 mm wide Connections for 16-way jumper link Integral coil indication and protection circuit Secure retention and easy
Remote Monitoring and REC 501 Control Unit Product Guide
Remote Monitoring and Control Unit REC 501 Product Guide Issued: May 1999 Status: Updated Version: B/06.11.2001 Data subject to change without notice Features Remote control and monitoring unit for the
Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw
4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and
Waveguide Access Point WGA631. Product Guide
Waveguide Access Point Product Guide Waveguide Access Point Contents 1. Description............................ 3 2. Application............................ 3 3. Technical data... 4 4. Physical interfaces......................
Permissible ambient temperature Operation Storage, transport
The Sitras PRO combined DC protective unit and controller is used in the power supply for DC railways in mass transit and main-line systems up 3,000 V DC. It protects DC switch gear and contact line systems
Automation System TROVIS 6400 TROVIS 6493 Compact Controller
Automation System TROVIS 6400 TROVIS 6493 Compact Controller For panel mounting (front frame 48 x 96 mm/1.89 x 3.78 inch) Application Digital controller to automate industrial and process plants for general
Type: EASY719 DC RC Article No.: 274119. Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description
Type: EASY719 DC RC Article.: 274119 Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC Description 12 digital inputs (4 inputs available as analog inputs) 6 relay outputs LCD display
Current and voltage measuring relays
Current and voltage measuring relays RXIK 1, RXEEB 1 and Page 1 Issued June 1999 Changed since July 1998 Data subject to change without notice RXIK 1 RXEEB 1 (SE980082) (SE980081) (SE970869) Features Application
Single-phase (220...240 V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable
Features 70.11 70.31 70.41 Electronic voltage monitoring relays for single and three-phase applications Multifunctional types, providing the flexibility of monitoring Undervoltage, Overvoltage, Window
RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:
Application : RISH Master 3490 DS measures important electrical parameters of Utility (in normal mode) & Generators (in Power back up) in three phase and single phase Network & replaces the multiple analog
Three-phase monitoring relay CM-PFE
Data sheet Three-phase monitoring relay CM-PFE The CM-PFE is a three-phase monitoring relay that monitors the phase parameter phase sequence and phase failure in three-phase mains. 2CDC 251 005 S0012 Characteristics
MasterINTERFACE 39 Series - Relay interface modules
MasterINTERFACE 39 Series - 39 Common features Space saving 6.2 mm wide Connections for 16-way jumper link Integral coil indication and protection circuit Secure retention and easy ejection by plastic
Voltage Regulator SPAU 341 C. Product Guide
Issued: July 1998 Status: Updated Version: D/25.04.2006 Data subject to change without notice Features Comprehensive voltage regulation for power transformers with on-load tapchangers in distribution substations
Feeder protection. for overhead lines and cables in isolated neutral or compensated networks. Specification
Feeder protection for overhead lines and cables in isolated neutral or compensated networks Specification Feeder protection for overhead lines and cables in isolated neutral or compensated networks Version
Trip circuit supervision relay. Type RXTCS
Trip circuit supervision relay Type RXTCS ABB a global technology leader ABB is a global leader in Power and Automation technologies that enable utility and industry customers to improve performance while
RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER
Application : The RISH CON - Hz transducer is used for frequency measurement. The output signal is proportional to measured frequency and is either load independent DC Current or load independent DC Voltage.
Power-monitoring unit PowerLogic System. Technical data sheet. Power Meter Series 800
Power-monitoring unit PowerLogic System Technical data sheet 2003 Power Meter Series 800 Function and characteristics PB100313 The PowerLogic Power Meter Series 800 offers all the high-performance measurement
Rack mounted telephone- and leased line modem for industrial applications
Rack mounted telephone- and leased line modem for industrial applications TR-6 Rack modem for industrial PSTNand /-wire leased line applications The TR-6 is an analogue V. 9 -rack PSTN modem as well as
38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A
38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 SERIES Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit EMR Electromechanical
Short Form Catalogue. Alarm Systems. Reliable Supervision and Control
Short Form Catalogue Alarm Systems Reliable Supervision and Control Alarm Monitors and Indicators The SELCO product range includes a number of alarm monitors and indicator panels for use in numerous applications.
AMIS. Automated Metering and Information System. Integration of meters from other manufacturers
AMIS Automated Metering and Information System TD-3530/TACU30 Third-Party Device Gateway Integration of meters from other manufacturers Connection and integration of max. 3 meters from third party manufactureres
Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection)
Data sheet Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection) The temperature monitoring relays CM-TCS monitor overtemperature,
Electronic timer CT-VBS.17+18 OFF-delayed without auxiliary voltage, for DC contactors Data sheet
Characteristics Single-function OFF-delay timer for DC contactors, without auxiliary voltage Width.5 mm CDC 5 6 F3 Approvals A culus E CCC CT-VBS a Circuit diagram b Marker label Marks a CE b C-Tick Order
Telephone- and leased line modem for industrial applications TD-36
Telephone- and leased line modem for industrial applications TD-36 Modem for industrial PSTN- and leased line applications The TD-36 is an analogue V.34 PSTN modem as well as an industrial 2-wire leased
RM4TG20 three-phase network control relay RM4-T - range 200..500 V
Characteristics three-phase network control relay RM4-T - range 200..500 V Complementary [Us] rated supply voltage Output contacts Setting accuracy of time delay Delay at power up Measuring cycle Marking
MILLENIUM INSTALLATION MANUAL NTR 735 A. Simple Automation Control Module (MAS)
MILLENIUM Table of contents 1. INTRODUCTION 1 2. HARDWARE DESCRIPTION 2 3. INSTALLATION 5 4. CONNECTION 6 5. USER SAFETY AND PROTECTION OF EQUIPMENT 8 1. Introduction The MILLENIUM series has been designed
Relion 605 series. Self-powered feeder protection REJ603 Product Guide
Relion 605 series Relion 605 series Relion 605 series Self-powered feeder protection Product Guide Product version: 3.0 Contents 1.... 3 2. Relay functions... 3 3. Protection functions... 4 4. Application...
Thermistor motor protection relays CM-MSS.22 and CM-MSS.23
Data sheet Thermistor motor protection relays CM-MSS.22 and CM-MSS.23 The thermistor motor protection relays CM-MSS.22 and CM-MSS.23 monitor the winding temperature of motors and protect them from overheating,
LINETRAXX VMD460-NA. Network and system protection (NS protection) for monitoring the power feed-in of power generation systems
LIETRAXX -A etwork and system protection (S protection) for monitoring the power feed-in of power generation systems TDB301021en/06.2013 LIETRAXX -A etwork and system protection (S protection) for monitoring
Catalog. Arc Guard System TM TVOC-2
Catalog Arc Guard System TM TVOC-2 Introduction An even better Arc Guard System TVOC-2, ABB s latest Arc Monitor, builds on the well known TVOC design. Its new functions and features improve an already
ISIO 200. Binary Input/Output (I/O) Terminal with IEC 61850 Interface
ISIO 200 Binary Input/Output (I/O) Terminal with IEC 61850 Interface Compact and Easy ISIO 200 Put your Binary I/Os where you need them ISIO 200 is a simple and versatile binary I/O terminal with IEC 61850
Multi-Protocol decoder 76 200 with Load regulation
Multi-Protocol decoder 76 2 with Load regulation For locomotives with universal motors on digital layouts operating in the DCC and Motorola data format. Features 76 2 Load regulated multi-protocol decoder
Energy Management Energy Meter Type EM23 DIN
Energy Management Energy Meter Type EM23 DIN Class 1 (kwh) according to EN62053-21 Class B (kwh) according to EN50470-3 Class 2 (kvarh) according to EN62053-23 Accuracy ±0.5 RDG (current/voltage) Energy
Documentation. M-Bus 130-mbx
Documentation M-Bus 130-mbx Introduction The mx M-Bus module is part of the mx Smart Slot communications family. With the integrated SmartSlot technology, mx systems ag offers automatic consumer data read-out
Reyrolle Protection Devices. 7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for energy
Reyrolle Protection Devices 7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for energy Siemens Protection Devices Limited 2 7PG17 XR101 & XR102 Intertripping Relay
Multifunction devices
devices devices devices, electronic Type Page LED multifunction displays pulse, frequency, time (DC) Codix 524 240 pulse, frequency, time (AC+DC) Codix 544 243 LCD multifunction preset counters 1 or 2
Option field bus: without bus with profibus DP. Design-Index (Subject to change)
Amplifier / controller cards ED1 Digital amplifier / controller card ED1 for 1 or 2 proportional solenoids 4 analogue inputs, of which 2 for differential inputs 8 digital inputs Card setting via PC, multi-function
ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application.
1SR 430 824 F9300 Features Monitoring of three-phase mains for phase sequence and failure Powered by the measuring circuit 2 c/o (SPDT) contacts 1 LED for status indication Approvals R: yellow LED - relay
Physical Specifications (Custom design available.)
Helmholtz Coils A useful laboratory technique for getting a fairly uniform magnetic field, is to use a pair of circular coils on a common axis with equal currents flowing in the same sense. For a given
How To Protect Your Power Supply From Dangerous Currents And Voltages
ids ACOS 300 Protection equipment for medium and highvoltage grids ACOS 300 Protection Devices Already minor incidents, such as branches dropping on overhead lines or underground cables damaged by construction
Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages
Data sheet Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages The CM-ESS.M is an electronic voltage monitoring relay that provides reliable monitoring of voltages as well as detection of
Arc Terminator Active Arc-Resistant Switchgear
Arc Terminator Active Arc-Resistant Switchgear Increasing safety and productivity by extinguishing internal arcing faults within the switchgear. The Square D Arc Terminator from Schneider Electric offers
TM7BDM8B expansion block - TM7 - IP67-8 DI/DO - 24V DC - 0.5 A - M8 connector
Product datasheet Characteristics TM7BDM8B expansion block - TM7 - IP67-8 DI/DO - 24V DC - 0.5 A - M8 connector Main Range of product Product or component type Range compatibility Enclosure material Bus
Power Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1
Power Supply Unit, Primary Switched, Narrow Design MINI POWER provides: Extra narrow design with widths of 22.5 mm, 45 mm, and 67.5 mm (0.886, 1.772, and 2.657 in.) Global use due to a wide-range input
Indoor / Outdoor Antenna
z300 High Precision NTP Time Server Indoor / Outdoor Antenna High Precision NTP Time Server with PoE (Indoor or Outdoor use) synchronized by GPS Revision 4 ZTI / 1 boulevard d'armor / BP 20254 / 22302
Features. Display. Measurements. Intelligent. Accuracy. Models. Installation DEIF A/S. Multi-instrument 4921210109D
7000/7000C/7020 Multi-instrument 4921210109D Features Measurements All 3-phase AC measurements True RMS Replaces analogue meters Demand on each phase current Accuracy U, I and F class 0.5 Other values
Contactless Encoder RI360P0-QR24M0-INCRX2-H1181
Compact, rugged housing Many mounting possibilities Status displayed via LED Immune to electromagnetic interference 1024 pulses per revolution (default) 360, 512, 1000, 1024, 2048, 2500, 3600, 4096, parametr.
Earth Fault Detection Basics in Theory
Earth Fault Detection Basics in Theory Author: Dipl.-Ing. Ingo Kühnen Woodward Power Solutions Krefelder Weg 47 47906 Kempen, Germany Kempen, 16.04.2010 Earth_Fault_Detection_20100416.doc page 1 1. Star
E-STOP relays, safety gate monitors
Unit features Safety features Gertebild ][Bildunterschrift_NOT_Sch.tuer_Licht Safety relay for monitoring E-STOP pushbuttons, safety gates and light beam devices Approvals Gertemerkmale Positive-guided
Disturbance Recoder SPCR 8C27. Product Guide
Issued: April 1999 Status: Updated Version: C/26.04.2006 Data subject to change without notice Features Versatile digital disturbance recorder module for recording various phenomena in the electric power
PSU-U-24V/AC-6A/10/FTA-TR-MC PSAC 0624
PSU-U-24V/AC-6A/10/FTA-TR-MC PSAC 0624 v.1.0 AC/AC power supply unit Edition: 1 from 24 th October 2008 Supercedes edition: ---------- 10062009 CONTENTS: 1. Technical description. 1.1. General description
Product Information Sheet UH36 Hi Pot Tester
Product Information Sheet UH36 ETL Prüftechnik GmbH Telefon: +49 711 83 99 39-0 E-Mail: [email protected] Carl-Peters-Straße 23 D-70825 Korntal-Münchingen Telefax: +49 711 83 99 39-9 Internet: www.etl-prueftechnik.de
Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous
Safety relay for monitoring E-STOP pushbuttons. Approvals Unit features Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous 1 auxiliary contact (N/C), instantaneous Safe separation of
Process modules Digital input PMI for 24 V DC inputs for 120 V AC inputs
E031026 000823 Process modules Digital input PMI for inputs for 120 V AC inputs PMI Input E4, E5, GND L- PMI 120 V AC Input E4, E5, Common C E6, E7, GND L- E6, E7, Common C LEDs for the inputs operation
THYRISTORS T1-1PH from 850A to 2700A Specifications Universal 1 Phase Thyristor Unit 55-77-03-62, March 2012
Technical Information THYRISTORS T1-1PH from 850A to 2700A Specifications Universal 1 Phase Thyristor Unit 55-77-03-62, March 2012 GENERAL DESCRIPTION THYRISTORS T1-1PH is a full digital and universal
L-LAS-TB-CL serie. laser light curtains for inline measuring tasks
L-LAS-TB-CL serie laser light curtains for inline measuring tasks Maximum distance 2.000 mm Measurement range 6 up to 98 mm Resolution up to 4 µm up to 1,5 khz scan rate 0-10 V or 4-20 ma analogue output
DS1621 Digital Thermometer and Thermostat
Digital Thermometer and Thermostat www.dalsemi.com FEATURES Temperature measurements require no external components Measures temperatures from 55 C to +125 C in 0.5 C increments. Fahrenheit equivalent
Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated. Ordering information
Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated Ordering information Connection technique Description Description Rated operational current Screw terminals 3 pole AC
Safety technique. Emergency stop module BO 5988 safemaster
Safety technique Emergency stop module BO 5988 safemaster 0221562 Function diagram Pushbutton on Mains or emergencystop () K1 According to EC Directive for machines 98/37/EG According to IEC/E 60204-1
Thermistor motor protection
Thermistor motor protection CM-E Range Thermistor motor protection Thermistor motor protection relays Benefits and advantages Selection table Operating principle and fields of application for thermistor
Substation Automation Products Relion 670/650 series IEC and ANSI Hardware
Substation Automation Products Relion 670/650 series IEC and ANSI Hardware ABB Group 1MRG014097 October 2013 Relion 670/650 series hardware Contents Relion 670/650 series Relion Hardware Relion Common
Analog signal converters CC-E I/I Current / current isolators
ata sheet Analog signal converters CC-E I/I Current / current isolators The CC-E I/I is an isolator for the electrical isolation of current signals without auxiliary supply. It allows the isolation between
ABB 1 NEW. Three-phase monitoring relay for grid feeding CM-UFS.1. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories
2CDC 251 014 F0t09 Features Monitoring of three-phase mains for grid feeding Type-tested in accordance with DIN V VDE V 0126-1-1: February 2006 Neutral conductor connection configurable Can also be used
HCR3.2/.. Chipcard reader HOTEL SOLUTION
s 6 332 HOTEL SOLUTION Chipcard reader HCR3.2/.. Chipcard reader for hotel room access control Reads access code on chipcard Transfers access code to room controller Built-in optical display of messages
ABB i-bus EIB / KNX Analogue Input AE/S 4.2
Product Manual ABB i-bus EIB / KNX Analogue Input AE/S 4.2 Intelligent Installation Systems This manual describes the functionality of Analogue Input AE/S 4.2. Subject to changes and errors excepted. Exclusion
J TB/TW Temperature limiter, temperature monitor
JUMO GmbH & Co. KG Delivery address:mackenrodtstraße 14, 36039 Fulda, Germany Postal address: 36035 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-607 e-mail: [email protected] Internet: www.jumo.net
Differential Pressure Sensors for air and non-corrosive gases, with calibration certificate
1 919 1919P01 1919P03 QBM65/C, QBM75-1U/C Differential Pressure Sensors for air and non-corrosive gases, with calibration certificate QBM751-1/C QBM65/C QBM75/C Highly accurate measurements with calibration
0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N
55 Series - General purpose relays 7-10 A Features 55.12 55.13 55.14 Printed circuit mount, general purpose 2, 3 & 4 Pole relays 55.12-2 Pole 10 A 55.13-3 Pole 10 A 55.14-4 Pole 7 A AC coils & DC coils
Preset Counter signo 721
Most simple handling Impressive, clearly readable display in 48x48 mm Input frequency up to 60 khz Easy installation due to pluggable terminals TECHNICAL DATA GENERAL Display Height of digits Supply voltage
For a complete explanation of all the functions and configurations available please refer to the SC6006: Manual of operation.
PRELIMINARY TECHNICAL INFORMATION Three-phase Digital SCR Firing Board HIGHLIGHTS - Up to 480 V AC input supply voltage - Up to 700 V AC sync input - DSP controlled - Digital or analog input signaling
T 3000. Substation Maintenance and Commissioning Test Equipment
T 3000 Substation Maintenance and Commissioning Test Equipment Multi function system for testing substation equipment such as: current, voltage and power transformers, all type of protection relays, energy
38 SERIES. Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A. EMR Electromechanical Relays. Common features. SSR Solid State Relays. 6.
38 Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit 6.2 mm wide EMR - DC, AC or AC/DC
15 Series - Electronic step relay and dimmer. Features 15.91 15.51 15.81 SERIE
Series - Electronic step relay and dimmer SERIE Features.91.51.81 Electronic step relay and dimmer for control of lighting levels Suitable for incandescent and halogen lighting loads (with or without transformer
DRTS 33. The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters
The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters Testing all relay technologies: electromechanical, solid state, numerical and IEC61850 Manual
Application/Connection Examples
This Quick Start Guide is designed to familiarize the user with the connection and configuration of the DTS-305 DIN rail mounted single / 3 phase power & energy meter with RS-485 or TCP communications.
Circuit Breaker LTB D with Motor Drive. Motor Drive. ABB PP/H/HV - Page 1. Ed 2006-04
Circuit Breaker LTB D with Motor Drive Motor Drive ABB PP/H/HV - Page 1 Ed 2006-04 Technology Traditional technology Traditional spring operating mechanism: Closing mechanism ABB PP/H/HV - Page 2 Tripping
Vibration analysis and monitoring Compact. Powerful. Modern technology.
Vibration analysis and monitoring Compact. Powerful. Modern technology. Maximum performance Vibration measurement with state of the art processor technology Expert Vibro is Delphin Technology's new device
Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller
Overview/Modes of Operation Bulletin 150 Smart Motor Controller The SMC-3 is a compact, simple to use, solid-state motor controller designed to operate 3-phase motors. It features a built-in overload relay
PCS0100en 02.2008. Persy Control Services B.V. Netherlands
P-Bus Gateway PBGW2.128 Universal gateway between the P-bus protocol and open standard protocols. The variety of available electrical interfaces on the gateway offers a wide range of possibilities for
Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages
Data sheet Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages The CM-ESS.2 is an electronic voltage monitoring relay that provides reliable monitoring of voltages as well as detection of
48.12. 2 pole, 8 A Safety relay. Screw terminal. 35 mm rail (EN 60715) mounting. 2 CO (DPDT) 8/15 250/400 2,000 500 0.37 8/0.65/0.
48 Series - Relay interface modules 8 A Features 48.12 2 Pole Safety relay interface modules, 15.8 mm wide 48.12-2 Pole 8 A (screw terminal) DC sensitive coils Relay with forcibly guided contacts according
Pressure monitoring equipment for oil-sf 6. bushings, type GOEK
Pressure monitoring equipment for oil-sf 6 bushings, type GOEK Installation and maintenance guide 5693 827-6 en, Rev. 3, 2002-01-30 This document must not be copied without our written permission, and
Cable Solutions for Servo and Variable Frequency Drives (VFD)
Cable Solutions for Servo and Variable Frequency Drives (VFD) Electric drive systems with continuous torque and speed control are widespread today. They allow an optimal adjustment of the drive with respect
FLOW CALCULATOR INSTRUCTION MANUAL MESURES BAMOPHOX 759 26-06-2007 759 M1 02 E MES FLOW CALCULATOR 759-02/1
BAMOPHOX 759 E - M FLOW CALCULATOR INSTRUCTION MANUAL MESURES 22, Rue de la Voie des Bans - Z.I. de la Gare - 95100 ARGENTEUIL Tél : (33) 01 30 25 83 20 - Web : www.bamo.fr Fax : (33) 01 34 10 16 05 -
Fiessler Programmable Safety Center. Flexible Hard- and Software concept. Available with a safe bus system or/and two counter inputs
E L E K T R O N I K Appliance Description Programmable safety center FPSC Fiessler Programmable Safety Center Flexible Hard- and Software concept Available with a safe bus system or/and two counter inputs
Programmable set for Ethernet Modbus/TCP in IP67 TI-BL67-PG-EN-2
Type code Ident no. 1545065 Number of channels 2 Dimensions (W x L x H) 108 x 145 x 77.5 mm CoDeSys-programmable acc. to IEC 61131-3 Cable max. 50 m between interface and read/write head 10/100 Mbps Male
RRV934. Multi-controller. Synco living
s 2 709 Synco living Multi-controller RRV934 RF-based multi-controller For precontrol of up to 2 room groups For control of ventilation plant with up to 3 stages RF communication based on KNX standard
Power Meter Series 700
PowerLogic power-monitoring units Power Meter Series 700 Technical data sheet 2007 Functions and characteristics E90463 The PowerLogic Power Meter Series 700 offers all the measurement capabilities required
Type: DILM50(230V50HZ,240V60HZ) Article No.: 277830
Type: DILM50(230V50HZ,240V60HZ) Article No.: 277830 Ordering information Rated operational current AC 3 400 V I e A 50 Max. rating for three phase motors, 50 60 Hz AC 3 230 V Max. rating for three phase
ABB i-bus KNX Switch Actuator, x-fold, 16/20 A, MDRC SA/S x.16.6.1, 2CDG 110 1xx R0011
, 2CDG 110 1xx R0011 SA/S 8.16.6.1 2CDC 071 006 S0010 The 16/20 A Switch actuators are modular installation devices in Pro M Design for installation in the distribution board. The devices are especially
Digital input modules
8 172 TX-I/O Digital input modules TXM1.8D TXM1.16D Two fully compatible versions: TXM1.8D: 8 inputs, each with a three-color LED (green, yellow or red) TXM1.16D: As TXM1.8X, but 16 inputs, each with a
Electronic Pressure Switch EDS 300
Electronic Pressure Switch EDS 300 User manual Page 2 of 16 Content 1. Functions of the EDS 300...3 2. Mounting...3 3. Operating keys on the membrane keypad...4 4. Digital display...4 5. Output function...5
Vibration Monitoring System Adash 3600
" User's guide Application: Vibration Monitoring System Adash 3600! Vibration diagnostics, monitoring and protective on-line system! On-line vibration monitoring system of engines, fans, pumps, gearboxes,
Bulletin 150 SMC Flex Smart Motor Controller Specifications
Specifications Specifications Standard Features Optional Features Installation Setup Communications Power Wiring Control Wiring Keypad Software Starting and Stopping Modes Protection and Diagnostics Metering
SENSORS. Fiber Optic Sensors - S70. Advanced fiber optic amplifiers for high speed and low contrast applications
Fiber Optic Sensors - S7 Advanced fiber optic amplifiers for high speed and low contrast applications DIN rail mountable models with dual digital displays speed models: 2 μs...5 ms Super high speed models:
Power network telecommunication
www.siemens.com Power network telecommunication Teleprotection Answers for infrastructure and cities. Binary I/O The best protection against high-voltage grid failures When it comes to managing power networks,