Design, Construction, Installation and Use of Boilers and Pressure Vessels
|
|
|
- Jennifer Young
- 10 years ago
- Views:
Transcription
1 DESIGN, CONSTRUCTION, INSTALLATION AND 1 Design, Construction, Installation and Use of Boilers and Pressure Vessels Repealed by Chapter B-5.1 Reg 1 (effective January 1, 2007) Formerly Saskatchewan Regulation 262/67 (effective August 15, 1957) as amended by Saskatchewan Regulations 96/70. NOTE: This consolidation is not official. Amendments have been incorporated for convenience of reference and the original statutes and regulations should be consulted for all purposes of interpretation and application of the law. In order to preserve the integrity of the original statutes and regulations, errors that may have appeared are reproduced in this consolidation.
2 2 DESIGN, CONSTRUCTION, INSTALLATION AND Table of Contents Section 1 Section 2 Section 3 Section 4 Section 5 Section 6 Section 7 Section 8 Section 9 Section 10 Section 11 Section 12 Section 13 Section 14 Definitions Application and General Requirements Registration of Designs Registration of Fittings Registration Numbers for Saskatchewan Identification and Stamping Blow-Off Tanks and Piping Boiler Suspension and Support Supplementary Construction and Installation Requirements Pressure Gauges Design, Construction, and Installation of Hot Water Tanks and Hydropneumatic Tanks of More Than 24 Inch Diameter Rules for Welding Procedures, Welders, and Welding Operators Hot Water Heating Boilers Repealed
3 DESIGN, CONSTRUCTION, INSTALLATION AND 3 SASKATCHEWAN REGULATION 262/67 Respecting the Design, Construction, Installation and Use of Boilers and Pressure Vessels Made pursuant to sections 19 and 31 of The Boiler and Pressure Vessel Act SECTION 1 DEFINITIONS 101 In these regulations the expression: (a) Act means The Boiler and Pressure Vessel Act; (b) approved unless otherwise stated, means approved by the Chief Inspector; (c) authorized means with authority recognized by and having the approval of the Chief Inspector; (d) A.S.A. Code means the A.S.A. Pressure Piping Code B31.1 of the American Standards Association; (e) A.S.M.E. Code means the A.S.M.E. Boiler and Pressure Vessel Construction Code of the American Society of Mechanical Engineers; (f) A.S.T.M. means the American Society for Testing Materials; (g) air receiver means a pressure vessel as defined in the Act; (h) boiler means a boiler as defined in the Act and includes a heating boiler, a high pressure boiler and a miniature boiler as defined in these regulations; (i) C.R.N. means the Canadian Registration Number as recorded by Saskatchewan and as allotted by the Chief Inspector to an approved and registered design; (j) C.S.A. means the Canadian Standards Association; (k) Chief Inspector means the chief inspector of boilers and pressure vessels of the Province of Saskatchewan appointed under section 5 of the Act; (l) department means the Boiler and Pressure Vessel Inspection Branch of the Department of Labour of Saskatchewan; (m) design means and includes the blueprints and specifications, specimens or models, submitted to the Chief Inspector for approval and registration; (n) expansion tank means a vessel for installation in a closed hot-water heating system to provide an air cushion for the expansion of the water when heated by a hot water heating boiler;
4 4 DESIGN, CONSTRUCTION, INSTALLATION AND (o) fittings means safety valves, safety-relief valves, thermostatic relief valves, rupture discs, stop valves, check valves, automatic stop-and-check valves, blow-off valves, reducing valves, pressure or temperature regulating valves, water gauges, pressure gauges, gauge cocks, fusible plugs, regulating and controlling devices, boiler feeding devices, low-water cut-off devices and any other fitting or accessory including pipe fittings, designed for use with any boiler, pressure vessel or pressure piping provided for in these regulations; (p) heat exchanger means a condenser, evaporator, heater or cooler or any similar apparatus not specifically defined herein; (q) heating boiler means a low pressure heating boiler designed for a steam pressure of not more than 15 pounds to the square inch or a water pressure from 30 to not more than 160 pounds to the square inch in accordance with the A.S.M.E. Code for low pressure heating boilers and these regulations but does not include a hot water boiler operating in an open system and such a boiler in a private residence occupied by not more than three families; (r) heating surface means the total plate and tube or other material surface of a boiler in square feet which is exposed during operation to the products of combustion and is below the manufacturers high water mark or where no such mark is specified, below the top of the gauge glass, calculated by the manufacturer and approved by the department for the purpose of determining the horse power rating for registration purposes, the minimum sizing of safety valves, registration and inspection fees and for operating engineers certificates; (s) high pressure boiler means a boiler designed for a steam pressure exceeding 15 pounds to the square inch in accordance with the A.S.M.E. Code for Power boilers and these regulations (see also miniature boilers ); (t) hot water tank means a pressure vessel used to contain hot water at a pressure exceeding 15 pounds to the square inch and having a diameter of more than 24 inches but for the purpose of field inspection does not include a hot water tank in a private residence designed to accomodate not more than 3 families; (u) hydropneumatic tank means a pressure vessel used to contain liquid and air at a pressure exceeding 15 pounds to the square inch having a diameter of more than 24 inches, but for the purpose of field inspection does not include a hydropneumatic tank used for agricultural purposes or in a private residence designed to accomodate not more than 3 families; (v) inspector means an inspector appointed under section 5 of the Act or an inspector having the approval of and authorized by the Chief Inspector; (w) manufacturer means the company or person manufacturing a boiler, pressure vessel or fitting and who shall be responsible for the construction of same complying with the design approved and registered for use in Saskatchewan and for the stamping of the Saskatchewan registration number thereon;
5 DESIGN, CONSTRUCTION, INSTALLATION AND 5 (x) manufacturers affidavit means a certification made upon a special form obtained from the department, to the effect that a boiler or pressure vessel complies in every respect with the design submitted to and approved and registered by Saskatchewan and without which certification no boiler or pressure vessel shall enter the province; (y) manufacturers specification means the specifications respecting a boiler or pressure vessel made upon a special form obtained from the department and submitted to the Chief Inspector in triplicate along with the design drawings for approval and registration; (z) miniature boiler means a boiler having a shell with an inside diameter not greater than 16 inches, an over-all length from outside to outside of heads not greater than 42 inches, a heating surface not greater than 20 square feet, a design pressure not greater than 100 pounds to the square inch and designed in accordance vrith the A.S.M.E Code for Miniature Boilers and these regulations; (aa) National Board means the National Board of Boiler and Pressure Vessel Inspectors of the U.S.A.; (bb) oil refinery means a plant for separating, evaporating, cracking, desalting, purifying or refining oil or any of the constituents thereof and includes all fired or unfired pressure vessels other than boilers installed therein; (cc) person includes a manufacturer, association, corporation, firm, partnership and syndicate; (dd) pressure means gauge pressure in pounds per square inch (designation p.s.i. ); (ee) pressure piping means any pipe or fitting used or designed to be used in connection with any boiler, pressure vessel, or plant provided for in the Act or in these regulations; (ff) pressure plant means a plant as defined in the Act which is or may be used under pressure in connection with air, hot water, steam, oil, compressed gas or for refrigeration purposes; (gg) pressure vessel means a vessel as defined in the Act; (hh) pressure welding means any welding upon any boiler, pressure vessel or pressure piping which is subject to the requirements of these regulations, to Saskatchewan Pressure Welding Regulations or the Boiler and Pressure Vessel Act; (ii) registered design means registered by the Boiler and Pressure Vessel Inspection Branch of Saskatchewan for legal use in the province and allotted a registration number (C.R.N.) ending with decimal 3 (.3) by the Chief Inspector; (jj) seal means to seal with a department seal and prohibit the use of any boiler or pressure vessel shipped into the province prior to having its design approved and registered by the Chief Inspector or not designed and constructed in accordance with the requirements of the Act and these regulations;
6 6 DESIGN, CONSTRUCTION, INSTALLATION AND (kk) second hand vessel means a used boiler or pressure vessel prohibited by Sections 25 and 26 of the Act and these regulations from being shipped into the province or being reinstalled inside the province unless prior permission in writing has been obtained from the Chief Inspector, and where a violation of such requirements has occurred is subject to such fees and penalties as are specified in section 2 of these regulations; (ll) separator means a pressure vessel designed especially for well-head or oil-field use for the purpose of separating any gas or fluid from crude oil and for the purpose of field inspection includes every type separator irrespective of design pressure; (mm) steam processor means a pressure vessel used for the purpose of raising the temperature of any material placed therein by means of steam; (nn) symbol means letters or figures or a combination of same issued to an authorized pressure welder for stamping his work in accordance with Saskatchewan Pressure Welding Regulations; (oo) treater means a pressure vessel designed especially for oil-field or gas-field or well-head use for the purpose of extracting water or otherwise treating crude oil or gas and for the purpose of field inspection includes every type treater irrespective of design pressure; (pp) unfired pressure vessel means an air receiver, refrigerant receiver, heat exchanger, steam processor, digester, oil still, treater, unfired treater, separator petrochemical vessel, well-head vessel, oil-field or gas-field vessel, hot water tank, hot-water heat exchanger, hydropneumatic tank, blow-off tank, expansion tank, L.P. gas tank, anhydrous ammonia tank, reactor containment vessel, reactor vessel or any similar pressure vessel which is or may be used for containing, storing, distributing, transferring, distilling, treating, separating, evaporating, processing, or otherwise handling air, hot water, steam, oil, compressed gas or for nuclear reaction or refrigeration purposes; (qq) unfired steam boiler means an electric boiler or any similar pressure vessel in which steam is generated by means other than the direct combustion of fuel and for which requirements are provided in both the A.S.M.E. Unfired Pressure Vessels Code and the A.S.M.E. Power Boilers Code; and all other expressions shall have the same meaning as in the Act; (rr) a minimum of 1/16" corrosion allowance is required on all vessels using petroleum products. 19 Jly 57 s1; 8 May 70 SR 96/70.
7 DESIGN, CONSTRUCTION, INSTALLATION AND 7 SECTION 2 APPLICATION AND GENERAL REQUIREMENTS 201 These regulations apply to the design, construction, fabrication, shop inspection, installation, alteration, repair and operation of every high pressure boiler, low pressure boiler, pressure vessel, pressure piping or fitting which is subject to inspection, approval, or registration under the Boiler and Pressure Vessel Act or is defined herein and the design, construction, fabrication, shop inspection, installation and repair shall be strictly in accordance with the requirements of these regulations and any codes or standards adopted hereby except where same are at variance with these regulations or the Act. 202 These regulations do not apply to boilers or pressure vessels operating or used under the supervision of the Board of Transport Commissioners for Canada and constructed, marked and maintained in accordance with their specifications and requirements. 203(a) Except as otherwise provided in these regulations, the standards governing the design, construction, fabrication, shop inspection, installation and testing of boilers and pressure vessels as minimum requirements shall be those set forth in the current editions of the following codes of the American Society of Mechanical Engineers, namely Power Boilers, Material Specifications, Low Pressure Heating Boilers, Miniature Boilers, Unfired Pressure Vessels, Qualifications for Welding, and Boilers of Locomotives, and for piping and fittings as set forth in the A.S.A. Code for Pressure Piping. (b) Except where the same are at variance with the requirements of these regulations, C.S.A. Code B51 shall, where required herein, be complied with as constituting part of these regulations. 204 Where any requirements of these regulations is at variance with the requirements of the codes and standards mentioned in Rule 203, the requirements of these regulations shall govern and the Chief Inspector may approve or reject any revision or amendment hereafter made in any codes or standards referred to in these regulations. 205 The Chief Inspector may formulate rules in special cases, where appropriate rules have not been provided by these regulations, in accordance with Section 4 and Section 8 of the Act. 206 Any inspector appointed under Section 5 of the Act or an authorized inspector having the approval of the Chief Inspector may increase the factor of safety on any boiler or pressure vessel when he considers the construction, material or workmanship is such that a reduction in working pressure of the boiler or pressure vessel is necessary. 207 All fittings attached to any boiler or pressure vessel or used in any steam plant, refrigeration plant, or oil refinery, shall be for new installations such as are sanctioned by these Regulations, and for existing installations all fittings found to be unsafe or to be replaced, shall be replaced with fittings that are sanctioned by these regulations.
8 8 DESIGN, CONSTRUCTION, INSTALLATION AND 208(a) The age limit of every high pressure lap-seam riveted boiler shall be 20 years at its original design pressure after which the inspector shall reduce the working pressure by increasing the factor of safety by not less than 0.1 each year and if the boiler is over 36 inches in diameter and installed in a new location, the safety valves shall be set at not more than 15 pounds to the square inch; (b) No traction boiler more than 35 years old shall be allowed a working pressure of more than 100 pounds to the square inch. 209 For the purposes of design registration fees, inspection fees and other specified requirements of these regulations one boiler horse power shall be considered as being the equivalent of 10 square feet of heating surface as defined in Section 1 except that for an electric boiler, the maximum killowatt capacity of the heating element divided by ten shall be the horse power rating. 210(a) Liquefied petroleum gas storage tanks or containers other than those designed for use in an oil refinery and subject to special rulings, shall be designed, constructed and used in accordance with Saskatchewan Regulations Respecting L.P. Gas Pressure Vessels; (b) Anhydrous Ammonia storage tanks or containers for use with NH 3 as a liquid fertilizer shall be designed, constructed and used in accordance with Saskatchewan Regulations Respecting Anhydrous Ammonia Pressure Vessels; (c) Refrigeration vessels and refrigeration plants having a capacity of 5 tons or more, including all piping, fittings and appurtenances attached thereto, shall be designed, constructed and used in accordance with the requirements of C.S.A. Code B52 and these regulations; (d) Portable cylinders for L.P. gas shall be constructed in accordance with specifications of the Board of Transport Commissioners for Canada or the Interstate Commerce Commission of the U.S.A. 211 All piping used in connection with boilers, pressure vessels and pressure plants shall meet the requirements of: (a) the A.S.M.E. Codes where applicable; (b) the A.S.A. Code for Pressure Piping where the A.S.M.E. Codes are not applicable; (c) the requirements of Saskatchewan Pressure Welding Regulations where such piping is welded. 212 All low pressure steel heating boilers shall be constructed of flange or fire-box quality plate as a minimum requirement. 203 All boilers and pressure vessels defined in these regulations shall be registered. 214 Heat exchangers of the fin-tube type up to 100 square feet of tube heating surface shall be exempt from shop inspection, but a manufacturer s affidavit for same shall be forwarded the department. 215 Cast iron boilers shall be constructed in accordance with the A.S.M.E. Low Pressure Heating Boilers Code and these regulations except where these regulations are obviously not applicable.
9 DESIGN, CONSTRUCTION, INSTALLATION AND All welding in connection with boilers, pressure vessels and pressure piping for use in the province shall be strictly in accordance with Section 12 of these regulations and Saskatchewan Pressure Welding Regulations. 221 Non ferrous vessels including those of copper base material shall be designed with a factor of safety as specified in the A.S.M.E. Code provided that the yield point of the material shall not be exceeded to the extent that the material takes on a permanent elongation when the vessel is hydrostatically tested to twice the design pressure. 222 Where a non registered or second hand boiler or pressure vessel is installed or shipped into the province for installation in violation of any of the requirements of these regulations or the Act, the following requirements shall be applicable thereto: (a) a special inspection or inspections by an inspector and payment of the special inspection fees; (b) sealing by an inspector until the design has been approved; (c) payment of all expenses incurred by the department including those for any inspection trips made by an inspector; (d) a per diem fee for the inspector s time; (e) the payment of a fee of $ as specified in Section 14, Rule 1401.(3) for a special department survey; (f) registration if approved by the special survey and payment of the registration fee; (g) payment of the stamping fee as specified in Section 14, Rule 1401.(6); (h) any other charges in connection with the violation deemed by the Chief Inspector to be fair and just; irrespective of whether or not the vessel is found in a useable condition, is condemned, is registered or its use prohibited. 19 Jly 57 s2; 8 May 70 SR 96/70. SECTION 3 REGISTRATION OF DESIGNS (Drawings and Specifications) 301 Blueprints and specifications of designs in duplicate shall be submitted to the department for registration for all boilers and pressure vessels defined in these regulations or provided for in the Act. 302 Drawings and specifications of any boiler or pressure vessel shall give the maximum design pressure and temperature, the working pressure (for proportioning safety valves), the material thickness and specifications, method of fabrication and welding details and the purpose for which the boiler or pressure vessel is to be used.
10 10 DESIGN, CONSTRUCTION, INSTALLATION AND 303 Before commencing construction of any boiler or pressure vessel to be built under these regulations, the manufacturer's drawings and specifications shall have been submitted to, and approved by, the Chief Inspector. 304 Drawings or blueprints, submitted with applications for approval and registration, shall be provided with a blank or white area 4 inches by 4 inches on which an official approval stamp may be placed. 305 Specification forms and Affidavit of Manufacturer forms printed by the Province of Saskatchewan will be supplied by the department on request. 306 Fees for surveying designs of boilers and pressure vessels for approval and registration are as specified in the schedule of fees and shall be paid in Canadian funds upon the request of the department. 307 Designs, when finally approved, will be given a registration number (C.R.N.) for Saskatchewan and vessels may be manufactured to such registered designs in any quantity provided they meet the requirements of the registered design in every detail. Reference shall be made to the registration number, when submitting Affidavit of Manufacturer to the department respecting each vessel for use in the province. 308 Boilers and pressure vessels may be built in accordance with a registered design until changes are made in these regulations or in the codes adopted hereby which affect the design in which case the design shall become obsolete and no further construction shall be made to such a design after a period of 12 months except with the permission of the Chief Inspector. 309 Notwithstanding the fact that a design has been approved by the department, if it is afterwards found to be defective in any way, the manufacturer will be notified accordingly, and shall thereupon revise the design to meet the approval of the Chief Inspector. 310 Changes made by a manufacturer in a design already approved and registered will necessitate the submitting of new drawings and specifications to the department for approval. In such cases the manufacturer may at the discretion of the Chief Inspector be required to pay registration fees in the same manner as if they were original designs. 311 When a design is submitted and not approved, a report on the design will be sent by the department to the manufacturer by whom it was submitted, who shall forward new blueprints and specifications conforming with the requirements of these regulations. 312 The approval and registration of design drawings and specifications of a boiler or pressure vessel will not in any way relieve the manufacturer of full responsibility in connection with same. 313 Boilers or pressure vessels, the design of which differs from the requirements of these regulations, or which have been previously installed or used, may not be shipped into Saskatchewan for installation without first obtaining permission in writing from the Chief Inspector, who shall at the time of the request be supplied with complete design drawings, manufacture s specifications, affidavit of manufacturer and the last provincial inspection report, and where this requirement is violated all the provisions of Section 2, Rule 222 as specified for a non-registered or second hand boiler or pressure vessel shall apply thereto.
11 DESIGN, CONSTRUCTION, INSTALLATION AND When a boiler or pressure vessel is delivered to a purchaser in the province, an Affidavit of Manufacturer on a special Saskatchewan Affidavit form, bearing the signature of the authorized shop inspector where shop inspection is required by the Code or these regulations, shall be forwarded to the department. In the case of boilers or pressure vessels manufactured for stock, the name and address of the ultimate owner and location of the installation, when not available to the manufacturer at the time the boiler or pressure vessel leaves the plant, may be filled in by the sales agent. 315 All low pressure boilers of 50 square feet of heating surface and less are exempt from shop inspection unless otherwise required by the A.S.M.E. Code. All high pressure boilers, and low pressure boilers of more than 50 square feet of heating surface, shall be built under shop inspection and shop inspection of pressure vessels shall be as required in Section 8 of the A.S.M.E. Code. 316 All boilers and pressure vessels subject to shop inspection and manufactured in the U.S.A. for use in Saskatchewan shall be shop inspected by an inspector holding a current National Board Commission and shall be stamped National Board in addition to being stamped with the A.S.M.E. symbol. The authorized inspector holding the National Board Commission shall be a state inspector or an inspector regularly employed by a boiler insurance company. 19 Jly 57 s3; 8 May 70 SR 96/70. SECTION 4 REGISTRATION OF FITTINGS (Fittings include Accessories) 401(a) Blueprints and specifications, in duplicate, of all fittings to be used on boilers, pressure vessels and pressure piping connected therewith shall be submitted to the Chief Inspector for registration, before any fitting is used. The blueprints and specifications shall indicate all sizes and thicknesses of metal, compositions of all materials, tensile strength, compressive strength of all parts which are subject to compression, also the pressure to which the design was tested by the manufacturer. The pressure at which a sample fitting ruptured if tested to destruction shall also be given in addition to the maximum operating pressure and temperature rating of the fitting; (b) Registration of fittings shall in no way relieve the manufacturer or his agent of full responsibility in connection with the use of same; (c) Subject to the approval of the Chief Inspector, it shall not be necessary to register separately the design of every globe, angle, gate and check valve, or ells, tees, unions and flanges and similar appurtances provided they comply with all the requirements of the A.S.M.E. and A.S.A. Codes and Standards and these regulations. Each manufacturer may have such fittings registered collectively by forwarding a certificate in duplicate respecting same on a Saskatchewan form to the Chief Inspector; (d) Safety valves shall be registered separately in full compliance with subsection (a).
12 12 DESIGN, CONSTRUCTION, INSTALLATION AND 402 Should an inspector find that a manufacturer is supplying fittings that do not fully comply with the requirements of these regulations, the registration may be cancelled immediately. 403 Fees for surveying designs of fittings for registration are as specified in the schedule of fees and shall be paid in Canadian funds upon the request of the department. 404 When the Chief Inspector considers it necessary, sample fittings shall be forwarded to the department at the expense of the party wishing to register same and may be retained by the department or returned at the registering party s expense. 405 The Chief Inspector may select any registered fitting in an agents stock for test purposes and, should a number of fittings made to a registered design prove to be faulty, the Chief Inspector may cancel the registration. 19 Jly 57 s4; 8 May 70 SR 96/70. SECTION 5 REGISTRATION NUMBERS FOR SASKATCHEWAN 501 The registration number issued by the department to an approved and registered design shall be as specified in Section 5 of C.S.A. Code B51 for Saskatchewan and shall be allotted as follows: (a) for a boiler or pressure vessel design not previously registered in any other province the department will allot the next number on its registration files followed by the figure 3 after a decimal point, thus , the.3 designating Saskatchewan; (b) for a boiler or pressure vessel design previously registered in another province the department will use the number allotted in the previous registration followed by the figure 3 after the decial point thus, , the.3 designating Saskatchewan; (c) for any apparatus to be registered as a fitting under Section 4 the same procedure shall be followed in allotting a registration number as set forth in (a) and (b) provided also that the number shall be preceded by zero, thus ; (d) where a boiler, pressure vessel or fitting has been previously approved and registered in another province but changes have since been made in the design by the manufacturer or where changes are necessary in the design to obtain approval and registration in Saskatchewan, any registration number previously allotted the design by another province shall be ignored and a Saskatchewan registration number shall be allotted thereto. 502 When a design is submitted for approval and registration it shall be the responsibility of the manufacturer to inform the department respecting any registration numbers previously allotted the design by any other province also the previous registration date and where this information is not given, full registration fees may be charged for any changes required at a later date in the registration number allotted.
13 DESIGN, CONSTRUCTION, INSTALLATION AND The provinces are indicated by the following decimal figures for registration purposes: British Columbia....1 Quebec....6 Alberta....2 New Brunswick....7 Saskatchewan....3 Nova Scotia....8 Manitoba....4 Prince Edward Is Ontario....5 Newfoundland Jly 57 s5. SECTION 6 IDENTIFICATION AND STAMPING 601 Every boiler or pressure vessel built under these regulations shall conform to them in every detail and shall be distinctly stamped as follows denoting that the boiler or pressure vessel has been constructed in accordance with an approved and registered design for the Province of Saskatchewan: (a) For Power and Heating Boilers. Saskatchewan Registration number (C.R.N.). National Board number (if manufactured in U.S.A.). Manufacturer and manufacturer s serial number. A.S.M.E. or A.S.T.M. material specification number and tensile strength. Maximum working pressure with S for steam or W for water or both. Heating surface in square feet and year built. Initials or symbol of authorized shop inspector. Sample stamping for boiler: C.R.N Dom-Bridge... Sr. No. B-6431 Stelco SA 285C... T.S Max. W.P. 15 lb. S lb. W H.S Ft J.W.C. (b) For Unfired Pressure Vessels (except L.P. Gas and Anhydrous Ammonia vessels). Saskatchewan Registration number (C.R.N.). National Board number (if manufactured in U.S.A.). Manufacturer and manufacturer s serial number. Plate specification number and tensile strength for shell. Plate specification number and tensile strength for heads. Thickness of shell and heads.
14 14 DESIGN, CONSTRUCTION, INSTALLATION AND Maximum working pressure and temperature. A.S.M.E. Code paragraph number and year built. Initials or symbol of authorized shop inspector. Sample stamping for unfired pressure vessel: (c) (d) C.R.N Fab-weld... Sr. No U.S. Steel SA T.S Max. W.P. 200 lb.... Temp. 400 T. Shell T.Heads.4375 UW N.H. For Propane Storage Containers. The stamping shall be as designated in Saskatchewan Regulations for L.P. Gas Pressure Vessels. For Anhydrous Ammonia Containers. The stamping shall be as designated in Saskatchewan Regulations for Anhydrous Ammonia Pressure Vessels. 602(a) The figures and letters of the stamping shall be at least 3/8 inch in size and shall be located in accordance with the A.S.M.E. Code requirements unless otherwise approved by the Chief Inspector. When placed upon a permanently attached brass plate the figures and letters may be not less than 1/8 inch in size; (b) The letters and figures shall be legible and stamped fully into the plate of the boiler or pressure vessel (not of the smoke box) provided that for cast iron boilers the stamping shall be cast into the boiler or stamped on a permanently attached plate. For pressure vessels made of light gauge material, the stamping may be upon a permanently attached plate. (c) The stamping area shall be painted and outlined in a contrasting colour and worded This area not to be covered provided that this requirement may be omitted in the case of fire tube boilers where the stamping is on the front head exposed to the products of combustion and accessible through the smoke box door. (d) Exemptions: Boilers and pressure vessels manufactured outside Canada for installation in Saskatchewan may be stamped by the manufacturer with the stamping required by the A.S.M.E. Code in lieu of the stamping required in this Section. The Saskatchewan Registration number (C.R.N.) shall be stamped on the vessel in addition to the stamping required by the A.S.M.E. Code. This exemption is limited to unfired pressure vessels up to 5 cubic feet capacity, to low pressure heating boilers up to 50 square feet of heating surface and to miniature boilers (high pressure type) up to 20 square feet of heating surface.
15 DESIGN, CONSTRUCTION, INSTALLATION AND Any identification or stamping as required herein shall be kept free of insulation or other covering so that the stamping is plainly visible at all times to the field inspector and where this is impracticable the identification shall also be stamped upon a permanently attached plate, in addition to the stamping on the vessel, which plate shall be kept free of covering. 604 Hot water storage tanks, hydropneumatic tanks and expansion tanks as defined in these regulations shall be identified or stamped as required in Rule 601. (b) of this Section except that the plate manufacture, the working temperature, and thickness of heads and shell may be omitted. 19 Jly 57 s6. SECTION 7 BLOW-OFF TANKS AND PIPING 701 When the blow-down from any boiler having a working pressure exceeding 15 pounds per square inch is discharged into a closed sewer system, or where an inspector otherwise believes it necessary, an approved blow-off tank shall be placed between the boiler and the sewer, or otherwise used, for the purpose of reducing the pressure and temperature of the water discharged from the boiler or entering the sewer. 702 Where blow-off tanks are provided, they shall be of approved and registered designs, and have a minimum capacity or volume equivalent to the following: Size of Minimum Plate Blow-off Tank Thickness Nominal HP (Inches) (Inches) 5 to x /4 21 to x /4 51 to x /8 101 to x /8 201 to x /8 401 to x /8 801 and over... 48x /8 In a battery of boilers the largest size boiler shall establish the size of the blow-off tank. Note: The lengths referred to are overall lengths. 703 The outlet shall be at least three times the area of the inlet pipe to the blow-down tank and made to extend internally by means of a tee-pipe to within 6 inches of the bottom and top of the tank. A vent pipe of at least equal diameter to the outlet connection shall lead to the atmosphere from the top of the tank, and a drain connection having a minimum size of 1 1/4 inches shall be connected at the bottom. For convenience in cleaning the tank, a man- hole not less than 11 inches by 15 inches shall be provided.
16 16 DESIGN, CONSTRUCTION, INSTALLATION AND 704 All designs submitted and allotted a registration number shall be built with a factor of safety of 5 to carry a pressure not less than 30 per cent of the maximum boiler pressure. Such tank may be constructed of C.S.A. G40 or A.S.T.M. 283C plate or equivalent as a minimum requirement. 705 Blow-down tanks shall be installed so as to permit free access for external and internal inspection. They shall not be bedded in solid concrete. 706 All pipe, pipe connections and fittings between the boiler and tank shall be designed for the maximum boiler pressure, and made as direct as possible. The blow-down tank shall be installed so that wherever possible or practicable the lines from the boiler shall slope towards the tank. Where the elevation of the tank precludes the above condition, a drain shall be provided at the lowest point of the blow-off line. 707 Every boiler having a working pressure exceeding 15 pounds per square inch shall be equipped with two blow-off valves one of which shall be of an approved slow opening type. Where plug-cock type valves are used they shall have bolted covers with proper packing glands and be designed especially for blow-off service. 708 Each boiler in a battery of boilers shall have its blow-off line connected in such a manner that the boiler can be isolated from the other boilers under pressure. It is also recommended that for the purpose of blowing down, boilers when set in batteries shall be numbered both back and front. 19 Jly 57 s7. SECTION 8 BOILER SUSPENSION AND SUPPORT 801 The following rules shall be observed in the setting of horizontal return tubular boilers: (a) No boiler shall be suspended from the crown or allowed to stand on a pedestal at the back end. (b) Every boiler, up to and including 12 feet in length and less than 48 inches in diameter, may be supported upon 4 cast iron or steel brackets resting upon substantial plates set in the brickwork, the back lugs resting upon rollers between the lugs and plate to provide for free expansion and contraction of the boiler. (c) Every boiler over 12 feet long, and 48 inches and over in diameter shall be suspended at the front and back by side lugs set in pairs, or by appproved double-wing, single hangers. The design of the suspension lugs or hangers and their attachment shall meet the requirements of the A.S.M.E. Code. (d) Suspension, when required, shall be from steel beams, which shall be carried by and secured to steel columns having bases bolted to substantial foundations. (e) Suspension beams or supporting columns shall not rest on the side walls of the brick setting. Recommended sizes of beams and columns are shown in Table 1.
17 DESIGN, CONSTRUCTION, INSTALLATION AND 17 (f) The maximum fibre stress for suspension beams shall not exceed 15,000 pounds per square inch. The maximum fibre stress for suspension rods computed at the minimum next section at the bottom of the thread shall not exceed 10,000 pounds per square inch for iron rods or 12,500 pounds per square inch for steel rods. (g) In case of boilers suspended from 4 points, since any slackening of one support throws the whole weight of the boiler on 2 rods, each suspension rod shall be sufficiently strong to carry one-half the total weight of the boiler when filled with water without exceeding the fibre stress specified in (f). If a link arrangement is used, the link is subjected to bending and shearing stresses in addition to the direct pull on the rods and, consequently, in calculating the size of link required, allowance shall be made for these stresses. (h) Supporting columns shall not be enclosed within brickwork or any part of the setting which is subject to the heat from the furnace. Columns shall be placed not less than 1 inch clear of the outer walls of the boiler or battery of boilers, so that the columns and the brickwork behind them can be readily inspected. (i) Stacks and breeching shall, in general, be supported independently of the weight of the boiler. If, however, these components are permitted by the Chief Inspector to be supported on the boiler suspension, the suspension shall be made heavier, if necessary, to take care of the increased vertical loads and horizontal wind loads, if any, without exceeding the permissible unit stresses. The boiler brickwork shall not be considered effective for resisting horizontal loads. 802 The following rules shall be observed in the design of the supporting steelwork for the pressure parts of water tube and other type boilers not covered by Rule 801: (a) The several parts of the structure shall be so proportioned that the maximum stresses will not exceed those permitted by C.S.A. Specification S16, Steel Structures for Buildings. (b) Where the steel work is restrained or partially restrained from contracting or expanding due to temperature changes, the stresses so induced shall be combined with those from other sources in proportioning the material. Cautionary Note: The maximum stresses and length/depth ratios established by C.S.A. Specification S16, while adequate for the strength of beams, may need to be decreased in many cases to keep the deflections to practical limits or to reduce vibration. (c) Wherever practicable, supporting beams and columns shall be kept clear of the setting to provide access for inspection and to provide air circulation and cooling. Where these members form part of the boiler casing the setting shall be so constructed that the temperature of the steel will not exceed 350 degrees F. 19 Jly 57 s8.
18 18 DESIGN, CONSTRUCTION, INSTALLATION AND Table 1 - RECOMMENDED SIZES OF SUSPENSION BEAMS AND COLUMNS FOR HORIZONTAL RETURN TUBULAR BOILERS Diameter of Boiler "A" 48" 54" 60" 66" 72" 78" 84" Length of Boiler "B" 10'-0" 12'-0" 14'-0" 12'-0" 14'-0" 12'-0" 14'-0" 16'-0" 14'-0" 16'-0" 14'-0" 16'-0" 18'-0" 20'-0" 16'-0" 18'-0" 20'-0" 18'-0" 20'-0" Cross Channels for Single Setting 9.8 # 11.5 # 11.5 # 13.4 # 13.4 # 15.3 # 15.3 # 15.3 # 20.7 # 20.7 # 20.7 # 25 # 33.9 # Cross Beams for Double Setting 21.8 # 25.4 # 31.8 # 31.8 # 40.8 # 40.8 # 42.9 # 42.9 # 54.7 # 65 # 65.4 # 65.4 # 79.9 # "H" Columns for Either Single or Double Setting 13.8 # 18.9 # 18.9 # 18.9 # 20 # 20 # 32.6 # Note: Cross channels and cross beams referred to in this table shall be installed in pairs.
19 DESIGN, CONSTRUCTION, INSTALLATION AND 19 SECTION 9 SUPPLEMENTARY CONSTRUCTION AND INSTALLATION REQUIREMENTS 901(a) Stop valves of straightway type and approved design of the outside screw and yoke type with rising spindle shall be fitted in both steam and water connecting pipes between the water column and the boiler. The piping to the boiler shall be as short as possible, and conveniently arranged with crosses, having suitable plugs for clean-out and inspection purposes. A waste-pipe and blow-down valve, with a diameter of at least half the diameter of the connecting pipes from the boiler to the column shall be fitted at the bottom of the column. In the case of low pressure heating boilers the valves in the water column connections between the boiler and the water column may be omitted. Drain valves shall be provided on the base of the water- column and water gauge. (b) Where it is found necessary that the water column connecting pipes exceed fifteen feet, approval for same shall be obtained from the Chief Inspector. (c) Plans and specifications, and amendments to same, for all new installations and major rebuilding of old installations of boilers, pressure vessels and refrigerating plants shall be submitted to the department for approval. 902 Where the top connection is above 7 feet and under 20 feet from the floor or working-platform of the boiler-room, water gauges shall be fitted with rods or chains so that they may be operated from the floor or working-platform, and where the water-gauge is 20 feet or more from the operating-floor level they shall be of the inclined or other approved type. 903(a) Safe and effective means, including adequate lighting, shall be provided to permit the water-level in the gauge glass to be distinctly seen at all times. Where considered necessary by the Inspector, tubular water-gauges shall be encased within a suitable guard to provide against accidents. (b) Where 2 gauge glasses are required on large boilers as specified in the ASME Code, both shall be visable from the floor or working-platform of the boiler room. Mirrors may be used to obtain visibility. 904 Water-gauges shall be provided with approved gauge fittings equipped with shut-off valves, having packing glands designed to prevent the possibility of the packing obstructing the opening in the glass or otherwise interfering with its free action. 905 Water-gauges of the remote indicator type shall be of an approved design. Such water-gauges, where used, shall be in addition to standard equipment. 906(a) Every steam boiler, both high pressure and low pressure which is not under continuous attendance by a certified operator, when automatically fired, shall be equipped with an approved low-water cut-off device, designed to shut off the fuel feed and air supply in the event of low water, installed in such a manner that it cannot be rendered inoperative by the manipulation of any manual control or regulating apparatus. The low-water cut-off device shall be housed in either the water column or a separate chamber which shall be provided with a blow-off pipe and valve not less than ¾ inch pipe size. The arrangement shall be such that when the column or chamber is blown down, the water level in it will be lowered sufficiently to actuate the low-water cut-off.
20 20 DESIGN, CONSTRUCTION, INSTALLATION AND (b) Every automatically fired hot water heating boiler when installed in a forced circulation system and not under continuous attendance by a certified operator, shall be equipped in the manner described in Rule 906(a). (c) In a steam boiler, when a combination device incorporating the low-water fuel cut-off and a feed water supply control switch is used, the boiler shall also be equipped with a separate low-water fuel cut-off device installed as described in Rule 906(a), and with a separate water connection to the boiler. 907 Every fire tube boiler operating at a pressure of over 15 pounds to the square inch shall be provided with an approved fusible plug unless specifically exempted by the Chief Inspector which shall be located as recommended by the ASME Code, except where a change in location is allowed or required by the Chief Inspector. 908(a) Every heating boiler, with the exception of a vertical boiler, shall, at the time of manufacture, be provided with a permanently attached marker, indicating the lowest permissable low water level. The marker shall be located in a prominent position and designed so that it will not be covered over by lagging of normal thickness. The marker shall be located as follows: (1) For boilers where the upper row of tubes is in the first pass and exposed to primary temperature combustion gases, not lower than 2 inches above the top of the upper row of tubes; (2) For boilers where the upper row of tubes is in the second or subsequent pass and hence not exposed to primary temperature combustion gases, not lower than level with the top of the upper row of tubes. (b) The lowest visible part of the waterglass shall in no case be lower than the marker required in Rule 908 (a). 909 Every boiler having a working pressure exceeding 15 pounds to the square inch of 15 horsepower or more shall be equipped with two separate means capable of supplying feed water while carrying its maximum allowed pressure, but this does not necessitate two separate feed water connections to the boiler. In no case shall a boiler be fed water through its safety relief valve. 910 Rules in the Section which are obviously not applicable to hot water boilers may be ignored but where doubt exists a ruling shall be obtained from the Chief Inspector. 911(a) Every heating boiler over 48 inches in diameter shall be equipped with a manhole above the tubes, and every heating boiler 48 inches and under shall be equipped with a 4 inch by 5 inch handhole above the tubes in each head. On a boiler not over 6 feet in length a handhole shall be required in one head only. (b) In a water-leg boiler, inspection openings shall be provided near the bottom in each corner, placed alternately on the four sides of the fire-box each facing toward a different water leg. On boilers having water legs over 36 inches wide or 60 inches long, there shall be six inspection openings in the water legs with two on each alternate corners. Where screw-plugs are used, they shall be of brass and of a minimum size of 2 inches for boilers up to 300 square feet of heating surface. For boilers larger than 300 square feet of heating surface they shall be a minimum size of 2½ inches.
21 DESIGN, CONSTRUCTION, INSTALLATION AND 21 (c) Every heating boiler shall be equipped below the tubes with a manhole or adequately sized handhole. On boilers over 39 inches in diameter such handhole shall be not less than 4 inches by 5 inches. Where a 4 inch by 5 inch handhole, placed on the center line of the boiler, is impracticable, two 2¾ inch by 3½ inch handholes may be used. (d) Wherever there is a combustion chamber head, crown sheet or similar construction on a heating boiler, there shall be provided adequate handholes for inspection and cleaning. (e) Where the requirements of (a), (c) and (d) are applicable to a Marine Type Boiler they shall be complied with, and in addition, this type of boiler shall be provided with: i) One handhole or approved inspection opening not less than 2¾ inches x 3½ inches or equivalent area along the centre line of the boiler at the bottom of the shell, ii) Four adequately sized inspection openings on each side of the shell, one in each quarter except that the top openings may be omitted where a manhole is provided, and alternate handholes may be omitted on a boiler not over six feet in length. (f) All diameters referred to in (a), (b) and (c) are inside diameters. (g) Inspection openings in high-pressure boilers, where not specifically provided for in the ASME Code shall meet all the requirements of Rule 911 as minimum requirements. (h) (i) Every boiler and pressure vessel shall be installed in such a manner so as to provide adequate access to inspection openings. (ii) Except as provided in Rule 911(h)(iv) and (v) a passageway of at least 2 feet in width clear of all obstructions and appurtenances, shall be provided at each side and at the rear of each boiler. Where necessary, this clearance shall be further increased for the removal or opening of a closure, casing or cover. (iii) To provide for inspection of external surfaces, a clearance of at least 12 inches shall be provided between the floor and the bottom drum of water tube boilers and the shell of fire tube boilers which are set horizontally. If the bottom drum or shell is insulated, this clearance shall apply to the lowest portion of the insulation. (iv) Clearance for tube replacement and cleaning of fire tube boilers shall be equal to the length of the longest tube plus 1 foot. Upon approval of the Chief Inspector a door or other removable obstruction may be utilized to provide this clearance. (v) A clearance of not less than 4 feet shall be provided to permit the servicing and removal of boiler fuel burning equipment. (vi) Where it is impractical to provide adequate access for inspection of a boiler and with prior approval of the Chief Inspector, the vessel shall be installed so that it is readily removable.
22 22 DESIGN, CONSTRUCTION, INSTALLATION AND 912(a) All safety valves used on boilers and pressure vessels shall be rated valves, tested and listed in accordance with the requirements of the ASME Code. They shall be properly stamped with the rated capacity and the registration number. Manufacturers shall specify on the blueprints or specifications submitted for registration the number and capacity of the safety valves which shall be used for steam and hot water boilers. (b) Safety valves, blow down valves, check valves, stop valves, water gauges, steam gauges and their respective fittings shall, for steam boilers, be supplied by the manufacturer unless an exemption from this requirement is made by the Chief Inspector. (c) When a change in the relieving pressure of a safety valve is required a new spring shall be installed designed for the new pressure if such is more than 10% over or under the original relieving pressure. 913 Manhole and handhole doors, cover plates, bridges and fittings shall comply fully with ASME Code requirements including the specifications of material used for their construction. 914 Each main or auxiliary steam outlet from a boiler (except at safety valve connections) shall be fitted with a stop valve immediately at the boiler, in addition to any other stop valves which may be required on main or branch lines. Where two or more boilers carrying over 100 pounds to the square inch are connected to a common main, each boiler shall be equipped with an approved automatic stop-and-check valve located closest to the boiler in addition to the boiler stop valve located between the stop-and-check valve and the main steam header. The space between the stop-and-check valve and the boiler stop valve shall be provided with an adequate drain. 915 Every boiler shall be provided with adequate provision for easy inspection of all parts of the heating surface both internally and externally. Where such is not provided, any authorized inspector may require the owner or operator to shut down the boiler immediately and to remove any casings, cover plates, attachments or other obstructions which, in his opinion, hinder a proper inspection. 916 When a hot-water tank is heated indirectly by means of a steam coil or pipe, the pressure of the steam used shall not exceed the safe working pressure of the hot-water tank which shall be fitted with an approved hot water relief valve of not less than 1 inch size set to relieve at or below the safe working pressure of the tank. 917 Where steam from a boiler exceeding 15 pounds to the square inch is used for low pressure heating, the pressure shall be reduced by an approved reducing valve. A by-pass shall be provided to allow the servicing of the reducing valve. A low pressure safety valve or valves, capable of relieving all the pressure that may be built up in the low pressure system over and above that for which the low pressure system is designed if the reducing valve should fail, and a pressure gauge, shall be installed on the low pressure line within 10 feet of the reducing valve. 918 Where the aggregate boiler capacity exceeds 100 horsepower, calculated in accordance with Rule 109, there shall be at least one exit door from the boiler room leading directly to the outside of the building if practicable and except where boiler rooms are provided with sliding doors equipped with fusible links, all boiler room doors shall open outwards and shall not be locked when any boiler is in operation.
23 DESIGN, CONSTRUCTION, INSTALLATION AND Platforms, walkways, ladders and stairways equipped with suitable handrails and toe plates shall be installed to give access to and egress from all important parts of boilers and auxiliary equipment. They shall be of substantial fire-resistant construction. 920 Every air receiver where the safety valve is not installed upon the tank but upon a connecting line with a check valve between the safety valve and the receiver, shall be equipped with a fusible plug, to relieve the pressure in the event the tank becomes overheated by fire. 921 An inspector when making an inspection shall satisfy himself: (a) By thorough examination that all provisions of the Act and these Regulations respecting the boiler or pressure vessel and its design, registration, construction, installation, operation and maintenance have been and are being complied with and that the boiler, pressure vessel or plant may be and is being safely used. (b) That the safety valves are properly set and sealed and that the boiler, pressure vessel or plant is being operated at a working pressure which does not exceed the maximum working pressure allowed. (c) That all engines, turbines, fly-wheels, pulleys and other machinery are operated at safe speeds; that proper safeguards have been installed throughout the entire plant where in the inspector s opinion such are required and that the operation and maintenance of the plant and all the equipment therein meet all the requirements of the Act and these Regulations. 922(a) Manually operated uptake dampers shall not be installed in oil or gas fired low pressure heating boilers. (b) Power boilers, oil, gas, or pulverized-coal fired, shall have a minimum opening in the uptake damper of not less than 5 per cent of the total damper area unless specifically exempted by the Chief Inspector. 923 Unless otherwise approved for registration in Saskatchewan, the following procedure for determining the reinforcement of openings, which is the equivalent of replacing the amount of material cut from a vessel in making the opening as reinforcement, shall be followed: (a) Find actual minimum thickness of a blank head or seamless shell required for the design pressure in accordance with A.S.M.E. requirements and Rule 930. (b) Determine the cross sectional area to be cut from the head or shell. (Use longest measurements of opening if in a head.) (c) Replace this cross sectional area as a reinforcing ring or rings, either at right angles to or parallel to the openings, by replacing one half the area on each side of the opening. (d) The effective width of a ring or flue attached at right angles to an opening shall be limited to 6 times the required thickness of the material as found in (a), and any additional reinforcing required shall be provided by an attached flat plate.
24 24 DESIGN, CONSTRUCTION, INSTALLATION AND (e) Where corrosion allowance is required, this shall be provided for separately from the above. 924 All welding for low pressure steel-plate heating boilers shall be in accordance with Rule 924 and figure 1 of CSA Code B51 minimum requirements. 930 Unless otherwise approved for registration the thickness of all types of concave heads for boilers and pressure vessels shall be no thinner than those based upon A.S.M.E. Code formula. 931 Except for use with miniature boilers, heads without flanges shall not be used on high pressure boilers. 932 Head to shell joints shall be butt welded on any air receiver to operate at more than 100 pounds to the square inch. 933 Firebox type boilers shall have the furnace fully stayed to the shell or other opposite parts with no credit allowed for the o-gee joint for high pressure boilers and a credit allowed of only 1 stay pitch for low pressure heating boilers. 19 Jly 57 s9; 8 May 70 SR 96/70. SECTION 10 PRESSURE GAUGES 1001 All gauges used on boilers and pressure vessels subject to inspection shall be of an approved design which has been registered with the department and shall bear the manufacturer s name and Canadian Registration number Applications made to the department for registration shall in addition to describing the design in detail be accompanied by the manufacturer s certification that the gauge has passed the following tests: (a) Withstood for 6 hours a pressure equal to the maximum pressure marked on the dial without the tube showing a permanent set of more than 0.5 per cent at the end of one hour, after the release of the pressure. (b) When subjected to calibration tests, showed an accuracy within 2 per cent on the lower fifth and upper fifth of the graduated scale, and within one per cent on the other three-fifths of the scale When making application for registration, if the gauge design has been previously submitted for approval to another province, the application shall state the registration number previously allotted the design The dial of the steam gauge shall be graduated to approximately double the pressure at which the safety valve is set but in no case to less than 1½ times this pressure All gauges shall be made of such materials that the service in which it is to be used will not appreciably deteriorate any part of the gauge, decrease its efficiency or affect its accuracy. 19 Jly 57 s10.
25 DESIGN, CONSTRUCTION, INSTALLATION AND 25 SECTION 11 DESIGN, CONSTRUCTION, AND INSTALLATION OF HOT WATER TANKS AND HYDROPNEUMATIC TANKS OF MORE THAN 24 INCH DIAMETER 1101 The design, construction, and installation of hot water tanks shall be as follows: (a) All hot water tanks over 24 inches in diameter shall be of registered design, with separate drawings and specifications submitted for each diameter and pressure. (b) Such tanks may be constructed of CSA G40 or ASTM 283C plate or equivalent as a minimum requirement. (c) The minimum design factor of safety shall be 5 and minimum design pressure shall be subject to the particular location but in no case less than 100 pounds to the square inch. For non-ferrous vessels the factor of safety shall be such that it meets the requirements of Section 2 Rule 221. (d) All tanks shall be provided with inspection and access openings free of external attachments, as follows: (1) For tanks over 24 inches to 36 inches inclusive, at least two 2½ inch by 3½ inch handhole openings or two 2½ inch threaded openings, one near each end on opposite sides of shell; (2) For tanks over 36 inches, one manhole opening. (e) Bumped or dished heads without knuckles shall not be used. (f) Heads, convex to pressure, shall not be used. (g) Welded tanks shall be constructed only by tested and qualified pressure welders. (h) All tanks over 30 inches in diameter shall be built under shop inspection and the hydro-static test pressure shall be one and one-half times the design pressure. Tanks 30 inches and under in diameter may be built without shop inspection in which case the hydro-static test pressure shall be twice the design pressure. (i) Stamping and marking shall comply with that required for unfired pressure vessels as specified in Section 6 of these regulations or as specified on a Saskatchewan Manufacturer s Affidavit form except that the plate manufacturer, the working temperature, and thickness of heads and shell may be omitted. (j) A Manufacturer s Affidavit form shall be submitted for each tank constructed. (k) Each tank when installed shall be equipped with one or more officially rated and approved safety relief valves installed so that these valves cannot be isolated from the tank. The safety valve shall preferably be on a separate opening or may be on the cold water inlet line. Where temperature pressure relief valves are used they shall be installed within 2 inches of the tank in the hot water outlet line.
26 26 DESIGN, CONSTRUCTION, INSTALLATION AND (l) The safety relief valve shall be of adequate capacity with a minimum size of ¾ inch. (m) Where the hot water tank is heated by a jacket heater which is isolated from the storage tank by shut-off valves a separate officially rated approved safety valve shall be installed on the jacket heater All hydropneumatic tanks over 24 inches in diameter for installation in premises frequented by the public or used in a commercial or industrial capacity shall meet all the rules outlined above for hot water tanks. 19 Jly 57 s11. SECTION 12 RULES FOR WELDING PROCEDURES, WELDERS, AND WELDING OPERATORS 1201 All welding and the testing of welding procedures and welding operators in connection with boilers, pressure vessels or pressure piping for use in the province shall be strictly in accordance with Saskatchewan Regulations Respecting the Welding of Boilers, Presure Vessels and Pressure Piping The following rules shall be complied with to ensure the interchangeability of boilers and pressure vessels, also fabricated piping and fittings throughout the Canadian provinces and other jurisdictions using the ASME Boiler and Pressure Vessel Construction Code: (a) Every welding procedure and performance test shall conform to or be the equivalent of those specified in Section 9 Welding Qualifications of the ASME Code, and those of the ASA Code for Pressure Piping; (b) Approval and/or registration of welding procedures and the testing of welders shall be performed by the Provincial Boiler Inspection Branch under the Provincial Boiler and Pressure Vessel Act, provided that for vessels properly approved and registered and shipped into the province from outside Canada, the Chief Inspector of the province may accept tests conducted by an inspector employed by an approved insurance company commissioned for the purpose by the National Board; (c) Welders shall be retested, preferably annually, but in no case shall the interval between retests be longer than eighteen months; (d) Manufacturers, prior to commencing any welded construction, shall submit tested and proven welding procedures to the department for approval and registration which shall show that not less than one coupon was given a tensile test, one coupon a root bend test, one coupon a face bend test and one coupon a nick break or x-ray test for each welding position; (e) Manufacturers when completing Manufacturer s Affidavit forms required by the department, shall give all details asked for in the affidavit including the date of last weld tests and the name of the inspector witnessing the tests, and failure to do this may result in non-acceptance of the vessel.
27 DESIGN, CONSTRUCTION, INSTALLATION AND Where a boiler or pressure vessel has been welded by welders who have not been tested within an 18 months period as required in this section and is shipped into the province for use, the Chief Inspector may require that all or any welded seams be x-rayed, trepanned or the vessel be given a proof pressure test amounting to 3 times the design pressure The testing of welders and of procedures by department inspectors for the welding of pipe-lines not subject to the requirements of the Boiler and Pressure Vessel Act may be arranged with the Chief Inspector who together with the contractor or engineering agency responsible for the pipe-line construction shall specify the standard to be used for such tests which as far as is practicable shall be in accordance with ASA Code B and Appendix 4 of Saskatchewan Pressure Welding Regulations. In such tests the contractor or engineering agency shall supply all test materials. 19 Jly 57 s12; 8 May 70 SR 96/ Expansion or cushion tanks. SECTION 13 HOT WATER HEATING BOILERS The design, construction and installation of expansion tanks for use with hot water heating boilers or systems shall be as follows: (a) All expansion tanks over 24 inches in diameter or to operate at more than 30 pounds to the square inch shall be designed and constructed in accordance with the ASME Unfired Pressure Vessels Code with separate drawings and specifications submitted for registration for each diameter and pressure. (b) Expansion tanks of 24 inches in diameter or less if to operate at not more than 30 pounds to the square inch need not be of registered design and may be constructed with dished heads without flanges having a maximum head radius not greater than the tank diameter. (c) All expansion tanks shall be constructed of not less than No. 10 U.S. gauge material which may be CSA G40 or ASTM 283C or the equivalent as a minimum requirement. (d) Heads convex to pressure shall not be used for tanks over 24 inches in diameter. (e) Welded tanks shall be constructed only by tested and qualified pressure welders in accordance with Section 12 of these Regulations. (f) All expansion tanks over 30 inches in diameter shall be built under shop inspection and the hydro-static test pressure shall be one and one-half times the design pressure. Tanks 30 inches and under in diameter may be built without shop inspection in which case the hydro- static test pressure shall be twice the design pressure. (g) All expansion tanks constructed in accordance with a registered design shall be stamped or marked as specified in Section 6 of CSA Code B51 and in these Regulations.
28 28 DESIGN, CONSTRUCTION, INSTALLATION AND (h) A Manufacturer s Affidavit form shall be submitted for each tank constructed in accordance with a registered design Safety Relief Valve Requirements. (a)(1) Every hot-water heating boiler or hot-water supply boiler and operating in a closed system shall be equipped with one or more approved and registered safety relief valves having an aggregate relieving capacity of not less than 5,000 B.T.U. per hour or 5 pounds of steam per hour, for each square foot of boiler heating surface. Such relief valves shall meet all the requirements of Rule (2) Where the capacity rating of the boiler in B.T.U. or pounds of steam as specified by the manufacturer exceeds the capacity of safety relief valves as required in (a)(1), the boiler shall be equipped with valves capable of relieving the full boiler capacity as specified by the manufacturer. (b) If any unregistered valve is used in any installation, its capacity shall not be considered as relieving capacity required in rule (a) and its installation shall in no manner interfere with the safe operation of the required registered valve or valves. (c) No safety-relief valve required by these rules shall be smaller than 3/4 inch pipe size or larger than 4 1/2 inch pipe size and any combination of such sizes may be used provided their installation meets the requirements of these rules. (d) Every safety-relief valve required under these rules shall be set to relieve at or below the maximum allowable working pressure of the boiler as approved by the department provided that where more than one valve is used they may be set as follows: (1) a valve or valves having at least 25 per cent of the relieving capacity of the boiler as required in rule (a) shall be set to relieve at or below the maximum allowable working pressure; (2) the additional valve or valves require may be set to relieve at not more than 10 psi above the maximum allowable working pressure. Note: Approximately 90 per cent of all such boilers are approved and registered by the department for a working pressure of 30 p.s.i. (e)(1) For new installations all safety-relief valves required by these rules shall be installed directly upon the upper part of the boiler shell or its cast iron sections provided that where more than one valve is required an approved multiple connection may be used; (2) For boilers in use before the coming into force of these rules, any additional safety-relief valves required to meet the relieving capacity specified in rule (a) may be installed upon piping immediately adjacent to the upper part of the boiler provided that such piping is of a size that will adequately serve its original purpose if any, and in addition allow the valve or valves to discharge their full relieving capacity at all times. There shall be no intervening stop-valve or similar device in such piping by which the safetyrelief valve or valves may be isolated from the boiler. (3) Discharge pipes shall be provided on all safety-relief valves required herein which shall be of such size that the valves will discharge their full capacity and shall be so arranged that there is no danger of scalding attendants.
29 DESIGN, CONSTRUCTION, INSTALLATION AND 29 (f) No newly installed hot water boiler to which these rules apply shall be put into service unless it is equipped with approved safety-relief valves as specified herein and any used boiler required by the department to be thus equipped shall be made to comply with these requirements within 30 days or the boiler may be sealed and its use prohibited Relief Valve Registration and Design. (a) Every safety relief valve required under rule (1302) shall have its design approved and registered by the department who shall allot thereto a registration number and each valve constructed to an approved and registered design shall have stamped thereon or on a permanently attached plate the following: (i) the name or identifying trademark of the manufacturer; (ii) the pipe size of the valve inlet; (iii) the pressure at which it is set to relieve; (iv) the capacity in B.T.U. per hour or pounds of steam per hour or both; (v) the provincial registration number as allotted by the department or the ASME safety valve symbol as authorized by the ASME Boiler Code Committee. (b) Every safety relief valve design submitted to the department for approval and registration shall include the following: (i) two sets of drawings and specification sheets giving all design detail; (ii) a facsimile showing all markings and identification required in rule (a) which facsimile may be upon the design drawings or upon separate sheets; (iii) a certification or photostatic copy of same showing that the valve design has been capacity tested and rated by the National Board of Boiler and Pressure Vessel Inspectors in accordance with the requirements of the ASME Low Pressure Heating Boiler Code; (iv) particulars, including registration numbers, of prior registration in other provinces. (c) The design of every safety-relief valve submitted for registration shall meet the following requirements: (i) the valve shall be spring loaded, especially designed for hot-water boiler service; (ii) there shall be no wing guides on the pressure side of the disc; (iii) the seat and discs shall he capable of withstanding a temperature of 275 degrees F without deterioration; (iv) the valve shall be constructed with a substantial lifting device which will positively lift the pressure relieving disc from its seat for testing purposes; (v) provision shall be made for an inspectors seal to prevent alteration to or tampering with the relieving pressure; (vi) the design shall meet all requirements of the ASME Low-Pressure Heating Boiler Code.
30 30 DESIGN, CONSTRUCTION, INSTALLATION AND 1304 Other Safety Devices. (a) Every hot-water heating boiler or hotwater supply boiler to which these rules apply, if gas, oil or stoker fired and equipped with automatic control shall in addition to being equipped with safety-relief valves as specified herein be fitted as follows: (1) with at least one temperature control device and, (2) if having more than 100 square feet of heating surface with a low water cut-off device. (b) Every device used as specified in (1) and (2) shall be of an approved design capable of shutting off the fuel fire in the event of excessive temperature or low water, and the low water cut-off device shall be installed in a column or chamber separate from the boiler in such a manner that its proper operation may be tested by thoroughly blowing down the column or chamber 1305 Every hot-water heating boiler shall be fitted with a pressure or altitude gauge, a hot-water thermometer and a bottom blow-off or drain connection of not less than ¾ inch pipe size. 19 Jly 57 s13; 8 May 70 SR 96/70. SECTION 14 FEES Repealed. 8 May 70 SR 96/70. REGINA, SASKATCHEWAN Printed by the authority of THE QUEEN S PRINTER Copyright 1997
PLEASE NOTE. For more information concerning the history of these regulations, please see the Table of Regulations.
PLEASE NOTE This document, prepared by the Legislative Counsel Office, is an office consolidation of this regulation, current to March 1, 2014. It is intended for information and reference purposes only.
CHAPTER 10 BOILERS, WATER HEATERS AND PRESSURE VESSELS
CHAPTER 10 BOILERS, WATER HEATERS AND PRESSURE VESSELS SECTION 1001 GENERAL 1001.1 Scope. This chapter shall govern the installation, alteration and repair of boilers, water heaters and pressure vessels.
PRESSURE EQUIPMENT SAFETY REGULATION
Province of Alberta SAFETY CODES ACT PRESSURE EQUIPMENT SAFETY REGULATION Alberta Regulation 49/2006 With amendments up to and including Alberta Regulation 195/2015 Office Consolidation Published by Alberta
PLEASE NOTE. For more information concerning the history of this Act, please see the Table of Public Acts.
PLEASE NOTE This document, prepared by the Legislative Counsel Office, is an office consolidation of this Act, current to December 2, 2015. It is intended for information and reference purposes only. This
The Boiler and Pressure Vessel Regulations
BOILER AND PRESSURE VESSEL B-5.1 REG 1 1 The Boiler and Pressure Vessel Regulations being Chapter B-5.1 Reg 1 (effective January 1, 2007) as amended by Saskatchewan Regulations 79/2008 and 121/2008. NOTE:
POWER ENGINEERS REGULATION
Province of Alberta SAFETY CODES ACT POWER ENGINEERS REGULATION Alberta Regulation 85/2003 With amendments up to and including Alberta Regulation 84/2014 Office Consolidation Published by Alberta Queen
Sec. 29-232 page 1 (5-98)
Department of Public Safety Sec. 29-232 page 1 (5-98) TABLE OF CONTENTS Boiler Design, Construction, Installation, Repair, Use and Operation Definitions.... 29-232- 1 General Requirements Manufacturer
FLASH TANK ECONOMIZER PRODUCT GUIDE
FLASH TANK ECONOMIZER PRODUCT GUIDE Overview A flash tank is used to recover blowdown energy in the form of flash steam and blowdown. This can only be used with a deaerator or some other pressurized device.
2010 Residential Water Heater Replacement Check List
2010 Residential Water Heater Replacement Check List The intent of this check list is to provide installers a general reference for the enforcement of code requirements in the Greater San Diego Area. This
Factory owners must ensure the boiler is:
Factory owners must ensure the boiler is: * Registered with the Boilers and Pressure Vessels Division, Labour Department * Examined by an appointed examiner and has a valid certificate of fitness * Supervised
The Boiler and Pressure Vessel Act, 1999
1 BOILER AND PRESSURE VESSEL c. B-5.1 The Boiler and Pressure Vessel Act, 1999 being Chapter B-5.1 of The Statutes of Saskatchewan, 1999 (effective January 1, 2007) as amended by the Statutes of Saskatchewan,
Routine and Emergency Boiler Operation
Routine and Emergency Boiler Operation Learning Outcome When you complete this module you will be able to: Describe the routine safe and efficient operation of a packaged boiler. Learning Objectives Here
Indirect-Fired Storage Water Heater Models WH-30 through WH-80 INSTALLATION AND OPERATING INSTRUCTIONS
Indirect-Fired Storage Water Heater Models WH-30 through WH-80 INSTALLATION AND OPERATING INSTRUCTIONS Contents Page Ratings and Specifications..................... 2 Installation Requirements......................
Boiler & Pressure Vessel Inspection discrepancies and failures
Boiler & Pressure Vessel Inspection discrepancies and failures Water Heaters / Pressure Vessels Pressure Vessels are inspected once every three years. This requires a test of A: safety relief devices B:
TYPICAL FIRE SAFETY INSPECTION VIOLATIONS
TYPICAL FIRE SAFETY INSPECTION VIOLATIONS The following is a list of typical violations often found by inspectors and a generic solution. You can use this list to improve the safety of your facility, to
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression
SECTION 105 PERMITS. 2. Fences not over 6 feet (1829 mm) high. 3. Oil derricks.
SECTION 105 PERMITS 105.1 Required. Any owner or authorized agent who intends to construct, enlarge, alter, repair, move, demolish, or change the occupancy of a building or structure, or to erect, install,
SAMPLE TEST QUESTIONS STEAMFITTER/PIPEFITTER - ITA WEBSITE
1 Which tool is used to correct internal hi-low when preparing a 4-in. steel pipe for welding? A. 4-in. grinder with cutting disc. B. Mini-grinder with flapper disc. C. Pencil grinder with cone stone.
OPERATIONS & MAINTENANCE (O&M) FOR PROPANE STORAGE FACILITIES
OPERATIONS & MAINTENANCE (O&M) FOR PROPANE STORAGE FACILITIES Reference: National Fire Protection Association (NFPA) Pamphlet No. 58 Liquefied Petroleum Gas Code, 2001, Chapter 11 Type of Facility: Petroleum
ELECTRODE BOILERS VAPOR POWER INTERNATIONAL
ELECTRODE BOILERS WITH JET-FLO Technology VAPOR POWER INTERNATIONAL ELECTRODE boilers The Electrode Steam Boiler with Jet-Flo technology consists of an insulated pressure vessel and is fully enclosed in
Chicago Stationary Engineer Licensure Examination Information
Chicago Stationary Engineer Licensure Examination Information This candidate guide should help you prepare for the Chicago Stationary Engineer licensure examination. Part I contains general information
LAKE COUNTY ANIMAL SERVICES EXPANSION SECTION 15459
SECTION 15459 PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification sections, apply to work
PIPES AND TUBES FOR HVAC PIPING AND EQUIPMENT
PIPES AND TUBES FOR HVAC PIPING AND EQUIPMENT GENERAL INFORMATION 1.1 This section applies to piping systems for chilled water, hot water, condenser water, steam, condensate return, fuel oil, refrigerant
NFPA31FuelOilPiping 1 Revised 3-1-11
NFPA 31 Fuel Oil Piping, Installation and Testing Chapter 8 Fuel Piping Systems and Components 8.1 Scope. This chapter shall apply to piping systems and their components used to transfer fuel oil from
The Passenger and Freight Elevator Act
1 PASSENGER AND FREIGHT ELEVATOR c. P-4 The Passenger and Freight Elevator Act being Chapter P-4 of The Revised Statutes of Saskatchewan, 1978 (effective February 26, 1979) as amended by the Statutes of
CHAPTER 5 WATER HEATERS
PlumbingCode06_ch05 5/29/06 8:12 AM Page 1 CHAPTER 5 WATER HEATERS Water heaters are only a small portion of a plumbing system, but they are important, and they can be dangerous. Many plumbers take water
CHAPTER 7 BUILDING ARTICLE 7-1 UNIFORM CODES 1. 7-1-1 Adoption. Board of Appeals. Annual Review
CHAPTER 7 BUILDING ARTICLE 7-1 UNIFORM CODES 1 7-1-1 Adoption 7-1-2 Board of Appeals 7-1-3 Annual Review Section 7-1-1 Adoption A. Those certain documents known as the 1997 Uniform Building Code, Volumes
CHAPTER IV SPECIAL REGULATIONS - GAS UTILITIES ONLY. Records. Each gas utility shall maintain and keep the following records:
CHAPTER IV SPECIAL REGULATIONS - GAS UTILITIES ONLY Section 401. Records. Each gas utility shall maintain and keep the following records: (a) Monthly record of the heating value of gas produced or purchased
SIZING AND CAPACITIES OF GAS PIPING
APPENDIX A (IFGS) SIZING AND CAPACITIES OF GAS PIPING (This appendix is informative and is not part of the code.) A.1 General. To determine the size of piping used in a gas piping system, the following
CONSTRUCTION FIRE SAFETY PLANNING GUIDELINES
CONSTRUCTION FIRE SAFETY PLANNING GUIDELINES Review the following information pertaining to Construction Fire Safety Planning: B.C. Building Code Sections 8.1 up to and including Subsection 8.2.3 B.C.
Commercial Gas Water Heaters
POWERED BURNER MODELS LARGE-VOLUME POWERED BURNER FEATURES The large-volume powered burner line includes the largest, most powerful A. O. Smith tanktype gas water heaters. With tank capacities up to 600
WHITE PLAINS PLUMBING CODE PART 1. GENERAL REQUIREMENTS
WHITE PLAINS PLUMBING CODE PART 1. GENERAL REQUIREMENTS a. New Plumbing and Gas Piping Systems. This code in conjunction with the Plumbing and Fuel Gas Codes of the State of New York shall apply to plumbing
Blowdown vessels Meeting the requirements of HSE PM60
Blowdown vessels Meeting the requirements of HSE PM60 BDV60 blowdown vessels complete range of equipment for the safe disposal of boiler blowdown Boiler blowdown Steam boilers must be blown down to remove
Section 20 TABLE OF CONTENTS Pressurized Equipment and Systems. 20.A General... 20-1. 20.B Compressed Air and Gas Systems... 20-4
Section 20 TABLE OF CONTENTS Pressurized Equipment and Systems Section: Page 20.A General... 20-1 20.B Compressed Air and Gas Systems... 20-4 20.C Boilers and Systems... 20-7 20.D Compressed Gas Cylinders...
BLADDER SURGE CONTROL SYSTEM
PART I GENERAL 1.01 Description BLADDER SURGE CONTROL SYSTEM This specification describes the requirements for a Bladder Surge Control System. The purpose of the system is to minimize transient pressures
Welding of Boilers, Pressure Vessels and Pressure Piping
WELDING OF BOILERS, PRESSURE VESSELS 1 Welding of Boilers, Pressure Vessels and Pressure Piping Repealed by Chapter B-5.1 Reg 1 (effective January 1, 2007) Formerly Saskatchewan Regulation 61/78 (effective
External Visual Inspection Form
Tank ID Code Part 1 (a): Information on Registered Facility Name of Registered Facility: Address: Town: Postal Code: Province: Phone Number: Person Conducting the Inspection: Transport Canada Facility
DARTMOUTH COLLEGE DESIGN January 3, 2012 & CONSTRUCTION GUIDELINES
SECTION 15062 STEAM AND CONDENSATE PIPING PART 1 DESIGN DIRECTIVES 1.1 QUALITY ASSURANCE A. Comply with the provisions of the following: 1.2 DESIGN CRITERIA 1. ASME B 31.9 Building Services Piping : for
Boiler and Burner Cleaning and Servicing Specifications
Boiler and Burner Cleaning and Servicing Specifications The Town of Groton of Public Works Department is requesting bids to provide manufacturers recommended maintenance, repairs and emergency service
5.23.22 STEAM AND CONDENSATE PIPING AND PUMPS DESIGN AND CONSTRUCTION STANDARD PART 1: GENERAL. 1.01 Purpose:
PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is
Indiana Boiler and Pressure Vessel Safety Section Frequently Asked Questions
Indiana Boiler and Pressure Vessel Safety Section Frequently Asked Questions What are the licensing requirements for boiler operators? Answer: Indiana statute (IC 22-15-6) and administrative rules (680
MANAGEMENT AND USE OF WORK EQUIPMENT: PRESSURE SYSTEMS
Health & Safety Services Unit name goes here Safety Code of Practice 46, Part 2 1st Edition, November 2009 MANAGEMENT AND USE OF WORK EQUIPMENT: PRESSURE SYSTEMS University of Reading 2015 Page 1 Contents
ASTM A860/A860M-09 Standard Specification for Wrought High Strength. Ferritic Steel Butt Welding Fittings. 1. Scope :- 2. Reference Documents :-
Standard Specification for Wrought High Strength Ferritic Steel Butt Welding Fittings 1. Scope :- 1.1 This specification covers wrought high strength ferritic steel butt-welding fitting of seamless and
AIR RELEASE, CLEANOUT, AND SEWER MANHOLES
AIR RELEASE, CLEANOUT, AND SEWER MANHOLES **From Hartford IM BLDG(10) DESCRIPTION. This work shall consist of the construction of air release, cleanout, and sanitary sewer manholes; and the furnishing
What to Expect From the Examination. How to Study the Plumbing Codes
Texas State Board of Plumbing Examiners Plumbing Inspector Examination Review Course The following Examination Review Course is designed to assist an applicant in preparing for the Plumbing Inspector examination.
Originators of the Flexible Water Tube design
BRYAN FLEXIBLE WATER TUBE AB SERIES STEAM AND WATER BOILER 900,000 TO 3,000,000 BTUH FORCED DRAFT GAS, OIL OR DUAL FUEL FIRED Water Boiler AB120-W-FDGO Steam Boiler AB250-S-150-FDG Originators of the Flexible
Subpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715,
4658.4500 PLUMBING SYSTEMS; NEW CONSTRUCTION. Subpart 1. Installation. All plumbing systems must be installed and tested according to this chapter and chapter 4715, the Minnesota Plumbing Code. Subp. 2.
SECTION 15410 GROUND WATER STORAGE TANKS
SECTION 15410 GROUND WATER STORAGE TANKS PART 1 GENERAL.01 SCOPE A. Section Includes Requirements for designing, fabricating, and erecting a welded steel ground storage tank..02 SYSTEM DESCRIPTION A. Design
Pressure Vessels (Air Compressors) and LPG Tanks
Pressure Vessels (Air Compressors) and LPG Tanks 1. Identification of Workplace Hazard Any container, tank or vessel that contains pressurized material is a potential hazard to employees due to the force
HS-901(A) BASIC STEAM HEATING SYSTEMS
HS-901(A) BASIC HEATING SYSTEMS One-Pipe Two-Pipe Basic Steam Heating Systems One-pipe steam heating system EQUALIZER SAFETY FACTOR STATIC HEAD PRESSURE DROP 2" HEATING UNIT 15" DRIP CONNECTION In a one-pipe,
Some Criteria for Choosing a Steam Boiler for a Microbrewery
Some Criteria for Choosing a Steam Boiler for a Microbrewery Jack Coe Rite Engineering and Manufacturing Corporation Breweries rely on steam heating for a number of functions, primarily to heat the brew
SECTION 15076 CEMENT-MORTAR LINED AND COATED STEEL PIPE
SECTION 15076 CEMENT-MORTAR LINED AND COATED (CML&C) STEEL PIPE PART 1 GENERAL 1.01 DESCRIPTION This section designates the requirements for steel pipe fabrication, test in shop, installation of steel
PLEASE NOTE. For more information concerning the history of this Act, please see the Table of Public Acts.
PLEASE NOTE This document, prepared by the Legislative Counsel Office, is an office consolidation of this Act, current to December 2, 2015. It is intended for information and reference purposes only. This
Department of Veterans Affairs VHA DIRECTIVE 2008-062 Veterans Health Administration Washington, DC 20420 October 15, 2008 BOILER PLANT OPERATIONS
CORRECTED COPY Department of Veterans Affairs VHA DIRECTIVE 2008-062 Veterans Health Administration Washington, DC 20420 BOILER PLANT OPERATIONS 1. PURPOSE: This Veterans Health Administration (VHA) Directive
STATE OF NEW JERSEY DEPARTMENT OF LABOR AND WORKFORCE DEVELOPMENT LABOR STANDARDS & SAFETY ENFORCEMENT DIVISION OF PUBLIC SAFETY
STATE OF NEW JERSEY DEPARTMENT OF LABOR AND WORKFORCE DEVELOPMENT LABOR STANDARDS & SAFETY ENFORCEMENT DIVISION OF PUBLIC SAFETY AND OCCUPATIONAL SAFETY & HEALTH INFORMATION GUIDE FOR THE INSPECTION OF
DRAFT 2015 SEATTLE BOILER CODE
DRAFT 2015 SEATTLE BOILER CODE Comments may be addressed to Larry Leet, [email protected] no later than November 25, 2015. October 26, 2015 Contents Section 1 Administrative... 5 1.1 Title... 5 1.2
The Pipelines Regulations, 2000
PIPELINES, 2000 P-12.1 REG 1 1 The Pipelines Regulations, 2000 being Chapter P-12.1 Reg 1 (effective April 1, 2000) as amended by the Statutes of Saskatchewan, 2014, c.21. NOTE: This consolidation is not
SECTION 221413 FACILITY STORM DRAINAGE PIPING
SECTION 221413 FACILITY STORM DRAINAGE PIPING PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01
Chapter 18 - Plumbing Code City of South Milwaukee
Chapter 18 - Plumbing Code City of South Milwaukee NOTE: The information listed below may not be accurate and up-to-date. The information is accurate as of the date listed at the bottom of the page; however,
WHEN IS A PERMIT REQUIRED?
WHEN IS A PERMIT REQUIRED? Any owner, builder, contractor, or other authorized agent who intends to construct, enlarge, alter, repair, move, demolish, or change the occupancy of a building or structure,
Welding Codes and How They're Used (DOD) (ANSI). (AWS), (ASME) (API). not American Welding Society AWS D1.1 AWS D1.2 AWS D1.3 AWS D1.4 AWS D1.
Welding Codes and How They're Used Almost all design, welding, fabrication, material, repair, testing, and inspection requirements are covered under three main governing organizations. Even the Department
INSTALLATION AND OPERATION INSTRUCTIONS - (LOW FLOW MODELS) (Before installation, compare electrical needed for the model of heater selected)
CHRONOMITE INSTANT-FLOW WATER HEATER INSTALLATION AND OPERATION INSTRUCTIONS - (LOW FLOW MODELS) (Before installation, compare electrical needed for the model of heater selected) TABLE 1 Model No. Wattage
PLBG/GAS SAFETY Information Bulletin
PLBG/GAS SAFETY Information Bulletin November 2012 P/G-08-02-PLBG/GAS [Rev 3] Page 1 of 11 SUBJECT: REQUIREMENTS FOR COMBINATION HEATING SYSTEMS: DUAL PURPOSE WATER (POTABLE) HEATER (COMBO UNIT) Safety
Walking and Working Surface Checklist:
Walking and Working Surfaces Purpose: This information is presented to improve the level of safety in our operations, and to inform you that we will comply with the OSHA Standard 29 CFR 1910.23. Responsibility:
G234X-55 Conventional Gas Boiler
Engineering Submittal Sheet Boiler Overview C US Engineering Specifications There shall be provided and installed a quantity of Buderus G234X-55 fl oor standing hot water boiler(s), suitable with natural
Arapahoe County Residential Water Heater Installation and Inspection Guide
Arapahoe County Residential Water Heater Installation and Inspection Guide The attached handout is designed to be a general permit submittal and inspection guide covering most installation instances, however
The following definitions apply with regard to requirements specified in this document:
GUIDELINES FOR INSTALLATION OF TEMPORARY AND PERMANENT ABOVEGROUND DIESEL FUEL TANKS FOR EMERGENCY AND STANDBY POWER SYSTEMS LOCATED OUTSIDE OF BUILDINGS For Use by Unidocs Member Agencies or where approved
1 RCNY 101-07 CHAPTER 100
1 RCNY 101-07 CHAPTER 100 Subchapter A Administration 101-07 Approved Agencies. (a) Definitions. For the purposes of this section, all terms used herein shall have the same meanings as set forth in the
ASME Packaged Indirect Fired Water Heater
Utilizes Or HTHW To Heat Domestic Water, Semi-Instantaneous or Storage Type Model BW Features Reliable Only high grade materials used in construction to ensure long operating life Hydrastone cement lining
MUELLER FALLING FILM CHILLERS
MUELLER FALLING FILM CHILLERS MUELLER FALLING FILM CHILLERS ARE DESIGNED TO COOL ANY FLUID TO WITHIN 2 F OF ITS FREEZE POINT. The primary application for Mueller s falling film chiller is to cool food-grade
G-704-0 SPECIFICATION: GAS METER AND REGULATOR INSTALLATION REQUIREMENTS. 3 and Gas Yellow Book. REVISIONS: (See ) 1/15/14 5 Years
LAST REVIEW DATE: REVIEW CYCLE: 1/15/14 5 Years SPECIFICATION: TITLE: VOLUME: G-704-0 3 and Gas Yellow Book REVISIONS: (See ) 1) This specification is being issued for the first time. G-704-0 Gas Operations
SECTION 1 GENERAL REQUIREMENTS
Page 1 of 6 SECTION 1 GENERAL REQUIREMENTS 1. SCOPE OF WORK: The work to be performed under the provisions of these documents and the contract based thereon includes furnishing all labor, equipment, materials,
The following definitions apply with regard to requirements specified in this document:
GUIDELINES FOR INSTALLATION OF TEMPORARY AND PERMANENT ABOVEGROUND DIESEL FUEL TANKS FOR EMERGENCY AND STANDBY POWER SYSTEMS LOCATED OUTSIDE OF BUILDINGS For Use by Unidocs Member Agencies or where approved
Top 10+ Mistakes of DWV plumbing design
Top 10+ Mistakes of DWV plumbing design Listed below are the some of the most frequently missed items, noticed by our inspectors, at plumbing rough-in when non-plumbers attempt plumbing design. Most of
Recommended Administrative Boiler and Pressure Vessel Safety Rules and Regulations
Recommended Administrative Boiler and Pressure Vessel Safety Rules and Regulations Approved by Board of Trustees: October 25, 2004 The National Board of Boiler & Pressure Vessel Inspectors 1055 Crupper
Hot Water Boilers and Controls Why Condensing Boilers are Different. Presented Oct. 14, 2008 Long Island Chapter, ASHRAE
Hot Water Boilers and Controls Why Condensing Boilers are Different Presented Oct. 14, 2008 Long Island Chapter, ASHRAE H.W. Boilers and Controls Major types of boilers Advantages and disadvantages Resistance
Essentials Welding QA/QC Plan Sample
Essentials Welding QA/QC Plan Sample Good for smaller projects and bid qualifications Has All the Essential Elements of a well-founded Quality Control Plan Contact: Ed Caldeira 410-451-8006 Pat [Pick the
Plumbing Installations. A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling
Plumbing Installations A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling February 2001 contents General Information 3 Inspection 4 New Drain and Vent Installations
Services Enclosures and Protected Shafts - Maintaining Compartmentation
Introduction When a fire resisting element is used to provide fire compartmentation, every opening that allows services to pass through the element must be adequately protected by sealing, or fire stopping
Plumbing Installations A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling
PLANNING, PROPERTY AND DEVELOPMENT DEPARTMENT Plumbing Installations A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling October 2014 contents General Information
General Fire Code Requirements Within Commercial Tenant Spaces
FIRE DEPARTMENT in cooperation with Scope: General Fire Code Requirements Within Commercial Tenant Spaces This handout is designed to assist owners, architects, contractors and others in understanding
TABLE 1. Rugged cast aluminum alloy casing,celcon waterways with nichrome parts White (unless stainless steel housing)
CHRONOMITE INSTANT-FLOW MICRO WATER HEATER INSTALLATION AND OPERATION INSTRUCTIONS - (LOW FLOW MODELS) (Before installation, compare electrical needed for the model of heater selected) TABLE 1 Model No.
Course available 24/7 for up to six months from the date of purchase or until completion
SPED ONLINE COURSE TRAINING Piper BootCamp and Process Plant Layout BOTH Piper BootCamp and Process Plant Layout online courses contain: Approximately 25 hours of online videos Printable notes Links to
API Flanged Safety Relief Valves Series 526 CATALOG
API Flanged Safety Relief Valves Series 26 CATALOG The-Safety-Valve.com 1 Valve finder How to find the right product group High operating to set pressure ratio, high backpressure or low total height? Yes
UltraTech International, Inc. Canadian Secondary Containment Requirements
UltraTech International, Inc. 11542 Davis Creek Court Jacksonville, Florida 32256 Canadian Secondary Containment Requirements The Canadian Council of Ministers of the Environment (CCME) is the major intergovernmental
COMPRESSED GASES. 1.2 The contents of each cylinder and container must be clearly identified (by tag or stamp) on the cylinder.
Page 1 of 5 COMPRESSED GASES A compressed gas is defined as any mixture of gases in a container with a pressure exceeding 40 psi. at 70 o F, or 104 psi. at 130 o F; or any flammable liquid with an absolute
SIZING AND CAPACITIES OF GAS PIPING
CALIFORNIA RESIDENTIAL CODE MATRIX ADOPTION TABLE APPENDIX A SIZING AND CAPACITIES OF GAS PIPING (Matrix Adoption Tables are non-regulatory, intended only as an aid to the user. See Chapter 1 for state
Owner-User Pressure Equipment Integrity Management Requirements
the pressure equipment safety authority Owner-User Pressure Equipment Integrity Management Requirements AB-512 Edition 2, Revision 0 Issued 2015-06-25 Owner-user Pressure Equipment Integrity Management
Selecting TEMA Type Heat Exchangers
Selecting TEMA Type Heat Exchangers TEMA is a set of standards developed by leading heat exchanger manufacturers that defines the heat exchanger style and the machining and assembly tolerances to be employed
5.2. Vaporizers - Types and Usage
5.2. Vaporizers - Types and Usage 5.2.1. General Vaporizers are constructed in numerous designs and operated in many modes. Depending upon the service application the design, construction, inspection,
Revised April (May) 2015
Section 19.0 Cross Connection Control Policy 19.1 Responsibility 19.1.1 The Elkhart Water Utility has the responsibility to supply safe, potable water from the source to the point of delivery defined as
PLUMBING ROUGH IN INSPECTION
This Program is made Possible through the Code Officials Education & Training Fund. Revenue for the Fund comes from Assessments on Building Permits. Please turn down cell phones and put pagers on vibrate.
SANITARY SEWER SPECIFICATIONS
SANITARY SEWER SPECIFICATIONS OCTOBER 2003 HARVEST-MONROVIA WATER, SEWER, AND FIRE PROTECTION AUTHORITY SECTION 1.00 1.10 Purpose The purpose of this document is to assemble the sewer specifications, policies,
Gas Unit Heaters Duct Furnaces Horizontal - 60 HZ Form No. LF24-100-400 (10/2011) LF24 Standard
LF Standard Features Horizontal unit heaters are compact in design and easy to install. Steady State Efficiencies of up to 80.%. Ideal for economical commercial heating systems. Shipped completely assembled
DRY CLEANING PLANTS REQUIREMENTS FOR INSTALLATION AND OPERATION
DEPARTMENT OF TRADE MERCHANT SHIPPING NOTICE NO.M.847 DRY CLEANING PLANTS REQUIREMENTS FOR INSTALLATION AND OPERATION Notice to Shipowners, Masters, Shipbuilders and Repairers 1. It has come to the notice
BOILER CLASS 5, 5A/5B LICENSE EXAMINATION STUDY GUIDE
STATE OF OREGON DEPARTMENT OF CONSUMER AND BUSINESS SERVICES BUILDING AND CODES DIVISION BOILER CLASS 5, 5A/5B LICENSE EXAMINATION STUDY GUIDE 1 General Information for all Licensees The following study
