CLARK COUNTY DEPARTMENT OF BUILDING COMMERCIAL PLUMBING AND MECHANICAL INSPECTION CHECKLISTS 2006 CODE
|
|
|
- Angelica Ward
- 10 years ago
- Views:
Transcription
1 CLARK COUNTY DEPARTMENT OF BUILDING COMMERCIAL PLUMBING AND MECHANICAL INSPECTION CHECKLISTS 2006 CODE
2 GENERAL NOTES This checklist is intended for use as a GUIDE to assist and promote consistency in the application of the plumbing code and standard practices within Clark County. This list is for use of county inspectors and for the general public. This checklist is for wood frame and light commercial structures. The information in this checklist is not, nor was it ever intended to be, all-inclusive. It does not include all code or individual plan requirements. It is intended to reflect local policies, procedures and practices within Clark County. This checklist does not waive any specific code requirements not listed or allow for the decrease in the requirements of an engineered design. It also does not add requirements where the minimum of the code has been met. All approved plans, documents and revisions to plans must be maintained on site and available for review at all times the building is under construction. All plans and paperwork will be reviewed before performing any inspection. The owner, permit holder or responsible person, on the job site, is responsible for establishing safe access to perform all inspections. In the event that ladders are necessary to perform inspections, all ladders and equipment shall meet minimum OSHA standards. Inspectors are not responsible for setting up or moving ladders from one location to another, within or to other buildings or structures. Inspectors are not responsible for unscrewing /unbolting of items to verify information that is part of an inspection. PROHIBITED FITTINGS AND PRACTICES Combination fittings to catch or receive fixture trap arms Sanitary tees on their backs used for drainage Horizontal wet venting (excluding residential) Double combination fitting used in the horizontal Side inlet ¼ bends. Double Wisconsin or Nawlins fittings (singles are ok) Trap and trap arm shall be the same size (reduction may be made on the inlet side of the trap only). Code references coding o A= amendment o E= energy code o EL= NEC, electrical code o R= residential code COMMERCIAL PLUMBING GENERAL NOTES PAGE 1 OF 1
3 Drain, Waste and Vent Piping COMMERCIAL UNDERGROUND PLUMBING (4412) Clean outs on runs in excess of 100 feet Manholes in lieu of cleanouts at 300 feet and direction of flow Back water valves where indicted on site plan foot head test or 5 psi air test Trap primers installed where there is no maintenance or infrequent use. 708/T7-5 Grading of piping, ¼ inch per foot, unless otherwise noted. Use footnote #5, Table 7-5, for 4 inch and above, if approved Use of listed transition fittings and couplings; i.e., from cast iron to plastic or copper to plastic. 700 Use of accepted alternate materials and methods; i.e. Solvent Systems. Plans Check for rated materials used in specific occupancies and construction types. Plans Check for piping within rated envelopes and penetrations. ANSI Check to see that all ANSI A117.1 requirements for handicapped are met. T7-5 Check all venting runs and termination sizes. Cross sectional areas shall be maintained throughout the system. T7-5 Check for horizontal runs in excess of limitations of Table 7-5, footnotes. T7-3/T7-5 Sizing per Table 7-3 and 7-5 (don t forget the footnotes). T7-6 Cleanout sizing per Table 7-6: a. 1 ½ inch pipe 1 ½ inch c.o. b. 2 inch pipe 1 ½ inch c.o. c. 2 ½ inch 2 ½ inch c.o. d. 3 inch 2 ½ inch c.o. e. 4 & larger 3 ½ inch c.o Clean out with raised square heads or slotted heads. 312/305.1 Connection of building sewer to utility required (sewer inspection). FIG-P-019 Cleanouts installed at underground or locations marked with a brightly colored paint Cleanouts shall be at all sink locations, urinals and horizontal changes of direction exceeding 135 degrees and horizontal drain lines greater than 5 feet off the main line. FIG-P-012 Air admittance valves (Studor). COMMERCIAL UNDERGROUND PLUMBING (4412) PAGE 1 of 1
4 COMMERCIAL WATER PIPING (4425) ANSI Check that all 2003 ANSI A117.1 handicap requirements are met, to include the insulating of all exposed pipes and drains. Plans Specific type of piping and grade of piping to be installed per plan. T6-4 Sizing per Table 6-4 and 6-5 (remember the footnotes). T6-2 Backflow devices Table 6-2. T6-3 Minimum air gap Table 6-3. T6-6 Air chamber devices Table Air hammer chambers on quick acting valves and copper piping systems Pressure regulator valve (PRV) required where the psi is greater than 80 psi. E504.5 Weather protection (insulation) where exposed to freezing conditions. T3-2 Strapping and supports within the limits of Table Accessible strainer ahead of PRV or integral of the device Minimum of 12 inches of cover on piping below grade Provide sleeving on copper piping below grade and passing through concrete. T3-2 Pex piping installed to manufacturer s installation instructions and supported at 32 inches on center. Manufacture Pex piping to have slack for expansion and contraction. PE in stem wall, sleeved; sleeve to be a minimum 6 inches above stem wall with the PE termination 6 inches above the sleeve before any transition Flushometer installation according to Table Reclaimed water systems properly identified. 605/605.7 Proper shut off valves for fixtures. 402/402.6 Acceptable water conservation fixtures and preset devices per Chapter Water lines should have working pressure on the system or a 50 psi air test. COMMERCIAL WATER PIPING (4425) PAGE 1 of 1
5 Gas Piping General COMMERCIAL GAS PIPING (4422) FIG-P-002 Sizing of gas system per Table 12-1 and 12-3 (low pressure) Plans should outline what type of system is being installed, use 1000 BTU/cubic foot Follow the approved gas piping drawing for the installed gas piping. FIG-P-011 Gas systems to be a minimum of 6 inches above grade or structure (2) Support per Table 3-2 and 12-2 Shut off valves shall be accessible and within 3 feet of the appliance. NFPA 54 Gas line shall be sized through the gas valve. T12-1 Gas appliances within the limits of Table Chapter 12 Gas pipe sizing within the limits of the tables in Chapter Shut off valves located in the attic shall be above the insulation and above the platform on the firebox side of the appliances All gas piping installed on a roof shall be installed on nominal 6 inch weather treated wood block or preformed metal riser. Underground Gas Piping (A) PE tubing buried below grade a minimum of 18 inches to top of pipe with 3 inch sand bedding. Manufacturer PE installations using heat fusion shall have the applicators card on site (C) 18 gauge yellow tracer wire shall be attached to the PE piping and extended a minimum of 6 inches above grade on each end (A) Metallic gas piping buried below grade shall be a minimum of 12 inches Metallic gas piping below grade shall be factory coated pipe with all pipe scrapes and fittings protected with a minimum of four wraps of ten mill tape No gas piping shall be installed under any building or structure unless properly sleeved and vented. A Sleeves shall be minimum schedule 40 and ½ inch larger than pipe and 12 inches beyond slab When beneath concrete sleeving shall be in place and vented to the atmosphere Copper tube gas piping applications rated K, L or ACR are allowed. COMMERCIAL GAS PIPING (4422) PAGE 1 of 1
6 COMMERCIAL ROUGH PLUMBING (4441) ANSI Check fixtures for handicapped clearances per 2003 ANSI A T3-2 Pipe and fittings shall be properly supported, per Table Traps shall be the same size as the trap arm they serve. Reductions shall be made on the tail piece to the trap foot head water testing on all DWV piping. When in doubt, ask for the manufacturers installation instructions Piping within 1 inch of edge of framing members shall be protected by 18 gauge nail plates. Manufacturer Tub and shower pans installed per manufacturers installations instructions Nail or screw in each of the flange holes for showers and tubs Access panel to Jacuzzi pump and GFCI outlet Water closest flanges measured for side and back clearances Joints at roof around pipes to be water tight by approved flashing material. T10-1 Maximum trap arm lengths: 1 ½ 3 feet, 6 inches 2 5 feet, 0 inches 3 6 feet, 0 inches Trap arm minimum length two times the diameter of the trap arm Trap arm may be increased one pipe size as long as the trap arm is the same as the trap Back to back or side to side fixtures use double fixture fitting Second floor check tub and shower pans are filled with water for test Built up shower pan liners sloped to drain Built up shower pans min 3 inches above dam level Second floor Closet flange holes shall be filled with corrosion resistant screws Access panels minimum 12 inches by 12 inches for concealed slip joints Clothes washer standpipe minimum 18 inches, maximum 30 inches above the trap weir Island sink vented properly to the nearest wall and foot vent to have cleanout Vent piping terminating a minimum of 6 inches above the roof Vents shall rise a minimum of 6 inches above flood rim of the fixture or use drainage fittings Aggregate vent area shall not be less than the minimum building drain Wet vent limited to one and two fixture unit fixtures and vertical applications only Wet vent piping to be one pipe size larger than the upper most fixture Wet vent shall be in the same story and a minimum size of 2 inches Built up shower pan shall have water proof membrane with 2 part drain. COMMERCIAL ROUGH PLUMBING (4441) PAGE 1 of 3
7 T6-4 Fixture counts within the limits of Tables 6-4, 6-5, Appendix A, 7-3, 7-5. T3-2 All supports (vertical and horizontal) within the limits of Table 3-2. T5-2 Verify all hanger rod, per pipe sizes within the limits of Table 5-2. T6-2 Verify minimum requirements for backflow protection per Table 6-2. T6-3 Minimum requirement for airgaps within the limits of Table 6-3. T6-7 Verify flushometer installations are within the limits of Table All needed cleanouts shall be installed and accessible (3) No cleanouts required above the first floor. T7-6 Verify cleanout sizing within the limits of Table 7-6: 1 ½ inch pipe 1 ½ inch c.o. 2 inch pipe 1 ½ inch c.o. 2 ½ inch 2 ½ inch c.o. 3 inch 2 ½ inch c.o. 4 & larger 3 ½ inch c.o Clean out with raised square heads or slotted heads Clean out extensions shall be from a wye or wye and 1/8 bend. T10-1 Verify trap and trap arm minimum and maximum lengths per Table T11-1/T11-2 Storm drainage sizing per the correct tables in Chapter 11 (use 2 inch column). T11-5 Verify scuppers and their sizing within the limits of Table T3-2 Pex piping supported every 32 inches horizontally or per manufacturer A full way valve shall be installed on the cold water supply piping Shower and tub/shower combination shall have individual control valves of the pressure balance or thermostatic mixing valve types for scald protection An expansion tank or temperature relief valve shall be installed on the cold side of the water heater to control thermal expansion A full way valve shall be installed on the cold side of the water heater supply A temperature and pressure relief line shall be installed at the water heater and terminated to the outside of the building Water heater shall be on a stand a minimum of 18 inches from the floor to the burner or element. In the 2000 UPC/UMC, if the equipment has a sealed combustion chamber, the equipment may sit directly on the garage floor Water heaters in furred space shall have a corrosion resistant pan with a minimum ¾ inch drain Water heaters and other mechanical equipment shall be protected from damage by adequate barriers Check for water hammer arresters at quick closing valves in copper piping systems. COMMERCIAL ROUGH PLUMBING (4441) PAGE 2 of 3
8 Mechanical Code B-Vents and single wall piping T8-2 B-Vent supported with min 1 inch clearance to combustibles, with flow up. A802.6(1) Shall terminate a minimum of 4 feet from a vertical surface No limit on 45 0 degree offsets Only one 60 0 degree offset allowed (5) Gas vent 3 inch minimum vent, in no case less than the appliance draft diverter Remember the termination of vents above the roof is determined by its size and roof slope, check Section Direct vent appliances and their terminations are in Section exception Shall terminate 1 foot above the roof into an approved vent cap. Manufacturer Vents 4 feet from property lines. Combustion Air Openings Plans Check for plan specific notes and manufacturers recommendations for guidance If the volume of the area in which gas fired appliances are located is equal to 50 cubic feet per 1000 BTU s, combustion air opening are not required. T5-2 See Chapter 5, Table 5-2. Take the volume of the room; width times length times height WxLxH. This number, when greater than the BTU rating of the appliance, needs no additional combustion air. T5-2 Refer to Table 5-2 in the Plumbing Code or Table 7-1 of the Mechanical Code. Plans Does the room have/need doors or louvers? Plans Does the enclosure open from the outside or inside the building? It makes a difference. COMMERCIAL ROUGH PLUMBING (4441) PAGE 3 of 3
9 Vent Connectors FINAL PLUMBING (4499) Single wall metal pipe cannot be in a concealed location Minimum 6 inches separation from combustibles for single wall Connectors shall rise a minimum of ¼ inch per foot Sheet metal screws shall attach the single wall to the draft diverter and single wall to the B-Vent Roof termination shrouds must be listed for system used. Gas piping Manufacturer Flex connectors shall be rated for the BTU of the appliance. Manufacturer Flex connectors rated for Mobile Homes are permitted to be used on mobile home applications only Flex connectors max length 6 feet Gas meters in gang installations shall be identified in a permanent manner identifying the location that the meter serves per Section Gas valves installed and properly capped or plugged. 319/ Final gas test air pressure at minimum 10 psi for 15 minutes (low pressure) Gauge to be max 2 times test pressure and 1/10 pound increments. 319/ psi for 30 minutes (medium pressure) Gauge to be max 2 times test pressure and 1 pound increments. Numbered gas tags shall be used when completing the final for multi-tenant spaces. FIG If gas test passes, issue gas tag, record number in history. FINAL PLUMBING (4499) PAGE 1 of 2
10 FINAL PLUMBING (4499) ANSI Verify all accessibility requirements. ANSI Verify handicapped fixtures to ANSI 2003 A Verify working clearances for cleanouts. Verify all backflow prevention devices are installed. If property has irrigation, verify that pressure vacuum breaker is installed a minimum of 12 inches above all downstream piping. 1 inch air break at water softener backwash line Main water shut-off shall be accessible and not in contact with soil Dishwasher air gap fitting shall be a minimum of 1 inch above flood level rim of the sink. 402/402.6 Verify water conservation aerators are in place Verify all required air breaks a minimum of 1 inch above. 402 Verify water conservation fixtures Locate all cleanouts and verify accessibility No double traps on any fixtures. Water heater set level. T & P terminated minimum 6 inches, maximum 24 inches above grade and pointing downward Single wall vent connectors to be a minimum of 6 inches from combustibles Combustion air requirements, in garage and attic Hot water heater seismic zone strapping shall be a minimum of two straps; one in the upper one-third and one in the bottom one-third and/or 4 inches above the controls. FINAL PLUMBING (4499) PAGE 2 of 2
11 GENERAL NOTES This checklist is intended for use as a GUIDE to assist and promote consistency in the application of the Mechanical Code and standard practices within Clark County. This list is for use of county inspectors and for the general public. This checklist is for wood frame and light commercial structures. The information in this checklist is not, nor was it ever intended to be, all-inclusive. It does not include all code or individual plan requirements. It is intended to reflect local policies, procedures and practices within Clark County. This checklist does not waive any specific code requirements not listed or allow for the decrease in the requirements of an engineered design. It also does not add requirements where the minimum of the code has been met. All approved plans, documents and revisions to plans must be maintained on site and available for review at all times the building is under construction. All plans and paperwork will be reviewed before performing any inspection. The owner, permit holder or responsible person, on the job site, is responsible for establishing safe access to perform all inspections. In the event that ladders are necessary to perform inspections, all ladders and equipment shall meet minimum OSHA standards. Inspectors are not responsible for setting up or moving ladders from one location to another, within or to other buildings or structures. Inspectors are not responsible for unscrewing /unbolting of items to verify information that is part of an inspection. COMMERCIAL MECHANICAL GENERAL NOTES PAGE 1 OF 1
12 COMMERCIAL ROUGH MECHANICAL (5551) B No rough inspections until approval of control diagram Verify all listed mechanical equipment and its locations per approved plan for model numbers, manufacturers installation instructions and BTU ratings /307.3 Verify HVAC equipment sizes, BTU ratings and location requirements per name plate listing Verify clearances and approved use (indoor/outdoor, vertical/ horizontal) Minimum size attic access openings 22 inches by 30 inches, or largest piece of equipment to remove Catwalk minimum 2 feet wide and maximum 20 feet long working platform and minimum clearances. 305/ Working platforms and minimum working clearance of 30x30x30 inches Electrical disconnect and lighting requirement Combustion air opening requirements Condensing line set insulated, supported and attachment to unit and exit through an exterior wall and sealed at supporting flashing Terminate primary condensate line to the exterior Terminate secondary condensate line to a visible location for quick detection Check manufacturers listing for size of pipe, use of traps or use of vents on condensate lines (minimum size ¾ inch). T3-2 UPC Condensate lines shall be properly supported (PVC every 4 feet horizontally). P If PVC piping is used for condensate lines, the piping shall have primer applied to all pipes and fittings before gluing Duct sizes, locations and UL-181 listings Check flex duct for support every 4 feet, mechanical bands and proper connections with UL-181B tape for flex ducts and 181A for metallic duct. B803.9 Supply registers supported on two opposite sides Return air return grills supported on all sides. E Proper insulation of ducts, wye branches, connections, fittings and metal plenums with minimum R-8 insulation or per Energy calculations. A Permanent ladder requirements and installed Verify smoke and fire dampers (horizontal or vertical applications) Verify access to smoke and fire dampers (if break away ducting is used, no need for an access panel in duct) Verify UL listing of factory made duct work or class 1 non metallic Identify all equipment on the roof with permanent signs as to what area the equipment serves. COMMERCIAL ROUGH MECHANICAL (5551) PAGE 1 OF 2
13 Vents COMMERCIAL ROUGH MECHANICAL (5551) T8.2 B-Vent supported with min 1 inch clearance to combustibles, with flow upward Horizontal run limited to 75% of vertical height Offsets limited to one not more than A802.6(1) Termination min 4 feet from property line, vertical walls Size of B-Vent per unit output. Environmental Air Duct Dryer Vents Kitchen Exhausts Bathroom Exhaust Fans Kitchen hood duct smooth interior. Plans/T6-7 Verify size, length and support of ducts Dryer exhaust 14 feet with 2-90 s rule. In excess of this rule, the duct sizes and length shall be engineered and plans check approved No screws in dryer vent connections. A Vent terminations to have back draft dampers Dryer vent requires a non-screened back draft damper. Back draft dampers are not required when terminating in the vertical position. T4-4 Verify means for natural ventilation for bath, water closets areas or provide exhaust 50 cfm fan. Manufactured Fireplaces/Decorative Fireplaces 907 All fireplaces and decorative fireplaces shall be installed per the manufacturers installation instructions, including mantles, clearances and venting (A) Standoffs not removed (no combustibles below stand-offs) Check combustion air per the appliance listing and Chapter 7. Listing Remove all loose material from fireplace chase (wood/paper/insulation) per its listing for distance to combustibles. COMMERCIAL ROUGH MECHANICAL (5551) PAGE 2 OF 2
14 COMMERCIAL ROUGH GREASE DUCT (5546) All welds to be smooth and liquid tight Access doors at 10 foot intervals horizontally and changes of direction Listing of specific wraps and terminations Duct supported separate from shaft enclosure. A Supports on the outside of the duct Listed enclosure Fire rated access doors, same gauge as duct, that require no tool for access. COMMERCIAL ROUGH GREASE DUCT (5546) PAGE 1 OF 1
15 COMMERCIAL TYPE I HOOD (5575) Hood installed per manufacturers details for support Air balance reports. a. Smaller installations use the air balance form and the installer fills out report. b. Larger installations use QAA, third party agencies or contracts for balance reports. c. Air balance report has to be completed before Fire Department will sign off. d. Check manufacturers instruction for balance requirements Hood to overhang equipment by 6 inches Distance between bottom of hood and cooking surface not to exceed 4 feet. Clearance of 3 inches between hood and combustible wall surface Verify grease drip tray Listed filters installed Exhaust outlets not to exceed 12 feet between Verify make-up air source Make-up air volume to equal exhaust volume Exhaust fan for type I hoods. a. Terminate 10 feet from property line or air intakes. b. Terminate 2 feet above roof. c. Drywall duct enclosure shaft to be vented above roof. Send report to Records. COMMERCIAL TYPE I HOOD (5575) PAGE 1 OF 1
16 DUCT DETECTOR TEST (5535) 1. Section and field guideline FIG-M Duct detectors 5 or less can be checked for shut down by the inspector, if time allows. 3. Duct detectors of 6 or more will be completed by a third party agency, report will be submitted before final will be approved. 4. Duct detectors will be tested for shut down purposes with either smoke or a magnet per its listing. 5. Measurement of air across the duct detector shall be per listing and installation instructions. 6. Instruments for measuring air flow shall be provided by the installer. 7. Tests shall be verified by the inspector or a third party testing agency pre-approved by Clark County. COMMERCIAL DUCT DETECTOR TEST (5535) PAGE 1 OF 1
17 COMMERCIAL FINAL MECHANICAL (5599) A Final Mechanical-QAA report is completed and approved in the computer. FIG- M-003 Copies of all duct detector testing is completed and approved in the computer. A513.9 Copies of all damper tests are completed, turned in and approved in the computer. T4-1 Outside air requirements are met Verify all registers and filters are installed. E All thermostats are installed meeting energy code requirements All roof top equipment is installed and identified All access openings are operable All smoke management requirements have been met and are on the Mechanical- QAA report approved in the computer Equipment in garages, with ignition sources, a minimum 18 inches above floor. B Duct penetration through garage membrane minimum of 26 gauge thickness with no openings into the garage area Equipment installed at grade level shall be supported on a level non-combustible platform a minimum of 3 inches above final grade Disconnect and over current protection within sight of each piece of equipment. AR1008 Decorative gas appliances shall be installed per their listing with logs, glass doors, ember strip. AR1008 Decorative appliance dampers shall be permanently blocked open. T8-2 Verify vent connectors for clearances and terminations with approved caps. Listing Verify exhaust terminations for screens and operation of dryer back draft damper as required for environmental air ducts Verify combustion air duct requirements and location Verify protection of equipment in garages by bumper guards, bollards, raised platform or outside the travel path of traffic. COMMERCIAL FINAL MECHANICAL (5599) PAGE 1 OF 1
Plumbing. Helpful Hints Residential Construction. Lincoln County. Bert Polk Plumbing Inspector
Plumbing Helpful Hints Residential Construction Bert Polk Plumbing Inspector Lincoln County 2015 Waste and vent fittings Vent 90 medium 90 long 90 1/16 bend,1/8 bend,1/6 bend, medium 90 san tee combination
2006 Codes. Please verify the following before calling for inspection
INSPECTION CHECKLIST RESIDENTIAL PLUMBING ROUGH IN 2006 Codes This checklist is intended for use to prepare for an inspection. This is only a general list and is not intended to address all possible conditions.
2010 Residential Water Heater Replacement Check List
2010 Residential Water Heater Replacement Check List The intent of this check list is to provide installers a general reference for the enforcement of code requirements in the Greater San Diego Area. This
Top 10+ Mistakes of DWV plumbing design
Top 10+ Mistakes of DWV plumbing design Listed below are the some of the most frequently missed items, noticed by our inspectors, at plumbing rough-in when non-plumbers attempt plumbing design. Most of
CONSTRUCTION CHECKLIST Residential Plumbing Rough-In September 2004
Bellevue Bothell Kenmore Kirkland Issaquah Mercer Island Sammamish Snoqualmie Woodinville CONSTRUCTION CHECKLIST Residential Plumbing Rough-In September 2004 This checklist is intended for use to prepare
INSPECTION CHECKLIST Residential Plumbing Rough In April 2011 Mercer Island Mill Creek Sammamish Snohomish County Snoqualmie Woodinville
Bellevue Bothell Burien Issaquah Kenmore Kirkland INSPECTION CHECKLIST Residential Plumbing Rough In April 2011 Mercer Island Mill Creek Sammamish Snohomish County Snoqualmie Woodinville 2009 Codes This
Plumbing Installations A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling
PLANNING, PROPERTY AND DEVELOPMENT DEPARTMENT Plumbing Installations A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling October 2014 contents General Information
Arapahoe County Residential Water Heater Installation and Inspection Guide
Arapahoe County Residential Water Heater Installation and Inspection Guide The attached handout is designed to be a general permit submittal and inspection guide covering most installation instances, however
Plumbing Installations. A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling
Plumbing Installations A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling February 2001 contents General Information 3 Inspection 4 New Drain and Vent Installations
Subpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715,
4658.4500 PLUMBING SYSTEMS; NEW CONSTRUCTION. Subpart 1. Installation. All plumbing systems must be installed and tested according to this chapter and chapter 4715, the Minnesota Plumbing Code. Subp. 2.
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression
PLUMBING ROUGH IN INSPECTION
This Program is made Possible through the Code Officials Education & Training Fund. Revenue for the Fund comes from Assessments on Building Permits. Please turn down cell phones and put pagers on vibrate.
What to Expect From the Examination. How to Study the Plumbing Codes
Texas State Board of Plumbing Examiners Plumbing Inspector Examination Review Course The following Examination Review Course is designed to assist an applicant in preparing for the Plumbing Inspector examination.
GROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL 34471 (352) 629-8421; FAX: (352) 629-8264
BUILDING CODE GUIDELINE FOR MECHANICAL INSPECTIONS Building Code compliance is the obligation of design professionals and/or contractors. Plan Review and Inspection Guidelines are intended to be used by
CHAPTER 9 VENTS. copper drainage tube Type DWV, Schedule 40 plastic piping, or borosilicate glass.
CHAPTER 9 VENTS 901 GENERAL 901.1 Scope The provisions of this chapter shall govern the materials, design, construction, and installation of vents. 901.2 Protection of Trap Seals The protection of trap
BUILDING DEPARTMENT 8748 W. 82 nd Place - Justice, IL 60458 Phone: (708) 458-2130 Fax: (708) 458-3207
BUILDING DEPARTMENT 8748 W. 82 nd Place - Justice, IL 60458 Phone: (708) 458-2130 Fax: (708) 458-3207 SELF EVALUATION CHECKLIST FOR RESIDENTIAL AND MULTI-FAMILY DWELLING INSPECTIONS The attached checklist
When Should Examination Preparation Begin?
Texas State Board of Plumbing Examiners Tradesman Plumber-Limited Licensee Examination Review Course The following Examination Review Course is designed to assist a registered Plumber s Apprentice in preparing
HV AC CODE CHECKLISTS
The following text is informational only and shall serve as an informational guide for HV AC contractors, journeymen, and apprentices working in the Heating, Ventilation, and Air Conditioning industry.
www.citiesinspection.com October 5, 2015 Dear Client,
www.citiesinspection.com October 5, 2015 Dear Client, On 9/14/2015, Cities Inspection Service, Inc. completed a building inspection of the property located at 123 Oak Street, Someplace, Minnesota for you.
The purpose of this document is to provide standards for persons requesting or subject to County building inspections.
STANDARD OPERATING PROCEDURE BUILDING & SITE DEVELOPMENT Number: 310.1 Approval: Yves Khawam Effective Date: December 27, 2006 Subject: Requirements for County building inspections Page 1 of 7 1.0 PURPOSE:
City of St. Charles Basement Finish or Remodel
City of St. Charles Basement Finish or Remodel Building & Code Enforcement Division 2 East Main Street St. Charles IL 60174 630.377.4406 (Office) 630.443.4638 (Fax) http://www.stcharlesil.gov Please direct
PMA ONLINE TRAINING Venting for Plumbing Systems
PMA ONLINE TRAINING Venting for Plumbing Systems One Hour Continuing Education Venting PMA training disclaimer The information provided in this document is intended for use as a guideline and is not intended
CHAPTER 5 WATER HEATERS
PlumbingCode06_ch05 5/29/06 8:12 AM Page 1 CHAPTER 5 WATER HEATERS Water heaters are only a small portion of a plumbing system, but they are important, and they can be dangerous. Many plumbers take water
Element D Services Plumbing
PART 1 - GENERAL 1.01 OVERVIEW A. This section addresses domestic cold, hot and hot water return distribution systems within and to five feet beyond building perimeter. PART 2 - DESIGN CRITERIA 2.01 GENERAL
CITY OF SELMA, TEXAS Inspection Checklist: Commercial
Rev Y71004 The Permits and Inspections Department welcomes you to the City of Selma. The following information is provided to you as guidance through the inspection process. The City of Selma provides
All work shall comply with applicable codes and ordinances. Work shall comply with the BOCA National Plumbing Code, latest edition.
DIVISION 15 MECHANICAL SECTION 15100 - PLUMBING PART 1 - GENERAL SCOPE Plumbing work includes all domestic water, gas, and sanitary sewer systems as shown on plans. Also all fixtures and equipment which
Chapter 7 Plumbing Connections
Chapter 7 Plumbing Connections 7-1 General All plumbing equipment and installations must be designed, constructed, and installed in accordance with this code and where not specific, to the applicable provisions
Land Use and Environmental Service Agency (Code Enforcement) NC Plumbing Code. Table of Contents
Chapter 1 Administration Chapter 3 General Regulations Chapter 5 Water Heaters Chapter 7 Sanitary Drainage Chapter 9 Vents Chapter 11 Storm Drainage Policy Statements Table of Contents Chapter 2 Definitions
Uniform Construction Code (UCC) Building Permit Application Package
Uniform Construction Code (UCC) Residential Building Permit Application Package Per the Uniform Construction Code (UCC) all structures must be built per the standards of the most currently adopted International
This handout is a guide only and does not contain all of the requirements of the Minnesota State Building Code or city ordinances.
Basement Finishing Guide Community Development Department Building Inspections Division 5200 85 th Avenue North / Brooklyn Park, MN 55443 Phone: (763) 488-6379 / Fax: (763) 493-8171 6/15 www.brooklynpark.org
EFFECTIVE FEBRUARY 2014. note: drainage permit required to call for a dampproof inspection
EFFECTIVE FEBRUARY 2014 note: drainage permit required to call for a dampproof inspection 1. ROOF DRAINS/DECK DRAINS (INTERIOR ) All roof and deck drains within the perimeter of the building shall be APPROVED
GROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL 34471 (352) 629-8421; FAX: (352) 629-8264
BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS Building Code compliance is the obligation of design professionals and/or contractors. Plan Review and Inspection Guidelines are intended to be used
Home Inspection Report
4949 Brownsboro Rd Suite 293 Louisville, KY 40223 (502) 414-1440 [email protected] Inspected By: William Carter, HI-1956 Home Inspection Report Prepared For: Edward Cullen Property Address:
Pre-Drywall Inspection Report
SM MEDALLION INSPECTIONS helping people make informed decisions Pre-Drywall Inspection Report 5657 Garden Valley Place Milton, Georgia 30024 Prepared for Betsy and Paul Dougherty January12, 2015 Medallion
KITCHEN AND BATH REMODELING BUILDING PERMIT REQUIREMENTS
St. Louis County Department of Public Works Division of Code Enforcement KITCHEN AND BATH REMODELING BUILDING PERMIT REQUIREMENTS This guideline is intended to provide the homeowner/contractor with the
WELCOME INTERNATIONAL RESIDENTIAL CODE 2009 EDITION PLUMBING SECTION
WELCOME INTERNATIONAL RESIDENTIAL CODE 2009 EDITION PLUMBING SECTION 1 HOUSEKEEPING 2 CHANGES We will be covering the significant changes to the International Residential Code and the changes common to
Propery Inspection Report
Propery Inspection Report Cover Page,, Ok Inspection prepared for: Date of Inspection: 9/28/2014 Time: 8:30 AM Age of Home: 2011 MOL Weather: Clear 62 degrees Inspector: License #130 5400 Hwy 177, Marland,
PLUMBING. For HOME OWNERS
PLUMBIG For HOM OR If your property is located in the ational cenic rea, the Columbia River Gorge IRODUCIO Commission requires you to comply with all ational cenic rea regulations. hey can be contacted
PLAN REVIEW SERVICES CONSTRUCTION DOCUMENTS NECESSARY FOR A THOROUGH PLAN REVIEW
CONSTRUCTION DOCUMENTS NECESSARY FOR A THOROUGH PLAN REVIEW PRELIMINARY BUILDING REVIEW two sets of the following: Architectural/engineering design development drawings indicating size of the building,
BUILDING PERMIT SPECIFICATIONS
BUILDING PERMIT SPECIFICATIONS The below noted requirements are based upon La Plata County Building Code. These specifications are not intended as a complete set of requirements, but are intended to provide
Inspection Item COMMENTS
APPENDIX 9 AFFORDABLE HOUSING PROGRAM INSPECTION CHECKLIST Participating Jurisdiction: Homeowner Name: Assisted Property Address: Date of Physical Inspection of Property: Total Square Footage of Property:
Plumbing Code in Commercial Kitchens. NH BOA May 9, 2012
Plumbing Code in Commercial Kitchens NH BOA May 9, 2012 Main Topics Grease Interceptors Indirect Waste Receptors Cleaning Chemical Dispensers Thermal Expansion IPC - Chapter 10 Traps Interceptors Separators
HVAC Code Requirements
one and two family dwellings? Answer: SECTION 2001: GENERAL 2001.1 Air supply. Fuel-burning equipment shall be provided with a supply of air for fuel combustion, draft hood dilution and ventilation of
Town House 11265 Center Highway North Huntingdon, PA 15642
APPENDIX C SPECIFICATIONS FOR THE CONSTRUCTION OF BUILDING LATERAL SANITARY SEWERS DECEMBER 2004, INCLUDING AMENDMENTS ADOPTED ON FEBRUARY 6, 2008 AND APRIL 2, 2008; EFFECTIVE ON MAY 1, 2008 Town House
Orlando Home Inspection Services
PLEASE NOTE: Orlando Home Inspection Services Serving Central Florida since 1999 P O Box 915451, Longwood, Florida, 32791-5451 Phone: (321) 228-2493 Fax: (407) 374-8505 Web: http://www.orlando-home-inspections.com
City of Elk River BASEMENT Office Use Only
City of Elk River BASEMENT Office Use Only Fire and Building Safety Division (FABS) Building Permit Application Notes Scan Permit Total Date Permit # PID # $ Site Address Suite/Unit Structure Type Single
2. What building projects are exempted? (permit not required)
BUILDING AND SAFETY DEPARTMENT 1. What building projects require a permit? Following is a list of projects that require building permits based on Appendix chapter 1 of the California Building Code and
Does Wall Township require an inspection by the building department on resale of a home?
Selling your home Does Wall Township require an inspection by the building department on resale of a home? No. We do not require a Certificate of Continued Occupancy on the resale of home. A Smoke Detector,
#506 New Multi-Family Buildings & Additions Plan Intake Submittal Checklist
#506 New Multi-Family Buildings & Additions Plan Intake Submittal Checklist Case #: Date: Project Name: Site Address: Application Submittal Building permit applications and plans can be submitted to the
BASEMENT FINISH PERMIT AND BUILDING CODE REQUIREMENTS (REVISED 3/20/2009)
BASEMENT FINISH PERMIT AND BUILDING CODE REQUIREMENTS (REVISED 3/20/2009) PERMIT SUBMITAL CHECKLIST: Signed and completed Building Permit application form. 2 Copies of plans showing proposed layout and
PDmB, Inc. Definitions
Page 1 of 11 Definitions S Satisfactory Meets industry standards for proper material and installation NP Not Present Condition or item was not present at time of inspection NI Not Inspected Condition or
BUILDING SAFETY UNIT
POLICY Page 1 of 5 SUBMITTAL REQUIREMENTS FOR ONE AND TWO FAMILY DWELLINGS, ADDITIONS AND RENOVATIONS All submittals shall be site specific and designed to the provisions of the 2012 International Residential
CITY OF LOS ANGELES 2011 PLUMBING/MECHANICAL PLAN CHECK LIST
CITY OF LOS ANGELES 2011 PLUMBING/MECHANICAL PLAN CHECK LIST Plan Check No. Plan Check Expiration Date Job Address: Square Footage Use Zone Fire Zone Occ. Group Type of Construction No. of Stories Applicant
Home Maintenance Checklist
Regular maintenance keeps your home functioning efficiently and safely and helps protect its value. We're happy to offer this checklist of ongoing and seasonal maintenance steps to help you safeguard your
4 Installation Requirements
4 Installation Requirements 9 4.1 Code Reference The authority having jurisdiction should be referenced to determine what law, ordinance or code shall apply in the use of flexible duct. Ducts conforming
Amendments to the 2012 International Plumbing Code
Amendments to the 2012 International Plumbing Code North Central Texas Council of Governments region The following sections, paragraphs, and sentences of the 2012 International Plumbing Code are hereby
ONE AND TWO FAMILY DWELLINGS Plumbing July, 2007
ONE AND TWO FAMILY DWELLINGS Plumbing July, 2007 The following are general requirements pertaining to plumbing in one and two family dwellings. This does not represent all the provisions regulating plumbing
Report for. Dick and Jane Homeowner. 1234 Lovers Lane, Houston, Texas 77000
Report for Dick and Jane Homeowner 1234 Lovers Lane, Houston, Texas 77000 March 17, 2004 I NI NP R Inspection Item I. STRUCTURAL SYSTEMS o o o A. Foundations (If all crawl space areas are not inspected,
DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION 15430 PLUMBING SPECIALTIES
PART 0 DESIGN STANDARDS 0.01 GENERAL DESIGN GUIDELINES A. Roof drains 1. Coordinate location and depth of drains to assure adequate pitch of the drainage area to drain. 2. Overflow system shall be piped
Development Services City of Lawrence, KS
Development Services City of Lawrence, KS Building Planning Table R301.2 (1) Climatic & Geographic Design Criteria Building Planning The design criteria for wind speed increased from 90 MPH to 115 MPH.
2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property
2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property A brief summary of the most used code references for residential wiring State of Idaho Division of Building Safety Electrical
COMPREHENSIVE PROPERTY INSPECTIONS
COMPREHENSIVE PROPERTY INSPECTIONS Thank you for selecting CPI for your Deficiency Observation. A full home inspection was not performed on this property at the buyers request. This inspection is a limited
Mobile Home Pre-Inspection Checklist
Mobile Home Pre-Inspection Checklist TWO (2) STEP INSPECTION PROCESS STEP ONE: CALL FOR THE FIRST INSPECTION WHEN THESE ITEMS ARE COMPLETE. 1. Septic tank installed and plumbing complete. (SEE PLUMBING
How To Make A House Safe
1 RESIDENTIAL Screen Enclosures Orange County Residential Code Compliance Alternative design method for screen enclosures R301.2.1.1.3 PLAN REVIEW Engineered plans must state that the Alternative Design
CROWN BOILER COMPANY BWF SERIES BOILER CATEGORY I VENT KIT INSTALLATION AND OPERATING INSTRUCTIONS
CROWN BOILER COMPANY BWF SERIES BOILER CATEGORY I VENT KIT INSTALLATION AND OPERATING INSTRUCTIONS WARNING Improper installation, adjustment, alteration, service, or maintenance of this product can cause
Building Permit Application
Building Permit Application Administrative Use Only PARENT PERMIT NUMBER (Required if part of another project) PERMITTEE: PERMITTEE ADDRESS: E-MAIL ADDRESS: ARCHITECT/ENGINEER: PHONE: PHONE: ARCHITECT/ENGINEER
Total Home Inspection Checklist
Total Home Inspection Checklist Use a checklist like this to make sure that you are looking at all parts of the house. Check off those items that are in good condition and make notes about those that are
Excerpts from the Canadian National Building Code (NBC)
Excerpts from the Canadian National Building Code (NBC) Reproduced here with Permission of the Copyright Owner, the National Research Council of Canada, Institute for Research in Construction. For more
SWF Home Inspections
Cover Page SWF Home Inspections Property Inspection Report Inspection prepared for: Mr & Mrs Home Buyer Real Estate Agent: My Favorite Agent - Date of Inspection: 7/4/2013 Age of Home: 2004 Size: 1568
HomeSpec REPORT SUMMARY
HomeSpec 04/25/2007 Ms. Rachel Trujeque Re: 13038 West Plum Road Lot #1225 - Peoria, AZ. 85383 - Pre Drywall Inspection Dear Ms. Trujeque, At your request, a visual pre drywall inspection of the above
8 plumbing. plumbing. 2010 PulteGroup, Inc. All Rights Reserved.
8 90 2010 PulteGroup, Inc. All Rights Reserved. drains All the water you use leaves the home through a drain. Maintaining drains prevents clogging, overflows, water damage, and other problems. care and
C I T Y O F S E L M A F I R E D E P A R T M E N T
C I T Y O F S E L M A F I R E D E P A R T M E N T Informational Bulletin Regarding Residential Fire Sprinkler Systems for One and Two Family Homes: Frequently Asked Questions ADMINISTRATIVE PROVISIONS:
HVAC INSTALLATION SUCCESS WITH 2012 IECC DELAWARE. for Builders & Trades. Recommended Practices for Optimized Energy Savings
SUCCESS WITH 2012 IECC DELAWARE Recommended Practices for Optimized Energy Savings for Builders & Trades COPYRIGHT 2015 ADVANCED ENERGY. ALL RIGHTS RESERVED VERSION 2015.1.0 CHECKLIST: JOB READY 1. 2.
COMMERCIAL PLAN SUBMISSION FOR NEW CONSTRUCTION AND/OR RENOVATIONS
COMMERCIAL PLAN SUBMISSION FOR NEW CONSTRUCTION AND/OR RENOVATIONS Permit applicants shall submit three (3) COMPLETE SETS of plans and specifications with each application for a permit. Plans and specifications
NAVIEN AMERICA INC. 17855 FITCH AVENUE
Navien America Inc. Specification Details for the Navien models: CC-240 CC-240A For Potable Water Heating and Space Heating NAVIEN AMERICA INC. 17855 FITCH AVENUE IRVINE, CALIFORNIA, USA 92614 Toll Free:
CITY OF FAIRFAX CODE ADMINISTRATION 703-385-7830 / FAX 703-385-9265 www.fairfaxva.gov
CITY OF FAIRFAX CODE ADMINISTRATION 703-385-7830 / FAX 703-385-9265 www.fairfaxva.gov Finishing a basement to make additional living space in a house is a popular construction project for many homeowners.
DRYER VENTING SPECIFICATIONS DRYER SAFETY
DRYER VENTING SPECIFICATIONS Table of Contents DRYER SAFETY...1 INSTALLATION REQUIREMENTS...4 Venting Requirements...5 DRYER INSPECTION AND CLEANING...7 Frequency of Exhaust System Cleaning...7 Inspecting
Inspecting to a higher standard.
Inspecting to a higher standard. Rob Hopkin Silver Spring, MD 20902 Monday, June 2, 2014 ProTec Inspection Services Inc. 19736 Selby Ave Poolesville, MD 20837 301-972-8531 www.protec-inspections.com [email protected]
Inspection Tech. (330) 310-6559 http://www.inspectiontech.us [email protected] Inspected By: Aaron Westerburg
Inspection Tech (330) 310-6559 http://www.inspectiontech.us [email protected] Inspected By: Aaron Westerburg Inspection Tech Home Inspection Report Prepared For: Mr. & Mrs. Homebuyer Property
CHAPTER 10 TRAPS, CLEAN-OUTS, AND INTERCEPTORS
PlumbingCode06_ch10 5/29/06 8:16 AM Page 1 CHAPTER 10 TRAPS, CLEAN-OUTS, AND INTERCEPTORS We have covered most of the regulations you will need to know about drains and vents. This chapter will round out
Home Energy Evaluation Report for Fritz Kreiss and Catherine McQueen
Home Energy Evaluation Report for Fritz Kreiss and Catherine McQueen May 2008 Wisconsin Area PO BOX 115 Lake Geneva, WI 53147 CELL (414) 550-4765 Home Performance with ENERGY STAR Evaluation Report Customer
Name Of Occupancy Date. Yes No Describe
FIRE PREVENTION INSPECTION CHECKLIST For Class A Occupancy (For Assembly Buildings, Bars, Restaurants, Gyms, Churches, Arenas, Theatres or wherever people gather) Name Of Occupancy Date Physical Address
CHAPTER 9 VENTS TRANSPORTATION OF SEWER GAS
PlumbingCode06_ch09 5/29/06 8:16 AM Page 1 CHAPTER 9 VENTS Most people don t think much about vents when they consider the plumbing in their home or office, but vents play a vital role in the scheme of
PART 6: VENTING, COMBUSTION AIR & CONDENSATE REMOVAL
PART 6: VENTING, COMBUSTION AIR & CONDENSATE REMOVAL Boiler Manual A. INSTALLING EXHAUST VENT AND INTAKE AIR VENT B. GENERAL n DANGER The Elite Heating Boiler must be vented as detailed in this section.
city of edmonds development information
#B17 city of edmonds development information Commercial Kitchen Hood & Hood Fire Suppression System Permit Submittal Requirements PERMIT REQUIRED: CODES: FEES: A Commercial Kitchen Hood Mechanical Permit
GUIDELINES FOR WIRING SINGLE FAMILY DWELLING UNITS
GUIDELINES FOR WIRING SINGLE FAMILY DWELLING UNITS This guideline has been prepared to assist the owner/occupant of a single family dwelling with compliance to the requirements of the National Electrical
Understanding and Designing Plumbing Systems
Lesson A3 15 Understanding and Designing Plumbing Systems Unit A. Mechanical Systems and Technology Problem Area 3. Construction Systems Lesson 15. Understanding and Designing Plumbing Systems New Mexico
ESTIMATING PLUMBING, HEATING, VENTILATING, AND AIR CONDITIONING (HVAC), AND ELECTRICAL WORK
C H A P T E R 7 ESTIMATING PLUMBING, HEATING, VENTILATING, AND AIR CONDITIONING (HVAC), AND ELECTRICAL WORK OBJECTIVES After reading this chapter and completing the review questions, you should be able
UB1 AIR CONDITIONING UNIT INSTALLATION INSTRUCTIONS
UB1 AIR CONDITIONING UNIT INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS: Carefully read these instructions before installing your new air-conditioner. AUSTRALIAN AUTOMOTIVE AIR AL00500054E 1 Table
DESIGN CHECKLIST PROJECT NAME DISCIPLINE DATE TYPE REVIEW REVIEWER DRAWINGS REVIEWED
DESIGN CHECKLIST PROJECT NAME DISCIPLINE DATETYPE REVIEW_ REVIEWER DRAWINGS REVIEWED EVERY ITEM WILL BE REVIEWED AND NOTED FOR COMPLIANCE (C), OR NON- APPLICABILITY (NA). A. GENERAL SECTION 7 PLUMBING
SECTION 5 - COMMERCIAL CONSTRUCTION MECHANICAL, ELECTRICAL, PLUMBING AND SOLAR OTHER TECHNICAL CODES
SECTION 5 - COMMERCIAL CONSTRUCTION MECHANICAL, ELECTRICAL, PLUMBING AND SOLAR OTHER TECHNICAL CODES 5.1.0 GENERAL Section five reviews consolidates the various local amendments technical code information
HVAC INSTALLATION. Success with 2015 IECC Northeast & Mid-Atlantic. Checklist for Builders & Trades
Success with 2015 IECC Northeast & Mid-Atlantic Checklist for Builders & Trades COPYRIGHT 2015 ADVANCED ENERGY. ALL RIGHTS RESERVED TEMPLATE 2015.1.0 PAGE 1 CHECKLIST: JOB READY 1. 2. 3. 4. 5. 6. 7. 8.
Building Condition Assessment Report
C2 - Nurses Resident (aka Administration) Building Condition Assessment Report Asset Address Address Construction Year Size (Gross Floor Area) Asset Type Floors Above Ground Inspection Date C2 - Nurses
Inspection Report. Dream Home Inspections. www.timinspects.com. 415 Second Ave. Frisco CO 80443-1789 (970) 368-2668
Inspection Report Property Address: 123 Dream Home Way Frisco, CO 80443 Prepared for: Inspector: Tim Nixon Tim Nixon Inspection date: 3/28/2014 1 of 9 General Information Property Information Address:
SECTION 221413 FACILITY STORM DRAINAGE PIPING
SECTION 221413 FACILITY STORM DRAINAGE PIPING PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01
2014 British Columbia Building Code Changes
District of Houston 250-845-2238 2014 British Columbia Building Code Changes A District of Houston interpretation of the 2014 Building Code Changes for 9.36 & 9.32 The following changes reflect the most
PLAN CHECK CORRECTION SHEET FOR PLUMBING SYSTEMS 2014 LAPC
PLAN CHECK CORRECTION SHEET FOR PLUMBING SYSTEMS 2014 LAPC This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly. Section:
BPC Green Builders. Green building for new and existing homes. Health Comfort Energy
BPC Green Builders Green building for new and existing homes Health Comfort Energy Mechanical Systems Installed HVAC Systems Primary energy source large, roof mounted, solar thermal array (AET flat plate)