Liebert DM Series Air Conditioner Technical Manual. Precision Cooling For Business-Critical Continuity
|
|
|
- Matthew Parks
- 10 years ago
- Views:
Transcription
1 Liebert DM Series Air Conditioner Technical Manual Precision Cooling For Business-Critical Continuity
2 Liebert_DM Series Air Conditioner Technical Manual Version V.0 Revision date BOM Emerson Network Power provides customers with technical support. Users may contact the nearest Emerson local sales office or service center and company headquarters. Copyright 0 by Emerson Network Power Co., Ltd. All rights reserved. The contents in this document are subject to change without notice. Emerson Network Power Co., Ltd. Address: No. Kefa Rd., Science & Industry Park, Nanshan District 58057, Shenzhen China Postcode: Customer Service Hotline: Homepage: [email protected]
3
4 Contents Chapter Preface.... Special Requirements On The Equipment Room Environment.... Liebert_DM Series AC Designed For Equipment Room... Chapter Overview Appearance Model Description Product Introduction Main Components Indoor Unit Outdoor Unit Options Humidifier Heater Remote Monitor Energy-Saving Card Power SPD... 5 Chapter 3 Technical Parameter Technical Parameter Of The Indoor Unit Technical Parameter Of The Outdoor Unit Mechanical Parameter Indoor Unit Outdoor Unit Operation Environment... 9 Chapter 4 Application Guidline General Arrangement General Principles Piping Model Configuration Cooling Circulation... Chapter 5 Micro-Processing controller Appearance LCD Screen Control Buttons Function Description Operation Example Control Screen ON Screen Normal Screen Password Screen Control Logic... 5
5 5.5. Cooling logic Heating Logic Dehumidifying Logic Humidifying Logic Outdoor Fan Control Economy Mode Control Sleep Mode Control Host/Standby Unit Control Alarm Function Alarm Category Alarm State And History Alarm Prerequisites And Handling Methods Other Functions Real-Time Clock Operating Record Parameter Protection Password Protection Shutdown Mode Diagnosis Output Sensor Calibration Deployment Management... 4 Appendix Menu Structure... 5 Appendix Wiring Diagram... 6 Appendix 3 Glossary... 8
6 Chapter Preface Chapter Preface This chapter mainly introduces the special requirements on the equipment room environment and the features and advantages of Liebert_DM series air conditioners (AC for short).. Special Requirements For The Equipment Room Environment The precise environment control is very important for the operation of the computers, therefore, the computers have strict requirements for the equipment room environment, which cannot be achieved by the commercial air conditioners designed for comfort. The relevant requirements mainly include the following four aspects. Temperature control: Huge amount of sensible heat is generated when computers and exchanges are operating in the equipment room, whose density is 6 to 0 times of that of the general offices. To ensure that the computers and the devices exert their optimal effect, the temperature of the equipment room is best controlled within 4 C± C; This requires that the AC units have sufficient cooling capacity and timely response regulatory capacity to cope with drastic changes in temperature, which cannot be implemented by the commercial air conditioners. Humidity control: In computer room, ultra-high or ultra-low humidity will damage the computers. The ultra-high humidity makes the air moisture condense to form condensation water in the computers, resulting in short-circuit or damage of the host hardware. The ultra-low humidity will make the static electricity generate in the computer room, making the computers unable to operate or even crash. The commercial air conditioners cannot control the humidity within the required range. Airflow / cleanliness control: Computers and exchanges will produce huge sensible heat during the operation. To eliminate the heat rapidly, The ACs are required to have large enough large cooling cycle airflow and long blowing distance. Besides, because of the strict requirement of air cleanliness, the AC should provide an airflow equivalent to the ventilating rate of 30 times per hour, so as to filter the air. The commercial ACs cannot achieve these. All-year-round running: The commercial ACs (cooling operation) are only used in summer and they only run for 8 ~ 0 hours each day. In the equipment room, however, the ACs are required to work all year round even in winter when the temperature reached -34 C outdoors.. Liebert_DM Series AC Designed For Equipment Room The Liebert_DM series AC includes units with a cooling capacity of 7.5kW and.5kw. You can configure them freely to meet different requirements of large-, medium-, and small-sized equipment rooms and base stations. Besides, the AC has precise temperature/ humidity control and reliability design, fully meeting the special use environment requirement of the equipment rooms. Special development: As a part of the integration solution to equipment room, the Liebert_DM series ACs are specially designed for the electrical devices and provides a proper environment for the running of the precise devices, such as sensitive devices, industry process devices, communication devices and computers. Considerate design: Being concerned about inter-device practical applications, the Liebert_DM series ACs are designed to keep the overall layout between devices and ensure onsite installation and maintenance. Saving space: The Liebert_DM series AC occupies 0.3 m and a total of m area is required plus the maintenance space. Precise control: The precise control system of the Liebert_DM series ACs implement precision control over indoor environment, guaranteeing the safe working and stable running of devices to a maximum degree. For the indoor unit control panel, see Figure -.
7 Chapter Preface J3 Board power supply input J34 Temp/Hum detection board J3 Pressure sensor J4 Monitoring J Display board power supply ON J39 Display board data line J8 SCR output to contactor J Switch input, such as high pressure switch J3 DI input power supply J8 Output, such as J9 Remote switch electric heater output Figure - Control board of the indoor unit Outstanding man-machine interface: The Liebert_DM series ACs provide a large Chinese/English LCD, a user-friendly man-machine interface and an expert diagnosis system, as well as implement multi-level password protection (avoid misoperation) and intelligent display of running states. High reliability: Relying on the excellent quality and considerate services of Emerson, the Liebert_DM series ACs ensure 4-hour reliable running all year round. Strong adaptability to power grid: The Liebert_DM series ACs allow a wide range of voltage and provide the following distinctive functions: unique phase loss protection, phase-sequence detection and protection, automatic high-voltage & low-voltage detection and protection, self-recovery upon power failure. All-weather operation: According to the distinct heating load feature of equipment rooms, the Liebert_DM series ACs implement 4-hour running all year round in temperature ranging from -5 C to +45 C. If a Lee-Temp outdoor unit is configured, the allowed running temperature ranges from -34 C to +45 C. Strong network management: Being configured with a standard RS485 monitor interface, the Liebert_DM series ACs implement flexible automatic switchover between active and standby devices, work shift, remote turn-off and turn-on, remote alarm, and fault query and troubleshooting over standard telecommunication protocols. Easy maintenance: The Liebert_DM series ACs provide a full front maintenance structure, facilitating maintenance. Table - describes the differences between the Liebert_DM series ACs and commercial ACs. Table - Differences between the Liebert_DM series ACs and commercial ACs Design focus Precision Temperature control Monitoring All-rear-round continually operating Testing before delivery Control design Cleanliness Liebert_DM series AC ± C; ±%RH Humidifying and dehumidifying control Local and romote monitoring All-year-around cooling Strict requirement Precise control High Commercial AC Generally ±3 C None in general None No cooling needed in winter Simple testing CPU Low
8 Chapter Overview 3 Chapter Overview This chapter expounds the appearance, model description, product introduction, components and variety of accessory options.. Appearance Taking the indoor unit of the Liebert_DM series air conditioner as an example, the appearance as shown in Figure -.. Model Description Figure - Indoor unit of the air conditioner The model description of the air conditioner is shown in Figure -. DM E 07 M C T : Standard; : High efficiency Version code C: cooling only; O: with heater; H : with heater and humidifier Input power supply. M : 380V-3-ph-50Hz Cooling capacity. 07 : 7.5kW ; :.5kW E : indoor unit; C : outdoor unit; L : Lee-Temp outdoor unit Liebert_D series air conditioner Figure - Model description.3 Product Introduction The Liebert_DM AC is a small precise environment control system, specially designed for cooling the electrical devices. It is applicable to environment control in equipement room and computer room. Featuring high reliability, it can maintain a favorable environment for precise devices such as sensitive devices, industry process devices, communication devices and computers. The cooling kit is provided as standard and it can precisely control the ambient temperature. The heater and humidifier are provided as options and they can precisely control the ambient humidity. If the AC unit is only available for cooling, the options are not needed.
9 4 Chapter Overview The Liebert_DM AC provides a micro-processing controller that can automatically switch over to the required function (cooling or heating, dehumidifying or humidifying), based on the programmed setpoints and room ambient conditions. Each Liebert_DM AC consists of an indoor unit and an outdoor unit. Both units are installed on the floor separately. Indoor unit The Liebert_DM AC includes units with a cooling capacity of 7.5kW and.5kw, which are applicable to power supply of 380V, 3-ph. You can select them according to the actual equipment room conditions. Outdoor unit The outdoor unit adopts air cooled mode. It is classified into two models: standard model and Lee-Temp model. The Lee-Temp model can be used at lower temperature (see Table -) than the standard model..4 Main Components.4. Indoor Unit The indoor unit consists of evaporator, compressor, fan, micro-processing controller, thermal expansion valve, strainer, filter, heater (optional), humidifier (optional) and surge protective devices (SPD, optional). For option introduction, refer to.5 Options. Evaporator Adopt a fin-tube heat exchanger with high efficiency. The distributor is designed and verified according to individual model to ensure that the refrigerant is distributed evenly in each loop, improving the efficiency of the heat exchanger to a great extent. Compressor Adopt a compressor with high efficiency ratio. It features low vibration, low noise and high reliability. Fan Adopt a centrifugal fan with high efficiency and high reliability. It features large airflow, long blowing distance, direct driving and easy maintenance. Micro-processing controller Provide a simple-operation user interface with multi-level password protection, self-recovery upon power failure, high-voltage & low-voltage protection, phase loss protection, automatic phase-sequence switching upon anti-phase and rotate speed control of the outdoor fan. The expert-level fault diagnose system can automatically display current fault information to facilitate equipment maintenance by maintenance personnel. Thermal expansion valve Adopt a thermal expansion valve with external equalizer type. It collects temperature and pressure signals at the same time to accurately regulate the refrigerant flow. Strainer Filtrate the impurities generated during long-term system operation and ensure normal system operation. Filter Adopt nylon filter material with big mesh for Liebert_DM AC. The filter features compact structure and easy maintenance. It can be washed repeatedly..4. Outdoor Unit The outdoor unit consists of fan and condenser. Other than the above components, the Lee-Temp model also includes a low-temperature unit. Fan Adopt axial flow blades with low noise. The single-phase motor with high performance is customized based on the power grid of base stations, so it can work over a wide voltage range with high reliability.
10 Chapter Overview 5 Condenser Adopt a fin-tube heat exchanger with high heat dissipation and wavy fins. It is free of dust accumulation, and can be easily cleaned and maintained. Low-temperature unit Make the AC unit operate in cooling mode normally at the lowest outdoor temperature of -34 C..5 Options.5. Humidifier The humidifier can add pure water vapor (up to.5kg/hour) into the room to control the indoor humidity within ranges required by devices and computer. The humidifier consists of a steam canister with automatic flushing control function, inlet tube, drain tube, solenoid valve and steam distributor. Note. The electrode humidifier should be installed and tested in factory.. The Liebert_DM AC can control the ambient humidity only after a humidifier is installed..5. Heater A ceramic heater with positive temperature coefficient can be selected. It is safe and reliable. When the surface temperature is too high, it will reduce the heating power to avoid danger caused by over-temperature. A temperature switch is provided on the surface of the heater, and it will cut off the power of the heater when the surface temperature is too high. When the surface temperature decreases to normal, the temperature switch will restore the operation of the heater automatically..5.3 Remote Monitor The Liebert_DM AC communicates with the host computer through a configured RS485 port and receives the control of the host software. You can also select and configure a monitoring card to realize different monitoring functions. For the descriptions of the host monitoring software SiteMonitor developed by Emerson, refer to Appendix 3 SiteMonitor Software Introduction..5.4 Energy-Saving Card The Liebert_DM AC can monitor the maximum room temperature with the energy-saving card located outside the unit cabinet. The card is placed in position with high heat load and temperature. Up to four cards can be used for an AC unit. When the temperatures measured by all energy-saving cards are lower than the setpoint in Sleep Mod and only indoor fan is running, if the Sleep Mod is set to ENAB, the AC unit will turn off the indoor fan and enter the sleep mode for saving the energy..5.5 Power SPD The power SPD is used for second level (C level) lightning over-voltage protection of the AC power. It can be maintained easily and provides status indicating and alarm function. Note The power SPD should be installed in factory.
11 6 Chapter 3 Technical Parameter Chapter 3 Technical Parameter This chapter expounds the technical parameter, mechanical parameter and operating environment of the indoor/outdoor unit of the Liebert_DM series AC. 3. Technical Parameter Of The Indoor Unit Cooling capacity and sensible cooling capacity (kw) Fan Type Table 3- Technical parameter of DME07 series indoor unit DME07 MCT DME07 MOT DME07 MHT Model DME07 MCP DME07 MOP DME07 MHP 4 CdB Cooling capacity %RH Sensible cooling capacity Standard airflow (m 3 /h) Number Static pressure outside the fan (Pa) Compressor Number Front face area (m ) Evaporator coil Face air velocity (m/s) Electric heater Power (kw) Electrode humidifier Filter Humidifier water rate (kg/h) Front filter size (mm, pcs) Side filter size (mm, pcs) Number Liquid return pipe ID (mm) Discharge pipe ID (mm) Port size Humidifier Charging pipe OD (mm) Condensed water drain pipe OD (mm) Net weight (kg) Electrical Max. current (A) parameter Air breaker Note: all the cooling capacity is nominal, ±5% error exists in the actual capacity Table 3- Technical parameter of DME series indoor unit Cooling capacity and sensible cooling capacity (kw) Fan Type DME MCT DME MOT DME MHT Model DME MCP DME MOP DME MHP 4 CdB Cooling capacity %RH Sensible cooling capacity Standard airflow (m 3 /h) Number Static pressure outside the fan (Pa)
12 Chapter 3 Technical Parameter 7 Compressor Number Evaporator coil Front face area (m ) Face air velocity (m/s)..... Electric heater Power (kw) Electrode humidifier Filter Port size Humidifier water rate (kg/h) Front filter size (mm, pcs) Side filter size (mm, pcs) Number Liquid return pipe ID (mm) Discharge pipe ID (mm) Humidifier Charging pipe OD (mm) Condensed water drain pipe OD (mm) Net weight (kg) Electrical parameter Max. current (A) Air breaker Note: all the cooling capacity is nominal, ±5% error exists in the actual capacity 3. Technical Parameter Of The Outdoor Unit Item Table 3-3 Technical parameter of the standard outdoor unit DMC07WT Model DMCWT Airflow (CMH) Condenser coil CSA (m ) Number of the condenser coil row Motor power (W) Operating temperature range ( C) -5 C ~ +45 C -5 C ~ +45 C Refrigerant charge quantity (g) Size of the liquid pipe (mm) Size of the discharge pipe (mm).7 6 Item Table 3-4 Technical parameter of the Lee-Temp outdoor unit DML07W Model DMLW Airflow (CMH) Condenser coil CSA (m ) Number of the condenser coil row Motor power (W) Operating temperature range ( C) -34 C ~ +45 C -34 C ~ +45 C Refrigerant charge quantity (g) Size of the liquid pipe (mm) Size of the discharge pipe (mm) Mechanical Parameter 3.3. Indoor Unit The mechanical parameters of the indoor unit are listed in Figure 3- and Table 3-6.
13 8 Chapter 3 Technical Parameter DME07kW Figure 3- Dimensions of the indoor unit (unit: mm) DMEkW The shadows in Figure 3- indicate a reasonable installation and service space. For 7.5kW units, 50mm must be reserved to facilitate maintenance; For.5kW unit, 600mm must be reserved to facilitate maintenance. The AC unit equipped with a heater should be kept a distance of minimum 50mm from combustible substance. When testing the AC unit, keep the external static pressure below 50Pa lest the air volume becomes too low and the heater becomes too hot. 3.4 Outdoor Unit The mechanical parameters of the outdoor unit are shown in Figure 3-, Figure 3-3 and Table Figure 3- Dimensions of standard outdoor unit (unit: mm)
14 Chapter 3 Technical Parameter Figure 3-3 Dimensions of Lee-Temp outdoor unit (unit: mm) Table 3-5 Mechanical parameters of indoor unit and outdoor unit Indoor unit Outdoor unit Model Cooling capacity (kw) Dimensions (W D H, mm) Net weight (kg) DME07*** DME*** DMC07WT DMCWT DML07W DMLW Operation Environment The operation environment requirements are listed in Table 3-7. Item Installation position Installation mode Ambient temperature Ambient humidity Protection level Altitude Table 3-6 Operation environment requirements Requirements The maximum equivalent horizontal distance between the indoor unit and outdoor unit [] : 50m; Vertical distance ΔH [] : -5m ΔH 0m Indoor unit: vertical mode; mounting base 50mm; outdoor unit: horizontal airflow mode Indoor: 0 C ~ 40 C Outdoor: standard model, -5 C ~ +45 C; Lee-Temp model, -34 C ~ +45 C 30%RH ~ 80%RH Outdoor unit: IPX4 < 000m. Derating is required when the altitude exceeds 000m Operation voltage range 380V (-5% ~ +5%), settable according to different environments, the error is 3% Note: []: The value is positive if the outdoor unit is installed above the indoor unit; negative if the indoor unit is installed above the outdoor unit. []: ΔH = Altitude of the outdoor unit - Altitude of the indoor unit [3]:Total transportation and storage time should not exceed six months. Otherwise, the performance needs to be re-calibrated
15 0 Chapter 4 Application Guidline Chapter 4 Application Guidline This chapter mainly introduces the general arrangement, general principle, piping, model configuration and cooling cycle. 4. General Arrangement The general system arrangement diagram is shown in Figure 4-. The standard pipe sizes are shown in Table 4-. Note Figure 4- General arrangement diagram. : Factory piping.. : Field piping (by technicians). 3. *: Check valve and traps are optional and not supplied by Emerson. But they are recommended for normal system operation and easy maintenance. They should be installed on site by technicians. 4. +: Solenoid valve is a part of extended piping kit. Table 4- Standard pipe sizes Actual cooling capacity Pipe length (m) Discharge pipe OD Liquid pipe OD Liebert_DM series 7.5kW unit 5 / (mm) 3/8 (0mm).5kW unit 5 5/8 (6mm) / (mm) 4. General Principles. Use copper pipes with quick thread connector to connect the indoor unit and the outdoor unit. If the pipe length exceeds the standard pipe length (see Table 4-) and straight copper pipe is used, piping joints must be brazed.. Follow standard industry procedures in selection and placement of pipe, system evacuation and charging with refrigerant (only when pipeline is too long). The standard refrigerant of the AC unit is R. 3. Give considerations to pipeline pressure drop, oil return to the compressor, to avoid oil leakage and clogging in parts of the system and minimize noise and vibration to the greatest extend. 4. Consult Emerson before installation on whether measures such as using extended piping kit are needed, if the equivalent length exceeds 50m, or if the vertical distance between the indoor unit and the outdoor unit exceeds the values in Table 4-.
16 Table 4- Vertical distance between indoor unit and outdoor unit Relative position Outdoor unit installed higher than indoor unit Outdoor unit installed lower than indoor unit Chapter 4 Application Guidline Value Maximum: 0m Maximum: 5m 5. The equivalent length of each part is given in Table 4-3. The resistance loss caused by elbows and valves has been taken into consideration. The installer should confirm if these values are appropriate for site conditions. Table 4-3 Equivalent length of each part Liquid pipe OD (inch) Equivalent length (m) 90 elbow 45 elbow T-type three way 3/ / / / / / Piping All equipment must be installed vertically. The Liebert_DM AC is available in two installation modes: outdoor unit installed higher than indoor unit and indoor unit installed higher than outdoor unit. See Figure 4- and Figure 4-3 for details. Outdoor unit Liquid pipe (not be exposed to sun) Indoor unit Max. 0m 7.5m Trap Protection tube Isolataion floor Humidifier canister water supply pipe (to water tap) Sealed Discharge pipe (slope) :00 Figure 4- Outdoor unit above indoor unit Insulation material Floor Condensation water drain pipe (to outdoor) :00
17 Chapter 4 Application Guidline Indoor unit Protection tube Sealed Discharge pipe (slope) :00 Isolation floor Humidifier canister water supply pipe (to water tap) Liquid pipe (not be exposed to sun) Outdoor unit Min. 5m Insulation material Floor Condensation water drain pipe (to outdoor) :00 Figure 4-3 Indoor unit above outdoor unit 4.4 Model Configuration Main power 380V/3P/50Hz Cooling capacity Table 4-4 Configuration of the indoor unit and the outdoor unit Single cooling Indoor unit With electric heating With humidifying and heating Standard model Outdoor unit Lee-Temp model 7.5kW DME07MCT(P) DME07MOT(P) DME07MHT(P) DMC07WT DML07W.5kW DMEMCT(P) DMEMOT(P) DMEMHT(P) DMCWT DMLW 4.5 Cooling Circulation As shown in Figure 4-4, the compressor () presses the high-temperature gaseous refrigerant into the air-cooled condenser (). The refrigerant is condensed as fluid in the condenser and sent to the evaporator (4) after being throttled by the thermostatic expansion valve (3). In the evaporator (4), the refrigerant performs heat exchange with the indoor air that is driven and circulated by the indoor fan (5) and then evaporates. The refrigerant is sent back to the compressor () to start a new circulation. The system adjusts the rotation speed of the outdoor fan (6) to retain the discharge pressure normal. The compressor () is configured with a crankcase heating strip to prevent the refrigerant from flowing back from the condenser in summer. This can protect the compressor from liquid strike during startup. Figure 4-4 Schematic diagram of the system
18 Chapter 5 Micro-Processing Controller 3 Chapter 5 Micro-Processing controller This chapter gives a detailed description on appearance, LCD screen, control buttons, control screen, control logic, alarm function of the micro-processing controller of the Liebert_DM AC. 5. Appearance The micro-processing controller panel is shown in Figure LCD Screen Figure 5- Micro-processing controller panel The LCD screen displays English menus with white backlight. When the system is operating normally, it displays the current temperature & humidity (whether to display humidity is optional. Only the unit configured with a humidifier can display humidity), unit output status (cooling, heating, dehumidifying and humidifying), unit status (single, host, standby), unit operation status (running, standby, locked), alarm information and current date & time, as shown in Figure 5-. C Heat SIG 50%rh Hum RUN High Hum /4 0/0/0 00:00 Figure 5- LCD screen More detailed operating status of certain component and alarm information are available from the Main Menu screen. The selected menu item will be highlighted while browsing. The digit to be changed will be highlighted while you are changing setting. 5.3 Control Buttons 5.3. Function Description The micro-processing controller provides five control buttons, as shown in Figure 5-3. ON/OFF button Up button Enter button Esc button Down button Figure 5-3 Control keypad The functions of the control buttons are described in Table 5-. Table 5- Function descriptions of control buttons Control button Function descriptions
19 4 Chapter 5 Micro-Processing Controller ON/OFF button Enter button (ENT) Esc button (ESC) Up button Down button Press this button for 3s to turn on or off the unit Enter the selected menu screen. Validate the parameter setting value Exit the current menu and return to the Normal screen or previous menu screen. Abort parameter change; silence the audible alarm Move the cursor up or increase the parameter value. For a toggle selection: scroll through the options. For a multi-screen menu: scroll up the screen Move the cursor down or decrease the parameter value. For a toggle selection: scroll through the options. For a multi-screen menu: scroll down the screen 5.3. Operation Example Example : Inputting password to enter the Main Menu After the unit is started up, you can enter the Main Menu through conducting the following operations on the Normal screen.. Press the Enter button to enter the Password screen.. Press the Enter button to highlight the input data field in the Password screen. 3. Press the Up or Down button to change the current password number. 4. Press the Enter button to confirm the password and enter the Main Menu screen. Example : changing parameters Taking Hi Temp in Alarm Output screen as an example, the procedures are as follows:. Press the Up or Down button to move the cursor on the Alarm Menu in the Main Menu screen.. Press the Enter button to enter the Alarm Menu. 3. Press the Up or Down button to move the cursor on Alarm Output in the Alarm Menu screen. 4. Press the Enter button to enter the Alarm Output screen. 5. Press the Up or Down button to move the cursor on Hi Temp. 6. Press the Enter button to highlight the parameter field of Hi Temp. 7. Press the Up or Down button to select the parameter option. 8. After selecting, press the Enter button to confirm. The parameter will take effect. 9. Press the Esc button to return to the previous menu screen. Note After changing the parameter, if you do not press the Enter button to validate the changed parameter, the change will be invalid. 5.4 Control Screen 5.4. ON Screen After the AC unit is powered on, the LCD screen will display the ON screen, as shown in Figure 5-4. Connecting Please wait... Figure 5-4 ON screen 5.4. Normal Screen After the AC unit is powered on, the Normal screen will be displayed after 0 seconds (default) for heat startup delay or through pressing the Enter button directly, as shown in Figure 5-5. The Normal screen displays the following information: the current temperature and humidity, unit operation state (cooling, heating, dehumidifying, humidifying), unit mode (single, host, standby), unit operation status (running, standby, locked, off, sleep), alarm information and current date & time.
20 Chapter 5 Micro-Processing Controller 5 C Heat SIG 50%rh Hum RUN No alarm 0 0/0/0 00:00 Figure 5-5 Normal screen Password Screen Press the Enter button on the Normal screen, and the Password screen will appear, as shown in Figure 5-6. Password: *** Figure 5-6 Password screen Three levels of passwords are provided for accessing the menus. The detailed descriptions are listed in Table 5-. Table 5- Password level Password level User Initial password Remark Level General operator 000 Level Maintenance personnel - Set all parameters Level 3 Factory technician - - Browse all menu information. Only set temperature and humidity setpoints (see Figure 5-) and cannot change any values and settings For detailed operation on entering the password, refer to 5.3. Operation Example. If entering a wrong password, you can only view the menu, but cannot change the settings. In this case, you can press the Esc button to return to the Normal screen, and then press the Enter button to enter the Password screen again. Note If pressing the Enter button in the Password screen instead of inputting any password, you can only view the menu settings but cannot change any parameters. 5.5 Control Logic 5.5. Cooling logic When the actual temperature = set temperature + temperature precision value, the cooling requirement reaches 00%. When the actual temperature = set temperature, the cooling requirement is 0%. When the actual temperature rises to the degree corresponding to the 00% cooling requirement, cooling starts; when the actual temperature drops to the degree corresponding to the 0% cooling requirement, cooling stops (the compressor is turned off). Figure 5-7 shows the cooling logic diagram.
21 6 Chapter 5 Micro-Processing Controller The compressor is turned off The compressor is turned on 0% +00% Set point Indoor temperature Figure 5-7 Cooling logic 5.5. Heating Logic When the actual temperature = set temperature - temperature precision value, the heating requirement reaches 00%. When the actual temperature = set temperature, the heating requirement is 0%. When the actual temperature drops to the degree corresponding to the 00% heating requirement, heating starts; when the actual temperature rises to the degree corresponding to the 0% heating requirement, heating stops (the electronic heater is turned off). Figure 5-8 shows the heating logic diagram. Electric heater is turned on Electric heater is turned off -00% Indoor temperature 0% Set point Figure 5-8 Heating logic Dehumidifying Logic. Relative humidity control logic Dehumidifying is activated when the cooling requirement is smaller than 5% and the dehumidifying requirement is larger than 00%. Dehumidifying is deactivated when the dehumidification requirement is no larger than 50%. Figure 5-9 shows the dehumidifying activation and deactivation requirements. Exit dehumidifying mode Enter dehumidifying mode Set point +50% +00% Indoor humidity Figure 5-9 Dehumidifying activation and deactivation requirements
22 Chapter 5 Micro-Processing Controller 7 In the dehumidifying mode, the fan switches to high gear immediately when the cooling requirement is larger than 5%. The fan switches back to low gear when the temperature drops normal. Figure 5-0 shows the high/low gear switch diagram of the fan in the dehumidifying mode. Switch to low gear Switch to high gear Set point +5% Indoor temperature Figure 5-0 High/low gear switch diagram of the fan in the dehumidifying mode In the temperature compensation mode, the compressor is turned on when the cooling requirement is larger than 0% and it is turned off when the cooling requirement is smaller than -00%; the electronic heater is turned on when the cooling requirement is smaller than 0% and it is turned off when the cooling requirement is larger than 5%. Figure 5- shows the control logic of the compressor in a) and the control logic of the electronic heater in b). The compressor is turned off The compressor is turned on The electric heater is turned on The electric heater is turned off -00% Indoor Set point temperature Set point a) Control logic of the compressor b) Control logic of the electronic heater Figure 5- Dehumidification logic in the temperature compensation mode In the non-temperature compensation mode, the compressor is turned on and the electronic heater is turned off when the cooling requirement is no smaller than 0%; the compressor is turned off and the electronic heater is turned on when the cooling requirement is smaller than -00%. Figure 5- shows the control logic of the compressor in a) and the control logic of the electronic heater in b). +5% Indoor temperature The compressor is turned off The compressor is turned on The electric heater is turned on The electric heater is turned off -00% Indoor Set point temperature a) Control logic of the compressor b) Control logic of the electronic heater Figure 5- Dehumidifying logic in the non-temperature compensation mode. Absolute Humidity Control Logic -00% Indoor Set point temperature If absolute humidity control logic is used, users should calculate the absolute humidity based on the actual temperature and humidity and perform humidity control by referring to. Relative humidity control logic in this section.
23 8 Chapter 5 Micro-Processing Controller Humidifying Logic. Relative humidity control logic When the actual humidity = set humidity - humidity precision value, the humidification requirement reaches 00%. When the actual humidity = set humidity, the humidification requirement is 00%. When the actual humidity drops to the value corresponding to the 00% humidification requirement, humidification starts; when the actual humidity rises to the value corresponding to the 0% humidification requirement, humidification stops. Figure 5-3 shows the humidification logic diagram. The humidifier is turned on The humidifier is turned off. Absolute humidity control logic If absolute humidity control logic is used, users should calculate the absolute humidity based on the actual temperature and humidity and perform humidity control by referring to. Relative humidity control logic in this section Outdoor Fan Control 0% -00% Indoor Set point temperature Figure 5-3 Humidification logic. If the pressure sensor is faulty, the fan operates at full speed.. If frequency deviation happens, the fan stops operating. 3. If the compressor is supplied with power and the pressure in the condenser meets requirements for starting the fan, the fan starts. 4. If the compressor is supplied with power and the pressure in the condenser meets requirements for stopping the fan, the fan stops. Alternatively, if the compressor is stopped for more than one minute, the fan stops. 5. Figure 5-4 shows the voltage control curve during fan operating, which is on the basis of FSCP control curve. V 00% Vin F E L MaxV B C D Vx A L 00% output MinV I H Poff G Pband Pset Px Condensation pressure point Pv00 = (Pset + Pband + 5) Pmaxv Pv00 P Figure 5-4 FSCP control curve During fan startup, the voltage is obtained based on the pressure-voltage curve if the pressure is kept within the set range and the voltage is the value of MaxV if the pressure exceeds the set range. During fan operating, the power system stops supplying power to the fan if the condensation pressure is smaller than (Pset - ), namely Poff. The
24 Chapter 5 Micro-Processing Controller 9 control process is A -> B -> C -> D -> E -> F -> C -> B -> A -> G -> H -> I (point A corresponds to the pressure ranging from B to G). In the case of 00% voltage output, the voltage restores to MaxV after the pressure drops by bars to the point of Pmaxv. Table 5-3 lists the voltage and pressure parameters. Table 5-3 Voltage and pressure setting table Parameter Lower limit Upper limit Default Min. power supply voltage (%) Max. power supply voltage (%) Start pressure (Bar) 5 3 Pressure bandwidth (Bar) Economy Mode Control. The AC units enter the Economy mode after this mode is enabled.. When the system starts to operate in this mode, the temperature control precision is added with the precision amplification value. When the system exits this mode, the normal precision value recovers. Table 5-4 lists the parameter setting in the Economy mode. Table 5-4 Parameter setting in the Economy mode Parameter Default value Lower limit Upper limit Economy mode OFF (0) OFF (0) ON () Start At : 00 8: 00 3: 00 Start At 7: 00 5: 00 0: 00 Zoom ( C) Sleep Mode Control. The AC units enter the Sleep mode when there is one energy-saving card or more.. In this mode, the fan stops operating when the following conditions are met: ) All the other moving parts do not need to operate except for the indoor fan. ) The temperature of all energy-saving cards (four at most) is lower than the sleep temperature. 3) The energy-saving cards are kept in the temperature for 600 seconds. 3. The AC units exit the Sleep mode when either of the following conditions is met: ) The temperature of an energy-saving card exceeds the value of sleep temperature plus and the energy-saving card is kept in the temperature for 30 seconds. ) No energy-saving card is available. Table 5-5 lists the parameter setting in the Sleep mode. Table 5-5 Parameter setting in the Sleep mode Parameter Default value Lower limit Upper limit EngySave Cd Num Sleep At 7 C Host/Standby Unit Control. The host unit automatically switches as a standby unit after a rotate cycle ends.. The host unit switches as a standby unit and the standby unit switches as an host unit after a fault occurs in the host unit or standby unit, such as high pressure locking, low pressure locking, or discharge locking. 3. The standby unit works as a host unit after a high temperature alarm is generated by the host unit. Table 5-6 lists the parameter setting for host/standby unit control. Table 5-6 Parameter setting for host/standby unit control Parameter Lower limit Upper limit Default Remark Unit Status 0 0 0: SIG; : HST; : Standby Switch Mod 0 0 0: Standby; : Rotate Rt Time By day (,, 3, 4, 5, 6, and 7) The number indicates the interval days between two polling cycles.
25 0 Chapter 5 Micro-Processing Controller Rt At 0: 00 3: 00 : Alarm Function 5.6. Alarm Category Alarms fall into the following categories: high pressure alarm, low pressure alarm, discharge temperature alarm, high temperature alarm, low temperature alarm, high humidity alarm, low humidity alarm, humidifier fault, fault of return air temperature sensor, high pressure locking, low pressure locking, discharge temperature locking, floor wetting, power loss, over-voltage alarm, under-voltage alarm, frequency deviation, loss phase alarm, negative phase alarm, custom alarm (lightning protection), energy-saving card fault, air flow loss, pressure sensor fault, humidity sensor fault, air flow sensor fault, and custom alarm Alarm State And History. Alarm state recording ) Alarms are recorded based on alarm occurrence time. ) Both the alarm category and alarm time are recorded. 3) Alarm states are cleared upon power failure.. Alarm history recording ) Historical alarms are recorded based on alarm occurrence time. ) A maximum of 00 historical alarms are recorded. 3) A historical alarm includes the alarm SN., alarm category, alarm time, and alarm clearance time. 4) Historical alarms are saved upon power failure. 5) Historical alarms can be manually cleared. 6) Two-level password protection is enabled for historical alarms Alarm Prerequisites And Handling Methods Table 5-7 Alarm prerequisites and handling methods No. Alarm Alarm Prerequisite Alarm Mode Clearance Method 3 4 High pressure alarm Low pressure alarm Discharge temperature alarm High temperature alarm The high pressure switch is kept open-circuited for a duration of alarm reporting delay The low pressure switch is kept open-circuited for a duration of alarm reporting delay in the case of compressor operating. The state of the low pressure switch is ignored for 80 seconds. The duration is configurable, ranging from 30 seconds to 600 seconds The discharge temperature switch is kept turned off for a duration of alarm reporting delay in the case of compressor operating The fan is enabled for 0 minutes and the return air temperature is kept higher the compressor is forcibly the compressor is forcibly the compressor is forcibly the electronic Keep the high pressure switch turned off for a duration of alarm reporting delay Keep the low pressure switch turned off for a duration of alarm reporting delay Keep the discharge temperature switch turned off for a duration of alarm reporting delay Keep the return air temperature lower than the value (current Alarm reporting delay (unit: second) Alarm Output disabled disabled disabled disabled/
26 Chapter 5 Micro-Processing Controller No. Alarm Alarm Prerequisite Alarm Mode Clearance Method Low temperature alarm High humidity alarm Low humidity alarm Humidifier fault Fault of the return air temperature sensor High pressure locking Low pressure locking Discharge temperature locking Floor wetting alarm than the high temperature threshold for a duration of alarm reporting delay while the return air temperature sensor operates normally The fan is enabled for 0 minutes and the return air temperature is kept lower than the low temperature threshold for a duration of alarm reporting delay while the return air temperature sensor operates normally The fan is enabled for 0 minutes and the return air humidity is kept higher than the high humidity threshold for a duration of alarm reporting delay while the return air humidity sensor operates normally The fan is enabled for 0 minutes and the return air humidity is kept lower than the low humidity threshold for a duration of alarm reporting delay while the return air humidity sensor operates normally The humidifier switch is kept turned off for a duration of alarm reporting delay The return air temperature is kept out of the allowed range for a duration of alarm reporting delay The high pressure alarm is reported for three times within an hour or the alarm is kept uncleared within 0 minutes The low pressure alarm is reported for three times within an hour or the alarm is kept uncleared within 0 minutes The discharge temperature alarm is reported for three times within an hour or the alarm is kept uncleared for 0 minutes The floor wetting switch is kept turned off for a duration of alarm reporting delay heater is the cooling system is humidification stops dehumidificati on stops triggered the cooling system is forcibly started the compressor is locked the compressor is locked the compressor is locked humidification stops high temperature threshold - C) for a duration of alarm reporting delay Keep the return air temperature higher than the value (current low temperature threshold + C) for a duration of alarm reporting delay Keep the return air humidity lower than the value (current high humidity threshold - %) for a duration of alarm reporting delay Keep the return air humidity higher than the value (current low humidity threshold + %) for a duration of alarm reporting delay Keep the humidifier switch turned off for a duration of alarm reporting delay Keep the return air temperature within the allowed range for a duration of alarm reporting delay Manually clear the alarm Manually clear the alarm Manually clear the alarm Keep the floor wetting switch turned off for a duration of alarm reporting delay Alarm reporting delay (unit: second) / / / 0 Alarm Output d isabled/ disabled/ disabled/ disabled/ disabled/ disabled disabled disabled disabled/
27 Chapter 5 Micro-Processing Controller No. Alarm Alarm Prerequisite Alarm Mode Clearance Method 4 Power loss Over-voltag e alarm Under-volta ge alarm Frequency deviation Open phase alarm Negative phase alarm Custom alarm (lightning protection) Energy saving card fault Air flow loss 3 Fault of pressure sensor (lightning protection) Power loss occurs when the AC units are in operation The input voltage increases by 5% The input voltage decreases by 5% The input frequency is deviated by 5Hz Open phase occurs Negative phase occurs The set polarities are kept inconsistent with those input for a duration of alarm reporting delay The number of normally online energy-saving cards is less than the set number or more than one energy-saving card exceed the allowed temperature range The value (temperature measured by using the sensor NTC0 - return air temperature) is kept larger than the set temperature for a duration of alarm reporting delay when the fan is in normal operation. The air flow detection thermal resistor output is when the fan is shut down. This alarm is not reported if the fan is and the temperature sensor is faulty The condensing pressure is kept out of the allowed range for a duration of alarm reporting delay triggered the system is locked the system is locked the system is locked the system is locked the system is locked triggered the dormancy mode cannot be activated if all energy-saving cards are faulty shut down all the devices except for the fan triggered automatically cleared one second later Restore the input voltage Restore the input voltage Alarm reporting delay (unit: second) Restore the frequency 3 Manual restoration 3 Manual restoration / Keep the set polarities consistent with those input for a duration of alarm reporting delay Keep the number of the cards consistent with the set number and keep the cards in normal temperature Keep the value (temperature measured by using the sensor NTC0 - return air temperature) smaller than the value (set temperature - C) Keep the condensing pressure within the allowed range for a duration of alarm reporting delay / Alarm Output disabled/ disabled/ disabled/ disabled/ disabled/ disabled/ disabled/ disabled/ disabled disabled 4 Humidity The return air humidity is Keep the return air 0
28 Chapter 5 Micro-Processing Controller 3 No. Alarm Alarm Prerequisite Alarm Mode Clearance Method 5 sensor fault Air flow sensor fault kept out of the allowed range for a duration of alarm reporting delay The temperature measured by using the air flow loss sensor (NTC0) is kept out of the allowed range for a duration of alarm reporting delay triggered triggered humidity within the allowed range for a duration of alarm reporting delay Keep the temperature measured by using the air flow loss sensor (NTC0) within the allowed range for a duration of alarm reporting delay Note:. Alarm reporting delay is a fixed configuration.. In the case of system locking, the compressor, heater, humidifier, and outdoor fan are locked. Alarm reporting delay (unit: second) 0 Alarm Output disabled/ disabled/ 5.7 Other Functions 5.7. Real-Time Clock. Set and display the system date and time.. This function provides the accurate time of data recording Operating Record. Device startup and stop record A maximum of 50 records about device startup and stop are recorded, including the fan, compressor, electronic heater, and humidifier.. Operating time record The operating time of the fan, compressor, electronic heater, and humidifier is recorded by hour Parameter Protection. All parameters that need to be protected are saved in the internal EEPROM.. Default parameter settings can be restored. 3. Two-level password protection is enabled Password Protection. A password consists of four digits, ranging from 0000 to Password protection is classified into three levels.. Level password is available for ordinary users. They can modify password protection parameters and level password. 3. Level password is available for operators. They can modify password protection parameters and level and level password. 4. Level 3 password is available for maintenance personnel. Except for level 3 password, they can modify password parameters and level and level password Shutdown Mode. Shutdown modes fall into local shutdown, monitor shutdown, and remote shutdown.. Local shutdown is implemented by pressing the on/off button on the display panel. 3. Monitor shutdown is implemented through the background monitor RS Remote shutdown has the highest priority and is in serial relationship with the other shutdown modes.
29 4 Chapter 5 Micro-Processing Controller Diagnosis Output. In the diagnosis mode, devices such as the primary fan, compressor, electronic heater, and humidifier can be tested.. A tested device can be automatically or manually shut down when it diagnoses another load. 3. If a device is not manually shut down within an hour, the device automatically exits the manual shutdown mode. 4. The fan must be always in operation. If the fan stops operating, the other devices are forcibly shut down. The system must be protected in the case of major alarms, such as air flow loss, high pressure alarm, low pressure alarm, discharge alarm and locking, and power fault Sensor Calibration. The temperature calibration range is ±5 C.. The humidity calibration range is ±0% Deployment Management Deployment management is required during initial system operating.
30 Appendix Menu Structure 5 Appendix Menu Structure Main Menu Alarm Menu Set Points System Status Temp Calib System Menu Help Menu LCD Setting Alarm Status Alarm History Alarm Setpoint Temp Stpt Temp Sens Hum Stpt Hum Sens Hi Temp Lo Temp Hi Hum Lo Hum Air Loss Analog Time/Date In/Out Status Run Time SS Record Hum Calib NTC0 Calib In Fan SS Record Comp SS Record Heat SS Record Hum SS Record Out Fan SS Record Setup System Outdoor Unit Mntr Prtcl Version Info Mntr Addr Enab Open Baut Rate Over Press Under Press Pwr Freq Devia Min. Volt Max. Volt Out Volt Start Press Contrast Language Press BdWdth Heat Num Hum Num Select Options CostSave Mod EngySave Cd Num Unit Mode Switch Mod Figure Menu structure Change Password Factory Reset
31 Appendix Wiring Diagram 6 Appendix Wiring Diagram J3- J3- Yellow-green PE N PELN PE N To outdoor unit QF- QF-3 QF V/50Hz 3N~ Power MCB N L L L3 Power SPD ALARM COM NC SPD/D Cable description: Factory supplied line Field supplied line Yellow-green PE J9- SPD-N J9- SPD- SPD- SPD-3 Grounding point of the electrical control box J3-4 J8-3 KM- KM- KM-3 KM-5 A 3 5 KM A 4 6 T KM-4 Brown T KM-6 Gray T3 Grounding point of the electrical control box KM- KM- Electric heater belt of the compressor L Blue Blue J8-3 TB- KM- A KM A Brown Electric heater KM-3 Brown Red Yellow Transformer T Indoor connection Yellow Fuse terminal TB TB-N N N Yellow N N TB-N N N Transformer T TB-N TB-N N N TB- TB- TB- TB-3 TB TB TB-5 TB TB TB-8 Standby unit is available 8 8 TB TB-0 Public alarm 00 J8- J8- J3 J3 KM-A J8-3 3 J J0 5 J4 J4- J4- J0 Power J-N J J-L J0 J board GND J V Filter A J03 J39 B board J9 Yellow-green J J J34 Indoor fan Grounding point of the electrical control box J9- SPD-NC J9- SPD-COM 3 4 J9-5 J9 5 Remote turn on/off J9-6 6 J9-7 Grounding point 7 Start capacitor Standby unit request J9-8 of the electrical 8 control box Yellow-green J8-7 J8-8 J8-9 J8-0 Brown White Connection cables between indoor and outdoor connection terminal L Brown J- J- J3-4 KM-A Indoor connection terminal J3- J3- N L Figure DME07 model J30 Control board J8 J3 3 J36 J8-3 3 J J8-7 7 J8-8 8 J8-9 9 J J-5 J 5 J V GND CANH CANL Compressor Energysaving card GND 4 V A B 3 J4 Display board Temp/Hum detection board High pressure switch Air discharging switch N N Parts supplied line PE Pressure sensor Inserted terminals Outdoor connection Connection description: terminal. This diagram is only for 7.5kW model.. There is no electric heater contactor KM, electric heater and the corresponding cables in the single cooling unit. 3. There are transformer T and connection terminal TB Only when the heating function is select; The single cooling model is not equipped with transformer T and connection terminal TB. 4. The energy-saving card and the monitoring card are options; If you need them, field connection is essential. 5. The power SPD is equipped with T version unit; P version unit does not have power SPD and corresponding cables, J9- and J9- of the control board is shorted using cable. GND VIN J0- +5V Green Red J0-3 J0-5 J0-7 Yellow Fuse 34 Indoor connection terminals TB TB- KM-A TB- J8-4 Gray Gray Blue Blue Brown DB9 KM-A TB- TB-7 TB-8 TB-9 TB-0 Low pressure switch Floor overflow Monitoring card
32 Appendix Wiring Diagram 7 Yellow Fuse J3- J3- PELN To outdoor unit PE Yellow-green N Blue QF- QF-3 QF Power PE N 4 6 MCB 380V/50Hz 3N~ Cable description: Factory supplied line Field supplied line Parts supplied line Inserted terminal PE Yellow-green SPD-N SPD- SPD- SPD-3 N ALARM COM NC J9- J9- L N Outdoor L L L3 Power SPD SPD/D J3-4 J8-3 KM- KM- KM-4 KM-3 KM-6 KM-5 KM- KM- A 3 5 KM A 4 6 T T Grounding point of the electrical control box T3 Compressor Grounding point of the electrical control box Electric heater belt of the compressor KM3-A TB-5 Blue Blue J9-3 J9-4 J8- J8- Connection cable between the indoor and outdoor terminal L N PE TB- KM- KM-3 A A KM KM3 KA A A J8-3 Brown Brown Electric heater TLR TLR AL AL +VR SET GND AB AB Indoor terminal block TAM Humidifying control board TLR TB- KM3-3 KM3- KM3-6 KM3-3 HUM-L HUM-N Humidify -ing tub G G0 ON GND DR EV G EV LS LS CS CS J8-7 J8-8 J8-9 J8-0 Yellow-green Grounding point of the electrical control box TB-3 TB-6 Indoor connection terminal TB N N TB-N N N TB-N TB-N N N TB-N TB-N N N TB- TB- TB- TB-3 TB TB TB-5 TB TB TB TB TB TB Indoor fan Start capacitance 0 Drain manually Humidify normally Inlet solenoid valve Water level probe Conductivity probe Figure 3 DME model Filter board J J8-5 TB-8 Brown J J Standby unit request J8- J8- J8-3 3 J8 J J0 J-N J-L J0- Grounding point of the electrical control box 3 4 J J03 J03 Red Yellow Transformer T Yellow Fuse Yellow Transformer T J0 Power board J J30 Control board J3 3 Pressure sensor J36 J3 J3 J4 J J39 J34 +V GND CANH CANL Energy-saving card High pressure switch Low pressure switch Air discharging switch Floor overflow 4 3 J4 Display board Temp/Hum detection board connection Connection description: terminal. This diagram is only for.5kw model.. There is no electric heater contactor KM, electric heater, humidifying contactor KM3, inner fan relay KA, humidifying control board and the corresponding cables in the single cooling unit. 3. There is no humidifying contactor KM, inner fan relay KA, humidifying control board and the corresponding cables in the heating model. 4. Both single cooling model and heating model are not equipped with inner fan relay KA. The black plug of the inner fan connects J8-4 terminal directly; after crimped by the end connectors, the blue plug connects to the electric control box. 5. There are transformer T and connection terminal TB Only when the heating and humidifying function are select; The single cooling model is not equipped with transformer T and connection terminal TB. 6. The energy-saving card and the monitoring card are options; If you need them, field connection is essential. 7. The power SPD is equipped with T version unit; P version unit does not have power SPD and corresponding cables, J9- and J9- of the control board is shorted using cable. KA-4 Blue White Brown Outlet solenoid valve J- J- J3-4 J3- KM-A N Standby unit is available Public alarm J3- L KM-A SPD-NC SPD-COM AL AL Remote turn on/off Yellow-green J9- J9- J9-3 J9-4 J9-5 J9-6 J9-7 J9-8 J0- J0-3 J0-5 J0-7 GND VIN +5V Green Red J4- J4- GND V A B J8- J8- Brown J8-3 3 J8-4 4 J8-5 J8 5 J8-6 6 J8-7 7 J8-8 8 J8-9 9 J8-0 0 Blue 3 Blue 4 J 5 Brown TB-8 TB- TB- TB-3 TB-4 TB-5 TB-6 TB-3 KA-3 KM-A KM3-A G J8-4 TLR G0 J8-6 Gray Gray DB9 +VR SET KM-A TB-4 KA- TB-3 TB-7 TB-8 TB-9 TB-0 Indoor connection terminal TB Monitoring card GND V A B
33 Appendix 3 Glossary 8 Appendix 3 Glossary AC ID LCD Lee-Temp OD SPD SCR Air conditioner Inside diameter Liquid crystal display Low temperature Outside diameter Surge protective device Silicon controlled rectifier
34 Emerson Network Power Asia Australia T: F: Indonesia T: F: Japan T: F: Korea T: F: Malaysia T: F: Pakistan T: to 8 F: Philippines T: F: Singapore T: F: Thailand T: F: to 78 Vietnam T: F: New Zealand T: F: While every precaution has been taken to ensure the accuracy and completeness of this literature, Emerson Network Power assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions. Emerson, Business-Critical Continuity and Emerson Network Power are trademarks of Emerson Electric Co. or one of its affiliated companies. 03 Emerson Electric Co. All rights reserved throughout the world. Specifications subject to change without notice. Emerson Network Power. The global leader in enabling Business-Critical Continuity. AC Power Embedded Computing Infrastructure Management & Monitoring Precision Cooling Connectivity Embedded Power Outside Plant Racks & Integrated Cabinets DC Power Industrial Power Power Switching & Controls Services AP3DPG-LiebertDM_Aircooled-TM
Chilled Water Precision Air Conditioner For Critical Application
AIRSYS-P-SC-OPTIMA-HD-E1304V01.2 HD Chilled Water Precision Air Conditioner For Critical Application Cooling capacity: 42.1kW~161.5kW OPTIMA product family is designed for medium to large data center.
SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS
SECTION 15750 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for roof mounted, self-contained units, with electric cooling, and electric or reverse refrigeration cycle (heat pump) heating
CoolTeg Plus Chilled Water (CW) version: AC-TCW
version: 12-04-2013 CONTEG DATASHEET TARGETED COOLING CoolTeg Plus Chilled Water (CW) version: AC-TCW CONTEG, spol. s r.o. Czech Republic Headquarters: Na Vítězné pláni 1719/4 140 00 Prague 4 Tel.: +420
CRAC Precision climate control units for data centres
CRAC Precision climate control units for data centres 2 Rittal Computer Room Air Conditioner The whole is more than the sum of its parts The same is true of Rittal The System. With this in mind, we have
Si10-417_C. Pocket Manual. Service Diagnosis SPLIT & MULTI
Pocket Manual Service Diagnosis SPLIT & MULTI Service Diagnosis SPLIT & MULTI 1. Troubleshooting with LED...5 1.1 Indoor Unit... 5 1.2 Outdoor Unit... 10 2. Troubleshooting by Symptoms...11 2.1 Air conditioner
Liebert Hiross HPW The High Performance Wallmount Cooling Solutions for Telecom Mobile Remote Access Nodes
Precision Cooling for Business-Critical Continuity Liebert Hiross HPW The High Performance Wallmount Cooling Solutions for Telecom Mobile Remote Access Nodes We re Emerson Network Power, backed by Emerson,
HEAT PUMP FREQUENTLY ASKED QUESTIONS HEAT PUMP OUTDOOR UNIT ICED-UP DURING COLD WEATHER:
HEAT PUMP FREQUENTLY ASKED QUESTIONS HEAT PUMP OUTDOOR UNIT ICED-UP DURING COLD WEATHER: It is normal for a heat pump to have a build up of white frost on the outside coil during cold damp weather. The
Heat Pump Water Heater IOM Manual
Heat Pump Water Heater IOM Manual Installation Operation & Maintenance This manual is intended as an aid to qualified service personnel for proper installation, operation and maintenance of the heat pump
Programmable Thermostat MODEL 3312026.XXX With Dehumidify 3312024.XXX With Out Dehumidify
Comfort Control Center 2 Thermostat Operating Instructions Programmable Thermostat MODEL 3312026.XXX With Dehumidify 3312024.XXX With Out Dehumidify TABLE OF CONTENTS About your new thermostat Features...2
STERILIZERS, LABORATORY DRYING OVENS
TS9026 TS9053 TS9135 TS9430 TS 9000 SERIES: STERILIZERS, LABORATORY DRYING OVENS Series TS9000 consists of four different cabinets available in sizes from 26 litres to 430 litres. Interior housing and
14. Troubleshooting Guide
14. Guide 14.1 Refrigeration Cycle System In order to diagnose malfunctions, ensure the air conditioner is free from electrical problems before inspecting the refrigeration cycle. Such problems include
Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF
Daker DK 1, 2, 3 kva Manuel d installation Installation manual Part. LE05334AC-07/13-01 GF Daker DK 1, 2, 3 kva Index 1 Introduction 24 2 Conditions of use 24 3 LCD Panel 25 4 Installation 28 5 UPS communicator
Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)
Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) I. Demonstrate safety skills in typical HVACR work situations to NATE Core Installer Knowledge Areas for Technician Excellence for Safety
CLOSE CONTROL SYSTEM. PFD series provide you with highly reliable computer room cooling system. High Reliability
PFD-P250VM-E PUHY-P250YJM-A(-BS) PUHY-P500YSJM-A(-BS) PQHY-P250YHM-A CLOSE CONTROL SYSTEM MITSUBISHI ELECTRIC s Close Control System (PFD series) is specifically designed for computer rooms, laboratories
Operation and Installation Manual. Max Series
Operation and Installation Manual Max Series Models 95MAX 155MAX 155ECM 155MAXRX 200MAX 200MAXRX MAXTOP 195DCS 300DCS 200ERV 200ERVD New Auto Dehumidistat Function prevents unwanted use of the dehumidistat
SWIMMING POOL HEAT PUMP Owners Manual
SWIMMING POOL HEAT PUMP Owners Manual This manual refers to the 17.0kw and 21.0kw models only. The heat pump unit is sold with a 1 year warranty. In addition there is a 2 year parts warranty on the compressor
HP switch LP switch Discharge thermo Comp. Surface thermo
1 Specifications Zubadan Model Name PUHZ-SHW80VHA PUHZ-SHW11VHA PUHZ-SHW11YHA Power supply (phase, cycle, voltage) 1φ, V, Hz 1φ, V, Hz 3φ, 0V, Hz Max. current A 9.5 35.0 13.0 Breaker size A 3 16 Outer
NetworkAIR FM Precision Air Conditioner. Operation and Maintenance
NetworkAIR FM Precision Air Conditioner Operation and Maintenance Contents Operation...1 Display Interface.................................... 1 Using the Display................................... 2
The High Performance Floormount Indoor Package Cooling Solution. Precision Cooling for Business-Critical Continuity
Liebert HPF The High Performance Floormount Indoor Package Cooling Solution Precision Cooling for Business-Critical Continuity We re Emerson Network Power, backed by Emerson, a global company that brings
SERVICE MANUAL. Room Air Conditioner Multi Split type Outdoor unit /R410A DC Inverter/
SERVICE MANUAL Room Air Conditioner Multi Split type Outdoor unit /R410A DC Inverter/ FS2MI-147HFD FS2MI-187HFD FS3MI-217HFD FS3MI-277HFD FS4MI-277HFD FS4MI-367HFD FS5MI-367HFD NOTE: Before servicing the
ECOCIAT. Domestic hot water heat recovery unit
Heat recovery unit Domestic hot water High energy efficiency with R410A Compact and quiet Scroll compressors Brazed-plate heat exchangers Heating Heat recovery ENVIRONMENTALLY HFC R410A PROTECTION DE FRIENDLY
TABLE OF CONTENTS. 1.1 Features... 1. 2.1 System Screen... 4 2.2 Main Unit Screen... 6 2.3 Navigating Through the Liebert icom Menus...
Liebert icom User Manual -Intelligent Communications & Monitoring for Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert DS Liebert PeX with Software Version PA2.01.029.03R TABLE OF
Liebert CRV Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment. Precision Cooling For Business-Critical Continuity
Liebert Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment Precision Cooling For Business-Critical Continuity The Intelligent Data Center Cooling Solution: Liebert Trust the industry
FULL DC INVERTER SYSTEMS
FULL DC INVERTER SYSTEMS INDIDUAL AND MODULAR DESIGN & FLEXIBLE COMBINATION commercial air conditioners SDV4 2011/2012 AIR CONDITIONING 1 WELCOME TO THE WORLD of SINCLAIR AIR CONDITIONERS Company operation
Appendix - Controllers 179
Version: 200703 Appendix - Controllers 179 -3- -4- -5- -6- -7- -8- 2. Specifications 2.1 Specifications for inverter units item Model AB182ACERA Function cooling heating Capacity kw 5.01.8--5.8 5.22.0---6.2
Glossary of Heating, Ventilation and Air Conditioning Terms
Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment
COOLSIDE box R410A. conditioned server - racks for direct installation into the room INVERTER E C
COOLS conditioned server - racks for direct installation into the room COOLSIDE box INVERTER R410A E C 2 COOLSIDE box GENERAL FEATURES COOLSIDE BOX is a split system consisting of an outdoor motocondensing
Lesson 36 Selection Of Air Conditioning Systems
Lesson 36 Selection Of Air Conditioning Systems Version 1 ME, IIT Kharagpur 1 The specific objectives of this chapter are to: 1. Introduction to thermal distribution systems and their functions (Section
USER S MANUAL HSC-24A
AIRREX AIR CONDITIONER USER S MANUAL HSC-24A Thank you for purchasing an AIRREX AIR CONDITIONER. BEFORE operation please read this user s manual carefully. Keep this manual readily available. It is ESSENTIAL
technical data air conditioning systems RXS20-25-35E (single phase) FBQ-B8V1-B8V3B Split Heat Pump Condensing Units Split Sky Air
technical data RXS20-25-35E FBQ-B8V-B8V3B (single phase) Split Heat Pump Condensing Units air conditioning systems Split Sky Air Outdoor Units R-40A RXS-E2VB Split Sky Air Outdoor Units Features O u t
CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. ELECTRICAL SCHEMATIC DIAGRAM 13 5. EXPLOSION VIEW 16 6
TCL WALL MOUNTED SPLIT-TYPE AIR CONDITIONERS SERVICE MANUAL No.TE080528 Models KFTHP-12 KFTHP-18 KFTHP-24 CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. ELECTRICAL
How and Why Mission- Critical Cooling Systems Differ From Common Air Conditioners
How and Why Mission- Critical Cooling Systems Differ From Common Air Conditioners White Paper #56 Revision 2 Executive Summary Today's technology rooms require precise, stable environments in order for
TABLE OF CONTENTS. 1.1 Features... 1. 2.1 Control Interface Large Display... 4. 2.1.1 Navigating to Various Views in the Liebert icom...
Liebert icom User Manual -Intelligent Communications & Monitoring for Liebert Challenger 3000, Liebert CW and Liebert DS with Software Version PA2.01.48R TABLE OF CONTENTS 1.0 INTRODUCTION..........................................................1
SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS
SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS TABLE OF CONTENTS 1. Warnings...2 2. Accessibility Of Appliance...3 3. Unit Dimensions And Specifications...3 4. Unit Specifications
Dehumidification Frequently Asked Questions
Dehumidification Basics Why do you want to keep indoor Rh between 30-60%? ASHRAE recommends keeping the relative humidity in a home between 30-60% to limit the effects of many unwanted conditions and harmful
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2
Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MM14CHCSCS
Portable Air Conditioner OWNER S MANUAL Read these instructions before use Model: MM14CHCSCS Voltage rating: 120V~60Hz Power rating : 1400W(Cooling) Power rating : 1350W(Heating) Customer Support : 1-800-474-21477
SERVICE MANUAL MUZ-GE25VA - E1 MUZ-GE25VAH - E1 MUZ-GE35VA - E1 MUZ-GE35VAH - E1 MUZ-GE42VA - E1 MUZ-GE42VAH - E1 MUZ-GE50VA - E1 MUZ-GE50VAH - E1
SPLIT-TYPE AIR CONDITIONERS Revision A: MUZ-GE42/50VA(H) - E1 has been added. Please void OBH516. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH516 REVISED EDITION-A Models MUZ-GE25VA - E1 MUZ-GE25VAH
Single Zone LCD Thermostat Operating Instructions
Fan Cool Furnace *Heat Pump or Heat Strip On/Off F Single Zone LCD Thermostat Operating Instructions MODEL 3313192.XXX Cool/Furnace 3313193.XXX Cool/Furnace/Heat Pump 3313194.XXX Cool/Furnace/Heat Strip
Operating Instructions Split System Air Conditioner
Operating Instructions Split System Air Conditioner Model No. Indoor Unit Type Indoor Unit Type Nominal Capacity 26 36 F2 Low Silhouette Ducted S-26PF2U6 S-36PF2U6 Connectable outdoor unit lineup This
Data Center Precision Cooling: The Need For A Higher Level Of Service Expertise. A White Paper from the Experts in Business-Critical Continuity
Data Center Precision Cooling: The Need For A Higher Level Of Service Expertise A White Paper from the Experts in Business-Critical Continuity Executive Summary Today s data centers are changing rapidly,
REMOTE CONTROL MANUAL
REMOTE CONTROL MANUAL ENGLISH CONTENT PRECAUTIONS...1-2 USING THE REMOTE CONTROL UNIT...3 OPERATION...4-9 Thank you for purchasing our Room Air Conditioner. Before using your air-conditioner, please read
Please read this owner s Manual carefully before operating the unit. - Cooling - Heating - Dehumidifying - Fan
Please read this owner s Manual carefully before operating the unit. - Cooling - Heating - Dehumidifying - Fan TABLE OF CONTENTS INTRODUCTION 2 IMPORTANT SAFEGUARDS...2 PACKAGE CONTAINS..2 NAMES OF PARTS.3
Element D Services Heating, Ventilating, and Air Conditioning
PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer
COMPTROL 5000 INDEX 52. Issue 5.99 AIR CONDITIONING MICROPROCESSOR OPERATING INSTRUCTIONS. STULZ GmbH, Hamburg
COMPTROL 5000 INDEX 52 Issue 5.99 AIR CONDITIONING MICROPROCESSOR STULZ GmbH, Hamburg OPERATING INSTRUCTIONS Contents Page INTRODUCTION... 4 NOTES ON SAFETY... 4 PAGE CODE... 4 DESCRIPTION OF THE CONTROLLER...
SWIMMING POOL HEAT PUMP
SWIMMING POOL HEAT PUMP Installation & User Manual Model HP40B HP50B HP65B Hayward Pool Products Canada, Inc. T: 1-888-238-7665 www.haywardpool.ca CONTENT I. Application 4 II. Features 4 III. Technical
UR...3 URX CF...7 URHE CF...11. Heat recovery unit. Heat recovery unit with refrigerant circuit(442-1947 cfm)
UR...3 Heat recovery unit URX CF...7 Heat recovery unit with refrigerant circuit(442-1947 cfm) URHE CF...11 High efficiency heat recovery unit with refrigeration circuit(588-1942 cfm) UR Heat recovery
Failure code manual. content
Failure code manual content 一 wall split AC series 2 二 floor standing AC series. 4 三 portable AC series.. 5 四 dehumidifer 6 五 DC inverter single split series...7 六 DC inverter multi-split series 10 1 一
Oil and Coolant Circulating Heating System. Model - OCSM
Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine
Tech Byte 27: Small Computer Room and IT Closet Cooling
Questions Answered in This Paper Sensible cooling capacity is the measuring stick for IT cooling capacity needs. What is the sensible cooling capacity of the comfort split system in comparison to the precision
york air-conditioning products Residential & VRF News 2015
york air-conditioning products Residential & VRF News 2015 york air-conditioning products Catalogue Content Split Systems Pag. High wall High Efficiency Inverter YWHJZH 09 to 24 K 6 High wall Inverter
Liebert DS Thermal Management Unit
Liebert DS Thermal Management Unit System Design Manual - 28-105kW (8-30 Tons), Downflow/Upflow, 60Hz Floor Mounted, Air-Cooled, Water/Glycol-Cooled, GLYCOOL Economizer Coil, Dual-Cool DX with Secondary
Gree Solar Hybrid Hi Wall Inverter Air Conditioner
Gree Solar Hybrid Hi Wall Inverter Air Conditioner Utilize the natural power of the sun to heat or cool your home. Find out more at www.greeonline.com Why Choose a Solar Hybrid Inverter? The new Gree Solar
SERVICE INSTRUCTION R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit
SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit ASYG07LECA ASYG09LECA ASYG12LECA ASYG14LECA AOYG07LEC AOYG09LEC AOYG12LEC AOYG14LEC R410A CONTENTS
USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR
USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR CONTENTS Introduction Safety Notes Identification of parts Installation instructions Operation instructions Maintenance Troubleshooting
ROOFTOP - HEAT PUMP UNIT. This document applies when installing into an air handler or as part of an air handling system.
ROOFTOP - HEAT PUMP UNIT Technical data Applies to Model YNRA R410A This document applies when installing into an air handler or as part of an air handling system. CONTENTS 1. General description... 2
DESIGN STANDARDS SECTION 23 60 00
PART 1 - GENERAL 1.01 Work included: A. Piping, tubing and fittings. B. Piping specialties. C. Special duty valves. D. Refrigerants. E. Chillers. F. Refrigerant monitors. 1.02 General requirements: A.
KINGDOM OF SAUDI ARABIA SAUDI ARABIAN STANDARDS ORGANIZATION SASO. SAUDI STANDARD DRAFT No. 3457/2005
KINGDOM OF SAUDI ARABIA SAUDI ARABIAN STANDARDS ORGANIZATION SASO SAUDI STANDARD DRAFT No. 3457/2005 NON-DUCTED AIR CONDITIONERS AND HEAT PUMPS TESTING AND RATING PERFORMANCE This standard is developed
CoolTop. A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60
CoolTop A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60 Application CoolTop is a new, unique air conditioning unit especially designed for datacenters.
Circuit breaker panel. Power supply for condensing unit. Power supply for furnace. Air handler (Furnace)
UNIT OBJECTIVES Describe the concept of year-round air conditioning List three typical year-round air conditioning system types List the five ways to condition the air Determine airflow for a cooling system
FOXAIR 60/50 ALL MODELS
FOXAIR 60/50 ALL MODELS OPERATION AND SERVICE MANUAL UNIT WEIGHT - ALL MODELS APPROX. 300 POUNDS FOXTRONICS, INC. 38 L x 28 W x 24 H Love Field-Dallas TX MADE IN THE USA 3448 West Mockingbird Lane Dallas,
Technical Service Manual. Version One
[Gree Central Air Conditioner] Technical Service Manual Ducted type unit 2.3KW-16KW Version One GREE ELECTRIC APPLIANCES.INC.OF ZHUHAI - 1 - FG Series wind pipe blowing air-conditioning unit Section One:
Use and Care Manual. Model CPA12KH AIR CONDITIONER
Use and Care Manual Model CPA12KH AIR CONDITIONER Introduction Thank you for choosing this air conditioner to provide you and your family with all of the "Home Comfort" requirements for your home, cottage
SERVICE MANUAL SPLIT SYSTEM ROOM AIR CONDITIONER SHARP CORPORATION SHARP CORPORATION CONTENTS
SERVICE MANUAL SPLIT SYSTEM ROOM AIR CONDITIONER INDOOR UNIT AH-129 AH-MP14 OUTDOOR UNIT AU-129 AU-MP14 CONTENTS SPECIFICATIONS...2 EXTERNAL DIMENSIONS...4 WIRING DIAGRAMS...5 ELECTRICAL PARTS...6 MICROCOMPUTER
T5000 T000 LCD Digital Fan Coil Thermostat
T5000 T000 LCD Digital Fan Coil Thermostat T000 LCD Digital Fan Coil Thermostat T000 LCD Digital Fan Coil Thermostats are designed to control heating, cooling, or year round air conditioning unit in Commercial,
hore PRODUCT CATALOGUE nd Offsh arine an ms for Ma & Refrig AUTONOMOUS AIR CONDITIONERS HV VAC &
hore nd Offsh arine an ms for Ma geration System & Refrig HV VAC & PRODUCT CATALOGUE AUTONOMOUS AIR CONDITIONERS O ! "# $ % & " ' (! ) * +,+( -../01..2 PRODUCT CATALOGUE 72-17 AUTONOMOUS AIR CONDITIONERS
Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MM14CCS. Voltage rating: 115V~60Hz Power rating : 1400W
Portable Air Conditioner OWNER S MANUAL Read these instructions before use Model: MM14CCS Customer Support : 1-800-474-2147 Voltage rating: 115V~60Hz Power rating : 1400W For product inquiries or support
CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. WIRING DIAGRAM 11 5. EXPLOSION VIEW 12 6.
TCL WALL MOUNTED SPLIT-TYPE AIR CONDITIONERS SERVICE MANUAL No.TE051220 Models TAC-09CHSA/GI TAC-12CHSA/GI CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. WIRING DIAGRAM
D SERIES MODULAR AIR-COOLED SCROLL CHILLER. TECHNICAL SALES GUIDE-50Hz CAPACITY RANGE:65~130kW SUPER HIGH AMBIENT OPERATION TO 43
D SERIES MODULAR AIR-COOLED SCROLL CHILLER TECHNICAL SALES GUIDE-50Hz CAPACITY RANGE:65~130kW SUPER HIGH AMBIENT OPERATION TO 43 CONTENTS 1.MODELS LIST... 3 2.NOMENCLATURE... 3 3.FEATURES... 3 4.PRODUCT
New Deluxe Wall Mounted Heat Pump Series EXTERIOS
New Deluxe Wall Mounted Heat Pump Series EXTERIOS May 2013 New Deluxe Wall Mounted Heat Pump Series Panasonic Adding New Air Conditioner Lineup Setting Another Mile Stone in the US Ductless Split History
Cool Design for Homes and Offices
AIR BLUE AIR BLUE air conditioning Homes Easy to install and use, quiet, attractive, and designed to fit any space: there are Cool Design for Homes and Offices a lot of reasons why Air Blue air conditioners
HVAC Processes. Lecture 7
HVAC Processes Lecture 7 Targets of Lecture General understanding about HVAC systems: Typical HVAC processes Air handling units, fan coil units, exhaust fans Typical plumbing systems Transfer pumps, sump
ELECTRIC CENTRAL HEATING FLOW BOILER
ELECTRIC CENTRAL HEATING FLOW BOILER EKCO.T Used product can t be treated as general communal waste. Disassembled appliance has to be delivered to the collection point of electrical and electronic equipment
International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS
International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES
Service manual. Website: www.andico.com.au CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.
Website: www.andico.com.au Service manual CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL. - ONLY FOR AUTHORISED SERVICE PERSONNEL. MODELS: MPK1-09CR-QB8 MPK1-12ER-QB6
SWIMMING POOL AIR-HANDLING UNITS KU-DB Series
SWIMMING POOL AIR-HANDLING UNITS KU-DB Series ME20 proklima 2 SWIMMING POOL AIR-HANDLING UNITS - KU-DB Series proklima 3 TABLE OF CONTENTS 1 Introduction page 3 2 Features page 4 SWIMMING POOL AREA t =
Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency
A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency
Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MN12CES / MN10CESWW
Portable Air Conditioner OWNER S MANUAL Read these instructions before use 8 Model: MN12CES / MN10CESWW Voltage rating: 120V~60Hz Power rating : 1100W (MN12CES) Power rating : 900W (MN10CESWW) Customer
EasiCool EZRE. Operation and Maintenance Manual
EasiCool EZRE Operation and Maintenance Manual EasiCool EZRE Precision Air Conditioning Introduction Warranty, Commissioning & Maintenance As standard, Airedale guarantees all non-consumable parts only
PORTABLE AIR CONDITIONER
VERY IMPORTANT! MODEL: GDC-AC9RW / GDC-AC9RCS GDC-AC9RCW / GDC-AC12RW GDC-AC12RB / GDC-AC12RCB GDC-AC12RCW INSTRUCTIONS FOR USE PORTABLE AIR CONDITIONER Do not install and use your portable air conditioner
HEAT HEAT COOL HEAT PUMP COOL
OWNER S MANUAL RESIDENTIAL THERMOSTAT P/N P374-1800 HEAT COOL HEAT PUMP Su AUTO 0I20: Pm 74 COOL HEAT 27 7-DAY MABLE DIGITAL THERMOSTAT 3 Configurable Outputs Accepts Optional Humidity Module: Control
Liebert Deluxe System/3
Precision Cooling For Business-Critical Continuity Liebert Deluxe System/3 Operation and Maintenance Manual 50 and 60 Hz, 6-30 Ton DX Systems (DH/DE/VH/VE); 12-60 Ton CW Systems (FH/UH) TABLE OF CONTENTS
Dehumidifier D 850E. - Instruction manual version 02
Dehumidifier D 850E - Instruction manual version 02 Content 1. Description of dehumidifier 1.1. General data 1.2. Technical data 2. Operation and usage 2.1. Usage 2.2. Location and installation 2.3. Preparing
www.inspection-for-industry.com
Quality Control Form (TEST RUNNING RECORD FOR AIR HANDLING UNIT) SUB POWER SUPPLY: MAIN POWER V, Hz, CONTROL V, Blower 1 kw, Blower 2 kw, Compressor: (1) kw (2) kw (3) kw (4) kw Heating Element: kw 1.
REFRIGERATED TYPE COMPRESSED AIR DRYERS INSTRUCTION MANUAL. For Sales & Service please contact:
7610.478.16 8/99 INSTRUCTION MANUAL Models 8005, 8010, 8015 For Sales & Service please contact: CENTRAIR Air Systems & Supplies Phone: 705-722-5747 Fax: 705-722-5458 Email: [email protected] Website: www.centrair.ca
Air Conditioner Water Heater - A Product of HotSpot Energy LLC
Air Conditioner Water Heater - A Product of HotSpot Energy LLC PLEASE READ THIS BEFORE YOU INSTALL THE UNIT 1. This air conditioner must be installed and/or repaired by a qualified technician. If you perform
Midea Commercial Air Conditioner Malfunction Handbook
Midea Commercial Air Conditioner Malfunction Handbook May 1, 2008 Customer Service Philosophy of Midea Air Conditioner Service Target: 100% Customer Satisfaction Service Standard: 100% Earnestness Service
Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MF08CESWW. Voltage rating: 115V~60Hz Power rating : 800W
MODE ALARM Portable Air Conditioner OWNER S MANUAL Read these instructions before use 8 Model: MF08CESWW Voltage rating: 115V~60Hz Power rating : 800W Customer Support : 1-800-474-2147 For product inquiries
Why and How we Use Capacity Control
Why and How we Use Capacity Control On refrigeration and air conditioning applications where the load may vary over a wide range, due to lighting, occupancy, product loading, ambient weather variations,
SERVICE MANUAL OUTDOOR UNIT. No. OBH590 REVISED EDITION-B. Models HFC
SPLIT-TYPE AIR CONDITIONERS Revision B: MUZ-EF25/35/42/50VE - E2 and MUZ-EF25/35VEH - E2 have been added. Please void OBH590 REVISED EDITION-A. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH590 REVISED
Why Do I Need Precision Air Conditioning?
Why Do I Need Precision Air Conditioning? Executive Summary Today's technology rooms require precise, stable environments in order for sensitive electronics to operate optimally. Standard comfort air
Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty
Codes Room Air Conditioner range: Indoor unit alarm s If timer lamp flashes for 1 second on, 1 second off, this indicates pre heating on the coil during heating mode and is not an error. If timer lamp
Liebert CW 26-181kW Chilled Water Cooled Precision Air Conditioning For Data Centers
Liebert CW 26-181kW Chilled Water Cooled Precision Air Conditioning For Data Centers Precision Cooling For Business-Critical Continuity A Chilled Water Precision System That Handles The Most Demanding
Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw
4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and
BlueSolar Pro Remote Panel For BlueSolar PWM-Pro charge controllers 12/24V 5, 10, 20, 30A Article number SCC900300000
Manual EN BlueSolar Pro Remote Panel For BlueSolar PWM-Pro charge controllers 12/24V 5, 10, 20, 30A Article number SCC900300000 Contents EN 1.Important safety instructions... 2 2. Installation... 2 3.Product
Chilled Water HVAC Systems
Chilled Water HVAC Systems By Ron Prager, Brinco Mechanical Services, Inc. Types of water based systems: There are three types of HVAC systems that utilize water as a heat transfer medium. The first system,
PRODUCT PRODUCT CODE TECHNICAL INSTRUCTIONS PAGE
Table of Contents PRODUCT PRODUCT CODE TECHNICAL INSTRUCTIONS PAGE # Electric Room Comfort Controller NEW! RDY2000 Room Comfort Controller RDY 129-905 D-3 Electric for Specialized Applications Surface
Monitoring Network DMN
Monitoring Network DMN User Manual Table of contents Table of contents... 2 1. Product features and capabilities... 3 2. System requirements... 5 3. Getting started with the software... 5 3-1 Installation...
sip Sanyo Modbus Guide Technical Specification Pinouts, Cable Connections & Wiring Issue 2: February 2009 Synapsys Solutions Ltd, all rights reserved
Sanyo Section : Section : Section : Section : Section : sip Modbus Guide Configuration Modbus Table Technical Specification Pinouts, Cable Connections & Wiring Alarm Fault Codes Issue : February 009 Section
543-0032-00, 943-0032-00. User s Manual
543-0032-00, 943-0032-00 User s Manual 1 Comfort Alert Diagnostics Faster Service And Improved Accuracy The Comfort Alert diagnostics module is a breakthrough innovation for troubleshooting heat pump and
