Circuit Breakers in Data Centers: The Hidden Danger

Size: px
Start display at page:

Download "Circuit Breakers in Data Centers: The Hidden Danger"

Transcription

1 Circuit Breakers in Data Centers: The Hidden Danger How to efficiently protect critical IT equipment by choosing the most reliable overcurrent protection device for your Rack Power Distribution Unit. By Dr. Jim Anderson and Mike Jansma Contents Introduction... 1 How Are Servers Kept On All the Time... 1 Overcurrent Protection Devices... 1 The Problem with Fuses in a Data Center... 3 Circuit Breakers and PDUs: A Match Made In Heaven... 3 All PDU Circuit Breakers Are Not Created The Same... 4 Conclusion... 6 About the Authors... 7 About Enlogic... 7

2 Introduction How much does a modern data center cost? Millions? Hundreds of millions? The total cost of building a data center is increasing every day. Why do these buildings cost so much? The answer is simple: the job that they do is hard to do perfectly. A modern data center is designed to provide a secure, reliable home to hundreds (or even thousands) of servers servers that run mission critical software for companies all over the world. One part of a data center's job is to provide reliable, clean, power to each of the servers in the data center. Here in the 21 st century, that part of the job would be relatively simple, right? In our homes, when we flip switches things happen: lights turn on, the computer powers up, or the TV flickers on. However, think about all of the times that you've lost power or how often the lights flicker. A data center is designed to prevent these events. When it comes to the job of providing power to servers, data center designers have two primary tasks to accomplish: to provide reliable power and avoid unsafe operating conditions. But doing this is more difficult than you might imagine. How Are Servers Kept On All the Time? To ensure that servers always have power, data center designers go to great lengths. They often build two completely separate and redundant electrical power distribution systems along with multiple types of power backup solutions. These expensive and complex solutions ensure that if power to the data center is ever lost, backup systems can quickly provide the needed energy. Additionally, if there is ever a failure of one of the redundant power systems, the secondary system can provide the required electricity until the failed system is repaired. What makes all of the expensive design so fascinating is that it all comes down to a single component to ensure that all of the servers continue to receive the energy required in order to stay powered up: the rack power distribution unit (rack PDU). The rack PDU receives electricity from the data center's redundant power delivery systems and it is responsible for delivering that energy to the individual servers and IT equipment. If the rack PDU fails, then the attached servers will fail. The rack PDU is a data center operator's last line of defense against accidental circuit overloads and harmful faults. In many countries, the rack PDU includes design features that are required by electric code and mandatory industry standards requiring protection against these events. As such, rack PDU vendors incorporate solutions to for these occurrences. Overcurrent Protection Devices While most servers and IT equipment have become more energy efficient, the total energy demand required per unit has risen dramatically over the past 15 years from an average power density of 1-2 kw to an average of 4-6 kw per rack. Some high density IT racks have power loads of 20 kw and above. Page 1 of 7

3 These increasing rack power densities have led to dramatically larger input power feeds to the rack PDU devices. Rack PDUs are no longer built similarly to the power strip under your desk. Today, the most common power feed is a single phase, V input rated at 30-32A (depending on regional codes). Some have three-phase inputs with ratings as high as 23 kw and higher. At these high power densities, the amount of heat generated in the electrical conductor wires becomes substantial and dangerous if not limited to thermal design specification. These thermal limits are strained as the data center hot aisle temperatures become warmer due to higher power density. Thermal limits are additionally burdened with energy efficiency initiatives such as raising the operating temperature due to the new data center industry thermal standards (set about by ASHRAE). When electrical circuits are exposed to overcurrent or excessive temperatures, the conductor insulation melts and there is a real danger of smoke, fire, and electrical shorting faults, all of which create a danger to data center workers. Today s rack PDU requires Overcurrent Protective Devices (OCPD) to mitigate the overcurrent risks in the rack PDU and IT equipment. As more IT equipment is consolidated into fewer, more densely packed IT equipment racks, it has become critical to isolate potential electrical faults within one server rack in order to protect upstream power distribution equipment. There are 2 major types of OCPD used in today's rack PDU: supplemental protectors and branch-rated OCPD. Supplemental protective devices are devices that serve a single purpose: limit the total current output of a circuit. However, they are prone to inconsistent protection characteristics, highly sensitive to the surrounding thermal environment, and incapable of protecting circuits in failure situations. These types of highly disruptive faults pass by the supplemental protector (often the device fails) and usually result in upstream circuit breaker tripping to contain the fault with additional servers and IT equipment placed at risk for surge damage and dropped loads. These simple overcurrent protective devices might conform to and be labeled with industry standards including UL1077, UL489A, or other local standards. Conversely, branch rated circuit OCPD devices provide comprehensive protection against simple circuit current overload and isolation protection for harmful equipment circuit fault conditions. As the power density of IT racks climb, these fault protection devices become more critical to both reliability and safety. In many cases, protection is required by electric codes and industry standards. When a short circuit or ground fault failure occurs, the branch rated OCPD can normally respond by opening the circuit to isolate the fault to only the attached equipment. Often these OCPD devices are labeled to conform to branch rated standards such as UL. Figure 1 shows some typical examples of the OCPD used in IT rack PDUs. To further complicate the selection process, there are multiple technologies used in both supplemental and branch rated OCPD devices. Simple thermal fuses are the most basic technology, while resettable circuit breakers are the most common OCPD device utilized in most rack PDU devices. The most professional-grade rack PDUs will use non-thermal based, hydraulic-magnetic (hy-mag) circuit breakers to provide the most comprehensive overcurrent and fault protection within the rack PDU. Page 2 of 7

4 The Problem with Fuses in a Data Center How does a PDU keep the data center servers safe from dangerous overcurrent and fault conditions? There are many ways for a PDU to do this, but the least expensive method (in terms of cost to PDU vendors) is by the use of thermal fuses. Fuses are a special type of resistor that exists for one purpose: to fail when exposed to electrical currents beyond the designed capacity. A fuse works by flowing the electrical current through a piece of metal designed to melt when the current exceeds the rated limit. When an overcurrent condition occurs, the metal melts and the circuit is prevents electrical flow. The servers will lose power; however, if the fuse melts quickly enough the servers will not be damaged or destroyed. Because the fuse is designed to melt as a function of temperature, the use of fuses in thermally hot environments requires a derating of the current carrying capacity. In a data center, this means that a fuse rated for 16A or 20A might melt (or fail) at electrical currents lower than the designed. Failure to account for this derating results in a tripping of the fuse during normally safe operation. Fuses have other negative attributes for use in a data center. Sure, a fuse can step in and save the servers in an overcurrent event, however, it's what you have to do after such an event that makes fuses no longer an acceptable solution for data center application. Once a fuse has blown, it must be replaced. This replacement is dangerous for the user. As a result, the entire rack PDU must be powered down. Often this type of replacement must be performed by a licensed electrician. And the electrician must have the correct fuses on hand to replace the blown fuse. Considering that if a current overload condition occurs, you'll probably have fuses in all of the PDUs that are connected to that power source blow, you may be looking at an expensive and time consuming repair job. As long as those blown fuses are still installed in PDUs, all of the servers are running on a single backup power source. If a fault occurs to that power source, all of the attached severs will be lost. While fuses are inexpensive, recovering from a blown fuse can be devastating in terms of cost and downtime in the data center environment. Circuit Breakers and PDUs: A Match Made In Heaven The good news is that there is a much better solution: circuit breakers. Circuit breakers detect overcurrent (or fault) situations and break the electrical circuit providing power. How they do this and how well they do it is what distinguishes one PDU from another. There are several differences between fuses and circuit breakers. One of the most important differences is that unlike a fuse, when a circuit breaker trips because a circuit overload, no replacement is required it can be reset manually or automatically by data center operators. In a circuit breaker, an internal pilot device senses a fault current and trips the device. When a circuit overload condition occurs, contacts in the circuit breaker have to open to interrupt the circuit. To separate the metal contacts mechanically, stored energy within the breaker opens the circuit. Page 3 of 7

5 All PDU Circuit Breakers Are Not Created the Same So circuit breakers are better than fuses in a PDU, end of story, right? Well, no. There are different types of circuit breakers available. Different types of circuit breakers have different costs and physical size. When vendors build rack PDUs, they have to make a cost / benefit decision about which circuit breaker they will use. The type of circuit breaker has a significant impact on how well servers are protected against fault conditions and accidental tripping. Two different types of circuit breakers are often used in PDUs, and although these two different types of circuit breakers perform the same job, they do it differently based on performance characteristics Thermal-based circuit breakers Hydraulic-magnetic (hy-mag) circuit breakers Thermal Fuse Thermal Circuit Breaker Hydraulic Magnetic Circuit Breaker UL248 type UL489 Thermal type UL489 Hydraulic-Magnetic type Branch Rated OCPD Supplemental Protector Figure 1. Typical OCPD found in IT Rack PDUs. Thermal-based circuit breakers are also known as thermal circuit breakers or thermal-magnetic circuit breakers. These thermal-based circuit breakers are made using a bi-metallic strip. This strip has two different pieces of metal welded together; each meant to expand when in contact with the heat of an electric current. With two different kinds of metal, the expansion rate for each is different. The thermal based circuit breaker depends on the heat generated by the passing electrical current; the greater the heat, the more severely the metal strip bends. When there is an electric overload, the heat generated bends the strip enough to pull the circuit level to the off position, protecting the wiring from damage. When a thermal circuit breaker is reset, it is likely to trip again if the overload condition still exists. Page 4 of 7

6 Breaker Derating as % of Nameplate The problem with using a thermal circuit breaker in a PDU is that they are susceptible to unintended tripping when used in high temperature environments. Because the PDU is contained in a rack and is exposed to high temperatures, the PDU's thermal circuit breaker can accidentally trip and lose power. Figure 2 illustrates how the trip setting of a typical thermal circuit breaker changes due to ambient temperature; for many rack PDUs, the trip setting can vary by more than 15%. 130% 120% 110% 100% 90% 80% 70% Ambient Temperature, C Figure 2. Temperature Derating Curve for Typical Thermal Circuit Breaker. Another challenge when using a thermal circuit breaker is the tripping temperature changes by more than 15% over the rack PDU's operating temperature specification! Thermal circuit breaker vendors recommend a PDU load current at 80% or less of the rated current to account for the variation in temperature that the external rack temperature can cause a trip. This restricts total power output per rack, and results in unplanned downtime conditions. An alternative type of circuit breaker used in a PDU is the type used by Enlogic: the hydraulic-magnetic, or hy-mag, circuit breaker. The hy-mag breaker is independent of temperature as a tripping mechanism Hy-mag breaker's tripping mechanism does not use thermal elements (bimetal) and is not affected by ambient rack temperature. Rather, the current load is connected through a solenoid coil. At currents above the circuit breaker rating, the coil generates magnetic flux necessary to force a spring mechanism to open the electrical circuit and prevent current flow through the breaker. What this means is that the tripping current is related to the amount of current only; the hy-mag breaker will keep consistent tripping characteristics across the entire range of data center ambient temperatures. When a circuit breaker trips, the data center operator wants the affected servers powered up as quickly as possible. This is where another big difference between fuses and circuit breakers, and further between thermal and hydraulic-magnetic circuit breakers becomes clear. When a circuit breaker trips or fuse blows, users should explore why the event occurred and take action to prevent reoccurrence. However, in the case of a fuse: the entire rack PDU must be powered down and specially trained personnel must replace the blown fuse. In the case of the resettable circuit breaker: the circuit failure is often isolated to just one portion of the rack PDU output. Users can independently eliminate the fault condition and reset the circuit breaker Page 5 of 7

7 without powering down the remainder of the rack PDU. Further, circuit breakers don t require specially trained personnel to reset the device after failure. When a hydraulic-magnetic circuit breaker is tripped, it provides the ability to be instantaneously reset once you've corrected the cause of the circuit failure. This is not the case with thermal circuit breakers. With thermal circuit breakers, once the bimetal has been bent due to the tripping event, it does not immediately return to its original position. Instead, this circuit breaker remains tripped until the bimetal is cooled. The time from the circuit breaker tripping until it can be reset is called the reset time. Reset time can vary between 3 20 minutes depending on the breaker. Conclusion Currently, there are PDUs in data centers without any fuses or circuit breakers. These PDUs leave servers exposed and vulnerable to the fluctuating power system. With ever-growing rack power density, and increasingly variable power loads in the IT rack, the need for comprehensive circuit overload and fault protection is increasingly important. The two types of protection available include fuses and circuit breakers. Fuses are an older technology that requires problematic downtime and specialized effort to replace. Circuit breakers come in two primary types: thermal and hydraulic-magnetic circuit breakers. Thermal circuit breakers are susceptible to the ambient heat generated in a rack environment and are subject to accidental tripping. Hydraulic-magnetic circuit breakers, such as those used in Enlogic PDUs, provide comprehensive protection against circuit overload and isolation of faults. Unlike the thermal breakers, Enlogic s hydraulic-magnetic breakers are unaffected by heat and can be reset immediately after being tripped. Page 6 of 7

8 About the Authors Dr. Jim Anderson - Dr. Anderson is the Director of Product Line Management for Enlogic. He is responsible for ensuring that Enlogic creates the correct products with the correct features. Dr. Anderson received his Ph.D. in Computer Science from Florida Atlantic University and his MBA from the University of Texas at Dallas. He has worked as a Director of Product Line Management for a number of very large firms including Verizon, Alcatel, Siemens, and Boeing as well as working at a number of successful startups. Dr. Anderson is also a senior member of the Institute for Electrical and Electronics Engineers (IEEE) and holds a senior management position in the U.S. branch of the organization. Mike Jansma Mike Jansma is Co-founder and Chief Marketing Officer of Enlogic. As a technology innovation leader, Mike has an exceptional history of listening to customers, digging into complex problems, and providing innovative solutions for real customer pains in energy technology and power distribution fields. To date, Mike holds 7 technology patents with additional technology patents pending. Prior to founding Enlogic, Mike received his Bachelors and Masters degrees in Mechanical Engineering from The Illinois Institute of Technology and an MBA from Washington University in St. Louis. Mike began his career in Energy Technology at the US Department of Energy s Argonne National Laboratory. Later he held technical and marketing leadership positions at ABB and Schneider Electric/APC. About Enlogic Enlogic is a new company that makes an entire family of world class 4 th generation PDUs. Founded by the engineers who created the first three generations of PDUs that are on the market, Enlogic's PDUs are revolutionary in how reliable they are and how easy they are to both install and support. Enlogic's PDUs are amazingly slender in order to not interfere with any hot-swappable server components, they use hydraulic-magnetic circuit breakers and are temperature rated up to degree C in order to ensure proper operation in today's increasingly hot data center environment, and they feature Enlogic's novel field replaceable network control card that permits equipment changes without having to power down connected servers. You won't find these features in anyone else's PDUs, including any APC PDU. To find out more about what are arguably the world's best 4 th generation PDUs, contact your local Enlogic sales representative in order to request more information or even better, to set up an appointment to see what makes Enlogic's PDUs the right choice for your data center. Page 7 of 7

Data Center Power Overload Protection: Circuit breakers and branch circuit protection for data centers

Data Center Power Overload Protection: Circuit breakers and branch circuit protection for data centers Data Center Power Overload Protection: Circuit breakers and branch circuit protection for data centers 2009, Raritan Inc. Introduction Over the past few years, average power consumption per server has

More information

Considerations for a Highly Available Intelligent Rack Power Distribution Unit. A White Paper on Availability

Considerations for a Highly Available Intelligent Rack Power Distribution Unit. A White Paper on Availability Considerations for a Highly Available Intelligent Rack Power Distribution Unit A White Paper on Availability Introduction Data centers are currently undergoing a period of great change. Data center managers

More information

Proper Application of 415V Systems in North American Data Centers. A White Paper from the Experts in Business-Critical Continuity

Proper Application of 415V Systems in North American Data Centers. A White Paper from the Experts in Business-Critical Continuity Proper Application of 415V Systems in North American Data Centers A White Paper from the Experts in Business-Critical Continuity Introduction Increasing pressure to reduce operating expenses and be more

More information

Advantages of a Company Switch vs. a Safety Switch Receptacle Combination:

Advantages of a Company Switch vs. a Safety Switch Receptacle Combination: Advantages of a Company Switch vs. a Safety Switch Receptacle Combination: Why a Company Switch Delivers Greater Benefits A Lex Products Corporation Whitepaper. Copyright 2012. Overview: Advantages of

More information

Optimizing Power Distribution for High-Density Computing

Optimizing Power Distribution for High-Density Computing Optimizing Power Distribution for High-Density Computing Choosing the right power distribution units for today and preparing for the future By Michael Camesano Product Manager Eaton Corporation Executive

More information

Electrical Resistance Resistance (R)

Electrical Resistance Resistance (R) Electrical Resistance Resistance (R) Any device in a circuit which converts electrical energy into some other form impedes the current. The device which converts electrical energy to heat energy is termed

More information

Power Distribution Considerations for Data Center Racks

Power Distribution Considerations for Data Center Racks Power Distribution Considerations for Data Center Racks Power Distribution Considerations for Data Center Racks Table of Contents 3 Overview 4 At what voltage do you run all the IT equipment? 4 What electrical

More information

Fundamentals of Power

Fundamentals of Power Fundamentals of Power Fundamentals of Power 2008 American Power Conversion Corporation. All rights reserved. All trademarks provided are the property of their respective owners. Learning Objectives At

More information

Fuses. Introduction. Measuring is knowing. Who chooses?

Fuses. Introduction. Measuring is knowing. Who chooses? Fuses Introduction. There are many theories going around about the necessity for protecting PDUs (Power Distribution Unit / multiple socket / socket, etc.). A fuse is by definition a Single Point of Failure

More information

Data Center Power Distribution at the Cabinet Level: The top 12 questions you need to ask to improve data center energy effciency

Data Center Power Distribution at the Cabinet Level: The top 12 questions you need to ask to improve data center energy effciency Data Center Power Distribution at the Cabinet Level: The top 12 questions you need to ask to improve data center energy effciency White Paper STI-100-010 November 2013 HEADQUARTERS - NORTH AMERICA Server

More information

Visit us on the web: www.autoshop101.com

Visit us on the web: www.autoshop101.com This Automotive Series CIRCUIT PROTECTION has been developed by Kevin R. Sullivan Professor of Automotive Technology Skyline College All Rights Reserved Visit us on the web: www.autoshop101.com CIRCUIT

More information

Section B: Electricity

Section B: Electricity Section B: Electricity We use mains electricity, supplied by power stations, for all kinds of appliances in our homes, so it is very important to know how to use it safely. In this chapter you will learn

More information

Server Technology Inc.

Server Technology Inc. Server Technology Inc. Alternating Phase Power Distribution at the Data Center Rack PDU White Paper STI-100-012 2013-April-18 By Steve Hammond, Product Manager, Server Technology Headquarters Server Technology,

More information

Mission Critical Data Center Systems

Mission Critical Data Center Systems Mission Critical Systems Mission Critical/ Electrical Distribution Systems Data center electrical distribution designs are rapidly evolving, driven by needs such as increasing power densities, energy efficiency,

More information

How SafePlug Smart Receptacles Can Save Money in Commercial Buildings

How SafePlug Smart Receptacles Can Save Money in Commercial Buildings How SafePlug Smart Receptacles Can Save Money in Commercial Buildings by Steve Montgomery, P.E. 2D2C, Inc. SafePlug smart receptacle system add the ability to accurately identify exactly what appliance

More information

101 BASICS SERIES LEARNING MODULE 3: FUNDAMENTALS OF ELECTRICAL DISTRIBUTION. Cutler-Hammer

101 BASICS SERIES LEARNING MODULE 3: FUNDAMENTALS OF ELECTRICAL DISTRIBUTION. Cutler-Hammer 101 BASICS SERIES LEARNING MODULE 3: FUNDAMENTALS OF ELECTRICAL DISTRIBUTION Cutler-Hammer WELCOME Welcome to Module 3, Fundamentals of Electrical Distribution. If you have successfully completed Module

More information

Power to the adaptable data center

Power to the adaptable data center Business Unit Manager, Data Center Solutions, Eaton s electrical group IT managers have more options than ever to tailor the power infrastructure to their unique data center and business requirements.

More information

What are the basic electrical safety issues and remedies in solar photovoltaic installations?

What are the basic electrical safety issues and remedies in solar photovoltaic installations? What are the basic electrical safety issues and remedies in solar photovoltaic installations? Presented by: Behzad Eghtesady City of Los Angeles Department of Building and Safety Topics Covered Photovoltaic

More information

Alternating Phase Power Distribution at the Data Center Rack PDU

Alternating Phase Power Distribution at the Data Center Rack PDU Alternating Phase Power Distribution at the Data Center Rack PDU White Paper STI-100-012 November 2013 - Updated August 2014 By Steve Hammond, Product Manager, Server Technology Marc Cram, Director of

More information

Motor Protection Voltage Unbalance and Single-Phasing

Motor Protection Voltage Unbalance and Single-Phasing Motor Protection Voltage Unbalance and Single-Phasing Cooper Bussmann contributes the following information, which is an excerpt from their 190-page handbook SPD Selecting Protective Devices Based on the

More information

Dynamic Power Variations in Data Centers and Network Rooms

Dynamic Power Variations in Data Centers and Network Rooms Dynamic Power Variations in Data Centers and Network Rooms By Jim Spitaels White Paper #43 Revision 2 Executive Summary The power requirement required by data centers and network rooms varies on a minute

More information

Help protect your home, possessions and family.

Help protect your home, possessions and family. Help protect your home, possessions and family. A guide to your Square D electrical distribution system SM Make the most of your energy Understanding your home s electrical distribution system As one of

More information

ALUMINUM ELECTRICAL WIRING

ALUMINUM ELECTRICAL WIRING ALUMINUM ELECTRICAL WIRING prepared by Fire Prevention and Investigation Division Denver Fire Department Department of Safety and Electrical Inspections Section Denver Building Inspection Division Community

More information

Common Power Problems & Power Protection Solutions

Common Power Problems & Power Protection Solutions W H I T E P A P E R Common Power Problems & Power Protection Solutions Executive Summary All systems, from home theaters and office desktops to enterprise IT equipment in data centers, are prone to downtime,

More information

Protect your home and family with Advanced Technology from Cutler-Hammer

Protect your home and family with Advanced Technology from Cutler-Hammer Protect your home and family with Advanced Technology from Cutler-Hammer Residential Home Fire Statistics Annually - over 415,000 Residential Fires Annually - over 40,000 electrical fires over 350 deaths

More information

Inverter / Charger Installation General Operations and AC and DC Connections

Inverter / Charger Installation General Operations and AC and DC Connections Inverter / Charger Installation General Operations and AC and DC Connections The Inverter is just one piece. Sometimes, a tendency is to mount the inverter and batteries, and make it work It is better

More information

Server Technology, Inc.

Server Technology, Inc. Server Technology, Inc. Branch Circuit Protection: Power Distribution for IT Equipment in the Data Center Server Technology, Inc. 1040 Sandhill Drive Reno, NV 89521 +1 (775) 284-2000 www.servertech.com

More information

Dynamic Power Variations in Data Centers and Network Rooms

Dynamic Power Variations in Data Centers and Network Rooms Dynamic Power Variations in Data Centers and Network Rooms White Paper 43 Revision 3 by James Spitaels > Executive summary The power requirement required by data centers and network rooms varies on a minute

More information

Efficiency and Other Benefits of 208 Volt Over 120 Volt Input for IT Equipment

Efficiency and Other Benefits of 208 Volt Over 120 Volt Input for IT Equipment Efficiency and Other Benefits of 208 Volt Over 120 Volt Input for IT Equipment By Neil Rasmussen White Paper #27 Revision 2 Executive Summary Decisions made regarding the distribution of 208V or 120V power

More information

Application Briefs: Remote Office Environment

Application Briefs: Remote Office Environment Overview Remote offices are a definite sign of growth, but it can constitute an immense challenge from an IT infrastructure standpoint. Remote offices may include a wide variety of wiring closets and small

More information

Georgia Tech Aerospace Server French building Server Room. Server Room Policy Handbook: Scope, Processes and Procedure

Georgia Tech Aerospace Server French building Server Room. Server Room Policy Handbook: Scope, Processes and Procedure Georgia Tech Aerospace Server French building Server Room Server Room Policy Handbook: Scope, Processes and Procedure Version History Version/Status Release Date Comments 1.1/Draft 1.2 1.3 1.4 1.5 1.6

More information

Increasing Data Center Efficiency by Using Improved High Density Power Distribution

Increasing Data Center Efficiency by Using Improved High Density Power Distribution Increasing Data Center Efficiency by Using Improved High Density Power Distribution By Neil Rasmussen White Paper #128 Executive Summary A new approach to power distribution for high density server installations

More information

High-Efficiency AC Power Distribution for Data Centers

High-Efficiency AC Power Distribution for Data Centers High-Efficiency AC Power Distribution for Data Centers White Paper 128 Revision 2 by Neil Rasmussen > Executive summary The use of 240 volt power distribution for data centers saves floor space, simplifies

More information

HEAT PUMP FREQUENTLY ASKED QUESTIONS HEAT PUMP OUTDOOR UNIT ICED-UP DURING COLD WEATHER:

HEAT PUMP FREQUENTLY ASKED QUESTIONS HEAT PUMP OUTDOOR UNIT ICED-UP DURING COLD WEATHER: HEAT PUMP FREQUENTLY ASKED QUESTIONS HEAT PUMP OUTDOOR UNIT ICED-UP DURING COLD WEATHER: It is normal for a heat pump to have a build up of white frost on the outside coil during cold damp weather. The

More information

NFPA 70E 2012 Rolls Out New Electrical Safety Requirements Affecting Data Centers

NFPA 70E 2012 Rolls Out New Electrical Safety Requirements Affecting Data Centers NFPA 70E 2012 Rolls Out New Electrical Safety Requirements Affecting Data Centers A market position paper from the experts in Business-Critical Continuity TM Executive Summary Electrocutions are the fourth

More information

Arc Fault Circuit Interrupters Frequently Asked Questions

Arc Fault Circuit Interrupters Frequently Asked Questions Contents My AFCI is tripping! What do I do? What is the difference between branch feeder and combination type Arc Fault Circuit Interrupters? What is new with the 2008 NEC versus the 2005 NEC with respect

More information

Choosing Close-Coupled IT Cooling Solutions

Choosing Close-Coupled IT Cooling Solutions W H I T E P A P E R Choosing Close-Coupled IT Cooling Solutions Smart Strategies for Small to Mid-Size Data Centers Executive Summary As high-density IT equipment becomes the new normal, the amount of

More information

Guidance on Proper Use of EXTENSION CORDS, POWER STRIPS & SURGE PROTECTORS

Guidance on Proper Use of EXTENSION CORDS, POWER STRIPS & SURGE PROTECTORS Guidance on Proper Use of EXTENSION CORDS, POWER STRIPS & SURGE PROTECTORS The Language Used In This Document Does Not Create An Employment Contract Between The Employee And The Agency. This Document Does

More information

Trade of Electrician. Three-phase Distribution Boards And Socket Circuits

Trade of Electrician. Three-phase Distribution Boards And Socket Circuits Trade of Electrician Standards Based Apprenticeship Three-phase Distribution Boards And Socket Circuits Phase 2 Module No. 2.3 Unit No. 2.3.2 COURSE NOTES Created by Charlie Walsh - Athlone TC Revision

More information

Availability and Disaster Recovery: Basic Principles

Availability and Disaster Recovery: Basic Principles Availability and Disaster Recovery: Basic Principles by Chuck Petch, WVS Senior Technical Writer At first glance availability and recovery may seem like opposites. Availability involves designing computer

More information

Electrical Safety Plugs What are the different types of plugs? Extension Cords What are some potential hazards involving extension cords?

Electrical Safety Plugs What are the different types of plugs? Extension Cords What are some potential hazards involving extension cords? Electrical Safety Electricity can be a friend, but it can also hurt if you do not treat it with respect. Everyday someone loses his or her home or business due to an electrical fire. These tragedies are

More information

Three-Phase Electric Power Distribution for Computer Data Centers

Three-Phase Electric Power Distribution for Computer Data Centers Three-hase Electric ower Distribution for Computer Data Centers WHITE AER E901 Geist January 008 Summary This paper will describe the characteristics of three-phase power and outline the advantages of

More information

(Examples of various colocation sites)

(Examples of various colocation sites) Overview The largest factor involved in maintaining business servers today are the fixed costs associated with data centers. The Colocation Environment is an outsourcing model whereby a colocation company

More information

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application g Digital Energy ITI Instrument Transformer Basic Technical Information and Application Table of Contents DEFINITIONS AND FUNCTIONS CONSTRUCTION FEATURES MAGNETIC CIRCUITS RATING AND RATIO CURRENT TRANSFORMER

More information

415V DISTRIBUTION FOR GREEN DATA CENTERS

415V DISTRIBUTION FOR GREEN DATA CENTERS White Paper: HMRP-WP001-A5 June 5, 2012 415V DISTRIBUTION FOR GREEN DATA CENTERS Prepared by: Anthony (Tony) Hoevenaars, P. Eng President and CEO Mirus International Inc. Copyright 2012 Mirus International

More information

MOTOR PROTECTION AGAINST SINGLE-PHASING

MOTOR PROTECTION AGAINST SINGLE-PHASING THE SINGLE-PHASE DILEMMA: FACT OR FICTION PROTECTION AGAINST SINGLE-PHASING Bulletin PSP The Single-Phasing Issue: Fact or Fiction Overview Before discussing SINGLE-PHASING, let s take a look at some of

More information

Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services

Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services Circuit Breakers and Switchgear Thomas Greer Director of Engineering TLG Services Presentation Outline Switchgear Definition Overcurrent Protection Devices Circuit Breaker Trip Curves and Coordination

More information

415V DISTRIBUTION FOR GREEN DATA CENTERS

415V DISTRIBUTION FOR GREEN DATA CENTERS White Paper: HMRP-WP001-A1 October 1, 2010 415V DISTRIBUTION FOR GREEN DATA CENTERS Prepared by: Anthony (Tony) Hoevenaars, P. Eng President and CEO Mirus International Inc. Copyright 2005 Mirus International

More information

The Pros and Cons of Modular Systems

The Pros and Cons of Modular Systems The Pros and Cons of Modular Systems Kevin Brown, Vice President Global Data Center Offer Schneider Electric Schneider Electric 1 Foundational BUSINESS OVERVIEW Rev 2 Desired characteristics of pre-fabricated

More information

Unit 4: Electricity (Part 2)

Unit 4: Electricity (Part 2) Unit 4: Electricity (Part 2) Learning Outcomes Students should be able to: 1. Explain what is meant by power and state its units 2. Discuss the importance of reducing electrical energy wastage 3. State

More information

21 st Century Facilities

21 st Century Facilities Electrical Testing 21 st Century Facilities Facility Owners face tough challenges 24 X 7 reliability needed Non linear loads cause harmonics VFD Computers Switching transients disrupt operations Less customer

More information

The Application of Circuit Breakers to Reduce Downtime in Datacentres

The Application of Circuit Breakers to Reduce Downtime in Datacentres The Application of Circuit Breakers to Reduce Downtime in Datacentres Tim Campbell BEng MIET. Marketing Manager, Terasaki Electric (Europe) Ltd. Abstract Circuit breakers fulfil several functions in the

More information

How To Improve Energy Efficiency In A Data Center

How To Improve Energy Efficiency In A Data Center Google s Green Data Centers: Network POP Case Study Table of Contents Introduction... 2 Best practices: Measuring. performance, optimizing air flow,. and turning up the thermostat... 2...Best Practice

More information

Top 12 Questions to Consider When Choosing UPS Systems for Network/Server Applications

Top 12 Questions to Consider When Choosing UPS Systems for Network/Server Applications W H I T E P A P E R Top 12 Questions to Consider When Choosing UPS Systems for Network/Server Applications Executive Summary One of the fundamental decisions in the design of data centers, server rooms

More information

Report in respect of. Service Disruption on 9 April 2012

Report in respect of. Service Disruption on 9 April 2012 Report in respect of Service Disruption on 9 April 2012 1. Introduction On 9 April 2012, a power outage occurred in the Shatin Switching Centre, one of three switching centres deployed by SmarTone Mobile

More information

6.0 Electrical Installations

6.0 Electrical Installations 6.0 An electrical installation is a combination of electrical equipment installed to fulfill a specific purpose and having coordinated characteristics. In dealing with the electrical installation, it is

More information

Electronic Trip Circuit Breaker Basics Circuit Breaker Application Guide Class 0600

Electronic Trip Circuit Breaker Basics Circuit Breaker Application Guide Class 0600 Electronic Trip Circuit Breaker Basics Circuit Breaker Application Guide Class 0600 Data Bulletin 0600DB1104 03/2012 Retain for future use. Electronic Trip Circuit Breaker Basics 0600DB1104 Table of Contents

More information

ISS Data Centre Server Hosting. Service Description

ISS Data Centre Server Hosting. Service Description ISS Data Centre Server Hosting Service Description March 9, 2011 Information Solutions and Services Page 1 TABLE OF CONTENTS INTRODUCTION...3 ISS SERVER HOSTING SERVICE OVERVIEW...3 WHAT IS THE ISS DATA

More information

Creating Order from Chaos in Data Centers and Server Rooms

Creating Order from Chaos in Data Centers and Server Rooms Creating from in Data Centers and Server Rooms By Dennis Bouley White Paper #119 Executive Summary Data center professionals can rid themselves of messy racks, sub-standard under floor air distribution,

More information

SOC Understanding Overcurrent Circuit Protectors

SOC Understanding Overcurrent Circuit Protectors SOC Understanding Overcurrent Circuit Protectors Carl E.Lindquist VP New Product Development San-O Industrial Corporation Introduction to Overcurrent Circuit Protectors Overcurrent (Series) vs. Overvoltage

More information

Simplified Guide To Understanding Short-Circuit Current Rating FIND IT, FIX IT, FORGET IT

Simplified Guide To Understanding Short-Circuit Current Rating FIND IT, FIX IT, FORGET IT Simplified Guide To Understanding Short-Circuit Current Rating FIND IT, FIX IT, FORGET IT Are You Ready For The New SCCR Marking Requirements? What Is A Short-Circuit Current Rating (SCCR)? SCCRs on components

More information

Optimizing Rack Power Distribution

Optimizing Rack Power Distribution Optimizing Rack Power Distribution Best practices for selecting the right rack power distribution unit for your environment By Joe Skorjanec Product Manager Eaton Executive summary With information increasingly

More information

Circuit Breakers. Next Generation of Protection Capabilities

Circuit Breakers. Next Generation of Protection Capabilities Circuit Breakers Next Generation of Protection Capabilities Circuit Breaker Offering Rockwell Automation offers a full line of Allen-Bradley circuit breakers and motor protection devices to help meet many

More information

Capacity Planning in the Modern Datacenter

Capacity Planning in the Modern Datacenter in the Modern Datacenter SERVER TECHNOLOGY - INDUSTRY BRIEF -001 July 2015 Executive Overview Today s datacenter managers oversee more infrastructure than ever, with an exponential increase in complexity

More information

Chapter 5. Components, Symbols, and Circuitry of Air-Conditioning Wiring Diagrams

Chapter 5. Components, Symbols, and Circuitry of Air-Conditioning Wiring Diagrams Chapter 5 Components, Symbols, and Circuitry of Air-Conditioning Wiring Diagrams Objectives Upon completion of this course, you will be able to: Explain what electrical loads are and their general purpose

More information

ELECTRICAL SAFETY. The standard unit for measuring electrical current.

ELECTRICAL SAFETY. The standard unit for measuring electrical current. ELECTRICAL SAFETY Introduction The following sections provide general safety guidelines and procedures for electrical safety. This chapter covers the following topics: TOPIC PAGE General Electrical Safety

More information

Understanding Emergency Power Off (EPO)

Understanding Emergency Power Off (EPO) Understanding Emergency Power Off (EPO) White Paper #22 Executive Summary Emergency Power Off (EPO) is the capability to power down a piece of electronic equipment or an entire installation from a single

More information

Integrating SPDs in Switchgear & Switchboards Causes More Problems than it Solves

Integrating SPDs in Switchgear & Switchboards Causes More Problems than it Solves Integrating SPDs in Switchgear & Switchboards Causes More Problems than it Solves White Paper July 2010 Integrating surge protective devices (SPD) into distribution equipment (i.e. switchgear, switchboards,

More information

Qualitative Analysis of Power Distribution Configurations for Data Centers

Qualitative Analysis of Power Distribution Configurations for Data Centers Qualitative Analysis of Power Distribution Configurations for Data Centers White Paper #4 2007 The Green Grid. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted,

More information

LEVEL 3 DATA CENTER ASSESSMENT

LEVEL 3 DATA CENTER ASSESSMENT Nationwide Services Corporate Headquarters 410 Forest Street Marlborough, MA 01752 USA Tel: 800-342-5332 Fax: 508-303-0579 www.eecnet.com LEVEL 3 DATA CENTER ASSESSMENT Submitted by: Electronic Environments

More information

Rule 5.500 Fast Track Analysis for National Life Insurance Co.

Rule 5.500 Fast Track Analysis for National Life Insurance Co. Rule 5.500 Fast Track Analysis for National Life Insurance Co. For a 500 kw Solar array to be located at 155 Northfield Street in Montpelier, Vermont Green Mountain Power Pam Allen Date: 5/31/13 SECTION

More information

Data Centre Solutions... energy efficient by design. APC by Schneider Electric Elite Data Centre Partner. APC s leading Elite Data Centre Solutions

Data Centre Solutions... energy efficient by design. APC by Schneider Electric Elite Data Centre Partner. APC s leading Elite Data Centre Solutions Data Centre Solutions... energy efficient by design APC by Schneider Electric Elite Data Centre Partner APC s leading Elite Data Centre Solutions Partner providing customers with expert advice, integration

More information

Intersection Preassembled 19-inch Rack

Intersection Preassembled 19-inch Rack Intersection Preassembled 19-inch Rack The intersection preassembled 19-inch rack comes fully assembled, wired and ready to be installed in a server rack. The rack provides communications, power conversion

More information

The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies

The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies DATE: November 17, 1999 REVISION: AUTHOR: John Merrell Introduction In some short circuit studies, the X/R ratio is ignored when comparing

More information

CHAPTER 4 UTILITY SYSTEMS ELECTRICAL. Utility Systems Electrical. Main Panel

CHAPTER 4 UTILITY SYSTEMS ELECTRICAL. Utility Systems Electrical. Main Panel CHAPTER 4 UTILITY SYSTEMS ELECTRICAL Utility Systems Electrical The electrical supply to your home begins outside, where you will see either an overhead feed and piping down the side of your home or (if

More information

Part 1 System Modeling & Studies for Existing Systems

Part 1 System Modeling & Studies for Existing Systems Part 1 System Modeling & Studies for Existing Systems Operation Technology, Inc. Copyright 2009 Result of rapid release of energy due to an arcing fault between two conductors. Bus voltages > 208V Temperatures

More information

Energy Management Solutions

Energy Management Solutions Energy Management Solutions Introducing the world s most innovative intelligent Power Distribution Units (ipdus) designed to simplify rack energy and environmental management of your data center. Enlogic

More information

Power and Cooling Guidelines for Deploying IT in Colocation Data Centers

Power and Cooling Guidelines for Deploying IT in Colocation Data Centers Power and Cooling Guidelines for Deploying IT in Colocation Data Centers White Paper 173 Revision 0 by Paul Lin and Victor Avelar Executive summary Some prospective colocation data center tenants view

More information

Oil and Coolant Circulating Heating System. Model - OCSM

Oil and Coolant Circulating Heating System. Model - OCSM Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine

More information

APPLICATION NOTES. Bimetal Disc Thermostat. Operating Principle

APPLICATION NOTES. Bimetal Disc Thermostat. Operating Principle Bimetal Disc Thermostat APPLICATION NOTES Operating Principle Bimetal disc thermostats are thermally actuated switches. When the bimetal disc is exposed to its predetermined calibration temperature, it

More information

Cooling Small Server Rooms Can Be. - Jim Magallanes Computer Room Uptime: www.cruptime.com Uptime Racks: www.uptimeracks.com

Cooling Small Server Rooms Can Be. - Jim Magallanes Computer Room Uptime: www.cruptime.com Uptime Racks: www.uptimeracks.com Cooling Small Server Rooms Can Be Inexpensive, Efficient and Easy - Jim Magallanes Computer Room Uptime: www.cruptime.com Uptime Racks: www.uptimeracks.com Server Rooms Description & Heat Problem Trends

More information

How To Power A Bladecenter H Servers

How To Power A Bladecenter H Servers Solutions Guide for IBM Data Center Architecture: IBM BladeCenter H Servers In today s high-demand enterprise environment, organizations need a reliable infrastructure to run compute-intensive applications

More information

UL 508A Industrial Control Panels Power Distribution and Control. Lunch & Learn Training. 2002 Eaton Corporation. All rights reserved.

UL 508A Industrial Control Panels Power Distribution and Control. Lunch & Learn Training. 2002 Eaton Corporation. All rights reserved. UL 508A Industrial Control Panels Power Distribution and Control Lunch & Learn Training 2002 Eaton Corporation. All rights reserved. Agenda Who is UL and what role do they play? What is the UL 508A Standard?

More information

Your Guide to. Electrical Safety

Your Guide to. Electrical Safety Your Guide to Electrical Safety AN INTRODUCTION Electricity is an important part of our daily lives. It's everywhere. It lights our homes, cooks our food, powers our tools, and runs our televisions, radios

More information

Neutral Wire Facts and Mythology. White Paper #21

Neutral Wire Facts and Mythology. White Paper #21 Neutral Wire Facts and Mythology White Paper #21 Executive Summary This Technical Note discusses many common misunderstandings about the function of the neutral wire and its relation to power problems.

More information

Power Management Strategies for High-Density IT Facilities and Systems. A White Paper from the Experts in Business-Critical Continuity TM

Power Management Strategies for High-Density IT Facilities and Systems. A White Paper from the Experts in Business-Critical Continuity TM Power Management Strategies for High-Density IT Facilities and Systems A White Paper from the Experts in Business-Critical Continuity TM Executive Summary Increases in data center density and diversity

More information

Arc Flash Safety in 400V Data Centers

Arc Flash Safety in 400V Data Centers Arc Flash Safety in 400V Data Centers Strategies for protecting employees from underappreciated yet potentially deadly hazards By Dave G. Loucks PCM Solution Manager Eaton Corporation Executive summary

More information

Minor maintenance issues proving difficult to detect for many solar PV system owners

Minor maintenance issues proving difficult to detect for many solar PV system owners Minor maintenance issues proving difficult to detect for many solar PV system owners Challenges occurring even when system owners have access to their realtime and historical generation data Lack of detection

More information

NEC Class 2 Power Circuits and Power Supplies

NEC Class 2 Power Circuits and Power Supplies NEC Class 2 Power Circuits and Power Supplies Abstract: The NEC (National Electrical Code) is a North American standard, which can be regarded as a law in most of the North American states. Among others,

More information

Arc Flash Mitigation & Selective Co-ordination

Arc Flash Mitigation & Selective Co-ordination Arc Flash Mitigation & Selective Co-ordination Michael Hodder March 2015 Overview This seminar will provide information on: Mitigating arc flash hazards Selective Coordination What can we do to make these

More information

Sentron Series Circuit Breakers

Sentron Series Circuit Breakers Sentron Series Circuit Breakers Siemens Sentron Series circuit breakers are available in nine frame sizes: ED, FD, JD, LD, LMD, MD, ND, PD, and RD. Sentron Series circuit breakers have a wide range of

More information

The Anatomy of a. High-Availability Rack. November 2009. Online Tech, Inc. 220 E. Huron Ann Arbor, MI 48104 (734) 213-2020. www.onlinetech.

The Anatomy of a. High-Availability Rack. November 2009. Online Tech, Inc. 220 E. Huron Ann Arbor, MI 48104 (734) 213-2020. www.onlinetech. Online Technologies Corporation September 2008 If you have questions, please contact: The Anatomy of a Onl (734) 213-2020 phone High-Availability Rack November 2009 Online Tech, Inc. 220 E. Huron Ann Arbor,

More information

Use your troubleshooting superpowers for good Application Note

Use your troubleshooting superpowers for good Application Note Use your troubleshooting superpowers for good Application Note Unleash your full troubleshooting powers with innovative new tools from Fluke. You ve got skill. You ve got experience. Now you have some

More information

Predictive Maintenance in a Mission Critical Environment

Predictive Maintenance in a Mission Critical Environment March 2009 Predictive Maintenance in a Mission Critical Environment This paper discusses the need to proactively protect mechanical and electrical support systems in data processing centers and data storage

More information

Designed for uptime. Defining data center availability via a tier classification system

Designed for uptime. Defining data center availability via a tier classification system Defining data center availability via a tier classification system MIETEK GLIKOWSKI All systems can fail this is a simple fact that every industry must deal with. The paramount concern for the data center

More information

Creating Order from Chaos in Data Centers and Server Rooms

Creating Order from Chaos in Data Centers and Server Rooms Creating from in Data Centers and Server Rooms White Paper 119 Revision 1 by Dennis Bouley > Executive summary Data center professionals can rid themselves of messy racks, sub-standard under floor air

More information

Cheat Sheets to Data Center Infrastructure Management

Cheat Sheets to Data Center Infrastructure Management ^ Business-wise, Future-drivenTM Cheat Sheets to Data Center Infrastructure Management The Brands You Trust. Table of Contents Introduction...3 How DCIM helps operations...4 How DCIM helps planning...5

More information

A guide to understanding and maintaining your home s electrical system. A publication presented by the Electrical Safety Foundation International

A guide to understanding and maintaining your home s electrical system. A publication presented by the Electrical Safety Foundation International A guide to understanding and maintaining your home s electrical system A publication presented by the Electrical Safety Foundation International What s Inside? Everything you need to know Should You Do-It-Yourself?

More information

Monitoring the Computer Room s Physical Environment A white paper from Sensaphone, Inc.

Monitoring the Computer Room s Physical Environment A white paper from Sensaphone, Inc. Monitoring the Computer Room s Physical Environment A white paper from Sensaphone, Inc. Introduction Nearly all small- and medium-sized businesses rely on a computer network to maintain operations, communicate

More information

Server Technology, Inc.

Server Technology, Inc. Server Technology, Inc. Power Efficiency Gains by Deploying 415 VAC Power Distribution in North American Data Centers White Paper STI-100-008 2009-April-07 Headquarters Server Technology, Inc. 1040 Sandhill

More information