1 Environmentally sound 1 Data Centres: Policy measures, metrics, and methodologies Summary report on a workshop organised by DG CONNECT on 1 st April The original title Green Data Centres:... has been reformulated, reflecting the wide view of the workshop participants that green is a misused or misunderstood term and should not be used in this context.

2 Disclaimer: This report reflects the views only of the workshop participants, and the Commission cannot be held responsible for any use, which may be made of the information contained therein. The rapporteur has compiled the report based on the background material provided by the participants, as well as presentations and discussions during the workshop. He has subsequently integrated the participants feedback on the draft report to the best knowledge. Additional reporting by Mike Gilmore is gratefully acknowledged. Prepared for: European Commission Directorate-General for Communications Networks, Content and Technology (CONNECT) Directorate Sustainable & Secure Society (CONNECT-H) Unit Smart Cities & Sustainability (CONNECT-H5) Contact Officer: Svetoslav MIHAYLOV Prepared by: Marc-Andree Wolf maki Consulting Am Falkenberg 66 - D Berlin - Germany - Marc-Andree.Wolf@maki-consulting.com Office: +49 (0) Mob: +49 (0) FAX: +49 (0) maki Consulting is a company in sole proprietorship and registered in Germany with the owner Marc-Andree Wolf Prepared by maki Consulting for the European Commission, DG CONNECT, Unit H5 ii

3 Table of contents EXECUTIVE SUMMARY...iv 1 INTRODUCTION Context Purpose and scope of the workshop and this report IS THERE A LACK OF ENVIRONMENTAL POLICY MEASURES AND PUBLICLY AVAILABLE DATA ON DATA CENTRES? Current situation Challenges/Discussion Options Recommendations IS THERE A NEED OF NEW METRICS / HARMONISATION OF EXISTING ONES ON THE ENVIRONMENTAL IMPACT OF DATA CENTRES? Current situation Challenges/Discussion Options Recommendations SHOULD THE DATA CENTRE, IN THE CONTEXT OF ENVIRONMENTAL POLICY MEASURES / METHODOLOGIES / METRICS, BE APPROACHED AS A SYSTEM OR SHOULD IT BE APPROACHED AS ITS INDIVIDUAL COMPONENTS? Current situation Challenges/Discussion Options Recommendations REFERENCES ANNEX I: ACRONYMS ANNEX II: AGENDA ANNEX III: PARTICIPANTS Prepared by maki Consulting for the European Commission, DG CONNECT, Unit H5 iii

4 Purpose of the workshop Executive Summary The purpose of the workshop was to help DG CONNECT define future policies and actions in the area of data centre energy efficiency and environmental performance. The issue The share of data centres in electricity consumption now reaches 2% globally, with a high, exponential growth rate. Data centres hence contribute a relevant and growing share to the EU overall energy consumption and environmental impact. This growth is driven by the strongly growing amount of data generated by citizens, companies and public institutions that outpaces efficiency improvements of data centre technology and management. Faster internet access as part of the problem Pursuing a faster internet access for all users is on the one hand recognised as key for economic growth. This development is identified, on the other hand, as a driver for data growth, particularly via social media and video streaming, not to mention the expected increase through the developing Internet of Things (IoT). The participants recommend in view of the environmental implications that policies promoting and facilitating a fast growth of bandwidth in the EU should take quantitatively into account the limitations of technological developments to cope, in environmental terms, with this intended growth. Metrics and indicators As to environmental metrics and environmental Key Performance Indicators (KPIs), a wide range of such indicators has been developed over the past decade. Most participants see no need for new or further developed indicators. Instead, they recommend filtering the over 50 KPIs down to the relevant ones for the sought objective, using a systematic approach, and considering their practicality but also other aspects. Such work is already under way by the Standards Development Organizations (SDOs) and in several ongoing EU FP7 research projects. Several KPIs have been already pre-selected by the SDOs for consideration and possible standardisation. Harmonisation of how to measure the finally selected KPIs would be the next step, promotion of their voluntary use the last step needed. The subsequent choice and use of the KPIs for internal analysis and external communication/marketing should be left to the data centre operators, according to a majority of the participants, taking into account the local situation with e.g. water shortage favouring water-related KPIs. It was however also widely agreed among the participants that these currently discussed KPIs, including the most widely used Power Usage Effectiveness (PUE), are not suitable and have not been developed for comparisons of data centres and data centre services. They do not consider the important computational performance, hence do not effectively indicate environmental preference, and therefore cannot help procurers to identify more environmentally sound data centres. Several participants therefore recommended (further) development of more advanced, performance-based metrics/kpis. There was limited support among the participants for the EC to play a role in further harmonising/developing KPIs and the life cycle based methods that were developed by the Prepared by maki Consulting for the European Commission, DG CONNECT, Unit H5 iv

5 SDOs and private organisations. The supportive participants have however highlighted the necessity to overcome the weaknesses of the currently available indicators as well as the insufficient reproducibility and hence comparability of the ICT- or Data centre-specific life cycle based methods: Both would warrant EC involvement, since the efforts of standardisation and private initiatives did not solve these issues. Policy instruments Similarly to the situation for environmental indicators, policies on EU-level or in the EU Member States (MS) that would address the overall energy efficiency or environmental performance of the large majority of data centres and their services, do not exist. Existing policies relate instead to single components or the data centre building or address only specific aspects. Most participants however disfavour new policy measures on data centres. They highlight the achievements of standardisation and that the high share of energy costs for data centres would automatically lead to environmental improvements by efforts undertaken for reducing energy consumption. However, the lack of effective environmental policies on the data centre system and services, were the arguments by some participants to recommend instead the development of new policies. The aim of lowering the ICT industry s own environmental footprint and its better contribution to the EU2020 targets could otherwise not be achieved. Such policies should then consider the data centre s computational performance as basis for the environmental performance and - in view of some participants in addition be life cycle based. Best practice guides instead of policies The uptake by the EC, promotion, and translation of documents such as the EU Code-of- Conduct for Data Centre Energy Efficiency (EUCoCDC 2 ) to EU main languages was generally recommended as an important measure to help improve operational energy-efficiency of data centres. Maintenance and further detailing of the EUCoCDC was argued to be important and funds should be made available to this end. In view of some participants, the EUCoCDC could be made mandatory for data centres in the EU and data centre services offered in the EU market. The development of training materials and University courses on environmentally sound data centres were generally seen as further, important measures. Data Centres as a system and the need for differentiation It was generally agreed among the participants that the overall performance and environmental impact of the data centre needs to be improved in system perspective: a data centre is more than the sum of its components. Moreover, the actual operation needs to be considered beyond the design specifications of the data centre. To ensure validity, data centre differences in type, availability class, security-level, size, and location would need to be considered by any potential policy measures. The fact that data centre hardware is 2 Institute for Energy and Transport (IET), JRC, EC (2014): Best Practices for the EU Code of Conduct on Data Centres. Version Prepared by maki Consulting for the European Commission, DG CONNECT, Unit H5 v

6 constantly being replaced over the data centre life time - with different life times of the different kind of components and new technologies being introduced - would have to be taken into account by any policy measure, as well. It was moreover generally supported by the participants that new policies should not set fixed limits for KPIs and that the enabling effect of data centres on other industries must not be negatively impacted by the policies. The focus of measures should finally be the data centre s use phase, while shifting of environmental burdens to production or end-of-life should at least be monitored. Prepared by maki Consulting for the European Commission, DG CONNECT, Unit H5 vi

7 1 Introduction 1.1 Context The European Commission has put energy efficiency and sustainability aspects of ICT at the forefront of the Digital Agenda. Key action 12 invites the industry to propose a common framework to account for its energy consumption and greenhouse gas (GHG) emissions. The adoption of such methodologies by the industry should lead to increased transparency and create a better level playing field for competing around environmental performance. The ICT industry has mobilized resources to contribute to international standardization organizations and industry-led consortia to develop related methodologies. The European Commission aims to ensure that these methodologies are in line with its environmental objectives and policies. It also intends to potentially use them as a basis for future policy initiatives in the area of energy efficiency and the environmental impact of ICT. The storage of the ever-increasing amounts of data generated by citizens, companies and governments level is increasingly being moved from in-house servers and server-rooms to external facilities: Data Centres. Data Centres (DC) are defined in European Standardisation as a structure, or group of structures, dedicated to the centralised accommodation, interconnection and operation of information technology and network telecommunications equipment providing data storage, processing and transport services together with all the facilities and infrastructures for power distribution and environmental control together with the necessary levels of resilience and security required to provide the desired service availability. The overall energy consumption and environmental impact of data centres is growing at a high rate, although commercial or multi-tenant data centres are understood to offer in principle the possibility of better environmental and energetic performance than decentralised solutions. This increase is due to the growing number of data centre capacity, which is driven by the strongly growing amount of data. The share of data centres in national electricity consumption was in 2010 around 2% in the U.S. ( %) and 1.1 to 1.5% globally 3. Since then it has reaches 2% globally at high annual growth rates Purpose and scope of the workshop and this report This report summarises the views, arguments and recommendations expressed in the workshop and the position papers submitted prior to the WS by some participating organisations. The report is structured in its main part along the following guiding questions of the workshop: Is there a lack of environmental policy measures and publicly available data on Data Centres? 3 Jonathan Koomey Growth in Data center electricity use 2005 to Oakland, CA: Analytics Press. August Acc. to DG CONNECT s introduction presentation to this workshop. Prepared by maki Consulting for the European Commission, DG CONNECT, Unit H5 1

8 Is there a need of new metrics / harmonisation of existing ones on the environmental impact of Data Centres? Should the Data Centre, in the context of environmental policy measures/methodologies/metrics, be approached as a system or should it be approached as its individual components? This summary is prepared in view of the expressed purpose of the workshop to help DG CONNECT define future policies and actions in the area of data centre energy and environmental efficiency. Prepared by maki Consulting for the European Commission, DG CONNECT, Unit H5 2

9 2 Is there a lack of environmental policy measures and publicly available data on Data Centres? 2.1 Current situation The following, main EU environmental policy targets and instruments are in place that directly or indirectly relate to ICT, and hence also to data centres: March 2010 Europe 2020: Smart, Sustainable and inclusive Growth: Confirmation of 20/20/20 targets for March 2011 Roadmap for moving to a competitive low carbon economy by 2050: GHG emissions by 80-95% below 1990 values by July 2012 European Innovation Partnership on Smart Cities and Communities: largescale deployment of smart city solutions in Europe, focusing on intersections of ICT, energy and transport. September 2012 European Cloud Computing Strategy: Unleashing potential of Cloud Computing in Europe. June 2013 Start of the Ecodesign Directive s preparatory study on "enterprise servers and ancillary equipment": The study assesses the feasibility of ecodesign requirements and/or of an energy labelling scheme for enterprise servers, data storage devices and transmission equipment. Implementing Measures (IMs) are already in place that relate to chargers for computers and small servers. January 2014 A policy framework for climate and energy in the period from 2020 to 2030: GHG emissions 40% below the 1990 level by Renewable energy share to increase to at least 27% by It was moreover pointed out by some participants that additional European or national policy instruments directly deal with the hardware of the data centre or at corporate level, including CRC and CCL for UK industry and mandatory carbon reporting as well as the EU ETS (ETS for a few especially large facilities only). In addition, a current UK governmental scheme grants limited tax reductions for those data centres of the size class above 200 kw that report their PUE and achieve a reduction in their PUE. However, the environmental and general benefit of these policy instruments was doubted by these participants. These policies in any case do cover only specific aspects and were not made to serve GPP and similar needs for comparable information on the environmental performance of data centres and data centre services. Next to policies, EU research funding has been put on various data centre-specific and horizontal themes under FP7 and H2020. Examples of ongoing or completed research projects are CoolEmAll, All4Green, Fit4Green, GAMES, RenewIT, GreenDataNet, Dolfin, GENiC, DC4Cities, GEYSER, and PEDCA. A new call was open at the time of the workshop under H2020 on support to GPP of innovative technologies, including data centres. Prepared by maki Consulting for the European Commission, DG CONNECT, Unit H5 3

10 2.2 Challenges/Discussion Current EU policy measures are forecasted to achieve a reduction by 40% of greenhouse gases by 2050 compared to 1990, i.e. half of the minimum aim of the EC of minus 80%. Additional or improved measures or other initiatives are therefore needed. Among the EU2020 targets, the energy-efficiency target is currently seen as the most challenging one to achieve 5. Data centres play an important role in this context, as they are large electricity consumers and hence CO 2 emitters that show a strong exponential increase in global energy consumption and hence emissions: Data centres consume today more than 2% of global electricity (expected to double soon). As important drivers for this exponential growth in data, social media and video streaming were identified by the participants, more than industry, education and other such uses. At the same time, ICT helps other industries to reduce their environmental footprint by its enabling effect, i.e. by providing the ICT hardware and software support to better measure, analyse and manage emissions and resource consumptions at these other industries. This important function of ICT should not be negatively impacted by environmental policy measures on data centres. Potential policy measures and KPIs moreover face the challenge of very different types and sizes of data centres. Given different business concepts and ownership models, information and data that are required to quantify the energy efficiency and environmental performance of a data centre and the options for improvement may lay with different organisations, as the following overview of the main types of big data centres shows: Enterprise data centre: operated by an enterprise with the sole purpose of the delivery and management of services to the enterprise s employees and customers. Owner, operator and (main) user of data centre is the same organisation, bearing all energy cost and having access to all relevant energy efficiency and environmentally relevant data. Co-hosting data centre: multiple customers are provided with access to network(s), servers and storage equipment on which they operate their own services/applications. Both the information technology equipment and the support infrastructure of the building are provided as a service by the data centre operator, who bears initially all energy costs, while users pay indirectly, depending on their contracts/tariffs, which are not related to energy consumption and often are flat rates. Energy efficiency and environmentally relevant data is available at the same organisation. Co-location data centre: A data centre where multiple carriers create a carrier dense network for customers to locate their own servers and storage equipment in a common structure. The support infrastructure of the data centre (such as power distribution, security and environmental control) is provided as a service by the data centre infrastructure operator, who bears all initial energy costs. Customers pay energy costs to data centre infrastructure operator, based on their contract which include actual 5 Workshop introduction presentation by DG CONNECT. Prepared by maki Consulting for the European Commission, DG CONNECT, Unit H5 4

11 energy consumption and a possible fee related to the additional energy costs such as cooling systems, UPS and other losses. Energy efficiency and environmentally relevant data is hence spread across different actors. Network operator data centre: primary purpose is the delivery and management of broadband services to the operator s customers (= Core network - attached operator sites). The data centre operator bears initially all energy costs and the final users pay indirectly, depending on their contracts/tariffs, while these are not related to energy consumption and often are flat rates; similar to Co-hosting data centre. Energy efficiency and environmentally relevant data is spread across different actors. It was also widely agreed by the participants that the large majority of data centres by number are small single rack and single room data centres, typically without active cooling equipment, separate power supply etc. This needs to be taken into account for potential policy measures and KPIs. It was however not clarified, which share of overall data storage and traffic is made up of small and large data centres, respectively. In addition to the main types of big data centres, as listed above, their individual availability (i.e. the amount of redundant paths/systems) and security level (i.e. the amount of security components firewalls, intrusion protection systems, etc.) have to be taken into account by policies, KPIs and comparisons. The four availability tiers of data centres and specific security objectives for certain data centres were argued to come along unavoidable with a different extent of redundant equipment and different energy efficiency and environmental impact for the same amount of data stored, processed and transmitted. Policies and KPIs on data centres face moreover the reality that data centres are constantly changing systems with different components of different life times: basic infrastructure, cables, cooling equipment may be in use for e.g. 10 to 15 years, but some core elements such as CPUs may be changed already any 3 to 5 years (or even annually in some especially large enterprise data centres), storage equipment e.g. any 4 to 7 years, and network equipment e.g. any 8 to 12 years. Uptake of beneficial new technologies must not be hampered by any policy measure. Also, existing hardware-related performancelimitations cannot be changed by new policies. Policies can only address data centre operation and new hardware, meaning that some of the possible improvements can be effective only some years later. It was also pointed out that if energy efficiency was suddenly substantially improved, the amount of waste heat would diminish, undermining any capital investment made for using the waste heat. It was also argued that any attempt to artificially increase energy costs for high energy use data centres could cause their construction outside the EU, as energy costs differ in each country. This could also drive the re-location of enterprises associated with the data centres (due to issues such as latency). Moreover, considerations of data security may be of importance, as EU citizen and companies would lose physical control of their data. Also, where data centres move to e.g. China with less clean electricity production, the net environmental effect could be negative. A participant highlighted that the promotion of GPP when purchasing data centre or data centre services faces moreover the general challenge of budget limitations/reductions. The topic of publicly available data on data centres was discussed during the WS exclusively in terms of core energy consumption data that must be published by data centres Prepared by maki Consulting for the European Commission, DG CONNECT, Unit H5 5

12 that sign the European Code of Conduct for Energy Efficiency in Data Centres (EUCoCDC), which has been developed under the lead of the EC s JRC. Some participants however criticize the EUCoCDC as not taking appropriately into account existing European Standards (incl. CENELEC EN series, ETSI ES series, ETSI TS series, ETSI GS OEU 001) and prefer to first develop a European Standard, based on the EUCoCDC. Other data, e.g. life cycle assessment (LCA), or data on the computational performance were not addressed in the WS. The distorted perception in the public of big data centres as being environmentally problematic because of their size should be overcome: commercial data centres that are driven by profitability and hence put special effort to reduce energy-cost were argued to be more energy-efficient than enterprise data centres and server rooms, a view generally supported by the participants. Also generally is the public image of data centre operators important for them, including their environmental image, why measures would be undertaken to improve it. It was argued that environmental policies on data centres might negatively affect the perceived environmentally beneficial trend of shifting data from less efficient in-house servers and small data centres to large commercial data centres. This view assumes that legislation would have a cut-off, excluding data centres below a certain size and thereby rendering exclusively the large data centres more costly. It was also said that the net environmental benefit of shifting data to big commercial data centres could be small or even negative, because many small data centres would still be kept. The actual relevance of the use phase of the data centre as opposed to hardware production and end-of-life/waste management was judged differently by the participants. It was however generally supported that the use phase is the most important life cycle phase in terms of energy consumption over the life cycle and potentially having also the biggest energy-related improvement potential. While the majority of the participants did not see the need for any new environmental policy measures on data centres, a few other participants saw the need for such policies as well as for better metrics (see chapter 3.4). The first group claimed that new data centres are energy-efficient because energy cost is a main (sometimes: the main) cost factor, which was however contradicted by an example of a large bank s data centre where energy cost make up a much smaller share of total cost, with the large majority being staff and services cost and hardware cost. The majority of the participants recommend that instead of hard policy measures, the EC should endorse and promote soft ones such as the EUCoCDC. SDOs could maintain the EUCoCDC as a TR. Further detailing and differentiating the guidance would be good, as well as translation to other EU languages. Updating of the EUCoCDC could draw on the Green Grid s Data Centre Maturity Model (DCMM). (Other guides were named e.g. by ETSI and the ITU on infrastructure design and operation, which share a common core with the EUCoCDC.) The level of awareness and use of the EUCoCDC particularly among small data centres should be increased. In this context, the need for the development of training material and of education courses at University level were highlighted as important to contribute to achieve better data centre energy management and energy-efficiency. The pro-new-environmental-policy group argued that promoting good practice via the EUCoCDC alone did not allow procurement to differentiate between data centres of different environmental performance: none of those KPIs that were currently favoured by Prepared by maki Consulting for the European Commission, DG CONNECT, Unit H5 6

13 the data centre industry and that were subject to discussion on their potential standardisation (see chapter 3.4) expresses the environmental performance of data centres. Moreover, they are not made for and may not be used for comparisons among data centres, according to their developers. Software improvement is another heading of a set of areas for improving overall data centre performance: Smart ways to increase the value of the actual task supported by data centres should be identified and followed, e.g. increase the usefulness of an internet search provider request return. Also reducing data duplication within and across data centres (e.g. video-on-demand) was named as an option with room for improvement. Multiple, parallel requests sent by users should be better managed, since all but one are cancelled when the first results come in. Moreover, upcoming research projects on smart cities were named as an option to further exploit the system integration and enabling potential of ICT and data centres. Development of new uses of waste heat and other system integration was suggested, while dependency of the partners with changing technologies (e.g. no-cooling data centres are upcoming) was named as a limit to this option. Similarly, offering free heat for district heating in existing housing infrastructure was found not viable in one case in the UK due to installation costs, although the heat was for free. Focus of initial measures should be on the data centre use phase, while a shifting of environmental impacts to infrastructure and hardware production or end-of-life impacts should at least be monitored, since environmental impacts are not only related to energy consumption, but also to process-specific emissions during production and during end-of-life management of the equipment. The participants recommend in view of the environmental implications that policies promoting and facilitating a fast growth of bandwidth in the EU should take quantitatively into account the limitations of technological developments to cope, in environmental terms, with this intended growth. 2.3 Options Apart from the zero option of not developing any new policy measures, the following main options were named in the WS presentations and discussions, beyond standardisation efforts: Harmonising public procurement procedures for data centres among EU Member States. Endorsing and promoting operational guides, such as the European Code-of-Conduct for Data Centres (EUCoCDC); the option to make the EUCoCDC mandatory for data centres in Europe (potentially including data Centres that offer data centre services in the EU market). Develop data centre-specific policy measures (voluntary or mandatory), based on existing basic KPIs (PUE etc.), on advanced KPIs that consider computational performance (e.g. DCeP, DPPE), and/ or that are life cycle based (e.g. under the European Commission s Product Environmental Footprint (PEF)), building on and harmonising existing achievements by SDOs and private schemes. Prepared by maki Consulting for the European Commission, DG CONNECT, Unit H5 7

14 2.4 Recommendations It was proposed to start with soft measures, e.g. in form of best-practice guides such as the EUCoCDC and self-commitments, and evaluate at a later stage if there is the need for additional policy, or not Availability tiers and security levels of the data centres need to be considered by policies Development of new uses of waste heat and other system integration aspects Software improvement increase the usefulness of an internet search, reduce data duplication, better manage multiple/parallel requests, etc. Initial focus should be on the use phase, but shifting of environmental impacts to infrastructure and hardware production or end-of-life impacts needs to be at least monitored Bandwidth growth needs to be better linked to the ability of technological developments to cope with it in terms of the related energy consumption and environmental impacts Prepared by maki Consulting for the European Commission, DG CONNECT, Unit H5 8

15 3 Is there a need of new metrics / harmonisation of existing ones on the environmental impact of Data Centres? 3.1 Current situation The large variety of data centre energy and environmental KPIs can be usefully grouped into three types: Efficiency and effectiveness indicators (of the data centre or its components) during data centre operation, but not related to performance of data services and not life cycle based. For example the PUE, WUE,. Performance-based indicators (of the data centre or its components), but not life-cycle based. For example DCeP, DPPE,... Life cycle based performance-related indicators (of the data centre or its components). For example PEF, CF,. Fig. 1 illustrates the scopes of these three types of KPIs. Three different levels of KPI for data Centres and their scopes in dotted lines; note that the individual KPI may cover only a part or specific aspect of the potential scope. Independent from the three types of KPIs that were identified above, a different logic is used by several SDOs: Technical KPIs that relate to the design and engineering phase for the components, sub-assemblies, products and systems to be employed in data centres. Objective KPIs that apply to the data centre infrastructures in the operational phase Global KPIs that provide a different/wider view of a user s commitment to strategic energy management practices than the Objective KPIs. Prepared by maki Consulting for the European Commission, DG CONNECT, Unit H5 9

16 Figure 1 gives an overview of standardisation achievements and ongoing efforts related to data centres, including on KPIs. Figure 1 Overview of standardisation achievements and ongoing efforts related to data centres (prepared by Mike Gilmore of e-ready Building). In total, at least 50 KPIs have been developed and many of them tested, most of them of the first type of efficiency and effectiveness KPIs 6. In some cases, different organisations have developed identical or very similar indicators under different names. A selection of these KPIs is documented and evaluated in the background report to this WS KPIs for Green Data Centres. Ongoing research projects (CoolEmAll, All4Green, Fit4Green, GAMES, RenewIT, GreenDataNet, Dolfin, GENiC, DC4Cities, GEYSER) evaluate, in parallel, subsets of the KPIs. The Global Harmonization Taskforce, including the Japanese Green IT Promotion Council, the US Department of Energy, the Green Grid, and the European Commission's Joint Research Centre, has reached an agreement on Measurement Protocols for GEC, ERF, and CUE and continues the discussion of additional energy efficiency metrics. IEC/ISO is establishing standards on data centre Power Usage Effectiveness (PUE) and have in its queue for consideration: Carbon Usage Effectiveness (CUE), Renewable Energy Use (REF), IT Efficiency (ITEE), IT Utilization (ITEU), Water Usage Effectiveness (WUE), Energy 6 Among these are: PUE, WUE, CUE, CADE, DCIE, CPE, DCEP, THD, ERF, ERE, GEC, CEF, REF, GPUE, TUE, DCU, ScE, DCeE, DCPD, DCD, Swap, Useful Work, Productivity DC, TPS/Watt, DH-UR, SI-POM, H-POM, U Server, U Network, U Storage, ITUE, ITEE, ITZU, RWH, CEB, CIUD, PAR4, DPPE, DC FVER, DCMM. Prepared by maki Consulting for the European Commission, DG CONNECT, Unit H5 10

17 Reuse (ERE) aka Reuse of Waste Heat (RWH), and cooling efficiency, amongst others. On international level, currently only the PUE is subject to ongoing standardisation activity. According to the widely shared view of the participants, almost exclusively one KPI is in wider practical use at data centres: the PUE. However, small data centres usually cannot calculate the PUE as they lack separate measurements of electricity consumption for IT and for other equipment. Often they do not even know about the PUE. KPIs such as overall greenhouse gas (GHG) emissions are sometimes used, with the need to get additional information on the GHG intensity of supplied electricity. Other indicators such as green energy use (GEC) and energy reuse outside the data centre (ERF) are sometimes used and communicated as well. In some cases, particularly in Japan, performance-based KPIs are being developed and tested, such as the DPPE 7. The Global Taskforce has recently recommended to start measuring the more advanced, performance-based indicator DCeP 8. Several SDOs and other initiatives have developed and/or coordinated life cycle based methods on ICT, such as ETSI, ITU, IEC, WRI/WBCSD, and The Green Grid. Work is planned moreover on developing Product Category Rules (PCR) for the environmental footprint of data centres. Linked to this foreseen PCR development is the ongoing pilot testing of the EC s approach to Environmental footprinting, led by the European Commission s DG Environment: one of these pilot projects that will develop PCR-like Product Environmental Footprint Category Rules (PEFCRs) focuses on IT equipment and another one on UPS Challenges/Discussion Several participants expressed the view that most of the over 50 KPIs that were mentioned in the discussions would have limited or no value to help improving data centres operation and energy efficiency and as KPIs for measuring environmental performance for use e.g. in GPP. Most of these indicators and particularly the PUE were widely seen by the participants as not being suitable for measuring environmental performance of data centres; they should not be used for comparisons. Similarly, FP7 research projects on data centres have found that Standardization should go beyond PUE and similar KPIs, and should include computational efficiency and other aspects. The different business models for big data centres (see data centre types in chapter 2.2) pose moreover the challenge that the data centre operator may not have access to some of the information required to measure the data centre energy efficiency and may have no influence on the clients equipment and actual operation, hence can influence the environmental performance only to a limited degree. 7 Japan Green IT Promotion Council 8 Recommendation of the Global Taskforce from March 2014, to measure the Data Centre energy Productivity (DCeP) that relates energy consumption to useful work of data centres ( ng=en). The method had been developed by The Green Grid originally in 2008: Prepared by maki Consulting for the European Commission, DG CONNECT, Unit H5 11

18 For green energy use (GEC) the necessity was expressed widely to avoid green-washing, both when using electricity that is green only on paper, and when promoting energy inefficient data centres with the misleading argument of using green energy. Additional demand for green energy by data centres was however argued to have had a beneficial effect, e.g. in France, where EDF would now be acquiring additional green energy. Intermittently available green energy such as wind power was however seen as an inherent challenge and the concern of selling the same green energy twice was expressed. Lack of public incentives to purchase green energy was mentioned as one shortcoming. In first priority and in any case, the energy-efficiency of the data centre would be key, as is its overall energy consumption, a view commonly shared among the participants. The risk was mentioned that not well designed or inappropriate KPIs lead to measures that serve KPI reporting rather than improving energy-efficiency, what needs to be avoided. Despite of some coordination activities across SDOs, procedures and development cycles may still prevent the necessary full coordination and cooperation as was exemplified by one participant. According to many participants, the selection of which KPIs to report or use has to be made in consideration also of the local relevance, e.g. where water is in shortage, the WUE would serve well, in other places the PUE may be better, etc. A combined approach should allow that the better or less good performances of a data centre in the different KPIs can compensate each other. A widely expressed view was that the KPIs developed under CEN, CENELEC and ETSI, and monitored by the joint coordination group for Green Data Centres, may not be aggregated to an overall KPI and also individually not be used for comparisons among data centres (as also made explicit in ISO/IEC ), but serve exclusively as trend indicators to help improve the respective data centre operation. Other participants argued (in view of the weakness of these currently industry-favoured KPIs) for the need of more advanced KPIs, i.e. performance-based or life cycle based KPIs to overcome the inherent limitations. Several participants stated that a commonly applicable and comparable KPI does not exist. It was suggested that very simple performance metrics such as the amount of data hosted and transferred to/from the client may be easier to measure and also more suitable than more complex metrics. Some participants argued that most KPIs serve the data centre developer or operator, but less the user. It was also warned of KPIs that overlap with other efforts e.g. under EMS and CRC which would lead to double reporting or accountability. It was stated and generally supported that it needs first to be defined what one wants to achieve and only then to select or develop the right indicator and define/standardise exactly what to measure and how and where. The large number of available KPIs hence needs to be filtered down along criteria including simplicity/practicality, scalability, worldwide applicability etc. to those that serve a specific purpose and do so well. Particularly the practicality was highlighted as important for uptake in practice. It should then be decided which body would take care of which KPI. According to several participants, it would be important to first support the use or testing of existing KPIs before any further development. It was generally supported that the different purposes of data centres and their different requirements on e.g. availability, security etc. affect the data centre efficiency and need Prepared by maki Consulting for the European Commission, DG CONNECT, Unit H5 12

19 hence to be taken into account when defining or interpreting KPIs: a direct comparison necessitates to explicitly consider data centre availability and security level differences. The computational performance or (useful) work of data centres was said to escape a generally applicable definition, while this widely shared opinion was questioned by several participants: the Global Taskforce has just recommended (March 2014) to measure the DCeP. They argued that the DCeP and the DPPE are indicators that work with this concept, have been tested, and that such approaches should be further pursued. It was suggested by some participants to perform a Life Cycle Assessment (LCA) when designing and building a data centre, but use other KPIs to manage them during data centre operation. There was only limited support for the EC to play a role in further harmonisation or further development of KPIs or of life cycle based methods that were developed by the SDOs and private organisations. The need, in this context, to overcome the weaknesses of the currently available indicators and the insufficient reproducibility and hence comparability of the ICT- or data centre-specific life cycle based methods, was however raised by the participants and an active role of the EC supported to this end. 3.3 Options The following options were addressed: Standardisation of KPIs in IEC, CENELEC, ETSI, and/or ITU Private initiatives, such as The green grid, WRI/WBCSD GHG protocol, to advance KPIs and methods Research initiatives on sustainable data centres, collaborating on advancing or developing KPIs (methodology) to measure the results or progress The possible role of the EC in the development of KPIs and methods and/or their harmonisation 3.4 Recommendations First, what one wants to achieve needs to be defined and then the large number of available KPIs need to be filtered down along criteria including simplicity/practicality, scalability, worldwide applicability etc. According to several participants, it would be important to first support the use or testing of existing KPIs before any further development Data centre aspects such as purpose, availability, security etc. need to be taken into account when interpreting KPIs Prepared by maki Consulting for the European Commission, DG CONNECT, Unit H5 13

20 Performance-based or life cycle based KPIs might be needed to overcome the inherent limitations of KPIs under consideration and harmonisation by the SDOs, according to several participants10 It was suggested by some participants to perform a Life Cycle Assessment (LCA) when designing and building a data centre, but use other KPIs to manage them during data centre operation 10 Current development support this view: The Global Taskforce has just recommended (March 2014) to measure the performance-based DCeP Prepared by maki Consulting for the European Commission, DG CONNECT, Unit H5 14

21 4 Should the Data Centre, in the context of environmental policy measures / methodologies / metrics, be approached as a system or should it be approached as its individual components? 4.1 Current situation While the available methodologies, guides, metrics and KPIs cover the whole range from single components through the main layers / functional units to the entire data centre as a system, policy measures relate to only a few components and to the buildings in general, none on the data centre as a system or to data centre services (with the exception of the EU ETS for a few very large facilities). 4.2 Challenges/Discussion The data centre provides its services as a system. It was commonly agreed that data centres are complex systems and their overall performance must be improved, even including interrelations with the data centre surroundings, such as use of waste heat. The different types of data centres, with different organisations being in control of the computational equipment and the operation for some types, need to be considered when compiling data and information for an analysis and when identifying improvement options. Improvement measures on the ground are seen by most participants to be effectively guided by the EUCoCDC, which deals with the various data centre components, aiming at an overall energetic and environmental improvement. This overall improvement was expressed by the participants as the overall aim, yet no comprehensive and practice-tested overall metric or policy is available, so far. The necessity to focus more on the actual operation of the data centre (as opposed to e.g. the data centre design) was highlighted. Another item of relevance is the necessity to consider seasonal differences and peak situations e.g. in cooling, i.e. to capture the overall situation and operation. Data centres in cities (and in large industrial sites) were argued to have the advantage of better possibilities to use the waste heat, e.g. for office heating, also have better cable access, allow better security measures (while backups are being kept physically far away). It was disputed among the participants, whether or not big data centres would still be built in cities, but data centres in cities including their interactions with the surroundings, were positively discussed as options to improve system performance. The majority of participants, however, did also favour to continue adopting measures on component level, e.g. by following the EUCoCDC recommendations. Internal monitoring and management would use mainly KPIs for components/parts of the data centre, while external monitoring and reporting would be more useful regarding the overall energy consumption of the data centre and its overall KPIs such as e.g. the PUE or more advanced, performance-based KPIs. Prepared by maki Consulting for the European Commission, DG CONNECT, Unit H5 15

22 4.3 Options Implicitly, the following two options were addressed in the workshop: Improving/selecting/regulating/monitoring single components according to their environmental performance. Improving/selecting/regulating/monitoring the data centre as a whole and its services according to their environmental performance. 4.4 Recommendations Data centres should be treated as systems including the interactions with their surroundings Continue adopting measures on component level Internal management of data centre operation should be based on component-level KPIs External reporting should be based on KPIs for the data centre as a system Prepared by maki Consulting for the European Commission, DG CONNECT, Unit H5 16

23 5 References ASTAP Working Group on ICT and Climate Change (2011): APT Report on Introduction to Green ICT Activities. Data Centre Alliance (2013): DCA Certification of Data Centres Standard V1.0, 01 March ETSI GS OEU 001, v Operational energy Efficiency for Users (OEU); Technical Global KPIs for Data Centres. 01p.pdf. ETSI TS "Life Cycle Assessment (LCA) of ICT equipment, networks and services; General methodology and common requirements" methodology. European Commission (2010): Communication from the Commission. EUROPE A strategy for smart, sustainable and inclusive growth. (COM(2010) 2020 final) European Commission - Joint Research Centre - Institute for Environment and Sustainability (2010): International Reference Life Cycle Data System (ILCD) Handbook - General guide for Life Cycle Assessment - Detailed guidance. First edition March EUR EN. Luxembourg. Publications Office of the European Union; European Commission (2011): Towards A European Roadmap for Data centres and their Economic and Environmental Impact. European Commission (2013): Building the Single Market for Green Products Facilitating better information on the environmental performance of products and organisations. COM(2013) 196 final. European Commission (2013): COMMISSION RECOMMENDATION of 9 April 2013 on the use of common methods to measure and communicate the life cycle environmental performance of products and organisations. (2013/179/EU). European Commission, DG Environment (2014): Guidance for the implementation of the EU Product Environmental Footprint (PEF) during the Environmental Footprint (EF) pilot phase. Version 4.0. Guohui Wang T. S. Eugene Ng (2011): The Impact of Virtualization on Network Performance of Amazon EC2 Data Centre. Huston Eubank, Joel Swisher, Cameron Burns, Jen Seal, and Ben Emerson (2003): Design Recommendations for High-Performance Data Centres: Report of the Integrated Design Charrette. IEC/TR "Quantification methodology of greenhouse gas emissions (CO2e) for electrical and electronic products and systems". Institute for Energy and Transport (IET), JRC, EC (2014): Best Practices for the EU Code of Conduct on Data Centres. Version Institute for Energy and Transport (IET), JRC, EC (2014): European Code of Conduct on Data Centre Energy Efficiency. Introductory guide for applicants. Version Prepared by maki Consulting for the European Commission, DG CONNECT, Unit H5 17

DG CONNECT (Unit H5) Overview of the European Data Centre/Smart Cities initiatives in DG Connect H5

DG CONNECT (Unit H5) Overview of the European Data Centre/Smart Cities initiatives in DG Connect H5 DG CONNECT (Unit H5) Overview of the European Data Centre/Smart Cities initiatives in DG Connect H5 Svetoslav Mihaylov Scientific/Technical Project Officer Smart Cities and Sustainability Directorate-General

More information

European perspectives in addressing sustainability in data centres (in context, in particular, of urban environments)

European perspectives in addressing sustainability in data centres (in context, in particular, of urban environments) European perspectives in addressing sustainability in data centres (in context, in particular, of urban environments) Mercè Griera i Fisa Smart Cities and Sustainability Directorate-General Communications

More information

Green Data Net datacenters in Europa op basis van zonne en windenergie

Green Data Net datacenters in Europa op basis van zonne en windenergie FP7 ICT 2013.6.2 Green Data Net datacenters in Europa op basis van zonne en windenergie ICTroom, ir. Norbert Engbers (ir. Eric Taen) 6 nov 2014 IT Room Infra Deze lezing wordt u aangeboden door: The Data

More information

GEYSER: Data Centres as Prosumers within the Smart City. Green IT Amsterdam Vasiliki Georgiadou

GEYSER: Data Centres as Prosumers within the Smart City. Green IT Amsterdam Vasiliki Georgiadou GEYSER: Data Centres as Prosumers within the Smart City Green IT Amsterdam Vasiliki Georgiadou A consortium of public-private cooperation in the Amsterdam region that aims to stimulate:» IT energy efficiency

More information

Existing Data Centres energy metrics Task 1

Existing Data Centres energy metrics Task 1 Smart City Cluster Collaboration Existing Data Centres energy metrics Task 1 Task duration: January-February, 2014 Task leader: TUC (GEYSER) Task Participants: DC4Cites (ENEA, HP, Freemind, GNF), DOLFIN

More information

COMMISSION STAFF WORKING PAPER EXECUTIVE SUMMARY OF THE IMPACT ASSESSMENT. Accompanying the document

COMMISSION STAFF WORKING PAPER EXECUTIVE SUMMARY OF THE IMPACT ASSESSMENT. Accompanying the document EUROPEAN COMMISSION Brussels, 22.6.2011 SEC(2011) 780 final COMMISSION STAFF WORKING PAPER EXECUTIVE SUMMARY OF THE IMPACT ASSESSMENT Accompanying the document DIRECTIVE OF THE EUROPEAN PARLIAMENT AND

More information

Green Data Centers. Energy Efficiency Data Centers. André ROUYER Director of Standardization & Environment. The importance of standardization

Green Data Centers. Energy Efficiency Data Centers. André ROUYER Director of Standardization & Environment. The importance of standardization Green Data Centers GOING FORWARD ENERGY EFFICIENCY TRENDS André ROUYER Director of Standardization & Environment All content in this presentation is protected 2008 American Power Conversion Corporation

More information

A Market Transformation Programme for Improving Energy Efficiency in Data Centres

A Market Transformation Programme for Improving Energy Efficiency in Data Centres A Market Transformation Programme for Improving Energy Efficiency in Data Centres Paolo Bertoldi, European Commission Joint Research Centre ABSTRACT The European Code of Conduct for Data Centres is a voluntary

More information

COMMITTEE ON STANDARDS AND TECHNICAL REGULATIONS (98/34 COMMITTEE)

COMMITTEE ON STANDARDS AND TECHNICAL REGULATIONS (98/34 COMMITTEE) EUROPEAN COMMISSION ENTERPRISE AND INDUSTRY DIRECTORATE-GENERAL Regulatory Policy Standardisation Brussels, 9 th November 2005 Doc.: 34/2005 Rev. 1 EN COMMITTEE ON STANDARDS AND TECHNICAL REGULATIONS (98/34

More information

ICT footprint. Pilot testing on methodologies for energy consumption and carbon footprint of the ICT-sector

ICT footprint. Pilot testing on methodologies for energy consumption and carbon footprint of the ICT-sector ICT footprint Pilot testing on methodologies for energy consumption and carbon footprint of the ICT-sector FINAL REPORT A study prepared for the European Commission DG Communications Networks, Content

More information

CEN-CENELEC reply to the European Commission's Public Consultation on demand-side policies to spur European industrial innovations in a global market

CEN-CENELEC reply to the European Commission's Public Consultation on demand-side policies to spur European industrial innovations in a global market CEN Identification number in the EC register: 63623305522-13 CENELEC Identification number in the EC register: 58258552517-56 CEN-CENELEC reply to the European Commission's Public Consultation on demand-side

More information

Georges Da Costa IRIT / Toulouse University GreenDays@Lille 29 11 2013. Green Data Centers: The European Sky

Georges Da Costa IRIT / Toulouse University GreenDays@Lille 29 11 2013. Green Data Centers: The European Sky Georges Da Costa IRIT / Toulouse University GreenDays@Lille 29 11 2013 Green Data Centers: The European Sky Key concern in Europe EU climate and energy package 20-20-20 targets A 20% reduction in EU greenhouse

More information

FIRST ANNOUNCEMENT AND CALL FOR ABSTRACTS. 7th International Conference on Energy Efficiency in Domestic Appliances and Lighting (EEDAL 13)

FIRST ANNOUNCEMENT AND CALL FOR ABSTRACTS. 7th International Conference on Energy Efficiency in Domestic Appliances and Lighting (EEDAL 13) FIRST ANNOUNCEMENT AND CALL FOR ABSTRACTS 7th International Conference on Energy Efficiency in Domestic Appliances and Lighting (EEDAL 13) 11-13 September 2013 Coimbra, Portugal Introduction Citizens and

More information

ETNO Reflection Document in reply to the EC consultation on Future networks and the Internet early challenges regarding the Internet of things

ETNO Reflection Document in reply to the EC consultation on Future networks and the Internet early challenges regarding the Internet of things ETNO Reflection Document in reply to the EC consultation on Future networks and the Internet early challenges regarding the Internet of things November 2008 Executive Summary The Internet of the future

More information

Research, innovation, and policy on energy efficient data centres: an EU perspective

Research, innovation, and policy on energy efficient data centres: an EU perspective Research, innovation, and policy on energy efficient data centres: an EU perspective e-energy 2012 Madrid, 9 May 2012 Dr. Max Lemke, Deputy Head of Unit Embedded Systems and Control, INFSO From 1 July:

More information

GT Data Centre & Durabilité Gestion énergétique des Data Centres

GT Data Centre & Durabilité Gestion énergétique des Data Centres GT Data Centre & Durabilité Gestion énergétique des Data Centres Jean-Marc Alberola, Airbus Industry Dominique Roche, ORANGE (copilote GT) The ICT Users Green Way S Gestion energétique & Green ICT CTO

More information

Harmonizing Global Metrics for Data Center Energy Efficiency

Harmonizing Global Metrics for Data Center Energy Efficiency Harmonizing Global Metrics for Data Center Energy Efficiency Dan Azevedo, Symantec Chairman - Metrics & Measurements Work Group Industry Trends Energy Efficient IT The Climate Group: Smarter technology

More information

Environmental footprinting of products. The policy outlook

Environmental footprinting of products. The policy outlook Environmental footprinting of products The policy outlook Mr Michele Galatola Product Team Leader DG Environment, C1 Sustainable Production and Consumption Unit The World is moving. Second level Third

More information

Unleashing the Potential of Cloud Computing in Europe - What is it and what does it mean for me?

Unleashing the Potential of Cloud Computing in Europe - What is it and what does it mean for me? EUROPEAN COMMISSION MEMO Brussels, 27 September 2012 Unleashing the Potential of Cloud Computing in Europe - What is it and what does it mean for me? See also IP/12/1025 What is Cloud Computing? Cloud

More information

Low Carbon Data Centres without compromise

Low Carbon Data Centres without compromise Low Carbon Data Centres without compromise Thursday 16 th September 2010 Pip Squire, Engineering & Project Director delivered by: Ark Continuity - Continuously Delivering high integrity data centres Introduction

More information

Environmental footprinting of products The policy outlook

Environmental footprinting of products The policy outlook Environmental footprinting of products The policy outlook Mr Michele Galatola Product Team Leader DG Environment, C1 Sustainable Production and Consumption Unit The World is moving. Problem definition

More information

CEN and CENELEC response to the EC Consultation on Standards in the Digital Single Market: setting priorities and ensuring delivery January 2016

CEN and CENELEC response to the EC Consultation on Standards in the Digital Single Market: setting priorities and ensuring delivery January 2016 CEN Identification number in the EC register: 63623305522-13 CENELEC Identification number in the EC register: 58258552517-56 CEN and CENELEC response to the EC Consultation on Standards in the Digital

More information

Summary of the Impact assessment for a 2030 climate and energy policy framework

Summary of the Impact assessment for a 2030 climate and energy policy framework Summary of the Impact assessment for a 2030 climate and energy policy framework Contents Overview a. Drivers of electricity prices b. Jobs and growth c. Trade d. Energy dependence A. Impact assessment

More information

THE ACS BACKGROUND GENERAL COMMENTS

THE ACS BACKGROUND GENERAL COMMENTS The ACS (Australian Computer Society) Submission on the Whole-of-Government Information and Communication Technology (ICT) Sustainability Plan, Department of the Environment, Water, Heritage and the Arts

More information

Code of Conduct on Data Centre Energy Efficiency. Endorser Guidelines and Registration Form. Version 3.0.0

Code of Conduct on Data Centre Energy Efficiency. Endorser Guidelines and Registration Form. Version 3.0.0 1 EUROPEAN COMMISSION DIRECTORATE-GENERAL JRC JOINT RESEARCH CENTRE Institute for Energy Renewable Energies Unit Ispra, 1 st January 2015 Code of Conduct on Data Centre Energy Efficiency Endorser Guidelines

More information

EUROPEAN COMMISSION ENTERPRISE AND INDUSTRY DIRECTORATE-GENERAL. Space, Security and GMES Security Research and Development

EUROPEAN COMMISSION ENTERPRISE AND INDUSTRY DIRECTORATE-GENERAL. Space, Security and GMES Security Research and Development Ref. Ares(2011)193990-22/02/2011 EUROPEAN COMMISSION ENTERPRISE AND INDUSTRY DIRECTORATE-GENERAL Space, Security and GMES Security Research and Development Brussels, 17 th February 2011 M/487 EN PROGRAMMING

More information

New Trends in Data Center Metrics

New Trends in Data Center Metrics New Trends in Data Center Metrics Chuck Carroll September 14, 2011 Critical Infrastructure of the Cable Industry Critical Infrastructure can encompass a number of different types of facilities Data Centers

More information

Harmonizing Global Metrics for Data Center Energy Efficiency. Global Taskforce Reaches Agreement Regarding Data Center Productivity.

Harmonizing Global Metrics for Data Center Energy Efficiency. Global Taskforce Reaches Agreement Regarding Data Center Productivity. Harmonizing Global Metrics for Data Center Energy Efficiency Global Taskforce Reaches Agreement Regarding Data Center Productivity March 13, 2014 The data center has become an increasingly important part

More information

Green Cloud Computing: Case Study Sri Lanka & Pakistan

Green Cloud Computing: Case Study Sri Lanka & Pakistan Green Cloud Computing: Case Study Sri Lanka & Pakistan 28-30 July 2015 Colombo, Sri Lanka Sameer Sharma, Senior Advisor Regional Office Asia-Pacific Recalling ITU TRCSL Workshop in 2013 ITU TRCSL Workshop

More information

PROGRAMME OVERVIEW: G-CLOUD APPLICATIONS STORE FOR GOVERNMENT DATA CENTRE CONSOLIDATION

PROGRAMME OVERVIEW: G-CLOUD APPLICATIONS STORE FOR GOVERNMENT DATA CENTRE CONSOLIDATION PROGRAMME OVERVIEW: G-CLOUD APPLICATIONS STORE FOR GOVERNMENT DATA CENTRE CONSOLIDATION 1. Introduction This document has been written for all those interested in the future approach for delivering ICT

More information

Green IT Promotion Council, Japan

Green IT Promotion Council, Japan Concept of New Metrics for Data Center Energy Efficiency Introduction of Datacenter Performance per Energy [ DPPE ] Green IT Promotion Council, Japan February2010 Abstract Power Usage Effectiveness (PUE)

More information

Demand Response in Data Centers Feasibility and Proof of Concept Demonstration

Demand Response in Data Centers Feasibility and Proof of Concept Demonstration Demand Response in Data Centers Feasibility and Proof of Concept Demonstration Jay Madden, SCE; Mukesh Khattar, EPRI; Henry Wong, Intel; Chris Battista, Calit2 CalPlug Workshop Series #7 University of

More information

Energy Union. Integrated, Interconnected, Resilient and Secure

Energy Union. Integrated, Interconnected, Resilient and Secure Energy Union Integrated, Interconnected, Resilient and Secure 1 «I want to reform and reorganise Europe s energy policy in a new European Energy Union. Jean Claude Juncker 2 Energy in the EU Results achieved

More information

Greening The Data Center

Greening The Data Center Greening The Data Center A Five Step Method for CIO s and Data Center Managers Professionals who manage Data Centers know what is expected from them for performance and uptime. What many are only just

More information

ETSI GS OEU 001 V1.2.3 (2013-07)

ETSI GS OEU 001 V1.2.3 (2013-07) GS OEU 001 V1.2.3 (2013-07) Group Specification Operational energy Efficiency for Users (OEU); Global KPI for Data Centres Disclaimer This document has been produced and approved by the Operational energy

More information

TOSCA. How companies work to realize sustainability goals

TOSCA. How companies work to realize sustainability goals TOSCA How companies work to realize sustainability goals What it s all about Project TOSCA is a project on Life Cycle Management aiming to show how companies can work towards sustainability. TOSCA addresses

More information

Draft Scope 2 Accounting Guidance: What it could mean for corporate decisions to purchase environmental instruments

Draft Scope 2 Accounting Guidance: What it could mean for corporate decisions to purchase environmental instruments Draft Scope 2 Accounting Guidance: What it could mean for corporate decisions to purchase environmental instruments September 2014 Corporate Scope 2 accounting has traditionally been relatively straight

More information

Comments of PU Europe on the Energy Efficiency Plan 2011 Commission Communication COM(2011) 109 final

Comments of PU Europe on the Energy Efficiency Plan 2011 Commission Communication COM(2011) 109 final Comments of PU Europe on the Energy Efficiency Plan 2011 Commission Communication COM(2011) 109 final PU Europe is the European association representing the polyurethane insulation industry (PUR/PIR).

More information

VISIT 2010 Fujitsu Forum Europe 0

VISIT 2010 Fujitsu Forum Europe 0 VISIT 2010 Fujitsu Forum Europe 0 Virtualization & Automation Room 13a Shaping tomorrow with you. Green Data Center Services Martin Provoost Director, Data Centers and Networks, Fujitsu UK & Ireland 14:00

More information

European Distribution System Operators for Smart Grids. Position paper on Electric Vehicles Charging Infrastructure

European Distribution System Operators for Smart Grids. Position paper on Electric Vehicles Charging Infrastructure European Distribution System Operators for Smart Grids Position paper on Electric Vehicles Charging Infrastructure European Distribution System Operators for Smart Grids Position paper on ELECTRIC VEHICLES

More information

EUROPEAN COMMISSION ENTERPRISE AND INDUSTRY DIRECTORATE-GENERAL

EUROPEAN COMMISSION ENTERPRISE AND INDUSTRY DIRECTORATE-GENERAL EUROPEAN COMMISSION ENTERPRISE AND INDUSTRY DIRECTORATE-GENERAL Innovation policy Technology for innovation; ICT industries and E-business Brussels, 7 th December 2005 DG ENTR/D4 M 376 - EN STANDARDISATION

More information

Green Power Accounting Workshop: Concept Note For discussion during Green Power Accounting Workshop in Mexico City, May 13th 2011

Green Power Accounting Workshop: Concept Note For discussion during Green Power Accounting Workshop in Mexico City, May 13th 2011 Introduction As more companies and government organizations prepare greenhouse gas (GHG) inventories that reflect the emissions directly and indirectly associated with their operations, they increasingly

More information

Capacity Building in the New Member States and Accession Countries on Further Climate Change Action Post-2012

Capacity Building in the New Member States and Accession Countries on Further Climate Change Action Post-2012 Capacity Building in the New Member States and Accession Countries on Further Climate Change Action Post-2012 (Service Contract N o 070402/2004/395810/MAR/C2) 29 November 2007 Almost all New Members States

More information

The EU Code of Conduct on Data Centres

The EU Code of Conduct on Data Centres The EU Code of Conduct on Data Centres Liam Newcombe BCS Data Centre Specialist Group Secretary EU CoC Data Centres Chair, Best Practice Working Group Development Becoming a Signatory Best Practices Use

More information

HMT Consultation Reforming the business energy efficiency tax landscape: Response from the Energy Intensive Users Group

HMT Consultation Reforming the business energy efficiency tax landscape: Response from the Energy Intensive Users Group HMT Consultation Reforming the business energy efficiency tax landscape: Response from the Energy Intensive Users Group General comments The Energy Intensive Users Group (EIUG) represents manufacturing

More information

June 2015. Position Paper Contribution to the debate on electricity market design and capacity markets

June 2015. Position Paper Contribution to the debate on electricity market design and capacity markets June 2015 Position Paper Contribution to the debate on electricity market design and capacity markets Eurogas is the association representing the European gas wholesale, retail and distribution sectors.

More information

HORIZON 2020. ENERGY context and Calls 2014/15. Ljubljana, 23 January 2014 THE EU FRAMEWORK PROGRAMME FOR RESEARCH AND INNOVATION

HORIZON 2020. ENERGY context and Calls 2014/15. Ljubljana, 23 January 2014 THE EU FRAMEWORK PROGRAMME FOR RESEARCH AND INNOVATION THE EU FRAMEWORK PROGRAMME FOR RESEARCH AND INNOVATION HORIZON 2020 ENERGY context and Calls 2014/15 Ljubljana, 23 January 2014 Jeroen SCHUPPERS European Commission, DG Research and Innovation Europe's

More information

The Green Grid, Metrics and DCMM. Presented by: Jay Taylor

The Green Grid, Metrics and DCMM. Presented by: Jay Taylor The Green Grid, Metrics and DCMM Presented by: Jay Taylor About The Green Grid A not-for-profit international consortium committed to advancing resource efficiency in business computing ecosystems and

More information

Call to Action on Smart Sustainable Cities

Call to Action on Smart Sustainable Cities Call to Action on Smart Sustainable Cities 1. Introduction Achieving sustainable urbanization, along with the preservation of our planet, has been recognized as one of the major challenges of our society

More information

Key Performance Indicators (KPIs) and Standards for Smart Sustainable Cities

Key Performance Indicators (KPIs) and Standards for Smart Sustainable Cities Key Performance Indicators (KPIs) and Standards for Smart Sustainable Cities Smart Sustainable Cities Training Programme, Module SSC-3 1 Contents Aim of this Module Overview of KPIs for SSCs KPI definitions

More information

EU Code of Conduct for Data Centre Efficiency

EU Code of Conduct for Data Centre Efficiency EU Code of Conduct for Data Centre Efficiency A Green Practice Accredited by British Computer Society (BCS) EU Code of Conduct for Data Centre Efficiency Local Organizer Practices in Data Centre Industry

More information

ICT and the Green Data Centre

ICT and the Green Data Centre ICT and the Green Data Centre Scott McConnell Sales Manager c/o Tanya Duncan MD Interxion Ireland Green Data Centres Our Responsibility Data centre greenhouse gas emissions are projected to quadruple by

More information

Greenhouse Gas Offsets and Renewable Energy Certificates: Distinct Commodities in an Evolving Market The Climate Trust

Greenhouse Gas Offsets and Renewable Energy Certificates: Distinct Commodities in an Evolving Market The Climate Trust Greenhouse Gas Offsets and Renewable Energy Certificates: Distinct Commodities in an Evolving Market The Climate Trust Introduction The framework for future climate policy is emerging in the United States

More information

Energy storage in the UK and Korea: Innovation, Investment and Co-operation Appendix 4.1: Stakeholder interviews from Korea

Energy storage in the UK and Korea: Innovation, Investment and Co-operation Appendix 4.1: Stakeholder interviews from Korea Energy storage in the UK and Korea: Innovation, Investment and Co-operation Appendix.1: Stakeholder interviews from Korea Peter Taylor & Lloyd Davies, University of Leeds Appendix.1: Stakeholder interviews

More information

NECAQ Sustainability Program The Business Case

NECAQ Sustainability Program The Business Case NECAQ Sustainability Program The Business Case Key messages Energy efficiency is a fundamental element in the progression towards a future low-carbon economy. Actions to increase energy efficiency can

More information

Standardization: Plans and Progress Franz ZICHY Vice-Chairman Working Party 3 of ITU-T Study Group 5

Standardization: Plans and Progress Franz ZICHY Vice-Chairman Working Party 3 of ITU-T Study Group 5 Standardization: Plans and Progress Franz ZICHY Vice-Chairman Working Party 3 of ITU-T Study Group 5 ITU: unique public/private partnership UN agency for ICTs Members: 193 Member States (Governments and

More information

Energy efficiency in communication networks in Horizon 2020 perspective

Energy efficiency in communication networks in Horizon 2020 perspective Energy efficiency in communication networks in Horizon 2020 perspective Pertti Jauhiainen Network Technologies European Commission DG CONNECT September 25, 2013 EU action to tackle climate change 20-20-20

More information

Green Evaluation Metrics and Software Tool for Data Center

Green Evaluation Metrics and Software Tool for Data Center Green Evaluation Metrics and Software Tool for Data Center Wong Hui Shin Faculty of Computing and Informatics, Multimedia University, Cyberjaya, Selangor, Malaysia. hswong@mmu.edu.my Saravanan Muthaiyah

More information

How To Promote A Green Economy In The European Constitution

How To Promote A Green Economy In The European Constitution Informal Meeting of EU Environment Ministers Background document Session Green growth: greening the European Semester and the EU 2020 Strategy 1) Introduction Milan, 16July 2014-15.00-18.00 The European

More information

COMMISSION RECOMMENDATION. of XXX

COMMISSION RECOMMENDATION. of XXX EUROPEAN COMMISSION Brussels, XXX [ ](2013) XXX draft COMMISSION RECOMMENDATION of XXX on the use of common methods to measure and communicate the life cycle environmental performance of products and organisations

More information

DCA Certification of Data Centres Requirements V1.5

DCA Certification of Data Centres Requirements V1.5 1 2 3 4 5 6 7 8 9 10 11 DCA Certification of Data Centres Requirements V1.5 2015, Data Centre Alliance Limited (www.datacentrealliance.org). All rights reserved. This publication may not be reproduced

More information

Product Environmental Information in EU Environmental Policy

Product Environmental Information in EU Environmental Policy Product Environmental Information in EU Environmental Policy Pavel MISIGA Sustainable Production and Consumption Directorate General for Environment European Commission 1 Tonnes CO2 equiv/capita/year GHGs

More information

Introducing Gazprom Energy Stable, secure, reliable energy from one of the world s biggest names. With deals tailored around your needs, not ours.

Introducing Gazprom Energy Stable, secure, reliable energy from one of the world s biggest names. With deals tailored around your needs, not ours. Introducing Gazprom Energy Stable, secure, reliable energy from one of the world s biggest names. With deals tailored around your needs, not ours. About us Gazprom Energy customers receive a long lasting

More information

ICT SOLUTIONS FOR A SMART LOW-CARBON FUTURE Supporting a solution agenda in Cancun

ICT SOLUTIONS FOR A SMART LOW-CARBON FUTURE Supporting a solution agenda in Cancun ICT SOLUTIONS FOR A SMART LOW-CARBON FUTURE Supporting a solution agenda in Cancun This paper is a result of a public private dialogue in Guadalajara, Mexico, the 8-9th of November 2010, focusing on the

More information

Report of Study Group on Revitalization Policies of Data. Centers in the Cloud Computing Age

Report of Study Group on Revitalization Policies of Data. Centers in the Cloud Computing Age Attachment Report of Study Group on Revitalization Policies of Data Centers in the Cloud Computing Age Study Group on Revitalization Policies of Data Centers in the Cloud Computing Age May 2010 http://www.soumu.go.jp/english/ict

More information

Finding the Supply Chain Carbon Lever

Finding the Supply Chain Carbon Lever Finding the Supply Chain Carbon Lever Workshop Summary May 13, 2013 Key takeaways Major themes across the discussions in the room and over lunch focused on the following: Supply chain offers one of the

More information

Energy Efficiency Policy Options for Australian and New Zealand Data Centres

Energy Efficiency Policy Options for Australian and New Zealand Data Centres Energy Efficiency Policy Options for Australian and New Zealand Data Centres Final Report Consumer Research Associates April 2014 A joint initiative of Australian, State and Territory and New Zealand Governments.

More information

The NREN cloud strategy should be aligned with the European and national policies, but also with the strategies of the member institutions.

The NREN cloud strategy should be aligned with the European and national policies, but also with the strategies of the member institutions. 4 External influences PESTLE Analysis A PESTLE analysis is a useful tool to support the investigation and decision process relating to cloud services. PESTLE in general covers Political, Economic, Social,

More information

Can the Cloud Be Green? Emerging Standards, Programs and Metrics for Decision-Makers

Can the Cloud Be Green? Emerging Standards, Programs and Metrics for Decision-Makers Can the Cloud Be Green? Emerging Standards, Programs and Metrics for Decision-Makers Emerging Green Conference Portland, OR September 23, 2015 Peter May-Ostendorp, PhD, LEED AP O+M Principal, Xergy Consulting

More information

Introduction to the 2015 Horizon 2020 Energy Call for Proposals. 14 July 2014

Introduction to the 2015 Horizon 2020 Energy Call for Proposals. 14 July 2014 Introduction to the 2015 Horizon 2020 Energy Call for Proposals 14 July 2014 Overview Horizon 2020 Overview Energy Challenge Work Programme and Calls for Proposals Horizon 2020 opportunities outside the

More information

Contact: Environment and Green Technologies Department Phone: 01-7272480 Email: greentech@enterprise-ireland.com www.envirocentre.

Contact: Environment and Green Technologies Department Phone: 01-7272480 Email: greentech@enterprise-ireland.com www.envirocentre. Contact: Environment and Green Technologies Department Phone: 01-7272480 Email: greentech@enterprise-ireland.com www.envirocentre.ie Enterprise Ireland August 08 (152) Eco-labels GreenTech Support Eco-labels

More information

Your guide to hosted data centres: How to evaluate potential providers

Your guide to hosted data centres: How to evaluate potential providers Your guide to hosted data centres: How to evaluate potential providers Finding the right hosted data centre More than ever, organizations require a secure, reliable and flexible data centre to meet growing

More information

Introduction to AWS Economics

Introduction to AWS Economics Introduction to AWS Economics Reducing Costs and Complexity May 2015 2015, Amazon Web Services, Inc. or its affiliates. All rights reserved. Notices This document is provided for informational purposes

More information

Energy Savings in the Data Center Starts with Power Monitoring

Energy Savings in the Data Center Starts with Power Monitoring Energy Savings in the Data Center Starts with Power Monitoring As global competition intensifies, companies are increasingly turning to technology to help turn mountains of data into a competitive edge.

More information

University of Brighton Sustainable Procurement Strategy 2011-2015

University of Brighton Sustainable Procurement Strategy 2011-2015 University of Brighton Sustainable Procurement Strategy 2011-2015 Sustainable procurement in a challenging environment Introduction There is widespread recognition that climate change and the use of dwindling

More information

A New World Of Colocation

A New World Of Colocation Colocation Whitepaper A New World Of Colocation Can colocation service providers evolve their service offerings to satisfy today's commercial needs, demands and expectations; while differentiating themselves

More information

How to promote bio-based products?

How to promote bio-based products? How to promote bio-based products? Introduction In the past few years there has been a growing interest among consumers all over the world in the protection of the environment. The limited availability

More information

Measuring Energy Efficiency in a Data Center

Measuring Energy Efficiency in a Data Center The goals of the greening of the Data Center are to minimize energy consumption and reduce the emission of green house gases (carbon footprint) while maximizing IT performance. Energy efficiency metrics

More information

The NREN s core activities are in providing network and associated services to its user community that usually comprises:

The NREN s core activities are in providing network and associated services to its user community that usually comprises: 3 NREN and its Users The NREN s core activities are in providing network and associated services to its user community that usually comprises: Higher education institutions and possibly other levels of

More information

Deep Dive Think Tank: Energy Costs and Strategies for Reduction

Deep Dive Think Tank: Energy Costs and Strategies for Reduction Deep Dive Think Tank: Energy Costs and Strategies for Reduction Andrew Donoghue European research manager, Datacenter Technologies 1 Discussion points Does energy cost really matter or does uptime still

More information

Data Centre and ICT Energy Metrics - The View from Australia

Data Centre and ICT Energy Metrics - The View from Australia 2010/TEL42/DSG/WKSP2/013 Data Centre and ICT Energy Metrics - The View from Australia Submitted by: Australia Green ICT Seminar Bandar Seri Begawan, Brunei Darussalam 3 August 2010 Data Centre and ICT

More information

MACHINE TO MACHINE COMMUNICATIONS. ETSI TC M2M Overview June 2011

MACHINE TO MACHINE COMMUNICATIONS. ETSI TC M2M Overview June 2011 MACHINE TO MACHINE COMMUNICATIONS ETSI TC M2M Overview June 2011 About the ETSI TC M2M ETSI: the European Telecommunication Standards Institute One of the 3 European SDOs (CEN, CENELEC, ETSI). ETSI is

More information

Uninterruptible Power Supply Product Regulations and Standardization in the European Union. By Matteo Tricarico Patents and Regulatory Engineer

Uninterruptible Power Supply Product Regulations and Standardization in the European Union. By Matteo Tricarico Patents and Regulatory Engineer Uninterruptible Power Supply Product Regulations and Standardization in the European Union By Matteo Tricarico Patents and Regulatory Engineer Abstract The Uninterruptible Power Supply (UPS) design falls

More information

Information Economy Strategy amee s Consultation Response to the Department for Business, Innovation & Skills

Information Economy Strategy amee s Consultation Response to the Department for Business, Innovation & Skills Information Economy Strategy amee s Consultation Response to the Department for Business, Innovation & Skills March 2013 amee 4th Floor, 70/74 City Road London EC1Y 2BJ 1 amee amee s mission is to provide

More information

Table of Contents. 2 Why IT Organizations Everywhere Need to go Green. 3 Greening the Data Center

Table of Contents. 2 Why IT Organizations Everywhere Need to go Green. 3 Greening the Data Center WHITE PAPER: Energy Efficiency Go Green: Energy Efficiency for the IT Organization Table of Contents 2 Why IT Organizations Everywhere Need to go Green 3 Greening the Data Center 5 Savvis Commitment to

More information

Energy Efficient Systems

Energy Efficient Systems Energy Efficient Systems Workshop Report (September 2014) Usman Wajid University of Manchester United Kingdom Produced as a result of Workshop on Energy Efficient Systems @ ICT4S conference, Stockholm

More information

Smart Cities Stakeholder Platform. Public Procurement for Smart Cities

Smart Cities Stakeholder Platform. Public Procurement for Smart Cities Smart Cities Stakeholder Platform Public Procurement for Smart Cities SMART CITIES STAKEHOLDER PLATFORM FINANCE WORKING GROUP GUIDANCE DOCUMENT PUBLIC PROCUREMENT FOR SMART CITIES Document information

More information

IV. SHIFT TO THE CLOUD: ACHIEVING EFFICIENCY THROUGH CLOUD COMPUTING AND DATA CENTER CONSOLIDATION *

IV. SHIFT TO THE CLOUD: ACHIEVING EFFICIENCY THROUGH CLOUD COMPUTING AND DATA CENTER CONSOLIDATION * IV. SHIFT TO THE CLOUD: ACHIEVING EFFICIENCY THROUGH CLOUD COMPUTING AND DATA CENTER CONSOLIDATION * OVERVIEW The federal government is the world s largest consumer of information technology (IT), spending

More information

Reforming the business energy efficiency tax landscape

Reforming the business energy efficiency tax landscape Reforming the business energy efficiency tax landscape Consultation response from: Emission Trading Group (ETG) Contact details: John Craven, john.craven@etg.uk.com ETG welcomes this review of the business

More information

Agenda. The Digital Agenda for Europe Instruments to implement the vision EC actions to promote ehealth interoperability

Agenda. The Digital Agenda for Europe Instruments to implement the vision EC actions to promote ehealth interoperability IHE epsos Connectahon Pisa, 12 April 2011 The European Commission s s vision for ehealth interoperability Benoit Abeloos Research Program Officer, Interoperability - Standardization European Commission

More information

COMMISSION OF THE EUROPEAN COMMUNITIES

COMMISSION OF THE EUROPEAN COMMUNITIES EN EN EN COMMISSION OF THE EUROPEAN COMMUNITIES Brussels, 28.11.2008 COM(2008) 798 final COMMUNICATION FROM THE COMMISSION TO THE COUNCIL, THE EUROPEAN PARLIAMENT, THE EUROPEAN ECONOMIC AND SOCIAL COMMITTEE

More information

Office of the Government Chief Information Officer. Green Data Centre Practices

Office of the Government Chief Information Officer. Green Data Centre Practices Office of the Government Chief Information Officer Green Data Centre Practices Version : 2.0 April 2013 The Government of the Hong Kong Special Administrative Region The contents of this document remain

More information

Data centres in 2009 What is happening to facilities? November 2009

Data centres in 2009 What is happening to facilities? November 2009 Data centres in 2009 What is happening to facilities? November 2009 Data centres in 2009 Should I teleconference or fly to California? Easy Should I teleconference or get the train to Luton? Harder Data

More information

REPORT FROM THE COMMISSION TO THE EUROPEAN PARLIAMENT AND THE COUNCIL. on the voluntary ecodesign scheme for games consoles

REPORT FROM THE COMMISSION TO THE EUROPEAN PARLIAMENT AND THE COUNCIL. on the voluntary ecodesign scheme for games consoles EUROPEAN COMMISSION Brussels, 22.4.2015 COM(2015) 178 final REPORT FROM THE COMMISSION TO THE EUROPEAN PARLIAMENT AND THE COUNCIL on the voluntary ecodesign scheme for games consoles {SWD(2015) 88 final}

More information

A new electricity market for Northern Ireland and Ireland from 2016 - Integrated Single Electricity Market (I-SEM)

A new electricity market for Northern Ireland and Ireland from 2016 - Integrated Single Electricity Market (I-SEM) A new electricity market for Northern Ireland and Ireland from 2016 - Integrated Single Electricity Market (I-SEM) Non-technical summary High level design Draft Decision Paper SEM -14-047 June 2014 1 INTRODUCTION

More information

SCP Issues for Business and Industry

SCP Issues for Business and Industry SCP Issues for Business and Industry Introduction Business and industry are key players in the SCP agenda. They are at the core of production and are also key organizational consumers. As the most important

More information

Matthijs SOEDE Research Programme Officer Unit G3 Renewable Energy Sources DG Research and Innovation

Matthijs SOEDE Research Programme Officer Unit G3 Renewable Energy Sources DG Research and Innovation HORIZON HORIZON 2020 2020 Matthijs SOEDE Research Programme Officer Unit G3 Renewable Energy Sources DG Research and Innovation The Multiannual Financial Framework 2014-2020: European Council conclusions,

More information

Norwegian position on the proposed EU framework for climate and energy policies towards 2030

Norwegian position on the proposed EU framework for climate and energy policies towards 2030 Norwegian position on the proposed EU framework for climate and energy policies towards 2030 The EU plays an important role as a global leader in climate policy and has a fundamental interest in strengthening

More information

for Oil & Gas Industry

for Oil & Gas Industry Wipro s Upstream Storage Solution for Oil & Gas Industry 1 www.wipro.com/industryresearch TABLE OF CONTENTS Executive summary 3 Business Appreciation of Upstream Storage Challenges...4 Wipro s Upstream

More information

Published 2Q 2012. Eric Woods Research Director. Clint Wheelock President

Published 2Q 2012. Eric Woods Research Director. Clint Wheelock President EXECUTIVE SUMMARY: Green Data Centers IT Equipment, Power and Cooling Infrastructure, and Monitoring and Management Tools: Global Industry Drivers, Market Analysis, and Forecasts NOTE: This document is

More information