INSTALLATION MANUAL. PC3OOO Version 7.51

Size: px
Start display at page:

Download "INSTALLATION MANUAL. PC3OOO Version 7.51"

Transcription

1 INSTALLATION MANUAL PC3OOO Version 7.51

2 DOC NOTICE NOTICE: The Canadian Department of Communications label identifies certified equipment. This certification means that the equipment meets certain telecommunications network protective, operational and safety requirements. The Department does not guarantee the equipment will operate to the user's satisfaction. Before installing this equipment, users should ensure that it is permissible to be connected to the facilities of the local telecommunications company. The equipment must also be installed using an acceptable method of connection. In some cases, the company's inside wiring associated with a single line individual service may be extended by means of certified connector assembly (telephone extension cord). The customer should be aware that compliance with the above conditions may not prevent degradation of service in some situations. Repairs to certified equipment should be made by an authorized Canadian maintenance facility designated by the supplier. Any repairs or alterations made by the user to this equipment, or equipment malfunctions, may give the telecommunications company cause to request the user to disconnect the equipment. User should ensure for their own protection that the electrical ground connections of the power utility, telephone lines and internal metallic water pipe system, if present, are connected together. This precaution may be particularly important in rural areas. CAUTION: Users should not attempt to make such connections themselves, but should contact the appropriate electric inspection authority, or electrician, as appropriate. The Load Number (LN) assigned to each terminal device denotes the percentage of the total load to be connected to a telephone loop which is used by the device, to prevent overloading. The termination on a loop may consist of any combination of devices subject only to the requirement that the total of the Load Numbers of all the devices does not exceed 100. The Load Number of this device is 42. AVIS: L'étiquette du ministère des Communications du Canada identifie le matériel homologué. Cette étiquette certifie que le matériel est conforme à certaines normes de protection, d'exploitation et de sécurité des réseaux de télécommunications. Le Ministère n'assure toutefois pas que le matétiel fonctionnera à la satisfaction de l'utilisateur. Avant d'installer ce matériel, l'utilisateur doit s'assurer qu'il est permis de le raccorder aux installations de l'entreprise locale de télécommunication. Le matériel doit également être installé en suivant une méthod acceptée de raccordement. Dans certains cas, les fils intérieurs de l'entreprise utilisés pour un service individuel a ligne unique peuvent être prolongés au moyen d'un dispositif homologué de rassordement (cordon prolongateur tèlèphonique interne). L'abonné ne doit pas oublier qu'il est possible que la conformité aux conditions énoncées ci-dessus n'empechent pas la dégradation du service dans certaines situations. Actuellement, les entreprises de télécommunication ne permettent pas que l'on raccorde leur matériel a des jacks d'abonné, sauf dans les cas précis prévus par les tarrifs particuliers de ces entreprises. Les réparations de matériel homologué doivent etre effectuées par un centre d'entretien canadien autorisé désigné par le fournisseur. La compagnie de télécommunications peut demander à l'utilisateur de débrancher un appareil à la suite de réparations ou de modifications effectuées par l'utilisateur ou à cause de mauvais fonctionnement. Pour sa propre protection, l'utilisateur doit s'assurer que tous les fils de mise à la terre de la source d'énergie électrique, des lignes téléphoniques et des canalisations d'eau métalliques, s'il y en a, sont raccordés ensemble. Cette précaution est particulièrement importante dans les régions rurales. AVERTISSEMENT: L'utilisateur ne doit pas tenter de faire ces raccordements lui-meme; il doit avoir recours a un service d'inspection des installations électriques, ou a electricien, selon le cas. L'indice de charge (IC) assigné a chaque dispositif terminal indique, pour éviter toute surcharge, le pourcentage de la charge totale qui peut etre raccordée a un circuit téléphonique bouclé utilisé par ce dispositif. La terminaison du circuit bouclé peut etre constituée de n'import quelle combinaison de dispositifs, pourvu que la somme des indices de charge de l'ensemble des dispositifs ne dépasse pas 100. L'indice de charge de cet dispositif est 42.

3 TABLE OF CONTENTS Specifications 1 Features 2 Installation 3 Bench Testing 3 Mounting Panel 3 Hook-up Procedure 3 Terminal Connections 4 Guidelines for Smoke Detector Location 6 Keypad Functions 7 Introduction 7 Master Code 7 Installer s Programming Code 7 Arming 7 Disarming 7 Auto-Bypass/Home-Away Arming 7 Zone Bypassing [Q]+[1] 7 Trouble Display [Q]+[2] 8 Alarm Memory Display [Q]+[3] 8 Switched Auxiliary Supply Control [Q]+[Hold Down 4] 9 User s Programming Commands [Q]+[5]+[Master Code] 9 User s Functions Command [Q]+[6]+[Master Code] 9 Installer s Test [Q]+[6]+[Master Code]+[0] 10 Setting the Clock [Q]+[6]+[Master Code]+[1] 10 Auto-arm Time of Day [Q]+[6]+[Master Code]+[2] 10 Quick Arm [Q]+[6]+[Master Code]+[4] 10 Auto-arm Enable [Q]+[6]+[Master Code]+[5] 10 Door Chime [Q]+[6]+[Master Code]+[6] 10 System Test [Q]+[6]+[Master Code]+[8] 10 User Callup [Q]+[6]+[Master Code]+[9] 10 Utility Output Command [Q]+[7] or [Q]+[7]+[Access Code] 11 Installer s Programming Commands _ [Q]+[8]+[Installer s Code] 11 At Home Arming [Q]+[9]+[Access Code] 11 Quick Arm Command [Q]+[0] 11 Quick Exit [Q]+[0] when armed 11 Keypad Zones 11 Printer Setup 12 Configuring the Printer 12 Programming the Panel for Use with a Printer 12 Downloading 13 Programming Guide 14 Introduction 14 Reviewing Programmed Data 14 [00] Binary Programming 14 [01] 1st Phone Number 14 [02] 1st Account Code 15 [03] 2nd Phone Number 15

4 [04] 2nd Account Code 15 [05]...[15] Reporting Code Explanation 15 [05] Alarm Reporting Codes Zones 1 to 8 15 [06] Alarm Reporting Codes Zones 9 to [07] Restoral Reporting Codes Zones 1 to 8 15 [08] Restoral Reporting Codes Zones 9 to [09] Utility Alarm Reporting Codes 16 [10] Utility Restoral Reporting Codes 16 [11] Reporting Codes for Closing (Arming) with Access Codes 1 to 8 16 [12] Reporting Codes for Closing (Arming) with Access Codes 9 to [13] Reporting Codes for Opening (Disarming) with Access Codes 1 to 8 16 [14] Reporting Codes for Opening (Disarming) with Access Codes 9 to [15] Reporting Codes for Miscellaneous Functions 17 [16] Zone Definitions for Zones 1 to 8 17 [17] Zone Definitions for Zones 9 to [18] 1st System Option Code 18 [19] 2nd System Option Code 18 [20] Zones 1 to 8 Bypass Mask 18 [21] Zones 9 to 16 Bypass Mask 18 [22] System Times 18 [23] System Clock Times 19 [24] New Installer s Code 19 [25] New Master Code (Access Code Number 1) 19 [26] Downloading Access Code 19 [27] Communicator Format Options 19 [28] Programmable Input and Output Options 20 [29] [30] [31] [32] Split Arming 21 [33] Communicator Call Direction Options 21 [34] Software Reset EEPROM Memory to Factory Defaults 22 [35] Through [42] - For Future Use 22 [43] Access Bypass Mask (Codes 1 to 8) 22 [44] Access Bypass Mask (Codes 9 to 16) 22 [45] TLM Restoral Reporting Code 22 [46] Downloading Computer Telephone Number 22 [47] Modem Configuration 22 [48] Panel Identification Code 22 [49] Printer Configuration 22 [50] After Alarm Reporting Code 23 [51] 3rd System Option Code 23 [52] Delay Before Transmission 23 [53] Auto-arm Abort Reporting Code 23 [54] System Test Reporting Code 23 [90] Installer s Lockout Enable 23 [91] Installer s Lockout Disable 23 Programming Work Sheets 24 Just for the Record 35 Hookup Diagrams 36 Limited Warranty 38

5 SPECIFICATIONS Control Panel Specifications 21 zones including: 16 fully programmable supervised zones (EOL resistors) Supervised fire zone 1 auxiliary normally open zone 3 keypad activated zones Audible alarm output: Bell output 700 ma, fused at 5 Amps, 12 VDC unregulated Steady or pulsed output EEPROM memory: Does not lose codes or system status on complete AC and battery failure Programmable output: Transistor switch sinks 50 ma to ground Operation controllable through program options Powerful 1.5 amp regulated power supply: 400 ma auxiliary supply, 12 VDC unregulated Separately fused for battery, keypad/auxiliary supply and bell output Supervision for loss of AC power, low battery Internal clock locked to AC power frequency Switched Smoke Detector Supply Output: Controlled from keypad [Q][4] command Battery required: 12 volt 4 Ah minimum rechargeable gel-cell or sealed lead-acid battery Remote Keypad Specifications (PC3000RK) Four wire (QUAD) hook-up and up to 3 keypads per system Built-in piezoelectric buzzer Full annunciation of zones and system status Nominal current draw 60 ma Dimensions 5.5 x 4.5 x 1 deep (140 x 114 x 25 mm) Output Voltage Specification Typically, with normal AC in and a fully charged battery, the output voltage will be 13.8 VDC. With AC off and a discharged battery, the voltage will go to 10 volts. Devices that require power from the control panel should be capable of normal operation over the voltage range of 10 to 14 VDC. Digital Communicator Specifications 94 reporting codes Transmits all 10BPS and 20BPS single line and extended formats Radionics Rounds and Radionics Parity formats Sescoa Superfast format 3/1, 4/2 and hexadecimal numbers DTMF and Pulse dialing DPDT line seizure True dial tone detection Anti-jam feature Two telephone numbers and two account codes Split reporting of selected transmissions to each telephone number Transformer required: 16.5 VAC, 40VA Dimensions: 11 x 11.8 x 3.3 deep (279 x 300 x 84 mm) Weight: 6.5 lbs (3 kg) 1

6 FEATURES Keypad Programming The PC3000 comes with a default program so it is operational with a minimum of programming. It is completely programmable from the keypad. The panel uses EEPROM memory so that all information is retained even if the panel loses both AC and battery power. Multiple Level Static/Lightning Protection The PC3000 has been carefully designed and tested to provide reliable service. It is built to take static and lightning induced surges and keep on working. Multiple level surge filters are on all zone inputs, the power supply, the keypad connections, the bell output, the auxiliary power supply and the telephone interface. A special ZAP-TRAC circuit board configuration catches high voltage impulses right at the wiring terminals. Protective ground planes surround sensitive areas preventing the spread of damaging voltage surges. Metal Oxide Varistors (MOV s) are placed in all the critical areas to further reduce impulses to safe levels. WATCHDOG MONITOR Circuit Even when all precautions are taken so that voltage surges do not cause damage to the control panel, it is possible to cause temporary disruption to the operation of the microprocessor causing it to lose track of the program sequence. The PC3000 is equipped with an external Watchdog Monitor circuit which continually checks the microprocessor program execution. Advanced Features The PC3000 has many advanced features. Features which provide the security system design flexibility and selling advantage necessary to win those demanding jobs and make them profitable. Some of these features include: EEPROM memory retains all data even on complete AC and battery failure. Panel powers up in last armed or disarmed state before power loss. All programmable zones may be selected as one of 10 different types including; delay, double delay, quadruple delay, instant, follower, follower with home-away, delay with home-away, and 4 types of 24 hour emergency and supervisory circuits. Keypad programming of up to sixteen security codes. Zone bypassing from the keypad. Individual zone and system function indicators on keypad. A keypad activated utility output function for operating lights, door openers, cameras or other devices. Although the PC3000 has many features, it is not difficult to use. All keypad commands are similar and are assisted by audible and visual cues. System Supervision Features The PC3000 continuously monitors a number of possible trouble conditions including: An active battery supervision circuit that periodically tests the battery under load. A loss of the AC power supply. A supervised circuit trouble condition. A telephone line monitoring circuit. A bell circuit failure indicates open circuit or fuse failure. A test code feature which transmits a communicator test code to the monitoring station at a selected time everyday. The test code can be sent at intervals from 1 to 99 days. A bell/siren/communicator test feature which can be activated from the keypad. TLM (Telephone Line Monitoring) restoral transmission. 2

7 INSTALLATION Bench Testing The PC3000 contains a factory default program. Any additional programming required can be done through the keypad. For many applications all that will be required is to enter the telephone number and alarm codes with keypad entries that are as straight forward as dialing a telephone number. If you need help talk to your DSC equipment distributor. Connect 1K ohm 1/2 watt end of line resistors from each zone (Z1 to Z16) input to the closest common COM terminal. Connect an end of line resistor between the Fire input terminal and the COM terminal between Z1 and Z2. Unless all zone are properly terminated with end of line resistors the Ready light will not be on and the panel will not arm unless the Ready light is on. Connect the four keypad wires to the control panel as shown in the connection drawing. To completely test the PC3000 including the communicator data, it is necessary to connect the panel to a digital receiver through a telephone line connection or by connecting the telephone terminals on the PC3000 to a digital communicator test set such as the DSC DTS-1. The DSC DTS-1 digital communicator test set is an inexpensive unit which can simulate the telephone system dial tone and the receiver hand shake and kiss-off tones as well as display the data sent out by a digital communicator. Also, the DTS-1 has a listen-in feature which makes it ideal for monitoring the transmission between communicator and receiver when the PC3000 is connected to the telephone line. If you are using a DTS-1, connect the green and red telephone clips to the TIP and RING terminals and connect the red and black power clips to the AUX [+] and AUX [-] terminals on the PC3000. When power is applied to the panel press the red local-line button on the DTS-1 and observe the display window area. The local-line indicator should be in the local position. For testing purposes, so that the sound level is not too loud, connect a small buzzer to the BELL [+] and BELL [-] terminals to indicate when the panel is in alarm. Connect a 16.5 VAC, 40 VA transformer to the AC terminals. Before plugging in the transformer be sure the circuit board is not resting on anything metallic which may cause a short. Note: The PC3000 will not start up is AC is off and the battery is low. The panel will display trouble #1 under these conditions. When the transformer is plugged in there should be lights on the keypad and the buzzer connected to the bell terminals may go on for a few seconds. The Armed light may be on or off the first time the panel is powered. The last armed/disarmed condition is stored in the EEPROM memory so the panel will always power up in the last armed/disarmed state. If the Armed light is on, enter the default master code [1234] to disarm the panel. If the keypad is not active, check for the presence of AC power at the AC terminals, check the keypad connections and check the panel fuses. If all the zones are properly connected with end of line resistors all of the zone lights will be off. Note that the panel will arm only if all zones are properly connected with end of line resistors (including FIRE zone) so that the Ready light is on. The keypad should beep several times to indicate acceptance of the master code. Enter the master code to arm or disarm the panel. Read the Keypad Commands section of this manual or the Instruction Manual and enter commands on the keypad to become familiar with the different commands. Turn to the Programming Guide in this manual and enter a sample program into the panel through the keypad to become familiar with the programming commands. Mounting Panel Select a dry location close to an unswitched AC source, a ground connection and the telephone connection. Remove printed circuit board, mounting hardware and keypad from cardboard retainer inside panel. Before attaching cabinet to wall, press the five white nylon printed circuit board mounting studs and the ground connection screw into cabinet from the back. Pull all cables into cabinet and prepare them for connection before mounting the circuit board to the back of the cabinet. Press circuit board down onto mounting studs. Hook-up Procedure DO NOT connect transformer or battery until all other wiring has been connected. See power-up procedure. Connect a ground cable from the cabinet ground connection by the shortest and most direct route to a grounding rod. Connect zone cables to zone inputs and put end of line resistors on any unused zones. Connect wires supplying power to motion detectors to auxiliary supply. Install keypads and connect wires to keypad terminals on panel. Connect RJ31-X cord to telephone terminals. Do not insert plug into RJ31-X jack. Warning: Do not use this equipment on a telephone line equipped with call holding feature because the tone generated may interfere with the communicator operation. Connect bell or siren to BELL [+] and BELL [-] terminals. Observe correct polarity for sirens and polarized bells. Connect 1K ohm 1/2 watt resistor across terminals to eliminate trouble condition if bell circuit is not being used. 3

8 Terminal Connections AC Power Terminals Use a 16.5 VAC transformer with a minimum 40 VA rating to supply AC power to the PC3000. The transformer should not be connected to an outlet that is controlled by a switch. If AC failure occurs it is displayed as a trouble on the keypad (see Keypad Functions [Q][2] Trouble Conditions ). It can also be transmitted to the monitoring station as a trouble condition (see Programming Guide [Q][8] sections [09] and [10] for alarm and restore codes and section [20] for AC transmission delay). Auxiliary Power Terminals AUX and GND The auxiliary power supply can be used to power motion detectors and other devices requiring 12 VDC. 400 ma 12 VDC is available from the AUX (positive) and GND (negative) terminals when the PC3000 is used with one keypad. For each additional keypad the auxiliary supply rating must be reduced by 60 ma. The auxiliary supply is fused with the keypad supply at 1 amp. Auxiliary fuse failure transmission can be sent (see [Q][8] sections [09] and [10]). Switched Auxiliary Power Terminals SW AUX and GND The switched auxiliary supply can be switched off momentarily from the keypad (see Keypad Commands [Q][4] ). The SW AUX terminal is positive and the GND terminal negative. The 400 ma auxiliary supply rating must be reduced by any current taken from the switched auxiliary supply. The switched supply shares the same fuse as the auxiliary supply. Bell/Siren Terminals BELL [+] and BELL [-] These terminals are for powering bells or other devices requiring a steady output voltage on alarm. The bell output is fused for 5 amps. When connecting sirens (speakers with siren driver already built-in), be sure to observe the correct polarity. Connect the positive lead to the BELL [+] terminal and the negative lead to the BELL [-] terminal. If no siren or bell is used, connect a 1000 ohm resistor between BELL [+] to BELL [-]. The bell/siren alarm output is pulsed (1 second on 1 second off) when an alarm is created by the [F] keypad zone, by the FIRE zone, or when the Bell Pulse option is enabled in section [19] light 1. Keypad Terminals RED, BLK, YEL and GRN Connect the four coloured wires from the keypads to these terminals. When connecting more than one keypad, connect in parallel across the keypad terminals at the control panel (i.e. all reds wires together, all blacks together, all yellows together and all greens together). The keypad red and black power supply terminals are fused through the auxiliary fuse. Programmable Output Terminal PGM OUT The operation of the Programmable Output depends upon which option is selected in the programming table. See the Programming Guide section [28] for a list of options for the PGM OUT output. The PGM OUT is a 50 ma maximum switch to ground. A 100 ohm current limiting resistor is connected in series. A small relay, a buzzer or other DC operated device may be connected between the 12 VDC AUX (positive) terminal and the PGM OUT (switched negative) terminal on the main board. Auxiliary Input Terminal AUX IN (also KEY ARMING) The AUX IN input terminal is a normally open 24 hour zone. It can be programmed from the keypad to be silent or audible. There is no display on the keypad for the AUX IN input. An alarm on this input is created by applying a positive voltage or by closing a contact between the AUX IN terminal and the positive auxiliary supply. See Programming Guide [Q] [8] sections [09] and [10] for programming the alarm and restoral codes. The AUX IN terminal can also be used as a momentary key arming/disarming input. See Programming Guide section [28] for a list of options for the AUX IN terminal. FIRE Zone Input The FIRE zone is a supervised (normally open alarm initiating contact) end-of-line resistor circuit designed to accept Latching four-wire smoke detectors. (See Fire Circuit Installation Diagram.) On alarm, (fire zone shorted) the bell output will pulse the signal to indicate that the fire zone has been activated. Alarm memory and transmission by the digital communicator is delayed 30 seconds. If the alarm is acknowledged, by pressing the [#] key before the 30 second delay has expired the signals will silence and the transmission will be aborted. If the alarm is not acknowledged and the 30 second delay expires, the fire memory latches and the transmission cannot be aborted. If after signal silence, the smoke detector is not restored to normal, the signals will resound after 90 seconds, and 30 seconds after that, the communicator will transmit. If the signals resound, they may again be silenced, [#] key, and the communicator will be aborted if silence occurs within the 30 second delay period. To restore the smoke detector to normal, clear all products of combustion from the detector and reset the detector by pressing [Q] and then holding down [4] for 2 or 3 seconds. This action will remove power from the smoke detector and if it is clear of smoke, the detector will return to normal. If the detector is still in alarm, the signals will sound immediately and the above sequence will repeat. For an open on the FIRE zone, the keypad sounder will beep twice every 10 seconds and the Trouble light will show on the keypad. The communicator will transmit the trouble condition if programmed for trouble transmission. The audible Trouble signal may be silenced by pressing the [#] key. To determine the nature of the trouble, press [Q][2]. (see the Trouble Display section.) 4

9 Zone Input Terminals Z1 to Z16 Zone inputs Z1 to Z16 are supervised end of line (E.O.L.) resistor circuits. Each input must be terminated with a 1K ohm E.O.L. resistor. An alarm condition will be created if a normally open contact is used to short across the E.O.L. resistor. An alarm is also created if normally closed contacts, wired in series with the E.O.L. resistor, are opened. See the wiring diagram for normally open and normally closed contact connection. The type of circuit or zone definition (delay, instant, 24 hour etc.) is programmed from the keypad using the [Q][8] Installer s Programming commands ("Programming Guide" sections [16] and [17]). Telephone Terminals TIP, RNG, T-1 and R-1 The wires from the RJ31-X telephone jack are connected to these terminals in the following way. TIP Green wire Incoming line from RNG Red wire telephone company T-1 Brown wire Outgoing line to R-1 Grey wire house telephone(s) Note: For proper operation there must be no other telephone equipment connected between the control panel and the telephone company's facilities. Battery Connections Do not connect the battery or the transformer until the wiring is complete. Connect the red battery lead to the positive battery terminal and the black lead to the negative battery terminal. If the connection is made in the reverse the battery fuse will fail. The battery charging voltage is factory adjusted and normally needs no adjustment. Keypad Installation Mount the keypads near the exit-entry doors. The PC3000RK keypad has a red, a black, a green and a yellow wire on the back. Connect these four wires to the four keypad terminals on the control panel using four conductor (quad) telephone wire. Up to three keypads may be connected to one PC3000. Connect all green wires from the keypads to the GRN terminal on the panel. Connect all yellow wires from the keypads to the YEL terminal on the panel. Connect all red wires from the keypads to the RED terminal. Connect all black wires from the keypads to the BLK terminal. Power-up Procedure If the keypads are located a distance from the panel, install an extra keypad temporarily at the panel during power up testing. An extra keypad with a short length of cable and alligator clips attached is helpful for testing and programming PC3000 systems. Connect the transformer, wait approx. 5 seconds. Enter a few keypad commands and open a zone to be sure that the panel and keypad are responding to signals. If the keypad does not respond and there are no indicators on, check for AC voltage at the AC terminals. If there is 16 VAC present, check that the keypad wiring is correct and check the keypad/auxiliary supply fuse. If the keypad/ auxiliary supply fuse is blown check for a short between the keypad red and black wires before replacing the fuse. If the keypad is responding normally, connect the battery. The red battery lead attaches to the positive battery post and the black battery lead attaches to the negative battery post. Note: The PC3000 will not start up is AC is off and the battery is low. The panel will display trouble #1 under these conditions. Testing The System See Installer s test - [Q] [6] [Master Code] [0] (page 9), or do the following. Contact the monitoring station to request a transmission test. Plug the telephone cord into the RJ31-X jack. If a DTS-1 is being used to monitor communicator transmissions, connect as described in Bench Testing section and place the DTS-1 in the line mode by pressing the red LINE/LOCAL button. Arm the panel, wait for the exit delay to expire and trip a detector on an instant circuit. Wait for the communication to complete. Disarm panel and check with the monitoring station to confirm the transmission. Perform additional transmissions required by the monitoring station. Check the Trouble light on the keypad. If it is on, press [Q] then [2] to determine if there is a system trouble. The Trouble Display section in Keypad Commands gives a description of the different trouble conditions. Instructing End-User Fill out the system reference guide in the PC3000 Instruction Manual. Check off sections in the manual which apply to the user s system and make additional notes if necessary. Describe the system to an authorized user. Describe arming and disarming procedures. Describe the basic keypad functions. Assist the user in working through examples of each type of command. Provide user with the Instruction Manual and instruct them to read the manual to become familiar with the system operation. Instruct the user to test the system on a regular basis as described in the Instruction Manual. The Master Code should be changed from the default setting and recorded in the Instruction Manual. 5

10 GUIDELINES FOR SMOKE DETECTOR LOCATION Experience has shown that all hostile fires in family living units generate smoke to a greater or lesser extent. Experiments using typical fires in family living units indicate that detectable quantities of smoke precede detectable levels of heat in most cases. For these reasons, smoke detectors should be installed outside of each sleeping area and on each additional story of the family unit. The following information is for general guidance only and it is recommended that the smoke detector manufacturer's literature be used for detailed installation instructions. It is recommended that additional smoke detectors beyond those required be installed for increased protection. The added areas include: basement, bedrooms, dining rooms, furnace room, utility room and hallways not protected by the required detectors. Bedroom Living Room Basement Hall Bedroom Dining Room Bedroom Bedroom FIG. 3: A smoke detector should be located on each story of the living unit. Bathroom Bedroom Ceiling 4 in. (0.1m) Kitchen Living Room Acceptable here Never here 4 in. (0.1m) minimum FIG. 1: A smoke detector should be located between the sleeping area and the rest of the family unit. Top of detector acceptable here 12 in. (0.3m) maximum Bedroom Kitchen Dining Room Note: Measurements shown are to the closest edge of the detector. Side wall Bedroom Living Room Family Room Bedroom FIG. 2: In the family living units with more than one sleeping area, a smoke detector should be located to protect each sleeping area. FIG. 4: Smoke Detector mounting - Dead Air Space. The smoke from a fire generally rises to the ceiling, spreads out across the ceiling surface and begins to bank down from the ceiling. The corner where the ceiling and wall meet is an air space into which the smoke may have difficulty penetrating. In most fires, this dead air space measures about 4 in. (0.1m) along the ceiling from the corner and about 4 in. (0.1m) down the wall as shown in Figure 4. Detectors should not be placed in the dead air space. 6

11 KEYPAD FUNCTIONS Introduction The PC3000RK remote keypad provides complete information and control of the PC3000 control panel. The panel can be fully programmed from the keypad. The 16 zone lights and the fire alarm light provide alarm and status indication for the alarm circuits. The 6 function lights guide the user in operating the system. The built-in buzzer lets the user hear correct key entries and other alert signals. The 12 digit keypad is used for code entry and other programming functions. All keypad entries are made by pressing one key at a time. The keypad is normally resting in the arm-disarm mode. In this condition the zone lights are indicating the opening and closing of zones. The Ready light comes on when all zones are closed. The system can be directed to perform other functions such as zone bypassing, displaying trouble conditions, displaying alarm memory and programming by entering one of the various [Q] commands described below. Pressing the [#] key or not making any key entry for 2 minutes always returns the keypad to the arm-disarm mode. Master Code A default Master Security Code 1234 is programmed into the PC3000 at the factory. The Master Security Code is used for arming and disarming the control panel, for programming up to fifteen additional security codes using the [Q][5] command and for entering other user functions using the [Q][6] command. The Master Code can be reprogrammed if the installer leaves section [19] light 2 off. Because the PC3000 uses EEPROM memory the codes and other data are retained even after complete AC and battery failure. Installer s Programming Code A default Installer s Programming Code 3000 is programmed into the PC3000. This code is used with the [Q][8] command by the installer to gain access to the system in order to enter panel or communicator program information. The Installer s Programming Code may be changed by the installer. Arming Check to see if the Trouble or Bypass light is on before arming the PC3000. Close all protected doors and windows and stop movement in areas covered by motion detectors. Check to see that the Ready light is on (all zones are closed). The system cannot be armed unless the Ready light is on. Enter a [4 Digit Security Code]. As each digit is entered the keypad buzzer will beep. If the security code was entered incorrectly, the sounder will beep steadily for 2 seconds. If the code was entered correctly but the Ready light was not on, the keypad will beep quickly followed by a steady tone. When the correct code is entered, the Armed light will come on and the keypad buzzer will beep quickly. Exit the premises through the designated exit-entry door. At the end of the allowed exit time all lights on the keypad will go out except the Armed light. See the Installer s Programming [Q][8] Command section for instructions on how to change the exit time. Also see, Quick Arm and At Home Arming. Disarming Enter the premises through the designated exit-entry door. The keypad buzzer will be on. Go to the keypad and enter the [4 digit security code]. If an error is made in entering the code, press the [#] key and enter the code again. The Armed light will go out and the keypad sounder will stop. The correct security code must be entered before the allowed entry time expires. To change the entry time see Installer s Programming Command, [Q][8]. If an alarm occurred while the panel was armed, the Memory light and the Zone light which caused the alarm will start to flash and stay flashing for 2 minutes when the panel is disarmed. Pressing the [#] key returns the panel to the normal armdisarm mode. Auto-bypass/Home-Away Arming If a correct security code is entered, and you do not exit the premises, the system will, at the end of the Exit delay time, arm with interior zones automatically bypassed if those interior zones have been programmed as Home-Away zones. The Bypass light will come on immediately following the arming code being entered until a delay zone is tripped or [Q] [1] is entered to reactivate bypassed home-away zones. (See programming sections [16] and [14], zone definitions for programming zones as Home-Away.) This is a convenience feature for the user who wishes to remain at home with the system armed. The user does not have to manually bypass the home-away zones. To reactivate the home-away zones that have been automatically bypassed, press [Q] [1]. The Bypass light will go out. This command is a quick method of fully arming the system before going to bed. Zone Bypassing [Q]+[1] A bypassed zone will not cause an alarm. If a zone is bypassed the panel may be armed ( Ready light will be on) even if the zone is open. Use zone bypassing when access is needed to part of the protected area. Also, damaged wiring or contacts on a zone may be temporarily bypassed until repairs can be made so that the panel can be armed. To bypass zones, enter [Q] [1] and the zone number(s) to be bypassed. Press [#] to return to Ready (arm-disarm mode). When bypassing zones, two digits must be entered for the zone number(s) to be bypassed (e.g. [Q] [1] [01]...[16]). To remove all bypasses, enter [Q] [1] [00] [#]. The Zone lights which are on, while the Bypass light is flashing, indicate the bypassed zones. Remember that if no keypad entry is made for more than 2 minutes the keypad will return to the arm-disarm mode. Then, in order to bypass a zone the complete command must be re-entered. Once 7

12 the bypass command is entered, pressing [99] recalls the last zone or group of zones which was bypassed. If the same group of zones is bypassed each time, this bypass recall feature can be used instead of having to bypass zones individually. When the PC3000 is programmed, the ability to bypass certain zones may be eliminated. In this case, the Zone lights for those zones will not come on in response to the bypass command. See the Zone Bypass Mask instruction in the [Q][8] Installer s programming section. If the Bypass light is on when arming the panel, the [Q][1] command should be used to see which zones are bypassed so that zones are not unintentionally bypassed. Zone bypasses are automatically cancelled when the panel is disarmed. If light 8 in section [19] is on then a code must be entered with [Q]+[1] to bypass zones. Only the zones assigned to the same side of the system as the user code can be bypassed. The ability to bypass using certain access codes can be eliminated. See the Access Bypass Mask instruction in the [Q] [8] Installer s Programming section. Note: At no time can any armed zone be bypassed. Trouble Display [Q]+[2] The PC3000 continuously monitors a number of possible trouble conditions. If one of these conditions occurs, the keypad Trouble indicator will light and the audible indication will sound (two short beeps every 10 seconds). When the [#] key is pressed the audible indication will stop but the Trouble indicator light will remain on until the trouble is cleared. Trouble conditions can also be transmitted to the monitoring station (see Programming Guide sections [09] and [10] for alarm and restoral trouble codes). Press the [Q] then [2] keys to display the type of trouble. The Zone lights indicate the type of trouble condition. 1 Low stand-by battery 2 AC power failure 3 Day zone trouble 4 Telephone line trouble 5 Unsuccessful communication attempt with monitoring station 6 Bell circuit failure 7 Smoke detector zone trouble 8 Loss of time on internal clock Press [#] to return to Ready. 1 Low Battery...A battery trouble will be displayed and can be reported if the battery is weak, disconnected or the battery fuse is blown. Only one low battery alarm or restoral transmission takes place per arming period. Low battery trouble display is latching and can only be cleared by battery restoration, arming and disarming panel then accessing trouble indication. 2 AC Power Failure...There is no audible annunciation on AC power failure. The system Trouble light will come on but the audible indication will not sound until there is a low battery condition. Transmission delay can be programmed for 1 to 99 minutes. See Programming Guide section [22]. 3 Day Zone Trouble...This trouble applies only to zones which have been programmed as day zones. ( Programming Guide section 16 & 17). A day zone creates a trouble signal when the panel is disarmed and an alarm signal when the panel is armed. 4 Telephone Line Trouble...A telephone line trouble is generated when the line voltage drops below 3 volts for more than 30 seconds. It generates a keypad trouble when the system is disarmed and rings a local alarm when the panel is armed if section [19] light 5 is off. 5 Unsuccessful Communication...If the digital communicator is unsuccessful communicating with the monitoring station after eight attempts, a trouble is generated. If a later attempt to communicate is successful the trouble is cleared. 6 Bell Circuit Failure...If the bell fuse is blown or the bell circuit is open, a keypad trouble and a trouble transmission are generated. 7 Smoke Detector Zone Trouble...If a FIRE zone is open circuit, a keypad trouble and a trouble transmission are generated. A trouble on the FIRE zone will unconditionally initiate an audible indication on the keypad. This means that even if any other previous trouble has been silenced, a FIRE zone trouble will restart the keypad buzzer. 8 Loss of Internal Time...When the PC3000 is powered up or reset, the internal time of day clock needs to be set to the correct time. This trouble is cleared when the trouble display is viewed and exited or when an attempt is made to reset the internal time of day clock. See [Q][6] User s Function Command for resetting time of day clock. If the [9] is pressed while in the trouble display mode the most recent trouble will be displayed on the zone LEDs. This trouble memory feature is useful as a diagnostic aid when installing and servicing the PC3000. Alarm Memory Display [Q]+[3] Press [Q] then [3] to enter the alarm memory mode. The Memory light will flash and any alarm caused during the last armed period will be displayed on the zone lights. In addition to the last alarm memory there are 2 history levels. After entering the memory mode (pressing [Q] then [3]), pressing [9] will cause the keypad to display the two other levels of alarm history. Each time [9] is pressed the keypad will beep 1, 2 or 3 times to indicate which level of history is being viewed. When the panel is armed, the last alarm memory is cleared and the contents moves to the 1st history level. The Memory light will only be on when there was an alarm during the last armed period. Press [#] to return to Ready. Switched Auxiliary Supply Control [Q]+[Hold Down 4] To interrupt the switched auxiliary power supply press [Q] then hold down [4] for the desired interrupt time. When the [4] is released the system returns to the Ready mode and the switched auxiliary supply is restored. 8

13 User s Programming Commands [Q]+[5]+[MASTER CODE] The [Q][5] user s programming command is used to program additional access codes. Up to 16 user arm-disarm codes may be programmed. The 1st code is the master code (factory default [1234]). The 16th code is optionally a One Time Use or maid code. The 16th code may be changed from a One Time Use code to a regular code using an installer s programming command (section [18]...1st system option code). Remember if no keypad entry is made for more than 2 minutes the keypad will return to the normal arm-disarm display and the complete command will have to be re-entered to program a new access code. Programming Additional Access Codes 1 Press the [Q] and [5] keys then enter the Master Security Code (default [1234]) to enter the additional code programming mode. The Program light and Zone 1 light will be on to show that the first code (the Master Code) is already programmed with the factory default code [1234]. The Master Code may be changed but do not try to erase the Master Code. The installer can disable user changing of the Master Code by turning on light 2 in section [19] additional codes may be programmed. The zone lights are used to indicate which of these codes are already programmed (zone light on steady) and the one which is currently being programmed (zone light is flashing). 3 To program the second code, press [02] then enter a 4 digit code. Zone 2 light will flash and sounder will beep three times and zone light 2 will come on steady after the 4 digit code is entered. 4 To remove the second code, press [02] - the buzzer will beep three times and zone light 2 will flash. Enter [Q] [Q] [Q] [Q], the buzzer will beep three times and zone 2 light will go out to show that the code has been removed. 5 Follow the instructions in 3 or 4 for programming or removing any of the other additional codes. 6 Do not try to remove the Master Code (1st code). The Master Code may be changed but it must not be removed. When changing the Master Code be sure to enter a valid 4 digit number (use only number keys 0 to 9). Do not enter [#] or [Q] as one of the digits. If the Master Code is forgotten and the panel is left disarmed, program a new Master Code using the [Q][8][Installer s Code][25] command. If the Master Code is forgotten and the panel is left armed, the entire programming can be reset to factory default by using the Hardware Reset method described on page To successfully program or remove additional codes, the panel must be put into the code program mode by following step 1 followed by steps 3 or 4. Note that if no key entry is made for 2 minutes the panel will go back to the normal arm/disarm mode, after which step 1 must be repeated to get back into the code program mode. 8 To exit the code program mode press [#]. To review: programming a new code; enter [Q] [5] [Master Code] [01 to 16] [4 digit code] eliminating an existing code; enter [Q] [5] [Master Code] [02 to 16] [Q Q Q Q]. Note: The access code, numbers must be entered as two digits. E.g. 02, 03,..., 15, 16. User s Functions Command [Q]+[6]+[MASTER CODE] This command is used to set the system clock time and to set the Auto-arm time. It is also used to turn on and off a number of system functions. The command is used by entering [Q], [6], [Master Code] then a number from the following list to select the item to be changed. [0] Installer s test [1] System 24 hour clock (enter HH:MM) [2] Auto-arming time (enter HH:MM) [3] DO NOT USE [4] Quick arm enable/disable [5] Auto-arm enable/disable [6] Door chime enable/disable [7] DO NOT USE [8] Bell test function [9] User Initiated Callup Note: The system clock is a 24 hour clock and times must be entered as two digit numbers. e.g.hh - 00, 01,...10,11,...22, 23 MM - 00, 01,...35, ,59 If a printer is attached Day , Month , Year - XX (two digits) e.g. HH: MM: DAY: MONTH: YEAR. Items 1 & 2 are time setting functions. Enter 4 digits representing the time in hours and minutes (HH:MM) based on the 24 hour or military clock. Always enter a leading zero where only one digit is required, 8:05 am would be entered as 0805, 1:30 pm would be entered as Items [0], [4], [5] and [6] turn on and off various features. When the item key is pressed, the feature is turned on if the keypad beeps quickly 3 times. The feature is turned off if the keypad sounds one long beep. Pressing item [8] gives a 2 second bell and keypad light test. Pressing [9] makes the panel call the Downloading computer if enabled in section [47]. If a printer is attached to the panel (see section [28]) and is enabled (see section [49]) the clock data entry will be automatically extended to include the day (two digits ), the month (two digits ) and the year (two digits...e.g. 91, 92, 93...etc.). 9

14 Installer s Test [Q]+[6]+[MASTER CODE]+[0] This feature is designed to assist the installer in testing the system. In this mode, the bell or siren will operate for two seconds each time a device is tripped and the zone alarm will be put into the first level memory. The feature is automatically disabled when the panel is armed and disarmed. Each time a zone is tripped or restored in this mode, a signal, if programmed, will be transmitted to the monitoring station. If this is not desired, it is possible to disable the communicator during the test (see section [18] 1st System Option Code ). A printer, if attached, will not function if the communicator is disabled. Notes: Do not use the PC16OUT module during the installer s test. Do not use the installer s test when the panel is partially armed. Setting the Clock [Q]+[6]+[MASTER CODE]+[1] Setting the System 24 Hour Clock (item [1]) tells the system the correct time of day. If the system is without battery and AC power it cannot continue to keep time. Therefore when the panel is first powered up or when it has been without AC power long enough to completely discharge the stand-by battery, the System 24 Hour Clock must be reset. If the time needs to be reset a Trouble #8 will be indicated on the keypad (see [Q][2] System Trouble Command ). If a printer is attached to the panel, setting the clock must include the day, month and year. e.g. HH: MM: DAY: MONTH: YEAR. Auto-arm Time of Day [Q]+[6]+[MASTER CODE]+[2] The PC3000 can be programmed to arm at the same time each day. Programming item [2] sets this time and the feature must be enabled as shown in item [5] (see Autoarm Enable on this page). At the selected auto-arm time the keypad beeper begins to sound and the Bell/Siren will pulse once every 10 seconds to alert anyone on the premises that the system is about to arm. The Bell/Siren pulse can be silenced in section [51] by turning light 1 on. The keypad beeper will sound for one minute before autoarming unless one of the following two methods is used to abort the auto-arm. Auto-arm abort: Any key can be pressed to abort the auto-arm sequence and silence the keypad during the one minute pre-alert (this is the default condition). If section [51] light 2 is on, then a valid 4 digit access code is required to abort the auto-arm sequence. The auto-arm will be attempted at the same time the following day. Auto-arm abort with transmission: Any time an autoarm is aborted using one of the above methods, the reporting code programmed in section [53] will be transmitted to the central station. Quick Arm [Q]+[6]+[MASTER CODE]+[4] The Quick Arm feature is enabled by pressing the [4] key while in the User Functions Command section. When enabled (enabled 3 beeps...disabled one long beep) the panel can be armed by entering [Q][0]. The closing code transmitted for Quick Arm is the same as the code which is programmed for the Master Code. Auto-arm Enable [Q]+[6]+[MASTER CODE]+[5] Entering [Q] [6] [Master Code] [5] will enable/disable the Auto-arming feature. When the feature is being Enabled, the keypad buzzer will sound 3 beeps and when being Disabled the buzzer will sound one long beep. Door Chime [Q]+[6]+[MASTER CODE]+[6] The Door Chime feature is enabled by pressing the [6] key while in the User s Functions Command section. When enabled the keypad buzzer will beep quickly 5 times each time any zone defined as a delay or instant circuit opens or closes. The Door Chime feature does not operate on other zone definitions. Zone bypass may be used to eliminate beeping on doors where it is not wanted. This feature operates only while the panel is disarmed. System Test [Q]+[6]+[MASTER CODE]+[8] The system test feature sounds the bell or siren, lights the keypad indicators and beeps the keypad buzzer for 2 seconds. If a code is programmed in section [54] it will be transmitted at the same time. User Callup [Q]+[6]+[MASTER CODE]+[9] This function is enabled in section [47]. When activated, the panel will call the downloading computer. The downloading computer must be waiting for the panel to call before downloading can be performed. Utility Output Command [Q]+[7] OR [Q]+[7]+[ACCESS CODE] The programmable output (PGM terminal) on the PC3000 can be made to activate by a command from the keypad. This output can be used for operating other devices such as; garage door opener, special lighting or door strikes. The programmable output must be selected for keypad utility using the [Q][8][Installer s Code][28] command and programming a [2], [3], [4] or [5]. Depending on the option chosen in the programming section, the programmable output is activated by pressing the [Q] then [7] keys followed by a Group A access code. 10

15 Group B access code, any access code, or no code at all. When the proper keys are pressed the keypad sounder and the programmable output are activated for 5 seconds. Installer s Programming Commands [Q]+[8]+[INSTALLER S CODE] The PC3000 is completely programmed from the keypad by using commands in the [Q] [8] section. The commands are described in detail in the programming section of this manual. At Home Arming [Q]+[9]+[ACCESS CODE] Entering [Q], [9] before the arming code, arms the panel without any entry delay on the delay zones and bypasses zones that are defined as Home-Away. This command is used for arming the system while at home. When the panel is armed using [Q], [9], the Armed light will be on flashing and the Bypass light will be on to indicate that the Home- Away zones are bypassed. Once the panel is armed in this mode, using [Q], [1] will remove the bypass from those zones defined as Home-Away if they have NOT been manually bypassed. The [Q], [1] command used here, only removes the bypass from zones that have been Automatically bypassed with the [Q], [9] command. Keypad Zones There are three zones which can be activated from the keypad. The alarm and restoral codes for keypad zones are programmed using the [Q][8] command. Pressing the [F] key for 2 seconds activates a Fire alarm. The fire alarm sounds the siren/bell in a pulsed mode and is annunciated as a memory condition. Pressing the [A] key for 2 seconds activates an Auxiliary keypad zone. If a reporting attempt is made to an alarm receiver and it is successful the PC3000 will acknowledge the transmission with a short series of beeps from the keypad. Pressing the [P] key for 2 seconds activates the Police (or Panic) alarm. The panic alarm can be programmed for audible or silent operation (see section [18] in Programming Guide ). There is no light annunciation from the keypad for the last two keypad zones, however, the keypad buzzer beeps 3 times to confirm activation on any of the keypad zones. If the keys are held down the buzzer continues to beep. The panic alarm can be programmed for silent confirmation in section [51] light 4. See section [15] for alarm and restoral codes for all three keypad zones. Quick Arm Command [Q]+[0] Entering [Q][0] is accepted as a valid arming code when the Quick Arm feature is activated. Quick Arm may be used as a convenience for regular users or when the sytem is to be armed by individuals who are not authorized to disarm the system. See instructions in the [Q][6] User s Functions Command section for activating the Quick Arm feature. This feature should not be enabled if the One Time Use Code is enabled. The One Time Use Code must be used for arming before it is erased. Quick Exit [Q]+[0] When Armed Entering [Q] [0] when the system is fully armed will allow the user 2 minutes to exit the premises through any delay zone without altering the status of the system if the Quick Exit feature is enabled. The Quick Exit feature can be enabled by turning on light 6 in section [51]. After [Q] [0] is entered into an armed system, one and only one delay zone may be tripped. Any additional activity on any other active zone will cause that zone to begin its alarm sequence. [Q] [0] for Quick Exit on a partially armed system is not supported. 11

16 PRINTER SETUP The PC3000 with version 7.0 or higher software is capable of sending data to a local printer. The printer must be capable of serial communication (RS- 232). The PC3000 should work with most serial printers, however the printers on the following list are strongly recommended. Compatible printers: 1. Brother M Brother M Star DP Epson EP C - Itoh model 8510 B 6. Citizen 120-D with serial card 7. Citizen 180-D with serial card 8. Rolland DG PR 1112 with serial card 9. Panasonic KX P1091 I with serial card 10.Mannesman Tally MT81 with serial card Configuring the Printer 1. Serial interface 2.Baud rate = 2400 (other baud rates may be used but section [49] must be changed accordingly) 3.Parity = None 4.Character length = 8 bits 5.Auto linefeed = Off 6. American/Canadian character set To hook up the printer, start by fully powering down the panel and the printer. Using A DB-25 connector, connect the printer to the panel as shown below. The maximum cable length should be 6 feet. Programming the Panel for Use with a Printer Section [49] in the panel must be programmed to enable the printer function. See section [49], page 23. Power up the panel and program it as described below. Enter the Installer s Programming section and edit the following sections. ([Q]+[8]+[Installer s Code]) Section Printer Only Monitored and Printer [01] Do not program Program normally [02] Program normally Program normally [03] Do not program Program (see section [49] zone light 6) [04] Do not program Program normally [05] to [15], [45], Program everything Program everything [50], [53] and [54] you wish printedyou wish printed [16] to [18] Program normally Program normally [19] Light 4 must be off Light 4 must be off [20] to [27] Program normally Program normally [28] Program with 0C Program with 0C [29] to [32] Program normally Program normally [33] Program all 1's Program normally [43] to [48] Program normally Program normally [49] Printer setup Printer setup [50] to [54] Program normally Program normally Note: the time of day, day, month and year must be programmed into the panel using the [Q]+[6]+[Master Code]+[1] command as described on page 10. Plug in the printer, insert paper and turn it on line. Your serial printer is now ready to use. The following is a sample of a printout from the serial printer: Note: If SRTS is not available turn on light 7 in section [49] and attach yellow to 4 (RTS) or to 20 (DTR) :33 04\01\91 STATION 2 ACC. # 5678 CLOSING ACCESS 1 12:57 04\01\91 STATION 1 ACC. # 1234 ALARM ZONE 2 ALARM ZONE 12 13:01 04\01\91 STATION 1 ACC. # 1234 RESTORE ZONE 2 RESTORE ZONE 12 18:01 04\01\91 STATION 2 ACC. # 5678 OPENING AFTER ALARM OPENING ACCESS 1 Notes: Station 0 is for a local only printer. Station 1 is telephone number 1. Station 2 is telephone number 2.

17 DOWNLOADING The PC3000 with version 7.0 or higher software, supports the DSC downloading package. See the downloading manual for details on specific capabilities. There are several sections pertaining to the downloading feature which must be programmed. Section [23] The time of day that the periodic download or test transmission will be done, if selected, is programmed in this section. Section [26] - Downloading Access Code A four digit code must be programmed into this section to allow access to the control panel by the downloading computer. Section [46] - Downloading Computer Telephone Number If Callback is enabled, section [47] zone light [8], then this section must be programmed with the telephone number of the downloading computer. Section [47] - Modem Configuration Zone lights [1] to [4] are programmed to set the number of rings the panel will look for before it answers a call from the downloading computer. Zone light [5] is programmed to enable or disable the control panel for downloading. If downloading is disabled, all other programming sections relating to downloading need not be programmed. Zone light [6] enables or disables user initiated callup to the downloading computer. Zone light [7] enables or disables the answering machine defeat option (Answering Machine Over-ride). Downloading and Answering Machine The PC3000 software provides a means to handle downloading when an answering machine is also connected to the telephone line. In section [47], if zone light 7 is off, it is assumed that there is no answering machine connected to the telephone line and the panel will capture the line after the set number of rings. If zone light 7 is off and an answering machine is connected and it is set to answer before the panel, the panel will be unable to receive a call from a downloading computer. If the panel is set to answer before the answering machine, the answering machine will be unable to receive incoming messages. If zone light 7 is on and the panel is called for 1 or 2 rings only and then called again within a set time of 60 or 120 seconds (set in section 51, light 7), the panel will then answer the second call on the first ring (Answering Machine Over-ride Timer). Once the panel is connected to a downloading computer, no [Q] functions can be performed. If the [Q] key is pressed while the panel is connected to a downloading computer, the keypad buzzer will sound one long tone to indicate an error. Zone light [8] is programmed to enable or disable callback. If callback is disabled, the downloading computer will have immediate access to the control panel. The disabled mode is useful if there are multiple downloading computers (at different telephone numbers). If callback is enabled the downloading computer will call, request access then hang up and wait for the control panel to call. After the control panel has called back and the downloading computer and the control panel accept each other as valid, downloading operations are enabled. Section [48] - Panel Identification Code A four digit code must be programmed into this section to allow the downloading computer to identify the panel it is communicating with. Section [49] - Printer Configuration Zone light [8] is programmed to choose between periodic download (light ON) or test transmission (light OFF). Section [51] - 3rd System Option Code Zone light [7] sets the Answering Machine Over-ride Timer to either 60 or 120 seconds for defeating the answering machine. See Downloading and Answering Machine. 13

18 PROGRAMMING GUIDE Introduction The PC3000 is programmed by entering instructions from the panel keypad. The PC3000 memory is EEPROM and can be reprogrammed thousands of times. The EEPROM will not lose memory even on total AC and battery failure. All essential program information required to define the operation of the control panel and the communicator is stored in a section of the EEPROM which can only be accessed using the Installer s Programming Code. If the code is forgotten, the default program code can be reinserted by using the Hardware Reset described on page 22, unless Installer s Lockout is enabled. See sections [90] and [91]. To begin programming the PC3000, enter [Q], [8], [3000] while the panel is disarmed. Installer s Programming can only be done while the panel is disarmed and not in alarm. The factory default Installer s Programming Code is [3000]. This default code can be changed using the Section [24] command listed below (new Installer s Code). Once the basic Installer s command is entered ([Q] [8] [3000]) the Program light will start to flash. The Program light will continue to flash while programming. Note that while programming, if no key entry is made for more than 2 minutes, the keypad will return to the arm-disarm mode and the complete installers command ([Q] [8] [3000]) must be entered before programming can resume. The next step is to enter a 2 digit section entry for any of the commands described in the following pages. Note that while the keypad is waiting for the section entry the Armed light is on steady. As soon as the 2 digits are entered for the section the keypad will beep 3 times, the Armed light will go out and the Ready light will go on. The keypad is then ready to accept data entry for the selected section. A complete description of each programming section will be given in the remaining pages of this section. A programming work sheet summarizing all programming commands is provided in the next section of the manual. Fill out the work sheet and use it as a guide when programming. As the required data for a programming section is entered, the hexadecimal value of the information in that location is displayed on zone lights Most sections contain several groups of two digit entries. The keypad beeps twice and the Armed light flashes after each group of two digits is entered. When the required data is completely entered for the section being programmed, the keypad will beep 5 times and the Armed light will come back on to indicate that the expected data has been entered and another section can be selected for programming. After completing one section, it is not necessary to re-enter the [Q] [8] [Installers code] portion of the command. Just enter the number of another programming section. When programming a section, it is possible to exit by pressing [#]. Only the data entered before pressing [#] will be changed in the EEPROM. Practice entering data in several sections until you become familiar with the programming commands. Certain programming entries may require HEX data. That is the numbers 0 through 9 and the letters A through F (in HEX numbering the letters A...F represent the numbers ). Where commands require HEX data A-F, first press [Q]. The keys 1-6 now assume the hex values A-F and the Ready light begins to flash. Key 1 = A, Key 2 = B, Key 3 = C, Key 4 = D, Key 5 = E and Key 6 = F. Pressing the [Q] again stops the Ready light from flashing and the keys assume the normal values for the numbers from 1 to 9. The most common mistake in entering HEX data is forgetting to press [Q] again after entering the HEX digit to return to normal number entry. The data for sections 18, 19, 20, 21, 29, 30, 31, 32, 43, 44, 47, 49 and 51 is entered using the keypad zone lights to indicate which functions are active and the number keys to turn functions on and off. When the section number is entered, the zone lights will display which functions are currently on. Pressing the number key corresponding to the zone light alternately turns the function on and off. All functions can be turned off by entering [0]. When the correct selections have been made press [#] to record them in memory and to go on to program the next section. Reviewing Programmed Data Enter the section you wish to review by entering the 2 digit section number. The zone LED s will represent the value (hexadecimal format) of the first digit in that section. Each press of the F key will advance the display to the next digit. At the end of the section, the keypad buzzer will beep several times and return you to the program mode where another section can be selected for review or programming. Note: Only sections [01] through [17], [22] through [28], [33], [45], [46], [48], [50] and [52] through [54] can be reviewed using the above method. [00] Binary Programming This section is normally used upon instruction from factory technical personnel for specialized programming not covered by the standard programming instructions. [01] 1st Phone Number This is the 1st telephone to which the communicator will dial. See section [33] Transmission to 1st or 2nd Telephone Number Options. After entering the section number [01], enter the communicator telephone number the way you would dial it on a telephone. Press [#] after the last digit to complete the telephone number programming. Enter [ Q 2 Q ] to dial a Q (Hex B) Enter [ Q 3 Q ] for a 4 second pause (Hex C) Enter [ Q 4 Q ] for additional dial tone search (Hex D) Enter [ Q 5 Q ] to dial a # (Hex E) The total number of digits including dial tone searches and pauses must not exceed 16. Remember to press [#] after 14

19 entering the last digit of the phone number. Press [02] to program the next section, enter another section number or press [#] a second time to return to the arm/disarm mode. [02] 1st Account Code The 1st account code is always transmitted to the 1st phone number to identify the alarm customer. After entering the Section number [02], enter a 4 digit number. If HEX digits A to F are required; enter [Q], [1]...[6] and [Q] again to return keys to normal decimal entry. Where a zero digit in the account code is required use HEX A ([Q][1][Q] to transmit 10 pulses. The receiver at the monitoring station interprets 10 pulses for a digit as a zero. If a three digit code is required as in 3/1 formats, enter [0] as the last digit. [0] represents a null digit...no pulses transmitted. [03] 2nd Phone Number This is the second telephone number to which the communicator will dial. See section [01] 1st Phone Number for programming instructions. [04] 2nd Account Code The 2nd account code is always transmitted to the 2nd phone number. See section [02] 1st Account code for programming instructions. [05]...[15] Reporting Code Explanation Sections [05] to [15] are used to program the communicator reporting codes. A reporting code is transmitted along with the account code with each transmission. If the reporting codes are not programmed in these sections no transmission will be sent when an event (i.e. alarm, restoral, opening/closing, trouble etc.) takes place. To prevent a transmission from being sent for any event in the following sections leave it unprogrammed or enter [00] as the reporting code. Eight reporting codes are programmed in each section. Once the section number is entered, the keypad expects 8 two digit numbers to be entered for the 8 reporting codes in that section. The keypad beeps twice and the Armed light flashes after each 2 digit number is entered. After the 8th code is entered, programming of the current section is complete. The keypad will beep 5 times, the Ready light will go off and the Armed light will go on. The keypad is then ready to accept the next section number for programming. When changing the reporting codes in a section, only code entries up to the one which is being changed need to be entered. Press [#] to exit from the programming sequence. Only codes up to the last one entered will be changed. [05] Alarm Reporting Codes Zones 1 to 8 Once the Section code [05] is entered, the keypad expects 8 two digit numbers to be entered as the reporting codes for zones 1 to 8 alarms (restorals in Section [07]). These codes are used by the communicator when there has been an alarm on zones 1 to 8. Listed below are several programming examples and the resulting transmission using different formats for the reporting codes. Obtaining different formats requires entering data correctly in the account code section ([02] or [04]) reporting codes sections ([05] to [15]) and communication format options, section ([27]). 3/1 Format...Single Line or Non-extended Reporting Required: 3 digit account code in sections [02] or [04] i.e. enter [1230] for account code 123 Format code [0], [1], [2], [3], [4] depending on receiver type selected in section [27] Single digit alarm reporting code in section [05] i.e. enter [30] for single digit code 3 (0 is null digit i.e. no pulses transmitted) Transmission sent: /2 Format...Single Line Reporting Required: 4 digit account code in Sections [02] or [04] i.e. enter [1234] for account code 1234 Format code [0], [1], [2], [3], [4] depending on receiver type selected in section [27] Two digit alarm reporting code in section [05] i.e. enter [31] for two digit code 31 Transmission sent: /1 Format...Extended Reporting Required: 3 digit account code in Sections [02] or [04] i.e. enter [1230] for account code 123 Format code [8], [9], [A], [B], [C] depending on receiver type selected in section [27] Two digit alarm reporting code in section [05] i.e. enter [31] Transmission sent: 1st round nd round If a transmission is not wanted for a particular reporting code, then enter 00 to disable that reporting code. [06] Alarm Reporting Codes Zones 9 to 16 These reporting codes are used by the communicator to transmit a zone alarm for zones 9 to 16. Use instructions in section [05] as a guide for programming. [07] Restoral Reporting Codes Zones 1 to 8 These reporting codes are used by the communicator to transmit a zone restoral for zones 1 to 8. Use instructions in section [05] as a guide for programming. 15

20 [08] Restoral Reporting Codes Zones 9 to 16 These reporting codes are used by the communicator to transmit a zone restoral for zones 9 to 16. Use instructions in section [05] as a guide for programming. [09] Utility Alarm Reporting Codes These reporting codes are used by the communicator to transmit the following conditions. Fire Zone Auxiliary Input Zone Battery Trouble AC Failure Trouble Day Zone(s) Trouble Bell Circuit Trouble Fire Zone Trouble Auxiliary Power Supply Trouble Use instructions in section [05] as a guide for programming. See Terminal Connections section of manual for a description of the operation of the Fire Zone and the Auxiliary Input Zone. Section [28] contains options for Auxiliary Input Zone. The Battery Trouble reporting code will be sent when the battery voltage drops below 11.5 volts. This reporting code will also be sent because of a battery fuse failure. The battery is tested under load every 10 seconds. Only one transmission will be sent during an arm or disarm period to prevent multiple transmission from a weak battery. The AC Failure Trouble reporting code will be sent after the delay time programmed in section [22]. This prevents transmissions during temporary power failures. Auxiliary Power Supply Trouble reporting code is sent when the auxiliary power supply fuse failed. The Bell Circuit Trouble reporting code is sent when the bell circuit is open or the fuse failed. The Fire Zone Trouble code is sent when the fire zone becomes open circuit (E.O.L. resistor is disconnected). The Day Zone Trouble code is sent when any zone defined as a Day Zone (see section [16], [17]) goes open when the system is disarmed. See [Q][2] Trouble Command section for additional description of troubles. [10] Utility Restoral Reporting Codes These reporting codes are used by the communicator to transmit the following list of restoral conditions which correspond to alarm conditions in section [09]. Use instructions in section [05] as a guide for programming. Fire Zone Auxiliary Input Zone Battery Trouble AC Trouble Day Zone(s) Trouble Bell Circuit Trouble Fire Zone Trouble Auxiliary Power Supply Trouble [11] Reporting Codes for Closing (Arming) with Access Codes 1 to 8 The reporting codes in sections [11] to [14] are used to identify Openings and Closings (disarming and arming of the system) by user access code. After entering the section code [11], enter 8 two digit reporting codes. The 8 reporting codes correspond to the first 8 access codes which are programmed using the [Q][5] command. When the system is armed using one of the access codes, the corresponding reporting code is transmitted. When transmitting in any of the extended formats, (see examples in section [05]), closing codes would be programmed as follows. [C1], [C2], [C3], [C4], [C5], [C6], [C7], [C8]... Where the first digit HEX C is one which is used to represent a closing signal (this could be another number depending on what is used at the monitoring station) the 2nd digit represents the access code which was used to arm the system. The closing code transmission takes place after the exit delay time. Therefore if the system is armed and disarmed before the expiry of the exit time, no transmission will take place. Remember that the 1st user code is the master code and that the 16th code may be the temporary or maid s code. The 16th user code can be converted to a normal code using one of the options in section [18]. When the system has been armed using Quick Arm [Q][0] or Auto-arm (see [Q][6] Keypad Commands ), the 1st reporting code (reporting code for master code) will be transmitted. The master code is required to enable or disable these functions. When the system is armed with one or more zones bypassed (see [Q][1] command for zone bypassing), the monitoring station can be notified by programming the Partial Arm reporting in section [15]. Note that the Partial Closing code is sent in tandem with the regular closing code to identify it as a partial closing condition. [12] Reporting Codes for Closing (Arming) with Access Codes 9 to 16 See section [11] for further information. [13] Reporting Codes for Opening (Disarming) with Access Codes 1 to 8 The 8 reporting codes correspond to the first 8 user access codes which are programmed using the [Q][5] command. When the system is disarmed using one of the access codes, the corresponding reporting code in this section is transmitted. See section [11] for an example of Opening and Closing reporting code programming. 16

SPECIFICATIONS. Remote Keypad Specifications (PC2550RK) Output Voltage Specification. Digital Communicator Specifications

SPECIFICATIONS. Remote Keypad Specifications (PC2550RK) Output Voltage Specification. Digital Communicator Specifications SPECIFICATIONS Control Panel Specifications 13 zones including: 8 fully programmable supervised zones (EOL resistors) Supervised fire zone 1 auxiliary normally open zone 3 keypad activated zones Audible

More information

INSTALLATION MANUAL PC2525. Version 1.1

INSTALLATION MANUAL PC2525. Version 1.1 INSTALLATION MANUAL PC2525 Version 1.1 TABLE OF CONTENTS FEATURES 1 SPECIFICATIONS 1 INSTALLATION 2 Mounting the Panel... 2 Mounting the Keypad... 2 Auxiliary Power Connection... 2 Bell/Siren Connection...

More information

INSTRUCTION MANUAL PC15OO/155O WITH LED615 KEYPAD

INSTRUCTION MANUAL PC15OO/155O WITH LED615 KEYPAD INSTRUCTION MANUAL PC15OO/155O WITH LED615 KEYPAD Department of Communications Notice NOTICE: The Canadian Department of Communications label identifies certified equipment. This certification means that

More information

TABLE OF CONTENTS FEATURES

TABLE OF CONTENTS FEATURES TABLE OF CONTENTS FEATURES 2 Keypad Programmable... 2 EEPROM Memory... 2 Static/Lightning Protection... 2 Supervision... 2 Operation... 2 SPECIFICATIONS 2 PC1550 Control Panel... 2 PC1500RK Keypad... 2

More information

Instruction Manual PC55O. With PC5OORK Keypad. 1996, 2002 Digital Security Controls Ltd. Toronto, Canada Printed in Canada 29000534 R3

Instruction Manual PC55O. With PC5OORK Keypad. 1996, 2002 Digital Security Controls Ltd. Toronto, Canada Printed in Canada 29000534 R3 Instruction Manual 1996, 2002 Digital Security Controls Ltd. Toronto, Canada Printed in Canada 29000534 R3 PC55O With PC5OORK Keypad Industry Canada Notice NOTICE: The Industry Canada label identifies

More information

TABLE OF CONTENTS FEATURES 2 SPECIFICATIONS 2

TABLE OF CONTENTS FEATURES 2 SPECIFICATIONS 2 TABLE OF CONTENTS FEATURES 2 SPECIFICATIONS 2 INSTALLATION 3 Mounting the Panel... 3 Mounting the Keypad... 3 Auxiliary Power Connection... 3 PGM Terminal Connections... 3 Bell/Siren Connection... 3 Keypad

More information

Instruction Manual. version 1.0

Instruction Manual. version 1.0 Instruction Manual version 1.0 Table of Contents About Your ADT Security System 1 Fire Detection 1 Testing 1 Monitoring 1 General System Operation 1 System Information 2 Access Codes 4 Arming the System

More information

INSTRUCTION MANUAL PC255O

INSTRUCTION MANUAL PC255O INSTRUCTION MANUAL PC255O Canadian Department of Communications Notice NOTICE: The Canadian Department of Communications label identifies certified equipment. This certification means that the equipment

More information

Using your LED Plus keypad

Using your LED Plus keypad Using your LED Plus keypad System 238 System 2316 System 238i System 2316i Part Number 5-051-372-00 Rev B Thank you for purchasing this C&K alarm system Your system is one of the most powerful and advanced

More information

User's Manual 4110DL/4110XM

User's Manual 4110DL/4110XM S e c u r i t y S y s t e m User's Manual 4110DL/4110XM N5100V5 9/96 TABLE OF CONTENTS SYSTEM OVERVIEW... 4 Keypads... 4 Zones... 4 Alarms... 5 Fire Protection... 5 Burglary Protection... 5 Memory of Alarm...

More information

Simon Security System. User Guide. Technical Manuals Online! - http://www.tech-man.com. 466-1871-01 Rev A June 2004. Part No: 60-875 600-1012

Simon Security System. User Guide. Technical Manuals Online! - http://www.tech-man.com. 466-1871-01 Rev A June 2004. Part No: 60-875 600-1012 ) *(6HFXULW\ 466-1871-01 Rev A June 2004 ZZZ*(6HFXULW\FRP Part No: 60-875 600-1012 Doors & Windows Motion Sensors System Status HOME SECURITY Arm Disarm 1/2 3/4 5/6 7/8 9/0 CODE Chime Doors Motion Time

More information

Simon Security System. User Guide. 466-1871 Rev F September 2002. Part No: 60-875 ZZZ*(,QWHUORJL[6HFXULW\FRP. System Status HOME SECURITY

Simon Security System. User Guide. 466-1871 Rev F September 2002. Part No: 60-875 ZZZ*(,QWHUORJL[6HFXULW\FRP. System Status HOME SECURITY ) 466-1871 Rev F September 2002 *(,QWHUORJL[ ZZZ*(,QWHUORJL[6HFXULW\FRP Part No: 60-875 Doors & Motion Windows Sensors System Status HOME SECURITY Arm Disarm 1/2 3/4 5/6 7/8 9/0 CODE Chime Doors Motion

More information

Simon Security System. User Guide. 466-1871 Rev J May 2003. Part No: 60-875 ZZZ*(,QWHUORJL[FRP. System Status HOME SECURITY. Windows Sensors.

Simon Security System. User Guide. 466-1871 Rev J May 2003. Part No: 60-875 ZZZ*(,QWHUORJL[FRP. System Status HOME SECURITY. Windows Sensors. ) 466-1871 Rev J May 2003 *(,QWHUORJL[ ZZZ*(,QWHUORJL[FRP Part No: 60-875 Doors & Motion Windows Sensors System Status HOME SECURITY Arm Disarm 1/2 3/4 5/6 7/8 9/0 CODE Chime Doors Motion Time Sensor On

More information

Simon Security System. User Guide. 466-1871 Rev H April 2003. Part No: 60-875 ZZZ*(,QWHUORJL[FRP. System Status HOME SECURITY. Windows Sensors.

Simon Security System. User Guide. 466-1871 Rev H April 2003. Part No: 60-875 ZZZ*(,QWHUORJL[FRP. System Status HOME SECURITY. Windows Sensors. ) 466-1871 Rev H April 2003 *(,QWHUORJL[ ZZZ*(,QWHUORJL[FRP Part No: 60-875 Doors & Motion Windows Sensors System Status HOME SECURITY Arm Disarm 1/2 3/4 5/6 7/8 9/0 CODE Chime Doors Motion Time Sensor

More information

User's Manual. N7229-4V4 Rev B 4/99

User's Manual. N7229-4V4 Rev B 4/99 Security System User's Manual N7229-4V4 Rev B 4/99 About This Manual This manual is a step-by-step guide that will aquaint you with your system's features and benefits. It defines the components and their

More information

Control/Communicator Installation Manual

Control/Communicator Installation Manual DAS NETWORX NX-8 Control/Communicator Installation Manual Page General Description... 2 Ordering Information... 2 Option Definitions... 2 Programming the LED Code Pads... 4 Programming the NX-8... 8 Types

More information

SILENT KNIGHT 5000 Series

SILENT KNIGHT 5000 Series SILENT KNIGHT 5000 Series Entry System Installation and Operation Manual Part Number 151174D, 01/03 Content Section 1 Overview... 1-1 1.1 User Features... 1-1 1.2 What s In the Box... 1-2 1.3 About this

More information

System Introduction S E C T I O N 1

System Introduction S E C T I O N 1 System Introduction S E C T I O N 1 1.1 Specifications Flexible Zone Configuration Six fully programmable zones; system expandable to eight zones using keypad zone inputs and wireless zones 38 access codes:

More information

INSTRUCTION MANUAL LCD-6OO SECURITY STATION

INSTRUCTION MANUAL LCD-6OO SECURITY STATION INSTRUCTION MANUAL 1993 Digital Security Controls Ltd. 1645 Flint Road, Downsview, Ontario, Canada M3J 2J6 Printed in Canada 29000144 R1 LCD-6OO SECURITY STATION Table of Contents Introduction 1 About

More information

FIRE DETECTION Note: Your installer must enable the fire detection portion of this equipment before it becomes functional.

FIRE DETECTION Note: Your installer must enable the fire detection portion of this equipment before it becomes functional. Table of Contents Introduction... 2 About Your Security System... 2 Fire Detection... 2 Monitoring... 2 General System Operation... 3 Keypad LED Displays... 3 System Master Menu Functions... 3 Partition

More information

N5100-3V3 9/96. USER'S MANUAL FA120C Security System

N5100-3V3 9/96. USER'S MANUAL FA120C Security System N5100-3V3 9/96 USER'S MANUAL FA120C Security System TABLE OF CONTENTS SYSTEM OVERVIEW... 4 Keypads... 4 Zones... 4 Alarms... 5 Fire Protection... 5 Burglary Protection... 5 Memory of Alarm... 5 Pager Notification...

More information

Instruction Manual. PC5O15 v2.2. WARNING This manual contains information on limitations

Instruction Manual. PC5O15 v2.2. WARNING This manual contains information on limitations Instruction Manual WARNING This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. The entire manual should

More information

Serial Adapter Module. Supplement. Part No. 303124-A Rev 01 November 1998. *303124-A Rev 01*

Serial Adapter Module. Supplement. Part No. 303124-A Rev 01 November 1998. *303124-A Rev 01* Serial Adapter Module Supplement Part No. 303124-A Rev 01 November 1998 *303124-A Rev 01* 4401 Great America Parkway 8 Federal Street Santa Clara, CA 95054 Billerica, MA 01821 Copyright 1998 Bay Networks,

More information

About Your Security System. General System Operation. Fire Detection. Testing. Monitoring

About Your Security System. General System Operation. Fire Detection. Testing. Monitoring About Your Security System Your DSC security equipment has been designed to provide you with the greatest possible flexibility and convenience. Read this manual carefully and have your installer instruct

More information

INTRODUCTION 2 Features... 2 Specifications... 2

INTRODUCTION 2 Features... 2 Specifications... 2 TABLE OF CONTENTS INTRODUCTION 2 Features... 2 Specifications... 2 INSTALLATION 3 Mounting the Panel... 3 Mounting the Keypad... 3 Wiring... 4 Burglary Zone Wiring... 4 Auxiliary Power Connection... 4

More information

AC-115 Compact Networked Single Door Controller. Installation and User Manual

AC-115 Compact Networked Single Door Controller. Installation and User Manual AC-115 Compact Networked Single Controller Installation and User Manual December 2007 Table of Contents Table of Contents 1. Introduction...5 1.1 Key Features... 6 1.2 Technical Specifications... 7 2.

More information

WARNING NT9010 www.dsc.com

WARNING NT9010 www.dsc.com WARNING This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. The entire manual should be carefully

More information

616, 626, 636 & 646 Keypads

616, 626, 636 & 646 Keypads 616, 626, 636 & 646 Keypads User s Manual TABLE OF CONTENTS 1.0 BASIC OPERATION...2 2.0 ACCESS CODES...4 3.0 ARMING & DISARMING...6 4.0 PANIC ZONES...13 5.0 KEY ACCESS PROGRAMMING.14 6.0 ADDITIONAL FEATURES...15

More information

Reference & Installation Manual

Reference & Installation Manual & Versions 4.4 (728ULT) & 4.1 (738ULT) 728ULT 738ULT Reference & Installation Manual Table of Contents Introduction... 1 About This Manual... 1 New Features... 1 Main Features... 1 Specifications... 1

More information

User s Information Guide R1A

User s Information Guide R1A HSC505-R Home Security Controller - User Manual Release R1a Pi HSC505 and Pi HSC505R Home Security Controller User s Information Guide R1A Page 1 QD Dynamics (Pty) Ltd reserves the right to make changes

More information

INSTRUCTION MANUAL PC2525

INSTRUCTION MANUAL PC2525 INSTRUCTION MANUAL PC2525 Canadian Department of Communications Notice NOTICE: The Canadian Department of Communications label identifies certified equipment. This certification means that the equipment

More information

PHONE ACCESS USER'S GUIDE

PHONE ACCESS USER'S GUIDE PHONE ACCESS USER'S GUIDE For Security Systems With Ademco s V I P (VISTA Interactive Phone) U.S. PATENT No. 4791658 N6432V2 9/94 TABLE OF CONTENTS INTRODUCTION... 4 General Information... 4 Type of Telephone

More information

IDS X-Series User Manual 700-398-01D Issued July 2012

IDS X-Series User Manual 700-398-01D Issued July 2012 1 2 Contents 1. Introduction to the IDS X-Series Panels... 7 2. Before Operating Your Alarm System... 7 3. Understanding the Keypad LEDs... 8 3.1 Viewing Data on an LED Keypad... 12 3.1.1 LED Status Indicators...

More information

500r+ Installation and User Guide

500r+ Installation and User Guide 500r+ Installation and User Guide Compatible Equipment 502rUK-50 Watch/Pendant PA. 509rUK-50 Smoke Detector 515rUK-00 10 metre passive infra red movement detector. 525rUK-00 Remote Set/Unset (Full and

More information

INSTRUCTION MANUAL DSC 1550

INSTRUCTION MANUAL DSC 1550 INSTRUCTION MANUAL DSC 1550 A WORD ABOUT YOUR SYSTEM The PC1550 Security System has been designed to give you the greatest possible flexibility and convenience. Read this manual carefully and become familiar

More information

ICP-CC488. Installation Guide ICP-CC488 Control Panel

ICP-CC488. Installation Guide ICP-CC488 Control Panel ICP-CC488 EN Installation Guide ICP-CC488 Control Panel ICP-CC488 Installation Guide Notices EN 2 Copyright Notice Unless otherwise indicated, this publication is the copyright of Bosch Security Systems,

More information

728 SERIES REFERENCE & INSTALLATION MANUAL 728+ VERSION 3.2. 728 series

728 SERIES REFERENCE & INSTALLATION MANUAL 728+ VERSION 3.2. 728 series 728 SERIES 728+ VERSION 3.2 728 series REFERENCE & INSTALLATION MANUAL TABLE OF CONTENTS INTRODUCTION... 2 About This Manual... 2 Features... 2 Specifications... 3 Accessories and Keypads... 3 About Paradox...

More information

User Guide for the DS7060 Control/Communicator

User Guide for the DS7060 Control/Communicator DS7060 User Guide Copyright 1996-97 Detection Systems, Inc. User Guide for the DS7060 Control/Communicator Copyright 1996-97 Detection Systems, Inc. Detection Systems, Inc., 130 Perinton Parkway, Fairport,

More information

IDS. Users Guide to Keypad Functions S E C U R I T Y MANUAL NO. 700-171-01B ISSUED AUG 2002 VERSION 1.18

IDS. Users Guide to Keypad Functions S E C U R I T Y MANUAL NO. 700-171-01B ISSUED AUG 2002 VERSION 1.18 INHEP DIGITAL IDS S E C U R I T Y Users Guide to Keypad Functions MANUAL NO. 700-171-01B ISSUED AUG 2002 VERSION 1.18 Summary of Operation A rm/ disarm [#] + [USER CODE] Quick Quick Quick Away Arm Stay

More information

SPECIAL CODES AUXILIARY CODES SYSTEM NOTES

SPECIAL CODES AUXILIARY CODES SYSTEM NOTES Installing/Service Company Monitoring Center SPECIAL CODES Master Code Duress Code AUXILIARY CODES "Quick Arm" " Chime" 08 02 09 03 10 04 11 05 12 06 13 07 14 SYSTEM NOTES Exit Delay Time Entry Delay Time

More information

PK5500 v1.1 Installation Instructions

PK5500 v1.1 Installation Instructions PK5500 v1.1 Installation Instructions 1 2 3 4 5 6 7 8 9 * 0 # WARNING: Please refer to the System Installation Manual for information on limitations regarding product use and function and information on

More information

FIRST ALERT INSTRUCTION MANUAL FOR FA 270 KEYPADS SECURITY SYSTEM

FIRST ALERT INSTRUCTION MANUAL FOR FA 270 KEYPADS SECURITY SYSTEM FIRST ALERT INSTRUCTION MANUAL FOR FA 270 KEYPADS SECURITY SYSTEM Page 0 Table of Contents Introduction 1 System Basics.. 1 Burglary Protection.. 1 Fire Protection.. 1 Security Codes. 1 Zones and Partitions

More information

SECURITY SYSTEM NOTES. EMERGENCY ACTIVATION KEYS (check if enabled) PROGRAMMED FUNCTIONS

SECURITY SYSTEM NOTES. EMERGENCY ACTIVATION KEYS (check if enabled) PROGRAMMED FUNCTIONS SECURITY SYSTEM NOTES Installing/Service Company For Service Call Installation Date / / Central Station Duress Code EMERGENCY ACTIVATION KEYS (check if enabled) Fire Auxiliary Emergency Police PROGRAMMED

More information

SECURITY SYSTEM NOTES

SECURITY SYSTEM NOTES SECURITY SYSTEM NOTES Installing/Service Company For Service Call Central Station Duress Code FUNCTION CODES Function Code Controls Function EMERGENCY ACTIVATION KEYS (check if enabled) Fire Auxiliary

More information

SECURITY SYSTEM NOTES SPECIAL CODES. Security System Configuration

SECURITY SYSTEM NOTES SPECIAL CODES. Security System Configuration Installing / Service Company: SECURITY SYSTEM NOTES For Service Call: Master Code SPECIAL CODES Duress Code Security System Configuration Auxiliary Code(s) Quick Arm" Digit: 2 9 3 10 4 11 5 12 6 13 7 14

More information

SECURITY SYSTEM NOTES

SECURITY SYSTEM NOTES SECURITY SYSTEM NOTES Installing/Service Company For Service Call Central Station Duress Code FUNCTION CODES Function Code Controls Function This system is is not partitioned. EMERGENCY ACTIVATION KEYS

More information

Users Guide to Keypad Functions

Users Guide to Keypad Functions Users Guide to Keypad Functions MANUAL NO. 700-175-01J ISSUED JAN 2002 VERSION 1.41 Summary of Operation A rm/ disarm [#] + [USER CODE] Quick Quick Quick Panic Fire Medical Away Arm Stay Arm Stay Arm &

More information

VOICE SECURITY SYSTEM

VOICE SECURITY SYSTEM OPERATING INSTRUCTIONS VOICE SECURITY SYSTEM VS-900 Please follow the instructions in this manual to obtain the optimum results from this unit. We also recommend that you keep this manual handy for future

More information

NetworX NX-6V2. LED Keypad User Manual

NetworX NX-6V2. LED Keypad User Manual NetworX NX-6V2 LED Keypad User Manual POWER Light is on when AC power is present; flashes to indicate a low battery condition. ARMED Light is on when armed; off when disarmed; flashes to indicate a previous

More information

PC Tab Security System INSTRUCTION MANUAL

PC Tab Security System INSTRUCTION MANUAL PC Tab Security System INSTRUCTION MANUAL This manual is intended as a Quick Start manual covering the basic functions that have been enabled on the alarm panel. The alarm panel is capable of extensive

More information

INSTRUCTION MANUAL. DSC Security Products PC1500/PCI550

INSTRUCTION MANUAL. DSC Security Products PC1500/PCI550 INSTRUCTION MANUAL DSC Security Products PC1500/PCI550 ABOUT YOUR SECURITY SYSTEM Your DSC security equipment has been designed to give you the greatest possible flexibility and convenience. Read this

More information

CAPTAIN 6. USER GUIDE System ver. 6.0. 6 Zones Intruder Alarm System. PIMA Electronic Systems Ltd. www.pima-alarms.com

CAPTAIN 6. USER GUIDE System ver. 6.0. 6 Zones Intruder Alarm System. PIMA Electronic Systems Ltd. www.pima-alarms.com CAPTAIN 6 6 Zones Intruder Alarm System USER GUIDE System ver. 6.0 PIMA Electronic Systems Ltd. www.pima-alarms.com P/N 4410049, G2 XX en, Jan. 2010 2 CAPTAIN 6 User Guide SAFETY INSTRUCTIONS Your CAPTAIN-i

More information

SECURITY SYSTEM NOTES. Security System Configuration

SECURITY SYSTEM NOTES. Security System Configuration Installing / Service Company: For Service Call: SECURITY SYSTEM NOTES Security System Configuration Master Code: Auxiliary Code(s) 2 3 4 5 6 "Quick Arm" Digit: Exit Delay Time Auxiliary Exit Delay Time

More information

Using your LED Plus keypad

Using your LED Plus keypad Using your LED Plus keypad System 238 System 2316 System 238i System 2316i Part Number 5-051-372-00 Rev B Thank you for purchasing this C&K alarm system Your system is one of the most powerful and advanced

More information

SECURITY SYSTEM NOTES SPECIAL CODES ENTRY / EXIT DELAY TIMES ARM / DISARM CODES

SECURITY SYSTEM NOTES SPECIAL CODES ENTRY / EXIT DELAY TIMES ARM / DISARM CODES SECURITY SYSTEM NOTES Installing/Service Company For Service Call SPECIAL CODES "Chime" Digit 1 "Partial Arm" Digit 2 "Quick Arm" Digit 3 ENTRY / EXIT DELAY TIMES Exit Delay Time Entry Delay Time Secondary

More information

HUNTER-PRO 32 Ver. 3.8 Intruder Alarm System RXN-9/416 User Guide

HUNTER-PRO 32 Ver. 3.8 Intruder Alarm System RXN-9/416 User Guide HUNTER-PRO 32 Ver. 3.8 Intruder Alarm System RXN-9/416 User Guide PIMA Electronic Systems Ltd. 5 Hatzoref Street, Holon 58856, Israel +972-3-5587722 +972-3-5500442 support@pima-alarms.com http://www.pima-alarms.com

More information

Solution-16 Operators Manual ISSUE 1.60

Solution-16 Operators Manual ISSUE 1.60 Solution-16 Operators Manual ISSUE 1.60 !"#$%&"'()*+ Operators Manual Copyright 2002 by, SYDNEY, AUSTRALIA Document Part Number MA880O DOCUMENT ISSUE 1.60 Printed 22 March 2002 This documentation is provided

More information

Operation Manual Software Version 1.1

Operation Manual Software Version 1.1 Operation Manual Software Version 1.1 W A R N I N G This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer.

More information

SECURITY SYSTEM NOTES SPECIAL CODES AUXILIARY ARM / DISARM CODES ENTRY / EXIT DELAY TIMES ZONE DESCRIPTIONS

SECURITY SYSTEM NOTES SPECIAL CODES AUXILIARY ARM / DISARM CODES ENTRY / EXIT DELAY TIMES ZONE DESCRIPTIONS SECURITY SYSTEM NOTES Installing/Service Company For Service Call SPECIAL CODES Master Code Duress Code "Quick Arm" Digit "Chime" Digit "Entry-Guard" Digit AUXILIARY ARM / DISARM CODES 02 12 22 03 13 23

More information

Understanding the Code Pad lights...4. Code Pad tones...5. Fully arming the system On MODE...6. Fully arming the system - Quick Arm MODE...

Understanding the Code Pad lights...4. Code Pad tones...5. Fully arming the system On MODE...6. Fully arming the system - Quick Arm MODE... TABLE OF CONTENTS...Glossary of terms...2...code Pad Diagram...3 Understanding the Code Pad lights...4 Code Pad tones...5 Fully arming the system On MODE...6 Fully arming the system - Quick Arm MODE...6

More information

About Your Security System. General System Operation. Fire Detection. Testing. Monitoring

About Your Security System. General System Operation. Fire Detection. Testing. Monitoring About Your Security System Your DSC Power832 Security System has been designed to provide you with the greatest possible flexibility and convenience. Read this manual carefully and have your installer

More information

SECURITY SYSTEM NOTES AREA LISTINGS SPECIAL CODES ENTRY / EXIT DELAY TIMES ARM / DISARM CODES ZONE DESCRIPTIONS

SECURITY SYSTEM NOTES AREA LISTINGS SPECIAL CODES ENTRY / EXIT DELAY TIMES ARM / DISARM CODES ZONE DESCRIPTIONS SECURITY SYSTEM NOTES Installing/Service Company For Service Call Area 1 Area 2 Area 3 AREA LISTINGS SPECIAL CODES "Quick Arm" Digit "Partial Arm" Digit "Chime" Digit ENTRY / EXIT DELAY TIMES Exit Delay

More information

NESS D16. 16 Zone Control Panel and Dialler OWNER S MANUAL

NESS D16. 16 Zone Control Panel and Dialler OWNER S MANUAL NESS D16 16 Zone Control Panel and Dialler OWNER S MANUAL REVISION 2, JULY 2001 Ness Security Products Pty Ltd Quality Endorsed Company ISO9001 LIC.No. QEC2074 NSW Head Office only WWW.NESS.COM.AU Australia

More information

USER S MANUAL. SMDC-16 Digital Control Communicator and SMPC-32 Personal Control

USER S MANUAL. SMDC-16 Digital Control Communicator and SMPC-32 Personal Control SMDC-16 USER S MANUAL SMDC-16 Digital Control Communicator and SMPC-32 Personal Control Table of Contents General Descriptions Page Description of Your Alarm System 3 Description of Keypads 3 Keypad Maintenance

More information

CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems

CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems EN Security System CM705B CM705B - Universal Expander Module The CM705B universal expander provides a cost effective way

More information

www.ealarm.com.my P/N 5-051-371-00 Rev D

www.ealarm.com.my P/N 5-051-371-00 Rev D System 236 System 236i P/N 5-051-371-00 Rev D Thank you for purchasing this C&K alarm system Your system is one of the most powerful and advanced alarm systems on the market today, designed to provide

More information

SCORPION Z16040C Alarm Controller User Instructions

SCORPION Z16040C Alarm Controller User Instructions SCORPION Z16040C Alarm Controller User Instructions Thank you for choosing to purchase this micron security alarm controller. Micron product is manufactured to exacting quality standards. We understand

More information

9452/9453 Installation and User Guide

9452/9453 Installation and User Guide 9452/9453 Installation and User Guide Compatible Equipment 9425 Remote Keypad 9040 Internal Sounder 660 Speech Communicator 8440 4-Channel Minicom 496330 Issue 1 1 of 10 9452/3 Introduction The 9452 and

More information

Using your Alpha Plus keypad With your

Using your Alpha Plus keypad With your Using your Alpha Plus keypad With your q q q System 236 System 238 System 2316 q q q System 236i System 238i System 2316i Part Number 5-051-373-00 Rev B Thank you for purchasing this C&K alarm system Your

More information

CONTENTS QUICK SETUP & INSTALLATION USER MANUAL. SUPA8 Quick Setup & User Manual

CONTENTS QUICK SETUP & INSTALLATION USER MANUAL. SUPA8 Quick Setup & User Manual SUPA8 Quick Setup & User Manual QUICK SETUP & INSTALLATION CONTENTS FACTORY DEFAULTS... 1 INSTALLATION OF THE SECURITY SYSTEM... 2 COMMISSIONING THE DIALLER PANEL... 5 ZONE INPUT CONNECTIONS... 7 PANEL

More information

INSTRUCTION MANUAL PC5OO WITH PC5OORK KEYPAD

INSTRUCTION MANUAL PC5OO WITH PC5OORK KEYPAD INSTRUCTION MANUAL PC5OO WITH PC5OORK KEYPAD TABLE OF CONTENTS SYSTEM INFORMATION 2 INTRODUCTION 3 Test Your System Regularly...3 Important Notice...3 Glossary...3 BASIC OPERATION 4 Arming Your System...4

More information

P/N 5-051-371-00 Rev D

P/N 5-051-371-00 Rev D System 236 System 236i P/N 5-051-371-00 Rev D Thank you for purchasing this C&K alarm system Your system is one of the most powerful and advanced alarm systems on the market today, designed to provide

More information

Destiny 4100. Destiny 4100. Owners Manual

Destiny 4100. Destiny 4100. Owners Manual Destiny 4100 Destiny 4100 Owners Manual TABLE OF CONTENTS INTRODUCTION Control Panel...3 Detection Devices...3 Telephone Keypads...3 GLOSSARY... 4-5 LOCAL PHONE ACCESS Using Your Telephones As Keypads...6

More information

NetworX Series. NX- 4/8 Code Pad. User Manual (Australian Version)

NetworX Series. NX- 4/8 Code Pad. User Manual (Australian Version) NetworX Series NX- 4/8 Code Pad User Manual (Australian Version) Table Of Contents Code Pad Diagram... Inside Front Glossary of Terms...2 Understanding the Code Pad lights...3 Code Pad Tones...4 Fully

More information

CONTENTS 4. HOW TO UNSET THE PANEL...7

CONTENTS 4. HOW TO UNSET THE PANEL...7 Pi-8 USER MANUAL CONTENTS 1. THE KEYPAD AND ITS OPERATION...3 1.1 DESCRIPTION OF THE KEYPAD LEDS... 3 1.1.1 READY LED (RED)...3 1.1.2 TAMPER LED (RED)...3 1.1.3 POWER LED (GREEN)...3 1.1.4 CIRCUIT LEDs

More information

LCD and 16-Zone LED Keypads. User s Manual

LCD and 16-Zone LED Keypads. User s Manual LCD and 16-Zone LED Keypads 1689 1641 16-Zone LED Keypad LCD Keypad User s Manual TABLE OF CONTENTS 1.0 INTRODUCTION...3 2.0 BASIC OPERATION...4 2.1 Keypad Indicator Lights... 4 2.2 Visual Feedback...

More information

Solution 862 Operators Manual. Issue 1.00

Solution 862 Operators Manual. Issue 1.00 Solution 862 Operators Manual Issue 1.00 Solution 862 Operators Manual Copyright 1998 by Electronics Design and Manufacturing Pty Limited, SYDNEY, AUSTRALIA Document Part Number MA406O Document Issue

More information

!"#$%&"'()**+),-+)).( /'0%1##1%&"'(21'$1#( ISSUE 1.40

!#$%&'()**+),-+)).( /'0%1##1%&'(21'$1#( ISSUE 1.40 !"#$%&"'()**+),-+)).( /'0%1##1%&"'(21'$1#( ISSUE 1.40 MA8XXI 34&0(5167(410(877'(&'9#$:7:(;"

More information

XP-600 Programming Instructions

XP-600 Programming Instructions Hexadecimal Data Entry To Enter a hexadecimal digit enter the following A= A1 D= A4 B= A2 E= A5 C= A3 F= A6 XP-600 Programming Instructions Note These Programming Instructions are intended to be used in

More information

INSTRUCTION MANUAL SOFTWARE VERSION 1.0R

INSTRUCTION MANUAL SOFTWARE VERSION 1.0R INSTRUCTION MANUAL SOFTWARE VERSION 1.0R FCC COMPLIANCE STATEMENT CAUTION: Changes or modifications not expressly approved by Digital Security Controls Ltd. could void your authority to use this equipment.

More information

PC4020 v3.3 Instruction Manual

PC4020 v3.3 Instruction Manual PC4020 v3.3 Instruction Manual WARNING: This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. The entire

More information

SPECIAL CONTROL BUTTON FUNCTIONS

SPECIAL CONTROL BUTTON FUNCTIONS Operating Guide 1 2 3 CONTENTS Page No. OPERATING YOUR ALARM 5 General Information 5 Arming the Alarm 5 Disarming the Alarm 6 Arming in Stay Mode 7 Disarming Stay Mode 8 Bypassing Zones 8 Manual Panic,

More information

10-Zone Spectra LED Keypads

10-Zone Spectra LED Keypads 10-Zone Spectra LED Keypads 1686V 1686H User s Guide We hope this product performs to your complete satisfaction. Should you have any questions or comments, please visit www.paradox.com and send us your

More information

SCORPION. micron security products

SCORPION. micron security products SCORPION 4120 6020 & 8020 USER INSTRUCTIONS Thank you for purchasing a Quality Micron Security Alarm Controller. Micron product is manufactured to exacting quality standards. We understand the importance

More information

Automatic Telephone Dialer TD-101(W)

Automatic Telephone Dialer TD-101(W) Automatic Telephone Dialer TD-101(W) The TD-101 is an automatic dialing device which can transmit prerecorded information via the telephone line. The dialer can send two different 10 second voice messages

More information

ICP-CC488 ICP-CC488 EN. Control Panel. User s Guide

ICP-CC488 ICP-CC488 EN. Control Panel. User s Guide ICP-CC488 EN User s Guide ICP-CC488 Control Panel ICP-CC488 User's Guide Notices EN 2 Copyright Notice Unless otherwise indicated, this publication is the copyright of Bosch Security Systems, Inc. ( Bosch

More information

Solution 880 Operators Manual ISSUE 1.10

Solution 880 Operators Manual ISSUE 1.10 Solution 880 Operators Manual ISSUE 1.10 Solution 880 Operators Manual Copyright 2001 by, SYDNEY, AUSTRALIA Document Part Number MA408O DOCUMENT ISSUE 1.10 Printed 25 May 2001 This documentation is provided

More information

HILLS Series LED Code Pad User Manual

HILLS Series LED Code Pad User Manual HILLS Series LED Code Pad User Manual Not all features may be available on your system Check with your installer to find out which features are programmed Page 2 TABLE OF CONTENTS Code Pad Diagrams...2

More information

SECTION 13850 DETECTION AND ALARM

SECTION 13850 DETECTION AND ALARM SECTION 13850 DETECTION AND ALARM PART 1 GENERAL 1.01 SUMMARY A. Section Includes 1. Control Panel 2 Associated Equipment B. Products Installed But Not Supplied Under This Section 1. Section 16140 - Wiring

More information

HAM841K ALARM CONTROL PANEL FOR COMMERCIAL AND RESIDENTIAL SECURITY SYSTEMS

HAM841K ALARM CONTROL PANEL FOR COMMERCIAL AND RESIDENTIAL SECURITY SYSTEMS ALARM CONTROL PANEL FOR COMMERCIAL AND RESIDENTIAL SECURITY SYSTEMS USER MANUAL USER MANUAL ALARM CONTROL PANEL FOR COMMERCIAL AND RESIDENTIAL SECURITY SYSTEMS INTRODUCTION The (HA-841K) is a complete

More information

Elite 8D/Lite Version 8 Zone Controller. Arrowhead Alarm Products Ltd. Operating Guide. Proudly Designed and Manufactured in New Zealand

Elite 8D/Lite Version 8 Zone Controller. Arrowhead Alarm Products Ltd. Operating Guide. Proudly Designed and Manufactured in New Zealand Elite 8D/Lite Version 8 Zone Controller 8 Arrowhead Alarm Products Ltd Operating Guide 1 Proudly Designed and Manufactured in New Zealand 2 CONTENTS Page No. INTRODUCTION 4 About your Alarm 4 OPERATING

More information

HILLS Series LED Code Pad User Manual

HILLS Series LED Code Pad User Manual HILLS Series LED Code Pad User Manual Not all features may be available on your system Check with your installer to find out which features are programmed Page 2 TABLE OF CONTENTS Code Pad Diagrams...2

More information

642 LCD Keypad User Manual

642 LCD Keypad User Manual 642 LCD Keypad User Manual TABLE OF CONTENTS Introduction...3 Legend... 3 Basic Operation...5 Keypad Indicator Lights... 5 Visual Feedback... 5 Auditory Feedback... 6 Info List... 7 Access Codes...8 User

More information

GE Concord 4 Quick User Guide

GE Concord 4 Quick User Guide GE Concord 4 Quick User Guide GE Concord 4 Quick User Guide Page 1 Before Calling Is the keypad beeping? Press *. This will silence the beeping and let you know where the trouble is. Is there a flashing

More information

www.sebury.com.cn Digital Keypad Use s Manual

www.sebury.com.cn Digital Keypad Use s Manual K3 K4 www.sebury.com.cn Digital Keypad Use s Manual Contents Introduction Introduction Specifications Intramural Interface Circuit 3 Mounting 3 Wiring 5 Power UP 7 Engineer Programming Mode 7 The K3/K4

More information

HM-W536 Install Guide

HM-W536 Install Guide HM-W536 Install Guide 9/13/2013 IMPORTANT SAFETY INSTRUCTIONS Warning - When using electrical devices, basic safety precautions should be followed to reduce the risk of fire, electrical shock or injury.

More information

Vision Security System OWNER MANUAL V-LCD1

Vision Security System OWNER MANUAL V-LCD1 Vision Security System OWNER MANUAL V-LCD1 Congratulations on your purchase of the OPTEX Vision security system. Vision is an advanced microprocessor based alarm system which provides fire and burglar

More information

Microprocessor Home Security System

Microprocessor Home Security System numbers of sensor s activations in the zone and after which activations the zone will be discarded (ignored). On every system s arming the counter is cleared in self. 6.3.11. 2 - Triger Timer - enter a

More information

How To Use A Powerline On A Iphone Or Ipa (Aero) With A Powerpoint (A2) On A Blackberry) With An Iphones 2 (A3) Or Ipad (A4) With

How To Use A Powerline On A Iphone Or Ipa (Aero) With A Powerpoint (A2) On A Blackberry) With An Iphones 2 (A3) Or Ipad (A4) With NOTE After 15 minutes of keypad inactivity the keypad will emit a steady tone indicating the panel has been left in Dealer Program Mode. Enter Dealer Code to exit or press the C key to return to Dealer

More information

SECURITY ALARM CONTROL PANEL QUICK SETUP & USER MANUAL

SECURITY ALARM CONTROL PANEL QUICK SETUP & USER MANUAL SECURITY ALARM CONTROL PANEL QUICK SETUP & USER MANUAL PINKERTON Quick Setup & User Manual QUICK SETUP & INSTALLATION CONTENTS FACTORY DEFAULTS...1 INSTALLATION OF THE SECURITY SYSTEM...2 COMMISSIONING

More information