1 Technical data sheet e n DDC3000 Central Control Unit The DDC3000 Central Control Unit is a component of the DDC3000 system. The introductory chapter DDC3000 Central Control Units summarizes all general technical data of the DDC3000 Central Congtrol Unit in an overview. The following sections explain the general design, technical data, wiring diagrams and installed basic programs of the individual DC3000 Central Control Units. Contents Page DDC3000 Central Control Unit...1 Overview...2 DDC3000 Central Control Units...3 Voltage supply and electric wiring diagram...4 Operator interface...6 DDC3000 Central Control Units address...7 Digital inputs and outputs...8 Analog inputs and outputs...8 Interfaces...9 Collected error messages issued over the digital output...10 Error messages issued to a serial printer...11 Send error messages to a D1/D2 SMS cellular telephone...13 Building management system BMS connection...15 Building management system BMS via modem connection...17 Data backup / recovery via building management system BMS...19 Data backup / recovery via FLASH card...20 Data backup / recovery via PC with DOS-operating system...21 Update with FLASH card...22 Update with EKART card...23 Modifying code numbers of the DDC3000 Central Control Unit...24 Cable connections...25 Date Kieback & Peter GmbH & Co KG Tempelhofer Weg 50 D Berlin Telefon 030 / Telefax 030 / Page 1/26

2 Technical data sheet e n Overview Type Inputs and Functions Area Comments Technical Data Data sheet for outputs sheet In general DDC3010 DDC3035 DDC3200 DDC3200S1 DDC3002 DDC3002S DDC BE 2 BA 2 BE 2 BA 2 BE 2 BA 16 BE 8 BE/BA 8 BA 16 AE 8 AA 16 BE 8 BE/BA 8 BA 16 AE 8 AA 16 BE 8 BE/BA 8 BA 16 AE 8 AA 16 BE 8 BE/BA 8 BA 16 AE 8 AA 2 BE 2 BA 0 DDC control loops DDC cassette bus Engineering Parameterization Softwaremenu 0 DDC control loops 499 flags 99 timers DDC cassette bus Field bus Engineering Parameterization Softwaremenu 0 DDC control loops Room bus Engineering Parameterization Softwaremenu 12 DDC control loops 21* DDC control loops 499 flags 99 timers 12 DDC control loops 21* DDC control loops 499 flags 99 timers 4 DDC control loops 7* DDC control loops 499 flags 99 timers 4 DDC control loops 7* DDC control loops 499 flags 99 timers 12 DDC control loops 21* DDC control loops 499 flags 99 timers DDC DDC control loops 21* DDC control loops 499 flags 99 timers DDC BE 2 BA 4 DDC control loops 7* DDC control loops 499 flags 99 timers Field bus Control cabinet bus Field bus Control cabinet bus Field bus Control cabinet bus Field bus Control cabinet bus DDC cassette bus Field bus Control cabinet bus Field bus Control cabinet bus LONWORKS- Interface Field bus Control cabinet bus Engineering Parameterization Softwaremenu Engineering Parameterization Softwaremenu Engineering Parameterization Softwaremenu Engineering Parameterization Softwaremenu Engineering Parameterization Softwaremenu Engineering Parameterization Softwaremenu Engineering Parameterization Softwaremenu LON-Knoten DDC BE BACnet Engineering BA DDC DDC-Display-Modul Engineering * additional DDC control loops by softwaremenu BE, BA binary inputs, binary outputs AE, AA analog inputs, analog outputs Page 2/26

3 Technical data sheet e n DDC3000 Central Control Units All DDC3000 Central Control Units consist of a 19" short cassette made of non-flammable plastic. They are designed as four-fold cassettes and have two plug-in sockets in the rear. Both plug-in sockets provide the operating voltage and the energy supply for the coupling to the DDC Central Control Unit bus, the DDC cassette bus, the DDC room bus, the DDC field bus and the DDC control cabinet bus. The front panel contains the operator and display elements and a diagnostic jack. Behind a removable front panel are two rotary select switches for setting the address of the DDC3000 Central Control Unit. The DDC3000 Central Control Units are supplied with an operating voltage of 24V AC, Hz. The DDC3000 Central Control Units are bus-capable multi-circuit open- and closed-loop control systems for control, optimization, control and monitoring functions. The DDC Central Control Unit bus is based on the Profibus according to DIN and allows for the connection of max. 99 DDC3000 Central Control Units. The central processing unit consists of a 32 bit processor and a real-time multitasking operating system. These functional units are completed with a battery-buffered RAM, an open-ended data backup in case of mains breakdown and a clock module. The actual time with date and hour can be called up. The summer / winter time switching is done automatically. The user communicates with the DDC3000 Central Control Unit via the operator keyboard and a 4x20- character illuminated LCD display. The dialog is carried out in plaintext in three possible operator levels for queries, and input for the DDC data, such as actual value, setpoints and times. A plaintext can be installed for all DDC parameters. All DDC open- and closed-loop control parameters are entered in the program level,. A virtual parameterization is possible. The three operator levels and the program level are divided into four priority levels per code key. The open- and closed-loop control software acts differently depending on the type installed in the DDC3000 Central Control Unit, the DDC control loop cassettes, and the DDC single-room regulators. The DDC control loop cassettes and the DDC single-room regulator continue to work autonomously even when the DDC3000 Central Control Unit has failed. The manual activation level is a constituent part of the basic program of the DDC control loop cassette. Switching processes are entered and carried out via digital inputs and outputs in the DDC3000 Central Control Unit. Every possible digital output and input can be used for issuing a collected error message and for its receipt. For all digital inputs and outputs, a separate power supply is provided to supply the 24V DC. Analog inputs and outputs are processed according to type. Via a parameterizable sensor switching mechanism, the analog inputs can be made to accommodate the input signal. The serial interface allows for RS-232 communication on the basis of the P90 protocol. The following functions are realized via the serial interface: - BMS operator station, BMS central control station with direct line connection or modem send via the SMS (Short Message Service) malfunction notifications in plaintext to a cellular phone - data backup / data recovery with portable PC / BMS central control station (data backup) The DDC3000 Central Control Units are connected on a common DDC Central Control Unit bus. This makes possible the access of the parameters of other DDC3000 Central Control Units the transfer of error messages to other DDC3000 Central Control Units the execution of commands from a distance on the DDC3000 Central Control Units (Remote Control) Date Kieback & Peter GmbH & Co KG Tempelhofer Weg 50 D Berlin Telefon 030 / Telefax 030 / Page 3/26

4 Technical data sheet e n Central Unit bus Anlage Istwert Sollwert Zeiten < > 0. +/- Block Menü Kreis Diagnose Anlage Istwert Sollwert Zeiten < > 0. +/- Block Menü Kreis Diagnose Daten Error Daten Error Hand Zurück CE Uhr SET Meldung Install Param Code Hand Zurück CE Uhr SET Meldung Install Param Code DDC DDC 3000 GND Z-Bus - Z-Bus + term. resistence ca Ohm (Extras DDC3000 Central unit) Signal line continuously twisted Voltage supply and electric wiring diagram Operating voltage 24V AC 10%; Hz no grounding on the secondary side Recommended power supply 230 V AC; Hz for 24V AC TF60 60VA TF VA TF VA Recommended power supply for voltage supply of digital inputs and outputs 24V DC +/-10% ETN1 0.1A Z63 1.0A Z24 6.0A Page 4/26

5 Technical data sheet e n (Z-Bus) max. 1000m Anlage Istwert Sollwert Zeiten < > Hand Zurück CE Uhr SET Meldung 0. +/- Block Menü Kreis Install Param Code Diagnose Daten Error avoid final branch feed (not longer than 10m) Anlage Istwert Sollwert Zeiten < > Hand Zurück CE Uhr SET Meldung 0. +/- Block Menü Kreis Install Param Code Diagnose Daten Error DDC 3000 DDC max. 1000m term. resistance ca Ohm (Extras DDC3000 Central unit) Bus cabling cable type IY(St)Y 2x2x0.8 maximum cable length 1000m extension via bus driver (DDC58, DDC59) possible Z-bus + and Z-bus must be twisted pair-wise no final branch feeders (not longer then 5m in the control cabinet ) no star configurations no ring configurations terminator resistors Ohm on the most distant DDC3000 Central Control Units (accessory pack of the DDC3000 Central Control Unit) Bus extensions maximum with two DDC58, DDC59 each extending a further 1000m (3000m maximum) (see DDC100 project engineering documentation) DDC58, DDC59 also with terminator resistor. Date Kieback & Peter GmbH & Co KG Tempelhofer Weg 50 D Berlin Telefon 030 / Telefax 030 / Page 5/26

6 Technical data sheet e n Operator interface Function display A green LED "data" and a red LED "error" has been provided to display the function of all equipment. The green LED blinks whenever data is being exchanged between connected DDC modules. The red LED lights up whenever the DDC3000 Central Control Unit has some problem in its equipment function (hardware) or no communication to the DDC modules can take place. LCD display A 4 x 20 character LCD display is available for the display of all data of the DDC3000 System. The illumination of the DDC3000 Central Control Unit display is always turned on with the first (arbitrary) keystroke. Only when the display is illuminated will further operations via the keyboard be evaluated. Approx. 1 minute after the last keystroke, the illumination of the display is automatically turned off. Basic design of the displays: - 1st and 2nd row Plaintext for plant and parameter messages - 3rd row Display ACTUAL VALUES, SETPOINTS,.. - 3rd and 4th row Dialog guides with the display for subsequent possible operating actions User keyboard The operation of the DDC3000 Central Control Unit is menu-driven. Dialog guidance takes place via the display of subsequent possible user actions. The user keyboard is divided up according to user functions and color coded. The following keys are available: - 12 keys for the plant operation [plant], [actual values], [setpoints], keys for the data inputs for plant operation and setting parameters [0], [1], [2], keys for the setting parameters [block], [menu],.. Operating and program levels are provided according to the importance of the individual parameter (display, operation, regulator setting, system monitoring). These levels are addressed via code numbers. The following levels have been prepared: - 3 for the operator control levels - 1 for the program level. The parameters displayed in a code level can be modified in the next higher code level. The code numbers can be modified with the help of a code key. The parameters for the code numbers can be accessed by inserting the code key on the front panel diagnostic jack and pushing the key [Code]. Using these parameters, the code numbers of all four code levels can be modified. Note: The operation and display of the DDC3000 Central Control Units are described completely in CHAPTER 3. Page 6/26

7 Technical data sheet e n DDC3000 Central Control Units address Selection DDC3000 central address behind the front panel +/ Daten Error Code Fig. 2- Address switch of the DDC3000 Central Control Unit behind the removable front panel valid DDC3000 Central Control Unit addresses DDC3000 Central Control Unit (basic setting) , , ,... and DDC , , ,... and DDC DDC DDC , , ,... and DDC3300 Date Caution when changing the address! The address of the DDC3000 Central Control Unit may be changed only when the system is in a voltage-free state! Upon switching on the operating voltage, the set address of the DDC3000 Central Control Unit is entered into the system. Kieback & Peter GmbH & Co KG Tempelhofer Weg 50 D Berlin Telefon 030 / Telefax 030 / Page 7/26

8 Technical data sheet e n Digital inputs and outputs Technical data digital inputs digital outputs voltage-free contact, typ. current requirement ca. 5mA / DE freely assignable, can incorporate into control connections transistor output, max. 50mA as connection node parameterizable with 4 digital inputs In the DDC3000 system digital inputs are reserved which can also be used as digital outputs. The change-over can be done with the parameterization of the respective contacts. For example, DDC3200 function digital input: basic setting, data acquisition of a digital value. function digital output: if the contact is parameterized. (entry of addresses) Caution when wiring these digital inputs and outputs! The voltage-free contacts of the digital inputs switch to -24V DC. The consumers switched to the digital output are driven with +24V DC. Analog inputs and outputs Technical data analog inputs analog outputs input 0..10V or KP10 (base) parameterizable for each analog input via separate parameters output 0..10V, max. 5mA The DDC3000 system has analog inputs which can be switched to different sensors. The change-over is carried out by parameterization. For example, DDC3200 function for KP10 basic setting function for 0..10V Caution when wiring these analog inputs! The sensor KP10 is driven by another incoming line (terminal 2, 15, 22, 35) than the active detector 0..10V (terminal 21 (0V)). Page 8/26

9 Technical data sheet e n Interfaces When configuring the interfaces of the DDC3000 Central Control Units, various settings for the hardware and the software must be made. The wiring possibilities and the required parameterization are detailed in the following sections. output malfunction message on digital output output error messages on a serial printer send error messages to a D1/D2 SMS cellular telephone building management system BMS connection building management system BMS via modem connection data backup with BMS data backup with flash-card (as of Vers. 2.54) except for DDC3010,, DDC3035 data backup with PC, DOS operating system update with flash-card update with EKART except for DDC3010,, DDC3035 only DDC3010,, DDC3035 modify code numbers cable connections Date Kieback & Peter GmbH & Co KG Tempelhofer Weg 50 D Berlin Telefon 030 / Telefax 030 / Page 9/26

10 Technical data sheet e n Collected error messages issued over the digital output Plant messages (DDC software menu M070 plant messages), collected error messages of the DDC control loop cassettes (DDC software menu M110 K/Kx bus) and system messages (DDC software menu M113 system messages), can switch an internal signaling contact I900 in the DDC3000 Central Control Unit. The internal signaling contact I900 can be parameterized as a digital source in the control connection, for example, to switch an external signal. The internal signaling contact I900 remains active until a receipt is returned over the digital source parameter I901. In the digital source I901, for example, the contact of a receipt key can be parameterized. For switching the internal signaling contacts I900 in the above-mentioned DDC software menu in the DDC parameters, SIGN. DEST. should be set to "1" for "all signaling contacts", that is, "local signaling contact". M070 Plant messages notification destination 8616/01= M110 K/Kx bus destination coll. malf. messages 1095/01= Set Reset K03 of the output for collected malfunction messages of the output for collected malfunction messages M069 system menu notification contact I900= 1 M069 system menu notification contact receipt I901= K03 M000 basic program K01= N I N N N K01 Principle of operation for collected error messages issued to a digital output Page 10/26

11 Technical data sheet e n Error messages issued to a serial printer Plant messages (DDC software menu M070 plant messages), collected error messages of the DDC control loop cassettes (DDC software menu M110 K/Kx bus) and system messages (DDC software menu M113 system messages), can be issued on the serial interface RS-232 of the DDC3000 Central Control Unit on to a serial pin printer black/white (for example, BMS2248). The printouts of messages can be carried out from a number of DDC3000 Central Control Units on one (or more) connected printers. For the printout of messages in the above-mentioned DDC software menu in the DDC parameters, SIGN. DEST should be set to "1" for "printer". Anlage Istwert Sollwert Zeiten < > 0. +/- Diagn ose Da ten Error Hand Zurück CE Uhr SET Meldung Install Param Code DDC Data line MRP008 Connection DDC3000 Central Control Unit with serial pin printer The following remarks are for the connection of serial pin printers to the DDC3000 Central Control Unit: Establish cable connection according to following table. data line MRP008 DDC3010 or DDC3035 DDC3200 DDC3002 DDC3300 Signal line 0 terminal 31 terminal 24 terminal 60 GND line 1 terminal 30 terminal 32 terminal 59 Rx line 2 terminal 29 terminal 31 terminal 58 Tx line 3 unused unused unused line 4 unused unused unused Configuration of the serial interface for the pin printer in the DDC basic program of the DDC3000 Central Control Unit: DDC parameters plaintext setting 2031 ser. interface rear printer Date Kieback & Peter GmbH & Co KG Tempelhofer Weg 50 D Berlin Telefon 030 / Telefax 030 / Page 11/26

12 Technical data sheet e n In the system menu M069 of the DDC3000 Central Control Unit, no DDC parameters need to be changed. If, in DDC parameters 2031 (2032) printer is selected, the serial interface is automatically set to 4800 Baud. For diagnostic purposes, the serial interface of the diagnostic jack can be used instead of the rear serial interface (connection base). In this case, the rear serial interface must be switched off via parameterization and the front one activated. The DDC cable should be used as the connection cable. The following DDC parameters in the DDC basic program of the DDC3000 Central Control Unit must be set. DDC parameters plaintext setting 2031 ser. interface rear freely 2032 ser. interface diagnostic jack printer Printout of messages If a limit value is violated or by a change in the status of the signal source, a message is sent to all printers attached to the central bus. These messages are printed out in the same form as is usual for the display on the LCD display. Example: / 16:45:10 airstream monitoring exhaust MALFUNCTION address K003/01 Negative as well as positive messages are documented. Page 12/26

13 Technical data sheet e n Send error messages to a D1/D2 SMS cellular telephone Plant messages (DDC software menu M070 plant messages), collected error messages of the DDC control loop cassettes (DDC software menu M110 K/Kx bus) and system messages (DDC software menu M113 system messages) can be sent to a cellular telephone via the P90 interface of the DDC3000 Central Control Unit. For the transmission of messages a "1" should be parameterized for "D1/D2 SMS" in the above-mentioned DDC software menu in the DDC parameter "MSG DEST". Anlage Istwert Sollwert Zeiten < > 0. +/- Diagnose Daten Error Hand Zurück CE Uhr SET Meldung Install Param Code DDC 3000 Modem telephone net Modem Principle of operation for sending a message to a cellular telephone The following points for the transmission of messages to a cellular telephone should be noted. Cable connection between the DDC3000 Central Control Unit and a modem are made according to the following table: Note: data line MRP008 DDC3010 or DDC3035 DDC3200 DDC3002 DDC3300 signal line 0 terminal 31 terminal 24 terminal 60 GND line 1 terminal 29 terminal 31 terminal 58 Rx line 2 terminal 30 terminal 32 terminal 59 Tx line 3 unused unused unused line 4 unused unused unused The data line MRP008 is maximum 5m long. Date Kieback & Peter GmbH & Co KG Tempelhofer Weg 50 D Berlin Telefon 030 / Telefax 030 / Page 13/26

14 Technical data sheet e n The following setting in the DDC software menu M069 system menu should be made before the commencement of data communication on the DDC3000 Central Control Unit: P90 MODE 2051/01= DST-MODE DDC parameters plaintext setting 2051 P90-Mode DST-MODE 4599 P90-protocol ON 4600 P90-baud rate 9600 The DDC software menu M081 modem should only then be parameterized and switched active if a modem connection to the BMS is required at the same time! The DDC software menu M086 D1/D2 SMS should be parameterized and switched to active. Page 14/26

15 Technical data sheet e n Building management system BMS connection The connection to the BMS central control station is done via the serial RS-232 interface of the DDC3000 Central Control Unit. The following connection variations are possible: connection direct (ca. 5m) connection by means of RS-232 driver, dedicated line driver connection by means of modem (see software menu M081 modem) Anlage Istwert Sollwert Zeiten < > 0. +/- Diagn ose Da ten Error Hand Zurück CE Uhr SET Meldung Install Param Code DDC Data line MRP008 Connection DDC3000 Central Control Unit and BMS direct The following points should be noted for the connection of the DDC3000 Central Control Units to the BMS central control station: The compatibility of the BMS central control station version and the DDC3000 Central Control Unit must be guaranteed. Make certain that the documentation matches the update of the BMS version! Before connecting DDC3000 <--> BMS be sure that: - the 24V AC supply lines of the DDC3000 Central Control Unit and the shield lines are truly not connected to the ground conductor system, directly-earthed system and control cabinet ground! - there are no voltages (for example, statically generated) between the ground potential of the DDC3000 Central Control Units (GND) and the BMS! Create the cable connection between BMS central control station and DDC3000 Central Control Unit according to the following table: data line MRP008 DDC3010 or DDC3035 DDC3200 DDC3002 DDC3300 Signal line 0 terminal 31 terminal 24 terminal 60 GND line 1 terminal 30 terminal 32 terminal 59 Rx line 2 terminal 29 terminal 31 terminal 58 Tx line 3 unused unused unused line 4 unused unused unused Note: The data line MRP008 can be maximum 5m long. For distances greater than 5m, the RS-232 driver or modem should be used. Date Kieback & Peter GmbH & Co KG Tempelhofer Weg 50 D Berlin Telefon 030 / Telefax 030 / Page 15/26

16 Technical data sheet e n The following setting in the DDC software menu M069 system menu should be made before the commencement of data communication on the DDC3000 Central Control Unit: P90 MODE 2051/01= DST-MODE DDC parameters plaintext setting 2051 P90-Mode DST-MODE 4599 P90-protocol ON 4600 P90-baud rate 9600 Page 16/26

17 Technical data sheet e n Building management system BMS via modem connection The connection to the BMS central control station is carried out via the serial RS-232 interface of the DDC3000 Central Control Unit. The following variations of the connection are possible (among others): connection direct (ca. 5m) connection via RS-232-driver, dedicated line driver connection via modem (see software menu M081 modem) Anlage Istwert Sollwert Zeiten < > Hand Zurück CE Uhr SET Meldung 0. +/- Diagn ose Block Menü Kreis Da ten Error Install Param Code telephon net DDC 3000 Data line DDC GND RX TX Modem Modem Connection between the DDC3000 Central Control Unit and BMS per modem The following points should be noted for the connection of the DDC3000 Central Control Unit to the BMS central control station: The compatibility between the BMS central control station versions and the DDC3000 Central Control Unit must be guaranteed. Make sure that the documentation matches the respective update of the BMS! Make sure the cable connection between the BMS central control station and the modem as well as the DDC3000 Central Control Unit and the modem is made. Cable connection between the DDC3000 Central Control Unit and modem must be made according to the following table: Note: data line MRP008 DDC3010 or DDC3035 DDC3200 DDC3002 DDC3300 signal line 0 terminal 31 terminal 24 terminal 60 GND line 1 terminal 29 terminal 31 terminal 58 Rx line 2 terminal 30 terminal 32 terminal 59 Tx line 3 unused unused unused line 4 unused unused unused The data line MRP008 may be maximum 5m long. Date Kieback & Peter GmbH & Co KG Tempelhofer Weg 50 D Berlin Telefon 030 / Telefax 030 / Page 17/26

18 Technical data sheet e n The following setting in the DDC software menu M069 system menu should be made before the commencement of data communication on the DDC3000 Central Control Unit: P90 MODE 2051/01= DST-MODE DDC parameters plaintext setting 2051 P90-Mode DST-MODE 4599 P90-protocol ON 4600 P90-baud rate 9600 The software menu M81 modem must be parameterized (see description of the software menu). The software menu M81 modem must be switched active (+) by pressing the key. Page 18/26

19 Technical data sheet e n Data backup / recovery via building management system BMS Stationary building management system BMS BMS is connected according to the instructions on page Data backup according to menu guide for the operator interface of the BMS Transportable building management system BMS (KD-PC) Connection of DDC3000 Central Control Unit and BMS according to instructions, page as per the following figure: Anlage Istwert Sollwert Zeiten < > 0. +/- Diag nose Daten Error Hand Zurück CE Uhr SET Meldung Install Param Code DDC 3000 Data line DDC Connection of DDC3000 Central Control Unit with KD-PC for data backup Connect diagnostic jack of the DDC3000 Central Control Unit and serial interface of the KD-PC with data line DDC Caution: The serial interface RS-232 on the plug-in socket may not be simultaneously used! (for example, when connecting to the stationary BMS) The following setting in the DDC software menu M069 system menu should be made before commencement of data communication on the DDC3000 Central Control Unit: DDC parameters plaintext setting 2051 P90-Mode DST-MODE 4599 P90-protocol ON 4600 P90-baud rate 9600 Data backup according to the menu direction of the BMS operator interface After completion of the data backup / data recovery, the line connections and the communication parameters of the DDC software menu M69 system menu returned to the original setting. Date Kieback & Peter GmbH & Co KG Tempelhofer Weg 50 D Berlin Telefon 030 / Telefax 030 / Page 19/26

20 Technical data sheet e n Data backup / recovery via FLASH card The DDC3000 Central Control Unit DDC3002, DDC3200 and DDC3300 have a PCMCIA plug-in socket on the front side (under the front panel), on the left next to the LCD display. A FLASH card can be plugged in here. With the FLASH cards, the parameterization is backed up, restored, and new DDC3000 programs are loaded (update). The backup / recovery of the parameterization of the DDC3000 Central Control Unit is possible after version (Note: The FLASH card hardware must be adequately suited for this!) 0. +/- FLASH card on the PCMCIA plug-in socket on the DDC3000 Central Control Unit For the backup of the parameterization, prepare the following settings in the DDC software menu M69 system menu: (do not push [SET] yet!) DDC parameters plaintext setting 2051 P90-Mode DDC >FLASH remove front panel of the DDC3000 Central Control Unit. plug in FLASH card on the PCMCIA plug-in socket. confirm above-mentioned setting of the DDC parameters 2051 P90 Mode = DDC >FLASH by pressing the key [SET]. After completion of the backup, the DDC parameters 2051 P90 Mode = INACTIVE are automatically switched. For the restoration of the parameterization, prepare the following setting in the DDC software menu M69 system menu: (do not push [SET] yet!) DDC parameters plaintext setting 2051 P90-Mode FLASH->DDC Page 20/26

21 Anlage Istwert Sollwert Hand Zurück CE Zeiten Uhr < SET > Meldung Block Install Menü Param Kreis Code D iag nose D aten Error Technical data sheet e n Data backup / recovery via PC with DOS-operating system The serial interface RS-232 of the DDC3000 Central Control Unit is used for data backup with the KD-PC (operating system MS-DOS). For data backup, this interface is available as a diagnostic jack and is installed on the front panel of the DDC3000 Central Control Unit. 0. +/- DDC 3000 Data line DDC Connection of DDC3000 Central Control Unit with KD-PC for data backup Diagnostic jack of the DDC3000 Central Control Unit and serial interface of the KD-PC connected with the data line DDC Caution: The serial interface RS-232 on the plug-in socket may not be simultaneously assigned! (for example, with a connection to the stationary BMS) Date Program diskette (only for MS-DOS) Data backup / data recovery DDC3000 (data backup / data recovery DDC EZR) Select via the menu system of the KD-PC the menu position [DDC3000] ([EZR]). In the menu of the started data backup program, select the desired menu position. data backup (3000 to the PC) = 1 data recovery (PC to the 3000) = 2 After the query and the input of an arbitrary name for the backup file, the parameter settings are shown on the PC, which must be set on the DDC3000 Central Control Unit in the software menu 69 system menu. Set parameters in the system menu of the DDC3000 as follows: No P90-protocol = ON No P90-baud rate = 9600 No P90-Mode = DATA BACKUP and finally confirm the P90-Mode on of the DDC3000 with <SET>. Now the data will be backed up. Sich35 V 3.1 (c) Kieback & Peter 1993 data backup on interface COM1 with 9600 Baud, File a:\backup. Abort any time with key <ESC>. Make the required parameter settings on the DDC3000 Central Control Unit in the DDC software menu M069 system menu. When the last parameter is set and the key [SET] is pressed on the DDC3000 Central Control Unit, the data backup runs by itself and terminates automatically. The data backup runs as a background program of the DDC3000 Central Control Unit. That is, other operator commands on the DDC3000 Central Control Unit can be carried out, but do slow down the process of data backup. After completion of data backup / data recovery, the line connections and the communication parameters of the DDC software menu M069 system menu are returned to their original settings. Kieback & Peter GmbH & Co KG Tempelhofer Weg 50 D Berlin Telefon 030 / Telefax 030 / Page 21/26

22 Technical data sheet en Update with FLASH card The DDC3000 Central Control Unit DDC3002, DDC3200 and DDC3300 have a PCMCIA plug-in socket on the front side (under the front panel), on the left next to the LCD display. A FLASH card can be plugged in here. With the FLASH cards, the parameterization can be backed up, restored or new DDC3000 programs can be loaded (update). As of the version 2.54, updating the DDC3000 Central Control Unit via the parameters setting of the DDC software menu M69 is possible. When updating the DDC3000 Central Control Unit, i.e. when loading a new program version, the following processes occur: 1. The parameterization of the DDC3000 Central Control Unit on the FLASH card is backed up automatically. 2. The new DDDC3000 program in the DDC3000 Central Control Unit is loaded automatically. 3. The parameterization of the FLASH card in the DDC3000 Central Control Unit is restored automatically. 4. The DDC3000 Central Control Unit is automatically started new with a warm start. 1. Parameterization Parameterization DDC3000-Program DDC3000-Program 0. +/- Automatic processes when updating the DDC3000 Central Control Unit with FLASH card For the update of the DDC3000 Central Control Unit for a new DDC3000 program, prepare the following setting in the DDC software menu M69 system menu: (do not push [SET] yet!) DDC parameters plaintext setting 2051 P90-Mode DDC UPDATE Remove front panel of the DDC3000 Central Control Unit. Insert FLASH card in the PCMCIA plug-in socket. Confirm above-mentioned setting of the DDC parameters 2051 P90 Mode = DDC UPDATE by pressing the key [SET]. After completion of the update, the DDC3000 Central Control Unit automatically restarts with a warm start. Page 22/26

23 Technical data sheet en Update with EKART card The DDC3000 Central Control Unit DDC3010, and DDC3035 have the DDC3000 program permanently stored in EPROM. These EPROMs are installed on the EKART printed circuit card. When updating the DDC3000 Central Control Unit, the EKART located in the DDC3000 Central Control Unit must be replaced. EKART Rear side of the DDC3000 Central Control Unit with EKART For an update of the DDC3010, and DDC3035, you must order the EKART with the new program version. Back up parameterization of the DDC3000 Central Control Unit! Turn off DDC3000 Central Control Unit, take out of the rack. Remove the screws on the rear panel of the DDC3000 Central Control Unit. Pull the present EKART out of the housing of the DDC3000 Central Control Unit. (The EKART can be recognized by the three equally large plug-in sockets for EPROM) Insert new EKART in the housing of the DDC3000 Central Control Unit. Make sure the card is securely seated. Remount the rear panel of the DDC3000 Central Control Unit, tighten all screws again. Reinsert the DDC3000 Central Control Unit in the rack, switch on. Further start-up functions such as restore parameterization, etc. Please send the removed EKART back to the factory or customer service so that it can be recycled for further use. Date Kieback & Peter GmbH & Co KG Tempelhofer Weg 50 D Berlin Telefon 030 / Telefax 030 / Page 23/26

24 Technical data sheet en Modifying code numbers of the DDC3000 Central Control Unit With the code key Z300, the standard code numbers can be set to customer-specific codes on the DDC3000 Central Control Unit of the DDC3000 system. Code modifications are possible on the following DDC3000 Central Control Units DDC3010/ after version 3.6 DDC3035 after version 4.6 DDC3200 after production release Anlage Istwert Sollwert Zeiten < > 0. + /- Block Menü Kreis Diagnose DDC3002 after production release Daten Error DDC3300 after production release Hand Zurück CE Uhr SET Meldung Install Param Code DDC 3000 Code modifications Insert code key as shown in the diagnostic jack of the DDC3000 Central Control Unit Press key [Code], the display shows Code key The program level is back automatically unlocked Press key [Back] and call up M69 system menu. In the DDC parameters 1221 the standard code number 4712 of the operator level 2 can be changed. In the DDC parameters 1222 the standard code number 2359 of the operator level 3 can be changed. In the DDC parameters 1223 the standard code number 2460 of the program level can be changed. The new code numbers are always stored by pressing the key [SET]. The current code numbers are displayed in the above three DDC parameters. When calling up these DDC parameters, modified (and not known) code numbers can later be displayed at any time (only possible with code key). Locking of the DDC3000 Central Control Unit is done by removing the code key and pressing the key [Code]. Page 24/26

25 DD C Anlage Istwert Sollwert Hand Zurück CE Zeit en Uhr < SET > Mel dung Block Install Menü Param Kreis Code Diagnose Daten Error DDC 3100 Technical data sheet en Cable connections 0. +/- DDC3000 Central Contol Unit Data backup / recovery via diagnostic jack DDC m DDC m DDC ,3m 9-polig 25-polig Data backup / recovery via backside terminal MRP008 PC/ADT 9-25pol 9-polig m MRP008 0,3m 25-polig 5m Overview of possible cable connections between the DDC3000 Central Control Unit and the BMS Date Kieback & Peter GmbH & Co KG Tempelhofer Weg 50 D Berlin Telefon 030 / Telefax 030 / Page 25/26

26 Technical data sheet en Page 26/26

Modular I/O System Analog and Digital Interface Modules

Modular I/O System Analog and Digital Interface Modules OPERATING INSTRUCTIONS Modular I/O System Analog and Digital Interface Modules Installation Operation Maintenance Document Information Document ID Title: Operating Instructions Modular I/O System Part

More information

Documentation. M-Bus 130-mbx

Documentation. M-Bus 130-mbx Documentation M-Bus 130-mbx Introduction The mx M-Bus module is part of the mx Smart Slot communications family. With the integrated SmartSlot technology, mx systems ag offers automatic consumer data read-out

More information

How To Power A Power Control On An Ip40 (Ipl) With A Power Supply (Iplug) With An Ip20 Controller (Iphones) With Power Control (Power Control) With No Antenna) With The Ip20 (Power)

How To Power A Power Control On An Ip40 (Ipl) With A Power Supply (Iplug) With An Ip20 Controller (Iphones) With Power Control (Power Control) With No Antenna) With The Ip20 (Power) MODEL NUMBER: ISC910-1-0-GB-XX ISC911-5-0-GB-XX IXP20 CONTROLLER SPECIFICATIONS Working Environment Plastic Housing... Power ImproX IXP20 Controller INSTALLATION MANUAL Designed to work in an indoor (dry)

More information

Product Information Sheet UH36 Hi Pot Tester

Product Information Sheet UH36 Hi Pot Tester Product Information Sheet UH36 ETL Prüftechnik GmbH Telefon: +49 711 83 99 39-0 E-Mail: info@etl-prueftechnik.de Carl-Peters-Straße 23 D-70825 Korntal-Münchingen Telefax: +49 711 83 99 39-9 Internet: www.etl-prueftechnik.de

More information

VOICE RECORDING SYSTEM ISDN PRI / BRI

VOICE RECORDING SYSTEM ISDN PRI / BRI Sense Box VOICE RECORDING SYSTEM ISDN PRI / BRI / Analog SUB-SYSTEM ISDN2, ISDN30 Sense Box USER MANUAL TABLE OF CONTENTS 1. STATUTORY INFORMATION... 3 1.1 SAFETY WARNING... 3 1.2 SAFETY EXTRA LOW VOLTAGE

More information

HERZ-Thermal Actuators

HERZ-Thermal Actuators HERZ-Thermal Actuators Data Sheet 7708-7990, Issue 1011 Dimensions in mm 1 7710 00 1 7710 01 1 7711 18 1 7710 80 1 7710 81 1 7711 80 1 7711 81 1 7990 00 1 7980 00 1 7708 11 1 7708 10 1 7708 23 1 7709 01

More information

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency echnical data sheet NV24A--RE Communicative globe valve actuator for 2-way and 3-way globe valves Actuating force 1000 N Nominal voltage AC/DC 24 V Control Modulating DC (0)2...10 V Variable Nominal stroke

More information

Technical Description. Multifunctional Desk-Top Call Station Digital Version 8, 16 Keys L.No. 1 760 4, 1 761 5

Technical Description. Multifunctional Desk-Top Call Station Digital Version 8, 16 Keys L.No. 1 760 4, 1 761 5 Technical Description Multifunctional Desk-Top Call Station Digital Version 8, 16 Keys L.No. 1 760 4, 1 761 5 Contents 1. General remarks 2. Design 3. Block diagram 4. Function 4.1 Controller system with

More information

DeviceNet Bus Software Help for Programming an Allen Bradley Control System

DeviceNet Bus Software Help for Programming an Allen Bradley Control System FBP FieldBusPlug V7 DeviceNet Bus Software Help for Programming an Allen Bradley Control System DeviceNet Software Help for Programming an Allen Bradley Control System Contents Page General Purpose...

More information

DCS Data and communication server

DCS Data and communication server 8 58 PLD.TOWER PLD.RACK VISONIK DCS Data and communication server PLD.TOWER PLD.RACK Data and communication servers (DCS) are used as management stations in building automation and control (BAC). With

More information

T7560A,B,C Digital Wall Module

T7560A,B,C Digital Wall Module T7560A,B,C Digital Wall Module HONEYWELL EXCEL 5000 OPEN SYSTEM BEFORE INSTALLATION All wiring must comply with local electrical codes and ordinances or as specified on installation wiring diagrams. Digital

More information

Programming and Using the Courier V.Everything Modem for Remote Operation of DDF6000

Programming and Using the Courier V.Everything Modem for Remote Operation of DDF6000 Programming and Using the Courier V.Everything Modem for Remote Operation of DDF6000 1.0 Introduction A Technical Application Note from Doppler System July 5, 1999 Version 3.x of the DDF6000, running version

More information

PCS0100en 02.2008. Persy Control Services B.V. Netherlands

PCS0100en 02.2008. Persy Control Services B.V. Netherlands P-Bus Gateway PBGW2.128 Universal gateway between the P-bus protocol and open standard protocols. The variety of available electrical interfaces on the gateway offers a wide range of possibilities for

More information

NC-12 Modbus Application

NC-12 Modbus Application NC-12 Modbus Application NC-12 1 Table of Contents 1 Table of Contents... 2 2 Glossary... 3 SCADA...3 3 NC-12 Modbus in general... 3 4 Entire system... 4 4.1 PFC to PC connection alternatives...4 4.1.1

More information

MDM192 MULTI-DROPS DIGITAL MODEM FOR PRIVATE LINE. USER GUIDE Document reference : 9010709-03

MDM192 MULTI-DROPS DIGITAL MODEM FOR PRIVATE LINE. USER GUIDE Document reference : 9010709-03 MDM192 MULTI-DROPS DIGITAL MODEM FOR PRIVATE LINE USER GUIDE Document reference : 9010709-03 If you have questions about the MDM192 or desire assistance, contact ETIC TELECOMMUNICATIONS at the following

More information

ENET-710. ENET-710 - Ethernet Module ENET-710 JAN / 06 FOUNDATION

ENET-710. ENET-710 - Ethernet Module ENET-710 JAN / 06 FOUNDATION ENET-710 ENET-710 - Ethernet Module JAN / 06 ENET-710 FOUNDATION E N E T 7 1 0 ME smar www.smar.com Specifications and information are subject to change without notice. Up-to-date address information is

More information

BACnet Automation Interface Module (Network Version)

BACnet Automation Interface Module (Network Version) Sense +V Tx Rx LAN LINK Over ARCNET KBaud BACnet Rx BACnet Tx Archive Valid Port S Tx Port S Rx Low Battery Network- Enhanced Access Default MSTP PTP = Download Required on Rnet and Port S IP Address IP

More information

Inwall 4 Input / 4 Output Module

Inwall 4 Input / 4 Output Module Inwall 4 Input / 4 Output Module IO44C02KNX Product Handbook Product: Inwall 4 Input / 4 Output Module Order Code: IO44C02KNX 1/27 INDEX 1. General Introduction... 3 2. Technical data... 3 2.1 Wiring Diagram...

More information

LOVELINK III- Process Monitoring, Logging, Graphing, & Configuration

LOVELINK III- Process Monitoring, Logging, Graphing, & Configuration LOVELINK III- Process Monitoring, Logging, Graphing, & Configuration VERSION 1.00.00 USER MANUAL Updated 09/13/2002 Table of Contents Hardware/Software Requirements...2 Computer Requirements...2 Instrument

More information

FLOW CALCULATOR INSTRUCTION MANUAL MESURES BAMOPHOX 759 26-06-2007 759 M1 02 E MES FLOW CALCULATOR 759-02/1

FLOW CALCULATOR INSTRUCTION MANUAL MESURES BAMOPHOX 759 26-06-2007 759 M1 02 E MES FLOW CALCULATOR 759-02/1 BAMOPHOX 759 E - M FLOW CALCULATOR INSTRUCTION MANUAL MESURES 22, Rue de la Voie des Bans - Z.I. de la Gare - 95100 ARGENTEUIL Tél : (33) 01 30 25 83 20 - Web : www.bamo.fr Fax : (33) 01 34 10 16 05 -

More information

CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems

CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems EN Security System CM705B CM705B - Universal Expander Module The CM705B universal expander provides a cost effective way

More information

BMR-Tool Kieback&Peter GmbH & Co. KG

BMR-Tool Kieback&Peter GmbH & Co. KG BMR-Tool Kieback&Peter GmbH & Co. KG Tempelhofer Weg 50 12347 Berlin/Germany Telefon: +49 30 60095-0, Telefax: +49 30 60095-164 www.kieback-peter.de, info@kieback-peter.de A This user manual replaces all

More information

TO-PASS. TO-PASS -FAQ- Remote Monitoring. What is TO-PASS used for? What are the special functions of TO-PASS?

TO-PASS. TO-PASS -FAQ- Remote Monitoring. What is TO-PASS used for? What are the special functions of TO-PASS? TO-PASS -FAQ- Remote Monitoring What is TO-PASS used for? TO-PASS modules are used as/for: Permanent online connection Fault detectors Remote data polling Data storage Telecontrol module What are the special

More information

How to read this guide

How to read this guide How to read this guide The following shows the symbols used in this Quick start guide with descriptions and examples. Symbol Description Example P oint Reference Caution [ ] This symbol explains information

More information

FLEET MANAGEMENT & CAR SECURITY SYSTEM GPRS/GPS

FLEET MANAGEMENT & CAR SECURITY SYSTEM GPRS/GPS FLEET MANAGEMENT & CAR SECURITY SYSTEM FOR PROVIDERS AND CUSTOMERS The Tracker Server Communication Program for data collection The Tracker Client Map Program intended for dispatching desks The GSM/GPRS

More information

MANUAL PC1000R INFO@APART-AUDIO.COM

MANUAL PC1000R INFO@APART-AUDIO.COM MANUAL PC1000R INFO@APART-AUDIO.COM Features The APart PC1000R is a professional multisource CD/USB/SD card music player, equipped with balanced and unbalanced analog outputs, coaxial and optical digital

More information

Alcatel-Lucent OmniPCX Enterprise Communication Server TA-MMK (MMK V2)

Alcatel-Lucent OmniPCX Enterprise Communication Server TA-MMK (MMK V2) Alcatel-Lucent OmniPCX Enterprise Communication Server TA-MMK (MMK V2) Legal notice: Alcatel, Lucent, Alcatel-Lucent and the Alcatel-Lucent logo are trademarks of Alcatel-Lucent. All other trademarks are

More information

FX07 Field Controller

FX07 Field Controller Product Bulletin FX07 Field Controller Issue Date March 25, 2008 FX07 Field Controller The FX07 is a high performance field controller designed specifically for commercial Heating, Ventilating, Air Conditioning,

More information

Electronic Control Devices The European Product Catalogue 2007

Electronic Control Devices The European Product Catalogue 2007 FX14 Field Controller (1/4) FX14 Field Controller The FX14 is an equipment field controller in the Facility Explorer range of products. The controller is designed specifically for commercial Heating, Ventilating,

More information

Firmware version: 1.10 Issue: 7 AUTODIALER GD30.2. Instruction Manual

Firmware version: 1.10 Issue: 7 AUTODIALER GD30.2. Instruction Manual Firmware version: 1.10 Issue: 7 AUTODIALER GD30.2 Instruction Manual Firmware version: 2.0.1 Issue: 0.6 Version of the GPRS transmitters configurator: 1.3.6.3 Date of issue: 07.03.2012 TABLE OF CONTENTS

More information

AC-115 Compact Networked Single Door Controller. Installation and User Manual

AC-115 Compact Networked Single Door Controller. Installation and User Manual AC-115 Compact Networked Single Controller Installation and User Manual December 2007 Table of Contents Table of Contents 1. Introduction...5 1.1 Key Features... 6 1.2 Technical Specifications... 7 2.

More information

T3 Mux M13 Multiplexer

T3 Mux M13 Multiplexer T3 Mux M13 Multiplexer User Manual [Type the abstract of the document here. The abstract is typically a short summary of the contents of the document. Type the abstract of the document here. The abstract

More information

Option field bus: without bus with profibus DP. Design-Index (Subject to change)

Option field bus: without bus with profibus DP. Design-Index (Subject to change) Amplifier / controller cards ED1 Digital amplifier / controller card ED1 for 1 or 2 proportional solenoids 4 analogue inputs, of which 2 for differential inputs 8 digital inputs Card setting via PC, multi-function

More information

MicroTech II McQuay Maverick II Rooftop Unit Controller BACnet Communication Module (MS/TP)

MicroTech II McQuay Maverick II Rooftop Unit Controller BACnet Communication Module (MS/TP) Installation and Maintenance Manual IM 852 Group: Controls Part Number: IM 852 Date: June 2007 Supercedes: New MicroTech II McQuay Maverick II Rooftop Unit Controller BACnet Communication Module (MS/TP)

More information

GSM HOME SECURITY SYSTEM

GSM HOME SECURITY SYSTEM Cell /Mobile phone home security system GSM HOME SECURITY SYSTEM Model : GSM-120 TABLE OF CONTENTS 1. FEATURES... 1 2. APPLICATION... 2 3. SPECIFICATIONS... 3 4. FRONT PANEL & LAYOUT DESCRIPTION...6 5.

More information

Technical Manual. For use with Caller ID signaling types: Belcore 202, British Telecom, & ETSI

Technical Manual. For use with Caller ID signaling types: Belcore 202, British Telecom, & ETSI Technical Manual For use with Caller ID signaling types: Belcore 202, British Telecom, & ETSI Caller ID.com WHOZZ CALLING? POS 2 Caller ID Monitoring Unit Technical Manual For use with Caller ID signaling

More information

OZW30. Central Unit SYNERGYR

OZW30. Central Unit SYNERGYR 2 841 SYNERGYR Central Unit OZW30 Collects billing data from the apartments. Generates an image of each apartment's heat consumption and makes it available for readout. Acts on room temperature control

More information

SIMATIC NET. CP 243-2 AS-Interface Master B C. Preface Contents. Technical Description and Installation Instructions Interface to the User Program

SIMATIC NET. CP 243-2 AS-Interface Master B C. Preface Contents. Technical Description and Installation Instructions Interface to the User Program Preface Contents SIMATIC NET CP 243-2 AS-Interface Master Manual Technical Description and Installation Instructions Interface to the User Program 2 in the S7-200 CPU Access to the Data of the AS-i Slaves

More information

Combi B Alarm box. Mounting instructions

Combi B Alarm box. Mounting instructions Combi B Alarm box Mounting instructions EN Mounting instructions Alarm box Combi B VdS, G113064, G113065, G113066 Table of Contents 1 Description... 3 2 System overview... 3 3 Structure... 3 3.1 Power

More information

Data Bulletin. Communications Wiring for POWERLINK G3 Systems Class 1210 ABOUT THIS BULLETIN APPLICATION INTRODUCTION.

Data Bulletin. Communications Wiring for POWERLINK G3 Systems Class 1210 ABOUT THIS BULLETIN APPLICATION INTRODUCTION. Data Bulletin 1210DB0002R3/05 03/2005 LaVergne, TN, USA Communications Wiring for POWERLINK G3 Systems Class 1210 Retain for future use. ABOUT THIS BULLETIN This data bulletin describes the proper wiring

More information

e-4 AWT07MLED 7 Q TFT LCD MONITOR (LED Backlighted) USER MANUAL

e-4 AWT07MLED 7 Q TFT LCD MONITOR (LED Backlighted) USER MANUAL Thank you for purchasing our product. Please read this User s Manual before using the product. Change without Notice AWT07MLED 7 Q TFT LCD MONITOR (LED Backlighted) USER MANUAL e-4 SAFETY PRECAUTIONS Federal

More information

DK40 Datasheet & Hardware manual Version 2

DK40 Datasheet & Hardware manual Version 2 DK40 Datasheet & Hardware manual Version 2 IPC@CHIP DK40 Evaluation module Beck IPC GmbH http://www.bcl.de page 1 of 11 Table of contents Table of contents... 2 Basic description... 3 Characteristics...

More information

LDG DTS-4/4R Desktop Coaxial Switch / Remote

LDG DTS-4/4R Desktop Coaxial Switch / Remote LDG DTS-4/4R Desktop Coaxial Switch / Remote LDG Electronics 1445 Parran Road, PO Box 48 St. Leonard MD 20685-2903 USA Phone: 410-586-2177 Fax: 410-586-8475 ldg@ldgelectronics.com www.ldgelectronics.com

More information

TX OPEN RS232/485 module

TX OPEN RS232/485 module s 8 185 8185P01 TX-I/O ; DESIGO OPEN TX OPEN RS/485 module for integrating third-party systems and devices to DESIGO (V4 or higher) TXI1.OPEN Platform to integrate third-party systems and devices to the

More information

RN-WIFLY-EVAL-UM. WiFly Evaluation Kit. 2012 Roving Networks. All rights reserved. RN-WIFLY-EVAL-UM Version 1.32r 10/9/2012 USER MANUAL

RN-WIFLY-EVAL-UM. WiFly Evaluation Kit. 2012 Roving Networks. All rights reserved. RN-WIFLY-EVAL-UM Version 1.32r 10/9/2012 USER MANUAL WiFly Evaluation Kit 2012 Roving Networks. All rights reserved. Version 1.32r 10/9/2012 USER MANUAL OVERVIEW This document describes the hardware and software setup for Roving Networks evaluation kits,

More information

HCS-3300/3302/3304 USB Remote Programmable Laboratory Grade Switching Mode Power Supply

HCS-3300/3302/3304 USB Remote Programmable Laboratory Grade Switching Mode Power Supply 1. INTRODUCTION HCS-3300/3302/3304 USB Remote Programmable Laboratory Grade Switching Mode Power Supply User Manual This family of efficient, upgraded SMPS with small form factor, auto cross over CV CC,

More information

ModBus Server - KNX. Gateway for integration of KNX equipment into Modbus (RTU and TCP) control systems.

ModBus Server - KNX. Gateway for integration of KNX equipment into Modbus (RTU and TCP) control systems. IntesisBox ModBus Server - KNX Gateway for integration of KNX equipment into Modbus (RTU and TCP) control systems. Integrate KNX based lighting control into your SCADA, BMS, PLC "talking" Modbus. Master

More information

R60 USB to CAN interface Manual (1.5 EN)

R60 USB to CAN interface Manual (1.5 EN) R60 USB to CAN interface Manual (1.5 EN) General information R60 USB to CAN interface Manual Version 1.5 EN, 02/2010, DOC01586 Copyright 2010 by ; all rights reserved. Eugen-Adolff-Strasse 134, D-71522

More information

M1000 Process Alarm Monitor

M1000 Process Alarm Monitor Data Sheet Process Alarm Monitor Reliable Supervision and Control 10 inputs with LED indications Supports both NO/NC input contacts 10 open collector outputs Built-in siren relay Text label for alarm descriptions

More information

Quick Connect. quick - simple - efficient. www.g-mw.de

Quick Connect. quick - simple - efficient. www.g-mw.de Quick Connect quick - simple - efficient www.g-mw.de Phone: +49 9103 7129-0 Fax: +49 9103 7129-207 Innovative connection technology to plug three single-phase current transformers to multifunctional power

More information

Automation System TROVIS 6400 TROVIS 6493 Compact Controller

Automation System TROVIS 6400 TROVIS 6493 Compact Controller Automation System TROVIS 6400 TROVIS 6493 Compact Controller For panel mounting (front frame 48 x 96 mm/1.89 x 3.78 inch) Application Digital controller to automate industrial and process plants for general

More information

Keep it Simple Timing

Keep it Simple Timing Keep it Simple Timing Support... 1 Introduction... 2 Turn On and Go... 3 Start Clock for Orienteering... 3 Pre Start Clock for Orienteering... 3 Real Time / Finish Clock... 3 Timer Clock... 4 Configuring

More information

DDC4002 Automation Station with Operator Function

DDC4002 Automation Station with Operator Function Issue 2014-04-16 Datasheet 2.60-10.202-01-EN utomation Station with Operator Function pplication Color touchscreen with BCnet communication Standalone station with operator function for closed-loop and

More information

Inwall Room Temperature Unit

Inwall Room Temperature Unit Inwall Room Temperature Unit TM11B01KNX TM11B11KNX TM11B21KNX Product Handbook Product: Inwall Room Temperature Unit Order Code: TM11B01KNX TM11B11KNX TM11B21KNX Application Program ETS: TM11B_1KNX Inwall

More information

ZC-24DO CANopen I/O Module: 24 Digital Outputs

ZC-24DO CANopen I/O Module: 24 Digital Outputs Z-PC Line EN ZC-24DO CANopen I/O Module: 24 Digital Outputs Installation Manual Contents: - General Specifications - Technical Specifications - Installation Rules - Electrical connections - DIP-switches

More information

Switch Actuator, 8-fold, 10 A, MDRC AT/S 8.10.1, GH Q631 0075 R0111

Switch Actuator, 8-fold, 10 A, MDRC AT/S 8.10.1, GH Q631 0075 R0111 , GH Q631 0075 R0111 The 8-fold switch actuator is a DIN rail mounted device for insertion in the distribution board. It is connected to the EIB via a bus terminal. In the event of bus voltage failure,

More information

Belimo Gateway MP to Modbus RTU - UK24MOD

Belimo Gateway MP to Modbus RTU - UK24MOD Product information UK24MOD MODBUS RTU Belimo Gateway MP to Modbus RTU - UK24MOD Contents Complete overview 2 Technical data 3 Safety notes 4 Product features 4 Installation and commissioning 4 Electrical

More information

MI4 - Operator Panel : Engineering

MI4 - Operator Panel : Engineering MI4 - Operator Panel : Engineering MI4 - Operator Panel : Engineering Overview MI4 Text Operator Panel MI4 Graphic Operator Panel MI4 Touch Operator Panel Communication modules Accessories MI4-CFG-1 Engineering

More information

Electronic Control Devices The European Product Catalogue 2007

Electronic Control Devices The European Product Catalogue 2007 FX07 Field Controller (1/4) FX07 Field Controller Display Model Dimensions in mm (inches) The FX07 is a terminal unit controller in the Facility Explorer range of products. The controller is designed specifically

More information

Monitoring,Telemaintenance,... HACCP. Innovative Supermarket solutions. Tecnologia ed Evoluzione

Monitoring,Telemaintenance,... HACCP. Innovative Supermarket solutions. Tecnologia ed Evoluzione Monitoring,Telemaintenance,... HACCP Innovative Supermarket solutions Tecnologia ed Evoluzione For more compact systems, with the same management and control needs as larger areas, PlantWatch offers the

More information

RS - SPM. Serial parallel translator module

RS - SPM. Serial parallel translator module ReSatron GmbH Boisheimer Str. 162 D-41751 Viersen Telefon (+49) 02162-45 06 80 Telefax (+49) 02162-45 03 04 email: info@resatron.de RS - SPM Serial parallel translator module RSSPM000215SPM-021 - Subject

More information

MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE

MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE DESCRIPTION MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE DESCRIPTION The SST Model 5010 Two Channel Smoke/Fire Detection Module provides two independent detection input channels for the NOVA-5000

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS LIGHTING CONTROL PANELS 4 AND 8 RELAYS INSTALLATION INSTRUCTIONS INSTALLATION OVERVIEW The installation instructions contained in this document are provided as a guide for proper and reliable installation.

More information

FOSTCDR. Industrial Serial to Multimode Fiber Optic Converter PRODUCT INFORMATION B&B ELECTRONICS. Specifications Serial Technology

FOSTCDR. Industrial Serial to Multimode Fiber Optic Converter PRODUCT INFORMATION B&B ELECTRONICS. Specifications Serial Technology FOSTCDR pn 8684R1 FOSTCDR-0812ds page 1/5 Industrial Serial to Multimode Fiber Optic Converter Data Rates up to 115.2 kbps 2.5 Mile (4 km) Range 10 to 30 VDC Input Voltage Wide Operating Temperature 2000V

More information

Light scene push button 8gang comfort flush-mounted 751688xx

Light scene push button 8gang comfort flush-mounted 751688xx 751688xx Documentation Product name: Light scene push button 8gang comfort Design: flush-mounting type (Up) ETS search path: Push button / Push button general / Light scene push button 8gang comfort Functional

More information

UCC 1 USB-CAN CONVERTER

UCC 1 USB-CAN CONVERTER Owner s Manual UCC 1 USB-CAN CONVERTER Contents 1. Description... 17 2. Controls and Connections... 18 3. Installation... 19 3.1 Unpacking... 19 3.2 Rack-Mounting... 19 4. Initial Operation... 20 4.1 PC

More information

TEMON 8-C. Doc. N MO-0370-ING TEMPERATURE MONITOR DEVICE TYPE TEMON 8-C OPERATION MANUAL. Microener - Copyright 2010 FW 2.2 Date 01.12.2008 Rev.

TEMON 8-C. Doc. N MO-0370-ING TEMPERATURE MONITOR DEVICE TYPE TEMON 8-C OPERATION MANUAL. Microener - Copyright 2010 FW 2.2 Date 01.12.2008 Rev. TEMPERATURE MONITOR DEVICE TYPE TEMON 8-C OPERATION MANUAL Microener - Copyright 2010 FW 2.2 Date 01.12.2008 Rev. 0 1. Generality 3 2. Introduction 3 3. Accessories and Options 3 4. Installation 3 5. Connection

More information

WEA-Base. User manual for load cell transmitters. UK WEA-Base User manual for load cell transmitters Version 3.2 UK

WEA-Base. User manual for load cell transmitters. UK WEA-Base User manual for load cell transmitters Version 3.2 UK WEA-Base User manual for load cell transmitters 1 Contents 1. Technical data... 3 2. Assembly... 4 2.1 Power supply... 4 2.2 Load cells... 4 2.3 RS-485... 4 2.4 Relays... 5 2.5 Digital input... 5 2.6 Analogue

More information

Easy! Smooth! GP/ST-3500 Series->GP4000 Series Replacement Guidebook

Easy! Smooth! GP/ST-3500 Series->GP4000 Series Replacement Guidebook Easy! Smooth! GP/ST-3500 Series->GP4000 Series Replacement Guidebook 1/46 The 6th Edition April 2013 Copyright 2013.4 Digital Electronics Corporation. All Rights Reserved. Preface This guidebook introduces

More information

CONFIGURABLE SAFETY RELAYS

CONFIGURABLE SAFETY RELAYS MSI-s/R, MSI-sx/Rx Configurable MSI provide important functions for the efficient flow of automated production processes Special features Combined guarding types by connecting up to 4 AOPDs Additional

More information

Digital display DA 48

Digital display DA 48 Loop powered plug-in LCD display No auxiliary energy source needed Scale freely adjustable on site Can be turned to any position Suitable for any 0 ma transmitter with EN 175301-803A connector Digital

More information

VP23, 3-way proportional pressure control valves Seat valve with μp-driven pressure control

VP23, 3-way proportional pressure control valves Seat valve with μp-driven pressure control VP, -way proportional pressure control valves > > Port size: G/... G/ > > All-digital control electronics > > Variable pressure control > > Optional actuation via fieldbus (separate datasheet on request)

More information

Ethernet. Customer Provided Equipment Configuring the Ethernet port.

Ethernet. Customer Provided Equipment Configuring the Ethernet port. Installing the RDSP-3000A-NIST Master Clock. Ethernet Connect the RJ-45 connector to a TCP/IP network. Equipment The following equipment comes with the clock system: RDSP-3000A-NIST Master Clock Module.

More information

INTEGRATED MONITORING RECEIVER WITH MICRO SERVER STAM-IRS. 1. Features. 2. Description

INTEGRATED MONITORING RECEIVER WITH MICRO SERVER STAM-IRS. 1. Features. 2. Description INTEGRATED MONITORING RECEIVER WITH MICRO SERVER STAM-IRS stam-irs_en 01/11 STAM-IRS is a dedicated server to be used with the STAM-2 monitoring station which enables receiving transmissions sent via telephone

More information

Programmable set for Ethernet Modbus/TCP in IP67 TI-BL67-PG-EN-2

Programmable set for Ethernet Modbus/TCP in IP67 TI-BL67-PG-EN-2 Type code Ident no. 1545065 Number of channels 2 Dimensions (W x L x H) 108 x 145 x 77.5 mm CoDeSys-programmable acc. to IEC 61131-3 Cable max. 50 m between interface and read/write head 10/100 Mbps Male

More information

Allen-Bradley/Rockwell

Allen-Bradley/Rockwell MANUFACTURER DATA SHEET High Speed Counter Manufacturer: Allen-radley/Rockwell Model Number: 1746-HSCE See www.geomartin.com for additional PDF datasheets Martin Part Number: E-014901-03 VendorPartNumber:

More information

Smarthome SELECT Bluetooth Wireless Stereo Audio Receiver and Amplifier INTRODUCTION

Smarthome SELECT Bluetooth Wireless Stereo Audio Receiver and Amplifier INTRODUCTION Smarthome SELECT Bluetooth Wireless Stereo Audio Receiver and Amplifier INTRODUCTION The Smarthome SELECT Bluetooth Wireless Stereo Audio Receiver and Amplifier is a multi-functional compact device. It

More information

ALARM SYSTEM PLC. MODICON 984 - A120 Description. 01 September 2000 ASI GmbH B. Dittmer LADESTRASSE 3-3A 28197 BREMEN

ALARM SYSTEM PLC. MODICON 984 - A120 Description. 01 September 2000 ASI GmbH B. Dittmer LADESTRASSE 3-3A 28197 BREMEN ALARM SYSTEM PLC MODICON 984 - A120 Description 01 September 2000 ASI GmbH B. Dittmer LADESTRASSE 3-3A 28197 BREMEN Alarm System PLC 984 - A120, Sheet 2 1. Compact Hardware The Alarm- and Monitoring System,

More information

MILLENIUM INSTALLATION MANUAL NTR 735 A. Simple Automation Control Module (MAS)

MILLENIUM INSTALLATION MANUAL NTR 735 A. Simple Automation Control Module (MAS) MILLENIUM Table of contents 1. INTRODUCTION 1 2. HARDWARE DESCRIPTION 2 3. INSTALLATION 5 4. CONNECTION 6 5. USER SAFETY AND PROTECTION OF EQUIPMENT 8 1. Introduction The MILLENIUM series has been designed

More information

DOSISYS. Hands Free Reader LDM 210 - LDM 220. User Manual 127356A

DOSISYS. Hands Free Reader LDM 210 - LDM 220. User Manual 127356A DOSISYS LDM 210 - LDM 220 Hands Free Reader User Manual 127356A Publication, translation and reproduction total or partial of this document is strictly forbidden without authorization MGP Instruments

More information

Installation and start-up guide NETA-21 remote monitoring tool

Installation and start-up guide NETA-21 remote monitoring tool Remote monitoring options for ABB drives, converters and inverters Installation and start-up guide NETA-21 remote monitoring tool 3AUA0000096881 REV C Effective: 2013-03-01 2013 ABB Oy. All rights reserved.

More information

M68EVB908QL4 Development Board for Motorola MC68HC908QL4

M68EVB908QL4 Development Board for Motorola MC68HC908QL4 M68EVB908QL4 Development Board for Motorola MC68HC908QL4! Axiom Manufacturing 2813 Industrial Lane Garland, TX 75041 Email: Sales@axman.com Web: http://www.axman.com! CONTENTS CAUTIONARY NOTES...3 TERMINOLOGY...3

More information

PACKAGE OUTLINE DALLAS DS2434 DS2434 GND. PR 35 PACKAGE See Mech. Drawings Section

PACKAGE OUTLINE DALLAS DS2434 DS2434 GND. PR 35 PACKAGE See Mech. Drawings Section PRELIMINARY DS2434 Battery Identification Chip FEATURES Provides unique ID number to battery packs PACKAGE OUTLINE Eliminates thermistors by sensing battery temperature on chip DALLAS DS2434 1 2 3 256

More information

Product Manual. ABB i-bus KNX IP Interface IPS/S 2.1. Intelligent Installation Systems ABB

Product Manual. ABB i-bus KNX IP Interface IPS/S 2.1. Intelligent Installation Systems ABB Product Manual ABB i-bus KNX IP Interface IPS/S 2.1 Intelligent Installation Systems ABB This manual describes the function of the IP Interface IPS/S 2.1 with the application program IP Interface. Subject

More information

3x cinch/s-video socket Order no.: 33 1532 xx. USB/3.5 mm audio socket Order no.: 33 1539 xx. VGA socket Order no.: 33 1540 xx

3x cinch/s-video socket Order no.: 33 1532 xx. USB/3.5 mm audio socket Order no.: 33 1539 xx. VGA socket Order no.: 33 1540 xx 3x cinch/s-video socket Order no.: 33 1532 xx USB/3.5 mm audio socket Order no.: 33 1539 xx VGA socket Order no.: 33 1540 xx VGA socket with screw-in lift terminals Order no.: 33 1541 xx High definition

More information

WEB log. Device connection plans

WEB log. Device connection plans WEB log LIGHT+ 20 BASIC 100 PRO unlimited Device connection plans Version 20151210* Copyright Copyright for this manual remains with the manufacturer. No part of this manual may be reproduced or edited,

More information

LINETRAXX VMD460-NA. Network and system protection (NS protection) for monitoring the power feed-in of power generation systems

LINETRAXX VMD460-NA. Network and system protection (NS protection) for monitoring the power feed-in of power generation systems LIETRAXX -A etwork and system protection (S protection) for monitoring the power feed-in of power generation systems TDB301021en/06.2013 LIETRAXX -A etwork and system protection (S protection) for monitoring

More information

Automatic AES Change-Over

Automatic AES Change-Over Automatic AES Change-Over Thank you for choosing a GHIELMETTI product. We are convinced that your choice will prove to be a wise and worthy decision for many years to come. Your GHIELMETTI product has

More information

ABB RTU560A Series CMU & Modules

ABB RTU560A Series CMU & Modules ABB RTU560A Series CMU & Modules 1KGT 150 648 V1.02 March 4, 2012 Slide 1 Contents RTU560A rack solutions March 4, 2012 Slide 2 560CSR01 Available for wall mounting and swing frame Supports redundant power

More information

* DISCLAIMER: Contents. How to Use This Guide: COMMERCIAL INSTALL GUIDE 2

* DISCLAIMER: Contents. How to Use This Guide: COMMERCIAL INSTALL GUIDE 2 COMMERCIAL INSTALL GUIDE 2 Contents How to Use This Guide: The first section of this guide is designed to assist you with the installation of your DECK Monitoring hardware. The revenue grade meter and

More information

How To Control A Power Supply With A Mini Transmitter And Switch (Power Supply)

How To Control A Power Supply With A Mini Transmitter And Switch (Power Supply) transmitter (2 wire) / switch for continuous or On/Off Control Indication, monitoring, transmitting and continuous or On/Off control in one device Output signal 4...20 ma, 2-wire for continuous control

More information

IntesisBox KNX LG Air Conditioning

IntesisBox KNX LG Air Conditioning IntesisBox KNX LG Air Conditioning Gateway for integration of LG Air Conditioners with KNX control systems. 1. Main Features Direct connection to KNX TP-1 (EIB) bus. Direct connection to LG outdoor unit

More information

TX GSM SMS Auto-dial Alarm System. Installation and User Manual

TX GSM SMS Auto-dial Alarm System. Installation and User Manual TX GSM SMS Auto-dial Alarm System Installation and User Manual Product Features: 1. 16 wireless zones, 3 wired zones alarm system, suitable for small to medium size offices and homes. 2. The system uses

More information

How To Use A Network Card With A Network Box (Ios) On A Microsoft Powerbook 2.5 (I2) (I3) (Io2) And I2 (Io) (Net) (Ipo) (

How To Use A Network Card With A Network Box (Ios) On A Microsoft Powerbook 2.5 (I2) (I3) (Io2) And I2 (Io) (Net) (Ipo) ( FACTORY AUTOMATION MANUAL BM100 BACKUP MODULE With regard to the supply of products, the current issue of the following document is applicable: The General Terms of Delivery for Products and Services of

More information

16-Port RS232 to USB2.0 High Speed Multi Serial Adapter (w/ Metal Case) Installation Guide

16-Port RS232 to USB2.0 High Speed Multi Serial Adapter (w/ Metal Case) Installation Guide 16-Port RS232 to USB2.0 High Speed Multi Serial Adapter (w/ Metal Case) Installation Guide 1. Introduction Thank you for purchasing this 16-Port RS232 to USB2.0 High Speed Multi Serial Adapter. It is an

More information

1 Technical Description Lokal-200PC

1 Technical Description Lokal-200PC 1 Technical Description Lokal-200PC 1.1 Overview laptop with in-built accummulator USB connection correlator box internal power supply laptop (if the device has been supplied by F.A.S.T.) BNC aerial connection

More information

EDI Distributor Control Interface Wiring and Setup Instructions

EDI Distributor Control Interface Wiring and Setup Instructions Universal I/O EDI Distributor Control Interface Wiring and Setup Instructions EDI UNIVERSAL I/O INTERFACE MODULE The only interface needed for EDI-V5 controls Network compatible with all older EDI controls

More information

IPG/7700 Hardware Manual SYSTECH. Document number 80-001099-7 Revision A

IPG/7700 Hardware Manual SYSTECH. Document number 80-001099-7 Revision A IPG/7700 Hardware Manual SYSTECH C O R P O R A T I O N Document number 80-001099-7 Revision A Created 2010, and Protected Under the U.S. Copyright Act of 1976. Copyright 2010, SYSTECH Corporation All Rights

More information

JNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410

JNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410 The INTEG is an Ethernet I/O (digital, analog) device that monitors and controls a small set of process signals. functions as both basic I/O for integration with another application or system AND as a

More information

5-port / 8-port 10/100BaseTX Industrial Ethernet Switch User Manual

5-port / 8-port 10/100BaseTX Industrial Ethernet Switch User Manual 5-port / 8-port 10/100BaseTX Industrial Ethernet Switch User Manual Content Overview... 1 Introduction... 1 Features... 3 Packing List... 4 Safety Precaution... 4 Hardware Description... 5 Front Panel...

More information