1 Data Center Combined Heat and Power Benefits and Implementation Justin Grau, Google Inc. Sam Brewer, GEM Energy

2 Data Center Challenges Electric Load Densification Thermal Dissipation Requires constant cooling Power limits from utility Electric costs Unreliable electric grid Moore s Law

3 Market Fundamentals Energy has been very inexpensive traditionally A wasteful energy economy has evolved that is running into limits to growth As limits are approached or exceeded, energy prices become expensive and reliability decreases Growth in population and standard of living puts pressure on our energy system Environmental degradation issues are related to our energy system Regulatory bias against clean energy technologies is being removed

4 Risk Electric supply availability and quality is the key variable for data operations Current planning does not adequately address reliability for long duration electric outages (48 hours+) Computers run almost everything Diesel reciprocating generators are not reliable for long duration events Standby diesel generator have high emissions due to the costs of adding emission reducing equipment

5 Legacy Electrical Distribution Model

6 Current Legacy Data Center Normal Operation Diesel Fuel Storage Utility Provides Electric Power UPS provides quality control of electricity Diesel Generators Battery System Central Grid Utility Switchgear UPS PDU IT Equipment Infrastructure Chillers DX Units Pumps Lights Cooling Interface / Infrastructure Key Raw Electricity Clean Electricity Fuel Chilled Water

7 Current Legacy Data Center Emergency Operation Diesel Fuel Storage Utility is absent UPS components fail because of generator output quality Diesel Generators provide power Diesel Generators Battery System Central Grid Utility Switchgear UPS PDU IT Equipment Infrastructure Chillers DX Units Pumps Lights Cooling Interface / Infrastructure Key Raw Electricity Clean Electricity Fuel Chilled Water Cooling system becomes less reliable because of power quality and switching Reliability decreases to ~0 after 1 2 weeks

8 Distributed Generation Model 50% fewer links in the distribution chain Resource Recovery Gas Distribution End User Gas Drilling Company Gas Utility You

9 On Site Power Generation Technology Needs a primary fuel Must operate unattended and be reliable Must be cost effective Must be less polluting than the utility

10 Benefits of CHP over 1MW Legacy Data center Increased Reliability Tier 4 data center (Uptime Institute) 4 hour outage in any 5 year period 48 minute outage in any 1 year period CHP Data Center (US EPA) CHP + 1 utility feed provides for an expected 43 minute outage in any 1 year period CH + 2 utility feeds provides for an expected 7 minute outage in any 1 year period

11 Green Data Center CHP Retrofit Reduces Operational Costs Additional network deliverable fuel source Alternate cooling technology Environmentally friendly

12 Green Data Center New Build

13 Green Data Center New Build 2

14 Benefits of CHP over 1 MW Legacy Data center Reduced annual electricity costs Utility= $1,350,000 CHP= $390,000 Decreased annual emissions (metric tons) Utility CO2= 10,800 Nox= 12.5 CHP CO2= 5,300 NOx= 1.6

15 University of Toledo Project Summary Modular Construction Project Vitals Type Data Center Year 2012 Location Function Reason Electric Heat Cooling Toledo, OH Mission Critical Cost Reduction 260 kw 1.0 MMBTU/hr 100 Tons Backup Level 1 Configuration CPS M C Savings $150,000+

16 Syracuse University Project Summary Project Vitals Type Data Center Year 2010 Location Function Reason Electric Heat Syracuse, NY Mission Critical Cost Reduction 780 kw 4.0 MMBTU/hr Cooling Backup Level Tons Chilled Water Configuration Savings IPS M c(2) $300,000+/year

17 Questions? Contact Information: Justin Grau Sam Brewer

Data Center Combined Heat and Power (CHP): Benefits and Implementation

Data Center Combined Heat and Power (CHP): Benefits and Implementation Data Center Combined Heat and Power (CHP): Benefits and Implementation by Sam Brewer Justin Grau Page 1 of 14 I. Common Causes of Failure Major trends in the United States have reached an intersection

More information

Efficiency Metrics for CHP Systems: Total System and Effective Electric Efficiencies

Efficiency Metrics for CHP Systems: Total System and Effective Electric Efficiencies Efficiency Metrics for CHP Systems: Total System and Effective Electric Efficiencies Combined heat and power (CHP) is an efficient and clean approach to generating power and thermal energy from a single

More information

Evaluating cogeneration for your facility: A look at the potential energy-efficiency, economic and environmental benefits

Evaluating cogeneration for your facility: A look at the potential energy-efficiency, economic and environmental benefits Power topic #7018 Technical information from Cummins Power Generation Inc. Evaluating cogeneration for your facility: A look at the potential energy-efficiency, economic and environmental benefits > White

More information

Heat Recovery from Data Centres Conference Designing Energy Efficient Data Centres

Heat Recovery from Data Centres Conference Designing Energy Efficient Data Centres What factors determine the energy efficiency of a data centre? Where is the energy used? Local Climate Data Hall Temperatures Chiller / DX Energy Condenser / Dry Cooler / Cooling Tower Energy Pump Energy

More information

ABSTRACT DCMCCT PROJECT OVERVIEW

ABSTRACT DCMCCT PROJECT OVERVIEW Title: Case Study of the Austin Energy Dell Regional Children s Medical Center of Central Texas Packaged Hybrid CHP Energy Plant in Austin, Texas Authors: Mr. Ed Mardiat, Burns & McDonnell Mr. Jim Teigen,

More information

Combined Heat & Power. Discussion with Connecticut Energy Advisory Board. February 23, 2010

Combined Heat & Power. Discussion with Connecticut Energy Advisory Board. February 23, 2010 Combined Heat & Power Discussion with Connecticut Energy Advisory Board February 23, 2010 Discussion Topics Introduce NRG Thermal Representative NRG Thermal projects District Energy Combined Heat and Power

More information

World s Greenest High Performance Data Center

World s Greenest High Performance Data Center World s Greenest High Performance Data Center EcoDataCenter Sustainability for future generations Our Services Colocation Data Center for Mission Critical Requirements Lockable racks, cages, private rooms

More information

University of Melbourne Symposium on ICT Sustainability Dan Pointon 25 November 2008

University of Melbourne Symposium on ICT Sustainability Dan Pointon 25 November 2008 University of Melbourne Symposium on ICT Sustainability Dan Pointon 25 November 2008 Contents Welcome and Introduction Chapter 1: Data centre energy recap Chapter 2: Co-generation Chapter 3: CTC case study

More information

Micro-Turbine Combined Heat & Power Generators (CHP) Cold Climate Applications 2014 Polar Technology Conference Richard S.

Micro-Turbine Combined Heat & Power Generators (CHP) Cold Climate Applications 2014 Polar Technology Conference Richard S. Micro-Turbine Combined Heat & Power Generators (CHP) Cold Climate Applications 2014 Polar Technology Conference Richard S. Armstrong, PE DISTRIBUTED CO-GENERATION DEFINED Electricity and Heat production

More information

Recommendations for Measuring and Reporting Overall Data Center Efficiency

Recommendations for Measuring and Reporting Overall Data Center Efficiency Recommendations for Measuring and Reporting Overall Data Center Efficiency Version 2 Measuring PUE for Data Centers 17 May 2011 Table of Contents 1 Introduction... 1 1.1 Purpose Recommendations for Measuring

More information

High Natural Gas Prices and the Updated Market For CHP

High Natural Gas Prices and the Updated Market For CHP High Natural Gas Prices and the Updated Market For CHP World Energy Engineering Congress Paul Lemar, President E.J. Honton, Director Resource Dynamics Corporation 8605 Westwood Center Drive Vienna, Virginia

More information

University of Maryland College Park District Energy System. IDEA Campus Energy Conference February 9, 2012

University of Maryland College Park District Energy System. IDEA Campus Energy Conference February 9, 2012 University of Maryland College Park District Energy System IDEA Campus Energy Conference February 9, 2012 UMCP District Energy System The University of Maryland district energy system consists of a well

More information

DOE Data Center Energy Efficiency Program

DOE Data Center Energy Efficiency Program DOE Data Center Energy Efficiency Program Paul Scheihing U.S. Department of Energy Energy Efficiency and Renewable Energy April 2009 1 DOE Industrial Technologies Program Worki king to improve th e energy

More information

Recommendations for Measuring and Reporting Overall Data Center Efficiency

Recommendations for Measuring and Reporting Overall Data Center Efficiency Recommendations for Measuring and Reporting Overall Data Center Efficiency Version 1 Measuring PUE at Dedicated Data Centers 15 July 2010 Table of Contents 1 Introduction... 1 1.1 Purpose Recommendations

More information

Data Center Industry Leaders Reach Agreement on Guiding Principles for Energy Efficiency Metrics

Data Center Industry Leaders Reach Agreement on Guiding Principles for Energy Efficiency Metrics On January 13, 2010, 7x24 Exchange Chairman Robert Cassiliano and Vice President David Schirmacher met in Washington, DC with representatives from the EPA, the DOE and 7 leading industry organizations

More information

Data Center Analysis and Design Analysis of SU s Green Data Center Performance

Data Center Analysis and Design Analysis of SU s Green Data Center Performance Data Center Analysis and Design Analysis of SU s Green Data Center Performance Dustin W. Demetriou, PhD Development Engineer Advanced Thermal Energy Efficiency Lab IBM D. W. Demetriou October 29, 2013-1

More information

Source: EIA Natural Gas Issues and Trends 1998

Source: EIA Natural Gas Issues and Trends 1998 7.0 System Redesign Analysis 7.1 Emissions Natural gas is a clean burning fossil fuel. It consists of a mixture of hydrocarbon gases, primarily Methane (CH 4 ). In analyzing the combustion process, it

More information

ICT and the Green Data Centre

ICT and the Green Data Centre ICT and the Green Data Centre Scott McConnell Sales Manager c/o Tanya Duncan MD Interxion Ireland Green Data Centres Our Responsibility Data centre greenhouse gas emissions are projected to quadruple by

More information

CHP & ENVIRONMENTAL COMMODITIES: MARKET & POLICY UPDATE FOR MONETIZING RENEWABLE ENERGY CREDITS FROM CHP PROJECTS. Thomas Jacobsen October 2012

CHP & ENVIRONMENTAL COMMODITIES: MARKET & POLICY UPDATE FOR MONETIZING RENEWABLE ENERGY CREDITS FROM CHP PROJECTS. Thomas Jacobsen October 2012 CHP & ENVIRONMENTAL COMMODITIES: MARKET & POLICY UPDATE FOR MONETIZING RENEWABLE ENERGY CREDITS FROM CHP PROJECTS Thomas Jacobsen October 2012 ELEMENT MARKETS US Emissions House of the Year Launched in

More information

DEMONSTRATION OF COMBINED HEAT AND POWER TECHNOLOGY AT A DATA CENTER

DEMONSTRATION OF COMBINED HEAT AND POWER TECHNOLOGY AT A DATA CENTER E n e r g y R e s e a r c h a n d Development Division F I N A L P R O J E C T R E P O R T DEMONSTRATION OF COMBINED HEAT AND POWER TECHNOLOGY AT A DATA CENTER Prepared for: Prepared by: California Energy

More information

CHP Strategies and Options / Stored Energy. 2014 ENERGY SYMPOSIUM April8, 2014 Reading Country Club

CHP Strategies and Options / Stored Energy. 2014 ENERGY SYMPOSIUM April8, 2014 Reading Country Club CHP Strategies and Options / Stored Energy Jim Freihaut, Ph.D. Director, DOE Mid Atlantic CHP Technical Assistance Partnership Director, Indoor Aerosol Laboratory Professor, Architectural Engineering 104

More information

Scalable. Affordable. Flexible. Fast.

Scalable. Affordable. Flexible. Fast. Modular Data Center Solutions Scalable. Affordable. Flexible. Fast. Build the data center you need today with the flexibility to meet tomorrow s challenges The only constant in business is change. Fluctuations

More information

CRITICAL COOLING FOR DATA CENTERS

CRITICAL COOLING FOR DATA CENTERS IDEA 100 th Annual Conference & Trade Show CRITICAL COOLING FOR DATA CENTERS Presented by Ron Johanning, PE, LEED AP Mission Critical Market Leader Agenda EPA Report Data Center Energy Trends IT Best Practice

More information

Energy-efficient data center achieves 2N reliability; MTU Onsite Energy generator sets provide critical backup

Energy-efficient data center achieves 2N reliability; MTU Onsite Energy generator sets provide critical backup Press Release Contact: Gary Mason Tognum America Inc. Phone: +1 248 560 8480 E-mail: gary.mason@tognum.com Agency contact: Robert E. Sheldon, APR Creative Communications Consultants, Inc. Phone: +1 210

More information

GREEN DATA CENTER DESIGN

GREEN DATA CENTER DESIGN Jeffrey Menig Global Facilities Facility Engineering The application of multiple available technologies resulting in improved energy optimization without significantly increasing capital investment. A

More information

Wesleyan University. Electrical Power Study

Wesleyan University. Electrical Power Study 1 Wesleyan University Business Continuity Planning Electrical Power Study 2 October 2011 snow storm 80% of Connecticut lost power including Wesleyan Wesleyan buildings were without power 3-6 days Without

More information

Combined Heat & Power (CHP) UGI Webinar. Presented By: Barry Wentzel, UGI Utilities Eric Burgis, Energy Solutions Center June 18, 2013

Combined Heat & Power (CHP) UGI Webinar. Presented By: Barry Wentzel, UGI Utilities Eric Burgis, Energy Solutions Center June 18, 2013 Combined Heat & Power (CHP) UGI Webinar Presented By: Barry Wentzel, UGI Utilities Eric Burgis, Energy Solutions Center June 18, 2013 Topics to Discuss What is CHP and CCHP? What is the CHP System and

More information

Rapid Prototyping Reveals

Rapid Prototyping Reveals Rapid Prototyping Reveals The Key to Unlocking Electricity Investment, t Innovation, and Improvements September 15, 2010 Galvin Initiative Background Started by former Motorola Chairman Robert Galvin in

More information

Fuel Cell Systems for Telecom Backup Power

Fuel Cell Systems for Telecom Backup Power Fuel Cell Systems for Telecom Backup Power Shanna Knights Manager, Research January 28, 2014 Smarter Solutions for a Clean Energy Future Ballard - Who We Are Ballard is the global leader in clean energy

More information

Richard Sweetser, Principal Investigator, EXERGY Partners Corp. Email: rsweetser@exergypartners.com, Phone: 703.707.0293

Richard Sweetser, Principal Investigator, EXERGY Partners Corp. Email: rsweetser@exergypartners.com, Phone: 703.707.0293 Richard Sweetser, Principal Investigator, EXERGY Partners Corp. Email: rsweetser@exergypartners.com, Phone: 703.707.0293 U.S. DOE Industrial Distributed Energy Portfolio Review Meeting Washington, D.C.

More information

AbSTRACT INTRODUCTION background

AbSTRACT INTRODUCTION background february 20, 2007 GREEN GRID METRICS: Describing Datacenter Power Efficiency Technical Committee White Paper white paper 1 Abstract The Green Grid is an association of IT professionals seeking to dramatically

More information

DISTRICT HEATING & COOLING INTEGRATION OF CHP. BURNS & MCDONNELL October 2014

DISTRICT HEATING & COOLING INTEGRATION OF CHP. BURNS & MCDONNELL October 2014 DISTRICT HEATING & COOLING INTEGRATION OF CHP BURNS & MCDONNELL October 2014 INTRODUCTION: SCOTT CLARK TIM BURKHALTER PROJECT DEVELOPMENT REPRESENTATIVE PROJECTS CANADA PROJECTS Chevron Refueler Inspection

More information

Data Center Technology: Physical Infrastructure

Data Center Technology: Physical Infrastructure Data Center Technology: Physical Infrastructure IT Trends Affecting New Technologies and Energy Efficiency Imperatives in the Data Center Hisham Elzahhar Regional Enterprise & System Manager, Schneider

More information

Metrics for Data Centre Efficiency

Metrics for Data Centre Efficiency Technology Paper 004 Metrics for Data Centre Efficiency Workspace Technology Limited Technology House, PO BOX 11578, Sutton Coldfield West Midlands B72 1ZB Telephone: 0121 354 4894 Facsimile: 0121 354

More information

California Air Resources Board s Distributed Generation Program

California Air Resources Board s Distributed Generation Program California Air Resources Board s Distributed Generation Program 6 th Annual Microturbine Applications Workshop January 17, 2006 Air Resources Board California Environmental Protection Agency Overview California

More information

Five Nines and Infrared (IR) Testing at Data Centers

Five Nines and Infrared (IR) Testing at Data Centers Five Nines and Infrared (IR) Testing at Data Centers By Gregory R. Stockton 99.999% uptime five nines. That is what IT (information technology) customers are looking for. Uptime or availability at data

More information

Combined Heat Power Supported Microgrids: Essential for the Evolution of Distributed Generation

Combined Heat Power Supported Microgrids: Essential for the Evolution of Distributed Generation Combined Heat Power Supported Microgrids: Essential for the Evolution of Distributed Generation October 16, 2012 Joe Sullivan, VP, Energy Policy & Development Concord Engineering District Energy CCHP Historic

More information

Electrical Systems. <Presenter>

Electrical Systems. <Presenter> Review Root Causes of Energy Inefficiency Roadmap to Maximize Energy Efficiency Best Practices Alternative Energy Sources Controls Take Aways Seek Professional Help. ENERGY INEFFICIENCY OF

More information

CarbonDecisions. The green data centre. Why becoming a green data centre makes good business sense

CarbonDecisions. The green data centre. Why becoming a green data centre makes good business sense CarbonDecisions The green data centre Why becoming a green data centre makes good business sense Contents What is a green data centre? Why being a green data centre makes good business sense 5 steps to

More information

Uptime Institute Network Top 10 Data Center Technology Priorities for 2013. Vice President, Global Director

Uptime Institute Network Top 10 Data Center Technology Priorities for 2013. Vice President, Global Director Uptime Institute Network Top 10 Data Center Technology Priorities for 2013 Anton Hios Vice President, Global Director Uptime Institute Network Tony Ulichnie Vice President Uptime Institute Network About

More information

Enabling an agile Data Centre in a (Fr)agile market

Enabling an agile Data Centre in a (Fr)agile market Enabling an agile Data Centre in a (Fr)agile market Phil Dodsworth Director, Data Centre Solutions 2008 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without

More information

David Mezzacappa, P.E. SCS Engineers Contractor to U.S. EPA on LMOP

David Mezzacappa, P.E. SCS Engineers Contractor to U.S. EPA on LMOP LMOP Workshop: LFG Collection & LFG Energy Technologies David Mezzacappa, P.E. SCS Engineers Contractor to U.S. EPA on LMOP Introduction Goal convert LFG into a useful energy form Technologies include:

More information

Introducing UNSW s R1 Data Centre

Introducing UNSW s R1 Data Centre Introducing UNSW s R1 Data Centre R1-DC Our New High Density Data Centre Right here Right now - Welcome to our newest UNSW Data Centre R1-DC R1 Location on UNSW Randwick campus. Keeping it in the family

More information

Columbia University Master Planning & Optimization

Columbia University Master Planning & Optimization Columbia University Master Planning & Optimization February 20, 2014 Mr. Frank Martino Vice President, Operations 1 Agenda Columbia University Campus District Energy Overview Evolution of Columbia s District

More information

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America 7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer

More information

Enabling Tier III Certifications Worldwide

Enabling Tier III Certifications Worldwide Enabling Tier III Certifications Worldwide BendBroadband Vault The Vitals» Located in Bend, OR» 30,000 sq ft carbon neutral enterprise class data center» Colocation, disaster recovery, dedicated managed

More information

Gas Absorption Heat Pumps. Future proofing your heating and hot water

Gas Absorption Heat Pumps. Future proofing your heating and hot water Gas Absorption Heat Pumps Future proofing your heating and hot water Gas Absorption Heat Pumps 1 Contents Gas Absorption Heat Pumps (GAHPs) The heating solution What is a Gas Absorption Heat Pump? How

More information

Deep Dive Think Tank: Energy Costs and Strategies for Reduction

Deep Dive Think Tank: Energy Costs and Strategies for Reduction Deep Dive Think Tank: Energy Costs and Strategies for Reduction Andrew Donoghue European research manager, Datacenter Technologies 1 Discussion points Does energy cost really matter or does uptime still

More information

ENERGY STAR Data Center Infrastructure Rating Development Update. Web Conference November 12, 2009

ENERGY STAR Data Center Infrastructure Rating Development Update. Web Conference November 12, 2009 ENERGY STAR Data Center Infrastructure Rating Development Update Web Conference November 12, 2009 Web Conference Tips Background Noise Please mute your phone until you are ready to speak. Hold & Music

More information

Your partner of choice for integrated energy solutions

Your partner of choice for integrated energy solutions E.ON Connecting Energies Your partner of choice for integrated energy solutions Would you like to reduce your company s energy costs? Do you have ambitious environmental objectives? Are you concerned about

More information

IT@Intel. Thermal Storage System Provides Emergency Data Center Cooling

IT@Intel. Thermal Storage System Provides Emergency Data Center Cooling White Paper Intel Information Technology Computer Manufacturing Thermal Management Thermal Storage System Provides Emergency Data Center Cooling Intel IT implemented a low-cost thermal storage system that

More information

UTILITIES AND ENERGY MANAGEMENT

UTILITIES AND ENERGY MANAGEMENT UTILITIES AND ENERGY MANAGEMENT University of Texas at Austin increases investment in co-generation to achieve greater utility reliability and economy. ENVIRONMENTAL BENEFITS AND ENERGY SAVINGS Power plant

More information

Energy Efficient High-tech Buildings

Energy Efficient High-tech Buildings Energy Efficient High-tech Buildings Can anything be done to improve Data Center and Cleanroom energy efficiency? Bill Tschudi Lawrence Berkeley National Laboratory Wftschudi@lbl.gov Acknowledgements California

More information

Minimizing Energy-Related Costs In Data Centers and Network Operations Centers

Minimizing Energy-Related Costs In Data Centers and Network Operations Centers Minimizing Energy-Related Costs In Data Centers and Network Operations Centers Energy Management By Design by Barry J. Needle energy management by design: to minimize energy consumption and maximize energy

More information

GENERATOR RATINGS AND THE IMPLICATIONS FOR DATA CENTERS

GENERATOR RATINGS AND THE IMPLICATIONS FOR DATA CENTERS Systems POWER SYSTEMS TOPICS 109 GENERATOR RATINGS AND THE IMPLICATIONS FOR DATA CENTERS By Todd Matte Manager - Corporate Accounts Project Management Group KOHLER Systems Understanding how generator ratings

More information

Combined Heat and Power: Economic, Proven, Reliable, Clean

Combined Heat and Power: Economic, Proven, Reliable, Clean Combined Heat and Power: Economic, Proven, Reliable, Clean Tom Bourgeois US DOE Northeast Clean Energy Application Center May 2013 Environmental and Energy Study Institute CHP Benefits o Improved fuel

More information

Siemens turbine solutions for urban cogeneration

Siemens turbine solutions for urban cogeneration BRUSSELS GREENTECH Siemens turbine solutions for urban cogeneration Restricted Siemens AG 2013 All rights reserved. Agenda Introduction Company in short Gas turbines Steam turbines Urban cogeneration references

More information

Powering the world s energy infrastructure

Powering the world s energy infrastructure GE Energy Gas Engine Waukesha * gas engines Powering the world s energy infrastructure GE Energy s Waukesha* gas engines power the world s energy infrastructure Waukesha engines are hard at work powering

More information

ENERGY SERVICES ENVIRONMENTAL BENEFITS AND ENERGY SAVINGS

ENERGY SERVICES ENVIRONMENTAL BENEFITS AND ENERGY SAVINGS ENERGY SERVICES University of California Los Angeles reduces operating costs and air pollution with landfill gasfueled cogeneration and creative financing. ENVIRONMENTAL BENEFITS AND ENERGY SAVINGS Reduced

More information

Guideline for Water and Energy Considerations During Federal Data Center Consolidations

Guideline for Water and Energy Considerations During Federal Data Center Consolidations Guideline for Water and Energy Considerations During Federal Data Center Consolidations Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory

More information

National Grid s Energy Efficiency Programs

National Grid s Energy Efficiency Programs National Grid s Energy Efficiency Programs Place your chosen image here. The four corners must just cover the arrow tips. For covers, the three pictures should be the same size and in a straight line.

More information

Energy Efficiency and Availability Management in Consolidated Data Centers

Energy Efficiency and Availability Management in Consolidated Data Centers Energy Efficiency and Availability Management in Consolidated Data Centers Abstract The Federal Data Center Consolidation Initiative (FDCCI) was driven by the recognition that growth in the number of Federal

More information

Dallas/Fort Worth International Airport District Energy Plant Upgrades Project Making More with Less Sustainable Communities Conference Dallas, TX

Dallas/Fort Worth International Airport District Energy Plant Upgrades Project Making More with Less Sustainable Communities Conference Dallas, TX Dallas/Fort Worth International Airport District Energy Plant Upgrades Project Making More with Less Sustainable Communities Conference Dallas, TX March 10, 2009 Agenda DFW Capital Development Program

More information

Data Center Infrastructure & Managed Services Outline

Data Center Infrastructure & Managed Services Outline Data Center Infrastructure & Managed Services Outline The 360 Technology Center Solutions Data Center is located in Lombard, IL, USA. We are 20 minutes outside of downtown Chicago. The 360TCS staff consists

More information

CyberFortress Data Center at Innovation Park Infrastructure and Topology Guide. Innovation Park Charlotte. NC 28262. DRAFT V0.

CyberFortress Data Center at Innovation Park Infrastructure and Topology Guide. Innovation Park Charlotte. NC 28262. DRAFT V0. Innovation Park Charlotte. NC 28262 DRAFT V0.1 Page 2 CyberFortress Data Center at Innovation Park BECO South purchased Innovation Park in March 2010 and immediately launched a dramatic top-to-bottom $30M

More information

scalable data centre energy management solution

scalable data centre energy management solution scalable data centre energy management solution scalable data centre energy management solution EcoMeasure - Scalable Data Centre Energy Management & Efficiency Measurement Solution by Workspace Technology

More information

Overview of New Jersey Energy Resilience Bank. Prepared by Michael Hornsby Chief Project Development Officer

Overview of New Jersey Energy Resilience Bank. Prepared by Michael Hornsby Chief Project Development Officer Overview of New Jersey Energy Resilience Bank Prepared by Michael Hornsby Chief Project Development Officer Prepared for Mid-Atlantic Solar Energy Industries Association Annual Member Meeting February

More information

DATA CENTER ASSESSMENT SERVICES

DATA CENTER ASSESSMENT SERVICES DATA CENTER ASSESSMENT SERVICES ig2 Group Inc. is a Data Center Science Company which provides solutions that can help organizations automatically optimize their Data Center performance, from assets to

More information

Two-Phase Evaporative Precision Cooling Systems

Two-Phase Evaporative Precision Cooling Systems Two-Phase Evaporative Precision Cooling Systems For heat loads from 3 to 300kW Using non-conductive refrigerant fluid, our patented Next-generation, two-phase evaporative precision cooling systems enable

More information

Boilers and cogeneration/trigeneration. Abhi Sawant Business Development Manager Simons Green Energy

Boilers and cogeneration/trigeneration. Abhi Sawant Business Development Manager Simons Green Energy Boilers and cogeneration/trigeneration Abhi Sawant Business Development Manager Simons Green Energy HEATING - COOLING - SUSTAINABLE ENERGY ENERGY EFFICIENCY IN BOILERS, COGENERATION & TRIGENERATION Presented

More information

Overview of Baltimore Gas & Electric s Combined Heat & Power (CHP) Program. Bill Wolf Manager I&C Energy Efficiency Programs April 1, 2014

Overview of Baltimore Gas & Electric s Combined Heat & Power (CHP) Program. Bill Wolf Manager I&C Energy Efficiency Programs April 1, 2014 Overview of Baltimore Gas & Electric s Combined Heat & Power (CHP) Program Bill Wolf Manager I&C Energy Efficiency Programs April 1, 2014 Combined Heat & Power is Part of BGE s Smart Energy Savers Program

More information

BRUNS-PAK Presents MARK S. EVANKO, Principal

BRUNS-PAK Presents MARK S. EVANKO, Principal BRUNS-PAK Presents MARK S. EVANKO, Principal Data Centers of the Future and the Impact of High Density Computing on Facility Infrastructures - Trends, Air-Flow, Green/LEED, Cost, and Schedule Considerations

More information

Princeton University Microgrid

Princeton University Microgrid Princeton University Microgrid IDEA evolvingenergy Conference Toronto, Canada 28th 30th October 2014 Edward Ted Borer, PE etborer@princeton.edu Overview Campus Energy Demands Energy Plant Equipment Combined

More information

Understanding Power Usage Effectiveness (PUE) & Data Center Infrastructure Management (DCIM)

Understanding Power Usage Effectiveness (PUE) & Data Center Infrastructure Management (DCIM) Understanding Power Usage Effectiveness (PUE) & Data Center Infrastructure Management (DCIM) Salim Janbeh Physical Infrastructure Consultant uae-sj@panduit.com PANDUIT You Can t Manage What You Don t Measure:

More information

CRM Sample Questions

CRM Sample Questions CRM Sample Questions 1. What are the CO 2 emissions for a facility in Miami that uses 1,000,000 kwh/year? 2. What are the CO 2 e emissions for the facility in question 1? 3. You install a solar PV panel

More information

Managing Data Centre Heat Issues

Managing Data Centre Heat Issues Managing Data Centre Heat Issues Victor Banuelos Field Applications Engineer Chatsworth Products, Inc. 2010 Managing Data Centre Heat Issues Thermal trends in the data centre Hot Aisle / Cold Aisle design

More information

Tim Facius Baltimore Aircoil

Tim Facius Baltimore Aircoil Presented By: Tim Facius Baltimore Aircoil Slide No.: 1 CTI Mission Statement To advocate and promote the use of environmentally responsible Evaporative Heat Transfer Systems (EHTS) for the benefit of

More information

Chad Dozier Market Development Manager Electric Power Division. August 2013

Chad Dozier Market Development Manager Electric Power Division. August 2013 Understanding Generator Set Ratings Smart rating choices combined with the latest in onsite power generation systems can help match equipment to a specific application for optimal long-term performance

More information

EPA Report to Congress on Server and Data Center Energy Efficiency

EPA Report to Congress on Server and Data Center Energy Efficiency EPA Report to Congress on Server and Data Center Energy Efficiency Executive Summary The United States (U.S.) Environmental Protection Agency (EPA) developed this report in response to the request from

More information

BCA-IDA Green Mark for New Data Centres Version NDC/1.0

BCA-IDA Green Mark for New Data Centres Version NDC/1.0 BCA-IDA Green Mark for New Data Centres Version NDC/1.0 To achieve GREEN MARK Award Pre-requisite Requirement All relevant pre-requisite requirements for the specific Green Mark Rating are to be complied

More information

ALWAYS ON GLOBALSWITCH.COM

ALWAYS ON GLOBALSWITCH.COM ALWAYS ON GLOBALSWITCH.COM Data Centre Design Considerations Kelvin Fong Managing Director, Hong Kong ALWAYS ON GLOBALSWITCH.COM Agenda 1. Introduction to Global Switch 2. Customer Requirements 3. Development

More information

Eaton s backup power systems. Mother nature strikes when you re least expecting it. Let Eaton be the solution for your backup power needs.

Eaton s backup power systems. Mother nature strikes when you re least expecting it. Let Eaton be the solution for your backup power needs. Eaton s backup power systems Mother nature strikes when you re least expecting it. Let Eaton be the solution for your backup power needs. For over 100 years, Eaton has earned a global reputation as a leader

More information

Why Data Center Design and Innovation Matters

Why Data Center Design and Innovation Matters Why Data Center Design and Innovation Matters Michael Ponke Principal, DCE Practice Professional Services October 07, 2009 Agenda The Eco Challenge Data Center revolution Why Data Center Design and Innovation

More information

Combined Heat and Power (CHP) En Banc Hearing October 7, 2014, University of Pittsburgh

Combined Heat and Power (CHP) En Banc Hearing October 7, 2014, University of Pittsburgh Combined Heat and Power (CHP) En Banc Hearing October 7, 2014, University of Pittsburgh Thomas G. Bourgeois Deputy Director (914) 422 4013 tbourgeois@pace.edu CHP in the Northeast States CT, MA, NY recognize

More information

POD S in Data Centres. The Frame Group Pty Ltd

POD S in Data Centres. The Frame Group Pty Ltd Presented by: Greg Goode The Frame Group Pty Ltd DATA Centres? POD SOLUTIONS REFERRED TO AS: Cells Modular Rooms High Density Zones Portable Modular Data Centres (Containers) Multiple Interpretations Varied

More information

Designed for uptime. Defining data center availability via a tier classification system

Designed for uptime. Defining data center availability via a tier classification system Defining data center availability via a tier classification system MIETEK GLIKOWSKI All systems can fail this is a simple fact that every industry must deal with. The paramount concern for the data center

More information

Green Development of Infrastructure and Campus: Modern Practice and Approach in District Heating and Cooling System

Green Development of Infrastructure and Campus: Modern Practice and Approach in District Heating and Cooling System Green Development of Infrastructure and Campus: Modern Practice and Approach in District Heating and Cooling System Hongxi Yin, Ph.D. School of Civil Engineering January 22, 2009 Page 1 The Impacts of

More information

Big Buildings lead to big savings

Big Buildings lead to big savings GE Power & Water Distributed Power Big Buildings lead to big savings GE s combined heat and power solutions for commercial buildings and data centers can reduce your costs and emissions. Saving energy,

More information

Tour of new eircom Data Centre Blanchardstown by Dervan Engineering Consultants 11 th March 2015

Tour of new eircom Data Centre Blanchardstown by Dervan Engineering Consultants 11 th March 2015 Tour of new eircom Data Centre Blanchardstown by Dervan Engineering Consultants 11 th March 2015 Presentation Outline Mechanical Overview Chillers and Pumps Pipework and Ancillaries In Row Cooling Units

More information

NO-BREAK KS 7e. Concentrated Energy. 2750 kva (50Hz) 3000 kva (60Hz) DIESEL ROTARY UNINTERRUPTIBLE POWER SUPPLY SYSTEM

NO-BREAK KS 7e. Concentrated Energy. 2750 kva (50Hz) 3000 kva (60Hz) DIESEL ROTARY UNINTERRUPTIBLE POWER SUPPLY SYSTEM NO-BREAK KS 7e Concentrated Energy e 2750 kva (50Hz) 3000 kva (60Hz) DIESEL ROTARY UNINTERRUPTIBLE POWER SUPPLY SYSTEM Data Centre owners, operators and designers are required to meet ever increasing and

More information

Data Centres A complete solution to noise control and acoustic packages

Data Centres A complete solution to noise control and acoustic packages Data Centres A complete solution to noise control and acoustic packages Introduction World class noise control. Expertise you can trust. IAC Acoustics is world-renowned for providing cost effective solutions

More information

PHOENIX ENERGY of NEVADA, LLC (PENV) (PENV)

PHOENIX ENERGY of NEVADA, LLC (PENV) (PENV) PHOENIX ENERGY of NEVADA, LLC (PENV) INDUCTION FIELD ENERGY POWERED INDUCED FEED WATER RE-HEAT ING STEAM WASTE HEAT ENERGY RECOVERY DRY COOLING REVERSE CONDENSER REGENERATIVE STEAM CYCLE ELECTRIC POWER

More information

CHICAGO S PREMIERE DATA CENTER

CHICAGO S PREMIERE DATA CENTER CHICAGO S PREMIERE DATA CENTER White City collocation was founded in June, 2010 by a highly experienced industry executive in conjunction with several investment companies. The strategy of White City is

More information

Strategic Data Centre Site Profiles. Data Centre Co-Location London East

Strategic Data Centre Site Profiles. Data Centre Co-Location London East Strategic Data Centre Site Profiles Data Centre Co-Location London East Document details Version: 1 Last Updated: 12/07/2013 Version 1.0 Page 1 of 5 Contents 1. LONDON EAST...3 1.1 LOCATION...3 1.2 TECHNICAL

More information

Green Data Centers. Jay Taylor Director Global Standards, Codes and Environment (512) 818-2073

Green Data Centers. Jay Taylor Director Global Standards, Codes and Environment (512) 818-2073 Green Data Centers Jay Taylor Director Global Standards, Codes and Environment (512) 818-2073 The energy dilemma: With Me, Without Me The facts The need Energy demand By 2050 Electricity by 2030 Source:

More information

Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect

Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect of Record: SPARCH Project Overview The project is

More information

This presentation is posted for public use. ACEEE does not endorse any product or service.

This presentation is posted for public use. ACEEE does not endorse any product or service. This presentation is posted for public use. ACEEE does not endorse any product or service. ACEEE accepts no responsibility for any facts or claims this presentation may contain. SOLAR Solar Water Heating

More information

Western Forest Economists 43 rd Annual Meeting May, 7, 2008

Western Forest Economists 43 rd Annual Meeting May, 7, 2008 Western Forest Economists 43 rd Annual Meeting May, 7, 2008 Biomass Energy Economics Presented by John R. Martin, P.E. Pacific Energy Systems, Inc. 15160 NW Laidlaw Road Portland, Oregon 503-227-7611 JohnM@PacificEnergySystems.com

More information

Datacentre Reading East 2 Data sheet

Datacentre Reading East 2 Data sheet Datacentre Reading East 2 Data sheet Data sheet Datacentre Reading East 2 Find us With 10 datacentres, over 4,500 racks and a 10Gb resilient core network between our datacentre locations, Pulsant has the

More information

COMMODITIZING THE DATA CENTER MARKET

COMMODITIZING THE DATA CENTER MARKET COMMODITIZING THE DATA CENTER MARKET Site Summary The building at 1360 Kifer Road has approximately 94,500 SF of server and support space and is currently divided into two independent data center areas.

More information