ARC-FLASH PROTECTIVE CLOTHING FOR NFPA 70E

Size: px
Start display at page:

Download "ARC-FLASH PROTECTIVE CLOTHING FOR NFPA 70E"

Transcription

1 ARC-FLASH PROTECTIVE CLOTHING FOR NFPA 70E

2

3 NFPA 70E is the national consensus standard for electrical safety in the workplace. The scope of this standard is to address safety-related work practices for the practical safeguarding of employees relative to the hazards associated with working around electrical energy. It specifically covers those electrical work practices performed by electricians and maintenance workers within a facility. Nearly all industries fall under the practices outlined in NFPA 70E. Manufacturing industries using high-voltage electrical equipment, such as aerospace, automotive, food processing, pulp and paper, industrial equipment, electronics, pharmaceuticals, and many others, are all covered by NFPA 70E. However, NFPA 70E does not cover electrical work performed outside of the facility that is under the exclusive control of an electric utility. This industry is covered by the National Electrical Safety Code (NESC). Many state OSHA agencies use NFPA 70E as their guideline for evaluating the protection of electrical workers. Those companies not protecting their employees from electric arc-flash hazards as described by this standard are at risk for potential fines should a safety inspection take place or an accident occur. So compliance with NFPA 70E not only protects workers but reduces the risk of OSHA fines. This informational guide will give you a brief overview of the NFPA 70E sections related to arc-flash protective clothing and other personal protective equipment (PPE). Arc-Flash Protective Clothing FOR NFPA 70E 1

4 NFPA 70E Article 130 Work Involving Electrical Hazards This is the section within NFPA 70E that addresses the conditions under which PPE is required and the type and level of protection needed for various work conditions. It starts by stating, Energized electrical conductors and circuit parts shall be put into an electrically safe work condition before an employee performs work With that said, the standard goes on to state that energized work shall be permitted where the employer can demonstrate that de-energizing introduces additional hazards or increased risk. It also states that energized work shall be permitted where the employer can demonstrate that the task to be performed is infeasible in a de-energized state due to equipment design or operational limitations. PLUS: Equipment operating at less than 50 volts is not required to be de-energized. Section Arc-Flash Risk Assessment A critical piece of the hazard assessment is performing an arc-flash hazard analysis. This analysis is required in order to establish the arc-flash boundary, the incident energy at the working distance and the PPE that people within the arc-flash boundary shall use. This section allows for the selection of the protective clothing and other PPE to be established by either performing an incident energy analysis or by using the PPE tables established in the standard. You can determine the PPE category by comparing the desired job with common tasks found in NFPA 70E table (C)(15) (A) (b). Once the task has been identified on the table, one of five PPE category numbers will be identified as appropriate for that task. Each of these categories requires garments with the minimum associated arc rating and other PPE to be worn. Hazard Assessment In order to determine the proper type and protection level of PPE, a hazard assessment must be performed. In addition, federal OSHA requires employers to conduct hazard assessments in accordance with 29 CFR (d). If an arc-flash hazard is present, OSHA deems the employer to be in compliance if NFPA 70E is the basis of determining the arc-flash protection boundary and the necessary PPE. Fig. 1 ARC FLASH BOUNDARY = The distance at which the incident energy equals 1.2 cal/cm². This is the energy level that will generate a second-degree burn on exposed skin. Energized Component Flash Boundary Within the flash boundary, a person could receive at least a second-degree burn from an arc flash. 2 Workrite Uniform Company, Inc.

5 70E Arc-Flash Hazard PPE Categories for Alternating Current (ac) Systems Table (C)(15)(A)(b) Equipment PPE Category Arc-Flash Boundary Panelboards or other equipment rated 240V or below. Maximum of 25kA short-circuit current available; maximum of 0.03 sec (two cycles) fault clearing time; working distance 455 mm (18 in.) mm (19 in.) Panelboards or other equipment rated > 240V and up to 600V. Parameters: Maximum of 25kA short-circuit current available; maximum of 0.03 sec (two cycles) fault clearing time; working distance of 455 mm (18 in.) mm (3 ft.) Other 600 V class (277 V through 600 V, nominal) equipment. Parameters: Maximum of 65 ka short-circuit current available; maximum of 0.03 sec (two cycle) fault clearing time; minimum 18 in. working distance m (5 ft.) Metal-clad switchgear, 1kV through 15 kv. Parameters: Maximum if 35 kv shirt-circuit current available; maximum of up to 0.24 sec (15 cycles) fault clearing time; working distance 910 mm (36 in.). 4 12m (40 ft.) Once the HRC number has been identified from the task table, the PPE table (C)(16) (see page 4) shall be used to determine the requirements for the specific protective clothing and other PPE based on that HRC number. HRC 1 and 2 are typically standard work clothes that have been arc rated from between a minimum of 4 cal/cm² for HRC 1, and a minimum of 8 cal/cm² for HRC 2. When the incident energy potential reaches 25 cal/cm², HRC 3 is required; at 40 cal/cm² and greater, HRC 4 garments are required. Arc-Flash Protective Clothing FOR NFPA 70E 3

6 70E Hazard/Risk Category Classification Table (Cont.) Table (C)(16) PPE Category Clothing & PPE Description Minimum Arc Rating 1 Arc-Rated Clothing: Arc-rated long-sleeve shirt and pants or arc-rated coverall, arc-rated face shield or arc-flash suit hood, arc-rated jacket, parka, rainwear or hard hat liner as needed Protective Equipment: Hard hat, safety glasses or goggles, hearing protection, leather gloves, leather footwear 4 cal/cm² 2 Arc-Rated Clothing: Arc-rated long-sleeve shirt and pants or arc-rated coverall, arcrated face shield and arc-rated balaclava or arc-flash suit hood, arc-rated jacket, parka, rainwear or hard hat liner as needed Protective Equipment: Hard hat, safety glasses or goggles, hearing protection, leather gloves, leather footwear 8 cal/cm² 3 Arc-Rated Clothing: Arc-rated long-sleeve shirt, arc-rated pants, arc-rated coverall, arc-rated flash suit jacket, arc-rated flash suit pants, arc-rated flash suit hood, arc-rated gloves, arc-rated jacket, parka, rainwear or hard hat liner as needed Protective Equipment: Hard hat, safety glasses or goggles, hearing protection, leather gloves, leather footwear 25 cal/cm² 4 Arc-Rated Clothing: Arc-rated long-sleeve shirt, arc-rated pants, arc-rated coverall, arc-rated flash suit jacket, arc-rated flash suit pants, arc-rated flash suit hood, arc-rated gloves, arc-rated jacket, parka, rainwear or hard hat liner as needed Protective Equipment: Hard hat, safety glasses or goggles, hearing protection, leather gloves, leather footwear 40 cal/cm² 4 Workrite Uniform Company, Inc.

7 Section Personal and Other Protective Equipment This is the section that provides specific requirements for those employees working in areas where electrical hazards are present. Those employees are required to be provided with and use protective equipment designed for the specific part of the body to be protected at the incident energy level, as established in the arc hazard analysis or as specified in the HRC tables. The specific parts of the body required to be protected include: Head, Face, Neck and Chin (Head Area) Protection Non-conductive head protection whenever there is a danger from shock, contact burns or flying objects from electrical explosions. The face, neck and chin shall be protected from exposure to electric arcs or flashes and flying objects. If hairnets or beardnets are used, they must be arc-rated. Eye Protection Eye protection when there is a danger from electric arcs, flashes or flying objects. Hearing Protection Hearing protection whenever working within the arc-flash boundary. Body Protection Arc-rated clothing whenever there is a possibility of exposure to an electric arc flash above an incident energy level of 1.2 cal/cm². Hand and Arm Protection Hand and arm protection as appropriate for either shock and/or arc flash as detailed in other sections. Factors in Selection The specific factors in the selection of protective clothing are stated as: If arc-rated clothing is required, it shall cover associated parts of the body as well as all flammable apparel. It goes on to state that garments that are not arc-rated shall not be permitted to be used to increase the arc rating of a garment or of a clothing system. Layering, Coverage and Fit General non-melting, flammable fiber garments are permitted to be used as under layers in conjunction with arc-rated garments for added protection. The arc rating of the system must be sufficient to prevent break-open of the innermost arc-rated layer. Outer Layers The outermost layer, such as jackets or rainwear, must be made of arc-rated material. Under Layers Meltable fibers such as acetate, nylon, polyester, polypropylene and spandex are not permitted in fabric under layers (underwear) next to the skin. Coverage Clothing must cover potentially exposed areas as completely as possible. Shirts and coverall sleeves shall be fastened at the wrist, shirts shall be tucked into pants, and shirts, coveralls and jackets should be closed at the neck. Fit Tight-fitting clothing should be avoided. Loose-fitting clothing provides additional insulation because of air spaces. Interference The garment should have the least interference with the task but still provide the necessary protection. Arc-Flash Protective Clothing FOR NFPA 70E 5

8 Simplified Choices with Two Clothing Sets Though different clothing is specified for each arc-rating minimum, many companies simplify their needs by choosing just two sets of clothing for their people to handle all electrical tasks: (a) A garment set with an arc rating of at least 8 cal/cm² for the more routine tasks of PFE category 1 and 2 (b) A garment set with an arc rating of at least 40 cal/cm² for more specialized tasks of PFE category 3 and 4 Standards on Protective Equipment Table 130.7(C)(14) lists the various performance standards, to which the protective clothing and PPE needs to conform. PPE Type Document Number Document Title Apparel Arc-Rated ASTM F1506 Standard Performance for Flame-Resistant and Arc-Rated Textile Materials for Wearing Apparel for Use by Electrical Workers Exposed to Momentary Electric Arc and Related Thermal Hazards Eye and Face General ANSI/ASSE Z87.1 Practice for Occupational and Educational Eye and Face Protection Face Arc-Rated Gloves Leather Protectors ASTM F2178 ASTM F696 Standard Test Method for Determining the Arc Rating and Standard Specification for Face Protective Products Standard Specification for Leather Protectors for Rubber Insulating Gloves and Mittens Gloves Rubber Insulating ASTM D120 Standard Specification for Rubber Insulating Gloves Head Protection Hard Hat ANSI/ISEA Z89.1 Personal Protection Protective Headwear for Industrial Workers Rainwear Arc-Rated ASTM F1891 Standard Specification for Arc- and Flame-Resistant Rainwear 6 Workrite Uniform Company, Inc.

9 So What Role Can Arc-Rated Clothing Play? Arc-rated clothing: Does not ignite or continue to burn Provides a protective barrier against the arc flash Insulates the wearer from heat Why is this important? Most severe burns are caused by ignited clothing rather than by the original hazard Clothed areas can be burned more severely than skin that is exposed directly to the arc flash, because the initial exposure is of a short duration while the burning clothing continues to apply heat to the skin until it either goes out or is removed The long-term cost of a single burn injury can exceed the cost of an entire FR clothing program Rehabilitation for burn injuries can be extremely long and painful Arc-rated clothing is worn as insurance. In the unlikely event of an arc flash, these garments: Minimize or reduce burn injury Increase chances of survival Surviving a Burn Injury 100 Burn Survival Rate % Survival % Body Burn 50% Body Burn 75% Body Burn Age Groups Summary Each year, more than 2,000 employees are admitted to burn centers with severe burns resulting from arc-flash accidents. Manufacturing facility workers within the arc-flash boundary are at risk of being exposed to an arc-flash event while performing common electrical work on energized parts or equipment. Because of that, being in compliance with the NFPA 70E safety standard not only protects those workers but reduces the risk of fines to the company should an accident occur. Arc-Flash Protective Clothing FOR NFPA 70E 7

10 Our mission is to protect today s workers by delivering trusted, innovative and market-leading, flame-resistant branded apparel solutions. An Affiliate of Williamson-Dickie Manufacturing Company 1701 North Lombard Street, Suite 200 Oxnard, California / Fax Monday Friday / 6 a.m. 4 p.m. PST workrite.com Workrite Uniform Company

2012 NFPA 70E. Ten Most Important Changes. John A. DeDad

2012 NFPA 70E. Ten Most Important Changes. John A. DeDad 2012 NFPA 70E Ten Most Important Changes John A. DeDad GE Energy Management 41 Woodford Avenue Plainville, CT 06062 USA 860-747-7344 John.dedad@ge.com Abstract The 2012 Edition of NFPA 70E, Standard for

More information

BRANDON AND CLARK INC. // SCOTT W. CLARK, P.E. ELECTRICAL CONTINUING EDUCATION ARC FLASH - NFPA 70E

BRANDON AND CLARK INC. // SCOTT W. CLARK, P.E. ELECTRICAL CONTINUING EDUCATION ARC FLASH - NFPA 70E BRANDON AND CLARK INC. // SCOTT W. CLARK, P.E. ELECTRICAL CONTINUING EDUCATION ARC FLASH - NFPA 70E Training is not a substitute for following corporate safety guidelines. Always refer to the latest safety

More information

NFPA 70E Updates Affect Your Most Valuable Assets

NFPA 70E Updates Affect Your Most Valuable Assets NFPA 70E Updates Affect Your Most Valuable Assets EXECUTIVE SUMMARY Electrocution is a well-known hazard associated with direct contact with electrical energy. According to the U.S. Department of Labor,

More information

Arc Flash Avoidance and its Application to Overhead Traveling Cranes

Arc Flash Avoidance and its Application to Overhead Traveling Cranes Arc Flash Avoidance and its Application to Overhead Traveling Cranes Whitepaper August 2012 Jason Wellnitz, Controls Product Manager Material Handling Numerous technical papers, bulletins, magazine articles

More information

SAFE ELECTRICAL WORK PRACTICES & 2015 NFPA 70E

SAFE ELECTRICAL WORK PRACTICES & 2015 NFPA 70E SAFE ELECTRICAL WORK PRACTICES & 2015 NFPA 70E This easy-to-use Leader s Guide is provided to assist in conducting a successful presentation. Featured are: INTRODUCTION: A brief description of the program

More information

The Other Hazard of Electricity. Larren Elliott Ph.D. Lindsay Polic, CSP, REHS

The Other Hazard of Electricity. Larren Elliott Ph.D. Lindsay Polic, CSP, REHS The Other Hazard of Electricity Larren Elliott Ph.D. Lindsay Polic, CSP, REHS Presenters Larren Elliott Ph.D. EORM Electrical Safety Service Partner 45 years practical and hands-on industrial experience

More information

ARC Flash Boundary & NFPA-70E Requirements PPE Program

ARC Flash Boundary & NFPA-70E Requirements PPE Program ARC Flash Boundary & NFPA-70E Requirements PPE Program 1. Purpose and Scope The Arc Flash Boundary - PPE Program was developed to minimize the risk to AMS employees from safety and health hazards in the

More information

IMPLEMENTING THE NEW ELECTRICAL SAFETY REQUIREMENTS

IMPLEMENTING THE NEW ELECTRICAL SAFETY REQUIREMENTS IMPLEMENTING THE NEW ELECTRICAL SAFETY REQUIREMENTS Paul A Zoubek, CSP, CIH Occupational Services, Inc. San Diego, CA 619-861 861-0612 paul@occsev.com OCCUPATIONAL SERVICES, INC. BACKGROUND Update Update

More information

Understanding Arc Flash

Understanding Arc Flash Understanding Arc Flash Presented by Eddie F. Jones, PE 1 2 3 4 5 Five to 10 arc flash explosions occur in electric equipment every day in the United States. This number does not include cases in which

More information

Campus Safety Procedure Electrical Safety

Campus Safety Procedure Electrical Safety Campus Safety Procedure Electrical Safety Electrical Safety Procedures 1.0 Purpose The purpose of this procedure is to provide guidance in the performance of work on electrical systems, wiring, and equipment

More information

Hampshire College. Lockout/Tagout and Electrical Safety Program and Procedures

Hampshire College. Lockout/Tagout and Electrical Safety Program and Procedures Hampshire College Lockout/Tagout and Electrical Safety Program and Procedures January 2007 In Compliance with the OSHA 29 CFR 1910.147 and 29 CFR 1910.331 through.335 And NFPA 70E Environmental Health

More information

Arc Flash Hazards. Electrical Hazards. Dan Neeser Field Application Engineer DanRNeeser@Eaton.com. Electrical Hazards 2/18/2015. Shock.

Arc Flash Hazards. Electrical Hazards. Dan Neeser Field Application Engineer DanRNeeser@Eaton.com. Electrical Hazards 2/18/2015. Shock. Arc Flash Hazards Dan Neeser Field Application Engineer DanRNeeser@Eaton.com Electrical Hazards Electrical Hazards Shock Arc Flash Arc Blast 2 1 Arcing Fault Basics 35,000 F Radiant Heat & UV Speed of

More information

Electrical Safety Program

Electrical Safety Program CALIFORNIA STATE UNIVERSITY, STANISLAUS Electrical Safety Program LAST UPDATED 6/2/11 CALIFORNIA STATE UNIVERSITY, STANISLAUS ELECTRICAL SAFETY PROGRAM TABLE OF CONTENTS 1.0 Purpose......2 2.0 Scope......2

More information

What s up with Arc Flash?

What s up with Arc Flash? What s up with Arc Flash? Presented by Mark Haskins, CSP Practical Safety Solutions, LLC CONN OSHA Breakfast Roundtable February 18, 2014 2014 Practical Safety Solutions, LLC What is Arc Flash? Definition

More information

Introduction to Arc Flash

Introduction to Arc Flash Introduction to Arc Flash Worker Training of Electrical Hazards Including Arc Flash SH-16614-7 This material was produced under grant number SH-16614-7 from the Occupational Safety and Health Administration,

More information

INTRODUCTION ARC FLASH PROTECTION AND SAFETY MEASURES. September 2010

INTRODUCTION ARC FLASH PROTECTION AND SAFETY MEASURES. September 2010 ARC FLASH PROTECTION AND SAFETY MEASURES September 2010 Introduction Hazards of Electrical Energy Electrical Safety Program Safety-Related Work Practices Electrical Safety Procedures Presented By: Ken

More information

PROCEDURES FOR SAFE WORKING AND TESTING OF ENERGIZED ELECTRICAL EQUIPMENT

PROCEDURES FOR SAFE WORKING AND TESTING OF ENERGIZED ELECTRICAL EQUIPMENT Human Resources Support Services Health, Wellness and Safety PROCEDURES FOR SAFE WORKING AND TESTING OF ENERGIZED ELECTRICAL EQUIPMENT 1 SCOPE The electrical safety procedure shall be part of the Peel

More information

ARC FLASH CALCULATIONS & LABELING REQUIREMENTS

ARC FLASH CALCULATIONS & LABELING REQUIREMENTS ARC FLASH CALCULATIONS & LABELING REQUIREMENTS Presented by: Edmund Elizalde EYP Mission Critical Facilities, Inc. Slides by: Lonnie Lindell SKM Systems Analysis, Inc. 1 Agenda NEC 110.16 NFPA 70E IEEE

More information

Electrical Safety Program

Electrical Safety Program California State University-Fullerton 800 N. State College Blvd. Fullerton, CA 92831 Prepared by: Paul A Zoubek, CSP, CIH President/Principal Consultant Zoubek Consulting, LLC 3737 Granada Ave. San Diego,

More information

Myths and Facts on Complying with NFPA 70E's Clothing Requirements By Hugh Hoagland

Myths and Facts on Complying with NFPA 70E's Clothing Requirements By Hugh Hoagland Myths and Facts on Complying with NFPA 70E's Clothing Requirements By Hugh Hoagland Stop. Don't switch garments for electric arc protection before you read this article. Companies are now claiming to have

More information

SALISBURY ASSESSMENT SOLUTIONS

SALISBURY ASSESSMENT SOLUTIONS SALISBURY ASSESSMENT SOLUTIONS Electrical engineering services for a safe and compliant workplace Electrical Safety Program Assessments - Electrical Safety Training Arc Flash Risk Assessments - Power Systems

More information

Written Program ELECTRICAL SAFETY. Based on OSHA Subpart S and NFPA 70E Standards

Written Program ELECTRICAL SAFETY. Based on OSHA Subpart S and NFPA 70E Standards Written Program ELECTRICAL SAFETY Based on OSHA Subpart S and NFPA 70E Standards Revised November 2012 Disclaimer The presentations and program provided by Workplace Safety Solutions, Inc. are based on

More information

Midwest Healthcare Engineering Conference and Trade Show 2012 Indianapolis, Indiana

Midwest Healthcare Engineering Conference and Trade Show 2012 Indianapolis, Indiana Midwest Healthcare Engineering Conference and Trade Show 2012 Indianapolis, Indiana Arc Flash Overview An engineering solutions company November 7, 2012 Agenda Introductions Arc Flash defined History and

More information

2013WWOA Conference Technical Conference Program

2013WWOA Conference Technical Conference Program 2013WWOA Conference Technical Conference Program Understanding Arc-Flash Hazards, Its Implications on Operations and Solutions that Mitigate Such Exposure Presented by Jerry Baskin Senior Product Manager

More information

Analyzing Electrical Hazards in the Workplace

Analyzing Electrical Hazards in the Workplace Analyzing Electrical Hazards in the Workplace By Dennis K. Neitzel, CPE AVO Training Institute, Inc. The need for analyzing electrical hazards in the workplace has been recognized by a small segment of

More information

UNIVERSITY OF CENTRAL FLORIDA ELECTRICAL SAFETY PROGRAM

UNIVERSITY OF CENTRAL FLORIDA ELECTRICAL SAFETY PROGRAM UNIVERSITY OF CENTRAL FLORIDA ELECTRICAL SAFETY PROGRAM December 2011 Table of Contents UNIVERSITY OF CENTRAL FLORIDA... 0 Table of Contents... 1 INTRODUCTION... 2 PURPOSE... 2 SCOPE... 3 RESPONSIBILITIES...

More information

OSHA & ARC FLASH HAZARD ANALYSIS

OSHA & ARC FLASH HAZARD ANALYSIS OSHA & ARC FLASH HAZARD ANALYSIS Impact of Revisions to the OSHA Electrical Safety Regulations Presented by: John J. Kolak, MS, CSP Introduction Important Definitions Understanding OSHA Applicable standards

More information

ELECTRICAL SAFETY PROGRAM

ELECTRICAL SAFETY PROGRAM ELECTRICAL SAFETY PROGRAM Adopted January 2014 Table of Contents Chapter 1: Introduction... 1 1.1 Purpose... 1 1.2 Scope... 1 1.3 Definitions... 1 1.4 Responsibilities... 8 1.5 Basic Electrical Safety

More information

ELECTRICAL & ARC FLASH SAFETY PROGRAM

ELECTRICAL & ARC FLASH SAFETY PROGRAM ELECTRICAL & ARC FLASH SAFETY PROGRAM ADOPTED VERSIO 2, SEPTEMBER 26, 2012 Supercedes all prior versions A. COMMITTEE OVERSIGHT OF PROGRAM The University of Montana ( University ) recognizes the importance

More information

ELECTRICAL SAFETY / ARC FLASH PROGRAM

ELECTRICAL SAFETY / ARC FLASH PROGRAM INTRODUCTION ELECTRICAL SAFETY / ARC FLASH PROGRAM This program establishes minimum standards to prevent hazardous electrical exposures to personnel and ensure compliance with regulatory requirements applicable

More information

NFPA 70E 2012 Rolls Out New Electrical Safety Requirements Affecting Data Centers

NFPA 70E 2012 Rolls Out New Electrical Safety Requirements Affecting Data Centers NFPA 70E 2012 Rolls Out New Electrical Safety Requirements Affecting Data Centers A market position paper from the experts in Business-Critical Continuity TM Executive Summary Electrocutions are the fourth

More information

Industrial Flash Fire and Burn Injury Fundamentals with an Instrumented Manikin Demonstration of Protective Clothing Performance

Industrial Flash Fire and Burn Injury Fundamentals with an Instrumented Manikin Demonstration of Protective Clothing Performance Abstract Industrial Flash Fire and Burn Injury Fundamentals with an Instrumented Manikin Demonstration of Protective Clothing Performance Susan L. Lovasic Thomas E. Neal, Ph.D. NFPA 2112 and 2113 are the

More information

Additional information: -OSHA Instruction CPL 2.103, Field Inspection Reference Manual, Chapter IV, Section A -29 CFR 1910, Subpart I, Appendix B

Additional information: -OSHA Instruction CPL 2.103, Field Inspection Reference Manual, Chapter IV, Section A -29 CFR 1910, Subpart I, Appendix B 1 Additional information: -OSHA Instruction CPL 2.103, Field Inspection Reference Manual, Chapter IV, Section A -29 CFR 1910, Subpart I, Appendix B -1910.1000(e) 2 1910.132(h) 72 FR 64341, Nov. 15, 2007

More information

Using Infrared Sightglasses to Protect Against Arc-Flash Exposure

Using Infrared Sightglasses to Protect Against Arc-Flash Exposure Using Infrared Sightglasses to Protect Against Arc-Flash Exposure Antony J. Holliday IEEE Member Hawk IR International, Ltd. 117 High Street, Marske-by-Sea Redcar, Cleveland TS116JX, United Kingdom Ph:

More information

FLAME RESISTANT (FR) NFPA 70E NESC OSHA 1910.269 ASTM F1506. CSA Z462 (Canada) Secondary Protection from Electric Flash fire hazards

FLAME RESISTANT (FR) NFPA 70E NESC OSHA 1910.269 ASTM F1506. CSA Z462 (Canada) Secondary Protection from Electric Flash fire hazards FLAME RESISTANT (FR) CLOTHING featuring: NFPA 70E NESC OSHA 1910.269 ASTM F1506 CSA Z462 (Canada) Secondary Protection from Electric Flash fire hazards NFPA 2112 (Select Styles) NION MADE IN THE USA 31

More information

Arc Flash Overview. Arc-Flash Hazard. Who is Eaton. Engineering Studies ABSTRACT. Eaton PSE s

Arc Flash Overview. Arc-Flash Hazard. Who is Eaton. Engineering Studies ABSTRACT. Eaton PSE s Arc-Flash Hazard Arc Flash Overview Tom Studer Eaton Electrical Power Systems Engineering Tempe, AZ Who is Eaton?: Company Overview Electrical Engineering Services What is Arc-Flash?: Definitions / Examples

More information

OSHA Published First-Ever Arc Flash Protection Requirements for the Electric Power Industry Significant changes and unprecedented compliance

OSHA Published First-Ever Arc Flash Protection Requirements for the Electric Power Industry Significant changes and unprecedented compliance OSHA Published First-Ever Arc Flash Protection Requirements for the Electric Power Industry Significant changes and unprecedented compliance deadlines require high-voltage facilities to take immediate

More information

ARC FLASH HAZARD OVERVIEW. Presented August 13, 2015 WWOA Lake Michigan District by Mead & Hunt, Inc.

ARC FLASH HAZARD OVERVIEW. Presented August 13, 2015 WWOA Lake Michigan District by Mead & Hunt, Inc. ARC FLASH HAZARD OVERVIEW Presented August 13, 2015 WWOA Lake Michigan District by Mead & Hunt, Inc. ARC FLASH EXPERIENCE Christopher J. DeWaal, MS, MEM, PE, LEED AP, HACCP How did I get involved? A client

More information

TAMPA ELECTRIC COMPANY ENERGY SUPPLY ELECTRICAL SAFETY PROGRAM

TAMPA ELECTRIC COMPANY ENERGY SUPPLY ELECTRICAL SAFETY PROGRAM TABLE OF CONTENTS TITLE PAGE # PURPOSE / INTRODUCTION 1 SCOPE 2 RESPONSIBILITY 3 EMPLOYEE TRAINING INCLUDING DOCUMENTATION 4 ELECTRICAL EQUIPMENT LABELING 5 APPROACH DISTANCES AND BOUNDARIES 5-8 GENERAL

More information

NESC Update. James R. Tomaseski International Brotherhood of Electrical Workers

NESC Update. James R. Tomaseski International Brotherhood of Electrical Workers NESC Update James R. Tomaseski International Brotherhood of Electrical Workers NATIONAL ELECTRICAL SAFETY CODE 2017 Change Proposal Activity PART 4 Work Rules for the Operation of Electric Supply and Communications

More information

Electrical Safety Program Version 0

Electrical Safety Program Version 0 Electrical Safety Program Version 0 This Electrical Safety Program is hereby approved by: Robert Andrews Facilities Director 9-3-12 Signature Title Date Donna Placzek Director, EHS 9-20-12 Signature Title

More information

The Performance of Voltage Rated Gloves in Arc Flash Exposures

The Performance of Voltage Rated Gloves in Arc Flash Exposures The Performance of Voltage Rated Gloves in Arc Flash Exposures Background. Ever since NFPA 70E -2000 was published many customers came to us with a question How will your gloves perform in arc flash? From

More information

Environmental Health & Safety Electrical Safety Program

Environmental Health & Safety Electrical Safety Program **Printed copies of this document are uncontrolled, visit the EHS website at http://www.wright.edu/admin/ehs/ for the latest revision** I. Purpose Ensure the safety of employees who may work on or near

More information

2008 Eaton Corporation. All rights reserved.

2008 Eaton Corporation. All rights reserved. FlashGard TM Motor Control Center Electrical Safety Hazards Design Philosophy The Product 2008 Eaton Corporation. All rights reserved. Research studies say. Five to 10 arc flash explosions occur in electrical

More information

misconceptions about arc-flash hazard assessments

misconceptions about arc-flash hazard assessments misconceptions about arc-flash hazard assessments There are some common misconceptions about Arc-Flash Hazard Assessments which reduce the effectiveness of the Assessments and can increase electrical hazards.

More information

PERSONAL PROTECTIVE EQUIPMENT (PPE)

PERSONAL PROTECTIVE EQUIPMENT (PPE) Page 1 of 6 (PPE) Personal protective equipment (PPE) is used to protect an individual from hazards associated with their work tasks or environment. Specific types of personal protective equipment include

More information

90.2(A) Covered & 90.2(B) Not Covered 6/23/2015. Learning Objectives. 90.2(A) Covered & 90.2(B) Not Covered. Change Summary

90.2(A) Covered & 90.2(B) Not Covered 6/23/2015. Learning Objectives. 90.2(A) Covered & 90.2(B) Not Covered. Change Summary Learning Objectives After reviewing this material, the student will be able to: 1. Identify the installations that fall under the scope of the 2015 edition of NFPA 70E. 2. Identify the assessments required

More information

UL Validated Testing of Arc-Resistant Motor Control Centers

UL Validated Testing of Arc-Resistant Motor Control Centers UL Validated Testing of Arc-Resistant Motor Control Centers Ensure Protective Features Perform as Designed Larry Sifers Account Manager Littleton, CO Siemens Industry June 1st - 3rd, 2011 Western Mining

More information

Roadmap to Compliance with NFPA 70E Arc Flash Requirements

Roadmap to Compliance with NFPA 70E Arc Flash Requirements Roadmap to Compliance with NFPA 70E Arc Flash Requirements TAHFM Interlink 2015 March 30, 2015 Antony Parsons, Ph.D., P.E. Schneider Electric Engineering Services 1 2 How do we get to Reliable Power? >

More information

Union County Public Schools. Facilities Department. Electrical. Safe Work Practices

Union County Public Schools. Facilities Department. Electrical. Safe Work Practices 1 Union County Public Schools Facilities Department Electrical Safe Work Practices 2 Purpose In accordance with OSHA Standards 1910.331-335, safety-related work practices shall be used by Union County

More information

GEORGIA INSTITUTE OF TECHNOLOGY ENVIRONMENTAL HEALTH AND SAFETY PERSONAL PROTECTIVE EQUIPMENT

GEORGIA INSTITUTE OF TECHNOLOGY ENVIRONMENTAL HEALTH AND SAFETY PERSONAL PROTECTIVE EQUIPMENT PURPOSE To protect the health and welfare of GEORGIA TECH employees in areas where there may be a risk of injury or exposure to hazardous substances or conditions employees who work in areas where physical

More information

Safety, Health, and Environmental Standard

Safety, Health, and Environmental Standard Department of the Air Force HQ AEDC (AFMC) Arnold AFB, TN 37389 Safety, Health, and Environmental Standard Title: Standard.: Low-Voltage Electrical Safety-Related Work Practices B6 Effective Date: 03/30/2015

More information

Part 1 System Modeling & Studies for Existing Systems

Part 1 System Modeling & Studies for Existing Systems Part 1 System Modeling & Studies for Existing Systems Operation Technology, Inc. Copyright 2009 Result of rapid release of energy due to an arcing fault between two conductors. Bus voltages > 208V Temperatures

More information

PERSONAL PROTECTIVE EQUIPMENT (PPE) a short guide for wildland firefighters

PERSONAL PROTECTIVE EQUIPMENT (PPE) a short guide for wildland firefighters PERSONAL PROTECTIVE EQUIPMENT (PPE) a short guide for wildland firefighters Fighting fire is not only physically demanding work, but can be physically punishing as well. Fighting fire without exposing

More information

100% Rule Alternate Method Arc Blast Arc Flash Approved Approved Equipment Authority Having Jurisdiction (AHJ) Authorized Work Bare Hand Work

100% Rule Alternate Method Arc Blast Arc Flash Approved Approved Equipment Authority Having Jurisdiction (AHJ) Authorized Work Bare Hand Work Definitions 100% Rule Work on or near energized parts must be performed only after all participating qualified electrical workers are in 100% agreement on the work to be completed, on the sequence in which

More information

Health, Safety, Environment and Community. Management System. Personal Protective Equipment PETROLEUM CSG HSEC MANAGEMENT SYSTEM PROCEDURE

Health, Safety, Environment and Community. Management System. Personal Protective Equipment PETROLEUM CSG HSEC MANAGEMENT SYSTEM PROCEDURE PETROLEUM CSG HSEC MANAGEMENT SYSTEM PROCEDURE PERSONAL PROTECTIVE EQUIPMENT Petroleum HSEC Procedure No: Date: June 14, 2012 Revision: 2.1 Owner: Kim Phillips, Occupational Health and Hygiene Manager

More information

Understanding 2015 Changes to NFPA 70E Safety-related work practices and maintenance requirements mandate more robust electrical safety programs for

Understanding 2015 Changes to NFPA 70E Safety-related work practices and maintenance requirements mandate more robust electrical safety programs for Understanding 2015 Changes to NFPA 70E Safety-related work practices and maintenance requirements mandate more robust electrical safety programs for data centers Executive Summary Every three years, the

More information

ARC FLASH CLOTHING - Spentex NG2 by Encon

ARC FLASH CLOTHING - Spentex NG2 by Encon - Spentex NG2 by Encon More Protection In heat and stress tests (NFPA 2112/ ASTM 1930), Spentex NG2 by Encon FR outperforms traditional FR fabrics. Higher Durability Setting the new standard in FR wear

More information

NFPA 70E SYNOPSIS ARC FLASH WHITE PAPER BY SYDUL HAQUE ELK ENGINEERING ASSOCIATES, INC.

NFPA 70E SYNOPSIS ARC FLASH WHITE PAPER BY SYDUL HAQUE ELK ENGINEERING ASSOCIATES, INC. A. Introduction NFPA 70E SYNOPSIS ARC FLASH WHITE PAPER BY SYDUL HAQUE ELK ENGINEERING ASSOCIATES, INC. NFPA 70E Standard for Electrical Safety in the Workplace, 2009 Edition further copies electrical

More information

Electrical Safety For General Industry

Electrical Safety For General Industry Train-the-Trainers Guide to Electrical Safety For General Industry A Review of Common OSHA Regulations and Workplace Violations 1 Table of Contents Common Electrical Hazards... 5 It s Your Life Protect

More information

Rubber Insulating Products, Safety Equipment & Dielectric Testing Services

Rubber Insulating Products, Safety Equipment & Dielectric Testing Services Rubber Insulating Products, Safety Equipment & Dielectric Testing Services For Electric Utilities, Contractors, Telecom, Cable Providers and General Industry VOLTGARD TEST LAB SAF-T-GARD INTERNATIONAL

More information

Arc Flash Mitigation. Remote Racking and Switching for Arc Flash danger mitigation in distribution class switchgear.

Arc Flash Mitigation. Remote Racking and Switching for Arc Flash danger mitigation in distribution class switchgear. Arc Flash Mitigation Remote Racking and Switching for Arc Flash danger mitigation in distribution class switchgear. Distance is Safety We will discuss through examples of actual occurrences and possible

More information

Understanding 2015 Changes to NFPA 70E Safety-related work practices and maintenance requirements mandate more robust electrical safety programs for

Understanding 2015 Changes to NFPA 70E Safety-related work practices and maintenance requirements mandate more robust electrical safety programs for Understanding 2015 Changes to NFPA 70E Safety-related work practices and maintenance requirements mandate more robust electrical safety programs for commercial and industrial facilities Executive Summary

More information

SALISBURY ASSESSMENT SOLUTIONS

SALISBURY ASSESSMENT SOLUTIONS SALISBURY ASSESSMENT SOLUTIONS Electrical engineering services for a safe and compliant workplace Electrical Safety Program Assessment - Safety Training Arc Flash Hazard Analysis - Power Systems Engineering

More information

Integrating SPDs in Switchgear & Switchboards Causes More Problems than it Solves

Integrating SPDs in Switchgear & Switchboards Causes More Problems than it Solves Integrating SPDs in Switchgear & Switchboards Causes More Problems than it Solves White Paper July 2010 Integrating surge protective devices (SPD) into distribution equipment (i.e. switchgear, switchboards,

More information

MAXIMUM USE VOLTAGE AC/DC 500 / 750 1,000 / 1,500 7,500 / 11,250 17,000 / 25,500 26,500 / 39,750 36,000 / 54,000

MAXIMUM USE VOLTAGE AC/DC 500 / 750 1,000 / 1,500 7,500 / 11,250 17,000 / 25,500 26,500 / 39,750 36,000 / 54,000 ELECTRICAL GLOVES ELECTRICAL GLOVES Encon offers a full line of Novax electrician's gloves. Novax rubber insulating gloves are offered in 6 different voltage classes and in different sizes and colors.

More information

Procedure Number 1022. Arc Flash Hazard Calculation and Required Protection Revision 5. TVA Safety Procedure Page 1 of 25. 1.

Procedure Number 1022. Arc Flash Hazard Calculation and Required Protection Revision 5. TVA Safety Procedure Page 1 of 25. 1. TVA Safety Procedure Page 1 of 25 Arc Flash Hazard Calculation and 1. Purpose April 30, 2007 1.1. This procedure defines TVA s method for calculating the electric arc flash incident energy at various distances,

More information

PLANT OPERATIONS ELECTRICAL SAFETY PROGRAM

PLANT OPERATIONS ELECTRICAL SAFETY PROGRAM PLANT OPERATIONS ELECTRICAL SAFETY PROGRAM Prepared by the Department of Occupational Safety & Environmental Health PLANT ELECTRICAL SAFETY PROGRAM TABLE OF CONTENTS Page I. Purpose and Scope 1 II. Definitions

More information

Job Site Electrical Safety A Matter of Life and Death

Job Site Electrical Safety A Matter of Life and Death Job Site Electrical Safety A Matter of Life and Death Scott Forsyth, PE Senior Engineer Johnson Controls Performing the Job Right and on Time is Top Priority!!!! Right? Wrong!!!! Performing the Job Safely

More information

RISK MITIGATION for ELECTRICAL WORK. Feb 2013 San Diego CA

RISK MITIGATION for ELECTRICAL WORK. Feb 2013 San Diego CA RISK MITIGATION for ELECTRICAL WORK Feb 2013 San Diego CA Agenda I. RISK Define the Risks Arc Flash Review II. MITIGATION 3 Easy Steps New Designs Vs. Existing Systems III. DUKE UNIVERSITY EXAMPLE I. Risk

More information

A USERS GUIDE TO ARC RESISTANT LOW VOLTAGE SWITCHGEAR & MOTOR CONTROL ANALYTICAL COMPARISON VS ARC FLASH TEST RESULTS

A USERS GUIDE TO ARC RESISTANT LOW VOLTAGE SWITCHGEAR & MOTOR CONTROL ANALYTICAL COMPARISON VS ARC FLASH TEST RESULTS A USERS GUIDE TO ARC RESISTANT LOW VOLTAGE SWITCHGEAR & MOTOR CONTROL ANALYTICAL COMPARISON VS ARC FLASH TEST RESULTS By: Gabriel Arce, ABB, San Luis Potosi, Mexico Casey McCollum, ABB, Houston, TX John

More information

Common Electrical Hazards in the Workplace Including Arc Flash. Presented by Ken Cohen, PhD, PE & CIH (Ret.)

Common Electrical Hazards in the Workplace Including Arc Flash. Presented by Ken Cohen, PhD, PE & CIH (Ret.) Common Electrical Hazards in the Workplace Including Arc Flash Presented by Ken Cohen, PhD, PE & CIH (Ret.) 1 What s New In February 1972, OSHA incorporated the 1971 edition of the National Fire Protection

More information

Safety and Health Policy and Procedure Manual. PERSONAL PROTECTIVE EQUIPMENT Section 0130. Table of Contents

Safety and Health Policy and Procedure Manual. PERSONAL PROTECTIVE EQUIPMENT Section 0130. Table of Contents Safety and Health Policy and Procedure Manual PERSONAL PROTECTIVE EQUIPMENT Section 0130 Table of Contents I. INTRODUCTION II. STANDARDS III. SCOPE IV. PURPOSE V. GENERAL REQUIREMENTS VI. EMPLOYEE OWNED

More information

Low Voltage Circuit Breakers. Arc flash hazards

Low Voltage Circuit Breakers. Arc flash hazards Low Voltage Circuit Breakers Arc flash hazards Index Low voltage selectivity with ABB circuit breakers Introduction... 2 Definitions, acronyms and terms used... 3 Electrical arcs and their dangerous effects

More information

How to Build a Safe and Effective Electrical Maintenance Program

How to Build a Safe and Effective Electrical Maintenance Program How to Build a Safe and Effective Electrical Maintenance Program The Business Case Ask Yourself the Following Questions: What is your dependence on electrical energy and control systems? What are the consequences

More information

Dielectric Withstand Testing in a Production Environment

Dielectric Withstand Testing in a Production Environment Dielectric Withstand Testing in a Production Environment Performing a routine product safety test should not in itself represent a shock hazard to the operator who is conducting the test, yet anytime you

More information

Electrical Safety Program. Electrical Safety Program Audit (Appendix: X) Performed By: Date:

Electrical Safety Program. Electrical Safety Program Audit (Appendix: X) Performed By: Date: Performed By: Date: The following sets of audit questions can be used to validate and verify that the is understood and being properly applied. Any non-compliant issues will be identified and prioritized

More information

PERSONAL PROTECTIVE EQUIPMENT FOR CALIFORNIA STATE UNIVERSITY, LOS ANGELES

PERSONAL PROTECTIVE EQUIPMENT FOR CALIFORNIA STATE UNIVERSITY, LOS ANGELES PERSONAL PROTECTIVE EQUIPMENT FOR CALIFORNIA STATE UNIVERSITY, LOS ANGELES OCTOBER 2007 PROGRAM APPROVAL AND AUTHORIZATION James M. Rosser, President Date TABLE OF CONTENTS TITLE Section PURPOSE...1.0

More information

OPTIONAL INFORMATION ELECTRICAL SAFETY WORK PRACTICES SELF INSPECTION CHECKLIST

OPTIONAL INFORMATION ELECTRICAL SAFETY WORK PRACTICES SELF INSPECTION CHECKLIST Name of School: OPTIONAL INFORMATION Date of Inspection: Vocational Program/Course/Room: Signature of Inspector: ELECTRICAL SAFETY WORK PRACTICES SELF INSPECTION CHECKLIST Instructions: This checklist

More information

Electrical Wiring Methods, Components and Equipment for General Use. Approved for Public Release; Further Dissemination Unlimited

Electrical Wiring Methods, Components and Equipment for General Use. Approved for Public Release; Further Dissemination Unlimited Electrical Wiring Methods, Components and Equipment for General Use Approved for Public Release; Further Dissemination Unlimited At the completion of this unit you shall be able to: 1. Utilize section

More information

Wenaas Offshore. A new and innovative collection redefining the standard for flame retardant workwear

Wenaas Offshore. A new and innovative collection redefining the standard for flame retardant workwear Wenaas Offshore A new and innovative collection redefining the standard for flame retardant workwear WE HELP OIL AND GAS COMPANIES DO THEIR JOB In 1931, Lars Wenaas started up a small garment factory in

More information

Webinar April 29, 2015

Webinar April 29, 2015 Webinar April 29, 2015 Dennis L. Mater dennis.l.mater@dupont.com FR Apparel Sales Technical Leader North America 1 Introduction Topic Overview Burn Injury Basics Type of Burns Degree of Skin Damage Burn

More information

DuPont Personal Protection TECHNICAL BULLETIN NUCLEAR RISKS

DuPont Personal Protection TECHNICAL BULLETIN NUCLEAR RISKS DuPont Personal Protection TECHNICAL BULLETIN NUCLEAR RISKS Specific questions have arisen related to the recent disaster which has occurred in Japan. A question frequently asked relates to protection

More information

Winter Survival Clothing System

Winter Survival Clothing System Winter Survival Clothing System How to clothe yourself for successful wilderness survival The most workable outdoor clothing method ever devised is known as the 3-layer system. Used by mountaineers, wilderness

More information

Safety Training Topic PERSONAL PROTECTIVE EQUIPMENT

Safety Training Topic PERSONAL PROTECTIVE EQUIPMENT Safety Training Topic PERSONAL PROTECTIVE EQUIPMENT Purpose of Meeting To remind workers that using personal protective equipment (PPE) can protect them from serious injury. To reince PPE safety rules.

More information

Proper Application of 415V Systems in North American Data Centers. A White Paper from the Experts in Business-Critical Continuity

Proper Application of 415V Systems in North American Data Centers. A White Paper from the Experts in Business-Critical Continuity Proper Application of 415V Systems in North American Data Centers A White Paper from the Experts in Business-Critical Continuity Introduction Increasing pressure to reduce operating expenses and be more

More information

Demystifying arc flash hazard management

Demystifying arc flash hazard management Demystifying arc flash hazard management Presented by Matt Brazier Senior Electrical Engineer Gove Operations November 2013 Standard NFPA 70E IEEE 1584 AS/NZS 4836 TERMINOLOGY Arc arc flash hazard analysis

More information

Who sets the rules for electrical testing and safety?

Who sets the rules for electrical testing and safety? Who sets the rules for electrical testing and safety? Application Note Alphabet soup There s no question that electrical safety is a key concern for electricians and engineers, their employers, unions

More information

AN UNCOMPROMISING COMMITMENT TO SAFETY

AN UNCOMPROMISING COMMITMENT TO SAFETY AN UNCOMPROMISING COMMITMENT TO SAFETY 866.493.7839 WESTEX.COM 2845 W. 48th Place Chicago, IL 60632 USA TABLE OF CONTENTS The Westex Story... 4-7 Overview of Westex Flame Resistant Fabrics... 8-11 Westex

More information

A Guide to Performing An Arc Flash Hazard Assessment Using Power Analysis Software

A Guide to Performing An Arc Flash Hazard Assessment Using Power Analysis Software A Guide to Performing An Arc Flash Hazard Assessment Using Power Analysis Software Abstract: The nature of explosive equipment failures, and the rate of serious burn injuries in the electrical industry

More information

Report on Proposals June 2011 NFPA 70E. 70E-1 Log #7 EEW-AAA

Report on Proposals June 2011 NFPA 70E. 70E-1 Log #7 EEW-AAA 70E-1 Log #7 EEW-AAA Palmer L. Hickman, National Joint Apprentice & Training Committee Revise text as follows: This edition of,, was prepared by the Technical Committee on Electrical Safety in the Workplace

More information

INDUSTRY WIDE LABOR-MANAGEMENT SAFETY COMMITTEE SAFETY BULLETIN #23

INDUSTRY WIDE LABOR-MANAGEMENT SAFETY COMMITTEE SAFETY BULLETIN #23 INDUSTRY WIDE LABOR-MANAGEMENT SAFETY COMMITTEE SAFETY BULLETIN #23 GUIDELINES FOR WORKING WITH PORTABLE POWER DISTRIBUTION SYSTEMS AND OTHER ELECTRICAL EQUIPMENT "ADDENDUM C" WORKING WITH 480 VOLT SYSTEMS

More information

Management Systems 10 Electrical Safety Audit 14 PPE 20 Arc Mitigation 22 Hazard Assessment 26

Management Systems 10 Electrical Safety Audit 14 PPE 20 Arc Mitigation 22 Hazard Assessment 26 Management Systems 10 Electrical Safety Audit 14 PPE 20 Arc Mitigation 22 Hazard Assessment 26 Assessing The Hazards Of High and Low Voltage Single-Phase Arc-Flash By Albert Marroquin One common question

More information

2004 TRANSMISSION SYSTEMS SEMINAR MEDIUM VOLTAGE, METAL-CLAD ARC RESISTANT SWITCHGEAR: ENHANCING WORKPLACE SAFETY

2004 TRANSMISSION SYSTEMS SEMINAR MEDIUM VOLTAGE, METAL-CLAD ARC RESISTANT SWITCHGEAR: ENHANCING WORKPLACE SAFETY 2004 TRANSMISSION SYSTEMS SEMINAR MEDIUM VOLTAGE, METAL-CLAD ARC RESISTANT SWITCHGEAR: ENHANCING WORKPLACE SAFETY Thomas P. McNamara, P.E. Manager, Development Engineering ABB Inc. Power Technologies Medium

More information

FLAME-RESISTANT APPAREL ELECTRIC UTILITY GENERAL INDUSTRIES ARC FLASH PROTECTION OIL & GAS

FLAME-RESISTANT APPAREL ELECTRIC UTILITY GENERAL INDUSTRIES ARC FLASH PROTECTION OIL & GAS 20 15 FLAME-RESISTANT APPAREL ELECTRIC UTILITY GENERAL INDUSTRIES ARC FLASH PROTECTION OIL & GAS THE BULWARK ADVANTAGE WORLD S LARGEST MANUFACTURER OF FLAME-RESISTANT APPAREL INDUSTRY LEADER IN FLAME-RESISTANT

More information

How to reduce exposure to arc flash hazards

How to reduce exposure to arc flash hazards GE Energy Industrial Solutions How to reduce exposure to arc flash hazards Multiple solutions for new and existing facilities imagination at work Multiple Issues Today s power system engineer must not

More information

Types of electrical injuries

Types of electrical injuries Types of electrical injuries Electrical injury is a term for all injuries caused by contact with electrical energy. Electrical contact can cause a wide variety of injuries involving most organ systems.

More information

OCCUPATIONAL SAFETY AND HEALTH PROGRAM

OCCUPATIONAL SAFETY AND HEALTH PROGRAM OCCUPATIONAL SAFETY AND HEALTH PROGRAM As stated in NFPA 1500, Standard on Fire Department Occupational Safety and Health Program, "Firefighting has been recognized as the most hazardous occupation in

More information