Electrical Safety Program. Electrical Safety Program Audit (Appendix: X) Performed By: Date:

Size: px
Start display at page:

Download "Electrical Safety Program. Electrical Safety Program Audit (Appendix: X) Performed By: Date:"

Transcription

1 Performed By: Date: The following sets of audit questions can be used to validate and verify that the is understood and being properly applied. Any non-compliant issues will be identified and prioritized as corrective actions to ensure that the is being properly and consistently applied. The audit questions are organized into sets of questions based on the prioritized preventive and protective control measures that the outlines as well as Occupational Health & Safety Management System Standards. 1. De-energize is always the first choice; 2. Substitution; 3. Engineering and Equipment Safety by Design. Maintain Critical Electrical Equipment; 4. Increase awareness by the application of signs and the use of barriers; 5. Administrative controls, training and procedures; 6. Electrical Specific PPE, Tools & Equipment, as the last line of defence, and ensure it is appropriately used and maintained. Table 2 identifies items that should be examined during the Internal Electrical Safety Audit. Validation and verification can be completed by Plant/Facility walk-through inspection(s), interviews with the responsible Qualified Electrical Worker(s) or other Worker Roles, and a review of related documentation. Auditing the items listed will provide an indication of the effective implementation of the Electrical Safety Program and related documentation such as supporting policies, practices, safe operating procedures, electrical safe work procedures, related Canadian Electrical Code (CEC) Part 1 compliance and recognized industry best practices. CSA Z462 Workplace electrical safety Standard or NFPA 70E Standard for Electrical Safety in the Workplace are the primary reference Standards. The following Electrical Safety Audit Process should be followed: 1. Schedule when you will complete the Audit, and advise management and workers that it will be completed and that they may have to participate in an interview or in verification/validation of the audit questions. 2. The Electrical Safety Audit will also validate that applicable requirements of the overall Occupational Health & Safety Management System (OHSMS) are in place, and been followed with respect to energized electrical work. Relevant content that should be applied against electrical hazard management is Safe Work Permit, Hazard Assessment, FLHA/FLRA, Preventative and Protective Control Measures (e.g. specific information on Electrical Specific PPE, Tools & Equipment), Incident Reporting & Investigation, Emergency Response, Management of Change, etc.. 3. Retrieve the latest revisions of the Electrical Safety Program, and supporting policies, practices, safe operating procedures, forms, checklists, and electrical safe work procedures. 4. Retrieve and confirm that you have the latest Revision of the Plant/Facility Electrical Single Line Diagram(s) and they are as-built. 5. Execute the Internal Electrical Safety Audit by completing the questions in Table ( ) Page 1 of 20

2 Use of the : This list of questions provides a broad review of the requirements of the Electrical Safety Program. The questions should be reviewed while completing the walk through inspection of the electrical power distribution system(s), during interviews, and when you have retrieved relevant documents. You will also have to inspect all available Electrical Specific PPE, Tools and Equipment (e.g. available for use, stored properly, individually or shared, check in/out system if shared, properly laundering, general condition as found (e.g. not torn, contaminated), valid third party test date (e.g. rubber insulating gloves within the last 6 months, hot sticks within the last 24 months and temporary protective grounds within the last 36 months). When completing inspections, interviews, or reviewing documents or inspecting Electrical Specific PPE, Tools & Equipment the criteria against which you are reviewing the findings can be identified by: You can use the criteria letter when recording results in the Comments/Observation column of Table 1. R C S M Table 1 Comments/Observation Verification/Validation Criteria Description Regulations Codes Standards, CSA Z462, Other Overall Occupational Health & Safety Management System Requirements (e.g. CSA Z1000, ANSI Z10etc.) Generally as the auditor you are looking for the acceptable E Electrical Safety Program application of the prioritized list of preventative and protective B Best Practice control measures with an electrical hazard focus that are included O Other in the Electrical Safety Program: 1. Eliminate the hazard, de-energize is the first choice (e.g. application of LOTO program, Establishing an Electrically Safe Work Condition); 2. Substitution (e.g. use of NGRs, Arc Resistant Switchgear) 3. Reduce the risk by design (e.g. Engineering solutions, equipment solutions, Safety by Design, Engineering Incident Energy Analysis, circuit breaker & relay changes to reduce incident energy, incident energy reduction with Arc Reduction Maintenance Switches (ARMs), incident energy reduction with Arc Flash Relays, IR scanning windows used, etc.); 4. Electrical equipment maintenance (e.g. appropriate PMs in place); 5. Use safer work systems that increase awareness of potential hazards (e.g. apply safeguards like signage, barriers, etc. the Electrical Work Zone is been used with red tape and a tag, proper use of Shock Approach Boundaries and Arc Flash Boundary); 6. Implement administrative controls training and procedures (e.g. review training records, use of Energized Electrical Work Permits, use of Energized Electrical Job Hazard Analysis (EEJHAs), audit status of Electrical Safe Work Procedures/Standard Operating Procedures, etc.); and 7. Use Electrical Specific Personal Protective Equipment (PPE), Tools & Equipment, as a last line of defense, and ensure it is appropriately used and maintained (e.g. available, stored properly, shared check in/out system working, check condition, laundered properly, tested current, etc.). Please also note that the Auditor can add to this list of questions or modify the way the question is asked in an effort to extract the verification/validation data required to make a credible assessment of the status quo. Note: Please review Appendix Q Recommended Pre-Use Checks for Electrical Specific PPE, Tools & Equipment of the for a Summary of Options for Mitigating of Limiting Arc Flash & Shock Hazards ( ) Page 2 of 20

3 Table 2 Audit Findings Table General Company Overall Occupational Health & Safety 1. Management System in place and active? 2. Company Electrical Safety Program available? CSA Z462, Clause Have workers received training on the Electrical Safety Program and its requirements? Has any electrical hazard and Electrical Safety Program practice information been posted on Safety Bulletin Boards in order to get the profile higher in the general worker community? Has any communication gone out to the general worker community and appropriate contracting companies with respect to awareness of encroachment on Overhead Power Lines and the risk of shock and electrocution? Has any communication been sent out to the general worker community on the importance of using a GFCI and pre-use test and reset requirements? Has any communication been sent out to the general worker community on the importance of pre-use inspecting power cords and plugs to ensure no damage? Company requires Hazard Task Analysis to be completed for all work tasks completed? CSA Z462, Clause CSA Z462, Clause CSA Z462, Clause CSA Z462, Clause Company requires Job Planning & Briefing be completed by all workers before proceeding to complete a work task? Is a Joint Health & Safety Committee (JHSC) in place are QEWs represented? Is an Electrical Safety Steering Committee (ESSC) in place as a sub-committee of the JHSC? Does the ESSC meet at least annually to review the Electrical Safety Program? With respect to the Roles & Responsibilities of the Electrical Safety Program, is an Electrical Safety Program Manager is in place? CSA Z462, Clause CSA Z1000, Clause CSA Z1000, Clause ( ) Page 3 of 20

4 13. If the company has multiple divisions or business units is there an established Electrical Safety Program Coordinator in place for each division of business unit? 14. Company Emergency Response Plan in place and active? Company Incident Reporting and Investigation Policy in effect and active? Have all workers been advised that all electrical shocks (no matter what the voltage of exposure was) and arc flash events are to be reported? Have any electrical incidents occurred since the last Electrical Safety Audit was completed? Electrical Safety Program Appendix V Electrical Incident Rescue Procedure & Investigation Form used for electrical incidents investigation and reporting? Class C fire extinguishers are located in SWGR and MCC buildings and tested current? 20. First aid kits are available? Are there written procedures for care, use, maintenance, 21. testing and pre-use inspection for Electrical Specific PPE, Tools & Equipment? General Comments: De-energizing Control of Hazardous Energy 22. Company Lockout and Tagout Program/Policy is in place and current? 23. As a priority energized electrical equipment is de-energized before any work it completed on it e.g. repair or alteration?, CEC Part 1, Rule ( ) Page 4 of 20

5 The concept of Establishing an Electrically Safe Work Condition is practiced before any repair or alteration work on energized electrical equipment? If energized electrical work is justified and electrical hazard analysis is completed before proceeding with the energized electrical work? The risk assessment process is utilized before undertaking energized electrical work to consider any mitigation or control measures that can be applied to reduce the risk related to the work task to As Low As Reasonable Practicable (ALARP)? Electrical Single Line Diagrams both low voltage (<750V) and high voltage (>750V) are available to workers to be used for job planning and identifying electrical isolation locations related to a work task? and CSA Z462, Clause 4.2 and CSA Z462, Clause and CSA Z462 Annex F For high voltage, CEC Part 1, Rule CSA Z462 Annex F provides a comprehensive review of risk assessment. 28. Workers are trained on the requirements of the Company Lockout and Tagout Program/Policy? 29. Personal locks and tags are available to all workers? Appropriate adapters to attach locks are available for electrical isolation devices? Locks and tags are installed on electrical isolation devices by individual workers? Group lockout is used when required for electrical isolations? Are locks readily available and controlled, locks out board available in MCC / Electrical Rooms? A Lockout Logbook is located in the MCC / Electrical Room and are locks logged on and off? All conductors and circuit parts are tested for absence of voltage (e.g. zero, 0 ) before they are touched with bare hands? TEST-BEFORE-TOUCH! Where cables or capacitors were energized are they discharged to ground before been worked on? Long runs of wiring will act as capacitors and should be discharged to ground to eliminate any residual voltage. and CSA Z462, 4.2 and CSA Z462, ( ) Page 5 of 20

6 No lock(s) are removed (e.g. cut off) unless all means of contacting the owner of the lock(s) have been undertaken 37. and documented and a lock removal form has been signed by management? General Comments: and CSA Z460 Electrical Engineering / Equipment Safety by Design 38. Ensure SLD(s) are current, approved and P.Eng stamped Ensure hazardous area classification drawings, are current, approved and P.Eng. stamped. Is there a Neutral Ground Resistor (NGR) present and is it shown on the SLD(s) for LV and HV (e.g. 4160V, 13800V)? Has the MCC or SWGR been sized correctly, what is the fault withstand capacity of the bus, is it noted on the single line drawing? Are the as-built single lines adequately posted in MCC Buildings or available in the MCC Buildings? Is the utility fault current noted on the single line diagram with a date? Has engineering incident energy analysis been completed? If detailed labels are applied an engineering based incident energy analysis has been completed and P.Eng. stamped report issued, is it readily available for review and is it current to within the last 5 years? For determination of appropriate wiring methods and approved equipment For high voltage CEC Part 1, Rule Information used to determine Arc Flash Boundary and Incident Energy at the Working Distance. CSA Z462m Clause recommends 5 year review of labels to ensure still valid ( ) Page 6 of 20

7 Audit If engineering incident energy analysis has been complete is the P.Eng. stamped report available for Qualified Electrical Workers to review? Has the Qualified Electrical Worker confirmed that the circuit breakers or relays settings match the P.Eng. stamped report? If engineering incident energy analysis has been completed was a back-up copy of the power engineering software files and all custom libraries received and archived and backed up? If an engineering incident energy analysis was completed was any mitigation installed? If incident energy analysis mitigation has been installed is it properly labeled and understood by Qualified Electrical Workers? If Arc Reduction Maintenance Switches (ARMs) have been installed are they identified in Electrical Safe Work Procedures? Is remote switching available for power circuit breakers (e.g. mimic panel, remote operating device, timed switches)? Are remote racks in and out robots available for racking in and out power circuit breakers? Are voltages indicating devices installed for high voltage equipment that can be viewed through an installed viewing window before the door is opened? General Comments: See Appendix Q Summary of Options for Mitigating or Limiting Arc Flash & Shock Hazards for a detailed list of options that could be applied. Electrical Safety Program Changes to Breaker & Relay Settings, installing an Arc Flash Relay, installing Arc Reduction Maintenance Switch(es), new Relays Installed, etc. Risk reduction, voltage indicated as off before opening the door. A voltage detector is still required to be used to test all conductors and circuit parts for absence of voltage ( ) Page 7 of 20

8 Electrical Equipment Maintenance 54. Is an Electrical Equipment Maintenance Program available? 55. Is industry Standards such as the NETA Acceptance and Maintenance Standards utilized? CSA Z462, Clause CSA Z463 Guideline for Electrical Equipment Maintenance utilized (available 2013)? This is a new CSA Guideline under development since 2011, currently not available. Separately NFPA 70B Recommended Practice for Electrical Equipment Maintenance could be referenced for guidance. 57. Are PMs in place for critical electrical equipment e.g. Switchgear cleaning, MCC cleaning, power circuit breakers, relays, etc.? CSA Z462, Clause Is Infrared Scanning e.g. thermography completed at some determined frequency as an established PM? 59. Are identified hot spots from IR scanning eliminated? Is a third party electrical maintenance and testing contractor used? Are they a NETA Accredited company? Is electrical equipment inspected at a regular frequency for any external indication of overheating or other abnormal condition (e.g. standing water on the equipment or in proximity to the equipment)? Are the electrical protective devices installed remotely monitored and alarmed indicating a fault condition? If there is no remote monitoring is frequent inspections of the electrical equipment completed specifically to check indication on electrical protective devices (e.g. fault, failure of the device)? Is electrical equipment shut down and inspected internally for any abnormal conditions (e.g. dust, evidence of rodents)? If electrical distribution equipment includes power circuit breakers (e.g. 480V, 600V, 4160V, 13800V, 25000V, 35000V) are they removed inspected, cleaned and tested at a regular frequency? CSA Z462, Clause 5 CSA Z462, Clause 5 CSA Z462, Clause 5 CSA Z462, Clause ( ) Page 8 of 20

9 66. Are electrical protective relays tested on a regular frequency? Are settings confirmed to match the P.Eng. stamped engineering report? CSA Z462, Clause If large power transformers are owned is regular maintenance completed (e.g. oil analysis)? CSA Z462, Clause Are power tools and their cords in good condition, three prong plug and are double insulated? All power cords are three wire cords with the ground pin intact, are in good condition? 70. Electrical supplied welding equipment is bonded to ground? General Comments: Safe Installations CEC Are all electrical buildings or areas clean and free of nonessential items? Is minimum working space provided around electrical equipment? Electrical equipment properly closed and protected. No exposure to energized electrical conductors or circuit parts? Is all electrical equipment protected against mechanical damage? CEC & and CSA Z462, Clause CEC meter minimum CEC CEC Junction boxes properly labeled? CEC Is all electrical equipment, including JBs, properly supported and provided with required access? Are Panel Schedules located inside panels and as-built and legible? Is all electrical equipment marked with CSA or equivalent approvals? CEC , & CEC CEC Housekeeping ( ) Page 9 of 20

10 Are all unused wires and cables properly terminated and labeled? Where NGR devices are used are appropriate warning signs provided (e.g. on transformer or generator or both, switchgear or MCC, and supply authorities metering equipment)? CEC 2-100, & CEC Signs on all connected equipment. 81. Is all electrical equipment properly grounded? CEC Section Is all electrical equipment openings closed off and all bolts or screws in place? Physical protection and clearance provided around all power transformers? Are cable trays filled to within design capacity, i.e. not overfilled? Are cable trays properly installed, e.g. adequately supported? All cables and conductors must be properly supported and secured. CEC CEC Section 26 CEC CEC CEC , , , & Is there minimum clearance space around cable trays? CEC Are cable trays properly bonded and connected to ground if required? CEC Do cable trays have cover where needed? CEC Appendix B 90. Where electrical equipment is fed from multiple sources are warning signs appropriately provided? CEC Equipment installed in hazardous areas must be approved and labeled for the location? CEC & Check seals are provided and properly installed where necessary for hazardous locations? CEC & Are receptacles in the hazardous area approved for the location? CEC & Are high voltage single lines posted in proximity to high voltage electrical equipment? CEC Does high voltage equipment have proper signage? CEC Are high voltage cables identified? CEC (1) (d) 97. Is piping with electrical heat tracing properly labeled? CEC ( ) Page 10 of 20

11 98. Does any electrical equipment show signs of excessive heating? CEC Are JB s protected from ice or water build-up? Recommended Practice 100. Do JB s have a breather drain? Recommended Practice 101. Are illumination levels adequate at electrical equipment? CEC & Is the service transformer ground grid connected to the plant ground grid? Is the plant ground grid network continuous, i.e. no isolated ground systems? 104. Is the system ground conductor properly sized? CEC Good practice to avoid hazardous step-touch potential. CEC Table 52 CEC , , Tables 16 & Is an NGR provided and properly installed? CEC thru Is a NGR warning sign provided at all appropriate locations, e.g. transformer, incoming breaker, and on the NGR? CEC Is the cable tray system continuously bonded? CEC Are building skids properly grounded? CEC Section Is all electrical equipment, e.g. MCC s bonded to the plant ground system? General Comments: CEC Warning Signs & Barricading Portable barriers and warning tape available for use to establish the Electrical Work Zone? Are MCC Building man-doors labeled with a unique identification tag, and Warning signs (e.g. Danger xx Volts, Authorized Personnel Only)? CSA Z462, Clause CSA Z462, Clause Electrical Safety Program, Appendix H 19929( ) Page 11 of 20

12 Is all electrical distribution equipment identified with a unique tag or ID # that is indicated on the single line diagram? Has the voltage rating of electrical distribution equipment been posted on the equipment e.g. 120/240V, 480V, 600V, 4160V? CSA Z462, Clause CSA Z462, Clause Has look-alike equipment been labeled on the back and front with unique sections/cell identification IDs? CSA Z462, Clause , Are detailed Arc Flash and Shock Warning labels attached to Switchgear, MCCs, Panel boards etc.? Are detailed Warning labels properly installed and the equipment that they apply to indicated? Are detailed Arc Flash and Shock Danger labels attached to Switchgear, MCCs, Panel boards etc.? Are detailed Danger labels properly installed and the equipment they apply to indicated? If arc flash mitigation has been installed is it uniquely identified and labeled indicating that it is arc flash mitigation? 120. Are detailed Arc Flash and Shock labels reviewed every 5 years to confirm no changes to the electrical distribution system have occurred that would change the incident energy values calculated? CSA Z462, Clause No significant changes that would increase or lower the short circuit current. General Comments: Administrative Controls Training Based on worker role appropriate technical training has been received? Based on worker role CEC Part 1 latest edition update training has been received? CSA Z462, Clause CEC Part 1 is adopted into law by the jurisdiction having authority. QEW Journeyman Electricians should be aware of the latest requirements that could impact new capital work installations or ongoing maintenance ( ) Page 12 of 20

13 123. Refresher training on CSA Z462 and its related work practices is completed for appropriate worker roles at least every 3 years? CSA Z462, Clause Qualified Electrical Workers have received First Aid and CPR training? CSA Z462, Clause If an AED is available for use workers have been trained on how to use the AED properly? CSA Z462, Clause Review the Training Matrix in Appendix U of the Electrical Safety Program and check training records to confirm that 126. appropriate worker roles have the training identified and it is still valid? General Comments: Administrative Controls Procedures and Practices The latest revision of CSA Z462 Workplace electrical safety Standard is available for reference by workers and supervisors? Job Briefing & Planning forms are filled out by QEWs when planning their energized electrical work tasks? All required hazard task analysis forms, and permits required by the overall Occupational Health & Safety Management system are completed for energized electrical work tasks? Electrical hazard analysis is completed for all energized electrical work tasks as outlined in the Electrical Safety Program? An Energized Electrical Work Permit (EEWP) is completed for high risk non-routine energized electrical work tasks? CSA Z462, Clause ,, CSA Z462, CSA Z462, Clause At least one copy should be available for workers reference. Recommended at least the supervisor has a copy ( ) Page 13 of 20

14 132. An Arc Flash & Shock Hazard Analysis Form Table Method or Detailed Label is completed for energized electrical work tasks? 133. An Energized Electrical Job Hazard Analysis (EEJHA) form is completed for every energized electrical work task? 134. Electrical safe work procedures are used for energized electrical work? 135. Electrical safe work procedures are audited on an annual basis by workers and their supervisors? 136. The Electrical Work Zone is been established before energized electrical work is performed with red Danger tape and a tag? The Electrical Work Zone should be established at the Limited Approach Boundary for shock or the Arc Flash Boundary whichever is further away? 137. Work tasks on temporary power systems are analyzed for arc flash and shock hazard exposure and Boundaries established and Electrical Specific PPE, Tools & Equipment selected? Plug and cord conditions are been checked by workers before use? Work related to personnel and equipment near Overhead Power Lines is identified and when required Limits of Approached utilized? Workers are alert when completing energized electrical work tasks? No work tasks are allowed where blind reaching is identified? Adequate illumination for energized electrical tasks is established before the work task is completed? Any energized electrical work in confined or enclosed spaces that is justified has additional control measures implemented? Housekeeping in and around electrical distribution equipment (e.g. Panel boards, Lighting Transformers, MCCs, Switchgear, etc.) is controlled so that there is at least 1 m clearance and free ingress and egress?, CSA Z462, Clause 4.3.6, CSA Z462, Clause 4.3.6, CSA Z462, Clause 4.3.6, CSA Z462, Clause 4.3.6, CSA Z462, Clause ( ) Page 14 of 20

15 145. All MCC / Electrical Room / Substations have appropriate Warning or Danger signs installed? 146. When required an Electrical Safety Watch/Standby person is utilized for energized electrical work that is identified as requiring it?, CSA Z462, Clause Look-alike equipment has been suitably labeled with an identification tag on the back and front?, CSA Z462, Clause Portable ladders used for electrical work have nonconductive side rails? The use of metal scaffolding for energized electrical worker isn t allowed? Metal scaffolding is not used in proximity to energized electrical equipment where there are exposed conductors or circuit parts? Qualified Electrical Workers are not wearing metal, conductive jewelry when completing energized electrical work and are inside the Restricted Approach Boundary? For complex switching and isolation a procedure(s) are implemented and used to execute the work?,, CSA Z462, Clause Switching order forms are used when required? General Comments: Electrical Specific PPE, Tools & Equipment Electrical Specific PPE, Tools & Equipment readily available and are they adequately rated? QEWs wear 100% cotton natural fibre clothing to work every day? All workers that may be exposed to arc flash must wear non-meltable clothing underneath arc rated clothing. There is no concern if arc rated clothing is what is worn against the skin as everyday wear clothing ( ) Page 15 of 20

16 155. Every day wear clothing is arc-rated, indicated on the clothing collar tag or on the inside of the garment? Arc rating in ATPV or E BT is minimum 8 cal/cm 2 (Level 1)? Label is compliant with ASTM F a labeling requirements? The clothing is clean and no visible damage or contamination? Does arc-rated every day wear clothing have any exposed (not insulated/covered by fabric or other non-conductive materials) conductive metal snaps or zippers on the inside of the garment? Underwear worn by workers under arc-rated every day wear is made of either 100% natural fibre or arc-rated materials? Potential pass through pockets or side slit openings in coveralls and bib-overalls can be sealed to prevent underwear ignition? If layering arc-rated protective garments for additional protection is the appropriate ASTM F1959 testing documentation on file and up to date with the most current edition of the standard? e.g. ASTM F When high visibility stripping is used on arc-rated protective garments the material is arc-rated or FR? The stripping pattern is compliant with CSA Z96-09 Standard for High Visibility Safety Apparel? All Logos, name tags, and other heraldry, such as flag patches and company insignias are manufactured using inherently FR thread? Alternatively are their overall area on the garment as minimized as possible? e.g. large company logos across the back of the garment shall not be used. Arc-rated faceshields are available for workers and arcrated 12 cal/cm 2 ATPV (Level 1)? No visible damage and suitable for use? Stored in protective storage bag? Arc-rated faceshields, hard hats, accessories and components are pre-use inspected before each use? ASTM F a CSA Z Clause.11 CSA Z462-12, Clause.9 CSA Z96-09 ASTM F a, CSA Z462, Clause CSA Z Clause ( ) Page 16 of 20

17 Arc-rated faceshields and arc flash hood windows are marked with Z87.1+? All arc-rated faceshields and arc flash suit hoods shall meet the requirements of ASTM F2178 including ANSI Z87.1 High Impact protection. All arc-rated faceshields and arc flash suit hoods have antiscratch coatings (outside) and permanent anti-fog coatings (inside)? Arc-rated balaclavas of the equal or greater arc rating (ATPV, Level 1) as the arc-rated faceshield are available to every worker? ASTM F , CSA Z462, Clause 166. When electrical specific PPE is shared are arc-rated balaclavas and arc flash suit hoods are cleaned and disinfected before each use? Regulations 167. Is an arc-rated arc flash suit available consisting of a hood, coat and bib-overall. A minimum 40 cal/cm 2 arc rating (Level 2) as ATPV or E BT? Does the hood have a hood ventilation system installed? The arc flash suit including hood window (lens) is clean and no visible damage or contamination? Is the arc flash suit a lab coat style with shin covers?, CSA Z462, Clause If the arc flash suit is a lab coat style with Velcro down the front, then when the worker bends down the bottom Velcro will open and the worker will not be protected if there is an arc flash. This style of arc flash suit is not recommended Hood Ventilation system has no exposed non-fr or arcrated components, e.g. Fan, hose, battery, wiring. The Hood Ventilation System batteries are charged and replacement units or recharging station is readily available? CSA Z Clause Arc Flash suits and all included components are pre-use inspected before each use? CSA Z Clause Applicable workers have been trained on how to properly wear (don/doff), care, store and maintain their individually assigned or shared arc-rated protective equipment? CSA Z Clause All applicable testing documentation for arc-rated PPE is on file and current to the most recent edition of the standards? i.e. ASTM F1959, ASTM F2178, ASTM F2621 etc Hard hats worn with arc-rated faceshields or arc flash suit hoods are Class E, non-conductive to 20kV? Hard hat suspension consists of a ratchet style configuration?, CSA Z462, Clause 19929( ) Page 17 of 20

18 Have workers been advised of unique laundering instructions for arc-rated clothing? If industrial laundering, laundering at the workplace or home laundering is utilized for arc-rated clothing, have written laundering instructions been provided?, CSA Z462, Clause, CSA Z462, Clause The arc rating of some clothing (e.g. treated cotton) can be negatively affected with continuous washing in fabric softener and bleach. Employer needs to ensure manufacturer s laundering instructions are followed Arc-rated gloves are used for protection of hands where there is an arc flash risk related to an energized electrical work task and no shock risk?, CSA Z462, Clause Using an arc rated glove would be approved, but is not recommended as these gloves are large and oversized and the worker cannot effectively hold certain tools Leather work gloves are used for protection of hands where there is an arc flash risk related to an energized electrical work task and no shock risk? CSA Z462, Clause.10 Leather gloves are not currently tested for an ATPV, but informal tests and depending on the glove thickness can provide protection for >10 cal/cm Rubber insulating or voltage rated gloves with leather protectors rated for the working voltage are used for protection of hands when there is an arc flash risk related to an energized electrical work task and no shock risk?, CSA Z462, Clause 178. QEWs are wearing approved safety shoes or boots, Grade 1, Ohm rated (e.g. should have an Omega symbol tag)?, CSA Z462, Clause 179. Approved Safety Glasses or Goggles are available and worn underneath the arc flash suit hood and the arc-rated faceshield?, CSA Z462, Clause 180. Appropriately rated canal insert ear plugs and/or ear muffs (dual hearing protection) are available and worn underneath the arc flash suit hood and the arc-rated faceshield?, CSA Z462, Clause 181. Electrical Specific PPE, Tools & Equipment are properly stored e.g. individual bags, cases, lockers used etc.?, CSA Z462, Clause 182. Inventory list of all Electrical Specific PPE, Tools & Equipment Available?, CSA Z462, Clause 183. Check in/out system utilized for shared Electrical Specific PPE, Tools & Equipment?, CSA Z462, Clause 184. Has Electrical Specific PPE, Tools & Equipment been uniquely tagged (including their cases or bags), e.g. rubber insulating gloves, hot sticks, temporary protective grounds, and kit bags or lockers for reference in procedures and tracking purposes? 19929( ) Page 18 of 20

19 Is any Performance Management of Electrical Specific PPE, Tools & Equipment in place e.g. Electrical Specific PPE, Tools & Equipment evaluated that it worked as intended? Rubber insulating gloves for low voltage < 750V work available, stored properly, not damaged, clean, tested current (e.g. within last 6 months) and at least Class 0, 1000 V rated? Rubber insulating gloves for use on >750 V work available, stored properly, not damaged, clean, tested current (e.g. within the last 6 months), rated for at least Class 1 (7.5 kv) and Class 2 (17 kv) as required? Rubber insulating gloves and leather protectors are pre-use inspected by QEWs, both visual and air test? Temporary Protective Grounding cables on-site and if yes, are they rated for maximum fault current, at the assumed clearing time? Have they been testing in the last 36 months?, CSA Z462, Clause, CSA Z462, Clause, CSA Z462, Clause, CSA Z462, Clause, CSA Z462, Clause Temporary Protective Grounding cables are pre-use inspected before each use?, CSA Z462 Clause Insulated hand tools for use on equipment <750 V available, rated for 1000 V (e.g. double triangle with 1000V beside the triangles), and stored properly in wrap or protective case? Not stored in the same tool box or pouch with normal tools? 192. Insulated hand tools are pre-use inspected before use? Insulated hand tools are available and used for DC Battery termination work? For DC Battery work where the batteries use liquid electrolyte are both chemical and electrical PPE, Tools & Equipment worn? Shotgun hot stick, 4 length available for use for application of temporary protective grounds? Test date indicates tested within last 24 months? If a Rescue Hot Stick is available has it been tested within the last 24 months?, CSA Z462, Clause, CSA Z462, Clause, CSA Z462, Clause 6.3.3, CSA Z462, Clause 6.3.3, CSA Z462, Clause, CSA Z462, Clause The use of a Rescue style hot stick is not mandatory. Any approved hot stick can be used for emergency release of shock victim ( ) Page 19 of 20

20 All hot sticks are pre-use checked before use and kept clean and stored in manufacturer s storage bag (where one is available)? Digital Multi-Meters and other electrical test equipment for <750 V work certified to at least Category IIII, 600 V? Stored in protective case? Digital Multi-Meters and voltage detectors are pre-use inspected before use? Digital Multi-Meters and voltage detectors are pre-use function tested on 120V receptacle before and after use to verify functioning?, CSA Z462, Clause 201. Is a high voltage proximity detector available for use? Is a voltage source from the manufacturer available to preuse test the high voltage proximity detector? High voltage proximity detector is pre-use function tested on lighting or receptacle? If a fall arrest harness is required for arc flash risked work is it ASTM F887 approved, which is arc-rated at 40cal/cm 2?, CSA Z462, Clause Not mandatory, standard test is to test voltage detector on 120VAC receptacle or fluorescent light fixture before and after used to verify functioning Is Class 0, 1000VAC maximum use rubber insulating blanket available for use? Where the magnets or plastic clips purchased with the rubber insulating blanket?, CSA Z462, Clause General Comments: 19929( ) Page 20 of 20

BRANDON AND CLARK INC. // SCOTT W. CLARK, P.E. ELECTRICAL CONTINUING EDUCATION ARC FLASH - NFPA 70E

BRANDON AND CLARK INC. // SCOTT W. CLARK, P.E. ELECTRICAL CONTINUING EDUCATION ARC FLASH - NFPA 70E BRANDON AND CLARK INC. // SCOTT W. CLARK, P.E. ELECTRICAL CONTINUING EDUCATION ARC FLASH - NFPA 70E Training is not a substitute for following corporate safety guidelines. Always refer to the latest safety

More information

2012 NFPA 70E. Ten Most Important Changes. John A. DeDad

2012 NFPA 70E. Ten Most Important Changes. John A. DeDad 2012 NFPA 70E Ten Most Important Changes John A. DeDad GE Energy Management 41 Woodford Avenue Plainville, CT 06062 USA 860-747-7344 John.dedad@ge.com Abstract The 2012 Edition of NFPA 70E, Standard for

More information

SAFE ELECTRICAL WORK PRACTICES & 2015 NFPA 70E

SAFE ELECTRICAL WORK PRACTICES & 2015 NFPA 70E SAFE ELECTRICAL WORK PRACTICES & 2015 NFPA 70E This easy-to-use Leader s Guide is provided to assist in conducting a successful presentation. Featured are: INTRODUCTION: A brief description of the program

More information

Written Program ELECTRICAL SAFETY. Based on OSHA Subpart S and NFPA 70E Standards

Written Program ELECTRICAL SAFETY. Based on OSHA Subpart S and NFPA 70E Standards Written Program ELECTRICAL SAFETY Based on OSHA Subpart S and NFPA 70E Standards Revised November 2012 Disclaimer The presentations and program provided by Workplace Safety Solutions, Inc. are based on

More information

90.2(A) Covered & 90.2(B) Not Covered 6/23/2015. Learning Objectives. 90.2(A) Covered & 90.2(B) Not Covered. Change Summary

90.2(A) Covered & 90.2(B) Not Covered 6/23/2015. Learning Objectives. 90.2(A) Covered & 90.2(B) Not Covered. Change Summary Learning Objectives After reviewing this material, the student will be able to: 1. Identify the installations that fall under the scope of the 2015 edition of NFPA 70E. 2. Identify the assessments required

More information

Arc Flash Avoidance and its Application to Overhead Traveling Cranes

Arc Flash Avoidance and its Application to Overhead Traveling Cranes Arc Flash Avoidance and its Application to Overhead Traveling Cranes Whitepaper August 2012 Jason Wellnitz, Controls Product Manager Material Handling Numerous technical papers, bulletins, magazine articles

More information

Electrical Safety Program

Electrical Safety Program California State University-Fullerton 800 N. State College Blvd. Fullerton, CA 92831 Prepared by: Paul A Zoubek, CSP, CIH President/Principal Consultant Zoubek Consulting, LLC 3737 Granada Ave. San Diego,

More information

ARC FLASH CALCULATIONS & LABELING REQUIREMENTS

ARC FLASH CALCULATIONS & LABELING REQUIREMENTS ARC FLASH CALCULATIONS & LABELING REQUIREMENTS Presented by: Edmund Elizalde EYP Mission Critical Facilities, Inc. Slides by: Lonnie Lindell SKM Systems Analysis, Inc. 1 Agenda NEC 110.16 NFPA 70E IEEE

More information

Union County Public Schools. Facilities Department. Electrical. Safe Work Practices

Union County Public Schools. Facilities Department. Electrical. Safe Work Practices 1 Union County Public Schools Facilities Department Electrical Safe Work Practices 2 Purpose In accordance with OSHA Standards 1910.331-335, safety-related work practices shall be used by Union County

More information

Arc Flash Hazards. Electrical Hazards. Dan Neeser Field Application Engineer DanRNeeser@Eaton.com. Electrical Hazards 2/18/2015. Shock.

Arc Flash Hazards. Electrical Hazards. Dan Neeser Field Application Engineer DanRNeeser@Eaton.com. Electrical Hazards 2/18/2015. Shock. Arc Flash Hazards Dan Neeser Field Application Engineer DanRNeeser@Eaton.com Electrical Hazards Electrical Hazards Shock Arc Flash Arc Blast 2 1 Arcing Fault Basics 35,000 F Radiant Heat & UV Speed of

More information

ARC FLASH HAZARD OVERVIEW. Presented August 13, 2015 WWOA Lake Michigan District by Mead & Hunt, Inc.

ARC FLASH HAZARD OVERVIEW. Presented August 13, 2015 WWOA Lake Michigan District by Mead & Hunt, Inc. ARC FLASH HAZARD OVERVIEW Presented August 13, 2015 WWOA Lake Michigan District by Mead & Hunt, Inc. ARC FLASH EXPERIENCE Christopher J. DeWaal, MS, MEM, PE, LEED AP, HACCP How did I get involved? A client

More information

NFPA 70E Updates Affect Your Most Valuable Assets

NFPA 70E Updates Affect Your Most Valuable Assets NFPA 70E Updates Affect Your Most Valuable Assets EXECUTIVE SUMMARY Electrocution is a well-known hazard associated with direct contact with electrical energy. According to the U.S. Department of Labor,

More information

Electrical Safety Program

Electrical Safety Program CALIFORNIA STATE UNIVERSITY, STANISLAUS Electrical Safety Program LAST UPDATED 6/2/11 CALIFORNIA STATE UNIVERSITY, STANISLAUS ELECTRICAL SAFETY PROGRAM TABLE OF CONTENTS 1.0 Purpose......2 2.0 Scope......2

More information

2008 Eaton Corporation. All rights reserved.

2008 Eaton Corporation. All rights reserved. FlashGard TM Motor Control Center Electrical Safety Hazards Design Philosophy The Product 2008 Eaton Corporation. All rights reserved. Research studies say. Five to 10 arc flash explosions occur in electrical

More information

INTRODUCTION ARC FLASH PROTECTION AND SAFETY MEASURES. September 2010

INTRODUCTION ARC FLASH PROTECTION AND SAFETY MEASURES. September 2010 ARC FLASH PROTECTION AND SAFETY MEASURES September 2010 Introduction Hazards of Electrical Energy Electrical Safety Program Safety-Related Work Practices Electrical Safety Procedures Presented By: Ken

More information

Understanding Arc Flash

Understanding Arc Flash Understanding Arc Flash Presented by Eddie F. Jones, PE 1 2 3 4 5 Five to 10 arc flash explosions occur in electric equipment every day in the United States. This number does not include cases in which

More information

The Other Hazard of Electricity. Larren Elliott Ph.D. Lindsay Polic, CSP, REHS

The Other Hazard of Electricity. Larren Elliott Ph.D. Lindsay Polic, CSP, REHS The Other Hazard of Electricity Larren Elliott Ph.D. Lindsay Polic, CSP, REHS Presenters Larren Elliott Ph.D. EORM Electrical Safety Service Partner 45 years practical and hands-on industrial experience

More information

Common Electrical Hazards in the Workplace Including Arc Flash. Presented by Ken Cohen, PhD, PE & CIH (Ret.)

Common Electrical Hazards in the Workplace Including Arc Flash. Presented by Ken Cohen, PhD, PE & CIH (Ret.) Common Electrical Hazards in the Workplace Including Arc Flash Presented by Ken Cohen, PhD, PE & CIH (Ret.) 1 What s New In February 1972, OSHA incorporated the 1971 edition of the National Fire Protection

More information

What s up with Arc Flash?

What s up with Arc Flash? What s up with Arc Flash? Presented by Mark Haskins, CSP Practical Safety Solutions, LLC CONN OSHA Breakfast Roundtable February 18, 2014 2014 Practical Safety Solutions, LLC What is Arc Flash? Definition

More information

Electrical Wiring Methods, Components and Equipment for General Use. Approved for Public Release; Further Dissemination Unlimited

Electrical Wiring Methods, Components and Equipment for General Use. Approved for Public Release; Further Dissemination Unlimited Electrical Wiring Methods, Components and Equipment for General Use Approved for Public Release; Further Dissemination Unlimited At the completion of this unit you shall be able to: 1. Utilize section

More information

IMPLEMENTING THE NEW ELECTRICAL SAFETY REQUIREMENTS

IMPLEMENTING THE NEW ELECTRICAL SAFETY REQUIREMENTS IMPLEMENTING THE NEW ELECTRICAL SAFETY REQUIREMENTS Paul A Zoubek, CSP, CIH Occupational Services, Inc. San Diego, CA 619-861 861-0612 paul@occsev.com OCCUPATIONAL SERVICES, INC. BACKGROUND Update Update

More information

PROCEDURES FOR SAFE WORKING AND TESTING OF ENERGIZED ELECTRICAL EQUIPMENT

PROCEDURES FOR SAFE WORKING AND TESTING OF ENERGIZED ELECTRICAL EQUIPMENT Human Resources Support Services Health, Wellness and Safety PROCEDURES FOR SAFE WORKING AND TESTING OF ENERGIZED ELECTRICAL EQUIPMENT 1 SCOPE The electrical safety procedure shall be part of the Peel

More information

Roadmap to Compliance with NFPA 70E Arc Flash Requirements

Roadmap to Compliance with NFPA 70E Arc Flash Requirements Roadmap to Compliance with NFPA 70E Arc Flash Requirements TAHFM Interlink 2015 March 30, 2015 Antony Parsons, Ph.D., P.E. Schneider Electric Engineering Services 1 2 How do we get to Reliable Power? >

More information

Part 1 System Modeling & Studies for Existing Systems

Part 1 System Modeling & Studies for Existing Systems Part 1 System Modeling & Studies for Existing Systems Operation Technology, Inc. Copyright 2009 Result of rapid release of energy due to an arcing fault between two conductors. Bus voltages > 208V Temperatures

More information

ELECTRICAL SAFETY. The standard unit for measuring electrical current.

ELECTRICAL SAFETY. The standard unit for measuring electrical current. ELECTRICAL SAFETY Introduction The following sections provide general safety guidelines and procedures for electrical safety. This chapter covers the following topics: TOPIC PAGE General Electrical Safety

More information

Electrical Safety in the Workplace

Electrical Safety in the Workplace Electrical Safety in the Workplace NFPA 70 E Presented by Sabine Mueller What Made Sabine Choose Such a DRY Topic? Ulterior Motive Metso Mueller Engineering has been visiting many scrap yards two or more

More information

RMM 306 Lockout/Tagout (LOTO) Program for the Control of Hazardous Energy Page 2 June 2016

RMM 306 Lockout/Tagout (LOTO) Program for the Control of Hazardous Energy Page 2 June 2016 RMM 306 Lockout/Tagout (LOTO) Program for the Control of Hazardous Energy Page 2 3 Related Documents 3.1 Occupational Health and Safety Act, R.S.O. 1990 3.2 Regulations for Industrial Establishments, R.R.O.

More information

Installation Instructions for Alarm Module Kit A043F059

Installation Instructions for Alarm Module Kit A043F059 Instruction Sheet 07-2013 Installation Instructions for Alarm Module Kit A043F059 1 Introduction The information contained within is based on information available at the time of going to print. In line

More information

2013WWOA Conference Technical Conference Program

2013WWOA Conference Technical Conference Program 2013WWOA Conference Technical Conference Program Understanding Arc-Flash Hazards, Its Implications on Operations and Solutions that Mitigate Such Exposure Presented by Jerry Baskin Senior Product Manager

More information

100% Rule Alternate Method Arc Blast Arc Flash Approved Approved Equipment Authority Having Jurisdiction (AHJ) Authorized Work Bare Hand Work

100% Rule Alternate Method Arc Blast Arc Flash Approved Approved Equipment Authority Having Jurisdiction (AHJ) Authorized Work Bare Hand Work Definitions 100% Rule Work on or near energized parts must be performed only after all participating qualified electrical workers are in 100% agreement on the work to be completed, on the sequence in which

More information

SALISBURY ASSESSMENT SOLUTIONS

SALISBURY ASSESSMENT SOLUTIONS SALISBURY ASSESSMENT SOLUTIONS Electrical engineering services for a safe and compliant workplace Electrical Safety Program Assessments - Electrical Safety Training Arc Flash Risk Assessments - Power Systems

More information

INDUSTRY WIDE LABOR-MANAGEMENT SAFETY COMMITTEE SAFETY BULLETIN #23

INDUSTRY WIDE LABOR-MANAGEMENT SAFETY COMMITTEE SAFETY BULLETIN #23 INDUSTRY WIDE LABOR-MANAGEMENT SAFETY COMMITTEE SAFETY BULLETIN #23 GUIDELINES FOR WORKING WITH PORTABLE POWER DISTRIBUTION SYSTEMS AND OTHER ELECTRICAL EQUIPMENT "ADDENDUM C" WORKING WITH 480 VOLT SYSTEMS

More information

OPTIONAL INFORMATION ELECTRICAL SAFETY WORK PRACTICES SELF INSPECTION CHECKLIST

OPTIONAL INFORMATION ELECTRICAL SAFETY WORK PRACTICES SELF INSPECTION CHECKLIST Name of School: OPTIONAL INFORMATION Date of Inspection: Vocational Program/Course/Room: Signature of Inspector: ELECTRICAL SAFETY WORK PRACTICES SELF INSPECTION CHECKLIST Instructions: This checklist

More information

NFPA 70E 2012 Rolls Out New Electrical Safety Requirements Affecting Data Centers

NFPA 70E 2012 Rolls Out New Electrical Safety Requirements Affecting Data Centers NFPA 70E 2012 Rolls Out New Electrical Safety Requirements Affecting Data Centers A market position paper from the experts in Business-Critical Continuity TM Executive Summary Electrocutions are the fourth

More information

ELECTRICAL SAFETY RISK ASSESSMENT

ELECTRICAL SAFETY RISK ASSESSMENT ELECTRICAL SAFETY RISK ASSESSMENT The intent of this procedure is to perform a risk assessment, which includes a review of the electrical hazards, the associated foreseeable tasks, and the protective measures

More information

ELECTRICAL & ARC FLASH SAFETY PROGRAM

ELECTRICAL & ARC FLASH SAFETY PROGRAM ELECTRICAL & ARC FLASH SAFETY PROGRAM ADOPTED VERSIO 2, SEPTEMBER 26, 2012 Supercedes all prior versions A. COMMITTEE OVERSIGHT OF PROGRAM The University of Montana ( University ) recognizes the importance

More information

3053 Electrical Safety Training Program Course Outline

3053 Electrical Safety Training Program Course Outline 3053 Electrical Safety Training Program Course Outline The following outline summarizes the major points of information presented in the program. The outline can be used to review the program before conducting

More information

LABORATORY SAFETY INSPECTION CHECKLIST

LABORATORY SAFETY INSPECTION CHECKLIST LABORATORY SAFETY INSPECTION CHECKLIST As part of EH&S's laboratory safety survey program, we have compiled a list of the most common safety problems. This is not a list of every possible hazard, but can

More information

ELECTRICAL SAFETY: QUALIFIED/NON QUALIFIED

ELECTRICAL SAFETY: QUALIFIED/NON QUALIFIED Preparation: Safety Mgr Authority: Dennis Johnston Issuing Dept: Safety Page: Page 1 of 9 Purpose The purpose of the Electrical Safety program is to set forth procedures for the safe use of electrical

More information

Campus Safety Procedure Electrical Safety

Campus Safety Procedure Electrical Safety Campus Safety Procedure Electrical Safety Electrical Safety Procedures 1.0 Purpose The purpose of this procedure is to provide guidance in the performance of work on electrical systems, wiring, and equipment

More information

! WARNING Arc Flash and Shock Hazard Appropriate PPE Required

! WARNING Arc Flash and Shock Hazard Appropriate PPE Required Arc Flash Hazard Labeling Do s and Don ts! WARNING Arc Flash and Shock Hazard Appropriate PPE Required 11' - 3" Flash Hazard Boundary 9 cal/cm2 Flash Hazard at 18 inches #3 PPE Level Cotton underwear plus

More information

UNIVERSITY OF CENTRAL FLORIDA ELECTRICAL SAFETY PROGRAM

UNIVERSITY OF CENTRAL FLORIDA ELECTRICAL SAFETY PROGRAM UNIVERSITY OF CENTRAL FLORIDA ELECTRICAL SAFETY PROGRAM December 2011 Table of Contents UNIVERSITY OF CENTRAL FLORIDA... 0 Table of Contents... 1 INTRODUCTION... 2 PURPOSE... 2 SCOPE... 3 RESPONSIBILITIES...

More information

Test Before Touch Easier Said Than Done. Ken Crawford, DuPont Kent Haggerty, Dupont

Test Before Touch Easier Said Than Done. Ken Crawford, DuPont Kent Haggerty, Dupont Test Before Touch Easier Said Than Done Ken Crawford, DuPont Kent Haggerty, Dupont Overview Test Before Touch (TBT) Principles Key Learnings by One Company One Method for Performing a TBT Induced Voltages

More information

Hampshire College. Lockout/Tagout and Electrical Safety Program and Procedures

Hampshire College. Lockout/Tagout and Electrical Safety Program and Procedures Hampshire College Lockout/Tagout and Electrical Safety Program and Procedures January 2007 In Compliance with the OSHA 29 CFR 1910.147 and 29 CFR 1910.331 through.335 And NFPA 70E Environmental Health

More information

HAZARDS, INCLUDING SHOCK, ARC FLASH AND FIRE

HAZARDS, INCLUDING SHOCK, ARC FLASH AND FIRE Appendix B-2 - Electrical Safety In Design Final Report TECHNOLOGIES THAT REDUCE LIKELIHOOD OF INJURY FROM ELECTRICAL HAZARDS, INCLUDING SHOCK, ARC FLASH AND FIRE The following are technologies that reduce

More information

Introduction to Arc Flash

Introduction to Arc Flash Introduction to Arc Flash Worker Training of Electrical Hazards Including Arc Flash SH-16614-7 This material was produced under grant number SH-16614-7 from the Occupational Safety and Health Administration,

More information

misconceptions about arc-flash hazard assessments

misconceptions about arc-flash hazard assessments misconceptions about arc-flash hazard assessments There are some common misconceptions about Arc-Flash Hazard Assessments which reduce the effectiveness of the Assessments and can increase electrical hazards.

More information

PLANT OPERATIONS ELECTRICAL SAFETY PROGRAM

PLANT OPERATIONS ELECTRICAL SAFETY PROGRAM PLANT OPERATIONS ELECTRICAL SAFETY PROGRAM Prepared by the Department of Occupational Safety & Environmental Health PLANT ELECTRICAL SAFETY PROGRAM TABLE OF CONTENTS Page I. Purpose and Scope 1 II. Definitions

More information

TAMPA ELECTRIC COMPANY ENERGY SUPPLY ELECTRICAL SAFETY PROGRAM

TAMPA ELECTRIC COMPANY ENERGY SUPPLY ELECTRICAL SAFETY PROGRAM TABLE OF CONTENTS TITLE PAGE # PURPOSE / INTRODUCTION 1 SCOPE 2 RESPONSIBILITY 3 EMPLOYEE TRAINING INCLUDING DOCUMENTATION 4 ELECTRICAL EQUIPMENT LABELING 5 APPROACH DISTANCES AND BOUNDARIES 5-8 GENERAL

More information

Low Voltage Switchgear

Low Voltage Switchgear Arc Resistant Switchgear n Insulated and isolated bus n Separation barriers and top venting n Breaker shutters 12 SWITCHGEAR Arc resistant metal-enclosed low voltage switchgear is an optional product offering

More information

City Of Ottawa High Voltage Substation Inspection, Maintenance Rev 00 2015 July 17 and Testing, ROPEC Page 1

City Of Ottawa High Voltage Substation Inspection, Maintenance Rev 00 2015 July 17 and Testing, ROPEC Page 1 2015 July 17 and Testing, ROPEC Page 1 PART 1 GENERAL 1.1. Scope.1 Equipment replacement and testing for a 44 kv 4.16kV/600V substation: a. Replacement of Insulators as indicated on the drawings in Appendix

More information

Electrical Safety Tips. Help us keep you safe

Electrical Safety Tips. Help us keep you safe Electrical Safety Tips Help us keep you safe To help you stay safe when using electricity, ActewAGL has compiled these electrical safety tips. For natural gas safety tips please see ActewAGL s natural

More information

Understanding 2015 Changes to NFPA 70E Safety-related work practices and maintenance requirements mandate more robust electrical safety programs for

Understanding 2015 Changes to NFPA 70E Safety-related work practices and maintenance requirements mandate more robust electrical safety programs for Understanding 2015 Changes to NFPA 70E Safety-related work practices and maintenance requirements mandate more robust electrical safety programs for commercial and industrial facilities Executive Summary

More information

DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE CONSTRUCTION SAFETY STANDARDS

DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE CONSTRUCTION SAFETY STANDARDS MIOSHA-STD-1313 (10/15) 6 Pages For further information Ph: 517-284-7740 www.michigan.gov/mioshastandards DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE CONSTRUCTION SAFETY STANDARDS

More information

Course Title: Safety Issues in Electronics Engineering Technology Number of Credits: 3 B.A. B.S. B.A.S A.A. A.S. Degree Type

Course Title: Safety Issues in Electronics Engineering Technology Number of Credits: 3 B.A. B.S. B.A.S A.A. A.S. Degree Type GENERAL INFORMATION Name: Diane King Phone #: 77021 Course Prefix/Number: ETI3704 Course Title: Safety Issues in Electronics Engineering Technology Number of Credits: 3 B.A. B.S. B.A.S A.A. A.S. Degree

More information

Arc Flash Mitigation. Remote Racking and Switching for Arc Flash danger mitigation in distribution class switchgear.

Arc Flash Mitigation. Remote Racking and Switching for Arc Flash danger mitigation in distribution class switchgear. Arc Flash Mitigation Remote Racking and Switching for Arc Flash danger mitigation in distribution class switchgear. Distance is Safety We will discuss through examples of actual occurrences and possible

More information

Electrical Safety Products

Electrical Safety Products Electrical Safety Products Trelleborg Electrical Safety Products A safe working environment is important in all industries, but in the electrical generation and supply industry, it is paramount. Trelleborg

More information

1 General Responsibility. 1.1 Participants. 1.2 Documentation. 1.3 Lockout/Tagout

1 General Responsibility. 1.1 Participants. 1.2 Documentation. 1.3 Lockout/Tagout Electrical Safety Plan This plan establishes rules for both the design and operation of the LPRDS. These rules are intended to enhance the safety of the participants in the initial project and future users

More information

FACILITY SAFETY SIGNAGE GUIDE: 10 SIGNS TO SPOT DURING A PLANT WALKTHROUGH

FACILITY SAFETY SIGNAGE GUIDE: 10 SIGNS TO SPOT DURING A PLANT WALKTHROUGH FACILITY SAFETY SIGNAGE GUIDE: 10 SIGNS TO SPOT DURING A PLANT WALKTHROUGH Safety signs are the primary way to communicate important warnings and messages to your employees, on-site contractors and other

More information

Addendum #2 Contract UK-11-13

Addendum #2 Contract UK-11-13 Addendum #2 Contract UK-11-13 Utilities Kingston Purchase and Replacement of Switchgear at Kingston Hydro Substation MS11 March 25, 2011 Delivered to: All RFP recipients Total number of pages: Nine (9)

More information

ELECTRICAL SAFETY / ARC FLASH PROGRAM

ELECTRICAL SAFETY / ARC FLASH PROGRAM INTRODUCTION ELECTRICAL SAFETY / ARC FLASH PROGRAM This program establishes minimum standards to prevent hazardous electrical exposures to personnel and ensure compliance with regulatory requirements applicable

More information

Safety Electrical Work - A Page 1 Overview

Safety Electrical Work - A Page 1 Overview Page 1 Overview Purpose This Devon Energy Protocol establishes minimum safe work practices and electrical safety management requirements. Employees must comply with this protocol as well as all applicable

More information

Dennis Fire Department Fire Prevention Mark Dellner Fire Chief

Dennis Fire Department Fire Prevention Mark Dellner Fire Chief Dennis Fire Department Fire Prevention Mark Dellner Fire Chief FIRE SAFETY INSPECTION GUIDELINES FOR COMMERCIAL PROPERTIES (MA Fire Prevention Regulations 527 CMR, MGL Chapter 148) FIRE PREVENTION CHECKLIST-

More information

Kidd Mine Barricade Standards

Kidd Mine Barricade Standards Kidd Mine Barricade Standards Wednesday, February 13, 2013 Why Upgrade Our Barricade Standard? Eliminate any confusion with fences, signs and their purpose in our operation by applying an easily recognizable

More information

Environmental Health & Safety Electrical Safety Program

Environmental Health & Safety Electrical Safety Program **Printed copies of this document are uncontrolled, visit the EHS website at http://www.wright.edu/admin/ehs/ for the latest revision** I. Purpose Ensure the safety of employees who may work on or near

More information

Electrical Safety Plugs What are the different types of plugs? Extension Cords What are some potential hazards involving extension cords?

Electrical Safety Plugs What are the different types of plugs? Extension Cords What are some potential hazards involving extension cords? Electrical Safety Electricity can be a friend, but it can also hurt if you do not treat it with respect. Everyday someone loses his or her home or business due to an electrical fire. These tragedies are

More information

Understanding 2015 Changes to NFPA 70E Safety-related work practices and maintenance requirements mandate more robust electrical safety programs for

Understanding 2015 Changes to NFPA 70E Safety-related work practices and maintenance requirements mandate more robust electrical safety programs for Understanding 2015 Changes to NFPA 70E Safety-related work practices and maintenance requirements mandate more robust electrical safety programs for data centers Executive Summary Every three years, the

More information

Name Of Occupancy Date. Yes No Describe

Name Of Occupancy Date. Yes No Describe FIRE PREVENTION INSPECTION CHECKLIST For Class A Occupancy (For Assembly Buildings, Bars, Restaurants, Gyms, Churches, Arenas, Theatres or wherever people gather) Name Of Occupancy Date Physical Address

More information

Evaluating Water-Damaged Electrical Equipment

Evaluating Water-Damaged Electrical Equipment Evaluating Water-Damaged Electrical Equipment 1 USE OF THIS PUBLICATION This publication provides information on how to evaluate electrical equipment that has been exposed to water through flooding, fire

More information

Electrical Safety in the Marine Environment

Electrical Safety in the Marine Environment January 3, 2001 TEHNIAL BULLETIN 010 Electrical Safety in the Marine Environment Approach Boundaries Electrical Safety in the Marine Environment presented by adick orporation 1 Overview Electrical power

More information

OSHA Training Guidelines (An Unofficial Summary)

OSHA Training Guidelines (An Unofficial Summary) OSHA Training Guidelines (An Unofficial Summary) Many standards promulgated by the Occupational Safety and Health Administration (OSHA) explicitly require the employer to train employees in the safety

More information

OSHA & ARC FLASH HAZARD ANALYSIS

OSHA & ARC FLASH HAZARD ANALYSIS OSHA & ARC FLASH HAZARD ANALYSIS Impact of Revisions to the OSHA Electrical Safety Regulations Presented by: John J. Kolak, MS, CSP Introduction Important Definitions Understanding OSHA Applicable standards

More information

Electrocution Hazards

Electrocution Hazards Electrocution Hazards 1 Electricity Accidents People who work directly or indirectly with electricity can be the victims of serious electrocution injury or death on construction sites. These accidents

More information

Laboratory Safety Guideline Electrical Safety

Laboratory Safety Guideline Electrical Safety Introduction The typical laboratory contains a wide variety of electrically-powered equipment including stirrers, shakers, pumps, hot plates, heaters, power supplies, ovens, and electrophoresis equipment.

More information

ELECTRICAL PRACTICES FOR CONSTRUCTION WORK

ELECTRICAL PRACTICES FOR CONSTRUCTION WORK CONTRACTOR S CHECKLIST ELECTRICAL PRACTICES FOR CONSTRUCTION WORK 2007 WorkCover. Watching out for you. New South Wales Government Disclaimer This publication contains information regarding occupational

More information

Example ESD Control Program Document Based on ANSI/ESD S20.20-2007

Example ESD Control Program Document Based on ANSI/ESD S20.20-2007 PROFESSIONAL STATIC CONTROL SERVICES Example ESD Control Program Document Based on ANSI/ESD S20.20-2007 The following document demonstrates the structure for an ESD control program that is compliant to

More information

ELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F

ELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F ELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F TABLE OF CONTENTS Appendix F - Electrical Engineering Design Criteria F.1 Introduction...F-1 F.2 Codes and Standards...F-1 F.3 Switchyard and Transformers...F-1

More information

Why Construction Workers are Getting Electrocuted

Why Construction Workers are Getting Electrocuted Why Construction Workers are Getting Electrocuted Michael McCann, PhD, CIH Director of Safety and Ergonomics The Center to Protect Workers Rights mmccann@cpwr.com Causes of Death in Construction, 1992-98

More information

Electrical Hazards. Power Tools. Extension Cords

Electrical Hazards. Power Tools. Extension Cords Electrical Hazards Electrical hazards can be found in nearly every roofing work site. Whether the hazard is posed by worn or damaged power tools or cords, improperly grounded tools or equipment, or the

More information

Arc Flash Mitigation & Selective Co-ordination

Arc Flash Mitigation & Selective Co-ordination Arc Flash Mitigation & Selective Co-ordination Michael Hodder March 2015 Overview This seminar will provide information on: Mitigating arc flash hazards Selective Coordination What can we do to make these

More information

Electrical Grounding. Appendix C

Electrical Grounding. Appendix C Appendix C Electrical Grounding Low-Voltage Equipment Grounding The most frequently cited Office of Safety and Health Administration (OSHA) electrical violation is improper occupational grounding of equipment

More information

Requirements for Electrical Installations

Requirements for Electrical Installations ARTICLE 110 Requirements for Electrical Installations INTRODUCTION TO ARTICLE 110 REQUIREMENTS FOR ELECTRICAL INSTALLATIONS Article 110 sets the stage for how you ll implement the rest of the NEC. This

More information

Integrating SPDs in Switchgear & Switchboards Causes More Problems than it Solves

Integrating SPDs in Switchgear & Switchboards Causes More Problems than it Solves Integrating SPDs in Switchgear & Switchboards Causes More Problems than it Solves White Paper July 2010 Integrating surge protective devices (SPD) into distribution equipment (i.e. switchgear, switchboards,

More information

LOCK-OUT/TAG-OUT PROGRAM I. Purpose

LOCK-OUT/TAG-OUT PROGRAM I. Purpose LOCK-OUT/TAG-OUT PROGRAM I. Purpose This procedure establishes requirements for the lockout of energy isolating devices. It should be used to ensure that the machine or piece of equipment is isolated from

More information

OSHA Published First-Ever Arc Flash Protection Requirements for the Electric Power Industry Significant changes and unprecedented compliance

OSHA Published First-Ever Arc Flash Protection Requirements for the Electric Power Industry Significant changes and unprecedented compliance OSHA Published First-Ever Arc Flash Protection Requirements for the Electric Power Industry Significant changes and unprecedented compliance deadlines require high-voltage facilities to take immediate

More information

PERSONAL PROTECTIVE EQUIPMENT (PPE)

PERSONAL PROTECTIVE EQUIPMENT (PPE) Page 1 of 6 (PPE) Personal protective equipment (PPE) is used to protect an individual from hazards associated with their work tasks or environment. Specific types of personal protective equipment include

More information

ARC Flash Boundary & NFPA-70E Requirements PPE Program

ARC Flash Boundary & NFPA-70E Requirements PPE Program ARC Flash Boundary & NFPA-70E Requirements PPE Program 1. Purpose and Scope The Arc Flash Boundary - PPE Program was developed to minimize the risk to AMS employees from safety and health hazards in the

More information

What Are the Qualifications to Conduct Arc Flash Studies? Where Do You Begin?

What Are the Qualifications to Conduct Arc Flash Studies? Where Do You Begin? What Are the Qualifications to Conduct Arc Flash Studies? Where Do You Begin? Comparing apples-to-apples bids Plant Services Special Report A shock hazard analysis should be included as part of an arc

More information

RISK MITIGATION for ELECTRICAL WORK. Feb 2013 San Diego CA

RISK MITIGATION for ELECTRICAL WORK. Feb 2013 San Diego CA RISK MITIGATION for ELECTRICAL WORK Feb 2013 San Diego CA Agenda I. RISK Define the Risks Arc Flash Review II. MITIGATION 3 Easy Steps New Designs Vs. Existing Systems III. DUKE UNIVERSITY EXAMPLE I. Risk

More information

Electrical Safety Program Version 0

Electrical Safety Program Version 0 Electrical Safety Program Version 0 This Electrical Safety Program is hereby approved by: Robert Andrews Facilities Director 9-3-12 Signature Title Date Donna Placzek Director, EHS 9-20-12 Signature Title

More information

VERIFY HARD COPY AGAINST WEB SITE IMMEDIATELY PRIOR TO USE

VERIFY HARD COPY AGAINST WEB SITE IMMEDIATELY PRIOR TO USE Nuclear Safe Work Practice 6.7 Safety Signs/Tapes/Ropes/Chains and Tags 1.0 PURPOSE/SCOPE To provide consistent standards for using safety signs, tapes, ropes and chains (barriers) to communicate existing

More information

CPPSEC2021A Install security equipment and systems

CPPSEC2021A Install security equipment and systems CPPSEC2021A Install security equipment and systems Release: 1 CPPSEC2021A Install security equipment and systems Modification History Not Applicable Unit Descriptor Unit descriptor This unit of competency

More information

OSHA 29CFR1910 Subpart S

OSHA 29CFR1910 Subpart S OSHA 29CFR1910 Subpart S By Michael V. Brown New Standard Institute It's the Law. Design safety related work practices for persons who install, maintain and repair electrical circuits or equipment, as

More information

School of Engineering University of Glasgow

School of Engineering University of Glasgow School of Engineering University of Glasgow Electronics Workshops Rankine Building 319A (2 Technicians) 510 (1 Technician) 712A (4 Technicians, 1 Modern Apprentice) James Watt South 619 (2 Technicians)

More information

A Safe Workplace A Workplace Safety and Health Manual for Your Community Section: III-C Subject: G-9

A Safe Workplace A Workplace Safety and Health Manual for Your Community Section: III-C Subject: G-9 Page 1 of 7 The following procedure provides the requirements for. Refer to part 15 Confined Spaces, part 6 Personal Protective Equipment, part 14 Fall Protection, of The Manitoba Workplace Safety and

More information

Reducing Liability through Safety Labeling - Industrial Automation. Todd Fries

Reducing Liability through Safety Labeling - Industrial Automation. Todd Fries Reducing Liability through Safety Labeling - Industrial Automation Todd Fries Disclaimer HellermannTyton makes no representation or warranty regarding code compliance. The user is solely responsible to

More information

Work in Substations - General

Work in Substations - General Work in Substations - General Summary: This document supports the Power System Safety Rules and its requirements assembled under Work in Substations General Category 3 and apply to all persons working

More information

University Of Cincinnati

University Of Cincinnati University Of Cincinnati Qualified Electrical Worker Safety Program Page 1 Table of Contents Table of contents.2 1.0 Purpose... 3 2.0 Scope... 3 3.0 Authority / Ownership... 3 4.0 Definitions.. 4-10 5.0

More information