1 1 1. Introduction A is implemented to ensure the fire safety of building occupants or a building area when the automatic fire protection system has been temporarily disabled. This Environmental Health & Safety Standard Operating Procedure (SOP) for implementing a fire watch was developed by the Department of Environmental Health & Safety in accordance with the University s Policy Statement on Health and Safety and to ensure compliance with the requirements of the Ontario Building and Fire Codes. Assistance in using this guidelines and meeting the requirements of applicable codes is available from the Department of Environmental Health & Safety. 2. Scope This SOP outlines the requirements of a in Queen s University buildings where there is a temporary impairment of the Fire Alarm System or Fire Suppression System. For the purpose of this document a Fire Protection System shall mean a Fire Alarm System or Fire Suppression System. 3. Applicable Legislation Ontario Fire Code NFPA 101, Life Safety Code 4. Requirements to Implement a The Ontario Fire Code requires that buildings equipped with fire alarm systems and sprinkler systems be fully operational at all times. Therefore, in the event any of these systems are offline for any reason, a is to be initiated immediately. A is only intended as a short term alternative that permits continued occupancy of the building while corrective measures are being implemented. If a cannot be implemented, the building may not be occupied.
2 2 5. Notification to Building Occupants When Fire Protection System maintenance is scheduled, building occupants are to be notified in writing: The nature and duration of the outage; That a will be in place; Emergency procedures during the outage. Signage shall be posted at all entrances and in common areas of the building indicating which Fire Protection system is out of order and emergency procedures. (see sample Signage) 6. Notification to Kingston Fire and Rescue If a fire protection system will be offline for less than 24 hours, Queen s Security and Emergency Services shall contact Kingston Fire & Rescue to advise what fire protection system is off-line and that a has been implemented in the building. If a fire protection system is to be offline for more than 24 hours, Queen s Environmental Health and Safety shall provide written notification to Kingston Fire and Rescue. Queen s Security and Emergency Services shall notify Kingston Fire and Rescue of the status daily. 7. Hot Works Hot works such as welding or cutting shall be prohibited in the area where the sprinkler protection is impaired. If hot work cannot be avoided in areas where the sprinkler system is impaired, alternate precautions as approved by the Department of Environmental Health & Safety shall be implemented.
3 3 8. Personnel A may be performed by Queen s Security and Emergency Services staff, responsible occupant, employee, or contractor. At least one (1) qualified person shall be employed to complete fire watch duties in all unprotected portions of the building. personnel are to be familiar with the building and procedures for sounding an alarm and alerting the fire service in the event of a fire. If the fire sprinkler system is out of service, the Personnel are to have fire extinguishing equipment readily available and be trained in its use. If the fire alarm system is still capable of sounding an alarm, personnel shall be instructed how to activate the alarm signal. inspections shall be the primary duty of the individual responsible for the Fire Watch. Each person assigned to duties should be provided with the following equipment: Suitable means of communication (cell phone, portable radio, etc.) for notifying Kingston Fire and Rescue A portable air horn, whistle or other approved means of sounding an alarm Flashlight Copy of Duties Copy of the Log Sheet Keys and/or access codes to provide entry to all rooms/spaces Floor plan(s) of the building under
4 4 9. Procedures The must be continuous until the fire protection system is repaired and online. personnel must tour all unprotected portions of the building each hour. Upon the completion of each inspection, the person conducting the shall record the time each round was completed and sign or initial each entry. personnel are to actively look for evidence of smoke and fire and listen for inroom smoke detectors sounding. In locations where construction or maintenance activities are occurring, exit doors, access to exits and corridors are to be checked periodically for proper operation and obstructions. 10. If Fire or Smoke Conditions are Discovered: Do not attempt to extinguish the fire unless it is safe to do so. Leave the fire area immediately and close doors Alert building occupants by activating the fire alarm or sounding a series of 3 long blasts of a portable air horn or whistle and yelling Fire Fire Fire or activate the fire alarm system if it is capable of sounding an alarm. From a safe location: o Notify the Emergency Reporting Centre via radio; or o Call 911 and Campus Security & Emergency Services ( ) Assist persons requiring assistance. Evacuate the building via the nearest safe exit DO NOT use the elevator. Await the arrival of the Fire Department and Campus Security and Emergency Services. No one shall re-enter the building until the ALL CLEAR has been given by the Fire Department as communicated by the Campus Security and Emergency Services Supervisor.
5 5 11. Unoccupied Buildings In a building that is unoccupied, where a fire protection system is offline, a fire watch is required unless approved by the Department of Environmental Health & Safety. 12. Cancellation of a Cancelling the is based on an assessment by a Qualified Fire Protection System Technician; that the fire protection system(s) is fully operational. Queen s Security and Emergency Services shall notify Kingston Fire & Rescue and Fire Monitoring Canada when the Fire Protection system(s) is fully operational. Revision History : Initial Release
6 WARNING FIRE ALARM SYSTEM OUT OF SERVICE IN CASE OF FIRE CALL 911 or x36111 A FIRE WATCH IS PATROLLING THE AFFECTED AREAS OF THIS BUILDING IF YOU HEAR 3 BLASTS OF AN AIR HORN OR WHISTLE EVACUATE THE BUILDING FOLLOW POSTED EMERGENCY PROCEEDURES
7 FIRE WATCH LOG SHEET Name or Address of Building: Area of Building Under : Date Time er Signature Comments / Observations All areas of the building under must be inspected and documented hourly. This Log is to be maintained at the facility until the re-establishment of fire protection system; at which time this sheet is to be submitted Queen s Environmental Health and Safety. (613)
Fire Watch. Fire safety systems may not be deactivated in whole or in part for any reason other than for repairs or hot work.
Emergency Guideline GU.FAC.039 For Team Leaders, Caretakers, Trades, and Project Supervisors Approved by FS Leadership Team, August 28, 2013 Fire Watch A Fire Watch is a temporary surveillance system for
More informationFire Alarm and Protection Impairment Policy and Procedures
1.0 Policy Statement The University of New Haven has developed a Fire Alarm and Protection Impairment Plan in accordance with the National Fire Protection Associations (NFPA) codes. Specific codes referenced
More informationFire Alarm Log Book. Any activity regarding this system must be documented in writing.
CASTLE ROCK FIRE AND RESCUE DEPARTMENT 300 Perry Street Castle Rock, Colo. 80104 303-660-1066 Do not remove from the premises: Fire Alarm Log Book Any activity regarding this system must be documented
More informationFIRE ALARM /FIRE PROTECTION OUTAGE/IMPAIRMENT RESPONSE GUIDELINE
Page 1 of 10 FIRE ALARM /FIRE PROTECTION OUTAGE/IMPAIRMENT RESPONSE GUIDELINE SYSTEM TESTING 1. Testing of the Fire Alarm and Fire Protection Systems 1.1. The Building Engineer, Electrician, Plumber (or
More informationFire Alarms- Use of buildings when they are out of service
Fire Alarms- Use of buildings when they are out of service Document control information Published document name: no-alarm-gn.pdf Date issued: January 2016 Version: 4 Previous review dates: May 2014 Next
More informationOVERVIEW SCOPE DEFINITIONS
Procedure No 400.10 Subject: Fire Protection Impairment Program Reference: NFPA (see bottom of page 5) Effective Date: March 2008 Distribution All Employees Review Date: April 2008 Purpose: To establish
More informationInspection, Testing and Maintenance
Page 18 ABOUT CODE CORNER CCFS would like to remind you to check with your local Authority Having Jurisdiction (AHJ) for questions and opinions concerning your local Fire and Building Codes. The information
More informationAmendments to the 2012 INTERNATIONAL FIRE CODE
Amendments to the 2012 INTERNATIONAL FIRE CODE 2012 Edition, International Fire Code. Section 101.1 Amend to read as follows. 101.1 Title. These regulations shall be known as the Fire Code of the City
More informationCONSTRUCTION FIRE SAFETY PLANNING GUIDELINES
CONSTRUCTION FIRE SAFETY PLANNING GUIDELINES Review the following information pertaining to Construction Fire Safety Planning: B.C. Building Code Sections 8.1 up to and including Subsection 8.2.3 B.C.
More informationALVERNIA UNIVERSITY OSHA REGULATION: 29 CFR 1910.252 WELDING, CUTTING, AND BRAZING ( HOT WORK ) SECTION: 3600
OSHA REGULATION: 9 CFR 90.5 WELDING, CUTTING, AND BRAZING ( HOT WORK ) A. POLICY. This procedure follows requirements set forth in 9 CFR 90.5.. This policy applies to all Hot Work operations being done
More informationPOINT UNIVERSITY CAMPUS SECURITY Emergency Response Plan
POINT UNIVERSITY CAMPUS SECURITY Emergency Response Plan Introduction The Point University Emergency Response Plan establishes guidelines for campus-wide communication, service coordination and safety
More information1.1.4 The findings from Fire Risk Assessment must be incorporated into the FRAMS Action Plan to manage fire safety at each premise.
Fire Safety Policy 1.1 Policy Statement of Intent 1.1.1 Under the current UK Legislation (In England and Wales, the Regulatory Reform (Fire Safety) Order 2005, Fire (Scotland) Act 2005, Fire and Rescue
More informationA. OCCUPANT FIRE PROCEDURES... 3 B. THE TENANT FIRE SAFETY TEAM... 6 C. SENIOR FIRE WARDEN... 7 D. DEPUTY FIRE WARDEN... 8
Brookfield Place BROOKFIELD PLACE Page 2 of 12 OCTOBER 2006 TABLE OF CONTENTS A. OCCUPANT FIRE PROCEDURES... 3 B. THE TENANT FIRE SAFETY TEAM... 6 C. SENIOR FIRE WARDEN... 7 D. DEPUTY FIRE WARDEN... 8
More informationENVIRONMENTAL HEALTH AND SAFETY. Fire Protection System Impairment Procedure
ENVIRONMENTAL HEALTH AND SAFETY Fire Protection System Impairment Procedure April 2013 Fire Protection System Impairment Procedures Table of Contents I. Purpose II. III. IV. Fire Protection Systems Compliance
More informationFire Safety Risk Assessment Checklist for Residential Care Premises
Checklist for Residential Care Premises Name of Premises: Address of Premises: Name of Responsible Person: What area / location does the assessment cover? Does the assessment cover the whole site YES or
More informationEnvironment of Care Fire Safety Management Plan 2014
Environment of Care Fire Safety Management Plan 2014 Updated 4.29.2014 PURPOSE The purpose of the Fire Safety Management Plan is to ensure that all facilities are designed, constructed, maintained, and
More informationAustin Independent School District Police Department Policy and Procedure Manual
Policy 8.07 Austin Independent School District Police Department Policy and Procedure Manual Life Safety Systems I. POLICY The proper operations of the AISD Life Safety Systems (LSS) are essential for
More informationFire Risk Assessment Safety Checklist
Fire Risk Assessment Safety Checklist This checklist has been prepared to help you comply with The Regulatory Reform Fire Safety Order 2005 What is the Regulatory Reform (Fire Safety) Order 2005? The Regulatory
More information(Sample) Building Emergency Plan
(Sample) Building Emergency Plan for XXXXXX 2815 Commons Way Cincinnati, OH 45221 August 2016 University of Cincinnati Department of Public Safety Department a 2 Table of Contents A. Introduction B. Components
More informationFire Safety PROCEDURES January 2011
Fire Safety PROCEDURES January 2011 firesafety@uwo.ca Campus Phones EMERGENCY Dial 911 Fire Safety Service is the focal point for the coordinated administration of the University Fire Safety program and
More informationBerkeley Castle. Occupant Fire Safety
BERKELEY CASTLE 2 Berkeley Street, Suite 100, Toronto, Ontario, M5A 4J5 (Phone) 416-366-3704 (Fax) 416-366-3857 www.berkeleycastle.ca Berkeley Castle Occupant Fire Safety OCCUPANT FIRE SAFETY RESPONSIBILITIES
More informationFIRE AND LIFE SAFETY TRAINING
FIRE AND LIFE SAFETY TRAINING 1 Objectives General Information Emergency Evacuation Plans / Regulatory Requirements Notification Systems Emergency Exits and Fire Doors Electrical Safety Fire Prevention
More informationBeth Israel Deaconess Medical Center Environment of Care Manual
Beth Israel Deaconess Medical Center Environment of Care Manual Title: Interim Life Safety Measures (ILSM) Plan Policy #: EC39 Purpose: ILSM are fully adhered to in areas where the hospital/site occupants
More informationFIRE SAFETY ONLINE TRAINING
INTRODUCTION This Fire Safety Training module is designed to teach you preventive measures that will eliminate or minimize causes of fire or fire hazards in the workplace, and to teach you proper emergency
More informationFire Safety Plan University Stadium
Fire Safety Plan University Stadium Building # 53 Safety, Health, Environment Effective: March 14, 2018 Revised: December 2014 Revision: 1 Approved on: Pending Approval WILFRID LAURIER UNIVERSITY Contact:
More informationEmergency Procedures
FIRE AND LIFE SAFETY Building Systems Hayden Ferry Lakeside is state of the art and designed to offer maximum protection to its building occupants. The building is monitored 24 hours a day, seven days
More informationBETTENDORF PUBLIC LIBRARY INFORMATION CENTER EMERGENCY RESPONSE AND FACILITY CLOSURE POLICY
BETTENDORF PUBLIC LIBRARY INFORMATION CENTER EMERGENCY RESPONSE AND FACILITY CLOSURE POLICY PURPOSE This policy serves to provide guidelines for staff and patrons to be used in response to an event or
More informationEmergency Evacuation Plan: 232 King St.
Emergency Evacuation Plan: 232 King St. Effective Date: July 2003 Revisions: 0 Approved on: April 20, 2004 Table of Contents 1.0 Building Resources... 1 2.0 Human Resources... 2 3.0 Definitions... 3 4.0
More informationNY Fire Safety Institute
NY Fire Safety Institute Presents the FDNY Coordinator of Fire Safety and Alarm Systems Homeless Shelters (Premise Related) Certificate of Fitness F-80 Definitions and Terminology Established 1995 Preparing
More informationHotel Fire Safety for staff
Teaching Guide Hotel Fire Safety for staff Seattle Fire Department Fire Prevention Division Hotel Fire Safety Instructor Outline Introduction Goals: To ensure that hotel employees are knowledgeable in
More informationFire Response Plan - Code Red
Fire Response Plan - Code Red SUMMARY & PURPOSE The purpose of the Fire Response Plan Code Red is to provide guidelines for hospital personnel to follow during a Code Red. As more fully described below,
More informationENVIRONMENTAL HEALTH & SAFETY 6 East Dr., Amherst MA 01002-5000
AMHERST COLLEGE ENVIRONMENTAL HEALTH & SAFETY 6 East Dr., Amherst MA 01002-5000 Michael Zlogar April 11, 2001 Assistant Fire Chief Amherst Fire Department 68 North Pleasant St. Amherst, MA 01004 FIRE ALARM
More informationEMERGENCY ACTION, EVACUATION AND FIRE PREVENTION SAFETY PROGRAM
EMERGENCY ACTION, EVACUATION AND FIRE PREVENTION SAFETY PROGRAM REGULATORY STANDARD: OSHA - 29CFR1910.36-29CFR1910.38-29CFR1910.157-29CFR1910.165 NFPA-10 BASIS: The OSHA Emergency Action Planning and the
More informationCBD-233. Fire Alarm and Detection Systems
Page 1 of 5 CBD-233. Fire Alarm and Detection Systems Originally published August 1984. R.H.L. McEwen Fire alarm systems are normally required by building codes. In the case of new buildings, this is usually
More informationWORKPLACE WRITTEN PROCEDURES OH&S Regulation, Section 3
WORKPLACE WRITTEN PROCEDURES OH&S Regulation, Section 3 BASIC REQUIREMENTS Every worker must be made aware of the location of First Aid for the workplace and how to call the First Aid attendant, if one
More informationFire Safety Report 2014-2015. Fire Statistics 2013-2014-2015
Fire Safety Report 2014-2015 Fire Statistics 2013-2014-2015 Fire Log 2013-2014-2015 The New York Conservatory for Dramatic Arts Annual Fire Safety Report for Campus Housing 2014-2015 In August 2008, the
More informationWOLVERINE TOWER BUILDING INCIDENT RESPONSE TEAM (BIRT) MEMBER RESPONSIBILITIES
WOLVERINE TOWER BUILDING INCIDENT RESPONSE TEAM (BIRT) MEMBER RESPONSIBILITIES 1. Each floor must have at least one BIRT member and an alternate. 2. Names, phone numbers and changes of BIRT members should
More informationVOLUNTEER FIRE WARDENS
FIRE PRE-PLAN FACILITIES SERVICES VOLUNTEER FIRE WARDENS & EMERGENCY RESPONSE MEMBERS KEELE CAMPUS & GLENDON CAMPUS Ken Wong, P.Eng. SFPE. Mgr., Building Code / Fire Protection Code Compliance Facilities
More information1.1. EMERGENCY PROCEDURE On discovering a fire or being informed of an emergency;
Fire Action Plan FIRE ACTION PLAN SEStran aims to provide and maintain safe & healthy working conditions, equipment and systems of work for all our employees, and to provide such information, training
More informationbuild safe live safe
NYC Buildings Department 280 Broadway, New York, NY 10007 Robert D. LiMandri, Commissioner BUILDINGS BULLETIN 2012-009 Technical Supersedes: Issuer: None Thomas Fariello, R.A. First Deputy Commissioner
More informationRisk Engineering Guideline
www.hdi.global HDI Risk Consulting Risk Engineering Guideline Impairment of fire protection systems Basic protection systems should not be impaired without adequate replace compensation with provisions.
More informationFIRE PREVENTION & INVESTIGATION DIVISION 125 Idylwyld Drive South Saskatoon, SK S7M 1L4 Phone: (306) 975-2578 Fax: (306) 975-2589.
FIRE PREVENTION & INVESTIGATION DIVISION 125 Idylwyld Drive South Saskatoon, SK S7M 1L4 Phone: (306) 975-2578 Fax: (306) 975-2589 Bulletin 16-12 Fire Drills This guideline was developed to assist persons
More informationBemidji State University Building Emergency Preparedness Plan. Building Representatives. Contact Points. Building: Department: Room(s):
Bemidji State University Building Emergency Preparedness Plan Building: Department: Room(s): Preparation Date: Building Emergency Information Emergency Numbers E- 911 Address Internal Shelter Site External
More informationBold items are particular to the City of Euless
EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 2/12 Fire Chief Wes Rhodes Fire Marshal Paul Smith EFD-FMO 3-2 2009 International Fire & Building Code as Amended NFPA Standards Adopted
More informationFIRE SAFETY MANUAL. Table of contents can be found on the left side of this document.
FIRE SAFETY MANUAL Table of contents can be found on the left side of this document. 1. INTRODUCTION The University of Regina strives to preserve life and property by recognizing that a prompt, efficient
More informationFire Safety Requirements for Rehabilitation Agencies
DEPARTMENT OF HEALTH & HUMAN SERVICES Centers for Medicare & Medicaid Services 7500 Security Boulevard, Mail Stop C2-21-16 Baltimore, Maryland 21244-1850 Center for Clinical Standards and Quality/Survey
More informationSCHOOL FIRE AND LIFE SAFETY INSPECTION CHECKLIST
SCHOOL FIRE AND LIFE SAFETY INSPECTION CHECKLIST School Name: School Address: Town: Phone: Inspected By (Please Print): Inspection Organization Name: Inspector Phone: Date of Inspection: Building Name:
More informationMetropolitan Washington Airports Authority Office of Public Safety Fire & Rescue Department. Fire Code Enforcement Division
Metropolitan Washington Airports Authority Office of Public Safety Fire & Rescue Department Fire Code Enforcement Division Fire Protection System Impairment Requirements For Contractors and Service Personnel
More informationEmergency Procedures IF YOU DISCOVER A FIRE. Upon discovering a fire: the following steps are to be taken:
IF YOU DISCOVER A FIRE Upon discovering a fire: the following steps are to be taken: 1. Leave the fire area immediately removing any person in immediate danger. Make sure that doors to the affected area
More informationSPILL RESPONSE PROCEDURE
SPILL RESPONSE PROCEDURE Queen's University Spill Response Procedure May 2000 1 SOP-HAZMAT-01 1.0 Preamble This document outlines emergency spill response procedures as part of the overall Queen's University
More informationGeneral Fire Code Requirements Within Commercial Tenant Spaces
FIRE DEPARTMENT in cooperation with Scope: General Fire Code Requirements Within Commercial Tenant Spaces This handout is designed to assist owners, architects, contractors and others in understanding
More informationFire Safety Director On Site Examination for Hotels and Office Buildings F-58 Study Guide
Fire Safety Director On Site Examination for Hotels and Office Buildings F-58 Study Guide It is recommended that this guide be kept at all times at the Fire Command Center. This publication is provided
More informationUNIVERSITY OF TOLEDO
UNIVERSITY OF TOLEDO SUBJECT: INTERIM LIFE SAFETY MEASURES AND INFECTION Procedure No: LS-08-008 CONTROL PROCEDURE STATEMENT Interim life safety and infection control measures will be implemented to protect
More informationMesa Campus. Annual Fire Safety Report on Student Housing
Mesa Campus Annual Fire Safety Report on Student Housing Calendar Year Jan. 1 Dec. 31, 2014 Table of Contents Annual Security Report... 3 Fire Log... 3 Non Campus Student Housing Fire Safety Systems...
More informationFire Evacuation Procedures Network Building, 97 Tottenham Court Road, London, W1
Network Building Fire Safety Management Plan & Fire Evacuation Procedures Contents 1.0 Introduction 2.0 Means of Escape in Case of Fire 3.0 Means for Giving Warning in Case of Fire 4.0 Means for Fighting
More informationHow To Evacuate The University Of California Building
University of California Washington Center Emergency Evacuation Plan UC Washington Center 1608 Rhode Island Ave., NW Washington, DC 20036 Revised February 16, 2012 I. Purpose of the Plan II. Building Description
More informationThis document contains the text of Secretary of the State regulations concerning
1 This document contains the text of Secretary of the State regulations concerning Emergency Contingency Model Plan for Elections (Sections 9-174a-1 to 9-174a-34) This document was created by the Office
More informationFIRE ALARM SYSTEM SUBMITTAL CHECKLIST AND APPLICATION
PERMITS AND INSPECTIONS FIRE ALARM SYSTEM SUBMITTAL CHECKLIST AND APPLICATION 911 Assigned PROJECT LOCATION Subdivision: Lot: Blk: Sec: PROJECT New Construction Addition/Remodel Demolition Other: Number
More informationFIRE PREVENTION DEPARTMENT. CONTAINMENT/RESTORATION UCDHS ILSM Procedure For Water Damage Repair
FIRENET FIRE PREVENTION DEPARTMENT January 2014 CONTAINMENT/RESTORATION UCDHS ILSM Procedure For Water Damage Repair Purpose: After staff respond to and take those immediate actions necessary to stop a
More informationFire Safety Log Book
Fire Safety Log Book Company... Address........ Responsible Person. Competent Person. Date Started For Additional Information: Safety Management (UK) Ltd Holme Suite, Clawthorpe Hall Business Centre, Burton
More informationEMERGENCY MANAGEMENT PROCEDURE
EMERGENCY MANAGEMENT PROCEDURE STANDARD OPERATING PROCEDURES (SOP) INTRODUCTION All organisations involved in the Venue Management industry must have policies and procedures that aim to protect the health
More informationCITY OF HOUSTON HIGH-RISE OFFICE BUILDING FIRE SAFETY PLAN
CITY OF HOUSTON HIGH-RISE OFFICE BUILDING FIRE SAFETY PLAN DATE PROPERTY MANAGER ADDRESS Houston, TX _(Zip Code)_ PHONE NUMBER LIFE SAFETY IS THE GOAL OF THIS PLAN. ALL DUTIES CALLED FOR HEREIN SHOULD
More informationSARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS
SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS I. APPLICATION AND DEFINITIONS 1.01 Authorization for Standards 1.02 Application of Standards 1.03 Definitions
More informationFire Risk Assessment For Simple Premises
Fire Risk Assessment For Simple Premises Responsible Person (Employer or other person having control of the relevant premises) Company / Premises Name Address of Premises Postcode Primary Use of Premises
More information2015 Annual Fire Safety Report
2015 Annual Fire Safety Report The Higher Education Opportunity Act enacted on Aug. 14, 2008, requires institutions that maintain on-campus housing facilities to publish an annual fire safety report that
More informationLife Safety Code Enabling References
SUPPLEMENT 4 Life Safety Code Enabling References Editor s Note: Supplement 4 provides users of NFPA 72, National Fire Alarm and Signaling Code, with a summary of requirements from NFPA 101, Life Safety
More informationFire Safety Plan (No Fire Alarm System):
Fire Safety Plan (No Fire Alarm System): Fire Safety Plan No Fire Alarm System for: (Business Name) (Business Address) I,, have read and understand my responsibilities under this Fire Safety Plan. Signature
More informationTAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST
TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST In order to provide a comprehensive plan review in a timely manner, and to insure the design and installation of fire alarm systems
More informationFire Alarm Systems Permit Packet. City of Greer Fire Department
Fire Alarm Systems Permit Packet City of Greer Fire Department Updated July 2004 If you have any questions or comments regarding the information contained within; or of you need assistance interpreting
More informationFIRE SAFETY RECORD OF TESTS LOGBOOK
FIRE SAFETY RECORD OF TESTS LOGBOOK PREMISES ADDRESS: Responsible person AN INTRODUCTION TO YOUR LOG BOOK The Regulatory Reform (Fire Safety) Order 2005 requires the responsible person for a premises to
More informationAn inventory of hazardous materials used in your workplace will prove useful.
Introduction Fire Protection is an organized approach designed to prevent fires. In the event of a fire, a fire protection program will help prevent or minimize personal injuries, losses, and harm to the
More informationFire Alarm and Detection Systems And Central Station Monitoring Plan Submittal Guidelines
Fire Alarm and Detection Systems And Central Station Monitoring Plan Submittal Guidelines Red Oak Fire Rescue Office of the Fire Marshal 547 N. Methodist Red Oak, TX 75154 Phone: 469-218-7713 Fax: 468-218-7719
More informationSafe Operating Procedure
Safe Operating Procedure (Revised 07/09) HOT WORK PERMIT OPERATIONS (For assistance, please contact EHS at (402) 472-4925, or visit our web site at http://ehs.unl.edu/) Authority In recognition of the
More informationEMERGENCY PROCEDURES
EMERGENCY PROCEDURES In an Emergency Call 911 Using County Telephone System Call 9-911 Fresno County Sheriff 600-3111 Fresno County Security 600-6785 TABLE OF CONTENTS Introduction 3 Accidents 4 Serious
More informationColumbia University Medical Center. Policies and Procedures for Shutdowns and Modifications to Fire Alarm Systems and Fire Suppression Systems
Columbia University Medical Center Policies and Procedures for Shutdowns and Modifications to Fire Alarm Systems and Fire Suppression Systems 1. Modifications to Fire Alarm or Fire Suppression System A.
More informationRancho Cucamonga Fire Protection District Prevention Bureau Standard
Rancho Cucamonga Fire Protection District Prevention Bureau Standard Title: Fire Alarm and Monitoring Systems Standard # 9-3 Effective: May 2002 Number of Pages: 7 Revised: January 2014 INTENT The intent
More informationGreater Manchester Fire and Rescue Service
Greater Manchester Fire and Rescue Service Record of Fire Safety Equipment Testing CONTENTS 1. MEANS OF ESCAPE 2. FIRE WARNING AND AUTOMATIC FIRE DETECTION 3. FIRE EXTINGUISHERS AND HOSEREELS 4. EMERGENCY
More informationThe University of Texas at San Antonio Environmental Health, Safety and Risk Management
The University of Texas at San Antonio Environmental Health, Safety and Risk Management TO: FROM: UTSA Campus Community John DeLaHunt, MBA, ARM Risk & Life Safety Manager University Fire Marshal J. Brian
More informationFactors to Consider When Developing an Evacuation Plan
The following should be viewed only as suggestions: Factors to Consider When Developing an Evacuation Plan 1. You must identify your document with a specific title and explanation. Example: Evacuation
More informationWorkplace Fire Safety
Teaching Guide Workplace Fire Safety for staff Seattle Fire Department Fire Prevention Division Workplace Fire Safety Instructor Outline Introduction Goals: To ensure that employees are knowledgeable in
More informationArea of Rescue Assistance Communication System ADA Code Applicable excerpts:
Area of Rescue Assistance Communication System ADA Code Applicable excerpts: CONTENTS (Guidelines and Definitions) Page 1 Area of Rescue Assistance Requirements Page 2 Emergency Communication Equipment
More informationRequired Certification Documentation. Contractor's installation certification for range hood fire suppression systems.
OFFICE OF UNIVERSIT BUILDING OFFICIAL PROJECT/CONSTRUCTION MAGER: Sample Manager Required Aboveground only Required Certification Documentation Contractor s material and test certifications for both above
More informationLOUISVILLE FIRE PROTECTION DISTRICT 895 West Via Appia, Louisville, Colorado 80027 303-666-8809
LOUISVILLE FIRE PROTECTION DISTRICT 895 West Via Appia, Louisville, Colorado 80027 303-666-8809 Contractor s Checklist and Installation Guide TABLE OF CONTENTS Fire Protection Narrative........... 3 Fire
More informationEducational. Educational-Existing 1/28/2014. OCCUPANT LOADS [no change] Application. Application
February 2014 Code Requirements and Inspections in Educational Occupancies Presented By: Barry W. Rickert Douglas M. Schanne Fire Marshal Training Program Supervisor Office of Education & Data Management
More informationCity of Bettendorf Fire Alarm System Requirements
City of Bettendorf Fire Alarm System Requirements Section 907 of the 2009 Edition of the International Fire Code (IFC) and Section 10-7-3 of the Municipal Code provide fire alarm requirements. IFC Section
More informationFIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS. 1. All Floors (inspect from top floor to basement): Yes No
General Inspection FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS 1. All Floors (inspect from top floor to basement): Yes are fire exits and directional signs properly illuminated? is the emergency
More informationEmergency Procedures Manual For MGEX Building Tenants
March 2011 Emergency Procedures Manual For MGEX Building Tenants Emergency Contacts Emergency/Security... ( 612) 250-3269 Police...911 Fire...911 Paramedics...911 Poison Control...1-800-222-1222 MGEX Property
More informationHERNANDO COUNTY FIRE ALARM GUIDELINES
HERNANDO COUNTY FIRE ALARM GUIDELINES To be used for all commercial building fire alarm system plan review. The procedures set forth in this document are the minimum requirements necessary to ensure a
More informationISLE OF MAN FIRE & RESCUE SERVICE FIRE PRECAUTIONS LOGBOOK. Website www.iomfire.com
ISLE OF MAN FIRE & RESCUE SERVICE FIRE PRECAUTIONS LOGBOOK Website www.iomfire.com ADDRESS OF PREMISES FIRE CERTIFICATE No. (where applicable).. LOCATION OF LOG BOOK. CONTENTS OF LOG BOOK Useful telephone
More informationThe terms hazard and risk are often used, which we define as the following:
Fire Safety Last updated in October 2010 This information sheet aims to give safety reps a basic understanding of fire safety and fire risk assessments under the current law. More detailed information
More informationMichael Catalano 24 Nassau Avenue, Islip NY 11751 Phone (631) 224-5477 Chief Fire Marshal fireprevention@islipny.gov Fax (631) 224-5458
OFFICE OF THE FIRE MARSHAL BUREAU OF FIRE PREVENTION Michael Catalano, Phone Chief Fire Marshal fireprevention@islipny.gov Fax To whom it may concern: Enclosed please find the NFPA 72 forms needed for
More informationFire Policy and Procedures. Cañada Blanch Spanish School
Fire Policy and Procedures Cañada Blanch Spanish School SUMMARY 1. Introduction (p. 3) 2. Roles and responsibilities (p. 3) -- Headteacher -- Fire Team -- All staff -- Contractors 3. Fire procedures (p.
More informationFIRE SAFETY PLAN FOR KITCHENER, ONTARIO
FIRE SAFETY PLAN FOR KITCHENER, ONTARIO Additional information of fire safety plans may be found at our website at www.kitchener.ca/fire.htm. Before submission, please read and change all sections to address
More informationFIRE SAFETY PRECAUTIONS
FIRE SAFETY PRECAUTIONS LOG BOOK PLEASE KEEP AVAILABLE 1 Business Name Premises Information Building / Unit Number Property Name Road: (Address Line 1) (Address Line 2) Locality: Town: Post Code: Name
More informationFire Coordinator Course. Office of Safety, Health & Environment
Fire Coordinator Course Office of Safety, Health & Environment COURSE OBJECTIVES To impart sufficient knowledge to personnel appointed as building Fire Safety Coordinator so that they are able to perform
More informationEMERGENCY ACTION AND FIRE PREVENTION PLAN
Sample Written Safety Program For EMERGENCY ACTION AND FIRE PREVENTION PLAN Page 1 EMERGENCY ACTION AND FIRE PREVENTION PLAN (YOUR COMPANY NAME) EMPLOYEE EMERGENCY AND FIRE PREVENTION PLANS Emergencies
More informationCITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS
CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS PROPERTY ADDRESS (BRT Address Required) TESTING CONTRACTOR (Name and Address) License No. ANNUAL
More informationCHANGES IN NFPA 72 NATIONAL FIRE ALARM CODE 1999 2002
CHANGES IN NFPA 72 NATIONAL FIRE ALARM CODE 1999 2002 Three new chapters were added. What was chapter 1 in 1999 was reorganized into chapters 1 (Fundamentals), 2 (Referenced Publications), and 3 (Definitions).
More informationCAL FIRE/San Luis Obispo County Fire Fire Prevention Bureau
CAL FIRE/San Luis Obispo County Fire Fire Prevention Bureau g GUIDELINE FOR SAFETY REQUIREMENTS FOR HAUNTED HOUSES PURPOSE This guide is intended to provide safety standards and regulations for the construction
More information