Lighthouse Engineering, L.L.C.

Size: px
Start display at page:

Download "Lighthouse Engineering, L.L.C."

Transcription

1 Monday, May 07, 2012 Lighthouse Engineering, L.L.C. Michael Gandy, P.E. Registered Professional Engineer (TX: 95672) Registered Engineering Firm (F: 9334) Phone: Fax: Website: TO: Our Client RE: Initial Engineering Evaluation Foundation Performance Anywhere in North Texas The following report constitutes the engineering opinion requested on the foundation of the subject residence. This report has been prepared in general accordance with the requirements of a Level B survey as defined by the Texas Chapter of the American Society of Civil Engineers (ASCE) and the Texas Board of Professional Engineers ( This report is provided for the exclusive use of the person or persons this report was prepared for as shown above. We have no contractual relationship with, or obligation to, any party other than the party for whom this report was prepared. The purpose of this inspection was to evaluate the foundation and determine what, if any, foundation repairs are necessary. The foundation was visually inspected and a floor elevation survey was performed. The opinions contained herein are based on the experience and judgment of the writer, as well as conditions observed without taking soil samples, performing plumbing leak tests, removing floor or wall coverings, or performing invasive tests or procedures. The opinions offered herein are based solely on the observations made at the time of the inspection, and do not take into consideration any changes in the condition of the foundation after that date. This report does not predict or warrant the future performance of the subject foundation. You are encouraged to review the Agreements and Limitations attached to the end of this report for other important limitations and standard recommendations. Observations This structure is a two - story wood framed structure with brick veneer and siding on the exterior. The home has a hip roof and composition shingles. The interior walls are drywall with various finishes over the drywall including texture, paint and wallpaper. The foundation is a pier and beam. The home was constructed in 1985 per the Dallas County Appraisal District Records. All directions in this report are annotated by left, right, front and rear as if looking at the front door Lighthouse Engineering Page 1 of 5

2 Lighthouse Engineering, L.L.C. Observations and Discussions: 1. Jason Conklin, EIT (under the direct supervision of Mike Gandy, PE) physically inspected the above referenced residence to make an evaluation of the current foundation performance and to offer recommendations for repair, if needed. I performed a Level B engineering analysis as defined by the Texas Chapter of the ASCE. I made careful observations of the interior and exterior for signs of drainage and foundation distress. I entered and accessed all of the crawl space areas. I performed an interior elevation survey denoted below and as shown on Drawing Pictures 1 and 2: The structure of the foundation beneath the crawl space access area is in poor condition. Multiple bucket piers were noted below make-shift block piers. The soils throughout the home were generally dry. Some moist areas were identified towards the front of the home. Pictures 3 and 4: The foundation contains a mix of pier types including poured-in-place piers, jack supports (at right of Picture 3), block and base, and bucket piers. The lumber beneath the home is also mixed in size and support installation. Numerous beams were noted to be bracketed to the concrete grade beam and lag-bolted together. The main beams generally run front left to right (when looking at the home) but change direction towards the rear half of the home (beams run front to back). This is clearly depicted on Drawing no Lighthouse Engineering Page 2 of 5

3 Lighthouse Engineering, L.L.C. 4. Picture 5: Close-up of end bracketed main beam. Picture 6: All jack supports were noted to be leaning off-center of the beam above jacks. A block and base pier is pictured to the right of the jack support. The pier is not in direct contact with the beam lumber. 5. Picture 7: Some poor attempts at foundation repair were made previously, possibly during a home remodel. The chicken wire mesh was installed to contain fiberglass batt insulation. Picture 8: Beneath the kitchen area most of the existing 2 x6 wood joists were noted to be joist hanger supported. This is recommended in the area beneath the master bathroom where sistering the existing joists is recommended. See Drawing no for the location of these joists to be sistered. 6. Picture 9: Access to the rear portions of the home were difficult due to numerous large ducts and plenums. The master bathroom plumbing can be seen towards the left of the photo Lighthouse Engineering Page 3 of 5

4 Lighthouse Engineering, L.L.C. Picture 10: The area beneath the master bathroom where sistering the existing joists is recommended. The current joists are 2 x8 joists with 2 x4 lumber sistered to one side of the 2 x8. Some joists were split and/or notched from plumbing work. Interior Elevation Survey Interior floor elevations were taken with a Technidea Pro-2000 Ziplevel. Elevations were recorded to the nearest.1-inch throughout the home. A benchmark of was established in the central hallway area and is shown on drawing no with a star. An adjustment was made for floor coverings if they were a different elevation than the floor covering at the benchmark location. Elevation differentials varied by a maximum of 1.5 vertical inches in fifty (50) horizontal feet. It should be noted that the elevation measurements include effects of elevation variation in the original construction which normally are 0.6 inches to 1.0 inches. A sketch of the house with the elevations is attached as Drawing Recommendations 1. Install (27) new 24 round by 24 high and at least 24 deep (below soil level) concrete Sonotube poured in-place piers. 2. Remove and replace approximately (61) linear feet (LF) of 2 x8 rim joist with new pressure treated (PT) lumber. 3. Remove and replace approximately (137) linear feet (LF) of 2 x4 sill plate with new pressure treated (PT) lumber. 4. Remove the existing main beam located near the front of the home and replace with approximately (38) linear feet (LF) of 3-2 x8 main beam using new pressure treated (PT) lumber. 5. Remove and replace with approximately (187) linear feet (LF) of 2-2 x8 main beam using new pressure treated (PT) lumber. 6. Sister approximately (12) 2 x8 x12 floor joists with new pressure treated (PT) lumber. Install (24) Simpson Strong-Tie LU26-2/4-16d face mount joist hangers beneath the existing and new joists. 7. Support approximately (190) square feet (SF) of subfloor with new pressure treated (PT) plywood lumber. 8. Re-shim and re-level all piers with new metal shims. 9. Install a surface drainage system to include (10) 12 x12 catch basins and 4 drain line. Direct both lines to discharge at the front street. Tie in all existing gutter downspouts to the new surface drainage system. Set catch basins slightly below soil level and contour soils to direct water towards catch basins. 10. Perform a post lift plumbing leak test and repair any plumbing leaks that are found Lighthouse Engineering Page 4 of 5

5 Lighthouse Engineering, L.L.C. Agreements and Limitations Use of this report for any reason implies consent to all agreements and limitations of this report. This report is the professional opinion of Lighthouse Engineering, LLC and is based upon a limited evaluation of the property. This report is provided for the exclusive use of the addressee. We have no contractual relationship with, or obligation to, any party other than the addressee of this report. This report does not constitute a structural warranty or performance contract with the purchaser of this report to or with any other party. It only states conditions observed at the time of the inspection. The evaluation of the property included a visual examination of the exposed interior and exterior finishes of the structure and the ground surfaces adjacent to the structure and to the taking of relative floor elevations. The taking and testing of soil samples was not included. Unless written in the report, the original design drawings and any design conditions were not known. Determination of construction to Building Code is best done during the original construction and is not a part of this evaluation. Testing for plumbing leaks was not performed but is recommended after foundation work is performed. It is possible that future repairs could be required for the subject foundation. This evaluation only addresses the current condition of the foundation. Lighthouse Engineering, LLC does not offer or imply any warranty for the repairs or for the repair company s acts or omissions or for any other person conducting the repairs. The fee collected is for this inspection only. Additional engineering services are available at an additional cost. Requests for these services must be made in a timely manner before commencement of work. Please contact this office for additional inspection scheduling and fee arrangements. Sincerely, Michael Gandy, P.E. 5/7/2012 Registered Engineering Firm F Lighthouse Engineering Page 5 of 5

6 THIS REPORT DOES NOT PREDICT OR WARRANT THE FUTURE PERFORMANCE OF THE FOUNDATION F/P MONO 0.1 GAR NON-MONO PATIO PRE-LIFT ELEVATION MEASUREMENTS MAY 4, 2012 Lighthouse Engineering BENCHMARK ELEVATION 0 INCHES ELEVATIONS ARE SHOWN IN TENTHS OF AN INCH Michael Gandy, P.E. Phone: MikeGandy@LighthouseEng.com Registered Engineering Firm F-9334

7 THIS REPORT DOES NOT PREDICT OR WARRANT THE FUTURE PERFORMANCE OF THE FOUNDATION LOCATION OF EXISTING PIERS LOCATION OF NEW PIERS REMOVE AND REPLACE APPROX. (61) LF OF 2"X8" RIM JOIST WITH NEW NON-MONO PATIO REMOVE AND REPLACE APPROX. (61) LF OF 2"X4" SILL PLATE WITH NEW REMOVE EXISTING BEAM AND REPLACE WITH APPROX. (38) LF OF 3-2"X8" MAIN BEAM WITH NEW MONO GAR X X X X X X X X X X X X F/P X X X X X X X X REMOVE AND REPLACE APPROX. (52) LF OF 2-2"X8" MAIN BEAM WITH NEW. VERY DIFFICULT ACCESS. SUPPORT APPROX. (190) SF OF SUBFLOOR WITH NEW PRESSURE TREATED PLYWOOD LUMBER REMOVE AND REPLACE APPROX. (76) LF OF 2"X4" SILL PLATE WITH NEW SISTER APPROX. (24) - 2"x8"x8' FLOOR JOISTS WITH NEW PT LUMBER. INSTALL (36) SIMPSON STRONG-TIE LUS d FACE MOUNT JOIST HANGERS REMOVE EXISTING BEAM AND REPLACE WITH APPROX. (135) LF OF 3-2"X8" MAIN BEAM WITH NEW INSTALL (27) NEW CONC. SONOTUBE POURED IN-PLACE PIERS. BASES 24" x 24" X 24" SET BELOW SOIL LEVEL. USE 12" DIAMETER SONOTUBE. USE (2) LAYERS OF (4) #3 REBAR TIED AND (2) #3 EXTENDED INTO SONOTUBE. USE 3000 PSI CONCRETE. RE-SHIM AND RE-LEVEL ALL PIERS. Lighthouse Engineering BENCHMARK ELEVATION 0 INCHES ELEVATIONS ARE SHOWN IN TENTHS OF AN INCH Michael Gandy, P.E. Phone: MikeGandy@LighthouseEng.com Registered Engineering Firm F-9334

8 THIS REPORT DOES NOT PREDICT OR WARRANT THE FUTURE PERFORMANCE OF THE FOUNDATION NON-MONO PATIO F/P MONO GAR MAY 4, 2012 INSTALL A SURFACE DRAINAGE SYSTEM TO INCLUDE (10) 12"X12" CATCH BASINS AND 4" DRAIN LINE. DIRECT BOTH LINES TO DISCHARGE AT FRONT STREET. TIE ALL EXISTING GUTTER DOWNSPOUTS TO THE NEW SURFACE DRAINAGE SYSTEM. SET CATCH BASINS SLIGHTLY BELOW SOIL LEVEL AND CONTOUR SOILS TO DIRECT WATER TOWAR CATCH BASINS. ADD EXTRA SOIL ALONG THE SIDE OF THE HOME Lighthouse Engineering BENCHMARK ELEVATION 0 INCHES ELEVATIONS ARE SHOWN IN TENTHS OF AN INCH Michael Gandy, P.E. Phone: MikeGandy@LighthouseEng.com Registered Engineering Firm F-9334

Lighthouse Engineering, L.L.C.

Lighthouse Engineering, L.L.C. Registered Engineering Firm (F: 9334) Phone: 214-577-1077 Fax: 214-224-0549 Website: www.lighthouseeng.com Email: Office@LighthouseEng.com Thursday, September 04, 2014 TO: Our Client RE: Engineering Evaluation

More information

Lighthouse Engineering, L.L.C.

Lighthouse Engineering, L.L.C. Registered Engineering Firm (F: 9334) Phone: 214-577-1077 Fax: 214-224-0549 Website: www.lighthouseeng.com Email: Office@LighthouseEng.com Thursday, September 04, 2014 TO: Our Client RE: Initial Engineering

More information

Lighthouse Engineering, L.L.C.

Lighthouse Engineering, L.L.C. Wednesday, August 20, 2014 Lighthouse Engineering, L.L.C. Michael Gandy, P.E. Registered Professional Engineer (TX: 95672) Registered Engineering Firm (F: 9334) Phone: 214-577-1077 Fax: 214-224-0549 Website:

More information

National Home Builder - Name Wednesday, August 20, 2014 Regional Customer Care Manager 1234 Main Street Houston, Texas 77067

National Home Builder - Name Wednesday, August 20, 2014 Regional Customer Care Manager 1234 Main Street Houston, Texas 77067 Lighthouse Engineering, L.L.C. Michael Gandy, P.E. Registered Professional Engineer (TX: 95672) Registered Engineering Firm (F: 9334) Phone: 214-577-1077 Fax: 214-224-0549 Website: www.lighthouseeng.com

More information

October 30, 2014. Mr. & Mrs. Daniel Vick 101 Southwind Cove Benton, AR. Report of Findings, Structural Investigation, Benton, Arkansas, Dear Mr.

October 30, 2014. Mr. & Mrs. Daniel Vick 101 Southwind Cove Benton, AR. Report of Findings, Structural Investigation, Benton, Arkansas, Dear Mr. 117 S. Market St. Benton, AR 72015 * 501-315-2626 * Fax 501-315-0024 October 30, 2014 Mr. & Mrs. Daniel Vick 101 Southwind Cove Benton, AR Re: Report of Findings,, Benton, Arkansas, Dear Mr. Vick: This

More information

Simpson Engineering A state licensed engineering firm F-1607

Simpson Engineering A state licensed engineering firm F-1607 Simpson Engineering A state licensed engineering firm F-1607 4126 Allencrest 13901 Midway Lane, Dallas, Road, Texas Ste.102-136 75244 Telephone: 214-351-1637 Dallas, - Fax: TX 214-351-1639 75244-4388 Telephone:

More information

HEDDERMAN ENGINEERING, INC. www.heddermanengineering.com Office 281-355-9911, Fax 281-355-9903 office@heddermanengineering.com

HEDDERMAN ENGINEERING, INC. www.heddermanengineering.com Office 281-355-9911, Fax 281-355-9903 office@heddermanengineering.com HEDDERMAN ENGINEERING, INC. www.heddermanengineering.com Office 281-355-9911, Fax 281-355-9903 office@heddermanengineering.com, 2011 TO: Mr. REF: CONDITION OF PROPERTY SURVEY Dear Mr. : At your request,

More information

Foundation Evaluation Report for PROPERTY ADDRESS Houston, Texas 77089. August 30, 2012. Prepared for:

Foundation Evaluation Report for PROPERTY ADDRESS Houston, Texas 77089. August 30, 2012. Prepared for: A Full Service Real Estate Inspection & Engineering Firm for Houston, Texas 77089 August 30, 2012 Prepared for: CLIENT S NAME MAILING ADDRESS Houston, Texas 77089 Prepared by: Charles J. Jenkins, P.E.

More information

PROFESSIONAL ENGINEERING INSPECTIONS, INC.

PROFESSIONAL ENGINEERING INSPECTIONS, INC. PROFESSIONAL ENGINEERING INSPECTIONS, INC. P. O. BOX 271492 HOUSTON, TEXAS 77277 Registered Engineering Firm #1503 http://www.profengineering.com (713) 664-1264 July 8, 2004 Mr. Simple Samson 2831 Octoberfest

More information

Vision Home Inspection

Vision Home Inspection Vision Home Inspection 324 Rams Run Shepherdsville KY 40165-7877 Inspector: James McFadden Property Inspection Report Client(s): Property address: Inspection date: View report summary This report is the

More information

Building Condition Assessment: 109-111 North Howard Street Baltimore, Maryland

Building Condition Assessment: 109-111 North Howard Street Baltimore, Maryland KPA The Joint Venture of EBA Engineering, Inc. and Kennedy Porter & Associates, Inc. 4813 Seton Drive, Baltimore, MD 21215 Phone: (410-358-7171) Fax: (410)358-7213 Building Condition Assessment: Baltimore,

More information

Estimated Cost of Repair

Estimated Cost of Repair 1 Applicant: Property: Home: Business: Assessor: Applicant Number: Type of Loss: Hurricane Date Contacted: 1/18/2014 Date of Loss: 10/29/2012 Date Received: 1/14/2014 Date Inspected: 2/4/2014 Date Entered:

More information

Superform Products Ltd.

Superform Products Ltd. TYPICAL CORNER REINFORCING NOTE : SEE ENGINEERED REBAR SCHEDULES SUPPLIED BY THE MANUFACTURER STEEL REINFORCEMENT WALL CORNER 90 Copyright 2012 Sept. 2012 5.1.1 Rebar Spacing 6" 12" Max. Load LB./FT. 2000

More information

How To Repair A House

How To Repair A House Assessing Structural Damages Please note-this presentation is only intended to be used as a basic educational tool and is by no means all encompassing. Each property should be treated on a case by case

More information

Foundation Experts, LLC Specializes in Foundation Repair and Waterproofing

Foundation Experts, LLC Specializes in Foundation Repair and Waterproofing 1 Most basements show some signs of leaking and cracking. Through the years, problems with water, poor soils, grading, drainage and possible settling affect the integrity of a basement. Being able to recognize

More information

Additions and Alterations

Additions and Alterations Additions and Alterations Addition and alteration construction is a miscellaneous grouping of home improvement and renovation projects that are generally geared toward the enhancement of an existing principal

More information

Residential Foundations and Basements

Residential Foundations and Basements Residential Foundations and Basements Disclaimer All of the following information is based on the 2006 International Residential Code with Kentucky Amendments. As some information is paraphrased, article

More information

Foundation Repair Fundamentals And how they relate to the Real Estate Industry in the DFW Area

Foundation Repair Fundamentals And how they relate to the Real Estate Industry in the DFW Area Foundation Repair Fundamentals And how they relate to the Real Estate Industry in the DFW Area Presented by MBRGFR.COM www.mbrgfr.com Office: 817-469-1090 E-mail: mbr@mbrgfr.com Objectives: I: Understanding

More information

Structure Survey Findings:

Structure Survey Findings: Structure Survey Findings: Visible portions of the following were observed: foundations; structure to walls, columns, floors, roofs, overhang posts, and columns; attached or firmly abutting decks, balconies,

More information

REQUIREMENTS FOR SUBMITTING PLANS FOR NEW CONSTRUCTION

REQUIREMENTS FOR SUBMITTING PLANS FOR NEW CONSTRUCTION RESIDENTIAL: REQUIREMENTS FOR SUBMITTING PLANS FOR NEW CONSTRUCTION 2 COMPLETE SETS OF PRINTS WITH ENGINEERS STAMP ON FOUNDATION PLAN INCLUDING ELECTRICAL, PLUMBING, ETC. SITE PLAN SHOWING HOUSE LOCATION

More information

Basement & Foundation Damage

Basement & Foundation Damage Basement & Foundation Damage Please note-this presentation is only intended to be used as a basic educational tool and is by no means all encompassing. Each property should be treated on a case by case

More information

REPORT OF FLOOR ELEVATIONS On Property Located at: Bordeaux Village Dallas TX JOB #11766

REPORT OF FLOOR ELEVATIONS On Property Located at: Bordeaux Village Dallas TX JOB #11766 520 Central Parkway East, Ste. 112 Plano TX 75074 T: 972.994.0747 F: 972.692.5713 www.jensenengineers.com CCMC Ms. Michele Drain 2301 W. Plano Pkwy Suite 100 Plano TX 75075 REPORT OF FLOOR ELEVATIONS On

More information

Steve Brinkman Alain Pinel Realtors 167 S San Antonio Road Los Altos, CA 94022 RE: Foundation Inspection for 162 Del Monte Ave. Los Altos, CA 94022

Steve Brinkman Alain Pinel Realtors 167 S San Antonio Road Los Altos, CA 94022 RE: Foundation Inspection for 162 Del Monte Ave. Los Altos, CA 94022 M G C O N S T R U C T O R S & E N G I N E E R S, I N C. I N S P E C T O R S E N G I N E E R S B U I L D E R S C A L I F O R N I A E N G I N E E R I N G A N D B U I L D I N G L I C E N S E A / B 6 4 2 0

More information

Page & Turnbull imagining change in historic environments through design, research, and technology

Page & Turnbull imagining change in historic environments through design, research, and technology DCI+SDE STRUCTURAL EVALUATIONS OFFICE BUILDING, TOOL SHED & WATER TANK, AND BLACKSMITH & MACHINE SHOP BUILDINGS SAN FRANCISCO, CALIFORNIA [14290] PRIMARY PROJECT CONTACT: H. Ruth Todd, FAIA, AICP, LEED

More information

HEDDERMAN ENGINEERING, INC. 3011 Carrie Cove Ct., Spring, TX 77386 281-355-9911, fax 281-355-9903 Tim@heddermanengineering.com

HEDDERMAN ENGINEERING, INC. 3011 Carrie Cove Ct., Spring, TX 77386 281-355-9911, fax 281-355-9903 Tim@heddermanengineering.com HEDDERMAN ENGINEERING, INC. 3011 Carrie Cove Ct., Spring, TX 77386 281-355-9911, fax 281-355-9903 Tim@heddermanengineering.com 2007 TO: Mr. REF: CONDITION OF PROPERTY SURVEY Dear Mr. : At your request,

More information

CLIENT. Inspection Report. 271 Front St. Alert Bay, B.C. Island Building Inspections V ANCOUVER I SLAND B. C.

CLIENT. Inspection Report. 271 Front St. Alert Bay, B.C. Island Building Inspections V ANCOUVER I SLAND B. C. CLIENT Inspection Report 271 Front St. Alert Bay, B.C. Island Building Inspections 2013 V ANCOUVER I SLAND B. C. Elevation Photos For the Property at 271 Front Street Alert Bay, BC ELEVATION PICTURES Front

More information

I NI NP R Inspected Items

I NI NP R Inspected Items 6/ /07 The Inspection of the property listed above must be performed in compliance with the rules of TREC. The inspection is of conditions which are present and visible at the time of the inspection, and

More information

STRUCTURAL ASSESSMENT. Full Metal Jacket Building 0 Prince Street, Alexandria, VA

STRUCTURAL ASSESSMENT. Full Metal Jacket Building 0 Prince Street, Alexandria, VA STRUCTURAL ASSESSMENT FOR Full Metal Jacket Building 0 Prince Street, Prepared by: ALPHA CORPORATION (Alpha) 1850 S. Loudoun Street, Suite 200 Winchester, VA 22601 540-723-0704 September 22, 2010 J. Michael

More information

INSPECTION PROPERTY ADDRESS: Fort Bend County, Texas

INSPECTION PROPERTY ADDRESS: Fort Bend County, Texas 5006 Cherry Ridge Road Richmond, Texas 77406 281-342-9944 harris31@sbcglobal.net INSPECTION PROPERTY ADDRESS: INSPECTION PERFORMED FOR: XXXX Drive Fort Bend County, Texas Mr. and Mrs. New Construction

More information

Building Condition Assessment Report

Building Condition Assessment Report Building Condition Assessment Report Asset C3c - Oak Terrace Cottage 121 Address Riverview Lands, 2601 Lougheed Highway, Coquitlam, BC. V5C 4J2 Construction Year Size (Gross Floor Area) 1920. 2,553 Sq.Ft.

More information

Residential Deck Safety, Construction, and Repair

Residential Deck Safety, Construction, and Repair Juneau Permit Center, 4 th Floor Marine View Center, (907)586-0770 This handout is designed to help you build your deck to comply with the 2006 International Residential Building code as modified by the

More information

5006 Cherry Ridge Road Richmond, Texas 77406 281-342-9944 harris31@sbcglobal.net LIMITATIONS AND DISCLAIMERS

5006 Cherry Ridge Road Richmond, Texas 77406 281-342-9944 harris31@sbcglobal.net LIMITATIONS AND DISCLAIMERS 5006 Cherry Ridge Road Richmond, Texas 77406 281-342-9944 harris31@sbcglobal.net INSPECTION PROPERTY ADDRESS: INSPECTION PERFORMED FOR: XXXX Court Richmond, Texas Mr. Foundation Concerns INSPECTION DATE:

More information

Inspection Item COMMENTS

Inspection Item COMMENTS APPENDIX 9 AFFORDABLE HOUSING PROGRAM INSPECTION CHECKLIST Participating Jurisdiction: Homeowner Name: Assisted Property Address: Date of Physical Inspection of Property: Total Square Footage of Property:

More information

Mark Cramer Inspection Services, Inc.

Mark Cramer Inspection Services, Inc. Mark Cramer Inspection Services, Inc. 492 Twentieth Avenue, Indian Rocks Beach, FL 34635-2970 (727) 595-4211 Fax (727) 596-7583 Certified Member #12085 American Society of Home Inspectors Construction

More information

A RESIDENTIAL PROPERTY LOCATED AT xxxxxxxxxxxxxx, PASADENA, TX 77505

A RESIDENTIAL PROPERTY LOCATED AT xxxxxxxxxxxxxx, PASADENA, TX 77505 REPORT # SFR12- DATE OF INSPECTION: xx/xx/xxxx (04:30PM) A RESIDENTIAL PROPERTY LOCATED AT xxxxxxxxxxxxxx, PASADENA, TX 77505 FOR MR. & MRS. xxxxxxxxxxxxxx (CLIENT) BY: JITENDRA M. VARMA, Licensed Professional

More information

Report on Sanctuary/Chancel Crawl Space Inspection. St. John in The Wilderness, 2896 Old Lakeshore Road Bright s Grove. Project No.

Report on Sanctuary/Chancel Crawl Space Inspection. St. John in The Wilderness, 2896 Old Lakeshore Road Bright s Grove. Project No. Report on Sanctuary/Chancel Crawl Space Inspection St. John in The Wilderness, 2896 Old Lakeshore Road Bright s Grove Project No. E112056 1. Background St. John in the Wilderness (SJITW) is considering

More information

SUMMARY REPORT THE BOTTOM LINE. Electrical. Report Number: 1860. Inspection Date: Saturday, February XX, XXXX

SUMMARY REPORT THE BOTTOM LINE. Electrical. Report Number: 1860. Inspection Date: Saturday, February XX, XXXX SUMMARY REPORT Report Number: 1860 Inspection Date: Saturday, February XX, XXXX Property Address: XX XXXXX XXX Toronto, ON XXX XZX Client Name: Xxxx Xxxxxxxxxxxxx Prepared by: Andrew Marioselva BSc,CHI

More information

LITITZ MUTUAL INSURANCE COMPANY 2 North Broad Street Lititz, Pennsylvania - MAIN OFFICE -

LITITZ MUTUAL INSURANCE COMPANY 2 North Broad Street Lititz, Pennsylvania - MAIN OFFICE - The original section of this building was constructed in 1941. The exterior walls are built of good quality stone. In the early 1980 s a similar addition was added to the north elevation. The exterior

More information

HomeSpec REPORT SUMMARY

HomeSpec REPORT SUMMARY HomeSpec 04/25/2007 Ms. Rachel Trujeque Re: 13038 West Plum Road Lot #1225 - Peoria, AZ. 85383 - Pre Drywall Inspection Dear Ms. Trujeque, At your request, a visual pre drywall inspection of the above

More information

Proposed Minimum Subterranean Termite Treatment Standards

Proposed Minimum Subterranean Termite Treatment Standards Proposed Minimum Subterranean Termite Treatment Standards Introduction This document is intended to serve as a model for states considering the adoption of standards for soil application of termiticides.

More information

C I T Y O F P E A R S A L L

C I T Y O F P E A R S A L L The Largest City Between San Antonio and Laredo COMMUNITY DEVELOPMENT C I T Y O F P E A R S A L L A Business-Friendly, Family-Oriented Community Building Department Application Information (Please read

More information

BUILDING ASSESSMENT QUESTIONNAIRE. B. TENANTS Is there more than one tenant in the building? YES

BUILDING ASSESSMENT QUESTIONNAIRE. B. TENANTS Is there more than one tenant in the building? YES Department of Health and Human Services, Division of Public Health Occupational and Environmental Epidemiology Branch 1912 Mail Service Center, Raleigh, North Carolina 27699-1912 BUILDING ASSESSMENT QUESTIONNAIRE

More information

Fig. 2 WALL-TO-WALL PANEL CONNECTIONS CORNER WALL CONNECTION

Fig. 2 WALL-TO-WALL PANEL CONNECTIONS CORNER WALL CONNECTION SIPS SCREWS WITH MINIMUM 1" PENETRATION IN WOOD MEMBER IN SIP WALL PANEL CONNECTED TO @ 24" O.C. MAXIMUM OUTSIDE SKIN EACH SIDE OF FRAMING TYP. AS RECOMMENDED BY FOAM CORE AS EACH SIDE OF FRAMING TYP.

More information

Typical Finished Basement Details

Typical Finished Basement Details Fauquier County, Virginia Typical Finished Basement Details Based on the 2012 International Residential Code Finished basements must be constructed in conformance with this document. For requirements,

More information

Photos showing the change in condition from 2006 to 2012 are located in Appendix A.

Photos showing the change in condition from 2006 to 2012 are located in Appendix A. January 27, 2012 Ms. Theresa Gallavan Economic Development Director City of Lompoc 100 Civic Center Plaza Lompoc, California 93436 RE: Lompoc Theater Limited Visual Condition Assessment Dear Theresa: Representatives

More information

14 September 2015. Sarah Zorn Planning and Economic Development 25 West Fourth Street, Ste. 1100 St. Paul, MN 55102

14 September 2015. Sarah Zorn Planning and Economic Development 25 West Fourth Street, Ste. 1100 St. Paul, MN 55102 Sarah Zorn Planning and Economic Development 25 West Fourth Street, Ste. 1100 St. Paul, MN 55102 Project No.: 15538.00 Re: Structural Condition Review of the building at 700 4 th St. E. Dear Sarah: We

More information

INSTALLATION OF A BAY WINDOW

INSTALLATION OF A BAY WINDOW INSTALLATION OF A BAY WINDOW Installation of a Bay Window These instructions relate to the replacement of an existing bay window or replacement of a straight window with a new bay window, in an opening

More information

Home Inspection Report

Home Inspection Report Home Inspection Report Report Number: 144 For The Property Located On: 123 Any Street 27587 Prepared For Exclusive Use By: Mr. Sample N/A,,, Report Prepared By: Edward Carapezza; License No.: 3447 Inspector

More information

Inspection of the exterior found a tree in the back yard and a tree in the front yard within influential distance from the residence foundation.

Inspection of the exterior found a tree in the back yard and a tree in the front yard within influential distance from the residence foundation. Gerard J. Duhon, P.E., #59832 Engineered Foundation Solutions, #F-12259 281-788-7393 gerard@texashomeengineer.com ENGINEERING OPINION INVESTIGATION OF FOUNDATION PERFORMANCE RESIDENCE AT 12345 ANYSTREET,

More information

POST AND FRAME STRUCTURES (Pole Barns)

POST AND FRAME STRUCTURES (Pole Barns) POST AND FRAME STRUCTURES (Pole Barns) Post and frame structures. The following requirements serve as minimum standards for post and frame structures within all of the following structural limitations:

More information

Basement Moisture Problems

Basement Moisture Problems Foundations Foundation Purpose The purpose of a foundation is to distribute the weight of a structure securely into the ground. Engineering data regarding soil, rock and water conditions are used to design

More information

SAMPLE REPORT. Convention regarding directions: Front faces the street, left and right are as seen from the street facing the house.

SAMPLE REPORT. Convention regarding directions: Front faces the street, left and right are as seen from the street facing the house. SAMPLE REPORT Gerard J. Duhon, P.E., #XXXXX Engineered Foundation Solutions, #X-XXXX ENGINEERING OPINION INVESTIGATION OF FOUNDATION PERFORMANCE RESIDENCE AT XXXXXXXX WAY, HOUSTON, TEXAS, 77084 Date of

More information

FORENSIC INVESTIGATION QUESTIONNAIRE

FORENSIC INVESTIGATION QUESTIONNAIRE FORENSIC INVESTIGATION QUESTIONNAIRE PSE Project Number: - - Project Name: Person(s) Interviewed: Relationship to House: Please answer the following questions to the best of your ability. Exact dates are

More information

SECTION 1 GENERAL REQUIREMENTS

SECTION 1 GENERAL REQUIREMENTS Page 1 of 6 SECTION 1 GENERAL REQUIREMENTS 1. SCOPE OF WORK: The work to be performed under the provisions of these documents and the contract based thereon includes furnishing all labor, equipment, materials,

More information

STRUCTURAL ASSESSMENT

STRUCTURAL ASSESSMENT STRUCTURAL ASSESSMENT Project: 1432-1434 East Commerce St. Job. No: 122200 Location: San Antonio, TX Date: Dec. 10, 2012 Weather: Sunny, Windy,60 deg Performed by: Jeff Haughton and Frank Lamas, Alpha

More information

This handout is a guide only and does not contain all of the requirements of the Minnesota State Building Code or city ordinances.

This handout is a guide only and does not contain all of the requirements of the Minnesota State Building Code or city ordinances. Basement Finishing Guide Community Development Department Building Inspections Division 5200 85 th Avenue North / Brooklyn Park, MN 55443 Phone: (763) 488-6379 / Fax: (763) 493-8171 6/15 www.brooklynpark.org

More information

NCMA TEK CONCRETE MASONRY FOUNDATION WALL DETAILS. TEK 5-3A Details (2003)

NCMA TEK CONCRETE MASONRY FOUNDATION WALL DETAILS. TEK 5-3A Details (2003) NCMA TEK National Concrete Masonry Association an information series from the national authority on concrete masonry technology CONCRETE MASONRY FOUNDATION WALL DETAILS TEK 5-3A Details (2003) Keywords:

More information

Typical Finished Basement Details

Typical Finished Basement Details Fairfax County, Virginia Typical Finished Basement Details Based on the 2012 International Residential Code Finished basements must be constructed in conformance with this document. For requirements, details

More information

Residential Decks. Planning and Development Services Department

Residential Decks. Planning and Development Services Department Building Safety Division 8500 Santa Fe Drive Overland Park, KS 66212 (913) 895-6225 Fax (913) 895-5016 Email: permitservices@opkansas.org Planning and Development Services Department Residential Decks

More information

The better way to build TM. Installation Manual. FOUNDATION SIPs & FROST WALLS SIPs

The better way to build TM. Installation Manual. FOUNDATION SIPs & FROST WALLS SIPs The better way to build TM Installation Manual FOUNDATION SIPs & FROST WALLS SIPs February 2016 PWF FOUNDATION & FROST WALL SIPs Installation Manual Table of Contents Topics General Requirements...................................

More information

Report for. Dick and Jane Homeowner. 1234 Lovers Lane, Houston, Texas 77000

Report for. Dick and Jane Homeowner. 1234 Lovers Lane, Houston, Texas 77000 Report for Dick and Jane Homeowner 1234 Lovers Lane, Houston, Texas 77000 March 17, 2004 I NI NP R Inspection Item I. STRUCTURAL SYSTEMS o o o A. Foundations (If all crawl space areas are not inspected,

More information

Pre-Drywall Inspection Report

Pre-Drywall Inspection Report SM MEDALLION INSPECTIONS helping people make informed decisions Pre-Drywall Inspection Report 5657 Garden Valley Place Milton, Georgia 30024 Prepared for Betsy and Paul Dougherty January12, 2015 Medallion

More information

The Closed Crawl Space: Making the Transition Climate Zones 3A & 4A

The Closed Crawl Space: Making the Transition Climate Zones 3A & 4A TechSpecs A builder s blueprint for construction technologies January 2013 The Closed Crawl Space: Making the Transition Climate Zones 3A & 4A C B A E D H G F A. Wood Floor Framing - p. 2 B. Foundation

More information

Home Inspection Report

Home Inspection Report 4949 Brownsboro Rd Suite 293 Louisville, KY 40223 (502) 414-1440 tripleainspections@gmail.com Inspected By: William Carter, HI-1956 Home Inspection Report Prepared For: Edward Cullen Property Address:

More information

ENGINEERED FOUNDATIONS. Department of Public Works Jeff Hill, PE

ENGINEERED FOUNDATIONS. Department of Public Works Jeff Hill, PE ENGINEERED FOUNDATIONS Department of Public Works Jeff Hill, PE What is an engineered foundation. A Foundation Design Developed by a Trained Professional (Engineer) Types of Foundations (All of which can

More information

Prestige Home Inspection LLC

Prestige Home Inspection LLC Cover Page Prestige Home Inspection LLC IAC2/ESA - Mold Assessment and Water Damage Report 555 W. Brook ave., Client's town MI, 48059 Inspection prepared for: Client's name Inspection Date: 10/15/2012

More information

Beginning on Friday, Jan 22, and on subsequent investigations, the following issues were identified:

Beginning on Friday, Jan 22, and on subsequent investigations, the following issues were identified: Date: 2/15/2016 Project: To: Middleton Public Library Roof Repair Pamela K. Westby Library Director Middleton Public Library 7425 Hubbard Avenue Middleton WI 53562 Pamela, Strategic Structural Design,

More information

Name of course: Residential Construction Site Management (RCSM) Level 1

Name of course: Residential Construction Site Management (RCSM) Level 1 Name of course: Residential Construction Site Management (RCSM) Level 1 Core (required courses) or Optional (elective course): Required Delivery Method: This is an online course only with no classroom

More information

D Sample Notices to Property Owners, Sample Affidavits, and Other Material

D Sample Notices to Property Owners, Sample Affidavits, and Other Material D Sample Notices to Property Owners, Sample Affidavits, and Other Material These samples are offered to illustrate specific points in the Desk Reference. States and communities should examine them carefully

More information

PROPERTY INSPECTION OR ASSESSMENT OF DAMAGES

PROPERTY INSPECTION OR ASSESSMENT OF DAMAGES PROPERTY INSPECTION OR ASSESSMENT OF DAMAGES ADDRESS: Somewhere, FL CLIENT: GAIA GC ID No: 2015000 DATE: 12/31/2015 INSPECTION OR ASSESSMENT BY: GAIA CONSTRUCTION INC. CGC 1516136 FLORIDA HI-2792 FLORIDA

More information

Foundation. Foundation

Foundation. Foundation Moisture Aside from structural concerns, the most important consideration for foundation design is moisture. No client wants a wet basement. No client wants a damp basement. No client wants mold in their

More information

WOODLAND HOMES BUILDING PROCESS A STEP BY STEP CONSTRUCTION GUIDE TO YOUR NEW HOME

WOODLAND HOMES BUILDING PROCESS A STEP BY STEP CONSTRUCTION GUIDE TO YOUR NEW HOME WOODLAND HOMES BUILDING PROCESS A STEP BY STEP CONSTRUCTION GUIDE TO YOUR NEW HOME 1 THE BUILDING PROCESS The focus of Woodland Homes building department is Quality, Service and Predictability. Through

More information

How To Build A Basement House

How To Build A Basement House Single Family Basement Finish Purpose of Guide The purpose of this guide is to assist you in the permit process for your project. This handout is intended as a basic plan submittal under the 2009 International

More information

1. Concrete: T W L / 27 = Concrete C.Y. Multiply Feet Thickness x Feet Width x Feet Length / 27 = Cubic Yards.

1. Concrete: T W L / 27 = Concrete C.Y. Multiply Feet Thickness x Feet Width x Feet Length / 27 = Cubic Yards. Formulas: Formula Letters: H= Height BCY = Bank Cubic Yards L= Length CCY = Compact Cubic Yards P= Perimeter LCY = Loose Cubic Yards LF = Linear Feet or Lineal Feet BF = Board Foot or Feet SF = Square

More information

Rehab Inspection Report Page 1

Rehab Inspection Report Page 1 Rehab Inspection Report Page 1 Home Address: Construction Style: Number of bedrooms Square footage: Value of offer: Estimated rehab cost: Value of resale: Orientation of house: N S E W Note: orientation

More information

201 WATER STREET FORWARDERS MUSEUM AND VISITORS INFORMATION CENTRE

201 WATER STREET FORWARDERS MUSEUM AND VISITORS INFORMATION CENTRE STRUCTURAL INSPECTION REPORT DRAFT 201 WATER STREET FORWARDERS MUSEUM AND VISITORS INFORMATION CENTRE TOWN OF PRESCOTT Date: November 2013 GENIVAR No.: 131-20617-00 2611 Queensview Drive, Suite 300, Ottawa,

More information

AMERICAN GOTHIC PLAYHOUSE

AMERICAN GOTHIC PLAYHOUSE AMERICAN GOTHIC PLAYHOUSE Project Plan #856 Sheet 1 of 5 Pick a spot and get started with the beautiful that your kids will love. The design of the playhouse includes 35 square feet of interior space plus

More information

How To Prevent Water Damage To A Home

How To Prevent Water Damage To A Home Having inspected about 800 homes in the last four years, I have seen a lot of problems with many homes. Most of these problems are minor; however, there are some problems that are quite serious. One of

More information

Foundations 65 5 FOUNDATIONS. by Richard Chylinski, FAIA and Timothy P. McCormick, P.E. Seismic Retrofit Training

Foundations 65 5 FOUNDATIONS. by Richard Chylinski, FAIA and Timothy P. McCormick, P.E. Seismic Retrofit Training Foundations 65 5 FOUNDATIONS by Richard Chylinski, FAIA and Timothy P. McCormick, P.E. 66 Foundations Foundations 67 FOUNDATIONS Let's assume that the retrofit has been done correctly from the roofline

More information

Single Family Residential Building Permit Questions & Answers

Single Family Residential Building Permit Questions & Answers Single Family Residential Building Permit Questions & Answers Prepared by Dept. of Public Works Revised 07/01/13 200 East Park Street Edwardsville, IL 62025 (618) 692-7535 (618) 692-7505(Fax) Hours: Monday

More information

Comment Form on Proposed Gut Rehabilitation Alternatives

Comment Form on Proposed Gut Rehabilitation Alternatives Comment Form on Gut Rehabilitation Alternatives Name: Organization: Email: Instructions Submission: Please submit this form to energystarhomes@energystar.gov by October 10 th, 2012 with the subject line

More information

Structural Assessment Report

Structural Assessment Report Report Dallas Township Elementary School Dallas, Pennsylvania (JBCI Project No. 144911) 1655 Suburban Station Building 1617 John F. Kennedy Boulevard Philadelphia PA 19103 215 665 0497 5 Sandwood Drive

More information

PDmB, Inc. Definitions

PDmB, Inc. Definitions Page 1 of 11 Definitions S Satisfactory Meets industry standards for proper material and installation NP Not Present Condition or item was not present at time of inspection NI Not Inspected Condition or

More information

October 6, 2009. (B) the vantage point from which the crawl space was inspected; and

October 6, 2009. (B) the vantage point from which the crawl space was inspected; and 535.228. Standards of Practice: Minimum Inspection Requirements for Structural Systems (a) Foundations. The inspector shall: (1) inspect slab surfaces, foundation framing components, subflooring, and related

More information

www.citiesinspection.com October 5, 2015 Dear Client,

www.citiesinspection.com October 5, 2015 Dear Client, www.citiesinspection.com October 5, 2015 Dear Client, On 9/14/2015, Cities Inspection Service, Inc. completed a building inspection of the property located at 123 Oak Street, Someplace, Minnesota for you.

More information

6 RETROFITTING POST & PIER HOUSES

6 RETROFITTING POST & PIER HOUSES Retrofitting Post & Pier Houses 71 6 RETROFITTING POST & PIER HOUSES by James E. Russell, P.E. 72 Retrofitting Post & Pier Houses Retrofitting Post & Pier Houses 73 RETROFITTING POST AND PIER HOUSES This

More information

WEBSTER ELEMENTARY SCHOOL New Rochelle, New York Evaluation of Collapsed Ceiling Room 204

WEBSTER ELEMENTARY SCHOOL New Rochelle, New York Evaluation of Collapsed Ceiling Room 204 WEBSTER ELEMENTARY SCHOOL New Rochelle, New York Evaluation of Collapsed Ceiling Room 204 Structural Inspection Report Client: CSArch Architecture Engineering Construction Management 19 Front Street, Newburgh,

More information

Building Condition Assessment: 215-219 West Lexington Street Baltimore, Maryland

Building Condition Assessment: 215-219 West Lexington Street Baltimore, Maryland KPA The Joint Venture of EBA Engineering, Inc. and Kennedy Porter & Associates, Inc. 4813 Seton Drive, Baltimore, MD 21215 Phone: (410-358-7171) Fax: (410)358-7213 Building Condition Assessment: Baltimore,

More information

Envelope INSULATION BATT (2) Avoid Using Batt Insulation With Metal Framing. Pressure or Friction Fit

Envelope INSULATION BATT (2) Avoid Using Batt Insulation With Metal Framing. Pressure or Friction Fit R-H-DI1 INSULATION BATT NR-E-IB1 Avoid Using Batt Insulation With Metal Framing Batt insulation should not be used with metal framing systems. Although it is common to see fiberglass batt insulation installed

More information

Designed and Engineered to Perform

Designed and Engineered to Perform History EARTH CONTACT PRODUCTS, L.L.C., is a family owned company, based in Olathe, Kansas. This company was built upon Don May s U.S. Patented fourth-generation Steel Piering System that has led to the

More information

The minimum reinforcement for the stem wall is the placement of:

The minimum reinforcement for the stem wall is the placement of: PolySteel creates an ideal insulated stem wall for concrete slabs that can make this part of your project easier and faster, in addition to making your finished project more energy-efficient. Figures 3.20

More information

The Impact of Market Demands on Residential Post-Tensioned Foundation Design: An Ethical Dilemma

The Impact of Market Demands on Residential Post-Tensioned Foundation Design: An Ethical Dilemma The Impact of Market Demands on Residential Post-Tensioned Foundation Design: An Ethical Dilemma Bart B. Barrett, B.S., P.E.1 Kerry S. Lee, M.B.A., P.E., M. ASCE2 Erik L. Nelson, Ph.D., P.E., M. ASCE3

More information

BUILDING PERMIT SPECIFICATIONS

BUILDING PERMIT SPECIFICATIONS BUILDING PERMIT SPECIFICATIONS The below noted requirements are based upon La Plata County Building Code. These specifications are not intended as a complete set of requirements, but are intended to provide

More information

Property Inspection Report

Property Inspection Report Property Inspection Report LOCATED AT: 123 Address DFW, TX PREPARED EXCLUSIVELY FOR: Sample Report INSPECTED ON: Saturday, July 18, 2015 Inspector, Zach Faris - TREC #21548 INSPECT TX PROPERTY INSPECTION

More information

A TO Z HOME INSPECTIONS PROFESSIONAL HOME INSPECTION SERVICES FOR HOME BUYERS AND SELLERS

A TO Z HOME INSPECTIONS PROFESSIONAL HOME INSPECTION SERVICES FOR HOME BUYERS AND SELLERS A TO Z HOME INSPECTIONS PROFESSIONAL HOME INSPECTION SERVICES FOR HOME BUYERS AND SELLERS Insurance Inspection Report 1234 Main Street Tallahassee, Florida Report Prepared For: Charles Smith Report Prepared

More information

Elevating Your House. Introduction CHAPTER 5

Elevating Your House. Introduction CHAPTER 5 CHAPTER 5 Elevating Your House Introduction One of the most common retrofitting methods is elevating a house to a required or desired Flood Protection Elevation (FPE). When a house is properly elevated,

More information

Single Family Residential Basement Finish

Single Family Residential Basement Finish How to Use This Guide Building Guide Pottawattamie County Planning & Development Department Building & Safety Division Single Family Residential Basement Finish Provide two (2) sets of plans and complete

More information

The Lambton County Homeowner's BUILDING PERMIT INFORMATION GUIDE

The Lambton County Homeowner's BUILDING PERMIT INFORMATION GUIDE The Lambton County Homeowner's BUILDING PERMIT INFORMATION GUIDE BUILDING SERVICES DEPARTMENT 789 Broadway Street, Box 3000 Wyoming, ON N0N 1T0 Telephone: 519 845-0801 Toll-free: 1-866-324-6912 Fax: 519

More information

Sample Rehabilitation Proposal: Narrative

Sample Rehabilitation Proposal: Narrative Sample Rehabilitation Proposal: Narrative Submitted by Mr. And Mrs. John Doe RE: XXX North Xth St. Paducah, KY To: Urban Renewal and Community Development Agency: We are interested in purchasing the property

More information

CONDITION OF QUALITY ITEMS

CONDITION OF QUALITY ITEMS CONDITION OF QUALITY ITEMS FOUNDATION Always look for moisture problems and any bulges or irregularities in the walls. Lines on the walls or floors may indicate water problems. Have these been cured? If

More information