1 Metasys Connectivity Technical Manual Metasys Integrator Section Application Note Issue Date 0900 APPLICATION NOTE Metasys Integrator Notifier AFP-200 Fire Panel Application Introduction Page *3 Application Details *3 Component Requirements *5 Vendor Contact Information *6 Design Considerations *6 Cable Connections 9 Cable Pinouts *9 Connecting the Cable *9 Metasys Integrator Setup *11 Point Mapping Tables 13 Detector Points *13 Module Points *13 Bell/System Trouble Points *14 Metasys Network Setup *17 Mapping to a CS Object *17 Custom Integration *19 *Indicates those sections where changes have occurred since the last printing Johnson Controls, Inc. 1 Code No. LIT
2 2 Metasys Integrator Metasys Integrator Notifier AFP-200 Fire Panel Application
3 Introduction This document explains the Metasys Integrator Notifier AFP-200 Fire Alarm Panel application. Use this document with the Metasys Integrator technical bulletins that provide information on installing and commissioning the Metasys Integrator unit. For information on the AFP-200 Fire Panel, see the Notifier documentation. Please note that this application will also work with the Johnson Controls IFC-200 Fire Panel. Note: If you are using a Universal Packaging Module (UPM), you must install the Metasys Integrator 300 Series in a two high enclosure (EN-EWC25-0) rather than a one high enclosure (EN-EWC13-0) as shown in the figures in this application note. Application Details The Metasys Integrator unit allows the Notifier AFP-200 Fire Alarm Panel to communicate with the Metasys and Metasys Companion Networks. Once a Notifier AFP-200 Fire Panel is connected to a Metasys or Companion Network via the Metasys Integrator unit, its data is available to the full complement of Metasys Building Automation System (BAS) features, including Change-of-State (COS) monitoring, secondary reporting, alarm and trouble notification, trend, and totalization. Each Metasys Integrator vendor port can connect to one AFP-200 Fire Panel. The AFP-200 Fire Panel has a single Signaling Line Circuit (SLC) that supports up to 99 detectors and 99 modules, plus four Notification Appliance Circuits (NACs) designated Bell Circuits on the panel. When the AFP-200 Fire Panel is reset, all Binary Input () points are reset to an open or 0 value and any trouble status is cleared.! CAUTION: The Metasys Integrator unit is not Underwriters Laboratories (UL) 864 Listed as a fire alarm control unit. It is designed to provide only secondary ancillary monitoring, while the AFP-200 Fire Control Panel provides UL 864 Listed notification and control functions. Metasys Integrator Metasys Integrator Notifier AFP-200 Fire Panel Application 3
4 N1LAN Standard NCU RS-232 AFP-200 Fire Panel Metasys Integrator UNT Note: If you are using a UPM, you must install the Metasys Integrator 300 Series in a two high enclosure (EN-EWC25-0) rather than a one high enclosure (EN-EWC13-0) as shown in the figures in this application note. afp1 Figure 1: AFP-200 Fire Panel and Metasys Integration Panel Unit Workstation Metasys Integrator RS-232 (50 ft maximum) AFP-200 Fire Panel UNT N2 Bus Note: A PC version and converter may be substituted for the Panel unit. afp200comp Note: If you are using a UPM, you must install the Metasys Integrator 300 Series in a two high enclosure (EN-EWC25-0) rather than a one high enclosure (EN-EWC13-0) as shown in the figures in this application note. Figure 2: AFP-200 Fire Panel and Metasys Companion Integration 4 Metasys Integrator Metasys Integrator Notifier AFP-200 Fire Panel Application
5 Component Requirements Metasys Release Requirements Metasys Companion Release Requirements To integrate the AFP-200 Fire Panel, you need the following: properly installed AFP-200 Fire Panel with firmware Version 2.4 RS-232 cable (for connecting the AFP-200 Fire Panel s RS-232 port to the Metasys Integrator unit) Metasys Integrator unit B&B Optical Isolator, Model RS232 OP4 N2 Bus (for connecting the Metasys Integrator unit to the Metasys Network Control Module [NCM] or Companion Network) portable Personal Computer (PC) for downloading vendor communication tables (.VCT files) and network setup information into the Metasys Integrator unit, and for running diagnostics cable for connecting the portable PC to the Metasys Integrator unit cables for connecting AFP-200 Fire Panel to the Metasys Integrator unit (see pin requirements in the Cable Connections section of this document) standard duplex 120 VAC outlet, required within one foot of the B&B Optical Isolator, Model RS232 OP4 to power this device. This device has two plug-in power supply transformers. This document describes the RS-232 cable and vendor communication tables. Notifier documentation describes their equipment. The remaining components are described in the Metasys Integrator technical bulletins. To integrate the AFP-200 panel into the Metasys Network, you need: Metasys Operator Workstation (OWS) software Release 7.0 or higher Metasys Integrator software/firmware Release 9.0 or higher To integrate the AFP-200 panel into the Metasys Companion Network, you need: Metasys Companion Release 6.0 or higher Metasys Integrator software/firmware Release 9.0 or higher Metasys Integrator Metasys Integrator Notifier AFP-200 Fire Panel Application 5
6 Vendor Component Requirements Vendor Contact Information Integration between the Metasys Integrator unit and Notifier AFP-200 Fire Panel application has been tested with Notifier AFP-200 Firmware Release Version 2.4 and B&B Optical Isolator Model RD232 OP4. B&B Optical Isolator Model RS232 OP4 is required between AFP-200 panel RS-232 port and Metasys Integrator vendor port to eliminate the ground fault. Changes to this equipment or integration of either Notifier or B&B products not discussed in this document require additional software development and testing by Johnson Controls Systems Products. For information on integrating other products, refer to the Custom Integration section of this application note. Notifier One Fire-Lite Place Northford, CT Phone: (203) FAX: (203) B&B Electronics Company 707 Dayton Road P. O. Box 1040 Ottawa, IL Phone: (815) FAX: (815) Design Considerations When integrating the AFP-200 Fire Panel, consider the following: Make sure that the AFP-200 Fire Panel is set up and running properly with Version 2.4 firmware before integrating with a Metasys or Companion system. This includes configuring the AFP-200 Fire Panel s RS-232 printer port in remote terminal mode. (The Notifier representative is responsible for the configuration and operation of Notifier equipment.) The Metasys Integrator unit is not UL 864 Listed as a fire alarm control unit. It is designed to provide secondary ancillary monitoring only, while the AFP-200 Fire Panel provides notification and control functions. When the AFP-200 Fire Panel is reset, all points are set to open state and the trouble status is reset. The AFP-200 Fire Panel must be reset to clear alarms. RS-232 cable distance between the Metasys Integrator unit and the AFP-200 Fire Panel cannot exceed 50 feet. The trouble status is cleared when a device reports a normal or off state. 6 Metasys Integrator Metasys Integrator Notifier AFP-200 Fire Panel Application
7 Programming at the AFP-200 Fire Panel will cause the Notifier AFP-200 Fire Panel to go offline. Also, continuous pressing of the panel keys (e.g., Ack/Step) may cause the AFP-200 Fire Panel to go offline at the Metasys Integrator unit. The AFP-200 Fire Panel, when used alone without the Metasys Integrator unit, has a feature that scrolls through trouble messages when multiple messages exist on the system. This feature is not present when the Metasys Integrator unit is connected to the AFP-200 Fire Panel. If multiple messages exist on the system, the Ack/Step key must be pressed to view each individual message.! WARNING: Some change-of-state messages may be missed while running the Diagnostic Analyzer on the Metasys Integrator commissioning PC. Do not run the Metasys Integrator Diagnostic Analyzer after commissioning is complete. Disconnect the Metasys Integrator unit from the AFP-200 printer port while programming the Fire Panel, then reset the AFP-200 panel after reconnecting the Metasys Integrator unit. Metasys Integrator Metasys Integrator Notifier AFP-200 Fire Panel Application 7
8 8 Metasys Integrator Metasys Integrator Notifier AFP-200 Fire Panel Application
9 Cable Connections Cable Pinouts Use the following cable pinouts for the RS-232 connection between the Metasys Integrator unit and the AFP-200 Fire Panel. You must connect the male end of the converter to the Metasys Integrator unit. Vendor Port A or B of Metasys Integrator DB-9 Female Signal RD TD GND Pin VDC/ 120 VAC Male (25 Pin) Duplex Outlet Optical Isolator Model 2320 P4 (50 ft maximum) Female (25 Pin) RS-232 Printer Port on APF-200 (TB4) TX RX RF afp3 Figure 3: Cable Pinouts Connecting the Cable Connect the female end of RS-232 cable to either Vendor Port A or Vendor Port B on the Metasys Integrator unit. Connect the other open end (no connector) of the cable to terminal TB4 of the panel as specified in AFP-200 Fire Panel installation documentation. Metasys Integrator AFP-200 Fire Panel Vendor Port A or B Optical Isolator RS-232 Printer Terminal Port TBA (EIA-232) afp4 Figure 4: Port-to-Port Connection Metasys Integrator Metasys Integrator Notifier AFP-200 Fire Panel Application 9
10 10 Metasys Integrator Metasys Integrator Notifier AFP-200 Fire Panel Application
11 Metasys Integrator Setup To set up the Metasys Integrator unit, use a portable PC connected to Metasys Integrator Terminal Port. Metasys Integrator setup involves: downloading the correct vendor communication tab (.VCT files) setting up the ports setting up the network addressing The following table provides information specific to the AFP-200 Fire Panel application. For detailed procedures, see the Metasys Integrator technical bulletins. Table 1: Metasys Integrator Setup for AFP-200 Fire Panel Vendor Communication Table (.VCT File) Detector Points Module Points Bell (NAC) and System Trouble Points Port Setup Baud Rate 2400 Word Length 7 Stop Bit 1 Parity Interface Network Setup Vendor Address Detectors Modules Bell (NAC) and System Trouble Points Timeout Value Poll Delay Retries 5 Approximate Scan Time (for an N2 address) Detectors Modules Bell (NAC) and System Trouble Points Time to Receive Alarm/Trouble (after the message generated at the panel) * Be sure to use uppercase characters. IFC2_DET.VCT IFC2_MOD.VCT IFC2_BEL.VCT Even RS-232 D* M* B* 3000 ms 0 ms 60 seconds 60 seconds 10 seconds 2 seconds Metasys Integrator Metasys Integrator Notifier AFP-200 Fire Panel Application 11
12 12 Metasys Integrator Metasys Integrator Notifier AFP-200 Fire Panel Application
13 Point Mapping Tables The following tables show the points available for mapping on the AFP-200 Fire Panel: Detector Points points for each sensor have corresponding Binary Data (BD) points, which are used to map the pre-alarm status of the sensor. These points also indicate the trouble status of the detector. Table 2: Detector Points NPT 1 NPA 2 Description Value Mapped 1-99 Detector SLC Address-LPA 1-Alarm BD 1-99 Pre-alarm status of detector at LPA 1-Alarm 1 Network Point Type 2 Network Point Address When any detector point goes in or out of trouble, its value remains as it was before the trouble occurred. Module Points points also indicate the trouble status. These points also indicate the trouble status of the module. Table 3: Module Points NPT 1 NPA 2 Description Value Mapped 1-99 Module SLC Address-LPA 1-Alarm (Monitor Modules) 0-Off, 1-On (Control Modules) 1 Network Point Type 2 Network Point Address Metasys Integrator Metasys Integrator Notifier AFP-200 Fire Panel Application 13
14 Bell/System Trouble Points When any system trouble occurs, you must reset the IFC-200 Fire Panel manually after clearing the trouble. Table 4 is a list of all the bell circuits and system trouble status points. Table 4: Bell/System Trouble Points NPT 1 NPA 2 Description Value Mapped Network Point Type 2 Network Point Address Bell Circuit 1 Bell Circuit 2 Bell Circuit 3 Bell Circuit 4 Ground Fault AC Fail Battery Style 6 Option Module Term. Supervisory Annunciator 1 No Answer Annunciator 1 Trouble Annunciator 2 No Answer Annunciator 2 Trouble EPROM Error Internal RAM Error External RAM Error Program Corrupted No Device Installed AVPS. Trouble 0-Off, 0-Off, 0-Off, 0-Off, 1-On 1-On 1-On 1-On Note: All system trouble points remain unreliable once a device goes offline/online, until the panel is reset using the system-reset button. Individual points report online when a trouble status is reported for that point. 14 Metasys Integrator Metasys Integrator Notifier AFP-200 Fire Panel Application
15 Getting Point Summary Information from AFP-200 Fire Panel to Map Points with the Metasys Network The commissioning person should have the details of point summary at the time of commissioning. If they are not available, collect the status summary from the panel using the following steps: 1. Disconnect the Metasys Integrator unit from the AFP-200 Fire Panel. 2. Connect a serial printer at printer port (the same serial port which is used for Metasys Integrator interface). 3. Press the Enter key at the panel. 4. Select 2 - read status. 5. To print all points, press 1 (print points), then Enter. A summary will be printed for all programmed points with their current status. The last three characters in each line of the message are the actual point SLC address. (For example: D01 is detector at SLC address 01, which is -1 in vendor table file IFC2_DET.VCT. M01 is module at SLC address 01, which is -1 in vendor table file IFC2_MOD.VCT. B01 is Bell Circuit 1, which is -1 in vendor table file IFC2_BEL.VCT.) See Table 2 for detector points, see Table 3 for module points, and see Table 4 for bell/system trouble points. Metasys Integrator Metasys Integrator Notifier AFP-200 Fire Panel Application 15
16 16 Metasys Integrator Metasys Integrator Notifier AFP-200 Fire Panel Application
17 Metasys Network Setup Metasys Network setup is described in the Metasys Integrator technical bulletins in the Metasys Connectivity Technical Manual (FAN 629.5). This section contains details specific to the AFP-200 Fire Panel. We recommend that all points that report an alarm or trouble status be directly mapped to objects. Mapping to a CS Object Table 5: Software Model and CS Object Definition Application AFP-200 Detector SLC AFP-200 Module SLC AFP-200 Bell (NAC) and System Trouble Points Software Model (on Tables and Models CD-ROM) IF2_DLOP.DDL IF2_MLOP.DDL IF2_SYST.DDL Display Attributes (recommended) 1 Status of Detector 1 NI1 Status of Module 1 17 Network Fail NT Command Attributes 1 Status of Detector 1 1 Status of Module 1 17 Network Fail Metasys Integrator Metasys Integrator Notifier AFP-200 Fire Panel Application 17
18 18 Metasys Integrator Metasys Integrator Notifier AFP-200 Fire Panel Application
19 Custom Integration For information on integrating products which are not discussed in this document, first refer to the Metasys Compatible Global Catalog, an online list of released Connectivity products. If this list does not provide the information you require, consider using the System Integration Project Data Sheet to request a custom contract from the System Integration Team. Both the Metasys Compatible Global Catalog and the System Integration Project Data Sheet can be accessed from The Advisor by performing the following steps: 1. Click on the Systems Products button located on the left side of The Advisor home page. 2. Click on the Product Literature link. 3. Click on the Manuals-FANS link. 4. Click on the Metasys Connectivity Sales Resource Manual link. 5. Find the System Integration Project Data Sheet link in the Table of Contents. Click on this link to view an online copy of the System Integration Project Data Sheet, or click on the Metasys Compatible Global Catalog link below it to view a list of released Connectivity products. The System Integration Project Data Sheet (LIT ) can also be found in the Metasys Connectivity Sales Resource Manual (FAN 629). If you need further assistance, contact the Johnson Controls Field Support Center. Metasys Integrator Metasys Integrator Notifier AFP-200 Fire Panel Application 19
20 Notes Controls Group FAN E. Michigan Street Metasys Connectivity Technical Manual P.O. Box 423 Metasys Integrator Release 9.0 Milwaukee, WI Printed in U.S.A. 20 Metasys Integrator Metasys Integrator Notifier AFP-200 Fire Panel Application
PRT3 Printer Module: ASCII Protocol Programming Instructions
PRT3 Printer Module: ASCII Protocol Programming Instructions We hope this product performs to your complete satisfaction. Should you have any questions or comments, please visit www.paradox.com and send
More informationMS830 / MS833 Barcode Reader v1.0 9-December-2014
MS830 / MS833 Barcode Reader v1.0 9-December-2014 Publication Information 2014 Imagine Communications Corp. Proprietary and Confidential. Imagine Communications considers this document and its contents
More informationSECTION 13850 DETECTION AND ALARM
SECTION 13850 DETECTION AND ALARM PART 1 GENERAL 1.01 SUMMARY A. Section Includes 1. Control Panel 2 Associated Equipment B. Products Installed But Not Supplied Under This Section 1. Section 16140 - Wiring
More informationISDN Phone Lines with Metasys
Metasys Network Technical Manual 636 App. Notes: Network Communications Section Application Note Issue Date 0696 APPLICATION NOTE Phone Lines with Metasys Introduction Page 3 What is? *3 References *3
More informationNC-12 Modbus Application
NC-12 Modbus Application NC-12 1 Table of Contents 1 Table of Contents... 2 2 Glossary... 3 SCADA...3 3 NC-12 Modbus in general... 3 4 Entire system... 4 4.1 PFC to PC connection alternatives...4 4.1.1
More informationProgramming and Using the Courier V.Everything Modem for Remote Operation of DDF6000
Programming and Using the Courier V.Everything Modem for Remote Operation of DDF6000 1.0 Introduction A Technical Application Note from Doppler System July 5, 1999 Version 3.x of the DDF6000, running version
More informationHONEYWELL COMMERCIAL FIRE/BURG PANEL UL LISTING REQUIREMENTS (Compiled from VistaFBPT Installation Instructions 800-09617V1 Rev A 11/12)
HONEYWELL COMMERCIAL FIRE/BURG PANEL UL LISTING REQUIREMENTS (Compiled from VistaFBPT Installation Instructions 800-09617V1 Rev A 11/12) UL864 (Commercial Fire) Compliance General Requirements The VISTA-128FBPT/VISTA250FBPT
More informationAPPLICATION NOTE. Leased Line Modem. Leased Line Modem...3. Introduction... 3. Key Concepts... 4
Issue Date 02/18/02 APPLICATION NOTE Leased Line Modem Leased Line Modem...3 troduction... 3 Key Concepts... 4 Application Details...4 Theory of Operation...6 Components...8 Planning Considerations...10
More informationBIT COMMANDER. Serial RS232 / RS485 to Ethernet Converter
BIT COMMANDER Serial RS232 / RS485 to Ethernet Converter (Part US2000A) Copyrights U.S. Converters 1 Contents Overview and Features... 3 Functions..5 TCP Server Mode... 5 Httpd Client Mode.5 TCP Auto mode....6
More informationModbus Communications for PanelView Terminals
User Guide Modbus Communications for PanelView Terminals Introduction This document describes how to connect and configure communications for the Modbus versions of the PanelView terminals. This document
More informationPortable BACnet /IP to MS/TP Router
Portable BACnet /IP to MS/TP Router Installation Instructions TL-BRTRP-0 Part No. 24-10414-2, Rev. F Issued April 2016 Refer to the QuickLIT website for the most up-to-date version of this document. Applications
More informationIntesisBox KNX LG Air Conditioning
IntesisBox KNX LG Air Conditioning Gateway for integration of LG Air Conditioners with KNX control systems. 1. Main Features Direct connection to KNX TP-1 (EIB) bus. Direct connection to LG outdoor unit
More informationRouteFinder SOHO. Quick Start Guide. SOHO Security Appliance. EDGE Models RF825-E, RF825-E-AP CDMA Models RF825-C-Nx, RF825-C-Nx-AP
RouteFinder SOHO SOHO Security Appliance EDGE Models RF825-E, RF825-E-AP CDMA Models RF825-C-Nx, RF825-C-Nx-AP Quick Start Guide RouteFinder RF825 Series Quick Start Guide RouteFinder SOHO Security Appliance
More informationTCP/IP MODULE CA-ETHR-A INSTALLATION MANUAL
TCP/IP MODULE CA-ETHR-A INSTALLATION MANUAL w w w. c d v g r o u p. c o m CA-ETHR-A: TCP/IP Module Installation Manual Page Table of Contents Introduction...5 Hardware Components... 6 Technical Specifications...
More informationData Bulletin. Communications Wiring for POWERLINK G3 Systems Class 1210 ABOUT THIS BULLETIN APPLICATION INTRODUCTION.
Data Bulletin 1210DB0002R3/05 03/2005 LaVergne, TN, USA Communications Wiring for POWERLINK G3 Systems Class 1210 Retain for future use. ABOUT THIS BULLETIN This data bulletin describes the proper wiring
More informationRemote Data Collection Device CE Model DCDSS1
Remote Data Collection Device CE Model DCDSS1 Documentation Number DCDSS11702 This product designed and manufactured in Ottawa, Illinois USA of domestic and imported parts by International Headquarters
More informationOmron I/O Driver (Series 2) Programmable Serial Interface Card
Omron I/O Driver (Series 2) Programmable Serial Interface Card USER MANUAL Rev. P1.55 June 8, 2012 DeltaV is a trademark of Emerson Process Management, Inc Emerson Process Management, Inc. 1998, 1999.
More informationDriver Manual (Supplement to the FieldServer Instruction Manual) FS-8700-90 (Notifier NFS-640 NFS-320 NFS2-640)
A Sierra Monitor Company Driver Manual (Supplement to the FieldServer Instruction Manual) FS-8700-90 (Notifier NFS-640 NFS-320 NFS2-640) APPLICABILITY & EFFECTIVITY Effective for all systems manufactured
More informationUser Manual Revision 1.400 English Converter / Adapter Ethernet to RS232 / RS485 (Order Code: HD67038-2 HD67038-2-M HD67038-25 HD67038-25-M)
Document code: MN67038-2_ENG Revision 1.400 Page 1 of 25 User Manual Revision 1.400 English Converter / Adapter Ethernet to RS232 / RS485 (Order Code: HD67038-2 HD67038-2-M HD67038-25 HD67038-25-M) for
More informationIntesisBox KNX Modbus RTU master
IntesisBox KNX RTU master Gateway for integration of RTU devices into KNX control systems. Integrate RTU devices (Chillers, Roof Tops, electricity meters, heating floors, heat pumps, PLCs ) into KNX control
More informationRS-232 Baud Rate Converter CE Model 232BRC Documentation Number 232BRC-3903 (pn5104-r003)
S-232 Baud ate Converter CE Model 232BC Documentation Number 232BC-3903 (pn5104-r003) International Headquarters B&B Electronics Mfg. Co. Inc. 707 Dayton oad -- P.O. Box 1040 -- Ottawa, IL 61350 USA Phone
More informationTroubleshooting Tips Lifestyle SA-2 & SA-3 Amplifier. Troubleshooting Tips
Troubleshooting Tips Lifestyle SA-2 & SA-3 Amplifier Refer to the Lifestyle SA-2 & SA-3 Amplifier service manuals, part number 271720 for schematics, PCB layouts and parts lists. Preventative Repair Measures
More informationFOSTCDR. Industrial Serial to Multimode Fiber Optic Converter PRODUCT INFORMATION B&B ELECTRONICS. Specifications Serial Technology
FOSTCDR pn 8684R1 FOSTCDR-0812ds page 1/5 Industrial Serial to Multimode Fiber Optic Converter Data Rates up to 115.2 kbps 2.5 Mile (4 km) Range 10 to 30 VDC Input Voltage Wide Operating Temperature 2000V
More informationINTELLIGENT FIRE ALARM CONTROL UNITS. MMX-2017-12NDS Intelligent Network Fire Alarm Control Unit. Features. Description
INTELLIGENT FIRE ALARM CONTROL UNITS MMX-2017-12NDS Intelligent Network Fire Alarm Control Unit Description Secutron s MMX-2017-12NDS Network Fire Alarm Control Unit offers modular components to meet a
More informationPowerLogic Sub Meter Display (SMD and SMDOPN)
Instruction Bulletin Z203742-0B PowerLogic Sub Display (SMD and SMDOPN) CONTENTS Introduction... 2 Parts of the Sub Display... 3 Dimensional Drawing... 4 Installation... 5 Mounting the SMD... 5 Mounting
More informationEZ-View Network Communications Guide www.cszindustrial.com
Network Communications Guide EzView Network Communications Guide RevB July 2013 (V2.2) Supersedes: RevA (May 2011) Cincinnati Sub-Zero Products, LLC 513-772-8810 12011 Mosteller Road Cincinnati, Ohio 45241
More informationRS232 Programming and Troubleshooting Guide for Turbo Controls
RS232 Programming and Troubleshooting Guide for Turbo Controls This Troubleshooting guide is intended for the set up and troubleshooting of the control panels onboard RS232 output. Refer to the Installation
More informationModBus Server - KNX. Gateway for integration of KNX equipment into Modbus (RTU and TCP) control systems.
IntesisBox ModBus Server - KNX Gateway for integration of KNX equipment into Modbus (RTU and TCP) control systems. Integrate KNX based lighting control into your SCADA, BMS, PLC "talking" Modbus. Master
More informationRS-232 Communications Using BobCAD-CAM. RS-232 Introduction
RS-232 Introduction Rs-232 is a method used for transferring programs to and from the CNC machine controller using a serial cable. BobCAD-CAM includes software for both sending and receiving and running
More informationRS232C < - > RS485 CONVERTER S MANUAL. Model: LD15U. Phone: 91-79-4002 4896 / 97 / 98 (M) 0-98253-50221 www.interfaceproducts.info
RS232C < - > RS485 CONVERTER S MANUAL Model: LD15U INTRODUCTION Milestone s model LD-15U is a RS232 to RS 485 converter is designed for highspeed data transmission between computer system and or peripherals
More information16-Port RS232 to USB2.0 High Speed Multi Serial Adapter (w/ Metal Case) Installation Guide
16-Port RS232 to USB2.0 High Speed Multi Serial Adapter (w/ Metal Case) Installation Guide 1. Introduction Thank you for purchasing this 16-Port RS232 to USB2.0 High Speed Multi Serial Adapter. It is an
More informationINTELLIGENT CONTROL MODULE SA-2000-II HARDWARE MANUAL. Access Technologies International, Inc.
SA-2000-II HARDWARE MANUAL Access Technologies International, Inc. 1 Table of Contents 1. Introduction 3 2. Features 3 3. Specification 4 4. Identifying Supplied Parts 4 5. Panel Description 5 6. Connection
More informationIntesisBox Modbus Server SAMSUNG Air Conditioners
IntesisBox Modbus Server SAMSUNG Air Conditioners Gateway for monitoring and control of Samsung NASA compatible Air Conditioning Systems from any Modbus master device TCP or RTU (BMS, PLC, SCADA, HMI,
More informationConnecting instruments serially to your computer
Connecting instruments serially to your computer This TechNote will review how to connect instruments (GPS, Sounder, Heading Sensor ) to a computer. Important points such as electrical specification (RS-232
More informationINTELLIGENT FIRE ALARM CONTROL PANELS. MR-2100/MR-2200 Intelligent Fire Alarm Control Panels MEA. Features. Description
INTELLIGENT FIRE ALARM CONTROL PANELS MR-2100/MR-2200 Intelligent Fire Alarm Control Panels Description MR-2100/MR-2200 Intelligent Fire Alarm Control Panel (shown with optional LED modules) Secutron's
More informationIntesisBox KNX Modbus TCP master
IntesisBox KNX TCP master Gateway for integration of TCP slave devices into KNX control systems. Integrate any TCP slave device into KNX. KNX TCP slave EIB Bus IntesisBox Ethernet slave LinkBoxEIB Configuration
More informationPlena Voice Alarm System Firmware update
Plena Voice Alarm System Firmware update 1. Introduction It is advised to update a Bosch Plena Voice Alarm System with the latest released firmware. This Application Note describes how a firmware update
More informationDSX Master Communications
DSX Access Systems, Inc. PC to Master Controller - Direct Connect Communications DSX Master Communications Communications between the Comm Server PC and the Master Controller can take several forms which
More informationModbus Server SAMSUNG Air Conditioners
IntesisBox Server SAMSUNG Air Conditioners Gateway for monitoring and control of Samsung Air Conditioning Systems from any master device TCP or RTU (BMS, PLC, SCADA, HMI, TouchPanel ) Master TCP Master
More informationPCMCIA 1 Port RS232 2.1 EDITION OCTOBER 1999
232 232232 PCMCIA 1 Port RS232 2.1 EDITION OCTOBER 1999 Guarantee. FULL 36 MONTHS GUARANTEE. We guarantee your interface card for a full 36 months from purchase, parts and labour, provided it has been
More informationVOICE RECORDING SYSTEM ISDN PRI / BRI
Sense Box VOICE RECORDING SYSTEM ISDN PRI / BRI / Analog SUB-SYSTEM ISDN2, ISDN30 Sense Box USER MANUAL TABLE OF CONTENTS 1. STATUTORY INFORMATION... 3 1.1 SAFETY WARNING... 3 1.2 SAFETY EXTRA LOW VOLTAGE
More informationUsing a Laptop Computer with a USB or Serial Port Adapter to Communicate With the Eagle System
Using a Laptop Computer with a USB or Serial Port Adapter to Communicate With the Eagle System ECU DB9 USB 20-060_A.DOC Page 1 of 18 9/15/2009 2009 Precision Airmotive LLC This publication may not be copied
More information2100 POS System. 2100 User Guide
2100 POS System 2100 User Guide Thank you for selecting UTC RETAIL s innovative Model 2100 Point of Sale solution! This guide is designed to acquaint you with the features and functionality of the 2100
More informationParagon Explorer Lite Communication Software
CU-111 APRIL 11, 2013 Paragon Explorer Lite Communication Software For Fireye Paragon Scanners using Windows XP DESCRIPTION Paragon Explorer Lite, is the basic PC based configuration tool for Paragon model
More informationHow To Use A 1232 On A 1236 On A Computer Or A Cell Phone
12-36-1000 Autodialler and Relay Telephone Interface 1.0 INTRODUCTION 12-36-1000 I/O Telephone Interface with AutoDialer The 12-36-1000 is a autodialer and telephone interface that can be used autonomously
More informationT3 Mux M13 Multiplexer
T3 Mux M13 Multiplexer User Manual [Type the abstract of the document here. The abstract is typically a short summary of the contents of the document. Type the abstract of the document here. The abstract
More informationEDI Distributor Control Interface Wiring and Setup Instructions
Universal I/O EDI Distributor Control Interface Wiring and Setup Instructions EDI UNIVERSAL I/O INTERFACE MODULE The only interface needed for EDI-V5 controls Network compatible with all older EDI controls
More informationISHIDA BC-3000. Scale to Scale Communications
ISHIDA BC-3000 Scale to Scale Communications Setup Procedure & Operating Instructions March 2006 PN 94561 Revision History Date Page Description March 2006 Initial publication August 2006 2 Added RS-232
More informationOFF-LINE COMMUNICATIONS WITH CINCINNATI EQUIPMENT Pg. 1 of 5
Pg. 1 of MACHINE TYPE BACKGROUND CAPABILITIES SOFTWARE NEEDED* C. I. SOFTWARE AVAILABLE Autoform - VMEI NO Kermit - Off-Line Programming - -D Programming Autoform - VMEII YES Kermit - Same as above - D
More informationSEC 4100 SYSTEM MONITOR Programmable Serial Interface Card Series 2
SEC 4100 SYSTEM MONITOR Programmable Serial Interface Card Series 2 USER MANUAL Rev. P1.11 September 13, 2006 DeltaV is a trademark of Emerson Process Management, Inc Emerson Process Management, Inc. 1998,
More informationFirmware version: 1.10 Issue: 7 AUTODIALER GD30.2. Instruction Manual
Firmware version: 1.10 Issue: 7 AUTODIALER GD30.2 Instruction Manual Firmware version: 2.0.1 Issue: 0.6 Version of the GPRS transmitters configurator: 1.3.6.3 Date of issue: 07.03.2012 TABLE OF CONTENTS
More informationNOTE: It is the responsibility of the installation organization to have only technically qualified personnel performing the installation.
This quick start guide provides, basic installation information, drawings, first time power-on instructions, and short descriptions of key terms and concepts for installing the EntraGuard Platinum Telephone
More informationRIGtalk. Revision 5. Owner s Manual 2012.
RIGtalk Revision 5 Owner s Manual 2012 www.westmountainradio.com 1020 Spring City Drive Waukesha, WI 53186 262-522-6503 sales@westmountainradio.com 2012 West Mountain Radio, All rights reserved. All trademarks
More informationUSER GUIDE. Ethernet Configuration Guide (Lantronix) P/N: 2900-300321 Rev 6
KRAMER ELECTRONICS LTD. USER GUIDE Ethernet Configuration Guide (Lantronix) P/N: 2900-300321 Rev 6 Contents 1 Connecting to the Kramer Device via the Ethernet Port 1 1.1 Connecting the Ethernet Port Directly
More informationHomeSeer Technologies. HomeSeer Technologies LLC 35 Constitution Dr, Suite C Bedford NH, 03110 www.homeseer.com
HomeSeer Technologies HomeSeer Z-Troller Z-Wave Computer Interface Installation guide HomeSeer Technologies LLC 35 Constitution Dr, Suite C Bedford NH, 03110 www.homeseer.com Description Thank for your
More informationAPR-PRT3 Printer Module: C-Bus Programming Instructions
APR-PRT3 Printer Module: C-Bus Programming Instructions We hope this product performs to your complete satisfaction. Should you have any questions or comments, please visit www.paradox.com and send us
More informationUsing HyperTerminal with Agilent General Purpose Instruments
Using HyperTerminal with Agilent General Purpose Instruments Windows HyperTerminal can be used to program most General Purpose Instruments (not the 531xx series counters) using the RS-232 Serial Bus. Instrument
More informationTroubleshooting and Diagnostics
Troubleshooting and Diagnostics The troubleshooting and diagnostics guide provides instructions to assist in tracking down the source of many basic controller installation problems. If there is a problem
More information1. Make sure that no client accounts are open. 2. Click on Setup, then click Modem. The Modem Setup window will appear.
SECURITY SYSTEM MANAGEMENT SOFTWARE FOR WINDOWS WINLOAD MODEM SETUP The modem setup is a very important step in the connection process. If the modem setup is not properly completed communication between
More informationPRODUCTIVITY THROUGH INNOVATION 600 CONTROL DIRECT DRIVE TECHNICAL/OPERATION MANUAL
Rev. D PRODUCTIVITY THROUGH INNOVATION 600 CONTROL DIRECT DRIVE TECHNICAL/OPERATION MANUAL 10 BORIGHT AVENUE, KENILWORTH NEW JERSEY 07033 TELEPHONE: 800-524-0273 FAX: 908-686-9317 TABLE OF CONTENTS Page
More informationOne Port Serial Server Users Manual Model ESP901, ESP901E
One Port Serial Server Users Manual Model ESP901, ESP901E Documentation Number: ESP901-2303 International Headquarters B&B Electronics Mfg. Co. Inc. 707 Dayton Road -- P.O. Box 1040 -- Ottawa, IL 61350
More informationHow to setup a serial Bluetooth adapter Master Guide
How to setup a serial Bluetooth adapter Master Guide Nordfield.com Our serial Bluetooth adapters part UCBT232B and UCBT232EXA can be setup and paired using a Bluetooth management software called BlueSoleil
More informationWinPFT File Transfer Utility (Catalog No. 2711-ND7)
Technical Data WinPFT File Transfer Utility (Catalog No. 2711-ND7) Overview WINPFT is a stand-alone Windows utility which lets you transfer applications developed for standard PanelView terminals or Dataliner
More informationHow To Connect A Directsofl To A Powerpoint With An Acd With An Ctel With An Dm-Tel Modem On A Pc Or Ipad Or Ipa (Powerpoint) With A Powerline 2 (Powerline
Application Note Last reviewed: 03/17/2008 AN-KEP-003.doc Page 1 of 23 Introduction... 1 Recommended s and ports to use... 1 Cable Wiring... 2 MDM-TEL Configuration ( Wizard)... 3 Direct Logic Communications
More information5-port / 8-port 10/100BaseTX Industrial Ethernet Switch User Manual
5-port / 8-port 10/100BaseTX Industrial Ethernet Switch User Manual Content Overview... 1 Introduction... 1 Features... 3 Packing List... 4 Safety Precaution... 4 Hardware Description... 5 Front Panel...
More informationS88XPressNetLI v1.0. Installation, user and reference manual. 2008 KDesign Electronics, PCB design by RoSoft
S88XPressNetLI v1.0 Installation, user and reference manual 2008 KDesign Electronics, PCB design by RoSoft Table of contents 1 Introduction... 3 2 Specifications... 4 3 Installation... 5 3.1 Connecting
More informationIntesisBox. KNX SAMSUNG Air Conditioning. Gateway for integration of Samsung air conditioners into KNX control systems. RS485.
IntesisBox KNX SAMSUNG Air Conditioning Gateway for integration of Samsung air conditioners into KNX control systems. Integrate Samsung Air Conditioners into KNX. KNX EIB Bus IntesisBox RS485 MIM-B13x/B04A
More informationChassis, Power Supply, and Element Management
Chassis, Power Supply, and Element Management C-COR CHP Max5000 Converged Headend Platform Accelerate deployment of new, revenue generating advanced services Innovative technology creating converged high-
More informationIntesisBox KNX Mitsubishi Heavy Industries AC
IntesisBox KNX Mitsubishi Heavy Industries AC Gateway for integration of Mitsubishi Heavy Indsutries (MHI) Air Conditioners with KNX control systems. 1. Main Features Direct connection to KNX TP-1 (EIB)
More informationEthernet. Customer Provided Equipment Configuring the Ethernet port.
Installing the RDSP-3000A-NIST Master Clock. Ethernet Connect the RJ-45 connector to a TCP/IP network. Equipment The following equipment comes with the clock system: RDSP-3000A-NIST Master Clock Module.
More informationATS Communication Overview
ATS Communication Overview Viewpoint ATS 485 Communication link IBM Compatible Slide 1 of 23 Contents 1. Introduction 2. LonWork 3. Modbus Cards 4. Modbus Factory Configuration 5. Modbus Test Software
More informationINSTALLATION / OPERATION MANUAL API-8/232
INSTALLATION / OPERATION MANUAL API-8/232 MONITOR TECHNOLOGIES INC. Installation of this product in accordance with this manual, applicable codes, and the instructions of the Authority Having Jurisdiction
More informationIntesisBox Modbus Server Fidelio IP
IntesisBox Server Fidelio IP Gateway for integration of Micros Fidelio Ho management system into (RTU and TCP) enabled control systems. Integrate your Micros Fidelio Ho management system into your master
More informationVroom Hardware manual ver. 1.00 Code 114VROOHWE00. Vroom CANBUS USER INTERFACE WITH LCD GRAPHIC DISPLAY AND WITH TEMPERATURE AND HUMIDITY SENSOR
Vroom CANBUS USER INTERFACE WITH LCD GRAPHIC DISPLAY AND WITH TEMPERATURE AND HUMIDITY SENSOR ENGLISH HARDWARE MANUAL ver. 1.00 CODE 114VROOHWE00 page 1 of 22 Important Important Read these instructions
More informationTechnical Manual. For use with Caller ID signaling types: Belcore 202, British Telecom, & ETSI
Technical Manual For use with Caller ID signaling types: Belcore 202, British Telecom, & ETSI Caller ID.com WHOZZ CALLING? POS 2 Caller ID Monitoring Unit Technical Manual For use with Caller ID signaling
More informationUsing Xbee 802.15.4 in Serial Communication
Using Xbee 802.15.4 in Serial Communication Jason Grimes April 2, 2010 Abstract Instances where wireless serial communication is required to connect devices, Xbee RF modules are effective in linking Universal
More informationSTIM202 Evaluation Kit
Table of contents: 1 FEATURES... 2 2 GENERAL DESCRIPTIONS AND SYSTEM CONTENTS... 2 3 SYSTEM REQUIREMENTS... 2 4 GETTING STARTED... 3 4.1 INSTALLATION OF NI-SERIAL CABLE ASSEMBLY DRIVER... 3 4.2 INSTALLATION
More informationIntesisBox ASCII Server - LON
IntesisBox ASCII Server - LON Gateway for integration of LON devices into ASCII enabled control systems. Integrate Air Conditioning from the main manufacturers (DAIKIN, Mitsubishi Electric, Mitsubishi
More informationQuick Installation. A Series of Intelligent Bar Code Reader with NeuroFuzzy Decoding. Quick Installation
Quick Installation A Series of Intelligent Bar Code Reader with NeuroFuzzy Decoding This chapter intends to get your new FuzzyScan scanner working with your existing system within minutes. General instructions
More informationMetasys Historical Data Visualization
Installation Bulletin Issue Date 11/01/01 INSTALLATION BULLETIN Metasys Historical Data Visualization Metasys Historical Data Visualization...2 Introduction... 2 Key Concepts... 3 Overview of MHDV Configuration
More informationMetasys System Direct Connection and Dial-Up Connection Application Note
Metasys System Direct Connection and Dial-Up Connection Application Note Code No. LIT-1201639 Software Release 5.1 Issued August 27, 2013 Supersedes October 4 2010 Refer to the QuickLIT website for the
More informationRS485 Adapters. User Manual October 26, 2008 V1.02 Copyright Light O Rama, Inc. 2006, 2007, 2008 SC485 USB485B USB485 USB485-ISO
SC485 USB485B USB485 USB485-ISO User Manual October 26, 2008 V1.02 Copyright Light O Rama, Inc. 2006, 2007, 2008 This page intentionally blank Table of Contents Introduction... 4 What s in the Box... 5
More informationHWg-STE HWg-STE PoE MANUAL
HWg-STE HWg-STE PoE MANUAL www.hw-group.com Page 2 HWg-STE connectors LED indicators Green: Power & Mode Yellow: Link & Activity SENSORS S1 and S2 ports for connecting temperature or humidity sensors.
More informationTRP-C31M MODBUS TCP to RTU/ASCII Gateway
TRP-C31M MODBUS TCP to RTU/ASCII Gateway User s Manual Printed Feb. 2007 Rev 1.0 Trycom Technology Co., Ltd 1F, No.2-11, Sihu street, Yingge Township, Taipei, Taiwan ROC Tel: 886-2-86781191, Fax: 886-2-86781172
More information4 Port VGA Video Audio Switch with RS232 control
4 Port VGA Video Audio Switch with RS232 control VS410RVGAA *actual product may vary from photos DE: Bedienungsanleitung - de.startech.com FR: Guide de l'utilisateur - fr.startech.com ES: Guía del usuario
More informationAN00140-003: Using Wago CANOpen IO
AN00140-003: Using Wago CANOpen IO Overview Baldor now offers WAGO Modular IO Systems for use with Mint Motion Controllers using the CANOpen field bus interface. The WAGO units provide a very flexible
More informationUser Manual. Thermo Scientific Orion
User Manual Thermo Scientific Orion Orion Star Com Software Program 68X637901 Revision A April 2013 Contents Chapter 1... 4 Introduction... 4 Star Com Functions... 5 Chapter 2... 6 Software Installation
More informationSecure Ethernet Gateway SEG-1 and SEG-M for IEI Access Systems Installation Manual
Secure Ethernet Gateway SEG-1 and SEG-M for IEI Access Systems Installation Manual Section 1: Introduction SECURITY WARNING: New SEG's shipped after April 2008 will have Telnet setup option enabled by
More informationSVA025 Netcom2 FAQ Rev 1. Mitsubishi Netcom 2 FAQ
SVA025 Netcom2 FAQ Rev 1 Mitsubishi Netcom 2 FAQ SVA025 Netcom2 FAQ Rev 1 2 What series of Netcom did we purchase? Netcom 2 FAQ Mitsubishi has several different versions of communications available. 1.
More informationVisorALARM-Manager Application Quick Guide. (Ver. 1.3) Dm 380-I. V:3.0
VisorALARM-Manager Application Quick Guide. (Ver. 1.3) Dm 380-I. V:3.0 1. Installation Requirements 1.1. PC Pentium III processor or higher. Minimum RAM memory: 128 Mbytes Operating system: Windows XP
More informationVicon Flash Upgrade Software
INSTRUCTION MANUAL Notes Refer to XX134 NO. XX134-13-01 REV. 1212 Vicon Flash Upgrade Software It is possible to upgrade software for the SurveyorVFT and Surveyor -Mini Camera Domes through a PC using
More informationWorkshop 7 PC Software - Tracker
Workshop 7 PC Software - Tracker Goal: You will startup and perform advanced setup functions using Tracker PC software. You will also setup equations to control MP503 binary outputs. The Binary Output
More information1.1 Connection. 1.1.1 Direct COM port connection. 1. Half duplex RS232 spy cable without handshaking
POS function Marchen POS-DVR surveillance system is a professional surveillance integrated with POS system. By bringing video and POS transaction data together, the POS-DVR surveillance system provides
More informationomega.com ΩOMEGA RS232 Multi-Drop www.omega.com FMA1600-MDB Multi-Drop Box
omega.com ΩOMEGA RS232 Multi-Drop www.omega.com FMA1600-MDB Multi-Drop Box 1 3/29/2010 Rev.0 DOC-OMEGABB9MAN 2 Introduction FMA1600-MDB Multi-Drop Box Operating Bulletin The FMA1600-MDB Multi-Drop Box
More informationUser Manual. AS-Interface Programmer
AS-Interface Programmer Notice: RESTRICTIONS THE ZMD AS-INTERFACE PROGRAMMER HARDWARE AND ZMD AS-INTERFACE PROGRAMMER SOFTWARE IS DESIGNED FOR IC EVALUATION, LABORATORY SETUP AND MODULE DEVELOPMENT ONLY.
More informationFX-BTCVT Bluetooth Commissioning Converter Commissioning Guide
FX-BTCVT Bluetooth Commissioning Converter Commissioning Guide FX-BTCVT-1 (Bluetooth Commissioning Converter) Code No. LIT-12011665 Issued December 5, 2014 Refer to the QuickLIT website for the most up-to-date
More informationFINS Gateway For OMRON PLCs
1 Purpose This Technical Note describes how to set up a remote collaboration. A remote collaboration consists in configuring, programming or monitoring a PLC from a remote location, without the need of
More informationUsing the AnyBus -X Gateway to Communicate between a DVT camera and a Profibus Master
Using the AnyBus -X Gateway to Communicate between a DVT camera and a Profibus Master Page 1 of 13 Table of Contents 1 OVERVIEW... 3 2 INSTALLING AND CONFIGURING THE ANYBUS -X GENERIC GATEWAY AND ETHERNET
More informationINSTALLATION & SERVICE MANUAL. Display Panel
INSTALLATION & SERVICE MANUAL Display Panel The PowerLine EMS TM is a specialized power distribution and energy management system intended to be used in recreational vehicles. The Control Module is housed
More informationFloat Current Monitor FS3. User Manual
Float Current Monitor FS3 User Manual Version 4.2.1 Copyright Polytronics Engineering Ltd. 2009-2013 All Rights Reserved Table of Contents 2.1 Installing the Core... 9 2.1.1 Installing as Ground Fault
More information