Storage, assembly and maintenance instructions. 24 kv-72.5 kv A CERAMIC BUSHING INSULATIONS. 12 kv 52 kv 250 A 8000 A
|
|
- Esmond Greene
- 7 years ago
- Views:
Transcription
1 CERAMIC BUSHING INSULATIONS Storage, assembly and maintenance instructions 24 kv-72.5 kv A 12 kv 52 kv 250 A 8000 A
2 Ceramic bushing insulators 12 kv 52 kv 250 A 8000 A General information These instructions are applicable to ceramic bushing insulators with rated voltages from 12 kv to 52 kv and rated currents from 250 A to 8000 A. These bushings are designed to operate with the upper part in air (pollution level up to P4) and with the lower part immersed in the transformer oil. Ceramic bushing insulators have been designed and produced in conformity with the standard IEC The specifications, dimensions and description are stated in the catalogue. Packaging All ceramic bushing insulators are shipped inside a cardboard box positioned on a pallet to facilitate transport and storage. Acceptance Upon receiving the bushing, the Customer must carry out the following operations: examine the outer surface of the packaging to check that it is intact; open the packing crate removing the lid ; check that the fastening elements are intact and well secured; check that there are no breakages. If any damages are found, please contact, quoting the data provided in the shipping list Montebello Vicentino (VI) Italy Tel info@comem.com Page 2
3 Rating plate data The rating plate data is indicated on each ceramic bushing insulator in accordance with the standard IEC 60137: name of manufacturer, rated voltage U m, rated current I r, year of manufacture. Storage The ceramic bushing insulator must be stored in the original packaging indoors. Permissible storage temperatures are in the range of -25 C to 60 C. Lifting The ceramic bushing insulator has sturdy packaging; nonetheless, some precautions must be taken during handling to prevent damaging the insulation bushing. Packaged insulation bushing: the ceramic bushing insulator must be handled using the pallet. Insulation bushings out of the crate: to remove the insulation bushing from the crate screw an eyebolt tightly into the upper end of the conductor. The rope for lifting the bushing must be fastened to the eyebolt so that the bushing cannot be damaged during transport. The best position for transport out of the crate is vertical. The bushing must not be handled using the sheds, as this could compromise correct operation. Page 3
4 Operating conditions Altitude: ceramic bushing insulators can be used up to an altitude of 1000 m. For installation at higher altitudes please contact Ambient air and immersion medium temperature: ambient air: maximum 40 C, daily average: maximum 30 C, minimum -25 C, transformer oil: maximum for normal load: 100 C daily average: maximum 90 C Temporary over-voltages: according to the standard IEC Assembly on the transformer box For correct installation of the ceramic bushing insulator follow the procedure below: 1. Make a hole with diameter D1 (see Table 1) in the transformer box, ensuring there are no uneven surfaces that could cause problems for correct operation of the bushing. 2. The stud bolts for securing the bushing (see Table 1) must be placed along a circumference of diameter D2 coaxial with the hole made previously (Figure 1). 3. Position the gasket provided standard (Figure 1). 4. The bushing must be positioned as shown in Figure 2, apply a tightening torque of 15 Nm with stud bolt M10 and 25 Nm with stud bolt M12 to the fixing nuts of the flange (Figure 2). Figure 1 Figure 2 Page 4
5 Voltage (kv) Current (A) Standard Flange Diameter of the hole D1 (mm) Number Thread Stud bolts Diameter D2 (mm) Max height (mm) DIN DIN DIN EN A 80 4 B 80 3 M DIN EN A 6 90 B DIN DIN COMEM DIN COMEM DIN EN M EN EN Table 1 5. The internal insulation shall be filled with oil, so it should come out from the top of the isolator until the air is leaking oil, this can be done through the bleed screw in this insulators larger (figure 3), or smaller ones acting on the hood (figure 4). At the end of this screw the nut over the bolt (figure 3-4) by applying the torque recommended in table 2.
6 6. Optional: spark gap are the horns to be mounted with all accompanying materials as in figure 5 Flag Nut Vent screw Cap Nut Cap Figure 3 Figure 4 Figure 5 Page 6
7 Connecting the cables After carefully choosing the section of the connections to be used, connect them applying the torque recommended in Table 2 as a function of the rated current. Care must be taken over electrical connection to avoid ionization phenomena. In the event that the wires are attached with a terminal connector (Figure 3), we must tighten it so that the whole thread is tightened, then tighten the bolts with a torque as in Table 3. The pair of bolts is determined by the class strength of the bolt, making sure that the connection does not cause overheating. Rated current (A) Nominal torque (Nm) Thread of bolt Nominal torque (Nm) M8 12 M10 15 M12 40 M16 90 Table Table 2 Should it become necessary to disconnect the connections, please loosen the nut to be removed while holding the counter-nuts clamped to avoid damage. Page 7
8 Cleaning Cleaning of the sheds during periodic maintenance of the transformer is recommended. If the bushing has a high level of pollution due to the environment in which it is installed, we recommend cleaning by rubbing the entire surface with a soft sponge soaked in a solution of soap and water at 50 C. The bushing must then be rinsed thoroughly with tap water. Moreover, we recommend cleaning of the sheds at more frequent intervals. Page 8
9 Troubleshooting If malfunctions should occur during normal operation, please consult the following table: Fault Oil loss from the flange of the bushing Oil leaking from the top of the bushing There are hissing noises at the flange There are hissing noises at the connection in air Electric discharge at the air end outside the bushing Abnormal distribution of temperatures in the bushing. Physical phenomenon Leakage Leakage Corona effect Corona effect Electric discharge Thermal effect Solutions Tighten the stud bolts to the recommended torque. Check correct positioning of the gasket. Check the surfaces of the box have no uneven parts or excessive roughness. Better tighten the nut on the hood bushing (figure 3 and 4) Check the voltage applied The correct assembly of the bushing. Check oil inside the bushing insulator. Check whether the conductor connected to the bushing has any edges that cause increased electric field density. The correct assembly of the bushing Check the connection at the air end of the bushing. Check cleanliness of insulating surfaces. Check the connections applying the torque recommended in Table 2. Check that the section of the conductors for connection to the bushing is correct. If the problem is not mentioned in the cases above, please contact: Montebello Vicentino (VI) - Italy Page 9
PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES
PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES BUSHING WITH PLUG CONNECTION WITH OUTER CONE PPS CHARACTERISTICS The PPS bushing can be used as a fixed section for the entry of medium
More informationToroidal Conductivity Sensor
Instruction Sheet PN 51A-/rev.C June 2012 Toroidal Conductivity Sensor For additional information, please visit our website at www.emersonprocess.com/rosemountanalytical.com SPECIFICATIONS Wetted Materials:
More information1ZSE 2750-105 en, Rev. 8. Transformer bushings, type GOE and GOE(2) Technical guide
1ZSE 2750-105 en, Rev. 8 Transformer bushings, type GOE and GOE(2) Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible
More information1ZSC000563-AAC en, Rev. 7. Resin impregnated paper bushing, oil to air, type GSB Technical guide
1ZSC000563-AAC en, Rev. 7 Resin impregnated paper bushing, oil to air, type GSB Technical guide Original instruction The information provided in this document is intended to be general and does not cover
More informationOLI. Oil level indicator
OLI Oil level indicator Oil level indicator Unexpected or accidental oil leakages may occur randomly along transformer s lifetime. Clear indication of oil level inside transformer tank and on load tap
More information33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application
33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application Features Compliant with the IEEE802.3at Standard -40 to +60 C Temperature Range Diagnostic LEDs Full Protection
More informationOutdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points
Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points Features SELV Compliant No Detection Passive Injector Gigabit Compatible Full Protection
More informationInstallation instruction CASAFLEX - Connecting piece DN 100
1 CASAFLEX - 11 10 114,3 x 4,5 3 5 2 4 1 7 6 8 12 9 Do not begin work until you have read the installation instruction carefully. 1 internal backing sleeve 2 graphite packing 3 connecting piece 4 thrust
More information2740 Whitten Rd Bldg 103 Memphis, TN 38133 Telephone 901-380-9290 Email Bwilliams@Dieselcare.net
Fuel Injection Pump Replacement REMOVAL Diesel Care & Performance Inc 1. Disconnect negative battery terminal. 2. Remove throttle linkage. Fuel Injection Pump Bracket 3. Remove injection pump bracket.
More informationSystem 8. ü www.nassmagnet.com ( +49 511 6746-0. System 8
System 8 ü www.nassmagnet.com ( +9 11 7-0 System 8 The name System 8 stands for a modular system of solenoid coils, armature systems, solenoid operators and solenoid valves. The diameter of the armatures
More informationCAUTION. 4. Cable Connections DANGER WARNING CAUTION. 3. Bushing Components
Instruction Manual for POC Bushings 1. Scope This instruction contains general procedures to be followed during receiving, installation, storage and maintenance of all PCORE POC bushings. This instruction
More informationOperating Instructions Drill rig DRU160
Operating Instructions Drill rig DRU160 Index 000 / 001 Original operating instructions 10988825 en / 20.10.2009 Congratulations! With a Hydrostress unit from TYROLIT you have chosen a tried and tested
More informationa Nexans company Catalogue 2014
a Nexans company Catalogue 2014 Nexans Network Solutions Div. Euromold COMPANY PRESENTATION EUROMOLD Euromold is the leading European specialised designer, manufacturer and distributor of prefabricated
More informationTECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW52AL AW64AL AW52AL 387030095 AW64AL 0.8180.463.0 07/05
TECHNICAL DATA & SERVICE MANUAL INDOOR UNIT: AW52AL AW64AL SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. AW52AL 387030095 AW64AL 387030096 0.8180.463.0 07/05 IMPORTANT! Please read before installation
More informationINSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS FOR EXHEAT INDUSTRIAL IMMERSION HEATERS (INCLUDING FLAMEPROOF)
INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS FOR EXHEAT INDUSTRIAL IMMERSION HEATERS (INCLUDING FLAMEPROOF) Please read these instructions thoroughly before installation and ensure they are passed
More informationGas insulated wall bushing, type GGFL
1ZSC000563-AAJ en, Rev. 1 Gas insulated wall bushing, type GGFL Installation and maintenance guide, applicable for wall bushings: 1ZSC002776-AAA, GGFL 400 1ZSC003517-AAA, GGFL 600 1ZSC002777-AAA, GGFL
More information11. COOLING SYSTEM 11-0 COOLING SYSTEM BET & WIN 50
11 COOLING SYSTEM SERVICE INFORMATION------------------------------------------------ 11-1 TROUBLESHOOTING----------------------------------------------------- 11-1 RADIATOR ------------------------------------------------------------------
More informationSureSite Magnetic Liquid Level Indicator
SureSite Magnetic Liquid Level Indicator Instruction Bulletin No. 177664-1 (Rev. E) Section 1: Weldments Thank you for purchasing the GEMS SureSite Magnetic Level Indicator. Please read this document prior
More informationCylinder head gasket, replacement
"VCC065612 EN 20110604" 1(7) Cylinder head gasket, replacement Special tools: 999 5098 Disconnect battery earth lead Drain coolant Remove heat shield over exhaust manifold. (Only the two bottom bolts on
More informationLED 18W/12V SWIMMING POOL LIGHT WITH REMOTE CONTROL INSTALLATION AND OPERATING INSTRUCTIONS
LED 18W/12V SWIMMING POOL LIGHT WITH REMOTE CONTROL INSTALLATION AND OPERATING INSTRUCTIONS i Read the operating instructions Contents I. Pack contents... 3 II. Basic information... 3 III. Positioning
More informationQuartzone Infrared Quartz Tube & Metal Sheathed Electric Heaters
Quartzone Owner s Manual File E97759 COMFORT S for INDOOR* and OUTDOOR** USE *Excluding Residences ** With Quartz Elements and when mounted Underneath an Overhang by means of brackets out of the reach
More informationSUB Universal water baths SBB Boiling baths JB, PB Unstirred water baths
SUB Universal water baths SBB Boiling baths JB, PB Unstirred water baths Operating instructions Universal water baths SUB6: 6 litres SUB14: 14 litres SUB28: 28 litres SUB36: 36 litres Boiling baths SBB6:
More informationSTORAGE, INSTALLATION AND MAINTENANCE PROCEDURES
GATE VALVE O.S. & Y 1.0 Periodic Inspections 1.1 The valve stem packing should be inspected at least monthly. If the stem packing shows signs of leakage, simply tighten the adjusting nuts to compress the
More informationInstructions Manual. Electromagnetic sensor Series FLOMID FX. instrumentation for fluids. R-MI-FlomidFX Rev.: 0 English version
instrumentation for fluids Electromagnetic sensor Series FLOMID FX Instructions Manual! Conforms with the Pressure Equipment Directive 97/23/EC. 0830 This equipment is considered as being a pressure accessory
More informationAgilent X/P/K281C Adapters
Agilent X/P/K281C Adapters Including Options 006, 012, 013, 106 Operating and Service Manual Contents 1 Introduction 7 Product Overview 8 Options 8 Instruments Covered by Manual 10 2 Installation 11 Initial
More informationSTEERING HANDLEBAR/FRONT WHEEL/ FRONT SHOCK ABSORBER
14 14 STEERING HANDLEBAR/FRONT WHEEL/ SCHEMATIC DRAWING ------------------------------------------------- 14-1 SERVICE INFORMATION------------------------------------------------ 14-2 TROUBLESHOOTING-----------------------------------------------------
More informationErgo-Pro Single Line Solar Station Installation and Operating Instructions
Rp 3/4 Ergo-Pro Single Line Solar Station Installation and Operating Instructions Item No Pump type 677.21.70 WILO ST 15/6 13 2 4 11 Technical Specifications Max. operating pressure: 6 bar Max. operating
More informationSection 6 Brake Drum Failure Analysis. Brake Drum Wear Conditions. What is Normal Wear? What is Deep or Excessive Wear? WARNING. Deep, Uniform Wear
Section Brake Drum 6 Failure Analysis WARNING To prevent serious eye injury, always wear safe eye protection when you perform vehicle maintenance or service. Figure 6.1 ASBESTOS AND NON-ASBESTOS FIBERS
More information25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp and 1250 Amp
Page 1 2015 Grounded Metal Equipment Plate Equipment Connection Bus Bar or Other Component 15 kv or 25 kv Separable Insulated Connector (elbow) Equipment Connection Power Cable Power Cable Grounded Metal
More informationCooling system components, removing and installing
Engine BHW Cooling system components, removing and installing Page 1 / 24 19-1 Cooling system components, removing and installing Warning! When doing any repair work, especially in the engine compartment,
More informationThis instruction is valid for all ACD pump models shown on page 2
Screw pumps ACD Maintenance and Service Instruction This instruction is valid for all ACD pump models shown on page 2 Contents Page List of components 2 Exploded view/ordering code 3 Service intervals
More informationChar-Lynn Hydraulic Motor. Repair Information. 10 000 Series. October, 1997
Char-Lynn Hydraulic Motor October, 1997 Repair Information Geroler Motor Two Speed 001 27 Retainer inside bore of valve plate bearingless motors only 4 15 16 3 6 35 Parts Drawing 25 2 2 1 19 17 36 40 47
More informationImportant: Please read these instructions carefully and completely before starting the installation. TITAN Fuel Tanks
TITAN pt. no.: 03 0000 0120 Important: Please read these instructions carefully and completely before starting the installation. TITAN Fuel Tanks INSTALLATION INSTRUCTIONS G e n e r a t i o n V Extended
More informationTRS 090/105 Compressor. Repair Procedures
TRS 090/105 Compressor Repair Procedures GENERAL FGG All repair and service operations should be performed on a clean bench and with the use of clean tools. Use genuine parts and correct tools for all
More information5800 Temperature Sensor Cable Assembly
5800 Temperature Sensor Cable Assembly Removal and Replacement Instruction Sheet #60-4702-070 Revision D, January 14, 2013 Overview The 5800 has two refrigeration temperature sensors, one attached to the
More informationMaintenance and Instruction Manual. December 2011 Rev. 01 Page 1 of 12
Maintenance and Instruction Manual December 2011 Rev. 01 Page 1 of 12 Table of Contents 1. Description of product and function 1.1 The NOREVA non-return valve range 1.2 Correct use 1.3 Transport and storage
More informationTrunnion-Design Ball Valves
Trunnion-Design Ball Valves 12" 20" (DN 300 500) Series 7150 12" (DN 300) Series 730S 12" 20" (DN 300 500) Series 7300 14" 24" (DN 350 600) Series 9150 14" 24" (DN 350 600) Series 9300 Installation, Maintenance
More informationINSTALLATION INSTRUCTIONS: Viewline 52 mm
-5 Safety information The product was developed, manufactured and inspected according to the basic safety requirements of EC Guidelines and state-of-the-art technology. The instrument is designed for use
More informationFeed-through terminal block - SSK 110 KER-EX - 0502058
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's documentation. Our General Terms of Use for Downloads are valid
More informationCo-location Interconnect Power Panel (CIPP) Installation Guide
Co-location Interconnect Power Panel (CIPP) Installation Guide Document INS-97xxxxxxx This guide covers the following part numbers- Trimm 97xxxxxxx Series Table of Contents Section 1 - General Information...
More informationConnecting the Channel A
20 Edge Lighting. All Rights Reserved. Installation Instructions for Cirrus Channel Suspension T, Tubular Lens w/2sq or 2RD Canopy IMPORTANT INFORMATION - This product is suitable for indoor locations.
More informationELECTRIC MOTOR TEFC OPERATION & MAINTENANCE. meps Approved
SOUTH AUSTRALIA HEAD OFFICE (Accounts / Payments) 34-36 Kinkaid Avenue NORTH PLYMPTON SA 5037 Ph: (08) 8295 5566 Fax: (08) 8295 5533 VICTORIA 23 James Street CLAYTON SOUTH VIC 3169 Ph: (03) 9544 2324 Fax:
More informationPressure monitoring equipment for oil-sf 6. bushings, type GOEK
Pressure monitoring equipment for oil-sf 6 bushings, type GOEK Installation and maintenance guide 5693 827-6 en, Rev. 3, 2002-01-30 This document must not be copied without our written permission, and
More informationIOM SERIES 820-E/P Electro-Pneumatic Positioner
FLUID CONTROL DIVISION Parker Hannifin Corporation 95 Edgewood Avenue New Britain, CT 06051 Telephone (860) 827-2300 IOM SERIES 820-E/P Electro-Pneumatic Positioner INSTALLATION, OPERATING & MAINTENANCE
More informationXL PREMIUM OIL COOLER KIT
-J05 REV. 0-0-0 XL PREMIUM OIL COOLER KIT GENERAL Kit Number 0008 Models For model fitment information, see the P&A Retail Catalog or the Parts and Accessories section of www.harley-davidson.com (English
More informationSELECTION, APPLICATION AND MAINTENANCE
DIESEL PROTECTION SYSTEMS Automatic Diesel Engine Shut Down System for Safe Area Applications SELECTION, APPLICATION AND MAINTENANCE Series 300 Series 310 SYSTEM DESCRIPTION Suitable for attended engine
More informationInstallation Guide of Sunrise Solartech PV Modules. Term 2013. Contents. Purpose of this guide. General. Safety precaution for installing a solar
Installation Guide of Sunrise Solartech PV Modules Term 2013 Contents Purpose of this guide General Safety precaution for installing a solar Photovoltaic system Product Identification Mechanical Installation
More informationInstallation Guide 2010 BMW S1000RR Full Exhaust System
Installation Guide 2010 BMW S1000RR Full Exhaust System!! THIS PRODUCT IS DESIGNED FOR USE IN CLOSED COURSE RACING AND IS NOT INTENDED FOR HIGHWAY USE!! Congratulations on the purchase of your new TaylorMade
More informationJames M. Pleasants Company
James M. Pleasants Company SUBMITTAL DATA GAINESVILLE MECHANICAL DECEMBER 20, 2013 PROJECT: GSU: J-183 HUMANITIES LAW BLDG. QUOTE NO:12116 ENGINEER: STEVENS & WILKINSON GASKETED PLATE HEAT EXCHANGER Tag:
More informationBRAKE DRUM AND ROTOR SERVICE INFORMATION
SERVICE INFORMATION To achieve maximum drum life and optimum performance, proper brake maintenance and brake balance are essential. Consult your truck or trailer manufacturer s maintenance manual for proper
More informationExplosion proof enclosures
1 of 7 Explosion proof enclosures DE8 C 2 of 7 The Ex d enclosures are rugged and designed for harsh environment like: Oil and gas industry Chemical industry Pharmaceutical industry Agribusiness Without
More informationType 3244-1 and Type 3244-7 Pneumatic Control Valves. Type 3244 1 (left) and Type 3244-7 (right) Mounting and Operating Instructions EB 8026 EN
Type 3244-1 and Type 3244-7 Pneumatic Control Valves Type 3244 1 (left) and Type 3244-7 (right) Mounting and Operating Instructions E 8026 EN Edition July 2014 Definition of signal words DNGER! Hazardous
More informationTITAN Fuel Tanks. INSTALLATION INSTRUCTIONS G e n e r a t i o n V
TITAN pt. no.: 02 0000 0143 Important: Please read these instructions carefully and completely before starting the installation. TITAN Fuel Tanks INSTALLATION INSTRUCTIONS G e n e r a t i o n V Extended
More informationOUTDOOR DISCONNECTORS A division of ACTOM (Pty) Ltd
OUTDOOR DISCONNECTORS A division of ACTOM (Pty) Ltd ACTOM OUTDOOR DISCONNECTORS Single Side Break (SSB) Disconnector 22-132 kv, 800-1 A, 25 ka - 3s Typical bearing assembly. Voltage range 11 kv to 132
More informationFinding and Fixing Oil leaks on the LT5 Engine Marc Haibeck
Finding and Fixing Oil leaks on the LT5 Engine Marc Haibeck Most LT5 s drip oil on the floor by the time 10,000 miles are covered. This may be disappointing, but it is not as bad as it may seem. Here s
More informationFront brakes (FN- 3), servicing
j a t Front brakes (FN- 3), servicing 46-1 Front brakes, servicing Note: Install complete repair kit. After replacing brake pads and before moving vehicle, depress brake pedal several times firmly to properly
More informationSTEERING SYSTEM - POWER
STEERING SYSTEM - POWER 1990 Nissan 240SX 1990 STEERING Nissan - Power Rack & Pinion Axxess, Maxima, Pulsar NX, Sentra, Stanza, 240SX, 300ZX DESCRIPTION The power steering system consists of a rack and
More informationSubmersion/Insertion Toroidal Sensor
Instruction Sheet PN 51A-228/rev.P December 2010 Model 228 Submersion/Insertion Toroidal Sensor For additional information, please visit our website at www.emersonprocess.com/raihome/liquid/. CAUTION SENSOR/PROCESS
More information39HQ Airovision Air Handling Units
39HQ Airovision Air Handling Units Mounting instructions CONTENTS 1 - TRANSPORT AND LIFTING INSTRUCTIONS... 3 1.1 - General... 3 1.2 - Transport and storage... 3 1.3 - Roof edge protection during transport
More informationWE-350 Series ¼ Turn Electric Actuator
WE-350 Series ¼ Turn Electric Actuator Operation and Installation Manual Pg 1 (Rev. 020113) Table of Contents 1.0 General 1.1 Pre-Installation Inspection 1.2 Storage 1.3 Features & General Information
More informationLEVEL GAUGES WITH MAGNETIC JOINT L 14 - L 22 - L 34
LEVEL GAUGES WITH MAGNETIC JOINT L 14 - L 22 - L 34 2 LEVEL GAUGES WITH MAGNETIC JOINT SIZE Ø 140/220/340 58 58 TYPE LA TYPE LA 14 30 S 22 33 TYPE LA 22-34 NO. HOLES Ø D2 76 O-RING CENTRE OF THE CONSERVATOR
More informationInstallation. Smart-UPS VT MGE Galaxy 3500. Maintenance Bypass Panel. 10-40 kva 400 V
Installation Smart-UPS VT MGE Galaxy 3500 Maintenance Bypass Panel 10-40 kva 400 V Contents Safety.................................................. 1 Save these instructions...................................
More informationEVC40 EMERGENCY VOICE COMMUNICATION SYSTEM
EVC40 EMERGENCY VOICE COMMUNICATION SYSTEM INSTALLATION MANUAL Protec Fire Detection PLC, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0) 1282 717171 Fax: +44 (0) 1282 717273
More information3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance
SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132
More informationINSTRUCTIONS AND PARTS LIST FOR MODEL 70H & 75H HAND-OPERATED HYDRAULIC PRESS
INSTRUCTIONS AND PARTS LIST FOR MODEL 70H & 75H HAND-OPERATED HYDRAULIC PRESS SETTING UP THE PRESS FOR OPERATION For shipping convenience, the gauge, pump handle, hoist crank, screw nose and base angles
More informationINSTRUCTION. Industrial Sewing Machines. No. 010012. First published : June 1997 Second edition : March 2001
INSTRUCTION Industrial Sewing Machines First published : June 1997 Second edition : March 2001 No. 010012 INTRODUCTION Thank you for your purchasing Kansai Special's DLR Series. Read and study this instruction
More informationAM/FM ANTENNA RELOCATION KIT
-J0 REV. 008-09-0 AM/FM ANTENNA RELOCATION KIT GENERAL Kit Number 766-09 Models This kit is used to relocate a fender-mounted AM/FM antenna to a Detachable Tour-Pak on specific model motorcycles. For model
More informationReverse Cycle Inverter Split System Air Conditioner
Reverse Cycle Inverter Split System Air Conditioner Model Number TAC-09CHSA/JAI5 INSTALLATION MANUAL Contents 03 Warranty Details 04 Welcome 05 General Safety Instructions 06 Product Overview 07 Selecting
More informationEZ-Steer Assisted Steering System
EZ-Steer Assisted Steering System Installation Instructions Platform Kit P/N 53059-54 Case IH CVX 1135 CVX 1145 CVX 1155 CVX 1170 CVX 1190 CVX 1195 CVX 135 CVX 145 CVX 155 CVX 175 CVX 195 New Holland TVT
More informationSplit-type Air-Conditioner INSTALLATION MANUAL CONTENTS FOR INSTALLER MXZ-3A30NA MXZ-4A36NA ATTENTION. English. Français. Español
Split-type Air-Conditioner MXZ-3A30NA MXZ-4A36NA INSTALLATION MANUAL Refer to the installation manual of each indoor unit for indoor unit installation. English Français Español ATTENTION This manual mentions
More informationWaterproof Connectors for Outdoor Use
Waterproof Connectors for Outdoor Use HR41A Series Mated condition diagram Nut-tightening rear mount type (panel thickness=mm) 70.5 Features 1. Waterproof connector designed for outdoor use Light-weight
More informationChecking Wheel Brakes Wear
Issue 1 en 1 Checking Wheel Brakes Wear Contents Disc Brakes... 3 Removing the wheels... 4 Checking the Brake Pads... 5 Check brake disc thickness... 7 Checking brake disc for cracks... 8 Drum Brakes...
More information3-Component Measuring System
Force 3-omponent Measuring System for utting Force Measurement During Turning Modular system for measurement of cutting forces when turning outside and inside diameters on turret lathes. Machine adapters
More informationREMOVAL AND INSTALLATION
303-01C-1 REMOVAL AND INSTALLATION Engine Body On Special Tool(s) Adapter For 303-D043 303-D043-02 or equivalent Special Tool(s) 303-01C-1 Turbocharger Lifting Bracket 303-1266 Wrench, Fan Clutch Nut 303-214
More information6720616592.00-1.SD. Flat roof. Rack Mounting. Installation instructions 6 720 647 036 (2010/11) AU
6720616592.00-1.SD Flat roof Rack Mounting AU Installation instructions 2 Contents AU Contents 1 Key to symbols and safety instructions....... 3 1.1 Explanation of symbols................ 3 1.2 Safety
More informationRear wheel brakes, servicing. Стр. 1 из 45. Note:
Volkswagen Touareg - Rear wheel brakes, servicing Стр. 1 из 45 46-2 Rear wheel brakes, servicing Rear brakes, FN 44 brake caliper, servicing Note: After replacing brake pads, depress brake pedal firmly
More informationCommand devices Pull-wire emergency stop switches One-side operation ZS 71 range 6.1 6.1.1 6.1.1.1. 312 Schmersal -10 0 10 20 30 40 50 60 70 T [] C
.1.1.1 One-side operation ZS 71 range 40 30 ø10 10 53,5(63)* 6 8 18 24 105 33 56 12 22 M20x1,5 52 17,5 42 15 Features To EN 418 / IEC 60947-5-5 Metal enclosure 2 contacts Small body 2 cable entries M20
More information225-230T-05-S2. Rotary drive without spring return. Technical data sheet. Description. Technical data. Actuators
Actuators Technical data sheet 225-230T-05-S2 Rotary drive without spring return Description Actuator for adjusting air dampers of 90 angle of rotation to be used in HVAC installations. Torque Motor 5
More informationElektromotoren und Gerätebau Barleben GmbH
Elektromotoren und Gerätebau Barleben GmbH OPERATING INSTRUCTIONS Transformer Protection Relay (Buchholz principle) Elektromotoren und Gerätebau Barleben GmbH Table of contents Page 1 Safety instructions
More informationInstallation guide for the SafeLine type anchorage device. Tested in compliance with EN 795: 1996. No.: SE-...
Installation guide for the SafeLine type anchorage device Tested in compliance with EN 795: 1996 No.: SE-... Version: 09.10.2008 SE 67 Subject to technical alterations! Contents 1. General information
More informationINSTRUCTION MANUAL Oil level indicator with pointer
INSTRUCTION MANUAL Oil level indicator with pointer 5COL868200 REV.01 I II CONTENTS 1. SAFETY... 1 1.1 Safety instructions... 1 1.2 Specified applications... 1 1.3 Safety notes on the equipment operation...
More informationBLADE S-MAX Cabinet for Blade Server
Cabinet for Blade Server 1 2 Overview Material specification Corner verticals: 1.5 mm steel End frames: 1.5 mm steel Panel mounts: 2.0 mm steel Panel mount supports: 1.5 mm steel Side panels, door and
More informationAM/FM ANTENNA KIT (TOUR-PAK MOUNT)
-J077 REV. 008-0-0 AM/FM ANTENNA KIT (TOUR-PAK MOUNT) GENERAL Kit Number 7-98A Models For model fitment information, see the P&A Retail Catalog or the Parts and Accessories section of www.harley-davidson.com
More informationVolkswagen Jetta, Golf, GTI 1999, 2000 Brake System 47 Brakes - Hydraulic Components (Page GR-47)
47 Brakes - Hydraulic Components (Page GR-47) FS III front brake calipers, servicing Front brake caliper piston, removing and installing FN 3 front brake calipers, servicing Front caliper piston, removing
More informationDuctless Split Air Conditioner
Ductless Split Air Conditioner Installation Manual Indoor HSU09VHG(DB)-W HSU12VHG(DB)-W HSU18VHH(DB)-W HSU24VHG(DB)-W Outdoor HSU09VHG(DB)-G HSU12VHG(DB)-G HSU18VHH(DB)-G HSU24VHG(DB)-G Table of Contents
More informationSHOT BLAST CABINET MODEL NO: CSB20B
SHOT BLAST CABINET MODEL NO: CSB20B PART NO: 7640110 USER INSTRUCTIONS GC0216 INTRODUCTION Thank you for purchasing this CLARKE Shot Blast Cabinet which is designed for professional workshop use. Before
More informationInstallation Instructions
PUSH Installation Instructions A DA C O M PLIA NT shown with optional Bradley 90-75 faucet Front-Mounted Barrier Free Rectangular Bowl Stainless Steel Lav Table of Contents Pre-Installation Information...........2
More informationEasy Tool Retracting System CMC-SR2159ER36
Easy Tool Retracting System CMC-SR2159ER36 Pepperl+Fuchs, Inc. 1600 Enterprise Parkway Twinsburg, Ohio 44087 Phone: +1 330 486 0002 e-mail: pa-info@us.pepperl-fuchs.com Mounting the Easy Tool Refer to
More informationCHARISMA SHOWER/TUB DOOR INSTALLATION INSTRUCTIONS
CHARISMA SHOWER/TUB DOOR INSTALLATION INSTRUCTIONS IMPORTANT DreamLine reserves the right to alter, modify or redesign products at any time without prior notice. For the latest up-to-date technical drawings,
More informationDirectory chapter 04
M Directory chapter 04 D-Sub Mixed subminiature D connectors New Page D-Sub mixed connector system general information................... 04.02 Contact arrangements............................................
More informationINSTALLATION INSTRUCTIONS: Viewline 85 mm
1-10 1 Safety information The product was developed, manufactured and inspected according to the basic safety requirements of EC Guidelines and state-of-the-art technology. The unit is designed for use
More informationElektromotoren und Gerätebau Barleben GmbH
Elektromotoren und Gerätebau Barleben GmbH OPERATING INSTRUCTIONS Transformer Protection Relay NM Series (Buchholz principle) Elektromotoren und Gerätebau Barleben GmbH Table of contents Page 1. Safety
More informationFloat and Thermostatic Traps Series H, C and X
Hoffman Specialty Installation & Maintenance Instructions HS-(E) and Thermostatic Traps Series H, C and X Series C & NPT Series C NPT Series X NPT Series C NPT Series H Ratings Maximum Max. Operating NPT
More informationRedundancy Module QUINT-DIODE/40
Redundancy Module QUT DIODE provides: 00% decoupling of power supplies connected in parallel Can be installed in potentially explosive areas Load currents up to 60 A supported Easy assembly by snapping
More informationATS Overhead Table Shelf System INSTRUCTION MANUAL
ATS Overhead Table Shelf System INSTRUCTION MANUAL ATS Overhead Table Shelf System Instruction Manual Warranty Newport Corporation warrants this product to be free of defects in material and workmanship
More informationGISMA UNDERWATER CONNECTORS SERIES 40
CONTENTS SEITE / PAGE GENERAL 4 GENERAL ARRANGEMENT 5 DESIGN MECHANICAL FEATURES 7 FIBRE OPTIC FEATURS 7 ELECTRICAL FEATURES 7 REFERENCE SYSTEM 8 REFERENCE SYSTEM CONTACTS 9 CONTACT LAYOUTS 9 SUGGESTIONS
More informationAllen-Bradley 1397 400-600HP AC Line Filter Kit
Installation Instructions IN Allen-Bradley 1397 400-600HP AC Line Filter Kit Cat. Nos. 1397-LF600 What This Option Provides What This Kit Contains This option is intended to be applied when the primary
More informationDXPE*J 85 320/215 ED. DIRECtIONAL CONtROL VALVE PILOt OPERAtED, WItH OBE AND FEEDBACK. Q max (see performance table) SERIES 30
85 320/215 ED DXPE*J DIRECtIONAL CONtROL VALVE PILOt OPERAtED, WItH OBE AND FEEDBACK SUBPLAtE MOUNtINg DXPE5J CEtOP P05 DXPE5RJ ISO 4401-05 (CETOP R05) DXPE7J ISO 4401-07 (CETOP 07) DXPE8J ISO 4401-08
More informationOperation Manual For NDJ-8S Digital Rotary Viscometer
Operation Manual For NDJ-8S Digital Rotary Viscometer 1 Contents 1. General... 2 2. Main technical data... 2 3. Working principle... 2 4. Installation... 3 5. Operation procedures... 4 6. Precautions...
More informationTechnical Specification for Oil insulated Transformers U m < 24 kv up to 1250 kva
to 1250 kva Page 1/10 Technical Specification for Oil insulated Transformers U m < 24 kv up to 1250 kva This technical specification is valid for the business unit E.ON Sweden of the market unit E.ON Nordic.
More information