IOM SERIES 820-E/P Electro-Pneumatic Positioner

Size: px
Start display at page:

Download "IOM SERIES 820-E/P Electro-Pneumatic Positioner"

Transcription

1 FLUID CONTROL DIVISION Parker Hannifin Corporation 95 Edgewood Avenue New Britain, CT Telephone (860) IOM SERIES 820-E/P Electro-Pneumatic Positioner INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS 820 SERIES ANGLE BODY VALVES 2-WAY NORMALLY CLOSED CONTAINING INTEGRATED E/P POSITIONER! WARNING GENERAL SAFETY INSTRUCTIONS BEFORE INSTALLATION FAILURE OR IMPROPER SELECTION OR IMPROPER USE OF THE PRODUCTS AND/OR SYSTEMS DESCRIBED HEREIN OR RELATED ITEMS CAN CAUSE DEATH, PERSONAL INJURY AND PROPERTY DAMAGE. This document and other information from Parker Hannifin Corporation, its subsidiaries and authorized distributors provide product and/or system options for further investigation by users having technical expertise. It is important that you analyze all aspects of your application, including consequences of any failure, and review the information concerning the product or system in the current product catalog. Due to the variety of operating conditions and applications for these products or systems, the user, through its own analysis and testing, is solely responsible for making the final selection of the products and systems and assuring that all performance, safety and warning requirements of the application are met. The products described herein, including without limitation, product features, specifications, designs, availability and pricing, are subject to change by Parker Hannifin Corporation and its subsidiaries at any time without notice. Carefully read installation, operation and maintenance procedures prior to installing or servicing valve. Do not use valve as a safety shut-off valve when making repairs. Do not install a valve before depressurizing system down to atmospheric pressure. Care must be taken to ensure that the valve materials selected are suitable for the media being handled. Parker assumes no liability for damage caused by improper material selection in the case of corrosion from aggressive media. Caution: Do not, at any time, make any alteration or modifications to any angle body valves without the express and written approval of Parker s Fluid Control Division. DESCRIPTION These valves are 2-way normally closed (N.C.) valves. The product line contains stainless construction. The valves can be actuated pneumatically. The pilot operated models require a minimum operating pressure differential to ensure valve operation. Pilot valves may be ordered with either NEMA 2, 4, 4X integrated coils for ordinary locations or NEMA 4, 4X, 7, and 9 for hazardous locations: Divisions I and II; Class I, Groups A, B, C, and D; Class II, Groups E, F, and G. PRINCIPLES OF OPERATION 2-way 820 SERIES - NORMALLY CLOSED VALVES The angle seat valve is kept closed by a spring which presses against a piston and piston rod forcing the seating seal tightly against the valve seat. When pressure is applied to the actuator pilot connection, the piston, piston rod and thus the seating seal are raised opening the valve. The valve tightly closes when pressure is removed from the pilot connection. The maximum permitted angle body valve pressure and pilot valve pressure and temperature ranges are described on the valve nameplate. CAUTION: A minimum pilot operating pressure differential is required for proper angle valve operation. Installation Instructions Mounting position and pressure limits: Valves can be mounted directly on piping and are designed to operate in any position. The valves may be installed in any line regardless of the direction in which the line runs. However, for optimum life and performance the valves should be mounted vertically upright so as to minimize wear and reduce the possibility of foreign matter accumulating inside the stem area. Pilot valve line pressure, voltage and frequency must conform to nameplate rating. Allow adequate clearance above valve for removal of coil. Page 1

2 WARNING: The actuator is spring loaded. Depressurize system and turn off electrical power to the pilot valve before attempting repair. The coil must not be energized unless it is installed on the valve. Otherwise, the coil will overheat and burn out. Failure to depressurize the system could result in injury. Dismantle the actuator circle clip exclusively with the appropriate tools provided in the repair kit only. Follow the instructions provided in the repair kit. CAUTION: The valve body need not be removed from the line. When dismantling the actuator assembly, it may be necessary to provide proper support to prevent the valve from rotating thereby causing damage to piping. Where the valve is to be removed from the piping system, the pipeline must be drained completely before removing the valve especially with hazadous or aggressive media that can be hazardous to health. Installation Steps Installation must be done according to all applicable Safety Codes and Standards and by qualified personnel. Inspect valve prior to installation. actuators must not be installed. Damaged valves or Ensure that the valves are installed whose pressure class, line pressure, type of connection and connection dimensions correspond to the usage conditions. WARNING: Do not install a valve whose permitted pressure / temperature ratings are inadequate to meet the operating conditions. Threaded connections are the most common. ANSI flanges, welded ends and tri-clamps are also available. Piping: Remove any protective enclosures from the body ports and connect line pressure to the inlet port of the valve. An arrow on the body indicates direction of flow. Use of Teflon tape, thread compound or sealant is permissible, but should be used sparingly to male pipe threads only. Connect outlet line to the opposite port. Ports should not be subjected to excessive torque by use of an oversized wrench, wrench extension or by impacting the wrench handle. Do not use the valve to stretch or align the pipe. Using the pipe to close a large gap can distort the valve or at least stress it unduly, and possibly cause it to malfunction, or the threaded ports may be damaged or stripped. Flanges: For flanged mounted valves, follow applicable ANSI, DIN, JIS specifications for bolting and torque recommendations. The bolt should pass first through the mounting flange before engaging the valve flange. Allow proper spacing for installing the valve. Do not use the valve to stretch or align the pipe. Using flange bolts to close a large gap can distort the valve or at least stress it unduly, and possibly cause it to malfunction, or the bolts may be damaged or stripped. The flange endings on the pipeline must align with the connection flanges on the valve and the faces must be parallel. Flanges which are out of alignment or not parallel may result in unacceptable stresses in the pipeline during installation and could thereby damage the valve. Welding: Care should be taken when soldering connections to avoid damage to synthetic internal parts. If pipeline welding is to be performed, care must be taken to ensure the cleanliness of both joints. It is recommended that the flame be directed away from the valve body. Cool body with a wet cloth or heat sink on the extensions at the body to prevent overheating while soldering. E/P POSITIONER Connections The original adjustment of the i/p positioner was performed with the positioner in the vertical position. When changing the original position, it is necessary to readjust the zero setpoint and end values. Connect the air supply with the corresponding connection P (G1/8). CAUTION: Supply air must be instrument quality free of water and oils. The pneumatic control signal is connected to connection W (G1/8). CAUTION: The control signal air pressure must NOT exceed 90 psi (6 bar). The i/p positioner is pre-set at 58 psi (4 bar) supply air pressure. Variations in supply air pressure from the pre-set value requires the i/p positioner to be adjusted. Input Signal Connection The connection of the input signal is provided bya 2m twoterminal clamp located in a side-mounted clamp adapter. The clamp adapter with the cable bushing is closed by a screwed cap. The polarity depends on the operating mode of the valve as follows: Standard Ordinary Location Operating Mode: Rising input signal brown + opens the valve Rising input signal closes the valve white or black brown white or black + Explosion Proof Operating Mode: Rising input signal 1 or brown + opens the valve 2 or black - Rising input signal 1 or brown + (works adjustment) closes the valve 2 or black - (works adjustment) The factory adjustment of the i/p positioner is stamped on the label. The electrical signal is converted to a signal pressure by the e/p converter. This pressure can be controlled by a gauge fitted into the G1/8 manometer connection port when the threaded stopper plug is removed. This eases adjustment and troubleshooting. E/P Positioner Adjustment Both zero set-point and end value (span) of the converter have to be adjusted: ZERO SET-POINT ADJUSTMENT: 1. Remove the zero set-point cap. 2. Turn the spur wheel with a screwdriver + increases converter pressure - decreases converter pressure Page 2

3 SPAN ADJUSTMENT: 1. Remove bleeder screw 2. Turn trimmer with a small screwdriver. counterclockwise increases converter pressure clockwise decreases converter pressure It may be necessary to repeatedly alternate the zero and span adjustments as they influence each other. Rising input signal opens the valve, springs closes valve, signal range 0-20 ma Connect the current source for the input signal (input resistance < 200 ohms for standard location) (input resistance < 420 ohms for explosion proof location) Input signal 0 ma Input signal 2 ma Input signal 20 ma valve is completely closed valve starts to open 4 ± 0.4 psi (0.3 ± 0.03 bar) (adjust with ZERO ) valve is completely opened 15 ± 0.4 psi (1.0 ± 0.03 bar) (adjust with SPAN ) Rising input signal opens the valve, springs closes valve, signal range 4-20 ma Connect the current source for the input signal (input resistance < 285 ohms for standard location) (input resistance < 460 ohms for explosion proof location) Input signal 4 ma Input signal 6 ma Input signal 20 ma valve is completely closed valve starts to open 4 ± 0.4 psi (0.3 ± 0.03 bar) (adjust with ZERO ) valve is completely opened 15 ± 0.4 psi (1.0 ± 0.03 bar) (adjust with SPAN ) Rising input signal closes the valve, springs closes valve, signal range 0-20 ma Connect the current source for the input signal (input resistance < 220 ohms for standard location) (input resistance < 420 ohms for explosion proof location) Input signal 0 ma valve is completely opened 15 ± 0.4 psi (1.0 ± 0.03 bar) (adjust with ZERO ) Input signal 18 ma valve starts to close 4 ± 0.4 psi (0.3 ± 0.03 bar) (adjust with SPAN ) Input signal 20 ma valve is completely closed Rising input signal closes the valve, springs closes valve, signal range 4-20 ma Connect the current source for the input signal (input resistance < 285 ohms for standard location) (input resistance < 460 ohms for explosion proof location) Input signal 4mA valve is completely opened 15 ± 0.4 psi (1.0 ± 0.03 bar) (adjust with ZERO ) Input signal 18 ma valve starts to close 4 ± 0.4 psi (0.3 ± 0.03 bar) (adjust with SPAN ) Input signal 20 ma valve is completely closed After the adjustments have been made, remove the control gauge and re-install the threaded stopper plug (with sealing). Replace the bleeder screw and the zero set-point caps. Air Supply Adjustment The adjustable nozzle screw controls the actuator air consumption and velocity. Turning the nozzle screw clockwise decreases the air supply thus slowing the opening of the valve or increasing valve response time. Caution: By turning the screw clockwise too far, the valve may not completely open. Turning the nozzle screw counterclockwise increases the air supply thus decreasing valve response time. Caution: By turning the screw counterclockwise too far, the valve may not completely close. Changing the E/P Positioner WARNING: Do not open the i/p positioner. If required, send the e/p positioner to Parker for repair. To change the i/p positioner, perform the following steps: 1. Disconnect the cable from the signal source. 2. Disconnect the air supply from port P. 3. Loosen the 3 screws at the ring fastener using a 2.5mm hexagon screwdriver. 4. Loosen the coupling nut from the tube. 5. Remove positioner. Pressure Testing and Valve Functioning It is recommended that newly installed pipeline systems first be flushed thoroughly to wash out all foreign matter. The test pressure of an open valve must not exceed 1.5 times the maximum rated pressure of the angle body valve. The test pressure of a closed valve must not exceed 1.1 times the maximum rated pressure of the angle body valve. Normal Operation and Maintenance The e/p positioner should be continuously connected to 58 psi (4 bar) air supply when being used with water or other fluids (e.g. when cleaning the installation). The angle body pneumatic valves are operated by pneumatic control signals. The valves do not require regular maintenance work. While the valves are design to operate over millions of cycles, it is recommended that valves be rebuild every 2 million cycles to ensure optimum quality performance. During routine system checks, no leakage should be found in the valve. If unacceptable leakage occurs, reference Troubleshooting section for recommended solutions. If a valve is to be removed from a pipeline carrying hazardous media, the parts of the valve in contact with the hazardous media must be properly cleaned and decontaminated before repairs are performed. Note: Depending on service conditions, fluid being used, filtration, and lubrication, it may be required to periodically clean and/or replace worn components. Page 3

4 CAUTION: Do not expose plastic or elastomeric materials to any type of commercial cleaning fluid. Parts should be cleaned with a mild soap and water solution. Replacement Parts: When ordering replacement parts kits, specify valve number and voltage from nameplate. Parts kits are available for each valve. Parts included in each kit are marked with an asterisk (*). See exploded views. REFERENCE CROSS SECTION DRAWINGS! Pilot Valve Installation Instructions Optional if pre-installed. These valves are 3-way, direct operated models. The brass versions are offered for multipurpose functionality for normally closed or normally open requirements. The stainless versions are offered in separate normally closed (N.C.), normally open (N.O.) versions. Valves may be ordered with either NEMA 2, 4, 4X integrated coils for ordinary locations or NEMA 4, 4X, 7, and 9 for hazardous locations: Divisions I and II; Class I, Groups A, B, C, and D; Class II, Groups E, F, and G. Media filtration: For protection of the pilot control valve, install a suitable strainer or filter in the inlet side as close to the valve as possible. Dirt or foreign material in the media may cause excessive leakage, wear, or in exceptional cases, malfunction. Clean periodically depending on service conditions. Lubrication: Lubrication is not required although air line lubrication will substantially increase valve life. Electrical connection: Electrical supply must conform to nameplate rating. Connect coil leads or terminals to the electrical circuit using standard electrical practices in compliance with local authorities and the National Electrical Code. Do not power coil until it has been fitted and the retaining washer and nut have been installed to prevent possible coil damage from overheating. WARNING: Turn off electrical power before connecting pilot control valve to the power source. WARNING: Valves to be installed in Hazardous Locations, must be outfitted with Hazardous Location coils only. Verify nameplate data and coil part number before installing the valve. Diagram of Normally Closed Valve WARNING: The actuator is spring loaded. Dismantle actuator with tools provided in repair kit. If the coil assembly is located in an inconvenient orientation, it may be reoriented to facilitate installation. Loosen coil assembly nut, rotate coil assembly to desired position, then retighten the nut with an input torque of in-lbs. MANUAL BYPASS OPTIONAL FEATURE Note: Pilot valve manual bypass is an option. The manual bypass operator allows manual operation when desired or during an electrical power outage. Page 4 COIL ASSEMBLY ASSEMBLY INSTRUCTIONS FOR ALL COIL TYPES Position coil (as described below) on the sleeve, install valve identification plate on top of coil, slide the wave washer over the sleeve and tighten coil assembly nut with an input torque of in-lbs. DIN Coil and various cable option terminations: Loosen cable screw and remove plastic housing from DIN coil. Do not remove the gasket from the DIN spades on the coil. Separate the plastic block from the housing with a small screwdriver to expose the electrical terminations. Feed the lead wires through the DIN connector housing and attach them to the appropriate screw terminal. Snap the plastic block back into place. Replace the plastic housing onto the

5 DIN spades and tighten the screws. To secure the housing and coil together, apply 20 to 30 in-lbs. Conduit Coil with 1/2 NPT connection: Conduit coils are available with either NEMA 2, 4, 4X integrated coils for ordinary locations or NEMA 4, 4X, 7, and 9 for hazardous locations: Divisions I and II; Class I, Groups A, B, C, and D; Class II, Groups E, F, and G. Use suitable electrical cabling and conduit materials and components meeting applicable NEMA recommendations. Coil/enclosure temperature: The pilot control valves are supplied with coils designed for continuous duty service. Normal free space must be provided for proper ventilation. When the coil is energized continuously for long periods of time, the coil assembly will become hot. The coil is designed to operate permanently under these conditions. Smoking and/or odor of burning coil insulation will indicate any excessive heating. For the maximum valve ambient conditions, as well as the fluid temperatures, check the valve part number on the nameplate and refer to the catalog to determine the maximum temperatures. Page 5

6 STAINLESS STEEL ANGLE BODIED CONTROL VALVE WITH PISTON ACTUATOR AND E/P POSITIONER zero set point screw Bleeder screw cap (range) adjustable nozzle screw coupling nut tube screws (3) Page 6

7 E/P Positioner With Clamp Adapter Page 7

8 PROBLEM Angle Body Valve fails to operate. Angle Body Valve fails to close (normally closed valve). Angle Body Valve fails to close (normally open valve). External leakage at sleeve flange. Internal Seating Seal Leakage TROUBLE SHOOTING PROCEDURE 1. Check that pilot air supply is properly connected. 2. Verify that pilot air supply meets the minimum pressure required to actuate the specific angle valve model number. 3. Check pilot control valve functionality. Make sure that pressure complies with pilot control valve nameplate rating and pressure is supplied to actuator head through the output port of the pilot valve. 4. Check pilot control valve electrical supply with voltmeter. Voltage must agree with nameplate rating. 5. If supply voltage is too low, locate and correct cause of low voltage. Should exceed 85% of rated voltage. 6. Check coil with ohmmeter for shorted or open coil. 1. Check pilot control valve functionality. Make sure pilot valve closes eliminating pressure to the actuator head. 2. Verify that pilot valve is vented from valve actuator. 3. Check pilot control valve functionality. Make sure pilot valve closes eliminating pressure to the actuator head. 4. If the pilot control valve works properly, it will be necessary to disassemble angle body valve. WARNING: following all caution and safety precautions prior to Disassembly. 1. Check Angle Body Valve for functionality. 2. Check that pilot air supply is properly connected. 3. Verify that pilot air supply meets the minimum pressure required to actuate the specific valve model number. 4. Disassemble valve as per the Disassembly Instructions. Clean out extraneous matter. The plunger must be free to move without binding. 5. With coil energized, check power at coil wires. Power should be on. If power is present, correct faulty contacts or wiring. 1. Check that sleeve is torqued to in-lbs. 2. If leakage persists, it will be necessary to disassemble angle body valve. WARNING: following all caution and safety precautions prior to Disassembly. Remove sleeve and check O-ring seal for damage. Replace if defective. 1. Check if the actuator has closed the valve 100 percent. Debris or contamination can prevent full closure. 2. Disassemble valve as per the Repair Kit Disassembly Instructions. WARNING: following all caution and safety precautions prior to Disassembly. It is recommended that all components included in the repair kit be installed to prevent future problems. 3. Examine orifice in body for nicks. Damage may require a new replacement valve. 4. Inspect the seat sealing material for foreign matter or dirt accumulation. Worn sealing material requires replacement. Pilot Valve Troubleshooting Valve coil burn-out Valve is sluggish or inoperative electrical supply and pressure check out. External leakage at manual bypass stem (where available). 1. Continuous high voltage greater than 10% of rated voltage could result in coil failure. Locate and correct cause of high voltage. 2. Disassemble valve as per the Disassembly Instructions. Check for foreign material lodged in valve. Clean out extraneous matter. The plunger must be free to move without binding. 3. Check electrical wiring installation. 4. Valve located in high ambient temperature. Ventilate or isolate area from high temperatures. May require valve relocation to lower temperature area. 1. Disassemble valve as per the Disassembly Instructions. Clean out extraneous matter. The plunger must be free to move without binding. 2. Check all springs, if broken, replace. 1. Disassemble manual stem in valve per the Disassembly Instructions. Inspect components for damage. Replace o-ring if necessary. Page 8

9 DECLARATION Parker s Fluid Control Division certifies its valve appliance products complies with the essential requirements of the applicable European Community Directives. We hereby confirm that the appliance has been manufactured in compliance with the applicable standards and is intended for installation in a machine or application where commissioning is prohibited until evidence has been provided that the machine or application is also in compliance with EC directives. The data supplied in the Parker catalogs and general Installation, Operating & Maintenance Instructions are to be consulted and pertinent accident prevention regulations followed during product installation and use. Any unauthorized work performed on the product by the purchaser or by third parties can impair its function and relieves Parker Hannifin of all warranty claims and liability for any misuse and resulting damage. The angle body valve family complies with European Directive 97/23/EC in accordance with Annex II, category II, Group 2, module A1. A separate Declaration of Conformity or Manufacturer s declaration is available upon request. Please provide valve identification numbers and order serial numbers of products concerned. Page 9

OPERATING and MAINTENANCE MANUAL SERIES 2700A CONTROL VALVE CONTENTS. INTRODUCTION...1 Scope...1 Description...1 Valve Identification...

OPERATING and MAINTENANCE MANUAL SERIES 2700A CONTROL VALVE CONTENTS. INTRODUCTION...1 Scope...1 Description...1 Valve Identification... OPERATING and MAINTENANCE MANUAL SERIES 2700A CONTROL VALVE CONTENTS INTRODUCTION...1 Scope...1 Description...1 Valve Identification...2 1.0 VALVE INSTALLATION...2 2.0 VALVE MAINTENANCE...3 Actuator Disassembly...3

More information

! WARNING. Before using product, read and understand instructions.

! WARNING. Before using product, read and understand instructions. McDonnell & Miller Installation & Maintenance Instructions MM-600G) Series FS8-W General Purpose Liquid Flow Switch OPERATION This control is an independently mounted water flow sensing device that makes

More information

STC 3S012-020-A Series Solenoid Valves

STC 3S012-020-A Series Solenoid Valves STC 3S012-020-A Series Solenoid Valves 3S012-020-A Series Solenoid Valve Specifications Valve Model 3S012-1/8-A 3S012-1/4-A 3S020-1/8-A 3S020-1/4-A Port Size (NPT) 1/8 1/4 1/8 1/4 Valve Type Action 3 Way,

More information

WE-350 Series ¼ Turn Electric Actuator

WE-350 Series ¼ Turn Electric Actuator WE-350 Series ¼ Turn Electric Actuator Operation and Installation Manual Pg 1 (Rev. 020113) Table of Contents 1.0 General 1.1 Pre-Installation Inspection 1.2 Storage 1.3 Features & General Information

More information

PRESSURE REDUCING CONTROL VALVE

PRESSURE REDUCING CONTROL VALVE Schematics Throttles to reduce high upstream pressure to constant lower downstream pressure Low Flow By-Pass controls at low flows 4 PRESSURE REDUCING CONTROL VALVE with LOW FLOW BY-PASS FEATURE Main Line

More information

TABLE OF CONTENTS. SECTION 1 General Information: Pg 2 Description of Operation

TABLE OF CONTENTS. SECTION 1 General Information: Pg 2 Description of Operation GTRDD SERIES HEATLESS DRYER INSTALLATION, OPERATION & MAINTENANCE MANUAL TABLE OF CONTENTS SECTION 1 General Information: Pg 2 Description of Operation SECTION 2 Safety Instructions: Pg 3 Installation

More information

Installation Instructions 6028.801

Installation Instructions 6028.801 DAZZLE Installation Instructions 08.80 Spread Lavatory Faucet with Speed Connect Drain* Congratulations on purchasing your American Standard faucet with Speed Connect drain, a feature found only on American

More information

Float and Thermostatic Traps Series H, C and X

Float and Thermostatic Traps Series H, C and X Hoffman Specialty Installation & Maintenance Instructions HS-(E) and Thermostatic Traps Series H, C and X Series C & NPT Series C NPT Series X NPT Series C NPT Series H Ratings Maximum Max. Operating NPT

More information

Mustang Series PRESSURE REDUCING CONTROL VALVE WITH PRESSURE SUSTAINING FEATURE. M115-2 (Globe) M1115-2 (Angle) Schematic. Standard Components

Mustang Series PRESSURE REDUCING CONTROL VALVE WITH PRESSURE SUSTAINING FEATURE. M115-2 (Globe) M1115-2 (Angle) Schematic. Standard Components Schematic Throttles to reduce high upstream pressure to constant lower downstream pressure Throttles to maintain minimum upstream pressure PRESSURE REDUCING CONTROL VALVE WITH PRESSURE SUSTAINING FEATURE

More information

Installation and Operating Instructions Installation Instructions for SS EPE-316L Series

Installation and Operating Instructions Installation Instructions for SS EPE-316L Series INSTR3010 0406 Installation and Operating Instructions Installation Instructions for SS EPE-316L Series Congratulations on your purchase of this Aqua-Pure high flow, single housing filtration system. This

More information

Installation Instructions 4508 4508S

Installation Instructions 4508 4508S SYMPHONY Spread Lavatory Faucet with Speed Connect Drain Congratulations on purchasing your American Standard faucet with Speed Connect drain, a feature found only on American Standard faucets. Speed Connect

More information

Table of Contents. Overview 1. Pump Disassembly 2. Control Disassembly / Reassembly 7. Pump Reassembly 13. Adjustment Procedures DR Control 19

Table of Contents. Overview 1. Pump Disassembly 2. Control Disassembly / Reassembly 7. Pump Reassembly 13. Adjustment Procedures DR Control 19 Table of Contents Overview 1 Pump Disassembly 2 Control Disassembly / Reassembly 7 Pump Reassembly 13 Adjustment Procedures DR Control 19 Adjustment Procedures DRG Control 20 Adjustment Procedures DFR

More information

PBX Series Quick Fit Connector Bimetallic Steam Traps

PBX Series Quick Fit Connector Bimetallic Steam Traps 6262100/6 IM-P626-01 ST Issue 6 PBX Series Quick Fit Connector Bimetallic Steam Traps Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation 4. Commissioning

More information

Fleck 4650. Service Manual INSTALLATION AND START-UP PROCEDURE TABLE OF CONTENTS JOB SPECIFICATION SHEET

Fleck 4650. Service Manual INSTALLATION AND START-UP PROCEDURE TABLE OF CONTENTS JOB SPECIFICATION SHEET Fleck 4650 Service Manual TABLE OF CONTENTS JOB SPECIFICATION SHEET...1 INSTALLATION AND START-UP PROCEDURE...1 CONTROL VALVE DRIVE ASSEMBLY...2 CONTROL DRIVE ASSEMBLY FOR CLOCK...3 BYPASS VALVE ASSEMBLY...4

More information

Your safety and the safety of others are very important.

Your safety and the safety of others are very important. NATURAL GAS TO PROPANE CONVERSION KIT 090 INSTALLATION INSTRUCTIONS FOR ALTITUDES 0 -,00 FT. ONLY PROPANE CONVERSION KIT SAFETY... INSTALLATION REQUIREMENTS... Tools and Parts... LP Gas Requirements...

More information

AWWA Butterfly Valve Operation and Maintenance Manual Series 511A & 510A 20 and Smaller

AWWA Butterfly Valve Operation and Maintenance Manual Series 511A & 510A 20 and Smaller January 2013 AWWA Butterfly Valve Operation and Maintenance Manual Series 511A & 510A 20 and Smaller Milliken Valve Company 190 Brodhead Avenue, Suite 100 Bethlehem, PA 18017 Phone: (610) 861-8803 Fax:

More information

Fire Hydrant Troubleshooting

Fire Hydrant Troubleshooting Fire Hydrant Troubleshooting Pulsation or chatter during opening and flow of water from hydrant. Loose condition in stem at lower valve plate nut. Tighten lower valve plate nut and secure with SS lock

More information

HG600/HG800. Hydro-Power Unit. Installation and Operation Guide

HG600/HG800. Hydro-Power Unit. Installation and Operation Guide HG600/HG800 Hydro-Power Unit Installation and Operation Guide Copyright 04 HydroSpin, All rights reserved. The data contained in this document is proprietary to HydroSpin. It is disclosed to the receiving

More information

Fisher 1052 Size 20 Diaphragm Rotary Actuator with F and G Mounting Adaptation

Fisher 1052 Size 20 Diaphragm Rotary Actuator with F and G Mounting Adaptation Instruction Manual 1052 Size 20 Actuator (F & G) Fisher 1052 Size 20 Diaphragm Rotary Actuator with F and G Mounting Adaptation Contents Introduction... 1 Scope of manual... 1 Description... 1 Specifications...

More information

TYPE E Main Valve Sizes 3 /8 through 12

TYPE E Main Valve Sizes 3 /8 through 12 SD 3001F PRINTED IN U.S.A. SD 3001F/0707 A B TYPE E MAIN VALVE C D E TYPE E Main Valve Sizes 3 /8 through 12 The Spence Type E Main Valve is of normally closed, single seat design featuring packless construction,

More information

Part I - Installation

Part I - Installation 400 Series Pressure and Differential Pressure Switches Types: H400, H402, H403, H400K, H402K, J400, J402, J403, J400K, J402K UNITED ELECTRIC CONTROLS Installation and Maintenance Instructions Please read

More information

Installation, Maintenance, & Repair Series 4000B/LF4000B

Installation, Maintenance, & Repair Series 4000B/LF4000B Installation, Maintenance, & Repair Series 4000B/LF4000B Reduced Pressure Zone Assemblies Sizes: 1 2" 2" (15 50mm) RP/IS-A-4000B 4000B/LF4000B Size: 3 /4"! WARNING Testing Read this Manual BEFORE using

More information

Fuel Injection Pump, Rotary (005-014)

Fuel Injection Pump, Rotary (005-014) Fuel Injection Pump, Rotary View Related Topic Page 1 of 30 Fuel Injection Pump, Rotary (005-014) Table of Contents Summary General Information Preparatory Steps Remove Front Gear Train Rear Gear Train

More information

3. SEISCO PARTS & SERVICE REMOVAL AND REPAIR GUIDE

3. SEISCO PARTS & SERVICE REMOVAL AND REPAIR GUIDE 4 3. SEISCO PARTS & SERVICE REMOVAL AND REPAIR GUIDE A. Changing the Control Board B. Replacing a Heating Element C. Thermistor Replacement D. High Limit Switch Replacement E. Level Detector Replacement

More information

! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-217(I) Series 150S and 157S (Snap Switch, All Models except 157S-RB-P)

! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-217(I) Series 150S and 157S (Snap Switch, All Models except 157S-RB-P) Series 150S and 157S (Snap Switch, All Models except 157S-RB-P) Low Water Cut-Off/Pump Controllers For Steam Boilers and Other Level Control Applications McDonnell & Miller Installation & Maintenance Instructions

More information

How To Fix A Car With A Carbide Engine

How To Fix A Car With A Carbide Engine Section 12 Adjustment, Repair, and Replacement Page 12-1 Section 12 Adjustment, Repair and Replacement Section Contents Page Overview...12-5 Belts Belt Guard Removal/Installation...12-7 Belt Removal/Installation...12-11

More information

Bulletin 2537-M4/USA Service Bulletin Series CPOM

Bulletin 2537-M4/USA Service Bulletin Series CPOM Service Bulletin Series CPOM Effective: November 11, 1996 WARNING FAILURE OR IMPROPER SELECTION OR IMPROPER USE OF THE PRODUCTS AND/OR SYSTEMS DESCRIBED HEREIN OR RELATED ITEMS CAN CAUSE DEATH, PERSONAL

More information

Section 7 Adjustment, Repair and Replacement

Section 7 Adjustment, Repair and Replacement Section 7 Adjustment, Repair, and Replacement Page 7-1 Section 7 Adjustment, Repair and Replacement Section Contents Page Overview...7-5 Belts Belt Guard Removal/Installation...7-7 Belt Removal/Installation...7-11

More information

36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve

36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE. DESCRIPTION

More information

M A N U A L 13-10-05

M A N U A L 13-10-05 Documentation The following information sheets illustrate the description below: 12-WW01-4G-E Sectional view of the lance with main dimensions 12-W101-6G-E Sectional view of the head of the lance with

More information

OWNER S MANUAL FORCE 10 MARINE COMPANY 23080 HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) 522-0233 FAX: (604) 522-9608

OWNER S MANUAL FORCE 10 MARINE COMPANY 23080 HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) 522-0233 FAX: (604) 522-9608 Electric Water Heater OWNER S MANUAL FORCE 10 MARINE COMPANY 23080 HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) 522-0233 FAX: (604) 522-9608 If your water Heater is Damaged or you have questions

More information

Constantemp Double Wall Low pressure steam-water Heater F-340LDW,F-640LDW, F-940LDW and F-1240LDW

Constantemp Double Wall Low pressure steam-water Heater F-340LDW,F-640LDW, F-940LDW and F-1240LDW Installation, Operating and Maintenance Instructions 90/4.5.5 Rev. 0 Constantemp Double Wall Low pressure steam-water Heater F-340LDW,F-640LDW, F-940LDW and F-1240LDW Table of Contents SECTION I... 2 INSTALLATION...

More information

Product Manual. CVS Type 67AFR Filter Regulator. Introduction. Installation. Description

Product Manual. CVS Type 67AFR Filter Regulator. Introduction. Installation. Description Product Manual CVS Type 67AFR Filter Regulator Introduction This CVS Controls product manual includes instructions for the installation, adjustment, maintenance and parts ordering of the CVS Type 67AFR

More information

INSPECTION, MAINTENANCE AND RECHARGE SERVICE MANUAL P/N 16303

INSPECTION, MAINTENANCE AND RECHARGE SERVICE MANUAL P/N 16303 WATER MIST HAND PORTABLE FIRE EXTINGUISHERS Model B270 ¾ Gallon Model B272 2 ½ Gallon INSPECTION, MAINTENANCE AND RECHARGE SERVICE MANUAL P/N 6303 All fire extinguishers should be installed, inspected

More information

TECHNICAL DATA. Dry 122a. November 12, 2013

TECHNICAL DATA. Dry 122a. November 12, 2013 Dry 122a 1. PRODUCT DESCRIPTION The Viking is a quick-opening device. When installed with the required external Anti-flood Device, the assembly is designed to increase the operating speed of Viking Model

More information

ABV20 Air Actuated Boiler Blowdown Valve Installation and Maintenance Instructions

ABV20 Air Actuated Boiler Blowdown Valve Installation and Maintenance Instructions 4057250/8 IM-P405-16 AB Issue 8 ABV20 Air Actuated Boiler Blowdown Valve Installation and Maintenance Instructions 1 General safety information 2 General product information 3 Installation 4 Operation

More information

DiscPlus DX195 and DX225 Air Disc Brakes

DiscPlus DX195 and DX225 Air Disc Brakes Revised 11-04 Technical Bulletin Revised 1 Technical 11-04 Bulletin DiscPlus DX195 and DX225 Air Disc Brakes Inspection, Installation and Diagnostics Air Disc Brake Inspection Intervals and Procedures

More information

OPERATION AND MAINTENANCE MANUAL 5-1/4 B-84-B-5 FIRE HYDRANT

OPERATION AND MAINTENANCE MANUAL 5-1/4 B-84-B-5 FIRE HYDRANT OPERATION AND MAINTENANCE MANUAL 5-1/4 B-84-B-5 FIRE HYDRANT INDEX AMERICAN - DARLING 5-1/4 IN. B-84-B-5 FIRE HYDRANT OPERATION AND MAINTENANCE MANUAL OPERATION AND MAINTENANCE REPAIRS Operation and Maintenance...

More information

This instruction is valid for all ACD pump models shown on page 2

This instruction is valid for all ACD pump models shown on page 2 Screw pumps ACD Maintenance and Service Instruction This instruction is valid for all ACD pump models shown on page 2 Contents Page List of components 2 Exploded view/ordering code 3 Service intervals

More information

Trouble Shooting. Pump

Trouble Shooting. Pump Trouble Shooting Pump Trouble Possible Cause Remedy Oil leaking in the area of water pump crankshaft Worn crankshaft seal, bad bearing, grooved shaft, or failure of retainer o-ring. Excessive play on crankshaft

More information

Overview PARTS LIST. B. Lever mounting base C. Flush handle assembly D. Grey/Blue float stop E. Grey float (Full Flush) F. Flush valve washer

Overview PARTS LIST. B. Lever mounting base C. Flush handle assembly D. Grey/Blue float stop E. Grey float (Full Flush) F. Flush valve washer Overview READ ENTIRE INSTRUCTIONS BEFORE STARTING INSTALLATION PARTS LIST A. Flush valve B. Lever mounting base C. Flush handle assembly D. Grey/Blue float stop E. Grey float (Full Flush) F. Flush valve

More information

Assisted lift operated 2/2-way solenoid valves Type EV250B

Assisted lift operated 2/2-way solenoid valves Type EV250B MAKING MODERN LIVING POSSIBLE Data sheet Assisted lift operated 2/2-way solenoid valves Type EV250B EV250B with assisted lift can operate from zero and up to 10 bar differential pressure. This 2/2-way

More information

BERMAD Fire Protection

BERMAD Fire Protection 400E-2M/700E-2M IOM Bermad Electrically Controlled Deluge Valve with EasyLock Manual Reset Model: 400E-2M/700E-2M INSTALLATION OPERATION MAINTENANCE Application Engineering BERMAD 400E-2M/700E-2M Bermad

More information

3", 4", 6" & 8" Model H Series Alarm Check Valve Installation and Maintenance Guide

3, 4, 6 & 8 Model H Series Alarm Check Valve Installation and Maintenance Guide ", ", " & " Model H Series Alarm Check Valve Installation and Maintenance Guide 077 AIRPARK DRIVE STANDISH, MICHIGAN PHONE 99-- 00-2-0 FAX 99--92 www.globesprinkler.com OCTOBER 2 C- BULLETIN A.C.V.I.M.,

More information

3 WAY (3/2) POPPET VALVES FOR AIR AND VACUUM SERVICE SOLENOID OR AIR ACTUATED BROCHURE N-223

3 WAY (3/2) POPPET VALVES FOR AIR AND VACUUM SERVICE SOLENOID OR AIR ACTUATED BROCHURE N-223 3 WAY (3/2) POPPET VALVES FOR AIR AND VACUUM SERVICE SOLENOID OR AIR ACTUATED BROCHURE N-223 HERION S HIGH PERFORMANCE POPPET VALVES For those applications requiring high Cv, fast response times, large

More information

SunMaxx Solar Filling Station Operating Instructions

SunMaxx Solar Filling Station Operating Instructions SunMaxx Solar Filling Operating Instructions Content 1. Declaration of conformity... 2 2. Introduction... 2 3. Transportation and unpacking... 4 4. Mounting and commissioning... 5 5. End of operation...

More information

Operator s Manual. Pressure Injection Cell Model PC8500. Congratulations! Contents

Operator s Manual. Pressure Injection Cell Model PC8500. Congratulations! Contents Operator s Manual Pressure Injection Cell Model PC8500 Congratulations! Congratulations on your purchase of a Next Advance Pressure Injection Cell. Please read this operator s manual which explains proper

More information

BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS

BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS PLEASE READ COMPLETE INSTRUCTIONS BEFORE YOU BEGIN LEAVE INSTALLATION INSTRUCTIONS AND USER'S GUIDE WITH OWNER ALL ELECTRIC WIRING AND PLUMBING MUST BE DONE

More information

Stainless Steel Single and Dual Circulation Kits

Stainless Steel Single and Dual Circulation Kits Instruction Sheet P/N 160780 01 Stainless Steel Single and Dual Circulation Kits Introduction The single and dual high-pressure circulation kits allow you to vary and control the circulation rate of coating

More information

INSTALLATION AND OPERATING INSTRUCTIONS For Model GL1 Gate Locks

INSTALLATION AND OPERATING INSTRUCTIONS For Model GL1 Gate Locks Securitron Magnalock Corp. www.securitron.com ASSA ABLOY, the global leader Tel 800.624.5625 techsupport@securitron.com in door opening solutions INSTALLATION AND OPERATING INSTRUCTIONS For Model GL1 Gate

More information

POSEIDON 2-29, 2-25 & 2-22 POSEIDON 2-29, 2-25 & 2-22 XT

POSEIDON 2-29, 2-25 & 2-22 POSEIDON 2-29, 2-25 & 2-22 XT POSEION 2-29, 2-25 & 2-22 POSEION 2-29, 2-25 & 2-22 XT Repair Manual Index A. Safety precautions 3 B. Technical data 4 C. Structure 5-6. Service / Repair 7-23 E. Tools 24 F. Function 25-26 G. Electric

More information

Oil and Coolant Circulating Heating System. Model - OCSM

Oil and Coolant Circulating Heating System. Model - OCSM Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine

More information

I nstallation. M100Q Series Proportional Actuator with R81Q Controller Board for Thermistor Sensor Applications. Tools Needed.

I nstallation. M100Q Series Proportional Actuator with R81Q Controller Board for Thermistor Sensor Applications. Tools Needed. FANs 268.1, 1628.3 Installation Bulletin M100Q Issue Date 1099 M100Q Series Proportional Actuator with R81Q Controller Board for Thermistor Sensor Applications I nstallation Parts Included M110QGA-1 and

More information

Installation and Troubleshooting Instructions for Electric Tankless Residential Water Heaters.

Installation and Troubleshooting Instructions for Electric Tankless Residential Water Heaters. Model Number: Serial Number: Information Manual Installation and Troubleshooting Instructions for Electric Tankless Residential Water Heaters. ATTENTION: IF YOU ARE NOT A LICENSED PLUMBER OR A LICENSED

More information

SECTION G2: CABLE PROCESSOR MODULE MAINTENANCE

SECTION G2: CABLE PROCESSOR MODULE MAINTENANCE SECTION G2: CABLE PROCESSOR MODULE MAINTENANCE Cable Processor Module overview WARNING! When tipping the Cable Processor Module back, (after removing the toggle arm pin), use extreme caution not to drop

More information

STC 2P050 Series Solenoid Valves NSF Compliant Materials, 2 Way, Direct Acting

STC 2P050 Series Solenoid Valves NSF Compliant Materials, 2 Way, Direct Acting STC 2P050 Series Solenoid Valves NSF Compliant Materials, 2 Way, Direct Acting Female NPT Thread 3/8 OD Tube 3/8 Push-In Fitting 2P050 Series Solenoid Valve Specifications Valve Model 2P050-1/4 2P050-3/8

More information

Wiper Motor Marinco 2.5. Installation Instructions

Wiper Motor Marinco 2.5. Installation Instructions Wiper Motor Marinco 2.5 Installation Instructions Wiper Motor Marinco-2.5 The Marinco 2.5 Wiper Motor Offers the Following Features: Fully sealed base and housing which allows installation in outdoor wet

More information

Char-Lynn Hydraulic Motor. Repair Information. 10 000 Series. October, 1997

Char-Lynn Hydraulic Motor. Repair Information. 10 000 Series. October, 1997 Char-Lynn Hydraulic Motor October, 1997 Repair Information Geroler Motor Two Speed 001 27 Retainer inside bore of valve plate bearingless motors only 4 15 16 3 6 35 Parts Drawing 25 2 2 1 19 17 36 40 47

More information

Volkswagen New Beetle 2.0 Liter 4-cyl General, Engine (Engine Code AEG) 17 Engine-Lubrication system (Page GR-17)

Volkswagen New Beetle 2.0 Liter 4-cyl General, Engine (Engine Code AEG) 17 Engine-Lubrication system (Page GR-17) 17 Engine-Lubrication system (Page GR-17) Lubrication system components, removing and installing Oil pan, removing and installing Oil pressure and oil pressure switch, checking Dynamic oil pressure warning

More information

Baumann 24000SB Barstock Control Valve

Baumann 24000SB Barstock Control Valve Instruction Manual 24000SB Valve Baumann 24000SB Barstock Control Valve Contents Introduction... 1 Scope of Manual... 1 Safety Precautions... 2 Maintenance... 3 Installation... 3 Air Piping... 4 Disassembly...

More information

INSTRUCTIONS AND PARTS LIST FOR MODEL 70H & 75H HAND-OPERATED HYDRAULIC PRESS

INSTRUCTIONS AND PARTS LIST FOR MODEL 70H & 75H HAND-OPERATED HYDRAULIC PRESS INSTRUCTIONS AND PARTS LIST FOR MODEL 70H & 75H HAND-OPERATED HYDRAULIC PRESS SETTING UP THE PRESS FOR OPERATION For shipping convenience, the gauge, pump handle, hoist crank, screw nose and base angles

More information

4 Posiflow Proportional Solenoid Valves

4 Posiflow Proportional Solenoid Valves 4 Posiflow Solenoid Brass or Stainless Steel Bodies 1/4" to 1/2" NPT 2/2 Features Flow rates adjustable between 0% and 100% of rating Flow rate can also be regulated by a range of electrical inputs (sensors,

More information

MODEL G300 BRAKE BLEEDER

MODEL G300 BRAKE BLEEDER MODEL G300 BRAKE BLEEDER Installation, Operation & Repair Parts Information Branick Industries, Inc. 4245 Main Avenue P.O. Box 1937 Fargo, North Dakota 58103 REV060616 P/N: 81-0035G 1 THIS PAGE INTENTIONALLY

More information

Watts Pure Water Systems

Watts Pure Water Systems Watts Pure Water Systems WM-120-PT Installation and Operation Manual Premier Water Systems Do not use with water that is microbiologically unsafe or of unknown quality without adequate disinfection before

More information

BASYS INSTALLATION INSTRUCTIONS FOR ELECTRONIC CAPACITANCE SENSING LAVATORY FAUCETS EFX-3XX Pedestal, Sensor Activated Lavatory Faucets

BASYS INSTALLATION INSTRUCTIONS FOR ELECTRONIC CAPACITANCE SENSING LAVATORY FAUCETS EFX-3XX Pedestal, Sensor Activated Lavatory Faucets BASYS INSTALLATION INSTRUCTIONS FOR ELECTRONIC CAPACITANCE SENSING LAVATORY FAUCETS EFX-3XX Pedestal, Sensor Activated Lavatory Faucets Any Application. Any Environment. Code No: 0816407 Rev. 4 (07/12)

More information

Installation, Operating and Maintenance Instructions for AEON Metal Seated Gate Valve (MSGV) Water

Installation, Operating and Maintenance Instructions for AEON Metal Seated Gate Valve (MSGV) Water 1 Foreword 1.1 Thank you for choosing one of the range of AEON's BS standard valves. For safety purposes, the user shall read this instruction to fully understand the operation of the product. 2 AEON Design

More information

XL PREMIUM OIL COOLER KIT

XL PREMIUM OIL COOLER KIT -J05 REV. 0-0-0 XL PREMIUM OIL COOLER KIT GENERAL Kit Number 0008 Models For model fitment information, see the P&A Retail Catalog or the Parts and Accessories section of www.harley-davidson.com (English

More information

AMX300 DirectConnect Mixing Valve Kits

AMX300 DirectConnect Mixing Valve Kits AMX300 DirectConnect Mixing Valve Kits INSTALLATION INSTRUCTIONS Tools needed (not supplied) 1. Wrench 2. Pliers Safety Definitions These safety terms identify information you must read. CAUTION Indicates

More information

Easy Tool Retracting System CMC-SR2159ER36

Easy Tool Retracting System CMC-SR2159ER36 Easy Tool Retracting System CMC-SR2159ER36 Pepperl+Fuchs, Inc. 1600 Enterprise Parkway Twinsburg, Ohio 44087 Phone: +1 330 486 0002 e-mail: pa-info@us.pepperl-fuchs.com Mounting the Easy Tool Refer to

More information

PTU Series Ultrahigh-Purity Pressure Transducers

PTU Series Ultrahigh-Purity Pressure Transducers PTU Series UltrahighPurity Pressure Transducers User s Manual The Swagelok PTU series pressure transducer provides electronic monitoring of system pressure for ultrahighpurity applications. The PTU series

More information

System 8. ü www.nassmagnet.com ( +49 511 6746-0. System 8

System 8. ü www.nassmagnet.com ( +49 511 6746-0. System 8 System 8 ü www.nassmagnet.com ( +9 11 7-0 System 8 The name System 8 stands for a modular system of solenoid coils, armature systems, solenoid operators and solenoid valves. The diameter of the armatures

More information

Series 510 Submersible Level Transmitters

Series 510 Submersible Level Transmitters Series 510 Submersible Level Transmitters The Series 510 Submersible Level Transmitters are solid state instruments designed for direct submergence into many types of liquid for quick, accurate and reliable

More information

STABITHERM INSTALLATION & SERVICE BOOKLET

STABITHERM INSTALLATION & SERVICE BOOKLET STABITHERM INSTALLATION & SERVICE BOOKLET TABLE OF CONTENTS Introduction...3 Warranty...3 Product Range and Physical Description...4 Method of Operation...5 Recommended Pressures and Temperatures...6 Flow

More information

GATE VALVES ASAHI AV VALVES. Type P (Standard: Plug) Type S (Soft Seal) Contents. (1) Be sure to read the following warranty clauses of our product 1

GATE VALVES ASAHI AV VALVES. Type P (Standard: Plug) Type S (Soft Seal) Contents. (1) Be sure to read the following warranty clauses of our product 1 Serial No. H-V011-E-11 GATE VALVES Type P (Standard: Plug) Type S (Soft Seal) Contents (1) Be sure to read the following warranty clauses of our product 1 User s Manual (2) General operating instructions

More information

12-Volt Negative Ground Installation Instructions

12-Volt Negative Ground Installation Instructions 12-Volt Negative Ground Installation Instructions For Part Number: 1141, 1164, 1165, 1181 CAUTION!!! Before installing, please read the following important information... 1. The Ignitor is designed for

More information

Machine needle shut-off nozzle type HP

Machine needle shut-off nozzle type HP Machine needle shut-off nozzle type HP pneumatically or hydraulically controlled Index of contents Chapter Page Safety instructions... 2 Installation instructions... 3 - Installation steps... 3 Initial

More information

Type 3244-1 and Type 3244-7 Pneumatic Control Valves. Type 3244 1 (left) and Type 3244-7 (right) Mounting and Operating Instructions EB 8026 EN

Type 3244-1 and Type 3244-7 Pneumatic Control Valves. Type 3244 1 (left) and Type 3244-7 (right) Mounting and Operating Instructions EB 8026 EN Type 3244-1 and Type 3244-7 Pneumatic Control Valves Type 3244 1 (left) and Type 3244-7 (right) Mounting and Operating Instructions E 8026 EN Edition July 2014 Definition of signal words DNGER! Hazardous

More information

PALLET JACK - 2.5 TON

PALLET JACK - 2.5 TON PALLET JACK - 2.5 TON 39939 SET UP AND OPERATING INSTRUCTIONS Visit our website at: http://www.harborfreight.com Read this material before using this product. Failure to do so can result in serious injury.

More information

Series 30000 Hose Reels

Series 30000 Hose Reels Operating Instructions and Parts List for Series 30000 Hose Reels - MANUAL DRIVEN - - POWER DRIVEN - SAFETY PRECAUTIONS Personal injury and/or equipment damage may result if proper safety precautions are

More information

Rexroth Hydraulic Pump A10VO Series User Manual

Rexroth Hydraulic Pump A10VO Series User Manual Rexroth Hydraulic Pump A10VO Series User Manual Rexroth Hydraulic pump A10VO Series User Manual Revised 5/1/2009 Page 1 of 12 Functional Purpose This pump is preferred over a fixed displacement (gear)

More information

Equipped with AEM Dryflow Filter No Oil Required! INSTALLATION INSTRUCTIONS PART NUMBER 21-754DS. 2012-2015 BMW 335i 3.0L

Equipped with AEM Dryflow Filter No Oil Required! INSTALLATION INSTRUCTIONS PART NUMBER 21-754DS. 2012-2015 BMW 335i 3.0L Equipped with AEM Dryflow Filter No Oil Required! INSTALLATION INSTRUCTIONS PART NUMBER 21-754DS 2012-2015 BMW 335i 3.0L 1 ITEM NO. PART NUMBER DESCRIPTION QTY. 1 21-2057DK AIR FILTER 1 2 9-0442 TUBE;

More information

Universal Installation and Maintenance Instructions Double Wall Spill Containment Bucket (5 and 15 gal)

Universal Installation and Maintenance Instructions Double Wall Spill Containment Bucket (5 and 15 gal) Universal Installation and Maintenance Instructions Double Wall Spill Containment Bucket (5 and 15 gal) IMPORTANT: It is imperative that the user read these warnings and use of the assembly instructions

More information

POSITIVE DISPLACEMENT FLOWMETER - IM012P (PULSE)

POSITIVE DISPLACEMENT FLOWMETER - IM012P (PULSE) IM213P-MC 0312 0003 POSITIVE DISPLACEMENT FLOWMETER - IM012P (PULSE) INSTRUCTION MANUAL To the Owner PLEASE READ THIS INFORMATION CAREFULLY BEFORE USE. Read and retain this instruction manual to assist

More information

BETTIS CONVERSION INSTRUCTIONS TO CONVERT HD SERIES ACTUATORS TO HD-M3, HD-SR-M3 HD-M3HW OR HD-SR-M3HW SERIES PNEUMATIC ACTUATORS

BETTIS CONVERSION INSTRUCTIONS TO CONVERT HD SERIES ACTUATORS TO HD-M3, HD-SR-M3 HD-M3HW OR HD-SR-M3HW SERIES PNEUMATIC ACTUATORS BETTIS CONVERSION INSTRUCTIONS TO CONVERT HD SERIES ACTUATORS TO HD-M3, HD-SR-M3 HD-M3HW OR HD-SR-M3HW SERIES PNEUMATIC ACTUATORS PART NUMBER: 132581 REVISION: A RELEASE DATE: 24 March 2000 Page 1 of 10

More information

Colima Visco and Colima Viscorol Magnetic Level Indicators

Colima Visco and Colima Viscorol Magnetic Level Indicators 3.796.5275.200 IM-P329-02 CH Issue 1 Colima Visco and Colima Viscorol Magnetic Level Indicators Installation and Maintenance Instructions Colima Visco Colima Viscorol 1. Safety information 2. General product

More information

VSO MAX HP High Flow Proportional Valve

VSO MAX HP High Flow Proportional Valve VSO MAX HP High Flow Proportional Valve Typical Applications Ventilators Insufflators Anesthesia Delivery & Monitors Pressure & Flow Control Mass Flow Control Product Specifications Physical Properties

More information

Chapter 7 Hydraulic System Troubleshooting

Chapter 7 Hydraulic System Troubleshooting Chapter 7 Hydraulic System Troubleshooting General The following troubleshooting information is provided as a general guide to identify, locate and correct problems that may be experienced with the hydraulic

More information

Powers Controls TH 192 HC Heating/Cooling Room Thermostat

Powers Controls TH 192 HC Heating/Cooling Room Thermostat Powers Controls TH 192 HC Heating/Cooling Room Thermostat Technical Instructions Document No. 155-066P25 TH 192-2 50 60 70 80 70 TH0356R1 60 80 POWERS Description The TH 192 HC thermostats are proportional

More information

System Saver 318 Air Compressor for Mack E-Tech and ASET Engines

System Saver 318 Air Compressor for Mack E-Tech and ASET Engines Maintenance Manual 31 System Saver 318 Air Compressor for Mack E-Tech and ASET Engines Revised 08-05 NON-THROUGH DRIVE THROUGH DRIVE Service Notes About This Manual This manual provides service and repair

More information

A.Y. McDonald Mfg. Co. Troubleshooting Submersible and Jet Pumps

A.Y. McDonald Mfg. Co. Troubleshooting Submersible and Jet Pumps A.Y. McDonald Mfg. Co. Troubleshooting Submersible and Jet Pumps Troubleshooting Submersible Pumps Fuse overload or circuit breaker trips when motor is started 1. Incorrect line voltage. Check the line

More information

Model/Sprinkler Identification Numbers

Model/Sprinkler Identification Numbers Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 Series TY-L 5.6 and 8.0 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Standard Response, Standard Coverage General Description

More information

Maintenance and Service Instruction

Maintenance and Service Instruction Screw pumps E4 Maintenance and Service Instruction E4 1 IMO AB This instruction is valid for all E4 pump models shown on page 2 Contents Page List of components 2 Exploded view/ordering code 3 Service

More information

HYDRAULIC LIFT TABLE CART 2200-LB.

HYDRAULIC LIFT TABLE CART 2200-LB. HYDRAULIC LIFT TABLE CART 2200-LB. OWNER S MANUAL WARNING: Read carefully and understand all MACHINE ADJUSTMENT AND OPERATION INSTRUCTIONS before operating. Failure to follow the safety rules and other

More information

Replacement parts. WM97+ gas-fired water boiler Boiler Manual. OBTAIN PARTS ONLY THROUGH WEIL-McLAIN THE BOILER CONTAINS CERAMIC FIBER MATERIALS

Replacement parts. WM97+ gas-fired water boiler Boiler Manual. OBTAIN PARTS ONLY THROUGH WEIL-McLAIN THE BOILER CONTAINS CERAMIC FIBER MATERIALS Replacement parts DO NOT SERVICE THE BOILER WITHOUT A WM97+ MAINTENANCE KIT AVAILABLE Failure to adhere to these guidelines can result in severe personal injury, death or substantial property damage. The

More information

with MERCURY FREE 1 HP Relays ! WARNING Before using this product read and understand instructions.

with MERCURY FREE 1 HP Relays ! WARNING Before using this product read and understand instructions. B Installation & Maintenance Instructions MM-414 Series 150E and 157E Low Water Cut-Off/Pump Controllers For Steam Boilers and Other Level Control Applications A Typical Applications: Primary or secondary

More information

Single Phase Soft Starter

Single Phase Soft Starter Single Phase Soft Starter Installation & Operating Manual 6/02 Table of Contents Section 1 General Information................................................... 1 1 General Description................................................

More information

INSTALLATION & OPERATING INSTRUCTIONS

INSTALLATION & OPERATING INSTRUCTIONS INSTALLATION & OPERATING INSTRUCTIONS WARNING RISK OF ELECTRIC SHOCK. CONNECT ONLY TO A CIRCUIT PROTECTED BY A GROUND-FAULT CIRCUIT-INTERRUPTER. THE UNIT SHOULD BE INSTALLED BY A QUALIFIED SERVICE REPRESENTATIVE.

More information

Tri-Homo Style Operation and Maintenance Instructions

Tri-Homo Style Operation and Maintenance Instructions Tri-Homo Style Operation and Maintenance Instructions One Research Drive Stratford, CT 06615 (203) 375-0063 www.sonicmixing.com 1 Installation and Start-up Do not perform following adjustments without

More information

MP8000 Series Pneumatic Valve Actuators

MP8000 Series Pneumatic Valve Actuators 14-1161- 9, Rev. A Technical Bulletin MP8000 Issue Date March 2016 MP8000 Series Pneumatic Valve Actuators Pre-Assembly Details Page 3 MP8000 Actuator Components 3 Tools Required to Assemble an MP8000

More information

Wafer Check Valve ASAHI AV VALVES. Contents. User s Manual. (1) Be sure to read the following description of our product warranty 1

Wafer Check Valve ASAHI AV VALVES. Contents. User s Manual. (1) Be sure to read the following description of our product warranty 1 Serial No. H-V066-E-2 Wafer Check Valve User s Manual Contents (1) Be sure to read the following description of our product warranty 1 (2) General operating instructions 2 (3) General instructions for

More information