AccuSort MiniX Driver for DeltaV Programmable Serial Interface Card Series 2
|
|
|
- Eugene Doyle
- 9 years ago
- Views:
Transcription
1 AccuSort MiniX Driver for DeltaV Programmable Serial Interface Card Series 2 USER MANUAL Rev. P1.12 November 3, 2005 DeltaV is a trademark of Emerson Process Management Emerson Process Management 1998, All rights reserved. Printed in the U.S.A. While this information is presented in good faith and believed to be accurate, MYNAH Technologies does not guarantee satisfactory results from reliance upon such information. Nothing contained herein is to be construed as a warranty or guarantee, express or implied, regarding the performance, merchantability, fitness or any other matter with respect to the products, nor as a recommendation to use any product or process in conflict with any patent. MYNAH Technologies reserves the right, without notice, to alter or improve the designs or specifications of the products described herein.
2 1 INTRODUCTION 1.1 Scope This document is the User Manual for an AccuSort MiniX serial communication driver firmware for the Emerson DeltaV Control System; it provides information required to install, configure, and maintain the driver firmware on the DeltaV Series 2 Programmable Serial Interface Card (PSIC). The reader should be familiar with Emerson s DeltaV controller system and the scanner equipment. The section Document Format briefly describes the contents of each section of this manual. System Specifications outlines hardware and software requirements for the Driver (P1.12) firmware. Related Documents lists other documents used to prepare this manual. 1.2 Document Format This document is organized as follows: Introduction Theory of Operation Downloading Firmware PSIC Configuration Driver Communications Operational Check Electrical Interface Technical Support Describes the scope and purpose of this document. Provides a general functional overview of the Driver. Describes downloading procedures for the driver firmware on to the DeltaV PSIC. Describes procedures and guidelines for configuring the DeltaV PSIC. Describes how DeltaV PSIC dataset registers are used for bar code data. Provides tips and assistance to ensure PSIC is properly setup and configured. Describes the electrical interface between DeltaV and the bar code devices. Also describes the pin assignments for RS-232 communications. Describes who to call if you need assistance.
3 1.3 System Specifications The following table lists the minimum hardware requirements for the Driver: Table 1: System Specifications Firmware Protocol Compatibility Software Requirements Driver Firmware (P1.12) Scanner data as ASCII text. DeltaV System Software (Release 4.2 or later) installed on a hardware-appropriate Windows NT workstation configured as a ProPlus for DeltaV Serial Interface Port License (VE4102) Minimum Hardware Requirements FRSI DeltaV PSIC Hardware PN: 12P2506X022 FRSI DeltaV M3, M5, MD or Series 2 MD Controller, Power Supply and 2 wide controller carrier FRSI 8 wide I/O card carrier Scanner or other ASCII devices
4 2 THEORY OF OPERATION As part of the serial interface port license, a standard Modbus protocol is installed on the DeltaV PSIC prior to customization. The PSIC needs to be flash upgraded from the Modbus protocol to the ASCII Reader firmware before operation. The RS-232 communication settings must be configured properly to ensure accurate communication between the PSIC and external devices. RS-422/485 may be used directly, or through a RS-422/485 to RS-232 converter. This driver functions as a slave only. In slave mode, the PSIC waits for data to be received on its ports. The received data are reported to DeltaV via dataset registers. A fixed architecture with a maximum of one (1) device under each PSIC port will be allowed. Each device will support a single dataset, where the received bar code information will be reported. 3 Downloading the firmware The driver software is distributed on a CD. These files must be copied to the DeltaV directory (you must create the directory first) on your ProPlus Workstation. The path is: \DeltaV\ctl\ProgSerial\AccuSort MiniX The following shows a completed copy operation:
5 After copy completion, you are ready to program (or upgrade) the Programmable Serial Card with the supplied custom driver software. The steps are as follows:
6 1. Click on the Start button and select DeltaV, Installation, Controller Upgrade Utility as shown below. The following dialog will appear: Click on the Upgrade I/O Modules radio button as shown, and then click Next.
7 The above dialog will appear, listing all the available Controllers in your network. From this dialog, select the appropriate Controller and then Click Next After you Click Next, the following dialog will appear, listing all the I/O modules in your selected Controller. The shown list of I/O modules is an example only. Your list will be different. From this dialog, select the Programmable Serial Card I/O Module in the list. For example, we will select I/O Module 1. This will give you the following dialog, from
8 which you will select the file path to where the driver software is located. This will be: \DeltaV\ctl\ProgSerial\AccuSort MiniX Once you are in the specified directory, you will need to select the following file: MiniX.S2F After selecting the.s2ffile, Click on Open. This dialog will close and you will be back to the following:
9 In this dialog, Click Next again. You will get the following dialog, confirming the Controller and I/O Module to program. Click Next and the I/O Module upgrade process will begin. After completion, you will receive the following dialog, indicating success.
10 This completes the I/O Module upgrade process.
11 4 CONFIGURATION INFORMATION Powerful Solutions for Digital Plants This section describes the steps necessary to configure the DeltaV PSIC and the external device to obtain proper communication. 4.1 Device And Dataset Configuration The following paragraphs discuss some attributes in the device and dataset configuration: Device Address: You can configure a maximum of one (1) devices under each PSIC port. The driver does not use the device addresses, consequently these can be left at their default value Output Mode: All datasets will be of type Input DeltaV Data Type: The DeltaV Data Type can be configured as String, 8-Bit Int, 8-Bit Uint, 16- Bit Int, or 16-Bit Uint. Any other data types are not supported. UPC codes read can be 9 or more characters long, with the default length of 9 characters. Users can change the expected UPC code length by specifying it in Special Data1. For example, to receive a 12 character UPC, configure a 12 in Special Data1. By default, the data is expected to be numeric represented as ASCII bytes. The driver converts the ASCII bytes to numeric and then stores the data in the dataset registers. For example, for barcode data= , the received data stream will be 0x30, 0x30, 0x30, 0x30, 0x30, 0x31, 0x30, 0x38, 0x38. Non-numeric ASCII data bytes are also accepted. User can bypass the ASCII to numeric conversion of data bytes by setting Special Data2 to 1. For example, for barcode data=01234abcd, the received data stream will be 0x30, 0x31, 0x32, 0x33, 0x34, 0x41, 0x42, 0x43, 0x44. With Special Data2 equal to 1, the data bytes are stored as received. When using String type, the barcode data is stored in register 1 as a character string without any conversion. For example, for barcode = , the resulting data in DS1 will be R1 = When using 8-Bit, or 16-Bit datasets, each character of the barcode is stored in individual registers. For example, for barcode= , the resulting data in DS1 will be as follows: R1 = 0, R2 = 0, R3 = 0, R4 = 0, R5 = 0, R6 = 1, R7 = 0 R8 = 8, R9 = 8
12 4.1.4 DeviceDataType The driver does not use this value. Leave this value at its default setting of Starting Address and Number of Values The starting address of the dataset should be configured as 0, and the number of values is the total length of the expected UPC code Special Data Special Data1 and Special Data 2 registers are used as follows: Special Data1 is the length of the expected UPC code. This value can be in the range > 9 and <= 100. Special Data2 is a flag. When set to 1, the driver will bypass conversion of received ASCII data to numeric.
13 5 Operational Check 5.1 Scope The following sections provide some assistance to ensure the interface is working properly. 5.2 Verify Hardware and Software Version Number The user can verify that the driver has been installed using the DeltaV Diagnostics tool. The Diagnostics tool will show the Hardware Revision No. (HwRev) and the Software Revision No. (SwRev). To begin the DeltaV Diagnostic tool select Start-> DeltaV-> Operator-> Diagnostics. In the Diagnostics tool expand the Controller, I/O and then double click on the Programmable Serial Interface Card that has the driver installed. The following information will be displayed: : : : HwRev Hardware Revision 1.1 (or later) SwRev Software Revision P1.0 (or later) 5.3 Verify Configuration Verify port configuration: The serial port must be enabled. User needs to make sure communication settings such as baud rate, parity, and number of data bits match the external device settings. Verify dataset configuration: The datasets configured must be as shown above. 5.4 Verify I/O Communication With Control Studio User can create I/O modules in the control studio to verify correct values are read from the external device and the PSIC. For input data, the values should be changed in the external device and verified that the new data are correctly reported. 5.5 Using Diagnostics Verify PSIC communication: Select the PSIC on Diagnostics and press the right mouse button. Select Display Real -Time Statistics from the drop down menu. If the Programmable Serial Interface Card is functioning then the user will see the Valid Responses counter and the Async and/or Sync Transactions counters incrementing. There will not be any error counting up.
14 Verify port statistics: Select the Port on the Programmable Serial Interface Card and press the right mouse button. Then select Display Port Statistics form the drop down menu. Verify that the port communications statistics are being displayed properly and are counting as expected for the protocol s functionality. Verify dataset values: Select a dataset and press the right mouse button. Select View Dataset Registers from the Drop down window. Verify that the dataset values are displayed as expected. 5.6 LED Indication The Yellow LED for the port should be on solid when all communications on that port are valid. The Yellow LED should be blinking if there is some valid communications and some communications with errors on that port. The Yellow LED should be OFF if there are no valid communications on that port.
15 6 Electrical Interface The electrical interface between DeltaV and external devices conforms to the RS-232, or RS-422/RS-485 protocol. The RS-232 cable connecting DeltaV PSIC and external devices should not exceed 50 feet as specified by the EIA standard for RS-232 protocol. Section 6.1 shows the pin assignments for the PSIC serial terminal block for RS-232 protocol. If using RS-422/RS-485, the distance is 4000 feet. 6.1 RS-232 Pin Assignments for DeltaV PSIC Terminal Number Signal Description 1 Port 1 - Isolated Ground (GND) 2 Unused 3 Port 1 - Transmit Data (TXD) 4 Unused 5 Port 1 - Receive Data (RXD) 6 Unused 7 Port 1 - Data Terminal Ready (DTR) 8 Port 1 - Dataset Ready (DSR) 9 Port 2 - Isolated Ground (GND) 10 Unused 11 Port 2 - Transmit Data (TXD) 12 Unused 13 Port 2 - Receive Data (RXD) 14 Unused 15 Port 2 - Data Terminal Ready (DTR) 16 Port 2 - Dataset Ready (DSR) 6.2 Wiring Connections for RS-232 Communications Five terminals need to be connected between the PSIC and the external device port. Pins 3 (TXD) and 5 (RXD) need to be crossed so that the external device TXD is connected to PSIC RXD, and the external device RXD is connected to PSIC TXD. Pins 7 (DTR) and 8 (DSR) also need to be crossed in the same manner between the PSIC and the external device. Alternatively, you can jumper DTR and DSR on the PSIC terminal block. In all cases, the GND signal goes through, i.e., connect terminal block screw 1 to GND on the external device. If the external device port is 9-pin D-shell, then GND is pin 5. If the port is 25-pin D-Shell, then the GND is pin 7.
16 7 Technical Support For technical support or to report a defect, please give MYNAH Technologies a call at (636) If a defect is discovered, please document it in as much detail as possible and then fax your report to us at (636) You can also send us your questions via . Our address is: [email protected] Thank you for using DeltaV.
SEC 4100 SYSTEM MONITOR Programmable Serial Interface Card Series 2
SEC 4100 SYSTEM MONITOR Programmable Serial Interface Card Series 2 USER MANUAL Rev. P1.11 September 13, 2006 DeltaV is a trademark of Emerson Process Management, Inc Emerson Process Management, Inc. 1998,
Omron I/O Driver (Series 2) Programmable Serial Interface Card
Omron I/O Driver (Series 2) Programmable Serial Interface Card USER MANUAL Rev. P1.55 June 8, 2012 DeltaV is a trademark of Emerson Process Management, Inc Emerson Process Management, Inc. 1998, 1999.
PCMCIA 1 Port RS232 2.1 EDITION OCTOBER 1999
232 232232 PCMCIA 1 Port RS232 2.1 EDITION OCTOBER 1999 Guarantee. FULL 36 MONTHS GUARANTEE. We guarantee your interface card for a full 36 months from purchase, parts and labour, provided it has been
1.1 Connection. 1.1.1 Direct COM port connection. 1. Half duplex RS232 spy cable without handshaking
POS function Marchen POS-DVR surveillance system is a professional surveillance integrated with POS system. By bringing video and POS transaction data together, the POS-DVR surveillance system provides
RS-232 COMMUNICATIONS
Technical Note D64 0815 RS-232 COMMUNICATIONS RS-232 is an Electronics Industries Association (EIA) standard designed to aid in connecting equipment together for serial communications. The standard specifies
Additional Setup Instructions for Modbus: RTU, ASCII, TCP, Omni & Enron
Additional Setup Instructions for Modbus: RTU, ASCII, TCP, Omni & Enron Copyright 2000 2010 Frontline Test Equipment, Inc. All rights reserved. You may not reproduce, transmit, or store on magnetic media
Using IDENT M System T with Modbus/TCP
Using IDENT M System T with Modbus/TCP Introduction The Pepperl+Fuchs IDENT M System T consists of two models MTT3000-F180-B12- V45-MON, which is a read only unit and the MTT6000-F120-B12-V45 which is
Modbus Communications for PanelView Terminals
User Guide Modbus Communications for PanelView Terminals Introduction This document describes how to connect and configure communications for the Modbus versions of the PanelView terminals. This document
TCP/IP MODULE CA-ETHR-A INSTALLATION MANUAL
TCP/IP MODULE CA-ETHR-A INSTALLATION MANUAL w w w. c d v g r o u p. c o m CA-ETHR-A: TCP/IP Module Installation Manual Page Table of Contents Introduction...5 Hardware Components... 6 Technical Specifications...
How to setup a serial Bluetooth adapter Master Guide
How to setup a serial Bluetooth adapter Master Guide Nordfield.com Our serial Bluetooth adapters part UCBT232B and UCBT232EXA can be setup and paired using a Bluetooth management software called BlueSoleil
Vicon Flash Upgrade Software
NOTES NO. REV. SEC. INSTRUCTION MANUAL Refer to XX134-11-00 1108 3 XX134 Vicon Flash Upgrade Software It is possible to upgrade software for the SurveyorVFT through a PC using the Flash Upgrade software.
ALL-USB-RS422/485. User Manual. USB to Serial Converter RS422/485. ALLNET GmbH Computersysteme 2015 - Alle Rechte vorbehalten
ALL-USB-RS422/485 USB to Serial Converter RS422/485 User Manual ALL-USB-RS422/485 USB to RS-422/485 Plugin Adapter This mini ALL-USB-RS422/485 is a surge and static protected USB to RS-422/485 Plugin Adapter.
COM Port Stress Test
COM Port Stress Test COM Port Stress Test All rights reserved. No parts of this work may be reproduced in any form or by any means - graphic, electronic, or mechanical, including photocopying, recording,
Vicon Flash Upgrade Software
INSTRUCTION MANUAL Notes Refer to XX134 NO. XX134-13-01 REV. 1212 Vicon Flash Upgrade Software It is possible to upgrade software for the SurveyorVFT and Surveyor -Mini Camera Domes through a PC using
User s Manual TCP/IP TO RS-232/422/485 CONVERTER. 1.1 Introduction. 1.2 Main features. Dynamic DNS
MODEL ATC-2000 TCP/IP TO RS-232/422/485 CONVERTER User s Manual 1.1 Introduction The ATC-2000 is a RS232/RS485 to TCP/IP converter integrated with a robust system and network management features designed
How-To Set Custom Scale Format for FedEx Ship Manager
How-To Set Custom Scale Format for FedEx Ship Manager This document describes how to custom configure FedEx Ship Manager to communicate with an Avery Weigh-Tronix scale. Ship Manager should be version
Master-Touch and ValuMass. Modbus Communications. INSTRUCTION MANUAL 80202201 (Rev. 2.1)
Master-Touch and ValuMass Modbus Communications INSTRUCTION MANUAL 80202201 (Rev. 2.1) Eldridge Products, Inc. 2700 Garden Road, Building A Monterey, CA 93940 Tel: 800/321-3569 or 831/648-7777 Fax: 831/648-7780
MS830 / MS833 Barcode Reader v1.0 9-December-2014
MS830 / MS833 Barcode Reader v1.0 9-December-2014 Publication Information 2014 Imagine Communications Corp. Proprietary and Confidential. Imagine Communications considers this document and its contents
IP SERIAL DEVICE SERVER
IP SERIAL DEVICE SERVER ( 1 / 2 / 4 serial port ) Installation guide And User manual Version 1.0 1Introduction... 5 1.1Direct IP mode...5 1.2Virtual COM mode...5 1.3Paired mode...6 1.4Heart beat... 6
For support on the Beijer HMI please contact: [email protected].
Date: 8 August 2008 www.quicksilvercontrols.com Beijer HMI Associated Files: - Example.VF6 (Written with H-Designer) - Profile Velocity Continuous -Beijer.qcp Overview The Human Machine Interface (HMI)
User Manual. AS-Interface Programmer
AS-Interface Programmer Notice: RESTRICTIONS THE ZMD AS-INTERFACE PROGRAMMER HARDWARE AND ZMD AS-INTERFACE PROGRAMMER SOFTWARE IS DESIGNED FOR IC EVALUATION, LABORATORY SETUP AND MODULE DEVELOPMENT ONLY.
To perform Ethernet setup and communication verification, first perform RS232 setup and communication verification:
PURPOSE Verify that communication is established for the following products programming option (488.2 compliant, SCPI only): DCS - M9C & DCS M130, DLM M9E & DLM-M9G & DLM M130, DHP - M9D, P series, SG,
M-series Virtual I/O Module 2
DeltaV Distributed Control System Product Data Sheet M-series Virtual I/O Module 2 Non-intrusive DeltaV I/O simulation Powerful integration solution Easy to use Modular, flexible packaging The M-series
BIT COMMANDER. Serial RS232 / RS485 to Ethernet Converter
BIT COMMANDER Serial RS232 / RS485 to Ethernet Converter (Part US2000A) Copyrights U.S. Converters 1 Contents Overview and Features... 3 Functions..5 TCP Server Mode... 5 Httpd Client Mode.5 TCP Auto mode....6
Laser Barcode Scanner
Laser Barcode Scanner User s Manual FCC Compliance This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are
RS232C < - > RS485 CONVERTER S MANUAL. Model: LD15U. Phone: 91-79-4002 4896 / 97 / 98 (M) 0-98253-50221 www.interfaceproducts.info
RS232C < - > RS485 CONVERTER S MANUAL Model: LD15U INTRODUCTION Milestone s model LD-15U is a RS232 to RS 485 converter is designed for highspeed data transmission between computer system and or peripherals
Software User Guide UG-461
Software User Guide UG-461 One Technology Way P.O. Box 9106 Norwood, MA 02062-9106, U.S.A. Tel: 781.329.4700 Fax: 781.461.3113 www.analog.com ezlinx icoupler Isolated Interface Development Environment
Modbus TCP Master/Slave Driver for DeltaV Virtual I/O Module
Modbus TCP Master/Slave Driver for DeltaV Virtual I/O Module ModbusTCP Firmware v3.9.3 or later For Simplex and Redundant Applications USER MANUAL February 2011 Disclaimers MYNAH Technologies 20069. All
1-Port R422/485 Serial PCIe Card
1-Port R422/485 Serial PCIe Card Installation Guide 1. Introduction Thank you for purchasing this 1-Port RS422/485 Serial PCI Express (PCIe) Card. It is a universal add in card that connects to a PC or
Programming and Using the Courier V.Everything Modem for Remote Operation of DDF6000
Programming and Using the Courier V.Everything Modem for Remote Operation of DDF6000 1.0 Introduction A Technical Application Note from Doppler System July 5, 1999 Version 3.x of the DDF6000, running version
Laser Barcode Scanner User s Manual
Laser Barcode Scanner User s Manual FCC Compliance This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are
FREQUENTLY ASKED QUESTIONS (FAQs) 123Scan 2 Scanner Configuration Utility 19 April 2011
FREQUENTLY ASKED QUESTIONS (FAQs) 123Scan 2 Scanner Configuration Utility 19 April 2011 Table of Content Question No. Product Overview What model scanners are supported by 123Scan 2 1 What are the key
Using HyperTerminal with Agilent General Purpose Instruments
Using HyperTerminal with Agilent General Purpose Instruments Windows HyperTerminal can be used to program most General Purpose Instruments (not the 531xx series counters) using the RS-232 Serial Bus. Instrument
CP2110-EK CP2110 EVALUATION KIT USER S GUIDE. 1. Kit Contents. 2. Relevant Documentation. 3. Software Setup
CP2110 EVALUATION KIT USER S GUIDE 1. Kit Contents The CP2110 Evaluation Kit contains the following items: CP2110 Evaluation Board RS232 Serial Cable USB Cable DVD Quick Start Guide 2. Relevant Documentation
Modbus and ION Technology
70072-0104-14 TECHNICAL 06/2009 Modbus and ION Technology Modicon Modbus is a communications protocol widely used in process control industries such as manufacturing. PowerLogic ION meters are compatible
2-Port RS232/422/485 Combo Serial PCI Card
2-Port RS232/422/485 Combo Serial PCI Card Installation Guide 1. Introduction Thank you for purchasing this 2-Port RS232/422/485 Combo Serial PCI Card. It is a universal add in card that connects to a
RJ45 Shielded (standard) port pinout. CS9000, Jetstream 4000 + 8500, Lanstream 2000, RTA8/RJX, RRC16, MTA8/RJX & SXDC8/RJX
Shielded (standard) port pinout Pin Circuit Function 1 DCD Input Data Carrier Detect 2 DSR Output Data Set Ready 3 DTR Input Data Terminal Ready 4 S/GND Signal Ground 5 TXD Output Transmit Data 6 RXD Input
PM1122 INT DIGITAL INTERFACE REMOTE
PM1122 INT DIGITAL INTERFACE REMOTE PM1122 INT front panel description: 1. Clear wireless remotes knob: push this button for more than 2 seconds to clear the list of all assigned wireless remote settings
WHITEPAPER. August 15, 2006
August 15, 2006 WHITEPAPER DeltaV Integration with Rockwell PLCs Using Ethernet/IP Process DeltaV Integration with Rockwell PLCs is quick and cost-effective using the Ethernet/IP Driver for the DeltaV
LAN / WAN Connection Of Instruments with Serial Interface By Using a Terminal Server
Products: EFA with EFA Scan, DVRM and DVMD with Realtime Monitor or Stream Explorer DVMD-B1 LAN / WAN Connection Of Instruments with Serial Interface By Using a Terminal Server Remote control of test and
Quick Installation. A Series of Intelligent Bar Code Reader with NeuroFuzzy Decoding. Quick Installation
Quick Installation A Series of Intelligent Bar Code Reader with NeuroFuzzy Decoding This chapter intends to get your new FuzzyScan scanner working with your existing system within minutes. General instructions
XPort Universal Demo Board User Guide
XPort Universal Demo Board User Guide Part Number 900-563 Revision A September 2009 Copyright and Trademark Contacts 2009 Lantronix. All rights reserved. No part of the contents of this book may be transmitted
Using Xbee 802.15.4 in Serial Communication
Using Xbee 802.15.4 in Serial Communication Jason Grimes April 2, 2010 Abstract Instances where wireless serial communication is required to connect devices, Xbee RF modules are effective in linking Universal
L16. Quectel GNSS Engine. EVB User Guide L16_EVB_UGD_V1.0
L16 GNSS Engine EVB User Guide L16_EVB_UGD_V1.0 Document Title L16 EVB User Guide Version 1.0 Date 2012-07-18 Status Document Control ID Released L16_EVB_UGD_V1.0 General Notes offers this information
The Answer to the 14 Most Frequently Asked Modbus Questions
Modbus Frequently Asked Questions WP-34-REV0-0609-1/7 The Answer to the 14 Most Frequently Asked Modbus Questions Exactly what is Modbus? Modbus is an open serial communications protocol widely used in
Control Technology Corporation CTC Monitor User Guide Doc. No. MAN-1030A Copyright 2001 Control Technology Corporation All Rights Reserved Printed in USA The information in this document is subject to
Bluetooth to Serial Adapter
Bluetooth to Serial Adapter Third Edition, Oct 2007 Version 3.0 771-BTS1009C3-001 Contents 1.0 Features....P.2 2.0 Package Content....P.2 3.0 Hard Drives Requirement.P.2 4.0 Specifications.P.3 5.0 Pin
RS-422/485 Multiport Serial PCI Card. RS-422/485 Multiport Serial PCI Card Installation Guide
RS-422/485 Multiport Serial PCI Card Installation Guide 21 Contents 1. Introduction...1 2. Package Check List...2 3. Board Layouts and Connectors...3 3.1 2S with DB9 Male Connectors...3 3.1.1 JP5: UART
GV- RK1352 Card Reader
GV- RK1352 Card Reader The GV-RK1352 is a card reader with keypad, designed to recognize PIN codes, identification cards or both. Featured with the Wiegand and RS-485 outputs, the unit can be connected
Professional USB to Serial Adapter Hub with COM Retention
Professional USB to Serial Adapter Hub with COM Retention ICUSB2321X ICUSB2322X ICUSB2324X *actual product may vary from photos *actual product may vary from photos DE: Bedienungsanleitung - de.startech.com
WinPFT File Transfer Utility (Catalog No. 2711-ND7)
Technical Data WinPFT File Transfer Utility (Catalog No. 2711-ND7) Overview WINPFT is a stand-alone Windows utility which lets you transfer applications developed for standard PanelView terminals or Dataliner
M72. Quectel Cellular Engine. EVB User Guide M72_EVB_UGD_V1.0
M72 Quectel Cellular Engine EVB User Guide M72_EVB_UGD_V1.0 Document Title EVB User Guide Version 1.0 Date 2011-05-18 Status Document Control ID Release M72_EVB_UGD_V1.0 General Notes Quectel offers this
3.1 RS-232/422/485 Pinout:PORT1-4(RJ-45) RJ-45 RS-232 RS-422 RS-485 PIN1 TXD PIN2 RXD PIN3 GND PIN4 PIN5 T+ 485+ PIN6 T- 485- PIN7 R+ PIN8 R-
MODEL ATC-2004 TCP/IP TO RS-232/422/485 CONVERTER User s Manual 1.1 Introduction The ATC-2004 is a 4 Port RS232/RS485 to TCP/IP converter integrated with a robust system and network management features
Serial to Bluetooth Adapter
Serial to Bluetooth Adapter Serial (RS-232) to Bluetooth Class 1 Adapter ICRS232BT1 Actual product may vary from photo FCC Compliance Statement This equipment has been tested and found to comply with the
RS-232 Communications Using BobCAD-CAM. RS-232 Introduction
RS-232 Introduction Rs-232 is a method used for transferring programs to and from the CNC machine controller using a serial cable. BobCAD-CAM includes software for both sending and receiving and running
RouteFinder SOHO. Quick Start Guide. SOHO Security Appliance. EDGE Models RF825-E, RF825-E-AP CDMA Models RF825-C-Nx, RF825-C-Nx-AP
RouteFinder SOHO SOHO Security Appliance EDGE Models RF825-E, RF825-E-AP CDMA Models RF825-C-Nx, RF825-C-Nx-AP Quick Start Guide RouteFinder RF825 Series Quick Start Guide RouteFinder SOHO Security Appliance
Using a Laptop Computer with a USB or Serial Port Adapter to Communicate With the Eagle System
Using a Laptop Computer with a USB or Serial Port Adapter to Communicate With the Eagle System ECU DB9 USB 20-060_A.DOC Page 1 of 18 9/15/2009 2009 Precision Airmotive LLC This publication may not be copied
Paragon Explorer Lite Communication Software
CU-111 APRIL 11, 2013 Paragon Explorer Lite Communication Software For Fireye Paragon Scanners using Windows XP DESCRIPTION Paragon Explorer Lite, is the basic PC based configuration tool for Paragon model
Troubleshooting and Diagnostics
Troubleshooting and Diagnostics The troubleshooting and diagnostics guide provides instructions to assist in tracking down the source of many basic controller installation problems. If there is a problem
How To Set Up A Modbus Cda On A Pc Or Maca (Powerline) With A Powerline (Powergen) And A Powergen (Powerbee) (Powernet) (Operating System) (Control Microsci
Firmware Loader User Manual CONTROL MICROSYSTEMS SCADA products... for the distance 48 Steacie Drive Telephone: 613-591-1943 Kanata, Ontario Facsimile: 613-591-1022 K2K 2A9 Technical Support: 888-226-6876
NMEA 0183 INSTALLATION AND OPERATING GUIDELINES
NMEA 0183 INSTALLATION AND OPERATING GUIDELINES Revised July 2010 8.1.3 Documentation The following documentation shall be provided to the owner for each interfaced system and shall be kept on file by
isco Connecting Routers Back to Back Through the AUX P
isco Connecting Routers Back to Back Through the AUX P Table of Contents Connecting Routers Back to Back Through the AUX Ports...1 Introduction...1 Before You Begin...1 Conventions...1 Prerequisites...1
2-Port RS232/422/485 Combo Serial to USB2.0 Adapter (w/ Metal Case and Screw Lock Mechanism) Installation Guide
2-Port RS232/422/485 Combo Serial to USB2.0 Adapter (w/ Metal Case and Screw Lock Mechanism) Installation Guide 1. Introduction Thank you for purchasing this 2-Port RS232/422/485 Combo Serial to USB Adapter.
Introduction: Implementation of the MVI56-MCM module for modbus communications:
Introduction: Implementation of the MVI56-MCM module for modbus communications: Initial configuration of the module should be done using the sample ladder file for the mvi56mcm module. This can be obtained
Making a DB to RJ45 adapter.
Making a DB to RJ45 adapter. DB9 to RJ45 adapters are often used in combination with a RS232 repeater for extending the distance of a serial RS232 link, but can be used for any adapter or converter purposes.
ENET-710. ENET-710 - Ethernet Module ENET-710 JAN / 06 FOUNDATION
ENET-710 ENET-710 - Ethernet Module JAN / 06 ENET-710 FOUNDATION E N E T 7 1 0 ME smar www.smar.com Specifications and information are subject to change without notice. Up-to-date address information is
WHQL Certification Approval...2 User Interface...3 SUNIX s COMLab..4
INDEX WHQL Certification Approval...2 User Interface....3 SUNIX s COMLab..4 1.0 Introduction...5 2.0 Specification..5 2.1 Features 2.2 Universal Serial PCI Card 2.3 RS-232 Specification 2.4 Low Profile
DUKANE Intelligent Assembly Solutions
PC Configuration Requirements: Configuration Requirements for ipc Operation The hardware and operating system of the PC must comply with a list of minimum requirements for proper operation with the ipc
Virtual Integrated Design Getting started with RS232 Hex Com Tool v6.0
Virtual Integrated Design Getting started with RS232 Hex Com Tool v6.0 Copyright, 1999-2007 Virtual Integrated Design, All rights reserved. 1 Contents: 1. The Main Window. 2. The Port Setup Window. 3.
Schneider OS-Loader usage via Ethernet or USB.
LHC Gas Systems 28 th February, 2007 Schneider OS-Loader usage via Ethernet or USB. Jacques ROCHEZ - IT/CO/FE Abstract This document is a guideline on how to configure correctly a PC for the use of the
MCB3101 (Class I) WiRobot Serial Bluetooth Wireless Module User Manual
MCB3101 (Class I) WiRobot Serial Bluetooth Wireless Module User Manual Version: 1.0.1 Dec. 2005 Table of Contents I. Introduction 2 II. Operations 2 II.1. Theory of Operation 2 II.2. Configuration (PC-PC
The Wireless LAN (Local Area Network) USB adapter can be operated in one of the two following networking configurations :
SAGEM Wi-Fi 11g USB ADAPTER Quick Start Guide About this guide This Quick Start Guide describes how to install and operate your SAGEM Wi-Fi 11g USB ADAPTER. Please read this manual before you install the
FREQUENTLY ASKED QUESTIONS (FAQs) 123Scan 2 Scanner Configuration Utility
FREQUENTLY ASKED QUESTIONS (FAQs) 123Scan 2 Scanner Configuration Utility TABLE OF CONTENTS Question No. Product Overview What model scanners are supported by 123Scan 2 1 What are the key features of 123Scan
The Analyst RS422/RS232 Tester. With. VTR, Monitor, and Data Logging Option (LOG2) User Manual
12843 Foothill Blvd., Suite D Sylmar, CA 91342 818 898 3380 voice 818 898 3360 fax www.dnfcontrolscom The Analyst RS422/RS232 Tester With VTR, Monitor, and Data Logging Option (LOG2) User Manual Manual
Modbus and ION Technology
Modbus and ION Technology Modicon Modbus is a communications protocol widely used in process control industries such as manufacturing. ACCESS meters are compatible with Modbus networks as both slaves and
Testing Data Radio Modem with Serial Port Tool V1.20
Testing Data Radio Modem with Serial Port Tool V1.20 This document demonstrates how to test the communication of data radio modem with tool Advanced Serial Port Monitor from AGG Software and USB board.
Advanced Data Capture and Control Systems
Advanced Data Capture and Control Systems Tronisoft Limited Email: [email protected] Web: www.tronisoft.com RS232 To 3.3V TTL User Guide RS232 to 3.3V TTL Signal Converter Modules P/N: 9651 Document
How To Connect A Directsofl To A Powerpoint With An Acd With An Ctel With An Dm-Tel Modem On A Pc Or Ipad Or Ipa (Powerpoint) With A Powerline 2 (Powerline
Application Note Last reviewed: 03/17/2008 AN-KEP-003.doc Page 1 of 23 Introduction... 1 Recommended s and ports to use... 1 Cable Wiring... 2 MDM-TEL Configuration ( Wizard)... 3 Direct Logic Communications
EDI Distributor Control Interface Wiring and Setup Instructions
Universal I/O EDI Distributor Control Interface Wiring and Setup Instructions EDI UNIVERSAL I/O INTERFACE MODULE The only interface needed for EDI-V5 controls Network compatible with all older EDI controls
Laser Wireless Rechargeable Mouse. User s Manual
Laser Wireless Rechargeable Mouse Model #: LM8000WR User s Manual Rev. 060801 User s Record: To provide quality customer service and technical support, it is suggested that you keep the following information
Connecting the Console Port to a PC
This document covers tasks associated with connecting a console port to a PC, and includes the following topics: Console (rollover) Cable and Adapters Making the physical connection Connecting using HyperTerminal
Installation & Configuration Manuel. Socket Server. OpenAT application
Installation & Configuration Manuel Socket Server OpenAT application 2009 / 05 / 29 2 ! CAUTION! ELECTRIC SHOCK HAZARD IF COVER REMOVED SERVICE BY QUALIFIED PERSONEL ONLY Document History Date Version
In-System Programmer USER MANUAL RN-ISP-UM RN-WIFLYCR-UM-.01. www.rovingnetworks.com 1
RN-WIFLYCR-UM-.01 RN-ISP-UM In-System Programmer 2012 Roving Networks. All rights reserved. Version 1.1 1/19/2012 USER MANUAL www.rovingnetworks.com 1 OVERVIEW You use Roving Networks In-System-Programmer
One Port Serial Server Users Manual Model ESP901, ESP901E
One Port Serial Server Users Manual Model ESP901, ESP901E Documentation Number: ESP901-2303 International Headquarters B&B Electronics Mfg. Co. Inc. 707 Dayton Road -- P.O. Box 1040 -- Ottawa, IL 61350
Keep it Simple Timing
Keep it Simple Timing Support... 1 Introduction... 2 Turn On and Go... 3 Start Clock for Orienteering... 3 Pre Start Clock for Orienteering... 3 Real Time / Finish Clock... 3 Timer Clock... 4 Configuring
WA Manager Alarming System Management Software Windows 98, NT, XP, 2000 User Guide
WA Manager Alarming System Management Software Windows 98, NT, XP, 2000 User Guide Version 2.1, 4/2010 Disclaimer While every effort has been made to ensure that the information in this guide is accurate
Serial Over IP Ethernet Device Server
NETRS2321E NETRS2321EEU NETRS2321EGB Instruction Manual Serial Over IP Ethernet Device Server 1 Port RS-232/422/485 Serial over IP Ethernet Device Server Manual Revision:10/13/2010 For the most up-to-date
LBNP16312. RS-232/485/422 serial device server. User manual
Tu Sitio de Automatización! LBNP16312 RS-232/485/422 serial device server User manual Summarize-----------------------------------------------------------------------------14-3 Package checklist---------------------------------------------------------------------14-3
USER GUIDE. Ethernet Configuration Guide (Lantronix) P/N: 2900-300321 Rev 6
KRAMER ELECTRONICS LTD. USER GUIDE Ethernet Configuration Guide (Lantronix) P/N: 2900-300321 Rev 6 Contents 1 Connecting to the Kramer Device via the Ethernet Port 1 1.1 Connecting the Ethernet Port Directly
Instructions on How to Use HyperTerminal to Test Serial Ports ...
Print Date: 04.03.2010 Testing Serial Cards Instructions on How to Use HyperTerminal to Test Serial Ports... Brain Boxes Limited, Unit 3C, Wavertree Boulevard South, Wavertree Technology Park, Liverpool,
Fanuc 0 M/T Model C Serial (RS232) Connection Guide
Memex Automation Inc., Burlington, Ontario Canada L7N 1 http://www.memex.ca Fanuc 0 M/T Model C Serial (RS232) Connection Guide The Fanuc 0-C control has two RS-232 interfaces. Interface number 1 (M5)
TRP-C31M MODBUS TCP to RTU/ASCII Gateway
TRP-C31M MODBUS TCP to RTU/ASCII Gateway User s Manual Printed Feb. 2007 Rev 1.0 Trycom Technology Co., Ltd 1F, No.2-11, Sihu street, Yingge Township, Taipei, Taiwan ROC Tel: 886-2-86781191, Fax: 886-2-86781172
Metrologic MS1690 2D Scanner Installation Guide
Metrologic MS1690 2D Scanner Installation Guide Revision 1.0 Revision History 1.0 04/17/2007 Initial Release The latest version of this document can be found in the following places: Internally for Cerner
Installation Instructions For Controllers with MS/TP Automatic MAC Addressing. Patent Pending 000-019-01
Installation Instructions For Controllers with MS/TP Automatic MAC Addressing Patent Pending 000-019-01 KMC Controls Important notices Disclaimer 2009, KMC Controls, Inc. TotalControl, BACstage and FullBAC
Programming Flash Microcontrollers through the Controller Area Network (CAN) Interface
Programming Flash Microcontrollers through the Controller Area Network (CAN) Interface Application te Programming Flash Microcontrollers through the Controller Area Network (CAN) Interface Abstract This
Configuring the SST DeviceNet OPC Server
Overview This application note describes the steps necessary to configure the SST DeviceNet OPC Server for use under Windows NT (Service Pack 3 or higher). This example shows how to set up a configuration
Accessing Diagnostics using a Dialup Modem
Purpose This application note is meant to guide a user through the setup and use of a dial-up modem to retrieve diagnostics data from a remote master. Equipment Used This application note was written specifically
16-Port RS232 to USB2.0 High Speed Multi Serial Adapter (w/ Metal Case) Installation Guide
16-Port RS232 to USB2.0 High Speed Multi Serial Adapter (w/ Metal Case) Installation Guide 1. Introduction Thank you for purchasing this 16-Port RS232 to USB2.0 High Speed Multi Serial Adapter. It is an
NStar Build 648. Release Notes. Page 1 of 17
NStar Build 648 Release Notes Page 1 of 17 This page is left blank intentionally Page 2 of 17 NStar Build 648 Release Notes Release notes NStar Build 648 Overview These release
RIGtalk. Revision 5. Owner s Manual 2012.
RIGtalk Revision 5 Owner s Manual 2012 www.westmountainradio.com 1020 Spring City Drive Waukesha, WI 53186 262-522-6503 [email protected] 2012 West Mountain Radio, All rights reserved. All trademarks