Outdoor Vacuum Circuit-Breakers 3AF0/3AG0/SDV6

Size: px
Start display at page:

Download "Outdoor Vacuum Circuit-Breakers 3AF0/3AG0/SDV6"

Transcription

1 Outdoor Vacuum Circuit-Breakers 3AF0/3AG0/SDV6 Medium-Voltage Equipment Selection and Ordering Data Catalog HG

2 R-HG11-17.tif Siemens HG

3 Contents Contents Page Outdoor Vacuum Circuit-Breakers 3AF0 / 3AG0 / SDV6 Description General Construction and mode of operation, standards Ambient conditions and dielectric strength Medium-Voltage Equipment Catalog HG Product range overview 11 Equipment Selection Ordering data and configuration example Selection of basic type, live tank Selection of basic type, dead tank 0 Accessories and spare parts 5 Technical Data Electrical data, dimensions and weights, live tank Electrical data, dimensions and weights, dead tank 30 Operating times 3 Annex Inquiry form Configuration instructions Configuration aid Foldout page 4 Siemens AG 008 Siemens HG

4 R-HG11-XXX.tif 4 Siemens HG

5 Description Contents Contents Description General Live tank construction: Pole assembly Operating mechanism box Page Dead tank construction: Vacuum circuit-breaker Operating mechanism box 8 8 Transformer substation R-HG11-XXX.tif Construction and mode of operation: Operating mechanism Releases Closing Standards Ambient conditions Dielectric strength Product range overview Siemens HG

6 Description General Outdoor Vacuum Circuit-Breakers 3AF0 / 3AG0 / SDV6 Outdoor vacuum circuit-breakers The Weather-Proof 1 Outdoor vacuum circuit-breakers are especially designed for outdoor installation. The design comprises a minimum of moving parts and a simple construction, which guarantees a long electrical and mechanical endurance, offering the same advantages as indoor vacuum circuitbreakers. 3AF0 / 3AG0 live tank SDV6 dead tank R-HG11-XXX.eps R-HG11-XXX.eps In live-tank circuit-breakers, the vacuum interrupter is arranged in a weather-proof way inside an insulating enclosure, e.g. made of porcelain. The vacuum interrupter is at electrical potential, which means live. Due to their light and space-saving design, the outdoor vacuum circuit-breaker types 3AF0 and 3AG0 are easy to transport and can be divided into separate modules. Their ratings are convincing due to the proven components which are also used in indoor circuit-breakers. At the same time, they can be optimally adapted to the necessary applications using current and voltage transformers. The significant property of the dead-tank technology is the arrangement of a complete vacuum circuit-breaker in an earthed metal enclosure, thus defined as dead. The outdoor vacuum circuit-breakers SDV6 are circuitbreaker with an earthed, weather-proof housing, which contains current and voltage transformers and a low-voltage part with a protection device. 6 Siemens HG

7 Description Live tank construction Live tank construction 3AF0 and 3AG0 outdoor vacuum circuit-breakers consist of the pole assembly (1), the operating mechanism box () and a steel structure (3) to accommodate all components. In 3AF0 circuit-breakers, the pole assemblies are mounted on a base frame (4) equipped with a common operating shaft. In 3AG0 circuit-breakers, this operating shaft is integrated in the operating mechanism box The vacuum switching technology, proven and fully developed for more than 30 years, serves as arc-quenching principle by using vacuum interrupters. Pole assembly 3 HG eps 3 HG eps The pole assembly consists of the vacuum interrupter (5), porcelain insulators (6) and the terminal connectors (7 and 8). The vacuum interrupter is mounted in a porcelain insulator. At the upper end it is rigidly fixed to the terminal connector (7). The lower part allows free axial movement and is connected to the lower terminal connector (8) via flexible connectors (9). Another porcelain insulator, which separates the terminals from the steel structure and the operating mechanism box, contains the switching rod (10), which transmits the switching movement from the operating mechanism box to the vacuum interrupter. The poles can be air-insulated or gas-insulated AG0 circuit-breaker 1 Pole assembly Operating mechanism box 3 Steel structure 4 Base frame 5 Vacuum interrupter 6 Porcelain insulator 7 Upper terminal connector 8 Lower terminal connector 9 Flexible connector 10 Switching rod 10 HG eps 3AF0 circuit-breaker Live tank construction and pole assembly Operating mechanism box The operating mechanism box contains the circuit-breaker operating mechanism with motor, releases and auxiliary switches, as well as the completely wired control cabinet comprising the connections for remote operation, the auxiliary voltages for circuit-breaker operation and the necessary low voltage supply. At the same time, it accommodates the control elements for local operation of the circuit-breaker. Operating mechanism box of 3AF0 R-HG11-XXX.eps Siemens HG

8 Description Dead tank construction Outdoor Vacuum Circuit-Breakers 3AF0 / 3AG0 / SDV6 Dead tank construction Low-voltage box Operating mechanism section 3 High-voltage section 4 Bushing SDV6 outdoor vacuum circuit-breakers consist of an earthed enclosure incorporating an indoor vacuum circuit-breaker, current transformers and a low-voltage section with protection device, controlling and heating. The enclosure is divided into different sections which are segregated and protected from each other. These sections are accessible via separate doors. The low-voltage box (1) and the operating mechanism section () are located at the front side of the device. The high-voltage section (3) is accessible from the rear. Bushings (4) mounted on top of the device establish the connection to the high-voltage power system HG eps HG eps Pole assembly 6 Operating mechanism box 7 Post insulator 8 Switching rod 9 Vacuum interrupter 10 Upper interrupter support 11 Lower interrupter support 1 Brace The low-voltage box contains the connections for remote operation as well as the power supply for the switching device and the protection equipment. The operating mechanism section covers the operating mechanism box of the indoor circuit-breaker with the control elements. The pole assemblies of the circuit-breaker are accessible through the high-voltage section. Vacuum circuit-breaker The vacuum circuit-breaker consists of the pole assemblies (5) and the operating mechanism box (6). The pole assemblies are fixed to the operating mechanism box via post insulators (7). The switching movement is transferred by means of operating rods (8) and levers. The vacuum switching technology, proven and fully developed for more than 30 years, serves as arc-quenching principle by using vacuum interrupters. Dead tank construction and pole assembly The pole assembly consists of the vacuum interrupter (9) and the interrupter supports. The vacuum interrupters are airinsulated and freely accessible. The vacuum interrupter is rigidly fixed to the upper interrupter support (10). The lower part of the interrupter is guided in the lower interrupter support (11), allowing axial movement. The braces (1) absorb the external forces resulting from switching operations and the contact pressure. Operating mechanism box The whole operating mechanism with releases, auxiliary switches, indicators and actuating devices is accommodated in the operating mechanism box. The extent of the secondary equipment depends on the case of application and offers a multiple variety of options in order to meet almost every requirement. R-HG11-XXX.eps View into the open operating mechanism box 8 Siemens HG

9 Description Construction and mode of operation, standards Operating mechanism Both for live-tank and dead-tank circuit-breakers, the operating mechanism is a stored-energy mechanism. The closing spring is charged either electrically or manually. It latches tight after completion of the charging process and serves as an energy store. The force is transferred from the operating mechanism to the pole assemblies via switching rods. To close the breaker, the closing spring can be unlatched either mechanically by means of the local ON pushbutton or electrically by remote control. The closing spring charges the opening or contact pressure springs as the breaker closes. The now discharged closing spring will be charged again automatically by the mechanism motor or manually. Then the operating sequence OPEN-CLOSE-OPEN is stored in the springs. Releases A release is a device which transfers electrical commands from an external source, such as a control room, to the latching mechanism of the vacuum circuit-breaker so that it can be opened or closed. The maximum possible equipment is one shunt release and two other releases. For release combinations, refer to page 16 or page 8. The closing solenoid unlatches the charged closing spring of the vacuum circuit-breaker, closing it by electrical means. Shunt releases are used for automatic tripping of vacuum circuit-breakers by suitable protection relays and for deliberate tripping by electrical means. They are intended for connection to an external power supply (DC or AC voltage) but, in special cases, may also be connected to a voltage transformer for manual operation. Current-transformer operated releases comprise a storedenergy mechanism, an unlatching mechanism and an electromagnetic system. They are used when there is no external source of auxiliary power (battery). Tripping is effected by means of a protection relay (e.g. overcurrent-time protection) acting on the current-transformer operated release. Undervoltage releases comprise a stored-energy mechanism, an unlatching mechanism and an electromagnetic system which is permanently connected to the secondary or auxiliary voltage while the vacuum circuit-breaker is closed. If the voltage falls below a predetermined value, unlatching of the release is enabled and the vacuum circuit-breaker is opened via the stored-energy mechanism. The deliberate tripping of the undervoltage release generally takes place via an NC contact in the tripping circuit or via an NO contact by short-circuiting the magnet coil. With this type of tripping, the short-circuit current is limited by the built-in resistors. Undervoltage releases can also be connected to voltage transformers. When the operating voltage drops to impermissibly low levels, the circuit-breaker is tripped automatically. Closing In the standard version, the outdoor vacuum circuit-breakers can be remote-closed electrically. They can also be closed locally by mechanical unlatching of the closing spring via pushbutton. Instead of this manual mechanical closing, manual electrical closing is also available. In this version, the closing circuit of the circuit-breaker is controlled electrically by a pushbutton instead of the mechanical button. If constant CLOSE and OPEN commands are present at the vacuum circuit-breaker at the same time, the vacuum circuitbreaker will return to the open position after closing. It remains in this position until a new CLOSE command is given. In this manner, continuous closing and opening (= pumping ) is prevented. Standards 3AF0 and 3AG0 outdoor vacuum circuit-breakers conform to the following standards: IEC (former IEC 60056) IEC (in future IEC 671-1) VDE 0671 (former VDE 0670) SDV6 outdoor vacuum circuit-breakers conform to the following standards: ANSI C37.0 IEEE C ANSI Rain tested (C ) UBC/CBC Seismic Zone 1 or UBC/CBC Seismic Zone 3 or 4 Furthermore, an outdoor vacuum circuit-breaker is available for IEC applications. It conforms to the following standards: NOM-J-11 IEC 56 IEC 137 IEC 98 ANSI C37.0. ANSI C Siemens HG

10 Description Ambient conditions and dielectric strength Outdoor Vacuum Circuit-Breakers 3AF0 / 3AG0 / SDV6 Ambient conditions The outdoor vacuum circuit-breakers are designed for the normal operating conditions defined in IEC C Condensation can occasionally occur under the ambient conditions shown opposite. Outdoor vacuum circuit-breakers are suitable for use in the following climatic classes according to IEC 6071, Part 3-3: -40 C max. 95% per day max. 90% per month HG11-515a_en eps Climatic ambient conditions: Class 3K4 1) Biological ambient conditions: Class 3B1 Mechanical ambient conditions: Class 3M Chemically-active substances: Class 3C ) Mechanically-active substances: Class 3S 3) 1) Low temperature limit: 40 C (on request) ) Without icing and wind-driven precipitation 3) Restriction: Clean insulation parts Altitude correction factor HG11-517c_en eps Dielectric strength The dielectric strength of air insulation decreases with increasing altitude due to low air density. According to IEC 60694, the rated lightning impulse withstand voltage values specified in the chapter Technical Data apply to a site altitude of 1000 m above sea level. For an altitude above 1000 m, the insulation level must be corrected according to the opposite diagram m 4000 Site altitude The characteristic shown applies to the rated short-duration power-frequency withstand voltage and the rated lightning impulse withstand voltage. To select the devices, the following applies: U W U 0 x K a U U 0 K a Rated withstand voltage under standard reference atmosphere Rated lightning impulse withstand voltage requested for the place of installation Altitude correction factor according to the opposite diagram Example For a requested rated lightning impulse withstand voltage of 75 kv at an altitude of 500 m, an insulation level of 90 kv under standard reference atmosphere is required as a minimum: 90 kv W 75 kv x Siemens HG

11 Description Product range overview Product range overview Rated voltage Rated shortcircuit breaking current Rated normal current kv ka 150 A 1600 A 000 A 3000 A AG0 3AF01 3AF03 SDV6 Siemens HG

12 1 R-HG11-XXX.tif 1 Siemens HG

13 Equipment Selection Contents Contents Page Equipment Selection 13 Ordering data and configuration example 14 Selection of basic type, live tank: Voltage level 1 kv 15 Voltage level 17.5 kv 15 Voltage level 36 kv 15 Selection of secondary equipment, live tank Selection of additional equipment, live tank Selection of basic type, dead tank: Voltage level 15.5 kv 0 Voltage level 7.6 kv 0 3AG0 outdoor vacuum circuit-breaker (live tank) R-HG11-XXX.tif Voltage level 38 kv Selection of secondary equipment, dead tank 0 1 Accessories and spare parts 5 R-HG11-XXX.tif SDV6 outdoor vacuum circuit-breaker (dead tank) Siemens HG

14 Equipment Selection Ordering data and configuration example Outdoor Vacuum Circuit-Breakers 3AF0 / 3AG0 / SDV6 Order number structure The outdoor vacuum circuit-breakers consist of a primary and a secondary part. In the live-tank type, the relevant data make up the 16-digit order number. The primary part covers the main electrical data of the circuit-breaker poles. The secondary part covers the auxiliary devices which are necessary for operating and controlling the vacuum circuit-breaker. In the dead-tank type, the 16-digit order number describes the circuit-breaker. The versions for housings, controlling, etc. must be inquired and specified in clear text. Special versions ( ) In case of special versions, -Z is added to the order number and a descriptive order code follows. If several special versions are required, the suffix -Z is listed only once. If a requested special version is not in the catalog and can therefore not be ordered via order code, it has to be identified with Y 9 9 after consultation. The agreement hereto is made between your responsible sales partner and the order processing department in our Switchgear Factory in Berlin. Order codes Individual equipment versions, marked with 9 or Z in the 9 th to 16 th position, are explained more in detail by a 3-digit order code. Several order codes can be added to the order number in succession and in any sequence. Primary part 1 st position Superior group Switching devices a: alphabetical n: numerical Position: Ordercodes Order No.: a/n a a n n n n n a a n n n a a n nd position Main group Circuit-breaker 3 rd position Subgroup Circuit-breaker type series 4 th to 7 th position Basic equipment Design and ratings primary part Secondary part 8 th to 16 th position Secondary equipment Operating mechanism, releases, operating voltages and further auxiliary equipment Order codes Groupof3aftertheOrderNo. Format: a n a Special versions ( ) Initiated with -Z Groupof3aftertheOrderNo. Format: a n n Configuration example In order to simplify the selection of the correct order number for the requested circuit-breaker type, you will find a configuration example on each page of the chapter Equipment Selection. For the selection of the secondary part, always the last example of the primary part was taken over and continued, so that at the end of the equipment selection (pages 19 and 4) a completely configured circuit-breaker results as an example. On the foldout page we offer a configuring aid. Here you can fill in the order number you have determined for your circuit-breaker. Example for Order No.: 3 A F Order codes: 14 Siemens HG

15 Equipment Selection Selection of basic type, live tank 1 kv Position: Ordercodes 50/60 Hz Order No.: 3 A Rated voltage Rated lightning impulse withstand voltage Rated short-duration power-frequency withstand voltage Rated short-circuit breaking current at 36 % DC component Rated short-circuit making current (at 50/60 Hz) Rated normal current Seepage16 Seepage16 Seepage16 Seepage17 Seepage17 Seepage18 Seepage18 Seepage18 Seepage18 Seepage19 U r U p U d I sc I ma I r kv kv kv ka ka A / A G Special version: U p =95kV U d =38kV (onlypossibletogether) Z V kv 50/60 Hz U r U p U d I sc I ma I r kv kv kv ka ka A / A F A F kv 50/60 Hz U r U p U d I sc I ma I r kv kv kv ka ka A / A F A F / A F A F Special versions (available for all 36 kv circuit-breakers): U p = 00 kv U d =80kV (onlypossibletogether) Z V 1 0 U p = 00 kv U d =95kV (onlypossibletogether) Z V 1 3 Configuration example 3AF outdoor vacuum circuit-breaker 3 A F Rated voltage U r = 36 kv Rated short-circuit breaking current I sc = 5 ka Rated normal current I r = 000 A Special version U p = 00 kv, U d = 95 kv Z V 1 3 Example for Order No.: 3 A F Z Order codes: V 1 3 Siemens HG

16 Equipment Selection Selection of secondary equipment, live tank Outdoor Vacuum Circuit-Breakers 3AF0 / 3AG0 / SDV6 8 th position Position: Ordercodes Closing Order No.: 3 A Option Seepage17 Seepage17 Seepage18 Seepage18 Seepage18 Seepage18 Seepage19 Manual mechanical closing 3 Manual electrical closing 4 9 th position Operating voltage of the motor operating mechanism Standard voltages Special voltages Without A 4 V DC B 48 V DC C 60 V DC D 110 V DC E 0 V DC F 100 V AC 50/60 Hz 1) G 110 V AC 50/60 Hz 1) H 30 V AC 50/60 Hz 1) J 30 V DC Z J 1 A 3 V DC Z J 1 B 10 V DC Z J 1 C 15 V DC Z J 1 D 17 V DC Z J 1 E 40 V DC Z J 1 F 10 V AC 50/60 Hz 1) Z J 1 K 15 V AC 50/60 Hz 1) Z J 1 L 40 V AC 50/60 Hz 1) Z J 1 M 1) The AC frequency 50 or 60 Hz is selected at the 15 th and 16 th position (see page 18) 10 th position Release combination Closing solenoid 1 st shunt release nd shunt release (Y) nd shunt release (Y3) C.t.-operated release Undervoltage release A C D E N P R Configuration example 3AF outdoor vacuum circuit-breaker 3 A F (U r = 36 kv, I sc = 5 ka, I r = 000 A) Manual electrical closing 4 Operating voltage of the motor operating mechanism 48 V DC Release combination: Closing solenoid, 1 st shunt release, c.t.-operated release C D Example for Order No.: 3 A F C D Z Order codes: V Siemens HG

17 Equipment Selection Selection of secondary equipment, live tank 11 th position Position: Ordercodes Operating voltage of the closing solenoid Order No.: 3 A and 1 st shunt release Standard voltages Special voltages Seepage18 Seepage18 Seepage18 Seepage18 Seepage19 4 V DC 1 48 V DC 60 V DC V DC 4 0 V DC V AC 50/60 Hz 1) V AC 50/60 Hz 1) 7 30 V AC 50/60 Hz 1) 8 30 V DC 9 L 1 A 3 V DC 9 L 1 B 10 V DC 9 L 1 C 15 V DC 9 L 1 D 17 V DC 9 L 1 E 40 V DC 9 L 1 F 10 V AC 50/60 Hz 1) 9 L 1 K 15 V AC 50/60 Hz 1) 9 L 1 L 40 V AC 50/60 Hz 1) 9 L 1 M 1 th position Operating voltage of the nd release Release as shunt release, c.t.-operated release or undervoltage release Standard voltages Special voltages Without or c.t.-operated release 0 4 V DC 1 48 V DC 60 V DC V DC 4 0 V DC V AC 50/60 Hz 1) V AC 50/60 Hz 1) 7 30 V AC 50/60 Hz 1) 8 30 V DC 9 M 1 A 3 V DC 9 M 1 B 10 V DC 9 M 1 C 15 V DC 9 M 1 D 17 V DC 9 M 1 E 40 V DC 9 M 1 F 10 V AC 50/60 Hz 1) 9 M 1 K 15 V AC 50/60 Hz 1) 9 M 1 L 40 V AC 50/60 Hz 1) 9 M 1 M 1) The AC frequency 50 or 60 Hz is selected at the 15 th and 16 th position (see page 18) Configuration example 3AF outdoor vacuum circuit-breaker 3 A F (U r = 36 kv, I sc = 5 ka, I r = 000 A) C D Operating voltage of the closing solenoid and 1 st shunt release 48 V DC nd release as c.t.-operated release 0 Example for Order No.: 3 A F C D 0 Z Order codes: V 1 3 Siemens HG

18 Equipment Selection Selection of secondary equipment, live tank Outdoor Vacuum Circuit-Breakers 3AF0 / 3AG0 / SDV6 13 th /14 th position Position: Ordercodes Auxiliary switch, circuit-breaker tripping signal Order No.: 3 A Operations counter Auxiliary switch 6NO+6NC Auxiliary switch 1NO+1NC Circuit-breaker tripping signal Seepage19 T V W X 15 th /16 th position Frequency of operating voltages Frequency 50 Hz or DC A 60 Hz A 3 Configuration example 3AF outdoor vacuum circuit-breaker 3 A F (U r =36kV, I sc =5kA, I r = 000 A) C D 0 With auxiliary switch 6 NO + 6 NC and circuit-breaker tripping signal T Frequency of operating voltages 50 Hz or DC A Example for Order No.: 3 A F C D 0 T A Z Order codes: V Siemens HG

19 Equipment Selection Selection of additional equipment, live tank Additional equipment Position: Ordercodes Order No.: 3 A Available for Options 3AG01 3AF01 3AF03 Insulator creepage distance 1300 mm Z V 1 1 Rated voltage 40.5 kv Z V 1 Lockable operating mechanism box Z V 0 Fixing for current transformer Z V 3 0 Fixing for current and voltage transformers Z V 3 1 Extension unit 600 mm Z V 3 Main extension unit, extra height 600 mm Z V 3 3 With current transformer mounting brackets with ct- channels Z V 3 5 With screening for the central pole assembly (bird screen) Z V 4 0 Auxiliary switch 1 NO + 1 NC Z V 5 0 Wiring.5 mm Z V 5 1 Circuit-breaker application up to 40 C ambient air temperature Z V 6 0 Gas-filled version with pressure indicator Z V 8 DC 60 V coil as 1 st shunt release for DC 110 V operating voltage Z V 8 3 With extension parts for circuit-breaker supporting structure Z V 3 Configuration example 3AF outdoor vacuum circuit-breaker 3 A F Rated voltage U r = 36 kv Rated short-circuit breaking current I sc = 5 ka Rated normal current I r = 000 A Special version U p = 00 kv, U d = 95 kv Z V 1 3 Manual electrical closing 4 Operating voltage of the motor operating mechanism 48 V DC C Release combination: Closing solenoid, 1 st shunt release, c.t.-operated release D Operating voltage of the closing solenoid and 1 st shunt release 48 V DC nd release as c.t.-operated release 0 With auxiliary switch 6 NO + 6 NC and circuit-breaker tripping signal T Frequency of operating voltages 50 Hz or DC A Lockable operating mechanism box Z V 0 Circuit-breaker application up to 40 C ambient air temperature Z V 6 0 Example for Order No.: 3 A F C D 0 T A Z Order codes: V V 0 + V 6 0 Siemens HG

20 Equipment Selection Selection of basic type, dead tank Outdoor Vacuum Circuit-Breakers 3AF0 / 3AG0 / SDV kv Position: Ordercodes 50/60 Hz Order No.: S D V 6 Rated voltage Rated lightning impulse withstand voltage Rated short-duration power-frequency withstand voltage Rated short-circuit breaking current at 36 % DC component Rated short-circuit making current (at 50/60 Hz) Rated normal current Seepage1 Seepage1 Seepage1 Seepage Seepage Seepage Seepage3 Seepage4 Seepage4 U r U p U d I sc I ma I r kv kv kv ka ka A ) S D V S D V ) S D V S D V ) S D V S D V S D V ) S D V S D V S D V ) 150 A according to IEC standard 7.6 kv 50/60 Hz U r U p U d I sc I ma I r kv kv kv ka ka A ) S D V S D V ) S D V S D V ) 150 A according to IEC standard 38 kv 50/60 Hz U r U p U d I sc I ma I r kv kv kv ka ka A ) S D V S D V ) S D V S D V S D V IEC S D V S D V IEC S D V ) S D V S D V ) 150 A according to IEC standard Configuration example Outdoor vacuum circuit-breaker, dead tank S D V 6 Rated voltage U r = 38 kv Rated short-circuit breaking current I sc = 40 ka Rated normal current I r = 000 A 6 4 Example for Order No.: S D V Order codes: 0 Siemens HG

21 Equipment Selection Selection of secondary equipment, dead tank 8 th position Position: Ordercodes Release combination Order No.: S D V 6 Closing solenoid 1 st shunt release nd shunt release Seepage Seepage Seepage Seepage3 Seepage4 Seepage4 1 9 th position Operating voltage of the 1 st shunt release Voltage 4 V DC B 48 V DC C 110 V DC D 15 V DC E 50 V DC F 10 V AC 50/60 Hz 1) J 15 V AC 50/60 Hz 1) K 40 V AC 50/60 Hz 1) L 1) The frequency of the operating voltage was selected at the 14 th position together with the language and the color (see page 3) 10 th position Operating voltage of the nd shunt release Voltage Without nd shunt release (8 th position = 1) A 4 V DC B 48 V DC C 110 V DC D 15 V DC E 50 V DC F 10 V AC 50/60 Hz 1) J 15 V AC 50/60 Hz 1) K 40 V AC 50/60 Hz 1) L 1) The frequency of the operating voltage was selected at the 14 th position together with the language and the color (see page 3) Configuration example Outdoor vacuum circuit-breaker, dead tank S D V 6 (U r = 38 kv, I sc = 40 ka, I r = 000 A) 6 4 Release combination: Closing solenoid and 1 st shunt release 1 Operating voltage of the 1 st shunt release 15 V AC Without nd shunt release (8 th position = 1) K A Example for Order No.: S D V K A Order codes: Siemens HG

22 Equipment Selection Selection of secondary equipment, dead tank Outdoor Vacuum Circuit-Breakers 3AF0 / 3AG0 / SDV6 11 st position Position: Ordercodes Operating voltage of the closing solenoid Order No.: S D V 6 Voltage Seepage3 Seepage4 Seepage4 4 V DC 1 48 V DC 110 V DC 3 15 V DC 4 50 V DC 5 10 V AC 50/60 Hz 1) 6 15 V AC 50/60 Hz 1) 7 40 V AC 50/60 Hz 1) 8 1) The frequency of the operating voltage was selected at the 14 th position together with the language and the color (see page 3) 1 nd position Operating voltage of the motor operating mechanism Voltage 4 V DC 1 48 V DC 110 V DC 3 15 V DC 4 50 V DC 5 10 V AC 50/60 Hz 1) 6 15 V AC 50/60 Hz 1) 7 40 V AC 50/60 Hz 1) 8 1) The frequency of the operating voltage was selected at the 14 th position together with the language and the color (see page 3) 13 rd position Auxiliary switch and control cable connection Auxiliary Auxiliary Auxiliary 64-pole switch switch switch plug 6NO+6NC 1NO+1NC NO+NC connector 1 3 Configuration example Outdoor vacuum circuit-breaker, dead tank S D V 6 (U r = 38 kv, I sc = 40 ka, I r = 000 A) K A Operating voltage of the closing solenoid 15 V AC 7 Operating voltage of the motor operating mechanism 15 V AC 7 Auxiliary switch 6 NO + 6 NC and 64-pole plug connector 1 Example for Order No.: S D V K A Order codes: Siemens HG

23 Equipment Selection Selection of secondary equipment, dead tank 14 th position Position: Ordercodes Frequency of operating voltages, Order No.: S D V 6 languages of operating instructions and equipment color Frequency Language DC 50 Hz 50 Hz and DC 60 Hz 60 Hz and DC Color Seepage4 Seepage4 English ASA 61 A English ASA 61 B Spanish ASA 61 C Spanish ASA 61 D English ASA 70 E English RAL 703 F Spanish RAL 703 G Spanish Marfil (ivory) 4 H English ASA 70 (light gray) J English RAL 703 K Spanish Marfil (ivory) 4 L Spanish RAL 8001 M Spanish RAL 1004 N Spanish RAL 703 P English Special color Q English Special color R Spanish Special color S Spanish Special color T Configuration example Outdoor vacuum circuit-breaker, dead tank S D V 6 (U r = 38 kv, I sc = 40 ka, I r = 000 A) K A Language: Spanish; frequency: 60 Hz; color: RAL 1004 N Example for Order No.: S D V K A N Order codes: Siemens HG

24 Equipment Selection Selection of secondary equipment, dead tank Outdoor Vacuum Circuit-Breakers 3AF0 / 3AG0 / SDV6 15 th /16 th position Position: Ordercodes Enclosure material and low-voltage part Order No.: S D V 6 Enclosure Roof construction Low-voltage part Steel Stainless steel Steel Stainless steel 3 earthing terminals for lightning protection earthing terminals connected with the enclosure earthing Operation panel Connection panel A 0 B 0 C 0 D 0 E 0 F 0 G 0 H 0 J 0 A 1 B 1 C 1 D 1 E 1 F 1 G 1 H 1 J 1 A B C D E F G H J Configuration example Outdoor vacuum circuit-breaker, dead tank S D V 6 Rated voltage U r = 38 kv Rated short-circuit breaking current I sc = 40 ka Rated normal current I r = 000 A 6 4 Release combination: Closing solenoid and 1 st shunt release 1 Operating voltage of the 1 st shunt release 15 V AC K Without nd shunt release (8 th position = 1) A Operating voltage of the closing solenoid 15 V AC 7 Operating voltage of the motor mechanism 15 V AC 7 Auxiliary switch 6 NO + 6 NC and 64-pole plug connector 1 Language: Spanish; frequency: 60 Hz; color: RAL 1004 N Enclosure made of steel, roof made of stainless steel, 3 earthing terminals for lightning protection, connection panel E Example for Order No.: S D V K A N E Order codes: 4 Siemens HG

25 Equipment Selection Accessories and spare parts Retrofitting When releases/solenoids are retrofitted, the order numbers of the mounting parts must also be specified. For other additional equipment, the required mounting parts are included in the delivery. Spare parts When releases/solenoids are required as spare parts, the order number and the type of construction of the associated circuit-breaker type must also be specified. Remark for orders The order numbers are applicable to outdoor vacuum circuitbreakers of current manufacture. When mounting parts or spare parts are being ordered for an existing circuitbreaker, always quote the type designation, serial number, design code and the year of manufacture of the circuit-breaker to be sure to get the correct delivery. Accessories for the plug connector Included in the scope of supply of the basic equipment for outdoor vacuum circuit-breakers: For 4-pole plug connector Lower part of plug Crimp sockets according to number of contacts Upper part of plug with screwed contacts (no crimp sockets required) For 64-pole plug connector Lower part of plug Upper part of plug Crimp sockets according to number of contacts Vacuum interrupters and other spare parts must only be replaced by instructed personnel. Designation Remarks Operating voltage Order No. Lubricant 3AX AY Operating solenoid Used as closing solenoid or 4 V DC 3AY BY 1 st shunt release 30 V DC 3AY MY 110 V DC 3AY EY 0 V DC 3AY FY nd shunt release Without varistor, without rectifier 4 3 V DC 3AX11 01-BY Includingvaristor 48 60VDC 3AX11 01-CY V DC 3AX11 01-EY 0 40 V DC 3AX11 01-FY Including varistor and rectifier V AC, 50 Hz 3AX11 01-JY Current-transformer For rated normal current 0.5 A, operated release including varistor and rectifier 3AX11 0-AY Drive motor (500 W) 110 V DC 3AY EY 0 V DC 3AY FY (700 W) 110 V DC 3AY EY 0 V DC 3AY FY Rectifier component V AC, 50 Hz 3AY15 5-1FY Auxiliary switch (-S1) 5NO+ 5NC 3SV91-AY 6NO+ 6NC 3SV973-AY 11NO+11NC 3SV9-AY 1NO+1NC 3SV974-AY Auxiliary contactor NO+ NC 3TH30-0BB4 4 V DC 3TH30-0BC4 30 V DC 3TH30-0BF4 110 V DC 3TH30-0BM4 0 V DC Position switch Type 3SE406 (as spare part), without installation accessories Used for: Nos. Electrical anti-pumping (-S3) 1 Motor control (-S1, -S) Closing spring charged (-S4) 1 Siemens HG

26 Equipment Selection Accessories and spare parts Outdoor Vacuum Circuit-Breakers 3AF0 / 3AG0 / SDV6 Designation Remarks Operating voltage Order No. M.c.b. 5SX4 0-7 A, two-pole, 40 V AC, 50 Hz A 5SQ107YA0 5SX A, two-pole, 40 V AC, 50 Hz 4A 5SQ107YA04 5SX A, two-pole, 40 V AC, 50 Hz 6A 5SQ107YA06 Heating 100 W, 40 V AC, 50 Hz Local-remote switch (S13) Handle Hand crank to charge the spring Retaining elements Set of lock washers 3AY AY Circuit-breaker control switch (S14) Data on the nameplate "Leistungsschild wird neu gezeichnet" Note: For any request regarding spare parts, subsequent deliveries, etc. the following details are necessary: Type designation Serial No. Design code Year of manufacture 6 Siemens HG

27 Technical Data Contents Contents Technical Data Electrical data, dimensions and weights, live tank: Voltage level 1 kv Voltage level 17.5 kv Voltage level 36 kv Operating cycles Dimension drawings Page SDV6 outdoor vacuum circuit-breaker, porcelain bushings R-HG11-XXX.tif Electrical data, dimensions and weights, dead tank: Voltage level 15.5 kv 30 Voltage level 7.6 kv 30 Voltage level 38 kv 30 Operating cycles 31 Dimension drawings 31 Operating times 3 3 XXXXX R-HG11-XXX.tif Siemens HG

28 Technical Data Electrical data, dimensions and weights, live tank Outdoor Vacuum Circuit-Breakers 3AF0 / 3AG0 / SDV6 1 kv 50/60 Hz Order No. Rated normal current Pole-center distance Rated operating sequence: O-3min-CO-3min-CO O-0.3s-CO-3min-CO O-0.3s-CO-15s-CO Rated duration of short-circuit Rated short-circuit breaking current DC component in % of the rated short-circuit breaking current Asymmetrical breaking current Rated short-circuit making current (at 50/60 Hz) Rated lightning impulse withstand voltage Rated short-duration power-frequency withstand voltage Voltage drop ΔU between connections Minimum creepage distance, interrupter Minimum creepage distance, phase-to-earth Minimum clearance, phase-to-phase Minimum clearance, phase-to-earth Weights Detailed dimension drawing (can be ordered) Operating cycle diagram no. (see page 9) Catalog dimension drawing no. (see page 9) I r t k I sc I ma U p U d A mm s ka % ka ka kv kv mv mm mm mm mm kg 3AG / kv 50/60 Hz I r t k I sc I ma U p U d A mm s ka % ka ka kv kv mv mm mm mm mm kg 3AF / AF / kv 50/60 Hz I r t k I sc I ma U p U d A mm s ka % ka ka kv kv mv mm mm mm mm kg 3AF / AF / AF / AF / M Standard according to IEC Possible Fehlende Werte müssen noch ergänzt werden 8 Siemens HG

29 Technical Data Electrical data, dimensions and weights, live tank Operating cycle diagrams 3AF0/3AG0 Operating cycles ka 100 Breaking current (r.m.s. value) HG11-65_en eps The permissible number of electrical operating cycles is shown as a function of the breaking current (r.m.s. value). All vacuum circuit-breakers fulfil the endurance classes E, M and C according to IEC The curve shape beyond the parameters defined in IEC is based on average experience data. The number of operating cycles that can actually be reached can be different depending on the respective application. Operating cycles ka 100 Breaking current (r.m.s.value) HG11-651_en eps Dimension drawings 3AF0/3AG Maßbild 1 Maßbild M16 (8x) M16 x HG eps M16 (8x) M16 x HG11-650a eps Dimension drawing 1 Dimension drawing Siemens HG

30 Technical Data Electrical data, dimensions and weights, dead tank Outdoor Vacuum Circuit-Breakers 3AF0 / 3AG0 / SDV kv 50/60 Hz Order No. Rated normal current Pole-center distance Rated operating sequence: O-3min-CO-3min-CO O-15s-CO Rated duration of short-circuit Rated short-circuit breaking current DC component in % of the rated short-circuit breaking current Asymmetrical breaking current Rated short-circuit making current (at 50/60 Hz) Rated lightning impulse withstand voltage Rated short-duration power-frequency withstand voltage Voltage drop ΔU between connections Minimum creepage distance, interrupter Minimum creepage distance, phase-to-earth Minimum clearance, phase-to-phase Minimum clearance, phase-to-earth Weights Detailed dimension drawing (can be ordered) Operating cycle diagram no. (see page 31) Catalog dimension drawing no. (see page 31) I r t k I sc I ma U p U d A mm s ka % ka ka kv kv mv mm mm mm mm kg 3 SDV SDV SDV SDV SDV SDV SDV SDV SDV SDV kv 50/60 Hz I r t k I sc I ma U p U d A mm s ka % ka ka kv kv mv mm mm mm mm kg fehlende Daten müssen ergänzt werden fehlende Daten müssen ergänzt werden SDV SDV SDV SDV fehlende Daten müssen ergänzt werden fehlende Daten müssen ergänzt werden 38 kv 50/60 Hz I r t k I sc I ma U p U d A mm s ka % ka ka kv kv mv mm mm mm mm kg SDV SDV SDV SDV SDV SDV SDV SDV fehlende Daten müssen ergänzt werden fehlende Daten müssen ergänzt werden Standard according to IEC Possible 30 Siemens HG

31 Technical Data Electrical data, dimensions and weights, dead tank Operating cycle diagrams SDV6 Operating cycles Operating cycles ka 100 Breaking current (r.m.s. value) HG11-653_en eps ka 100 Breaking current (r.m.s.value) HG11-654_en eps Operating cycles ka Breaking current (r.m.s.value) HG11-655_en eps The permissible number of electrical operating cycles is shown as a function of the breaking current (r.m.s. value). All vacuum circuit-breakers fulfil the endurance classes E, M and C according to IEC The curve shape beyond the parameters defined in IEC is based on average experience data. The number of operating cycles that can actually be reached can be different depending on the respective application. 3 Dimension drawings SDV6 A B D (1135.1) (6.3) Dimension drawing no. A B C D J max (4010.7) Values in brackets for 38 kv C (1816.1) J (161.9) HG11-656_en eps Siemens HG

32 Technical Data Operating times Outdoor Vacuum Circuit-Breakers 3AF0 / 3AG0 / SDV6 Operating times Operating times at rated voltage of the secondary circuit Equipment of circuit-breaker Operating time of circuit-breaker 3AF0 3AG0 Closing time w 75 ms w 75 ms Opening time 1 st shunt release w 65 ms w 65 ms nd shunt release w 50 ms w 50 ms Arcingtime <15ms <15ms Break time 1 st shunt release w 80 ms w 80 ms nd shunt release w 65 ms w 65 ms Dead time 300 ms 300 ms CLOSE/OPEN contact time 1 st shunt release w 90 ms w 90 ms nd shunt release w 90 ms w 75 ms Minimum command duration Closing solenoid 40 ms 60 ms 1 st shunt release 40 ms 60 ms Additional releases 0 ms 0 ms Charging time for electrical operation w 15 s w 15 s Synchronism error between the poles w ms w ms 3 3 Siemens HG

33 Annex Contents Contents Annex Page 33 Inquiry form Configuration instructions Configuration aid Foldout page Brandenburg Gate, Berlin, Germany R-HG tif 4 Switchgear Factory in Berlin, Germany R-HG eps Siemens HG

34 Annex Inquiry form Outdoor Vacuum Circuit-Breakers 3AF0 / 3AG0 / SDV6 Please copy, fill in and return to your Siemens partner or you can use our prompted online configurator under Inquiry concerning Live tank Dead tank Technical data Other values Rated voltage, live tank 1 kv 17.5 kv 36 kv kv Rated voltage, dead tank 15.5 kv 7.6 kv 38 kv kv Rated lightning impulse withstand voltage 75 kv 150 kv 95 kv 170 kv 110 kv 00 kv kv Please Submit an offer Call us Visit us Rated short-duration power-frequency withstand voltage Rated short-circuit breaking current 8 kv 50 kv 80 kv 0 ka 31.5 ka 38 kv 60 kv 95 kv 5 ka 40 ka 4 kv 70 kv kv ka Rated normal current 100 A 000 A 150 A (IEC) 3000 A 1600 A A Your address Company Dept. Name Street Secondary equipment Possible combinations Motor operating mechanism VDC VAC, Hz Closing solenoid VDC VAC, Hz 1 st shunt release VDC VAC, Hz nd shunt release VDC VAC, Hz Postal code/city Current-transformer operated release 0.5 A 1A W 0.1 Ws (10 c) W 0.1 Ws (0 c) Phone Fax Undervoltage release VDC VAC, Hz Without energy store With energy store Auxiliary switch 6NO+6NC 1NO+1NC Low-voltage connection 4-pole terminal strip 4-pole plug 64-pole plug 4 Siemens AG Dept. Name Circuit-breaker tripping signal Operating instructions in English Spanish Application and other requirements Street Postal code/city Fax Please check off _ Please fill in 34 Siemens HG

35 You prefer to configure your 3AF0/3AG0/SDV6 outdoor vacuum circuit-breaker on your own? Please follow the steps for configuration and enter the order number in the configuration aid. Alternatively you can also use your prompted online configurator under For configuration of your 3AF0/3AG0/SDV6 outdoor vacuum circuit-breakers Instruction for configuration of the 3AF0/3AG0/SDV6 outdoor vacuum circuit-breaker Z 1 st step: Definition of the primary part Please specify the following ratings: Possible options: Rated voltage (U r ) U r : 1kVto38kV Rated lightning impulse withstand voltage (U p ) U p : 75 kv to 00 kv Rated short-duration power-frequency withstand voltage (U d ) U d : 8kVto95kV Rated short-circuit breaking current (I sc ) I sc : 0kAto40kA Rated short-circuit making current (I ma ) I ma : 4 ka to 104 ka Rated normal current (I r ) I r : 100 A to 3000 A These ratings define the positions 4 to 7 of the order number nd step: Definition of the secondary equipment, live tank Please specify the following equipment features: Possible options: Type of local closing (position 8) Operating voltage of the motor operating mechanism (position 9) Release combination (position 10) Operating voltage of the closing solenoid and 1 st shunt release (position 11) Operating voltage of the nd release (position 1) Number of auxiliary contacts (position 13/14) Circuit-breaker tripping signal Frequency of operating voltage (position 15/16) These equipment features define the positions 8 to 16 of the order number. Manual mechanical closing Manual electrical closing Operating voltages from 4 V DC to 40 V AC Shunt release, current-transformer operated release and undervoltage release Operating voltages from 4 V DC to 40 V AC Operating voltages from 4 V DC to 40 V AC 6NO+6NC,1NO+1NC With or without 50 Hz/60 Hz rd step: Do you have any further requirements concerning the equipment? Should you still need more options than the possible special equipment like closing with a lock, additional heaters, fixings for current and voltage transformers, etc., please contact your responsible sales partner Siemens HG

36 If not stated otherwise on the individual pages of this catalog, we reserve the right to include modifications, especially regarding the stated values, dimensions and weights. Drawings are not binding. All product designations used are trademarks or product names of Siemens AG or other suppliers. If not stated otherwise, all dimensions in this catalog are given in mm. Siemens AG Energy Sector Medium Voltage Division Nonnendammallee Berlin Germany For questions concerning Power Transmission and Distribution: You can contact our Customer Support Center 4 hours a day, 365 days a year. Tel.: / Fax: / (Charges depending on provider) support.energy@siemens.com Subject to change without notice Order No. E50001-K1511-A411-A Printed in Germany Dispo KG En /6508 Responsible for Technical contents: Siemens AG, Dept. PTD M C PPM Berlin General editing: Siemens AG, Dept. PTD CC M Erlangen The information in this document contains general descriptions of the technical options available, which do not always have to be present in individual cases. The required features should therefore be specified in each individual case at the time of closing the contract. R-HG11-18.tif

3AH5 Vacuum Circuit-Breakers. Answers for energy. Medium-Voltage Equipment Selection and Ordering Data. Catalog HG 11.05 2010

3AH5 Vacuum Circuit-Breakers. Answers for energy. Medium-Voltage Equipment Selection and Ordering Data. Catalog HG 11.05 2010 Medium-Voltage Equipment Selection and Ordering Data Catalog HG 11.05 2010 Answers for energy. R-HG11-172.tif 2 Siemens HG 11.05 2010 Contents Contents Page 3AH5 Vacuum Circuit-Breakers Medium-Voltage

More information

High-Voltage Circuit-Breakers 3AP1/2 72.5 kv up to 550 kv. Power Transmission and Distribution

High-Voltage Circuit-Breakers 3AP1/2 72.5 kv up to 550 kv. Power Transmission and Distribution High-Voltage Circuit-Breakers AP/ 7.5 kv up to 550 kv Power Transmission and Distribution The AP/ High-Voltage Circuit-Breakers Now Applicable for 550 kv Decades of our experience in high-voltage switching

More information

Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms

Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms ABB innovations for changing demands ABB (www.abb.com) is a leader in power and automation technologies that enables utility

More information

www.siemens.com/energy High Voltage Circuit Breakers 3AP Type 72.5 kv to 800 kv Answers for energy.

www.siemens.com/energy High Voltage Circuit Breakers 3AP Type 72.5 kv to 800 kv Answers for energy. s www.siemens.com/energy High Voltage Circuit Breakers AP Type 7.5 kv to 800 kv Answers for energy. The AP High Voltage Circuit Breakers Available up to 800 kv Decades of our experience in high voltage

More information

High-Voltage Compact Switchgear 3AP1 DTC for 145 kv and 245 kv

High-Voltage Compact Switchgear 3AP1 DTC for 145 kv and 245 kv High-Voltage Compact Switchgear AP1 DTC for 1 kv and kv Answers for energy. The AP1 DTC Complying with our Customers demands Experience you can rely on - at anytime, anywhere Decades of experience in high-voltage

More information

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4 CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,

More information

NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems. Safe energy distribution that meets the highest industrial requirements

NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems. Safe energy distribution that meets the highest industrial requirements NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems Safe energy distribution that meets the highest industrial requirements NATUS switchgear systems your advantages minimal use of insulant

More information

PRODUCT GUIDE. SL Medium Voltage IEC Vacuum Contactors

PRODUCT GUIDE. SL Medium Voltage IEC Vacuum Contactors PRODUCT GUIDE SL Medium Voltage IEC Vacuum Contactors Table of Contents 1 Overview Introduction....................................................2 Features........................................................2

More information

Outdoor vacuum circuit-breakers and reclosers for medium voltage. Switching technology for distribution networks. Answers for energy.

Outdoor vacuum circuit-breakers and reclosers for medium voltage. Switching technology for distribution networks. Answers for energy. Outdoor vacuum circuit-breakers and reclosers for medium voltage Switching technology for distribution networks Answers for energy. Reliable quality for all your medium-voltage network needs Quality from

More information

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. 2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to

More information

7.2KV SL400 Withdrawable Vacuum Contactor-Fuse Combination Units

7.2KV SL400 Withdrawable Vacuum Contactor-Fuse Combination Units Automotive Powering business worldwide Aerospace Eaton delivers the hundreds of power distribution products that are answering the demands of today s fast changing world. We help our customers worldwide

More information

ELEKTROTEHNI KO PODJETJE Leskoπkova cesta 12, 1000 Ljubljana, SLOVENIA

ELEKTROTEHNI KO PODJETJE Leskoπkova cesta 12, 1000 Ljubljana, SLOVENIA MRO Modularne Razdelilne Omare d.o.o. ELEKTROTEHNI KO PODJETJE Leskoπkova cesta 2, 000 Ljubljana, LOVENIA MC GENERAL When to use? MC - modular switchgear cabinets are type-tested, factory built switchgears,

More information

SF 6 Gas Insulated Switchgear Type SDF for 170 kv

SF 6 Gas Insulated Switchgear Type SDF for 170 kv Three Phase Encapsulated Type SF 6 Gas Insulated Switchgear Type SDF for 170 kv 06B1-E-0001 With Trustworthy Technology, Structure Fuji Electric as a manufacturer of comprehensive substation equipment

More information

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

Submit shop drawings for equipment provided under this section Shop drawings shall indicate: Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,

More information

26 3213.13 Diesel Engine Driven Generators Page 1 of 6

26 3213.13 Diesel Engine Driven Generators Page 1 of 6 Last Update: December 8, 2014 A. Description of System Consultant s Handbook Page 1 of 6 1. Provide a diesel engine driven electric generating unit, factory assembled, tested and certified to operate at

More information

Our brand POWER DYNAMIC PASSION COMMITMENT CREATIVITY. A strong brand for strong products: 8PU Premium. MV Energy

Our brand POWER DYNAMIC PASSION COMMITMENT CREATIVITY. A strong brand for strong products: 8PU Premium. MV Energy Our brand A strong brand for strong products: The ENERGOLINE brand represents our product portfolio of INDUSTRIAL SWITCHGEAR SYSTEMS. Our products are characterized by a high degree of safety, flexibility

More information

UniGear ZS1. Medium voltage, arc proof, air insulated switchgear for primary distribution

UniGear ZS1. Medium voltage, arc proof, air insulated switchgear for primary distribution UniGear ZS1 Medium voltage, arc proof, air insulated switchgear for primary distribution UniGear ZS1: an innovative solution for all installation requirements ABB UniGear is medium voltage metal-clad,

More information

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132

More information

Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated. Ordering information

Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated. Ordering information Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated Ordering information Connection technique Description Description Rated operational current Screw terminals 3 pole AC

More information

5SV Residual Current Protective Devices

5SV Residual Current Protective Devices s Siemens AG 2013 SENTRON 5SV Residual Current Protective Devices New portfolio for reliable personnel, material and fire protection Safe protection against residual currents Residual current protective

More information

CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH

CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH Cat transfer switches are designed for a variety of standby power applications. They provide flexibility, reliability and value in a

More information

Electronic overload relay EF65, EF96 and EF146

Electronic overload relay EF65, EF96 and EF146 Data sheet Electronic overload relay EF65, EF96 and EF146 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays.

More information

Siemens AG Power Transmission and Distribution Medium Voltage Division Mozartstr. 31c 91052 Erlangen Germany. www.siemens.

Siemens AG Power Transmission and Distribution Medium Voltage Division Mozartstr. 31c 91052 Erlangen Germany. www.siemens. Siemens AG Power Transmission and Distribution Medium Voltage Division Mozartstr. 31c 91052 Erlangen Germany www.siemens.com/energy For questions on power transmission and distribution, please contact

More information

Electronic overload relay EF19 and EF45

Electronic overload relay EF19 and EF45 Data sheet Electronic overload relay EF19 and EF45 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays. Motor

More information

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous Safety relay for monitoring E-STOP pushbuttons. Approvals Unit features Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous 1 auxiliary contact (N/C), instantaneous Safe separation of

More information

3TL Vacuum Contactors Selection and Ordering Data. www.siemens.com/3tl. Medium-Voltage Equipment Catalog HG 11.21 2014

3TL Vacuum Contactors Selection and Ordering Data. www.siemens.com/3tl. Medium-Voltage Equipment Catalog HG 11.21 2014 www.siemens.com/3tl 3TL Vacuum Contactors Selection and Ordering Data Medium-Voltage Equipment Catalog HG 11.21 2014 Answers for infrastructure and cities. R-HG11-343.psd 2 Siemens HG 11.21 2014 Contents

More information

Siemens Fusesaver. Highest availability and cost savings for your MV distribution network. www.siemens.com/fusesaver

Siemens Fusesaver. Highest availability and cost savings for your MV distribution network. www.siemens.com/fusesaver www.siemens.com/fusesaver Siemens Fusesaver Highest availability and cost savings for your MV distribution network Answers for infrastructure and cities. 2 In high demand: An intelligent solution Improving

More information

Tmax MCCBs. Molded case circuit breakers. Tmax

Tmax MCCBs. Molded case circuit breakers. Tmax Molded case circuit breakers Introduction ABB is once again demonstrating its commitment to new product development and its superiority in product performance. Never before has the industry seen such high

More information

Voltage Regulator SPAU 341 C. Product Guide

Voltage Regulator SPAU 341 C. Product Guide Issued: July 1998 Status: Updated Version: D/25.04.2006 Data subject to change without notice Features Comprehensive voltage regulation for power transformers with on-load tapchangers in distribution substations

More information

E-STOP relays, safety gate monitors

E-STOP relays, safety gate monitors Unit features Safety features Gertebild ][Bildunterschrift_NOT_Sch.tuer_Licht Safety relay for monitoring E-STOP pushbuttons, safety gates and light beam devices Approvals Gertemerkmale Positive-guided

More information

Thyristor-controlled power supplies and battery chargers

Thyristor-controlled power supplies and battery chargers Thyristor-controlled power supplies and battery chargers Input voltage: 115 / 230 VAC, single phase, 50 / 60 Hz or 208 / 400 / 480 VAC, three phases, 50 / 60 Hz Output voltage: 12 / 24 / 48 / 60 / 72 /

More information

VD4. Vacuum circuit-breaker

VD4. Vacuum circuit-breaker VD4 Vacuum circuit-breaker VD4. The economical solution in power distribution. Applications: Power stations Transformer stations Chemicals industry Steel industry Automotive industry Airport power supply

More information

METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV. tgood.com. Energy. Fast.

METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV. tgood.com. Energy. Fast. METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV tgood.com Energy. Fast. TGOOD produces over 5000 switchgear units annually for projects around the globe PRODUCT OVERVIEW Integral substation component

More information

AutoLink Three-Phase Sectionalizer Specifications. Scope. General. Applicable Standards. Operating principle

AutoLink Three-Phase Sectionalizer Specifications. Scope. General. Applicable Standards. Operating principle Scope This specification stipulates the minimum requirements for mechanically linked three-phase electronic sectionalizers, for use on outdoor medium voltage overhead lines of 15, 27, and 38 kv. Electronic

More information

Medium voltage indoor circuit breakers ANSI/IEC solutions

Medium voltage indoor circuit breakers ANSI/IEC solutions Medium voltage indoor circuit breakers ANSI/ solutions Table of contents Introduction... 3 Vmax/A... 4 ADVAC... 6 AMVAC... 8 Vmax... 10 VD4... 12 VM1... 16 HD4... 19 V-Contact VSC... 22 2 Medium voltage

More information

Voltage Rated operating voltage [kv] 12 24 Rated power frequency withstand voltage [kv] 28 50 Rated lightning impulse withstand voltage [kv] 75 125

Voltage Rated operating voltage [kv] 12 24 Rated power frequency withstand voltage [kv] 28 50 Rated lightning impulse withstand voltage [kv] 75 125 Standards and Regulations IEC 62271-200 ; VDE 0671-200 ; BS EN 62271-200 Technical Data MC3-12 MC3-24 Voltage Rated operating voltage [kv] 12 24 Rated power frequency withstand voltage [kv] 28 50 Rated

More information

Circuit Breakers. NRC Series. NRC Series. 900 www.idec.com

Circuit Breakers. NRC Series. NRC Series. 900 www.idec.com Switches & Pilot Lights Display Lights NRC series circuit breakers offer circuit protection which is far superior to using fuses in applications containing relay circuits, motor circuits, heater circuits,

More information

RY2 miniature industrial relays

RY2 miniature industrial relays 6 RY2 Relays of general application For plug-in sockets, 35 mm rail mount acc. to PN-EN 60715 or on panel mounting Flat insert connectors - faston x 0,5 mm Recognitions, certifications, directives: RoHS,

More information

R.C.C.B. s two-pole LEXIC

R.C.C.B. s two-pole LEXIC 87045 LIMOGES Cedex Telephone : (+33) 05 55 06 87 87 Fax : (+ 33) 05 55 06 88 88 R.C.C.B. s two-pole LEXIC 089 06/09/10/11/12/15/16/17/18/ 27/28/29/30/35, CONTENTS PAGES 1. Electrical and mechanical characteristics...

More information

Low Voltage Products. Switches Automatic Transfer Switches

Low Voltage Products. Switches Automatic Transfer Switches Low Voltage Products Switches Automatic Transfer Switches Growing importance of a secure power supply Standby power is an integral part of many industrial and domestic electrical systems. High energy prices,

More information

Circuit Breakers. Next Generation of Protection Capabilities

Circuit Breakers. Next Generation of Protection Capabilities Circuit Breakers Next Generation of Protection Capabilities Circuit Breaker Offering Rockwell Automation offers a full line of Allen-Bradley circuit breakers and motor protection devices to help meet many

More information

3RT1015-1BB41 CONTACTOR, AC-3 3 KW/400 V,

3RT1015-1BB41 CONTACTOR, AC-3 3 KW/400 V, Automation Technology > Industrial Controls > Switching Devices > Contactors and Contactor Assemblies > Power Contactors for Switching Motors > Contactors SIRIUS 3RT10, 3-pole, 3... 250 kw 3RT1015-1BB41

More information

Medium Voltage Products. ZN1 12 kv arc-proof air-insulated switchgear for primary distribution

Medium Voltage Products. ZN1 12 kv arc-proof air-insulated switchgear for primary distribution Medium Voltage Products ZN1 12 kv arc-proof air-insulated switchgear for primary distribution ZN1 an innovative switchgear for power distribution requirements ABB ZN1 primary distribution switchgear is

More information

Specification Guide. for RVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers

Specification Guide. for RVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers Specification Guide for RVAC Direct Replacement AC Medium Voltage Circuit Breakers Table of Contents 1.0 General Work Scope...3 2.0 Standards...3 3.0 Supplier Qualifications...4 4.0 Circuit Breaker Element

More information

The Intelligent AX1 Switchgear for Medium Voltage

The Intelligent AX1 Switchgear for Medium Voltage The Intelligent AX1 Switchgear for Medium Voltage Leif Lundin, Manager of Research and Development, Division Medium Voltage and Compact Substations, ABB Distribution, Sweden Abstract The newly launched

More information

AUTOMATIC TRANSFER SWITCH. Changeover Type from 250A to 2500A

AUTOMATIC TRANSFER SWITCH. Changeover Type from 250A to 2500A AUTOMATIC TRANSFER SWITCH Changeover Type from 250A to 2500A Table of Contents Preamble 1.1 Theoretical base 1.2 Selection the size of automatic transfer switch 1.3 Automatic transfer switch components

More information

Bimetallic Overload Relay Specifications

Bimetallic Overload Relay Specifications Technical Data Bimetallic Overload Relay Specifications Bulletin Number 193K, 193T1 Topic Page Product Overview 2 Standards compliance and Certifications 2 General Specifications 193K 3 Approximate Dimensions

More information

PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES

PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES BUSHING WITH PLUG CONNECTION WITH OUTER CONE PPS CHARACTERISTICS The PPS bushing can be used as a fixed section for the entry of medium

More information

Pluggable interface relays CR-P Pcb relays

Pluggable interface relays CR-P Pcb relays 2CDC 293 034 F0004 1 2 4 3 Features 9 different supply s: DC versions: 12 V, 24 V, 48 V, 110 V AC versions: 24 V, 48 V, 110 V, 120 V, 230 V Output contacts: 1 c/o (16 A) or 2 c/o (8 A) Cadmium-free contact

More information

SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches

SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches PART 1 GENERAL 1.01 Scope Optional Standby Power Generator Systems A. Furnish and install automatic transfer switches

More information

3K Load-Break Switches The Program for Safety and Performance. sentric

3K Load-Break Switches The Program for Safety and Performance. sentric 3K Load-Break Switches The Program for Safety and Performance sentric Whether for reliable switching and isolation under load, or for protection against overload or short-circuits our 3K range of load-break

More information

SIRCOVER. Manual changeover switches from 125 to 3200 A. Changeover switches. Function. Advantages. The solution for.

SIRCOVER. Manual changeover switches from 125 to 3200 A. Changeover switches. Function. Advantages. The solution for. The solution for Changeover switches svr_099_b_1_cat > Manufacturing industry. > Power distribution. 3200 Strong points svr_059_a_1_cat > complete range. > Easy connections. > Stable positions. > mproved

More information

Current and voltage measuring relays

Current and voltage measuring relays Current and voltage measuring relays RXIK 1, RXEEB 1 and Page 1 Issued June 1999 Changed since July 1998 Data subject to change without notice RXIK 1 RXEEB 1 (SE980082) (SE980081) (SE970869) Features Application

More information

Short Range Wireless Switch System Handheld 8 Installation and Operations Guide

Short Range Wireless Switch System Handheld 8 Installation and Operations Guide Phone: (866) 701-1146 Fax: (425) 216-7558 www.remotecontroltech.com Short Range Wireless Switch System Handheld 8 Installation and Operations Guide Introduction... 2 Before Installation... 2 Receiver Installation...

More information

Unified requirements for systems with voltages above 1 kv up to 15 kv

Unified requirements for systems with voltages above 1 kv up to 15 kv (1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to

More information

Data Sheet. Electro-mechanical counters Hengstler 800 series

Data Sheet. Electro-mechanical counters Hengstler 800 series Data Pack D Issued March 00 504897 Data Sheet Electro-mechanical counters Hengstler 800 series The 800 series totalising and predetermining batch counters, manufactured by Hengstler, is available from

More information

MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS

MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS Meher Capacitors offers reliable and innovative products and solutions in the fields of Reactive Power Compensation, Power Quality and Energy

More information

Secondary Unit Substations

Secondary Unit Substations 14 SWITCHGEAR Secondary Unit Substations Overview Siemens offers a wide variety of unit substation designs to meet customer requirements. A unit substation consists of one or more transformers mechanically

More information

BETA Switching. Switching Devices. 5TT5 8 Insta contactors, AC technology. Overview

BETA Switching. Switching Devices. 5TT5 8 Insta contactors, AC technology. Overview BETA Switching Siemens AG 200 5TT5 Insta contactors, AC technology Overview The 5TT5 Insta contactors are equipped with an AC magnetic system and are ideal for use under harsh conditions. The auxiliary

More information

49 Series - Relay interface modules 8-10 - 16 A. Features

49 Series - Relay interface modules 8-10 - 16 A. Features Features 1 & 2 Pole relay interface modules 5 µm Gold plate contacts for low level switching capability 49.31-50x0-1 Pole 10 A (screw terminal) 49.52-50x0-2 Pole 8 A (screw terminal) 49.72-50x0-2 Pole

More information

SENTRON Switching and Protection Devices Air Circuit Breakers

SENTRON Switching and Protection Devices Air Circuit Breakers Siemens AG 9 SENTRON Switching and rotection Devices Air Circuit reakers 5 5/ Introduction 3WL Air Circuit reakers 3WL Air Circuit reakers/ Non-Automatic Air Circuit reakers up to 63 A (AC) 5/6 General

More information

TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY

TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY 2 TRACTION NETWORK MONITORING AND PROTECTION SYSTEM Traction network monitoring and protection system,

More information

Example of use: Fuse for a solenoid valve. If the fuse is defective, no information is sent to the electronic component.

Example of use: Fuse for a solenoid valve. If the fuse is defective, no information is sent to the electronic component. Overview Switch and button modules The dimensions of the switch and button modules are adapted to the electronic components in the integral housing. The modules are equipped with the universal clip-on

More information

Manual Motor Starter MS 116 up to 16 A Technical Data

Manual Motor Starter MS 116 up to 16 A Technical Data Manual Motor Starter MS 116 up to 16 A Technical Data Type MS 116 Standards: Major International IEC 60 947-4-1 / IEC 60 947-2 and European Standards EN 60 947-4-1 / EN 60 947-2 Approvals, Certificates

More information

DS 600. A contact free flux gate based current measurement sensor 600A rms

DS 600. A contact free flux gate based current measurement sensor 600A rms DS 600 A contact free flux gate based current measurement sensor 600A rms DS 600 is member of the small housing sensor family. The family includes a 200A and a 600A version. 600A rms - 900A peak Maximum

More information

Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start 0225592. * see variants. Applications.

Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start 0225592. * see variants. Applications. Safety Technique SAFEMASTER Emergency Stop Module BG 5924, IP 5924 Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start 0225592 BG 5924 IP 5924 Product Description

More information

Remote Monitoring and REC 501 Control Unit Product Guide

Remote Monitoring and REC 501 Control Unit Product Guide Remote Monitoring and Control Unit REC 501 Product Guide Issued: May 1999 Status: Updated Version: B/06.11.2001 Data subject to change without notice Features Remote control and monitoring unit for the

More information

Relays High Capacity 50 Amp Mini Relays Standard Mini Relays Micro Relays Power Relays Connector Modules

Relays High Capacity 50 Amp Mini Relays Standard Mini Relays Micro Relays Power Relays Connector Modules CHIEF EN TERPRISES INC. M a s t e r I n t e r n a t i o n a l D i s t r i b u t o r Relays High Capacity 50 Amp Mini Relays Standard Mini Relays Micro Relays Power Relays Connector Modules M AS TER IN

More information

SURGE PROTECTIVE DEVICES

SURGE PROTECTIVE DEVICES SURGE PROTECTIVE DEVICES 1. INTRODUCTION In order to ensure safety of people, protection of equipment and, to a certain extent, continuity of supply, insulation co-ordination aims at reducing the likelihood

More information

E-STOP relays, safety gate monitors

E-STOP relays, safety gate monitors Unit features Safety features gang engertebild ][Bildunterschrift_NOT_Sch.tuer_Licht Safety relay for monitoring E-STOP pushbuttons, safety gates and light beam devices Approvals Gertemerkmale Positive-guided

More information

HERZ-Thermal Actuators

HERZ-Thermal Actuators HERZ-Thermal Actuators Data Sheet 7708-7990, Issue 1011 Dimensions in mm 1 7710 00 1 7710 01 1 7711 18 1 7710 80 1 7710 81 1 7711 80 1 7711 81 1 7990 00 1 7980 00 1 7708 11 1 7708 10 1 7708 23 1 7709 01

More information

Technicaldata General

Technicaldata General Currenttransformer-operatedoverloadrelay,60-90A,1N/O+1N/C Partno. ZW7-90 Articleno. 002618 CatalogNo. XTOT090C3S Deliveryprogramme Product range ZW7 current transformer-operated overload relays Description

More information

Mini Motor Contactor J7KNA Main contactor Accessories Approved Standards Standard Guide No (US,C) Ordering Information tage Model Number Legend gear

Mini Motor Contactor J7KNA Main contactor Accessories Approved Standards Standard Guide No (US,C) Ordering Information tage Model Number Legend gear Mini Motor Contactor J7KNA ) Main contactor AC & DC operated Integrated auxiliary contacts Screw fixing and snap fitting (35 mm DIN-rail) Range from 4 to 5.5 (AC 3, 380/415V) 4 -main pole version (4 AC

More information

FAQs-Main switchboard design criteria

FAQs-Main switchboard design criteria FAQs-Main switchboard design criteria Q: What is the Australian standard for main switchboards? Current Australian standard is AS/NZS 3439.1: 2002 originating from IEC 60439. The new series of standard

More information

SICONT Limit Switches Type 3SE3 upto 500 VAC, 600 VDC, 10A

SICONT Limit Switches Type 3SE3 upto 500 VAC, 600 VDC, 10A s SICONT Limit Switches Type 3SE3 upto 500 VAC, 600 VDC, 10A Introduction The technical and descriptive information on the function, construction and selection of the new types of 3SE3 limit switches is

More information

LC/LCD ranges level controllers

LC/LCD ranges level controllers GRUNDFOS WASTEWATER LC/LCD ranges level controllers 18 Grundfos Sololifts > Grundfos LC/LCD controllers Keeping a close eye on liquid levels Reliable level controllers from Grundfos Grundfos offers a choice

More information

DRTS 33. The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters

DRTS 33. The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters Testing all relay technologies: electromechanical, solid state, numerical and IEC61850 Manual

More information

The complete range of consumer switchboards and switchgear

The complete range of consumer switchboards and switchgear Power Distribution The complete range of consumer switchboards and switchgear www.nhp.com.au/mod6 The MOD6 range of consumer switchboards and switchgear is specifically designed for domestic and commercial

More information

48.12. 2 pole, 8 A Safety relay. Screw terminal. 35 mm rail (EN 60715) mounting. 2 CO (DPDT) 8/15 250/400 2,000 500 0.37 8/0.65/0.

48.12. 2 pole, 8 A Safety relay. Screw terminal. 35 mm rail (EN 60715) mounting. 2 CO (DPDT) 8/15 250/400 2,000 500 0.37 8/0.65/0. 48 Series - Relay interface modules 8 A Features 48.12 2 Pole Safety relay interface modules, 15.8 mm wide 48.12-2 Pole 8 A (screw terminal) DC sensitive coils Relay with forcibly guided contacts according

More information

Vario-Series Accessories

Vario-Series Accessories Accessories and spare parts for GMW analogue panel meters and controllers Current Transformers pages 2-9 Shunt Resistors 10-11 Voltage Dividers 12 Power supply for indicator/controllers 13 Blanking Plates

More information

Masterclad Medium Voltage Passive Arc-Resistant Switchgear

Masterclad Medium Voltage Passive Arc-Resistant Switchgear Masterclad Medium Voltage Passive Arc-Resistant Switchgear Square D Masterclad medium voltage passive arc-resistant (AR) switchgear is designed with utilities and industrial customers in mind who demand

More information

Table of Contents. TransformerIQ FAQs 1

Table of Contents. TransformerIQ FAQs 1 [12/12] FAQs Table of Contents FAQ 1. What size transformer will TransformerIQ monitor?... 2 FAQ 2. Are there different TransformerIQ versions?... 2 FAQ 3. How are the units powered?... 2 FAQ 4. What is

More information

Series 8146/5-V37 and Series 8150/5-V37

Series 8146/5-V37 and Series 8150/5-V37 www.stahl.de > Clear assignment safe technology easy installation > Intelligent structure only one rotary actuator for frequency-controlled drives ) 20 ms leading auxiliary contact for safe motor disconnection

More information

Disconnectors and Earthing Switches 36 kv up to 800 kv

Disconnectors and Earthing Switches 36 kv up to 800 kv Power Transmission and Distribution Disconnectors and Earthing Switches 36 kv up to 800 kv Ruhrtal & Siemens: A strong and successful team We manufacture high quality high-voltage disconnectors and earthing

More information

Safety technique. Emergency stop module BO 5988 safemaster

Safety technique. Emergency stop module BO 5988 safemaster Safety technique Emergency stop module BO 5988 safemaster 0221562 Function diagram Pushbutton on Mains or emergencystop () K1 According to EC Directive for machines 98/37/EG According to IEC/E 60204-1

More information

Type: EASY719 DC RC Article No.: 274119. Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description

Type: EASY719 DC RC Article No.: 274119. Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description Type: EASY719 DC RC Article.: 274119 Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC Description 12 digital inputs (4 inputs available as analog inputs) 6 relay outputs LCD display

More information

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw 4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and

More information

WE-350 Series ¼ Turn Electric Actuator

WE-350 Series ¼ Turn Electric Actuator WE-350 Series ¼ Turn Electric Actuator Operation and Installation Manual Pg 1 (Rev. 020113) Table of Contents 1.0 General 1.1 Pre-Installation Inspection 1.2 Storage 1.3 Features & General Information

More information

E-STOP relays, safety gate monitors

E-STOP relays, safety gate monitors Gertebild ][Bildunterschrift Safety relay for monitoring E-STOP pushbuttons and safety gates. Unit features Gertemerkmale Positive-guided relay outputs: 2 safety contacts (N/O), instantaneous Connection

More information

Auxiliary Relay. Type P8n, PQ8n, PN8n

Auxiliary Relay. Type P8n, PQ8n, PN8n Auxiliary Relay Type P8n, PQ8n, PN8n ABB a global technology leader ABB is a global leader in Power and Automation technologies that enable utility and industry customers to improve performance while lowering

More information

Plug-in relays Mini ISO relays

Plug-in relays Mini ISO relays Powertrain Systems Chassis Systems Safety Security Body Driver Information Convenience Description Features Limiting continuous current 70 A Dimensional characteristics and the functional allocation of

More information

PNOZsigma - Base units

PNOZsigma - Base units PNOZsigma - Base units Register Login Sensors Control and Communication Electronic monitoring relays Safety Relays PNOZ X PNOZsigma PNOZelog PNOZmulti PNOZpower Configurable control systems Programmable

More information

8146/5 Series Breaker Panelboards

8146/5 Series Breaker Panelboards 8146/5 Series Breaker Panelboards DISTRIBUTION BREAKER PANELBOARDS FOR HAZARDOUS & CORROSIVE ENVIRONMENTS Breaker Panels Features: Wide variety of Flameproof branch circuit breakers for Zone 1 & Division

More information

48 SERIES Relay interface modules 10 A

48 SERIES Relay interface modules 10 A 48 Relay interface modules 10 A 1 CO relay interface modules, mm wide Ideal interface for PLC and electronic systems Type 48.P3 1 CO 10 A s Type 48.31 1 CO 10 A s AC coils or DC sensitive coils Supply

More information

UFES Active protection for switchgear

UFES Active protection for switchgear Active protection for switchgear ABB AG Oberhausener Strasse 4047 Ratingen, Germany Phone: +49 0-0 Fax: +49 0-7 77 Note: We reserve the right to make technical changes or modify the contents of this document

More information

Outdoor circuit breaker GVR Recloser Hawker Siddeley Switchgear. rated voltage 15, 27 and 38 kv rated current 630 A

Outdoor circuit breaker GVR Recloser Hawker Siddeley Switchgear. rated voltage 15, 27 and 38 kv rated current 630 A Outdoor circuit breaker GVR Recloser Hawker Siddeley Switchgear rated voltage 15, 27 and 38 kv rated current 630 A Outdoor circuit breakers GVR Recloser GVR switchgear brings the reliability of modern

More information

Type: DILM9 10(24VDC) Article No.: 276705

Type: DILM9 10(24VDC) Article No.: 276705 Type: DILM9 10(24VDC) Article No.: 276705 Ordering information Rated operational current AC 3 400 V I e A 9 Max. rating for three phase motors, 50 60 Hz AC 3 230 V Max. rating for three phase motors, 50

More information

0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N

0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 55 Series - General purpose relays 7-10 A Features 55.12 55.13 55.14 Printed circuit mount, general purpose 2, 3 & 4 Pole relays 55.12-2 Pole 10 A 55.13-3 Pole 10 A 55.14-4 Pole 7 A AC coils & DC coils

More information

e 2 ALPHA Medium Voltage Switchgear Data Sheet K-1.1.2 EN

e 2 ALPHA Medium Voltage Switchgear Data Sheet K-1.1.2 EN e 2 ALPHA Medium Voltage Switchgear Data Sheet K-1.1.2 EN We create ideas with power! ELEKTROMETAL ENERGETYKA SA is a new Polish company providing solutions for electrical power engineering. Our services

More information

RDJ10RF/SET. Wireless room temperature controller with 24-hour time switch and LCD. Programmable, for heating systems

RDJ10RF/SET. Wireless room temperature controller with 24-hour time switch and LCD. Programmable, for heating systems 3 072 RDJ10RF RCR10/433 Wireless room temperature controller with 24-hour time switch and LCD Programmable, for heating systems RDJ10RF/SET Operating modes: Automatic, Comfort, Energy Saving, and Frost

More information