SECTION TEMPORARY GENERATOR QUICK CONNECTION SWITCHBOARD
|
|
- Julius Blair
- 7 years ago
- Views:
Transcription
1 SECTION TEMPORARY GENERATOR QUICK CONNECTION SWITCHBOARD PART 1 - GENERAL 1.1 DESCRIPTION A. This section specifies the furnishing, installation, connection, and testing of a low-voltage temporary Generator Quick Connection Switchboard, indicated as switchboard in this section. B. Generator Quick Connection Switchboard shall be designed to allow quick and safe connection of a mobile generator set to facilities experiencing loss of power. Permanent installation and connection of the switchboard to the facility power distribution system will minimize any unplanned power outages. 1.2 RELATED WORK (NOT USED) 1.3 QUALITY ASSURANCE A. Manufacturer: For equipment required for the work of this section, provide product which is the responsibility of one manufacturer. 1.4 FACTORY TESTS A. Perform factory and installation tests in accordance with applicable NEC, NEMA and UL requirements. 1.5 SUBMITTALS A. Product Data: Submit manufacturer's printed product data. B. Drawings: Submit shop drawings for approval. Include components, materials, finishes, detailed plan and elevation views, required breaker and cam type openings, anchors, and accessories. 1.6 APPLICABLE PUBLICATIONS A. Publications listed below (including amendments, addenda, revisions, supplements and errata) form a part of this specification to the extent referenced. Publications are referenced in the text by basic designation only. B. National Electrical Manufacturer's Association (NEMA): PB Deadfront Distribution Switchboards PB Proper Handling, Installation, Operation, and Maintenance of Deadfront Distribution Switchboards Rated 600 Volts or Less C. National Fire Protection Association (NFPA): National Electrical Code (NEC) D. Underwriters Laboratories, Inc. (UL): Molded-Case Circuit Breakers, Molded-Case Switches, and Circuit-Breaker Enclosures Switchboards
2 PART 2 - PRODUCTS 2.1 GENERAL A. Shall be in accordance with NEMA, NFPA, UL, as shown on the drawings, and have the following features: 1. Switchboard shall be a complete, grounded, continuous-duty, integral assembly, dead-front, dead-rear, self-supporting, outdoor type switchboard assembly. Incorporate devices shown on the drawings and all related components required to fulfill operational and functional requirements. 2. Switchboard shall be supplied as a complete system and shall include all the necessary components and equipment to accommodate described system operation unless otherwise noted. 3. Switchboard shall conform to the arrangements and details shown on the drawings. 4. Switchboards shall be assembled, connected, and wired at the factory so that only external circuit connections are required at the construction site. 5. All non-current-carrying parts shall be grounded. 6. Packaging shall include the switchboard to be shrink wrapped and mounted to a skid and to provide adequate protection against rough handling during shipment. 2.2 HOUSING A. Frames and enclosures: 1. Enclosure shall be designed according to NEMA 3R standard for outdoor operation which includes a sloped roof. 2. Floor standing, manufactured from Carbon Steel, Aluminum, or Stainless Steel with: 1. Frame - 11 gauge 2. Roof and Front Door - 12 gauge 3. Rear and Side Sheets - 14 gauge 3. Enclosure shall be of rigid frame construction. 4. The enclosure shall include a full front door with a two point latch to access permanent cables and an integral lower flip open door to allow cable connection of the portable generator set. 5. The access door shall have full height left or right hinge to allow easy access to the switchboard cam-lok type connections for cable connections to the mobile generator or site loads. The bottom portion of the door shall have an additional horizontal hinge to allow for the door to be closed while cables are connected. The hinged bottom portion of the door shall flip up to the extent needed to accommodate the cable entry/exit while providing the drip shield for the components inside of the enclosure. 6. Stainless Steel exterior hardware shall be utilized. 7. One (1) padlockable handle on full front door and One (1) padlockable handle on lower flip door. 8. Internal Climate Control to include two (2) Space Heaters shall be controlled by Thermostat and Humidistat; requires customer supplied 120VAC, 10A circuit. 9. For ease of on-site cable connections and maintenance an open bottom, removable full depth side sheets and rear sheets shall be provided. 10. For ease of the switchboard service, maintenance and future upgrades, all the support structures, braces and cover sheets for the circuit breakers, main bus, neutral bus, ground bus and circuit breakers runback extension bus shall be removable and attached to the frame via bolts
3 B. Markings and Nameplates: 1. Each switchboard section shall have a label permanently affixed to it, listing the following information: Name of manufacturer, system voltage, ampacity, type, and manufacturer's shop order number. 2. Switchboard shall bear a UL891 listing mark as Type 3R equipment for outdoor use in Carbon Steel, Aluminum, or Stainless Steel construction. 3. The nameplates shall be produced from clear textured polycarbonate, laminated on high performance pressure sensitive adhesive. The printing shall be done on the interior surface of the laminate to avoid scratching or other deterioration of text. The lettering shall be white on black background. 4. Each control switch, indicating light or other component mounted on the inner panel shall be identified by a nameplate. C. Finish: 1. One (1) powder coat of ANSI 61 Light Gray shall be applied to all interior and exterior surfaces. 2. The final finish must be exterior rated for NEMA 3R use. 2.3 BUSES A. Silver plated copper busbar shall be used for permanent cable connections to the facility via the (removable) side or rear sheets of enclosure. 2.4 CAM-LOK TYPE CONNECTORS A. Cam-lok type connectors shall be NEMA 3R rated so as to be used in direct rain should the door become open. B. Each color coded, male Cam-lok E1016 compatible single pole receptacles with cover shall be color coded per: 1. A phase Brown 2. B phase Orange 3. C phase Yellow 4. Neutral White 5. Ground Green 2.5 CIRCUIT BREAKERS A. Temporary Generator Circuit Breaker: 1. Switchboard shall be equipped with One (1) Manually Operated Circuit Breaker shall be (Fixed Mount), 100% Rated, Insulated Case Circuit Breaker, with (LI) solid state trip unit, stored energy mechanism, and a and b aux. contacts. 2. Interrupting Rating: a. For a circuit breaker rated under 2500A, interrupting rating shall be (65kA)@480VAC. b. For a circuit breaker rated at 2500A and up, interrupting rating shall be (100kA)@480VAC. 3. Circuit Breaker Shunt Trip - 120VAC shall be provided. B. Circuit breaker ratings shall be as indicated. 2.6 ANNUNCIATION A. All indicating lights shall be located behind full front door. B. All indicating lights shall be of high visibility, LED type with lenses of at least 1 inch outside diameter with service life of 100,000 hours at 77 F temperature
4 2.7 GROUND FAULT PROTECTION A. Include in the switchboard, ground fault protection and indication equipment. All parts of the systems specified shall be UL Listed. B. All ground fault protection and indication equipment shall be factory installed, wired and tested by the switchboard manufacturer. 2.8 PHASE ROTATION MONITORING A. Phase Rotation Monitoring shall ensure portable genset phase rotation matches that of the facility. B. An indicating light shall provide visual assurance of correct phasing. C. Circuit breaker shall be prevented from being closed if phase rotation is incorrect by operating the shunt trip coil. D. Instructions to easily fix incorrect phase rotation shall be included on a label inside each panel. 2.9 INTERLOCKING A. Interlock between facility main service circuit breaker and temporary generator circuit breaker shall be to prevent inadvertent paralleling of the Utility and Temporary Generator. B. The Kirk Key shall be removed from the facility circuit breaker (customer supplied Kirk Key lock) to hold circuit breaker in open position, and to be inserted in the Temporary Generator Breaker to allow connection of the generator to the facility. C. Customer shall provide site specific Kirk Key information ALTERNATE CONNECTIONS A. Alternate busbar connections with NEMA standard hole pattern and mechanical lugs shall be provided for use in the event a mobile genset is used that does not have cables with Cam-lok E1016 compatible plugs. B. Alternate busbar connections shall be accessible through a removable piece of sheet metal. Cables shall enter the switchboard via the integral lower flip door to connect to the alternate connection area SEQUENCE OF OPERATION A. Should the Utility fail, the facility s main breaker would be manually opened and the portable generator set would be connected to the Cam-lok type receptacles in the panel located behind lower flip door. B. The Temporary Generator Connection Circuit Breaker would be manually closed to allow the temporary generator to provide electrical power to the facility load. C. Upon restoration of the Utility s power, the Temporary Generator Connection Circuit Breaker would be manually opened to allow for the closing of facility s main breaker to restore the facility to the normal Utility power source
5 PART 3 - EXECUTION 3.1 INSTALLATION A. Install switchboards in accordance with the NEC, as shown on the drawings, and as recommended by the manufacturer. ---END
All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.
DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,
More informationBERTHOLD ELECTRIC GENERATOR CONNECTION CABINET
BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET Berthold Electric Company s Generator Connection Cabinet provides a quick and convenient station to connect a portable generator to a facility s main service
More informationSubmit shop drawings for equipment provided under this section Shop drawings shall indicate:
Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,
More informationSUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches
SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches PART 1 GENERAL 1.01 Scope Optional Standby Power Generator Systems A. Furnish and install automatic transfer switches
More informationGenerator DoCKInG StatIonS
Generator DOCKING STATIONS TRYSTAR Portable Power Cable Cam to cam cable extensions 2000V, 100A-400A rated to NEC table 400.5 (B) All portable power cable sold is highly flexible and UL & C-UL or CSA Listed
More informationMini Power-Zone Unit Substation Product Description. Product Description. Features. Typical Applications
Product Description Product Description The Mini Power-Zone Unit Substation from Schneider Electric is a miniaturized version of our Power-Zone Unit Substation. Included are: Circuit Breaker Sealed Step-Down
More informationSWITCHGEAR Section 16. SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less.
PART 1 - GENERAL SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less. RELATED SECTIONS Division 16 Section "Basic Electrical Materials and Methods" for general
More informationMini Power-Zone Unit Substation
Catalog 7440CT0901 2009 Class 7440 CONTENTS Description............................................. Page Product Description...........................................2 General Information...........................................3
More information2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.
2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to
More informationSECTION 08332 COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here)
SECTION 08332 COILING COUNTER DOORS Display hidden notes to specifier. (Don't know how? Click Here) PART 1 GENERAL 1.1 SECTION INCLUDES A. Coiling Metal Counter Doors. B. Coiling Counter Fire Doors. 1.2
More informationMCC Ratings. Voltage Rating
MCC Ratings In addition to the various ratings of individual components used in motor control centers, the overall ratings of the motor control center must also be considered. Voltage Rating Motor control
More informationCluster Box Units. (CBU s) 3300 Series CBU Door Sizes. Fully Integrated Parcel Lockers CLUSTER BOX UNITS FRONT LOADING. continued on pages 7-11
Cluster Box Units (CBU s) continued on pages 7-11 CLUSTER BOX UNITS FRONT LOADING Made of heavy duty aluminum and stainless steel hardware, Salsbury 3300 series U.S.P.S. approved Cluster Box Units (CBU
More informationMEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4
CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,
More informationLearning Module 13: Panelboards and Switchboards. 101 Basic Series
Learning Module 13: Panelboards and Switchboards 101 Basic Series What You Will Learn We ll step through each of these topics in detail: Introduction 4 Definitions 4 Similarities Between Panelboards and
More informationUNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation
Basis of Design This section applies to the design relating to low voltage switchboards. Design Criteria UW Class N1 facilities main switchboards shall be rear accessible. The main, tie and feeder breakers
More informationMETER REQUIREMENTS GENERAL REQUIREMENTS SECTION D
12 - ELECTRIC SERVICE HANDBOOK SECTION D METER REQUIREMENTS This chapter gives you information on Central Lincoln s metering requirements. It's divided into three sections: General requirements This section
More informationSpecification Guide. for RVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers
Specification Guide for RVAC Direct Replacement AC Medium Voltage Circuit Breakers Table of Contents 1.0 General Work Scope...3 2.0 Standards...3 3.0 Supplier Qualifications...4 4.0 Circuit Breaker Element
More informationLVA Take Offs in Bid Manager
Electrical Sales and Distributor Training Low Voltage Assemblies (LVA) LVA Take Offs in Bid Manager This job aid helps to define some of the common selection questions that are encountered when configuring
More informationFFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid
Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars Presented By: Greg Pelster & Robert Schmid FFI Ferrie, Franzmann Industries LOW VOLTAGE SWITCHGEAR & LOW VOLTAGE
More informationELECTRIC METERING COMMERCIAL & INDUSTRIAL
ELECTRIC METERING COMMERCIAL & 1.0 INDEX 1.0 INDEX 2.0 SCOPE 3.0 GENERAL REQUIREMENTS 4.0 METER LOCATIONS 5.0 UNDERGROUND TERMINATIONS 6.0 METERING TRANSFORMER ENCLOSURES 7.0 SINGLE CUSTOMER METER INSTALLATIONS
More informationSECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL
SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL 1.1 SUMMARY A. This section describes the requirements for the installation of Power Monitors and associated
More informationSample - No Commercial Use
COMPLETE REVISION October 2010 Electrical PIP ELSSG01 Design and Fabrication of Low-Voltage Metal-Enclosed AC Power Circuit Breaker Switchgear PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort
More informationASCO SERIES 185 Power Transfer Switches
ASCO SERIES 185 Power Transfer Switches 4-hour protection no matter when trouble strikes ASCO Series 185 Power Transfer Switches An Automatic Transfer Switch helps prevent... Your business or home from
More informationPREFACE. Your comments or suggestions are welcome and appreciated. They should be sent to:
PREFACE UL developed the Dead-Front Switchboard Marking Guide for code authorities, electric utilities, contractors, installers, users, designers, and other interested parties to aid in understanding deadfront
More informationIRRIGATION PUMPING Table of Contents - Section 900
IRRIGATION PUMPING Table of Contents - Section 900 PARAGRAPH 900.1 GENERAL 1 900.2 METERING REQUIREMENTS 1 900.3 CUSTOMER S CONTROL EQUIPMENT 2 900.4 SERVICE CONDUCTOR REQUIREMENTS 2 900.5 RECOMMENDATIONS
More informationSWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS. Presented by SAI Advanced Power Solutions
SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS POWER DISTRIBUTION RACKS IN A MISSION CRITICAL SYSTEM MODULES IN A MISSION CRITICAL SYSTEM UPS Convertor Main Inverter Load Battery BPC UPS & BATTERY
More informationELECTRICAL CONTRACTORS THE UNIVERSITY OF TENNESSEE KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1
KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1 PART 1 - GENERAL 1.01 RELATED DOCUMENTS: SECTION 16050 A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1
More informationElectrical Grounding. Appendix C
Appendix C Electrical Grounding Low-Voltage Equipment Grounding The most frequently cited Office of Safety and Health Administration (OSHA) electrical violation is improper occupational grounding of equipment
More informationInstallation Instructions
H5HK Series Installation Instructions 3 Phase Electric Heater Kits 7.5 and 0 TON Package A/C Systems Description Installation of 08/40V and 480V H5HK 3 Phase Heater Kits in 7.5 and 0 TON Packaged Air Conditioners.
More informationELECTRIC UTILITY SERVICE EQUIPMENT REQUIREMENTS COMMITTEE, EUSERC
ELECTRICAL SERVICE REQUIREMENTS ELECTRIC UTILITY SERVICE EQUIPMENT REQUIREMENTS COMMITTEE, EUSERC TABLE OF CONTENTS TITLE SECTION NO. List of Approved Electric Utility Service Equipment Requirements Committee
More informationSECTION 10680 MediaStation Model 125 Electric Lateral Files (ELF)
SECTION 10680 MediaStation Model 125 Electric Lateral Files (ELF) PART 1-GENERAL 1.01 RELATED WORK SPECIFIED IN OTHER SECTIONS A. Electrical connections see electrical specifications. 1.02 SUBMITTALS A.
More informationSECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT
SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION A. The Work specified in this Section consists of designing, furnishing and installing factory-assembled
More informationA. Shop Drawing submittals shall include, but not be limited to, the following:
SECTION 26 05 53 IDENTIFICATION FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical
More information26 3213.13 Diesel Engine Driven Generators Page 1 of 6
Last Update: December 8, 2014 A. Description of System Consultant s Handbook Page 1 of 6 1. Provide a diesel engine driven electric generating unit, factory assembled, tested and certified to operate at
More informationSecondary Unit Substations
14 SWITCHGEAR Secondary Unit Substations Overview Siemens offers a wide variety of unit substation designs to meet customer requirements. A unit substation consists of one or more transformers mechanically
More informationCircuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services
Circuit Breakers and Switchgear Thomas Greer Director of Engineering TLG Services Presentation Outline Switchgear Definition Overcurrent Protection Devices Circuit Breaker Trip Curves and Coordination
More informationProduct Specification instalert Rapid Messenger Variable Message Sign
instalert 2 units to cover any application instalert 18 (ia18): 18 x 28 full matrix instalert 24: (ia24): 24 x 60 full matrix Size, Weight without battery ia18: 30 x 20 x 2.74, 29 lbs ia24: Folds to fits
More informationSuitable for Emergency, Peak and Prime Power System Applications. Low Voltage Automatic Transfer Switch Systems
Suitable for Emergency, Peak and Prime Power System Applications Low Voltage Automatic Transfer Switch Systems THE POWER AUTHORITY THE POWER AUTHORITY ASCO s experience and commitment to excellence in
More informationFor Models #6-5001, #6-7501, #10-7501 & #10-12K1
EmerGen Switch Manual Transfer Switch Manufactured by CONNECTICUT ELECTRIC SWITCH MFG. CO. 1-800-730-2557 OWNER S MANUAL & INSTALLATION INSTRUCTIONS For Models #6-5001, #6-7501, #10-7501 & #10-12K1 PLEASE
More informationTemporary Power Outlet Panels
Power Outlet Panel Types Available ATTENTION PLEASE Siemens is proud to present our new line of temporary power products. This section describes our new product line that that will be available to order
More informationUNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Metering and Monitoring. Basis of Design
Basis of Design This section applies to the design, installation and integration of metering and monitoring equipment, including: hardware installed in the electrical service and distribution equipment,
More informationThis section applies to the design and installation of transformers.
ELECTRICAL: TRANSFORMERS BASIS OF DESIGN This section applies to the design and installation of transformers. Design Criteria 13.8-kV equipment shall be 15-kV class. Coordinate with short-circuit studies
More informationCAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH
CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH Cat transfer switches are designed for a variety of standby power applications. They provide flexibility, reliability and value in a
More informationSECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS
SECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS Display hidden notes to specifier by using Tools / Options / View / Hidden Text. On newer versions of Microsoft Word
More informationDistribution Dry Type Transformers
8 TRASFORMERS Distribution Dry Type Transformers Table (Contact Sales office for List Price) (commonly used) 1a. 115 C Rise F 1b. 80 C Rise B 4. Wall Brackets1 W 6. Low noise XdB below std. LX Type bg
More informationMODEL IX -WAC/HP AIR CONDITIONERS & HEAT PUMPS FOR HIGHLY CORROSIVE & HAZARDOUS AREAS
1.5, 2, 2.5, 3, 3.5, 4, 5 & 6 Ton Industrial Grade Wall Mounted Air Conditioners & Heat Pumps Unit Application Bebco Model IX-WAC/HP Industrial Grade Air Conditioners & Heat Pumps are designed as a total
More informationSECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines
PART 1 -- GENERAL 1.1 WORK OF THIS SECTION SECTION 16720 - City of San Diego, CWP Guidelines A. The WORK of this Section includes providing manual and automatic fire alarm and smoke detection systems meeting
More informationOEM Manual MODEL 2350 ELECTRONIC DUAL CYLINDER SCALE
OEM Manual MODEL 2350 ELECTRONIC DUAL CYLINDER SCALE Scaletron Industries, Ltd. Bedminster Industrial Park 53 Apple Tree Lane P.O. Box 365 Plumsteadville, PA 18949 USA Toll Free: 1-800-257-5911 (USA &
More informationSHORE POWER. Safely Connecting Ships to Shore SAFETY QUALITY INNOVATION VALUE CUSTOMER SERVICE
SHORE POWER Safely Connecting Ships to Shore SHIP-TO-SHORE SOLUTIONS FOR MILITARY & COMMERCIAL APPLICATIONS SAFETY QUALITY INNOVATION VALUE CUSTOMER SERVICE ESL Power Systems, Inc. ESL has established
More informationUtility Distribution Systems
Utility Distribution Systems 6/2012 A0011037 1 WARRANTY This equipment is warranted to be free from defects in materials and workmanship, under normal use and service, for a period of 12 months from date
More informationREAD THIS MANUAL BEFORE PROCEEDING WITH THE INSTALLATION. FAILURE TO FOLLOW THE INSTALLATION INSTRUCTIONS MAY VOID YOUR WARRANTY!
READ THIS MANUAL BEFORE PROCEEDING WITH THE INSTALLATION. FAILURE TO FOLLOW THE INSTALLATION INSTRUCTIONS MAY VOID YOUR WARRANTY! The main power to any existing system must be disconnected prior to the
More informationIntroduction. Upon completion of Basics of Switchboards you should be able to: Explain the role of switchboards in a distribution system
Table of Contents Introduction... 2 Distribution Systems... 4 Switchboard Definition... 9 Switchboard Construction... 12 Service Entrance Equipment... 18 Service Section... 20 Switchboard Grounding...
More informationTP-C2 Motor Operator CLEAVELAND / PRICE INC. Bulletin DB-111B12
Bulletin DB-111B12 TP-C2 Motor Operator CLEAVELAND / PRICE INC. 14000 Rt. 993, Trafford, PA 15085 (724) 864-4177 FAX (724) 864-9040 Email: sales@cleavelandprice.com Cleaveland/Price Type TP-C2 Motor Operator
More informationOASIS-PLUS 120V READ ALL INSTRUCTIONS BEFORE OPERATING READ ALL INSTRUCTIONS BEFORE OPERATING OZONE IS A POWERFUL OXIDIZER AND MUST BE USED WITH CARE
OASIS-PLUS 120V INFORMATION & OPERATING INSTRUCTIONS READ ALL INSTRUCTIONS BEFORE OPERATING READ ALL INSTRUCTIONS BEFORE OPERATING OZONE IS A POWERFUL OXIDIZER AND MUST BE USED WITH CARE 56041852 WARNING:
More informationDESIGN CLARIFICATION (DC)
DESIGN CLARIFICATION (DC) Owner: Victor Valley Wastewater Reclamation Authority Date: 03/03/2015 Contractor: W M Lyles Carollo Project No.: 8299A.20 Project Name: Subregional WRPs DC No.: 001 DC Title:
More informationDoc Ref: 2015.06.01.002. 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC
TM 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC TM D400E Data Module (60Hz) The EDGE D400E is designed to meet high power density requirements for both the HPC and Web Scale environments while
More informationInstallation Guide of Sunrise Solartech PV Modules. Term 2013. Contents. Purpose of this guide. General. Safety precaution for installing a solar
Installation Guide of Sunrise Solartech PV Modules Term 2013 Contents Purpose of this guide General Safety precaution for installing a solar Photovoltaic system Product Identification Mechanical Installation
More informationEast Central College 14434.03 HANSEN HALL LEVEL 300/400 RENOVATIONS PACKAGE
SECTION 260519 - BUILDING WIRE AND CABLE PART 1 - GENERAL 1.1 WORK INCLUDES A. Base and Alternate Bids: 1. Contractor Provide: a. Building wire and cable as shown on drawings or specified including feeders,
More informationBussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1
How to configure Part Numbers: Step : Select Switch Amperage Power Module Switch Rating (Amps) Power Module Switch Catalog No. 30 3 60 6 00 200 2 400 4 Step 2: Select Options Needed 5 Bussmann Power Module
More informationCLIENT. Inspection Report. 271 Front St. Alert Bay, B.C. Island Building Inspections V ANCOUVER I SLAND B. C.
CLIENT Inspection Report 271 Front St. Alert Bay, B.C. Island Building Inspections 2013 V ANCOUVER I SLAND B. C. Elevation Photos For the Property at 271 Front Street Alert Bay, BC ELEVATION PICTURES Front
More informationTERMINATION ENCLOSURE OPTIONS
TERMINATION ENCLOSURE OPTIONS Add suffix: R - Reverse Stagger the Bus Bars (to run cable in from the top) CU - Copper NEMA Mount Bus Bars C - Plastisol Covers for Bus Bars DF - Dead Fronts T - Tin Plated
More informationRAY-MAX Integrated Solar Power Strip
RAY-MAX Integrated Solar Power Strip 600008, 600009, 600010, 600208, 600209, 600210 Owner s Manual NEXTRONEX, INC. Revision Date: 10/27/14 Contents 1. Safety Instructions... 3 2. General Equipment Warnings...
More informationB. Related Sections: 1. Section 26 05 33 - Raceway and Boxes for Electrical Systems.
SECTION 262726 - WIRING DEVICES PART 1 - GENERAL 1.1 SUMMARY A. Section includes wall switches; wall dimmers; receptacles; multioutlet assembly; and device plates and decorative box covers. B. Related
More informationMetallic and Non-Metallic Air Conditioning Disconnects. A Complete Family of. Disconnects with Exclusive Time Saving Features
Metallic and Non-Metallic Air Conditioning Disconnects A Complete Family of Disconnects with Exclusive Time Saving Features Enclosed Molded Case Disconnect Switch Not-Fusible The preferred molded case
More informationSection 10 Electric Switchboards: 0 Through 600 Volts
Section 10 Electric Switchboards: 0 Through 600 Volts 10.1. Scope This section provides specific dimensions and details for service and meter equipment that is assembled by the manufacturer in freestanding,
More informationDENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION 17650 SECURITY SYSTEMS
PART 0 DESIGN STANDARDS 0.01 GENERAL DESIGN GUIDELINES A. Inspections and observations by the Owner do not relieve the A/E of contract responsibilities. B. Chain of command 1. The DPS Project Manager is
More informationRequirements for Electrical Installations
ARTICLE 110 Requirements for Electrical Installations INTRODUCTION TO ARTICLE 110 REQUIREMENTS FOR ELECTRICAL INSTALLATIONS Article 110 sets the stage for how you ll implement the rest of the NEC. This
More informationPAINT BOOTH LIGHTING
PAINT BOOTH LIGHTING PAINT BOOTH LIGHTING Lighting is comprised of many components that need to be considered when selecting the appropriate fixtures and lamps to accomplish a specific task. Selecting
More informationSECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS
SECTION 15750 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for roof mounted, self-contained units, with electric cooling, and electric or reverse refrigeration cycle (heat pump) heating
More informationFVSU-33201301 REPAIR & UPGRADE FIBER OPTIC 280000-1 SECTION 280000 FIRE ALARM SYSTEM CONNECTIVITY
FVSU-33201301 REPAIR & UPGRADE FIBER OPTIC 280000-1 SECTION 280000 FIRE ALARM SYSTEM CONNECTIVITY PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Fire-alarm control unit. 2. Addressable interface
More informationSOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings
*** Provide this document to the inspector along with ALL system installation instructions *** Project Address: Scope: Standard plan for the installation of grounded microinverter solar PV systems, not
More information-1- SPECIFICATIONS 002085 CONE SETTER PLATFORM ATTACHMENT INDEX
-1-002085 CONE SETTER PLATFORM ATTACHMENT INDEX I. GENERAL EQUIPMENT : A. Intent Statement B. Cone Setter Platform II. III. 1. Understructure Frame 2. Mounting Components 3. Paint 4. Basket 5. Labels 6.
More informationELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS:
ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS: Chapter 12 of the Burlington Code of ordinances allows owner occupants of single family homes to do their own wiring if they choose. If you choose to
More informationAMPSEAL* Automotive Plug Connector and Header Assembly
AMPSEAL* Automotive Plug Connector and Header Assembly Application Specification 24 SEP 97 Rev E All dimensions are given in millimeters unless otherwise specified. All dimensional tolerances are +0.2
More informationThe National Armored Cable Manufacturers Association Presents. Installation Standard for Types AC and MC Cables
The National Armored Cable Manufacturers Association Presents Installation Standard for Types AC and MC Cables An ANSI Standard Original document jointly produced by NECA and NACMA as Standard for Installing
More information3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance
SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132
More informationSECTION 25110 TELECOMMUNICATION ROOMS
PART 1 - GENERAL 1.1 SUMMARY A. SCOPE SECTION 25110 TELECOMMUNICATION ROOMS 1. This section includes the minimum installation requirements for equipment and cabling infrastructure in Telecommunication
More informationTRITON CONTAINER INTERNATIONAL. Reefer Technical Bulletins. Version 4.0
TRITON CONTAINER INTERNATIONAL Version 4.0 February 2013 Table Of Contents (Hold Ctrl button and click on any item below to go directly to that section of the manual.) 1 INTRODUCTION... 3 2 REFRIGERATED
More informationEngineers Edge, LLC PDH & Professional Training
510 N. Crosslane Rd. Monroe, Georgia 30656 (770) 266-6915 fax (678) 643-1758 Engineers Edge, LLC PDH & Professional Training Copyright, All Rights Reserved Engineers Edge, LLC An Introduction to Interior
More informationSPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT
SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT The purpose of these specifications is to insure that there are minimum
More informationTop Commercial / Residential Electrical Requirements *
Department of Community Development Building Division 4800 West 92 nd Avenue Westminster, Colorado 80031 For Information call (303) 658-2075 Fax (303) 706-3922 www.westminsterpermits.com Top Commercial
More informationSECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS
SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS PART 1 - GENERAL 1.01 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section
More informationLow Voltage Transformers Sealed, General Purpose, Dry Type
Low Voltage Transformers Sealed, General Purpose, Dry Type Catalog 7400CT9601R4/08 08 Class 7400 CONTENTS Description..............................................Page Introduction.................................................
More informationSECTION 15732 AIR CONDITIONING UNIT
SECTION 15732 AIR CONDITIONING UNIT PART 1 GENERAL 1.01 SUMMARY A. Section includes: 1. Packaged, split system air conditioning unit No. 1. 1.02 REFERENCES A. Air-Conditioning, Heating, and Refrigeration
More informationTrade of Electrician. Three-phase Distribution Boards And Socket Circuits
Trade of Electrician Standards Based Apprenticeship Three-phase Distribution Boards And Socket Circuits Phase 2 Module No. 2.3 Unit No. 2.3.2 COURSE NOTES Created by Charlie Walsh - Athlone TC Revision
More informationHPS Universal. Single and Three Phase Potted. Buck-Boost Transformers. Buck-Boost Applications & Standard Specification... 80
Buck-Boost Transformers Single and Three Phase Potted Buck-Boost Transformers Buck-Boost Applications & Standard Specification... 80 Selecting Buck-Boost Transformers... 81 Single Phase Selection Tables...
More informationRoof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS
Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS Ducted System RECORD THIS UNIT INFORMATION FOR FUTURE REFERENCE: Model Number: Serial Number: Date Purchased: This manual must be read and
More informationMONTGOMERY COUNTY EXECUTIVE REGULATION Offices of the County Executive. 101 Monroe Street. Rockville, Maryland 20850
Montgomery County Regulation on: ADOPTION OF THE 2008 NATIONAL ELECTRICAL CODE DEPARTMENT OF PERMITTING SERVICES Issued by County Executive Regulation # 15-09 Authority: Code Section 17-2 and 17-3 Supersedes:
More informationWhitley Manufacturing Co., Inc. 201 W. First Street S. Whitley, IN 46787 Phone (260) 723-5131 Sales Fax (260) 723-6396 whitley@whitleyman.
Building Type Building Code Whitley Classroom Buildings BOCA, UBC, SBCCI, NEC, ADA Structural Support Outrigger construction standard, Whitley model classrooms. Main support beams to be 12 11.8# per lineal
More information8146/5 Series Breaker Panelboards
8146/5 Series Breaker Panelboards DISTRIBUTION BREAKER PANELBOARDS FOR HAZARDOUS & CORROSIVE ENVIRONMENTS Breaker Panels Features: Wide variety of Flameproof branch circuit breakers for Zone 1 & Division
More informationBolted contact switches. Pringle switches
Bolted contact switches Pringle switches Eaton s Pringle bolted contact switches History Eaton s PringleT switches have helped pioneer the development of high-quality electrical products for commercial
More informationApplication Bulletin 103 - NEC Reference Guide for SolarBridge-Enabled AC Module Installers
9229 Waterford Centre Dr. Bldg C, Suite 110 Austin, Tx 78758 Application Bulletin 103 - NEC Reference Guide for SolarBridge-Enabled AC Module Installers Current Version: 13 AC Modules are a new product
More informationINDUSTRY WIDE LABOR-MANAGEMENT SAFETY COMMITTEE SAFETY BULLETIN #23
INDUSTRY WIDE LABOR-MANAGEMENT SAFETY COMMITTEE SAFETY BULLETIN #23 GUIDELINES FOR WORKING WITH PORTABLE POWER DISTRIBUTION SYSTEMS AND OTHER ELECTRICAL EQUIPMENT "ADDENDUM C" WORKING WITH 480 VOLT SYSTEMS
More informationElectrical Wiring Technical Bulletin
Electrical Wiring Technical Bulletin Overview In general, SIP construction is easier and more cost effective when things are planned and thought out before the panels are manufactured. This process will
More informationSection 9: Power Distribution Equipment Bill Brown, P.E., Square D Engineering Services
Section 9: Power Distribution Equipment Bill Brown, P.E., Square D Engineering Services Introduction Power Distribution Equipment is a term generally used to describe any apparatus used for the generation,
More informationDUPLEX 120 VOLT FLOAT CONTROL PANEL STANDARD SPECIFICATION
DUPLEX 120 VOLT FLOAT CONTROL PANEL STANDARD SPECIFICATION Prepared by: E G Controls Inc. 11790 Phillips Highway Jacksonville fl. 32256 Date Prepared: 3/1/07 3/14/07 1 Copyright, EG Controls, Inc. TABLE
More informationAmphenol C 091 A/B/D. Circular Connectors. Amphenol-Tuchel Electronics GmbH
Amphenol C 091 A/B/D Circular Connectors Amphenol-Tuchel Electronics GmbH C 091 A Main Features Metal threaded coupling acc. to IEC. Number of contacts are 2 to 8, 12 and 14. Internal metal strain relief
More informationMISCELLANEOUS ELECTRICAL JOBS REQUIRING PERMITS
MISCELLANEOUS ELECTRICAL JOBS REQUIRING PERMITS 01. SAFETY INSPECTION of service equipment at FPL Power Source 02. Construction GFI power outlets (Temp Pole for Construction) 03. 90 day temporary power
More informationDIVISION 27 COMMUNICATIONS. A. System design shall be completed by a Registered Communications Distribution Designer (RCDD).
DIVISION 27 COMMUNICATIONS 27 00 00 COMMUNICATIONS A. System design shall be completed by a Registered Communications Distribution Designer (RCDD). B. Comply with American National Standards Institute
More informationPROLINE Go l d Se r i e s. Desk Consoles and Accessories
Modular Enclosure Systems Application PROLINE Gold Series desk consoles are ergonomically designed for use in either a sitting or standing position. Single-access consoles have a front door and solid back.
More information