1 Electrical Sales and Distributor Training Low Voltage Assemblies (LVA) LVA Take Offs in Bid Manager This job aid helps to define some of the common selection questions that are encountered when configuring Low Voltage Assemblies (LVA) in Bid Manager. System Tab Guide 100% neutral should be selected when 4 wire loads are required. None should be selected when high resistance grounding is required. UL1558 and UL891 are available in drawout construction. Magnum DS breakers are provided in UL1558 and Magnum SB breakers are provided in UL891. PRLC Switchboards can be integrated into either UL1558 or UL891 assemblies and the PRLC structures will always be labeled UL891. See the Consulting and Application Guide (CAG) for breaker details. Typical service voltage is 480V or 480/277V. 600V rating has limited breaker options, see CAG for breaker details. Selection of voltage and short circuit (kaic) have implications on available layouts when arc construction is required. This is the interrupt rating of the gear, kaic. The interrupt rating determines the lowest possible breaker rating available in the gear. Short circuit (kaic) have implications on available layouts when arc construction is required. Select other to have all possible options available when using the layout tab. Provides notes on the bill of material (BOM), consult your district sales engineer (DSE) prior to selecting. Select 4 wire and neutral (#3) as none when high resistance grounding is required. This determines the number of incoming connections, not necessarily the distribution, load and connections. This is the main, horizontal, bus. The bus is not tapered, and the vertical risers may be rated less than the main bus unless otherwise noted. Configure close coupled connections to transformers, other gear and other equipment. Contact your district sales engineer prior to proceeding with any selection other than an Eaton-sourced transformer. Typical hertz is 60 for North America. Consult your district sales engineer prior to selecting 50. Select Power Xpert Gateway. Selection of non-standard nameplate background and text colors. Contact your district sales engineer prior to proceeding. Select miscellaneous control devices including customersupplied control power and 86 lockout relays.
2 System Tab Guide Insulation selection is for epoxy coated (3 mil thick) bus with insulating boots over maintainable joints. This is an environmental insulation system, and the epoxy coating does not provide electrical insulation. The neutral and ground busses are never insulated. This is not fluidized bed insulation. Insulation is not required to achieve required electrical clearances in Eaton Low Voltage Switchgear. Insulated runbacks only are selected on the options tab. Standard thicknesses of silver and tin plating thick silver plating is not provided as standard, contact DSE prior to proceeding. Contact sales engineer prior to proceeding with any selection other than standard. 1000A/sq.in. is not standard. Standard bus bracing (not interrupt rating, kaic) is 100ka. 150ka is available on all orders. 200ka bus bracing rating is only available when used in conjunction with 200 kaic systems and 200kaic breakers. Do not use. Ground bus options. Contact sales engineer prior to proceeding with any selection other than standard. Contact your district sales engineer and the Consulting and Application Guide for details of layout requirements for arc construction. Select type 2B, do not select type 2. Type 2B secondary door above the breaker is standard with 2B selection. Arc exhaust defaults to direct vent to room. Exhaust plenum and additional exhaust duct are selected on the option tab. Structures Tab Guide Enclosure type become active if NEMA 1 or EEMAC/N/A is selected within structures type. Labeled per UL requirements. Meets all seismic requirements of the California Building Code for zone and application is rear access has limited cable space depending on the number of breakers chosen in each structure. Recommend 72 or deeper for proper cable spacing. Floor plate material becomes active if floor plates is selected. Check to include screens and floor plates in gear. Filtered louvers is automatically checked when outdoor gear is selected. Check to include screens on all vents. Becomes active if cable selection pull box is checked. Two depths are available 18 and 30 inch.
3 Structures Tab Guide Default is incandescent, optional is florescent. Becomes active for NEMA 3R gear, check when required. Interior default. Exterior default. Used to secure gear to housekeeping pad. Wiring Tab Guide Mainly used by OEM customers. Consult factory for confirmation. This option is selected based on customer spec, where a greater degree of flame retardancy is desired and tested. This selection is for the type of terminals required (standard, ringtongue or locking fork). Ring-tongue Locking-fork Once these selections are set, voltage selections in the breaker takeoffs will be automatically filled-in. This selection is for the type of terminal blocks required (standard, heavy duty or states). If states terminals are required, make sure there is enough instrument space in the lineup for allocation. Consult factory for confirmation and details.
4 Lugs/Mimic/Transfer/CPT Tab Guide This selection is for the type of lugs required (mechanical or compression). The actual size of the lugs are to be specified in the breaker takeoff. This selection is for the type of GND lugs required (mechanical or compression). This selection is for the type of mimic bus required. Always offer plastic screw-on type. Size is 3/8 standard. Colors red and black are standard. All other colors are considered special and should consult with factory for availability and pricing. When applicable, must check the box to make selection active before selecting desired scheme. This option gives you the ability to select multiple sources. With only (1) main breaker, a single source control power would be appropriate. If there are multiple power sources in the lineup with a transfer scheme, then you have the option to choose more than one. It can also be customer supplied control power if external source is available. Trip units other than DT520 require control power. Accessories Tab Guide Circuit breaker not shipped in the assemblies. This selection should be used when requested by customer. Breakers will be shipped outside of the switchgear in their own individual packaging. Overhead breaker lifter is included by default. The lifter is removed when NEMA 3R aisle-less enclosure is selected under structures. This option is used when space heaters are required. Default is 3 heaters per structure, placed in breaker, bus and cable compartments. Maximum of 5 structures per thermostat. Quantity of thermostat needs to be increased when there are 5+ structures in the lineup. Voltage can be selected as 120 or 240VAC, switchgear or customer supplied. If switchgear supplied, then it will impact sizing of the CPT.
5 Breaker Tab Guide Greyed-out fields containing text values are non-selectable and typically driven by other selections within the takeoff. Pay close attention to short time rating spec requirements, especially when MDN breakers are selected. At higher short circuit ratings, MDN short time ratings may be significantly lower than MDS ratings. When MDSL breakers with current limiters are selected, short time current will be blank (limiter selection will determine short time). Manual (MO) is the default selection. When changing from manual (MO) to electric (EO), go to control/options tab and select appropriate control switch and indication. When changing from EO to MO, go to control/options tab and set the breaker control switch to none. Provision - does not contain a breaker, but is fully equipped to receive a breaker without field conversion (plug and play). All secondary wiring is included with this option as well. Space - does not contain a breaker. Contains connections to riser bus, but no breaker cell. Requires field conversion and secondary wiring to accept a future breaker. The plant recommends using provisions in lieu of spaces, unless there is a specific reason to utilize a space. Storage compartment - used specifically for storing a spare breaker in a lineup. Cannot be converted to an active breaker. Interrupt rating defaults to minimum short circuit rating selection from system tab. In some cases, a higher rating may be selected here if needed. When 200KAIC is required, frame type must be set to standard frame. Breaker frame rating. Determines MDS or MDN frame. Consult factory when 4 pole configurations are required. 4 pole breakers should only be configured with MDS frame (not MDN). 520MC or 1150 must be used when ARMS feature and/or communication is required. Nonauto may be selected when specification requires external relay protection (available up to 85kA max). Set sensor and trip ratings as needed per customer specific requirements. Trip function should be set to LSI when system is Delta, or when there is an HRG in the system. Does not affect pricing. All trip units are provided with instantaneous feature, whether checked or not. This field is currently n/a. Service entrance is selected under the structures tab. Configures digitrip power supply (DPS) voltage for 520M, 520MC, and 1150 trip units. 120-VAC is the default value unless preselected to a different voltage on the wiring tab. Only applicable to MDSL breakers. Default limiter selections are automatically populated. Based on frame/sensor rating. Some configurations allow changing the limiter size to meet specific coordination requirements. Refer to CAG Section for information regarding alternate selections and limiter characteristics. This selection will include a compartment (din-rail) mounted cap trip accessory. When cap trip box is checked, the shunt trip voltage under the related control/options tab will be fixed to 208V-250VAC/DC. Will be automatically set according to system tab (wye or delta, and 3W or 4W) selections, and trip function on this tab. For 4-wire systems that have 3-wire feeder loads, the default selections may be overridden. Source ground requires special consideration. If source or single point T ground system is required, consult the factory. Applicable to 1150 trip unit only. Allows user to configure whether PT connection is internally wired to the line side (upper terminals) or load side (lower terminals) of the breaker. The default is upper terminals and should generally not be changed except for special circumstances, such as when breaker is reverse-fed.
6 Breaker Tab Guide Cable quantities are pre-selected based on frame / sensor ratings. Phase / Neutral lug sizes default to 500kcmil cable. Sizes and quantities may be adjusted as necessary for the application. Use other when manual size and quantity selections need to be made. Cable is typically checked by default for mains and feeders. De-select when breaker is to be close-coupled to a transformer, or when busway connection is desired. The default selection will be determined by whether neutral has been selected on system tab. This selection will not be automatically updated if neutral is added (or removed) after breaker has been placed in the lineup. This determines line or load side cable terminations. The default setting for mains is line Side, and load side for feeder breakers. Both Line and load cables can be selected for special applications, such as single breaker cable in/cable out scenarios. However, the both line and load selection will not necessarily drive an accurate one line representation. If the breaker is to be busway connected instead of cable connected, the cable connection should first be unchecked. Typically, busway coordination details such as T direction and line number are unknown until after order entry. These details should not be pre-selected by sales unless coordination has been determined in advance. The following are limitations when busway connections are required and always consult the factory if there is any question regarding busway layout requirements: No A position busway connection is allowed when busway is top entry. Likewise, no D position allowed for bottom entry. When (top entry) busway connected breakers are stacked in the same vertical section with cable connected breakers, the busway connected breaker must be located above cable connected breakers. Contact the factory if two breakers stacked in a vertical section require busway connections. This situation can usually be accommodated with 84 or 90 depths. Non-segregated busway connections are preferred with arc-resistant switchgear assemblies. Contact the factory when non-segregated busway or non-eaton vendor is required. Non-segregated busway typically requires more layout consideration than Powerway III. 5000A connection maximum is currently available. Contact the factory for applications requiring >5000A busway connections. Contact the factory when aluminum busway is requested.
7 Breaker Tab Guide All breaker control voltages may be pre-selected by settings on the wiring tab. If control voltages are known, they should be set prior to populating breakers. Otherwise, the default setting is 120VAC, or 120VAC/DC for dual rated accessories. Motor, spring release, spring charge light applicable to EO breakers only. If second shunt trip is required, a maximum of 4a/4b aux contacts are available. Undervoltage (UVR) accessory is typically used for special applications, such as for E-Stop circuits or generator breaker applications. If spec requires an undervoltage trip, an 1150 trip unit with UPS or DC control should be considered in lieu of selecting UVR accessory. Latch check options provides indication that breaker is charged and trip latch is not engaged, or may prevent close signal from being applied until breaker is ready to close. Consult breaker IL for further details. Standard control switch and LED type is Eaton E34. When target and/or pistol grip switches are required per spec, W2 selection may be used for pricing purposes. In these cases (whenever possible), it should be noted in spec clarification that Electroswitch series 20 or 31 is preferred. W2 or Series 24 will not fit in breaker secondary compartment and require separate instrument compartment mounting space. Status lights may be selected for LED indication with MO breakers, or EO breakers with only remote open/close operation. White status LED supplied above breaker when selected. LED and remote contact supplied breaker when selected. These options typically auto-populated by other field selections. When selected in conjunction with UVR, includes separate instrument compartment (din rail) time delay module with selectable values of.1,.5, one and two seconds. Should only be used for specific applications. Indicator selection includes mechanical pop-out flag only. Select indicator with 2-Form C contacts, when local LED or remote overcurrent trip indication is required, or for any applications requiring multiple breaker interlocking. Set auxiliary contacts per specification requirements. For multiple breaker interlocking applications, 6a/6b contacts should be used. Set cell switch contacts per specification requirements. For multiple breaker interlocking applications, select 8-Form C cell switch contacts. Selectable when called for per specification requirements. Adds E34 2-position switch with padlockable cover and 30mm blue LED (located in compartment above corresponding breaker). Adds interposing relay in breaker wire way for remote activation of ARMS and local 30mm blue LED (located in compartment above corresponding breaker). Optional selection for EO breakers which are interlocked, or when pb close / open operation needs to be inhibited or padlocked out. Kirk is the default (and preferred) vendor for key lock when required. Note that key lock / cylinder assembly is cassette mounted in LVA assemblies (not breaker mounted). Only selectable when small remote control box is checked from the options tab. Includes wired receptacle for remote plug in in secondary compartment above corresponding breaker. If selected, trip units will be factory wired for zone interlock. Default selection for electrically interlocked breakers. Includes steel block plate over manual close pushbutton. Contact the factory if these selections need to be altered. Mechanical counter. Select when required per specification.
8 Eaton 1000 Eaton Boulevard Cleveland, OH United States Eaton.com 2015 Eaton All Rights Reserved Printed in USA October 2015 Eaton is a registered trademark. All other trademarks are property of their respective owners.
Submit shop drawings for equipment provided under this section Shop drawings shall indicate:
Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,
More informationUNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation
Basis of Design This section applies to the design relating to low voltage switchboards. Design Criteria UW Class N1 facilities main switchboards shall be rear accessible. The main, tie and feeder breakers
More informationFFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid
Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars Presented By: Greg Pelster & Robert Schmid FFI Ferrie, Franzmann Industries LOW VOLTAGE SWITCHGEAR & LOW VOLTAGE
More informationSWITCHGEAR Section 16. SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less.
PART 1 - GENERAL SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less. RELATED SECTIONS Division 16 Section "Basic Electrical Materials and Methods" for general
More informationSample - No Commercial Use
COMPLETE REVISION October 2010 Electrical PIP ELSSG01 Design and Fabrication of Low-Voltage Metal-Enclosed AC Power Circuit Breaker Switchgear PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort
More informationMasterclad Medium Voltage Passive Arc-Resistant Switchgear
Masterclad Medium Voltage Passive Arc-Resistant Switchgear Square D Masterclad medium voltage passive arc-resistant (AR) switchgear is designed with utilities and industrial customers in mind who demand
More informationSecondary Unit Substations
14 SWITCHGEAR Secondary Unit Substations Overview Siemens offers a wide variety of unit substation designs to meet customer requirements. A unit substation consists of one or more transformers mechanically
More informationSWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS. Presented by SAI Advanced Power Solutions
SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS POWER DISTRIBUTION RACKS IN A MISSION CRITICAL SYSTEM MODULES IN A MISSION CRITICAL SYSTEM UPS Convertor Main Inverter Load Battery BPC UPS & BATTERY
More information8146/5 Series Breaker Panelboards
8146/5 Series Breaker Panelboards DISTRIBUTION BREAKER PANELBOARDS FOR HAZARDOUS & CORROSIVE ENVIRONMENTS Breaker Panels Features: Wide variety of Flameproof branch circuit breakers for Zone 1 & Division
More information2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.
2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to
More informationQUESTIONS and ANSWERS RFB 745-15-9894, Metal Clad Switchgear and Power Control Room
QUESTIONS and ANSWERS RFB 745-15-9894, Metal Clad Switchgear and Power Control Room 1) When you click on the UTHSCSA Drawing the site takes you to the E-1 drawing no other. Will there be other drawings
More informationCircuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services
Circuit Breakers and Switchgear Thomas Greer Director of Engineering TLG Services Presentation Outline Switchgear Definition Overcurrent Protection Devices Circuit Breaker Trip Curves and Coordination
More informationThe following components are common to most cubicles; this example is an ABB HK cubicle.
4.0 CIRCUIT BREAKER CUBICLE Learning Objectives The circuit breaker cubicle is the component of the switchgear that holds the circuit breaker, and the controls and cabling for the distribution system.
More informationDecision-Maker Paralleling System. Power Distribution Switchboards and Circuit Breakers. Standard Features
Decision-Maker Paralleling System Power Distribution Switchboards and Circuit Breakers Power Distribution Switchboards and Circuit Breakers The generator paralleling circuit breakers for the Kohler Decision-Maker
More informationSECTION 16346A METAL-CLAD MEDIUM VOLTAGE ARC RESISTANT SWITCHGEAR
METAL-CLAD MEDIUM VOLTAGE ARC RESISTANT SWITCHGEAR PART 1 GENERAL 1.01 SCOPE A. The Contractor shall furnish and install the equipment as specified herein and as shown on the contract drawings. 1.02 RELATED
More informationBolted contact switches. Pringle switches
Bolted contact switches Pringle switches Eaton s Pringle bolted contact switches History Eaton s PringleT switches have helped pioneer the development of high-quality electrical products for commercial
More informationSECTION 16426C ARC RESISTANT DRAWOUT SWITCHGEAR (MAGNUM DS) LOW VOLTAGE
ARC RESISTANT DRAWOUT SWITCHGEAR (MAGNUM DS) LOW VOLTAGE PART 1 GENERAL 1.01 1.02 1.03 1.04 SCOPE The Contractor shall furnish and install, where indicated on the drawings, a deadfront type, arc resistant
More informationBERTHOLD ELECTRIC GENERATOR CONNECTION CABINET
BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET Berthold Electric Company s Generator Connection Cabinet provides a quick and convenient station to connect a portable generator to a facility s main service
More informationSECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL
SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL 1.1 SUMMARY A. This section describes the requirements for the installation of Power Monitors and associated
More informationTmax MCCBs. Molded case circuit breakers. Tmax
Molded case circuit breakers Introduction ABB is once again demonstrating its commitment to new product development and its superiority in product performance. Never before has the industry seen such high
More informationPrimary and Secondary Electrical Distribution Systems
Primary and Secondary Electrical Distribution Systems Critical Facilities Round Table 12th Quarterly Membership Meeting June 2, 2006 David D. Roybal. P.E. Eaton Electrical Cutler-Hammer Products Utility
More informationArc Terminator Active Arc-Resistant Switchgear
Arc Terminator Active Arc-Resistant Switchgear Increasing safety and productivity by extinguishing internal arcing faults within the switchgear. The Square D Arc Terminator from Schneider Electric offers
More informationPIP ELSSG02 Design and Fabrication of Medium Voltage Metal-Clad Switchgear from 4.76 kv to 38 kv
Electrical Design and Fabrication of Medium Voltage Metal-Clad Switchgear from 4.76 kv to 38 kv Table of Contents 1. Introduction...2 1.1 Purpose... 2 1.2 Scope... 2 2. References...2 2.1... 2 2.2 Industry
More informationInstructions for Magnum DS T
Instructions for Magnum DS T Contents Description Page 1: Introduction............................ 3 2: Receiving, Handling, and Storage........... 4 3: Equipment Description................... 8 4: Installation............................
More informationHow To Test A Power Switch On A Power Supply
transfer switches Soft load Innovative, reliable, integrated solution Built with years of experience Powered with innovation Delivered with reliability A history of experience, innovation and reliability
More informationIntroduction. Upon completion of Basics of Switchboards you should be able to: Explain the role of switchboards in a distribution system
Table of Contents Introduction... 2 Distribution Systems... 4 Switchboard Definition... 9 Switchboard Construction... 12 Service Entrance Equipment... 18 Service Section... 20 Switchboard Grounding...
More informationMEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4
CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,
More informationMCC Ratings. Voltage Rating
MCC Ratings In addition to the various ratings of individual components used in motor control centers, the overall ratings of the motor control center must also be considered. Voltage Rating Motor control
More informationIRRIGATION PUMPING Table of Contents - Section 900
IRRIGATION PUMPING Table of Contents - Section 900 PARAGRAPH 900.1 GENERAL 1 900.2 METERING REQUIREMENTS 1 900.3 CUSTOMER S CONTROL EQUIPMENT 2 900.4 SERVICE CONDUCTOR REQUIREMENTS 2 900.5 RECOMMENDATIONS
More informationSENTRON Switching and Protection Devices Air Circuit Breakers
Siemens AG 9 SENTRON Switching and rotection Devices Air Circuit reakers 5 5/ Introduction 3WL Air Circuit reakers 3WL Air Circuit reakers/ Non-Automatic Air Circuit reakers up to 63 A (AC) 5/6 General
More informationSuitable for Emergency, Peak and Prime Power System Applications. Low Voltage Automatic Transfer Switch Systems
Suitable for Emergency, Peak and Prime Power System Applications Low Voltage Automatic Transfer Switch Systems THE POWER AUTHORITY THE POWER AUTHORITY ASCO s experience and commitment to excellence in
More information01.4IB.51200B PowlVac-AR Arc Resistant Switchgear. 5kV & 15kV 1200A, 2000A, 3000A, & 4000A Forced Cooled. Powered by Safety
PowlVac-AR Arc Resistant Switchgear 1200A, 2000A, 3000A, & 4000A Forced Cooled Powered by Safety PowlVac-AR Arc Resistant Switchgear 01.4IB.51200B Contact Information Powell Electrical Systems, Inc. www.powellind.com
More informationSURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC INTEGRATED SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671A SECTION 16671A
SURGE PROTECTIVE DEVICES (SPDs) INTEGRATED UNITS LOW VOLTAGE AC SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS PART 1 GENERAL 01 02 03 SCOPE The Contractor shall furnish and install the Surge Protective
More informationLV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE
LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE 380/415/690 Volt AC 50/65/80/100 ka 1. Product Guide Low Voltage Motor Control Centre CONTSTRUCTION Continuous "poured in place" gasket
More informationLearning Module 13: Panelboards and Switchboards. 101 Basic Series
Learning Module 13: Panelboards and Switchboards 101 Basic Series What You Will Learn We ll step through each of these topics in detail: Introduction 4 Definitions 4 Similarities Between Panelboards and
More informationDoc Ref: 2015.06.01.002. 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC
TM 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC TM D400E Data Module (60Hz) The EDGE D400E is designed to meet high power density requirements for both the HPC and Web Scale environments while
More information3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance
SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132
More informationSentron Series Circuit Breakers
Sentron Series Circuit Breakers Siemens Sentron Series circuit breakers are available in nine frame sizes: ED, FD, JD, LD, LMD, MD, ND, PD, and RD. Sentron Series circuit breakers have a wide range of
More informationDead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms
Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms ABB innovations for changing demands ABB (www.abb.com) is a leader in power and automation technologies that enables utility
More informationLow voltage Direct Current Network. Compact NSX DC PV. Circuit breakers and switch disconnectors for solar application.
Low voltage Direct Current Network Compact NSX DC PV Circuit breakers and switch disconnectors for solar application Catalogue 2012 Compact NSX DC PV A complete DC offer for solar application from 80
More informationCAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH
CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH Cat transfer switches are designed for a variety of standby power applications. They provide flexibility, reliability and value in a
More informationMasterpact NW Circuit breakers and switch-disconnectors from 800 to 6300 A
Low voltage electrical distribution Masterpact NW Circuit breakers and switch-disconnectors from 800 to 6300 A User manual 09/2009 User manual for circuit breakers and switch-disconnectors Masterpact
More informationInstallation Instructions
H5HK Series Installation Instructions 3 Phase Electric Heater Kits 7.5 and 0 TON Package A/C Systems Description Installation of 08/40V and 480V H5HK 3 Phase Heater Kits in 7.5 and 0 TON Packaged Air Conditioners.
More informationBussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1
How to configure Part Numbers: Step : Select Switch Amperage Power Module Switch Rating (Amps) Power Module Switch Catalog No. 30 3 60 6 00 200 2 400 4 Step 2: Select Options Needed 5 Bussmann Power Module
More informationUnit substation solutions with type SIMOSEC primary switches quick reference guide E50001-F710-A389-X-4A00. Answers for energy.
Unit substation solutions with type SIMOSEC primary switches quick reference guide E50001-F710-A389-X-4A00 Answers for energy. Unit substation solution with type SIMOSEC primary switches, dry-type transformer
More informationExtend the Life of Existing Switchgear
Extend the Life of Existing Switchgear January 2011/1910DB1002 by Hal Theobald, Product Manager Schneider Electric USA, Inc. Make the most of your energy SM Summary Introduction... p 3 Maintenance Requirements...
More informationReverse-feed applications for circuit breakers
Technical Publication PU01200001E Contents Description Page Intoduction.......................................................................... 2 breaker classifications..........................................................
More informationUnified requirements for systems with voltages above 1 kv up to 15 kv
(1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to
More informationContents. Description. Product Selection Guide
.1 Medium Voltage Switchgear Introduction Indoor Type VCP-W Metal-Clad Switchgear Assembly (5/15 kv shown) Product Selection Guide Product Offering Chart Metal-Enclosed Contents Description Notes Additional
More informationA. Shop Drawing submittals shall include, but not be limited to, the following:
SECTION 26 05 53 IDENTIFICATION FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical
More informationDistribution Dry Type Transformers
8 TRASFORMERS Distribution Dry Type Transformers Table (Contact Sales office for List Price) (commonly used) 1a. 115 C Rise F 1b. 80 C Rise B 4. Wall Brackets1 W 6. Low noise XdB below std. LX Type bg
More informationMini Power-Zone Unit Substation
Catalog 7440CT0901 2009 Class 7440 CONTENTS Description............................................. Page Product Description...........................................2 General Information...........................................3
More informationEnhancing Personnel Safety with Arc Resistant Equipment
Enhancing Personnel Safety with Arc Resistant Equipment Carl Christian Power LV Offer Marketing Nashville, TN Sponsored by the Water Wastewater Competency Center 1 Enhancing Personnel Safety 5-10 Five
More informationSURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC EXTERNAL SIDEMOUNT SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671B SECTION 16671B
SURGE PROTECTIVE DEVICES (SPDs) EXTERNAL SIDEMOUNT UNITS LOW VOLTAGE AC SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION PART 1 GENERAL 01 02 03 SCOPE The Contractor shall furnish and install the Surge Protective
More informationCabinets 101: Configuring A Network Or Server Cabinet
Cabinets 101: Configuring A Network Or Server Cabinet North, South and Central America White Paper May 2012 www.commscope.com Contents Background Information 3 What is a network or server cabinet? 3 What
More informationGenerator DoCKInG StatIonS
Generator DOCKING STATIONS TRYSTAR Portable Power Cable Cam to cam cable extensions 2000V, 100A-400A rated to NEC table 400.5 (B) All portable power cable sold is highly flexible and UL & C-UL or CSA Listed
More informationINDUSTRIAL AND COMMERCIAL SERVICE TRANSFORMER & METERING INSTALLATION SPECIFICATION
INDUSTRIAL AND COMMERCIAL SERVICE TRANSFORMER & METERING INSTALLATION SPECIFICATION February 2013 NOTE: If conflict exists between St. Thomas Energy s Conditions of Service and this document, the Conditions
More informationRoof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS
Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS Ducted System RECORD THIS UNIT INFORMATION FOR FUTURE REFERENCE: Model Number: Serial Number: Date Purchased: This manual must be read and
More informationMini Power-Zone Unit Substation Product Description. Product Description. Features. Typical Applications
Product Description Product Description The Mini Power-Zone Unit Substation from Schneider Electric is a miniaturized version of our Power-Zone Unit Substation. Included are: Circuit Breaker Sealed Step-Down
More informationMiniature Circuit Breakers and Supplementary Protectors
Miniature Circuit Breakers and Supplementary Protectors Miniature Circuit Breakers and Supplementary Protectors. Industrial Circuit Breakers QUICKLAG............................................. QUICKLAG
More informationDimensions, Inches (mm) No. of Poles Width Height Depth 2, 3 8.25 (210) 16 (407) 5.5 (140) 4 11.125 (283) 16 (407) 5.5 (140)
9-10N Supersedes Selection Data 9-10N, pages, 1-, dated dated March March 1995 1995 Mailed to: E, D, C/9-100A, 31-A, INTERRUPTING CAPACITY RATINGS IEC 947- Interrupting Capacity s➀ Interrupting Capacity
More informationPart 1 System Modeling & Studies for Existing Systems
Part 1 System Modeling & Studies for Existing Systems Operation Technology, Inc. Copyright 2009 Result of rapid release of energy due to an arcing fault between two conductors. Bus voltages > 208V Temperatures
More informationEaton Safety & Reliability Solutions in the Oil & Gas Industry Electrical
Eaton Safety & Reliability Solutions in the Oil & Gas Industry Electrical Victor Lee Commercial Marketing Manager SEA Eaton Oil & Gas Solution Tech Day 2013 Eaton. All Rights Reserved. Eaton is a leading
More informationSUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches
SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches PART 1 GENERAL 1.01 Scope Optional Standby Power Generator Systems A. Furnish and install automatic transfer switches
More informationPower-Zone 4 Arc Resistant Low Voltage Switchgear
Power-Zone 4 Arc Resistant Low Voltage Switchgear with ArcBlok Technology Make the most of your energy SM Workplace safety 2 I Power-Zone 4 Arc Resistant Low Voltage Switchgear Five to ten arc flash explosions
More informationPRODUCT GUIDE. SL Medium Voltage IEC Vacuum Contactors
PRODUCT GUIDE SL Medium Voltage IEC Vacuum Contactors Table of Contents 1 Overview Introduction....................................................2 Features........................................................2
More informationA Comparison of Contemporary Electrical Distribution Equipment Standards. San Francisco IEEE Industry Applications Society May 26, 2009
A Comparison of Contemporary Electrical Distribution Equipment Standards San Francisco IEEE Industry Applications Society May 26, 2009 What are Standards? Clearly defined performance characteristics Based
More informationMedium voltage VCP-W MR2 (integral racking)
Supersedes March 2013 Contents Description Page Notices and warnings...................... 2 Introduction.............................. 3 Breaker pan configurations.................. 3 Inspection/maintenance.....................
More informationSHORE POWER. Safely Connecting Ships to Shore SAFETY QUALITY INNOVATION VALUE CUSTOMER SERVICE
SHORE POWER Safely Connecting Ships to Shore SHIP-TO-SHORE SOLUTIONS FOR MILITARY & COMMERCIAL APPLICATIONS SAFETY QUALITY INNOVATION VALUE CUSTOMER SERVICE ESL Power Systems, Inc. ESL has established
More informationAll work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.
DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,
More informationINSTALLATION INSTRUCTIONS
LIGHTING CONTROL PANELS 4 AND 8 RELAYS INSTALLATION INSTRUCTIONS INSTALLATION OVERVIEW The installation instructions contained in this document are provided as a guide for proper and reliable installation.
More informationInstructions for Eaton 7.2kV AMPGARD Arc Resistant Motor Control Centers
Contents Description Page 1. Introduction............................ 2 2. Receiving, Handling, and Storing........... 4 3. Installation............................ 5 4. Plenum and Duct Installation.............
More informationMedium Voltage Products. ZN1 12 kv arc-proof air-insulated switchgear for primary distribution
Medium Voltage Products ZN1 12 kv arc-proof air-insulated switchgear for primary distribution ZN1 an innovative switchgear for power distribution requirements ABB ZN1 primary distribution switchgear is
More informationHow To Get A Power Line Extension
GUIDELINES FOR COMMERCIAL ELECTRIC SERVICE HOOKUP 1 Steps to Commercial Service Pay the Design Deposit Commercial Buildings: Up to 1, sq ft = $1,. 1, 5, sq ft = $2,. Over 5, sq ft = $3,. Commercial jobs
More informationLow Voltage Switchgear
Arc Resistant Switchgear n Insulated and isolated bus n Separation barriers and top venting n Breaker shutters 12 SWITCHGEAR Arc resistant metal-enclosed low voltage switchgear is an optional product offering
More informationCircuit Breakers. Next Generation of Protection Capabilities
Circuit Breakers Next Generation of Protection Capabilities Circuit Breaker Offering Rockwell Automation offers a full line of Allen-Bradley circuit breakers and motor protection devices to help meet many
More informationELEKTROTEHNI KO PODJETJE Leskoπkova cesta 12, 1000 Ljubljana, SLOVENIA
MRO Modularne Razdelilne Omare d.o.o. ELEKTROTEHNI KO PODJETJE Leskoπkova cesta 2, 000 Ljubljana, LOVENIA MC GENERAL When to use? MC - modular switchgear cabinets are type-tested, factory built switchgears,
More informationHVL 5 38 kv Load Interrupter Switchgear. The Standard for Performance, Protection and Dependability
HVL 5 38 kv Load Interrupter Switchgear The Standard for Performance, Protection and Dependability For a generation of engineers, Square D High Voltage Load (HVL ) Interrupter Switchgear by Schneider Electric
More informationELECTRIC METERING COMMERCIAL & INDUSTRIAL
ELECTRIC METERING COMMERCIAL & 1.0 INDEX 1.0 INDEX 2.0 SCOPE 3.0 GENERAL REQUIREMENTS 4.0 METER LOCATIONS 5.0 UNDERGROUND TERMINATIONS 6.0 METERING TRANSFORMER ENCLOSURES 7.0 SINGLE CUSTOMER METER INSTALLATIONS
More informationMasterclad 5 15 kv Arc Resistant Metal-Clad Indoor Switchgear
Masterclad 5 15 kv Arc Resistant Metal-Clad Indoor Switchgear Class 6055 Instruction Bulletin 6055-62 06/2012 Retain for future use. Hazard Categories and Special Symbols Read these instructions carefully
More informatione 2 ALPHA Medium Voltage Switchgear Data Sheet K-1.1.2 EN
e 2 ALPHA Medium Voltage Switchgear Data Sheet K-1.1.2 EN We create ideas with power! ELEKTROMETAL ENERGETYKA SA is a new Polish company providing solutions for electrical power engineering. Our services
More informationEngineers Edge, LLC PDH & Professional Training
510 N. Crosslane Rd. Monroe, Georgia 30656 (770) 266-6915 fax (678) 643-1758 Engineers Edge, LLC PDH & Professional Training Copyright, All Rights Reserved Engineers Edge, LLC An Introduction to Interior
More informationGE Power Controls. MiniFORM Switchboards
GE Power Controls MiniFORM Switchboards MiniFORM MiniFORM MiniFORM switchboards Arrangement Modules Arrangement modules 1-6 6 Arrangement modules 7-12 7 Arrangement modules 12-14 8 Arrangement modules
More informationDATA CENTER UNIQUE CHARACTERISTICS AND THE ROLE OF MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS
DATA CENTER UNIQUE CHARACTERISTICS AND THE ROLE OF MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS ABSTRACT Data Centers are a critical part of the world economic systems. Billions of electronic transactions happen
More informationPower IT MV Air Insulated Switchgear. Technical Information and Application Guide Featuring Advance TM and SafeGear TM Technology
Power IT MV Air Insulated Switchgear Technical Information and Application Guide Featuring Advance TM and SafeGear TM Technology Introduction Millions of ABB circuit breakers are installed and operating
More informationIZM ACB/Circuit-breakers. Robust safety. Extract from Main Catalogue HPL2010 IZM26 Circuit-breakers IN26 Switch-disconnectors
IZM ACB/Circuit-breakers Robust safety Extract from Main Catalogue HPL2010 IZM26 Circuit-breakers IN26 Switch-disconnectors t [s] 0.1 0.05 0.04 0.03 0.02 0.01 20 1230DIA-125 (70C1043) 30 40 50 60 80 100
More informationTP-C2 Motor Operator CLEAVELAND / PRICE INC. Bulletin DB-111B12
Bulletin DB-111B12 TP-C2 Motor Operator CLEAVELAND / PRICE INC. 14000 Rt. 993, Trafford, PA 15085 (724) 864-4177 FAX (724) 864-9040 Email: sales@cleavelandprice.com Cleaveland/Price Type TP-C2 Motor Operator
More informationOVR-3SP Recloser with PCD Control Style Guide 1VAL263901-SG March 30, 2009 Revision B
OVR-3SP Recloser with PCD Control Style Guide 1VAL263901-SG March 30, 2009 Revision B The OVR-3SP three-phase recloser style guide aids in the proper selection of your OVR-3SP style number. The OVR-3SP
More informationEaton s E-Series protective relay family
E-Series protective relays Feeder distribution relays Motor relays Transformer relays Generator relays Eaton s E-Series protective relay family Microprocessor-based design Eaton s E-Series relay family
More informationAtlanta Chapter IEEE Industry Applications Society
Atlanta Chapter IEEE Industry Applications Society Electrical Equipment Room Design Considerations presented at the Sheraton Buckhead Hotel Atlanta, Georgia November 20, 2006 Outline 1. Definitions 2.
More informationBypass transfer switch mechanisms
Power topic #6013 Technical information from Cummins Power Generation transfer switch mechanisms > White paper By Gary Olson, Director, Power Systems Development This paper describes the configuration
More information-1- SPECIFICATIONS 002085 CONE SETTER PLATFORM ATTACHMENT INDEX
-1-002085 CONE SETTER PLATFORM ATTACHMENT INDEX I. GENERAL EQUIPMENT : A. Intent Statement B. Cone Setter Platform II. III. 1. Understructure Frame 2. Mounting Components 3. Paint 4. Basket 5. Labels 6.
More informationAlternate Methods to Short Circuit Breaker Coordination
Alternate Methods to Short Circuit Breaker Coordination Nguyen Perez, PE Senior Electrical Engineer 2600 Douglas Road, Suite 301 Coral Gables, Florida 305.529.1515 (p) www.brplusa.com Importance in Healthcare
More informationTop Commercial / Residential Electrical Requirements *
Department of Community Development Building Division 4800 West 92 nd Avenue Westminster, Colorado 80031 For Information call (303) 658-2075 Fax (303) 706-3922 www.westminsterpermits.com Top Commercial
More informationPower Plant Electrical Distribution Systems
PDH Course E184 Power Plant Electrical Distribution Systems Gary W Castleberry, PE 2008 PDH Center 2410 Dakota Lakes Drive Herndon, VA 20171-2995 Phone: 703-478-6833 Fax: 703-481-9535 www.pdhcenter.com
More informationCurrent valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw
4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and
More informationSpecification Guide. for RVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers
Specification Guide for RVAC Direct Replacement AC Medium Voltage Circuit Breakers Table of Contents 1.0 General Work Scope...3 2.0 Standards...3 3.0 Supplier Qualifications...4 4.0 Circuit Breaker Element
More informationGROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL 34471 (352) 629-8421; FAX: (352) 629-8264
BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS Building Code compliance is the obligation of design professionals and/or contractors. Plan Review and Inspection Guidelines are intended to be used
More informationSECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS
SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS PART 1 - GENERAL 1.01 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section
More informationUniGear ZS1. Medium voltage, arc proof, air insulated switchgear for primary distribution
UniGear ZS1 Medium voltage, arc proof, air insulated switchgear for primary distribution UniGear ZS1: an innovative solution for all installation requirements ABB UniGear is medium voltage metal-clad,
More information