Installation Effects Upon Alien Crosstalk and Equal Level Far End Crosstalk

Size: px
Start display at page:

Download "Installation Effects Upon Alien Crosstalk and Equal Level Far End Crosstalk"

Transcription

1 Installation Effects Upon Alien Crosstalk and Equal Level Far End Crosstalk Paul Vanderlaan Product Development Engineer Belden Presented at BICSI January 20, 1999 Introduction New Parameters involving category 5 cabling have recently been introduced and are currently under development in the standards committee. Several parameters will be specified and regulated in an attempt to assure the end user that the installed system will perform as designed. Three documents are currently in draft status. They are presently identified as the TSB-95 for Category 5, TIA/EIA 568A Addendum-5, and the recently released TIA/EIA 568A Addendum-3. This presentation covers the new parameters Power Sum Near-End Crosstalk (PS-NEXT), Equal Level Far-End Crosstalk (ELFEXT), and Powersum Equal Level Far- End crosstalk (PS-ELFEXT). Additionally, Alien crosstalk will be discussed and the effect various bundling techniques have upon the parameter. Various methods of bundling cables via binders, cinch ties, and conduit will evaluated. Finally, recommendations will be provided to minimize possible cable damage while maximizing LAN performance, if bundled cables are employed in the installation. Near-End Crosstalk : Past and Present Near-end crosstalk (NEXT) is simply defined as the unwanted signal coupling from a near-end transmitter into a pair measured at the same end. In the case of Figure 1, the signal is transmitted on orange pair. The coupled power, as indicated by the orange wave, is measured at the same end on the blue pair. Near End Crosstalk (NEXT)

2 Figure 1 Category 5 cables were originally specified in the ANSI/TIA/EIA-568-A document. This document was originally intended to assure that 2 pair networks (one transmitting pair, one receiving pair) would perform to their intended levels. However, with the creation of new encoding schemes utilizing all four pairs for data transmission, there is now a need to characterize and limit the crosstalk from more than one pair. This additional parameter is known as Powersum Near-End Crosstalk (PS-NEXT). It is defined in proposed TIA/EIA 568A Addendum-5 as the computation of the unwanted signal coupling from multiple transmitters at the near-end into a pair measured at the near-end. In the case of Figure 2, the signals are transmitted on orange, green and brown pairs. The coupled power, as indicated by the three orange waves, is measured at the same end on the blue pair. Power Sum Near End Crosstalk (PS-NEXT)

3 Figure 2 This is important in such systems such as Gigabit Ethernet or 100BaseT4 systems, which utilize all four pairs for the transmission of data. Figure 3 is an example of a NEXT trace of a 100-meter sample of cable as measured on an analyzer. The three combinations of orange/blue, green/blue and brown/blue are represented by the green, blue, and black traces respectively. The calculated PS-NEXT performance is indicated by the red trace. Note that the red trace is always higher due to the summation of the three traces from below. Power Sum Near End Crosstalk (PS-NEXT)

4 Figure 3 Far-End Crosstalk Far-end crosstalk (FEXT) is defined as a measure of the unwanted signal coupling from a transmitter at the near-end into a neighboring pair measured at the far-end. Figure 4 is the illustrated example. The signal is transmitted on the orange pair and the red arrow indicates the FEXT coupling. The FEXT level, indicated by the orange waveform, is reduced by attenuation as it travels down the blue pair. In old networks, each end of the cable had one transmitter and one receiver. Any information that coupled onto the adjacent pair was not important, for that pair, at the opposite end, was a dedicated transmitter not listening for transmitted data. However, newer systems utilizing bi-directional transmission schemes, have four transmitters and receivers at each end. Each pair end is sending and receiving data. It becomes necessary to limit the coupled noise from adjacent pairs to ensure data integrity. Far End Crosstalk (FEXT)

5 Figure 4 Figure 5 is an example of a FEXT trace of a 100-meter sample of cable as measured on an analyzer. The red arrow #1 indicates a smooth straight line of coupled FEXT. Since the attenuation at low frequencies is low, the line is almost straight. However, as the frequency increases, the signal level becomes affected by the attenuation of the pair. This is indicated by the gradual roll-off of the trace at the red arrow #2. It is apparent that the FEXT measurement is dependent on attenuation. This, in turn, makes the measurement length dependent as well. This can create field testing problems. Longer lengths of cable appear to exhibit better FEXT than short lengths. Therefore, a length independent measurement is needed to assure the performance of the channel. Far-End Crosstalk Trace

6 Figure 5 Equal Level Far-End Crosstalk Equal Level Far-End Crosstalk (ELFEXT) is defined as the measure of the unwanted signal coupling from a transmitter at the near-end into a neighboring pair measured at the far-end relative to the received signal level measured on that same pair. In simple terms, it puts the attenuation back into the FEXT signal. Figure 6 is the illustrated example. The signal is transmitted on the orange pair and the red arrow indicates the FEXT coupling. The FEXT level, indicated by the orange waveform, is reduced by attenuation as it travels down the blue pair. When the attenuation is removed from the measurement the resultant is a higher signal level as indicated by the yellow waveform. This is the calculated ELFEXT. Equal Level Far End Crosstalk (ELFEXT)

7 Figure 6 Figure 7 exhibits the components of ELFEXT. Arrow #1 indicates the FEXT coupling from the orange pair to the blue pair. Arrow # 2 indicated the attenuation characteristic of the blue pair. The equation is simple: ELFEXT= FEXT - Attenuation. The blue trace, indicated by arrow #3, is the resultant calculated ELFEXT. With the attenuation removed, the ELFEXT trace is very linear and smooth. FEXT - Attenuation = ELFEXT

8 Figure 7 Power Sum Equal Level Far-End Crosstalk Finally, the last parameter discussed is power sum equal level far-end crosstalk (PS-ELFEXT). It is defined as the computation of the unwanted signal coupling from multiple transmitters at the near-end into a pair measured at the far-end relative to the received signal level measured on that same pair. Similar to PS- NEXT this is merely the summation of the three combinations of ELFEXT into one trace. Figure 8 indicates the three coupled FEXT disturbances onto the blue pair. The orange waveforms are then summed, the attenuation of the pair removed, and the resultant yellow trace is the computed PS-ELFEXT. Power Sum Equal Level Far End Crosstalk (PS- ELFEXT) Cable Bundling and Alien Crosstalk Figure 8 Several questions have been raised recently as to the feasibility of bundling cables to speed the cable pulling process. Is bundling cables permitted within the ANSI/TIA/EIA-568-A? Can bundling cable degrade the cables' internal electrical performance? Can bundling cable reduce the potential LAN performance? Should you be concerned? The answer to all these questions is yes. Old Bundled Cable specifications Originally, the bundled cable specifications were vaguely specified in ANSI/TIA/EIA-568-A, Section 13.1 Hybrid Cables. This only addressed overall jacketed cable groups (e.g. 6 jacketed cables with an overall jacket) Assemblies wrapped with a binder or mylar tape were not covered and therefore exempt from the requirements. The document specified cable to cable NEXT as 6+10log(n) db, where n = number of cables

9 within the jacket assembly. This requirement was almost impossible to meet in cable counts higher than 3 cables. As an example, for two jacketed cables, the crosstalk from cable to cable was 9 db tighter than their respective internal NEXT specification. Six cables required a 13.9dB tighter NEXT specification. The high degree of difficulty in meeting these specifications in conjunction with the lack of a sound technological reason for the tight specification led to a more sensible approach. The new requirement is specified in the newly released ANSI/TIA/EIA 568-A-3 Addendum 3. This document creates a new definition to address wrapped or bound bundles of cables. It is aimed specifically at the manufacturers and assembly houses that generate this material. Currently, this document only addresses PS-NEXT from other cables in the assembly. Alien Crosstalk What is alien crosstalk and where is it regulated? There is no mention of alien crosstalk in any of the industry standards. The term alien crosstalk is not a recognized definition within the standards. Simply put, alien crosstalk is crosstalk noise from adjacent data cables as demonstrated in Figure 9. This phenomena falls under the TIA/EIA 568-A-3 Addendum 3, which addresses bundled cables' crosstalk performance. The requirement states that PS-NEXT from adjacent cables must be 3 db better than the cable's internal pair to pair requirements. This is an important parameter for network cards are unable to compensate for noise external to the cable so it is important to minimize the effects of adjacent cables. Alien Power Sum Near End Crosstalk (PSNEXT) Alien Near-End Crosstalk Testing Figure 9 In an attempt to generically characterize alien crosstalk performance, several bundling scenarios were examined. All cable samples were 100 meter, "high" performance category 5 cables. All samples were laid out and tested on the floor with bend radii well within the requirements of ANSI/TIA/EIA-568-A. Bundles of six cables were bound using various methods including: cabling and double wrapped with binders, cinched with plastic cinch ties, and pulled loosely into a 1 inch EMC conduit. The six cables in the conduit only represent a 22% fill factor. To more closely represent a typical 40% fill installation, 4 additional cables were pulled into the conduit and tested. Assemblies utilizing a type of mylar wrap were not considered due to the questionable ability to meet plenum smoke requirements.

10 Figure 10 is a picture of the cabled and bound sample. It is an attempt to simulate a neat assembly that might be provided by a manufacture or third party assembly house randomly selecting cables and bundling them in an aesthetically pleasing manner without regard to the impact of cable performance. Figure 10 Figure 11 represents a particular cable's internal performance before cabling. Figure 12 indicates the subunit performance after the assembly process. Notice the 100 MHz performance has deteriorated from over 10 db of NEXT margin to less than 1 db. The NEXT performance, for which the customer has paid a significant amount of money, has been lost. Cable NEXT Performance Before Binding Figure 11 Cable NEXT Performance After Binding

11 Figure 12 The alien, or cable to cable crosstalk, is depicted in Figure 13. The first red arrow indicates the specification for NEXT performance as specified in Addendum 3. It is 3 db tighter than the Category 5 specification. Arrows 2A and 2B indicate points of significant failure. The margin as indicated in the lower left hand corner is db. It is interesting to note that the NEXT from cable to cable actually exceeds Category 5 internal requirements. Not only has the process degraded the internal to the point of near failure, now there is crosstalk from the adjacent cable in excess of category 5 limits. Alien Power Sum NEXT Six Cables Double Bound

12 Cinch ties were used to bind the next sample. Figure 14 and 15 are provided to give an idea as to the frequency and tightness of the cinching. The sample was cinched every 48 inches in accordance with the minimum support distance in ANSI/TIA/EIA-569-A. The cinching slightly deformed the cables' jackets. Additionally, the cables were allowed to lie in their natural state. No attempt to spread the individual cables apart was made. Figure 16 indicates 4.6 db of margin to the Addendum-3 specification. Figure 14 Figure 15 Alien Power Sum NEXT Six Cables Cinched Every 48 Inches

13 Figure 16 The conduit samples consisted of six 100m cables pulled into approximately 280ft of 1 inch EMT conduit. This left 24 feet of exposed cable on each end of the sample under test. This was an attempt to simulate an installation with cable on each end representing patch cable going to the desktop and through the wiring closet. The conduit consisted of two 140ft straight runs connected at the far end by two 90 degree bends to form the shape of a 140 ft long letter U. Figure 17 represents the conduit at 22% fill. There is 3.5 db margin to the Addendum --3 specification. Alien Power Sum NEXT Six Cables - 22% Conduit Fill

14 Figure 17 When four more cables were pulled in to raise the fill factor to 40%, the margin dropped to 3.0 db. It is important to note that due to the intensive and lengthy measurements needed in the verification process, only the two worst performing cables in the 22% fill trial were remeasured and plotted. It is believed that this is a valid assumption since the cable to cable performance was approximately equal on an adjacent cable to cable basis. This being the case, it is not expected that the addition of 4 more cables would radically change the alien NEXT performance of any given cable. Figure 18 indicates that the alien NEXT performance dropped.5 db to a 3.0 db margin to the respective specification. Alien Power Sum NEXT Ten Cables - 40% Conduit Fill

15 Figure 18 Figure 19 is a summary of the margins for the respective bundling techniques. There are no surprises here in that the loosest bundled sample, the cinched bundle, exhibited the best alien crosstalk performance while the tightest, the cabled and double bound, exhibited the worst. However, it is possible that the deterioration of the individual cable's integrity, during the cabling assembly process, did exacerbate the alien NEXT failure. Alien Power Sum NEXT Margins to Addendum 3

16 Alien Equal Level Far End Crosstalk Testing Figure 19 Alien equal level far-end crosstalk (ELFEXT) is the same concept as mentioned earlier in the presentation. The only difference is the crosstalk is from cable to cable rather than pair to pair. Figure 20 illustrates this example. It is important to note that there is no current or proposed specification to regulate Alien ELFEXT. This was an attempt to characterize the performance and in no way indicates that any particular construction would pass or fail any future cable specification. The specification used for comparative purposes is the proposed category 5 Channel ELFEXT limit. Alien Power Sum Equal Level Far End Crosstalk (PS-ELFEXT) Figure 20 Figure 21 is the cabled and double bound sample. The margin as indicated is only.2 db to the channel specification. There is almost no margin left for connectors or any other installation effects. Figure 22, 23 and 24 represent the cinched, 22% filled conduit and 40% filled conduit. Alien Power Sum ELFEXT Six Cables Double Bound

17 Figure 21 Alien Power Sum ELFEXT Six Cables Cinched Every 48 Inches Figure 22 Alien Power Sum ELFEXT Six Cables - 22% Conduit Fill

18 Figure 23 Alien Power Sum ELFEXT Ten Cables - 40% Conduit Fill Figure 24 Figure 25's table summarizes the performance of the various assemblies. As expected the cabled and double bound assembly had the worst alien ELFEXT performance. However, the cinched assembly no longer has

19 the best performance. This may be due to the nature of ELFEXT, which depicts the coupling along the entire length of the cable unlike NEXT, which primarily represents only near end performance. The cinching of the ties may be producing periodic coupling, which is greater that that found in the cables enclosed loosely in conduit. Alien ELFEXT Margins to the Cat 5 Channel PS-ELFEXT Specification Conclusion Figure 25 There are new cable requirements, PS-NEXT, ELFEXT, and PS-ELFEXT which are under development or have been defined by Draft documents in TIA subcommittees. ANSI/TIA/EIA-568-A Addendum-3 specifically addresses the crosstalk from cable to cable, otherwise known as alien crosstalk. Cables are designed to meet their respective requirements. Care must be taken when cables are assembled by a third party. Unplanned twisting of the cable core can be detrimental to the internal performance. As an example, the cabled and double bound sample lost 10 db of internal crosstalk margin. Continuous tightly bound assemblies seem to have an inherent disadvantage for Alien crosstalk. The cabled and double bound sample failed Addendum -3 alien PS-NEXT by 4.5 db and only passed the category 5 channel PS-ELFEXT requirements by 0.2 db. Cinched cables appear to meet current requirements of alien PS-NEXT and exhibit good alien PS-ELFEXT, However, tight cinching may degrade the alien PS-ELFEXT at a higher rate than the alien PS-NEXT. Conduit does not appear to excessively degrade cable to cable performance. When compared to the cinched sample, the 22% filled conduit reduced alien PS-NEXT performance by 1.1 db but improved alien PS-ELFEXT performance by 1.9 db. The 40% filled conduit reduced the performance of alien PS-NEXT by 0.5 db but improved alien PS-ELFEXT by 1 db. It is important to realize that current generation hand held testers cannot verify alien crosstalk performance. In order to help assure maximum LAN performance bundled types of cable constructions should be avoided. If bundled assemblies are required, be sure to obtain the material from sources that have the capability to verify their finished assembly's performance to these new requirements.

Abstract: This document examines the alien NEXT performance of various bundled cables and measures the impact upon various networks performance.

Abstract: This document examines the alien NEXT performance of various bundled cables and measures the impact upon various networks performance. Title: Alien Crosstalk and Network Performance Source: Paul Vanderlaan Belden Electronics Division 2200 US Hwy 27 South Richmond, IN 47374 Phone (765)-983-5811 Fax (765)-983-5825 Email: Paul.Vanderlaan@belden.com

More information

Running 1000BASE-T Gigabit Ethernet over Copper Cabling 30 March 1999 Colin Mick/The Mick Group with Bruce Tolley/3Com and Willem Wery/Intel

Running 1000BASE-T Gigabit Ethernet over Copper Cabling 30 March 1999 Colin Mick/The Mick Group with Bruce Tolley/3Com and Willem Wery/Intel Running 1000BASE-T Gigabit Ethernet over Copper Cabling 30 March 1999 Colin Mick/The Mick Group with Bruce Tolley/3Com and Willem Wery/Intel Introduction When network managers decide on a cabling system,

More information

HIGH SPEED COMMUNICATIONS PLENUM CABLE CATEGORY 5e CMP FEP JACKETED, PVC-FREE UNSHIELDED TWISTED PAIR (UTP)

HIGH SPEED COMMUNICATIONS PLENUM CABLE CATEGORY 5e CMP FEP JACKETED, PVC-FREE UNSHIELDED TWISTED PAIR (UTP) Cable Specification Category 5e CMP HIGH SPEED COMMUNICATIONS PLENUM CABLE CATEGORY 5e CMP FEP JACKETED, PVC-FREE UNSHIELDED TWISTED PAIR (UTP) This cable specification complies with the electrical transmission

More information

Evolution of Cabling Standards TIA/EIA ISO/IEC CENELEC. by Paul Kish NORDX/CDT Chair TIA TR 41.8

Evolution of Cabling Standards TIA/EIA ISO/IEC CENELEC. by Paul Kish NORDX/CDT Chair TIA TR 41.8 Evolution of Cabling Standards TIA/EIA ISO/IEC CENELEC by Paul Kish NORDX/CDT Chair TIA TR 41.8 Outline Market trends Standards development where we were where we are where we are going Beyond Category

More information

ANSI/TIA/EIA - 568-A, Commercial Building Telecommunications Cabling Standard.

ANSI/TIA/EIA - 568-A, Commercial Building Telecommunications Cabling Standard. WIRING STANDARD INTRODUCTION This standard defines a telecommunications wiring system for North Dakota State Agencies, offices or buildings that will support a multi-product environment. The purpose of

More information

Gigabit Ethernet on Copper Cabling Infrastructures

Gigabit Ethernet on Copper Cabling Infrastructures Gigabit Ethernet on Copper Cabling Infrastructures Overview of Gigabit Ethernet (1000Base-T) Ethernet was developed by the Xerox Corporation in the early 1970 s and has emerged as the dominant networking

More information

The Evolution of Copper Cabling Systems from Cat5 to Cat5e to Cat6 Copper Cabling Standards and Technical Aspects

The Evolution of Copper Cabling Systems from Cat5 to Cat5e to Cat6 Copper Cabling Standards and Technical Aspects The Evolution of Copper Cabling Systems from Cat5 to Cat5e to Cat6 Copper Cabling Standards and Technical Aspects White Paper /7/0 Executive Summary Now that the TIA/EIA-568-B.- Category 6 Copper Cabling

More information

Enhanced Category 5 Cabling System Engineering for Performance

Enhanced Category 5 Cabling System Engineering for Performance Engineering for Performance Table of Contents 2 Introduction 2 Where Did It Come From? 2 Enhanced Category 5 Performance What to Test The Link The Channel Don t Forget the Cable Assembly 4 Performance

More information

Testing 10 Gb/s Performance of Category 6 and 6A Structured Copper Cabling Systems within the Unified Physical Infrastructure SM (UPI)

Testing 10 Gb/s Performance of Category 6 and 6A Structured Copper Cabling Systems within the Unified Physical Infrastructure SM (UPI) within the Unified Physical Infrastructure SM (UPI) www.panduit.com WP-11 April 2007 Introduction With the ratification of the IEEE 802.3an 10GBASE-T copper standard, end users now have more media options

More information

An Engineer s Guide to Full Compliance for CAT 6A Connecting Hardware

An Engineer s Guide to Full Compliance for CAT 6A Connecting Hardware for CAT 6A Connecting Hardware Written by: Antoine Pelletier Engineer, Global Cabling Products Intertek www.intertek-etlsemko.com 1-800-WORLDLAB Introduction The telecommunication industry recently achieved

More information

How to Choose the Right Cable Category

How to Choose the Right Cable Category How to Choose the Right Cable Category Why do I need a different category of cable? Not too long ago, when local area networks were being designed, each work area outlet typically consisted of one Category

More information

The Effect of Network Cabling on Bit Error Rate Performance. By Paul Kish NORDX/CDT

The Effect of Network Cabling on Bit Error Rate Performance. By Paul Kish NORDX/CDT The Effect of Network Cabling on Bit Error Rate Performance By Paul Kish NORDX/CDT Table of Contents Introduction... 2 Probability of Causing Errors... 3 Noise Sources Contributing to Errors... 4 Bit Error

More information

Understanding the Electrical Performance of Category Cables

Understanding the Electrical Performance of Category Cables Understanding the Electrical Performance of Category Cables By: Mike Levesque, Mike Karg & Himmeler Themistocle Obsessed with cable solutions. Understanding the Electrical Performance of Category Cables

More information

SYSTIMAX Copper Solutions Designed for the Digital Generation

SYSTIMAX Copper Solutions Designed for the Digital Generation SYSTIMAX Copper Solutions Designed for the Digital Generation SYSTIMAX Structured Connectivity Solutions www.systimax.com SYSTIMAX Solutions is the global leader in the enterprise cabling sector with a

More information

How To Get A Better Signal From A Fiber To A Coax Cable

How To Get A Better Signal From A Fiber To A Coax Cable Gigabit Transmission What s the Limit? Fanny Mlinarsky Page 1 What s the Limit? Speed Faster higher frequency higher attenuation less headroom Distance Longer higher attenuation more jitter less headroom

More information

The Permanent Link in Field Certification Reasons, Advantages, Testing Challenges

The Permanent Link in Field Certification Reasons, Advantages, Testing Challenges The Permanent Link in Field Certification Reasons, Advantages, Testing Challenges Table of contents Channel, Basic Link and Permanent Link defined....................... 2 Critical Performance Parameters......

More information

Total Solutions Verification

Total Solutions Verification Total Solutions Verification 3rd Party Electrical Performance Testing Author: Tom Boucino Applications Engineer Uniprise Solutions CommScope has always designed cables with connectivity in mind. Our engineers

More information

Planning for 10Gbps Ethernet over UTP Questions to Ask When Planning the Cabling Plant WHITE PAPER

Planning for 10Gbps Ethernet over UTP Questions to Ask When Planning the Cabling Plant WHITE PAPER Planning for 10Gbps Ethernet over UTP Questions to Ask When Planning the Cabling Plant WHITE PAPER Questions to Ask When Planning the Cabling Plant Planning a copper cabling plant to support 10Gbps transmission

More information

This paper will explain some of the more important factors on how UTP wires work; specifically it will cover the following:

This paper will explain some of the more important factors on how UTP wires work; specifically it will cover the following: UTP Technology In the late 1970s, unshielded twisted pair (UTP) cabling originated in the computer industry as a means of transmitting digital data over computer networks. This cable was designed to be

More information

GigaSPEED X10D Solution How

GigaSPEED X10D Solution How SYSTIMAX Solutions GigaSPEED X10D Solution How White Paper June 2009 www.commscope.com Contents Modal Decomposition Modeling and the Revolutionary 1 SYSTIMAX GigaSPEED X10D Performance MDM An Introduction

More information

ATT-TP-76440 Ethernet Copper Cable & Ethernet Copper Assembly Specification

ATT-TP-76440 Ethernet Copper Cable & Ethernet Copper Assembly Specification ATT-TP-76440 Ethernet Copper Cable & Ethernet Copper Assembly Specification Abstract Presented in this document are the standards to implement Electrical & Optical Ethernet components, cabling, connections,

More information

The Next Generation of Cable Technology. A technology primer from NORDX/CDT By, Eric d Allmen

The Next Generation of Cable Technology. A technology primer from NORDX/CDT By, Eric d Allmen A technology primer from NORDX/CDT By, Eric d Allmen Foreword The Telecommunications Industry Association (TIA) and the International Standards Organization (ISO/IEC) are actively engaged in the development

More information

White Paper: 10 Gigabit Ethernet over Twisted Pair Copper Systems

White Paper: 10 Gigabit Ethernet over Twisted Pair Copper Systems White Paper: 10 Gigabit Ethernet over Twisted Pair Copper Systems Asef Baddar, RCDD Principal Engineer / Applications Engineering Supervisor Leviton Network Solutions C/7 - #1928 Table of Contents Background

More information

Data Communications Competence Center

Data Communications Competence Center Importance of Cable Balance For Improving Noise Susceptibility Data Communications Competence Center DCCC03101702 July 11, 2007 Summary In a study of category 5e and category 6 UTP cables, a strong correlation

More information

Mixed High-Speed Ethernet Operations over Different Categories of Bundled UTP Cable

Mixed High-Speed Ethernet Operations over Different Categories of Bundled UTP Cable Mixed High-Speed Ethernet Operations over Different Categories of Bundled UTP Cable June 10, 2010 Contributors: Yinglin (Frank) Yang CommScope, Inc. Charles Seifert Ixia Ethernet Alliance 3855 SW 153 rd

More information

Communication, Signal & Data Cables

Communication, Signal & Data Cables Communication, Signal & Data Cables Used for indoor installation and interconnection of transmission, telephone, telegraph and electronic equipment as well as media equipments www.alfanar.com Communication

More information

Introduction to Digital Subscriber s Line (DSL)

Introduction to Digital Subscriber s Line (DSL) Introduction to Digital Subscriber s Line (DSL) Professor Fu Li, Ph.D., P.E. Chapter 3 DSL Fundementals BASIC CONCEPTS maximizes the transmission distance by use of modulation techniques but generally

More information

IT Cabling Solutions

IT Cabling Solutions IT Cabling Solutions Signamax & Hitachi Cable America System Performance Signamax & Hitachi Cable America (Hitachi) system quality assurance testing is based on the worst-case model - four-connector 100-meter

More information

COMMITTEE T1 TELECOMMUNICATIONS Working Group T1E1.4 (DSL Access) Costa Mesa, California, March 8 12, 1999

COMMITTEE T1 TELECOMMUNICATIONS Working Group T1E1.4 (DSL Access) Costa Mesa, California, March 8 12, 1999 COMMITTEE T1 TELECOMMUNICATIONS Working Group T1E1.4 (DSL Access) Costa Mesa, California, March 8 1, 1999 T1E1.4/99-16 CONTRIBUTION TITLE: SOURCE*: PROJECT: Proposal for an Improved Upstream FEXT Model

More information

Disclaimer This information is collected and composed by QUANG DUNG TECHNOLOGY from Cablingdb.com. All information is copyrighted by Cablingdb.com.

Disclaimer This information is collected and composed by QUANG DUNG TECHNOLOGY from Cablingdb.com. All information is copyrighted by Cablingdb.com. Commercial Building Telecommunications Cabling Standard Disclaimer This information is collected and composed by QUANG DUNG TECHNOLOGY from Cablingdb.com. All information is copyrighted by Cablingdb.com.

More information

Things You Must Know About Gigabit Ethernet 1. Understanding Gigabit Ethernet

Things You Must Know About Gigabit Ethernet 1. Understanding Gigabit Ethernet Things You Must Know About Gigabit Ethernet 1. Understanding Gigabit Ethernet Today s network managers know that modern demands on a network by its users can shrink bandwidth dramatically. Faster computers,

More information

PANDUIT TX6 10GIG SHIELDED COPPER CABLING SYSTEM. Innovative Connectivity Solution for Maximum Performance and Security

PANDUIT TX6 10GIG SHIELDED COPPER CABLING SYSTEM. Innovative Connectivity Solution for Maximum Performance and Security PANDUIT TX6 GIG SHIELDED COPPER CABLING SYSTEM Innovative Connectivity Solution for Maximum Performance and Security Gigabit Ethernet over Copper With ever increasing bandwidth requirements, advancements

More information

Cable Sharing in Commercial Building Environments

Cable Sharing in Commercial Building Environments Cable Sharing in Commercial Building Environments Reducing Cost, Simplifying Cable Management, and Converging Applications onto Twisted-Pair Media Cable sharing describes the practice of running more than

More information

CAT 5 Cable / RJ 45 Connectors and Making Cables for different connections

CAT 5 Cable / RJ 45 Connectors and Making Cables for different connections CAT 5 Cable / RJ 45 Connectors and Making Cables for different connections RJ 45: (RJ xx: telephone connection interfaces, registered with the FCC, the U.S. Federal Communications Commission.) Pins: When

More information

Chapter 4 Connecting to the Internet through an ISP

Chapter 4 Connecting to the Internet through an ISP Chapter 4 Connecting to the Internet through an ISP 1. According to Cisco what two things are essential to gaining access to the internet? a. ISPs are essential to gaining access to the Internet. b. No

More information

2 Network Media. Copper Core Cable

2 Network Media. Copper Core Cable Network Media Copper Core Cable After studying this chapter, you will be able to: Match the five forms of electronic signals to the media types on which they travel. Describe the major differences between

More information

advancing information transport systems advancing information transport systems

advancing information transport systems advancing information transport systems May/June BICSInews advancing information transport systems advancing information transport systems May/June 2008 2006 president s message 3 EXECUTIVE bicsi update DIRECTOR MESSAGE 4 6 bicsi update 35 course

More information

10 Gigabit Ethernet over copper: Unshielded, unprotected?

10 Gigabit Ethernet over copper: Unshielded, unprotected? Technical Article 10 Gigabit Ethernet over copper: Unshielded, unprotected? Copyright 2005 Reichle & De-Massari AG (R&M). All rights reserved. Transmission and reproduction of this publication or parts

More information

Discussion Paper Category 6 vs Category 5e Cabling Systems and Implications for Voice over IP Networks

Discussion Paper Category 6 vs Category 5e Cabling Systems and Implications for Voice over IP Networks Discussion Paper Category 6 vs Category 5e Cabling Systems and Implications for Voice over IP Networks By Galen Udell Belden CDT Networking 2006 Category 6 vs Category 5e Cabling Systems and Implications

More information

DIVISION 27 COMMUNICATIONS. A. System design shall be completed by a Registered Communications Distribution Designer (RCDD).

DIVISION 27 COMMUNICATIONS. A. System design shall be completed by a Registered Communications Distribution Designer (RCDD). DIVISION 27 COMMUNICATIONS 27 00 00 COMMUNICATIONS A. System design shall be completed by a Registered Communications Distribution Designer (RCDD). B. Comply with American National Standards Institute

More information

Network Engineers Everywhere:

Network Engineers Everywhere: Network Engineers Everywhere: Relax Your Minds Not Your Standards DataMax Commercial Ethernet Patch Cable The Strongest Link. DataMax Commercial Ethernet Patch Cable The Strongest Link. DataMax Patch Cable

More information

ANSI/TIA/EIA-570. 570-A A Revisited. Residential Telecommunications Cabling Standard (Draft 6/22/99) Larry L. Hamlin, RCDD

ANSI/TIA/EIA-570. 570-A A Revisited. Residential Telecommunications Cabling Standard (Draft 6/22/99) Larry L. Hamlin, RCDD BICS I CABLING INSTALLATION PROGRAM ANSI/TIA/EIA-570 Residential Telecommunications Cabling Standard (Draft 6/22/99) Larry L. Hamlin, RCDD Copyright BICSI, October 1999 -A Revisited 1.1 Purpose standardize

More information

Crestron CAT5 Wiring Reference Guide

Crestron CAT5 Wiring Reference Guide Crestron CAT5 Wiring Reference Guide This document was prepared and written by the Technical Documentation department at: Crestron Electronics, Inc. 15 Volvo Drive Rockleigh, NJ 07647 1-888-CRESTRON All

More information

Ethernet Patch Cord Wiring

Ethernet Patch Cord Wiring Ethernet Patch Cord Wiring C ONTENTS Ethernet Patch Cords & RJ-45 Connectors... 2 Ethernet Patch Cords and UTP Cabling... 3 What s all the twisting about?... 4 Ethernet Applications... 5 568A & 568B Wiring

More information

White Paper. Crestron 8G DigitalMedia Cable

White Paper. Crestron 8G DigitalMedia Cable White Paper Crestron 8G DigitalMedia Cable Table of contents A Higher Standard Introduction 3 Understanding category cable 4 How we measure cable 6 Network cable analyzer 6 HDBaseT-specific tools 7 Electrostatic

More information

CABLE TERMINATION BEST PRACTICES A guide to improved cable performance through proper termination and installation.

CABLE TERMINATION BEST PRACTICES A guide to improved cable performance through proper termination and installation. B E C A U S E Y O U R B U S I N E S S R U N S T H R O U G H U S CABLE TERMINATION BEST PRACTICES A guide to improved cable performance through proper termination and installation. Outstanding products

More information

1000BASE-T: Gigabit Ethernet. over Category. 5 copper. cabling. Acronyms and abbreviations

1000BASE-T: Gigabit Ethernet. over Category. 5 copper. cabling. Acronyms and abbreviations 1000BASE-T: Gigabit Ethernet over Category 5 copper cabling By Christopher T. Di Minico Acronyms and abbreviations ANSI American National Standards Institute BER Bit error rate DSL Digital subscriber line

More information

Cabling for 10GBASE-T and Beyond - A Tangled Web

Cabling for 10GBASE-T and Beyond - A Tangled Web Augmented Category 6 Category 6 A CLC TR 50173-99-1 TIA/EIA-TSB-155 TIA/EIA-568-B.2-10 ISO/IEC 11801 A1.1 Class E A Class F A ISO/IEC 11801 A1.2 Category 7 A ISO/IEC TR 24750 ISO/IEC 11801 Cabling for

More information

Innovative Connectivity Solution for Maximum Performance and Security

Innovative Connectivity Solution for Maximum Performance and Security Innovative Connectivity Solution for Maximum Performance and Security Financial Institutions Supports high performance backbone which enables transfer of real-time financial information through voice,

More information

Copper Patch Cords. Impact On Network Performance and Reliability

Copper Patch Cords. Impact On Network Performance and Reliability Copper Patch Cords Impact On Network Performance and Reliability 1 The Impact of Copper Patch Cords on Network Performance and Reliability As network infrastructures continue to have a higher impact on

More information

New Technology Developments and How They Impact Your Structured Wiring Choices

New Technology Developments and How They Impact Your Structured Wiring Choices New Technology Developments and How They Impact Your Structured Wiring Choices Author: Rob Wessels Vice President of Engineering Structured wiring has come a long way since the days when Category 3 and

More information

White Paper: What Component Compliance Means for CAT6A System Performance

White Paper: What Component Compliance Means for CAT6A System Performance White Paper: What Component Compliance Means for CAT6A System Performance Gary Bernstein, RCDD Director of Product Management Copper Systems Leviton Network Solutions Jeff Seefried Development Engineering

More information

Specification SFTP CAT6 Network Cable 23AWG CU

Specification SFTP CAT6 Network Cable 23AWG CU Specification SFTP CAT6 Network Cable 23AWG CU S/FTP CAT6 Shielded S/FTP PVC Cable 23AWG 4pair Solid, Wooden drum 1000 Grey CAT6 600MHZ CM Shielded (S/FTP) Solid Cable: Our CAT6 600MHZ Shielded (S/FTP)

More information

DIVISION 26 - ELECTRICAL SECTION 26 05 20 CABLES FOR INSTRUMENTATION

DIVISION 26 - ELECTRICAL SECTION 26 05 20 CABLES FOR INSTRUMENTATION DIVISION 26 - ELECTRICAL PART 1 - GENERAL 1.01 SUMMARY A. Section Includes 1. Instrumentation Cables 1.02 SUBMITTALS A. Submit in accordance with requirements of Section 01 33 00. B. Product Data: Submit

More information

HIGHSPEED ETHERNET THE NEED FOR SPEED. Jim Duran, Product Manager - Americas WHITE PAPER. Molex Premise Networks

HIGHSPEED ETHERNET THE NEED FOR SPEED. Jim Duran, Product Manager - Americas WHITE PAPER. Molex Premise Networks HIGHSPEED ETHERNET THE NEED FOR SPEED Jim Duran, Product Manager - Americas WHITE PAPER Molex Premise Networks EXECUTIVE SUMMARY Over the years structured cabling systems have evolved significantly. This

More information

Implementing Fast Ethernet

Implementing Fast Ethernet Implementing Fast Ethernet R The Next Generation of Ethernet Fast Ethernet (also known as IEEE 802.3u or 100BASE-T) is quickly becoming the successor to Ethernet as the network topology of choice. Fast

More information

The Axia Guide to Choosing Category Cable

The Axia Guide to Choosing Category Cable The Axia Guide to Choosing Category Cable By Stephen H. Lampen, Multimedia Technology Manager, Belden Electronics Division, Belden CDT Abstract If you ve gotten to this paper, you ve probably read the

More information

Category-6 / Class-E Cabling

Category-6 / Class-E Cabling Category-6 / Class-E Cabling IEEE 802 Tutorial July 7, 1998 San Diego, CA by: Luc Adriaenssens SYSTIMAX Systems Applications Director Bell Labs of Lucent Technologies How were the ISO Cat-6 Targets set?

More information

Digital Systems Ribbon Cables I CMPE 650. Ribbon Cables A ribbon cable is any cable having multiple conductors bound together in a flat, wide strip.

Digital Systems Ribbon Cables I CMPE 650. Ribbon Cables A ribbon cable is any cable having multiple conductors bound together in a flat, wide strip. Ribbon Cables A ribbon cable is any cable having multiple conductors bound together in a flat, wide strip. Each dielectric configuration has different high-frequency characteristics. All configurations

More information

with Component Rating A Simple Perspective

with Component Rating A Simple Perspective Cat-6A UTP and Shielded with Component Rating A Simple Perspective Asef Baddar RCDD, DCD Sr. Technical Manager Leviton Middle East Category Specifications Agenda Terminology International & North America

More information

Category 6 UTP - Cabling System

Category 6 UTP - Cabling System AMP NETCONNECT Category 6 UTP Cabling System...... real Category 6 Performance, both on Component as well as on System level! Owing to the extreme high performance of the AMP NETCONNECT Category 6 UTP

More information

Terminating 25-Pair Cable and 4-Pair Cross Connects

Terminating 25-Pair Cable and 4-Pair Cross Connects Terminating 25-Pair Cable and 4-Pair Cross Connects Estimated Time: 90 minutes Number of Teams: 2 Number of Team Members: one to four This Lab has four major parts that will be addressed separately. 1.

More information

The effect of temperature on the bandwidth of telecommunications cabling in commercial buildings. Focus on the IBDN System 4800LX from NORDX/CDT

The effect of temperature on the bandwidth of telecommunications cabling in commercial buildings. Focus on the IBDN System 4800LX from NORDX/CDT The effect of temperature on the bandwidth of telecommunications cabling in commercial buildings Focus on the IBDN System 4800LX from NORDX/CDT Table of Contents Introduction... 3 Bandwidth and Information

More information

Category 8 Cable Transmission Measurements Comparative Study between 4-port single wire measurements and 2-port balun measurements

Category 8 Cable Transmission Measurements Comparative Study between 4-port single wire measurements and 2-port balun measurements Category 8 Cable Transmission Measurements Comparative Study between 4-port single wire measurements and 2-port balun measurements Stefan Estevanovich Rafael Herrera, Nadim Kafati Hitachi Cable USA NDC

More information

Copper Cabling Troubleshooting Handbook

Copper Cabling Troubleshooting Handbook NETWORKSUPERVISION Copper Cabling Troubleshooting Handbook NETWORKSUPERVISION Table of Contents Introduction 2 Troubleshooting Basics 3 Link Models 4 The Automated DTX Series Diagnostics 5 Causes of Cabling

More information

CONTRIBUTION. +1-650-723-2150 cioffi@stanford.edu ABSTRACT

CONTRIBUTION. +1-650-723-2150 cioffi@stanford.edu ABSTRACT COMMITTEE T1 TELECOMMUNICATIONS Working Group T1E1. (DSL Access) Washington, DC: August 9, 200 T1E1./2003-87R1 CONTRIBUTION TITLE: SOURCE: J. Cioffi,B. Lee, M. Mohseni A. Leshem Li Youming GDSL (Gigabit

More information

SYSTIMAX Solutions. GigaSPEED X10D Shielded (F/UTP, S/FTP) Solution Guide Europe, Middle East and Africa Regions. www.commscope.

SYSTIMAX Solutions. GigaSPEED X10D Shielded (F/UTP, S/FTP) Solution Guide Europe, Middle East and Africa Regions. www.commscope. SYSTIMAX Solutions GigaSPEED X10D Shielded (F/UTP, S/FTP) Solution Guide Europe, Middle East and Africa Regions www.commscope.com The SYSTIMAX GigaSPEED X10D Shielded Solution provides unprecedented performance

More information

WHITEPAPER. Cable and Connector for Hiperface dsl motor drive applications

WHITEPAPER. Cable and Connector for Hiperface dsl motor drive applications WHITEPAPER Cable and Connector for Hiperface dsl motor drive applications information for cable manufacturers Version 02 Content Information for cable manufacturers...3 Communication...3 Crosstalk & shielding...3

More information

InstaPATCH Cu Cabling Solutions for Data Centers

InstaPATCH Cu Cabling Solutions for Data Centers SYSTIMAX Solutions InstaPATCH Cu Cabling Solutions for Data Centers Design Guidelines August 2008 www.commscope.com Contents Overview 1 Instapatch Cu Solution Specification 2 Harness Assembly Design 3

More information

De-Mystifying Cabling Specifications

De-Mystifying Cabling Specifications WP_DeMystifyingCble_E (US)_WP_DeMystifyingCble_B 9/10/10 2:21 PM Page 2 FROM 5e TO 7A De-Mystifying Cabling Specifications From 5e to 7A S tructured cabling standards specify generic installation and design

More information

Panduit 28 AWG Patch Cords Installation Guideline

Panduit 28 AWG Patch Cords Installation Guideline Panduit 28 AWG Installation Guideline Introduction Panduit is a leading supplier of Structured Cabling Systems and Unified Physical Infrastructure. Panduit solutions enable the physical infrastructure

More information

Cabling Requirements for the District of Columbia on behalf of the Criminal Justice Coordinating Council

Cabling Requirements for the District of Columbia on behalf of the Criminal Justice Coordinating Council Cabling Requirements for the District of Columbia on behalf of the Criminal Justice Coordinating Council Date: 6/19/2013 Version: 1.0 Prepared by: Gregory Cotten Department of General Services District

More information

B. Cross-Connect: A facility enabling the termination of cable elements and their interconnection or cross-connection.

B. Cross-Connect: A facility enabling the termination of cable elements and their interconnection or cross-connection. DIVISION 16 ELECTRICAL Section 16740 Telephone System PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Part 1: General Requirements TELECOMMUNICATIONS INDUSTRY ASSOCIATION

Part 1: General Requirements TELECOMMUNICATIONS INDUSTRY ASSOCIATION TIA/EIA STANDARD ANSI/TIA/EIA-568-B.1-2001 Approved: April 12, 2001 TIA/EIA-568-B.1 Commercial Building Telecommunications Cabling Standard Part 1: General Requirements TIA/EIA-568-B.1 (Revision of TIA/EIA-568-A)

More information

FIBER OPTIC CABLE PLANT DOCUMENTATION

FIBER OPTIC CABLE PLANT DOCUMENTATION C H A P T E R 13 FIBER OPTIC CABLE PLANT DOCUMENTATION JIM HAYES Documenting the fiber optic cable plant is a necessary part of the design and installation process for the fiber optic network. Documenting

More information

VE02AL / VE05AL / VE02ALR VGA & Stereo Audio CAT5 Extender with Chainable Output

VE02AL / VE05AL / VE02ALR VGA & Stereo Audio CAT5 Extender with Chainable Output VE02AL / VE05AL / VE02ALR VGA & Stereo Audio CAT5 Extender with Chainable Output Introduction: VE02AL, VE05AL is designed for VGA +Stereo Audio signal over cost effective CAT5 cable to instead of VGA and

More information

WHITE PAPER December, 2001

WHITE PAPER December, 2001 Is Superior Essex Outside Plant Copper Cable Rated Category 3? The applicability of the Category 3 specification to outside plant cables is sometimes misunderstood. This white paper examines that issue,

More information

BICSInews. plus. Show Issue. september/october 2012 volume 33, number 5. + Migration to High-Speed Ethernet

BICSInews. plus. Show Issue. september/october 2012 volume 33, number 5. + Migration to High-Speed Ethernet BICSInews m a g a z i n e september/october 2012 volume 33, number 5 plus + Migration to High-Speed Ethernet Show Issue + DAS in Your World + Planning Health Care Infrastructure + Fiber Considerations

More information

Discontinued. Volition. Fiber Optic Cable. 3Innovation

Discontinued. Volition. Fiber Optic Cable. 3Innovation Volition Fiber Optic Cable Tough enough to take it. Easy to handle. The Volition Network Solution from 3M includes horizontal and backbone cable with 62.5/125 µm and 50/125 µm multimode fiber, and 9/125

More information

CCTV System Troubleshooting Guide

CCTV System Troubleshooting Guide Wouldn t be nice to start and finish a CCTV System Project without running into any problems before, during and after the installation is completed. Well, in this article we will try and explain why we

More information

Impedance Matching. Throughput SOLUTIONS NETWORK PERFORMANCE. Only the TrueNet Impedance-matched System Protects Network Performance

Impedance Matching. Throughput SOLUTIONS NETWORK PERFORMANCE. Only the TrueNet Impedance-matched System Protects Network Performance Throughput SOLUTIONS Impedance Matching Protects NETWORK PERFORMANCE Original 100BaseT MLT-3 signal transmission Only the TrueNet Impedance-matched System Protects Network Performance Networks for today

More information

Session 2; Cabling Technology in the Data Centre Media Choices; Copper Twisted Pair

Session 2; Cabling Technology in the Data Centre Media Choices; Copper Twisted Pair Presentation; Session 2; Cabling Technology in the Data Centre Media Choices; Copper Twisted Pair 5 th April 2010 Paul Mathews MInstSMM, CCNA, MIEEE Global Channel Manager Media Types Physical Layer Cabling;

More information

1.1 SYSTEM DESCRIPTION.1 Data system includes data outlets and wiring for office and school applications.

1.1 SYSTEM DESCRIPTION.1 Data system includes data outlets and wiring for office and school applications. Issued 2005/06/01 Section 16743 Data System Page 1 of 7 PART 1 GENERAL 1.1 SYSTEM DESCRIPTION.1 Data system includes data outlets and wiring for office and school applications..2 Data system equipment

More information

STRUCTURED CABLING SYSTEMS

STRUCTURED CABLING SYSTEMS STRUCTURED CABLING SYSTEMS by Mario Okle (12/98) 1 Structured Cabling Versus System Specific Cabling Since the mid 80s the trend towards structured cabling systems has continued. When we talk about structured

More information

Giganet Copper Cabling Training

Giganet Copper Cabling Training Giganet Copper Cabling Training Giganet Certified Installer Course 5/14/2012 This manual has been produced as supporting documentation for the Giganet Fibre Optic Certification Course. Course attendees

More information

PHY Feasibility Study for One or Two pairs RTPGE

PHY Feasibility Study for One or Two pairs RTPGE PHY Feasibility Study for One or Two pairs RTPGE July 2012 IEEE Reduced Twisted Pair Gigabit Ethernet Benson Huang, Joseph Chou Realtek Semiconductor Corp. Supporters Mehmet Tazebay, Broadcom George Zimmerman,

More information

Introduction. Investigation

Introduction. Investigation A c h i e v i n g R e l i a b l e 1 0 G B A S E - T P e r f o r m a n c e M a r c h 2 0 1 4 Introduction In a densely cabled environment, such as a data center, the performance of 10GBASE-T links can be

More information

LAN Installation Handbook

LAN Installation Handbook ] LAN Installation Handbook LAN Installation Handbook Central Information Management Unit Office of the Prime Minister Version 1.0 April 2003 Contents Section 1 Introduction...1 Section 2 LAN Installation...3

More information

Cat7/Class F New Installation Concept New infrastructure. Handbook

Cat7/Class F New Installation Concept New infrastructure. Handbook Cat7/Class F New Installation Concept New infrastructure Handbook contents 1 Introduction 3 2 What is the Cat7/Class F installation concept 3 3 Distribution centre 3 3.1 Patch Modules 3 4 How to handle

More information

Shielding Effectiveness Test Method. Harbour s LL, SB, and SS Coaxial Cables. Designs for Improved Shielding Effectiveness

Shielding Effectiveness Test Method. Harbour s LL, SB, and SS Coaxial Cables. Designs for Improved Shielding Effectiveness Shielding Effectiveness Test Method Harbour s LL, SB, and SS Coaxial Cables Designs for Improved Shielding Effectiveness Harbour Industries 4744 Shelburne Road Shelburne Vermont 05482 USA 802-985-3311

More information

NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT SECTION 27 10 00 STRUCTURE CABLING TESTING

NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT SECTION 27 10 00 STRUCTURE CABLING TESTING RELATED SECTIONS: NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT Section 27 00 00 General Requirements Section 27 02 00 General Communication Requirements Section 27 05 26 Grounding and Bonding for Communications

More information

A Feasibility Study of One Twisted Pair Gigabit Ethernet

A Feasibility Study of One Twisted Pair Gigabit Ethernet A Feasibility Study of One Twisted Pair Gigabit Ethernet May 2012 IEEE Reduced Twisted Pair Gigabit Ethernet Benson Huang, Albert Kuo, Joseph Chou Realtek Semiconductor Corp. The Purpose This presentation

More information

The Optical Fiber Ribbon Solution for the 10G to 40/100G Migration

The Optical Fiber Ribbon Solution for the 10G to 40/100G Migration The Optical Fiber Ribbon Solution for the 10G to 40/100G Migration Bill Charuk, SR Product Manager, Data Center Solutions Introduction With the advent of data centers in communication infrastructure, various

More information

724-746-5500 blackbox.com

724-746-5500 blackbox.com $27.95 Networking Standards Cabling Structured Cabling System Installation & Testing 724-746-5500 blackbox.com Other Standards What is structured cabling? A structured cabling system is the wiring network

More information

White Paper. Cat. 6A vs. Cat. 6 A. What s the Difference and Why Should I Care?

White Paper. Cat. 6A vs. Cat. 6 A. What s the Difference and Why Should I Care? White Paper Cat. 6A vs. Cat. 6 A What s the Difference and Why Should I Care? Cat. 6A vs. Cat. 6 A What s the Difference and Why Should I Care? TABLE OF CONTENTS 1. Introduction...3 2. Component Standards

More information

Nexus Technology Review -- Exhibit A

Nexus Technology Review -- Exhibit A Nexus Technology Review -- Exhibit A Background A. Types of DSL Lines DSL comes in many flavors: ADSL, ADSL2, ADSL2+, VDSL and VDSL2. Each DSL variant respectively operates up a higher frequency level.

More information

Broadband Video over Twisted Pair Cabling. By Paul Kish Director, IBDN Systems & Standards NORDX/CDT

Broadband Video over Twisted Pair Cabling. By Paul Kish Director, IBDN Systems & Standards NORDX/CDT Broadband Video over Twisted Pair Cabling By Paul Kish Director, IBDN Systems & Standards NORDX/CDT December 2002 Introduction Over the last 10 years we have seen some tremendous advances in the manufacturing

More information

LocoNet, the Digitrax Difference

LocoNet, the Digitrax Difference LocoNet, the Digitrax Difference LocoNet is Digitrax's method of communication between LocoNet compatible devices on a model railroad layout. LocoNet Compatible devices are designed to work together on

More information

RTEX Cable 2015/10/1. Motor Business Unit Automotive & Industrial Systems Company Panasonic Corporation

RTEX Cable 2015/10/1. Motor Business Unit Automotive & Industrial Systems Company Panasonic Corporation RTEX Cable 2015/10/1 Motor Business Unit Automotive & Industrial Systems Company Panasonic Corporation Cable and Connector Page 2 2015/10/1 Rev. 5 Motor Business Unit, AIS Company The Kind of Ethernet

More information