1 SECTION 0833 STEEL ROLL-UP DOORS PART GENERAL 1.01 SCOPE OF WORK: A. WORK INCLUDED: The Contractor shall furnish all necessary labor, materials, equipment and services necessary for the complete installation of steel roll-up doors. Attention is directed to the drawings and specifically the door schedule for door type, size, operation, mounting and location. Work under this Section includes, but is not necessarily limited to the following: 1. Exterior steel roll-up weather doors. 2. Motor operators. 3. Door controls. B. INCIDENTALS: Doors and operators shall be provided complete with all hardware, controls and accessories, etc. to function in an operable manner meeting the approval of the Engineer and as specified herein. Furnish complete with each door all miscellaneous angles, bolts and all related items necessary for the approved installation of each door and operator. C. RELATED WORK SPECIFIED ELSEWHERE: 1. Steel Jambs - Section Electrical Power Wiring and Control Wiring - Division Dock Equipment - Section D. WORK BY OTHERS: Installation of push button control stations furnished under this Section shall be provided by the Electrical Contractor under Division APPLICABLE CODES AND STANDARDS: A. All work specified under this Section shall comply with the following codes: 1. North Carolina State Building Code. 2. International Building Code. 3. State and local building codes. 4. National Fire Codes published by the National Fire Protection Association QUALIFICATIONS: The door manufacturer or his authorized representative shall
2 install doors, operators, fittings, voltage-matching transformers and hardware. All workmen employed in the installation of steel roll-up doors shall be thoroughly trained and experienced in the proper installation of this type door SUBMITTALS: A. SHOP DRAWINGS: Shop drawings shall be submitted in accordance with Section 0130 for all doors, door accessories, controls and motor operators. Shop drawings shall show all pertinent details for proper installation of doors and operators at each opening. Shop drawings shall include wiring diagrams for power wiring and control wiring of motor operators. All required clearances for hoods, operators, guides, etc. shall be shown on shop drawings. Shop drawings shall clearly indicate the proper installation and clearance details of doors and operators as related to the construction details for each wall opening as shown on the project drawings. Standardized shop drawings not fulfilling these requirements will not be accepted. B. OPERATING AND MAINTENANCE MANUALS: Maintenance and operation manuals for doors and operators shall be provided upon completion of the work and prior to final payment. Manuals shall be bound in booklet form and submitted in accordance with Section C. CERTIFICATES OF COMPLIANCE: Underwriter's Laboratories Certificates shall be submitted in accordance with Section 0130 for all oversize fire rated doors PRODUCT HANDLING: A. PROTECTION: 1. All necessary means shall be used to protect materials specified under this Section from damage before, during and after installation. 2. The work of other trades shall be adequately protected from damage resulting from work specified under this Section. B. STORAGE AND HANDLING: All materials specified under this Section shall be properly stored in field warehouses or the equivalent. Materials shall be handled in such a manner that door slats and hoods will not be disfigured. C. REPLACEMENTS: 1. In the event of damage to materials or work in place, all necessary repairs and replacements shall be immediately made to the satisfaction of the Engineer at no additional cost to the Owner. 2. Bent, bowed or disfigured door hoods shall be replaced at no additional cost to the Owner
3 3. Bent or disfigured door slats shall be replaced at no additional cost to the Owner ACCEPTANCE AND TOLERANCES: Installation of work under this Section will not be considered acceptable until each and every door is lubricated, adjusted and functioning properly in every respect LABELS AND IDENTIFICATION: Fire rated doors shall have permanently attached metal labels indicating Underwriter's Laboratories and FM Global approval WARRANTY: The Contractor shall guarantee all work performed under this Section to be free of defects in materials and workmanship for a period of one year from date of final acceptance of the project. PART PRODUCTS 2.01 MATERIALS: A. MANUFACTURER: All doors shall be as manufactured by Raynor Garage Doors, Dixon, Illinois or approved equal. Doors complying with these specifications and manufactured by the following companies will be considered equal: 1. The Cookson Company. 2. Cornell Iron Works, Inc. 3. Overhead Door Corporation B. STEEL ROLL-UP WEATHER DOORS: Weatherstripped insulated steel roll-up weather doors shall be provided at all exterior door openings where steel roll-up doors are required by the door schedule. 1. Curtain shall consist of roll formed interlocking steel slats, galvanized before being formed and bonderized for paint adhesion. Zinc coating shall be of the 1.25 oz. per sq. ft. Class G90 as per ASTM A525. Slats shall have a flat vertical surface so that the exterior of the curtain will lie completely in a vertical plane. Exterior slats shall be Type IF 22 gauge minimum and shall have a minimum width of 2-9/16 inches and a minimum depth of 25/32 inch. Interior surface of curtain shall be 24 gauge. Insulated core shall be polyisocyanurate. Curtain "U" value shall be.16, maximum. Exterior doors shall be capable of withstanding a 30 pound per sq. ft. wind load with adequate factor of safety. Both ends of each slat shall be fitted with continuous combination malleable iron endlocks and windlocks. Curtains shall have a rolled bottom bar consisting of two (2) 3/16 inch minimum hot rolled angles thru bolted at 12 inches on center and a half a slat to reinforce lower edge of curtain against wind pressure. Angles shall be of equal weight, balance and
4 shall hang freely on the curtain to eliminate friction and possible binding in the guides. A compressible loop-type rubber astragal, which extends into each guide, shall be provided and secured to the bottom bar. Astragal material shall be reinforced with nylon, fiberglas or flexible wire mesh to provide a rip resistant weathertight seal suitable for heavy duty industrial application. 2. Counterbalance shall consist of oil tempered and heat treated steel helical torsion springs housed in steel pipe. Springs shall be anchored to a torsion rod extending the full length of springs. Torsion rod shall have fixed on it a single balancing wheel placed on the outside of one of the brackets. Steel pipe shall not exceed 0.03 inch per foot deflection and shall be provided with spiral cast iron rings whenever allowed by the design. 3. Brackets shall be of 1/4 inch minimum steel plate. Bracket mouth and stops shall be in an established distance between center and back of bracket providing a throat which permits smooth operation without friction and eliminates the excessive drag of curtain over the stops. 4. Guides shall be of 3/16 inch minimum hot rolled steel angles, and shall be equipped with windlocking bars and continuous vinyl weatherstripping which shall contact and seal the flat face of the curtain. Weatherstripping shall retain contact with the curtain at all times and shall be protected by windlocking bar from damaging compression. Guides shall form a slot of sufficient depth to retain curtain in guides against heavy wind pressure and shall be provided with anchors for windlocks. 5. Gears, except those which are part of the motor unit, shall be of high tensile gray iron castings conforming to Federal Specification QQ and shall be made from machine cut patterns. 6. Bearings shall be self-aligning precision type bearings of seal cartridge type, or self-aligning, self-lubricating bronze sleeve bearings. 7. Hood shall be not less than 24 gauge hot galvanized sheet steel, formed to fit contour of brackets and enclose the curtain coil. Hood shall be neatly formed and reinforced with beads or flanges to prevent deflection. Neoprene air baffle, attached to the hood connection and extending full length of barrel, shall be provided to prevent air infiltration at the top of door. Backside of hoods exposed to exterior shall be finished flush without deformity from 16 gauge minimum hot dipped galvanized sheet steel. 8. Bottom bar seal shall be neoprene loop suspended between the two hot rolled steel bottom bar angles thru bolted at 12 inches on center EQUIPMENT: A. MOTOR OPERATORS: Operators shall be Model CHO operators mounted bracket plate. Motor operator units shall consist of a motor, directly connected
5 2.03 CONTROLS: to a speed reducer, a solenoid activated brake, a limit switch and an endless chain for emergency operation. All electrical equipment shall conform to NEMA standards. The motor shall be of high starting torque and of sufficient capacity to operate door at a speed of approximately 2/3 of a foot per second, shall be suitable for operation on the current characteristics available at place of installation and shall have overload protection. Each unit shall be provided with a magnetic across the line starter having thermal overload protection and unless otherwise specified shall be equipped with push button marked "Open", "Close" and "Stop". The limit switch shall be of the adjustable screw type and shall be so mounted as not to have its timing affected when the door changes from motor to manual operation. The speed reducer shall be of the worm gear type, completely housed and running in an oil bath, shall satisfy the AGMA Standards and shall be of sufficient capacity for the use intended. Emergency operation shall be through auxiliary hand chain extending to a point easily accessible from the floor. Drive from reducer to door shaft shall be through roller chain operating on cut tooth steel sprockets. Each unit shall be provided with electric interlock so the motor cannot be started when door is being operated by hand and shall be constructed so manual operation may be effected even when motor is disconnected from the unit. 1. Chain holder locking devices shall be provided at all motor operated doors. 2. Electric power for door operators will be 208 volt, 3 phase, 60 Hz. It shall be the responsibility of the door supplier to verify and coordinate electrical current characteristics with the electrical contractor. 3. Transformers shall be provided as an integral part of door operator for 24 volt door control wiring. 4. Closing of doors shall require constant pressure on the close button on the control station. 5. Mounting of motor operators shall be on steel roll-up door bracket. A. CONTROL STATIONS: Control stations shall be furnished for all motor operated doors and provide to Electrical Contractor for installation in accordance with this Section. Control stations shall be three button (open, close, stop) heavy duty control stations as manufactured by Square D Company, Park Ridge, Illinois or approved equal. Control station types shall be as follows: Model NEMA Location Type Type Interior, wall mounted KYK33 Type
6 B. CONTROL VOLTAGE: Control voltage shall be 24 volts. C. CONTROL FUNCTIONS: 1. Controls shall allow door to be opened or closed from stopped position. 2. Reversing travel of a door that is in the process of opening shall be accomplished only by first activating the "stop" button and then activating the "close" button. 3. Reversing travel of a door that is in the process of closing shall be accomplished by activating the "open" button without first activating the "stop" button. 4. Activation of the "stop" button shall immediately stop the door at any point in the opening or closing cycle. 5. All exterior doors shall have one (1) 3 button wall mounted control station on the inside only SHOP FINISH: Finish on all doors and equipment shall be shop paint. Galvanized surfaces shall be treated for paint adhesion, primed with a zinc dust primer and painted with a rust inhibiting paint. All other surfaces except working parts of machinery and other surfaces not normally painted in good commercial practice shall be primed and given a shop coat of rust inhibiting paint. PART EXECUTION 3.01 EXAMINATION AND PREPARATION OF SURFACES: Wall openings, wall surfaces surrounding wall openings and adjacent construction shall be examined for any defects or undesirable features that will interfere with proper installation and operation of doors. Any adverse findings shall be brought to the attention of the Engineer in writing INSTALLATION AND WORKMANSHIP: A. MANUFACTURER'S INSTRUCTIONS: Installation of doors and operators shall be in strict accordance with the manufacturer's printed instructions and approved shop drawings. B. WORKMANSHIP: Workmanship shall be of the highest grade and in accordance with the best practice for this type of equipment. C. INSTALLATION: Door guides for non-fire rated doors shall be securely welded to steel door jambs by certified welders in a neat and workmanlike manner using a combination of plug welds in all guide holes and fillet welds. D. CONTROLS: Door controls stations shall be located as shown on the electrical drawings. Unless otherwise required, control stations shall be
7 mounted 4 feet above finish floor. The Contractor shall coordinate the exact location, orientation and mounting height of control stations for motorized door operators with the Owner's representative at the jobsite. Control stations shall be securely anchored to the building structure by appropriate means. E. TOUCH-UP: All welds shall be cleaned with a chipping hammer and wire brush. All welds and abrasions in shop finish shall then be touched up with a primer that matches shop finish. F. ADJUSTMENTS: After completion of door installation and door controls installation, adjust and lubricate doors, operators, controls and hardware to insure that doors will function properly under all operating conditions FIELD QUALITY CONTROL: A. FIELD TESTING: Each and every steel roll-up door shall be field tested by the Contractor just prior to final inspection to verify that doors operate properly under all operating conditions. Field testing procedures shall include the following where applicable: 1. Testing of each control station for execution of all specified control functions. 2. Testing of proper setting of limit switches for door travel. 3. Testing of chain operators including checking for automatic disengagement of motor operator while chain operator is engaged CLEANING: All rubbish resulting from installation of steel roll-up doors shall be systematically collected and removed from the jobsite. (End of Section)
DESIGN CLARIFICATION (DC)
DESIGN CLARIFICATION (DC) Owner: Victor Valley Wastewater Reclamation Authority Date: 03/03/2015 Contractor: W M Lyles Carollo Project No.: 8299A.20 Project Name: Subregional WRPs DC No.: 001 DC Title:
More informationSECTION 08332 COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here)
SECTION 08332 COILING COUNTER DOORS Display hidden notes to specifier. (Don't know how? Click Here) PART 1 GENERAL 1.1 SECTION INCLUDES A. Coiling Metal Counter Doors. B. Coiling Counter Fire Doors. 1.2
More informationSTANDARD FOR NON-FIRE RATED ROLLING DOORS
ANSI/DASMA 203-2004 AMERICAN NATIONAL STANDARD STANDARD FOR NON-FIRE RATED ROLLING DOORS Door & Access Systems Manufacturers Association, International Sponsor: 1300 Sumner Ave Cleveland, Ohio 44115-2851
More informationSECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS
SECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS Display hidden notes to specifier by using Tools / Options / View / Hidden Text. On newer versions of Microsoft Word
More informationMODEL HSR-007 Direct Drive Rolling Steel
MODEL HSR-007 Direct Drive Rolling Steel 200 Fairview Road, Unit #2, Barrie, Ontario L4N 8Z8 Tel: 866-792-9968 or 705-792-9968 Fax: 705-735-9564 www.tnrdoors.com email: info@tnrdoors.com Model HSR-007
More informationDisplay hidden notes to specifier. (Don't know how? Click Here) A. Advanced Upcoiling Security Grilles, power operated.
SECTION 08333 ADVANCED UPCOILING SECURITY GRILLE MODEL 600 ADV Display hidden notes to specifier. (Don't know how? Click Here) PART 1 GENERAL 1.1 SECTION INCLUDES A. Advanced Upcoiling Security Grilles,
More informationArchitectural Specifications MODEL HDXL 9. 200 Fairview Road, Unit #2, Barrie, Ontario L4N 8Z8
MODEL HDXL 9 200 Fairview Road, Unit #2, Barrie, Ontario L4N 8Z8 Tel: 866-792-9968 or 705-792-9968 Fax: 705-735-9564 www.tnrdoors.com email: info@tnrdoors.com Model HDXL 9 Tech Specs September 4, 2012
More informationArchitectural Specifications* MODEL HDE
MODEL HDE 200 Fairview Road, Unit #2, Barrie, Ontario L4N 8Z8 Tel: 866-792-9968 or 705-792-9968 Fax: 705-735-9564 www.tnrdoors.com email: info@tnrdoors.com TNR Model HDE Tech Specs September 4, 2012 Page
More informationPreformed Metal Roofing and Siding
Page -1-1. GENERAL 1.1. Description This specification along with the drawings covers the furnishing of all material, products, equipment, accessories, tools, services, transportation, labor and supervision
More informationA D D E N D U M # 3 QUESTIONS FROM BIDDERS: DATE: November 5, 2012. All Bidders. Jenne dos Santos, CBI Consulting Inc. City of Chelsea, MA
Page 1 of 10, Addendum No. 3 Temporary Garage Structure City of Chelsea, MA November 5, 2012 CBI Job No.: 12055-A A D D E N D U M # 3 DATE: November 5, 2012 TO: FROM: PROJECT: All Bidders Jenne dos Santos,
More informationResidential Garage Door Terminology
A Air Infiltration: The leakage or passage of air through a door system Anodize: A hard non-corrosive oxide film on the surface of aluminum Astragal: A compressible or deformable seal provided on the bottom
More informationSECTION 1 GENERAL REQUIREMENTS
Page 1 of 6 SECTION 1 GENERAL REQUIREMENTS 1. SCOPE OF WORK: The work to be performed under the provisions of these documents and the contract based thereon includes furnishing all labor, equipment, materials,
More informationSECTION 08330. FireGard ROLLING FIRE DOORS / SMOKESHIELD FIRE DOORS
SECTION 08330 FireGard ROLLING FIRE DOS / SMOKESHIELD FIRE DOS GENERAL NOTES TO SPECIFIER: THIS SPECIFICATION SECTION HAS BEEN PREPARED TO ASSIST DESIGN PROFESSIONALS IN THE PREPARATION OF PROJECT OFFICE
More informationSECTION 15076 CEMENT-MORTAR LINED AND COATED STEEL PIPE
SECTION 15076 CEMENT-MORTAR LINED AND COATED (CML&C) STEEL PIPE PART 1 GENERAL 1.01 DESCRIPTION This section designates the requirements for steel pipe fabrication, test in shop, installation of steel
More informationSECTION 14 20 10 - FREIGHT & PARKING GARAGE ELEVATORS PART I - GENERAL
SECTION 14 20 10 - FREIGHT & PARKING GARAGE PART I - GENERAL 1.1 SECTION INCLUDES [NOTE to AE: The following lists requirements that are specific to freight elevators. These requirements are in addition
More informationPTS HELICAL PIERS INSTALLATION SPECIFICATIONS NOTICE
FORM A PTS HELICAL PIERS INSTALLATION SPECIFICATIONS NOTICE The following suggested specifications are written as a guide to assist the specifier in writing his own specifications. Specific circumstances
More informationAll work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.
DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,
More informationMechanical Installation
Page -1-1. INTRODUCTION AND PURPOSE 1.1. This specification covers the installation, testing and precommissioning of mechanical equipment. Work is to be performed in conjunction with the manufacturer s
More informationPump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling
Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling 250_P1 R10/7/2015 Copyright 2015 Liberty Pumps Inc. All rights reserved. Specifications subject to change without notice.
More informationLOADING DOCK EQUIPMENT. A. Section 03100 - Concrete Forms and Accessories: Placement of anchors into concrete.
LOADING DOCK EQUIPMENT PART 1 GENERAL 1.1 SECTION INCLUDES A. Loading dock equipment of the following types: 1. Dock lifts. 2. Control stations. 1.2 RELATED SECTIONS A. Section 03100 - Concrete Forms and
More informationSECTION 11014 WINDOW WASHING SYSTEMS
SECTION 11014 WINDOW WASHING SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section includes, but is not limited to, design and furnishing portable davits, davit sleeves, dvit bases, four (4) removable outriggers,
More informationELECTRICAL CONTRACTORS THE UNIVERSITY OF TENNESSEE KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1
KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1 PART 1 - GENERAL 1.01 RELATED DOCUMENTS: SECTION 16050 A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1
More informationCLEAR-DIVISIONS CENTERFOLD
CLEAR-DIVISIONS CENTERFOLD Introduction: The following three (3) part specification offers the Standard and Optional features for the CLEAR-DIVISIONS CENTERFOLD moveable The yellow highlighted areas in
More informationPART 1 GENERAL 1.1 SECTION INCLUDES
J-1 Section 09110 Long Form Specification INTERIOR METAL STUD FRAMING This section includes lightweight, usually 0.036 inch (0.9 mm) thick or lighter, non-axial load bearing metal stud framing including
More informationTOP RUNNING SINGLE GIRDER BRIDGE CRANE
SECTION 14630 TOP RUNNING SINGLE GIRDER BRIDGE CRANE 1.01 SUMMARY PART 1- GENERAL A. The work required under this section shall include the designing, manufacturing, shipping, installing and field testing
More informationSECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT
SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION A. The Work specified in this Section consists of designing, furnishing and installing factory-assembled
More informationCity of San Diego, CWP Guidelines
PART 1 -- GENERAL SECTION 08520-1.1 WORK OF THIS SECTION City of San Diego, CWP Guidelines A. The WORK of this Section includes providing aluminum windows with frames, bracing, glazing attachments, screens,
More informationDENVER MODEL 30 X 30 SPECIFICATIONS
DENVER MODEL 30 X 30 SPECIFICATIONS Dimensions: Roof Dimensions 30-0 x 30-0 (4) Columns (Center to Center) 25-6½ x 25-6½ Minimum Clearance 8-0 Roof Height @ Peak Dependent on Col. Ht. Hip Roof 4:12 pitch
More informationSECTION 23 05 29 - HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT
SECTION 23 05 29 - HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Pipe hangers and supports. 2. Hanger rods. 3. Inserts. 4. Flashing. 5. Equipment
More informationPump Specifications 405 Series Commercial Drain Pump (High-Temp) 2 Solids handling
Pump Specifications 405 Series Commercial Drain Pump (High-Temp) 2 Solids handling 405_P1 R1/27/2012 Copyright 2012 Liberty Pumps Inc. All rights reserved. Specifications subject to change without notice.
More informationSECTION 6. Glass Storefront Doors:
SECTION 6 Glass Storefront Doors: Table of Contents 3070 Storefront Door System Description & Dimensions 6070 Storefront Door System Description & Dimensions Door Leaf Detail Optional 10 Bottom Rail Detail
More informationSERIES ASM NEOPRENE/EPMD FLANGED SINGLE SPHERE CONNECTOR CONNECTORS. Pressures to 225 PSIG (15.51 barg) Temperatures to 230ºF (110ºC)
APPLICATIONS Process Industry Weak Acids Alkalies Compressed Air Pulp & Paper MODELS ASM - Flanged Connection OPTIONS Control Rods Oil & Gas Water & Waste Pump suction & discharge Sea water Chemical lines
More informationSECTION 07 61 13 STANDING SEAM METAL ROOFING
SECTION 07 61 13 STANDING SEAM METAL ROOFING PART 1 GENERAL 1.01 SCOPE OF WORK A. The Work shall include all labor, materials, equipment and supervision required to complete the work of the above referenced
More informationCOLORADO MODEL. 35 x 65 SPECIFICATIONS
COLORADO MODEL 35 x 65 SPECIFICATIONS Dimensions: Roof Dimensions 35-0 x 65-0 Column Dimensions (center to center) 31-0 x 30-6 Minimum Clearance 14-0 Roof Height @ Peak ±18-8 Curved Roof ±42-6 radius Square
More informationCLEAR-DIVISIONS VARIOFOLD
CLEAR-DIVISIONS VARIOFOLD Introduction: The following three (3) part specification offers the Standard and Optional features for the CLEAR-DIVISIONS VARIOFOLD moveable The yellow highlighted areas in the
More informationHorizontal Jet Pumps 1/3-1-1/2 HP
Horizontal Jet s 1/3-1-1/2 FW01 0909 Supersedes 0409 The CPJ, CPH and EK models feature the famous Flint and Walling Service Plus motor, available in either NEMA J or Uni-frame flange construction. The
More informationSECTION 08560 SERIES 1500 VINYL PATIO DOORS
SERIES 1500 VINYL PATIO DOORS PART 1 GENERAL 1.1 SECTION INCLUDES A. Patio Doors 1.2 RELATED SECTIONS A. Section 05450: Cold Formed Metal Framing. B. Section 06100: Rough Carpentry. C. Section 06200: Finish
More informationCLEAR-DIVISIONS APERTO
CLEAR-DIVISIONS Introduction: The following three (3) part specification offers the Standard and Optional features for the CLEAR-DIVISIONS moveable glass wall system. The yellow highlighted areas in the
More informationSECTION 15140 - PIPE HANGERS AND SUPPORTS
Part I - GENERAL 1.01 SECTION INCLUDES A. The work covered under this section consists of the furnishing of all necessary labor, supervision, materials, equipment, and services to completely execute the
More informationREDI-EXIT COMMERCIAL FIRE DOOR AND EXTERIOR DOOR KITS INSTALLATION GUIDELINES
REDI-EXIT COMMERCIAL FIRE DOOR AND EXTERIOR DOOR KITS INSTALLATION GUIDELINES Tools Required Tape Measure Hammer Slotted Screw Driver #2 & #3 Philips Screw Driver 3-4 Foot Level 12 Pry Bar Cold Chisel
More informationJames M. Pleasants Company
James M. Pleasants Company SUBMITTAL DATA GAINESVILLE MECHANICAL DECEMBER 20, 2013 PROJECT: GSU: J-183 HUMANITIES LAW BLDG. QUOTE NO:12116 ENGINEER: STEVENS & WILKINSON GASKETED PLATE HEAT EXCHANGER Tag:
More informationOffice of the State Fire Marshal. Fire Rated Doors
Office of the State Fire Marshal Fire Rated Doors Fire Rated Doors These doors serve a purpose. They are manufactured in a way that is to help reduce the spread of fire and smoke. Fire rated doors allow
More informationMaxi-Stamper. 200 to 1,000 Tons STAMPING OUT DOWNTIME
TM Maxi-Stamper 200 to 1,000 Tons STAMPING OUT DOWNTIME Standard Features Steel Fabricated Construction Drive Capacity Rated 1/2 Above Bottom of Stroke Self-Diagnostic Solid State Controller Moveable Operator
More informationROLLING CURTAIN DOOR INSTALLATION, MAINTENANCE & PARTS MANUAL WINDLOCK MODEL 955WL
ROLLING CURTAIN DOOR INSTALLATION, MAINTENANCE & PARTS MANUAL WINDLOCK MODEL 955WL Read manual thoroughly prior to installing door. Rolling steel doors are large, heavy objects that move with the help
More informationHigh Strain Dynamic Load Testing of Drilled Shafts
Supplemental Technical Specification for High Strain Dynamic Load Testing of Drilled Shafts SCDOT Designation: SC-M-712 (9/15) September 3, 2015 1.0 GENERAL This work shall consist of performing high-strain
More informationSection 02702 SEWER PIPE INSTALLATION AND TESTING
PART 1 - GENERAL Section 02702 SEWER PIPE INSTALLATION AND TESTING 1-1. SCOPE. This section covers the installation and testing of all sewer pipe furnished under the following specification sections: Concrete
More informationWastewater Capital Projects Management Standard Construction Specification
CITY AND COUNTY OF DENVER ENGINEERING DIVISION Wastewater Capital Projects Management Standard Construction Specification 10.1 Precast Concrete Pipe 10.1.1 General This section covers material requirements,
More informationDUMP TARP KITS MANUAL TARP KITS ELECTRIC TARP SYSTEMS MECHANICAL CRANK ARM TARP SYSTEMS
ELECTRIC TARP & MANUAL SYSTEMS DUMP TARP KITS MECHANICAL CRANK ARM TARP SYSTEMS MANUAL TARP KITS ELECTRIC TARP SYSTEMS MECHANICAL CRANK ARM TARP SYSTEMS MANUAL TARP KITS TRAILER TARP KITS PARTS & ACCESSORIES
More informationDIVISION 8, METAL SOUND CONTROL DOOR ASSEMBLIES PART 1 GENERAL 1.1 RELATED DOCUMENTS
DIVISION 8, METAL SOUND CONTROL DOOR ASSEMBLIES PART 1 GENERAL 1.1 RELATED DOCUMENTS Drawings and general provisions of the contract, including general and supplementary conditions and other Division 1
More informationChapter 3 Pre-Installation, Foundations and Piers
Chapter 3 Pre-Installation, Foundations and Piers 3-1 Pre-Installation Establishes the minimum requirements for the siting, design, materials, access, and installation of manufactured dwellings, accessory
More informationAC Electric Motors best practice
If you want to learn more about best practice machinery maintenance, or world class mechanical equipment maintenance and installation practices, follow the link to our Online Store and see the Training
More informationLiftAlloy Chain Slings
CHAIN SLING BASICS Slings Lift-All chain slings meet or exceed all OSHA, ASME B30.9 and NACM standards and regulations. chain slings, available in 80 for 7/32" and 7/8"- /4" and 00 for 9/32"-3/4", are
More informationManual piston sampler...m 11
SAMPLING Manual piston sampler...m 11 Screw sampler...prec 22...PREC 100 Slide sampler...pr 55 Rotative screw sampler...prv Piston sampler...p 11 Sampler on belt conveyor...pba Rotating cup sampler...pgr
More informationEMH, Inc. Specifications for
EMH, Inc. Specifications for Top Running Cranes Under Running Cranes Wire Rope Hoists DISCLAIMER These SPECIFICATIONS ARE INTENDED AS GENERAL GUIDELINES ONLY for technical procedure. Questions concerning
More informationCONSOLIDATED EDISON CO. OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003 DISTRIBUTION ENGINEERING DEPARTMENT SUBSTATION & EQUIPMENT SECTION
CONSOLIDATED EDISON CO. OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003 DISTRIBUTION ENGINEERING DEPARTMENT SUBSTATION & EQUIPMENT SECTION SPECIFICATION EO-5023 REVISION 3 MARCH 2003 REQUIREMENTS FOR
More informationA. Contractor shall furnish, to the Engineer, all materials certifications available from the manufacturer for all required materials.
PART 1 GENERAL 1.1 SCOPE A. This item shall include the work necessary for the installation of storm sewer line construction. B. Reference Section 3800 Trenching and Backfill and the General Conditions,
More informationSECTION 10680 MediaStation Model 125 Electric Lateral Files (ELF)
SECTION 10680 MediaStation Model 125 Electric Lateral Files (ELF) PART 1-GENERAL 1.01 RELATED WORK SPECIFIED IN OTHER SECTIONS A. Electrical connections see electrical specifications. 1.02 SUBMITTALS A.
More informationA. Shop Drawing submittals shall include, but not be limited to, the following:
SECTION 26 05 53 IDENTIFICATION FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical
More informationSports and High Mast Lighting Poles Phone: (866) 474-7200 Fax: (817) 924-7049
Sports and High Mast Lighting Poles 4 High Mast Lighting Poles General American LitePole offers a raising and lowering system that allows for ease of maintaining the lighting system at ground level. Ideal
More informationCORROSION ENGINEERING RESIN-BASED POLYMER CONCRETES AND GROUTS
AN ERGONARMOR COMPANY TECHNICAL INFORMATION SPECIFICATION FOR INSTALLATION 07/11 SUPERSEDES 04/00 PAGE 1 OF 6 CORROSION ENGINEERING RESIN-BASED POLYMER CONCRETES AND GROUTS 1. SCOPE 1.1 This specification
More informationInstallation Instructions Double-Hung, Single-Hung, Casement, Awning, Sliding, Picture & Shapes Non-Impact & Impact Resistant Nailing Fin Windows
Installation Instructions Double-Hung, Single-Hung, Casement, Awning, Sliding, Picture & Shapes Non-Impact & Impact Resistant Nailing Fin Windows americancraftsmanwindows.com Project Requirements: Read
More informationCOATING & WRAPPING OF UNDERGROUND PIPING
CONSTRUCTION STANDARD SPECIFICATION DOCUMENT NO :SEC-PJ-000-SPC-PI-008 TOTAL PAGES : 8 Page 1 of 8 CONTENTS 1. SCOPE 2. DEFINITION 3. CODES AND STANDARDS 4. MATERIALS Page 2 of 8 1. SCOPE This specification
More informationSTANDARD SPECIFICATIONS SECTION 05500 METAL FABRICATIONS
STANDARD SPECIFICATIONS SECTION 05500 METAL FABRICATIONS PART 1 GENERAL 1.1 DESCRIPTION A. Section includes requirements for providing metal fabricated items like castings, gratings, hatchways, ladders,
More informationWindow Installation Instructions
Caution The correct installation methods of windows in full frame or insert applications is critical towards achieving the tested performance of the window and longterm enjoyment and energy savings for
More informationSolar Panel Installations
Solar Panel Installations Page 1 of 6 SINGLE-FAMILY RESIDENTIAL CHECKLIST City of Hayward Development Services Department Revised: 7-09-15 PERMIT REQUIREMENTS Permits are required for all solar panel installations.
More informationSPECIFICATION Section 03450 - Insulated Precast Concrete Wall Panels
Lafarge/CPCI Guide Specification SPECIFICATION Section 03450 - Insulated Precast Concrete Wall Panels 1.0 General 1.1 Description.1 The General conditions of the Contract and Supplementary General Conditions
More informationINSTALLATION OF A BAY WINDOW
INSTALLATION OF A BAY WINDOW Installation of a Bay Window These instructions relate to the replacement of an existing bay window or replacement of a straight window with a new bay window, in an opening
More informationSPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT
SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT The purpose of these specifications is to insure that there are minimum
More informationSpecification for Pipe Coating Repairs Offshore
Specification for Pipe Coating Repairs Offshore Specification for Pipe Coating Repairs Offshore 1 of 6 Table of Contents 1.0 SCOPE... 3 2.0 REFERENCE DOCUMENTS... 3 3.0 MATERIALS... 3 4.0 EQUIPMENT AND
More informationSECTION 32 31 13 CHAIN LINK FENCES AND GATES
PART 1 GENERAL 1.1 DESCRIPTION SECTION 32 31 13 CHAIN LINK FENCES AND GATES SPEC WRITER NOTES: 1. Delete or add information between //---// and any other items applicable to project. Cover any item added
More information1.02 DESCRIPTION A. This Section specifies furnishing and installing Cast in Place Detectable/Tactile Warning Surface tiles where indicated.
CAST IN PLACE DETECTABLE/TACTILE WARNING SURFACE TILE PART 1 GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Special Conditions and Division 1 Specifications
More informationCHAIN-LINK FENCES BID SPECIFICATIONS DESCRIPTION
CHAIN-LINK FENCES BID SPECIFICATIONS DESCRIPTION 1 This item shall consist of furnishing and erecting Chain-Link fence in accordance with these specifications and the details shown on the plans and in
More informationSECTION 807 PUMP STATION REHABILITATION
SECTION 807 PUMP STATION REHABILITATION 807-1 DESCRIPTION: Rehabilitation of pump stations shall be defined as the cleaning, removal, repair and/or replacement of any and/or all components including but
More informationVertical Break Parallel (VBP) / Vertical Break Slant (VBS)
August, 2009 Vertical Break Parallel (VBP) / Vertical Break Slant (VBS) Type VBPA (Aluminum) / Type VBPC (Copper) Type VBSA (Aluminum) / Type VBSC (Copper) PASCOR Air Break Switch Technology PASCOR offers
More informationAIRPORT SECURITY FENCING. A. American Society for Testing and Materials (ASTM):
SECTION 02832 AIRPORT SECURITY FENCING PART 1-GENERAL 1.1 SUMMARY A. Section includes: Construct airport security chain-link fence and gate at specified areas and conforming lines, grades, details indicated
More informationSECTION 15410 GROUND WATER STORAGE TANKS
SECTION 15410 GROUND WATER STORAGE TANKS PART 1 GENERAL.01 SCOPE A. Section Includes Requirements for designing, fabricating, and erecting a welded steel ground storage tank..02 SYSTEM DESCRIPTION A. Design
More informationSECTION 16402 UNDERGROUND ELECTRIC SERVICE
SECTION 16402 UNDERGROUND ELECTRIC SERVICE PART 1 GENERAL 1.1 SUMMARY A. Description of System 1. Furnish all labor, materials, and equipment for below grade work external to buildings as required, and
More informationTECHNICAL SPECIFICATION FOR PROJECTION WELDING MACHINE (Qty. 2 Nos.)
TECHNICAL SPECIFICATION FOR PROJECTION WELDING MACHINE (Qty. 2 Nos.) 1. Requirement: Two (02) Nos. DC Type, 3 phase, 3 wire Projection Welding Machine is required for welding of ventilation M.S. / Stainless
More informationLAKE COUNTY ANIMAL SERVICES EXPANSION SECTION 15459
SECTION 15459 PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification sections, apply to work
More informationBUTTERFLY VALVES. An industry leader in underground and in-plant applications. STYLE 4500 3 24 STYLE 1450 30 54. Consult factory for sizes 60 120
An industry leader in underground and in-plant applications. BUTTERFLY VALVES STYLE 4500 3 24 STYLE 1450 30 54 Consult factory for sizes 60 120 C504 Class 150B & 250B M&H Valve is a division of McWane,
More informationSECTION 08 41 1 ALUMINUM FRAMED ENTRANCES and STOREFRONTS. System 402 Flush-Glazed Screw Spline Storefront
PART 1 GENERAL 1.01 Work Included SECTION 08 41 1 ALUMINUM FRAMED ENTRANCES and STOREFRONTS System 402 Flush-Glazed Screw Spline Storefront A. Furnish and install aluminum architectural storefront system
More informationBUTTERFLY VALVES. An industry leader in underground and in-plant applications. STYLE 4500 3 24 STYLE 1450 30 54. Consult factory for sizes 60 120
An industry leader in underground and in-plant applications. BUTTERFLY VALVES STYLE 4500 3 24 STYLE 1450 30 54 Consult factory for sizes 60 120 C504 Class 150B & 250B M&H Valve is a division of McWane,
More informationATLANTA MODEL SPECIFICATIONS
ATLANTA MODEL 50 SPECIFICATIONS Dimensions: Roof Dimensions (point to point) 50-0 Column Dimensions (out to out of columns) 44-0 Eave Height 8-0 Roof Height @ Peak ±21-8⅞ Hip Roof 6:12 pitch Square Feet
More informationSWIMMING POOL, SPA, & HOT TUB GUIDELINES
SWIMMING POOL, SPA, & HOT TUB GUIDELINES Pool permit cost is based on the total value of the project. See Permit Fee Schedule Table 1A. A. Adopted construction codes and installation requirements 1. 2015
More informationWalking and Working Surface Checklist:
Walking and Working Surfaces Purpose: This information is presented to improve the level of safety in our operations, and to inform you that we will comply with the OSHA Standard 29 CFR 1910.23. Responsibility:
More informationSTATE OF NORTH CAROLINA 3950-3 DEPARTMENT OF ADMINISTRATION MARCH 10, 2010 PURCHASE AND CONTRACT DIVISION NEW ISSUE
STATE OF NORTH CAROLINA 3950-3 DEPARTMENT OF ADMINISTRATION MARCH 10, 2010 PURCHASE AND CONTRACT DIVISION SUPERSEDING NEW ISSUE SPECIFICATION FOR TRUCKS, FORKLIFT, ELECTRIC (This specification is released
More informationHMMA 830 HARDWARE SELECTION FOR HOLLOW METAL DOORS AND FRAMES HOLLOW METAL MANUAL -02 NAAMM STANDARD METAL DOORS & FRAMES NAAMM 01 NAAMM 01
HOLLOW METAL MANUAL NAAMM STANDARD HMMA 830-02 METAL S & FRAMES 8d NAAMM 01 02 HARDWARE SELECTION FOR HOLLOW METAL S AND FRAMES NAAMM 01 02 8d METAL S & FRAMES A Division of HOLLOW METAL MANUFACTURERS
More informationJANUS INTERNATIONAL CORPORATION INSTALLATION INSTRUCTIONS Pantheon Mini Operator
JANUS INTERNATIONAL CORPORATION INSTALLATION INSTRUCTIONS Pantheon Mini Operator The Janus Pantheon mini operator does not typically require the provision of any additional site requirements other than
More informationHIGH TENSION CABLE BARRIER
Special Provision September 11, 2006 SECTION 02845 S HIGH TENSION CABLE BARRIER PART 1 GENERAL 1.1 SECTION INCLUDES A. Cable barrier materials and installation procedures. 1.2 RELATED SECTIONS A. Section
More information9300BC SERIES Light Commercial Door Closer
Light Commercial Door Closer general information The 9300BC is a durable, economically priced door closer designed for commercial exterior and interior doors such as storefront and industrial applications.
More informationBasement Window Installation Guide Hopper and Sliding
Basement Window Installation Guide Hopper and Sliding americancraftsmanwindows.com Project Requirements: Installation must comply with all applicable building codes. Existing window frame, wall and weatherresistant
More informationSECTION 07400 STANDING SEAM METAL ROOF
SECTION 07400 STANDING SEAM METAL ROOF PART 1 - GENERAL 1.01 SECTION INCLUDES A. Work described in this section includes pre-formed standing seam metal roofing system complete with clips, perimeter and
More informationAIR RELEASE, CLEANOUT, AND SEWER MANHOLES
AIR RELEASE, CLEANOUT, AND SEWER MANHOLES **From Hartford IM BLDG(10) DESCRIPTION. This work shall consist of the construction of air release, cleanout, and sanitary sewer manholes; and the furnishing
More informationSECTION 22 LIGHTNING PROTECTION SYSTEM
SECTION 22 LIGHTNING PROTECTION SYSTEM 22.01 SCOPE: A. These Specifications shall form a part of the Contract Documents and shall govern construction work for all buildings to be built or modified for
More informationDivision 9. SignaFlor Pad and Pour Flooring System
Division 9 SignaFlor Pad and Pour Flooring System SPECIFICATIONS Page 1. General... 2 1.1 Description 2 1.2 Quality Assurance 2 1.3 Submittals 2 1.4 Delivery and Storage 3 1.5 Warranty 3 1.6 Working Conditions
More informationImportant Information for Installer & Homeowner
Important Information for Installer & Homeowner Homeowner: Please keep this information for your records, do not discard! Installation Instructions for Wood Frame Construction Replacement (See other side
More informationSECTION 02400 - STORM DRAIN SYSTEM
SECTION 02400 - STORM DRAIN SYSTEM CONTENTS: Part 1 - General... 1 1.01 Work Included... 1 1.02 Related Requirements... 1 1.03 Reference Standards... 1 1.04 Quality Assurance... 1 1.05 Measurement And
More informationPANELIZED HOME INSTALLATION GUIDELINE
PANELIZED HOME INSTALLATION GUIDELINE A typical home package will be constructed of Snap-N-Lock Insulated Panels clad with steel skins. 4" panels will be used for the walls, and 6" panels for the roof.
More informationCOMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression
More informationUB1 AIR CONDITIONING UNIT INSTALLATION INSTRUCTIONS
UB1 AIR CONDITIONING UNIT INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS: Carefully read these instructions before installing your new air-conditioner. AUSTRALIAN AUTOMOTIVE AIR AL00500054E 1 Table
More information