15kV GENERATOR CIRCUIT BREAKERS & 15KV STATION SERVICES SWITCHGEAR FOR HOLM POWER PLANT GENERATOR LINE BREAKER 52G ADDITION TECHNICAL SPECIFICATIONS

Size: px
Start display at page:

Download "15kV GENERATOR CIRCUIT BREAKERS & 15KV STATION SERVICES SWITCHGEAR FOR HOLM POWER PLANT GENERATOR LINE BREAKER 52G ADDITION TECHNICAL SPECIFICATIONS"

Transcription

1 1. SCOPE 1.01 SCOPE OF WORK A. The Contractor shall design, manufacture, test and deliver two (2) complete 15kV, 4000A generator rated breakers, two (2) 1200A feeder breakers, enclosures and all incoming, outgoing and interconnecting non-segregated phase bus with supports, current transformers, voltage transformers, surge arresters and capacitors as well as transitions and transition enclosures for interfacing switchgear non-segregated phase bus to the existing Isophase bus. Note: Non-Segregated phase bus to the existing isophase bus to be proposed as an option. B. The equipment will be used to provide generator circuit breakers (52-G1 & 52-G2) between each of the two 13.8kV, 95 MVA hydro generator units and the respective 84 MVA, 13.8/230 kv main generator step up (GSU) transformer banks at Holm Powerhouse. Additionally, the feeder breakers in each line up will be used to replace the existing 13.8kV current limiting reactors, and the station service supply and interconnection to the respective new replacement 500kVA, kV station service transformers (by Others). C. The existing installation consists of 4000 ampere isolated phase bus directly connecting each hydro generator unit to the respective main GSU transformer bank. The existing station service is connected to the generator output via a current limiting reactor directly tapped to the isophase bus. New potential transformers, surge suppression equipment and capacitors will be mounted within the 15kV switchgear lineup and will replace existing equipment also currently tapped directly to the isophase bus QUALITY ASSURANCE All materials used shall be new, of high grade and with properties best suited to the working environment SUBMITTALS A. All submittals shall conform to formats, conditions, and requirements as specified in Attachment D Submittals. B. Submit with the bid proposal the following: 1. Certificate of Compliance or complete list of all deviations from the drawings and specifications. ITSF /CD Page 1 of 18

2 2. Submit outline drawings for each 15kV switchgear lineup and non-segregated bus assembly including isophase bus transitions and enclosures, showing support point dimensions of enclosures and accessories, unit weight, and the following information: a. 15 kv Vacuum or SF6 Circuit Breaker Rated maximum voltage. Rated voltage range factor. Rated frequency. Rated continuous current. Short circuit interrupting. Rated standard operating duty. Rated permissible tripping delay. Rated interrupting time. Rated re-closing time. Rated dielectric strength. Rated control voltage. Load current switching. Circuit breaker enclosure dimensions. Circuit breaker weight. b. Current Transformers - Rating, data sheets, and catalog cuts. c. Potential Transformers - Rating, data sheets, and catalog cuts. d. Surge Arresters - Rating, data sheets, and catalog cuts. e. Capacitors - Rating, data sheets, and catalog cuts. f. Spare Circuit Breakers- Ratings and description. g. Arc Flash Mitigation System Description and Data Sheets h. Non-Segregated Phase Bus Duct or other Buswork Maximum Voltage Basic Impulse Level Rated frequency withstand Rated continuous current Momentary withstand current Conductor total temperature limit Enclosure total temperature limit All information shall be in the English language, clearly readable with IEEE, NEMA and ANSI symbols, device numbers and other requirements. C. Submit Contractor s installation instructions and certification. Instruction shall include procedures for items that are to be shipped disassembled but are to be assembled and interconnected for operation when installed. Instructions shall contain special rigging ITSF /CD Page 2 of 18

3 instructions as required for unloading, moving by skidding or rolling and lifting each 15kV switchgear lineup or non-segregated bus assembly, transitions, component, or accessories. D. Submit O&M Manual and spare parts list. The O&M manual shall include provisions for cleaning the 15kV switchgear lineups and non-segregated buswork assemblies and servicing or replacing components. Also included shall be instructions for accessing internally mounted components, special enclosure assembly and disassembly requirements, and setting and adjustment procedures and other information designed to assist in proper operation and periodic maintenance of the equipment being supplied. All manuals, instructions and supporting drawings and parts lists supplied by the manufacturer and supplemental instructions and data supplied by accessory manufacturers shall be in English, clearly readable and arranged in such format as to make the subject items easily identifiable. Each manual shall have an index and/or table of contents identifying each item/subject and shall include the location (name of manual, section, and/or page number) of information therein. All values shall be given in English units and may be in both English and metric values. See Attachment E, Operation and Maintenance Data. E. Drawing Requirements Shop drawings shall consist of the following: 1. Arrangement drawings. 2. Dimensioned drawings with plan and elevation views and other views, as necessary for clarity. 3. Cross-sectional drawings with views of bus bar arrangement, supporting blocks, and the enclosure arrangement. 4. Bus termination drawings showing details to connecting to isolated phase bus and vacuum or SF6 circuit breaker. 5. One-line diagram of each 15kV switchgear lineup and non-segregated bus arrangement. 6. Three-line diagram of each 15kV switchgear lineup and non-segregated bus arrangement. 7. Control schematic for each 15kV switchgear and non-segregated bus arrangement. 8. Control diagram for each type of 15kV breaker and non-segregated bus arrangement. 9. Wiring diagrams for each 15kV switchgear lineup and non-segregated bus arrangement. ITSF /CD Page 3 of 18

4 1.04 REFERENCES 10. Miscellaneous schematics, wiring diagrams, and outline drawings for miscellaneous components as necessary. The publications listed below form a part of this specification to the extent referenced. The publications are referred to in the text by basic designation. The latest addenda, revisions, and supplements in effect as of the date of purchase including any subsections there of shall be used in all cases. This list is not intended to be all inclusive. Therefore, it is the Contractor s responsibility to verify all applicable standard requirements. A. American National Standards Institute/Institute of Electrical and Electronic Engineering (ANSI/IEEE) 1. ANSI/IEEE Standard for AC High Voltage Generator Circuit Breakers Rated on a Symmetrical Current Basis 2. ANSI/IEEE C37.04 Standard Rating Structure for AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis 3. ANSI/IEEE C37.06 American National Standard for Switchgear AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis Preferred Ratings and Related Required Capabilities 4. ANSI/IEEE C37.11 Standard Requirements for Electrical Control for High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis 5. ANSI/IEEE C Standard for Metalclad and Station-Type Cubicle Switchgear 6. ANSI/IEEE C37.23 Standard for Metal Enclosed Bus and Calculating Losses in Isolated Phase Bus 7. ANSI/IEEE C37.32 Schedules of Preferred Ratings, Manufacturing Specifications, and Application Guide for the High Voltage Air Switches, Bus Supports, and Switch Accessories B. National Electrical Manufacturers Association (NEMA): NEMA SG4 Standard Publication for Alternating-Current High-Voltage Circuit Breakers C. Other standards and codes: Where applicable codes and standards from the following agencies shall apply: 1. OSHA (Federal) and Cal-OSHA (State of California) 2. National Electrical Code (NEC) ITSF /CD Page 4 of 18

5 1.05 ENVIRONMENTAL REQUIREMENTS FOR 15KV SWITCHGEAR LINEUPS A. Seismic Conditions All equipment and components including their supports and anchorages, supplied by the Contractor, shall be designed in accordance with provisions of the appropriate sections of the City and County of San Francisco Building Code, latest edition and the latest edition of the California Building code to withstand seismic loads in addition to other loads. The test response spectrum shall be based upon a 5% minimum dampening factor, IBC: a peak of 2.57g s ( Hz) and ZPA of 1.0g s applied at the base of the equipment. The tests shall fully envelop this response spectrum for all equipment natural frequencies up to at least 35 Hz. Equipment shall not be required to function properly during periods of seismic disturbance but shall be capable of manual restart following a disturbance. B. Ambient Environmental Conditions 2. EQUIPMENT All equipment is to be installed indoors in the following conditions: 1. Ambient air temperature (maximum) 104 deg. F (40 deg. C) 2. Altitude above sea level 2227-feet KV SWITCHGEAR LINEUPS A. Ratings: Circuit breakers and included switchgear bus shall be rated on the symmetrical basis, and shall have the following minimum ratings: Maximum Voltage kv 15 Nominal System Voltage, kv 13.8 Nominal 3-phase MVA Class 1000 Rated Voltage Range Factor (k) 1.3 Rated BIL (KV) 95 Rated Continuous Current, Amps - Breakers Generator Breakers 4000 Feeder Breakers 1200 Rated Continuous Current, Amps Bus Incoming from generator 4000 Outgoing to transformer 4000 Feeder breaker interconnections and taps 1200 Rated Short Circuit Current at Maximum kv, ka rms 37 ITSF /CD Page 5 of 18

6 Rated Interrupting Time, Cycles 5 Rated Permissible Tripping Delay, seconds 2 Related Required Capabilities at Maximum Voltage of 15 kv RMS Maximum Voltage, kv RMS 15 Symmetrical Interrupting Capability, amps, rms 48,000 3-Seconds Short Time Current Carrying Capability, amp, rms 48,000 Closing and Latching Capability Amps, rms 77,000 B. General Requirements for 15kV Switchgear Enclosures and Breakers 1. Stationary Structures The new switchgear shall consist of vacuum or SF6 circuit breaker units and auxiliary units as required, all assembled to form rigid, self-supporting, completely metalenclosed structures. In each unit, the major parts of the primary circuit such as the circuit breaker, buses, voltage transformers and control power transformers shall be completely enclosed by grounded metal barriers. This shall include an inner barrier in front of, or as a part of, the circuit breaker. 2. Arrangement The switchgear shall include the units shown on the attached one-line diagram and shall be indoor construction. It shall be used on a 13,800 volt high resistance ground system. 3. Circuit Breaker Compartment Each circuit breaker compartment shall be designed to house 15,000 volt, removable element circuit breakers. The stationary primary disconnect contacts shall be constructed of silver plated copper. Grounded metal safety shutters shall be provided which isolate all primary connections in the circuit breaker compartment when the breaker is withdrawn from the connected position. 4. Ground Bus A continuous ground bus of 1/4-inch by two-inch copper shall be installed in the lineups with connections to each grounding contact and each compartment ground terminal. All joints shall be made with at least two (2) 3/8 inch zinc plated; bronze iridescent chromate conversion coated steel bolts per joint. 5. Bus Compartment The main generator bus shall be rated 4,000 ampere. Bus bars shall have a continuous current rating in accordance with ANSI standards of temperature rise and documented ITSF /CD Page 6 of 18

7 6. Finish by design test. All joints shall be silver plated with at least FOUR (4) bolts per joint. Bus bars will be braced to withstand stresses developed by current equal to the main power circuit breaker closure, carry and interrupt rating. All bus connections 1200A or less shall be a minimum of two (2) bolts per joint. All interior and exterior steel surfaces shall be chemically cleaned after fabrication and treated with a rust-inhibitive phosphatizing or equivalent treatment to provide a bond between the primer and metal surfaces. The switchgear exterior surfaces shall then be primed, filled where necessary and finished with not less than two (2) coats cathodic electro-deposition of ANSI 61 gray epoxy paint. Finish coat shall be gloss. Interior surfaces shall receive not less than one (1) coat of corrosion-resisting paint in accordance with manufacturer s standard practice. 7. External Power Connections Provisions for termination of external power connections shall be as indicated in the specifics for each breaker. Where indicated, termination drillings for cable connections shall conform to standard NEMA 2-hole configuration. 8. Arc Flash System The entire 15kV switchgear lineup shall be provided with an arc flash mitigation system. As a minimum, each enclosure housing equipment capable of creating an arc flash shall have arc flash detection sensors. The arc flash relaying will include provisions to open remote disconnect devices. Arc flashes relaying to utilize photo electric arc detection devices with current magnitude supervision unless otherwise approved. Submit details of the proposed or alternate arc flash mitigation system with the bid proposal KV CIRCUIT BREAKER CUBICLE EQUIPMENT A. CIRCUIT BREAKERS The circuit breakers shall be rated 15,000 volts, maximum, 3-phase, 60 hertz, with a nominal interrupting rating of 1,000 MVA. All circuit breakers of equal rating shall be interchangeable. The circuit breakers shall be operated by an electrically charged, mechanically and electrically trip-free, stored-energy, operating mechanism. Provision shall be included for manual charging of the mechanism and for contact wear inspection. The circuit breakers shall be equipped with secondary disconnecting contacts, which shall automatically engage in the connected position. ITSF /CD Page 7 of 18

8 The breaker compartment shall be furnished with a mechanism that will move the breaker between the operating and disconnect position. The mechanism shall be designed so that the breaker will be self-aligning and will be held rigidly in the operating position without the necessity of locking bars or bolts. In the disconnect position, the breaker shall be easily removable from the compartment. Interlocks shall prevent moving the breakers to or from the operating position unless its contacts are in the open position. As a further safety precaution, the operating springs shall be discharged automatically when the breaker is rolled fully into the compartment or is moved into the disconnect position. Means shall be provided for padlocking the racking mechanism in either the connected (operating) position or the disconnected position. When locked in the disconnected position, the breaker shall be removable from the compartment. Padlocking the breaker shall not interfere with the operation of the breaker or its mechanism. The circuit breaker control voltage shall be 125 volts DC. B. Instrument Transformers 1. Current Transformers Current transformers shall have ratios as indicated in the details of each switchgear unit. The transformers shall have a mechanical rating equal to the momentary rating of the circuit breakers, and shall be insulated for full voltage rating of the switchgear. 2. Voltage Transformers C. Control Wiring Voltage transformers shall be drawout type, equipped with current-limiting fuses, and shall have accuracy as required by the details of each switchgear unit. The ratio shall be as indicted in each switchgear unit specification. 1. Secondary control wiring shall be minimum No. 14, extra-flexible, stranded, tinnedcopper control wire, rated 600 volts, except for CT secondary circuits which shall be No.10. Secondary control wire shall be armored or enclosed in grounded metal troughs where they pass through primary compartments. Wire markers shall be furnished at each termination. Control wiring to be terminated on terminal blocks with marker strips numbered in agreement with connection diagrams and schematics. 2. All inter-unit wiring, except CT secondary circuits, is to be made at the unit terminal boards. Connections wired directly between devices, installed in different units, will not be permitted. 3. All devices shall be completely wired, tested, and ready for use. SFPUC-HHWP will be responsible for setting all relays. ITSF /CD Page 8 of 18

9 D. Devices 4. Provide terminal blocks for all external sources and for manufacturer connection of the wiring for all panel and cabinet devices, including instrument transformers. Terminal blocks, fuse blocks, CT shorting blocks, and other control devices are to be mounted inside the enclosure, separate and isolated from the high voltage compartment. 5. Any spare or unused contacts of all devices are to be connected to suitable terminal blocks for use by SFPUC-HHWP. 6. Provide space for the addition of a minimum of one (1) 12-pole terminal block for customer use. 7. All internal wiring by Contractor shall be identified with wire labels or markers at each end of each wire. These markers shall correspond to the wire destination shown on the manufacturer s wiring and schematic diagrams. Wire markers shall be sleeve type. Adhesive wrap around labels are NOT acceptable. 8. Control and instrument wires are to be terminated with insulated locking fork or spade type lugs. Current transformer leads will be terminated with ring type lugs terminals. Wires terminating on devices with terminals that do not accept spade lugs shall be soldered or terminated with ferrules. Terminating bare wire will NOT be permitted. 9. All CT s, PT s and other equipment supplied as part of the 15kV switchgear shall be accessible. If located behind bolted coverplates, no devices or wiring shall be required to be removed for access. Where indicated, all protection, instrumentation and control devices shall be as shown, or equal. Instruments shall be switchboard type, with one percent (1%) accuracy. E. Basic Circuit Breaker Unit 1. The basic metal-clad unit for each individual circuit breaker shall consist of one metalclad compartment and include: a. 1,200 ampere, three phases, copper main bus, (does not apply to generator breaker incoming and outgoing bus). b. Hinged front door. c. Vacuum or SF6 power circuit breaker, three pole, single throw, 15kV with 1000 MVA nominal interrupting rating with a minimum close and latch rating of 77,000 ampere RMS and arranged for 125 volt DC close and trip. d. One (1) set of test switch terminal blocks to short out all CT wiring to meters and instruments, and open all voltage wiring to meters and instruments, leaving ITSF /CD Page 9 of 18

10 protective relay circuits complete (to disconnect instrument and meters for calibration). e. All primary cable terminations will be with high compression, NEMA 2- hole lugs provided by SFPUC HHWP. f. Circuit breaker control switch, with green and red indicating lights and with pull-out position (close in test position only). Refer to Appendix B for additional description. g. Minimum of four (4) each a and b truck operated contact (TOC) switches. h. Separately fused circuit with auxiliary close and trip relays to provide for remote control from a Synchronizing Panel or customers SCADA system. i. Provision for padlocking in the withdrawn (disconnected) position. j. Each breaker to have two (2) extra isolated a and two (2) extra isolated b contacts wired to terminal board for customers use. k. Provision for connection of external control wiring for control of circuit breaker while in the withdrawn (disconnected) position. This is for electrical maintenance only. l. CT s for differential functions shall meet the minimum standard relaying accuracy classification of C200. m. Space heater, separate, fused, humidistat control, powered from an external 120 volt AC Source. All heaters in a 15kV switchgear lineup shall be connected to a single control circuit. n. Mechanical operations counter to register breaker trip operations, non-resetable. o. White indicating light to indicate that the stored energy device is fully charged (include as part of control switch). p. Remote racking capability. q. Wheels for ease of movement. r. No lift truck, rails, ramps, channels, or transport devices of any kind shall be required for placing the circuit breaker in the fully connected position, once breaker is inserted into the cell SPECIFIC REQUIREMENTS/SPECIFICATIONS A. Metal Clad Switchgear, Generator Line Breaker 52G Addition for Holm Power Plant Unit 2 Item 1 New 15kVSwitchgear lineup H2 (reference drawings GB-HP-5000-SK)) One (1) line-up of indoor metal-clad 15kVswitchgear consisting of the following units and arranged from left to right when viewed from the hinged panel side of the structure in the ITSF /CD Page 10 of 18

11 following order: 1. Unit H2 52-G2 Holm Unit 2 Generator Line Breaker as identified in Section 2.02 and to meet or exceed IEEE Standard C for generator circuit breakers. Included is: Qty. Description A Bus incoming and outgoing 1 Basic unit with 4000 ampere breaker, natural convection cooled, and provision for connection to incoming and outgoing non-segregated 4000A bus system. 9 Phase CT s, 4000/5 ampere, Accuracy Class C200, thermal rated 2.0, for metering and remote relaying 3 3 phase sets of PT s connected WYE-GND WYE-GND, to provide 14, volt line-to-line ratio, connected as shown on the reference drawings 8 Isolated stationary auxiliary switches wired to terminals for use by the utility and as interlocks. Switches are to be cubicle mounted, not breaker mounted, so that the b contact remains closed and made up, and the a contact remains open when the breaker is in the test and disconnect positions. The b contacts shall be able to open and the a contacts shall be able to close, only when the breaker is in the full connected position. Minimum supply is four (4) a and four (4) b contacts. 1 Breaker control switch as indicated A, 3-phase tap to 4000A incoming line (generator) side bus for connection of two (2) 3/c 500 kcmil cables (Exciter Transformer) 1 SEL-2411 Programmable Automation Controller. Refer to Appendix B for additional description. 3 Polymer surge arresters, consisting of metal oxide disks, station class rated 15kV rms and MCOV 12.7kV rms designed and tested to ANSI/IEEE C Connections as shown on reference drawings. 3 High voltage shunt capacitors, 0.25 microfarad per pole, non-pcb dielectric, protective capacitors with internal discharge resistors, for indoor mounting, 95kV BIL, designed to IEEE Standard 18. Connections as shown on reference drawings. 2. Unit H , Holm Unit 2 Station Service Interconnect Breaker consisting of all equipment as identified in Section 2.02 and: Qty. Description ampere bus (minimum) ITSF /CD Page 11 of 18

12 1 Basic unit with 1200 ampere breaker and provision for connection of three (3) 3/C 500 kcmil cables. 3 Phase CT s, 4000/5 ampere, accuracy class C200, thermal rated 2.0, for remote differential relaying. 3 Phase CT s multi ratio, 400/5 ampere, accuracy class C200, thermal rated 2.0, for remote relaying. 3 PT s connected delta-delta to provide 14, volt line to line, connected to the outgoing (load) side of the breaker. 8 Isolated stationary auxiliary switches wired to terminals for use by the utility and as interlocks. Switches are to be cubicle mounted, not breaker mounted, so that the b contact remains closed and made up, and the a contact remains open when the breaker is in the test and disconnect positions. The b contacts shall be able to open and the a contacts shall be able to close, only when the breaker is in the full connected position. Minimum supply is four (4) a and four (4) b contacts. 1 Circuit breaker control as indicated 3. Unit H Holm Unit 2 Station Service breaker consisting of all equipment as identified in Section 2.02 and: Qty. Description A Bus (minimum) 1 Basic unit with 1200 ampere breaker and bus connection to transition section A transition sections with provision for direct connection to station service transformer (by Others). Transition section to be fitted with a blank Glastic or equal insulated panel for field modification 3 Phase CT s, 4000/5 ampere, Accuracy Class C200, thermal rated 2.0, for remote differential relaying 3 Phase CT s, multi ratio, 400/5 ampere accuracy class C200, thermal rated 2.0 for remote relaying. 8 Isolated stationary auxiliary switches wired to terminals for use by the utility and as interlocks. Switches are to be cubicle mounted, not breaker mounted, so that the b contact remains closed and made up, and the a contact remains open when the breaker is in the test and disconnect positions. The b contacts shall be able to open and the a contacts shall be able to close, only when the breaker is in the full connected position. Minimum supply is four (4) a and four (4) b contacts. 1 Circuit breaker control switch as indicated. ITSF /CD Page 12 of 18

13 B. Metal-clad switchgear, Generator Line Breaker 52G Addition for Holm Power Plant Unit 1. Item 2 New Switchgear (see attached Drawing No. GB-HP-5000-SK) One (1) line-up of indoor metal-clad switchgear consisting of the following units and arranged from left to right when viewed from the hinged panel side of the structure in the following order: 1. Unit 52-1 Holm Unit 1 Station Service Breaker consisting of the same as Unit H H Holm Unit 1 Station Service Interconnect Breaker consisting of the same as H except: without the 3PT s. 3. H1 52-G1 Holm Unit 1 Generator Breaker consisting of the same as unit H2 52-G2. C. Schematics, Generator Line Breaker 52G Addition for Holm Power Plant Unit 1 and Unit 2 Schematic diagrams for each switchgear lineup shall indicate all internal wiring and terminal boards. Field interface connection points shall be clearly identified NON SEGRATED BUS AND TRANSITION TO ISOPHASE BUS REQUIREMENTS A. General Description The non-segregated bus assembly shall include all required equipment, enclosures, transitions, hardware and miscellaneous components necessary to complete the bus transition between the generator breaker cubical and the existing isophase bus. This non-segregated bus work will connect the incoming (generator) side and the outgoing (GSU) side busses of each generator breaker cubical to the respective existing isolated phase busses. Alternate bus work systems will be considered. Submit details and supporting documentation with proposal. B. Ratings: Interconnecting buswork shall be rated on the symmetrical basis, and shall have the following minimum ratings: Current ratings based on 40 deg. C. Maximum voltage Basic impulse insulation level Rated frequency withstand Rated continuous current Momentary withstand current Conductor total temperature limit Enclosure total temperature limit 15kV rms 95kV 19Kv (1 minute dry) 60Hz 4000 Amperes 37kA Symmetrical 105 deg. C for tinned surface 80 deg. C ITSF /CD Page 13 of 18

14 C. Construction Each non-segregated phase bus assembly shall consist of two copper five-eighths inch by six inch (5/8-inch x 6-inch) bus bars per phase supported on insulators and insulated with antihygroscopic material and rated as described herein. Transition connections to the isolated phase bus shall be made via adequately sized flexible tinned copper connectors. All contact surfaces on all joints, splice plates, termination and other transitions intended for bolted connections shall be silver plated. All hardware necessary for assembly shall be supplied and be of new manufacture. Bus joint, splice, and transition hardware shall be high strength plated steel and include necessary spring pressure lock (Belleville), flat and lock washers. The complete nonsegregated bus assembly shall be designed and constructed to meet the following requirements: 1. Operate within specified temperature limits while continuously operating at the rated current, without supplemental (fan) cooling. 2. Bus bar temperature rise shall not exceed 65 C while operating at the maximum current rating. The limitation of hottest spot temperature shall meet the requirements of ANSI Standard C37.23, Table Conductor support system shall remain fully functional after exposure to system design short circuit conditions. Different 15kV bus work systems utilizing other construction methods that do not conform to a single enclosure configuration as described above will be considered. Contractor shall submit with the proposal all supporting documentation. Other such bus systems shall meet or exceed the performance requirements described herein. D. Insulation Bus bars shall be insulated with extruded polymer sleeve, and mounted with corona control devices in molded, glass-reinforced polyester support blocks or approved equal. Insulation shall conform to the following requirements: 1. The conductors shall have fully insulated conductors and conductor joints. Insulating materials shall be non-hygroscopic and flame retardant, rated for continuous operation at 105 C (class 105). The insulation level of the combined system shall meet or exceed the requirements of ANSI Standard C37.23 Table 5 2. Bus joints shall be insulated with EPR/PVC tapes or molded vinyl boots. 3. All bolted joints to be insulated shall be wrapped with a conductive mesh of the same material as the conductors prior to insulation. This mesh serves as a corona suppressant. E. Enclosure ITSF /CD Page 14 of 18

15 Non-segregated bus and non-segregated to isophase bus transition enclosures shall be fabricated from high grade aluminum to minimize circulating currents and magnetic heating. The transition enclosure shall not be electrically connected to any portion of the existing isophase bus. Existing electrical continuity between existing isophase bus sections modified for insertion of the generator breakers (52G1 and 52G2) shall be maintained but not connected to ground. Grounding of new non-segregated bus and transition enclosure shall comply with NEC and establish industry practices. Ventilation louvers shall be provided to maximize natural convection cooling of the enclosed bus and fittings. Access to bolted connection points and transitions shall be via hinged and/or removable panels. Provision for supporting all non-segregated bus duct work and isophase bus transition enclosures shall be included in the design of each enclosure segment. The installed duct work will ultimately be supported from overhead within the powerhouse. The following design requirements shall be met: 1. All exposed surfaces are to be finished as indicated in this specification. 2. Enclosure shall be designed for a maximum temperature rise of 40 C above ambient. 3. Indoor non-ventilated drip-proof NEMA 1 construction. Housing will include gasketed solid top and bottom covers and solid sides to prevent entry of falling liquid or solid particles. 4. Exposed hardware shall be stainless steel. Screened breather/drains are required along the enclosure bottom and at all low points along the installation. 5. Space heater, separate, fused, humidistat control, powered from an external 120 volt AC Source. All heaters in a non-segregated bus duct shall be connected to a single control circuit. Provide similarly configured heaters for non-segregated to isolated phase buswork transition enclosure. F. Grounding The bus housing shall be designed to carry the system ground fault current for a period of two seconds without excessive temperature rise. If necessary, a separate copper ground bus shall be provided on the inside or outside of the bus enclosure. Separate ground bus may terminate to equipment or a ground pad for the connection to the station ground. Flexible jumpers shall be provided at all expansion joints to ensure ground continuity. If the housing is used as the ground path, housing ground continuity shall be maintained at shipping splits by the use of housing ground spice plates. G. Conductor Support Systems Bus conductors shall be rigidly supported within the enclosure and shall be braced to withstand ITSF /CD Page 15 of 18

16 the short circuit currents specified herein. Bus conductors shall be supported on nonhygroscopic, track resistant and flame retardant molded high alumina ceramic blocks. H. Connections Contractor shall provide with the proposal the intended method for interconnecting isolated phase bus to the non- segregated phase bus for approval. Each equipment termination shall include flexible housing joint and flexible connectors to the equipment terminals MANUFACTURER S REPRESENTATIVES TECHNICAL FIELD SUPPORT/TRAINING A. The Supplier shall provide a qualified, factory trained, field service representative to provide field support and assist in commissioning and startup of both 15kV switchgear units H1 and H2. The Field service representative shall be responsible for certifying in writing that the equipment has been installed, adjusted and tested in accordance with the manufacturer s recommendations. The Supplier shall be responsible for all costs associated with travel and accommodation for their field service representative during this period. B. The Supplier shall provide a qualified representative(s) for a training session for up to ten City personnel, at a job site or location to be determined by the City. The object of the training program is to provide complete instructions on the proper operation and maintenance of the assembly, 15kV switchgear, circuit breakers and major components with each generator breaker switchgear assembly. C. It will be the responsibility of the Contractor to pay all their travel and lodging expenses related to these required field support and training services FACTORY TESTS Each 15kV switchgear lineup shall be tested prior to shipment. A direct current high potential impulse test shall be conducted at the factory; in addition the following tests in accordance with ANSI C "Metal-Clad & Station Type Cubicle Switchgear". A. Rated continuous current. B. Flame resistance insulation. C. Shop tests recommended by Contractor. A representative for SFPUC-HHWP shall be permitted to witness shop tests. The Supplier shall provide 10-days advance notice of scheduled tests. The Supplier shall pay, arrange, and schedule for the City Representative to be present for the shop testing at the manufacturer s factory for travel over 125 miles radius from Moccasin, CA. Bid price ITSF /CD Page 16 of 18

17 shall include airfare, local transportation, meals, and lodging for the City representative. Meals and lodging rates shall comply with the current Federal Rates for the Continental USA. The rates are available from the following website: then click on per diem rates. 3. BID REQUIREMENTS 3.01 SUPPLIER SHALL PROVIDE WITH THE PROPOSAL THE FOLLOWING: A. Price for indoor switchgear line-up per Section 2.03 New 15kV Switchgear Lineup H2, as specified. B. Price for indoor switchgear line-up, Section 2.03 New 15kV Switchgear Lineup H1, as specified. C. Price for incoming and outgoing non-segregated buswork transitions for generator line breaker 52-G1 D. Price for incoming and outgoing non-segregated buswork transitions for generator line breaker 52-G2 E. Price to add spare breaker as required for the 1200A breakers. F. Price to add spare breaker as required for the 43000A breakers. G. Price to add breaker lifting device if not included in base bid. H. Price for additional phase CT s, 4000/5 ampere, C200 accuracy to unit 52-G1 and 52-G2 for remote relay. Twelve each per generator. (For a total of 24 CT s). I. Cost for qualified, factory trained, field service representative to provide field support and assist in commissioning and startup of both 15kV switchgear units H1 and H2. The Field Service Representative shall be responsible for certifying in writing that the equipment has been installed, adjusted and tested in accordance with the manufacturer s recommendations. J. Total cost to provide a qualified representative(s) for training session for up to ten City personnel, at a job site or location to be determined by the City. K. Descriptive and dimensional data necessary to evaluate the proposal. Data shall include, but not be limited to, a front view layout showing proposed arrangement and approximate weights. L. Provide ratings for the generator breaker to include: Rated interrupting time ITSF /CD Page 17 of 18

18 Rated short circuit current Asymmetrical interrupting capability Interrupting capability for line to ground faults Close and latch capability Transient recovery voltage rating First pole to clear factor Load current switching capability No-load mechanical switching capability Out of phase current switching rating M. Provide price, details, and supporting documentation for any proposed arc flash mitigation system. N. Provide details and supporting documentation for alternate interconnecting buswork system. O. State warranty. P. State the delivery schedule of drawings and equipment EQUIPMENT SUPPLIED BY CITY A. 125VDC control power. B. Power for Space Heaters. C. Compression lugs for 15kV cable terminations. D. Field installation of supplied equipment. ***END OF ATTACHMENT*** ITSF /CD Page 18 of 18

19 APPENDIX B SEL Relay Requirements Electro Switch Requirements ITSF /CD Page 19 of 18

20 APPENDIX B STYLE No.: MODEL No.: SEL RELAY REQUIREMENTS 2411 PROGRAMMMABLE AUTOMATION CONTROLLER A1A1A711A I/O LISTING: INPUT OUTPUT POINT FUNCTION POINT FUNCTION Main Card A: IN 101 OUT 101 IN 102 OUT 102 OUT 103 NC Alarm Card C: 4 DI & 4(HC) DO, 52-G1, 52-G2 IN a Status OUT 301 Trip IN 302 TOC Status OUT 302 Close IN 303 TCM OUT 303 IN 304 Spring Charge OUT 304 Card D: 4 DI & 4(HC) DO, 52-1, 52-2 IN a Status OUT 401 Trip IN 402 TOC Status OUT 402 Close IN 403 TCM OUT 403 IN 404 Spring Charge OUT 404 Card E: Voltage Input 300VAC, 52-G1 (27), 52-G2 (27) Line PT's Card Z: 4 DI/4 (HC) DO, 52-11, IN a Status OUT 601 Trip IN 602 TOC Status OUT 602 Close IN 603 TCM OUT 603 IN 604 Spring Charge OUT 604 Page 20 of 21

21 ATTACHMENT C APPENDIX B STYLE No.: MODEL No.: ELECTRO SWITCH REQUIREMENTS CIRCUIT BREAKER CONTROL SWITCH 24PC50D PISTOL GRIP HANDLE WITH PULL-TO-LOCK, SPRING RETURN TO NORMAL LED INDICATORS: RED WHITE GREEN (125VDC) DECKS CONTACTS PULL-TO-LOCK TRIP NAT NAC CLOSE X X X X X X X X Page 21 of 21

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. 2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to

More information

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

Submit shop drawings for equipment provided under this section Shop drawings shall indicate: Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,

More information

Sample - No Commercial Use

Sample - No Commercial Use COMPLETE REVISION October 2010 Electrical PIP ELSSG01 Design and Fabrication of Low-Voltage Metal-Enclosed AC Power Circuit Breaker Switchgear PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort

More information

Specification Guide. for RVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers

Specification Guide. for RVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers Specification Guide for RVAC Direct Replacement AC Medium Voltage Circuit Breakers Table of Contents 1.0 General Work Scope...3 2.0 Standards...3 3.0 Supplier Qualifications...4 4.0 Circuit Breaker Element

More information

Masterclad Medium Voltage Passive Arc-Resistant Switchgear

Masterclad Medium Voltage Passive Arc-Resistant Switchgear Masterclad Medium Voltage Passive Arc-Resistant Switchgear Square D Masterclad medium voltage passive arc-resistant (AR) switchgear is designed with utilities and industrial customers in mind who demand

More information

MEDIUM VOLTAGE METAL CLAD SWITCHGEAR

MEDIUM VOLTAGE METAL CLAD SWITCHGEAR MEDIUM VOLTAGE METAL CLAD SWITCHGEAR PART 1 - GENERAL 1.1 DESCRIPTION This section specifies the furnishing, installation, connection and testing of the medium voltage switchgear. 1.2 SWITCHGEAR FEATURES

More information

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation Basis of Design This section applies to the design relating to low voltage switchboards. Design Criteria UW Class N1 facilities main switchboards shall be rear accessible. The main, tie and feeder breakers

More information

SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS. Presented by SAI Advanced Power Solutions

SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS. Presented by SAI Advanced Power Solutions SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS POWER DISTRIBUTION RACKS IN A MISSION CRITICAL SYSTEM MODULES IN A MISSION CRITICAL SYSTEM UPS Convertor Main Inverter Load Battery BPC UPS & BATTERY

More information

SWITCHGEAR Section 16. SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less.

SWITCHGEAR Section 16. SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less. PART 1 - GENERAL SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less. RELATED SECTIONS Division 16 Section "Basic Electrical Materials and Methods" for general

More information

SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches

SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches PART 1 GENERAL 1.01 Scope Optional Standby Power Generator Systems A. Furnish and install automatic transfer switches

More information

Secondary Unit Substations

Secondary Unit Substations 14 SWITCHGEAR Secondary Unit Substations Overview Siemens offers a wide variety of unit substation designs to meet customer requirements. A unit substation consists of one or more transformers mechanically

More information

SECTION 16346A METAL-CLAD MEDIUM VOLTAGE ARC RESISTANT SWITCHGEAR

SECTION 16346A METAL-CLAD MEDIUM VOLTAGE ARC RESISTANT SWITCHGEAR METAL-CLAD MEDIUM VOLTAGE ARC RESISTANT SWITCHGEAR PART 1 GENERAL 1.01 SCOPE A. The Contractor shall furnish and install the equipment as specified herein and as shown on the contract drawings. 1.02 RELATED

More information

PIP ELSSG02 Design and Fabrication of Medium Voltage Metal-Clad Switchgear from 4.76 kv to 38 kv

PIP ELSSG02 Design and Fabrication of Medium Voltage Metal-Clad Switchgear from 4.76 kv to 38 kv Electrical Design and Fabrication of Medium Voltage Metal-Clad Switchgear from 4.76 kv to 38 kv Table of Contents 1. Introduction...2 1.1 Purpose... 2 1.2 Scope... 2 2. References...2 2.1... 2 2.2 Industry

More information

26 3213.13 Diesel Engine Driven Generators Page 1 of 6

26 3213.13 Diesel Engine Driven Generators Page 1 of 6 Last Update: December 8, 2014 A. Description of System Consultant s Handbook Page 1 of 6 1. Provide a diesel engine driven electric generating unit, factory assembled, tested and certified to operate at

More information

FFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid

FFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars Presented By: Greg Pelster & Robert Schmid FFI Ferrie, Franzmann Industries LOW VOLTAGE SWITCHGEAR & LOW VOLTAGE

More information

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132

More information

01.4IB.51200B PowlVac-AR Arc Resistant Switchgear. 5kV & 15kV 1200A, 2000A, 3000A, & 4000A Forced Cooled. Powered by Safety

01.4IB.51200B PowlVac-AR Arc Resistant Switchgear. 5kV & 15kV 1200A, 2000A, 3000A, & 4000A Forced Cooled. Powered by Safety PowlVac-AR Arc Resistant Switchgear 1200A, 2000A, 3000A, & 4000A Forced Cooled Powered by Safety PowlVac-AR Arc Resistant Switchgear 01.4IB.51200B Contact Information Powell Electrical Systems, Inc. www.powellind.com

More information

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4 CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,

More information

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations. DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,

More information

CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH

CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH Cat transfer switches are designed for a variety of standby power applications. They provide flexibility, reliability and value in a

More information

The following components are common to most cubicles; this example is an ABB HK cubicle.

The following components are common to most cubicles; this example is an ABB HK cubicle. 4.0 CIRCUIT BREAKER CUBICLE Learning Objectives The circuit breaker cubicle is the component of the switchgear that holds the circuit breaker, and the controls and cabling for the distribution system.

More information

Customer Substation Manual 08/05/02

Customer Substation Manual 08/05/02 Customer Substation Manual Table of Contents Section Page 2 of 85 Description 0 Preface 010.00 General 010.10 Information Required for the Review of New Customer Substations 010.20 New Customer Substation

More information

This section applies to the design and installation of transformers.

This section applies to the design and installation of transformers. ELECTRICAL: TRANSFORMERS BASIS OF DESIGN This section applies to the design and installation of transformers. Design Criteria 13.8-kV equipment shall be 15-kV class. Coordinate with short-circuit studies

More information

Hyperlinks are Inactive

Hyperlinks are Inactive Prepared by: NIB/EOB PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES 05503 Department: Electric T&D Section: T&D Engineering and Technical Support Approved by: G.O. Duru (GOD)

More information

Unified requirements for systems with voltages above 1 kv up to 15 kv

Unified requirements for systems with voltages above 1 kv up to 15 kv (1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to

More information

ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013

ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013 ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013 READ CAREFULLY These instructions are intended to cover good practices in

More information

QUESTIONS and ANSWERS RFB 745-15-9894, Metal Clad Switchgear and Power Control Room

QUESTIONS and ANSWERS RFB 745-15-9894, Metal Clad Switchgear and Power Control Room QUESTIONS and ANSWERS RFB 745-15-9894, Metal Clad Switchgear and Power Control Room 1) When you click on the UTHSCSA Drawing the site takes you to the E-1 drawing no other. Will there be other drawings

More information

SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC INTEGRATED SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671A SECTION 16671A

SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC INTEGRATED SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671A SECTION 16671A SURGE PROTECTIVE DEVICES (SPDs) INTEGRATED UNITS LOW VOLTAGE AC SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS PART 1 GENERAL 01 02 03 SCOPE The Contractor shall furnish and install the Surge Protective

More information

SECTION 16341 MEDIUM VOLTAGE SWITCHGEAR

SECTION 16341 MEDIUM VOLTAGE SWITCHGEAR PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes metal-enclosed

More information

LVA Take Offs in Bid Manager

LVA Take Offs in Bid Manager Electrical Sales and Distributor Training Low Voltage Assemblies (LVA) LVA Take Offs in Bid Manager This job aid helps to define some of the common selection questions that are encountered when configuring

More information

CONSOLIDATED EDISON CO. OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003 DISTRIBUTION ENGINEERING DEPARTMENT SUBSTATION & EQUIPMENT SECTION

CONSOLIDATED EDISON CO. OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003 DISTRIBUTION ENGINEERING DEPARTMENT SUBSTATION & EQUIPMENT SECTION CONSOLIDATED EDISON CO. OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003 DISTRIBUTION ENGINEERING DEPARTMENT SUBSTATION & EQUIPMENT SECTION SPECIFICATION EO-5023 REVISION 3 MARCH 2003 REQUIREMENTS FOR

More information

Section 9: Power Distribution Equipment Bill Brown, P.E., Square D Engineering Services

Section 9: Power Distribution Equipment Bill Brown, P.E., Square D Engineering Services Section 9: Power Distribution Equipment Bill Brown, P.E., Square D Engineering Services Introduction Power Distribution Equipment is a term generally used to describe any apparatus used for the generation,

More information

SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL

SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL 1.1 SUMMARY A. This section describes the requirements for the installation of Power Monitors and associated

More information

DOCUMENT 009102 - ADDENDUM NO. 2. Issued to all Bidders: Date: February 3, 2015. Contract Name: 13,800-Volt and 480-Volt Switchgear

DOCUMENT 009102 - ADDENDUM NO. 2. Issued to all Bidders: Date: February 3, 2015. Contract Name: 13,800-Volt and 480-Volt Switchgear DOCUMENT 009102 - ADDENDUM NO. 2 Issued to all Bidders: Date: February 3, 2015 Contract Name: 13,800-Volt and 480-Volt Switchgear SUA Bid No.: #21-14/15 This addendum forms a part of the Bid described

More information

ELECTRIC UTILITY SERVICE EQUIPMENT REQUIREMENTS COMMITTEE, EUSERC

ELECTRIC UTILITY SERVICE EQUIPMENT REQUIREMENTS COMMITTEE, EUSERC ELECTRICAL SERVICE REQUIREMENTS ELECTRIC UTILITY SERVICE EQUIPMENT REQUIREMENTS COMMITTEE, EUSERC TABLE OF CONTENTS TITLE SECTION NO. List of Approved Electric Utility Service Equipment Requirements Committee

More information

NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems. Safe energy distribution that meets the highest industrial requirements

NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems. Safe energy distribution that meets the highest industrial requirements NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems Safe energy distribution that meets the highest industrial requirements NATUS switchgear systems your advantages minimal use of insulant

More information

Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components

Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components Course No: E02-010 Credit: 2 PDH Boris Shvartsberg, Ph.D., P.E., P.M.P. Continuing Education

More information

SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS

SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS PART 1 - GENERAL 1.01 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

How To Build A Germany Power Plant

How To Build A Germany Power Plant Medium Voltage Air Insulated Motor Control Featuring AdvanceTM Technology. Medium Voltage Motor Control Center Product Description Contemporary Design Advance TM medium voltage motor control center (MVMCC)

More information

Primary and Secondary Electrical Distribution Systems

Primary and Secondary Electrical Distribution Systems Primary and Secondary Electrical Distribution Systems Critical Facilities Round Table 12th Quarterly Membership Meeting June 2, 2006 David D. Roybal. P.E. Eaton Electrical Cutler-Hammer Products Utility

More information

HVL 5 38 kv Load Interrupter Switchgear. The Standard for Performance, Protection and Dependability

HVL 5 38 kv Load Interrupter Switchgear. The Standard for Performance, Protection and Dependability HVL 5 38 kv Load Interrupter Switchgear The Standard for Performance, Protection and Dependability For a generation of engineers, Square D High Voltage Load (HVL ) Interrupter Switchgear by Schneider Electric

More information

BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET

BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET Berthold Electric Company s Generator Connection Cabinet provides a quick and convenient station to connect a portable generator to a facility s main service

More information

Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms

Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms ABB innovations for changing demands ABB (www.abb.com) is a leader in power and automation technologies that enables utility

More information

Power Management Module 2. Installation

Power Management Module 2. Installation Power Management Module 2 30 300 kva Installation Table of Contents Safety... 1 Safety Instructions... 1 Certification Standards Three Phase... 1 Product Safety... 2 Special Precautions... 2 System Description...

More information

Switchgear Capabilities. NexGear is a Division of PowerSecure NASDAQ: POWR

Switchgear Capabilities. NexGear is a Division of PowerSecure NASDAQ: POWR Switchgear Capabilities NexGear is a Division of PowerSecure NASDAQ: POWR Discussion Points Introducing PowerSecure Introducing NexGear Solutions Offered Scope of Services Examples of Work Q & A NexGear,

More information

Spending too much to maintain aging switchgear? Circuit breaker solutions from Square D Services.

Spending too much to maintain aging switchgear? Circuit breaker solutions from Square D Services. Spending too much to maintain aging switchgear? Circuit breaker solutions from Square D Services. Spending too much time and money on equipment maintenance? Square D Services: Your source for circuit breaker

More information

Medium Voltage Products. ZN1 12 kv arc-proof air-insulated switchgear for primary distribution

Medium Voltage Products. ZN1 12 kv arc-proof air-insulated switchgear for primary distribution Medium Voltage Products ZN1 12 kv arc-proof air-insulated switchgear for primary distribution ZN1 an innovative switchgear for power distribution requirements ABB ZN1 primary distribution switchgear is

More information

RAY-MAX Integrated Solar Power Strip

RAY-MAX Integrated Solar Power Strip RAY-MAX Integrated Solar Power Strip 600008, 600009, 600010, 600208, 600209, 600210 Owner s Manual NEXTRONEX, INC. Revision Date: 10/27/14 Contents 1. Safety Instructions... 3 2. General Equipment Warnings...

More information

TOP RUNNING SINGLE GIRDER BRIDGE CRANE

TOP RUNNING SINGLE GIRDER BRIDGE CRANE SECTION 14630 TOP RUNNING SINGLE GIRDER BRIDGE CRANE 1.01 SUMMARY PART 1- GENERAL A. The work required under this section shall include the designing, manufacturing, shipping, installing and field testing

More information

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Metering and Monitoring. Basis of Design

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Metering and Monitoring. Basis of Design Basis of Design This section applies to the design, installation and integration of metering and monitoring equipment, including: hardware installed in the electrical service and distribution equipment,

More information

Power Plant Electrical Distribution Systems

Power Plant Electrical Distribution Systems PDH Course E184 Power Plant Electrical Distribution Systems Gary W Castleberry, PE 2008 PDH Center 2410 Dakota Lakes Drive Herndon, VA 20171-2995 Phone: 703-478-6833 Fax: 703-481-9535 www.pdhcenter.com

More information

Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services

Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services Circuit Breakers and Switchgear Thomas Greer Director of Engineering TLG Services Presentation Outline Switchgear Definition Overcurrent Protection Devices Circuit Breaker Trip Curves and Coordination

More information

METER REQUIREMENTS GENERAL REQUIREMENTS SECTION D

METER REQUIREMENTS GENERAL REQUIREMENTS SECTION D 12 - ELECTRIC SERVICE HANDBOOK SECTION D METER REQUIREMENTS This chapter gives you information on Central Lincoln s metering requirements. It's divided into three sections: General requirements This section

More information

Switchgear and Metal-Enclosed Bus

Switchgear and Metal-Enclosed Bus Section 18 Switchgear and Metal-Enclosed Bus 180. SWITCHGEAR ASSEMBLIES 180A. General Requirements for All Switchgear. This rule covers general requirements for all switchgear. Examples of switchgear found

More information

SECTION 16461 DRY-TYPE TRANSFORMERS

SECTION 16461 DRY-TYPE TRANSFORMERS SECTION 16461 PART 1 - GENERAL 1.1 SECTION INCLUDES A. Furnishing and installation of and testing of cast resin dry type MV/LV distribution transformer in accordance with specifications and drawings. Any

More information

Bussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1

Bussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1 How to configure Part Numbers: Step : Select Switch Amperage Power Module Switch Rating (Amps) Power Module Switch Catalog No. 30 3 60 6 00 200 2 400 4 Step 2: Select Options Needed 5 Bussmann Power Module

More information

Addendum #2 Contract UK-11-13

Addendum #2 Contract UK-11-13 Addendum #2 Contract UK-11-13 Utilities Kingston Purchase and Replacement of Switchgear at Kingston Hydro Substation MS11 March 25, 2011 Delivered to: All RFP recipients Total number of pages: Nine (9)

More information

METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV. tgood.com. Energy. Fast.

METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV. tgood.com. Energy. Fast. METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV tgood.com Energy. Fast. TGOOD produces over 5000 switchgear units annually for projects around the globe PRODUCT OVERVIEW Integral substation component

More information

ELECTRIC METERING COMMERCIAL & INDUSTRIAL

ELECTRIC METERING COMMERCIAL & INDUSTRIAL ELECTRIC METERING COMMERCIAL & 1.0 INDEX 1.0 INDEX 2.0 SCOPE 3.0 GENERAL REQUIREMENTS 4.0 METER LOCATIONS 5.0 UNDERGROUND TERMINATIONS 6.0 METERING TRANSFORMER ENCLOSURES 7.0 SINGLE CUSTOMER METER INSTALLATIONS

More information

PRODUCT GUIDE. SL Medium Voltage IEC Vacuum Contactors

PRODUCT GUIDE. SL Medium Voltage IEC Vacuum Contactors PRODUCT GUIDE SL Medium Voltage IEC Vacuum Contactors Table of Contents 1 Overview Introduction....................................................2 Features........................................................2

More information

Lightning Arresters P30027 18 KVA P30038 10 KVA. Description & Installation

Lightning Arresters P30027 18 KVA P30038 10 KVA. Description & Installation Lightning Arresters P30027 18 KVA P30038 10 KVA Description & Installation Printed in USA 09/11 TO330 Rev. B Table of Contents Page 1.0 SCOPE 2 2.0 PRODUCT OVERVIEW 2 2.1 Intended Uses 2 2.2 Lightning

More information

Low Voltage Transformers Sealed, General Purpose, Dry Type

Low Voltage Transformers Sealed, General Purpose, Dry Type Low Voltage Transformers Sealed, General Purpose, Dry Type Catalog 7400CT9601R4/08 08 Class 7400 CONTENTS Description..............................................Page Introduction.................................................

More information

AUTOMATIC TRANSFER SWITCH. Changeover Type from 250A to 2500A

AUTOMATIC TRANSFER SWITCH. Changeover Type from 250A to 2500A AUTOMATIC TRANSFER SWITCH Changeover Type from 250A to 2500A Table of Contents Preamble 1.1 Theoretical base 1.2 Selection the size of automatic transfer switch 1.3 Automatic transfer switch components

More information

ELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F

ELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F ELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F TABLE OF CONTENTS Appendix F - Electrical Engineering Design Criteria F.1 Introduction...F-1 F.2 Codes and Standards...F-1 F.3 Switchyard and Transformers...F-1

More information

FAQs-Main switchboard design criteria

FAQs-Main switchboard design criteria FAQs-Main switchboard design criteria Q: What is the Australian standard for main switchboards? Current Australian standard is AS/NZS 3439.1: 2002 originating from IEC 60439. The new series of standard

More information

What are the basic electrical safety issues and remedies in solar photovoltaic installations?

What are the basic electrical safety issues and remedies in solar photovoltaic installations? What are the basic electrical safety issues and remedies in solar photovoltaic installations? Presented by: Behzad Eghtesady City of Los Angeles Department of Building and Safety Topics Covered Photovoltaic

More information

SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC EXTERNAL SIDEMOUNT SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671B SECTION 16671B

SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC EXTERNAL SIDEMOUNT SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671B SECTION 16671B SURGE PROTECTIVE DEVICES (SPDs) EXTERNAL SIDEMOUNT UNITS LOW VOLTAGE AC SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION PART 1 GENERAL 01 02 03 SCOPE The Contractor shall furnish and install the Surge Protective

More information

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930. 2009 MTE Corporation

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930. 2009 MTE Corporation MTE SERIES RLW World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930 2009 MTE Corporation IMPORTANT USER INFORMATION NOTICE MTE Series RLW reactors are components designed to improve the reliability

More information

PREFACE. Your comments or suggestions are welcome and appreciated. They should be sent to:

PREFACE. Your comments or suggestions are welcome and appreciated. They should be sent to: PREFACE UL developed the Dead-Front Switchboard Marking Guide for code authorities, electric utilities, contractors, installers, users, designers, and other interested parties to aid in understanding deadfront

More information

Engineers Edge, LLC PDH & Professional Training

Engineers Edge, LLC PDH & Professional Training 510 N. Crosslane Rd. Monroe, Georgia 30656 (770) 266-6915 fax (678) 643-1758 Engineers Edge, LLC PDH & Professional Training Copyright, All Rights Reserved Engineers Edge, LLC An Introduction to Interior

More information

Installation, Operation and Maintenance Instructions Viper -S Solid Dielectric Reclosers Three Phase, Vacuum Recloser.

Installation, Operation and Maintenance Instructions Viper -S Solid Dielectric Reclosers Three Phase, Vacuum Recloser. Installation, Operation and Maintenance Instructions Viper -S Solid Dielectric Reclosers Three Phase, Vacuum Recloser GWI 531-1 Rev. 6 May, 2008 Supersedes Rev. 5 dated October,2005 Table of Contents Section

More information

MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS

MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS Meher Capacitors offers reliable and innovative products and solutions in the fields of Reactive Power Compensation, Power Quality and Energy

More information

25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp and 1250 Amp

25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp and 1250 Amp Page 1 2015 Grounded Metal Equipment Plate Equipment Connection Bus Bar or Other Component 15 kv or 25 kv Separable Insulated Connector (elbow) Equipment Connection Power Cable Power Cable Grounded Metal

More information

Medium Voltage Motor Control Assemblies

Medium Voltage Motor Control Assemblies Medium Voltage Motor Control Assemblies Arc Resistant AMPGARD.1 Product............................................. 2 Application........................................... 2 Features, Benefits and Functions...................................

More information

Learning Module 13: Panelboards and Switchboards. 101 Basic Series

Learning Module 13: Panelboards and Switchboards. 101 Basic Series Learning Module 13: Panelboards and Switchboards 101 Basic Series What You Will Learn We ll step through each of these topics in detail: Introduction 4 Definitions 4 Similarities Between Panelboards and

More information

IRRIGATION PUMPING Table of Contents - Section 900

IRRIGATION PUMPING Table of Contents - Section 900 IRRIGATION PUMPING Table of Contents - Section 900 PARAGRAPH 900.1 GENERAL 1 900.2 METERING REQUIREMENTS 1 900.3 CUSTOMER S CONTROL EQUIPMENT 2 900.4 SERVICE CONDUCTOR REQUIREMENTS 2 900.5 RECOMMENDATIONS

More information

FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval.

FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval. Polk School District Specifications for the New Fire Alarm in the Existing Building Eastside Elementary School FIRE ALARM SYSTEM 1.01 SUBMITTALS A. Shop drawings shall be submitted as follows: 1. Manufacturer's

More information

AMFA-27 AMFA-29. Operator s Manual & Installation Instructions. Rev. 2.5

AMFA-27 AMFA-29. Operator s Manual & Installation Instructions. Rev. 2.5 AMFA-27 AMFA-29 Operator s Manual & Installation Instructions Rev. 2.5 Date: 17 July, 2010 Permanently-connected, utility Interactive, single-phase, inverters Model AMFA-27 WIND TURBINE INVERTER (240 VAC

More information

TP-C2 Motor Operator CLEAVELAND / PRICE INC. Bulletin DB-111B12

TP-C2 Motor Operator CLEAVELAND / PRICE INC. Bulletin DB-111B12 Bulletin DB-111B12 TP-C2 Motor Operator CLEAVELAND / PRICE INC. 14000 Rt. 993, Trafford, PA 15085 (724) 864-4177 FAX (724) 864-9040 Email: sales@cleavelandprice.com Cleaveland/Price Type TP-C2 Motor Operator

More information

16300 MEDIUM VOLTAGE DISTRIBUTION

16300 MEDIUM VOLTAGE DISTRIBUTION 16300 MEDIUM VOLTAGE PART 1: GENERAL 1.01 SYSTEM DESCRIPTION A. Most new loads will be served from the underground electric distribution system. This system is a primary open loop configuration served

More information

Short Circuit Current Calculations

Short Circuit Current Calculations Introduction Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective devices based on these sections mandate that

More information

SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT

SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION A. The Work specified in this Section consists of designing, furnishing and installing factory-assembled

More information

SECTION 26 29 23 VARIABLE FREQUENCY DRIVES

SECTION 26 29 23 VARIABLE FREQUENCY DRIVES SECTION 26 29 23 VARIABLE FREQUENCY DRIVES PART 1 GENERAL 1.01 SCOPE A. Furnish and install individual freestanding variable frequency AC drives (VFD) as shown on the Drawings and specified herein. 1.02

More information

MCC Ratings. Voltage Rating

MCC Ratings. Voltage Rating MCC Ratings In addition to the various ratings of individual components used in motor control centers, the overall ratings of the motor control center must also be considered. Voltage Rating Motor control

More information

Contents. Description. Product Selection Guide

Contents. Description. Product Selection Guide .1 Medium Voltage Switchgear Introduction Indoor Type VCP-W Metal-Clad Switchgear Assembly (5/15 kv shown) Product Selection Guide Product Offering Chart Metal-Enclosed Contents Description Notes Additional

More information

D. Infrared scanning reports with pictures printed in a final report with any deficiencies and actions taken to rectify.

D. Infrared scanning reports with pictures printed in a final report with any deficiencies and actions taken to rectify. SECTION 263354 STATIC UPS TESTING AND COMMISSIONING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes 1. System start-up services. 2. Battery charging. 3. Load bank testing. 4. Battery load testing. 5.

More information

Project Name: Nortrax Section 26 41 00 Project No: 13-013 SURGE PROTECTION DEVICES Page 1

Project Name: Nortrax Section 26 41 00 Project No: 13-013 SURGE PROTECTION DEVICES Page 1 Page 1 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. General: Drawings and general provisions of the Contract, including General and Supplementary Conditions and Divisions 1 Specification sections apply to

More information

DESIGN CLARIFICATION (DC)

DESIGN CLARIFICATION (DC) DESIGN CLARIFICATION (DC) Owner: Victor Valley Wastewater Reclamation Authority Date: 03/03/2015 Contractor: W M Lyles Carollo Project No.: 8299A.20 Project Name: Subregional WRPs DC No.: 001 DC Title:

More information

SECTION 26 1316 MEDIUM-VOLTAGE FUSIBLE INTERRUPTER SWITCHGEAR

SECTION 26 1316 MEDIUM-VOLTAGE FUSIBLE INTERRUPTER SWITCHGEAR SECTION 26 1316 MEDIUM-VOLTAGE FUSIBLE INTERRUPTER SWITCHGEAR PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

COMPARISON OF ANSI/IEEE AND IEC REQUIREMENTS FOR LOW- VOLTAGE SWITCHGEAR

COMPARISON OF ANSI/IEEE AND IEC REQUIREMENTS FOR LOW- VOLTAGE SWITCHGEAR COMPARISON OF ANSI/IEEE AND IEC REQUIREMENTS FOR LOW- VOLTAGE SWITCHGEAR Copyright Material IEEE Paper No. PCIC 2003-13 Eddie Wilkie Eaton Cutler-Hammer 3990 Old Tasso Road NE Cleveland, TN 37312 USA Abstract

More information

FIRE ALARM AND DETECTION SYSTEMS SECTION 16721

FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 PART 1 - GENERAL 1.01 WORK INCLUDED FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 A. Provide a complete fully addressable, power limited, fire detection and evacuation system. The system shall be connected

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS LIGHTING CONTROL PANELS 4 AND 8 RELAYS INSTALLATION INSTRUCTIONS INSTALLATION OVERVIEW The installation instructions contained in this document are provided as a guide for proper and reliable installation.

More information

8146/5 Series Breaker Panelboards

8146/5 Series Breaker Panelboards 8146/5 Series Breaker Panelboards DISTRIBUTION BREAKER PANELBOARDS FOR HAZARDOUS & CORROSIVE ENVIRONMENTS Breaker Panels Features: Wide variety of Flameproof branch circuit breakers for Zone 1 & Division

More information

Power-Zone 4 Arc Resistant Low Voltage Switchgear

Power-Zone 4 Arc Resistant Low Voltage Switchgear Power-Zone 4 Arc Resistant Low Voltage Switchgear with ArcBlok Technology Make the most of your energy SM Workplace safety 2 I Power-Zone 4 Arc Resistant Low Voltage Switchgear Five to ten arc flash explosions

More information

Power IT MV Air Insulated Switchgear. Technical Information and Application Guide Featuring Advance TM and SafeGear TM Technology

Power IT MV Air Insulated Switchgear. Technical Information and Application Guide Featuring Advance TM and SafeGear TM Technology Power IT MV Air Insulated Switchgear Technical Information and Application Guide Featuring Advance TM and SafeGear TM Technology Introduction Millions of ABB circuit breakers are installed and operating

More information

Co-location Interconnect Power Panel (CIPP) Installation Guide

Co-location Interconnect Power Panel (CIPP) Installation Guide Co-location Interconnect Power Panel (CIPP) Installation Guide Document INS-97xxxxxxx This guide covers the following part numbers- Trimm 97xxxxxxx Series Table of Contents Section 1 - General Information...

More information

NRG. Intelligent Engine Start Battery Charger. The Smart Choice for Mission-Critical Engine Starting

NRG. Intelligent Engine Start Battery Charger. The Smart Choice for Mission-Critical Engine Starting NRG Intelligent Engine Start Battery Charger The Smart Choice for Mission-Critical Engine Starting Fast, accurate, mission-critical charging gives best starting reliability 4-rate, temperature-compensated

More information

SECTION 23 81 43 HEAT PUMPS

SECTION 23 81 43 HEAT PUMPS SECTION 23 81 43 HEAT PUMPS PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop heat pumps. 1.2 REFERENCES A. American Society of Heating, Refrigerating and Air-Conditioning Engineers:

More information

OVR-3SP Recloser with PCD Control Style Guide 1VAL263901-SG March 30, 2009 Revision B

OVR-3SP Recloser with PCD Control Style Guide 1VAL263901-SG March 30, 2009 Revision B OVR-3SP Recloser with PCD Control Style Guide 1VAL263901-SG March 30, 2009 Revision B The OVR-3SP three-phase recloser style guide aids in the proper selection of your OVR-3SP style number. The OVR-3SP

More information

James M. Pleasants Company

James M. Pleasants Company James M. Pleasants Company SUBMITTAL DATA GAINESVILLE MECHANICAL DECEMBER 20, 2013 PROJECT: GSU: J-183 HUMANITIES LAW BLDG. QUOTE NO:12116 ENGINEER: STEVENS & WILKINSON GASKETED PLATE HEAT EXCHANGER Tag:

More information