1 P01 Solar Impact Sensor QLS60 Sensor for acquiring the impact of solar radiation Output signal DC V 2-wire current output ma Use The solar impact sensor is used as a reference sensor in heating, ventilation and air conditioning plants where compensation of solar radiation is required. Solar compensation is necessary where buildings or building sections with large window areas are subjected to strong solar radiation, especially in plants where thermostatic radiator valves cannot be used. Ordering When ordering, please give name and type reference: Solar impact sensor QLS60 Equipment combinations The sensor can be used in connection with all types of systems and devices capable of acquiring and handling the sensor s ma or DC V output signal. Technical design To determine the impact of solar radiation, the sensor uses a solar cell which acquires the level of radiation. That cell generates an electrical current depending on the extent of radiation, which is then evaluated by the sensor. As a result, the sensor delivers an output signal of ma or DC V, which is proportional to the solar radiation range. CE1N1943en Building Technologies

2 Mechanical design The solar impact sensor is designed for wall mounting. The cable must be introduced from the bottom. The sensor consists of plastic housing with a transparent cover and a Pg 9 cable entry gland. The solar cell is located in the cover, the sensor electronics with the connection terminals inside the housing. The cover is secured to the housing with 2 screws and can be removed. A rubber seal is used between housing and cover to ensure degree of protection IP 65. The measured values from the photocell to the sensor electronics are transmitted via a 2-wire connection. Housing closed Housing open Z01 U G I M Legend 1 Solar cell 2 Connection terminals 3 Rubber seal 4 Sealing gland (conduit adapter supplied for US / Asia Pacific) Engineering notes The correct mounting location of the sensor is decisive for achieving the desired effect. It must be determined by the planning engineer. The information given in section "Mounting and installation notes" must be observed. Power supply line and measuring line must be run together. The voltage output can be used only if the current output is not required. Mixed operation is not possible. The measuring voltage is calculated as follows: 10V U = E W / m where E = solar radiation in W/m 2 When using the current output, the voltage output cannot be used. The electronic circuit receives its power from the current supply. For that, the current measuring voltage must lie in the range of DC V. The measuring current is calculated as follows: 16 ma I = 4 ma E W / m where E = solar radiation in W/m 2 2/5

3 Fitting and installation notes When deciding on the mounting location, it should first be determined for which part of the building (heating zone) the sensor shall acquire the solar radiation. It must be located on the wall having the windows of the rooms that are affected by solar radiation. This is, in general: The wall of the heating zone with the window area which receives the largest part of solar radiation for the longest period of time As high as possible, but at least 3 m above the ground Easily accessible (to facilitate checking), approximately 30 cm beside a window Note: Not in the shade of trees, houses, telephone poles, etc. The sensor must not be painted over. 30 cm 1943Z Z Z04 > 3 m The solar impact sensor is supplied complete with Mounting Instructions. Commissioning notes When commissioning the plant, the wiring must be checked. No settings can be made on the sensor itself. Disposal The devices are considered electronics devices for disposal in terms of European Directive 2012/19/EU and may not be disposed of as domestic waste. Dispose of the device via the channels provided for this purpose. Comply with all local and currently applicable laws and regulations. 3/5

4 Technical data Power supply (G, M) Range of use Functional data Measured value outputs (U, I) Electrical connections Degree of protection Environmental conditions Directives and Standards Environmental compatibility Materials and colors Weight Rated voltage range AC 24 V ±20 % (SELV) or DC 24 V ( V) (SELV) Rated frequency at AC 24 V 50/60 Hz Rated power consumption max. 2.5 VA (1 W) External supply line protection Fuse slow max. 10 A or Circuit breaker max. 13 A Characteristic B, C, D according to EN or Power source with current limitation of max. 10 A Measuring range W/m 2 Time constant t 63 Voltage signal output (U) DC V W/m 2 Current signal output (I) ma W/m 2 Perm. cable lengths with copper cable 1.0 mm 2 50 m 1.5 mm m 2.5 mm m 2 s Screw terminals for 2 x 1.5 mm 2 or 1 x 2.5 mm 2 Protection degree of housing IP65 according to EN Protection class III according to EN Operation to IEC Climatic conditions Class 3K5 Temperature C Humidity (noncondensing) % r. h. Mechanical conditions Class 3M2 Transportation to IEC Climatic conditions Class 2K3 Temperature C Humidity <95 % r. h. Mechanical conditions Class 2M2 Product standard EN Electrical equipment for measurement, control and laboratory use. EU Conformity (CE) CE1T1943xx *) The product environmental declaration CE1E1943 *) contains data on environmentally compatible product design and assessment (RoHS compliance, materials composition, packaging, environmental benefit, disposal). Housing Housing cover Packaging Without packaging Polycarbonate / RAL 9002 (gray-white) Polycarbonate (transparent), solar panel moulded in silicone / RAL9010 cardboard approx kg *) The documents can be downloaded from 4/5

5 Connection diagrams Internal diagrams G Operating voltage AC 24 V or DC 24 V (DC V) M Measuring neutral (power supply and signal), Solar radiation measuring signal ma U Solar radiation measuring signal DC V I Operating voltage DC 24 V (DC V) Connection diagrams Voltage measurement with AC supply: DC supply: U G I (1) (2) (3) M (4) 1943A01 U G I (1) (2) (3) M (4) 1943A02 DC V AC 24 V DC V DC V Current measurement: Dimensions ,5 8 SW19 Drilling plan Dimensions in mm 1943M01 5/ Siemens Switzerland Ltd. Subject to change

SEZ220. Signal Converter. Synco 200. With preprogrammed standard applications Freely programmable Menu-driven operation. Use

SEZ220. Signal Converter. Synco 200. With preprogrammed standard applications Freely programmable Menu-driven operation. Use s 5 146 Synco 200 Signal Converter SEZ220 With preprogrammed standard applications Freely programmable enu-driven operation Use The signal converter is for use in HVAC plant to provide minimum / maximum

More information

RRV934. Multi-controller. Synco living

RRV934. Multi-controller. Synco living s 2 709 Synco living Multi-controller RRV934 RF-based multi-controller For precontrol of up to 2 room groups For control of ventilation plant with up to 3 stages RF communication based on KNX standard

More information

Digital input modules

Digital input modules 8 172 TX-I/O Digital input modules TXM1.8D TXM1.16D Two fully compatible versions: TXM1.8D: 8 inputs, each with a three-color LED (green, yellow or red) TXM1.16D: As TXM1.8X, but 16 inputs, each with a

More information

Room Temperature Sensors

Room Temperature Sensors 1 721 1721P010 1721P020 QAA25 QAA27 oom Temperature Sensors with and without setpoint adjuster...27 Use In heating, ventilating and air conditioning plants, especially where a high level of comfort is

More information

Flush-mount room temperature sensor AQR2531ANW.

Flush-mount room temperature sensor AQR2531ANW. 1 408 Flush-mount room temperature sensor AQR2531... Passive sensor to acquire room temperature. Field of use 0 +50 C Use In heating, ventilation and air conditioning plants, primarily in the comfort range

More information

QFP910. Water detector. Building Technologies. CE1N2732en. Synco living

QFP910. Water detector. Building Technologies. CE1N2732en. Synco living 2 732 Synco living Water detector QFP910 Wireless radio sensor to record water puddles RF communication based on KNX standard (868 MHz unidirectional) Battery operation with standard 1.5 V batteries Use

More information

Air damper actuators

Air damper actuators 4 634 OpenAir TM Air damper actuators GDB...1 GLB...1 Rotary version, / AC 230 V Electronic motor driven actuators for three-position and modulating control Nominal torque 5 Nm (GDB), 10 Nm (GLB) Mechanically

More information

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw 4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and

More information

QFP910. Water detector. Building Technologies. CE1N2732en 2016-03-01. Synco living

QFP910. Water detector. Building Technologies. CE1N2732en 2016-03-01. Synco living 2 732 Synco living Water detector QFP910 Wireless radio sensor to record water puddles RF communication based on KNX standard (868 MHz unidirectional) Battery operation with standard 1.5 V batteries Use

More information

Differential Pressure Sensors for air and non-corrosive gases, with calibration certificate

Differential Pressure Sensors for air and non-corrosive gases, with calibration certificate 1 919 1919P01 1919P03 QBM65/C, QBM75-1U/C Differential Pressure Sensors for air and non-corrosive gases, with calibration certificate QBM751-1/C QBM65/C QBM75/C Highly accurate measurements with calibration

More information

RDJ10RF/SET. Wireless room temperature controller with 24-hour time switch and LCD. Programmable, for heating systems

RDJ10RF/SET. Wireless room temperature controller with 24-hour time switch and LCD. Programmable, for heating systems 3 072 RDJ10RF RCR10/433 Wireless room temperature controller with 24-hour time switch and LCD Programmable, for heating systems RDJ10RF/SET Operating modes: Automatic, Comfort, Energy Saving, and Frost

More information

Flush-mounted room thermostats

Flush-mounted room thermostats s 3 076 RDF300, RDF300.02, RDF340 RDF400.01 RDF600 RDF600 Flush-mounted room thermostats for 2-pipe, 2-pipe with el. heater and 4-pipe fan coil units for use with compressors in DX type equipment RDF300

More information

Input module, input/output module

Input module, input/output module Sinteso / Cerberus PRO Input module, input/output module FDCI221, FDCIO221 Input module and input/output module for the automatically addressed detector line Input module FDCI221: Monitorable contact input

More information

Power Supply and Indicator Unit Type 5024-1. Fig. 1 Type 5024-1. Mounting and Operating Instructions EB 9539 EN

Power Supply and Indicator Unit Type 5024-1. Fig. 1 Type 5024-1. Mounting and Operating Instructions EB 9539 EN Power Supply and Indicator Unit Type 5024-1 Fig. 1 Type 5024-1 Mounting and Operating Instructions EB 9539 EN Edition October 2003 Application 1 Application The Type 5024-1 Power Supply and Indicator Unit

More information

Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points

Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points Features SELV Compliant No Detection Passive Injector Gigabit Compatible Full Protection

More information

Duct Humidity Transmitter

Duct Humidity Transmitter SDC-H Duct Humidity Transmitter Features Replaceable sensor element Humidity measurement for air ducts Minimum and maximum value memory 0 0V, 0 0mA or 0V, 4 0mA measuring signals selectable with jumpers

More information

OZW30. Central Unit SYNERGYR

OZW30. Central Unit SYNERGYR 2 841 SYNERGYR Central Unit OZW30 Collects billing data from the apartments. Generates an image of each apartment's heat consumption and makes it available for readout. Acts on room temperature control

More information

33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application

33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application 33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application Features Compliant with the IEEE802.3at Standard -40 to +60 C Temperature Range Diagnostic LEDs Full Protection

More information

Cisco Unified IP Phone Power Injector

Cisco Unified IP Phone Power Injector Data Sheet Cisco Unified IP Phone Power Injector The Cisco Unified IP Phone Power Injector (Figure 1) increases the deployment flexibility of Cisco Unified IP phones by providing an alternative powering

More information

TX OPEN RS232/485 module

TX OPEN RS232/485 module s 8 185 8185P01 TX-I/O ; DESIGO OPEN TX OPEN RS/485 module for integrating third-party systems and devices to DESIGO (V4 or higher) TXI1.OPEN Platform to integrate third-party systems and devices to the

More information

Heating Controller. Building Technologies HVAC Products

Heating Controller. Building Technologies HVAC Products 2 474 Heating Controller RVP300 Multifunctional heating controller for use in residential and non-residential buildings; suitable for weather-dependent flow temperature control of heating zones with or

More information

Product and Application Description

Product and Application Description Technical Product - Information Product and Application Description The room temperature controller UP 237K and UP 252K are available in the following colors, matching the design of the wall switch design

More information

RVL470. Heating Controller. Building Technologies HVAC Products. Series B

RVL470. Heating Controller. Building Technologies HVAC Products. Series B 2 522 Heating Controller Series B RVL470 Multifunctional heating controller for use in residential and non-residential buildings; suitable for weather-dependent flow temperature control of heating zones

More information

FDCI222, FDCIO222, FDCIO224 Input module Input/output modules

FDCI222, FDCIO222, FDCIO224 Input module Input/output modules FDCI222, FDCIO222, FDCIO224 Input module Input/output modules addressable (FDnet/C-NET) Sinteso Cerberus PRO Input module FDCI222 with 4 monitored contact inputs for the acknowledgement of technical states

More information

Drayton Digistat +2RF/+3RF

Drayton Digistat +2RF/+3RF /+3RF Programmable Room Thermostat Wireless Model: RF700/22090 Model: RF701/22092 Power Supply: Battery - Thermostat Mains - Digistat SCR Invensys Controls Europe Customer Service Tel: 0845 130 5522 Customer

More information

Adjustable room thermostat for heating only or cooling only systems

Adjustable room thermostat for heating only or cooling only systems 3 003 Room hermostat RAA30 Adjustable room thermostat for heating only or cooling only systems Room thermostat with manual O/OFF switch wo-position control witching voltage AC 24 250 V Use he RAA30 room

More information

OZS164... Web server. For LPB/BSB plants

OZS164... Web server. For LPB/BSB plants s 5 711 Web server For LPB/BSB plants OZS164... Remotely operate and monitor a LPB or BSB device Web browser operation via PC/laptop or Smartphone SMS operation via mobile phone (OZS164.23) 2 digital inputs

More information

Radiant Temperature Sensor TY7321

Radiant Temperature Sensor TY7321 AB-5361-U Specifications/Instructions Radiant Temperature TY7321 General TY7321 Radiant Temperature s are designed to measure infrared radiation from perimeter windows and walls and provide a proportional

More information

Electronic Control Devices The European Product Catalogue 2007

Electronic Control Devices The European Product Catalogue 2007 FX14 Field Controller (1/4) FX14 Field Controller The FX14 is an equipment field controller in the Facility Explorer range of products. The controller is designed specifically for commercial Heating, Ventilating,

More information

XUSL4E4BB091NS2 XUSL type 4 - Slave2 - For body protection - 4 Beams, Hp = 910 mm

XUSL4E4BB091NS2 XUSL type 4 - Slave2 - For body protection - 4 Beams, Hp = 910 mm Characteristics XUSL type 4 - Slave2 - For body protection - 4 Beams, Hp = 910 mm Complementary Detection system Kit composition [EAA] effective aperture angle Emission Main Range of product Product or

More information

HERZ-Thermal Actuators

HERZ-Thermal Actuators HERZ-Thermal Actuators Data Sheet 7708-7990, Issue 1011 Dimensions in mm 1 7710 00 1 7710 01 1 7711 18 1 7710 80 1 7710 81 1 7711 80 1 7711 81 1 7990 00 1 7980 00 1 7708 11 1 7708 10 1 7708 23 1 7709 01

More information

HCR3.2/.. Chipcard reader HOTEL SOLUTION

HCR3.2/.. Chipcard reader HOTEL SOLUTION s 6 332 HOTEL SOLUTION Chipcard reader HCR3.2/.. Chipcard reader for hotel room access control Reads access code on chipcard Transfers access code to room controller Built-in optical display of messages

More information

PCS0100en 02.2008. Persy Control Services B.V. Netherlands

PCS0100en 02.2008. Persy Control Services B.V. Netherlands P-Bus Gateway PBGW2.128 Universal gateway between the P-bus protocol and open standard protocols. The variety of available electrical interfaces on the gateway offers a wide range of possibilities for

More information

CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE. General purpose single phase thyristors and solid state relays Product data.

CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE. General purpose single phase thyristors and solid state relays Product data. 425 CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE General purpose single phase thyristors and solid state relays Product data abc 425 EUROCUBE A complete range of low cost solid state relays and

More information

H/L = Power supply. FN = Nominal Frequency. RN = Rated value of output burden. UN = Nominal input voltage. IN = Nominal input current.

H/L = Power supply. FN = Nominal Frequency. RN = Rated value of output burden. UN = Nominal input voltage. IN = Nominal input current. Application : The transducer RISH CON - CA/CV (Fig.1) converts a sinusoidal AC Current or AC Voltage into a load independent DC Current or a load independent DC Voltage proportional to the measured value.

More information

RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER

RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER Application : The RISH CON - Hz transducer is used for frequency measurement. The output signal is proportional to measured frequency and is either load independent DC Current or load independent DC Voltage.

More information

How To Control A Power Supply With A Mini Transmitter And Switch (Power Supply)

How To Control A Power Supply With A Mini Transmitter And Switch (Power Supply) transmitter (2 wire) / switch for continuous or On/Off Control Indication, monitoring, transmitting and continuous or On/Off control in one device Output signal 4...20 ma, 2-wire for continuous control

More information

TM7BDM8B expansion block - TM7 - IP67-8 DI/DO - 24V DC - 0.5 A - M8 connector

TM7BDM8B expansion block - TM7 - IP67-8 DI/DO - 24V DC - 0.5 A - M8 connector Product datasheet Characteristics TM7BDM8B expansion block - TM7 - IP67-8 DI/DO - 24V DC - 0.5 A - M8 connector Main Range of product Product or component type Range compatibility Enclosure material Bus

More information

MILLENIUM INSTALLATION MANUAL NTR 735 A. Simple Automation Control Module (MAS)

MILLENIUM INSTALLATION MANUAL NTR 735 A. Simple Automation Control Module (MAS) MILLENIUM Table of contents 1. INTRODUCTION 1 2. HARDWARE DESCRIPTION 2 3. INSTALLATION 5 4. CONNECTION 6 5. USER SAFETY AND PROTECTION OF EQUIPMENT 8 1. Introduction The MILLENIUM series has been designed

More information

RM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC

RM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC Characteristics multifunction control relay RM17-TE - range 183..528 V AC Complementary Reset time Maximum switching voltage Minimum switching current Maximum switching current [Us] rated supply voltage

More information

Smile. The All-In-One Heating Controller

Smile. The All-In-One Heating Controller Smile EVERYTHING UNDER CONTROL The All-In-One Heating Controller Versatile, energy-efficient heating control. The All-In-One Heating Controller Smile controllers are ideal to gain maximum efficiency from

More information

FIREDEX 2200. Conventional Fire Panels

FIREDEX 2200. Conventional Fire Panels 68 Flexible, high specification system Choice of 1, 2, 4 or 8 zones Simple one-shot auto-reset user test facility Approved to EN54 Maintenance free poly switch circuit protection, with auto reset Class

More information

Digital inductive conductivity transmitter

Digital inductive conductivity transmitter Digital inductive conductivity transmitter Optimal solution for conductivity measurements in difficult fluids (polluted, dirty,...) PEEK/PPA version for CIP applications Large range of process connections

More information

OZW672...V5.2. Web-Server. For LPB/BSB plants

OZW672...V5.2. Web-Server. For LPB/BSB plants s 5 712 Web-Server For LPB/BSB plants OZW672...V5.2 Web server OZW672 allows for remote plant control and monitoring via the web and Smartphone-App. Web server is available in three versions: To connect

More information

Floodlight Range Installation Guide

Floodlight Range Installation Guide SPARTAN Floodlight Range Installation Guide CML13ATEX3007 IEC Ex CML14.0001 This installation guide provides instructions for installing the Infra-Red and White-Light SPARTAN SPX series of explosion protected

More information

HSP GmbH Zum Handwerkerhof 2 90530 Wendelstein Tel. 09129 / 2852-0 Fax: 09129 / 2852-11 Web: www.hsshsp.de EMAIL: HSP@hsshsp.de NTG-3000.

HSP GmbH Zum Handwerkerhof 2 90530 Wendelstein Tel. 09129 / 2852-0 Fax: 09129 / 2852-11 Web: www.hsshsp.de EMAIL: HSP@hsshsp.de NTG-3000. NTG-3000 Transducer Data Sheet Document Version 2.8 Page 1 of 10 Versions / Revisions: Document Creation Author Description version date 2.0 2012-07-25 P. Compensis First official version 2.1 2012-08-24

More information

DS 1.102 DRTE. AIR ROOM TEMPERATURE SENSOR with fan speed control switches

DS 1.102 DRTE. AIR ROOM TEMPERATURE SENSOR with fan speed control switches DS 1.102 02/99 AIR ROOM TEMPERATURE SENSOR with fan speed control switches Specification No. 528-X-XXX* The Active Room Temperature sensor incorporating fan speed control switches is designed to give a

More information

ABB i-bus EIB / KNX Analogue Input AE/S 4.2

ABB i-bus EIB / KNX Analogue Input AE/S 4.2 Product Manual ABB i-bus EIB / KNX Analogue Input AE/S 4.2 Intelligent Installation Systems This manual describes the functionality of Analogue Input AE/S 4.2. Subject to changes and errors excepted. Exclusion

More information

OZW772... V2.0. Web server. Synco TM, Synco TM living

OZW772... V2.0. Web server. Synco TM, Synco TM living s 5 701 Web server Synco TM, Synco TM living OZW772... V2.0 The OZW772 web server allows for remote operation and monitoring of plants via the web and send faults and system reports to e-mail recipients.

More information

N20xxA, N34xxA NON-SPRING RETURN DIRECT-COUPLED DAMPER ACTUATORS FOR FLOATING AND 2-POSITION CONTROL

N20xxA, N34xxA NON-SPRING RETURN DIRECT-COUPLED DAMPER ACTUATORS FOR FLOATING AND 2-POSITION CONTROL N2xxA, N34xxA NON-SPRING RETURN DIRECT-COUPLED DAMPER ACTUATORS FOR FLOATING AND 2-POSITION CONTROL SPECIFICATIONS Supply voltage N224A / N3424A N223A / N3423A PRODUCT DATA 24 Vac 15%, 5/6 Hz 23 Vac 15%,

More information

TLK 48 MICROPROCESSOR-BASED DIGITAL ELECTRONIC REGULATOR

TLK 48 MICROPROCESSOR-BASED DIGITAL ELECTRONIC REGULATOR TLK 48 MICROPROCESSOR-BASED DIGITAL ELECTRONIC REGULATOR TECHNICAL DATA CARATTERISTICHE MECCANICHE Housing Self-extinguishing plastic, UL 94 V0 Dimensions 48x48 mm DIN depth 98 mm Weight 225 g approx.

More information

Product and functional description

Product and functional description Product and functional description The KNX / DALI gateway N 141/02 is a 4 MU wide, DINrail mounted KNX device with one DALI interface to which up to 64 DALI actuators (e.g. DALI ballasts) can be connected

More information

BB800 Off-Grid Solar System

BB800 Off-Grid Solar System BB800 Off-Grid Solar System KEY PRODUCT FEATURES Control Box & Charge Controller 1000W of Solar Panels 4x200Ah of SLA Batteries in series 2KW Inverter Output Power Solar Panel & Battery Mounting Our entry

More information

ADM1TE 5/30A DIN rail single phase two wire energy meter

ADM1TE 5/30A DIN rail single phase two wire energy meter ADMTE 5/30A DIN rail single phase two wire energy meter. Safety instruction.2 Foreword.3 Performance criteria.4 Specifications.5 Basic errors.6 Description.7 Dimensions.8 Installation.9 Operating.0 Troubleshooting.

More information

ACS-30-EU-EMDR-10-MOD

ACS-30-EU-EMDR-10-MOD Multi-application heat tracing Control and Monitoring in commercial and residential buildings Roof & Gutter de-icing sensor module Technical Information Approvals Module IP rating Ambient operating temperature

More information

DC1100 & 1400 Energy Controllers. Satchwell DC1100 & DC1400 for energy-efficient temperature control in smaller buildings.

DC1100 & 1400 Energy Controllers. Satchwell DC1100 & DC1400 for energy-efficient temperature control in smaller buildings. 1100 & 1400 Energy Controllers Satchwell 1100 & 1400 for energy-efficient temperature control in smaller buildings. 02 1100 & 1400 Energy Controllers Features he 1100 and 1400 Energy Controllers are self-configuring

More information

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132

More information

Quick Connect. quick - simple - efficient. www.g-mw.de

Quick Connect. quick - simple - efficient. www.g-mw.de Quick Connect quick - simple - efficient www.g-mw.de Phone: +49 9103 7129-0 Fax: +49 9103 7129-207 Innovative connection technology to plug three single-phase current transformers to multifunctional power

More information

Shutter Actuator Standard, 4-fold, 230 VAC, MDRC RA/S 4.230.1, GH Q631 0076 R0111. ABB i-bus EIB

Shutter Actuator Standard, 4-fold, 230 VAC, MDRC RA/S 4.230.1, GH Q631 0076 R0111. ABB i-bus EIB , GH Q631 0076 R0111 2CDC 071 240 F0003 The Shutter Actuator Standard is used to control a maximum of four independent 230 VAC drives for positioning shutters, blinds, awnings and other hangings as well

More information

Thyristor-controlled power supplies and battery chargers

Thyristor-controlled power supplies and battery chargers Thyristor-controlled power supplies and battery chargers Input voltage: 115 / 230 VAC, single phase, 50 / 60 Hz or 208 / 400 / 480 VAC, three phases, 50 / 60 Hz Output voltage: 12 / 24 / 48 / 60 / 72 /

More information

DRM75A 230V 20/100A DIN rail single phase two wire energy meter

DRM75A 230V 20/100A DIN rail single phase two wire energy meter DRM75A 230V 20/100A DIN rail single phase two wire energy meter 1.1 Safety instruction 1.2 Foreword 1.3 Performance criteria 1.4 Specifications 1.5 Basic errors 1.6 Description 1.7 Dimensions 1.8 Installation

More information

Product and Applications Description. Application Programs. Example of Operation. GAMMA instabus Technical Product-Information.

Product and Applications Description. Application Programs. Example of Operation. GAMMA instabus Technical Product-Information. Product and Applications Description The power supply units N 125/x2 can supply DC 24 V power from an additional pair of terminals (yellowwhite). This DC 24 V output voltage can be used to power e.g. an

More information

Semi flush-mount room thermostat with KNX communications For VAV heating and cooling systems

Semi flush-mount room thermostat with KNX communications For VAV heating and cooling systems s 3 72 Semi flush-mount room thermostat with KNX communications For VAV heating and cooling systems RDU34 KNX bus communications (S-mode and LTE mode) Backlit display PI / P control Outputs for DC 0 0

More information

CompactLogix Power Supplies Specifications

CompactLogix Power Supplies Specifications Technical Data CompactLogix Power Supplies Specifications 1768 CompactLogix Power Supplies Catalog Numbers 1768-PA3, 1768-PB3 1769 Compact I/O Power Supplies Catalog Numbers 1769-PA2, 1769-PB2, 1769-PA4,

More information

Wiser Panel Meter, Model Number WISERCTPM200 Installer s Guide

Wiser Panel Meter, Model Number WISERCTPM200 Installer s Guide Instruction Bulletin EAV85226 08/2014 Wiser Panel Meter, Model Number WISERCTPM200 Installer s Guide Retain for future use. Product Description Kit Contents The Wiser Panel Meter is for use in energy management

More information

Stand Alone POTS Fiber Optic System. P31372 Station (Subscriber) Unit P31379 Remote (Exchanger) Unit. Description & Installation

Stand Alone POTS Fiber Optic System. P31372 Station (Subscriber) Unit P31379 Remote (Exchanger) Unit. Description & Installation Stand Alone POTS Fiber Optic System P31372 Station (Subscriber) Unit P31379 Remote (Exchanger) Unit Description & Installation Printed in USA 09/11 TO466 Rev. A Table of Contents Page 1.0 SCOPE 2 2.0 PRODUCT

More information

This unit is a pump that will clear the waste from a domestic shower and washbasin, bath, washing machine, glass washer and a sink.

This unit is a pump that will clear the waste from a domestic shower and washbasin, bath, washing machine, glass washer and a sink. 1. Description This unit is a pump that will clear the waste from a domestic shower and washbasin, bath, washing machine, glass washer and a sink. The unit will start automatically. Please pay particular

More information

How To Control A Korean Korean Power Plant

How To Control A Korean Korean Power Plant 2 510 District Heating Controller for 1 heating circuit and d.h.w. heating RVD120 RVD140 ultifunctional heating controller for use in district heating substations and district heating plants with odbus

More information

Technical Data. General specifications Switching element function Rated operating distance s n 15 mm

Technical Data. General specifications Switching element function Rated operating distance s n 15 mm 0102 Model Number Features Comfort series 15 mm flush Accessories MHW 01 Modular mounting bracket MH 04-2057B Mounting aid for VariKont and +U1+ Technical Data General specifications Switching element

More information

STEP-PS/1AC/12DC/1.5. Extract from the online catalog. Order No.: 2868567. DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase

STEP-PS/1AC/12DC/1.5. Extract from the online catalog. Order No.: 2868567. DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase Extract from the online catalog STEP-PS/1AC/12DC/1.5 Order No.: 2868567 DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase Commercial data EAN 4046356292924 Pack 1 pcs. Customs tariff

More information

IntesisBox Modbus Server SAMSUNG Air Conditioners

IntesisBox Modbus Server SAMSUNG Air Conditioners IntesisBox Modbus Server SAMSUNG Air Conditioners Gateway for monitoring and control of Samsung NASA compatible Air Conditioning Systems from any Modbus master device TCP or RTU (BMS, PLC, SCADA, HMI,

More information

REGULINE 600VA / 1000VA REGULATOR USER MANUAL

REGULINE 600VA / 1000VA REGULATOR USER MANUAL REGULINE 600VA / 1000VA REGULATOR USER MANUAL TUNÇMATİK REGULINE SERIES AUTOMATIC VOLTAGE REGULATOR Models: REGULINE 600VA / REGULINE 1000VA Principle of Operation Automatic Voltage Regulators regulate

More information

Nest Learning Thermostat Installation Guide. Installation step-by-step

Nest Learning Thermostat Installation Guide. Installation step-by-step Nest Learning Thermostat Installation Guide Installation step-by-step Contents Compatibility. 3 In the box. 4 Before you start. 5 Choose an installation method. 6 Replacing an existing wired thermostat.

More information

HEAT MONITORING AND CONTROL INSTRUMENTS FOR TRANSFORMERS MB 103 TEMPERATURE CONTROL UNIT PT 100 TEMPERATURE SENSOR

HEAT MONITORING AND CONTROL INSTRUMENTS FOR TRANSFORMERS MB 103 TEMPERATURE CONTROL UNIT PT 100 TEMPERATURE SENSOR HEAT MONITORING AND CONTROL INSTRUMENTS FOR TRANSFORMERS MB 103 TEMPERATURE CONTROL UNIT PT 100 TEMPERATURE SENSOR 2 MB 103 TRANSFORMER TEMPERATURE CONTROL UNIT WITH CONTROL SIGNAL Recent approval of new

More information

RM4TG20 three-phase network control relay RM4-T - range 200..500 V

RM4TG20 three-phase network control relay RM4-T - range 200..500 V Characteristics three-phase network control relay RM4-T - range 200..500 V Complementary [Us] rated supply voltage Output contacts Setting accuracy of time delay Delay at power up Measuring cycle Marking

More information

For UK only RXL39.1 and the applications package SP-03 are sold in the United Kingdom only.

For UK only RXL39.1 and the applications package SP-03 are sold in the United Kingdom only. s For UK only RX39.1 and the applications package SP-03 are sold in the United Kingdom only. 3 876 3876P01 RX Room controller Communicating controllers for fan-coil applications SP-03 RX39.1 The RX39.1

More information

PXM20-E. Operator unit DESIGO PX

PXM20-E. Operator unit DESIGO PX 9 234 DESIGO PX Operator unit PXM20-E Network-compatible operator unit for viewing and operating one or more DESIGO PX automation stations. High-grade display with adjustable contrast Simple key operation

More information

Art.S001-S002 SOLAR MODULE WITH DELIVERY AND RETURN CONNECTIONS

Art.S001-S002 SOLAR MODULE WITH DELIVERY AND RETURN CONNECTIONS Art.S001-S002 SOLAR MODULE WITH DELIVERY AND RETURN CONNECTIONS Technical Information sheet 0001/07/Rev01 ENG FUNCTION Series S001 and S002 circulation units are applied to the primary circuit of solar

More information

VAV compact controller KNX / PL-Link

VAV compact controller KNX / PL-Link s 3 547 OpenAir VAV compact controller KNX / PL-Link Series E GDB181.1E/KN GLB181.1E/KN Networked compact controller featuring KNX (S-mode / LTE-mode) and PL- Link capability for plants with variable air

More information

Features. Display. Measurements. Intelligent. Accuracy. Models. Installation DEIF A/S. Multi-instrument 4921210109D

Features. Display. Measurements. Intelligent. Accuracy. Models. Installation DEIF A/S. Multi-instrument 4921210109D 7000/7000C/7020 Multi-instrument 4921210109D Features Measurements All 3-phase AC measurements True RMS Replaces analogue meters Demand on each phase current Accuracy U, I and F class 0.5 Other values

More information

Automation System TROVIS 6400 TROVIS 6493 Compact Controller

Automation System TROVIS 6400 TROVIS 6493 Compact Controller Automation System TROVIS 6400 TROVIS 6493 Compact Controller For panel mounting (front frame 48 x 96 mm/1.89 x 3.78 inch) Application Digital controller to automate industrial and process plants for general

More information

ABB i-bus KNX Fan Coil Actuator, MDRC FCA/S 1.1M, 2CDG 110 084 R0011

ABB i-bus KNX Fan Coil Actuator, MDRC FCA/S 1.1M, 2CDG 110 084 R0011 , 2CDG 110 084 R0011 2CDC 071 112 F0008 The Fan Coil Actuator is a modular installation device (MDRC) in pro M design. It is intended for installation in the distribution board on 35 mm mounting rails.

More information

PSU-U-24V/AC-6A/10/FTA-TR-MC PSAC 0624

PSU-U-24V/AC-6A/10/FTA-TR-MC PSAC 0624 PSU-U-24V/AC-6A/10/FTA-TR-MC PSAC 0624 v.1.0 AC/AC power supply unit Edition: 1 from 24 th October 2008 Supercedes edition: ---------- 10062009 CONTENTS: 1. Technical description. 1.1. General description

More information

R4D0-FB-IA* FieldBarrier. Features. Assembly. Function. Connection IN + - S OUT ... ... Spur 2. Spur 1. Zone 1. Zone 0

R4D0-FB-IA* FieldBarrier. Features. Assembly. Function. Connection IN + - S OUT ... ... Spur 2. Spur 1. Zone 1. Zone 0 FieldBarrier Features Assembly 8... 12 outputs Ex ia IIC, FISCO and Entity Advanced fault isolation and diagnostics at the spur FieldBarrier in Zone 1/Div. 2 Instruments in Zone 0...1/Div. 1 For FOUNDATION

More information

2.8. Ex-Recess-mounted, ceiling emergency light fittings in compact metal design

2.8. Ex-Recess-mounted, ceiling emergency light fittings in compact metal design .8 Ex-Recess-mounted, ceiling emergency light fittings in compact metal design RLF/RLF-INOX 50 18-58 W / RLF/RLF-INOX 50... N 18-36 W (Zone 1,, 1, ) The explosion-protected lighting concept for clean rooms

More information

5SV Residual Current Protective Devices

5SV Residual Current Protective Devices s Siemens AG 2013 SENTRON 5SV Residual Current Protective Devices New portfolio for reliable personnel, material and fire protection Safe protection against residual currents Residual current protective

More information

Cable Plug acc. to DIN EN 175301-803, Form A

Cable Plug acc. to DIN EN 175301-803, Form A Cable Plug acc. to DIN EN 175301-803, Form A Complete program Contact form 18 mm Also available with LED indicator Optional 4-pin version for pressure switch or impulse valves respectively Versions with

More information

How To Use A Flowmeter

How To Use A Flowmeter INLINE flowmeter for continuous flow measurement Economic integration in pipe systems without any additional piping 3-wire frequency pulse version to directly interface with PLC s (both PNP and NPN) Connection

More information

Rotary actuator for 2 and 3-way (control) ball valves Torque 5 Nm Nominal voltage AC 100... 240 V Control: Open/close or 3-point Auxiliary switch

Rotary actuator for 2 and 3-way (control) ball valves Torque 5 Nm Nominal voltage AC 100... 240 V Control: Open/close or 3-point Auxiliary switch echnical data sheet Rotary actuator LR-S Rotary actuator for and -way (control) ball valves orque 5 Nm Nominal voltage C... 4 V Control: Open/close or -point uxiliary switch echnical data Electrical data

More information

NI 9423. NI C Series Overview DATASHEET. 8-Channel Sinking Digital Input Module

NI 9423. NI C Series Overview DATASHEET. 8-Channel Sinking Digital Input Module DATASHEET NI 9423 8-Channel Sinking Digital Input Module 8-channel, 100 µs digital input 24 V logic, sinking digital input Compatible with NI CompactDAQ counters 250 Vrms, CAT II isolation 10-position

More information

8146/5 Series Breaker Panelboards

8146/5 Series Breaker Panelboards 8146/5 Series Breaker Panelboards DISTRIBUTION BREAKER PANELBOARDS FOR HAZARDOUS & CORROSIVE ENVIRONMENTS Breaker Panels Features: Wide variety of Flameproof branch circuit breakers for Zone 1 & Division

More information

TMS TANK MANAGEMENT SYSTEM

TMS TANK MANAGEMENT SYSTEM TMS TANK MANAGEMENT SYSTEM Page 1 of 9 Operating Instructions GENERAL The Tank Management System is a bespoke design to control, monitor and accommodate efficient storage and dispensing of TMS. FUNCTIONS

More information

Electronic Control Devices The European Product Catalogue 2007

Electronic Control Devices The European Product Catalogue 2007 FX07 Field Controller (1/4) FX07 Field Controller Display Model Dimensions in mm (inches) The FX07 is a terminal unit controller in the Facility Explorer range of products. The controller is designed specifically

More information

Vario-Series Accessories

Vario-Series Accessories Accessories and spare parts for GMW analogue panel meters and controllers Current Transformers pages 2-9 Shunt Resistors 10-11 Voltage Dividers 12 Power supply for indicator/controllers 13 Blanking Plates

More information

Installing the Tracer ZN517 Unitary Controller Ordering number: 4950 0496, 4950 0596

Installing the Tracer ZN517 Unitary Controller Ordering number: 4950 0496, 4950 0596 Installing the Tracer ZN517 Unitary Controller Ordering number: 4950 0496, 4950 0596 Product overview The Tracer ZN517 controller is a field-installed, application-specific controller that provides directdigital

More information

IntesisBox KNX - LON

IntesisBox KNX - LON IntesisBox KNX - Gateway for integration of devices into KNX systems. Integrate Air Conditioning from the main manufacturers (DAIKIN, Mitsubishi Electric, Mitsubishi Heavy Industries, Toshiba, Fujitsu,

More information

aseries A13B Mini Bullet Camera User Manual

aseries A13B Mini Bullet Camera User Manual aseries A13B Mini Bullet Camera User Manual Thank you for purchasing our product. If there are any questions, or requests, please do not hesitate to contact the dealer. This manual applies to the MicroView

More information

CONNECTOR AMPLIFIER FOR PROPORTIONAL VALVES (4-20 ma Input Version)

CONNECTOR AMPLIFIER FOR PROPORTIONAL VALVES (4-20 ma Input Version) TECHNICAL DATASHEET #TD1102AX CONNECTOR AMPLIFIER FOR PROPORTIONAL VALVES (4-20 ma Input Version) Part Number: Connector Amplifier CAPV-H-4-20MA-x complete with cable CAPV-4C-yM Where: x = current output

More information

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency echnical data sheet NV24A--RE Communicative globe valve actuator for 2-way and 3-way globe valves Actuating force 1000 N Nominal voltage AC/DC 24 V Control Modulating DC (0)2...10 V Variable Nominal stroke

More information

Industrial Tower Uninterruptible Power Supply Specifications Bulletin Numbers 1609-P

Industrial Tower Uninterruptible Power Supply Specifications Bulletin Numbers 1609-P Technical Data Industrial Tower Uninterruptible Power Supply Specifications Bulletin Numbers 1609-P Topic Page 1609-P Specifications 2 1609-P Approximate Dimensions and Shipping Weights 3 Additional Resources

More information