HVAC Clinic. Psychrometrics

Size: px
Start display at page:

Download "HVAC Clinic. Psychrometrics"

Transcription

1 HVAC Clinic Psychrometrics

2 Table Of Contents Introduction... 3 Psychrometric State Points... 3 Psychrometric Chart... 6 Definitions... 9 Psychrometric Chart Analysis Example Example

3 Introduction Psychrometrics or psychrometry is the study of the physical and thermodynamic properties of an air water vapor mixture. While probably the least understood of the engineering topics related to HVAC systems, psychrometrics allows us to answer the most important questions related air conditioning. For example, these questions could include: What is the leaving air temperature of constant volume air hander? What is the relative humidity of a space served by an air conditioning system? How much moisture is added by an evaporative cooling? Without the study of psychrometrics, the answers of these questions would not be known. To emphasize the importance and misunderstanding of psychrometrics, one could ask a designer the simple question, what is the leaving air temperature of a handling system servicing a constant volume zone? Many designers would probably answer 55 degrees Fahrenheit. However, this response in most instances would be incorrect. Later in this clinic, we will explain in detail why. Psychrometric State Points There are five main psychrometric state points. Those points are: Dry-bulb temperature Wet-bulb temperature Dew-point temperature Humidity ratio Relative humidity Dry bulb temperature is a measure of the sensible or dry energy contained in an air water vapor mixture. Dry-bulb temperatures are read from an ordinary thermostat (figure 1). Figure 1. Dry Bulb Temperature WN Mechanical Systems Psychrometrics Page 3 of 23

4 Wet bulb temperature is an indicator of the amount of moisture contained in an air water vapor mixture. Wet-bulb temperatures are read from a thermometer whose bulb is covered by a wet wick. Another common device for measure the bulb temperature is the sling psychrometer. The difference between the wet bulb temperature and the dry bulb temperature is caused by the cooling effect created by the evaporation of moisture from the wet wick (figure 2). The evaporation from the wick reduces the temperature of the bulb and thus the thermometer reading. Figure 2. Wet Bulb Temperature Dew point temperature is precise indicator of the amount of moisture in an air water vapor mixture. Dew point temperature is the temperature at which moisture leaves the air and condenses on objects. Fog is formed when an air water vapor mixture can no longer hold any more moisture and condensation begins to form as droplets (figure 3). Figure 3. Dew Point Temperature WN Mechanical Systems Psychrometrics Page 4 of 23

5 Like the dew point temperature, humidity ratio is also an exact indication of the amount of moisture in an air water vapor mixture. Humidity ratio is defined humidity as the actual weight of water in an air water vapor mixture. Put another way, if you could remove and weigh all the water in an air water vapor mixture, the weight of that water per pound of dry air would be expressed as the humidity ratio (figure 4). Figure 4. Humidit Ratio Humidity ratio can be expressed as pounds of moisture per pound of dry air, or as grains of moisture per pound of dry air. There are 7000 grains of water in a pound. Humidity ratio is very commonly expressed as grains of moisture per pound of dry air simply so that we are not dealing in relatively small fractions. For example, an air water vapor mixture at 4500 elevation and 80 o F dry bulb temperature and 61 o F wet bulb temperature contains a mere 64 grain of moisture per each pound of dry air. Finally, the last psychrometric state point is relative humidity. Relative humidity is the amount of moisture that a given amount of air is holding compared to the amount of moisture that the same amount of air can hold at the same dry bulb temperature. Relative humidity is expressed as a percentage. For example if, an air water vapor mixture can hold 100 grains of moisture at saturation and that same air water vapor mixture is holding 50 grains of moisture, the relative humidity would be 50% (50 grains/ 100 grains = 50%). Figure 5. Relative Humidity WN Mechanical Systems Psychrometrics Page 5 of 23

6 Psychrometric Chart The ASHRAE fundamentals manual defines all off the psychrometric point values as a series of equations. These equations can be difficult to solve and typically involve multiple iterations. Ultimately, the goal is to be able to find all the psychrometric values given any two input values at a constant pressure (or altitude). Another alternative to iteratively solving the equations is to use a graphical representation of psychrometric states called a psychrometric chart. Psychrometric charts are plotted at a constant pressure or altitude. For example, many psychrometric charts are drawn at sea level or 24 inches of mercury. This is very convenient if we are in a locale that is at or near sea level. For the rest of us, a psychrometric chart at sea level is inaccurate. For this reason, we have created an online program that will draw a psychrometric chart at any elevation (and thus pressure) at If we were to create a psychrometric chart, we would want to organize it in a logical progression. We defined Psychrometrics as the interaction of an air water vapor mixture. Thus, we would probably want to define one of our axis as dry energy and the other axis as wet energy. Of the five primary psychrometric state points, dry bulb temperature is an exact measure of dry energy. Dry energy can also be expressed as sensible energy. As such, the horizontal axis on a psychrometric chart is used to represent dry bulb temperature. Next, we would want to define the vertical axis. We had established that the second axis would be a measure of wet energy. Wet energy is also known as latent energy. There are two psychrometric state points that are exact indicators of the amount of wet energy in an air water vapor mixture. Those two state points are humidity ratio and dew point. Humidity ratio measures the exact mass of moisture per pound of dry air measured as either grain or pounds or moisture. If the vertical axis is expressed as humidity ratio, the axis would be linear. However, dew point is not linear. When we express a vertical axis as dew point, you will notice that the axis is not linear. We will explain why a little later in this clinic. Figure 6. Axis Of Psychrometric Chart Having established both our horizontal and vertical axis (dry bulb and humidity ratio respectively), we next need to determine the outer boundary of our psychrometric chart. Being that psychrometrics is the study of an air water vapor mixture, the simple conclusion would be that saturation would establish the outer boundary of an air water vapor mixture. How do we establish saturation? Imagine we were to contain one pound of vaporless air in a box at a certain temperature and pressure. If we were to inject water vapor at a measured rate of mass until we observe condensation (fine droplets forming inside the box), we know we have reached saturation. Measure the mass of water vapor we have added at the exact moment of saturation and plot the point. If we continue to process for a range of dry bulb temperatures (32F to 120F), we establish a saturation curve (figure 7). WN Mechanical Systems Psychrometrics Page 6 of 23

7 Figure 7. Saturation The saturation curve can also be defined as 100% relative humidity. If relative humidity is defined as the amount of moisture that a given amount of air is holding compared to the amount of moisture that the same amount of air can hold at the same dry bulb temperature, then saturation is 100% relative humidity. If dry bulb temperature is a measure of pure dry (or sensible) energy, then the dry bulb or the horizontal axis represents 0% relative humidity. If we pick a temperature at any point (assume 70 o F) and measure the magnitude of a vertical line between the horizontal dry bulb axis at 70 o F and saturation, the magnitude of that line represents the mass of water per pound of dry air at that temperature. If we divide the magnitude of that line by exactly half (representing 50% mass of water vapor), and measure that point vertically from the horizontal axis, we have established a point at 50% relative humidity. If we continue the process at one degree intervals along the entire dry bulb range, we can establish a 50% relative humidity curve. A similar process can be applied at 10% relative humidity increments in order to establish all of our relative humidity curves (figure 8). Figure 8. Relative Humidity Next, we can establish our dew point curves. Dew point, like humidity ratio, is an exact representation of the amount of moisture in an air water vapor mixture. However, unlike humidity ratio, it is not linear. Dew point temperature is the temperature at which moisture leaves air and condenses on objects. We establish the dew point temperature by picking a dry bulb temperature and plotting a line vertically (representing latent only energy gain) until it intersects the saturation curve (the temperature at which condensation will occur). We then draw dry a line horizontally until it intersects the WN Mechanical Systems Psychrometrics Page 7 of 23

8 vertical humidity ratio line. That point represents the dew point at that particular dry bulb temperature. Repeat the process and we establish the non-linear vertical dew point axis (figure 9). Figure 9. Dew Point Finally, we can establish our last psychrometric curve, the wet bulb temperature. Wet bulb temperature is an indicator of the amount of moisture in an air water vapor mixture, but it is not a perfect indicator of the amount of moisture (unlike humidity ratio or dewpoint). We determine wet bulb temperature by placing a wet wick on the end of a dry bulb thermometer. Water will evaporate from the wet wick whenever we are a state that is not at saturation. The drier the air, the faster the evaporation from the wick and the higher the temperature will depress within the dry bulb thermometer. The dry bulb temperature minus the depression is the wet bulb temperature. Being that saturation is defined as the temperature at which air cannot hold any more moisture; the wet bulb temperature at saturation equals the dry bulb temperature. At saturation, it would be impossible for water to evaporate from the wet wick, and thus there would be no depression on the wet wick thermometer. We plot the points at various psychrometric conditions that establish a constant wet bulb temperature. The results represent a straight line that begins at the dry bulb temperature at saturation and decreases in moisture content (humidity ratio) as we increase dry bulb temperature (figure 10). Figure 10. Wet Bulb Temperature WN Mechanical Systems Psychrometrics Page 8 of 23

9 Finally, we combine the five psychrometric curves to establish a psychrometric chart for a given pressure (figure 11). Having established a psychrometric chart, we can easily find any three psychrometric properties given any two initial properties. Figure 11. Psychrometric Chart One other psychrometric property that is displayed on some psychrometric charts is specific volume. Specific volume is defined as the volume of one pound of dry air at a specific temperature and pressure. As a pound of air is heated, the air will expand and occupy more space and its associated specific volume will increase. Definitions Heating: The process of adding sensible heat or increasing the dry bulb temperature without increasing or decreasing moisture content (figure 12). Figure 12. Heating WN Mechanical Systems Psychrometrics Page 9 of 23

10 Cooling: The process of removing sensible heat or decreasing the dry bulb temperature without increasing or decreasing moisture content (figure 13). Figure 13. Cooling Humidifying: The process of adding moisture or latent energy without heating or cooling (figure 14) Figure 14. Humidiftying Dehumidifying: The process of removing moisture or latent energy without heating or cooling (figure 15). WN Mechanical Systems Psychrometrics Page 10 of 23

11 Figure 15. Dehumidiftying Evaporative Cooling: Simultaneous cooling and humidifying accomplished by the process of evaporating water. Psychrometrically, evaporative cooling follows a wet bulb line (figure 16). Figure 16. Evaporative Cooling Sensible Heat Ratio (SHR): The ratio of sensible heat gain to total heat gain introduced into the conditioned space. The slope of an SHR line is found by drawing a line at the circle located at 78 o F and 50% relative humidity. Extend the line to the SHR identified by the axis on the far right hand side of the chart (figure 17). This line establishes the slope of the SHR line. WN Mechanical Systems Psychrometrics Page 11 of 23

12 Figure 17. SHR Enthalpy: Measure of the heat content in a thermodynamic system. Measured as energy per unit mass flow. Enthalpy lines are very nearly parallel to wet bulb lines, but with a slightly shallower slope (figure 18). Figure 18. Enthalpy Coil Curves: The ability of a cooling coil to remove both sensible and latent moisture as a function of leaving air temperature and relative humidity. As relative humidity is low (<85% RH), the coil curve has no slope and removes no moisture from the airstream. As the air temperature approaches saturation, the coil begins removing moisture. Finally, as the air temperature approaches saturation, the coil curve begins to very nearly follow the saturation curve (figure 19). WN Mechanical Systems Psychrometrics Page 12 of 23

13 Figure 19. Coil Curve Equations Mixed Air Equation: The mixed air equation is used calculate the mixed air temperature of a system that mixes a quantity of outside air with a quantity of return air (figure 20). Figure 20. Mixing WN Mechanical Systems Psychrometrics Page 13 of 23

14 Sensible Heat Ratio: Enthalpy: Sensible Sea Level: Sensible 4500 : Total or Refrigeration Sea Level: Total or Refrigeration 4500 : Determining Supply 0 elevation: WN Mechanical Systems Psychrometrics Page 14 of 23

15 Psychrometric Chart Analysis Assumptions: Return duct heat, no fan heat. Known initial dry bulb and relative humidity. Known percentage of outside air. Step 1. Plot the outside air condition. Step 2. Plot desired room state point. Typically the conditioned dry bulb temperature is known. However, the conditioned space relative humidity is unknown. A psychrometric chart analysis can be an iterative process. The closer we are to guessing the initial relative humidity, the fewer the number of iterations required. Assume an initial space relative humidity based on your site elevation, climatic conditions, etc. Step 2a. Add return duct temperature rise If there is any return duct or return plenum temperature rise, it should be added to the space condition. This is a sensible only heat gain. Step 3. Find the mixed air condition. Draw a straight line between the return air condition and the outside air condition. The mixed air condition will fall somewhere on this line. Using the mixed air equation, find the mixed air condition dry bulb temperature. The intersection of the line connecting the return air condition and outside air condition and the calculated mixed air dry bulb identifies the mixed air state. Step 4. Draw a coil curve Draw a coil curve by using the program provided on our website at or a psychrometric chart that provides coil curves (i.e. The Trane Co). Extend the coil curve from the mixed air state point to a temperature that will be below the supply air temperature (45 o F is usually a safe assumption). Step 5. Draw a Sensible Heat Ratio (SHR) line Calculate the space SHR using the SHR equation. Your building load analysis will give you both the space sensible and latent load required to calculate the SHR. The SHR line should extend through your space return air condition (step 1) and follow the exact slope the SHR line as defined in the Chapter 2, Definitions. Extend the SHR line until it intersects with the coil curve. The intersection of coil curve with the SHR line defines the coil leaving air temperature. Step 6: Find intersection of coil curve and SHR line The point of intersection between the coil curve and SHR line determines your coil leaving air temperature. Step 7: Calculate supply airflow Using the supply air equation, calculate the supply airflow to the conditioned space. WN Mechanical Systems Psychrometrics Page 15 of 23

16 Step 8: Calculate the coil load Using the refrigeration load equation, calculate the coil load. Example 1 Figure 21. Example One For example 1, we will find the conditioned airflow and refrigeration load for a constant volume single zone system. Altitude is sea level or 0 elevation. Outside air design condition is 95 o F dry bulb, 73 o F wet bulb. Space sensible load is 10,800 Btu/hr. Space total load is 12,000 Btu/hr. Design space condition is 73 o F and 50% relative humidity. There is two degrees of return duct temperature rise. 25% of the supply airflow is outside air. WN Mechanical Systems Psychrometrics Page 16 of 23

17 Step 1. Plot the outside air condition. Figure 22. Step One Step 2. Plot desired room state point. Figure 23. Step Two WN Mechanical Systems Psychrometrics Page 17 of 23

18 Step 2a. Add return duct temperature rise Figure 24. Step Two A Step 3. Find the mixed air condition. Figure 25. Step Three Mixed air is 25% outside air, 75% return air. Thus, mixed air is 80 o F. Plot the mixed air condition that lies on a straight line between point 3 and point 4. WN Mechanical Systems Psychrometrics Page 18 of 23

19 Step 4. Draw (or plot at a coil curve Figure 26. Step Four Coil curve should intersect point 4 at 80 o F. Extend coil curve to 45 o F. Step 5. Draw a Sensible Heat Ratio (SHR) line The equation for SHR is: Total Heat Gain = Sensible Heat Gain + Latent Heat Gain. For the example, the sensible load is 10,800 Btu/hr and the total load is 12,000 Btu/hr. Therefore, for the example, our SHR is: WN Mechanical Systems Psychrometrics Page 19 of 23

20 Finally, we draw a line through state point 2 and intersects the coil curve that is parallel to the slope of an imaginary line that extends from the SHR circle (located at 78 o F and 50% RH) and.9 on the SHR vertical axis. Figure 27. Step Five Step 6: Find intersection of coil curve and SHR line, determining coil leaving air state point. The intersection of our coil curve and the SHR line extending through state point 2 intersects at 53 o F. Figure 28. Step 6 WN Mechanical Systems Psychrometrics Page 20 of 23

21 Step 7: Calculate supply airflow The equation for supply airflow at sea level is: The room dry bulb temperature is 73 degrees. The intersection of the SHR line and the coil curve establish the supply air temperature. For the example, the intersection occurs at 53 o F. Thus, the supply airflow is: Step 8: Calculate the coil load The equation for the coil load or refrigeration load is: Enthalpy at state point 4, the coil entering condition is 26.9 Btu/lb. The enthalpy at state point 5, the coil leaving condition is 21.5 Btu/lb. The refrigeration load is calculated as: WN Mechanical Systems Psychrometrics Page 21 of 23

22 Example 2 Figure 29. Example Two For example 1, find the space relative humidity and refrigeration coil load for a 100% outside air, indirect/direct energy recovery air handler. Assume 4500 elevation, 4000 CFM, 100 o F ambient dry bulb, 64 o F ambient wet bulb. Space setpoint to be 72 o F. There is two degrees of return duct heat gain. Space sensible heat ratio is.90. Sensible heat wheel effectiveness is 75% and the indirect evaporative cooler is 90% effective and the direct evaporative cooler is 65% effective. WN Mechanical Systems Psychrometrics Page 22 of 23

23 Figure 30. Example Two Psychometrics Total Refrigeration Load = 1.53 Tons Space Relative Humidity = % WN Mechanical Systems Psychrometrics Page 23 of 23

THE PSYCHROMETRIC CHART AND ITS USE

THE PSYCHROMETRIC CHART AND ITS USE Service Application Manual SAM Chapter 630-16 Section 3A THE PSYCHROMETRIC CHART AND ITS USE Psychrometry is an impressive word which is defined as the measurement of the moisture content of air. In broader

More information

Total Heat Versus Sensible Heat Evaporator Selection Methods & Application

Total Heat Versus Sensible Heat Evaporator Selection Methods & Application Total Heat Versus Sensible Heat Evaporator Selection Methods & Application Scope The purpose of this paper is to provide specifying engineers, purchasers and users of evaporators in industrial refrigeration

More information

Akton Psychrometric Chart Tutorial and Examples

Akton Psychrometric Chart Tutorial and Examples Akton Psychrometric Chart Tutorial and Examples December 1999 Akton Associates Inc. 3600 Clayton Road, Suite D Concord, California 94521 (925) 688-0333 http://www.aktonassoc.com Copyright 1999 Akton Associates

More information

Air Water Vapor Mixtures: Psychrometrics. Leon R. Glicksman c 1996, 2010

Air Water Vapor Mixtures: Psychrometrics. Leon R. Glicksman c 1996, 2010 Air Water Vapor Mixtures: Psychrometrics Leon R. Glicksman c 1996, 2010 Introduction To establish proper comfort conditions within a building space, the designer must consider the air temperature and the

More information

How To Understand And Understand Psychrometrics

How To Understand And Understand Psychrometrics Air Conditioning Psychrometrics Course No: M05-005 Credit: 5 PDH A. Bhatia Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F: (877) 322-4774 info@cedengineering.com

More information

Greenhouse Cooling. Why is Cooling Needed?

Greenhouse Cooling. Why is Cooling Needed? Greenhouse Cooling Why is Cooling Needed? Solar radiation is the heat input for the earth can radiate as much as 277 Btu/ft 2 /hr onto the surface of the earth on summer s day in coastal and industrial

More information

HVAC Made Easy - Overview of Psychrometrics

HVAC Made Easy - Overview of Psychrometrics PDHonline Course M135 (4 PDH) HVAC Made Easy - Overview of Psychrometrics Instructor: A. Bhatia, B.E. 2012 PDH Online PDH Center 5272 Meadow Estates Drive Fairfax, VA 22030-6658 Phone & Fax: 703-988-0088

More information

Characteristics of Evaporators

Characteristics of Evaporators Characteristics of Evaporators Roger D. Holder, CM, MSME 10-28-2003 Heat or Energy In this paper, we will discuss the characteristics of an evaporator coil. The variance of the operational condenses of

More information

Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal

Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal Technical Bulletin By Bruce I. Nelson, P.E., President, Colmac Coil Manufacturing, Inc. Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal SUMMARY Refrigeration air coolers (evaporators)

More information

THE HUMIDITY/MOISTURE HANDBOOK

THE HUMIDITY/MOISTURE HANDBOOK THE HUMIDITY/MOISTURE HANDBOOK Table of Contents Introduction... 3 Relative Humidity... 3 Partial Pressure... 4 Saturation Pressure (Ps)... 5 Other Absolute Moisture Scales... 8 % Moisture by Volume (%M

More information

How do I measure the amount of water vapor in the air?

How do I measure the amount of water vapor in the air? How do I measure the amount of water vapor in the air? Materials 2 Centigrade Thermometers Gauze Fan Rubber Band Tape Overview Water vapor is a very important gas in the atmosphere and can influence many

More information

By Tom Brooke PE, CEM

By Tom Brooke PE, CEM Air conditioning applications can be broadly categorized as either standard or critical. The former, often called comfort cooling, traditionally just controlled to maintain a zone setpoint dry bulb temperature

More information

Evaporative Cooling. Terminology. Date: February 28, 2012. Concepts

Evaporative Cooling. Terminology. Date: February 28, 2012. Concepts Evaporative Cooling Date: February 28, 2012 P R E S E N T E D B Y R O B E R T P A D G E T E 3 M S E N G I N E E R E D M E C H A N I C A L S Y S T E M S Concepts 1. Evaporation is a cooling process. Using

More information

Chapter 14. At temperatures below the critical temperature, the gas GAS VAPOR MIXTURES AND AIR-CONDITIONING. Objectives

Chapter 14. At temperatures below the critical temperature, the gas GAS VAPOR MIXTURES AND AIR-CONDITIONING. Objectives Chapter 14 GAS VAPOR MIXTURES AND -CONDITIONING At temperatures below the critical temperature, the gas phase of a substance is frequently referred to as a vapor. The term vapor implies a gaseous state

More information

Wet Bulb Temperature and Its Impact on Building Performance

Wet Bulb Temperature and Its Impact on Building Performance Wet Bulb Temperature and Its Impact on Building Performance By: Kurmit Rockwell, PE, CEM, LEED AP and Justin Lee, PE, LEED, AP BD+C Energy Solution Services, AtSite, Inc. 1 What is Wet Bulb Temperature?

More information

Temperature and Humidity

Temperature and Humidity Temperature and Humidity Overview Water vapor is a very important gas in the atmosphere and can influence many things like condensation and the formation of clouds and rain, as well as how hot or cold

More information

HVAC Calculations and Duct Sizing

HVAC Calculations and Duct Sizing PDH Course M199 HVAC Calculations and Duct Sizing Gary D. Beckfeld, M.S.E., P.E. 2007 PDH Center 2410 Dakota Lakes Drive Herndon, VA 20171-2995 Phone: 703-478-6833 Fax: 703-481-9535 www.pdhcenter.com An

More information

Hospital Application Guide. Cost-effective climate control for hospitals

Hospital Application Guide. Cost-effective climate control for hospitals Hospital Application Guide Cost-effective climate control for hospitals Munters is the world leader in dehumidification Munters is the largest manufacturer of dehumidifiers in the world. Since developing

More information

The HVAC Process: Changing the Properties of Air

The HVAC Process: Changing the Properties of Air The HVAC Process: Changing the Properties of Air Alexander Delli Paoli, Jr. ABSTRACT This discussion addresses the physical properties of air and water vapor mixtures. The components of the heating, ventilation,

More information

Dedicated Outdoor Air-Dual Wheel System Control Requirements

Dedicated Outdoor Air-Dual Wheel System Control Requirements 4428 Dedicated Outdoor Air-Dual Wheel System Control Requirements Stanley A. Mumma, Ph.D., P.E. Fellow ASHRAE ABSTRACT The central thrust of this paper is to develop a clear understanding of the performance

More information

CONDENSATION. Section Break (Next Page)

CONDENSATION. Section Break (Next Page) CONDENSATION Elimination of condensation on or within walls and floors is as important as reducing the heat loss through the wall or floor. In addition to the moisture damage caused to buildings by condensation,

More information

Energy Recovery Ventilation Equipment

Energy Recovery Ventilation Equipment AHRI Standard 1060 (I-P) 2013 Standard for Performance Rating of Airto-Air Exchangers for Energy Recovery Ventilation Equipment IMPORTANT SAFETY DISCLAIMER AHRI does not set safety standards and does not

More information

APPLICATION GUIDE. Moisture Management in Waterborne Climate Systems

APPLICATION GUIDE. Moisture Management in Waterborne Climate Systems APPLICATION GUIDE Moisture Management in Waterborne Climate Systems Contents Introduction 3 WBCS Concept 3 Condensation 4 Moisture Sources in the Space 4 Impact of a High Moisture Load 5 Designing to Manage

More information

Moisture Control. It s The Dew Point. Stupid! Its not the humidity.

Moisture Control. It s The Dew Point. Stupid! Its not the humidity. Moisture Control Its not the humidity. It s The Dew Point Stupid! Mike Schell EpiphanyTec Inc. Santa Barbara, CA mschell@epiphanytec.com 805 687-3175 Matching great technology to market need! Topics SHR

More information

APPLICATION GUIDE. Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application

APPLICATION GUIDE. Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application APPLICATION GUIDE Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application Section Comparison of Latent Cooling Performance of Introduction Most commercial HVAC systems

More information

Troubleshooting an Air Conditioning system. R D Holder Eng. Roger D Holder MSME

Troubleshooting an Air Conditioning system. R D Holder Eng. Roger D Holder MSME Troubleshooting an Air Conditioning system R D Holder Eng. Roger D Holder MSME Troubleshooting of an air conditioning system is a step by step procedure. I have found that a 4 step procedure is the best

More information

THE PSYCHROMETRIC CHART: Theory and Application. Perry Peralta NC State University

THE PSYCHROMETRIC CHART: Theory and Application. Perry Peralta NC State University THE PSYCHROMETRIC CHART: Theory and Application Perry Peralta NC State University PSYCHROMETRIC CHART Identify parts of the chart Determine moist air properties Use chart to analyze processes involving

More information

Energy Efficient Building Design College of Architecture Illinois Institute of Technology, Chicago. Relative Humidities RH% 49.4. 0.

Energy Efficient Building Design College of Architecture Illinois Institute of Technology, Chicago. Relative Humidities RH% 49.4. 0. Psychrometrics Psychrometric Chart Relative Humidities RH% 49.4 100% 80% 0.030 Enthalpies 70% H btu/lb 46.5 0.028 85 Not to Scale 0.026 Humidity Numbers and Values 43.7 60% Ratios are approximate 0.024

More information

Dehumidification Frequently Asked Questions

Dehumidification Frequently Asked Questions Dehumidification Basics Why do you want to keep indoor Rh between 30-60%? ASHRAE recommends keeping the relative humidity in a home between 30-60% to limit the effects of many unwanted conditions and harmful

More information

Because here you can see a simple an elementary direct evaporative cooling system this is called as a single stage system you can see from the

Because here you can see a simple an elementary direct evaporative cooling system this is called as a single stage system you can see from the Refrigeration and Air Conditioning Prof M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur Lecture No. # 38 Air Conditioning Systems Welcome back in the last lecture

More information

Purpose: To determine the dew and point and relative humidity in the classroom, and find the current relative humidity outside.

Purpose: To determine the dew and point and relative humidity in the classroom, and find the current relative humidity outside. Lab Exercise: Dew Point and Relative Humidity Purpose: To determine the dew and point and relative humidity in the classroom, and find the current relative humidity outside. Relative humidity is a measure

More information

ES 106 Laboratory # 6 MOISTURE IN THE ATMOSPHERE

ES 106 Laboratory # 6 MOISTURE IN THE ATMOSPHERE ES 106 Laboratory # 6 MOISTURE IN THE ATMOSPHERE 6-1 Introduction By observing, recording, and analyzing weather conditions, meteorologists attempt to define the principles that control the complex interactions

More information

UNDERSTANDING REFRIGERANT TABLES

UNDERSTANDING REFRIGERANT TABLES Refrigeration Service Engineers Society 1666 Rand Road Des Plaines, Illinois 60016 UNDERSTANDING REFRIGERANT TABLES INTRODUCTION A Mollier diagram is a graphical representation of the properties of a refrigerant,

More information

Humid Air. Water vapor in air. Trace Glasses 1% Argon (A) Water vapor (H 2

Humid Air. Water vapor in air. Trace Glasses 1% Argon (A) Water vapor (H 2 Humid Air Water vapor in air Oxygen 21% Trace Glasses 1% Argon (A) Water vapor (H 2 O) Carbon dioxide (CO 2 ) Neon (Ne) Helium (He) Krypton (Kr) Hydrogen (H) Ozone (O 3 ) Nitrogen 78% Humid Air Water vapor

More information

Environmental Data Center Management and Monitoring

Environmental Data Center Management and Monitoring 2013 Raritan Inc. Table of Contents Introduction Page 3 Sensor Design Considerations Page 3 Temperature and Humidity Sensors Page 4 Airflow Sensor Page 6 Differential Air Pressure Sensor Page 6 Water Sensor

More information

Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida

Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida Optimizing 100% Outside Air Systems with Heat Pipes Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida Introduction To meet increasingly rigorous building codes

More information

Evaporative Cooling for Residential and Light-Commercial

Evaporative Cooling for Residential and Light-Commercial EMERGING TECHNOLOGIES This article was published in ASHRAE Journal, October 2011. Copyright 2011 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Posted at www.ashrae.org.

More information

Measuring The Right Thing For Humidity Control It s the Dew Point Stupid!

Measuring The Right Thing For Humidity Control It s the Dew Point Stupid! Page 1 of 6 Measuring The Right Thing For Humidity Control It s the Dew Point Stupid! By Mike Schell, AirTest Technologies Corp. A version of this article appeared in the June 2004 edition of Indoor Air

More information

Absolute and relative humidity Precise and comfort air-conditioning

Absolute and relative humidity Precise and comfort air-conditioning Absolute and relative humidity Precise and comfort air-conditioning Trends and best practices in data centers Compiled by: CONTEG Date: 30. 3. 2010 Version: 1.11 EN 2013 CONTEG. All rights reserved. No

More information

Data Centres. Special Working Group Spin I Relative Humidity in Data Centres

Data Centres. Special Working Group Spin I Relative Humidity in Data Centres Data Centres Special Working Group Spin I Table of Contents 1. Introduction 1 2. Data Centre Climate 1 2.1 Temperature 1 2.2 Particles and dust 2 2.3 Gases 3 2.4 Humidity 3 3. What is Humidity? 4 3.1 How

More information

Creating the Ideal Environment for Accelerated Drying Times on Construction and Restoration Projects

Creating the Ideal Environment for Accelerated Drying Times on Construction and Restoration Projects 4.02.08 updated Creating the Ideal Environment for Accelerated Drying Times on Construction and Restoration Projects Moisture Removal Systems www.groundheaters.com www.wackerneuson.com Controlling moisture

More information

Refrigeration Manual. Part 3 - The Refrigeration Load

Refrigeration Manual. Part 3 - The Refrigeration Load Refrigeration Manual Part 3 - The Refrigeration Load FOREWORD The practice of refrigeration undoubtedly goes back as far as the history of mankind, but for thousands of years the only cooling mediums were

More information

Using Wet-Bulb Economizers. Data Center Cooling

Using Wet-Bulb Economizers. Data Center Cooling The following article was published in ASHRAE Journal, August 2008. Copyright 2008 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. It is presented for educational purposes

More information

Dedicated Outdoor Air Systems (D.O.A.S.)

Dedicated Outdoor Air Systems (D.O.A.S.) Commercial and Industrial Climate Control Systems Dedicated Outdoor Air Systems (D.O.A.S.) AMDOAS-1 What is it? Why use one? What are my options? Selection considerations Design steps What is it? A separate

More information

Improving Data Center Energy Efficiency Through Environmental Optimization

Improving Data Center Energy Efficiency Through Environmental Optimization Improving Data Center Energy Efficiency Through Environmental Optimization How Fine-Tuning Humidity, Airflows, and Temperature Dramatically Cuts Cooling Costs William Seeber Stephen Seeber Mid Atlantic

More information

Defining Quality. Building Comfort. Precision. Air Conditioning

Defining Quality. Building Comfort. Precision. Air Conditioning Defining Quality. Building Comfort. Precision Air Conditioning Today s technology rooms require precise, stable environments in order for sensitive electronics to operate optimally. Standard comfort air

More information

DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER

DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTERS 2009 IT Emissions = Aviation Industry Emissions Nations Largest Commercial Consumers of Electric Power Greenpeace estimates

More information

Refrigeration and Air Conditioning with Psychrometry

Refrigeration and Air Conditioning with Psychrometry Refrigeration and Air Conditioning with Psychrometry Refrigeration is a process of maintaining low temperature in comparison to surrounding temperature. Refrigeration is the process of removing heat from

More information

2. The map below shows high-pressure and low-pressure weather systems in the United States.

2. The map below shows high-pressure and low-pressure weather systems in the United States. 1. Which weather instrument has most improved the accuracy of weather forecasts over the past 40 years? 1) thermometer 3) weather satellite 2) sling psychrometer 4) weather balloon 6. Wind velocity is

More information

High Altitude HVAC. Silvertip Integrated Engineering Consultants mhaughey@earthlink.net www.silvertipconsultants.com

High Altitude HVAC. Silvertip Integrated Engineering Consultants mhaughey@earthlink.net www.silvertipconsultants.com Presentation to: Rocky Mountain ASHRAE 2013 Tech Conference April 19, 2013 High Altitude HVAC Design Considerations by: Michael D. Haughey, PE, HBDP, CEM, LEED TM AP 2013 Silvertip Integrated Engineering

More information

Cooling Tower Basics and Common Misconceptions

Cooling Tower Basics and Common Misconceptions Cooling Tower Basics and Common Misconceptions Introduction In comparison with most other industrial equipments, the water cooling tower is a simple device, based on the direct contact of two of the earth

More information

Venice Library Humidity Study. for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205. Report April 13, 2015

Venice Library Humidity Study. for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205. Report April 13, 2015 for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205 Report April 13, 2015 Moses & Associates, Inc. 2209 NW 40 th Terrace, Suite A Gainesville, FL 32605 FL License EB-0003097

More information

Chilled Water HVAC Systems

Chilled Water HVAC Systems Chilled Water HVAC Systems By Ron Prager, Brinco Mechanical Services, Inc. Types of water based systems: There are three types of HVAC systems that utilize water as a heat transfer medium. The first system,

More information

> Executive summary. Explanation of Cooling and Air Conditioning Terminology for IT Professionals. White Paper 11 Revision 2. Contents.

> Executive summary. Explanation of Cooling and Air Conditioning Terminology for IT Professionals. White Paper 11 Revision 2. Contents. Explanation of Cooling and Air Conditioning Terminology for IT Professionals White Paper 11 Revision 2 by Tony Evans Click on a section to jump to it > Executive summary As power densities continue to

More information

HVAC and REFRIGERATION

HVAC and REFRIGERATION This is a preview. Some pages have been omitted. PE principles and practice prracticce of engineering mechanical: HVAC and REFRIGERATION sample questions + solutions Copyright 2011 by NCEES. All rights

More information

Name: OBJECTIVES Correctly define: WEATHER BASICS: STATION MODELS: MOISTURE: PRESSURE AND WIND: Weather

Name: OBJECTIVES Correctly define: WEATHER BASICS: STATION MODELS: MOISTURE: PRESSURE AND WIND: Weather Name: OBJECTIVES Correctly define: air mass, air pressure, anemometer, barometer, cyclone, dew point, front, isobar, isotherm, meteorology, precipitation, psychrometer, relative humidity, saturated, transpiration

More information

It will be available soon as an 8.5 X 11 paperback. For easier navigation through the e book, use the table of contents.

It will be available soon as an 8.5 X 11 paperback. For easier navigation through the e book, use the table of contents. The System Evaluation Manual and Chiller Evaluation Manual have been revised and combined into this new book; the Air Conditioning and Refrigeration System Evaluation Guide. It will be available soon as

More information

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING V. Vakiloroaya*, J.G. Zhu, and Q.P. Ha School of Electrical, Mechanical and Mechatronic Systems,

More information

Analysis of data centre cooling energy efficiency

Analysis of data centre cooling energy efficiency Analysis of data centre cooling energy efficiency An analysis of the distribution of energy overheads in the data centre and the relationship between economiser hours and chiller efficiency Liam Newcombe

More information

Humidification Strategies for Data Centers and Network Rooms

Humidification Strategies for Data Centers and Network Rooms Humidification Strategies for Data Centers and Network Rooms By Tony Evans White Paper #58 Revision 1 Executive Summary The control of humidity in Information Technology environments is essential to achieving

More information

The formula for finding CFM is: CFM = BTUH OUTPUT_ Temp Rise (ACF)* *Altitude correction factor below 1000ft = 1.08

The formula for finding CFM is: CFM = BTUH OUTPUT_ Temp Rise (ACF)* *Altitude correction factor below 1000ft = 1.08 Air Volume Requirement Air conditioning systems are engineered with a specific amount of indoor air passing across the surface of the evaporator coil. The amount of air is measured in cubic feet per minute.

More information

COMMERCIAL HVAC EQUIPMENT. Condensers and Cooling Towers

COMMERCIAL HVAC EQUIPMENT. Condensers and Cooling Towers COMMERCIAL HVAC EQUIPMENT Condensers and Cooling Towers Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design, equipment selection and application topics.

More information

Strategy Guideline: HVAC Equipment Sizing

Strategy Guideline: HVAC Equipment Sizing Strategy Guideline: HVAC Equipment Sizing Arlan Burdick IBACOS, Inc. February 2012 This report received minimal editorial review at NREL NOTICE This report was prepared as an account of work sponsored

More information

EFFECTS OF INDOOR RELATIVE HUMIDITY ON REFRIGERATED DISPLAY CASE PERFORMANCE

EFFECTS OF INDOOR RELATIVE HUMIDITY ON REFRIGERATED DISPLAY CASE PERFORMANCE P (5, EFFECTS OF INDOOR RELATIVE HUMIDITY ON REFRIGERATED DISPLAY CASE PERFORMANCE Ronald H. Howell, Professor Luis Rosario, Graduate Student Antonio Bula, Graduate Student Department of Mechanical Engineering

More information

Name: Date: LAB: Dew Point and Cloud Formation Adapted from Exploration in Earth Science, The Physical Setting, United Publishing Company, Inc.

Name: Date: LAB: Dew Point and Cloud Formation Adapted from Exploration in Earth Science, The Physical Setting, United Publishing Company, Inc. Name: _ Date: LAB: Dew Point and Cloud Formation Adapted from Exploration in Earth Science, The Physical Setting, United Publishing Company, Inc. Introduction: Cumulus clouds are our puffy fair weather

More information

Theoretical Study on Separate Sensible and Latent Cooling Air-Conditioning System

Theoretical Study on Separate Sensible and Latent Cooling Air-Conditioning System Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2008 Theoretical Study on Separate Sensible and Latent Cooling Air-Conditioning

More information

newsletter Let s take a high-level look at airside economizing: what it is, what it requires, and how it s done. How does economizer cooling work?

newsletter Let s take a high-level look at airside economizing: what it is, what it requires, and how it s done. How does economizer cooling work? engineers volume 35 2 newsletter providing insights for today s hvac system designer keeping cool with outdoor air Airside Economizers from the editor For the denizens of commercial buildings, comfort

More information

Pool Dehumidification Basics

Pool Dehumidification Basics Copyright 2009 Wescor. All rights reserved. Permission granted to reproduce for personal and educational use only. When energy costs were low, many pool owners considered only first cost when choosing

More information

AIR CONDITIONING TECHNOLOGY

AIR CONDITIONING TECHNOLOGY AIR CONDITIONING TECHNOLOGY PART 9 Water Cooled Condensers & Cooling Towers IN LAST month s article we looked at how Air Cooled Condensers are used to transfer the total heat of rejection from the air

More information

Cooling Load Calculation

Cooling Load Calculation for A Probabilistic Approach Taperit Tongshoob 1 Chirdpun Vitooraporn 2 Cooling Load Calculation Abstract 1 Ph.D Student 2 Lecturer at Building Technology Environment Laboratory, Mechanical Engineering

More information

Glossary of Heating, Ventilation and Air Conditioning Terms

Glossary of Heating, Ventilation and Air Conditioning Terms Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment

More information

85 F 80 F 50% 75 F 70 F 73.0/61.8 45 F 10% Figure 1

85 F 80 F 50% 75 F 70 F 73.0/61.8 45 F 10% Figure 1 Feb. 07 INTRODUCTION: Wrap around heat pipes are air-to-air heat exchangers that are installed in the airstream upstream and downstream of a cooling coil to deliberately reduce the Sensible Heat Ratio

More information

Economizer Fundamentals: Smart Approaches to Energy-Efficient Free-Cooling for Data Centers

Economizer Fundamentals: Smart Approaches to Energy-Efficient Free-Cooling for Data Centers A White Paper from the Experts in Business-Critical Continuity TM Economizer Fundamentals: Smart Approaches to Energy-Efficient Free-Cooling for Data Centers Executive Summary The strategic business importance

More information

Role of Economizers in Dedicated Outdoor Air Systems

Role of Economizers in Dedicated Outdoor Air Systems Introduction: Role of Economizers in Dedicated Outdoor Air Systems A question that frequently arises when a dedicated outdoor air system (DOAS) (Mumma, 2001) is discussed, particularly when the parallel

More information

UNIT 6a TEST REVIEW. 1. A weather instrument is shown below.

UNIT 6a TEST REVIEW. 1. A weather instrument is shown below. UNIT 6a TEST REVIEW 1. A weather instrument is shown below. Which weather variable is measured by this instrument? 1) wind speed 3) cloud cover 2) precipitation 4) air pressure 2. Which weather station

More information

COURSE TITLE : REFRIGERATION AND AIR CONDITIONING COURSE CODE : 4029 COURSECATEGORY : A PERIODS/WEEK : 5 PERIODS/SEMESTER : 90 CREDITS : 4 OBJECTIVES

COURSE TITLE : REFRIGERATION AND AIR CONDITIONING COURSE CODE : 4029 COURSECATEGORY : A PERIODS/WEEK : 5 PERIODS/SEMESTER : 90 CREDITS : 4 OBJECTIVES COURSE TITLE : REFRIGERATION AND AIR CONDITIONING COURSE CODE : 4029 COURSECATEGORY : A PERIODS/WEEK : 5 PERIODS/SEMESTER : 90 CREDITS : 4 TIME SCHEDULE MODULE TOPICS PERIODS 1 Introduction 22 Principles

More information

HOT & COLD. Basic Thermodynamics and Large Building Heating and Cooling

HOT & COLD. Basic Thermodynamics and Large Building Heating and Cooling HOT & COLD Basic Thermodynamics and Large Building Heating and Cooling What is Thermodynamics? It s the study of energy conversion using heat and other forms of energy based on temperature, volume, and

More information

newsletter engineers energy-saving strategies for Water-Source Heat Pump Systems volume 36 2 providing insights for today s hvac system designer

newsletter engineers energy-saving strategies for Water-Source Heat Pump Systems volume 36 2 providing insights for today s hvac system designer engineers volume 36 2 newsletter providing insights for today s hvac system designer energy-saving strategies for Water-Source Heat Pump Systems from the editor... Water-source heat pump (WSHP) systems

More information

7613-1 - Page 1. Weather Unit Exam Pre-Test Questions

7613-1 - Page 1. Weather Unit Exam Pre-Test Questions Weather Unit Exam Pre-Test Questions 7613-1 - Page 1 Name: 1) Equal quantities of water are placed in four uncovered containers with different shapes and left on a table at room temperature. From which

More information

AIR SYSTEMS ENERGY SERIES Energy Recovery Wheels

AIR SYSTEMS ENERGY SERIES Energy Recovery Wheels AIR SYSTEMS ENERGY SERIES Energy Recovery Wheels APPLICATION GUIDE Supercedes: Nothing Form 102.20-AG6 (305) INTRODUCTION As fossil fuel reserves are depleted, the cost of energy continues to rise. According

More information

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES

More information

Humidity the story for teachers

Humidity the story for teachers Humidity the story for teachers As we have learned earlier, water may exist as a gas (water vapour). Even in the driest desert there is some water vapour in the air. Water vapour is the most important

More information

How to Save Over 60% on Cooling Energy Needed by a Data Center? The Roadmap from Traditional to Optimized Cooling

How to Save Over 60% on Cooling Energy Needed by a Data Center? The Roadmap from Traditional to Optimized Cooling How to Save Over 60% on Cooling Energy Needed by a Data Center? The Roadmap from Traditional to Optimized Cooling Abstract Data center managers are increasingly in search of methods and technologies for

More information

Heating and Cooling Basics Thermostat Control

Heating and Cooling Basics Thermostat Control Heating and Cooling Basics Thermostat Control UNI-LINE PRODUCT KNOWLEDGE 2012 Invensys. All Rights Reserved. The names, logos, and taglines identifying the products and services of Invensys are proprietary

More information

SKEW-T, LOG-P DIAGRAM ANALYSIS PROCEDURES

SKEW-T, LOG-P DIAGRAM ANALYSIS PROCEDURES SKEW-T, LOG-P DIAGRAM ANALYSIS PROCEDURES I. THE SKEW-T, LOG-P DIAGRAM The primary source for information contained in this appendix was taken from the Air Weather Service Technical Report TR-79/006. 1

More information

LIQUID DESICCANT AIR CONDITIONING Saves energy, Controls humidity, Cleans air. Trevor Wende Vice President, Marketing Advantix Systems, Inc.

LIQUID DESICCANT AIR CONDITIONING Saves energy, Controls humidity, Cleans air. Trevor Wende Vice President, Marketing Advantix Systems, Inc. LIQUID DESICCANT AIR CONDITIONING Saves energy, Controls humidity, Cleans air Trevor Wende Vice President, Marketing Advantix Systems, Inc. 0 Humidity: The Hidden Cost Driver Conventional A/C process Start

More information

HVAC FORMULAS. TON OF REFRIGERATION - The amount of heat required to melt a ton (2000 lbs.) of ice at 32 F. 288,000 BTU/24 hr. 12,000 BTU/hr.

HVAC FORMULAS. TON OF REFRIGERATION - The amount of heat required to melt a ton (2000 lbs.) of ice at 32 F. 288,000 BTU/24 hr. 12,000 BTU/hr. HVAC FORMULAS TON OF REFRIGERATION - The amount of heat required to melt a ton (2000 lbs.) of ice at 32 F 288,000 BTU/24 hr. 12,000 BTU/hr. APPROXIMATELY 2 inches in Hg. (mercury) = 1 psi WORK = Force

More information

Introduction. Motor Types

Introduction. Motor Types QwikSEER+ Theory of Operation and Retrofit Potential Mainstream Engineering Corporation Rockledge, FL 32955 http://www.qwik.com/products/qwikseer/index.jsp Prepared by Robert P. Scaringe and R. Paul Roth

More information

GAS TURBINE INLET AIR CHILLING FOR LNG

GAS TURBINE INLET AIR CHILLING FOR LNG GAS TURBINE INLET AIR CHILLING FOR LNG John L. Forsyth, P.Eng. LNG Business Development Manager TAS Energy, Houston, Texas ABSTRACT It is well recognized that gas turbines used as compressor drivers in

More information

VAV Laboratory Room Airflow The Lowdown on Turndown

VAV Laboratory Room Airflow The Lowdown on Turndown Technology Report March, 2003 VAV Laboratory The Lowdown on Turndown Turndown comparison of these two turndown ratios. Note the small actual airflow difference between them. control ranges are normally

More information

9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS

9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS 9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS 9.1 Introduction Air conditioning and refrigeration consume significant amount of energy in buildings and in process industries. The energy consumed in

More information

Humidity, Condensation, Clouds, and Fog. Water in the Atmosphere

Humidity, Condensation, Clouds, and Fog. Water in the Atmosphere Humidity, Condensation, Clouds, and Fog or Water in the Atmosphere The Hydrologic Cycle Where the Water Exists on Earth Evaporation From the Oceans and Land The Source of Water Vapor for the Atmosphere

More information

Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling

Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling Data Center Design Guide featuring Water-Side Economizer Solutions with Dynamic Economizer Cooling Presenter: Jason Koo, P.Eng Sr. Field Applications Engineer STULZ Air Technology Systems jkoo@stulz ats.com

More information

Walnut Drying Design and Operation. Selecting Dryer Type. Tray Drying Before 1920. Don Osias Jim Thompson

Walnut Drying Design and Operation. Selecting Dryer Type. Tray Drying Before 1920. Don Osias Jim Thompson Walnut Drying Design and Operation Don Osias Jim Thompson Selecting Dryer Type Tray Drying Before 1920 1 Stack Dryer Energy efficient High capital cost Pothole For small lots High labor cost Hopper-bottom

More information

Performance Rating of Room Fan- Coils

Performance Rating of Room Fan- Coils ANSI/AHRI Standard 440 with Addendum 1 (Formerly ARI Standard 440) 2008 Standard for Performance Rating of Room Fan- Coils ANSI/AHRI STANDARD 440-2008 WITH ADDENDUM 1, PERFORMANCE RATING OF ROOM FAN-COILS

More information

EVAPORATIVE COOLING DESIGN GUIDELINES MANUAL

EVAPORATIVE COOLING DESIGN GUIDELINES MANUAL Energy Conservation and Management Division Energy, Minerals and Natural Resources Department = HEAT + AIR + WATER = COOLING EVAPORATIVE COOLING DESIGN GUIDELINES MANUAL FOR NEW MEXICO SCHOOLS AND COMMERCIAL

More information

Fundamentals of HVAC Systems

Fundamentals of HVAC Systems Fundamentals of HVAC Systems This Page is Intentionally Left Blank Fundamentals of HVAC Systems Prepared by Robert McDowall, P. Eng. Engineering Change Inc. American Society of Heating, Refrigerating and

More information

Sustainable Preservation Practices for Managing Storage Environments Webinar: April 3, 2013

Sustainable Preservation Practices for Managing Storage Environments Webinar: April 3, 2013 The Fundamentals of HVAC: What Shapes the Storage Environment Sustainable Preservation Practices for Managing Storage Environments Webinar: April 3, 2013 Introduction Presenter Jeremy Linden, Preservation

More information

Evaporative Cooling System for Aquacultural Production 1

Evaporative Cooling System for Aquacultural Production 1 Fact Sheet EES-100 March 1993 Evaporative Cooling System for Aquacultural Production 1 C. D. Baird, R. A. Bucklin, C. A. Watson and F. A. Chapman 2 INTRODUCTION Florida aquaculture sales totaled $54 million

More information