DEPARTMENT OF DEFENSE HANDBOOK
|
|
|
- Regina Blair
- 9 years ago
- Views:
Transcription
1 NOT MEASUREMENT SENSITIVE 9 April 2004 DEPARTMENT OF DEFENSE HANDBOOK GUIDANCE FOR TEST PROCEDURES FOR DEMONSTRATION OF UTILIZATION EQUIPMENT COMPLIANCE TO AIRCRAFT ELECTRICAL POWER CHARACTERISTICS 28 VDC ( PART 8 OF 8 PARTS ) This Handbook is for guidance only. Do not cite this document as a requirement. AMSC N/A AREA SESS
2 FOREWORD 1. This handbook is approved for use by all Departments and Agencies of the Department of Defense. 2. This handbook provides guidance on test procedures for demonstration of 28 VDC utilization equipment to determine compliance with the applicable edition of MIL-STD is Part 8 in a series of 8 Parts. Part 8 describes the test methods and procedures to demonstrate that 28 VDC utilization equipment is compatible with the electric power characteristics of MIL-STD-704. These series of handbooks and MIL-STD-704 are companion documents. 4. Comments, suggestions, or questions on this document should be addressed to Commander, Naval Air Systems Command, Code 4.1.4, Highway 547, Lakehurst, NJ or to [email protected]. Since contact information can change, you may want to verify the currency of this address information using the ASSIST Online database at ii
3 CONTENTS PARAGRAPH PAGE FOREWORD... ii 1. SCOPE Scope APPLICABLE DOCUMENTS General Government documents Specifications, standards and handbooks DEFINITIONS Acronyms and definitions TEST METHODS INFORMATION Demonstration of compatibility Recording performance Calibration of test equipment Test methods TEST METHODS... 3 METHOD LDC101 Load Measurements... 4 METHOD LDC102 Steady State Limits for... 9 METHOD LDC103 Distortion Spectrum METHOD LDC104 Total Ripple METHOD LDC105 Normal Transients METHOD LDC201 Power Interrupt METHOD LDC301 Steady State Limits for METHOD LDC302 Abnormal Transients METHOD LDC401 Steady State Limits for METHOD LDC501 Starting Transients METHOD LDC601 Power Failure METHOD LDC602 Phase Reversal NOTES Intended use Subject term (keyword) listing TABLE LDC-I. Summary of 28 VDC utilization equipment MIL-STD-704 compliance tests... 2 CONCLUDING MATERIAL iii
4 1. SCOPE 1.1 Scope. This handbook provides, as guidance, test methods used to demonstrate that 28 VDC utilization equipment is compatible with the electric power characteristics of the applicable edition(s) of MIL-STD-704. This handbook is for guidance only and cannot be cited as a requirement. 2. APPLICABLE DOCUMENTS 2.1 General. The documents listed below are not necessarily all of the documents referenced herein, but are those needed to understand the information provided by this handbook. 2.2 Government documents Specifications, standards, and handbooks. The following specifications, standards, and handbooks form a part of this document to the extent specified herein. DEPARTMENT OF DEFENSE STANDARDS MIL-STD-704 DoD Interface Standard for Aircraft Electric Power Characteristics (Copies of these documents are available online at daps.dla.mil/quicksearch or or from the Standardization Document Order Desk, 700 Robbins Avenue, Building 4D, Philadelphia, PA ) 3. DEFINITIONS 3.1 Acronyms and definitions. The acronyms and definitions of MIL-STD-704 are applicable to this handbook. 4. TEST METHODS INFORMATION 4.1 Demonstration of compatibility. This section contains the test methods which will ensure that 28 VDC utilization equipment is compatible with the electric power characteristics of the applicable edition(s) of MIL-STD-704, by testing the Unit Under Test (UUT) in accordance with the test procedures as described in test methods LDC101 through LDC Recording performance. In table LDC-I, record the edition(s) of MIL-STD-704 that defined the aircraft electric power characteristics used for testing and the performance of the UUT for each of the test methods. 4.2 Calibration of test equipment. Test equipment and accessories required for measurement in accordance with this handbook should be calibrated in accordance with an approved calibration program traceable to the National Institute for Standards and Technology. 1
5 The serial numbers, model, and calibration date of all test equipment should be included with the test data. 4.3 Test methods. The test methods listed in table LDC-I are provided in section 5 of this handbook. TABLE LDC-I. Summary of 28 VDC utilization equipment MIL-STD-704 compliance tests. UUT: Compliance to MIL-STD-704 Edition(s): Test Dates: Test Description Method Normal, Aircraft Electrical Operation LDC101 Load Measurements LDC102 Steady State Limits for LDC103 Distortion Spectrum LDC104 Total Ripple LDC105 Normal Transients Transfer, Aircraft Electrical Operation LDC201 Power Interrupt Abnormal, Aircraft Electrical Operation LDC301 Abnormal Steady State Limits for LDC302 Abnormal Transients (Overvoltage/Undervoltage) Emergency, Aircraft Electrical Operation LDC401 Emergency Limits for Starting, Aircraft Electrical Operation LDC501 Starting Transients Power Failure, Aircraft Electrical Operation LDC601 Power Failure LDC602 Polarity Reversal Performance (Pass/Fail) Comments 2
6 5. TEST METHODS 3
7 METHOD LDC101 Load Measurements POWER GROUP: AIRCRAFT ELECTRICAL OPERATING CONDITION: PARAMETER: 28 Volt DC Normal Load Measurements 1. Scope. 1.1 Purpose. This test procedure is used to verify that 28 volt DC power utilization equipment meets the load limits, inrush limits, current distortion limits and current spectrum limits that may be required by the utilization equipment performance specification document. 2. Validation criteria. If required by the utilization equipment performance specification document, the utilization equipment is considered to have passed if the utilization equipment is within the load limits, inrush current limits, the current distortion limit, and the current spectrum limits specified in the utilization equipment performance specification document. As noted in table LDC101-I, the load limits, inrush current limits, the current distortion limit, and the current spectrum limits are not specified in MIL-STD-704 versions A through F. The utilization equipment must not suffer damage or cause an unsafe condition. Note: The utilization equipment performance specification document should include requirements that reduce the likelihood of the equipment having an adverse effect on the electrical power characteristics of the aircraft. Load, inrush currents, current distortion and current spectrum limits may be imposed to minimize undesirable effects to the electrical power characteristics. These limits should take into account the utilization equipment power draw, aircraft electrical system capacity and distribution characteristics, trade-offs with weight, volume, cost, and reliability that are specific to each type of equipment and aircraft. TABLE LDC101-I. MIL-STD-704 limits for load, inrush current, current distortion factor, and current spectrum for 28 volt DC utilization equipment. Limit 704A 704B 704C 704D 704E 704F Inrush N/A 1/ N/A 1/ N/A 1/ N/A 1/ N/A 1/ N/A 1/ Current Load (VA) N/A 1/ N/A 1/ N/A 1/ N/A 1/ N/A 1/ N/A 1/ Current N/A 1/ N/A 1/ N/A 1/ N/A 1/ N/A 1/ N/A 1/ Distortion Factor Current Spectrum N/A 1/ N/A 1/ N/A 1/ N/A 1/ N/A 1/ N/A 1/ 1/. Limits for Load, Inrush Current, Current Distortion Factor, and Current Spectrum must be defined in the utilization equipment performance specification document and are unique to each equipment. 4
8 3. Apparatus. The test equipment should be as follows: a. Adjustable DC power supply b. True RMS voltmeter c. Power meter d. Spectrum analyzer e. Distortion meter f. Current transformer g. Oscilloscope 4. Test setup. Configure the test setup as shown in figure LDC Measurements, except current, must be made within 10 cm of the input power terminals of the UUT. The current measurement must be taken from the 28 volt DC conductor. 5. Compliance test. With the power source off, install the UUT and the stimulation and monitoring equipment into the test setup of figure LDC Turn on the power source and adjust the voltage to the nominal steady state voltage of 28 VDC. If the utilization equipment performance specification document: a. Imposes inrush current limits, close the circuit breaker, energizing the UUT. Record the inrush current in the data sheet shown in table LDC101-II and compare with the limits of utilization equipment performance specification document. Allow sufficient time for the UUT to warm up. Conduct a performance test of the UUT according to the utilization equipment performance test procedures to verify that the UUT is providing specified performance for normal aircraft electrical conditions. Repeat for each mode of operation of the UUT. b. Imposes load limits, energize the UUT. Allow sufficient time for the UUT to warm up. Conduct a performance test of the UUT according to the utilization equipment performance test procedures to verify that the UUT is providing specified performance for normal aircraft electrical conditions. Record the load (Volt-Amps) and the voltage in the data sheet shown in table LDC101-II and compare with the limits of utilization equipment performance specification document. Repeat for each mode of operation of the UUT. c. Imposes current distortion limits, energize the UUT. Allow sufficient time for the UUT to warm up. Conduct a performance test of the UUT according to the utilization equipment performance test procedures to verify that the UUT is providing specified performance for normal aircraft electrical conditions. Record the current distortion factor in the data sheet shown in table LDC101-II and compare with the limits of utilization equipment performance specification document. Repeat for each mode of operation of the UUT. d. Imposes current spectrum limits, energize the UUT. Allow sufficient time for the UUT to warm up. Conduct a performance test of the UUT according to the utilization equipment performance test procedures to verify that the UUT is providing specified performance for 5
9 normal aircraft electrical conditions. Record the current spectrum (current amplitude vs. frequency) in the data sheet shown in table LDC101-II and compare with the limits of utilization equipment performance specification document. Repeat for each mode of operation of the UUT. 6
10 True RMS Voltm eter Power Meter Spectrum Analyzer Oscilloscope Distortion Meter (See Note 3) (See Note 3) (See Note 3) (See Note 3) (See Note 3) Hall Effect Current Probe See Note 1 7 Adjustable DC Power Supply (See Note 5) GND + - See Note 2 CAUTION 10 cm + - CHASSIS Unit Under Test (UUT) Ground Plane Notes: 1. measurements shall be made within 10 cm of UUT input power terminals. 2. CAUTION: Verify suitability of power supply MINUS and GROUND connections. 3. CAUTION: Verify suitability of instrumentation inputs and/or use appropriate attenuation. 4. Stimulation and Monitoring Equipment are user defined. This functional block shall provide appropriate inputs (stimulations) and monitor UUT outputs (e.g.: RPM, signals, data, etc.) Stim ulation & Monitoring Equipm ent (See Note 4) Normal Operation - Load and Current Distortion Measurement Figure LDC FIGURE LDC Normal operation - load and current distortion measurement.
11 TABLE LDC101-II. Sample data sheet for LDC101 load measurements. Parameter Measurement Unit Performance Pass/Fail Inrush Current Amps V dc N/A Load (VA) VA Total Current Distortion % Current Distortion Current Spectrum Attach Spectrum Plot Amplitude vs. Frequency 8
12 METHOD LDC102 Steady State Limits for POWER GROUP: AIRCRAFT ELECTRICAL OPERATING CONDITION: PARAMETER: 28 Volt DC Normal Steady State Limits for 1. Scope. 1.1 Purpose. This test procedure is used to verify that 28 volt DC power utilization equipment operates and maintains specified performance when provided power with voltage at that the Normal Low Steady State (NLSS) limits and the Normal High Steady State (NHSS) limits as specified in the applicable edition(s) of MIL-STD Validation criteria. The utilization equipment is considered to have passed if the utilization equipment operates and maintains performance as specified in the utilization equipment performance specification document for normal aircraft electrical conditions when supplied input power of voltage at the specified normal steady state limits of the applicable editions(s) of MIL- STD-704 and as noted in table LDC102-I. The utilization equipment must maintain specified performance for a length of time that confirms the utilization equipment can continuously operate at the steady state voltage and frequency limits and should be not less than thirty (30) minutes for each of the test conditions. The utilization equipment must demonstrate re-start at the steady state voltage limits. The utilization equipment must not suffer damage or cause an unsafe condition. Note: If the utilization has exactly the same full performance requirements for abnormal steady state limits and emergency steady state limits as required for the normal aircraft electrical conditions, then performance of test methods LDC301 and LDC401 will constitute performance of LDC102. TABLE LDC102-I. MIL-STD-704 normal limits for steady state voltage. Normal Limit NLSS NHSS 704A 704B 704C 704D 704E 704F 24 Vdc 22 Vdc 22 Vdc 22 Vdc 22 Vdc 22 Vdc 28.5 Vdc 29 Vdc 29 Vdc 29 Vdc 29 Vdc 29 Vdc 3. Apparatus. The test equipment should be as follows: a. Adjustable DC power supply b. True RMS voltmeter 9
13 4. Test setup. Configure the test setup as shown in figure LDC Measurements, except current, must be made within 10 cm of the input power terminals of the UUT. 5. Compliance test. With the power source off, install the UUT and the stimulation and monitoring equipment into the test setup of figure LDC Turn on the power source and adjust the voltage to the nominal steady state voltage of 28 VDC. Energize the UUT. Allow sufficient time for the UUT to warm up. Conduct a performance test of the UUT according to the utilization equipment performance test procedures to verify that the UUT is providing specified performance for normal aircraft electrical conditions. For each test condition A through C noted in table LDC102-II, the UUT must remain for a length of time that confirms the utilization equipment can continuously operate at the steady state voltage limits and should be not less than thirty (30) minutes. At each test condition conduct a performance test of the UUT according to the utilization equipment performance test procedures to verify that the UUT is providing specified performance for normal aircraft electrical conditions. For each test condition shutdown the UUT and verify that the UUT can be re-started. After re-start conduct a performance test of the UUT according to the utilization equipment performance test procedures to verify that the UUT is providing specified performance for normal aircraft electrical conditions. Record the voltage, frequency, time duration at test condition, successful/unsuccessful re-start and the performance of the UUT for each test condition in the data sheet shown in table LDC102-III. Repeat for each mode of operation of the UUT. After all test conditions are complete, adjust the voltage to the nominal steady state voltage of 28 VDC. Conduct a performance test of the UUT according to the utilization equipment performance test procedures to confirm that the UUT has not suffered damage and is providing specified performance for normal aircraft electrical conditions. TABLE LDC102-II. Test conditions for steady state limits of DC voltage. Test Condition A B C Nominal NLSS NHSS 10
14 True RMS Voltm eter (See Note 3) See Note 1 11 Adjustable DC Power Supply GND + - See Note 2 CAUTION Ground Plane 10 cm + - CHASSIS Unit Under Test (UUT) Notes: 1. measurements shall be made within 10 cm of UUT input power terminals. 2. CAUTION: Verify suitability of power supply MINUS and GROUND connections. 3. CAUTION: Verify suitability of instrumentation inputs and/or use appropriate attenuation. Stim ulation & Monitoring Equipm ent (See Note 4) 4. Stimulation and Monitoring Equipment are user defined. This functional block shall provide appropriate inputs (stimulations) and monitor UUT outputs (e.g.: RPM, signals, data, etc.) Normal Operation - Steady State Limits for Figure LDC FIGURE LDC Normal operation - steady state limits for voltage.
15 TABLE LDC102-III. Sample data sheet for LDC102 steady state limits for voltage. Test Parameters Performance Condition Frequency Time Duration Re-Start Pass/Fail at Condition (Yes/No) A V dc Hz min B V dc Hz min C V dc Hz min 12
16 METHOD LDC103 Distortion Spectrum POWER GROUP: AIRCRAFT ELECTRICAL OPERATING CONDITION: PARAMETER: 28 Volt DC Normal Distortion Spectrum 1. Scope. 1.1 Purpose. This test procedure is used to verify that 28 volt DC power utilization equipment operates and maintains specified performance when subjected to voltage distortion of frequencies and amplitudes as specified by the voltage distortion spectrum in the applicable editions(s) of MIL-STD Validation criteria. The utilization equipment is considered to have passed if the utilization equipment operates and maintains performance as specified in the utilization equipment performance specification document for normal aircraft electrical conditions when subjected to voltage distortions as specified by the voltage distortion spectrum in the applicable editions(s) of MIL-STD-704 and as noted in table LDC103-I. The utilization equipment must maintain specified performance for a length of time that confirms the utilization equipment can operate continuously when provided power having voltage distortion. The utilization equipment must not suffer damage or cause an unsafe condition. Note: This test method subjects the UUT to voltage distortion having frequencies components from 10 Hz to 10 khz. These voltage distortions simulate voltage distortions within aircraft due to the cumulative effects of generators, electrical distribution systems equipments, and aircraft loads. MIL-STD-461, (Requirements For The Control of Electromagnetic Interference Characteristics of Subsystems and Equipment), Test Method CS101, (Conducted Susceptibility, Power Leads, 30 Hz to 150 khz) is a complimentary test. Power levels of the voltage distortions differ for the two test methods. Performance of Test Method LDC103 of this handbook does not relinquish the requirement to perform test Method CS101 of MIL-STD-461, and performance of Method CS101 of MIL-STD-461 does not relinquish the requirement to perform Test Method LDC103 of this handbook. TABLE LDC103-I. MIL-STD-704 limits for voltage distortion spectrum. Limit 704A 704B 704C 704D 704E 704F Distortion Spectrum Figure 7 MIL-STD- 704A Figure 6 MIL-STD- 704B Figure 9 MIL-STD- 704C Figure 9 MIL-STD- 704D Figure 8 MIL-STD- 704E Figure 15 MIL-STD- 704F 13
17 3. Apparatus. The test equipment should be as follows: a. Programmable DC power supply b. Variable frequency power source c. Coupling transformer d. True RMS voltmeter e. Spectrum analyzer f. (2) Inductors, 50 µh g. Capacitor, 10 µf h. Resistor, calibrated load 4. Test setup (10 Hz and 25 Hz). Configure the test setup as shown in figure LDC103-1 voltage distortion spectrum setup for 10 Hz and 25 Hz. Measurements, except current, must be made within 10 cm of the input power terminals of the UUT. 5. Compliance test (10 Hz and 25 Hz). With the programmable DC power supply off, install the UUT and the stimulation and monitoring equipment into the test setup of figure LDC Turn on the programmable DC power supply and adjust the voltage to the nominal steady state voltage of 28 VDC. Energize the UUT. Allow sufficient time for the UUT to warm up. Conduct a performance test of the UUT according to the utilization equipment performance test procedures to verify that the UUT is providing specified performance for normal aircraft electrical conditions. For test condition A noted in table LDC103-II, set the DC programmable power supply to vary the amplitude of the DC voltage at a 10 Hz rate at an average DC voltage of 28 VDC to create a voltage distortion (ripple) for test condition A of the appropriate edition of MIL-STD-704. Remain for a length of time that confirms the utilization equipment can continuously operate with the voltage distortion and should be not less than five (5) minutes. At each test condition, conduct a performance test of the UUT according to the utilization equipment performance test procedures to verify that the UUT is providing specified performance for normal aircraft electrical conditions. For each test condition, record voltage, frequency of voltage distortion, amplitude of voltage distortion, time duration at test condition, and the performance of the UUT in the data sheet shown in table LDC103-III. Repeat for test condition B by setting the DC programmable power supply to vary the amplitude of the DC voltage at a 25 Hz rate at an average DC voltage of 28 VDC to create a voltage distortion (ripple) specified for test condition B of the appropriate edition of MIL-STD-704. Repeat for each mode of operation of the UUT. 6. Test setup (50 Hz to 10 khz). Configure the test setup as shown in figure LDC Measurements, except current, must be made within 10 cm of the input power terminals of the UUT. 6.1 Calibration (50 Hz to 10 khz). Install a calibrated resistive load in the test setup shown in figure LDC103-2 in place of the UUT. The calibrated resistive load must be sized to draw the same current as the UUT. Turn on the programmable DC power supply and adjust the voltage to the nominal steady state voltage of 28 VDC. Set the variable frequency power source to output a sine wave and adjust the frequency and amplitude so that the voltage distortion measured at the 14
18 input to the calibrated resistive load conforms to each test condition C through K as noted in table LDC103-II of the applicable editions(s) of MIL-STD-704. Record the settings of the variable frequency power source for each test condition. 7. Compliance test (50 Hz to 10 khz). With the programmable DC power supply off, install the UUT and the stimulation and monitoring equipment into the test setup of figure LDC Turn on the programmable DC power supply and adjust the voltage to the nominal steady state voltage of 28 VDC. Energize the UUT. Allow sufficient time for the UUT to warm up. Conduct a performance test of the UUT according to the utilization equipment performance test procedures to verify that the UUT is providing specified performance for normal aircraft electrical conditions. Set the variable frequency power source to the settings recorded for test condition C of the calibration procedure. For each test condition, remain for a length of time that confirms the utilization equipment can continuously operate with the voltage distortion and should be, not less than five (5) minutes. At each test condition, conduct a performance test of the UUT according to the utilization equipment performance test procedures to verify that the UUT is providing specified performance for normal aircraft electrical conditions. After each test condition, monitor the voltage distortion frequency and amplitude while slowly increasing the variable frequency power source frequency and adjusting the amplitude until the next test condition is reached. Do not exceed the voltage distortion spectrum limits. Repeat for each test condition C through K noted in table LDC103-II. For each test condition, record voltage, frequency of voltage distortion, amplitude of voltage distortion, time duration at test condition, and the performance of the UUT in the data sheet shown in table LDC103-III. Repeat for each mode of operation of the UUT. After all test conditions are complete, turn the programmable DC power supply off and remove the coupling transformer from the circuit. Turn on the programmable DC power supply. Adjust the voltage to the nominal steady state voltage of 28 VDC. Conduct a performance test of the UUT according to the utilization equipment performance test procedures to confirm that the UUT has not suffered damage and is providing specified performance for normal aircraft electrical conditions. 15
19 Test Condition TABLE LDC103-II. Test conditions for voltage distortion spectrum. Frequency of Distortion MIL-STD-704A Amplitude of Distortion rms MIL-STD-704B, C, & D Amplitude of Distortion rms MIL-STD-704E & F Amplitude of Distortion rms A 10 Hz Vrms Vrms Vrms B 25 Hz Vrms Vrms Vrms C 50 Hz Vrms Vrms Vrms D 60 Hz Vrms Vrms Vrms E 250 Hz Vrms Vrms Vrms F 1 khz Vrms Vrms Vrms G 1.7 khz Vrms Vrms Vrms H 2 khz Vrms Vrms Vrms I 5 khz Vrms Vrms Vrms J 6.5 khz Vrms Vrms Vrms K 10 khz Vrms Vrms Vrms 16
20 Spectrum Analyzer (See Note 3) True RMS Voltmeter (See Note 3) See Note 1 17 Programm able DC Power Supply GND + - See Note 2 CAUTION 10 cm + - CHASSIS Unit Under Test (UUT) Ground Plane Notes: 1. measurements shall be made within 10 cm of UUT input power terminals. 2. CAUTION: Verify suitability of power supply MINUS and GROUND connections. 3. CAUTION: Verify suitability of instrumentation inputs and/or use appropriate attenuation. Stimulation & Monitoring Equipment (See Note 4) 4. Stimulation and Monitoring Equipment are user defined. This functional block shall provide appropriate inputs (stimulations) and monitor UUT outputs (e.g.: RPM, signals, data, etc.) Normal Operation - Distortion Spectrum (10 Hz and 25 Hz) Figure LDC FIGURE LDC Normal operation - voltage distortion spectrum (10 Hz and 25 Hz).
21 Variable Frequency Power Source Spectrum Analyzer (See Note 3) True RMS Voltm eter (See Note 3) 18 Programmable DC Power Supply GND Notes: H 50 H Coupling XMFR 10 F See Note 2 CAUTION See Note 5 Ground Plane See Note 1 10 cm Calibrated Resistive Load + or Unit Under Test - (UUT) CHASSIS 1. measurements shall be made within 10 cm of UUT input power terminals. 2. CAUTION: Verify suitability of power supply MINUS and GROUND connections. 3. CAUTION: Verify suitability of instrumentation inputs and/or use appropriate attenuation. 4. Stimulation and Monitoring Equipment are user defined. This functional block shall provide appropriate inputs (stimulations) and monitor UUT outputs (e.g.: RPM, signals, data, etc.) Stim ulation & Monitoring Equipment (See Note 4) 5. CAUTION: Verify suitability of variable frequency power source and coupling transformer for distortion spectrum testing. Normal Operation - Distortion Spectrum (50 Hz to 50 khz) Figure LDC FIGURE LDC Normal operation - voltage distortion spectrum (50 Hz and 10 khz).
22 19 TABLE LDC103-III. Sample data sheet for LDC103 voltage distortion spectrum. Test Parameters Performance Condition Frequency of Amplitude of Time Duration Pass/Fail Distortion Distortion at Condition A V DC Hz V rms min B V DC Hz V rms min C V DC Hz V rms min D V DC Hz V rms min E V DC Hz V rms min F V DC khz V rms min G V DC khz V rms min H V DC khz V rms min I V DC khz V rms min J V DC khz V rms min K V DC khz V rms min
23 METHOD LDC104 Total Ripple POWER GROUP: AIRCRAFT ELECTRICAL OPERATING CONDITION: PARAMETER: LDC104 Normal Total Ripple 1. Scope. 1.1 Purpose. This test procedure is used to verify that 28 volt DC power utilization equipment operates and maintains specified performance when subjected to voltage having a ripple as specified by the applicable editions(s) of MIL-STD Validation criteria. The utilization equipment is considered to have passed if the utilization equipment operates and maintains performance as specified in the utilization equipment performance specification document for normal aircraft electrical conditions when subjected to ripple as specified by the applicable editions(s) of MIL-STD-704 and as noted in table LDC104- I. The utilization equipment must maintain specified performance for a length of time that confirms the utilization equipment can operate continuously when subjected to a distorted voltage waveform and should be not less than thirty (30) minutes. The utilization equipment must not suffer damage or cause an unsafe condition. TABLE LDC104-I. MIL-STD-704 limits for ripple DC voltage distortion. Limit 704A 704B 704C 704D 704E 704F Ripple 2 Volts Peak to Mean And Figure 7 MIL-STD- 704A 1.5 Volts Peak to Average And Figure 6 MIL-STD- 704B 1.5 Volts Peak to Average And Figure 9 MIL-STD- 704C 1.5 Volts Peak to Average And Figure 9 MIL-STD- 704D 1.5 Volts Peak to Average And Figure 8 MIL-STD- 704E 1.5 Volts Peak to Average And Figure 15 MIL-STD- 704F 3. Apparatus. The test equipment should be as follows: a. Programmable DC power supply b. True RMS voltmeter c. Spectrum analyzer d. Distortion meter 4. Test setup. Configure the test setup as shown in figure LDC Measurements, except current, must be made within 10 cm of the input power terminals of the UUT. 20
24 4.1 Calibration. Install a resistive load in the test setup shown in figure LDC104-1 in place of the UUT. The resistive load must be sized to draw the same current as the UUT. Set the programmable power supply to produce a DC voltage waveform having ripple as noted for test condition A in table LDC104-II for the applicable editions(s) of MIL-STD-704. The ripple should include all the frequencies components with amplitudes noted for test condition A. Turn on the programmable DC power supply and adjust the voltage to the nominal steady state voltage of 28 VDC. Confirm that the programmable power supply is producing a voltage waveform having ripple content listed in table LDC104-II. Record the settings of the programmable power supply. Repeat the process for test condition B in table LDC104-II. 5. Compliance test. With the programmable DC power supply off, install the UUT and the stimulation and monitoring equipment into the test setup of figure LDC Set the programmable power supply to the settings recorded during the calibration procedure for condition A. Turn on the programmable DC power supply and adjust the voltage to the nominal steady state voltage of 28 VDC. Energize the UUT. Measure the ripple frequencies spectrum and record the DC ripple frequency components and amplitudes. Allow sufficient time for the UUT to warm up. Conduct a performance test of the UUT according to the utilization equipment performance test procedures to verify that the UUT is providing specified performance for normal aircraft electrical conditions. Remain for a length of time that confirms the utilization equipment can continuously operate with the ripple voltage, and should be not less than thirty (30) minutes. Repeat for test condition B noted in table LDC104-II. For each test condition, record the voltage, distortion factor, frequency spectrum of ripple, time duration at test condition, and the performance of the UUT in the data sheet shown in table LDC104-III. Repeat for each mode of operation of the UUT. After all test conditions are complete, set the programmable power supply to produce a DC waveform without ripple. Adjust the voltage to the nominal steady state voltage of 28 VDC. Conduct a performance test of the UUT according to the utilization equipment performance test procedures to confirm that the UUT has not suffered damage and is providing specified performance for normal aircraft electrical conditions. 21
25 TABLE LDC104-II. Ripple frequency and amplitude. Test Condition A B Ripple Frequency Components MIL-STD-704A Amplitude of Ripple Component Vrms MIL-STD-704B, C, D, E, & F Vrms 1200 Hz 1.00 Vrms 0.80 Vrms 2400 Hz 0.20 Vrms 0.16 Vrms 3600 Hz 0.33 Vrms 0.26 Vrms 4800 Hz 0.10 Vrms 0.08 Vrms 6000 Hz 0.16 Vrms 0.13 Vrms 7200 Hz 0.05 Vrms 0.04 Vrms 8400 Hz 0.08 Vrms 0.06 Vrms 2400 Hz 0.80 Vrms 0.80 Vrms 4800 Hz 0.16 Vrms 0.16 Vrms 7200 Hz 0.26 Vrms 0.26 Vrms 9600 Hz 0.08 Vrms 0.08 Vrms Hz 0.13 Vrms 0.13 Vrms Hz 0.04 Vrms 0.04 Vrms Hz 0.06 Vrms 0.06 Vrms 22
26 Spectrum Analyzer (See Note 3) True RMS Voltm eter (See Note 3) Distortion Meter (See Note 3) See Note 1 23 Program m able DC Power Supply GND + - See Note 2 CAUTION 10 cm + - CHASSIS Unit Under Test (UUT) Ground Plane Notes: 1. measurements shall be made within 10 cm of UUT input power terminals. 2. CAUTION: Verify suitability of power supply MINUS and GROUND connections. 3. CAUTION: Verify suitability of instrumentation inputs and/or use appropriate attenuation. 4. Stimulation and Monitoring Equipment are user defined. This functional block shall provide appropriate inputs (stimulations) and monitor UUT outputs (e.g.: RPM, signals, data, etc.) Stim ulation & Monitoring Equipm ent (See Note 4) Normal Operation - Total Ripple Figure LDC FIGURE LDC Normal operation - total ripple.
27 TABLE LDC104-III. Sample data sheet for LDC104 total ripple. 24 Test Parameters Condition Distortion Factor Vdc No Units Ripple Frequency Amplitude of Component Ripple Hz Vrms A Hz Vrms Hz Vrms Hz Vrms Hz Vrms Hz Vrms Hz Vrms Distortion Factor Vdc No Units Ripple Frequency Amplitude of Component Ripple B Hz Vrms Hz Vrms Hz Vrms Hz Vrms Hz Vrms Hz Vrms Hz Vrms Time Duration at Condition min Time Duration at Condition min Performance Pass/Fail Pass/Fail
28 METHOD LDC105 Normal Transients POWER GROUP: AIRCRAFT ELECTRICAL OPERATING CONDITION: PARAMETER: 28 Volt DC Normal Normal Transients 1. Scope. 1.1 Purpose. This test procedure is used to verify that 28 volt DC power utilization equipment operates and maintains specified performance when subjected to normal voltage transients as specified in the applicable editions(s) of MIL-STD Validation criteria. The utilization equipment is considered to have passed if the utilization equipment operates and maintains performance as specified in the utilization equipment performance specification document for normal aircraft electrical conditions when subjected to voltage transients within the normal limits of the applicable editions(s) of MIL-STD-704 and as noted in table LDC105-I. The utilization equipment must maintain specified performance during and after the voltage transients. The utilization equipment must not suffer damage or cause an unsafe condition. TABLE LDC105-I. MIL-STD-704 limits for normal voltage transients. Limit 704A 704B 704C 704D 704E 704F Normal Transients Figure 9 MIL-STD- 704A Locus of Equivalent Step Function Curves 2 and 3 Figure 7 MIL-STD- 704B Figure 10 MIL-STD- 704C Figure 10 MIL-STD- 704D Figure 9 MIL-STD- 704E Figure 13 MIL-STD- 704F 3. Apparatus. The test equipment should be as follows: a. Programmable DC power supply b. True RMS voltmeter c. Oscilloscope 4. Test setup. Configure the test setup as shown in figure LDC Measurements, except current, must be made within 10 cm of the input power terminals of the UUT. 5. Compliance test. With the power source off, install the UUT and the stimulation and monitoring equipment into the test setup of figure LDC Turn on the power source and 25
29 adjust the voltage to the nominal steady state voltage of 28 VDC. Energize the UUT. Allow sufficient time for the UUT to warm up. Conduct a performance test of the UUT according to the utilization equipment performance test procedures to verify that the UUT is providing specified performance for normal aircraft electrical conditions. 5.1 Compliance test for MIL-STD-704A. The UUT must be subjected to the voltage transients for each test condition A through V noted in table LDC105-II. The voltage must increase or decrease from steady state voltage as noted in table LDC105-II to the voltage transient level within 1 milliseconds. The voltage must remain at the voltage transient level for the duration noted in table LDC105-II. The voltage must return to steady state over the time duration noted in table LDC105-II. For test condition E and J, three over-voltage transients of 70 Vdc for 12 milliseconds are performed, separated by 0.5 second. For test condition O and T, three under-voltage transients of 8 Vdc for 12 milliseconds are performed, separated by 0.5 second. For test condition U and V, an under-voltage transient of 8 Vdc for 10 milliseconds is immediately followed by an over-voltage transient of 70 Vdc for 15 milliseconds and the voltage returns to steady state over the time duration noted. For each test condition, monitor the performance of the UUT during the voltage transient according to the equipment performance test procedures to verify that the UUT is providing specified performance for normal aircraft electrical conditions. Repeat each test condition 5 times. After the power returns to normal steady state limits, conduct a performance test of the UUT according to the utilization equipment performance test procedures to verify that the UUT is providing specified performance for normal aircraft electrical conditions. Record the steady state voltage, voltage transient (oscilloscope trace), and the performance of the UUT for each test condition in the data sheet shown in table LDC105-IV. Repeat for each mode of operation of the UUT. In addition, for MIL-STD-704A test compliance perform the repetitive voltage transient test described below. 5.2 Compliance test for MIL-STD-704B, C, D, E, & F. The UUT must be subjected to the voltage transients for each test condition AA through RR noted in table LDC105-III. The voltage must increase or decrease from steady state voltage as noted in table LDC105-III to the voltage transient level within 1 milliseconds. The voltage must remain at the voltage transient level for the duration noted in table LDC105-III. The voltage must return to steady state over the time duration noted in table LDC105-III. For test condition EE and JJ, three over-voltage transients of 50 Vdc for 10 milliseconds are performed, separated by 0.5 second. For test condition MM and PP, three under-voltage transients of 18 Vdc for 10 milliseconds are performed, separated by 0.5 second. For test condition QQ and RR, an under-voltage transient of 18 Vdc for 10 milliseconds is immediately followed by an overvoltage transient of 50 Vdc for 12.5 milliseconds and the voltage returns to steady state over the time duration noted. For each test condition, monitor the performance of the UUT during the voltage transient according to the equipment performance test procedures to verify that the UUT is providing specified performance for normal aircraft electrical conditions. Repeat each test condition 5 times. After the power returns to normal steady state limits, conduct a performance test of the UUT according to the utilization equipment performance test procedures to verify that the UUT is providing specified performance for normal aircraft electrical conditions. Record the steady state voltage, voltage transient (oscilloscope trace), and the performance of the UUT for each test condition in the data sheet shown in table LDC105-V. Repeat for each mode of operation of the UUT. In 26
30 addition, for MIL-STD-704B, C, D, E, & F test compliance perform the repetitive voltage transient test described below. 5.3 Repetitive normal voltage transients test. Program the power supply to provide a continually repeating voltage transient that decreases from 28.5 Vdc to 18 Vdc in 2.5 msec, then increases to 45 Vdc over 30 msec, then decreases to 28.5 Vdc over 2.5 msec. The voltage transient is repeated every 0.5 second, see figure LDC The UUT must be subjected to the repetitive voltage transient for a length of time that confirms the utilization equipment can continuously operate and should be not less than thirty (30) minutes. Conduct a performance test of the UUT according to the utilization equipment performance test procedures to verify that the UUT is providing specified performance for normal aircraft electrical conditions. Record the voltage, voltage transient (oscilloscope trace), time duration at test condition, and the performance of the UUT in the data sheet shown in table LDC105-V. Repeat for each mode of operation of the UUT. After all test conditions are complete, adjust the voltage to the nominal steady state voltage of 28 Vdc. Conduct a performance test of the UUT according to the utilization equipment performance test procedures to confirm that the UUT has not suffered damage and is providing specified performance for normal aircraft electrical conditions. 27
31 TABLE LDC105-II. Test conditions for MIL-STD-704A normal voltage transients. Test Condition Steady State Vdc Time From Steady State to Transient Level milliseconds Transient Level Vdc Duration at Transient Level milliseconds Time From Transient Level to Steady State milliseconds Overvoltage Transients A 28.5 Vdc < 1 msec 70 Vdc 20 msec < 1 msec B 28.5 Vdc < 1 msec 70 Vdc 15 msec 9 msec C 28.5 Vdc < 1 msec 50 Vdc 75 msec < 1 msec D 28.5 Vdc < 1 msec 50 Vdc 55 msec 40 msec E 28.5 Vdc < 1 msec 70 Vdc 12 msec < 1 msec (3 times) Every 0.5 sec F 24 Vdc < 1 msec 70 Vdc 20 msec < 1 msec G 24 Vdc < 1 msec 70 Vdc 15 msec 10 msec H 24 Vdc < 1 msec 50 Vdc 75 msec < 1 msec I 24 Vdc < 1 msec 50 Vdc 55 msec 48 msec J 24 Vdc < 1 msec 70 Vdc (3 times) 12 msec Every 0.5 sec < 1 msec Undervoltage Transients K 28.5 Vdc < 1 msec 8 Vdc 50 msec < 1 msec L 28.5 Vdc < 1 msec 8 Vdc 38 msec 23 msec M 28.5 Vdc < 1 msec 14 Vdc 170 msec < 1 msec N 28.5 Vdc < 1 msec 14 Vdc 128 msec 83 msec O 28.5 Vdc < 1 msec 8 Vdc 12 msec < 1 msec (3 times) Every 0.5 P 24 Vdc < 1 msec 8 Vdc 50 msec < 1 msec Q 24 Vdc < 1 msec 8 Vdc 38 msec 18 msec R 24 Vdc < 1 msec 14 Vdc 170 msec < 1 msec S 24 Vdc < 1 msec 14 Vdc 128 msec 57 msec T Combined Transient U V 24 Vdc 28.5 Vdc then 24 Vdc then < 1 msec 8 Vdc (3 times) < 1 msec < 1 msec < 1 msec < 1 msec 8 Vdc 70 Vdc 8 Vdc 70 Vdc 12 msec Every msec 15 msec 10 msec 15 msec < 1 msec < 1 msec 9 msec < 1 msec 10 msec 28
32 TABLE LDC105-III. Test conditions for MIL-STD-704B, C, D, E and F normal voltage transients. Test Condition Steady State Vdc Time From Steady State to Transient Level milliseconds Transient Level Vdc Duration at Transient Level milliseconds Time From Transient Level to Steady State milliseconds Overvoltage Transients AA 29 Vdc < 1 msec 50 Vdc 12.5 msec < 1 msec BB 29 Vdc < 1 msec 50 Vdc 12.5 msec 70 msec CC 29 Vdc < 1 msec 40 Vdc 45 msec < 1 msec DD 29 Vdc < 1 msec 40 Vdc 45 msec 37.5 msec EE 29 Vdc < 1 msec 50 Vdc (3 times) 10 msec Every 0.5 msec < 1 msec FF 22 Vdc < 1 msec 50 Vdc 12.5 msec < 1 msec GG 22 Vdc < 1 msec 50 Vdc 12.5 msec 95 msec HH 22 Vdc < 1 msec 40 Vdc 45 msec < 1 msec II 22 Vdc < 1 msec 40 Vdc 45 msec 62.5 msec JJ 22 Vdc < 1 msec 50 Vdc (3 times) 10 msec Every 0.5 msec < 1 msec Undervoltage Transients KK 29 Vdc < 1 msec 18 Vdc 15 msec < 1 msec LL 29 Vdc < 1 msec 18 Vdc 15 msec 234 msec MM 29 Vdc < 1 msec 18 Vdc 10 msec < 1 msec (3 times) Every 0.5 sec NN 22 Vdc < 1 msec 18 Vdc 15 msec < 1 msec OO 22 Vdc < 1 msec 18 Vdc 15 msec 85 msec PP Combined Transient QQ RR 22 Vdc 29 Vdc then 22 Vdc then < 1 msec 18 Vdc (3 times) < 1 msec < 1 msec < 1 msec < 1 msec 18 Vdc 50Vdc 18 Vdc 50Vdc 10 msec Every 0.5 sec 10 msec 12.5 msec 10 msec 12.5 msec < 1 msec < 1 msec 70 msec < 1 msec 62.5 msec 29
33 O scilloscope (See Note 3) True RMS Voltm eter (See Note 3) See Note 1 30 Program m able DC Power Supply GND + - See Note 2 CAUTION 10 cm + - CHASSIS Unit Under Test (UUT) Ground Plane Notes: 1. measurements shall be made within 10 cm of UUT input power terminals. 2. CAUTION: Verify suitability of power supply MINUS and GROUND connections. 3. CAUTION: Verify suitability of instrumentation inputs and/or use appropriate attenuation. 4. Stimulation and Monitoring Equipment are user defined. This functional block shall provide appropriate inputs (stimulations) and monitor UUT outputs (e.g.: RPM, signals, data, etc.) Stim ulation & M onitoring Equipm ent (See Note 4) Normal Operation - Normal Transients Figure LDC FIGURE LDC Normal operation - normal voltage transients.
34 Repetition Rate (f) for transient pulse is twice per second Repetitive Normal Transient Test Pulse Detail Vdc Volts RMS Vdc Time, seconds Repetitive Norm al Transient Pulse Detail Volts, RMS Repetive Normal Transient Figure LDC105-2 Time, seconds FIGURE LDC Repetitive normal voltage transient.
35 TABLE LDC105-IV. Sample data sheet for LDC105 normal voltage transients for MIL-STD-704A. 32 Test Parameters Condition Steady State Transient Time at Oscilloscope Trace Transient Level A V DC V DC msec Attach Trace V DC vs Time B V DC V DC msec Attach Trace V DC vs Time C V DC V DC msec Attach Trace V DC vs Time D V DC V DC msec Attach Trace V DC vs Time E V DC V DC msec Attach Trace V DC vs Time F V DC V DC msec Attach Trace V DC vs Time G V DC V DC msec Attach Trace V DC vs Time H V DC V DC msec Attach Trace V DC vs Time I V DC V DC msec Attach Trace V DC vs Time J V DC V DC msec Attach Trace V DC vs Time K V DC V DC msec Attach Trace V DC vs Time L V DC V DC msec Attach Trace V DC vs Time M V DC V DC msec Attach Trace V DC vs Time N V DC V DC msec Attach Trace V DC vs Time O V DC V DC msec Attach Trace V DC vs Time P V DC V DC msec Attach Trace V DC vs Time Q V DC V DC msec Attach Trace V DC vs Time R V DC V DC msec Attach Trace V DC vs Time S V DC V DC msec Attach Trace V DC vs Time T V DC V DC msec Attach Trace V DC vs Time U V DC V DC msec Attach Trace V DC vs Time V V DC V DC V DC msec Attach Trace V DC vs Time V DC Performance Pass/Fail
36 TABLE LDC105-IV. Sample data sheet for LDC105 normal voltage transients for MIL-STD-704A. - Continued Test Condition Repetitive Transient Parameters Steady State Transient Time at Oscilloscope Trace Transient Level V DC V DC msec Attach Trace V DC vs Time V DC msec Time Duration At Test Condition min Performance Pass/Fail 33
37 TABLE LDC105-V. Sample data sheet for LDC105 normal voltage transients for MIL-STD-704B, C, D, E, & F. 34 Test Parameters Condition Steady State Transient Time at Oscilloscope Trace Transient Level AA V DC V DC msec Attach Trace V DC vs Time BB V DC V DC msec Attach Trace V DC vs Time CC V DC V DC msec Attach Trace V DC vs Time DD V DC V DC msec Attach Trace V DC vs Time EE V DC V DC msec Attach Trace V DC vs Time FF V DC V DC msec Attach Trace V DC vs Time GG V DC V DC msec Attach Trace V DC vs Time HH V DC V DC msec Attach Trace V DC vs Time II V DC V DC msec Attach Trace V DC vs Time JJ V DC V DC msec Attach Trace V DC vs Time KK V DC V DC msec Attach Trace V DC vs Time LL V DC V DC msec Attach Trace V DC vs Time MM V DC V DC msec Attach Trace V DC vs Time NN V DC V DC msec Attach Trace V DC vs Time OO V DC V DC msec PP V DC V DC msec Attach Trace V DC vs Time QQ V DC msec V DC V DC msec Attach Trace V DC vs Time RR V DC V DC msec Attach Trace msec V DC vs Time V DC Performance Pass/Fail
38 TABLE LDC105-V. Sample data sheet for LDC105 normal voltage transients for MIL-STD-704B, C, D, E, & F. - Continued Test Condition Repetitive Transient Parameters Steady State Transient Time at Oscilloscope Trace Transient Level V DC V DC msec Attach Trace V DC vs Time V DC msec Time Duration At Test Condition min Performance Pass/Fail 35
39 METHOD LDC201 Power Interrupt POWER GROUP: AIRCRAFT ELECTRICAL OPERATING CONDITION: PARAMETER: 28 Volt DC Transfer Interrupt Power Interrupt 1. Scope. 1.1 Purpose. This test procedure is used to verify that 28 volt DC power utilization equipment operates and maintains specified performance when subjected to power interrupts as specified in the applicable editions(s) of MIL-STD Validation criteria. The utilization equipment is considered to have passed if the utilization equipment operates and maintains performance as specified in the utilization equipment performance specification document for transfer aircraft electrical conditions when subjected to power interrupts as specified by the applicable editions(s) of MIL-STD-704 and as noted in table LDC201-I. The utilization equipment must maintain the specified performance during power interrupts. Unless otherwise specified in the utilization equipment performance specification document, the utilization equipment must automatically return to the performance specified for normal aircraft electrical conditions when the power returns to within normal limits. The utilization equipment must not suffer damage or cause an unsafe condition. TABLE LDC201-I. MIL-STD-704 power transfer limits. Limit 704A 704B 704C 704D 704E 704F Power 50 msec 50 msec 50 msec 50 msec 50 msec 50 msec Interrupt 24 Vdc 22 Vdc 22 Vdc 22 Vdc 22 Vdc 22 Vdc NLSS NHSS 28.5 Vdc 29 Vdc 29 Vdc 29 Vdc 29 Vdc 29 Vdc 3. Apparatus. The test equipment should be as follows: a. Programmable DC power supply b. True RMS voltmeter c. Oscilloscope d. Resistive dummy load 4. Test setup. Configure the test setup as shown in figure LDC The dummy resistive load placed in parallel to the UUT should be sized to draw three times the steady state current of the UUT up to a maximum 25 kw dummy load. Note: This is done to ensure that the UUT test does 36
40 not lose stored energy to other aircraft loads during power interrupts. Measurements, except current, must be made within 10 cm of the input power terminals of the UUT. 5. Compliance test. With the power source off, install the UUT and the stimulation and monitoring equipment into the test setup of figure LDC Turn on the power source and adjust the voltage to the nominal steady state voltage of 28 VDC. Energize the UUT. Allow sufficient time for the UUT to warm up. Conduct a performance test of the UUT according to the utilization equipment performance test procedures to verify that the UUT is providing specified performance for normal aircraft electrical conditions. For each test condition A through K noted in table LDC201-II, adjust the voltage to the steady state voltage listed. Perform a power interrupt (0 V) of the duration listed. The voltage must decrease from the steady state voltage to 0 Volts within 0.25 milliseconds, remain at 0 Volts for the duration listed for the test condition, and return form 0 Volts to the steady state voltage within 0.25 milliseconds. For test condition J, three 50 millisecond power interrupts are performed, separated by 0.5 seconds. For test condition K a normal overvoltage transient follows the power interrupt. The normal voltage transient is 50 Vdc for 12.5 milliseconds and returns to nominal voltage over the next 70 milliseconds. For test condition L a normal undervoltage transient follows the power interrupt. The normal voltage transient is 18 Vdc for 15 milliseconds and returns to nominal voltage over the next 85 milliseconds. For each test condition, monitor the performance of the UUT according to the utilization equipment performance test procedures for power transfer operation to verify that the UUT is providing specified performance for transfer aircraft electrical conditions. After the power returns to normal limits, conduct a performance test of the UUT according to the utilization equipment performance test procedures to verify that the UUT is providing specified performance for normal aircraft electrical conditions. Record the steady state voltage, time duration of power interrupt, and the performance of the UUT for each test condition in the data sheet shown in table LDC201-III. Repeat each test condition 5 times. Repeat for each mode of operation of the UUT. After all test conditions are complete, adjust the voltage to the nominal steady state voltage of 28 VDC. Conduct a performance test of the UUT according to the utilization equipment performance test procedures to confirm that the UUT has not suffered damage and is providing specified performance for normal aircraft electrical conditions. 37
41 TABLE LDC201-II. Test conditions for transfer interrupt. Test Condition Steady State Duration of Interrupt A Nominal 50 msec B NLSS 50 msec C NHSS 50 msec D Nominal 30 msec E NLSS 30 msec F NHSS 30 msec G Nominal 10 msec H NLSS 10 msec I NHSS 10 msec J Nominal 50 msec (repeated 3 times, separated by 0.5 sec ) K Nominal 50 msec (followed by a normal voltage transient of 50 Vdc for 12.5 msec and return to steady state voltage in 70 msec) L Nominal 50 msec (followed by a normal voltage transient of 18 Vdc for 15 msec and return to steady state voltage in 85 msec) 38
42 Oscilloscope (See Note 3) True RMS Voltm eter (See Note 3) See Note 1 39 Program m able DC Power Supply GND + - See Note 2 CAUTION See Test Procedure for details Dummy Resistive Load 10 cm + - CHASSIS Unit Under Test (UUT) Ground Plane Notes: 1. measurements shall be made within 10 cm of UUT input power terminals. 2. CAUTION: Verify suitability of power supply MINUS and GROUND connections. 3. CAUTION: Verify suitability of instrumentation inputs and/or use appropriate attenuation. 4. Stimulation and Monitoring Equipment are user defined. This functional block shall provide appropriate inputs (stimulations) and monitor UUT outputs (e.g.: RPM, signals, data, etc.) FIGURE LDC Transfer interrupt - power interrupt. Stim ulation & Monitoring Equipm ent (See Note 4) Transfer Interrupt - Power Interrupt Figure LDC 201-1
43 TABLE LDC201-III. Sample data sheet for LDC201 power interrupt. 40 Test Parameters Performance Condition Steady State Time Duration Pass/Fail of Power Interrupt A V DC msec B V DC msec C V DC msec D V DC msec E V DC msec F V DC msec G V DC msec H V DC msec I V DC msec J V DC msec V DC msec Overvoltage Transient K Transient Transient V DC msec V DC msec Overvoltage Transient L Transient Transient msec V DC
44 METHOD LDC301 Steady State Limits for POWER GROUP: AIRCRAFT ELECTRICAL OPERATING CONDITION: PARAMETER: 28 Volt DC Abnormal Steady State Limits for 1. Scope. 1.1 Purpose. This test procedure is used to verify that 28 volt DC power utilization equipment operates and maintains specified performance when provided power with voltage at that the Abnormal Low Steady State (ALSS) limits and the Abnormal High Steady State (AHSS) limits as specified in the applicable editions(s) of MIL-STD Validation criteria. The utilization equipment is considered to have passed if the utilization equipment operates and maintains performance as specified in the utilization equipment performance specification document for abnormal aircraft electrical conditions when supplied input power of voltage at the specified abnormal steady state limits of the applicable editions(s) of MIL-STD-704 and as noted in table LDC301-I. The utilization equipment must maintain specified performance for a length of time that confirms the utilization equipment can continuously operate at the steady state voltage and should be not less than thirty (30) minutes for each of the test conditions. Unless otherwise specified in the utilization equipment performance specification document, the utilization equipment must demonstrate re-start at the abnormal steady state voltage limits. Unless otherwise specified in the utilization equipment performance specification document, the utilization must automatically return to the performance specified for normal aircraft electrical conditions when the power returns to within normal limits. The utilization equipment must not suffer damage or cause an unsafe condition. TABLE LDC301-I. MIL-STD-704 abnormal limits for steady state voltage. Abnormal Limit NLSS NHSS 704A 704B 704C 704D 704E 704F 22.5 Vdc 20.0 Vdc 20.0 Vdc 20.0 Vdc 20.0 Vdc 20.0 Vdc 30.0 Vdc 31.5 Vdc 31.5 Vdc 31.5 Vdc 31.5 Vdc 31.5 Vdc 3. Apparatus. The test equipment should be as follows: a. Adjustable DC power supply b. True RMS voltmeter 4. Test setup. Configure the test setup as shown in figure LDC Measurements, except current, must be made within 10 cm of the input power terminals of the UUT. 41
45 5. Compliance test. With the power source off, install the UUT and the stimulation and monitoring equipment into the test setup of figure LDC Turn on the power source and adjust the voltage to the nominal steady state voltage of 28 VDC. Energize the UUT. Allow sufficient time for the UUT to warm up. Conduct a performance test of the UUT according to the utilization equipment performance test procedures to verify that the UUT is providing specified performance for normal aircraft electrical conditions. For each test condition A and B noted in table LDC301-II, the UUT must remain for a length of time that confirms the utilization equipment can perform as specified at the abnormal steady state voltage limits and should be not less than thirty (30) minutes. At each test condition conduct a performance test of the UUT according to the utilization equipment performance test procedures to verify that the UUT is providing specified performance for abnormal aircraft electrical conditions. For each test condition shutdown the UUT and verify that the UUT can be re-started. After re-start conduct a performance test of the UUT according to the utilization equipment performance test procedures to verify that the UUT is providing specified performance for abnormal aircraft electrical conditions. Adjust the voltage to the nominal steady state voltage of 28 VDC. Conduct a performance test of the UUT according to the utilization equipment performance test procedures to confirm that the UUT has automatically returned to the performance specified for normal aircraft electrical conditions, and has not suffered damage. Record the voltage, time duration at test condition, successful/unsuccessful re-start and the performance of the UUT for each test condition in the data sheet shown in table LDC301-III. Repeat for each mode of operation of the UUT. TABLE LDC301-II. Test conditions for abnormal steady state limits of DC voltage. Test Condition A B ALSS AHSS 42
46 True RMS Voltm eter (See Note 3) See Note 1 43 Adjustable DC Power Supply GND + - See Note 2 CAUTION 10 cm + - CHASSIS Unit Under Test (UUT) Ground Plane Notes: 1. measurements shall be made within 10 cm of UUT input power terminals. 2. CAUTION: Verify suitability of power supply MINUS and GROUND connections. 3. CAUTION: Verify suitability of instrumentation inputs and/or use appropriate attenuation. 4. Stimulation and Monitoring Equipment are user defined. This functional block shall provide appropriate inputs (stimulations) and monitor UUT outputs (e.g.: RPM, signals, data, etc.) Stim ulation & Monitoring Equipm ent (See Note 4) Abnormal Operation - Steady State Limits for Figure LDC FIGURE LDC Abnormal operation - steady state limits for voltage.
47 TABLE LDC301-III. Sample data sheet for LDC301 abnormal steady state limits for voltage. Test Parameters Condition Time Duration at Test Condition A V DC min B V DC min Re-Start (Yes/No) Performance Pass/Fail 44
48 METHOD LDC302 Abnormal Transients POWER GROUP: AIRCRAFT ELECTRICAL OPERATING CONDITION: PARAMETER: 28 Volt DC Abnormal Abnormal Transients 1. Scope. 1.1 Purpose. This test procedure is used to verify that 28 volt DC power utilization equipment operates and maintains specified performance when subjected to abnormal voltage transients as specified in the applicable editions(s) of MIL-STD Validation criteria. The utilization equipment is considered to have passed if the utilization equipment operates and maintains performance as specified in the utilization equipment performance specification document for abnormal aircraft electrical conditions when subjected to voltage transients within the abnormal limits of the applicable editions(s) of MIL-STD-704 and as noted in table LDC302-I. Unless otherwise specified in the utilization equipment performance specification document, the utilization equipment must automatically return to the performance specified for normal aircraft electrical conditions when the power returns to within normal limits. The utilization equipment must not suffer damage or cause an unsafe condition. TABLE LDC302-I. MIL-STD-704 limits for abnormal voltage transients. Limit 704A 704B 704C 704D 704E 704F Abnormal Transients Figure 9 MIL-STD- 704A Locus of Equivalent Step Function Curves 1 and 4 Figure 8 MIL-STD- 704B Figure 12 MIL-STD- 704C Figure 12 MIL-STD- 704D Figure 11 MIL-STD- 704E Figure 14 MIL-STD- 704F 3. Apparatus. The test equipment should be as follows: a. Programmable DC power supply b. True RMS voltmeter c. Oscilloscope 4. Test setup. Configure the test setup as shown in figure LDC Measurements, except current, must be made within 10 cm of the input power terminals of the UUT. 45
49 5. Compliance test. With the power source off, install the UUT and the stimulation and monitoring equipment into the test setup of figure LDC Turn on the power source and adjust the voltage to the nominal steady state voltage of 28 VDC. Energize the UUT. Allow sufficient time for the UUT to warm up. Conduct a performance test of the UUT according to the utilization equipment performance test procedures to verify that the UUT is providing specified performance for normal aircraft electrical conditions. 5.1 Compliance test for MIL-STD-704A. The UUT must be subjected to the voltage transients for each test condition A through V noted in table LDC302-II. The voltage must increase or decrease from steady state voltage as noted in table LDC302-II to the voltage transient level within 1 milliseconds. The voltage must remain at the voltage transient level for the duration noted in table LDC302-II. The voltage must return to steady state over the time duration noted in table LDC302-II. For test condition E and J, three over-voltage transients of 80 Vdc for 12 milliseconds are performed, separated by 0.5 second. For test condition O and T, three under-voltage transients of 6 Vdc for 12 milliseconds are performed, separated by 0.5 second. For test condition U and V, an under-voltage transient of 6 Vdc for 10 milliseconds is immediately followed by an overvoltage transient of 80 Vdc for 50 milliseconds and the voltage returns to steady state over the time duration noted. For each test condition, monitor the performance of the UUT during the voltage transient according to the equipment performance test procedures to verify that the UUT is providing specified performance for abnormal aircraft electrical conditions. Repeat each test condition 5 times. After the power returns to normal limits, conduct a performance test of the UUT according to the utilization equipment performance test procedures to verify that the UUT automatically returns to specified performance for normal aircraft electrical conditions when the power returns to within normal limits. Record the steady state voltage, voltage transient (oscilloscope trace), and the performance of the UUT for each test condition in the data sheet shown in table LDC302-V. Repeat for each mode of operation of the UUT. 5.2 Compliance test for MIL-STD-704B, C, & D. The UUT must be subjected to the voltage transients for each test condition AA through NN noted in table LDC302-III. The voltage must increase or decrease from steady state voltage as noted in table LDC302-III to the voltage transient level within 1 milliseconds. The voltage must remain at the voltage transient level for the duration noted in table LDC302-III. The voltage must return to steady state over the time duration noted in table LDC302-III. For test condition CC and FF, three over-voltage transients of 50 Vdc for 45 milliseconds are performed, separated by 0.5 second. For test condition LDC302-II and LL, three under-voltage transients of 7 Vdc for 45 milliseconds are performed, separated by 0.5 second. For test condition MM and NN, an under-voltage transient of 7 Vdc for 10 milliseconds is immediately followed by an over-voltage transient of 50 Vdc for 45 milliseconds and the voltage returns to steady state over the time duration noted. For each test condition, monitor the performance of the UUT during the voltage transient according to the equipment performance test procedures to verify that the UUT is providing specified performance for abnormal aircraft electrical conditions. Repeat each test condition 5 times. After the power returns to normal limits, conduct a performance test of the UUT according to the utilization equipment performance test procedures to verify that the UUT automatically returns to specified performance for normal aircraft electrical conditions when the power returns to within normal limits. Record the steady state voltage, voltage transient (oscilloscope trace), and 46
50 the performance of the UUT for each test condition in the data sheet shown in table VI. Repeat for each mode of operation of the UUT. 5.3 Compliance test for MIL-STD-704E & F. The UUT must be subjected to the voltage transients for each test condition AAA through NNN noted in table LDC302-IV. The voltage must increase or decrease from steady state voltage as noted in table LDC302-IV to the voltage transient level within 1 millisecond. The voltage must remain at the voltage transient level for the duration noted in table LDC302-IV. The voltage must return to steady state over the time duration noted in table LDC302-IV. For test condition CCC and FFF, three over-voltage transients of 50 Vdc for 50 milliseconds are performed, separated by 0.5 second. For test condition LDC302-III and LLL, three under-voltage transients of 7 Vdc for 50 milliseconds are performed, separated by 0.5 second. For test condition MMM and NNN, an under-voltage transient of 7 Vdc for 10 milliseconds is immediately followed by an over-voltage transient of 50 Vdc for 50 milliseconds and the voltage returns to steady state over the time duration noted. For each test condition, monitor the performance of the UUT during the voltage transient according to the equipment performance test procedures to verify that the UUT is providing specified performance for abnormal aircraft electrical conditions. Repeat each test condition 5 times. After the power returns to normal limits, conduct a performance test of the UUT according to the utilization equipment performance test procedures to verify that the UUT automatically returns to specified performance for normal aircraft electrical conditions when the power returns to within normal limits. Record the steady state voltage, voltage transient (oscilloscope trace), and the performance of the UUT for each test condition in the data sheet shown in table VII. Repeat for each mode of operation of the UUT. After all test conditions are complete, adjust the voltage to the nominal steady state voltage of 28 VDC. Conduct a performance test of the UUT according to the utilization equipment performance test procedures to confirm that the UUT has not suffered damage and is providing specified performance for normal aircraft electrical conditions. 47
51 TABLE LDC302-II. Test conditions for MIL-STD-704A abnormal voltage transients. Test Condition Steady State Vdc Time From Steady State to Transient Level milliseconds Transient Level Vdc Duration at Transient Level Time From Transient Level to Steady State milliseconds Overvoltage Transients A 28.5 Vdc < 1 msec 80 Vdc 50 msec < 1 msec B 28.5 Vdc < 1 msec 80 Vdc 37.5 msec 24 msec C 28.5 Vdc < 1 msec 60 Vdc 550 msec < 1 msec D 28.5 Vdc < 1 msec 60 Vdc 410 msec 280 msec E 28.5 Vdc < 1 msec 80 Vdc 12 msec < 1 msec (3 times) Every 0.5 sec F 24 Vdc < 1 msec 80 Vdc 50 msec < 1 msec G 24 Vdc < 1 msec 80 Vdc 37.5 msec 26 msec H 24 Vdc < 1 msec 60 Vdc 550 msec < 1 msec I 24 Vdc < 1 msec 60 Vdc 410 msec 320 msec J 24 Vdc < 1 msec 80 Vdc (3 times) 12 msec Every 0.5 sec < 1 msec Undervoltage Transients K 28.5 Vdc < 1 msec 6 Vdc 50 msec < 1 msec L 28.5 Vdc < 1 msec 6 Vdc 37.5 msec 26 msec M 28.5 Vdc < 1 msec 12 Vdc 550 msec < 1 msec N 28.5 Vdc < 1 msec 12 Vdc 410 msec 320 msec O 28.5 Vdc < 1 msec 6 Vdc 12 msec < 1 msec (3 times) Every 0.5 sec P 24 Vdc < 1 msec 6 Vdc 50 msec < 1 msec Q 24 Vdc < 1 msec 6 Vdc 37.5 msec 24 msec R 24 Vdc < 1 msec 12 Vdc 550 msec < 1 msec S 24 Vdc < 1 msec 12 Vdc 410 msec 280 msec T Combined Transient U V 24 Vdc 28.5 Vdc then 24 Vdc then < 1 msec 6 Vdc (3 times) < 1 msec < 1 msec < 1 msec < 1 msec 6 Vdc 80 Vdc 6 Vdc 80 Vdc 12 msec Every 0.5 sec 10 msec 50 msec 10 msec 50 msec < 1 msec < 1 msec 24 msec < 1 msec 24 msec 48
52 TABLE LDC302-III. Test conditions for MIL-STD-704B, C, and D abnormal voltage transients. Test Condition Steady State Vdc Time From Steady State to Transient Level milliseconds Transient Level Vdc Duration at Transient Level Time From Transient Level to Steady State or Next Level Overvoltage Transients AA 29 Vdc < 1 msec 50 Vdc 45 msec < 1 msec < 1 msec 50 Vdc 45 msec 15 msec then 45 Vdc decreasing 30 msec BB 29 Vdc then 40 Vdc decreasing 60 msec then 35 Vdc decreasing 4.85 sec then 30 Vdc decreasing 1 sec then 29 Vdc CC 29 Vdc < 1 msec 50 Vdc 45 msec < 1 msec (3 times) Every 0.5 sec DD 22 Vdc < 1 msec 50 Vdc 45 msec < 1 msec < 1 msec 50 Vdc 45 msec 15 msec then 45 Vdc decreasing 30 msec EE 22 Vdc then 40 Vdc decreasing 60 msec then 35 Vdc decreasing 4.85 sec then 30 Vdc decreasing 8 sec then 22 Vdc FF 22 Vdc < 1 msec 50 Vdc (3 times) 45 msec Every 0.5 sec < 1 msec Undervoltage Transients GG 29 Vdc < 1 msec 7 Vdc 45 msec < 1 msec < 1 msec 7 Vdc 45 msec 15 msec then 12 Vdc increasing 30 msec HH 29 Vdc then 17 Vdc increasing 60 msec then 22 Vdc increasing 4.85 sec then 28 Vdc increasing 1 sec then 29 Vdc II 29 Vdc < 1 msec 7 Vdc 45 msec < 1 msec (3 times) Every 0.5 sec JJ 22 Vdc < 1 msec 7 Vdc 45 msec < 1 msec < 1 msec 7 Vdc 45 msec 15 msec KK 22 Vdc then 12 Vdc increasing 30 msec then 17 Vdc increasing 60 msec then 22 Vdc LL 22 Vdc < 1 msec 7 Vdc (3 times) 45 msec Every 0.5 sec < 1 msec 49
53 TABLE LDC302-III. Test conditions for MIL-STD-704B, C, and D abnormal voltage transients. - Continued Test Condition Combined Transient MM NN Steady State Vdc 29 Vdc 22 Vdc Time From Steady State to Transient Level milliseconds Transient Level Vdc Duration at Transient Level Time From Transient Level to Steady State or Next Level < 1 msec < 1 msec 7 Vdc then 50Vdc 10 msec 45 msec < 1 msec 15 msec then 45 Vdc decreasing 30 msec then 40 Vdc decreasing 60 msec then 35 Vdc decreasing 4.85 sec then 30 Vdc decreasing 1 sec then 29 Vdc < 1 msec 7 Vdc then 10 msec < 1 msec < 1 msec 50Vdc 45 msec 15 msec then 45 Vdc decreasing 30 msec then 40 Vdc decreasing 60 msec then 35 Vdc decreasing 4.85 sec then 30 Vdc decreasing 8 sec then 22 Vdc 50
54 TABLE LDC302-IV. Test condition for MIL-STD-704E and F abnormal voltage transients. Test Condition Steady State Vdc Time From Steady State to Transient Level milliseconds Transient Level Vdc Duration at Transient Level Time From Transient Level to Steady State or Next Level Overvoltage Transients AAA 29 Vdc < 1 msec 50 Vdc 50 msec < 1 msec < 1 msec 50 Vdc 50 msec 15 msec then 45 Vdc decreasing 30 msec BBB 29 Vdc then 40 Vdc decreasing 60 msec then 35 Vdc decreasing 4.85 sec then 30 Vdc decreasing 1 sec then 29 Vdc CCC 29 Vdc < 1 msec 50 Vdc 50 msec < 1 msec (3 times) Every 0.5 sec DDD 22 Vdc < 1 msec 50 Vdc 50 msec < 1 msec < 1 msec 50 Vdc 50 msec 15 msec then 45 Vdc decreasing 30 msec EEE 22 Vdc then 40 Vdc decreasing 60 msec then 35 Vdc decreasing 4.85 sec then 30 Vdc decreasing 8 sec then 22 Vdc FFF 22 Vdc < 1 msec 50 Vdc (3 times) 50 msec Every 0.5 sec < 1 msec Undervoltage Transients GGG 29 Vdc < 1 msec 7 Vdc 50 msec < 1 msec < 1 msec 7 Vdc 50 msec 15 msec then 12 Vdc increasing 30 msec HHH 29 Vdc then 17 Vdc increasing 60 msec then 22 Vdc increasing 4.85 sec then 28 Vdc increasing 1 sec then 29 Vdc III 29 Vdc < 1 msec 7 Vdc 50 msec < 1 msec (3 times) Every 0.5 sec JJJ 22 Vdc < 1 msec 7 Vdc 50 msec < 1 msec < 1 msec 7 Vdc 50 msec 15 msec KKK 22 Vdc then 12 Vdc increasing 30 msec then 17 Vdc increasing 60 msec then 22 Vdc LLL 22 Vdc < 1 msec 7 Vdc (3 times) 50 msec Every 0.5 sec < 1 msec 51
55 TABLE LDC302-IV. Test conditions for ML-STD-704E & F abnormal voltage transients. - Continued Test Condition Combined Transient MMM NNN Steady State Vdc 29 Vdc 22 Vdc Time From Steady State to Transient Level milliseconds Transient Level Vdc Duration at Transient Level Time From Transient Level to Steady State or Next Level < 1 msec < 1 msec 7 Vdc then 50Vdc 10 msec 50 msec < 1 msec 15 msec then 45 Vdc decreasing 30 msec then 40 Vdc decreasing 60 msec then 35 Vdc decreasing 4.85 sec then 30 Vdc decreasing 1 sec then 29 Vdc < 1 msec 7 Vdc then 10 msec < 1 msec < 1 msec 50Vdc 50 msec 15 msec then 45 Vdc decreasing 30 msec then 40 Vdc decreasing 60 msec then 35 Vdc decreasing 4.85 sec then 30 Vdc decreasing 8 sec then 22 Vdc 52
56 O scilloscope (See Note 3) True RMS Voltm eter (See Note 3) See Note 1 53 Program m able DC Power Supply GND + - See Note 2 CAUTION 10 cm + - CHASSIS Unit Under Test (UUT) G round Plane Notes: 1. measurements shall be made within 10 cm of UUT input power terminals. 2. CAUTION: Verify suitability of power supply MINUS and GROUND connections. 3. CAUTION: Verify suitability of instrumentation inputs and/or use appropriate attenuation. 4. Stimulation and Monitoring Equipment are user defined. This functional block shall provide appropriate inputs (stimulations) and monitor UUT outputs (e.g.: RPM, signals, data, etc.) Stim ulation & M onitoring Equipm ent (See Note 4) Abnormal Operation - Abnormal Voltatge Transients FIGURE LDC Abnormal operation - abnormal voltage Figure transients. LDC 302-1
57 TABLE LDC302-V. Sample data sheet for LDC302 abnormal transients for MIL-STD-704A. 54 Test Parameters Condition Steady State Transient Time at Oscilloscope Trace Transient Level A V DC V DC msec Attach Trace V DC vs Time B V DC V DC msec Attach Trace V DC vs Time C V DC V DC msec Attach Trace V DC vs Time D V DC V DC msec Attach Trace V DC vs Time E V DC V DC msec Attach Trace V DC vs Time F V DC V DC msec Attach Trace V DC vs Time G V DC V DC msec Attach Trace V DC vs Time H V DC V DC msec Attach Trace V DC vs Time I V DC V DC msec Attach Trace V DC vs Time J V DC V DC msec Attach Trace V DC vs Time K V DC V DC msec Attach Trace V DC vs Time L V DC V DC msec Attach Trace V DC vs Time M V DC V DC msec Attach Trace V DC vs Time N V DC V DC msec Attach Trace V DC vs Time O V DC V DC msec Attach Trace V DC vs Time P V DC V DC msec Attach Trace V DC vs Time Q V DC V DC msec Attach Trace V DC vs Time R V DC V DC msec Attach Trace V DC vs Time S V DC V DC msec Attach Trace V DC vs Time T V DC V DC msec Attach Trace V DC vs Time U V DC msec V DC V DC msec Attach Trace V DC vs Time V V DC V DC msec Attach Trace msec V DC vs Time V DC Performance Pass/Fail
58 TABLE LDC302-VI. Sample data sheet for LDC302 abnormal voltage transients for MIL-STD-704B, C, & D. 55 Test Parameters Condition Steady State Time at Oscilloscope Trace Transient Transient Level AA V DC V DC msec Attach Trace V DC vs Time BB V DC V DC msec Attach Trace V DC vs Time CC V DC V DC msec Attach Trace V DC vs Time DD V DC V DC msec Attach Trace V DC vs Time EE V DC V DC msec Attach Trace V DC vs Time FF V DC V DC msec Attach Trace V DC vs Time GG V DC V DC msec Attach Trace V DC vs Time HH V DC V DC msec Attach Trace V DC vs Time II V DC V DC msec Attach Trace V DC vs Time JJ V DC V DC msec Attach Trace V DC vs Time KK V DC V DC msec Attach Trace V DC vs Time LL V DC V DC msec Attach Trace V DC vs Time MM V DC msec V DC V DC msec Attach Trace V DC vs Time NN V DC V DC msec Attach Trace msec V DC vs Time V DC Performance Pass/Fail
59 TABLE LDC302-VII. Sample data sheet for LDC302 abnormal voltage transients for MIL-STD-704E, & F. 56 Test Parameters Condition Steady State Time at Oscilloscope Trace Transient Transient Level AAA V DC V DC msec Attach Trace V DC vs Time BBB V DC V DC msec Attach Trace V DC vs Time CCC V DC V DC msec Attach Trace V DC vs Time DDD V DC V DC msec Attach Trace V DC vs Time EEE V DC V DC msec Attach Trace V DC vs Time FFF V DC V DC msec Attach Trace V DC vs Time GGG V DC V DC msec Attach Trace V DC vs Time HHH V DC V DC msec Attach Trace V DC vs Time III V DC V DC msec Attach Trace V DC vs Time JJJ V DC V DC msec Attach Trace V DC vs Time KKK V DC V DC msec Attach Trace V DC vs Time LLL V DC V DC msec Attach Trace V DC vs Time MMM V DC msec V DC V DC msec Attach Trace V DC vs Time NNN V DC V DC msec Attach Trace msec V DC vs Time V DC Performance Pass/Fail
60 METHOD LDC401 Steady State Limits for POWER GROUP: AIRCRAFT ELECTRICAL OPERATING CONDITION: PARAMETER: 28 Volt DC Emergency Steady State Limits for 1. Scope. 1.1 Purpose. This test procedure is used to verify that 28 volt DC power utilization equipment operates and maintains specified performance when provided power with voltage at that the Emergency Low Steady State (ELSS) limits and the Emergency High Steady State (EHSS) limits as specified in the applicable editions(s) of MIL-STD Validation criteria. The utilization equipment is considered to have passed if the utilization equipment operates and maintains performance as specified in the utilization equipment performance specification document for emergency aircraft electrical conditions when supplied input power of voltage at the specified emergency steady state limits of the applicable editions(s) of MIL-STD-704 and as noted in table LDC401-I. The utilization equipment must maintain specified performance for a length of time that confirms the utilization equipment can continuously operate at the steady state voltage and should be not less than thirty (30) minutes for each of the test conditions. Unless otherwise specified in the utilization equipment performance specification document, the utilization equipment must demonstrate re-start at the emergency steady state voltage limits. Unless otherwise specified in the utilization equipment performance specification document, the utilization must automatically return to the performance specified for normal aircraft electrical conditions when the power returns to within normal limits. The utilization equipment must not suffer damage or cause an unsafe condition. TABLE LDC401-I. MIL-STD-704 emergency limits for steady state voltage. Emergency Limit ELSS EHSS 704A 704B 704C 704D 704E 704F 16.0 Vdc 18.0 Vdc 16.0 Vdc 16.0 Vdc 18.0 Vdc 18.0 Vdc 24.0 Vdc 29.0 Vdc 30.0 Vdc 29.0 Vdc 29.0 Vdc 29.0 Vdc 3. Apparatus. The test equipment should be as follows: a. Adjustable DC power supply b. True RMS voltmeter 4. Test setup. Configure the test setup as shown in figure LDC Measurements, except current, must be made within 10 cm of the input power terminals of the UUT. 57
61 5. Compliance test. With the power source off, install the UUT and the stimulation and monitoring equipment into the test setup of figure LDC Turn on the power source and adjust the voltage to the nominal steady state voltage of 28 VDC. Energize the UUT. Allow sufficient time for the UUT to warm up. Conduct a performance test of the UUT according to the utilization equipment performance test procedures to verify that the UUT is providing specified performance for normal aircraft electrical conditions. For each test condition A and B noted in table LDC401-II, the UUT must remain for a length of time that confirms the utilization equipment can perform as specified at the emergency steady state voltage limits and should be not less than thirty (30) minutes. At each test condition conduct a performance test of the UUT according to the utilization equipment performance test procedures to verify that the UUT is providing specified performance for emergency aircraft electrical conditions. For each test condition shutdown the UUT and verify that the UUT can be re-started. After re-start conduct a performance test of the UUT according to the utilization equipment performance test procedures to verify that the UUT is providing specified performance for emergency aircraft electrical conditions. Adjust the voltage to the nominal steady state voltage of 28 VDC. Conduct a performance test of the UUT according to the utilization equipment performance test procedures to confirm that the UUT has automatically returned to the performance specified for normal aircraft electrical conditions, and has not suffered damage. Record the voltage, time duration at test condition, and the performance of the UUT for each test condition in the data sheet shown in table LDC401-III. Repeat for each mode of operation of the UUT. TABLE LDC401-II. Test conditions for emergency steady state limits for DC voltage. Test Condition A B ELSS EHSS 58
62 True RMS Voltm eter (See Note 3) See Note 1 59 Adjustable DC Power Supply GND + - See Note 2 CAUTION 10 cm + - CHASSIS Unit Under Test (UUT) G round Plane Notes: 1. measurements shall be made within 10 cm of UUT input power terminals. 2. CAUTION: Verify suitability of power supply MINUS and GROUND connections. 3. CAUTION: Verify suitability of instrumentation inputs and/or use appropriate attenuation. 4. Stimulation and Monitoring Equipment are user defined. This functional block shall provide appropriate inputs (stimulations) and monitor UUT outputs (e.g.: RPM, signals, data, etc.) Stim ulation & M onitoring Equipm ent (See Note 4) Em ergency Operation - Steady State Limits for Figure LDC FIGURE LDC Emergency operation - steady state limits for voltage.
63 TABLE LDC401-III. Sample data sheet for LDC401 emergency steady state limits for voltage and frequency. Test Parameters Performance Condition Time Duration Pass/Fail at Test Condition A V DC min B V DC min 60
64 METHOD LDC501 Starting Transients POWER GROUP: AIRCRAFT ELECTRICAL OPERATING CONDITION: PARAMETER: 28 Volt DC Starting Starting Transients 1. Scope. 1.1 Purpose. This test procedure is used to verify that 28 volt DC power utilization equipment operates and maintains specified performance when subjected to starting voltage transients as specified in the applicable editions(s) of MIL-STD Validation criteria. The utilization equipment is considered to have passed if the utilization equipment operates and maintains performance as specified in the utilization equipment performance specification document for starting aircraft electrical conditions when subjected to starting voltage transients for the applicable editions(s) of MIL-STD-704 and as noted in table LDC501-I. Unless otherwise specified in the utilization equipment performance specification document, the utilization equipment must automatically return to the performance specified for normal aircraft electrical conditions when the power returns to within normal limits. The utilization equipment must not suffer damage or cause an unsafe condition. TABLE LDC501-I. MIL-STD-704 limits for starting voltage transients. Limit 704A 704B 704C 704D 704E 704F Starting Transients 16.0 Vdc to 28.5 Vdc Use Limits of 704 C 16.0 Vdc to 30.0 Vdc 12.0 Vdc to 29.0 Vdc 12.0 Vdc to 29.0 Vdc 12.0 Vdc to 29.0 Vdc 3. Apparatus. The test equipment should be as follows: a. Programmable DC power supply b. True RMS voltmeter c. Oscilloscope 4. Test setup. Configure the test setup as shown in figure 1. Measurements, except current, must be made within 10 cm of the input power terminals of the UUT. 5. Compliance test. With the power source off, install the UUT and the stimulation and monitoring equipment into the test setup of figure LDC Turn on the power source and adjust the voltage to the nominal steady state voltage of 28 VDC. Energize the UUT. Allow sufficient time for the UUT to warm up. Conduct a performance test of the UUT according to the utilization equipment performance test procedures to verify that the UUT is providing specified performance for normal aircraft electrical conditions. 61
65 5.1 Compliance test for MIL-STD-704A, B and C. The UUT must be subjected to the starting voltage transients described in table LDC501-II (test condition A). The voltage must decrease from steady state voltage to the 16 Vdc within 1 millisecond. The voltage must return to steady state at a constant rate over 30 seconds. Monitor the performance of the UUT during the starting voltage transient according to the equipment performance test procedures to verify that the UUT is providing specified performance for starting aircraft electrical conditions. Repeat the test condition 5 times. After the power returns to normal limits, conduct a performance test of the UUT according to the utilization equipment performance test procedures to verify that the UUT automatically returns to specified performance for normal aircraft electrical conditions when the power returns to within normal limits. Record the steady state voltage, voltage transient (oscilloscope trace), and the performance of the UUT in the data sheet shown in table LDC501-IV. Repeat for each mode of operation of the UUT. 5.2 Compliance test for MIL-STD-704D, E, & F. The UUT must be subjected to the starting voltage transients described in table LDC501-III (test condition AA). The voltage must decrease from steady state voltage to the 12 Vdc within 1 millisecond. The voltage must return to steady state at a constant rate over 30 seconds. Monitor the performance of the UUT during the starting voltage transient according to the equipment performance test procedures to verify that the UUT is providing specified performance for starting aircraft electrical conditions. Repeat the test condition 5 times. After the power returns to normal limits, conduct a performance test of the UUT according to the utilization equipment performance test procedures to verify that the UUT automatically returns to specified performance for normal aircraft electrical conditions when the power returns to within normal limits. Record the steady state voltage, voltage transient (oscilloscope trace), and the performance of the UUT in the data sheet shown in table LDC501-IV. Repeat for each mode of operation of the UUT. TABLE LDC501-II. Test conditions for MIL-STD-704A, B and C starting voltage transients. Test Condition Steady State Vdc Time From Steady State to Transient Level milliseconds Transient Level Vdc Time From Transient Level to Steady State A 28.5 Vdc < 1 msec 16 Vdc 30 sec 62
66 TABLE LDC501-III. Test conditions for MIL-STD-704D, E and F starting voltage transients. Test Condition Steady State Vdc Time From Steady State to Transient Level milliseconds Transient Level Vdc Time From Transient Level to Steady State AA 29 Vdc < 1 msec 12 Vdc 30 sec 63
67 O scilloscope (See Note 3) True RMS Voltm eter (See Note 3) See Note 1 64 Program m able DC Power Supply GND + - See Note 2 CAUTION 10 cm + - CHASSIS Unit Under Test (UUT) G round Plane Notes: 1. measurements shall be made within 10 cm of UUT input power terminals. 2. CAUTION: Verify suitability of power supply MINUS and GROUND connections. 3. CAUTION: Verify suitability of instrumentation inputs and/or use appropriate attenuation. 4. Stimulation and Monitoring Equipment are user defined. This functional block shall provide appropriate inputs (stimulations) and monitor UUT outputs (e.g.: RPM, signals, data, etc.) Stim ulation & M onitoring Equipm ent (See Note 4) Starting Operation - Starting Transients Figure LDC FIGURE LDC Starting operation - starting voltage transients.
68 TABLE LDC501-IV. Sample data sheet for LDC501 starting voltage transients for MIL-STD-704A, B, C, D, E & F. Test Condition Parameters Steady State Transient Time to Return to Oscilloscope Trace Steady State V DC V DC sec Attach Trace V DC vs Time Performance Pass/Fail 65
69 METHOD LDC601 Power Failure POWER GROUP: AIRCRAFT ELECTRICAL OPERATING CONDITION: PARAMETER: 28 Volt DC Power Failure Power Failure 1. Scope. 1.1 Purpose. This test procedure is used to verify that 28 volt DC power utilization equipment operates and maintains specified performance when subjected to Power Failures as specified in the applicable editions(s) of MIL-STD Validation criteria. The utilization equipment is considered to have passed if the utilization equipment operates and maintains performance as specified in the utilization equipment performance specification document for power failure aircraft electrical conditions when subjected to power failures as specified by the applicable editions(s) of MIL-STD-704 and as noted in table LDC601-I. The utilization equipment must maintain the specified performance during power failures. Unless otherwise specified in the utilization equipment performance specification document, the utilization equipment must automatically return to the performance specified for normal aircraft electrical conditions when the power returns to within normal limits. The utilization equipment must not suffer damage or cause an unsafe condition. TABLE LDC601-I. MIL-STD-704 power failure limits. Limit 704A 704B 704C 704D 704E 704F Power Failure 7 sec Figure 9 Curve 4 MIL-STD- 704B 7 sec Figure 8 MIL-STD- 704B 7 sec Figure 12 MIL-STD- 704C 7 sec Figure 12 MIL-STD- 704D 7 sec Figure 11 MIL-STD- 704E 7 sec Figure 14 MIL-STD- 704F 3. Apparatus. The test equipment should be as follows: a. Programmable DC power supply b. True RMS voltmeter c. Oscilloscope 4. Test setup. Configure the test setup as shown in figure LDC Measurements, except current, must be made within 10 cm of the input power terminals of the UUT. 66
70 5. Compliance test. With the power source off, install the UUT and the stimulation and monitoring equipment into the test setup of figure LDC Turn on the power source and adjust the voltage to the nominal steady state voltage of 28 VDC. Energize the UUT. Allow sufficient time for the UUT to warm up. Conduct a performance test of the UUT according to the utilization equipment performance test procedures to verify that the UUT is providing specified performance for normal aircraft electrical conditions. For each test condition A through D noted in table LDC601-II, perform a power failure (0 V) of the duration listed. The voltage must decrease from the steady state voltage to 0 Volts within 0.25 milliseconds, remain at 0 volts for the duration listed for the test condition, and return from 0 Volts to the steady state voltage within 0.25 milliseconds. For each test condition, monitor the performance of the UUT according to the utilization equipment performance test procedures for power failure operation to verify that the UUT is providing specified performance for power failure aircraft electrical conditions. After the power returns to normal limits, conduct a performance test of the UUT according to the utilization equipment performance test procedures to confirm that the UUT has automatically returned to the performance specified for normal aircraft electrical conditions, and has not suffered damage. Record the steady state voltage, time duration of power failure, and the performance of the UUT for each test condition in the data sheet shown in table LDC601-III. Repeat each test condition 5 times. Repeat for each mode of operation of the UUT. After all test conditions are complete, adjust the voltage to the nominal steady state voltage of 28 VDC. Conduct a performance test of the UUT according to the utilization equipment performance test procedures to confirm that the UUT has not suffered damage and is providing specified performance for normal aircraft electrical conditions. TABLE LDC601-II. Test conditions for power failures. Test Condition A B C D Duration of Power Failure 100 msec 500 msec 3 seconds 7 seconds 67
71 Oscilloscope (See Note 3) True RMS Voltm eter (See Note 3) See Note 1 68 Program m able DC Power Supply GND + - See Note 2 CAUTION 10 cm + - CHASSIS Unit Under Test (UUT) Notes: Ground Plane 1. measurements shall be made within 10 cm of UUT input power terminals. 2. CAUTION: Verify suitability of power supply MINUS and GROUND connections. 3. CAUTION: Verify suitability of instrumentation inputs and/or use appropriate attenuation. 4. Stimulation and Monitoring Equipment are user defined. This functional block shall provide appropriate inputs (stimulations) and monitor UUT outputs (e.g.: RPM, signals, data, etc.) Stim ulation & Monitoring Equipm ent (See Note 4) Power Failure - Power Failure Figure LDC FIGURE LDC Power failure - power failure.
72 TABLE LDC601-III. Sample data sheet for LDC601 power failure. Test Parameters Performance Condition Time Duration Pass/Fail of Power Failure A V DC msec B V DC msec C V DC sec D V DC sec 69
73 METHOD LDC602 Phase Reversal POWER GROUP: AIRCRAFT ELECTRICAL OPERATING CONDITION: PARAMETER: 28 Volt DC Power Failure Phase Reversal 1. Scope. 1.1 Purpose. This test procedure is used to verify that 28 volt DC power utilization equipment is not damaged by phase reversal or a positive physical means is employed to prevent phase reversal. 2. Validation criteria. The utilization equipment is considered to have passed if the utilization equipment is not damaged and does not cause an unsafe condition when the positive and negative connection are reversed for the applicable editions(s) of MIL-STD-704 and as noted in table LDC602-I. A positive physical means to prevent phase reversal may be used to fulfill this requirement. TABLE LDC602-I. MIL-STD-704 phase reversal requirement. Limit 704A 704B 704C 704D 704E 704F Phase Reversal N/A N/A N/A N/A N/A Phase Reversal Does not Cause Damage 3. Apparatus. The test equipment should be as follows: a. Adjustable DC power supply b. True RMS voltmeter 4. Test setup. Configure the test setup as shown in figure LDC Measurements, except current, must be made within 10 cm of the input power terminals of the UUT. 5. Compliance test. If a positive physical means is employed to prevent phase reversal, confirm that the positive and negative conductors cannot be reversed. If the positive and negative conductors can be reversed, with the power source off, install the UUT and the stimulation and monitoring equipment into the test setup of figure LDC602-1 (positive and negative conductors reversed). Turn on the power source and adjust the voltage to the nominal steady state voltage of 28 VDC. Energize the UUT. The UUT must remain for a length of time that confirms the utilization equipment is not damaged and does not cause an 70
74 unsafe condition due to phase reversal and should be not less than thirty (30) minutes. Record the steady state voltage, time duration at phase reversal test condition, and the performance of the UUT in the data sheet shown in table LDC602-II. Repeat for each mode of operation of the UUT. With the power source off, install the UUT and the stimulation and monitoring equipment into the test setup of figure LDC602-2 (positive and negative conductors connected properly). Turn on the power source and adjust the voltage to the nominal steady state voltage of 28 VDC. Energize the UUT. The UUT must remain for a length of time that confirms the utilization equipment was not damaged and does not cause an unsafe condition after the phase reversal and should be not less than thirty (30) minutes. Conduct a performance test of the UUT according to the utilization equipment performance test procedures to confirm that the UUT has returned to the performance specified for normal aircraft electrical conditions and has not suffered damage. Record the steady state voltage, time duration at test condition, and the performance of the UUT in the data sheet shown in table LDC602-II. Repeat for each mode of operation of the UUT. 71
75 True RMS Voltmeter (See Note 3) See Note 1 72 Adjustable DC Power Supply GND + - See Note 2 CAUTION Ground Plane See Note 5 10 cm + - CHASSIS Unit Under Test (UUT) Notes: 1. measurements shall be made within 10 cm of UUT input power terminals. 2. CAUTION: Verify suitability of power supply MINUS and GROUND connections. 3. CAUTION: Verify suitability of instrumentation inputs and/or use appropriate attenuation. 4. Stimulation and Monitoring Equipment are user defined. This functional block shall provide appropriate inputs (stimulations) and monitor UUT outputs (e.g.: RPM, signals, data, etc.) 5. Phase Polarity is reversed. Stimulation & Monitoring Equipm ent (See Note 4) Phase Reversal Figure LDC FIGURE LDC Phase reversal.
76 True RMS Voltm eter (See Note 3) See Note 1 73 Adjustable DC Power Supply GND + - See Note 2 CAUTION G round Plane 10 cm + - CHASSIS Unit Under Test (UUT) Notes: 1. measurements shall be made within 10 cm of UUT input power terminals. 2. CAUTION: Verify suitability of power supply MINUS and GROUND connections. 3. CAUTION: Verify suitability of instrumentation inputs and/or use appropriate attenuation. 4. Stimulation and Monitoring Equipment are user defined. This functional block shall provide appropriate inputs (stimulations) and monitor UUT outputs (e.g.: RPM, signals, data, etc.) Stim ulation & Monitoring Equipm ent (See Note 4) Correct Phase Connection Figure LDC FIGURE LDC Correct phase connection.
77 TABLE LDC602-II. Sample data sheet for LDC602 phase reversal. Test Parameters Condition Phase Reversal Prevented by Positive Physical Means If No Time Duration at Condition Phase V dc min Reversal Correct Phase V dc min Connection Performance Yes/No Pass/Fail 74
78 6. NOTES 6.1 Intended use. This handbook should be used as guidance when establishing test requirements, for inclusion in performance specifications developed for the procurement of utilization equipment, to ensure compliance with the aircraft electrical power characteristics as specified by MIL-STD Subject term (keyword) listing. Aircraft, electrical power Aircraft, electrical test Electrical operating areas Equipment, utilization Power groups Specification, utilization equipment CONCLUDING MATERIAL Custodians: Army - AV Navy - AS Air Force - 11 Preparing Activity: Navy - AS (Project No. SESS-0054) Review Activities: Army - CR, MI, TE Navy - EC, MC, SA, SH, YD NOTE: The activities listed above were interested in this document as of the date of this document. Since organizations and responsibilities can change, you should verify the currency of the information above using the ASSIST Online database at 75
MILITARY STANDARD. Aircraft Electric Power Characteristics
NOTICE OF VALIDATION NOT MEASUREMENT SENSITIVE MIL-STD-704F NOTICE 2 25-Oct-2013 MILITARY STANDARD Aircraft Electric Power Characteristics MIL-STD-704F, dated 30-Dec-2008, has been reviewed and determined
IEC 1000-4-2 ESD Immunity and Transient Current Capability for the SP72X Series Protection Arrays
IEC 00-4-2 ESD Immunity and Transient Current Capability for the SP72X Series Protection Arrays Application Note July 1999 AN9612.2 Author: Wayne Austin The SP720, SP721, SP723, and SP724 are protection
ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE 46 2007. Test Method for AC to DC Power Supplies
ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE 46 2007 Test Method for AC to DC Power Supplies NOTICE The Society of Cable Telecommunications Engineers (SCTE)
Diode Applications. As we have already seen the diode can act as a switch Forward biased or reverse biased - On or Off.
Diode Applications Diode Switching As we have already seen the diode can act as a switch Forward biased or reverse biased - On or Off. Voltage Rectifier A voltage rectifier is a circuit that converts an
= V peak 2 = 0.707V peak
BASIC ELECTRONICS - RECTIFICATION AND FILTERING PURPOSE Suppose that you wanted to build a simple DC electronic power supply, which operated off of an AC input (e.g., something you might plug into a standard
BOARD-LEVEL TEST PROCEDURE GYROSCOPE SUSPENSION SYSTEM (GSS) HV AMPLIFIER AND BRIDGE (HVA) ASSEMBLY. GP-B Procedure P0829 Rev A
P0829 Rev. A September 26, 2001 W. W. Hansen Experimental Physics Laboratory STANFORD UNIVERSITY STANFORD, CALIFORNIA 94305-4085 Gravity Probe B Relativity Mission BOARD-LEVEL TEST PROCEDURE GYROSCOPE
RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:
Application : RISH Master 3490 DS measures important electrical parameters of Utility (in normal mode) & Generators (in Power back up) in three phase and single phase Network & replaces the multiple analog
Current Probes. User Manual
Current Probes User Manual ETS-Lindgren L.P. reserves the right to make changes to any product described herein in order to improve function, design, or for any other reason. Nothing contained herein shall
Considerations When Specifying a DC Power Supply
Programming Circuit White Paper Considerations When Specifying a DC Power Supply By Bill Martin, Sales/Applications Engineer Every automated test system that tests electronic circuit boards, modules or
Rated Power(W) 8W 2. EG-LED0840-01 8W 3. EG-LED1027-01 10W
14713221 001 Seite 2 von 37 Page 2 of 37 Model List: No Model Rated Voltage(V) 1. EG-LED0827-01 Rated Power(W) 8W 2. EG-LED0840-01 8W 3. EG-LED1027-01 10W 4. EG-LED1040-01 AC 100-240V, 10W 5. EG-LED1027-02
DEPARTMENT OF DEFENSE TEST METHOD STANDARD METHOD OF INSERTION LOSS MEASUREMENT
INCH-POUND MIL-STD-220C 14 May 2009 SUPERSEDING MIL-STD-220B 24 January 2000 DEPARTMENT OF DEFENSE TEST METHOD STANDARD METHOD OF INSERTION LOSS MEASUREMENT AMSC N/A FSC EMCS FOREWORD 1. This standard
TESTS OF 1 MHZ SIGNAL SOURCE FOR SPECTRUM ANALYZER CALIBRATION 7/8/08 Sam Wetterlin
TESTS OF 1 MHZ SIGNAL SOURCE FOR SPECTRUM ANALYZER CALIBRATION 7/8/08 Sam Wetterlin (Updated 7/19/08 to delete sine wave output) I constructed the 1 MHz square wave generator shown in the Appendix. This
Reading: HH Sections 4.11 4.13, 4.19 4.20 (pgs. 189-212, 222 224)
6 OP AMPS II 6 Op Amps II In the previous lab, you explored several applications of op amps. In this exercise, you will look at some of their limitations. You will also examine the op amp integrator and
AMERICAN NATIONAL STANDARD
ENGINEERING COMMITTEE Interface Practice Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE 46 2014 Test Method for AC to DC Outdoor Power Supplies NOTICE The Society of Cable Telecommunications Engineers
DATA SHEET. TDA8560Q 2 40 W/2 Ω stereo BTL car radio power amplifier with diagnostic facility INTEGRATED CIRCUITS. 1996 Jan 08
INTEGRATED CIRCUITS DATA SHEET power amplifier with diagnostic facility Supersedes data of March 1994 File under Integrated Circuits, IC01 1996 Jan 08 FEATURES Requires very few external components High
Precision Diode Rectifiers
by Kenneth A. Kuhn March 21, 2013 Precision half-wave rectifiers An operational amplifier can be used to linearize a non-linear function such as the transfer function of a semiconductor diode. The classic
Rectifier circuits & DC power supplies
Rectifier circuits & DC power supplies Goal: Generate the DC voltages needed for most electronics starting with the AC power that comes through the power line? 120 V RMS f = 60 Hz T = 1667 ms) = )sin How
SERIES-PARALLEL DC CIRCUITS
Name: Date: Course and Section: Instructor: EXPERIMENT 1 SERIES-PARALLEL DC CIRCUITS OBJECTIVES 1. Test the theoretical analysis of series-parallel networks through direct measurements. 2. Improve skills
See Horenstein 4.3 and 4.4
EE 462: Laboratory # 4 DC Power Supply Circuits Using Diodes by Drs. A.V. Radun and K.D. Donohue (2/14/07) Department of Electrical and Computer Engineering University of Kentucky Lexington, KY 40506 Updated
Product Family of Capacitor Chargers PS-17XX for 1500J/Sec in the range 500Vac to 1,000Vac PS-22XX for 2200J/Sec in the range 500Vac to 1,000Vac
Product Description Capacitor charger power supplies from Digital Power are designed to meet the exacting requirements of medical, aesthetic, and industrial pulsed energy systems. The modular design of
ANADOLU UNIVERSITY DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING
ANADOLU UNIVERSITY DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING EEM 102 INTRODUCTION TO ELECTRICAL ENGINEERING EXPERIMENT 9: DIODES AND DC POWER SUPPLY OBJECTIVE: To observe how a diode functions
MCR-VDC-UI-B-DC. Voltage Transducer for DC Voltages. INTERFACE Data Sheet 100260_en_01. 1 Description
Voltage Transducer for DC Voltages TERFACE Data Sheet 000_en_0 PHOENIX CONTACT - /00 Description The MCR voltage transducer measures DC voltages in several signal ranges from 0... ±0 V DC to 0... ±0 V
AC Direct Off-Line Power Supplies
AC Direct Off-Line Power Supplies r Introduction Many DC power supplies found in electronic systems, including those in this Tech School, rectify the 120 volts available at an electric outlet. The initial
FREQUENCY RESPONSE ANALYZERS
FREQUENCY RESPONSE ANALYZERS Dynamic Response Analyzers Servo analyzers When you need to stabilize feedback loops to measure hardware characteristics to measure system response BAFCO, INC. 717 Mearns Road
EE 1202 Experiment #4 Capacitors, Inductors, and Transient Circuits
EE 1202 Experiment #4 Capacitors, Inductors, and Transient Circuits 1. Introduction and Goal: Exploring transient behavior due to inductors and capacitors in DC circuits; gaining experience with lab instruments.
DIODE CIRCUITS LABORATORY. Fig. 8.1a Fig 8.1b
DIODE CIRCUITS LABORATORY A solid state diode consists of a junction of either dissimilar semiconductors (pn junction diode) or a metal and a semiconductor (Schottky barrier diode). Regardless of the type,
WHY DIFFERENTIAL? instruments connected to the circuit under test and results in V COMMON.
WHY DIFFERENTIAL? Voltage, The Difference Whether aware of it or not, a person using an oscilloscope to make any voltage measurement is actually making a differential voltage measurement. By definition,
LABORATORY 10 TIME AVERAGES, RMS VALUES AND THE BRIDGE RECTIFIER. Bridge Rectifier
LABORATORY 10 TIME AVERAGES, RMS VALUES AND THE BRIDGE RECTIFIER Full-wave Rectification: Bridge Rectifier For many electronic circuits, DC supply voltages are required but only AC voltages are available.
SL Series AC and DC Electronic Loads
SL Series AC and DC Electronic Loads Applications AC & DC Power Supply Testing Rechargeable batteries and chargers Fuel cell test - cells and stacks PFC circuit test Pulsed LED Test and Burn-in Laser Diode
Inductors in AC Circuits
Inductors in AC Circuits Name Section Resistors, inductors, and capacitors all have the effect of modifying the size of the current in an AC circuit and the time at which the current reaches its maximum
CPCI-3U-AC-300W-R. Rugged 300W AC Input 3U CompactPCI Power Supply. Electrical Specification for: Telkoor Part Number: 900-4602-0000
Electrical Specification for: CPCI-3U-AC-300W-R Rugged 300W AC Input 3U CompactPCI Power Supply Telkoor Part Number: 900-4602-0000 GENERAL SCALE RELEASE DATE 12/9/06 SHEET 1 OF 6 REVISION HISTORY Rev Level
APPLICATION NOTE USING A MODEL 3060-MS SERIES AS A REGENERATIVE AC SOURCE FOR PV INVERTER TEST APPLICATIONS. Abstract.
USING A MODEL 3060-MS SERIES AS A REGENERATIVE AC SOURCE FOR PV INVERTER TEST APPLICATIONS Abstract This application note describes the necessary procedure to use a standard Pacific Power Source Model
AC Measurements Using the Oscilloscope and Multimeter by Mr. David Fritz
AC Measurements Using the Oscilloscope and Multimeter by Mr. David Fritz 1 Sine wave with a DC offset f = frequency in Hz A = DC offset voltage (average voltage) B = Sine amplitude Vpp = 2B Vmax = A +
EMC STANDARDS STANDARDS AND STANDARD MAKING BODIES. International. International Electrotechnical Commission (IEC) http://www.iec.
EMC STANDARDS The EMC standards that a particular electronic product must meet depend on the product application (commercial or military) and the country in which the product is to be used. These EMC regulatory
By Authority Of THE UNITED STATES OF AMERICA Legally Binding Document
By Authority Of THE UNITED STATES OF AMERICA Legally Binding Document By the Authority Vested By Part 5 of the United States Code 552(a) and Part 1 of the Code of Regulations 51 the attached document has
However, industrial applications may utilize a relay, which short-circuits the ICL path after the inrush sequence.
Application note for Inrush Current Limiters (ICL) Turning on electrical devices generally cause high inrush currents which can damage electronic components and cause interruption of the line voltage if
MATERIALS. Multisim screen shots sent to TA.
Page 1/8 Revision 0 9-Jun-10 OBJECTIVES Learn new Multisim components and instruments. Conduct a Multisim transient analysis. Gain proficiency in the function generator and oscilloscope. MATERIALS Multisim
Properties of electrical signals
DC Voltage Component (Average voltage) Properties of electrical signals v(t) = V DC + v ac (t) V DC is the voltage value displayed on a DC voltmeter Triangular waveform DC component Half-wave rectifier
Electrical Resonance
Electrical Resonance (R-L-C series circuit) APPARATUS 1. R-L-C Circuit board 2. Signal generator 3. Oscilloscope Tektronix TDS1002 with two sets of leads (see Introduction to the Oscilloscope ) INTRODUCTION
Troubleshooting accelerometer installations
Troubleshooting accelerometer installations Accelerometer based monitoring systems can be tested to verify proper installation and operation. Testing ensures data integrity and can identify most problems.
Outer Diameter 23 φ mm Face side Dimension 20.1 φ mm. Baffle Opening. Normal 0.5 Watts Maximum 1.0 Watts Sine Wave.
1. MODEL: 23CR08FH-50ND 2 Dimension & Weight Outer Diameter 23 φ mm Face side Dimension 20.1 φ mm Baffle Opening 20.1 φ mm Height Refer to drawing Weight 4.0Grams 3 Magnet Materials Rare Earth Size φ 9.5
Series AMEPR30-AZ up to 2.5A AC-DC / DC-DC LED Driver / Converter
FEATURES: Click on Series name for product info on aimtec.com Models Single output Model Max Output Power (W) 1 AC-DC Constant Current or Constant Over temperature protection Voltage LED Driver Over current
LABORATORY 2 THE DIFFERENTIAL AMPLIFIER
LABORATORY 2 THE DIFFERENTIAL AMPLIFIER OBJECTIVES 1. To understand how to amplify weak (small) signals in the presence of noise. 1. To understand how a differential amplifier rejects noise and common
[F/T] [5] [KHz] [AMP] [3] [V] 4 ) To set DC offset to -2.5V press the following keys [OFS] [+/-] [2] [.] [5] [V]
FG085 minidds Function Generator Manual of Operation Applicable Models: 08501, 08501K, 08502K, 08503, 08503K Applicable Firmware Version: 1 ) 113-08501-100 or later (for U5) 2 ) 113-08502-030 or later
CAN Bus Transceivers Operate from 3.3V or 5V and Withstand ±60V Faults
CAN Bus Transceivers Operate from 3.3V or 5V and Withstand ±6 Faults Ciaran Brennan design features The LTC2875 is a robust CAN bus transceiver that features ±6 overvoltage and ±25kV ESD tolerance to reduce
Measurement, Modeling and Simulation of Capacitor Bank Switching Transients
Measurement, Modeling and Simulation of Capacitor Bank Switching Transients Mirza Softić*, Amir Tokić**, Ivo Uglešić*** *Kreka - Dubrave e, Dubrave, Bosnia and Herzegovina (e-mail: [email protected]).
ACT4077 Driver for MACAIR A3818, A5690, A5232, A4905 & MIL-STD-1553
ACT4077 Driver for MACAIR A3818, A5690, A5232, A4905 & MIL-STD-1553 Features CIRCUIT TECHNOLOGY www.aeroflex.com ACT4077 Driver meets MIL-STD-1553A & B, Macair A3818, A4905, A5232 and A5690 specs Bipolar
Technical Comparison of On-line vs. Line-interactive UPS designs
Technical Comparison of On-line vs. Line-interactive UPS designs By Jeffrey Samstad Michael Hoff White Paper #79 Executive Summary UPS systems below 5000VA are available in two basic designs: line-interactive
GenTech Practice Questions
GenTech Practice Questions Basic Electronics Test: This test will assess your knowledge of and ability to apply the principles of Basic Electronics. This test is comprised of 90 questions in the following
Experiment 2 Diode Applications: Rectifiers
ECE 3550 - Practicum Fall 2007 Experiment 2 Diode Applications: Rectifiers Objectives 1. To investigate the characteristics of half-wave and full-wave rectifier circuits. 2. To recognize the usefulness
Service Information CALIBRATION PROCEDURE AND TROUBLESHOOTING FOR LINEAR GOVERNOR CONTROLLERS NOTE
Service Information Calibration & Adjustments CALIBRATION PROCEDURE AND TROUBLESHOOTING FOR LINEAR GOVERNOR CONTROLLERS Part Number DYN1-10752-000-0-12/24 DYN1-10752-001-0-12/24* DYN1-10753-000-0-12/24
Chapter 3. Diodes and Applications. Introduction [5], [6]
Chapter 3 Diodes and Applications Introduction [5], [6] Diode is the most basic of semiconductor device. It should be noted that the term of diode refers to the basic p-n junction diode. All other diode
Panel Meters and Controllers Modular Panel Meter Type EDM 35
Panel Meters and Controllers Modular Panel Meter Type EDM 35 Modular digital panel meter, 3 1/2-digit Indicating or controlling current, voltage, resistance, temperature, tacho or frequency. Easy programming
The Basics of Digital Multimeters
IDEAL INDUSTRIES INC. The Basics of Digital Multimeters A guide to help you understand the basic Features and Functions of a Digital Multimeter. Author: Patrick C Elliott Field Sales Engineer IDEAL Industries,
Power Supplies. 1.0 Power Supply Basics. www.learnabout-electronics.org. Module
Module 1 www.learnabout-electronics.org Power Supplies 1.0 Power Supply Basics What you ll learn in Module 1 Section 1.0 Power Supply Basics. Basic functions of a power supply. Safety aspects of working
Antec TruePower User's Manual
User s Manual Antec TruePower User's Manual Antec TruePower ATX12V power supply Models: TRUE330, TRUE380, TRUE430, TRUE480, TRUE550 Antec Low Noise Technology: The Antec TruePower power supply is equipped
Output Ripple and Noise Measurement Methods for Ericsson Power Modules
Output Ripple and Noise Measurement Methods for Ericsson Power Modules Design Note 022 Ericsson Power Modules Ripple and Noise Abstract There is no industry-wide standard for measuring output ripple and
DATA SHEET. TDA1518BQ 24 W BTL or 2 x 12 watt stereo car radio power amplifier INTEGRATED CIRCUITS
INTEGRATED CIRCUITS DATA SHEET File under Integrated Circuits, IC01 July 1994 GENERAL DESCRIPTION The is an integrated class-b output amplifier in a 13-lead single-in-line (SIL) plastic power package.
Chapter 22 Further Electronics
hapter 22 Further Electronics washing machine has a delay on the door opening after a cycle of washing. Part of this circuit is shown below. s the cycle ends, switch S closes. t this stage the capacitor
Pow-R-Con Multi Function Control
37264 Pow-R-Con Multi Function Control Product Specification Product Specification 37264 Product Information DYNA Power Controls Pow-R-Con TM GENERAL The Barber-Colman Pow-R-Con TM represents an integrated
Lock - in Amplifier and Applications
Lock - in Amplifier and Applications What is a Lock in Amplifier? In a nut shell, what a lock-in amplifier does is measure the amplitude V o of a sinusoidal voltage, V in (t) = V o cos(ω o t) where ω o
1+1 PROTECTION WITHOUT RELAYS USING IDT82V2044/48/48L & IDT82V2054/58/58L HITLESS PROTECTION SWITCHING
1+1 PROTECTION WITHOUT RELAYS USING IDT82V2044/48/48L & IDT82V2054/58/58L APPLICATION NOTE AN-357 1.0 INTRODUCTION In today's highly competitive market, high quality of service, QOS, and reliability is
Rectifier filter stage post filtering sense
TopCon DC power supplies Customer support files Nr. 042.0208.016_e Topic: Protecting the DC output 1. Abstract TopCon DC power supplies are generally well suited for operation into reactive DC loads. Reactive
SELECTION GUIDE. Nominal Input
www.murata-ps.com NKE Series FEATURES RoHS Compliant Sub-Miniature SIP & DIP Styles 3kVDC Isolation UL Recognised Wide Temperature performance at full 1 Watt load, 40 C to 85 C Increased Power Density
GENERAL POWER SYSTEM WIRING PRACTICES APPLIED TO TECNADYNE DC BRUSHLESS MOTORS
1/5/2006 Page 1 of 6 GENERAL POWER SYSTEM WIRING PRACTICES APPLIED TO TECNADYNE DC BRUSHLESS MOTORS 1. Introduction The purpose of this application note is to describe some common connection and filtering
Diode Applications. by Kenneth A. Kuhn Sept. 1, 2008. This note illustrates some common applications of diodes.
by Kenneth A. Kuhn Sept. 1, 2008 This note illustrates some common applications of diodes. Power supply applications A common application for diodes is converting AC to DC. Although half-wave rectification
EXPERIMENT NUMBER 5 BASIC OSCILLOSCOPE OPERATIONS
1 EXPERIMENT NUMBER 5 BASIC OSCILLOSCOPE OPERATIONS The oscilloscope is the most versatile and most important tool in this lab and is probably the best tool an electrical engineer uses. This outline guides
Detailed Inverter Specifications, Testing Procedure, and Technical Approach and Testing Application Requirements for the Little Box Challenge
Detailed Inverter Specifications, Testing Procedure, and Technical Approach and Testing Application Requirements for the Little Box Challenge Introduction Thank you for your interest in the Little Box
Use and Application of Output Limiting Amplifiers (HFA1115, HFA1130, HFA1135)
Use and Application of Output Limiting Amplifiers (HFA111, HFA110, HFA11) Application Note November 1996 AN96 Introduction Amplifiers with internal voltage clamps, also known as limiting amplifiers, have
LM1036 Dual DC Operated Tone/Volume/Balance Circuit
LM1036 Dual DC Operated Tone/Volume/Balance Circuit General Description The LM1036 is a DC controlled tone (bass/treble), volume and balance circuit for stereo applications in car radio, TV and audio systems.
Line Reactors and AC Drives
Line Reactors and AC Drives Rockwell Automation Mequon Wisconsin Quite often, line and load reactors are installed on AC drives without a solid understanding of why or what the positive and negative consequences
Lab 3 Rectifier Circuits
ECET 242 Electronic Circuits Lab 3 Rectifier Circuits Page 1 of 5 Name: Objective: Students successfully completing this lab exercise will accomplish the following objectives: 1. Learn how to construct
7-41 POWER FACTOR CORRECTION
POWER FTOR CORRECTION INTRODUCTION Modern electronic equipment can create noise that will cause problems with other equipment on the same supply system. To reduce system disturbances it is therefore essential
SmartPro 230V 3kVA 2.25kW Line-Interactive UPS, Extended Run, SNMP, Webcard, Tower, USB, DB9 Serial
SmartPro 230V 3kVA 2.25kW Line-Interactive UPS, Extended Run, SNMP, Webcard, Tower, USB, DB9 Serial MODEL NUMBER: SMARTINT3000VS Highlights 3kVA / 3000VA / 2250W line interactive tower UPS system 230V
Lab E1: Introduction to Circuits
E1.1 Lab E1: Introduction to Circuits The purpose of the this lab is to introduce you to some basic instrumentation used in electrical circuits. You will learn to use a DC power supply, a digital multimeter
The full wave rectifier consists of two diodes and a resister as shown in Figure
The Full-Wave Rectifier The full wave rectifier consists of two diodes and a resister as shown in Figure The transformer has a centre-tapped secondary winding. This secondary winding has a lead attached
TEST REPORT EN 55014-2 (1997) +A1 (2001)
Page 1 of 23 TEST REPORT EN 55014-2 (1997) +A1 (2001) Electromagnetic compatibility - Requirements for household appliances, electric tools and similar apparatus Part 2: Immunity Report Reference No....
DCS Series 1 kw, 1.2 kw, & 3 kw
DCS Series 1 kw, 1.2 kw, & 3 kw AVAILABLE WITH LXI STANDARD COMPLIANT ETHERNET Applications Automotive Electronics Rackmount ATE System Battery Charging DCS Series DCS Series: 1 kw, 1.2 kw, & 3 kw DCS
Series 427. 1/16 DIN Multi-Mode Bar Graph Display Timer TIMERS PRODUCT HIGHLIGHTS
Series 427 1/16 DIN Multi-Mode Bar Graph Display Timer PRODUCT HIGHLIGHTS Digital Setting with 0.1% Accuracy Unique LED Bargraph Indicates Time Cycle in 20% Increments 8 Field Selectable Modes of Operation
FREJA 300 Relay Testing System
Relay Testing System A Megger Group Company FREJA 300 Relay testing system The FREJA 300 relay testing system is a computer-aided relay testing and simulation system. The weight of FREJA 300 is only 15
SST-ST70F-ESB SST-ST60F-ESB
STRIDER ESSENTIAL SERIES Power for everything you need SST-ST70F-ESB SST-ST60F-ESB High efficiency with 80 PLUS Bronze certification 24/7 continuous power output with 40 operating temperature Class-leading
unit : mm With heat sink (see Pd Ta characteristics)
Ordering number: EN1321E Monolithic Linear IC LA4261 3.5 W 2-Channel AF Power Amplifier for Home Stereos and Music Centers Features. Minimum number of external parts required (No input capacitor, bootstrap
LOW COST MOTOR PROTECTION FILTERS FOR PWM DRIVE APPLICATIONS STOPS MOTOR DAMAGE
LOW COST MOTOR PROTECTION FILTERS FOR PWM DRIVE APPLICATIONS STOPS MOTOR DAMAGE Karl M. Hink, Executive Vice President Originally presented at the Power Quality 99 Conference ABSTRACT Motor protection
CAN bus ESD protection diode
Rev. 04 15 February 2008 Product data sheet 1. Product profile 1.1 General description in a small SOT23 (TO-236AB) Surface-Mounted Device (SMD) plastic package designed to protect two automotive Controller
Design of Bidirectional Coupling Circuit for Broadband Power-Line Communications
Journal of Electromagnetic Analysis and Applications, 2012, 4, 162-166 http://dx.doi.org/10.4236/jemaa.2012.44021 Published Online April 2012 (http://www.scirp.org/journal/jemaa) Design of Bidirectional
FREQUENCY RESPONSE OF AN AUDIO AMPLIFIER
2014 Amplifier - 1 FREQUENCY RESPONSE OF AN AUDIO AMPLIFIER The objectives of this experiment are: To understand the concept of HI-FI audio equipment To generate a frequency response curve for an audio
Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies
Soonwook Hong, Ph. D. Michael Zuercher Martinson Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies 1. Introduction PV inverters use semiconductor devices to transform the
400-800. Series OMEGA WATTS POWER SUPPLY AC/DC SINGLE OR MULTIPLE OUTPUT. Flexible modular design. Programmable outputs** Power factor correction***
INPUT Input protection Thermal protection Switching frequency internal fuse standard 100KHz Input with PFC : (MML400PFC, MML600, MML800) Input voltage range 85*-264VAC Inrush current (peak) MML400PFC
electronics fundamentals
electronics fundamentals circuits, devices, and applications THOMAS L. FLOYD DAVID M. BUCHLA Lesson 1: Diodes and Applications Center-Tapped Full-wave Rectifier The center-tapped (CT) full-wave rectifier
AS2815. 1.5A Low Dropout Voltage Regulator Adjustable & Fixed Output, Fast Response
1.5A Low Dropout oltage Regulator Adjustable & Fixed Output, Fast Response FEATURES Adjustable Output Down To 1.2 Fixed Output oltages 1.5, 2.5, 3.3, 5.0 Output Current of 1.5A Low Dropout oltage 1.1 Typ.
Making Accurate Voltage Noise and Current Noise Measurements on Operational Amplifiers Down to 0.1Hz
Author: Don LaFontaine Making Accurate Voltage Noise and Current Noise Measurements on Operational Amplifiers Down to 0.1Hz Abstract Making accurate voltage and current noise measurements on op amps in
High Power Programmable DC Power Supplies PVS Series
Data Sheet High Power Programmable DC Power Supplies The PVS10005, PVS60085, and PVS60085MR programmable DC power supplies offer clean output power up to 5.1 kw, excellent regulation, and fast transient
Single-phase (220...240 V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable
Features 70.11 70.31 70.41 Electronic voltage monitoring relays for single and three-phase applications Multifunctional types, providing the flexibility of monitoring Undervoltage, Overvoltage, Window
Model 8220. POWER QUALITY ANALYZERS, METERS & LOGGERS Power Quality Meter
Special product features '''' ENERGY METER ''' MEASURES RPM POWER QUALITY ANALYZERS, METERS & LOGGERS Power Quality Meter Model A measurement tool for electrical parameters and distribution network disturbances
AND8480/D. CrM Buck LED Driver Evaluation Board APPLICATION NOTE
CrM Buck LED Driver Evaluation Board Prepared by: Fabien Franc ON Semiconductor Introduction This document describes the CrM Buck LED driver evaluation board. This board provides a step down converter
A Simple Current-Sense Technique Eliminating a Sense Resistor
INFINITY Application Note AN-7 A Simple Current-Sense Technique Eliminating a Sense Resistor Copyright 998 A SIMPE CURRENT-SENSE TECHNIQUE EIMINATING A SENSE RESISTOR INTRODUCTION A sense resistor R S,
VOLTAGE REGULATOR AND PARALLEL OPERATION
VOLTAGE REGULATOR AND PARALLEL OPERATION Generator sets are operated in parallel to improve fuel economy and reliability of the power supply. Economy is improved with multiple paralleled generators by
Evaluation Board for the AAT1275 Boost Converter with USB Power Switch
Introduction EVALUATION BOARD DATA SHEET The AAT1275 evaluation board provides a platform for test and evaluation of the AAT1275 switching boost converter with USB Power Switch. The evaluation board demonstrates
Current and Temperature Ratings
Document 361-1 Current and Temperature Ratings Introduction This application note describes: How to interpret Coilcraft inductor current and temperature ratings Our current ratings measurement method and
Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact
Data sheet Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact The CT-AHD.12 is an electronic time relay with OFF-delay. It is from the CT-D range. With their MDRC profile and a width of only
