Modularity in UPS Design What does it Mean, What are the Pro s and Con s?

Size: px
Start display at page:

Download "Modularity in UPS Design What does it Mean, What are the Pro s and Con s?"

Transcription

1 Modularity in UPS Design What does it Mean, What are the Pro s and Con s? Mike Elms Technical Manager Uninterruptible Power Supplies Ltd

2 Modularity in UPS Design What does it Mean, What are the Pro s and Con s? From Inefficient, Large- Footprint Transformer UPS Standalone UPS Technology Innovation To Efficient, Small-Footprint Transformerless UPS Modular UPS Technology Innovation

3 Modular Definition of Modular? Definition of modular: Adjective Employing or involving a module or modules as the basis of design or construction Oxford English dictionary

4 Modular Interpretation of Definition of Modular? 200kVA N kw 100 kw 33 kw 33 kw 33 kw Redun dant Capaci ty 2 x 200kVA 3 x 100kVA

5 Modular Interpretation of Definition of Modular? Bypass Switch UPS 1 UPS 2 UPS 3 UPS 4

6 Modular Interpretation of Definition of Modular? Power Modules Static Switch Rectifier

7 Modular Interpretation of Definition of Modular? Power Modules Static Switch Rectifier

8 UPS Evolution UPSL Definition of Modular? Bypass input Rectifier input = = = = Critical Load Each module is a complete UPS: IGBT rectifier and inverter Control logic and display Battery converter Static bypass switch

9 UPS Evolution UPSL Definition of Modular?

10 Definition of Modular De-Centralised Parallel Architecture Rectifier input Bypass input Designed to distribute the UPS Hardware and Software into modules in order to reduce the single points of failure Dual feed rectifier / static switch No common static switch No common control logic = Control logic UPS module = Control logic UPS module = Control logic UPS module = = = DISPLAY = = = DISPLAY = = = DISPLAY Output to the critical load

11 Selecting a UPS N System = N = 200 kw UPS = Load

12 200kW 200kW Selecting a UPS N + 1 System Standalone Modular A N + 1 B = = 200kW kw kw 100 kw Load = 200kW A = B = 200 kw Load = 200kW N+1 = 200kW + 200kW N+1 = 200kW + 100kW

13 Load = 200kW Selecting a UPS N + N or 2N System UPS = Load Standalone Modular N N A B = 100 kw 100 kw = A = B = 200 kw 2N = 2 x 200kW 2N = 2 x 200kW

14 Load = 200kW Load = 200kW Load = 200kW Selecting a UPS 2(N+1) System Standalone UPS = Load Modular A N + 1 N + 1 B A B 200 kw 200 kw 200 kw 200 kw = = 150 kw 150 kw 150 kw 150 kw 200 kw 100kW 200 kw 100kW A = B = 200 kw 2(N+1) = 2(200kW + 200kW) 2(N+1) = 2(200kW + 100kW)

15 UPS System Design Criteria Static UPS System: 200kVA N+1 Battery Autonomy: 15 mins

16 200KVA N+1 Standalone Topology (2 x 200kVA) Bypass Switch A B UPS 1 UPS 2 Load = 200kVA A = B = 200 kva

17 200KVA N+1 Standalone Topology (3 x 100kVA) Bypass Switch A B C UPS 1 UPS 2 UPS 3 Load = 200kVA A = B = C = 100 kva

18 200KVA N+1 Standalone Topology (5 x 50kVA) Bypass Switch 50kVA MODULAR UPS 1 50kVA 50kVA 50kVA Load = 200kVA 5 X 50kVA 50kVA

19 200KVA N+1 Modular Topology (3 x 100kVA) Bypass Switch Spare MODULAR UPS 1 Spare 100kVA Load = 200kVA 3 X 100kVA 100kVA 100kVA

20 200KVA N+1 Standalone Battery Options 2 x 200KVA

21 200KVA N+1 Standalone Battery Options 3 x 100KVA

22 200KVA N+1 Standalone Separate Battery Options

23 200KVA N+1 Standalone Separate Battery Options

24 200KVA N+1 Standalone Battery Options Standalone Standalone 200 KVA (N+1) Standalone 200 KVA (N+1) 200KVA 200KVA 100KVA 100KVA 100KVA Battery = 200KVA per unit = 400KVA in total Battery = 100KVA per unit = 300KVA in total

25 200KVA N+1 Standalone Battery Options Modular Battery = 50KVA per unit = 250kvA in total Battery = 100KVA per unit = 300kvA in total

26 200KVA N+1 Standalone Footprint

27 UPS System Design Ease of Repair- Problem off Site! HOT SWAP Service Plan 4 Hour Response Spare Module Defective Module Identified Defective Module Replaced = <30 mins <5 Hours Max Elapsed Time Standalone Service Plan 4 Hour Response Spares Kit Defective UPS Identified Diagnosis & Fix 1, 2 6+ Hours? 10+ Hours? 27

28 UPS System Design Rightsizing oversized power Load curve? start year 1 year 2 year 3 year 4 Modularity in design allows the power protection capacity to be added when needed to meet the existing/actual demand, instead total up front deployment.

29 UPS System Design Hot Swap Modularity Safe Removal and/or Insertion of Modules No Risk to Critical Load No Power Down Required Simple Power Upgrade Right-Sizing to Match Load

30 UPS System Design Low MTTR = High Availability RELIABILITY Measure of ability for a system to run without failures Mean time between failures (MTBF) Mean time to fail (MTTF) SERVICEABILITY The easiness and speed at which maintenance and service can be performed Mean time to repair / recover (MTTR)

31 UPS System Design Low MTTR = High Availability Standalone 6nines % Availability Standalone 2 x 400 kw (1+1) Configuration Modular, 4 x 100 kw (3+1) Configuration Availability = MTBF UPS / (MTBF UPS + MTTR UPS ) MTBF UPS 600,000h 400,000h MTTR UPS 6h 0.5h Availability % (5 Nines) % (6 Nines) 10x Availability Improvement MTBF : Mean Time Between Failures MTTR : Mean Time To Repair

32 Key Points to Take Away 1. Definition of Modular UPS - De-Centralised Parallel Architecture 2. Battery Options for Standalone and Modular Capex and Opex 3. Footprint UPS/Switchgear/Battery System 4. Rightsizing/Scalability/Flexibility 5. Ease of Servicing/Repair = High Availability 6. Modular technology is available for large data centres now, with 100KVA modules and 500KVA building blocks

33 Thank you for your time, any questions? Visit us at Stand L31 & in the Green Data Centre

Modular architecture for high power UPS systems. A White Paper from the experts in Business-Critical Continuity

Modular architecture for high power UPS systems. A White Paper from the experts in Business-Critical Continuity Modular architecture for high power UPS systems A White Paper from the experts in Business-Critical Continuity Abstract Today, more than ever before, energy efficiency and cost-savings are among the top

More information

Data centre experts. Advanced power protection for data centres

Data centre experts. Advanced power protection for data centres Data centre experts Advanced power protection for data centres A robust power protection strategy is critical to successful data centre operations. Uninterruptible Power Supplies Limited (UPSL), a Kohler

More information

An Uninterruptible Power Supply Topology to Manage the Arrival of Big Data Kenny Green

An Uninterruptible Power Supply Topology to Manage the Arrival of Big Data Kenny Green An Uninterruptible Power Supply Topology to Manage the Arrival of Big Data Kenny Green Biography Kenny Green is Technical Support Manager for Uninterruptible Power Supplies Ltd. He is a graduate of Imperial

More information

30-120 3 Phase Modular Finally the benefits of Modular ups are for all

30-120 3 Phase Modular Finally the benefits of Modular ups are for all MUST 30-120 3 Phase Modular UPS Finally the benefits of Modular ups are for all MUST 30-120 MUST means Modular UPS System Three-phase MUST 30-120 is an uninterruptible power supply with double conversion

More information

Standardization and modularity as the foundation of data center UPS infrastructure

Standardization and modularity as the foundation of data center UPS infrastructure ABB White Paper Standardization and modularity as the foundation of data center UPS infrastructure - ABB Power Protection Product Group Doc name: Advantages of modular and standardized UPS Date: 19.11.2013

More information

CEMEP UPS. The high environmental performance solution for power supply to high-availability data centers

CEMEP UPS. The high environmental performance solution for power supply to high-availability data centers CEMEP UPS The high environmental performance solution for power supply to high-availability data centers Exchanges of information and communication needs are growing at an exponential rate. That growth

More information

GAMATRONIC ELECTRONIC INDUSTRIES LTD.

GAMATRONIC ELECTRONIC INDUSTRIES LTD. GAMATRONIC GAMATRONIC ELECTRONIC INDUSTRIES LTD. History In house Activities International Awards Info-Tech 2012 Vendor Landscape Research WORLD REPRESENTATION Modular Solutions Single Phase Power Solutions

More information

UNINTERRUPTIBLE POWER SUPPLIES >9900AUPS UNINTERRUPTIBLE POWER SUPPLIES

UNINTERRUPTIBLE POWER SUPPLIES >9900AUPS UNINTERRUPTIBLE POWER SUPPLIES UNINTERRUPTIBLE POWER SUPPLIES 9900A >9900AUPS UNINTERRUPTIBLE POWER SUPPLIES 9900A The 9900A UPS system uses the most advanced IGBT in both the converter and inverter with Digital Signal Processor (DSP)

More information

Power protection for data centers

Power protection for data centers Power protection for data centers Power protection for data centers Data centers are major power users, with larger installations consuming tens of megawatts. As customers are often highly reliant on the

More information

Diesel Rotary UPS reliability and process availability

Diesel Rotary UPS reliability and process availability Diesel Rotary UPS reliability and process availability Availability in datacenter UPS infrastructures compared Summary The typical characteristics of a DRUPS system are advantageous for the reliability

More information

Product catalog ABB UPS products and solutions Power protection for critical infrastructures

Product catalog ABB UPS products and solutions Power protection for critical infrastructures Product catalog ABB UPS products and solutions Power protection for critical infrastructures Welcome to ABB s Power Protection catalog The number of critical applications that simply cannot be allowed

More information

IT White Paper. N + 1 Become Too Many + 1?

IT White Paper. N + 1 Become Too Many + 1? IT White Paper Balancing Scalability and Reliability in the Critical Power system: When Does N + 1 Become Too Many + 1? Summary Uninterruptible Power Supply (UPS) protection can be delivered through a

More information

GE Digital Energy. TLE Series UPS. 160-400 kw three phase 400 Vac. with best-in-class efficiency. gimagination at work

GE Digital Energy. TLE Series UPS. 160-400 kw three phase 400 Vac. with best-in-class efficiency. gimagination at work GE Digital Energy TLE Series UPS 160-400 kw three phase 400 Vac with best-in-class efficiency gimagination at work GE provides clean, efficient and reliable power for today s digital world with the ultra

More information

Solution Analysis White Paper CHOOSING THE RIGHT UPS FOR SMALL AND MIDSIZE DATA CENTERS: A COST AND RELIABILITY COMPARISON

Solution Analysis White Paper CHOOSING THE RIGHT UPS FOR SMALL AND MIDSIZE DATA CENTERS: A COST AND RELIABILITY COMPARISON Solution Analysis White Paper CHOOSING THE RIGHT UPS FOR SMALL AND MIDSIZE DATA CENTERS: A COST AND RELIABILITY COMPARISON Introduction A dependable uninterruptible power supply (UPS) system is essential

More information

Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager

Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager Introduction There is a growing trend in the UPS industry to create a highly efficient, more lightweight and smaller UPS

More information

Yam Hong 施 耐 德 電 機 亞 太 日 本 區 (APJ) 三 相 關 鍵 電 源 市 場 開 發 經 理. Schneider Electric - Division - Name Date

Yam Hong 施 耐 德 電 機 亞 太 日 本 區 (APJ) 三 相 關 鍵 電 源 市 場 開 發 經 理. Schneider Electric - Division - Name Date Yam Hong 施 耐 德 電 機 亞 太 日 本 區 (APJ) 三 相 關 鍵 電 源 市 場 開 發 經 理 1 Agenda 1 2 3 相 UPS 總 覽 Introduction & Overview of 3 Phase UPS 理 解 客 戶 最 大 的 考 量 點 Understanding Top Customer Concerns 3 Galaxy VM 關 鍵 技 術 創

More information

PX100 MBP with Configurable Distribution

PX100 MBP with Configurable Distribution PX100 MBP with Configurable Distribution High-performance, right-sized, 3-phase power protection with industry-leading efficiency, availability, and performance for small and medium data centers July 2012

More information

UPS Topologies & Architectures. Don Lemmon Tubbesing Solutions (214) 690-6866 don@tubbesing.com

UPS Topologies & Architectures. Don Lemmon Tubbesing Solutions (214) 690-6866 don@tubbesing.com UPS Topologies & Architectures Don Lemmon Tubbesing Solutions (214) 690-6866 don@tubbesing.com Tubbesing Solutions & Tubbesing Solutions Mike Farrell Mobile No. (214) 355-0493 Tubbesing Solutions Portfolio

More information

Alternative data center power

Alternative data center power Alternative data center power A quantitative TCO comparison of 400V AC and 600V AC power systems Abstract Power efficiency has become a critical focus for IT and facilities managers as they struggle to

More information

TLE Series UPS 160-800 kva/kw three phase 400 Vac with best-in-class efficiency

TLE Series UPS 160-800 kva/kw three phase 400 Vac with best-in-class efficiency GE Critical Power TLE Series UPS 160-800 kva/kw three phase 400 Vac with best-in-class efficiency imagination at work GE provides clean, efficient and reliable power for today s digital world with the

More information

Maximizing UPS Availability

Maximizing UPS Availability Maximizing UPS Availability A comparative assessment of UPS designs and deployment configurations for the highavailability data center By Chris Loeffler Product Manager, BladeUPS & Data Center Applications

More information

Variable Frequency Drives - a Comparison of VSI versus LCI Systems

Variable Frequency Drives - a Comparison of VSI versus LCI Systems Variable Frequency Drives - a Comparison of VSI versus LCI Systems Introduction TMEIC is a leader in the innovative design and manufacture of large ac variable f requency drive systems. TMEIC has been

More information

Opportunity of Energy Saving in electrical path is lesser as compared to other areas

Opportunity of Energy Saving in electrical path is lesser as compared to other areas Data Centre Power Map ` Energy Optimization Techniques Data Center Power Chain Venkat Rao B Country Manager Power Products Data Center Power Draws Cooling About 35 40 % Sources of Energy Waste Fans / Blowers

More information

4.0 UPS dedicated to ICT for unmatched energy savings

4.0 UPS dedicated to ICT for unmatched energy savings 4.0 UPS dedicated to ICT for unmatched energy savings Introducing UPSaver by Borri, a new modular UPS series for the ICT industry, totally configurable, quickly scalable, with high efficiency and low TCO.

More information

Trinergy from 200 to 1600 kw. High Power Modular Scalable UPS With Three Dynamic Functioning Modes

Trinergy from 200 to 1600 kw. High Power Modular Scalable UPS With Three Dynamic Functioning Modes Trinergy from 200 to 1600 kw High Power Modular Scalable UPS With Three Dynamic Functioning Modes Emerson Network Power, a division of Emerson, is a global company that combines technology with design

More information

Increased power protection with parallel UPS configurations

Increased power protection with parallel UPS configurations Increased power protection with parallel UPS configurations Making the selection between Centralized Bypass and Distributed Bypass systems Janne Paananen Application Engineer, Large Systems Group Eaton

More information

DISTRIBUTED REDUNDANCY:

DISTRIBUTED REDUNDANCY: DISTRIBUTED REDUNDANCY: MAXIMUM AVAILABILITY AT MINIMAL COST A White Paper by: Liebert Corporation As the need for greater system availability intensifies across virtually every industry from global banking

More information

Smart-UPS 3 Phase And MGE Galaxy 3500

Smart-UPS 3 Phase And MGE Galaxy 3500 Smart-UPS 3 Phase And MGE Galaxy 3500 Presenter: Nick Bobbit, Sr. Technical Trainer Call Information: 877-950-3594 Passcode: Creichwein All content in this presentation is protected 2008 American Power

More information

RIELLO ELETTRONICA. Master HP

RIELLO ELETTRONICA. Master HP RIELLO ELETTRONICA Master HP LOCAL AREA NETWORKS (LAN) SERVERS DATA CENTRES TELECOM- MUNICATIONS DEVICES E-BUSINESS (Servers Farms, ISP/ASP/POP) INDUSTRIAL PROCESSES INDUSTRIAL PLCS ELECTRO- MEDICAL DEVICES

More information

Protect. UPS Solutions for large Data centers

Protect. UPS Solutions for large Data centers Protect Blue UPS Solutions for large Data centers 2 AEG Power Solutions leading through innovative power management Deutsches Technikmuseum, Berlin At the peak of the industrial revolution, founded in

More information

The Pros and Cons of Modular Systems

The Pros and Cons of Modular Systems The Pros and Cons of Modular Systems Kevin Brown, Vice President Global Data Center Offer Schneider Electric Schneider Electric 1 Foundational BUSINESS OVERVIEW Rev 2 Desired characteristics of pre-fabricated

More information

TÓPICOS AVANÇADOS EM REDES ADVANCED TOPICS IN NETWORKS

TÓPICOS AVANÇADOS EM REDES ADVANCED TOPICS IN NETWORKS Mestrado em Engenharia de Redes de Comunicações TÓPICOS AVANÇADOS EM REDES ADVANCED TOPICS IN NETWORKS 2008-2009 Exemplos de Projecto - Network Design Examples 1 Hierarchical Network Design 2 Hierarchical

More information

The Different Types of UPS Systems

The Different Types of UPS Systems The Different Types of UPS Systems By Neil Rasmussen White Paper #1 Revision 5 Executive Summary There is much confusion in the marketplace about the different types of UPS systems and their characteristics.

More information

TOSHIBA G9000 80/100/160/225 kva

TOSHIBA G9000 80/100/160/225 kva CORPORATE OFFICE 13131 WEST LITTLE YORK ROAD HOUSTON, TX 77041 PHONE: (713) 466-0277 (800) 231-1412 FACSIMILE: (713) 896-5226 TOSHIBA G9000 80/100/160/225 kva GUIDE SPECIFICATION THREE PHASE UNINTERRUPTIBLE

More information

Designed for uptime. Defining data center availability via a tier classification system

Designed for uptime. Defining data center availability via a tier classification system Defining data center availability via a tier classification system MIETEK GLIKOWSKI All systems can fail this is a simple fact that every industry must deal with. The paramount concern for the data center

More information

Galaxy VM. Three-phase power protection. schneider-electric.com

Galaxy VM. Three-phase power protection. schneider-electric.com Galaxy VM Three-phase power protection schneider-electric.com 2 schneider-electric.com schneider-electric.com 3 Galaxy VM trusted partner for your business continuity Features and benefits Highly efficient,

More information

Influence of Availability on the Cost Analysis of Solar Powered Data Centers with AC and DC Architecture and Mirroring Functionality

Influence of Availability on the Cost Analysis of Solar Powered Data Centers with AC and DC Architecture and Mirroring Functionality Influence of Availability on the Cost Analysis of Solar Powered Data Centers with and Architecture and Mirroring Functionality Domagoj Talapko, Ph.D. Candidate Emerson Network Power Selska 93, Zagreb,

More information

Power Quality. Uninterruptible Power Supply

Power Quality. Uninterruptible Power Supply Quality Uninterruptible Supply In the electrical system environment, power disturbances will occur. These can be caused by faults on the distribution system, the operation of nearby equipment, lightning

More information

Tender Technical Specification. For Three phase UPS, on line double conversion (VFI) 30 kva 30 kw

Tender Technical Specification. For Three phase UPS, on line double conversion (VFI) 30 kva 30 kw Tender Technical Specification For Three phase UPS, on line double conversion (VFI) 30 kva 30 kw 1 di 14 Index 1 GENERAL REQUIREMENTS... 4 1.1 SUBJECT AND AGREEMENT TYPE... 4 1.2 CONDITIONS... 4 2 GENERALI

More information

Selecting a UPS Topology for your Data Center. by Dr. Daniel Becker, Ph.D., Methode Active Energy Solutions

Selecting a UPS Topology for your Data Center. by Dr. Daniel Becker, Ph.D., Methode Active Energy Solutions Selecting a UPS Topology for your Data Center by Dr. Daniel Becker, Ph.D., Methode Active Energy Solutions Uninterruptible Power Supplies (UPS) are both reaching into new markets and expanding in new ways

More information

ABB PSPS Erich Steinmann; Generator control-2013

ABB PSPS Erich Steinmann; Generator control-2013 ABB PSPS Erich Steinmann; Generator control-2013 GENERATOR CONTROL THE MODULAR SOLUTION FOR GENERATORS To make sure that power is efficiently converted into electric energy, it is necessary to supervise

More information

TLE Series. Product Description. 160-200-320-400 kva / 400Vac / S1 KEY BENEFIT APPLICATIONS FEATURES

TLE Series. Product Description. 160-200-320-400 kva / 400Vac / S1 KEY BENEFIT APPLICATIONS FEATURES TLE Series Product Description 160-200-320-400 kva / 400Vac / S1 KEY BEEFIT High efficiency up to 96.5% in on-line double conversion and 99% in eboost operation mode Unity output power factor; full power

More information

TÓPICOS AVANÇADOS EM REDES ADVANCED TOPICS IN NETWORKS

TÓPICOS AVANÇADOS EM REDES ADVANCED TOPICS IN NETWORKS Mestrado em Engenharia de Redes de Comunicações TÓPICOS AVANÇADOS EM REDES ADVANCED TOPICS IN NETWORKS 2009-2010 Projecto de Rede / Sistema - Network / System Design 1 Hierarchical Network Design 2 Hierarchical

More information

UPS Applications and VRLA Battery Sizing

UPS Applications and VRLA Battery Sizing TECHNICAL BULLETIN 41-7334 UPS Applications and VRLA Battery Sizing 41-7334/0213/CD www.cdtechno.com The uninterruptable power system (UPS) is used to protect critical equipment and processes from the

More information

The Different Types of UPS Systems

The Different Types of UPS Systems White Paper 1 Revision 7 by Neil Rasmussen > Executive summary There is much confusion in the marketplace about the different types of UPS systems and their characteristics. Each of these UPS types is

More information

SMART SHELTER CONTAINER

SMART SHELTER CONTAINER Da ta Ce nt er Total Flexibility and Security in a Modular Data Center Advantages Environmentally Friendly Short Delivery Time Smart Shelter Container (SSC) solution provides a fully functional Data Center

More information

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America 7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer

More information

Series 7400 M (10/20/30/40/60 kva) Maximum Protection For Mission Critical Network Applications. Series 7400 M

Series 7400 M (10/20/30/40/60 kva) Maximum Protection For Mission Critical Network Applications. Series 7400 M Power Protection for Business Critical Continuity Series 7400 M (10/20/30/40/60 kva) Maximum Protection For Mission Critical Network Applications Compact Three-phase UPS with Optimum Load Performance And

More information

A Solar Powered Cellular Base Station

A Solar Powered Cellular Base Station Technical Whitepaper SolarConnect Energy management solution for Base Stations A Solar Powered Cellular Base Station Many people in emerging markets like India live in rural areas with limited access to

More information

GE Consumer & Industrial Power Protection UPS. Uninterruptible Power Supplies. GE imagination at work

GE Consumer & Industrial Power Protection UPS. Uninterruptible Power Supplies. GE imagination at work GE Consumer & Industrial Power Protection UPS Uninterruptible Power Supplies GE imagination at work For more than a century, GE has led the way with innovative technologies and groundbreaking quality initiatives

More information

GE Consumer & Industrial Power Protection. Digital Energy LP Series UPS. Uninterruptible Power Supply 3-30 kva. GE imagination at work

GE Consumer & Industrial Power Protection. Digital Energy LP Series UPS. Uninterruptible Power Supply 3-30 kva. GE imagination at work GE Consumer & Industrial Power Protection Digital Energy LP Series UPS Uninterruptible Power Supply 3-30 kva GE imagination at work For more than a century, GE has led the way with innovative technologies

More information

AC versus DC Power Distribution in the Data Center

AC versus DC Power Distribution in the Data Center AC versus DC Power Distribution in the Data Center November 2013/AT328 by Kristopher Jones Make the most of your energy SM Revision #0 0/00 Summary Introduction... p 3 Background... p 4 Efficiency... p

More information

LIBRA USV-Anlagen von EBT (10-800KVA) LIBRA pro. UPS 10-100 kva three-phase / single-phase 10-800 kva three-phase / three-phase.

LIBRA USV-Anlagen von EBT (10-800KVA) LIBRA pro. UPS 10-100 kva three-phase / single-phase 10-800 kva three-phase / three-phase. LIBRA USV-Anlagen von EBT (10-800KVA) LIBRA pro online UPS 10-100 kva three-phase / single-phase 10-800 kva three-phase / three-phase LOCAL AREA NETWORKS (LAN) INTERNET CENTERS (ISP/ASP/POP) ELECTRO-MEDICAL

More information

Comparing UPS System Design Configurations

Comparing UPS System Design Configurations Comparing UPS System Design Configurations By Kevin McCarthy White Paper #75 Revision 1 Executive Summary There are five main UPS system design configurations that distribute power from the utility source

More information

A COMPARISON OF TYPICAL UNINTERRUPTIBLE POWER SUPPLY (UPS) DESIGNS IN TODAY S MARKETS

A COMPARISON OF TYPICAL UNINTERRUPTIBLE POWER SUPPLY (UPS) DESIGNS IN TODAY S MARKETS A COMPARISON OF TYPICAL UNINTERRUPTIBLE POWER SUPPLY (UPS) DESIGNS IN TODAY S MARKETS October 22, 2010 Authored by: Kevin Binnie, Senior Product Portfolio Manager ALPHA TECHNOLOGIES LTD. Executive Summary

More information

Power and Cooling for VoIP and IP Telephony Applications

Power and Cooling for VoIP and IP Telephony Applications Power and Cooling for VoIP and IP Telephony Applications By Viswas Purani White Paper #69 Executive Summary Voice Over IP (VoIP) deployments can cause unexpected or unplanned power and cooling requirements

More information

Kinetic energy recovery on railway systems with feedback to the grid

Kinetic energy recovery on railway systems with feedback to the grid Kinetic energy recovery on railway systems with feedback to the grid Authors: J.M. ORTEGA, METRO DE BILBAO;S:A: H. IBAIONDO, A. ROMO. INGETEAM TRACTION,S.A. 1. Introduction The increasing concern with

More information

Conceptpower DPA. 10 250 kva. True modular UPS system for critical applications. Modular Three-phase UPS system

Conceptpower DPA. 10 250 kva. True modular UPS system for critical applications. Modular Three-phase UPS system Conceptpower DPA 10 250 kva Modular Three-phase UPS system True modular UPS system for critical applications. continuous power protection availability A UPS designed to meet the needs of today and tomorrow.

More information

Qualitative Analysis of Power Distribution Configurations for Data Centers

Qualitative Analysis of Power Distribution Configurations for Data Centers Qualitative Analysis of Power Distribution Configurations for Data Centers White Paper #4 2007 The Green Grid. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted,

More information

Liebert APM from 30-150 kw. The Compact Row-Based UPS With FlexPower Technology TM

Liebert APM from 30-150 kw. The Compact Row-Based UPS With FlexPower Technology TM Liebert APM from 30-150 kw The Compact Row-Based UPS With FlexPower Technology TM Emerson Network Power, a division of Emerson, is a global company that combines technology with design to supply innovative

More information

LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification

LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification 08/17/12 Rev2 LTR Series General Specification 700 VA to 2.1 KVA 1.0 General LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA General Specification This specification describes the features and

More information

Evaluating the Opportunity for DC Power in the Data Center

Evaluating the Opportunity for DC Power in the Data Center A White Paper from the Experts in Business-Critical Continuity Evaluating the Opportunity for Power in the Data Center by Mark Murrill and B.J. Sonnenberg, Emerson Network Power Summary With data center

More information

Embedded Systems Lecture 9: Reliability & Fault Tolerance. Björn Franke University of Edinburgh

Embedded Systems Lecture 9: Reliability & Fault Tolerance. Björn Franke University of Edinburgh Embedded Systems Lecture 9: Reliability & Fault Tolerance Björn Franke University of Edinburgh Overview Definitions System Reliability Fault Tolerance Sources and Detection of Errors Stage Error Sources

More information

If you already have your SAN infrastructure in place, you can skip this section.

If you already have your SAN infrastructure in place, you can skip this section. Part 1: Configuring the iscsi SAN Infrastructure Our first step will be physically setting up the SAN. If you already have your SAN infrastructure in place, you can skip this section. In this article,

More information

Understanding Delta Conversion Online "Output Power Factor Ratings" - Part 7

Understanding Delta Conversion Online Output Power Factor Ratings - Part 7 Application Note #45 Understanding Delta Conversion Online "Output Power Factor Ratings" - Part 7 Introduction This application note is the seventh in a series on delta conversion theory of operation.

More information

LAP ENERGIA PARA DATACENTERS

LAP ENERGIA PARA DATACENTERS LAP ENERGIA PARA DATACENTERS Latin American Power. CABA, Argentina. 2 UPS INDOOR Latin American Power. CABA, Argentina. ALI ELITE SERIES Line Interactive UPS Tower/19 Rack Mount Versions 19 Rack Mount

More information

Eaton 93PM UPS Where aesthetics meet intelligence.

Eaton 93PM UPS Where aesthetics meet intelligence. Brochure 100 kw Eaton 93PM UPS Where aesthetics meet intelligence. 93PM features and benefits The Eaton 93PM UPS combines unprecedented and reliability with eye-catching design. A space-saving, flexible

More information

NO-BREAK KS 7e. Concentrated Energy. 2750 kva (50Hz) 3000 kva (60Hz) DIESEL ROTARY UNINTERRUPTIBLE POWER SUPPLY SYSTEM

NO-BREAK KS 7e. Concentrated Energy. 2750 kva (50Hz) 3000 kva (60Hz) DIESEL ROTARY UNINTERRUPTIBLE POWER SUPPLY SYSTEM NO-BREAK KS 7e Concentrated Energy e 2750 kva (50Hz) 3000 kva (60Hz) DIESEL ROTARY UNINTERRUPTIBLE POWER SUPPLY SYSTEM Data Centre owners, operators and designers are required to meet ever increasing and

More information

Maintenance Service 1.1 ANNUAL PREVENTIVE MAINTENANCE 1.2 ON-SITE REMEDIAL SERVICES

Maintenance Service 1.1 ANNUAL PREVENTIVE MAINTENANCE 1.2 ON-SITE REMEDIAL SERVICES Maintenance Service Statement of Work 1.0 Executive Summary - 1 - UPS/PDU Advantage Ultra UPS/PDU Advantage Ultra Service Service Table of Contents 1.0 Executive Summary 2.0 Features & Benefits 3.0 Details

More information

The Different Types of UPS Systems

The Different Types of UPS Systems Systems White Paper 1 Revision 6 by Neil Rasmussen Contents Click on a section to jump to it > Executive summary There is much confusion in the marketplace about the different types of UPS systems and

More information

Designing Fault-Tolerant Power Infrastructure

Designing Fault-Tolerant Power Infrastructure Designing Fault-Tolerant Power Infrastructure System Analysis and New Standards Enable Maximization of Operating Dependability for Data Centers & Other Mission Critical Facilities J.F. Christin (Author)

More information

Performing Effective MTBF Comparisons for Data Center Infrastructure

Performing Effective MTBF Comparisons for Data Center Infrastructure Performing Effective MTBF Comparisons for Data Center Infrastructure By Wendy Torell Victor Avelar White Paper #112 Executive Summary Mean Time Between Failure (MTBF) is often proposed as a key decision

More information

Module: Sharepoint Administrator

Module: Sharepoint Administrator Module: Sharepoint Administrator Mode: Classroom Duration: 40 hours This course teaches IT Professionals to design and deploy Microsoft SharePoint 2010. Course Outline: Module 1: Designing a Logical Architecture

More information

How To Upgrade An Hp Power Distribution Rack To A Power Distribution Unit

How To Upgrade An Hp Power Distribution Rack To A Power Distribution Unit Overview Power protection in the data center is critical to maintain up time, and the increased densities in data centers is driving the need for uninterruptible power with increased power density, power

More information

Symmetra PX. Industry-leading efficiency, availability, and performance for small, medium, and large data centers and mission critical environments

Symmetra PX. Industry-leading efficiency, availability, and performance for small, medium, and large data centers and mission critical environments Symmetra PX Scalable from 16 kw to 500 kw Parallel-capable up to 2,000 kw High-performance, right-sized, modular, hot-scalable, three-phase power protection with ultra-high availability and efficiency

More information

> Executive summary. The Role of Isolation Transformers in Data Center UPS Systems. White Paper 98 Revision 0. Contents.

> Executive summary. The Role of Isolation Transformers in Data Center UPS Systems. White Paper 98 Revision 0. Contents. The Role of Isolation Transformers in Data Center UPS Systems White Paper 98 Revision 0 by Neil Rasmussen > Executive summary Most modern UPS systems do not include the internal s that were present in

More information

Design a Phase Interleaving PFC Buck Boost Converter to Improve the Power Factor

Design a Phase Interleaving PFC Buck Boost Converter to Improve the Power Factor International Journal of Innovation and Scientific Research ISSN 2351-8014 Vol. 11 No. 2 Nov. 2014, pp. 445-449 2014 Innovative Space of Scientific Research Journals http://www.ijisr.issr-journals.org/

More information

Three-phase UPS DELPHYS MX from 250 to 900 kva the Mega Power protection up to 5.4 MVA

Three-phase UPS DELPHYS MX from 250 to 900 kva the Mega Power protection up to 5.4 MVA the Mega Power protection up to 5.4 MVA range is capable of a maximum system size of up to 5.4 MVA and specifically designed for demanding Data centre applications such as large DTC of banks / insurances,

More information

Product catalog. Cyberex data center products Overview catalog

Product catalog. Cyberex data center products Overview catalog Product catalog Cyberex data center products Overview catalog 2 Product catalog Cyberex data center products overview World class leader in mission critical power quality products and services About us

More information

SG Series UPS 10-600 kva three phase 400 Vac

SG Series UPS 10-600 kva three phase 400 Vac GE Critical Power SG Series UPS 10-600 kva three phase 400 Vac with ultra-high efficiency eboost TM technology imagination at work From protecting assets such as generators, transmission lines and motors,

More information

AIS 3000 APC AIS 3000 15kVA 208V w/2 Batt. Module Exp. To 4, Start-Up 5X8, Internal Maintenance Bypass

AIS 3000 APC AIS 3000 15kVA 208V w/2 Batt. Module Exp. To 4, Start-Up 5X8, Internal Maintenance Bypass AIS 3000 APC AIS 3000 15kVA 208V w/2 Batt. Module Exp. To 4, Start-Up 5X8, Internal Maintenance Bypass APC AIS 3000, 12 kw / 15 kva,input 208V 3PH / Output 120V, 208V, 208V 3PH, Interface Port DB-9 RS-232,

More information

Electrical Efficiency Modeling for Data Centers

Electrical Efficiency Modeling for Data Centers Electrical Efficiency Modeling for Data Centers By Neil Rasmussen White Paper #113 Revision 1 Executive Summary Conventional models for estimating electrical efficiency of data centers are grossly inaccurate

More information

Is an energy-wasting data center draining your bottom line?

Is an energy-wasting data center draining your bottom line? Abstract Is an energy-wasting data center draining your bottom line? New technology options and power distribution strategies can dramatically reduce the cost and carbon footprint of your data center.

More information

Common mistakes in datacentre planning

Common mistakes in datacentre planning Common mistakes in datacentre planning White Paper Last edited: March 2013 Document Control Document Information Title Author Common mistakes in datacentre planning Nick Ewing This document is based upon

More information

Fuji Electric DC Quick Charger. Comparison of Gen 3 25kW and Gen 2 / Other 50 kw Chargers

Fuji Electric DC Quick Charger. Comparison of Gen 3 25kW and Gen 2 / Other 50 kw Chargers Fuji Electric DC Quick Charger Comparison of Gen 3 25kW and Gen 2 / Other 50 kw Chargers Publication Date: July 2012 Product The Fuji Electric Generation 3 DC Quick Charger features a scalable 12.5 kw

More information

Multi DIALOG MDM/MDT. MDM 10-20kVA single/single-phase and three/single-phase MDT 10-80kVA three/three-phase NETWORK RANGE

Multi DIALOG MDM/MDT. MDM 10-20kVA single/single-phase and three/single-phase MDT 10-80kVA three/three-phase NETWORK RANGE Local Area Networks (LAN) Servers Data centers Internet centers (ISP/ASP/POP) Industrial PLCs EPOS (Electronic Point of Sale) Systems Emergency devices (lights/alarms) Electro-medical devices Telecommunication

More information

Which UPS is right for the job?

Which UPS is right for the job? Which UPS is right for the job? Considerations in choosing standby, line-interactive, double-conversion designs and new high-efficiency, multi-mode capabilities for your data center By Chris Loeffler Data

More information

Parallel UPS configurations Connecting multiple UPS modules for added capacity or redundancy

Parallel UPS configurations Connecting multiple UPS modules for added capacity or redundancy Parallel UPS configurations Connecting multiple UPS modules for added capacity or redundancy By Ed Spears Product Manager, Eaton Power Quality Solutions Operation Abstract Increasingly, organizations are

More information

Argus Technologies Pathfinder10kW to Cordex3.6kW Shelf Replacement Procedure

Argus Technologies Pathfinder10kW to Cordex3.6kW Shelf Replacement Procedure Summary Argus Technologies Pathfinder10kW to Cordex3.6kW Shelf Replacement Procedure This is a general procedure on how to replace Pathfinder 48-10kW shelf with a Cordex 3.6kW shelf. Part Numbers 010-567-20

More information

Smart-UPS 3 Phase And MGE Galaxy 3500

Smart-UPS 3 Phase And MGE Galaxy 3500 Smart-UPS 3 Phase And MGE Galaxy 3500 Presenter: Nick Bobbit, Sr. Technical Trainer Call Info: 800-779-7037 Passcode: Creichwein All content in this presentation is protected 2008 American Power Conversion

More information

White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code. June 2015 Revision 1.5

White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code. June 2015 Revision 1.5 White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code June 2015 Revision 1.5 Shalhevet Bar-Asher; SolarEdge Technologies, Inc. Bill Brooks, PE; Brooks Engineering LLC

More information

GE Digital Energy. SG-CE Series UPS. 60-500 kva three phase 400 Vac Uninterruptible Power Supply (UPS) imagination at work

GE Digital Energy. SG-CE Series UPS. 60-500 kva three phase 400 Vac Uninterruptible Power Supply (UPS) imagination at work GE Digital Energy SG-CE Series UPS 60-500 kva three phase 400 Vac Uninterruptible Power Supply (UPS) imagination at work From protecting assets such as generators, transmission lines and motors, to ensuring

More information

Advanced IT Pro Course for Office SharePoint Server 2007 and SharePoint Services 3.0

Advanced IT Pro Course for Office SharePoint Server 2007 and SharePoint Services 3.0 Advanced IT Pro Course for Office SharePoint Server 2007 and SharePoint Services 3.0 50047: Advanced IT Pro Course for Microsoft Office SharePoint Server 2007 and Windows SharePoint Services 3.0 (5 Days)

More information

How To Switch A Layer 1 Matrix Switch On A Network On A Cloud (Network) On A Microsoft Network (Network On A Server) On An Openflow (Network-1) On The Network (Netscout) On Your Network (

How To Switch A Layer 1 Matrix Switch On A Network On A Cloud (Network) On A Microsoft Network (Network On A Server) On An Openflow (Network-1) On The Network (Netscout) On Your Network ( Software- Defined Networking Matrix Switching January 29, 2015 Abstract This whitepaper describes a Software- Defined Networking use case, using an OpenFlow controller and white box switches to implement

More information

City of Leesburg, Florida I.T. Data Center 130551 APPENDIX A TOSHIBA UPS INFORMATION

City of Leesburg, Florida I.T. Data Center 130551 APPENDIX A TOSHIBA UPS INFORMATION City of Leesburg, Florida I.T. Data Center 130551 APPENDIX A TOSHIBA UPS INFORMATION This Appendix A includes technical documents and specifications for the Toshiba 4200 FA 30 kva Uninterruptable Power

More information

SG Series UPS 10-150 kva. high efficiency systems

SG Series UPS 10-150 kva. high efficiency systems SG Series UPS 10-150 kva high efficiency systems Touching all Areas of the Energy Industry With more than 100,000 employees in over 100 countries, GE s diverse portfolio of products and services is helping

More information

As close to perfection. development and production. Modular data center

As close to perfection. development and production. Modular data center As close to perfection development and production Modular data center August 2014 What is GreenMDC modular data center? Basically it is the modular design construction which is realized by the principle

More information

Wireless Networks and Power Quality

Wireless Networks and Power Quality Will installing wireless networking change my back-up power requirements? What data do I need to know in order to determine my wireless network back-up power requirements? What other issues should I consider

More information

National Grid Your Partner in Energy Solutions

National Grid Your Partner in Energy Solutions National Grid Your Partner in Energy Solutions National Grid Webinar: Enhancing Reliability, Capacity and Capital Expenditure through Data Center Efficiency April 8, 2014 Presented by: Fran Boucher National

More information

Network Power Business Overview. Scott Barbour February 13, 2014

Network Power Business Overview. Scott Barbour February 13, 2014 Network Power Business Overview Scott Barbour February 13, 2014 Network Power Summary 2013 2010 2013 2010 2011 2012 2013 CAGR / Chg. Sales $4.2B $5.1B $5.0B $4.9B 5% EBIT $0.7B $0.6B $0.6B $0.5B (8%) %

More information