1 TLE Series Product Description kva / 400Vac / S1 KEY BEEFIT High efficiency up to 96.5% in on-line double conversion and 99% in eboost operation mode Unity output power factor; full power for critical load without derating (kva=kw) for actual and future IT devices Saving installation space; compact design and true front access for operation and maintenance Excellent dynamic performance and low output voltage distortion with linear and non-linear loads such as IT equipment Redundant Parallel Architecture (RPA ) for reliability, redundancy & scalability. Parallel up to 6 UPS modules Enhanced communication with external BMS and embedded diagnostic software APPLICATIOS Data centers, Server farms: A data center that can t guarantee its customers continuous access to data, won t be in business for long such as Servers (LA, WA,...), Web providers, Data centers Healthcare: Protects critical equipment from power fluctuations and failures. Protect instruments from potentially harmful uncontrolled shutdowns. Industrial systems: Industrial automation equipments and controls systems rely on UPS systems for uninterruptible power to keep the process running Banking & Financial: Financial institutions use advances power quality systems to ensure that important work on personal accounts and large transactions is not lost due to system interruptions Transportation systems: Provide reliable energy to infrastructure, roads, railways, airways, to guarantee safe transportation of people and goods Critical infrastructure: Ensuring continuous and reliable power supply for critical applications, essential for public and private services FEATURES Installation Compact design small footprint Front access for operation and maintenance Input IGBT rectifier sine-wave input and unity power factor Wide voltage-frequency window Common & separate (rectifier+) input mains Output Unity power factor: full active power available for any loads. o derating required for IT applications High output stifness for output sine-wave with nonlear and pulsating loads g imagination at work Battery Multiple batteries brand/technology supported SBM (Superior Battery Managemen) for complete battery check and autonomy control Communication Easy integration with BMS (Bulding Management System) Interface via relay contact, SMP card, Modbus TCP Remote montitoring Integrated diagnostic Embedded Black box for data acquisition and analysis Enhanced service diagnostic Page 1
2 Introduction TLE Series UPS is one of the best performing three-phase UPS systems providing critical power protection for a wide range of applications. The TLE Series operates in VFI mode (Voltage Frequency Independent) and has been developed to satisfy the growing request of high efficiency through an innovative control algorithm with 3-level inverter technology. This innovative product provides best-in-class efficiency in double conversion mode as well as eboost operating mode. TLE Series represent the state of the art in UPS design by the combination of latest power conversion 3- level IGBT technology and key design elements like reliability, efficiency, installation, serviceability and connectivity. Thanks to RPA (Redundant Parallel Architecture) the system power can be expanded by paralleling units or increased in reliability by adding redundant units. Key features reduced switching and filter losses with respect to a standard two level technology. Combined with optimized magnetics, the net result is an ultimate 96.5% efficiency in double conversion. On top of this, the high level of integration and the optimized power layout result in clean commutations with no overvoltages which in turn translate into reduced component stress and increased reliability. Compact design & front access Front access for operation and maintenance are considered as key features in UPS design. This feature results in a limited installation space installation against a wall allowed and easier and fasted intervention by service engineers during maintenance activities. Modular & Draw Out Construction All the sub-assemblies for the TLE Series are designed and assembled to have slide out modular construction that allows fast maintenance and service. Standard Safety and Maintenance Feature TLE Series UPS has standard built in back-feed contactor as well as maintenance switch that avoids external installation of switches or breakers into input distribution panels for providing back-feed protection and maintenance disconnect. Improved Diagnostic and Reliability with new FLEX DSP Every TLE Series UPS incorporates improved diagnostic capabilities with the new FLEX DSP control board that provides capability of waveform capture, diagnostic and trend analysis. The TLE Series is also equipped with special hardware and monitoring capability for limited life components like fans and capacitors. Improved Diagnostic TLE Series new diagnostic features allows to store different wave forms and also provides fan failure detection as well as warning on capacitor life that improves UPS availability and enhances preventive maintenance capabilities. True On-Line Double Conversion VFI-SS-111 Double conversion guarantees the continuity of the output power supply. VFI technology (Voltage and Frequency Independent) avoids the propagation of any input mains disturbances to the critical loads. Total Cost of Ownership eboost technology Saving energy by supplying loads using automatic and protecting loads by transferring critical energy to inverter in case of trouble on input mains such as voltagedrop, black-out, frequency variation, etc. 3-level IGBT technology TLE Series UPS uses a three level technology with an Advanced eutral Point Clamped topology implemented with true Reverse Blocking IGBT. These result in Page 2
3 Efficiency TLE Series UPS are designed to optimize maximum efficiency for all operation modes, ensuring performance up to 96.5% in double conversion and 99% in eboost mode. These performances allow the optimization of ancillary equipment like air cooling, saving also direct and indirect energy costs. TLE series delivers efficiency up to 96.5% in double conversion (VFI) mode and 99% in eboost operating mode eboost technology Energy consumption is a critical issue for IT organizations as their datacentre energy demands continue to grow. Their goal is to reduce cost and keep the datacentre running. IT organizations can reduce energy consumption costs without sacrificing system reliability with GE s eboost technology. e = high efficiency up to 99% Boost= fast transfer to inverter < 2ms eboost operating mode Genset friendly IGBT rectifier guarantees the absence of current harmonics at UPS input as well as unity power factor (PF=1). This ensures compatibility with emergency generators, and limiting the oversizing to vs. UPS rating, reducing so costs and installation space. Output capability TLE Series is designed to supply all critical loads at full power without restriction or downgrades, the basic concept consists in an output active power equal to apparent power (kva = kw). This feature allows to provide full UPS power to critical loads regardless if they have inductive, unity or capacity power factor. Substantially the UPS is designed as critical power supply for actual and future generation of IT equipment. kva = kw UPS power capability chart Page 3
4 Main UPS components Rectifier The rectifier consists of a controlled 3-level IGBT bridge, which converts the 3-phase mains voltage into a controlled and regulated DC-voltage. This regulated DC-voltage is used to supply power to the inverter and to battery charger. Clean input technology IGBT rectifier bridge performs an input sinusoidal current ensuring a limited THDi (Total Current Harmonic Distortion) below 3% with power factor o additional filters to reduce current harmonics or to increase power factor are required. Soft start As standard feature the rectifier employs software control to limit the start-up current and voltage. The load power is applied to the mains gradually, preventing instable conditions for the upstream protection devices and for emergency GenSets regulation. In case of RPA configuration, the different UPS start sequentially. UPS block diagram Superior Output Voltage Dynamic Stiffness High output dynamic voltage stiffness, performing stable and pure sinusoidal voltage with non-linear and pulsating loads. Pure sine-wave output voltage guarantee the proper supply for equipment with critical power circuits without compromising functionality, performances and lifetime of the components. Rectifier input current waveform Input voltage and frequency windows TLE Series UPS are designed for nominal voltage 3x380/400/415V, 50 or 60 Hz. The wide AC input voltage ( V) and frequency (45 66Hz, 50/60Hz ±10%) accepted by the rectifier, avoids battery operation even with an unstable AC input voltage. The energy stored in the battery is so preserved for real critical mains perturbations. The reduced battery charge/ discharge cycles preserve also battery life. Different voltages are accepted by additional adaptation transformer. Hz +10% 50-10% UPS input current after mains recovery Inverter The 3-level IGBT inverter converts the DC-voltage into a three-phase AC-voltage with constant amplitude and frequency, which is completely independent and isolated from the AC-input voltage. Output voltage and frequency The UPS output voltage is set at 3x380/400/415 V + neutral, 50 or 60 Hz. Different output voltages are possible by additional adaptation transformer. Load non-linear current UPS output voltage with non-linear load -15% % V Page 4
5 Bypass The automatic consists of a static semiconductor-switch (SSM: Static Switch Module), used to provide an uninterrupted transfer of the load from inverter to mains and vice-versa. It also transfers the load to input mains in case of overload, load short-circuit, inverter fault condition or based on manual input. During overload and short-circuit, re-transfer to inverter is automatically initiated once normal load conditions are restored. The load can be transferred to provided that the input supply is within the voltage and frequency tolerances (adjustable); otherwise the inverter operates with its internal frequency (free running) and the transfer to mains inhibited. Bypass The manual consists of a pair of manual switches (Q1 and ), which remove the UPS from the load for maintenance, while still supplying the load with power directly from the mains. Back-feed protection TLE Series is equipped, as standard feature, by a back-feed protection tool installed inside the UPS cabinet. The back-feed protection is a safety requirement for servicing personnel, according to IEC (General and Safety Requirements for UPS), realized by an electromagnetic contactor in series with the static switch of the line. It avoids back-feed current, via the automatic, in case of SSM failure during operation in battery mode. This protection works automatically by opening contactor (in series with the thyristors of the static switch) and eventually K7, and acts in case of internal defects of the system, or due to wrong manipulations on the manual. Battery The battery supplies the DC power to the inverter when the mains is missing or out of acceptable tolerances. It is normally sized to supply the inverter at rated load for the required back-up time. TLE Series can operate with different battery technologies Pb sealed (VRLA) Pb vented icd for short to long autonomy time. Superior Battery Management (SBM) The battery system of a UPS is a critical element, which defines system reliability and must be effectively maintained and monitored to ensure optimum reliability and protection of the critical load. To preserve UPS system reliability and battery lifetime, TLE Series provides a battery management feature know as SBM (Superior Battery Management). SBM is a programmable management feature that monitors the battery by periodically testing the battery system. The programmable features of SBM allow the user to select the frequency and type of battery tests that are to be performed. The frequency can range from once a week to once a year and the type of test can range from deep cycle to a short time discharge. All tests are performed automatically with the UPS in normal operation mode. The tests data are logged in the UPS events menu and any failure of the battery system is reported by alarm on the front panel alarm. SBM also gives the user the ability to perform a manual test at any time. True battery autonomy SBM also performs the ability to calculate true battery autonomy and remaining back up time, during a mains outage, based on effective UPS load. Based on real autonomy time, the UPS initiate the shutdown procedure, named stop operation, starting when the remaining time is limited to 3 min. (adjustable) generating an alarm to warn the operator or to start-up the load shut down procedure. Battery voltage compensation Battery floating voltage is compensated according to effective operating temperature; this feature preserve battery from aging do to temperature effects. Fault current back to mains Inv erte r Battery charging/discharging current monitoring via iupsguard Page 5
6 Mimic touch screen display TLE Series UPS is equipped with menu-driven touch screen display panel, easy to read, with UPS status, metering, parameter settings and configuration. This user-friendly display panel provides: Critical measurement of input, output and battery included with mimic diagram Quick operational status Measurement and operational status of RPA system Different access level for user and service Multilanguage communication interface supporting: English, German, Italian, Spanish, French, Finnish, Polish, Portuguese, Czech, Slovakian, Chinese, Swedish, Russian and Dutch Functionality can be programmed to meet customer needs by changing parameters. Integration with BMS TLE Series can be easily integrated into a BMS (Building Management System) by Customer Interface board, RS232 port or SMP card which help to exchange information about the status of the UPS. Serial Port J35μP - RS2332 Total remote management of the system using software GE Power Diagnostics, GE Data Protection or GE Service Software for system protection and management of the UPS systems. Customer Interface board UPS supervision capability RJ45 connector for communication 6 programmable potential free alarm contacts Emergency Power OFF contact Gen-O Input contact Control Input contact The Gen-O contact integrated, allows operating in combination with an external emergency generator by defining the operation mode of the UPS by programmable setting. battery charging enable / disable on generator enable / disable synchronization on generator enabled / disable SMP card This optional SMP (Standard etwork Management Protocol) Plug In Card allows the UPS to communicate over a LA or interface through all major building management systems (BMS). Integrates a modern web server for UPS monitoring via LA, drives remote server shutdown in case of critical UPS alarms and works as Modbus TCP Converter as well as Modbus RTU 485. SMP is available as option. Page 6
7 Operation modes ormal operation mode VFI (Voltage Frequency Independent) Under normal conditions the load is permanently powered by the inverter with constant amplitude and frequency. The rectifier, powered by the mains, supplies the inverter and the battery-charger keeps the battery fully charged. The inverter converts the DC voltage in a new AC sine wave voltage with constant amplitude and frequency independently from the input mains power. eboost operation mode - eboost high efficiency (up to 99%) - fast power transfer (< 2ms) When the eboost operation mode is selected, and the mains power is available, the load is normally powered through the automatic. When the mains voltage is detected out of the prescribed tolerances, the load is automatically transferred to the Inverter. When the mains recovers, the load returns to the automatic after a variable time defined by the control unit. charge r charge r Inv erte r Inv erte r M a nual by p ass eboost TM can be operated in in single and in RPA mode, up to 6 UPS modules in parallel, with all units operating and switching as one through redundant communication bus. Mains failure operation When the mains is no longer within acceptable tolerances, the battery will provide the DC power to the inverter. The inverter will maintain continuous AC power to the load until the battery voltage reaches the lower limit of the Inverter operation capability. During the discharge, the displays shows the estimated time that the battery can support the critical load. Prior to complete battery discharge, the "stop operation" alarm (shutdown imminent) warns the operator that the battery is almost discharged and the UPS is about to shut down. Mains recovery operation As soon as the AC input power recovers, the rectifier will start automatically, supplying DC power to the inverter and recharging the battery. If the inverter was previously shut down due to low battery, the load will be initially supplied by mains through the automatic. When the battery is sufficiently recharged to ensure a minimum time of operation with the present load, the inverter will start automatically and the load will be transferred back to the inverter. charge r Inv erte r Inv erte r In normal operation, the load is supplied by the inverter. When the control system detects a fault in the inverter, an overload condition or a short-circuit condition, the automatic will transfer the critical load to the mains without interruption. When the inverter recovers, or the overload or short-circuit condition is corrected, the load will be automatically transferred back to the inverter. If the UPS is unable to return to normal mode following an automatic transfer to mode, an alarm condition will be initiated. A manual (operator initiated) will not be considered as an alarm condition. The manual circuit consists of manual switches Q1 and, which permit transfer of the load directly to the unconditioned AC power without interruption, leaving the UPS available for maintenance. Frequency converter TLE Series can run as frequency converter 50 to 60 Hz or vice-versa. and manual functions are inhibited, therefore the load cannot be transferred to mains in case of overload, short circuit, or inverter failure. Rectifier charge r Battery charger Battery charge r Inverter Inv erter Inv erte r Page 7
8 Reduntant Parallel Architecture (RPA ) Parallel System Operation Whenever a UPS are applied in mission critical applications, a single unit protection is no longer sufficient. To respond to this requirement for the highest level of reliability, GE developed a redundant-parallel system, known as RPA (Redundant Parallel Architecture), a GE exclusivity. All the inverters equally share the load. Two or more equal power units can be paralleled to increase the output power (paralleling for capacity) or to improve the overall reliability of an UPS system (paralleling for redundancy). The outputs of parallel units are connected to a common power bus, and in normal operation the units connected on the parallel bus share the load equally. The modular concept of TLE Series allows parallel operation of up to 6 units, without using paralleling switchgear, external circuits or common control circuitry. Parallel for power capacity Several units can be paralleled in order to achieve output power greater than the maximum power of a single unit. The maximum total power shared between the paralleled units is equal to the total installed nominal power. In the event of a failure of one unit, the power supplied by the UPS system becomes insufficient and the load will be transferred to the mains source. Parallel units for redundancy The nominal power rating of the n out of n+1 redundant paralleled modules must be equal to or higher than the required load power. The load will be equally shared by the n+1 units connected on the output bus. In case of one of the n+1-paralleled units trip off-line, the remaining (n) modules will supply the load, maintaining conditioned power to the critical load. From this results higher reliability and security for the load plus a higher MTBF (Mean Time Between Failures). RPA features The TLE Series parallel system is designed to provide a complete Redundant Parallel Architecture, and is free from common equipment. ot only the inverters but also the functions are redundant. When one UPS needs maintenance or service, the load is powered by the other units. The redundant communication bus to which all units are connected keeps each unit informed about the status of all the other units. The control panel located on each unit allows controlling and monitoring the status of this unit. System control A high-speed redundant, serial communication bus guarantees the exchange of data and thus the communication between the CPU's of each unit. Each module controls is own function and operational status and communicates with all other modules, in order to act or react if necessary, adapting to the new conditions. Synchronization All units are identical, but one unit is arbitrarily selected as the reference and all the other units synchronize to this unit, which in turn synchronizes to the mains voltage, as long as the latter is within tolerances. In case of reference failure, another unit in the parallel system is automatically chosen to take over the reference role. The input for all the units of the parallel system must be supplied from the same AC source (no phase shift allowed between them). Load sharing On each unit of the parallel system, inverter output voltage and current are measured and applied to a load sharing bus. An eventual difference between the units is therefore automatically equalized. Page 8
9 RPA operation modes ormal operation mode When the system is in normal operation mode, all the rectifiers as well as all the inverters of the installation are operating. The mains supplies the parallelconnected rectifiers. Each rectifier supplies both battery and inverter by converting the mains AC voltage into a DC voltage. All the inverters equally share the load. Inv erte r Inv erte r Rectifier failure Rectifier disturbance mode is recognised by a disturbance in one or more rectifiers. The disturbed rectifier(s) do not supply any energy. Depending on the set-up, defined by the customer, the inverters of those single units having disturbed rectifiers, will draw their energy from the battery or RPA will immediately isolate the disturbed unit. The other installations continue in normal operation mode. All the inverters acting jointly, as described under normal operation mode' sustain the load. Inv erte r Rectifier Inv erte r Bypass mode Bypass mode is triggered when all the available inverters are unable to sustain the load due to overload or due to failure on UPS units. All inverter output contactors (K7) are opened automatically and the inverters, depending on the type of disturbance, continue to operate and the rectifiers continue to charge the batteries. Once the load level returns in normal condition the UPS switch back to normal operation mode. Q4 K7 Q1 Inverter Q4 K7 Q1 Inverter Battery mode A mains failure will trigger battery mode. The rectifiers do not supply any energy. The batteries supply the inverters with the required energy. The inverters supply the load as described under normal operation mode. If the mains do not recover and the batteries are used up, the load will be cut off. In this situation, when the mains recover, the parallel will supply the load. For security reasons, the inverters will have to be switched O manually. Rectifier Inv erte r Inverter disturbance 'Inverter disturbance mode' is triggered by a disturbance in one or more inverters. As long as the output of the remaining single units is sufficient to sustain the load, RPA remains in normal operation mode but the system may become parallel and is no longer redundant. The inverter output contactors (K7) of the disturbed unit open automatically to isolate the disturbed unit from the load. The rectifier of the disturbed unit, depending on the nature of the disturbance, will continue to charge the battery. The disturbed unit can also be completely separated from the mains for service operation. Inv erte r eboost in RPA All the UPS run on eboost supplying the load via the. In case of perturbation on input mains all the UPS switch to normal operation till the normal situation is recovered. Maintenance mode The maintenance mode is used in case, all units are switched off and the system output has to remain powered. One maintenance for each UPS. Maintenance on each UPS subcomponents can be made voltage free. During this mode of operation the load is supplied directly by mains. Rectifier Inverter Battery Rectifier Inv erte r Inverter Rectifier Inverter Battery Page 9
10 Typical connections Single unit - Common input mains Single unit - Separate input mains UPS automatic 3-pole rectifier inverter L1,L2,L3 load 3-pole 3-pole UPS automatic rectifier inverter L1,L2,L3 load battery battery Common input mains for rectifier and (internal bridge). Separate input mains for rectifier and ; increased load reliability by providing two separate energy sources or different input mains paths. Parallel unit (RPA) - Common input mains Parallel unit (RPA) - Separate input mains UPS 1 automatic 3-pole rectifier inverter L1,L2,L3 3-pole 3-pole UPS automatic rectifier inverter L1,L2,L3 battery UPS 2 automatic 3-pole rectifier inverter L1,L2,L3 load 3-pole 3-pole battery UPS 2 automatic rectifier inverter L1,L2,L3 load battery battery Common input mains for rectifier and. Separate input mains for rectifier and. Rectifier can have different power sources while shall have the same sources for all the units in parallel. OTE The UPS is designed for T System. The input neutral shall be grounded at source and shall never be disconnected. 4 pole breaker shall not be used at the UPS input (see also IEC 60364, IEC 61140, IEC 61557). The protection of the UPS mains input must be exclusively with 3 pole breakers. Disconnection of the eutral is not permitted. The UPS needs the connection of the eutral to the input, to guarantee the function in T mode (eutral-earth). Page 10
11 Integrated diagnostic black box Black box far data acquisition and analysis: Waveform capture, diagnostic and trend analysis. Simultaneous acquisition of 32 channels. Sampling frequency up to 10kHz. Smart trigger capability with up to 16 independent trigger sources to record only specific events with pre/post trigger data acquisition. Buffer depth of 1000 samples per channel: each event is recorded for s.f. 10kHz 8 buffers to record up to 8 events, extended with external USB mass storage devices. Software & Connectivity Remote monitoring GE remote monitoring solution is an anytime, anywhere concept in UPS status monitoring and alarm notification supporting all GE UPS product lines. Accessing the latest site information via Web and being alerted by or SMS, it enables the user to make timely decisions in case of changing critical conditions. With comprehensive data collection and analysis it improves diagnostics capability and enhances response time. 24*7 remote access to your UPS data using standard web browser alerting in case of event direct and immediately to you cell phone or by Regularly operational reports with proactive information on critical data Preventative information using PMAD (Preventative Maintenance & Advanced Diagnostics) feature Possibility to reduce intervention and onsite work GE Data protection software GE Data Protection software can communicate with the UPS over RS-232, USB or SMP to receive status information and measurement values of the UPS. In case of a critical condition (time on battery, remaining battery autonomy time or low battery) for the load, the software starts a controlled shutdown. An enhanced alarm management system provides the possibility to start applications, send messages, and send s for every upcoming or disappearing alarm. Page 11
12 Technical Data Page 12
GE Digital Energy. TLE Series UPS. 160-400 kw three phase 400 Vac. with best-in-class efficiency. gimagination at work
GE Digital Energy TLE Series UPS 160-400 kw three phase 400 Vac with best-in-class efficiency gimagination at work GE provides clean, efficient and reliable power for today s digital world with the ultra
More informationTLE Series UPS 160-800 kva/kw three phase 400 Vac with best-in-class efficiency
GE Critical Power TLE Series UPS 160-800 kva/kw three phase 400 Vac with best-in-class efficiency imagination at work GE provides clean, efficient and reliable power for today s digital world with the
More informationSG Series UPS 10-600 kva three phase 400 Vac
GE Critical Power SG Series UPS 10-600 kva three phase 400 Vac with ultra-high efficiency eboost TM technology imagination at work From protecting assets such as generators, transmission lines and motors,
More informationLiebert GXT MT+ CX UPS, 1000VA - 3000VA Intelligent, Reliable UPS Protection. AC Power for Business-Critical Continuity
Liebert GXT MT+ CX UPS, 1000VA - 3000VA Intelligent, Reliable UPS Protection AC Power for Business-Critical Continuity Liebert GXT MT+ CX UPS, 1000VA -3000VA Intelligent, Reliable UPS Protection Liebert
More informationGE Digital Energy. SG-CE Series UPS. 60-500 kva three phase 400 Vac Uninterruptible Power Supply (UPS) imagination at work
GE Digital Energy SG-CE Series UPS 60-500 kva three phase 400 Vac Uninterruptible Power Supply (UPS) imagination at work From protecting assets such as generators, transmission lines and motors, to ensuring
More information4.0 UPS dedicated to ICT for unmatched energy savings
4.0 UPS dedicated to ICT for unmatched energy savings Introducing UPSaver by Borri, a new modular UPS series for the ICT industry, totally configurable, quickly scalable, with high efficiency and low TCO.
More informationGE Digital Energy. SG-CE Series UPS. 60-500 kva three phase 400 Vac Uninterruptible Power Supply (UPS) imagination at work
GE Digital Energy SG-CE Series UPS 60-500 kva three phase 400 Vac Uninterruptible Power Supply (UPS) imagination at work From protecting assets such as generators, transmission lines and motors, to ensuring
More informationMulti DIALOG MDM/MDT. MDM 10-20kVA single/single-phase and three/single-phase MDT 10-80kVA three/three-phase NETWORK RANGE
Local Area Networks (LAN) Servers Data centers Internet centers (ISP/ASP/POP) Industrial PLCs EPOS (Electronic Point of Sale) Systems Emergency devices (lights/alarms) Electro-medical devices Telecommunication
More informationDaker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF
Daker DK 1, 2, 3 kva Manuel d installation Installation manual Part. LE05334AC-07/13-01 GF Daker DK 1, 2, 3 kva Index 1 Introduction 24 2 Conditions of use 24 3 LCD Panel 25 4 Installation 28 5 UPS communicator
More informationTLE Series UPS 225-1500 kw for best-in-class multi-mode operating efficiency
TLE Series UPS 225-1500 kw for best-in-class multi-mode operating efficiency Ensuring Uptime for Critical Processes Mission-critical processes need a power system that is cleaner and more reliable than
More informationGalleon 6-10K Online UPS. Voltronic Power Technology Corporation
Galleon 6-10K Online UPS Voltronic Power Technology Corporation Features Galleon online UPS series delivers optimal power quality, provides superior power management, resolves utility power protection
More informationGE Consumer & Industrial Power Protection. Digital Energy LP Series UPS. Uninterruptible Power Supply 3-30 kva. GE imagination at work
GE Consumer & Industrial Power Protection Digital Energy LP Series UPS Uninterruptible Power Supply 3-30 kva GE imagination at work For more than a century, GE has led the way with innovative technologies
More informationUNINTERRUPTIBLE POWER SUPPLIES >9900AUPS UNINTERRUPTIBLE POWER SUPPLIES
UNINTERRUPTIBLE POWER SUPPLIES 9900A >9900AUPS UNINTERRUPTIBLE POWER SUPPLIES 9900A The 9900A UPS system uses the most advanced IGBT in both the converter and inverter with Digital Signal Processor (DSP)
More informationPowerGem Pro Uninterruptible Power Supply
Uninterruptible Power Supply User-friendly Intelligent Ultra reliable Range The Most Intelligent On-Line Double Conversion Power Protection System The range achieves higher reliability and greater immunity
More information30-120 3 Phase Modular Finally the benefits of Modular ups are for all
MUST 30-120 3 Phase Modular UPS Finally the benefits of Modular ups are for all MUST 30-120 MUST means Modular UPS System Three-phase MUST 30-120 is an uninterruptible power supply with double conversion
More informationLTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification
08/17/12 Rev2 LTR Series General Specification 700 VA to 2.1 KVA 1.0 General LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA General Specification This specification describes the features and
More informationRIELLO ELETTRONICA. Master HP
RIELLO ELETTRONICA Master HP LOCAL AREA NETWORKS (LAN) SERVERS DATA CENTRES TELECOM- MUNICATIONS DEVICES E-BUSINESS (Servers Farms, ISP/ASP/POP) INDUSTRIAL PROCESSES INDUSTRIAL PLCS ELECTRO- MEDICAL DEVICES
More informationAPC Smart-UPS RT. GUIDE SPECIFICATIONS FOR 3000VA, 5000VA and 6000 VA Smart-UPS RT 230VAC Uninterruptible Power Supply
APC Smart-UPS RT GUIDE SPECIFICATIONS FOR 3000VA, 5000VA and 6000 VA Smart-UPS RT 230VAC Uninterruptible Power Supply PART 1 - GENERAL 1.1 SUMMARY A. This specification describes the operation and functionality
More informationTransformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager
Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager Introduction There is a growing trend in the UPS industry to create a highly efficient, more lightweight and smaller UPS
More informationon-line LOCAL AREA NETWORKS (LAN) SERVERS DATA CENTERS internet centers (isp/asp/pop) industrial plcs industrial applications
ZP110 on-line UPS 1, 2, 3, 6, 10kVA single/single phase LOCAL AREA NETWORKS (LAN) SERVERS DATA CENTERS internet centers (isp/asp/pop) industrial plcs Emergency Devices (Lights/Alarms) Electro-Medical Devices
More informationLAP ENERGIA PARA DATACENTERS
LAP ENERGIA PARA DATACENTERS Latin American Power. CABA, Argentina. 2 UPS INDOOR Latin American Power. CABA, Argentina. ALI ELITE SERIES Line Interactive UPS Tower/19 Rack Mount Versions 19 Rack Mount
More informationLIBRA USV-Anlagen von EBT (10-800KVA) LIBRA pro. UPS 10-100 kva three-phase / single-phase 10-800 kva three-phase / three-phase.
LIBRA USV-Anlagen von EBT (10-800KVA) LIBRA pro online UPS 10-100 kva three-phase / single-phase 10-800 kva three-phase / three-phase LOCAL AREA NETWORKS (LAN) INTERNET CENTERS (ISP/ASP/POP) ELECTRO-MEDICAL
More informationTender Technical Specification. For Three phase UPS, on line double conversion (VFI) 30 kva 30 kw
Tender Technical Specification For Three phase UPS, on line double conversion (VFI) 30 kva 30 kw 1 di 14 Index 1 GENERAL REQUIREMENTS... 4 1.1 SUBJECT AND AGREEMENT TYPE... 4 1.2 CONDITIONS... 4 2 GENERALI
More informationDC UPS. RTB.e 50-1000 A. IMB.e/ITB.e 5-200 kva. E2001.e/E3001.e 5-200 kva. Input voltage: 110/125/220 Vdc. 115/120/230 Vac, 1-phase (IMB.
Oil & Gas Energy Catalogue DC UPS RTB.e 50-1000 A 3 phase rectifier battery chargers voltage: 400 Vac, 3-phase, 50/60 Hz voltage: 24/48/110/220 Vdc RMB.e/RCB.e 50-100-150 A 1 and 3 phase compact rectifier
More informationSG Series UPS 10-150 kva. high efficiency systems
SG Series UPS 10-150 kva high efficiency systems Touching all Areas of the Energy Industry With more than 100,000 employees in over 100 countries, GE s diverse portfolio of products and services is helping
More informationLiebert APM from 30-150 kw. The Compact Row-Based UPS With FlexPower Technology TM
Liebert APM from 30-150 kw The Compact Row-Based UPS With FlexPower Technology TM Emerson Network Power, a division of Emerson, is a global company that combines technology with design to supply innovative
More informationThree-phase UPS DELPHYS MX from 250 to 900 kva the Mega Power protection up to 5.4 MVA
the Mega Power protection up to 5.4 MVA range is capable of a maximum system size of up to 5.4 MVA and specifically designed for demanding Data centre applications such as large DTC of banks / insurances,
More informationTough Decision: On-Line or Line-Interactive UPS?
W H I T E P A P E R Tough Decision: On-Line or Line-Interactive UPS? How to Choose the Right Protection for Your Network Executive Summary In today s data-driven, technology-dependent world, no organization
More informationMGE Galaxy 7000. 160/200/250/300/400/500 kva Power efficiency for business continuity
MGE Galaxy 7000 160/200/250/300/400/500 kva Power efficiency for business continuity Performance three-phase power protection with high adaptability to meet the unique requirements of medium to large data
More informationGalaxy VM. Three-phase power protection. schneider-electric.com
Galaxy VM Three-phase power protection schneider-electric.com 2 schneider-electric.com schneider-electric.com 3 Galaxy VM trusted partner for your business continuity Features and benefits Highly efficient,
More informationEaton 93PM UPS Where aesthetics meet intelligence.
Brochure 100 kw Eaton 93PM UPS Where aesthetics meet intelligence. 93PM features and benefits The Eaton 93PM UPS combines unprecedented and reliability with eye-catching design. A space-saving, flexible
More informationGalaxy 7000: Unitary Specification guide: Single UPS, three-phase, 160 to 500 kva
Galaxy 7000: Unitary Specification guide: Single UPS, three-phase, 160 to 500 kva 1. UPS definition... 2 1.1. Purpose... 2 1.2. Brief description... 2 2. Operating principles... 2 2.1. Normal operation...
More informationThe Quest for Energy Efficiency. A White Paper from the experts in Business-Critical Continuity
The Quest for Energy Efficiency A White Paper from the experts in Business-Critical Continuity Abstract One of the most widely discussed issues throughout the world today is the rapidly increasing price
More informationD. Infrared scanning reports with pictures printed in a final report with any deficiencies and actions taken to rectify.
SECTION 263354 STATIC UPS TESTING AND COMMISSIONING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes 1. System start-up services. 2. Battery charging. 3. Load bank testing. 4. Battery load testing. 5.
More informationPRODUCT PRESENTATION PROTECT B.PRO YEAR 2013 NOVEMBER 2012 DATA & IT, SBU C-UPS, PM/SR
PRODUCT PRESENTATION PROTECT B.PRO YEAR 2013 NOVEMBER 2012 DATA & IT, SBU C-UPS, PM/SR CLASSIFICATION CLASSIFICATION ACC. TO - AEG S UPS PRODUCT PORTFOLIO - IT S APPLICATION ORIENTED USE - UPS PRODUCT
More informationTOSHIBA G9000 80/100/160/225 kva
CORPORATE OFFICE 13131 WEST LITTLE YORK ROAD HOUSTON, TX 77041 PHONE: (713) 466-0277 (800) 231-1412 FACSIMILE: (713) 896-5226 TOSHIBA G9000 80/100/160/225 kva GUIDE SPECIFICATION THREE PHASE UNINTERRUPTIBLE
More informationAPC Matrix-UPS 5kVA 208V/240V In 120/208/240V Out
APC Matrix-UPS 5kVA 208V/240V In 120/208/240V Out APC Matrix-UPS, 3750 Watts / 5000 VA,Input 208V / Output 120V, 208V, Interface Port DB-9 RS-232, SmartSlot, Extended runtime model Includes: CD with software,
More informationCity of Leesburg, Florida I.T. Data Center 130551 APPENDIX A TOSHIBA UPS INFORMATION
City of Leesburg, Florida I.T. Data Center 130551 APPENDIX A TOSHIBA UPS INFORMATION This Appendix A includes technical documents and specifications for the Toshiba 4200 FA 30 kva Uninterruptable Power
More informationUninterruptible Power Supply
96-01101 / rev. 2e / 2-2-12 Uninterruptible Power Supply EXCEPTIONAL SUPPORT & PROTECTION Uninterruptible Power Supply with Energy Saver design that is optimized to address the needs of A/V systems Features
More informationTechnical Data. back-up time in minutes 100% load 6 7 0 5 6 0 5 0 50% load 15 18 0 15 16 0 15 0
The protectoq is a On-Line double conversion UPS-system according to IEC / EN 62040-3 (VFI-SS-111) with sinus wave output voltage in each operation mode, LCDindication, RS232 interface, USB-connection,
More informationSmartOnline 200-240V 6kVA 4.2kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 6U Rack/Tower, DB9 Serial, Hardwire
SmartOnline 200-240V 6kVA 4.2kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 6U Rack/Tower, DB9 Serial, Hardwire MODEL NUMBER: SU6000RT3UHV Highlights 6000VA / 6kVA / 4200W on-line double-conversion
More informationOpportunity of Energy Saving in electrical path is lesser as compared to other areas
Data Centre Power Map ` Energy Optimization Techniques Data Center Power Chain Venkat Rao B Country Manager Power Products Data Center Power Draws Cooling About 35 40 % Sources of Energy Waste Fans / Blowers
More informationThyristor-controlled power supplies and battery chargers
Thyristor-controlled power supplies and battery chargers Input voltage: 115 / 230 VAC, single phase, 50 / 60 Hz or 208 / 400 / 480 VAC, three phases, 50 / 60 Hz Output voltage: 12 / 24 / 48 / 60 / 72 /
More informationLiebert NXC from 10 to 200 kva
Liebert NXC from 10 to 200 kva Emerson Network Power, a division of Emerson, is a global company that provides a unique combination of industry expertise, technology, and resources to make the future of
More informationSG Series UPS 225-750 kva. with ultra-high efficiency eboost technology
SG Series UPS 225-750 kva with ultra-high efficiency eboost technology Touching all Areas of the Energy Industry With more than 100,000 employees in over 100 countries, GE s diverse portfolio of products
More informationTrinergy from 200 to 1600 kw. High Power Modular Scalable UPS With Three Dynamic Functioning Modes
Trinergy from 200 to 1600 kw High Power Modular Scalable UPS With Three Dynamic Functioning Modes Emerson Network Power, a division of Emerson, is a global company that combines technology with design
More informationAPC Smart-UPS RT. GUIDE SPECIFICATIONS FOR 15kVA and 20kVA Smart-UPS RT 230VAC Uninterruptible Power Supply
APC Smart-UPS RT GUIDE SPECIFICATIONS FOR 15kVA and 20kVA Smart-UPS RT 230VAC Uninterruptible Power Supply PART 1 - GENERAL 1.1 SUMMARY A. This specification describes the operation and functionality of
More informationSmartOnline Expandable Rack / Tower UPS System Online, double-conversion protection for mission critical applications
SmartOnline Expandable Rack / Tower UPS System Online, double-conversion protection for mission critical applications Model #: SU3000RTXL3U 3000VA online 3U rack / tower UPS Enhanced serial communications
More informationAlways On UPS Systems Inc., #100-150 Campion Road, Kelowna, BC Canada V1X 7S8
Door Mount UPS (Patent Pending) Shelf Mount UPS (Patent Pending) DESCRIPTION: The Always On NDM (door mount) and NSM (shelf mount) Series UPS s are dual conversion online UPS systems provided in slim,
More informationSpecification guide no. 9 Active harmonic conditioner from 20 to 480 A
Active harmonic conditioner from 20 to 480 A Contents 1 - Installations concerned... 2 1.1 - New installations... 2 1.2 - Existing installations... 2 2 - General... 2 2.1 - Scope... 2 2.2 - Applicable
More informationThe UPS for the highest security in industry and data centres
The UPS for the highest security in industry and data centres P R E M I U M 6,000-20,000VA T E C H N O L O G Y www.online-usv.de Perfect: The ultimate protection against blackout and data loss The new
More informationCEMEP UPS. The high environmental performance solution for power supply to high-availability data centers
CEMEP UPS The high environmental performance solution for power supply to high-availability data centers Exchanges of information and communication needs are growing at an exponential rate. That growth
More informationSmartOnline 200-240V 5kVA 4.5kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 4U Rack/Tower, USB, DB9 Serial
SmartOnline 200-240V 5kVA 4.5kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 4U Rack/Tower, USB, DB9 Serial MODEL NUMBER: SU5000RT4UHV Description Tripp Lite SU5000RT4UHV 5000VA / 5kVA /
More informationABB PV + Storage REACT-3.6/4.6-TL 3.6 to 4.6 kw
Solar inverters ABB PV + Storage REACT-3.6/4.6-TL 3.6 to 4.6 kw PV energy, combined with energy storage systems, can help increase self-consumption and energy selfsufficiency*. One of the biggest challenges
More informationSpecification Requirements DBL 700MX and 1000MX Series UPS
Specification Requirements DBL 700MX and 1000MX Series UPS Theory of Operation Upon loss of utility power, the UPS inverter shall continue to provide seamless pure sine-wave AC from the batteries without
More informationPower Quality. Uninterruptible Power Supply
Quality Uninterruptible Supply In the electrical system environment, power disturbances will occur. These can be caused by faults on the distribution system, the operation of nearby equipment, lightning
More informationIncreased power protection with parallel UPS configurations
Increased power protection with parallel UPS configurations Making the selection between Centralized Bypass and Distributed Bypass systems Janne Paananen Application Engineer, Large Systems Group Eaton
More informationTURBOtech srl. SED-635 Digital Excitation System. Industrial Electronics Sector FEATURES
SED-635 Digital Excitation System SED-635 is a complete excitation system capable of adapting to control synchronous generators of any size. The integration of the TOUCH SCREEN operator interface and a
More informationModular architecture for high power UPS systems. A White Paper from the experts in Business-Critical Continuity
Modular architecture for high power UPS systems A White Paper from the experts in Business-Critical Continuity Abstract Today, more than ever before, energy efficiency and cost-savings are among the top
More informationBack-UPS 650 VA 120 V with AVR (BX650CI-LM)
Back-UPS 650 VA 120 V with AVR (BX650CI-LM) Overview Do not install the unit in direct sunlight, in areas of excessive heat or humidity, or in contact with fluids ON/OFF button Battery connector Circuit
More informationTECHNICAL SPECIFICATIONS FOR 1.5 KVA ONLINE UPS
Capacity Technology Inverter Technology Noise Level Operating Temperature Humidity Harmonic Distortion Total DC bus voltage Battery recharge time (After Complete discharge) to 100% charge Crest Factor
More informationTop 12 Questions to Consider When Choosing UPS Systems for Network/Server Applications
W H I T E P A P E R Top 12 Questions to Consider When Choosing UPS Systems for Network/Server Applications Executive Summary One of the fundamental decisions in the design of data centers, server rooms
More informationSECTION 16260 STATIC UNINTERRUPTIBLE POWER SUPPLY SYSTEM
1 0 1 0 1 SECTION 0 PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Uninterruptible power supply (UPS) system. B. Related Sections include but are not necessarily limited to: 1. Owner s - Bidding
More informationSmartPro 230V 3kVA 2.25kW Line-Interactive UPS, Extended Run, SNMP, Webcard, Tower, USB, DB9 Serial
SmartPro 230V 3kVA 2.25kW Line-Interactive UPS, Extended Run, SNMP, Webcard, Tower, USB, DB9 Serial MODEL NUMBER: SMARTINT3000VS Highlights 3kVA / 3000VA / 2250W line interactive tower UPS system 230V
More informationInstallation and Operation Manual Back-UPS BX800CI-AS/BX1100CI-AS
+ Installation and Operation Manual Back-UPS BX800CI-AS/BX1100CI-AS Inventory Safety and General Information bu001c This unit is intended for indoor use only. Do not operate this unit in direct sunlight,
More informationAPC Smart-UPS RT. GUIDE SPECIFICATIONS FOR 1000VA, 2000VA & 3000VA Smart-UPS RC 230VAC Uninterruptible Power Supply
APC Smart-UPS RT GUIDE SPECIFICATIONS FOR 1000VA, 2000VA & 3000VA Smart-UPS RC 230VAC Uninterruptible Power Supply PART 1 - GENERAL 1.1 SUMMARY A. This specification describes the operation and functionality
More informationSchneider Electric GALAXY VM Data Center Grade Three Phase Uninterruptible Power Supply Guide Specifications 160-200 kva UPS
Schneider Electric GALAXY VM Data Center Grade Three Phase Uninterruptible Power Supply Guide Specifications 160-200 kva UPS THIS GUIDE SPECIFICATION IS WRITTEN IN ACCORDANCE WITH THE CONSTRUCTION SPECIFICATIONS
More informationSeries 7400 M (10/20/30/40/60 kva) Maximum Protection For Mission Critical Network Applications. Series 7400 M
Power Protection for Business Critical Continuity Series 7400 M (10/20/30/40/60 kva) Maximum Protection For Mission Critical Network Applications Compact Three-phase UPS with Optimum Load Performance And
More informationExecutive Summary. Technical Description
Executive Summary The Cellwatch system is built using modules. The majority of the system is constructed with Data Collection Modules (DCMs). The DCMs are optically linked to Control Units (CUs) that in
More informationOptions and monitoring
Additional outlets Energy distribution unit with two Schuko-outlets and four IEC-outlets. Rackmount module version with a height of 2 units. Parallel Distribution Box with Bypasss A compact distribution
More informationProduct Description Full Voltage Starting Electric Fire Pump Controllers FTA1000
Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Description Firetrol FTA1000 Full Voltage Fire Pump Controllers are intended for use with electric motor driven fi re pumps
More information10000HXL31/15000HXL31/20000HXL31
Table of Contents www.eaton.com/dxups USER MANUAL ON LINE UPS 10000HXL31/15000HXL31/20000HXL31 Uninterruptible Power Supply Table of Contents 1. Brief introduction 1.1 System and model description---------------------------------------------------------------------1
More informationOnline UPS. PowerWalker VFI 1000R/1U
Online UPS PowerWalker VFI 1000R/1U Manual Uninterruptible Power Supply System Table of Contents 1. Important Safety Warning... 1 1-1. Transportation... 1 1-2. Preparation... 1 1-3. Installation... 1 1-4.
More informationRISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:
Application : RISH Master 3490 DS measures important electrical parameters of Utility (in normal mode) & Generators (in Power back up) in three phase and single phase Network & replaces the multiple analog
More informationYam Hong 施 耐 德 電 機 亞 太 日 本 區 (APJ) 三 相 關 鍵 電 源 市 場 開 發 經 理. Schneider Electric - Division - Name Date
Yam Hong 施 耐 德 電 機 亞 太 日 本 區 (APJ) 三 相 關 鍵 電 源 市 場 開 發 經 理 1 Agenda 1 2 3 相 UPS 總 覽 Introduction & Overview of 3 Phase UPS 理 解 客 戶 最 大 的 考 量 點 Understanding Top Customer Concerns 3 Galaxy VM 關 鍵 技 術 創
More informationNO-BREAK KS 7e. Concentrated Energy. 2750 kva (50Hz) 3000 kva (60Hz) DIESEL ROTARY UNINTERRUPTIBLE POWER SUPPLY SYSTEM
NO-BREAK KS 7e Concentrated Energy e 2750 kva (50Hz) 3000 kva (60Hz) DIESEL ROTARY UNINTERRUPTIBLE POWER SUPPLY SYSTEM Data Centre owners, operators and designers are required to meet ever increasing and
More informationUNINTERRUPTIBLE POWER SUPPLY (UPS)
Your Inspirations. Our Innovations. UNINTERRUPTIBLE POWER SUPPLY (UPS) Protecting Your Data CATALOGUE Revision 0 Table of Contents Table of Contents About Us - Company Profile Online UPS Professional
More informationModel #: SMART2200VS. 2200VA / 2.2kVA line interactive tower UPS. Maintains 120V nominal output over an input range of 79 to 147V
SmartPro VS Tower UPS System Intelligent, line-interactive power management system Model #: SMART2200VS 2200VA / 2.2kVA line interactive tower UPS Maintains 120V nominal output over an input range of 79
More informationVISION UPS UPS PRODUCT CATALOGUE
VISION UPS UPS PRODUCT CATALOGUE 2012 1 VISION UPS Systems S. à r. l. About VISION UPS VISION UPS SYSTEMS S. à r. l. was established in 2003 by the two belgian UPS-specialists Patrick Willems and Ralph
More informationEmergency Power System Services Industrial UPS, Batteries, Chargers, Inverters and Static Switches
Emergency Power System Services Industrial UPS, Batteries, Chargers, Inverters and Static Switches Downtime Is Not An Option The industrial uninterruptible power supply (UPS) is the foundation of your
More informationA COMPARISON OF TYPICAL UNINTERRUPTIBLE POWER SUPPLY (UPS) DESIGNS IN TODAY S MARKETS
A COMPARISON OF TYPICAL UNINTERRUPTIBLE POWER SUPPLY (UPS) DESIGNS IN TODAY S MARKETS October 22, 2010 Authored by: Kevin Binnie, Senior Product Portfolio Manager ALPHA TECHNOLOGIES LTD. Executive Summary
More informationUser Manual 1K/2K/3K Online UPS
User Manual 1K/2K/3K Online UPS Uninterruptible Power Supply System Table of Contents 1. Important Safety Warning... 1 1-1. Transportation... 1 1-2. Preparation... 1 1-3. Installation... 1 1-4. Operation...
More informationTheoretical review. Contents
Theoretical review Contents Supplying sensitive loads... 2 Types of electrical disturbances...2 Main disturbances in low-voltage electrical power...3 UPSs... 4 The UPS solution...4 UPS applications...5
More informationChloride 80-NET from 60 to 500 kw. Secure Power for Mission Critical Applications
Chloride 80-NET from 60 to 500 kw Secure Power for Mission Critical Applications Emerson Network Power, a division of Emerson, is a global company that combines technology with design to supply innovative
More informationPMCS. Integrated Energy Management Solution. Unlock the Full Potential of Power Networks Through Integration. Complete Solution. Informed Decisions
PMCS Integrated Energy Management Solution Unlock the Full Potential of Power Networks Through Integration Power Management Control System (PMCS) is a highly customizable, fully integrated end-to-end Energy
More informationIntelligent Power Distribution in the Data Center
Rack Power Intelligent Power Distribution in the Data Center Agenda Data Centre Power UPS Power Distribution Rack Mount PDU s UPS Power problems Configuration Capacity Power Distribution Types of Distribution
More informationIndustrial-Grade UPS System Heavy-duty power protection for harsh industrial environments
Industrial-Grade UPS System Heavy-duty power protection for harsh industrial environments Model #: SM2000RMX Heavy-duty, industrial-grade metal housings Shock and vibration rated to MIL-STD-810D 19 inch
More informationModel #: SMART2200CRMXL
Tripp Lite 1111 West 35th Street Chicago, IL 60609 USA Telephone: +(773) 869 1234 E-mail: saleshelp@tripplite.com Model #: SMART2200CRMXL SmartPro Compact Rackmount UPS System - Precision Protection for
More informationTechnical Comparison of On-line vs. Line-interactive UPS designs
Technical Comparison of On-line vs. Line-interactive UPS designs By Jeffrey Samstad Michael Hoff White Paper #79 Executive Summary UPS systems below 5000VA are available in two basic designs: line-interactive
More informationSmart-UPS APC Smart-UPS 1000VA USB & Serial 230V
Smart-UPS APC Smart-UPS 1000VA USB & Serial 230V APC Smart-UPS, 670 Watts / 1000 VA,Input 230V / Output 230V, Interface Port DB-9 RS-232, SmartSlot, USB Includes: CD with software, Smart UPS signalling
More informationAssembled in Florida, USA.
*some models Assembled in Florida, USA. Check our online UPS section at: www.olinsys.com/ups Descubra nuestra sección online de UPS en: www.olinsys.com/ups UPS Uninterruptible Power Supply / Alimentación
More informationInstallation and Operation Back-UPS 1250, 1300, 1500
Installation and Operation Back-UPS 1250, 1300, 1500 Inventory bu001a Safety and General Information This unit is intended for indoor use only. Do not operate this unit in direct sunlight, in contact with
More informationTechnical Specification Kohler PW 5000/TP
Technical Specification Kohler PW 5000/TP Pioneering solutions for total power protection 2 UPS472-01-01 Kohler PW 5000/TP Technical Specification Dated 17-11-2011 Kohler PW 5000/TP SYSTEM DESCRIPTION
More informationGENERIC REQUIREMENTS FOR UNINTERRUPTIBLE POWER SYSTEMS (UPS) TABLE OF CONTENTS
TR TSY 000757 GENERIC REQUIREMENTS FOR UNINTERRUPTIBLE POWER SYSTEMS (UPS) TABLE OF CONTENTS 1. Introduction.... 1.1 Purpose and Scope 1.2 Organization.. 1.3 Reason for Reissue From Technical Advisory
More informationTRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY
TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY 2 TRACTION NETWORK MONITORING AND PROTECTION SYSTEM Traction network monitoring and protection system,
More informationUser s Manual Before using the inverter, you need to read and save the safety instructions.
User s Manual Before using the inverter, you need to read and save the safety instructions. STI SERIES (STI200, STI300, STI500, STI700, STI1000) Power Frequency Pure Sine Wave Inverter The information
More informationMAJORSINE Power Inverter
MAJORSINE Power Inverter Product Features: 24, 48, 130 V 1 KVA/800 Watts Output 2 KVA/1600 Watts Output 100-120 VAC Range 208-240 VAC Range Standard 19 /23, Pure Sine Wave Output High Low EMI/RFI Emissions
More informationUPS UNINTERRUPTIBLE POWER SUPPLY GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES
UNINTERRUPTIBLE POWER SUPPLY GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES INDEX General characteristics page 4 Modular page 12 Conventional page 32 Line-interactive page 44 Communication
More informationLiebert 80-eXL from 100 to 1200 kw. Enhanced Design and Improved Efficiency
Liebert 80-eXL from 100 to 1200 kw Enhanced Design and Improved Efficiency Emerson Network Power, a division of Emerson, is a global company that combines technology with design to supply innovative solutions
More informationUninterruptible Power Supply
9 315 30 kva -160kVA Uninterruptible Power Supply Operation Manual 164200252 Rev. I ------------------------------------------------------------------------ ------------------------------------------------------------------------
More information