Honorable Mention: Educational Facilities, Existing
|
|
- Buddy Armstrong
- 7 years ago
- Views:
Transcription
1 Honorable ention: Educational Facilities, Existing The dedicated heat recovery chiller (DHR) at the Hamilton Heights Elementary School saved Heat Recovery for School By Thomas H. Durkin, P.E., ember ASHRAE, Alvaro Villalta, P.E. Thirty-three-year-old Hamilton Heights Elementary School in Arcadia, Ind., was not providing an optimal learning environment for its students. So the school district decided to upgrade the HVA system in One of the upgrades was dedicated heat recovery chiller enhanced runaround coils (DERA), which helped the school to increase its ENERGY STAR rating of 40 to 94. The coils also saved 70% more energy and took up less space than conventional runaround coils. About the Authors Thomas H. Durkin, P.E., is..., Alvaro Villalta, P.E., is ASHRAE Journal a s h r a e. o r g arch 2013
2 Reprinting of this proof for distribution or posting on web sites is not permitted. Authors may request from the editor an electronic 2013 file of the ASHRAE published article Technology to reprint or post Award on their website ase once Studies the final version has been published. Figure 1: Boiler and chiller arrangement at Hamilton Heights Elementary School. Old Air Air ooled hiller ondensing Boilers Tunnel HS DHR HR The original 1980 HVA system was heat-only with classroom induction units fed from underfloor primary air tunnels. The classroom induction units were built into bookshelves along the perimeter wall. Gas-fired hot water boilers provided heat. In the mid-1990s, an air-conditioning project was undertaken, and direct-expansion (DX) cooling coils were added to the existing primary air handlers. The classroom induction units were replaced by hot water (HW) fan coil units retrofitted into the existing bookshelves. The existing primary air tunnel supplied summer tempered air at 58 F to 65 F (14 to 18 ). However, unresolved issues from the 1990s renovation remained including temperature degradation of primary air; noise from classroom fan coils; lack of access to the fan coils units for maintenance; lack of adequate cooling; lack of Return Air Supply Air lassroom(s) hiller inimum Flow Valve New Heat Rejection/ Heat Recovery oil Air HR HS Dual oil Purpose oil Tunnel To Building Heat Load From Building Heat Load From Building ooling Load To Building ooling Load Air Supply Fan oil Air lassroom(s) Figure 2: lassroom airflow arrangements at Hamilton Heights Elementary School. Building at a Glance Hamilton Heights Elementary School Location: Arcadia, Ind. Owner: Hamilton Heights School orporation Principal Use: Grades 3 through 6 School Includes: lassrooms, administrative offices Employees/Occupants: 55 staff, 515 students Occupancy: 100% Gross Square Footage: 107,000 onditioned Space: 105,000 ft 2 Substantial ompletion/occupancy: August 2010 temperature control in summer; and inadequate classroom lighting. An HVA upgrade project in 2010 was initiated to improve the classroom environment for children and teachers. The owner s primary objective was an optimal learning environment defined as thermal comfort, indoor air quality, humidity control, low noise levels and appropriate lighting. Energy saving was a secondary objective as was delivering the optimal learning environment in the most cost-effective way. The solution included a dedicated outdoor air system () for ventilation, new classroom fan coils with ducted supply, low temperature (130 F [54 ] maximum) boilers, an air-cooled main chiller and a dedicated heat recovery chiller 1 (DHR) to address the need for summer reheat for humidity control and winter cooling for interior spaces (Figure 1). The existing underground air tunnels were reused for relief air rather than supply air, and new ventilation air supply ducts were run overhead. The delivers room-neutral (72 F [22 ] and dehumidified) air year-round (Figure 2). Design primary airflows for the renovation were 10,000 cfm (4719 L/s) makeup (calculated per ASHRAE Standard ) and 8,000 cfm (3776 L/s) exhaust/relief at each of two units serving the classroom wings. The balance of makeup air allows for building pressurization and general exhaust. Other areas of the facility (gym, media center, cafeteria and offices) are fed from conventional VAV air handlers that were not connected to the makeup/relief arrangement serving the classrooms. The mechanical room spaces and the configuration of the building dictated the size and location of the air handlers. There was not room to install conventional energy recovery devices such as total-energy wheels or air-to-air exchangers. Preliminary layout of an air handler with a conventional runaround coil (RA) per 2012 ASHRAE Handbook HVA Systems, hapter 26.13, would have four coils: runaround, heat- arch 2013 ASHRAE Journal 13
3 2013 Technology Award ase Studies Summer Heat Rejection/ Winter To Atmosphere Heat Rejection/ To Atmosphere Heat Recovery oil Heat Recovery oil HR From Tunnel HS HR HS HR From Tunnel HS HR HS HR Outside To lassroom(s) Outside To lassroom(s) Dual Purpose oil oil Figure 3: and relief air handler piping. Dual Purpose oil oil ing, cooling and reheating. Given the room dimensions, it was not possible to fit the four-coil unit. This dictated a two-coil dedicated outdoor air system () unit with a primary coil that would switch from heating to cooling, and a reheat coil. This plan reused the tunnels but changed their use from supply to relief air. Since the relief air ducts (existing tunnels) terminated in the location of the old primary air handlers, building relief was accomplished by relief air handlers (RAH), one for the north end of the school and another for the south. An energy recovery coil was installed in the RAH similar to a runaround coil but connected to both the building hot water loop (summer) and chilled water loop (winter). This makes the RAH coil a heat rejection coil (summer) and a heat recovery coil (winter) (Figure 3). This configuration does not make operating sense without a heat recovery chiller. Dedicated heat recovery chiller enhanced runaround coils (DERA) increase the heat recovery chiller operating window and create additional opportunities for the dedicated heat recovery chiller (DHR) to contribute to energy savings. Two three-way diverting valves are at each and RAH, and a two-way control valve is at each coil. In summer, the primary coil cools outdoor air to 53 F (12 ), and a reheat coil will raise the temperature to room neutral conditions of 72 F (22 ). The RAH coil heats up the relief airstream (heat rejection) when the efficiency of the DHR is better than the efficiency of the air-cooled main chiller. The boilers are locked out when the RAH is rejecting heat. In cooler temperatures, the three-way valves reverse position, and the primary coil becomes a heating coil. The coil is large enough to do all of the heating duty from 0 F to 72 F ( 18 to 22 ) using low temperature (130 F [54 ] maximum, reset versus outdoor air temperature) heating water. The RAH coil is now a heat recovery (cooling) coil lowering the relief air temperature. The school circulates an engineered heat transfer fluid for freeze protection, and the fluid is common to both heating and cooling loops. The reheat coil in the makeup air unit is always a heating coil, and it can provide supplemental heating in winter, allowing the boiler supply water temperatures to be lowered below the usual hot water reset schedule for additional energy savings. Dual-purpose coils make the unit smaller, and they decrease the fan static that otherwise would be seen from an additional large coil. Energy Efficiency Table 1 shows the cost to deliver 10,000 cfm (4719 L/s) of room neutral air (72 F [22 ] and 50% maximum humidity) with no energy recovery, with a traditional runaround coil and with a dedicated heat recovery chiller enhanced runaround coil. The relief airstream is 8,000 cfm (3776 L/s). Gas is calculated at $1 per therm ($0.009 per J) and a boiler efficiency of 90%. The electric rate is calculated at $0.085 per kwh ($0.024 per J). The heat recovery chiller is calculated to be operating at 120 F (49 ) leaving condenser water and 1.02 kw/ton (0.30 kw/kw). DHR power consumption includes pump power. In these calculations, the capacity of the DHR is limited to the amount of cooling that can be done to the relief airstream (winter) and the amount of heat that can be rejected into the relief airstream in the summer. Annualized for one school year, the energy intensity (kbtu/ft 2 yr [J/(m 2 yr)]) is: No Energy Recovery = ( ); RA = ( ); and 14 ASHRAE Journal ashrae.org arch 2013
4 Reprinting of this proof for distribution or posting on web sites is not permitted. Authors may request from the editor an electronic file of the published article to reprint 2013 or post Technology on their website once Award the final ase version Studies has been published. DERA = (69.377). Any winter cooling needs in the building, such as computer rooms and data centers, would further expand the DHR operating window (Note 3 on Table 1). Likewise, any other summer heating requirements, such as domestic water heating, natatoriums, or VAV reheat for humidity control, would also expand the DHR operating window (Note 2 on Table 1). Both would result in additional savings. The DHR has a heating OP of 4.4 and a combined heating/cooling OP of 7.7. It is noteworthy that the DHR operating as specified will be more efficient (1.02 kw/ton [0.30 kw/kw]) than a conventional air cooled chiller (1.25 kw/ton [(0.36 kw/kw)] at 95 F) most of the cooling hours. When the outdoor air temperatures are below 75 F (24 ), the heat rejection coil at the relief air handler is off, and the DHR is running only to satisfy and building reheat requirements. The boiler HW reset schedule is coordinated with the DHR so that the DHR can run 12 months per year. Unlike most energy recovery systems, the DERA can recover energy during all occupied hours. The school was awarded a 94 ENERGY STAR rating in spring 2012 (Table 2). In addition to the dedicated heat recovery chiller enhanced runaround coils, efficiency improvements include: controls upgrade, condensing boilers, eliminating envelope leakage, sealing of existing ducts, occupancy sensors and ventilation control strategies. Prior to the project, the school s lighting levels were low, an average classroom was at 38 footcandles (409 lux). Lighting throughout the school has been up-graded to T-5 and T-8 technology and now meets ASHRAE/ IESNA Standard (post-renovation classroom levels are 55 footcandles [592 lux]). The gym, the cafeteria and the corridors are now air conditioned (they were not prior). Installation osts Detailed cost estimates of alternates to the dedicated heat recovery chiller enhanced runaround coils were not done prior to design. Table 3 qualitative analysis indicates that the most efficient option dedicated heat recovery chiller enhanced runaround coils would also be least expensive to build, even less expensive than a no energy recovery option. Both the RA and the DHR enhanced version allow for size decrease in the heating plant. Also, the DHR enhanced system allows for tonnage decrease at the main chiller. The DERA No Energy Recovery Runaround oil (RA) DHR Enhanced (DERA) OAT, F HTG * LG * $/hr HTG * LG * kwh $/hr HTG * LG * kwh $/hr / / / / * BH required from boiler/chiller plant; Hot water is available for heating; hilled water is available for cooling. Table 1: Energy and cost top recondition 10,000 cfm (4719 L/s) to room neutral conditions. Hamilton Heights Elementary School Energy Intensity (Source) kbtu/ft 2 yr $/ft 2 yr ENERGY STAR Rating Table 2: Before and after energy performance. Equipment No Energy Recovery RA DERA ain hiller 250 ton 250 ton 200 ton DHR 15 ton 15 ton 50 ton Boilers 4.6 BH 4.2 BH 4.0 BH 3 oils, 9.4 bhp 4 oils, 13.1 bhp 2 oils, 7.2 bhp Fan No oil, 4.0 bhp HR coil, 5.05 bhp HR oil, 5.05 bhp Runaround Loop No Yes No Pumps Table 3: Equipment comparisons. results in less total tonnage since the heat recovery chiller can always contribute, while, in the other two scenarios, the DHR can only run to meet the building reheat requirements. Sometimes It s Not the Engineer s Fault When high utility bills occur or when systems don t perform as anticipated or when there are a lot of comfort complaints, the reason may be envelope issues rather than HVA system issues. Early in the design process, a visible difference in winter frost formations was observed from one end of the roof to the other. This dictated appropriate corrective measure is included in the project scope. The after thermoscan (Figure 4) showed only the windows and doors as identifiable thermo-leaks, and they were all judged to be in good condition given their age. onclusion The mechanical system at Hamilton Heights Elementary School ( with room neutral delivery) requires a sum- arch 2013 ASHRAE Journal 15
5 2013 Technology Award ase Studies mer reheat source for humidity control, and, in that situation, a DHR is the energy-efficient solution. System selections that do not require summer reheat will not find the dedicated heat recovery chiller enhanced runaround coils solution as beneficial. And, of course, comparative costs of gas and electricity will affect the savings. The dedicated heat recovery chiller enhanced runaround coils arrangement offers many benefits in the school s design. It is even more beneficial when the main chiller is air cooled. Where the lack of space limited the heat recovery options, the DHR enhanced runaround coils took less room than a conventional runaround system and than a no energy recovery system. The dedicated heat recovery chiller enhanced runaround coils saved money in all operating hours, including the moderate outdoor temperatures when small differences between inside and outdoor airstream make air-to-air energy recovery devices ineffective. The DRH enhanced version saved 70% more energy than a conventional runaround coil, although it was not as efficient in the coldest weather. This would dictate that future versions have the ability to function as conventional runaround coils in winter, and DHR enhanced runaround coils the rest of the time. Figure 4: Thermoscan image of gym entry. References 1. Durkin, T.H., J.B. Rishel Dedicated heat recovery. ASHRAE Journal 45(10). 16 ASHRAE Journal ashrae.org arch 2013
The next generation of geothermal systems for school buildings
The following article was published in ASHRAE Journal, August 2007. Copyright 2007 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. It is presented for educational purposes
More informationALBUQUERQUE PUBLIC SCHOOLS Facility Design & Construction / Maintenance & Operations
ALBUQUERQUE PUBLIC SCHOOLS Facility Design & Construction / Maintenance & Operations MECHANICAL SYSTEMS DESIGN STANDARDS Appendix A RECOMMENDED HVAC SYSTEMS BY TYPE OF SPACE Matt Higgins Valentin Lucero
More informationPresentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks
Presentation Outline Common Terms / Concepts HVAC Building Blocks Plant Level Building Blocks Description / Application Data Green opportunities Selection Criteria Air Distribution Building Blocks same
More informationUNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01
GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per
More informationInnovent LASER Packaged Fresh Air Conditioning Units
LASER Latent And Sensible Energy Reduction Latent And Sensible Energy Reduction For Outside Air Innovent LASER Packaged Fresh Air Conditioning Units Innovent LASER units provide both sensible and latent
More information2 STEPS TO CONDUCTING YOUR HVAC ASSESSMENT
Presentation Synopsis Heating, Ventilating and Air Conditioning Building Condition Assessment Vancouver, B.C. Prepared for: EPIC Prepared by: Douglas Spratt, P.Eng Douglas Spratt & Associates Ltd. www.dspratt-associates.com
More informationThe main steam enters the building in the basement mechanical room; this is where the condensate line also leaves the building.
MSV: Square Footage: 24,844 No. of Floors: 1 Year Built: 1963 Type of Use: Lounge and dining area open all night for snacks Steam Water-cooled condenser, 50-Ton York unit with a 6 cylinder-reciprocating
More informationExample Retrocommissioning Measure: Opening Throttled Discharge Valves
Opening Throttled Discharge Valves This 21-story building, constructed in 1997, is located in Oregon and contains 589,000 gross square feet of mostly office occupancy. The HVAC system includes six large
More informationSPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP
research journal 2013 / VOL 05.01 www.perkinswill.com SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP ARCHITECTURE AND ENGINEERING OF SUSTAINABLE BUILDINGS Current Trends in Low-Energy HVAC Design
More informationPreliminary Final Proposal
1 Butler Memorial Hospital New Inpatient Tower Senior Capstone Project Mechanical Option Preliminary Final Proposal Mechanical System Re-design and Breadth Topics Butler Memorial Hospital New Inpatient
More informationCreating Efficient HVAC Systems
Creating Efficient HVAC Systems Heating and Cooling Fundamentals for Commercial Buildings Heating, ventilating, and air conditioning (HVAC) systems account for nearly half of the energy used in a typical
More informationnewsletter engineers energy-saving strategies for Water-Source Heat Pump Systems volume 36 2 providing insights for today s hvac system designer
engineers volume 36 2 newsletter providing insights for today s hvac system designer energy-saving strategies for Water-Source Heat Pump Systems from the editor... Water-source heat pump (WSHP) systems
More informationAdvanced Energy Design Guide LEED Strategies for Schools. and High Performance Buildings
Advanced Energy Design Guide LEED Strategies for Schools and High Performance Buildings Today s Presenters Stephen Koontz, LEED AP Energy Services Leader Tampa Bay Trane Allen Irvine General Sales Manager
More informationMEETING AGENDA. Project Administrator:
MEETING AGENDA Project Administrator: To: Ann Green M. Baker, SLCS C. Bullinger, SLCS R. Clark, SLCS Board C. Cox, SLCS S. Dotinga, Granger J. Graham, SLCS J. Gusick, SLCS, Board C. Hanshaw, SLCS Board
More informationHVAC For Schools How to purchase an HVAC system that meets your school s unique requirements and stays within your budget
A PRIMER Educational HVAC For Schools How to purchase an HVAC system that meets your school s unique requirements and stays within your budget Contents: Introduction: The best HVAC system is durable, reliable
More informationCondensing Boiler Efficiency
Condensing Boiler Efficiency Date: July 17, 2012 PRES E NT ED BY DO N L E O NA RDI LE O N A RD I I NC. HV AC T RAI N I N G & C ON SU LT IN G Concepts 1 The current state of evolution in boiler design 2
More informationCURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers
CURBING THE COST OF DATA CENTER COOLING Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers OVERVIEW Compare Cooling Strategies in Free- Standing and In-Building
More informationBuilding Energy Systems. - HVAC: Heating, Distribution -
* Some of the images used in these slides are taken from the internet for instructional purposes only Building Energy Systems - HVAC: Heating, Distribution - Bryan Eisenhower Associate Director Center
More informationHVAC Systems: Overview
HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct
More informationTom Brooke, PE, MBA, CEM tabrooke@embarqmail.com
Tom Brooke, PE, MBA, CEM tabrooke@embarqmail.com Framework, perspective or example in a particular discipline at a given time These four new models are: New and additional, or Updated Today's Paradigm
More informationHEAT RECOVERY FROM CHILLED WATER SYSTEMS. Applications for Heat Reclaim Chillers
HEAT RECOVERY FROM CHILLED WATER SYSTEMS Applications for Heat Reclaim Chillers April 2008 TABLE OF CONTENTS INTRODUCTION... 3 WASTE HEAT SOURCES... 3,4 Capturing Sufficient Heat for Useful Purposes...
More informationREAL OPERATING COST SAVINGS FROM RETRO- COMMISSIONING OPPORTUNITIES FOR SAVINGS IN ACADEMIC MEDICAL CENTERS
REAL OPERATING COST SAVINGS FROM RETRO- COMMISSIONING OPPORTUNITIES FOR SAVINGS IN ACADEMIC MEDICAL CENTERS Ken L. Hansen P.E. University of Nebraska Medical Center hansenkl@unmc.edu 402-559- 5301 402-630-
More informationSelecting the Supply Air Conditions for a Dedicated Outdoor Air System Working in Parallel with Distributed Sensible Cooling Terminal Equipment
AT-01-7-3 Selecting the Supply Air Conditions for a Dedicated Outdoor Air System Working in Parallel with Distributed Sensible Cooling Terminal Equipment Kurt M. Shank Student Member ASHRAE Stanley A.
More informationEnergyPro Building Energy Analysis. Assisted Living Building
EnergyPro Building Energy Analysis Assisted Living Building EnergyPro Building Energy Analysis for an assisted living building Project Scope The purpose of the EnergyPro energy model was to evaluate the
More informationAir Conditioning. The opportunity for energy efficiency. Low cost actions to reduce energy usage now
Fact Sheet #6 Air Conditioning In this fact sheet you will discover: The opportunity for energy efficiency How air conditioning works Low cost actions to reduce energy usage now Investments to reduce costs
More informationMechanical Systems Proposal revised
Mechanical Systems Proposal revised Prepared for: Dr. William Bahnfleth, Professor The Pennsylvania State University, Department of Architectural Engineering Prepared by: Chris Nicolais Mechanical Option
More informationSecond Place: Industrial Facilities or Processes, New
Second Place: Industrial Facilities or Processes, New Photo: Paul Howell Texas Medical Center in Houston is the largest medical center in North America. It has a chilled water system of 160,000 tons. Big
More informationBring the fresh in. Dedicated Outside Air Systems
Bring the fresh in. Dedicated Outside Air Systems The inside story on outside air. On average, we breathe in 3,400 gallons of air each day. Ambient indoor air pollution is a major problem, affecting health
More informationENHANCED LABORATORY HVAC SYSTEM
ENHANCED LABORATORY HVAC SYSTEM INTRODUCTION Since the early 1980's the attention to more energy efficient laboratory designs has been on the rise due to the increase in energy cost and the emergence of
More informationPool Dehumidification Basics
Copyright 2009 Wescor. All rights reserved. Permission granted to reproduce for personal and educational use only. When energy costs were low, many pool owners considered only first cost when choosing
More informationKU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM
KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM AIR HANDLING UNITS... 1 CHILLERS... 2 COOLING TOWERS... 2 CLOSED LOOP COOLERS... 2 MISCELLANEOUS SUPPLY FANS...
More informationCHAPTER 8 HVAC (Heating, Ventilation, and Air-Conditioning)
CHAPTER 8 HVAC (Heating, Ventilation, and Air-Conditioning) Objectives Survey current HVAC system(s), operating procedures, and maintenance schedule. Analyze results of energy audit for HVAC system(s)
More informationElement D Services Heating, Ventilating, and Air Conditioning
PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer
More informationCommissioning - Construction Documents (Page 1 of 6)
Commissioning - Construction Documents (Page 1 of 6) A. General Information Climate Zone: Building Type: Conditioned Area (sf): Reviewer's Name: Reviewer's Agency: Note: Design Review for each system/subsystem
More informationGreenhouse Gas Implications of HVAC Upgrades in Multi-Unit Residential Buildings
Greenhouse Gas Implications of HVAC Upgrades in Multi-Unit Residential Buildings J A NUARY 2015 INTRODUCTION This Research Report explores best practices and approaches for reducing greenhouse gas (GHG)
More informationThe District Energy Manager and Classroom Heating
Mt. Carmel Area School District Energy Conservation Policy Adopted 6/19/06 These guidelines supersede all previous instructions. It is crucial that these energy guidelines be observed in the operation
More informationComponents HVAC General Standards HVAC Guidelines HVAC System Selection Life Cycle Cost Analysis
Components HVAC General System Selection Life Cycle Cost Analysis Outdoor Air Design Values Indoor Air Design Values Outdoor Air Ventilation Welding Ventilation Temperature Control Systems Ductwork HVAC
More informationHVAC Costs. Reducing Building. Building owners are caught between two powerful forces the need to lower energy costs. By Stephen J.
Reducing Building HVAC Costs of site rec By Stephen J. Pargeter Building owners are caught between two powerful forces the need to lower energy costs and the need to meet or exceed outdoor air ventilation
More informationJ O U R N A L. Energy Performance for. Proper Specification of Air Terminal Units Future Climate Impacts on Building Design
Copyright 24, American Society of Heating, Refrigerating & Air-Conditioning Engineers, Inc., 79 Tullie Circle NE, Atlanta, GA. 3329. Reprinted by permission from the September 24 Issue of ASHRAE Journal
More informationLesson 36 Selection Of Air Conditioning Systems
Lesson 36 Selection Of Air Conditioning Systems Version 1 ME, IIT Kharagpur 1 The specific objectives of this chapter are to: 1. Introduction to thermal distribution systems and their functions (Section
More informationULTRA-EFFICIENT HVAC DESIGN AND CONTROL
CASE STUDY ULTRA-EFFICIENT HVAC DESIGN AND CONTROL MAJOR HEATING, VENTILATING AND AIR- CONDITIONING REPLACEMENT AT THE COUNTY OF SAN DIEGO CRIME LAB December 30, 2005 8520 Tech Way, Suite 110 San Diego,
More informationSchool HVAC. Design Manual. Application Guide AG 31-004. Air Cooled Chiller. Chilled Water Pumps. Expansion Tank CHWR CHWS. Make up Water Line Boiler
Application Guide AG 31-004 School HVAC Design Manual Chilled Water Pumps Air Cooled Chiller CHWR HWR Make up Water Line Boiler Expansion Tank CHWS Hot Water Pumps CHWR HWR CHWS HWS CHWR HWR CHWS Unit
More informationDefining Quality. Building Comfort. Precision. Air Conditioning
Defining Quality. Building Comfort. Precision Air Conditioning Today s technology rooms require precise, stable environments in order for sensitive electronics to operate optimally. Standard comfort air
More informationHVAC Simplified Approach Option
HVAC Simplified Approach Option Part I Project Address: City: HVAC System Designer of Record: Date: Zip: Qualification The building is 2 stories or less in height and has a gross floor area is less than
More informationFlexibility, Efficiency In San Antonio Arena
2005, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Reprinted by permission from ASHRAE Journal, (Vol. 47, No. 9, September 2005). This article may not
More informationThe ASHRAE HQ Building Can the energy efficiency of the different mechanical systems really be compared? RESIDENTIAL LIGHT COMMERCIAL COMMERCIAL
The ASHRAE HQ Building Can the energy efficiency of the different mechanical systems really be compared? RESIDENTIAL LIGHT COMMERCIAL COMMERCIAL Technical Article April 2013 The ASHRAE HQ Building Can
More informationDr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida
Optimizing 100% Outside Air Systems with Heat Pipes Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida Introduction To meet increasingly rigorous building codes
More informationElement D Services Heating, Ventilating, and Air Conditioning
Load Calculation Criteria PART 1 - GENERAL 1.01 OVERVIEW A. This section includes requirements for calculating HVAC cooling and heating loads. B. Load calculations must be performed in accordance with
More informationUsing Time-of-Day Scheduling To Save Energy
The following article was published in ASHRAE Journal, May 29. Copyright 29 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. It is presented for educational purposes only.
More informationThe Different Types of Air Conditioning Equipment for IT Environments
The Different Types of Air Conditioning Equipment for IT Environments By Tony Evans White Paper #59 Executive Summary Cooling equipment for an IT environment can be implemented in 10 basic configurations.
More informationAPPLICATION GUIDE. Moisture Management in Waterborne Climate Systems
APPLICATION GUIDE Moisture Management in Waterborne Climate Systems Contents Introduction 3 WBCS Concept 3 Condensation 4 Moisture Sources in the Space 4 Impact of a High Moisture Load 5 Designing to Manage
More informationHOW TO CONDUCT ENERGY SAVINGS ANALYSIS IN A FACILITY VALUE ENGINEERING STUDY
HOW TO CONDUCT ENERGY SAVINGS ANALYSIS IN A FACILITY VALUE ENGINEERING STUDY Benson Kwong, CVS, PE, CEM, LEED AP, CCE envergie consulting, LLC Biography Benson Kwong is an independent consultant providing
More informationBuilding Performance With District Cooling
Reprinting this proof for distribution or posting on web sites is not permitted. Authors may request permission to reprint or post on their web site once the fi nal version has been published. A reprint
More informationfor K-12 School Buildings
Advanced Energy Design Guide for K-12 School Buildings HVAC Section John Murphy Applications Engineer, LEED AP Trane La Crosse, Wisconsin jmurphy@trane.com www.trane.com AEDG-K12 HVAC Subcommittee John
More informationMaximize energy savings Increase life of cooling equipment More reliable for extreme cold weather conditions There are disadvantages
Objectives Increase awareness of the types of economizers currently used for data centers Provide designers/owners with an overview of the benefits and challenges associated with each type Outline some
More informationMULTIZONE APPLICATION OF SOLUTION UNITS
MULTIZONE APPLICATION OF SOLUTION UNITS APPLICATION GUIDE Supersedes: 102.20-AG12 (206) Form: 102.20-AG12 (307) GENERAL Multi-zone heating and air conditioning units offer design and application advantages
More informationAchieving ENERGY EFFICIENCY with Standard Air-Conditioning Units. Mike West, PhD, PE Advantek Consulting, Inc
Achieving ENERGY EFFICIENCY with Standard Air-Conditioning Units Mike West, PhD, PE Advantek Consulting, Inc Standard Air Conditioning Unit Packaged Unit Split System DX (not chilled water) Air-cooled
More informationEnergy Efficiency Analysis for a Multi-Story Commercial Office Building. (LG Multi V Water II Heat Recovery VRF System)
Energy Efficiency Analysis for a Multi-Story Commercial Office Building (LG Multi V Water II Heat VRF System) Commercial Air-Conditioning Engineering Study VRF-ES-BL-001-US 011M05 Executive Summary Contents
More informationDATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER
DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTERS 2009 IT Emissions = Aviation Industry Emissions Nations Largest Commercial Consumers of Electric Power Greenpeace estimates
More informationInternational Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS
International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES
More informationVenice Library Humidity Study. for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205. Report April 13, 2015
for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205 Report April 13, 2015 Moses & Associates, Inc. 2209 NW 40 th Terrace, Suite A Gainesville, FL 32605 FL License EB-0003097
More informationPrinting and Publishing Energy Savings Guide
Printing and Publishing Energy Savings Guide Oregon printing and publishing plants face challenges of rising operating costs, environmental and other regulations, outdated equipment and customer demand
More informationRaising the Bar: A Comparison Study of Iowa s Current and Proposed Energy Code
Raising the Bar: A Comparison Study of Iowa s Current and Proposed Energy Code Julia Gauthier, LEED AP BD+C Jeanne Huntsman, AIA, LEED Green Associate The Weidt Group Raising the Bar Special statements
More informationHeating & Cooling Efficiency
Heating & Cooling Efficiency Advantages of Geothermal HVAC Efficiency Keith Swilley Gulf Power Company Why Gulf Power Promotes Energy Efficiency? Customer Satisfaction Education Help Customers Make Smart
More informationCauses of High Relative Humidity Inside Air Conditioned Buildings. Roger G.Morse AIA, Paul Haas CSP, CIH Morse Zehnter Associates
Causes of High Relative Humidity Inside Air Conditioned Buildings Roger G.Morse AIA, Paul Haas CSP, CIH Morse Zehnter Associates S. FLORIDA AVE. AMBIENT 91 F db / 78 F wb 16,000 HOURS ANNUALLY THAT wb
More informationGlossary of Heating, Ventilation and Air Conditioning Terms
Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment
More informationPOLK STATE COLLEGE CHILLER PLANT EVALUATION WINTER HAVEN, FLORIDA APRIL 2, 2014. C arastro & A ssociates, C&A# 5747
POLK STATE COLLEGE WINTER HAVEN, FLORIDA CHILLER PLANT EVALUATION APRIL 2, 2014 C&A# 5747 C arastro & A ssociates, c o n s u l t i n g e n g i n e e r s inc. 2609 W. De Leon Street, Tampa, Florida 33609
More informationfor Plans Examiners and Building Inspectors
Building Technologies Program HVAC Controls Guide for Plans Examiners and Building Inspectors September 2011 Authors: Eric Makela, PNNL James Russell, PECI Sarah Fujita, PECI Cindy Strecker, PECI Prepared
More informationEnergy Efficiency in Industrial HVAC Systems
Energy Efficiency in Industrial HVAC Systems Heating, ventilation and air conditioning (HVAC) constitutes up to 35 percent of energy used in manufacturing facilities. This fact sheet is geared towards
More informationMechanical Insulation. Hospitals and Schools
Study on Mechanical Insulation in Hospitals and Schools March 1, 2011 Study Mechanical Insulation in Hospitals and Schools G. Christopher P. Crall, P.E. Ronald L. King Executive Summary Mechanical insulation
More informationData Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling
Data Center Design Guide featuring Water-Side Economizer Solutions with Dynamic Economizer Cooling Presenter: Jason Koo, P.Eng Sr. Field Applications Engineer STULZ Air Technology Systems jkoo@stulz ats.com
More informationHEATING, VENTILATION & AIR CONDITIONING
HEATING, VENTILATION & AIR CONDITIONING as part of the Energy Efficiency Information Grants Program Heating and cooling can account for approximately 23 % of energy use in pubs and hotels 1. Reducing heating
More informationSustainable Energy and Resource Saving Concepts for HVAC/Process/Water/Wastewater. Thomas H. (Tom) Durkin, PE Dr. Glenn Krueger, EdD Bob Jacobi
Sustainable Energy and Resource Saving Concepts for HVAC/Process/Water/Wastewater Thomas H. (Tom) Durkin, PE Dr. Glenn Krueger, EdD Bob Jacobi Kankakee Valley High School 25% energy reduction $112,462/Yr
More information85 F 80 F 50% 75 F 70 F 73.0/61.8 45 F 10% Figure 1
Feb. 07 INTRODUCTION: Wrap around heat pipes are air-to-air heat exchangers that are installed in the airstream upstream and downstream of a cooling coil to deliberately reduce the Sensible Heat Ratio
More informationChignecto-Central Regional School Board. Highland Consolidated Middle School. Indoor Air Quality Issues Mechanical Systems
Chignecto-Central Regional School Board Highland Consolidated Middle School Mechanical Systems Prepared by: Neil Van Rossum, P.Eng. CJ MacLellan & Associates Antigonish, Nova Scotia November 2012 CJM File:
More informationEnclosed Football Stadium Design History and Lessons Learned
Enclosed Football Stadium Design History and Lessons Learned Robert L. Towell, P.E., LEED AP, QCxP btowell@cxegroup.com CxE Group LLC St. Louis, Missouri 314-436-6543 With thanks to the St. Louis Convention
More informationHVAC Basic Science - System Capacity
HVAC Basic Science - System Capacity Btu/hour, btu/h, b/h, btuh. btu?? 1 MBH = 1000 btu/hour 1 KBH = 1000 btu/hour 1 ton of cooling= 12,000 btu/hour 1 watt = 3.414 btu/hour 1 kilowatt = 1000 watts = 3,414
More informationEnergy Efficient Homes: Air Conditioning
Energy Efficient Homes: Air Conditioning Quick Facts The average energy bill for a typical single family home in the U.S. is $2,200. Roughly 46 percent of the bill, or $1,012, is spent on heating, ventilation,
More informationComparing Energy Savings of Different VAV Systems
Comparing Energy Savings of Different VAV Systems Prepared By: Martyn Dodd mart@energysoft.com EnergySoft LLC 1025 5th Street, Suite A Novato, CA 94945 415-897-6400 www.energysoft.com Last Modified: March
More informationThe Data Center Dilemma - A Case Study
Second Place: Industrial Facilities or Processes, Existing The TCS data center makes use of white cabinets and reflective surfaces as one method to reduce power for its lights and cooling. Data Center
More informationEnergy-Efficient Laboratory Design
2005, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Reprinted by permission from ASHRAE Journal, (Vol. 47, No. 5, May 2005). This article may not be
More informationEnergy Efficient Homes: Air Conditioning 1
FCS3262 Energy Efficient Homes: Air Conditioning 1 Wendell A. Porter, Hyun-Jeong Lee, and Kathleen C. Ruppert 2 Quick Facts Heating, ventilation and air conditioning accounts for more than 40% of your
More informationNEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES
NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES 8.1 INTRODUCTION Testing, adjusting, and balancing of HVAC systems can best be accomplished by following a series of systematic procedures. The NEBB TAB
More information3/29/2012 INTRODUCTION HVAC BASICS
INTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O HVAC systems or Heating, Ventilating and Air-Conditioning systems control the environment for people and equipment in our facilities.
More informationCOMPARATIVE LIFE-CYCLE ANALYSIS OF ENERGY-EFFICIENCY MEASURES AT TVA S CHATTANOOGA OFFICE COMPLEX: PHASE II RESULTS & FINAL DESIGN
COMPARATIVE LIFE-CYCLE ANALYSIS OF ENERGY-EFFICIENCY MEASURES AT TVA S CHATTANOOGA OFFICE COMPLEX: PHASE II RESULTS & FINAL DESIGN Umesh Atre Innovative Design Inc 850 W Morgan St Raleigh, NC 27603 umesh@innovativedesign.net
More informationHIGH EFFICIENCY RTU. www.reznorhvac.com HIGH EFFICIENCY, PACKAGED SPACE CONDITIONING. DX System IEER> 13.2 Gas Heat Efficiency > 92% Capacities Tons
Capacities 10-25 Tons 100-400 MBH HIGH EFFICIENCY, PACKAGED SPACE CONDITIONING DX System IEER> 13.2 Gas Heat Efficiency > 92% HIGH EFFICIENCY RTU 30-120 kw 3,000-11,550 CFM Comfort Comfort is determined
More informationAnswers to Your Questions from the Webinar
2008 Desert Aire and USA Swimming. Used by permission. Desert Aire & USA Swimming - Aquatics Webinar - Answers to Your Questions Answers to Your Questions from the Webinar Thank you for your interest in
More informationSanta Ana College Central Heating & Cooling
Santa Ana College Central Heating & Cooling Plant Project # 5807 P2S Engineering, Inc. T 562.497.2999 5000 East Spring Street, 8th Floor F 562.497.2990 Long Beach, CA USA 90815-5218 www.p2seng.com Table
More informationSection 2: Estimating Energy Savings and Incentives
Section 2: Estimating Energy Savings and Incentives 2.1 Estimating Energy Savings and Incentives... 2 2.2 Customized Measures - Estimation Software... 2 2.2.1 AC&R I - High Efficiency Chiller... 3 2.2.2
More informationDehumidification Design
Dehumidification Design Using Data-Center Heat Utilizing free heat from a server room was the concept behind an air-handling system in a college-campus building Considerable energy savings are possible
More informationHVAC Processes. Lecture 7
HVAC Processes Lecture 7 Targets of Lecture General understanding about HVAC systems: Typical HVAC processes Air handling units, fan coil units, exhaust fans Typical plumbing systems Transfer pumps, sump
More informationEnergy Efficiency Analysis for a Multi-Story Commercial Office Building. (LG Multi V III Heat Recovery VRF System)
Energy Efficiency Analysis for a Multi-Story Commercial Office Building (LG Multi V III Heat Recovery VRF System) Commercial Air-Conditioning Engineering Study VRF-ES-BK-011-US 011L18 Executive Summary
More informationDesign Guide. Retrofitting Options For HVAC Systems In Live Performance Venues
Design Guide Retrofitting Options For HVAC Systems In Live Performance Venues Heating, ventilation and air conditioning (HVAC) systems are major energy consumers in live performance venues. For this reason,
More informationDigital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect
Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect of Record: SPARCH Project Overview The project is
More informationCase Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia
Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Prepared for the U.S. Department of Energy s Federal Energy Management Program
More informationHEAT RECOVERY OPTIONS FOR DRYERS AND OXIDIZERS
HEAT RECOVERY OPTIONS FOR DRYERS AND OXIDIZERS William K. Scullion, Application Engineering Leader, MEGTEC Systems, De Pere, WI Introduction Competitive pressures continuously motivate us to examine our
More informationDesign Options for HVAC Distribution Systems
Design Options for HVAC Distribution Systems Course No: M06-017 Credit: 6 PDH A. Bhatia Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F: (877)
More informationBoiler System Efficiency
2006 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Journal (Vol. 48, July 2006). For personal use only. Additional distribution in
More informationModeling and Simulation of HVAC Faulty Operations and Performance Degradation due to Maintenance Issues
LBNL-6129E ERNEST ORLANDO LAWRENCE BERKELEY NATIONAL LABORATORY Modeling and Simulation of HVAC Faulty Operations and Performance Degradation due to Maintenance Issues Liping Wang, Tianzhen Hong Environmental
More informationBy Tom Brooke PE, CEM
Air conditioning applications can be broadly categorized as either standard or critical. The former, often called comfort cooling, traditionally just controlled to maintain a zone setpoint dry bulb temperature
More information