Hourly Analysis Program v.4.1 Page 1 of 1
|
|
|
- Bonnie Dalton
- 9 years ago
- Views:
Transcription
1 Air System Design Load Summary for Zona 9 DESIGN COOLING DESIGN HEATING COOLING DATA AT Feb 1800 HEATING DATA AT DES HTG COOLING OA DB / WB 32.4 C / 23.1 C HEATING OA DB / WB -0.6 C / -3.2 C Sensible Latent Sensible Latent ZONE LOADS Details (W) (W) Details (W) (W) Window & Skylight Solar Loads 0 m² 0-0 m² - - Wall Transmission 54 m² m² Roof Transmission 66 m² m² Window Transmission 0 m² 0-0 m² 0 - Skylight Transmission 0 m² 0-0 m² 0 - Door Loads 0 m² 0-0 m² 0 - Floor Transmission 66 m² 0-66 m² 0 - Partitions 63 m² 0-63 m² 0 - Ceiling 0 m² 0-0 m² 0 - Overhead Lighting 1774 W Task Lighting 0 W Electric Equipment 5585 W People Infiltration Miscellaneous Safety Factor 5% / 5% % >> Total Zone Loads Zone Conditioning Plenum Wall Load 0% Plenum Roof Load 0% Plenum Lighting Load 0% Return Fan Load 972 L/s L/s 0 - Ventilation Load 116 L/s L/s Supply Fan Load 1047 L/s L/s Space Fan Coil Fans Duct Heat Gain / Loss 5% 559-5% >> Total System Loads Central Cooling Coil Central Heating Coil >> Total Conditioning Key: Positive values are clg loads Positive values are htg loads Negative values are htg loads Negative values are clg loads
2 Psychrometric Analysis for Zona 9 Location: Buenos Aires, Argentina Altitude: 19.8 m. Data for: February DESIGN COOLING DAY, Outdoor Air Mixed Air 3. Central Cooling Coil Outlet 4. Supply Fan Outlet 5. Duct Heat 6. Room Air 7. Return Duct Outlet Specific Humidity ( kg/kg ) Temperature ( C )
3 Space Design Load Summary for Zona 9 TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' Zona 9 '' IN ZONE '' Zone 9 '' DESIGN COOLING DESIGN HEATING COOLING DATA AT Jan 1900 HEATING DATA AT DES HTG COOLING OA DB / WB 30.8 C / 22.7 C HEATING OA DB / WB -0.6 C / -3.2 C OCCUPIED T-STAT 23.9 C OCCUPIED T-STAT 21.1 C Sensible Latent Sensible Latent SPACE LOADS Details (W) (W) Details (W) (W) Window & Skylight Solar Loads 0 m² 0-0 m² - - Wall Transmission 54 m² m² Roof Transmission 66 m² m² Window Transmission 0 m² 0-0 m² 0 - Skylight Transmission 0 m² 0-0 m² 0 - Door Loads 0 m² 0-0 m² 0 - Floor Transmission 66 m² 0-66 m² 0 - Partitions 63 m² 0-63 m² 0 - Ceiling 0 m² 0-0 m² 0 - Overhead Lighting 1774 W Task Lighting 0 W Electric Equipment 5585 W People Infiltration Miscellaneous Safety Factor 5% / 5% % >> Total Zone Loads ENE EXPOSURE TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' Zona 9 '' IN ZONE '' Zone 9 '' COOLING COOLING HEATING Area U-Value Shade TRANS SOLAR TRANS (m²) (W/(m²- K)) Coeff. (W) (W) (W) WALL H EXPOSURE ROOF
4 Air System Sizing Summary for Zona 9 Air System Information Air System Name... Zona 9 Equipment Class... SPLT AHU Air System Type... SZCAV Number of zones... 1 Floor Area m² Sizing Calculation Information Zone and Space Sizing Method: Zone L/s... Sum of space airflow rates Space L/s... Individual peak space loads Calculation Months... Jan to Dec Sizing Data... Calculated Central Cooling Coil Sizing Data Total coil load kw Sensible coil load kw Coil L/s at Feb L/s Max block L/s L/s Sum of peak zone L/s L/s Sensible heat ratio m²/kw W/m² Water 5.6 K rise N/A Load occurs at... Feb 1800 OA DB / WB / 23.1 C Entering DB / WB / 18.9 C Leaving DB / WB / 14.8 C Coil ADP C Bypass Factor Resulting RH % Design supply temp C Zone T-stat Check... 1 of 1 OK Max zone temperature deviation K Central Heating Coil Sizing Data Max coil load kw Coil L/s at Des Htg L/s Max coil L/s L/s Water 11.1 K drop N/A Load occurs at... Des Htg W/m² Ent. DB / Lvg DB / 23.2 C Supply Fan Sizing Data Actual max L/s L/s Standard L/s L/s Actual max L/(s-m²) L/(s-m²) Outdoor Ventilation Air Data Design airflow L/s L/s L/(s-m²) L/(s-m²) Fan motor BHP BHP Fan motor kw kw Fan static Pa l/s/person l/s/person
5 Zone Design Load Summary for Zona 9 Zone 9 DESIGN COOLING DESIGN HEATING COOLING DATA AT Jan 1900 HEATING DATA AT DES HTG COOLING OA DB / WB 30.8 C / 22.7 C HEATING OA DB / WB -0.6 C / -3.2 C OCCUPIED T-STAT 23.9 C OCCUPIED T-STAT 21.1 C Sensible Latent Sensible Latent ZONE LOADS Details (W) (W) Details (W) (W) Window & Skylight Solar Loads 0 m² 0-0 m² - - Wall Transmission 54 m² m² Roof Transmission 66 m² m² Window Transmission 0 m² 0-0 m² 0 - Skylight Transmission 0 m² 0-0 m² 0 - Door Loads 0 m² 0-0 m² 0 - Floor Transmission 66 m² 0-66 m² 0 - Partitions 63 m² 0-63 m² 0 - Ceiling 0 m² 0-0 m² 0 - Overhead Lighting 1774 W Task Lighting 0 W Electric Equipment 5585 W People Infiltration Miscellaneous Safety Factor 5% / 5% % >> Total Zone Loads
6 Zone Sizing Summary for Zona 9 Sizing Calculation Information Zone and Space Sizing Method: Zone L/s... Sum of space airflow rates Space L/s... Individual peak space loads Calculation Months... Jan to Dec Sizing Data... Calculated Zone Sizing Data Maximum Design Minimum Time Maximum Zone Cooling Air Air of Heating Floor Sensible Flow Flow Peak Load Area Zone Zone Name (kw) (L/s) (L/s) Load (kw) (m²) L/(s-m²) Zone Jan Zone Terminal Sizing Data No Zone Terminal Sizing Data required for this system. Space Loads and Airflows Cooling Time Air Heating Floor Zone Name / Sensible of Flow Load Area Space Space Name Mult. (kw) Load (L/s) (kw) (m²) L/(s-m²) Zone 9 Zona Jan
Energy Efficient HVAC-system and Building Design
Energy Efficient HVAC-system and Building Design Maija Virta 1, Harri Itkonen 1, Panu Mustakallio 1, Risto Kosonen 1 1 Halton Oy, Finland Corresponding email: [email protected] SUMMARY This paper
Residential HVAC Load Sizing Training October 14, 2015. David Kaiser Green Code Plan Reviewer
Residential HVAC Load Sizing Training October 14, 2015 David Kaiser Green Code Plan Reviewer DCRA - Green Building Division Regulations of green codes including: Green Building Act Green Construction Code
EN 1279-5. Insulating glass units, intended to be used in buildings and construction works
4 (#2) - 12-4, Heat Control Glass (Low-E #2) + Dry Air (100%) + Clear 4-12 - 4 29 (-1; -4) db U-value (EN 673) 1,6 W / (m 2 K) Light transmission and reflection 0,79/0,12/0,12 Solar energy characteristics
APPLICATION GUIDE. Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application
APPLICATION GUIDE Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application Section Comparison of Latent Cooling Performance of Introduction Most commercial HVAC systems
EN 1279-5. Insulating glass units, intended to be used in buildings and construction works
4 (#2) - 12-4, Heat Control Glass (Low-E #2) + Argon (90%) + Clear 4-12 - 4 29 (-1; -4) db U-value (EN 673) 1,3 W / (m 2 K) Light transmission and reflection 0,79/0,12/0,12 Solar energy characteristics
CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION
CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION 3.1 Purpose of Thermal Load Estimation 3.2 Heating Load versus Cooling Load 3.3 Critical Conditions for Design 3.4 Manual versus Computer Calculations 3.5 Heating
Subtropical Cities September 2006. Design for Energy Efficiency in Commercial Buildings in Queensland
Subtropical Cities September 2006 Design for Energy Efficiency in Commercial Buildings in Queensland Contents Typical Building Constraints & Requirements Understanding Energy Consumption in Buildings HVAC
EN 1279-5. NPD Reaction to fire. NPD External fire behaviour. NPD Bullet resistance. NPD Explosion resistance. NPD Burglar resistance (EN 356)
4 (# 2) - 12-33.1, Heat Control Glass (Low-E #2) + Argon (90%) + Pendulum body impact resistance - 12-2 (B) 2 4-12 - 33.1 32 (-1; -3) db U-value (EN 673) 1,3 W / (m 2 K) Light transmission and reflection
EN 1279-5. Insulating glass units, intended to be used in buildings and construction works
4 (#2) - 12-4, Thermally Toughened Heat and Solar Control Glass 1 (C) 3-12 - 4-12 - 4 29 (-1; -4) db U-value (EN 673) 1,6 W / (m 2 K) Light transmission and reflection 0,71/0,10/0,11 Solar energy characteristics
Air Conditioning Contractors of America
Air Conditioning Contractors of America WHO IS ACCA???? Industry Manuals Residential D, J, S, H, RS, T, P A manual J load calculation is a measurement of how much heating and cooling capacity a home will
DEVELOPMENT OF AN OPEN SOURCE HOURLY BUILDING ENERGY MODELING SOFTWARE TOOL
DEVELOPMENT OF AN OPEN SOURCE HOURLY BUILDING ENERGY MODELING SOFTWARE TOOL Brittany Hanam, MASc, EIT RDH Building Engineering Ltd. Vancouver, BC John Straube, PhD, P.Eng. Building Engineering Group, Civil
Federation of European Heating, Ventilation and Air-conditioning Associations
Federation of European Heating, Ventilation and Air-conditioning Associations Address: Rue Washington 40 1050 Brussels Belgium www.rehva.eu [email protected] Tel: +32 2 514 11 71 Fax: +32 2 512 90 62 Use of
UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01
GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per
Causes of High Relative Humidity Inside Air Conditioned Buildings. Roger G.Morse AIA, Paul Haas CSP, CIH Morse Zehnter Associates
Causes of High Relative Humidity Inside Air Conditioned Buildings Roger G.Morse AIA, Paul Haas CSP, CIH Morse Zehnter Associates S. FLORIDA AVE. AMBIENT 91 F db / 78 F wb 16,000 HOURS ANNUALLY THAT wb
UNDERSTANDING AND USING THE HVAC DESIGN REVIEW FORM
Page 1 UNDERSTANDING AND USING THE HVAC DESIGN REVIEW FORM Each of the 38 points of requested information is discussed, and references to the supporting manual are given to substantiate the requirement.
HVAC Calculations and Duct Sizing
PDH Course M199 HVAC Calculations and Duct Sizing Gary D. Beckfeld, M.S.E., P.E. 2007 PDH Center 2410 Dakota Lakes Drive Herndon, VA 20171-2995 Phone: 703-478-6833 Fax: 703-481-9535 www.pdhcenter.com An
Element D Services Heating, Ventilating, and Air Conditioning
Load Calculation Criteria PART 1 - GENERAL 1.01 OVERVIEW A. This section includes requirements for calculating HVAC cooling and heating loads. B. Load calculations must be performed in accordance with
Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems
Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems If you're a designer or a BCA, this guidance on the energy efficiency of HVAC systems in commercial buildings may
NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES
NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES 8.1 INTRODUCTION Testing, adjusting, and balancing of HVAC systems can best be accomplished by following a series of systematic procedures. The NEBB TAB
Innovent LASER Packaged Fresh Air Conditioning Units
LASER Latent And Sensible Energy Reduction Latent And Sensible Energy Reduction For Outside Air Innovent LASER Packaged Fresh Air Conditioning Units Innovent LASER units provide both sensible and latent
CHAPTER 4 LOAD CALCULATIONS 4.1 CONTEXT
CHAPTER 4 LOAD CALCULATIONS 4.1 CONTEXT The accurate calculation of heating and cooling loads is essential to provide a sound bridge between fundamental building design decisions and an operating building.
How To Design A Building In New Delhi
ENERGY EFFICIENT HVAC DESIGN FOR COMPOSITE CLIMATE Overview of Design Conditions: Air conditioning system consumes most of the energy that a building needs in its operation. In order to reduce energy consumption
ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE
ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE Overview of Design Conditions: Air conditioning system consumes most of the energy that a building needs in its operation. In order to reduce
THERMAL LOSSES Thermal Losses Calculations
Calculations -1- THERMAL LOSSES Thermal Losses Calculations Employer : 4M SA Project Location : ASHRAE Office Room : Example from ASHRAE 2013 Handbook - Fundamentals : Chapter 18, Single Room Example Peak
Venice Library Humidity Study. for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205. Report April 13, 2015
for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205 Report April 13, 2015 Moses & Associates, Inc. 2209 NW 40 th Terrace, Suite A Gainesville, FL 32605 FL License EB-0003097
By Tom Brooke PE, CEM
Air conditioning applications can be broadly categorized as either standard or critical. The former, often called comfort cooling, traditionally just controlled to maintain a zone setpoint dry bulb temperature
Below are detailed instructions for using the EMS load calculator.
Introduction The EMS load calculator is designed to make load calculating as painless as possible. For sizing the equipment, only the first three tabs (Steps 1, 2 & 3) need to be completed. This process
Makeup Air For Exhaust Systems In Tight Houses. Tony Jellen Engineering Projects
Makeup Air For Exhaust Systems In Tight Houses Tony Jellen Engineering Projects PA Housing & Land Development Conference February 23, 2012 Effects of Kitchen Ventilation on Residential Dwellings Anthony
Energy Efficient Building Design College of Architecture Illinois Institute of Technology, Chicago. Relative Humidities RH% 49.4. 0.
Psychrometrics Psychrometric Chart Relative Humidities RH% 49.4 100% 80% 0.030 Enthalpies 70% H btu/lb 46.5 0.028 85 Not to Scale 0.026 Humidity Numbers and Values 43.7 60% Ratios are approximate 0.024
Greenhouse Cooling. Why is Cooling Needed?
Greenhouse Cooling Why is Cooling Needed? Solar radiation is the heat input for the earth can radiate as much as 277 Btu/ft 2 /hr onto the surface of the earth on summer s day in coastal and industrial
Flexibility, Efficiency In San Antonio Arena
2005, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Reprinted by permission from ASHRAE Journal, (Vol. 47, No. 9, September 2005). This article may not
Whole House Dehumidification for Occupant Comfort and Energy Savings
Downloaded from www.rsrews.com. Since 1968, RS Andrews has proudly served Atlanta's Heating, Air Conditioning & Plumbing Needs. Whole House Dehumidification for Occupant Comfort Energy Savings June 2009
Fans and Air Handling Units. Will Rea and Paul Pilutti February 16 th, 2011
Fans and Air Handling Units Will Rea and Paul Pilutti February 16 th, 2011 HTS Lunch and Learns Available Online Visit www.htseng.com Engineering Tools Resource Center Contents Fans Fan Curves Fan Laws
Load and Energy Calculations
BBSE2008 Air Conditioning and Refrigeration Engineering www.hku.hk/bse/bbse2008/ Load and Energy Calculations Dr. Sam C. M. Hui Department of Mechanical Engineering The University of Hong Kong E-mail:
Software Development for Cooling Load Estimation by CLTD Method
IOSR Journal of Mechanical and Civil Engineering (IOSR-JMCE) ISSN: 2278-1684Volume 3, Issue 6 (Nov. - Dec. 2012), PP 01-06 Software Development for Cooling Load Estimation by CLTD Method Tousif Ahmed Department
Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal
Technical Bulletin By Bruce I. Nelson, P.E., President, Colmac Coil Manufacturing, Inc. Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal SUMMARY Refrigeration air coolers (evaporators)
Benefits of. Air Flow Management. Data Center
Benefits of Passive Air Flow Management in the Data Center Learning Objectives At the end of this program, participants will be able to: Readily identify if opportunities i where networking equipment
FLORIDA SOLAR ENERGY CENTER
FLORIDA SOLAR ENERGY CENTER Creating Energy Independence High Performance Existing Homes Partnerships and Research Janet McIlvaine Research Analyst, Florida Solar Energy Center A Research Institute of
Dedicated Outdoor Air Systems (D.O.A.S.)
Commercial and Industrial Climate Control Systems Dedicated Outdoor Air Systems (D.O.A.S.) AMDOAS-1 What is it? Why use one? What are my options? Selection considerations Design steps What is it? A separate
APPLICATION GUIDE. Moisture Management in Waterborne Climate Systems
APPLICATION GUIDE Moisture Management in Waterborne Climate Systems Contents Introduction 3 WBCS Concept 3 Condensation 4 Moisture Sources in the Space 4 Impact of a High Moisture Load 5 Designing to Manage
Air Conditioning in Green Office Buildings?
Air Conditioning in Green Office Buildings? How to implement Demand Controlled Ventilation Stuttgart Rechte allein bei ICEBO 08 10.10.2008 CI / DrRo 1 Air Conditioning in Green Office Buildings ventilation
Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida
Optimizing 100% Outside Air Systems with Heat Pipes Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida Introduction To meet increasingly rigorous building codes
Trakya Cam Sanayii A.Ş. Adres: İş Kuleleri Kule 3 34330 4.Levent- İSTANBUL/TÜRKİYE 07 EN 1279-5
4 (#2) - 12-4, Thermally Toughened ISS114 #2 + Dry Air (%100) + Clear 1(C) 3-12 - 4-12 - 4 29 (-1; -4) db U-value (EN 673) 2,6 W / (m 2 K) Light transmission and reflection 0,14/0,34/0,37 Solar energy
HVAC Simplified Approach Option
HVAC Simplified Approach Option Part I Project Address: City: HVAC System Designer of Record: Date: Zip: Qualification The building is 2 stories or less in height and has a gross floor area is less than
ENERGY SAVINGS BY CHANGING CONSTANT AIR VOLUME SYSTEMS (CAV) TO VARIABLE AIR VOLUME SYSTEMS (VAV) IN EXISTING OFFICE BUILDINGS.
1 ENERGY SAVINGS BY CHANGING CONSTANT AIR VOLUME SYSTEMS (CAV) TO VARIABLE AIR VOLUME SYSTEMS (VAV) IN EXISTING OFFICE BUILDINGS. - EXPERIENCE FROM A PLANT RECONSTRUCTION BASED ON A NEW SUPPLY AIR TERMINAL
Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks
Presentation Outline Common Terms / Concepts HVAC Building Blocks Plant Level Building Blocks Description / Application Data Green opportunities Selection Criteria Air Distribution Building Blocks same
Mechanical and Natural Ventilation
BBSE3006: Air Conditioning and Refrigeration II http://www.hku.hk/bse/bbse3006/ Mechanical and Natural Ventilation Dr. Sam C. M. Hui Department of Mechanical Engineering The University of Hong Kong E-mail:
HVAC Systems: Overview
HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct
Residential HVAC System Sizing
Residential HVAC System Sizing William P. Goss University of Massachusetts, Amherst, Massachusetts, USA Corresponding email: [email protected] SUMMARY Heating, ventilating and air-conditioning (HVAC)
Glossary of Heating, Ventilation and Air Conditioning Terms
Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment
Comparing Energy Savings of Different VAV Systems
Comparing Energy Savings of Different VAV Systems Prepared By: Martyn Dodd [email protected] EnergySoft LLC 1025 5th Street, Suite A Novato, CA 94945 415-897-6400 www.energysoft.com Last Modified: March
HDA -----------------------------------------------------------
----------------------------------------------------------- Lightstrips ---------------------------------------------------------------------- Ceiling system for heating and cooling LIGHTSTRIPS LIGHTSTRIPS
Postharvest Sample Questions
What is the physical principle that allows mechanical refrigeration systems to remove heat from the storage environment? Draw or describe the basic components of a compression refrigeration system (=the
Cooling Load Calculations and Principles
Cooling Load Calculations and Principles Course No: M06-004 Credit: 6 PDH A. Bhatia Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F: (877) 322-4774
Air Conditioning Clinic
Air Conditioning Clinic Cooling and Heating Load Estimation One of the Fundamental Series April 2011 TRG-TRC002-EN Cooling and Heating Load Estimation One of the Fundamental Series A publication of Trane,
Trakya Cam Sanayii A.Ş. Adres: İş Kuleleri Kule 3 34330 4.Levent- İSTANBUL/TÜRKİYE 07 EN 1279-5
4-12 - 33.1, Thermally Toughened Helio Blue + Dry Air (%100) + Pendulum body impact resistance 1(C)3-12 - 2 (B) 2 4-12 - 33.1 32 (-1; -3) db U-value (EN 673) 2,8 W / (m 2 K) Light transmission and reflection
AIRCONDITIONING Cooling Loads Calculations
Calculations -1- AIRCONDITIONING Cooling s Calculations Employer : 4M SA Project Location : ASHRAE Office Room : Example from ASHRAE 2013 Handbook - Fundamentals : Chapter 18, Single Room Example (p. 18.37)
Building Performance Evaluation Guide Version 1.7
Building Performance Evaluation Guide Version 1.7 Prepared by Center for Energy and Environment January 2014 Minnesota Sustainable Building 2030: Building Performance Evaluation Guide p 1 1. Schematic
VE Compliance FAQ. Top Tips for Achieving Compliance
Integrated Environmental Solutions Ltd. VE Compliance FAQ The Building Regulations 2010: Conservation of fuel and power Approved Document L2A (2013 edition for use in England) Top Tips for Achieving Compliance
Data Centers WHAT S ONTHEHORIZON FOR NR HVAC IN TITLE 24 2013? SLIDE 1
WHAT S ONTHEHORIZON FOR NR HVAC IN TITLE 24 2013? SLIDE 1 Data Center CASE Scope Existing Title 24 2008 Scope Current scope ( 100 T24-2008) exempts process space from many of the requirements, however
85 F 80 F 50% 75 F 70 F 73.0/61.8 45 F 10% Figure 1
Feb. 07 INTRODUCTION: Wrap around heat pipes are air-to-air heat exchangers that are installed in the airstream upstream and downstream of a cooling coil to deliberately reduce the Sensible Heat Ratio
Fan Applications & System Guide
Fan Applications & System Guide Airflow for general ventilation can be calculated by; Area Method Air Change Method Occupancy Method Ventilation Calculation Methods Area Method Derives the ventilation
Why Do I Need Precision Air Conditioning?
Why Do I Need Precision Air Conditioning? Executive Summary Today's technology rooms require precise, stable environments in order for sensitive electronics to operate optimally. Standard comfort air
2011 National Energy Code for Buildings: Archetype Building Analysis for Newfoundland and Labrador
2011 National Energy Code for Buildings: Archetype Building Analysis for Newfoundland and Labrador Final Report Prepared for: Government of Newfoundland and Labrador Government Purchasing Agency 30 Strawberry
Dienstleistung. Certification as "Quality Approved Passive House" Criteria for Residential-Use Passive Houses
Passiv Haus Institut Passivhaus Dienstleistung GmbH Dr. Wolfgang Feist Rheinstr. 44/46 Rheinstr. 44/46 D-64283 Darmstadt D-64283 Darmstadt www.passiv.de www.passivhaus-info.de Certification as "Quality
International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS
International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES
Dealing with Thermal Issues in Data Center Universal Aisle Containment
Dealing with Thermal Issues in Data Center Universal Aisle Containment Daniele Tordin BICSI RCDD Technical System Engineer - Panduit Europe [email protected] AGENDA Business Drivers Challenges
EFA PSBP. Natural Ventilation Strategy. Introduction. 1.1 Relevant legislation. 1.1.1 The Building Regulations 2010
EFA PSBP Natural Ventilation Strategy Introduction The Baseline Designs Project will provide scheme design details for a number of Primary and Secondary School Exemplars. For the purposes of setting a
EN 1279-5. Insulating glass units, intended to be used in buildings and construction works
4-12 - 4 (#3), Thermally Toughened Helio Blue + Dry Air (100%) + 1(C)3-12 - 4-12 - 4 29 (-1; -4) db U-value (EN 673) 1,6 W / (m 2 K) Light transmission and reflection 0,58/0,/0,10 Solar energy characteristics
Total Heat Versus Sensible Heat Evaporator Selection Methods & Application
Total Heat Versus Sensible Heat Evaporator Selection Methods & Application Scope The purpose of this paper is to provide specifying engineers, purchasers and users of evaporators in industrial refrigeration
HVAC Checklist - Long Form
HVAC Checklist - Long Form Page 1 of 14 Appendix B discusses HVAC system components in relation to indoor air quality. utside Air Intake Location pen during occupied hours? Unobstructed? Standing water,
Air Conditioning. The opportunity for energy efficiency. Low cost actions to reduce energy usage now
Fact Sheet #6 Air Conditioning In this fact sheet you will discover: The opportunity for energy efficiency How air conditioning works Low cost actions to reduce energy usage now Investments to reduce costs
Preliminary Final Proposal
1 Butler Memorial Hospital New Inpatient Tower Senior Capstone Project Mechanical Option Preliminary Final Proposal Mechanical System Re-design and Breadth Topics Butler Memorial Hospital New Inpatient
Selecting the Supply Air Conditions for a Dedicated Outdoor Air System Working in Parallel with Distributed Sensible Cooling Terminal Equipment
AT-01-7-3 Selecting the Supply Air Conditions for a Dedicated Outdoor Air System Working in Parallel with Distributed Sensible Cooling Terminal Equipment Kurt M. Shank Student Member ASHRAE Stanley A.
Energy Efficiency in Buildings
Energy Efficiency in Buildings Supplemental Guide to SANS 10400-XA & SANS 204 V. 3.0 Registered to: The Drawing Studio Image: digitalart / FreeDigitalPhotos.net Report Date: 26 August 2014 Practice Name:
APC APPLICATION NOTE #112
#112 Best Practices for Deploying the InfraStruXure InRow SC By David Roden Abstract The InfraStruXure InRow SC (ACSC100 and ACSC101) is a self-contained air conditioner for server rooms and wiring closets.
HVAC Systems in Schools & Commercial Buildings and Radon
HVAC Systems in Schools & Commercial Buildings and Radon References US EPA Radon Prevention in the Design and Construction of Schools and Other Large Buildings http://www.epa.gov/ordntrnt/ord/nrmrl/pubs/1993/air/
ENERGY PERFORMANCE MODELLING AND HEAT RECOVERY UNIT EFFICIENCY ASSESSMENT OF AN OFFICE BUILDING
THERMAL SCIENCE: Year 2015, Vol. 19, No. 3, pp. 865-880 865 ENERGY PERFORMANCE MODELLING AND HEAT RECOVERY UNIT EFFICIENCY ASSESSMENT OF AN OFFICE BUILDING by Norbert L. HARMATI a*, Radomir J. FOLI] a,
Red River College MECB 101 School of Construction and Engineering Technologies Manitoba Energy Code for Buildings 101 (MECB 101)
Manitoba Energy Code for Buildings 101 (MECB 101) The National Research Council of Canada (NRC) has issued the National Energy Code for Buildings (NECB) in 2011. The main objective of NECB 2011 was to
CIBSE Loads User Guide
CIBSE Loads User Guide IES Virtual Environment Apache Contents CIBSE Loads User Guide... 1 1 Introduction... 3 1.1 Results file (for both.htg and.clg files)... 3 2 Heating Loads... 4 2.1 Interface for
Proper Applications & Sequences for Constant Volume Pressure Dependent Zoning Systems. History
Proper Applications & Sequences for Constant Volume Pressure Dependent Zoning Systems Ryan R. Hoger, LEED AP 708.670.6383 [email protected] History VAV systems came into favor for mid and large size
University of St Andrews. Energy Efficient Data Centre Cooling
Energy Efficient Data Centre Cooling St. Andrews and Elsewhere Richard Lumb Consultant Engineer Future-Tech Energy Efficient Data Centre Cooling There is no one single best cooling solution for all Data
Performance Rating of Room Fan- Coils
ANSI/AHRI Standard 440 with Addendum 1 (Formerly ARI Standard 440) 2008 Standard for Performance Rating of Room Fan- Coils ANSI/AHRI STANDARD 440-2008 WITH ADDENDUM 1, PERFORMANCE RATING OF ROOM FAN-COILS
Challenges and Failures in Green Building Design Using Under-Floor Air Distribution. Ken Urbanek, PE, HBDP, LEED AP Director of Engineering
Challenges and Failures in Green Building Design Using Under-Floor Air Distribution Ken Urbanek, PE, HBDP, LEED AP Director of Engineering Agenda UFAD Overview Challenges / Failures Steps for a Successful
Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling
Data Center Design Guide featuring Water-Side Economizer Solutions with Dynamic Economizer Cooling Presenter: Jason Koo, P.Eng Sr. Field Applications Engineer STULZ Air Technology Systems jkoo@stulz ats.com
CE6500 Energy Recovery Ventilator
ADVANCED COMMERCIAL Energy Recovery Ventilator PRODUCT SPECIFICATIONS & TECHNICAL DATA Features NOMINAL CAPACITY 5500-7000 CFM CASING Double-wall cabinet White exterior paint, -gauge galvanized steel -gauge
IDA ICE 4: Getting Started EQUA Simulation AB, September 2009
IDA ICE 4: Getting Started EQUA Simulation AB, September 2009 Manual version: 4.0 Copyright EQUA Simulation AB 2009 Contents Contents... 2 1 Introduction... 3 Caption for symbols in screenshots... 3 2
THE NATIONAL BUILDING REGULATIONS PART XA: ENERGY EFFICIENCY. Presentation by Peter Henshall-Howard: HEAD: BUILDING DEVELOPMENT MANAGEMENT.
THE NATIONAL BUILDING REGULATIONS PART XA: ENERGY EFFICIENCY. Presentation by Peter Henshall-Howard: HEAD: BUILDING DEVELOPMENT MANAGEMENT. A Diagrammatic representation of the relationship between the
WORKSHEET FOR RESIDENTIAL AIR SYSTEM DESIGN page 1
WORKSHEET FOR RESIDENTIAL AIR SYSTEM DESIGN page 1 Wallet card photocopy Inspection Authority: Signature: Date: / / Submitted For: ( Owner ) Name Address City Prov Postal code Phone ( ) Fax ( ) Designer/Signature:
Economic Evaluation of Residential Air Conditioner Designs for Hot and Dry Climates
Economic Evaluation of Residential Air Conditioner Designs for Hot and Dry Climates Arthur Rosenfeld, California Energy Commission Gregory Rosenquist, Lawrence Berkeley National Laboratory C. Keith Rice,
