1 UNSYMMETRICAL FAULT ANALYSIS & PROTECTION OF THE EXISTING POWER SYSTEM R. S. Meena* & M. K. Lodha** Department of Electrical Engineering, Sri Balaji College of Engineering & Technology, Jaipur, Rajasthan Rajasthan Technical University Kota Abstract: Now a day s electrical power system is in the process to convert in smart power system with interconnected national and regional grids. Modeling of power system has become a necessary in order to make right decision, check for any potential problems, and fault conditions in large interconnected network. In this paper we shell deal with unsymmetrical faults in a proposed network. In recent year power system engineers shifted protection method from classical methods to digital or numerical protection techniques, in this technique high crunching capability, which has made it possible to design digital filters in real time protection system with smart technologies. Multifunctional relay also installed in modern power system network for protection of transmission line, generator protection, motor protection, real time fault location, protection of busbar and other important equipments. This paper is devoted to abnormal system behaviour under conditions of unsymmetrical fault in power system networks using MATLAB Simulation Techniques. Key Words: Modern Power System, Unsymmetrical Fault, Generator Protection, Interconnected Network, Digital/ Numerical Protection. I. Introduction: In the modern large interconnected power system, heavy currents flowing during a fault must be interrupted much before the steady state conditions are established. This paper is devoted to abnormal system behaviour under conditions of unsymmetrical fault in power system networks. Various types of unsymmetrical faults that occur in power system- (a) Shunt type fault (b) Series type fault (a) Shunt Type Fault: In shunt type fault also three category- (i) Single-Line to Ground Fault (ii) Line-to-Line Fault (iii) Double -Line to ground Fault (i) Single line to ground fault: in this type of fault at the fault point, the currents out of the power system and the line to line ground voltages are constrained as follows:- Ib= Ic = 0 Va = Z f Ia The symmetrical components of the fault current are Ia1= Ia2 = Ia0 = 1/3Ia Va1+Va2+Va0 = ZfIa1 (ii) Line to line fault: line to line fault at any point in a power system then the currents and voltages at the fault can be expressed as- Ia= 0, Ib = -Ic Vb-Vc = IbZ f (iii) Double line to ground fault: For this condition the currents and voltages at the fault are expressed- Ia=0, Ia1+Ia2+Ia0 =0 Vb =Vc = Z f (Ib+Ic) = 3Z f Ia0 146

2 (b) Series Type Fault: It is also called open conductor fault, in series type fault two category mainly divided (i) One Conductor (ii) Two Conductor Open conductor fault is in series with the line. Line currents and series voltage between ends of the conductors are required to be determined. The set of series current and voltage at the fault are- Ia V aa' I P Ib ; VP Vbb' I c Vcc' Symmetrical component of current and voltage are- Ia1 Vaa '1 Is I b2 ; V s V bb'2 I V c0 cc'0 Case-1 When two conductor open- the current and voltage due to this fault are expressed as Vaa = 0, Ib=Ic=0 In term of symmetrical components, we can write- Vaa 1+Vaa 2+Vaa 0=0 Ia1=Ia2=Ia0=1/3Ia Case-2 One conductor open- the current and voltage due to this fault are expressed as Vbb =Vcc = 0, Ia=0 In term of symmetrical components, we can write- 2. Proposed System: Vaa 1=Vaa 2=Vaa 0=1/3Vaa Ia1+Ia2+Ia0=0 147

3 (i) A three phase electrical power system consists of 15KV, 50Hz transmitting power from a synchronous generator with 250MVA rating interconnected to an 2500 equivalent source which is a substation, through a 200Km transmission line. The transmission line is split in two 100Km lines connected between buses of single generator and equivalent source. (ii) 148

4 operating condition and no trip signal from the relay under healthy condition. (iii) Fig. 1 (i), (ii) & (iii) Configuration of System Used in Modeling and Simulation This is a multifunctional relay model in which simulation and steady state analysis testing is done using Matlab. In this paper unsymmetrical fault under different fault condition at generator end is shown by their respectively graphs. A three-phase system is modeled in continuous mode using blocks from three-phase library available in simulink. Stator phase faults, over-voltages, under-voltages and negative sequence current are protected with the developed relay model. Voltages and currents are measured in each condition. There is some case of protection (a) Stator Phase Faults Protection: All the stator phase faults including phase to ground, phase to phase and three phase faults are simulated. The protection against each fault is applied with the relay trip signal and opening of circuit-breaker. The simulation study also shows the normal Fig. 2 - Normal Healthy Condition of System 149

5 Fig.3 - Relay Operation in Healthy Condition In the condition of fault occurrence the trip signal is sended to the main circuit-breaker which is also generator transformer circuit breaker (GTCB). Fig.4 - Line to Ground fault Fig. 5 - Line to Line Fault Fig.6- Relay trip signal for Line to Line fault 150

6 (B) Abnormal Conditions: There are many no. of abnormal condition such as over-voltages, under-voltages and negative sequence current. Those can cause insulation failures, dip in the voltage and heating of the machine. Fig. 7 - Overvoltage Relay Signal Fig.8 - Under-Voltage Trip Signal The condition of overvoltage and under voltage is produced in such a way that it should not cause the sudden rise of current in three phases otherwise the relay will operate for over current protection. Negative sequence current arises in the condition of unbalanced load and is computed from three phase current in the stator using unsymmetrical analysis. For this purpose a subsystem is developed using MATLAB simulink and is introduced in the protective relay 151

7 Fig.9 - Negative sequence alarm 3. Scope: The need of Continuous and reliable power supply has increased due to this protection and monitoring of modern power system is necessary with in low cost and smart handling technique. Multifunctional relay scheme also helpful to protect generator against the stator fault, overvoltage, symmetrical, unsymmetrical balanced and unbalanced conditions. This relay system can be further implemented for the development to multi-functionalize the bus-bar, transformer and distance protection. Besides this the modern switchgear with vacuum circuit breaker is also being developed. This will be very interesting area to be studied further. 4. One Relay One Feeder: The following solutions are available within one relay family- Separate control and protection relays, Feeder protection and remote control of the line circuit-breaker via the serial communication link, combined relays for protection, monitoring and control. Mixed use of the different relay types is readily possible on account of the uniform operation and communication procedures. It sounds good for better protection of existing system. Modern relay families offer the user a uniform technique covering the whole range of protection applications. This includes a uniform operator concept, uniform housing technology, common communication protocols and a uniform technology. This offers a number of advantages for the user: Reduced engineering and testing efforts due to well-suited functions Reduced training due to uniform operation and setting Uniform data management due to a common operator program For the simulation study, a power system model having a synchronous generator interconnected with a substation is considered and analyzed under different faults, abnormal conditions faced by generator and protection against them. A subsystem for the calculation of negative sequence current has been developed. It has been observed that one relay performs combined protection of generator feeder. 152

8 5. Conclusion: From this study it can be concluded that combined relays should be used for protection and control. In transmission type substations, separation into independent hardware units is still preferred, whereas on the distribution level a trend towards higher function integration can be observed. Here, combined feeder/line relays for protection, monitoring and control are on the march. Relays with protection functions only and relays with combined protection and control functions are being offered. Relays support the one relay one feeder concept and thus contribute to a considerable reduction in space and wiring. With the development of digital technology modern protective relay supports both stand-alone and combined solutions on the basis of a single hardware and software platform. The user can decide within wide limits on the configuration of the control and protection functions in the line, without compromising the reliability of the protection functions. 6. Reference: [1] D P Kothari, I J Nagrath, Modern Power System Analysis, 4 Edition ISBN [2] Soman S A, S A Khaparde and Shubha Pandit, Computational Methods for large sparse power system analysis, KAP, Boston, [3] Gross, C A, Power System Analysis, Willy, New York, [4] K Ferling and H Rljanto, "Influence of the Latest Technologies on the Development of Protective Relays," International Conference on Electricity Distribution, Brighlo, pp: [5] Robert A.Kennedy and Larry E.Curtis. "Overcurrent Proleclive Device Coordination by Computer," IEEE Transactions on Industry Applications, Volume I A-1 8, No.5, October pp: [6] IEEE Industrial and Commercial Power Systems Department Working Group Report of the Protection Committee, Application Considerations of Static Over current Relays: A Working Group Report IEEE Trans. Industry Applications., Vol. 33, pp [7] M. S. Sachdev, "Advancements in Microprocessor Based Protection and Communication, A tutorial publication of the IEEE, Piscataway, NJ: IEEE Cat. No. 97TP120-0, pp

SAMPLE OF THE STUDY MATERIAL PART OF CHAPTER 3. Symmetrical Components & Faults Calculations

SAMPLE OF THE STUDY MATERIAL PART OF CHAPTER 3. Symmetrical Components & Faults Calculations SAMPLE OF THE STUDY MATERIAL PART OF CHAPTER 3 3.0 Introduction Fortescue's work proves that an unbalanced system of 'n' related phasors can be resolved into 'n' systems of balanced phasors called the

More information

The following table shows approximate percentage wise the

The following table shows approximate percentage wise the SHORT-CIRCUIT CALCULATION INTRODUCTION Designing an electrical system is easy and simple, if only the normal operation of the network is taken into consideration. However, abnormal conditions which are

More information

100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center. 598 N. Buth Rd 3215 Arrowhead Rd

100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center. 598 N. Buth Rd 3215 Arrowhead Rd 100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center Introduction Roger Hedding Steven Schoenherr, P.E. ABB Inc. Minnesota Power 598 N. Buth Rd 3215 Arrowhead Rd Dousman,

More information

Unified requirements for systems with voltages above 1 kv up to 15 kv

Unified requirements for systems with voltages above 1 kv up to 15 kv (1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to

More information

Eaton s Electrical Services & Systems. Technical Training Safety Training

Eaton s Electrical Services & Systems. Technical Training Safety Training Eaton s Electrical Services & Systems Technical Training Safety Training 2 EATON CORPORATION Eaton s Electrical Services & Systems Technical Training Safety Training Eaton conducts technical training and

More information

Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO 250447392

Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO 250447392 1 Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading By Ramandeep Kaur Aujla S.NO 250447392 ES 586b: Theory and applications of protective relays Department of

More information

SPECIAL TOPICS ON GROUND FAULT PROTECTION AND PROTECTION COORDINATION IN INDUSTRIAL AND COMMERCIAL POWER SYSTEMS

SPECIAL TOPICS ON GROUND FAULT PROTECTION AND PROTECTION COORDINATION IN INDUSTRIAL AND COMMERCIAL POWER SYSTEMS SPECIAL TOPICS ON GROUND FAULT PROTECTION AND PROTECTION COORDINATION IN INDUSTRIAL AND COMMERCIAL POWER SYSTEMS Claudio S. Mardegan claudio.mardegan@engepower.com www.engepower.com Phone: 55 3579-8777

More information

Permissible ambient temperature Operation Storage, transport

Permissible ambient temperature Operation Storage, transport The Sitras PRO combined DC protective unit and controller is used in the power supply for DC railways in mass transit and main-line systems up 3,000 V DC. It protects DC switch gear and contact line systems

More information

Relion. Power system protection and automation reference Extending substation life cycle with IEC 61850

Relion. Power system protection and automation reference Extending substation life cycle with IEC 61850 Relion Power system protection and automation reference Extending substation life cycle with IEC 61850 Extending substation life cycle with IEC 61850 A step-by-step power system retrofit approach for optimizing

More information

1 Introduction. 2 The Symmetrical Component Transformation. J.L. Kirtley Jr.

1 Introduction. 2 The Symmetrical Component Transformation. J.L. Kirtley Jr. Massachusetts Institute of Technology Department of Electrical Engineering and Computer Science 6.06 Introduction to Power Systems Class Notes Chapter 4 Introduction To Symmetrical Components J.L. Kirtley

More information

Engineering innovation

Engineering innovation Eaton's Electrical Engineering Services & Systems Solutions Focus Seamless Solutions for Reliable, Efficient and Safe Power Systems Engineering innovation Progressive solutions for today s power systems

More information

New Supervisory Control and Data Acquisition (SCADA) Based Fault Isolation System for Low Voltage Distribution Systems

New Supervisory Control and Data Acquisition (SCADA) Based Fault Isolation System for Low Voltage Distribution Systems International Conference on Computer and Communication Engineering (ICCCE 2010), 11-13 May 2010, Kuala Lumpur, Malaysia New Supervisory Control and Data Acquisition (SCADA) Based Fault Isolation System

More information

INTRODUCTION TO SYSTEM PROTECTION. Hands-On Relay School 2012

INTRODUCTION TO SYSTEM PROTECTION. Hands-On Relay School 2012 INTRODUCTION TO SYSTEM PROTECTION Hands-On Relay School 2012 CONGRATULATIONS On choosing the field of system protection. It is an exciting, challenging profession. System protection has changed considerably

More information

LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS

LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS Terence Hazel Senior Member IEEE Schneider Electric 38050 Grenoble France Abstract The power requirements for large industrial sites is increasing.

More information

Chapter 1. Network Structures

Chapter 1. Network Structures Chapter 1 Network Structures Definition Standard IEC 60038 defines voltage ratings as follows: Low voltage (): for a phase-to-phase voltage of between 100 V and 1,000 V, the standard ratings are: 400 V

More information

How the National Grid System Operates. Chris Gorman Lead Account Executive Syracuse

How the National Grid System Operates. Chris Gorman Lead Account Executive Syracuse How the National Grid System Operates Chris Gorman Lead Account Executive Syracuse 2 Parts of the Electric System Parts of the Electric System 1. Generating Station: Produces Electricity. 2. Transmission

More information

How To Test Power Quality Problem On An Induction Motor

How To Test Power Quality Problem On An Induction Motor American Journal of Electrical Power and Energy Systems 2015; 4(4): 39-44 Published online May 29, 2015 (http://www.sciencepublishinggroup.com/j/epes) doi: 10.11648/j.epes.20150404.12 ISSN: 2326-912X (Print);

More information

Both variants can be used for measuring the positive sequence voltage Up or the negative sequence voltage Un.

Both variants can be used for measuring the positive sequence voltage Up or the negative sequence voltage Un. Rev. - 2004-10-22 Page 1(5) General RXTBA 1 is a three-phase phase sequence voltage filter built up by resistors and capacitors. The filter is available in two voltage variants; one for rated voltage 3x110

More information

Voltage Regulator SPAU 341 C. Product Guide

Voltage Regulator SPAU 341 C. Product Guide Issued: July 1998 Status: Updated Version: D/25.04.2006 Data subject to change without notice Features Comprehensive voltage regulation for power transformers with on-load tapchangers in distribution substations

More information

For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690 V - 1000 V (at 50 Hz)

For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690 V - 1000 V (at 50 Hz) 24 1. NETWORK CONFIGURATIONS definition Standard IEC 38 defines voltage ratings as follows: - Low voltage () For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690

More information

Integration of Distributed Generation in the Power System. IEEE Press Series on Power Engineering

Integration of Distributed Generation in the Power System. IEEE Press Series on Power Engineering Brochure More information from http://www.researchandmarkets.com/reports/2171489/ Integration of Distributed Generation in the Power System. IEEE Press Series on Power Engineering Description: A forward

More information

Industrial IT for Substation Automation & Protection

Industrial IT for Substation Automation & Protection Industrial IT for Substation Automation & Protection Exploit the potential of ABB substation automation Improve your performance In view of the increasingly competitive arena where power providers are

More information

TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY

TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY 2 TRACTION NETWORK MONITORING AND PROTECTION SYSTEM Traction network monitoring and protection system,

More information

Staged-Fault Testing of Distance Protection Relay Settings

Staged-Fault Testing of Distance Protection Relay Settings 10.2478/v10048-012-0014-9 MEASUREMENT SCIENCE REVIEW, Volume 12, No. 3, 2012 Staged-Fault Testing of Distance Protection Relay Settings J. Havelka 1, R. Malarić 1, K. Frlan 2 1 Faculty of Electrical Engineering

More information

INTERNATIONAL JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY (IJEET)

INTERNATIONAL JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY (IJEET) INTERNATIONAL JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY (IJEET) International Journal of Electrical Engineering and Technology (IJEET), ISSN 0976 ISSN 0976 6545(Print) ISSN 0976 6553(Online) Volume

More information

Chapter 9 Balanced Faults

Chapter 9 Balanced Faults Chapter 9 alanced Faults 9.1 Introduction The most common types of fault are (in order) single-line-to-ground fault, line-to-line fault, and double-line-to-ground fault. All of these are unbalanced faults.

More information

30 ms High Speed Transfer System (HSTS) Product Description

30 ms High Speed Transfer System (HSTS) Product Description 30 ms High Speed Transfer System (HSTS) Product Description 2 30 ms High Speed Transfer System (HSTS) Product Description Content Page 1 General 5 1.1 Description of the 30 ms high speed transfer system

More information

Relion. Power system protection and automation reference Fast substation busbar protection with IEC 61850 and GOOSE

Relion. Power system protection and automation reference Fast substation busbar protection with IEC 61850 and GOOSE Relion Power system protection and automation reference Fast substation busbar protection with IEC 61850 and GOOSE Fast substation busbar protection with IEC 61850 and GOOSE Falu Elnät AB applies new power

More information

Design of WSN-Based Remote Monitoring System for Environmental Parameters in Substation

Design of WSN-Based Remote Monitoring System for Environmental Parameters in Substation International Journal of Smart Grid and Clean Energy Design of WSN-Based Remote Monitoring System for Environmental Parameters in Substation Aina Hu a *, Huanhuan Wang b, and Jianchen Wan a a Department

More information

Open Phase Conditions in Transformers Analysis and Protection Algorithm

Open Phase Conditions in Transformers Analysis and Protection Algorithm Open Phase Conditions in Transformers Analysis and Protection Algorithm Amir Norouzi GE Digital Energy Markham, ON amir.norouzi@ge.com Abstract This paper first provides an in-depth analysis of open phase

More information

Distribution Operations with High-penetration of Beyond the Meter Intermittent Renewables. Bob Yinger Southern California Edison April 15, 2014

Distribution Operations with High-penetration of Beyond the Meter Intermittent Renewables. Bob Yinger Southern California Edison April 15, 2014 1 Distribution Operations with High-penetration of Beyond the Meter Intermittent Renewables Bob Yinger Southern California Edison April 15, 2014 Southern California Edison SCE provides power to: Nearly

More information

The Application and Benefits of Multi-phase Auto-reclosing

The Application and Benefits of Multi-phase Auto-reclosing he Application and Benefits of Multi-phase Auto-reclosing etsuya Miyoshi*, Atsushi Kasai* Abstract - In this paper we explain the disadvantages in using single- and three-phase auto-reclosing on double

More information

PSS E. High-Performance Transmission Planning Application for the Power Industry. Answers for energy.

PSS E. High-Performance Transmission Planning Application for the Power Industry. Answers for energy. PSS E High-Performance Transmission Planning Application for the Power Industry Answers for energy. PSS E architecture power flow, short circuit and dynamic simulation Siemens Power Technologies International

More information

EVALUATION OF FAULT ANALYSIS IN TRANSMISSION LINES USING RELAY SETTINGS

EVALUATION OF FAULT ANALYSIS IN TRANSMISSION LINES USING RELAY SETTINGS EVALUATION OF FAULT ANALYSIS IN TRANSMISSION LINES USING RELAY SETTINGS N.VIJAYSIMHA 1*, CH.CHENGAIAH 2 1* M-TECH (PSOC), Department of Electrical and Electronics Engineering, Sri Venkateshwara University

More information

Scholars Research Library

Scholars Research Library Available online at www.scholarsresearchlibrary.com Scholars Research Library Archives of Applied Science Research, 2010, 2 (2):380-387 (http://scholarsresearchlibrary.com/archive.html) ISSN 0975-508X

More information

Medium voltage products UniSec for Smart Grid Air-insulated medium-voltage secondary distribution switchgear

Medium voltage products UniSec for Smart Grid Air-insulated medium-voltage secondary distribution switchgear Medium voltage products UniSec for Smart Grid Air-insulated medium-voltage secondary distribution switchgear Index 3 Overview 4 Standard Levels 6 Monitoring & Control 7 Measurements 8 Protection & Logic

More information

Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components

Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components Course No: E02-010 Credit: 2 PDH Boris Shvartsberg, Ph.D., P.E., P.M.P. Continuing Education

More information

Challenges of Protection and Control System Verification on DP3 vessels with Focus on Ride Through Fault and Blackout

Challenges of Protection and Control System Verification on DP3 vessels with Focus on Ride Through Fault and Blackout Author s Name Name of the Paper Session DYNAMIC POSITIONING CONFERENCE October 15-16, 2013 POWER SESSION Challenges of Protection and Control System Verification on DP3 vessels with Focus on Ride Through

More information

Application-oriented testing of line differential protection end to end in the field using the corresponding RelaySimTest template

Application-oriented testing of line differential protection end to end in the field using the corresponding RelaySimTest template Application Note Application-oriented testing of line differential protection end to end in the field using the corresponding RelaySimTest template Author Jens Baumeister jens.baumeister@omicron.at Date

More information

Simulation of Ungrounded Shipboard Power Systems in PSpice

Simulation of Ungrounded Shipboard Power Systems in PSpice Simulation of Ungrounded Shipboard Power Systems in PSpice Haibo Zhang IEEE Student Member Karen L.Butler IEEE Member Power System Automation Lab Electrical Engineering Department Texas A&M University

More information

Everything you need for protection scheme testing

Everything you need for protection scheme testing Power System Simulator for Testing Protection Relays and Schemes Everything you need for protection scheme testing The is the only instrument with the high power, flexibility and software to perform full

More information

Figure. 1 - Split Phase 240/120V circuit (180 phase shift)

Figure. 1 - Split Phase 240/120V circuit (180 phase shift) This technical note describes the option of connecting the 60Hz XW Inverter/Charger to a three-phase source by using a transformer to convert the AC source to split-phase 240/120V. INTRODUCTION: Split-phase

More information

Disturbance Recoder SPCR 8C27. Product Guide

Disturbance Recoder SPCR 8C27. Product Guide Issued: April 1999 Status: Updated Version: C/26.04.2006 Data subject to change without notice Features Versatile digital disturbance recorder module for recording various phenomena in the electric power

More information

SPECIFICATION COG-2007

SPECIFICATION COG-2007 Cleco Power LLC SPECIFICATION COG-2007 FOR PARALLEL OPPERATION OF CUSTOMER-OWNED GENERATION ON CLECO S ELECTRICAL SYSTEM Revised: March 7, 2014 CONTENTS ITEM NO. TITLE PAGE NO. 1.0 Scope 3 2.0 Policy On

More information

Electron S.R.L. A29 ELECTRICAL POWER SYSTEM TRAINERS. Production Transmission Distribution

Electron S.R.L. A29 ELECTRICAL POWER SYSTEM TRAINERS. Production Transmission Distribution lectron S..L. Design Production & Trading of ducational quipment A29 LCTICAL POW SYSTM TAINS Production Transmission Distribution FAX 9065 980 - -mail: electron@electron.it Web: www.electron.it ev 02 Specifications

More information

ABB PSPS Erich Steinmann; Generator control-2013

ABB PSPS Erich Steinmann; Generator control-2013 ABB PSPS Erich Steinmann; Generator control-2013 GENERATOR CONTROL THE MODULAR SOLUTION FOR GENERATORS To make sure that power is efficiently converted into electric energy, it is necessary to supervise

More information

Electrical Shore Connections / Cold Ironing

Electrical Shore Connections / Cold Ironing STANDARD FOR CERTIFICATION No. 2.25 Electrical Shore Connections / Cold Ironing JULY 2014 The electronic pdf version of this document found through http://www.dnv.com is the officially binding version

More information

Nuclear Power Plant Electrical Power Supply System Requirements

Nuclear Power Plant Electrical Power Supply System Requirements 1 Nuclear Power Plant Electrical Power Supply System Requirements Željko Jurković, Krško NPP, zeljko.jurkovic@nek.si Abstract Various regulations and standards require from electrical power system of the

More information

IEC 61850 in ZX Gas-insulated medium voltage switchgear

IEC 61850 in ZX Gas-insulated medium voltage switchgear IEC 61850 in ZX Gas-insulated medium voltage switchgear IEC 61850 in ZX Just as the supply of electrical power is becoming more and more important in a networked world, demands for the integration of electrical

More information

DC TRANSMISSION BASED ON VOLTAGE SOURCE CONVERTERS

DC TRANSMISSION BASED ON VOLTAGE SOURCE CONVERTERS DC TRANSMISSION BASED ON VOLTAGE SOURCE CONVERTERS by Gunnar Asplund, Kjell Eriksson, Hongbo Jiang, Johan Lindberg, Rolf Pålsson, Kjell Svensson ABB Power Systems AB Sweden SUMMARY Voltage Source Converters

More information

6545(Print), ISSN 0976 6553(Online) Volume 4, Issue 2, March April (2013), IAEME & TECHNOLOGY (IJEET)

6545(Print), ISSN 0976 6553(Online) Volume 4, Issue 2, March April (2013), IAEME & TECHNOLOGY (IJEET) INTERNATIONAL International Journal of JOURNAL Electrical Engineering OF ELECTRICAL and Technology (IJEET), ENGINEERING ISSN 0976 & TECHNOLOGY (IJEET) ISSN 0976 6545(Print) ISSN 0976 6553(Online) Volume

More information

SCADA Controlled Multi-Step Automatic Controlled Capacitor Banks & Filter Banks

SCADA Controlled Multi-Step Automatic Controlled Capacitor Banks & Filter Banks SCADA Controlled Multi-Step Automatic Controlled Capacitor Banks & Filter Banks Introduction SCADA (Supervisory Controlled and Data Acquisition) controlled multi-step metalenclosed automatic capacitor

More information

21 st Century Facilities

21 st Century Facilities Electrical Testing 21 st Century Facilities Facility Owners face tough challenges 24 X 7 reliability needed Non linear loads cause harmonics VFD Computers Switching transients disrupt operations Less customer

More information

PROGRAM CRITERIA FOR ELECTRICAL ENGINEERING TECHNOLOGY

PROGRAM CRITERIA FOR ELECTRICAL ENGINEERING TECHNOLOGY PROGRAM CRITERIA FOR ELECTRICAL ENGINEERING TECHNOLOGY Scope These program criteria apply to programs having titles involving Electrical Engineering Technology including: electrical engineering, electrical

More information

water is cooled in a secondary cooling control tasks: use of seawater. Treatment of the seawater formation of algal vegetation.

water is cooled in a secondary cooling control tasks: use of seawater. Treatment of the seawater formation of algal vegetation. for the start-up and shut-down procedures in the case of longer standstills. The diesel exhaust is fed into two turbochargers. A portion of the exhaust gases can be utilized in a waste-heat boiler producing

More information

Protection and Substation Automation. Training Programmes

Protection and Substation Automation. Training Programmes Protection and Substation Automation Training Programmes Protection and Substation Automation Training Programme Overview The objective of the Training Program is to provide education and training to make

More information

F.C. Chan General Manager, CLP Engineering Ltd., Hong Kong SAR, China

F.C. Chan General Manager, CLP Engineering Ltd., Hong Kong SAR, China ELECTRIC POWER DISTRIBUTION SYSTEMS F.C. Chan General Manager, CLP Engineering Ltd., Hong Kong SAR, China Keywords: Distribution system planning, Load characteristics, Subtransmission Lines, Distribution

More information

Typical Data Requirements Data Required for Power System Evaluation

Typical Data Requirements Data Required for Power System Evaluation Summary 66 Carey Road Queensbury, NY 12804 Ph: (518) 792-4776 Fax: (518) 792-5767 www.nepsi.com sales@nepsi.com Harmonic Filter & Power Capacitor Bank Application Studies This document describes NEPSI

More information

Power Systems Engineering Research Center

Power Systems Engineering Research Center Power Systems Engineering Research Center PSERC Background Paper What is Reactive Power? Peter W. Sauer Department of Electrical and Computer Engineering University of Illinois at Urbana-Champaign September

More information

Cahier technique no. 196

Cahier technique no. 196 Collection Technique... Cahier technique no. 196 Integration of local power generation in industrial sites and commercial buildings T. Hazel "Cahiers Techniques" is a collection of documents intended for

More information

FaultAnalysisandElectricalProtectionofDistributionTransformers

FaultAnalysisandElectricalProtectionofDistributionTransformers Global Journal of Researches in Engineering: F Electrical and Electronics Engineering Volume 14 Issue 3 Version 1.0 Type: Double Blind Peer Reviewed International Research Journal Publisher: Global Journals

More information

Distribution Automation Handbook. Section 8.13 Backup Protection

Distribution Automation Handbook. Section 8.13 Backup Protection Distribution Automation Handbook Section 8.13 Backup Protection 2 Contents 8.13 Backup Protection... 3 8.13.1 Introduction... 3 8.13.1.1 REQUIREMETS FOR BACKUP PROTECTIO... 3 8.13.1.2 JUSTIFICATIO OF RESERVE

More information

Distributed Generation and Power Quality Case Study

Distributed Generation and Power Quality Case Study 16 Distributed Generation and Power Quality Case Study Vu Van Thong and Johan Driesen C16.1 DISTRIBUTION NETWORK A segment of an existing Belgian medium-voltage distribution system is used to study the

More information

CIRCUIT BREAKER INTERRUPTING CAPACITY AND SHORT-TIME CURRENT RATINGS

CIRCUIT BREAKER INTERRUPTING CAPACITY AND SHORT-TIME CURRENT RATINGS CIRCUIT BREAKER INTERRUPTING CAPACITY AND SHORT-TIME CURRENT RATINGS David D. Roybal, P.E. Senior Member, IEEE Eaton Electrical 3697 Mount Diablo Boulevard Lafayette, CA 94549 Abstract Low-voltage circuit

More information

A student friendly toolbox for power system analysis using MATLAB

A student friendly toolbox for power system analysis using MATLAB A student friendly toolbox for power system analysis using MATLAB 67 X 4 A student friendly toolbox for power system analysis using MATLAB A. B. M. Nasiruzzaman Department of Electrical & Electronic Engineering,

More information

Electrical Network Management System

Electrical Network Management System Electrical Network Management System Optimisation of the electrical network Measure to understand Understand to control Control to optimise Cost of power and fluids Power quality Power availability 2 Improvement

More information

Numerical Differential Protection

Numerical Differential Protection Numerical Differential Protection Principles and Applications Publicis Corporate Publishing 1 Introduction 8 1.1 Protection Principle 8 1.2 Numerical Differential Protection 9 2 Deflnitions 10 3 Mode of

More information

CO-ORDINATION OF PARALLEL AC-DC SYSTEMS FOR OPTIMUM PERFORMANCE

CO-ORDINATION OF PARALLEL AC-DC SYSTEMS FOR OPTIMUM PERFORMANCE CO-ORDINATION OF PARALLEL AC-DC SYSTEMS FOR OPTIMUM PERFORMANCE Ana Diez Castro & Rickard Ellström Ying Jiang Häfner Christer Liljegren Vattenfall Utveckling AB ABB Power Systems Gotlands Energiverk AB

More information

REQUIREMENTS FOR AUTOMATED FAULT AND DISTURBANCE DATA ANALYSIS

REQUIREMENTS FOR AUTOMATED FAULT AND DISTURBANCE DATA ANALYSIS REQUIREMENTS FOR AUTOMATED FAULT AND DISTURBANCE DATA ANALYSIS Mladen Kezunovic *, Texas A&M University Tomo Popovic, Test Laboratories International, Inc. Donald R. Sevcik, CenterPoint Energy Aniruddha

More information

DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION

DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION ÿþ üûúùø öõöôùóùõò CT Dimensioning DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION Application note GER3973 1 CT Dimensioning ÿþ üûúùø öõöôùóùõò GER-3973 Application note ÿþ üûúùø öõöôùóùõò

More information

Modeling of PV Based Distributed Generator Systems with Diverse Load Patterns

Modeling of PV Based Distributed Generator Systems with Diverse Load Patterns Modeling of PV Based Distributed Generator Systems with Diverse Load Patterns Mehmet H. Cintuglu, mcint015@fiu.edu, Armando Altamirano, araltami@fiu.edu Osama A. Mohammed, mohammed@fiu.edu Energy Systems

More information

Measurement, Modeling and Simulation of Capacitor Bank Switching Transients

Measurement, Modeling and Simulation of Capacitor Bank Switching Transients Measurement, Modeling and Simulation of Capacitor Bank Switching Transients Mirza Softić*, Amir Tokić**, Ivo Uglešić*** *Kreka - Dubrave e, Dubrave, Bosnia and Herzegovina (e-mail: softic_mirza@yahoo.com).

More information

IAV. Time Delay Voltage. For AC and DC circuit applications. GE Multilin 1. Protection and Control. Features and Benefits.

IAV. Time Delay Voltage. For AC and DC circuit applications. GE Multilin 1. Protection and Control. Features and Benefits. IAV Time Delay Voltage For A and D circuit applications. Features and Benefits Frequency compensation (optional) Target seal-in unit (most units) Instantaneous units (optional) Applications A Generators

More information

Hyperlinks are Inactive

Hyperlinks are Inactive Prepared by: NIB/EOB PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES 05503 Department: Electric T&D Section: T&D Engineering and Technical Support Approved by: G.O. Duru (GOD)

More information

Data center power dynamics within the settings of regional power grid

Data center power dynamics within the settings of regional power grid Data center power dynamics within the settings of regional power grid Gulnara Zhabelova 1, Alireza Yavarian 1, Valeriy Vyatkin 1,2 1 Department of Computer Science, Electrical and Space Engineering Lulea

More information

Selecting Current Transformers Part 1 By Darrell G. Broussard, P.E.

Selecting Current Transformers Part 1 By Darrell G. Broussard, P.E. By Darrell G. Broussard, P.E. Introduction: As engineers, we are aware that electrical power systems have grown. How much have they grown? When was the last time you specified a 2400-volt system, a 4160-volt

More information

Summary for CIRED 2001 Conference paper in Amsterdam. Maintenance scheduling according to reliability targets and actual equipment performance

Summary for CIRED 2001 Conference paper in Amsterdam. Maintenance scheduling according to reliability targets and actual equipment performance Summary for CIRED 1 Conference paper in Amsterdam Maintenance scheduling according to reliability targets and actual equipment performance Vukan Polimac and Jelica Polimac A method of optimising the lengths

More information

ISL Insulation monitoring devices Continuous monitoring of IT systems from photovoltaic to industrial applications.

ISL Insulation monitoring devices Continuous monitoring of IT systems from photovoltaic to industrial applications. ISL Insulation monitoring devices Continuous monitoring of IT systems from photovoltaic to industrial applications. Ensuring operational continuity To ensure the operational continuity of an electrical

More information

GENERATOR DIFFERENTIAL PROTECTION RELAY STABILITY VIS-A -VIS SELECTION OF CTS MR. H. C. MEHTA & MR. JAY MEHTA Power Linker Group Co.

GENERATOR DIFFERENTIAL PROTECTION RELAY STABILITY VIS-A -VIS SELECTION OF CTS MR. H. C. MEHTA & MR. JAY MEHTA Power Linker Group Co. GENERATOR DIFFERENTIAL PROTECTION RELAY STABILITY VIS-A -VIS SELECTION OF CTS MR. H. C. MEHTA & MR. JAY MEHTA Power Linker Group Co., Mumbai ABSTRACT : For generator differential protection, one set of

More information

DISTRIBUTION RELIABILITY USING RECLOSERS AND SECTIONALISERS

DISTRIBUTION RELIABILITY USING RECLOSERS AND SECTIONALISERS ABB DISTIBUTION ELIABILITY USING ECLOSES AND SECTIONALISES obert E. Goodin Chief Engineer ABB Inc. Lake Mary, FL Timothy S. Fahey, PE Sr. Application Engineer ABB Inc. aleigh, NC Andrew Hanson, PE Executive

More information

What will MV switchgear look like in the future? by Jean-Marc Biasse

What will MV switchgear look like in the future? by Jean-Marc Biasse What will MV switchgear look like in the future? by Jean-Marc Biasse Table of contents Introduction... 2 Brief history of the technologies used in medium voltage switchgear and control gear... 4 Evolution

More information

White Paper. Fiber Optics in Solar Energy Applications. By Alek Indra. Introduction. Solar Power Generation

White Paper. Fiber Optics in Solar Energy Applications. By Alek Indra. Introduction. Solar Power Generation s in Solar Energy Applications White Paper By Alek Indra Introduction Solar energy has recently become a popular alternative energy source to meet demands around the world due to the fluctuation of oil/coal

More information

Shunt Capacitor Bank Fundamentals and Protection

Shunt Capacitor Bank Fundamentals and Protection 2003 Conference for Protective Relay Engineers - Texas A&M University April 8-10, 2003, College Station (TX) Shunt Capacitor Bank Fundamentals and Protection Gustavo Brunello, M.Eng, P.Eng Dr. Bogdan Kasztenny

More information

ISIO 200. Binary Input/Output (I/O) Terminal with IEC 61850 Interface

ISIO 200. Binary Input/Output (I/O) Terminal with IEC 61850 Interface ISIO 200 Binary Input/Output (I/O) Terminal with IEC 61850 Interface Compact and Easy ISIO 200 Put your Binary I/Os where you need them ISIO 200 is a simple and versatile binary I/O terminal with IEC 61850

More information

The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies

The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies DATE: November 17, 1999 REVISION: AUTHOR: John Merrell Introduction In some short circuit studies, the X/R ratio is ignored when comparing

More information

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

Submit shop drawings for equipment provided under this section Shop drawings shall indicate: Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,

More information

Alternating Current and Direct Current

Alternating Current and Direct Current K Hinds 2012 1 Alternating Current and Direct Current Direct Current This is a Current or Voltage which has a constant polarity. That is, either a positive or negative value. K Hinds 2012 2 Alternating

More information

32VFD Variable Frequency Drives for Centrifugal Chillers

32VFD Variable Frequency Drives for Centrifugal Chillers 32VFD 32VFD Variable Frequency Drives for Centrifugal Chillers ENERGY-SAVING CONTROL FOR CENTRIFUGAL CHILLERS Reduce energy consumption in your existing centrifugal chiller Your chiller was specified to

More information

PSS SINCAL - Overview -

PSS SINCAL - Overview - PSS SINCAL - Overview - PTI Day Buenos Aires, October 19/20, 2010 Dr. Michael Schwan,, Siemens PTI (Germany) www.siemens.com/energy/power-technologies PSS SINCAL Overview Page 3 Network Calculation Software

More information

A MULTILEVEL INVERTER FOR SYNCHRONIZING THE GRID WITH RENEWABLE ENERGY SOURCES BY IMPLEMENTING BATTERY CUM DC-DC CONERTER

A MULTILEVEL INVERTER FOR SYNCHRONIZING THE GRID WITH RENEWABLE ENERGY SOURCES BY IMPLEMENTING BATTERY CUM DC-DC CONERTER A MULTILEVEL INVERTER FOR SYNCHRONIZING THE GRID WITH RENEWABLE ENERGY SOURCES BY IMPLEMENTING BATTERY CUM DC-DC CONERTER 1 KARUNYA CHRISTOBAL LYDIA. S, 2 SHANMUGASUNDARI. A, 3 ANANDHI.Y 1,2,3 Electrical

More information

Guide to the electrical parameter classifications of IEC 60950 and IEC 62368 safety standards

Guide to the electrical parameter classifications of IEC 60950 and IEC 62368 safety standards Guide to the electrical parameter classifications of IEC 60950 and IEC 62368 safety standards Abstract This Guide is an informative listing of selected terms and definitions found in IEC Glossary entry

More information

Test & Data Management Software

Test & Data Management Software Test & Data Management Software TDMS protective relays energy meters transducers power quality CT-VT-PT transformers ground grid circuit breakers batteries surge arresters The Integrated Testing Solution

More information

TDMS Test & Data Management Software

TDMS Test & Data Management Software Test & Data Management Software TDMS protective relays energy meters transducers power quality CT-VT-PT transformers ground grid circuit breakers batteries surge arresters The Integrated Testing Solution

More information

NEURO-FUZZY BASED POWER QUALITY IMPROVEMENTS IN A THREE PHASE FOUR WIRE DISTRIBUTION SYSTEM USING DSTATCOM

NEURO-FUZZY BASED POWER QUALITY IMPROVEMENTS IN A THREE PHASE FOUR WIRE DISTRIBUTION SYSTEM USING DSTATCOM NEURO-FUZZY BASED POWER QUALITY IMPROVEMENTS IN A THREE PHASE FOUR WIRE DISTRIBUTION SYSTEM USING DSTATCOM E.Babu 1,R.Subramanian 2 1, Department of Electrical and electronics engg 2 Department of Electrical

More information

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application g Digital Energy ITI Instrument Transformer Basic Technical Information and Application Table of Contents DEFINITIONS AND FUNCTIONS CONSTRUCTION FEATURES MAGNETIC CIRCUITS RATING AND RATIO CURRENT TRANSFORMER

More information

Electric Power Distribution

Electric Power Distribution Electric Power Distribution A S Pabla Consulting Engineer and Former Chief Engineer Punjab State Electricity Board McGraw-Hill New York Chicago San Francisco Lisbon London Madrid Mexico City Milan New

More information

EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID

EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID Tension (kv) Impedance (Ohms) EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID frequency (Hz) Simon DESCHANVRES Yannick VERNAY RTE, CNER, Substations Department t (ms) EMTP-RV Users Group

More information

Estimation of electrical losses in Network Rail Electrification Systems

Estimation of electrical losses in Network Rail Electrification Systems Estimation of electrical losses in Network Rail Electrification Systems Page 1 of 16 Contents 1. BACKGROUND...3 2. PURPOSE...3 3. SCOPE...3 4. DEFINITIONS & ABBREVIATIONS...4 5. NETWORK RAIL INFRASTRUCTURE

More information

Eaton s E-Series protective relay family

Eaton s E-Series protective relay family E-Series protective relays Feeder distribution relays Motor relays Transformer relays Generator relays Eaton s E-Series protective relay family Microprocessor-based design Eaton s E-Series relay family

More information

Developing an Agent-based Backup Protection System for Transmission Networks

Developing an Agent-based Backup Protection System for Transmission Networks Power Systems and Communications Infrastructures for the Future, Beijing, September 2002 Developing an Agent-based Backup Protection System for Transmission Networks X. R. Wang* Member IEEE, K. M. Hopkinson**

More information