Demand-Controlled Ventilation

Size: px
Start display at page:

Download "Demand-Controlled Ventilation"

Transcription

1 Demand-Controlled Ventilation When a building is occupied, it is unlikely that every room is at occupant capacity at any given point in time. As the number of people in a zone varies, the quantity of outdoor air required to properly ventilate that zone also varies. However, most buildings are ventilated at design occupancy levels in all spaces at all times, resulting in over-ventilated buildings. Demand-controlled ventilation (DCV) is a strategy that attempts to dynamically reset the outdoor airflow delivered to a zone based on the changing population within that zone. DCV strategies include time-ofday schedules, occupancy sensors, and CO 2 sensors. This article discusses strategies for implementing CO 2 based DCV and how to model these strategies in TRACE 7. Minimum Breathing Zone Requirements ASHRAE Standard 62.1 states that amount of outside air required to properly ventilate a space is the sum of the outside air required to dilute volatile organic compounds (VOCs) given off by paints, wall paper, furniture, etc., and the outside air required to dilute bioeffluents from the occupants in a space. In addition, the standard also permits dynamic reset of intake (outdoor) airflow as operating conditions change, as long as the system provides at least the required breathing zone outdoor airflow whenever a zone is occupied. The minimum breathing zone outdoor airflow (V bz ), is determined using Equation 6-1: Where: V bz = (R p P z ) + (R a A z ) V bz = breathing zone outdoor airflow A z = zone floor area: the net occupiable floor area of the ventilation zone ft 2 (m 2 ) R a = outdoor airflow rate required per unit area as determined from Table 6-1 P z = zone population: the number of people in the ventilation zone during typical usage. R p = outdoor airflow rate required per person as determined from Table 6-1

2 TRACE Scenario Let s take a look at how equation 6-1 comes into play in TRACE, using an example break room that is 2 ft. by 14 ft. In TRACE, the Apply ASHRAE Std /27 field must be set to Yes on the Create Rooms-Rooms tab. The values for R a and R p are set on the Create Rooms - Airflows tab. In this example, R p = 5 cfm per person and R a =.6 cfm per square foot. Area can be calculated from the room dimensions: A z = 2 14 = 28 sq ft Knowing the population density, the design population can also be calculated: P z = 28 sq feet 2 sq feet = 1.4 people The design ventilation for the break room can then be calculated by solving equation 6-1: V bz = (5 cfm per person 1.4 people) + (.6 cfm per sq ft 28 sq ft) = 23.8 cfm

3 The result is a linear relationship between the outdoor air requirement and the zone population. Outside Air vs Population Vot - Vbz Figure 1 TRACE will recalculate the zone ventilation requirement on an hourly basis during the simulation phase when the system ventilation flag on the Create Systems Advanced screen is set to ASHRAE Std /27 w/ Vent Reset. Because the values for R a, R p and the square footage are fixed for a given room, the only variable in equation 6-1 is the zone population (P z ). In this example, the population varies according to the People Office schedule.

4 The hourly ventilation airflow is calculated by multiplying the design ventilation airflow by the percentage from the people schedule. For this example, the hourly weekday ventilation when DCV is enabled is shown in Table 1: Time Percentage Design Ventilation (cfm) Hourly Ventilation (cfm) Mid - 7 am am - 8 am am - 5 pm pm - 6 pm pm - 7 pm pm - Mid 23.8 Table 1 CO 2 Based DCV Just as our surroundings outgas volatile organic compounds (VOCs), humans are also a source of pollution. This is especially apparent when large numbers of people live or work in enclosed, poorly ventilated areas for extended periods of time. The substances we emit into the air through normal biological processes are called bioeffluents. Studies have found that bioeffluents emitted from each person into the air can contain as many as 15 volatile substances. Principal among these are acetone, human skin, ethyl alcohol, methyl alcohol, and ethyl acetate. CO 2 based DCV assumes that people produce both bioeffluents and CO 2 in proportion to their activity level and as a result, the concentration of CO 2 in a space accurately represents the concentration of human bioeffluents. It is also assumed that CO 2 based steady-state equations can be used to estimate the people component of the ventilation load. Equation C-1 in Appendix C of ASHRAE 62.1 provides the following mass balance equation to calculate the outdoor airflow rate needed to maintain the steady-state CO 2 concentration below a given limit. Where: V o = outdoor airflow rate per person N = CO 2 generation rate per person C s = CO 2 concentration in the space C o = CO 2 concentration in the outdoor air N V o = C s C o

5 CO 2 based DCV makes one additional assumption: occupant activity level in a zone (in terms of metabolic rate, m) can be estimated with reasonable accuracy. Then the CO 2 generation rate per person (N) can be expressed in terms of metabolic rate (m) and the per person CO 2 generation rate (k): N = m x k Where: N = CO 2 generation rate per person m = activity level of occupants, met k =.84 cfm per met per person for healthy people The outdoor airflow rate per person (V o ) can be expressed in terms of V bz and P z : V o = V bz Pz Where: V bz = the minimum breathing zone outdoor airflow P z = the zone population Rewriting equation C-1 and substituting for N and V o yields equation 1: C s = k m + C V o bz Pz Proportional Control DCV This control strategy varies the intake airflow in direct proportion to the actual differential CO 2 level. Two control points (min CO 2 concentration, min ventilation airflow) and (max CO 2 concentration, design ventilation airflow) establish a linear relationship between the CO 2 concentration in the space and the ventilation airflow. A CO 2 sensor in the space measures the concentration and reports this value to a controller programmed with this relationship which resets the outdoor requirement in the space. (See Figure 2) (max CO 2, design OA) Outside Air (cfm) (min CO 2, min OA) CO2 Concentration Figure 2 The minimum CO 2 concentration is generally accepted to be that of the outdoor air (35 ppm - 4 ppm). The minimum ventilation airflow and maximum ventilation airflow are

6 calculated using equation 6-1, selecting Pz values of zero and the design occupancy respectively. The maximum CO 2 concentration is calculated using equation 1 as shown in the following example. Applying the proportional control strategy to the break room example the calculations yield the following results: Minimum CO 2 concentration Minimum ventilation airflow (V bz min ) CO 2 min = 4 ppm (Assumed) V bz min = (5 cfm per person people) + (.6 cfm per sq ft 4 sq ft) = 24 cfm Maximum ventilation airflow (V bz max ) V bz max = (5 cfm per person 2 people) + (.6 cfm per sq ft 4 sq ft) = 124 cfm To calculate the maximum CO 2 concentration it is first necessary to determine the metabolic rate (m) using Figure C-2 from Appendix G in ASHRAE Std Choosing an activity level of office work for the break room the metabolic rate is determined to be 1.2 met units. (See Figure C.2)

7 The maximum CO 2 concentration can now be calculated for the design occupancy using equation 1. C max =.84 cfm per met per person 1.2 met 124 cfm per person 2 people ppm = ppm The resulting ventilation is plotted along with the ASHRAE Std minimum ventilation requirements in Figure 3. Outside Air vs Population Vot - Vbz Vot - CO2 Figure 3 The difference between the two lines is an excess amount of outside air the space will receive for any given population. The reason for the over ventilation is that the controller models the change in CO 2 as a linear function. A plot of the total CO 2 in the break room versus population shows that it is not. (Refer to Figure 4)

8 Total CO2 vs Population Total CO Co2 Linear Figure 4 To understand how the controller determines the ventilation airflow, choose a discrete value for the number of people currently in the space. For this example it will be assumed that there are four people in the break room. The resulting CO 2 level in the space will be 1316 ppm. (See Figure 5) Total CO2 vs Population Total CO ppm Co2 Figure 5 A controller employing proportional control DCV will sense 1316 ppm of CO 2 in the space but has no knowledge of the actual population. The only thing it can do is control based on where the CO 2 level intersects linear function shown in Figure 4. In this example, the CO 2 level of 1316 ppm corresponds to 11.3 people in the space. (Refer to Figure 6)

9 Total CO 2 vs Population 25 2 Total CO ppm 5 Figure 6 Plotting the calculated population of 11.3 people against the minimum ventilation requirements calculated using equation 6-1 results in an outside air requirement (V ot ) of 8.3 cfm. (Refer to Figure 7) Outside Air vs Population Vot - Vbz Figure 7 The outside air requirement (8.3 cfm) can now be plotted against the break room population of four people. (See Figure 8)

10 Outside Air vs Population Vot - Vbz 4 People Figure 8 Plotting the outside air requirements for the entire population results in the curve shown in Figure 9 along with ASHRAE Std minimum ventilation requirements. Outside Air vs Population Vot - Vbz Vot - CO2 Figure 9

11 Single Setpoint CO 2 DCV This single setpoint strategy requires the user to enter only one value, the zone population for which both the fixed CO 2 setpoint and minimum ventilation airflow limit are to be calculated. The controller adjusts the outdoor airflow intake to maintain a fixed CO 2 level in the space, thereby maintaining a fixed outdoor airflow rate per person. A minimum ventilation airflow limit is enforced if CO 2 levels in the space fall below the setpoint. Figure 1 illustrates how CO 2 levels will change in response to varying populations in the break room example with a setpoint population of 1 people. Total CO 2 vs Population Total CO Co2 Figure 1 The fixed CO 2 setpoint is calculated for the setpoint occupancy using equation 1. C max =.84 cfm per met per person 1.2 met 74 cfm per person 1 people ppm = ppm Where the minimum ventilation airflow (V bz min ) V bz min = (5 cfm per person 1 people) + (.6 cfm per sq ft 4 sq ft) = 74 cfm The resulting ventilation is plotted along with the ASHRAE Std minimum ventilation requirements in Figure 11.

12 1 People Single Setpoint Min 1 Vot Figure 11 The difference between the two lines is the excess amount of outside air the space will receive whenever the space population is above or below the setpoint population. Figures 12 and 13 illustrate how different setpoint populations will affect the amount of excess ventilation for different populations People Single Setpoint Min 5 Vot Figure 12

13 15 People Single Setpoint Min 15 Vot 2 Figure 13 Modeling CO 2 Based DCV in TRACE 7 On the Rooms tab of Create Rooms (or on the thermostat template), select a CO2 Sensor location (either Room or None) for the rooms that will have demand-control ventilation control. On the Airflows tab of Create Rooms, select Yes in the Apply ASHRAE Std /27 field.

14 The DCV Min OA Intake field must now be edited to calculate the appropriate setpoint according to the CO2 based DCV control strategy that is going to be implemented. DCV Min OA Intake options % Room Population Best practice is to select % Room Population for both proportional control and single setpoint DCV. When % Room Population is selected, the percentage is multiplied times the design occupancy of the space to determine the number of people at which to calculate the minimum ventilation airflow using equation 6.1. Where: V bz = (R p P z ) + (R a A z ) V bz = breathing zone outdoor airflow A z = zone floor area: the net occupiable floor area of the ventilation zone ft2 (m2) R a = outdoor airflow rate required per unit area as determined from Table 6-1 P z = zone population: the number of people in the ventilation zone during typical usage. R p = outdoor airflow rate required per person as determined from Table 6-1 When using Single Setpoint control, the number of people is also used to calculate the fixed CO 2 setpoint. (Refer to the Single Setpoint CO 2 DCV section of this document.) % Dsn OA Airflow Note: % Dsn OA Airflow is only applicable with proportional control DCV. The reason is that population is required to calculate the fixed CO 2 setpoint for single setpoint control. % Dsn OA Airflow allows the user to calculate a minimum ventilation airflow based on the design outside airflow rather than using equation C-1.

15 Default Values CO2 based DCV method: None or Proportional Control If the field is left blank, the program will default to % CO2 based DCV method: Single Setpoint If the field is left blank or set to %, the program defaults to 4%. If the value field is left blank the default of zero will be used. Selecting Proportional Control or Single Setpoint On the Selection tab of Create Systems, click the Advanced button. Select the option ASHRAE Std /27 w/ Vent Reset in the System Ventilation Flag field. Note: System-level ventilation reset is required for the system to be able to handle zone-level demand-control ventilation. At the bottom of the screen, select the desired C2-based DCV option (None, Proportional Control, or Single Setpoint).

CHAPTER 4 VENTILATION

CHAPTER 4 VENTILATION CHAPTER 4 VENTILATION SECTION 401 GENERAL 401.1 Scope. This chapter, in conjunction with the building code, shall govern the ventilation of spaces within a building intended to be occupied. Mechanical

More information

LEED Breadth. Introduction

LEED Breadth. Introduction LEED Breadth Introduction As of January 2007, the project team has attempted to achieve a total of 50 points under the Leadership in Energy and Environmental Design for New Construction (LEED-NC) rating

More information

Why Measure Carbon Dioxide Inside Buildings? By Rich Prill, Washington State University Extension Energy Program

Why Measure Carbon Dioxide Inside Buildings? By Rich Prill, Washington State University Extension Energy Program Why Measure Carbon Dioxide Inside Buildings? By Rich Prill, Indoor air quality Workers and students spend about half their waking hours at work or school. Therefore, maintaining adequate indoor air quality

More information

Information paper 20. Prepared by: David Clark. book:

Information paper 20. Prepared by: David Clark. book: Information paper 20 Ventilation rates in offices and natural mechanical Prepared by: David Clark A paper referenced in the book: Cundall Johnston & Partners LLP. 2013 Issue 1.0: 29 July 2013 This information

More information

Applying Schedules and Profiles in HAP

Applying Schedules and Profiles in HAP This HAP e-help discusses the importance of properly applying schedules and profiles in HAP. We will also discuss potential misapplications of these user inputs. First, we need to understand the differences

More information

Carbon Dioxide (CO2) HVAC Basics

Carbon Dioxide (CO2) HVAC Basics Carbon Dioxide (CO2) HVAC Basics Copyright 1998 Honeywell Inc. All Rights Reserved 1 63-7049 63-7049 BACKGROUND Building managers and owners have become aware that control of temperature and humidity alone

More information

Using Time-of-Day Scheduling To Save Energy

Using Time-of-Day Scheduling To Save Energy The following article was published in ASHRAE Journal, May 29. Copyright 29 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. It is presented for educational purposes only.

More information

Demand Control Ventilation Application Guide for Consulting Engineers. 145-400E Rev. 3, August 2013

Demand Control Ventilation Application Guide for Consulting Engineers. 145-400E Rev. 3, August 2013 Demand Control Ventilation Application Guide for Consulting Engineers 145-400E Rev. 3, August 2013 Rev. 3, August, 2013 Notice Document information is subject to change without notice by Siemens Industry,

More information

Building Performance Evaluation Guide Version 1.7

Building Performance Evaluation Guide Version 1.7 Building Performance Evaluation Guide Version 1.7 Prepared by Center for Energy and Environment January 2014 Minnesota Sustainable Building 2030: Building Performance Evaluation Guide p 1 1. Schematic

More information

PERCENT OUTDOOR AIR (%OA) CALCULATION AND ITS USE

PERCENT OUTDOOR AIR (%OA) CALCULATION AND ITS USE PERCENT OUTDOOR AIR (%OA) CALCULATION AND ITS USE APPLICATION NOTE TI-138 TSI s IAQ-CALC TM Indoor Air Quality Meter and TH-CALC TM Thermohygrometer calculate Percent Outdoor Air (%OA). In order to take

More information

Ammonia Detection System Codes and Design Specifications

Ammonia Detection System Codes and Design Specifications Ammonia Detection System Codes and Design Specifications December 28, 2015 Revision 5 920 N Trade Winds Pkwy Columbia, MO 65201 Ammonia detection system codes and design specifications Following is a discussion

More information

VAV Laboratory Room Airflow The Lowdown on Turndown

VAV Laboratory Room Airflow The Lowdown on Turndown Technology Report March, 2003 VAV Laboratory The Lowdown on Turndown Turndown comparison of these two turndown ratios. Note the small actual airflow difference between them. control ranges are normally

More information

SUMMARY OF ASHRAE S POSITION ON CARBON DIOXIDE (CO 2 ) LEVELS IN SPACES. Stephen Petty, P.E., C.I.H.

SUMMARY OF ASHRAE S POSITION ON CARBON DIOXIDE (CO 2 ) LEVELS IN SPACES. Stephen Petty, P.E., C.I.H. SUMMARY OF ASHRAE S POSITION ON CARBON DIOXIDE (CO 2 ) LEVELS IN SPACES Stephen Petty, P.E., C.I.H. Purpose of the Summary Statement: It is widely reported by the technical community involved in indoor

More information

Fan Applications & System Guide

Fan Applications & System Guide Fan Applications & System Guide Airflow for general ventilation can be calculated by; Area Method Air Change Method Occupancy Method Ventilation Calculation Methods Area Method Derives the ventilation

More information

Analysis of the UNH Data Center Using CFD Modeling

Analysis of the UNH Data Center Using CFD Modeling Applied Math Modeling White Paper Analysis of the UNH Data Center Using CFD Modeling By Jamie Bemis, Dana Etherington, and Mike Osienski, Department of Mechanical Engineering, University of New Hampshire,

More information

Dual Maximum VAV Box Controls

Dual Maximum VAV Box Controls ASHRAE Golden Gate Chapter November 13, 2014 Dual Maximum VAV Box Controls Steven T. Taylor, PE FASHRAE Taylor Engineering LLC staylor@taylor engineering.com Agenda VAV Box basics Sizing VAV Boxes How

More information

IES <Virtual Environment> training. Trainee notes. ASHRAE 90.1 Appendix G - PRM Navigator. Version 6.4.0.7

IES <Virtual Environment> training. Trainee notes. ASHRAE 90.1 Appendix G - PRM Navigator. Version 6.4.0.7 IES training Trainee notes ASHRAE 90.1 Appendix G - PRM Navigator Version 6.4.0.7 Introduction These training notes are to be used in conjunction with your ASHRAE 90.1 Appendix G

More information

Arizona State University. Understanding the Impact of Urban Heat Island in Phoenix

Arizona State University. Understanding the Impact of Urban Heat Island in Phoenix Understanding the Impact of Urban Heat Island in Phoenix ( ) Summer Night-time 'min-low' temperatures and its impact on the energy consumption of various building typologies Presented By: Sandeep Doddaballapur

More information

ASHRAE Std 62.1-2010 Update Where Are We Now?

ASHRAE Std 62.1-2010 Update Where Are We Now? ASHRAE Std 62.1-2010 Update Where Are We Now? October 2012 Dennis A. Stanke Trane La Crosse, WI ASHRAE Standard 62.1 What Is It? Title: Ventilation for Acceptable Indoor Air Quality Purpose: to specify

More information

34% 81% 84% 19% GOLD PROJECT HIGHLIGHTS. LEED Facts. Stubbs Laboratory

34% 81% 84% 19% GOLD PROJECT HIGHLIGHTS. LEED Facts. Stubbs Laboratory HARVARD UNIVERSITY FACULTY OF ARTS AND SCIENCES LEED-CI V3.0 STUBBS LABORATORY GORDON MCKAY LABS BUILDING Gordon McKay Building, 9 Oxford Street, Cambridge, MA 02138 GOLD The Stubbs Laboratory is a 2,035

More information

Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001

Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001 Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001 Presented by: Liberty Engineering, LLP 1609 Connecticut Avenue

More information

VENTILATION CHAPTER 4

VENTILATION CHAPTER 4 CHAPTER 4 VENTILATION SECTION 1 GENERAL 1.1 Scope. This chapter shall govern the ventilation of spaces within a building intended to be occupied. This chapter does not govern the requirements for smoke

More information

CHAPTER 4 VENTILATION

CHAPTER 4 VENTILATION CHAPTER 4 VENTILATION SECTION 1 GENERAL 1.1 Scope. This chapter shall govern the ventilation of spaces within a building intended to be occupied. Mechanical exhaust systems, including exhaust systems serving

More information

NCSS Statistical Software Principal Components Regression. In ordinary least squares, the regression coefficients are estimated using the formula ( )

NCSS Statistical Software Principal Components Regression. In ordinary least squares, the regression coefficients are estimated using the formula ( ) Chapter 340 Principal Components Regression Introduction is a technique for analyzing multiple regression data that suffer from multicollinearity. When multicollinearity occurs, least squares estimates

More information

Raising the Bar: A Comparison Study of Iowa s Current and Proposed Energy Code

Raising the Bar: A Comparison Study of Iowa s Current and Proposed Energy Code Raising the Bar: A Comparison Study of Iowa s Current and Proposed Energy Code Julia Gauthier, LEED AP BD+C Jeanne Huntsman, AIA, LEED Green Associate The Weidt Group Raising the Bar Special statements

More information

Basic Math for the Small Public Water Systems Operator

Basic Math for the Small Public Water Systems Operator Basic Math for the Small Public Water Systems Operator Small Public Water Systems Technology Assistance Center Penn State Harrisburg Introduction Area In this module we will learn how to calculate the

More information

Venice Library Humidity Study. for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205. Report April 13, 2015

Venice Library Humidity Study. for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205. Report April 13, 2015 for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205 Report April 13, 2015 Moses & Associates, Inc. 2209 NW 40 th Terrace, Suite A Gainesville, FL 32605 FL License EB-0003097

More information

engineers newsletter live Course Outline

engineers newsletter live Course Outline engineers newsletter live Course Outline ASHRAE Standards 62.1 and 90.1 and VAV Systems These days many designers want to comply with both Standard 62.1 and Standard 90.1. Requirements from both standards

More information

Comparables Sales Price

Comparables Sales Price Chapter 486 Comparables Sales Price Introduction Appraisers often estimate the market value (current sales price) of a subject property from a group of comparable properties that have recently sold. Since

More information

ENERGY EFFICIENCY COMPARISON

ENERGY EFFICIENCY COMPARISON California Energy Commission STAFF REPORT ENERGY EFFICIENCY COMPARISON California s Building Energy Efficiency Standards and the International Energy Conservation Code and American Society of Heating,

More information

Case Studies: Infrared Heating in Industrial Applications

Case Studies: Infrared Heating in Industrial Applications Case Studies: Infrared Heating in Industrial Applications Chao Chen, Puget Sound Energy ABSTRACT Puget Sound Energy (PSE) is a utility which serves more than one million electric customers and over 700,000

More information

Energy Savings With Adjustable Frequency Drives. for Centrifugal Fans

Energy Savings With Adjustable Frequency Drives. for Centrifugal Fans Energy Savings With Adjustable Frequency Drives for Centrifugal Fans 2 Centrifugal Fans Centrifugal Fan Fans are designed to be capable of meeting the maximum demand of the system in which they are installed.

More information

THE APPLICATION OF OZONE FOR AIR TREATMENT: CASE STUDY OF A BINGO HALL HVAC SYSTEM

THE APPLICATION OF OZONE FOR AIR TREATMENT: CASE STUDY OF A BINGO HALL HVAC SYSTEM 1 Application Note AT-102 THE APPLICATION OF OZONE FOR AIR TREATMENT: CASE STUDY OF A BINGO HALL HVAC SYSTEM Lawrence B. Kilham 1 and Randall M. Dodd 2 1 Eco Sensors, Inc. Santa Fe, New Mexico, USA larry@ecosensors.com

More information

Ammonia Detection System Codes and Design Specifications. Brian EuDaly, P.E. Calibration Technologies, Inc.

Ammonia Detection System Codes and Design Specifications. Brian EuDaly, P.E. Calibration Technologies, Inc. Ammonia Detection System Codes and Design Specifications Brian EuDaly, P.E. Calibration Technologies, Inc. Ammonia Detection Code Requirements IIAR-2A-2008 ASHRAE 15-2010 NFPA 1 2012 UMC 2012 Preprint

More information

Integrating Kitchen Exhaust Systems with Building HVAC

Integrating Kitchen Exhaust Systems with Building HVAC Design Guide 3 Improving Commercial Kitchen Ventilation System Performance Integrating Kitchen Exhaust Systems with Building HVAC This design guide provides information that may help achieve optimum performance

More information

HVAC Systems in Schools & Commercial Buildings and Radon

HVAC Systems in Schools & Commercial Buildings and Radon HVAC Systems in Schools & Commercial Buildings and Radon References US EPA Radon Prevention in the Design and Construction of Schools and Other Large Buildings http://www.epa.gov/ordntrnt/ord/nrmrl/pubs/1993/air/

More information

Slope Density. Appendix F F-1 STATEMENT OF PURPOSE DISCUSSION OF SLOPE

Slope Density. Appendix F F-1 STATEMENT OF PURPOSE DISCUSSION OF SLOPE Appendix F Slope Density F-1 STATEMENT OF PURPOSE This document has been prepared with the intent of acquainting the general reader with the slope-density approach to determining the intensity of residential

More information

HVAC Calculations and Duct Sizing

HVAC Calculations and Duct Sizing PDH Course M199 HVAC Calculations and Duct Sizing Gary D. Beckfeld, M.S.E., P.E. 2007 PDH Center 2410 Dakota Lakes Drive Herndon, VA 20171-2995 Phone: 703-478-6833 Fax: 703-481-9535 www.pdhcenter.com An

More information

2011 Energy Efficiency Expo!

2011 Energy Efficiency Expo! Welcome to the 2011 Energy Efficiency Expo! Thank you to our session sponsors! Comparison Between the 2009 and 2012 International Energy Conservation Code What s coming when the new commercial energy code

More information

SAVINGS with DCV retrofits

SAVINGS with DCV retrofits PROVEN ENERGY SAVINGS with DCV retrofits Using CO 2 levels to vary fresh air rate saves energy and assures good IAQ E very once in a while, a new technology innovation hits a sweet spot where both its

More information

Point Biserial Correlation Tests

Point Biserial Correlation Tests Chapter 807 Point Biserial Correlation Tests Introduction The point biserial correlation coefficient (ρ in this chapter) is the product-moment correlation calculated between a continuous random variable

More information

The Impact of Demand-Controlled and Economizer Ventilation Strategies on Energy Use in Buildings

The Impact of Demand-Controlled and Economizer Ventilation Strategies on Energy Use in Buildings 4276 The Impact of Demand-Controlled and Economizer Ventilation Strategies on Energy Use in Buildings Michael J. Brandemuehl, Ph.D., P.E. Member ASHRAE James E. Braun, Ph.D., P.E. Member ASHRAE ABSTRACT

More information

Problem Statement In order to satisfy production and storage requirements, small and medium-scale industrial

Problem Statement In order to satisfy production and storage requirements, small and medium-scale industrial Problem Statement In order to satisfy production and storage requirements, small and medium-scale industrial facilities commonly occupy spaces with ceilings ranging between twenty and thirty feet in height.

More information

HOW TO CONDUCT ENERGY SAVINGS ANALYSIS IN A FACILITY VALUE ENGINEERING STUDY

HOW TO CONDUCT ENERGY SAVINGS ANALYSIS IN A FACILITY VALUE ENGINEERING STUDY HOW TO CONDUCT ENERGY SAVINGS ANALYSIS IN A FACILITY VALUE ENGINEERING STUDY Benson Kwong, CVS, PE, CEM, LEED AP, CCE envergie consulting, LLC Biography Benson Kwong is an independent consultant providing

More information

SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP

SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP research journal 2013 / VOL 05.01 www.perkinswill.com SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP ARCHITECTURE AND ENGINEERING OF SUSTAINABLE BUILDINGS Current Trends in Low-Energy HVAC Design

More information

Enclosure and Airflow Management Solution

Enclosure and Airflow Management Solution Enclosure and Airflow Management Solution CFD Analysis Report Des Plaines, Illinois December 22, 2013 Matt Koukl- DECP Mission Critical Systems Affiliated Engineers, Inc. Contents Executive Summary...

More information

Rate of Heating Analysis of Data Centers during Power Shutdown

Rate of Heating Analysis of Data Centers during Power Shutdown 2011. American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Transactions, Volume 117, Part 1. For personal use only. Additional reproduction,

More information

DesignBuilder EMS - Intro

DesignBuilder EMS - Intro DesignBuilder EMS - Intro Functionality not provided in standard E+ can be programmed Programming language called E+ Runtime Language (Erl) DesignBuilder extensions added to form DB Erl E+ interprets and

More information

Element D Services Heating, Ventilating, and Air Conditioning

Element D Services Heating, Ventilating, and Air Conditioning Load Calculation Criteria PART 1 - GENERAL 1.01 OVERVIEW A. This section includes requirements for calculating HVAC cooling and heating loads. B. Load calculations must be performed in accordance with

More information

GeoGebra Statistics and Probability

GeoGebra Statistics and Probability GeoGebra Statistics and Probability Project Maths Development Team 2013 www.projectmaths.ie Page 1 of 24 Index Activity Topic Page 1 Introduction GeoGebra Statistics 3 2 To calculate the Sum, Mean, Count,

More information

Results Based Maintenance: Next Generation Preventive and Predictive Maintenance By Gordon Sharp, MSEE

Results Based Maintenance: Next Generation Preventive and Predictive Maintenance By Gordon Sharp, MSEE Results Based Maintenance: Next Generation Preventive and Predictive Maintenance By Gordon Sharp, MSEE Introduction For years the facility management industry has acted on the prudent belief that preventive

More information

Fans That Sense & Extract Volatile Organic Compounds and Humidity

Fans That Sense & Extract Volatile Organic Compounds and Humidity Premium Choice Ventilation Fans Featuring Fans That Sense & Extract Volatile Organic Compounds and Humidity Indoor Air Quality Concerns Today s homes are built to be tighter and more energy efficient than

More information

AIR DISTRIBUTION FOR COMFORT AND IAQ

AIR DISTRIBUTION FOR COMFORT AND IAQ AIR DISTRIBUTION FOR COMFORT AND IAQ Heating Piping and Air Conditioning March 1998 Dan Int-Hout Chief Engineer KRUEGER EXCELLENCE IN AIR DISTRIBUTION Modern environmentally controlled spaces consume significant

More information

Confidence Intervals for One Standard Deviation Using Standard Deviation

Confidence Intervals for One Standard Deviation Using Standard Deviation Chapter 640 Confidence Intervals for One Standard Deviation Using Standard Deviation Introduction This routine calculates the sample size necessary to achieve a specified interval width or distance from

More information

KINETIC DETERMINATION OF SELENIUM BY VISIBLE SPECTROSCOPY (VERSION 1.8)

KINETIC DETERMINATION OF SELENIUM BY VISIBLE SPECTROSCOPY (VERSION 1.8) Selenium Determination, Page 1 KINETIC DETERMINATION OF SELENIUM BY VISIBLE SPECTROSCOPY I. BACKGROUND. (VERSION 1.8) The majority of reactions used in analytical chemistry possess the following characteristics:

More information

This notice sets forth interim guidance, pending the issuance of regulations,

This notice sets forth interim guidance, pending the issuance of regulations, Part III - Administrative, Procedural, and Miscellaneous Deduction for Energy Efficient Commercial Buildings Notice 2006-52 SECTION 1. PURPOSE This notice sets forth interim guidance, pending the issuance

More information

Components HVAC General Standards HVAC Guidelines HVAC System Selection Life Cycle Cost Analysis

Components HVAC General Standards HVAC Guidelines HVAC System Selection Life Cycle Cost Analysis Components HVAC General System Selection Life Cycle Cost Analysis Outdoor Air Design Values Indoor Air Design Values Outdoor Air Ventilation Welding Ventilation Temperature Control Systems Ductwork HVAC

More information

UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01

UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01 GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per

More information

Unique Airflow Visualization Techniques for the Design and Validation of Above-Plenum Data Center CFD Models

Unique Airflow Visualization Techniques for the Design and Validation of Above-Plenum Data Center CFD Models Unique Airflow Visualization Techniques for the Design and Validation of Above-Plenum Data Center CFD Models The MIT Faculty has made this article openly available. Please share how this access benefits

More information

CITY PLAN REVIEW AND INSPECTION. Lisa Fleming Brown, CPM

CITY PLAN REVIEW AND INSPECTION. Lisa Fleming Brown, CPM CITY PLAN REVIEW AND INSPECTION Lisa Fleming Brown, CPM Houston Commercial Energy Conservation Code (2011) A choice of 2009 IECC or ASHRAE 90.1-2007 with amendments. Effective September 2, 2011. Complete

More information

Energy Savings in High-Rise Buildings Using High-Reflective Coatings

Energy Savings in High-Rise Buildings Using High-Reflective Coatings Energy Savings in High-Rise Buildings Using High-Reflective Coatings Executive Summary: Nevertheless, the simulation analyses showed that when designing a building for low energy consumption, even in cold

More information

Fan Basics and Selection Criteria (How to Use)

Fan Basics and Selection Criteria (How to Use) Feature: Understanding SANYO DENKI Products from Scratch Fan Basics and Selection Criteria (How to Use) Honami Osawa 1. Introduction In recent years, the importance of cooling technology has become even

More information

ME 315 - Heat Transfer Laboratory. Experiment No. 7 ANALYSIS OF ENHANCED CONCENTRIC TUBE AND SHELL AND TUBE HEAT EXCHANGERS

ME 315 - Heat Transfer Laboratory. Experiment No. 7 ANALYSIS OF ENHANCED CONCENTRIC TUBE AND SHELL AND TUBE HEAT EXCHANGERS ME 315 - Heat Transfer Laboratory Nomenclature Experiment No. 7 ANALYSIS OF ENHANCED CONCENTRIC TUBE AND SHELL AND TUBE HEAT EXCHANGERS A heat exchange area, m 2 C max maximum specific heat rate, J/(s

More information

CHAPTER 4 VENTILATION AIR SUPPLY

CHAPTER 4 VENTILATION AIR SUPPLY CHAPTER 4 VENTILATION AIR SUPPLY 401.0 General. 401.1 Applicability. This chapter contains requirements for ventilation air supply, exhaust, and makeup-air requirements for occupiable spaces within a building.

More information

The Kinetics of Enzyme Reactions

The Kinetics of Enzyme Reactions The Kinetics of Enzyme Reactions This activity will introduce you to the chemical kinetics of enzyme-mediated biochemical reactions using an interactive Excel spreadsheet or Excelet. A summarized chemical

More information

Sample Problems. Practice Problems

Sample Problems. Practice Problems Lecture Notes Quadratic Word Problems page 1 Sample Problems 1. The sum of two numbers is 31, their di erence is 41. Find these numbers.. The product of two numbers is 640. Their di erence is 1. Find these

More information

MECHANICAL SYSTEMS DESIGN. Team 2010 2

MECHANICAL SYSTEMS DESIGN. Team 2010 2 MECHANICAL SYSTEMS DESIGN Andrew Bridges, Ben Hollon, Sean Kolich, Weston Arbogast, Kaitlin Page Andrew Bridges, Ben Hollon, Sean Kolich, Weston Arbogast, Kaitlin Page Team 2010 2 PRESENTATION OVERVIEW

More information

Engineers Newsletter. Understanding Single-Zone VAV Systems. providing insights for today s hvac system designer. volume 42 2

Engineers Newsletter. Understanding Single-Zone VAV Systems. providing insights for today s hvac system designer. volume 42 2 providing insights for today s hvac system designer Engineers Newsletter volume 42 2 Understanding Single-Zone VAV Systems Single-zone variable-air-volume (VAV) is not a new concept, but due to new energy

More information

EFFECTS OF INDOOR RELATIVE HUMIDITY ON REFRIGERATED DISPLAY CASE PERFORMANCE

EFFECTS OF INDOOR RELATIVE HUMIDITY ON REFRIGERATED DISPLAY CASE PERFORMANCE P (5, EFFECTS OF INDOOR RELATIVE HUMIDITY ON REFRIGERATED DISPLAY CASE PERFORMANCE Ronald H. Howell, Professor Luis Rosario, Graduate Student Antonio Bula, Graduate Student Department of Mechanical Engineering

More information

Pearson's Correlation Tests

Pearson's Correlation Tests Chapter 800 Pearson's Correlation Tests Introduction The correlation coefficient, ρ (rho), is a popular statistic for describing the strength of the relationship between two variables. The correlation

More information

Confidence Intervals for the Difference Between Two Means

Confidence Intervals for the Difference Between Two Means Chapter 47 Confidence Intervals for the Difference Between Two Means Introduction This procedure calculates the sample size necessary to achieve a specified distance from the difference in sample means

More information

Methods for Effective Room Air Distribution. Dan Int-Hout Chief Engineer, Krueger Richardson, Texas

Methods for Effective Room Air Distribution. Dan Int-Hout Chief Engineer, Krueger Richardson, Texas Methods for Effective Room Air Distribution Dan Int-Hout Chief Engineer, Krueger Richardson, Texas Agenda Overview LEED issues and Update Perimeter Acoustics Thermal Comfort IAQ / Standard 62.1 Update

More information

DEVELOPMENT OF AN OPEN SOURCE HOURLY BUILDING ENERGY MODELING SOFTWARE TOOL

DEVELOPMENT OF AN OPEN SOURCE HOURLY BUILDING ENERGY MODELING SOFTWARE TOOL DEVELOPMENT OF AN OPEN SOURCE HOURLY BUILDING ENERGY MODELING SOFTWARE TOOL Brittany Hanam, MASc, EIT RDH Building Engineering Ltd. Vancouver, BC John Straube, PhD, P.Eng. Building Engineering Group, Civil

More information

Nonlinear Systems and the Conic Sections

Nonlinear Systems and the Conic Sections C H A P T E R 11 Nonlinear Systems and the Conic Sections x y 0 40 Width of boom carpet Most intense sonic boom is between these lines t a cruising speed of 1,40 miles per hour, the Concorde can fly from

More information

HVAC Checklist - Long Form

HVAC Checklist - Long Form HVAC Checklist - Long Form Page 1 of 14 Appendix B discusses HVAC system components in relation to indoor air quality. utside Air Intake Location pen during occupied hours? Unobstructed? Standing water,

More information

Comparing Energy Savings of Different VAV Systems

Comparing Energy Savings of Different VAV Systems Comparing Energy Savings of Different VAV Systems Prepared By: Martyn Dodd mart@energysoft.com EnergySoft LLC 1025 5th Street, Suite A Novato, CA 94945 415-897-6400 www.energysoft.com Last Modified: March

More information

SAM HOUSTON STATE UNIVERSITY

SAM HOUSTON STATE UNIVERSITY PART 1: GENERAL 1.01 General Requirements A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the

More information

T 3 Series VAV Diffusers Analog Diffuser Steel Square Panel Horizontal Pattern Model: T 3 SQ

T 3 Series VAV Diffusers Analog Diffuser Steel Square Panel Horizontal Pattern Model: T 3 SQ TSQ--0 7-7-07 T Series VAV Diffusers Analog Diffuser Steel Square Panel Horizontal Pattern Model: T SQ Model Configuration T SQ- Heating / Cooling Border Type (Lay-In) Full Face Nominal Round Duct Size

More information

New Homes EPS Modeling Frequently Asked Questions. Developed by Energy Trust of Oregon

New Homes EPS Modeling Frequently Asked Questions. Developed by Energy Trust of Oregon New Homes EPS Modeling Frequently Asked Questions Developed by Energy Trust of Oregon 1 General Questions 3 REM/Rate questions 4 -Creating custom entries 4 -Modeling Heat Pumps 5 -Modeling HRV/ERV 7 -Modeling

More information

Example Retrocommissioning Measure: Opening Throttled Discharge Valves

Example Retrocommissioning Measure: Opening Throttled Discharge Valves Opening Throttled Discharge Valves This 21-story building, constructed in 1997, is located in Oregon and contains 589,000 gross square feet of mostly office occupancy. The HVAC system includes six large

More information

Centrifugal Fans and Pumps are sized to meet the maximum

Centrifugal Fans and Pumps are sized to meet the maximum Fans and Pumps are sized to meet the maximum flow rate required by the system. System conditions frequently require reducing the flow rate. Throttling and bypass devices dampers and valves are installed

More information

ACFM vs. SCFM vs. ICFM Series of Technical White Papers from Ohio Medical Corporation

ACFM vs. SCFM vs. ICFM Series of Technical White Papers from Ohio Medical Corporation ACFM vs. SCFM vs. ICFM Series of Technical White Papers from Ohio Medical Corporation Ohio Medical Corporation 1111 Lakeside Drive Gurnee, IL 60031 Phone: (800) 448-0770 Fax: (847) 855-6304 info@ohiomedical.com

More information

City Code of ANN ARBOR, MICHIGAN Chapter 55 Zoning

City Code of ANN ARBOR, MICHIGAN Chapter 55 Zoning ARTICLE II. USE REGULATIONS 5:10.2. R1A, R1B, R1C, R1D single family dwelling district (1) Intent. (a) These single family residential districts are designed to provide an environment of predominantly

More information

Indoor air quality monitoring made easy

Indoor air quality monitoring made easy Indoor air quality monitoring made easy with the Fluke 985 Particle Counter Application Note Introduction Energy savings is top of facilities owners agenda. HVAC system tends to be the largest contributor

More information

Spectrophotometry and the Beer-Lambert Law: An Important Analytical Technique in Chemistry

Spectrophotometry and the Beer-Lambert Law: An Important Analytical Technique in Chemistry Spectrophotometry and the Beer-Lambert Law: An Important Analytical Technique in Chemistry Jon H. Hardesty, PhD and Bassam Attili, PhD Collin College Department of Chemistry Introduction: In the last lab

More information

CORRELATED TO THE SOUTH CAROLINA COLLEGE AND CAREER-READY FOUNDATIONS IN ALGEBRA

CORRELATED TO THE SOUTH CAROLINA COLLEGE AND CAREER-READY FOUNDATIONS IN ALGEBRA We Can Early Learning Curriculum PreK Grades 8 12 INSIDE ALGEBRA, GRADES 8 12 CORRELATED TO THE SOUTH CAROLINA COLLEGE AND CAREER-READY FOUNDATIONS IN ALGEBRA April 2016 www.voyagersopris.com Mathematical

More information

APC APPLICATION NOTE #112

APC APPLICATION NOTE #112 #112 Best Practices for Deploying the InfraStruXure InRow SC By David Roden Abstract The InfraStruXure InRow SC (ACSC100 and ACSC101) is a self-contained air conditioner for server rooms and wiring closets.

More information

Resources: The Room Inventory. Astra Schedule VII Training Manual

Resources: The Room Inventory. Astra Schedule VII Training Manual Last Update: August 2011 Release 7.5 Resources: The Room Inventory This lesson is specifically designed to help Astra Schedule administrators create and manage the system s room inventory as well as provide

More information

for Plans Examiners and Building Inspectors

for Plans Examiners and Building Inspectors Building Technologies Program HVAC Controls Guide for Plans Examiners and Building Inspectors September 2011 Authors: Eric Makela, PNNL James Russell, PECI Sarah Fujita, PECI Cindy Strecker, PECI Prepared

More information

Pricing complex options using a simple Monte Carlo Simulation

Pricing complex options using a simple Monte Carlo Simulation A subsidiary of Sumitomo Mitsui Banking Corporation Pricing complex options using a simple Monte Carlo Simulation Peter Fink Among the different numerical procedures for valuing options, the Monte Carlo

More information

DUAL SENSING DIGITAL THERMOSTAT PRODUCT INSTRUCTIONS. Construction Automotive Industry

DUAL SENSING DIGITAL THERMOSTAT PRODUCT INSTRUCTIONS.  Construction Automotive Industry DUAL SENSING DIGITAL THERMOSTAT PRODUCT INSTRUCTIONS www.rehau.com Construction Automotive Industry SCOPE This guide gives instruction regarding REHAU Programmable Digital Thermostat installation and operation.

More information

Exhaust Calculation Booklet

Exhaust Calculation Booklet Exhaust Calculation Booklet American Dryer Corporation 88 Currant Road Fall River MA 02720-4781 Telephone: (508) 678-9000 / Fax: (508) 678-9447 e-mail: techsupport@amdry.com ADC Part No. 450450 Exhaust

More information

IES <Virtual Environment> Tutorial. Apache Sim (Version 6.0)

IES <Virtual Environment> Tutorial. Apache Sim (Version 6.0) IES Tutorial Apache Sim (Version 6.0) Introduction This tutorial will begin by showing you how to use the Building Template Manager (BTM) to create thermal and construction data for

More information

Lighting Requirements

Lighting Requirements ASHRAE/IESNA Standard 90.1-1999 Lighting Requirements Joseph G. Howley Jr., IESNA GE Lighting Immediate Past Chair of ASHRAE SSPC 90.1 Lighting Subcommittee 1 How to Get the Standard Standard 90.1-2001

More information

CHAPTER 3: PRODUCTION BILL OF MATERIALS

CHAPTER 3: PRODUCTION BILL OF MATERIALS Chapter 3: Production Bill of Materials CHAPTER 3: PRODUCTION BILL OF MATERIALS Objectives The objectives are: Production Bill of Materials (BOM) Production BOM Advanced Features Production BOM Reports

More information

Variable Air Volume - VAV

Variable Air Volume - VAV Mode Enable Sensor Options Variable Air Volume - VAV The temperature of this sensor will determine if the unit is in heating, cooling or vent mode during occupied operation. The following options are available:

More information

IMPROVING DATA CENTER EFFICIENCY AND CAPACITY WITH AISLE CONTAINMENT

IMPROVING DATA CENTER EFFICIENCY AND CAPACITY WITH AISLE CONTAINMENT DATA CENTER RESOURCES WHITE PAPER IMPROVING DATA CENTER EFFICIENCY AND CAPACITY WITH AISLE CONTAINMENT BY: STEVE HAMBRUCH EXECUTIVE SUMMARY Data centers have experienced explosive growth in the last decade.

More information

The Base Shear Formula

The Base Shear Formula The Base Shear Formula You will have to do a bit of arithmetic and use a very simple formula known as the base shear formula to determine exactly how many bolts, how much plywood, and how many shear transfer

More information

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks Presentation Outline Common Terms / Concepts HVAC Building Blocks Plant Level Building Blocks Description / Application Data Green opportunities Selection Criteria Air Distribution Building Blocks same

More information

Part III. Administrative, Procedural, and Miscellaneous

Part III. Administrative, Procedural, and Miscellaneous Part III. Administrative, Procedural, and Miscellaneous Deduction for Energy Efficient Commercial Buildings Notice 2006 52 SECTION 1. PURPOSE This notice sets forth interim guidance, pending the issuance

More information