1 white paper Finding Electrical Failure Modes of Rotating Machinery with Electrical testing Mechanisms Begin >

2 Electrical maintenance professionals are expected to keep plant operations moving smoothly with an ever-decreasing budget and greater demands on their time and equipment. This dilemma creates a large and daunting task. In order to develop a comprehensive reliability program a wide variety of requirements need to be met. A unified approach to meeting these needs is to identify the most common failure modes in electrical equipment and then identify the tests that most effectively find those failures. In accomplishing this task, the amount of reactive maintenance due to unscheduled downtime is lessened. There is myriad equipment available to the maintenance professional for electrical predictive and preventative maintenance. Vibration technology is a usual starting point for most programs; however, there is also lubrication analysis, infrared, ultrasonic, along with testers that supply specific results on the motor circuit and insulation systems of electric motors. These testers include capabilities like torque and current signature analysis on the dynamic side of testing and inductance, impedance, capacitance, phase angle, winding resistance, Megohm, DC High potential (HiPot) and surge on the static side of testing. For the purpose of this article, the focus of failure modes and appropriate testing procedures will be for static testing of electric motors. These tests evaluate the integrity of the motor to run in the environment that it is installed. The instruments that perform these tests provide both low voltage and high voltage testing capabilities that look at different types of failures in one instrument. Most of these tests are governed by IEEE standards. Failure Modes in Electric Motors IEEE and EPRI have done independent studies focusing on failure modes in electric rotating machinery. Their conclusions state that over 40% of all motor failures are bearing related, over 25% are stator related, 8-9% are rotor related and the remaining 14-22% are a combination of other smaller faults. Insulation failure modes are broken up into four motor aging categories: Thermal aging, electrical aging, mechanical aging and environmental aging. An effective reliability program will have the tools necessary to identify and prevent these causes prior to catastrophic motor failure and unplanned downtime. For this paper, we will focus on electrical aging faults and how they affect the insulation of the motor. Electrical Aging Electrical aging occurs when voltage across the insulation causes deterioration. This aging occurs several ways. Overheating is a major contributor to deterioration along with manufacturing defects, winding ground faults, broken rotor bars or short circuit end rings, electrical discharges, surface tracking and moisture absorption, system surge voltages, transient overvoltages in rotor windings, high resistance connections among others. Voltage stress, i.e., O th er 14% IEEE Study Bear in g 41% Rotor 9% Bear in g 44% EPRI Study Stator 36% O th er 22% Stator Rotor 26% 8% voltage overload, reduces insulation service life. Causes include: bus transfers, switching surges, reflected wave phenomena due to variable frequency drives or even volts per turn that was not properly calculated in the motor design. Overheating Under-excitation and over-excitation of core elements can cause excessive heat in the core < Previous Page White Paper: Electrical Testing Page 2 Next Page >

3 laminate insulation. Higher temperatures reduce the dielectric strength of the inter laminar insulation over time and causes other stresses due to expansion and relative motion. Also circulating currents in the laminations can result in voltage being developed between adjacent core laminations. Even minor defects in the inter laminar insulation may provide paths for circulating currents causing further deterioration. This heat then affects the coils, turn-toturn and inter lamination insulation. A general rule of thumb: Every 10 rise in temperature cuts the insulation life in half. The large volume of core behind the slot is more prone to overheating due to increased flux compared to the tooth area. This area has less ventilation causing higher temperatures particularly as the iron begins to saturate. The increase in temperature creates a vicious cycle. Once the temperature is elevated, inter laminar breakdown of insulation increases, which gives rise to faults and eddy currents, which cause even higher temperatures to be produced. These higher temperatures cause mechanical stresses resulting in distortion and vibration. When combined, these effects eventually lead to fusing of laminations, melting of iron and core failure. [1] In addition to core faults, this increased temperature will also deteriorate the groundwall and turn-to-turn insulation. Manufacturing Defects of the Stator Core Lamination shorts can be introduced during manufacturing or refurbishment. Poor adhesion between the insulation and steel causes flaking, which creates weakness. Poor edge deburring of the laminations will cause sharp edges that cut through the insulation and create Having a unified approach to testing is the first step in reaching goals to lessen reactive maintenance and unscheduled downtime. metal-to-metal contact. In addition, the shorting of the diameter of the stator bore caused by smearing of the insulation in transportation or installation or the overfilling of stator slots can damage the core. All of these occurrences can shorten the life of the motor and deteriorate the insulation. [1] Shorting of the laminations will also lessen the efficiency of the motor. Winding Ground Faults in Core Slots The energy and heat produced by stator winding faults in the slot region are often high enough to melt and fuse the core laminations at the slot surface. If this core damage is not repaired when the failed coil or bar is replaced, the new coil might fail to ground because of the heat generated by the shorted laminations. [1] Stator Winding Insulation: Electrical Discharges A winding fails when the dielectric strength of the insulation can no longer support the operating voltage or transient overvoltages seen during startup or shut down. Electrical discharges generally occur in windings with voltage ratings of 5 kv rms or above and are commonly known as Partial Discharge. This gas breakdown phenomenon occurs in gas-filled pockets, which have solid insulation boundaries. A characteristic of partial discharge is that it requires a minimum voltage be met in order for a discharge to take place. The rate of deterioration of insulating materials that occurs due to partial discharge is a function of their discharge resistance properties. The fewer the voids produced due to the manufacturing process, the more resistant the insulation is to partial discharge. Generally, organic materials are more susceptible to partial discharge then nonorganic materials. Symptoms of aging due to partial discharge are evident of treeing through and burning of the groundwall insulation. This burning of the turn insulation occurs at its interface with the groundwall and is associated with turn-to-turn and strand-to-strand short circuits. [1] Surface Tracking and Moisture Absorption The formations of permanent conductive paths on the end-winding regions of the insu- < Previous Page White Paper: Electrical Testing Page 3 Next Page >

4 lation are caused by ac electrical stress. The surface of a stator coil in the end-winding region is highly resistive; however, small conductive areas can occur in normal operation due to contaminates such as oil, coal dust, chemicals or moisture. Leakage current will travel along these conductive patches causing degradation of the insulation surface. Failures resulting from this type of aging are ground or phase-to-phase. When motors absorb moisture from sources such as coolant systems, condensation or other moisture related problems, the resistance of the groundwall insulation is reduced and can create conductive paths especially in weakened or delaminated regions of the winding. These conductive paths can cause ground or phase-to-phase faults. In synchronous machines wound rotor windings are susceptible to problems with contamination of conducting materials due to proximity to these contaminates and that their insulating materials are often just separated instead of surrounded leaving items exposed between conductors. Contamination from oil dripping from a bearing and dust can cause surface tracking, which can lead to turn-to-turn or ground short circuits. [1] System Surge Voltages/Transient Overvoltages Turn-to-turn failures can be contributed to aging of turn insulation from exposure to power surges during start up and shut down of motors. If a fast rise time voltage surge strikes the stator winding from the switching of a motor, a voltage of several kilovolts above operating voltage can appear across the turn insulation for a short time. When the turn-to-turn insulation is in a weakened state this voltage can puncture the turn insulation-causing break down in the insulation. This will lead to a turn-to-turn short and high circulating currents ultimately resulting in motor failure. These random switching events can quickly age the insulation and degrade the system. High transient overvoltages may be introduced into rotor windings due to line-to-line stator winding short circuits, faulty synchronization, or asynchronous operation. Such transient voltage, together with weakened insulation can cause failures, mainly turn-to-turn. In a wound rotor induction motor there is a transformer effect between the stator and rotor windings. Consequently, power system surge voltage imposed on the stator winding will induce overvoltage in the rotor winding. Providing there is adequate turn and ground insulation on the rotor winding, such voltage should not cause electrical aging, however, these overvoltages will accelerate the failure of insulation that is already weak. [1] High Resistance Connections If a joint between two conductors is poorly soldered it creates a high resistance to the current flowing under load. This generates excessive heat and causes extensive thermal damage. This type of aging will develop turn-to-turn, phase-to-phase or ground faults. Quality control testing such as resistance When the insulation between turns is weak, the result is a low energy arc and a change in inductance. testing or thermal imaging will detect these joints and can help mitigate this type of fault in the manufacturing or rewinding process. [1] Fault Identification and Predictive Maintenance Insulation systems are subjected to a wide variety of events that can cause possible problems on a daily basis. With the progression of time, these issues turn into reality and can cause unexpected downtime of electric rotating machinery. The condition of electrical insulation materials is often best assessed through an electrical test. Such tests are broadly divided into two major categories: (1) high voltage and (2) low voltage tests. The former are definitive tests performed at some elevated ac or dc voltage to give assurance that rotating equipment can withstand the voltages that are typically seen during startup and shutdown. Test voltages are given in several standards and formulated by class and type of machine. < Previous Page White Paper: Electrical Testing Page 4 Next Page >

5 The later, low voltage, yields information such as an indication of moisture, dirt, or some other contaminant along with cracks or voids in the insulation. Low voltage tests also evaluate the motor circuit and identify failures such as shorts, opens, miss connections and unbalances in the phases. Predictive maintenance programs have been developed in order to investigate motor faults, find insulation weaknesses before it creates downtime and allows for root cause analysis. In order to obtain a comprehensive predictive maintenance program both high and low voltage testing is a necessity. The performed tests look at and identify problems in a portion of the insulating system. These tests work in conjunction with each other to produce an overall picture of the health of the machines insulation. In the following section Electrical Static Tests & Failure Modes Found Low Voltage Tests Impedance is defined as a circuit s total opposition to alternating current flow. It is a combination of the circuit s resistance, inductance and capacitance. When adding these terms we add the values of Resistance, Inductive Reactance, and Capacitive Reactance. The reactance is simply the resistive equivalents of the inductance or capacitance. In an AC circuit, we add an angle to the measurement to denote its effect on voltage to current displacement. That is to say, that the values of inductance and capacitance will cause the resulting current to be phase shifted from the applied voltage wave. Inductance causes a negative shift in current such that the current will tend to lag the applied voltage. The voltage rises first and the current rises some time later based on the level of inductance in the circuit. It is the inductor or coil and its opposition to changes in current that causes this effect. The changing magnetic field in the coil induces a voltage and resulting negative current flow back into itself. Lenz s Law describes this. Capacitance has the opposite effect and causes the current to lead the voltage. It is the capacitors opposition to changes in voltage that cause this to occur. Every motor circuit is defined by these parameters. The total impedance can be evaluated in much the same way we evaluate resistance in the motor. Where a resistive imbalance may show us high resistance connections or shorted turns due to variation between phases, Impedance can also be evaluated with respect to its balance in the circuit. A circuit with many turns of very fine wire that has a short turn to turn may show little effect on the resistive balance measurement but that same circuit will show a large difference in impedance due to the inductive imbalance created by missing turns. When a motor is wound, the inductive balance of the circuit can be helpful in validating the connections in the circuit. If we change the frequency of the applied AC voltage, it can have an even greater effect. This is because the Inductive Reactance (XsubL) is equal to 2 x Pi x L x F. The higher the applied frequency the larger the effective resistance of the circuit will be due to the inductor present. Capacitance has the inverse effect since it is equal to 1/(2 x Pi x C x F). As the frequency is increased in this circuit, the effective resistance to current flow is reduced. When using the parameters to analyze a motors condition it is important to understand how they each fit into the circuit. A three-phase motor is made up of groups of windings that form three phases. These three phases are connected in a star or delta configuration. In theory, these three circuits should be balanced perfectly. The cross sectional area and length of the copper should be even throughout all three phases. The number of turns per coil and coils per group, < Previous Page White Paper: Electrical Testing Page 5 Next Page >

6 and groups per phase should all be the same. The amount of insulation around each part of the winding and where the winding is laid in the slot adjacent to the iron should all be evenly distributed. Each of these design and construction conditions has a bearing on each of the three parameters (R, L, C). When the Impedance is measured, a low AC voltage is applied at a specific frequency. The resulting current flow is then measured. This measurement of current can then be used to calculate the circuit s total opposition to current flow at the applied voltage and frequency. This is the impedance of the circuit under test. The displacement of current and voltage (phase angle) will allow us to determine how much of the circuit is inductive or capacitive and values for each can be determined. Changing the frequency of the voltage applied will cause the values of capacitive and inductive reactance to vary as described above. This same type of measurement can also be performed through the ground wall insulation directly. When a motor is contaminated, the capacitance of the circuit will increase. This is due to the increase of the effective surface area of the winding. Capacitance is directly proportional to the surface area on each side of the dielectric material, in this case the insulation, being tested. Therefore, the level of cleanliness and moisture can be evaluated and trended over time. When a motor is wound, the inductive balance of the circuit can be helpful in validating the connections in the circuit. If a coil or group of coils were misconnected, this would have an effect on the inductance in the circuit. Any imbalance present in the impedance Lamination shorts can be introduced during manufacturing or refurbishment. measurement would indicate an unbalance turn count or misconnection of the windings. Since the impedance test is normally performed at a low voltage (<100V) this is not an effective test for testing weakened insulation between turns. The surge test is performed for this reason. The impedance and capacitance tests find hard turn shorts, improper turns count, misconnections of windings and moisture and particulate contamination. The Coil Resistance test consists of injecting a known constant DC current through the winding, measuring the voltage drop across the winding, and calculating the coil resistance using Ohm s law. If a coil is shorted somewhere in the interior of the winding, the resistance will be lower than normal. This lower coil resistance can be compared to previous measurements of the same coil, measurements of identical coils, or to the motor nameplate value in order to identify a bad coil. Low values indicate shorts, less turns, less cross sectional area. Measured values that are higher than normal can indicate loose, corroded connections or opens. The measured resistance is affected by the variation of copper conductivity with temperature. Before comparing two different measurements, correct the measured resistance value to a common temperature, usually 25 C per IEEE 118. Performing Resistance tests on the same motor over time provides early warning signs of motor connection problems. Motors operated in conditions that allow corrosion, contamination, or other physical damage may show initial warning signs of motor failure. Since the windings found in many motors have very low resistances, the injected current may have to be many amps to measure accurately the voltage drop across the coil. Difficulties in measuring the voltage drop across the coil itself are the affects of the contact resistance of internal relays and the contact resistance of the clip leads used to connect to the motor s winding. Contact resistances can be comparable or even greater than the resistance of some coils. A practical lower limit of the coil resistance < Previous Page White Paper: Electrical Testing Page 6 Next Page >

7 test exists to evaluate the copper winding conductors. The test instrument must be able to resolve the change in copper resistance caused by a short in the winding before conclusions are made regarding the coil resistance. The instrument should compare the percentage difference in resistance between leads with the calculation of Max Delta R. The user defines the acceptable Delta R tolerances for each motor, thereby giving the instrument its pass/fail limits. When the Resistance test results are displayed, measured resistance values, resistances corrected for temperature and the Delta Resistance percentage are listed. A problem with the motor under test may be indicated when Delta Resistance is high. The motor fails the test when the instrument detects Delta Resistance values not within the prescribed limits. The Meg-Ohm test consists of applying a DC voltage to the windings of a machine after isolating the winding from ground. According to IEEE 43 the test, voltage is usually near the operating voltage of the machine. The intended purpose of the Meg-Ohm test is to make an accurate measurement of the insulation resistance of the ground wall insulation. The insulation resistance, abbreviated IR, is a function of many variables: the physical properties of the insulating material, temperature, humidity, contaminants etc. The IR value is calculated using Ohm s law the applied voltage is divided by the measured leakage current. This leakage current is the current which passes from the winding through the Equipment Rated Voltage (V) ground wall insulation to the motor s steel core plus any surface leakage currents. The surface leakage currents flow through moisture or contaminants on the surface of the insulation. To determine accurately the insulation resistance, the surface leakage must be reduced to an inconsequential level. The Meg-Ohm test is best used for finding ground faults and the level of moisture or particulate contamination. The Polarization Index Test (PI test) is best used for determining if the winding is wet or is contaminated. The PI test is performed in order to measure quantitatively the ability of an insulator to polarize. When an insulator polarizes, the electric dipoles distributed throughout the insulator align themselves with an applied electric field. As the molecules polarize, a polarization current, or absorption current, is developed that adds to the insulation leakage current. This additional polarization current decreases over time and drops to zero when the insulation is completely polarized. PI results become confusing when attempting to attribute variations in the PI value to the Insulation Tester Voltage V DC 1000 and lower > polarizability of the insulator or other affects such as humidity or moisture, surface leakage or instrument error. The result is even more confusing when attempting to reconcile a PI of 1 when expecting a different PI result. The PI test is typically performed at 500, 1000, 2500 or 5000 Volts. This depends on the operating voltage of the motors being tested. The duration of the test is 10 minutes. The PI value is calculated by dividing the insulation resistance at 10 minutes by the resistance at 1 minute as shown in the formula: IR(10 min) PI = IR(1min) In general, insulators that are in good condition will show a high polarization index while insulators that are damaged will not. Unfortunately, most insulating materials recently developed (last 20 years) do not easily polarize. For example, the newer epoxy resins do not readily polarize. As recommended in IEEE , if the one-minute insulation resistance is greater than 5000 MOhms, the PI measurement may not be meaningful. < Previous Page White Paper: Electrical Testing Page 7 Next Page >

8 The Dielectric Absorption (DA) test is essentially a short-duration PI test and is usually intended for smaller motors. Larger motors whose insulation does not easily polarize are also good candidates for the DA test. Other than the shorter test time, all other principles are the same as the PI test, explained in the previous section. While the PI test is recommended only for motors 200 horsepower or greater, the DA test is often useful for motors in approximately the 50 to 200 horsepower range. In the situation where PI ratio may not be meaningful, the Dielectric Absorption (DA) is widely used. The DA is the IR value at 3 minutes divided by the IR value at 30 seconds as the formula states: IR(3 min) DA= IR(30 sec) The motivation for doing a DA test is to reduce the test time from 10 minutes to 3 minutes. To date there are no standardized accepted values for the DA test; however, useful information can be obtained by trending the DA values and graph over time. The PI and DA tests find insulation embrittlement (deterioration) along with moisture and particulate contamination. High Voltage Tests DC High-Potential (HiPot ) test The DC High-Potential (HiPot) test consists of applying a DC voltage to the windings of the machine, same as a Meg-Ohm/PI test, but at a higher voltage. The intended purpose of the DC HiPot test is to prove that the ground wall insulation system can withstand a high-applied voltage without exhibiting an extraordinarily high leakage current. Therefore, the DC HiPot test is often called a proof test. The observed insulation resistance or leakage current is recorded and compared to acceptable limits. If the insulation fails the DC HiPot test, the insulation to ground is determined to be unreliable. Knowledge of the real behavior of insulators/resistors, not just ideal resistors, will help the operator to test the winding insulation to a point before insulation breakdown. For an ideal resistor, good or poor, as the voltage is increased, the leakage current will increase proportionately. In real world applications, insulation resistance rarely behaves in this manner. Instead, the current in a typical resistor will increase proportionately with voltage until the voltage is within as little as five percent of breakdown voltage. Just before insulation breakdown, the current will rise faster than the voltage. At still higher voltages, the insulation will completely breakdown and the current will rise extremely fast. The key to DC HiPot testing is to look for leakage current that is rising faster than the increase in voltage that is applied to the winding. The HiPot test is considered a mainstay of motor testing. A HiPot test can be performed in one of two ways, AC or DC. The AC HiPot test brings the entire motor winding up to the IEEE test voltages same potential. Since all the windings are at the same potential, there is no turn-to-turn, or phase-to-phase insulation stress. There is uniform voltage stress applied between the winding insulation and the ground wall, throughout the entire winding. The HiPot test verifies groundwall insulation integrity. The Step Voltage test is similar to a HiPot in that it looks at the integrity of the groundwall insulation; however, at a less rigorous way. It is performed to a voltage of what the motor typically sees during starting and stopping. The test voltages are governed by IEEE and are posted below for reference. The DC voltage is applied to all three phases of the winding, raised slowly to a preprogrammed voltage step level, and held for a predetermined time period. It is then raised to the next voltage step and held for the appropriate time period. This is continued until the target test voltage is reached. Typical steps for a < Previous Page White Paper: Electrical Testing Page 8 Next Page >

9 Volt motor are 1000-volt increments, holding at one-minute intervals. For motors less than 4160, the step voltages should be 500 Volts. Data is logged at the end of each step. This is to ensure the capacitive charged, polarization current is removed, and only real leakage current remains, thus providing a true indication of the groundwall insulation condition. If at any point the leakage current (IµA) doubles, there is an indication of insulation weaknesses and the test should be stopped. If the leakage current (IµA) raises consistently less than double, the motor insulation is in good standing. The Step Voltage test is necessary to insure the ground wall insulation and cable can withstand the normal day-to-day voltage spikes the motor typically sees during operation. Whereas the Meg-Ohm/PI/ HiPot tests are used to detect ground wall insulation weakness, the Surge test is used to find turn-to-turn insulation weakness. Motor winding insulation failures often start as turn-to-turn failures, which eventually damage the ground wall insulation and lead to catastrophic failure. Surge testing can detect the early stages of a problem before it becomes severe. The surge test consists of applying a fast rise time, high current impulse to a winding. This fast-rise time impulse will induce a voltage difference between adjacent loops of wire within the winding. If the insulation between the two loops of wire is damaged or somehow weakened, and if the voltage difference between the wires is high enough, there will be an arc between the wires. This arc shows up as a change in the surge waveform. The surge test is performed with an impulse generator and a display to observe the surge waveform in progress. The surge waveform is the voltage present across the test leads of the instrument during the test. The indication of a weak insulation is a shift to the left, and/or a decrease in amplitude of the waveform when the arc between loops of wire occurs. The wave pattern observed during a Surge test is directly related to the coil s inductance. There are other factors that influence the wave pattern, but inductance is primary. The coil becomes one of two elements in what is known as a tank circuit or an LC-type circuit made up of the coils inductance (L) and the surge tester s internal capacitance (C). The inductance (L) of a coil is determined by its geometry, number of turns of wire and the type of iron core. The frequency of the wave pattern is approximated by the formula: 1 Frequency = 2π LC This formula implies that when the inductance decreases, the frequency will increase. A surge test can detect a fault between turns by observing a jump in the resonant frequency of this LC tank circuit. If the voltage potential is greater than the weakened dielectric strength < Previous Page White Paper: Electrical Testing Page 9 Next Page >

10 of the turn insulation, the current will find the quickest path to ground, bypassing the weakened turns. In effect, the number of turns in the coil is reduced. Fewer working turns reduce the inductance of the coil and increase the frequency of the ringing pattern from the surge. The voltage or amplitude of the surge wave pattern is also reduced due to the decrease in inductance of a coil with a fault between turns. It is determined by the following formula: di Voltage = L dt When the insulation between turns is weak, the result is a low energy arc and a change in inductance. When this happens, the wave pattern becomes unstable it may shift rapidly to the left and right, and back to the original position. In modern surge testers, the instrument will automatically register the fault, stop the test and inform the user of the fault. Added Capabilities of the Surge Test The Error Area Ratio When testing three phase motors, the waveforms of the three phases can be compared to each other. They should all be virtually the same: same shape, same zero crossings, and same amplitude. In practice; however, the three waveforms will not be exactly the same. There will be slight differences in the physical windings themselves as one phase is wound over another. However, how different should two waveforms be to identify a bad coil? The Error Area Ratio (EAR) was developed to answer that question. The EAR values give a quantitative number to how different two waveforms are. EAR is defined as: EAR 1 2 Npts Abs( F i= 1 = Npts j= 1 (1) i Abs( F F (1) j (2) i Where: F (1) = Data points representing waveform 1. F (2) = Data points representing waveform 2. EAR 1-2 = error area ratio of waveform 2 with respect to waveform 1. If two waveforms are exactly the same, the EAR value will be zero. Two waveforms that are almost exactly the same will have EAR values of 3-4%. Waveforms with obvious separation will have EAR values greater than 10%. This application of comparing one phase of a winding to another is called a Line-to-Line EAR (LL-EAR). The LL-EAR application above is used to compare two waveforms from two leads or two ) ) phases of a motor. A second application is to use the EAR formula as a way to compare the surge waveforms from a single lead or phase to itself. This application of the EAR is called the Pulse-to-Pulse EAR (abbreviated PP-EAR). To explain the PP-EAR, recall that weak insulation turn-to-turn is identified by a shift to the left of the surge waveform as the test voltage is slowly increased. On a good coil, the waveforms from consecutive pulses would appear almost the same the only difference being the increases in amplitude as the test voltage increases. On a weak coil, the consecutive pulses would look nearly the same until an arc occurs. At this voltage, the whole waveform shifts to the left and possibly drops in amplitude. Consider what a pp-ear calculation of two consecutive pulses could look like as voltage increases. Since the amplitudes of the two A characteristic of partial discharge is that it requires a minimum voltage be met in order for a discharge to take place. waveforms are different, there would be some EAR value calculated, possibly around 2-5%. Now consider doing the EAR calculation on the pulse just before weak insulation is detected and again on the pulse just after the detection. The EAR value would jump to a significantly higher value (10 to 100%). < Previous Page White Paper: Electrical Testing Page 10 Next Page >

11 Failure Modes found by each test. Static Test Resistive Balance Testing Inductive Balance Testing Impedance Phase Angle Frequency Response Meg-Ohm Testing Polarization Index Test/ Dielectric Absorption Test Capacitance Testing Step Voltage Test Surge Testing Conclusion With the ever-increasing demands of maintenance professional s time, budget and equipment to keep electrical rotating machinery operating effectively understanding the failure modes and tests available is highly important. Having a unified approach to testing is the first step in reaching goals to lessen reactive maintenance and unscheduled downtime. Failure modes in electrical equipment are broken into four major categories. Thermal, electrical, mechanical and environmental issues cause electric motors to fail prematurely. For this paper, we focused on the electrical aging processes. These include overheating due to under or over-excitation, manufacturing defects, winding ground faults in core slots, broken rotor bars and short circuit rings, stator winding electrical discharges, surface tracking and moisture absorption, system surge voltages, transient overvoltages and high resistance connections to name a few. In order to investigate insulation and motor circuit issues, a well-rounded battery of tests, both high and low voltage should be performed on a regular basis. These tests include inductance, impedance, capacitance, phase angle, coil resistance, meg-ohm, PI, DA, DC HiPot or step voltage and surge testing. These tests used together examine the health of the turnto-turn and ground wall insulation and circuit issues within motors. Having the tools available to perform a comprehensive predictive maintenance program is highly important in this age of increasing demands and decreasing budgets. The maintenance professional has a myriad of tools available, but the true task is picking the best tools to receive the greatest benefit for the plant or operation. References [1] EPRI Handbook to Access Rotating Machines Insulation Condition, Volume 16, November [2] IEEE Std : Recommended Practice for Testing Insulation Resistance of Rotating Machinery What Is Being Evaluated High Resistance connections Internal Shorts Hard Turn to Turn Faults Improper Turn Count Misconnection of Winding Ground Fault Determination Particulate/Moisture Contamination Level Insulation Embrittlement/Deterioration Moisture Contamination Particulate Contamination Moisture/Particulate Contamination Ground Wall Insulation Integrity Turn-to-turn Insulation Integrity Motor circuit issues: shorts, opens, reversed coils [3] IEEE Std : Recommended Practice for Insulation Testing of AC Electric Machinery (2300 V and Above) with High Direct Voltage [4] IEEE Std : IEEE Guide for Testing Turn-to-Turn Insulation on Form-Wound Stator Coils for Alternating-Current Rotating Electric Machines [5] IEEE Std : IEEE Guide for Induction Machinery Maintenance Testing and Failure Analysis < Previous Page Special Report: Electrical Testing Page 11 Next Page >

AC-Synchronous Generator

AC-Synchronous Generator Design Description AC Generators come in two basic types synchronous and non-synchronous. Synchronous generators lock in with the fundamental line frequency and rotate at a synchronous speed related to

More information

SYNCHRONOUS MACHINE TESTING WITH MOTOR CIRCUIT ANALYSIS INSTRUMENTATION

SYNCHRONOUS MACHINE TESTING WITH MOTOR CIRCUIT ANALYSIS INSTRUMENTATION SYNCHRONOUS MACHINE TESTING WITH MOTOR CIRCUIT ANALYSIS INSTRUMENTATION Introduction Howard W. Penrose, Ph.D., CMRP Vice President, Engineering and Reliability Services Dreisilker Electric Motors, Inc.

More information

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application g Digital Energy ITI Instrument Transformer Basic Technical Information and Application Table of Contents DEFINITIONS AND FUNCTIONS CONSTRUCTION FEATURES MAGNETIC CIRCUITS RATING AND RATIO CURRENT TRANSFORMER

More information

Line Reactors and AC Drives

Line Reactors and AC Drives Line Reactors and AC Drives Rockwell Automation Mequon Wisconsin Quite often, line and load reactors are installed on AC drives without a solid understanding of why or what the positive and negative consequences

More information

WIRE AND CABLE ENGINEERING GUIDE

WIRE AND CABLE ENGINEERING GUIDE DC Hi Pot Testing Excerpt from PRYSMIAN S WIRE AND CABLE ENGINEERING GUIDE (FOR INFORMATIONAL PURPOSES ONLY) Page 1 of 6 DC HIGH POTENTIAL TESTING DC Hi-Pot testing can be applied as a withstand test (a

More information

DC MOTOR ANALYSIS & TROUBLESHOOTING

DC MOTOR ANALYSIS & TROUBLESHOOTING DC MOTOR ANALYSIS & TROUBLESHOOTING By Don Shaw Condition assessment of DC motors requires a basic understanding of the design and operating characteristics of the various types available: the series motor,

More information

A Practical Guide to Dielectric Testing

A Practical Guide to Dielectric Testing Chroma Systems Solutions, Inc. A Practical Guide to Dielectric Testing 19032 Series Electrical Safety Analyzer & 19050 Series Hipot Tester AC/DC/IR/SCAN Keywords: Dielectric tests, insulation resistance

More information

DIRECT CURRENT GENERATORS

DIRECT CURRENT GENERATORS DIRECT CURRENT GENERATORS Revision 12:50 14 Nov 05 INTRODUCTION A generator is a machine that converts mechanical energy into electrical energy by using the principle of magnetic induction. This principle

More information

Understanding Insulation Resistance Testing

Understanding Insulation Resistance Testing Understanding Insulation Resistance Testing Why have an insulation testing program? A regular program of testing insulation resistance is strongly recommended to prevent electrical shocks, assure safety

More information

2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated?

2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated? Extra Questions - 2 1. A straight length of wire moves through a uniform magnetic field. The e.m.f. produced across the ends of the wire will be maximum if it moves: a) along the lines of magnetic flux

More information

Power-factor testing of rotating machinery is another valuable test

Power-factor testing of rotating machinery is another valuable test Feature Power-Factor Testing of Stator Winding Insulation: Understanding the Test Technique and Interpretation of Results Power-factor testing of rotating machinery is another valuable test technique providing

More information

13 ELECTRIC MOTORS. 13.1 Basic Relations

13 ELECTRIC MOTORS. 13.1 Basic Relations 13 ELECTRIC MOTORS Modern underwater vehicles and surface vessels are making increased use of electrical actuators, for all range of tasks including weaponry, control surfaces, and main propulsion. This

More information

Insulation resistance testing

Insulation resistance testing resistance testing Application Note Introduction resistance testers can be used to determine the integrity of windings or cables in motors, transformers, switchgear, and electrical installations. The test

More information

Basics of Electricity

Basics of Electricity Basics of Electricity Generator Theory PJM State & Member Training Dept. PJM 2014 8/6/2013 Objectives The student will be able to: Describe the process of electromagnetic induction Identify the major components

More information

Single and Three Phase Transformer Testing Using Static Motor Circuit Analysis Techniques

Single and Three Phase Transformer Testing Using Static Motor Circuit Analysis Techniques Single and Three Phase Transformer Testing Using Static Motor Circuit Analysis Techniques Howard W. Penrose, Ph.D On behalf of ALL-TEST Pro, LLC Old Saybrook, CT Introduction Field and shop testing of

More information

Product Data Bulletin

Product Data Bulletin Product Data Bulletin Power System Harmonics Causes and Effects of Variable Frequency Drives Relative to the IEEE 519-1992 Standard Raleigh, NC, U.S.A. INTRODUCTION This document describes power system

More information

WINDING RESISTANCE TESTING

WINDING RESISTANCE TESTING WINDING RESISTANCE TESTING WINDING RESISTANCE TEST SET, MODEL WRT-100 ADWEL INTERNATIONAL LTD. 60 Ironside Crescent, Unit 9 Scarborough, Ontario, Canada M1X 1G4 Telephone: (416) 321-1988 Fax: (416) 321-1991

More information

Troubleshooting accelerometer installations

Troubleshooting accelerometer installations Troubleshooting accelerometer installations Accelerometer based monitoring systems can be tested to verify proper installation and operation. Testing ensures data integrity and can identify most problems.

More information

Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO 250447392

Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO 250447392 1 Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading By Ramandeep Kaur Aujla S.NO 250447392 ES 586b: Theory and applications of protective relays Department of

More information

Electrical Safety Tester Verification

Electrical Safety Tester Verification Ensuring Validity of Regulatory Tests Verification of electrical safety testing equipment is a procedure that is often overlooked by manufacturers. Running test verification is crucial to ensuring that

More information

Table of Contents. The Basics of Electricity 2. Using a Digital Multimeter 4. Testing Voltage 8. Testing Current 10. Testing Resistance 12

Table of Contents. The Basics of Electricity 2. Using a Digital Multimeter 4. Testing Voltage 8. Testing Current 10. Testing Resistance 12 Table of Contents The Basics of Electricity 2 Using a Digital Multimeter 4 IDEAL Digital Multimeters An Introduction The Basics of Digital Multimeters is designed to give you a fundamental knowledge of

More information

Introduction. Harmonics and IEEE 519 Page 1 of 19

Introduction. Harmonics and IEEE 519 Page 1 of 19 Introduction In an ideal power system, the voltage supplied to customer equipment, and the resulting load current are perfect sine waves. In practice, however, conditions are never ideal, so these waveforms

More information

VOLTAGE REGULATOR AND PARALLEL OPERATION

VOLTAGE REGULATOR AND PARALLEL OPERATION VOLTAGE REGULATOR AND PARALLEL OPERATION Generator sets are operated in parallel to improve fuel economy and reliability of the power supply. Economy is improved with multiple paralleled generators by

More information

DC GENERATOR THEORY. LIST the three conditions necessary to induce a voltage into a conductor.

DC GENERATOR THEORY. LIST the three conditions necessary to induce a voltage into a conductor. DC Generators DC generators are widely used to produce a DC voltage. The amount of voltage produced depends on a variety of factors. EO 1.5 LIST the three conditions necessary to induce a voltage into

More information

Fundamentals of Inverter Fed Motors

Fundamentals of Inverter Fed Motors Fundamentals of Inverter Fed Motors Technical Manual 10/02 MN780 Contents Page The Growing Use Of Inverters.................................................................. 1 How Inverters Affect Motors....................................................................

More information

GenTech Practice Questions

GenTech Practice Questions GenTech Practice Questions Basic Electronics Test: This test will assess your knowledge of and ability to apply the principles of Basic Electronics. This test is comprised of 90 questions in the following

More information

A Practical Guide to Maximizing Machine Uptime

A Practical Guide to Maximizing Machine Uptime A Practical Guide to Maximizing Machine Uptime Every day, maintenance professionals across the world face the challenge of pushing maximum machine potential while at the same time, keeping repairs at a

More information

TAN δ (DELTA) CABLE TESTING OVERVIEW AND ANSWERS TO FREQUENTLY ASKED QUESTIONS. What Is Tan δ, Or Tan Delta?

TAN δ (DELTA) CABLE TESTING OVERVIEW AND ANSWERS TO FREQUENTLY ASKED QUESTIONS. What Is Tan δ, Or Tan Delta? TAN δ (DELTA) CABLE TESTING OVERVIEW AND ANSWERS TO FREQUENTLY ASKED QUESTIONS What Is Tan δ, Or Tan Delta? Tan Delta, also called Loss Angle or Dissipation Factor testing, is a diagnostic method of testing

More information

Drive circuit basics + V. τ e. Industrial Circuits Application Note. Winding resistance and inductance

Drive circuit basics + V. τ e. Industrial Circuits Application Note. Winding resistance and inductance ndustrial Circuits Application Note Drive circuit basics For a given size of a stepper motor, a limited space is available for the windings. n the process of optimizing a stepper motor drive system, an

More information

High Voltage Power Supplies for Analytical Instrumentation

High Voltage Power Supplies for Analytical Instrumentation ABSTRACT High Voltage Power Supplies for Analytical Instrumentation by Cliff Scapellati Power supply requirements for Analytical Instrumentation are as varied as the applications themselves. Power supply

More information

Lab 14: 3-phase alternator.

Lab 14: 3-phase alternator. Lab 14: 3-phase alternator. Objective: to obtain the no-load saturation curve of the alternator; to determine the voltage regulation characteristic of the alternator with resistive, capacitive, and inductive

More information

Why Buy HVI VLF Products?

Why Buy HVI VLF Products? Very Low Frequency AC Hipots AC testing of cables and electrical apparatus is now easier than ever. Since the introduction of the High Voltage, Inc. line of portable and affordable VLF hipots, there is

More information

Understanding the Alternator

Understanding the Alternator http://www.autoshop101.com THIS AUTOMOTIVE SERIES ON ALTERNATORS HAS BEEN DEVELOPED BY KEVIN R. SULLIVAN PROFESSOR OF AUTOMOTIVE TECHNOLOGY AT SKYLINE COLLEGE SAN BRUNO, CALIFORNIA ALL RIGHTS RESERVED

More information

Application Note. So You Need to Measure Some Inductors?

Application Note. So You Need to Measure Some Inductors? So You Need to Measure Some nductors? Take a look at the 1910 nductance Analyzer. Although specifically designed for production testing of inductors and coils, in addition to measuring inductance (L),

More information

Synchronous motor. Type. Non-excited motors

Synchronous motor. Type. Non-excited motors Synchronous motor A synchronous electric motor is an AC motor in which the rotation rate of the shaft is synchronized with the frequency of the AC supply current; the rotation period is exactly equal to

More information

Motor Fundamentals. DC Motor

Motor Fundamentals. DC Motor Motor Fundamentals Before we can examine the function of a drive, we must understand the basic operation of the motor. It is used to convert the electrical energy, supplied by the controller, to mechanical

More information

Insulation Resistance Testing of Low Voltage Cables in the Field

Insulation Resistance Testing of Low Voltage Cables in the Field Insulation Resistance Testing of Low Voltage Cables in the Field Table of Contents 1. Background...3 1.1. Before Making Measurements...3 1.2. How to Apply the Temperature Correction Factor...4 1.2.1. Calculation...4

More information

. Failure. Analysis... Report...

. Failure. Analysis... Report... . Failure. Analysis... Report..... for (Generation Company) (Station) Purchase Order Number XXXX (Dated XX/XX/XXXX) Report N-XXXX-FA, Revision 0 Schulz Electric Company Job Number N-XXXX Motor ID Number

More information

1. The diagram below represents magnetic lines of force within a region of space.

1. The diagram below represents magnetic lines of force within a region of space. 1. The diagram below represents magnetic lines of force within a region of space. 4. In which diagram below is the magnetic flux density at point P greatest? (1) (3) (2) (4) The magnetic field is strongest

More information

SYNCHRONOUS MACHINES

SYNCHRONOUS MACHINES SYNCHRONOUS MACHINES The geometry of a synchronous machine is quite similar to that of the induction machine. The stator core and windings of a three-phase synchronous machine are practically identical

More information

Circuits with inductors and alternating currents. Chapter 20 #45, 46, 47, 49

Circuits with inductors and alternating currents. Chapter 20 #45, 46, 47, 49 Circuits with inductors and alternating currents Chapter 20 #45, 46, 47, 49 RL circuits Ch. 20 (last section) Symbol for inductor looks like a spring. An inductor is a circuit element that has a large

More information

Power Quality Paper #3

Power Quality Paper #3 The Effect of Voltage Dips On Induction Motors by: M D McCulloch 1. INTRODUCTION Voltage depressions caused by faults on the system affect the performance of induction motors, in terms of the production

More information

Power surges can also be generated by equipment in your facility such as:

Power surges can also be generated by equipment in your facility such as: Power Quality Surge Suppressors What is Surge Protection A surge suppressor can be the first and best defense against the instant or gradual destruction of electrical equipment. Compared to the replacement

More information

BASIC ELECTRONICS AC CIRCUIT ANALYSIS. December 2011

BASIC ELECTRONICS AC CIRCUIT ANALYSIS. December 2011 AM 5-202 BASIC ELECTRONICS AC CIRCUIT ANALYSIS December 2011 DISTRIBUTION RESTRICTION: Approved for Pubic Release. Distribution is unlimited. DEPARTMENT OF THE ARMY MILITARY AUXILIARY RADIO SYSTEM FORT

More information

Predictive Maintenance

Predictive Maintenance PART ONE of a predictive maintenance series Predictive Maintenance Overview Predictive maintenance programs come in all shapes and sizes, depending on a facility s size, equipment, regulations, and productivity

More information

On-line PD Monitoring Makes Good Business Sense

On-line PD Monitoring Makes Good Business Sense On-line PD Monitoring Makes Good Business Sense An essential tool for asset managers to ensure reliable operation, improve maintenance efficiency and to extend the life of their electrical assets. Executive

More information

AND8008/D. Solid State Control Solutions for Three Phase 1 HP Motor APPLICATION NOTE

AND8008/D. Solid State Control Solutions for Three Phase 1 HP Motor APPLICATION NOTE Solid State Control Solutions for Three Phase 1 HP Motor APPLICATION NOTE INTRODUCTION In all kinds of manufacturing, it is very common to have equipment that has three phase motors for doing different

More information

SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS

SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS UNIT OBJECTIVES After studying this unit, the reader should be able to Describe the different types of open single-phase motors used to drive

More information

POWER AND VOLTAGE RATING

POWER AND VOLTAGE RATING POWER AND VOLTAGE RATING SCOPE: The purpose of this document is to take the confusion out of power and voltage ratings in specifications and in product information publications. This will be accomplished

More information

Critical thin-film processes such as deposition and etching take place in a vacuum

Critical thin-film processes such as deposition and etching take place in a vacuum WHITEPAPER INTRODUCING POWER SUPPLIES AND PLASMA Critical thin-film processes such as deposition and etching take place in a vacuum SYSTEMS chamber in the presence of a plasma. A plasma is an electrically

More information

(3) Explosion proof. Designed to prevent ignition of any explosive gases or dust and dirt which may surround the motor.

(3) Explosion proof. Designed to prevent ignition of any explosive gases or dust and dirt which may surround the motor. ELECTRIC MOTORS Enclosures for Motors Types of motor enclosures generally used in farm applications: (1) Open type; drip proof or splash-proof. A general purpose motor for use in dry locations which are

More information

CHAPTER 5 PHOTOVOLTAIC SYSTEM DESIGN

CHAPTER 5 PHOTOVOLTAIC SYSTEM DESIGN CHAPTER 5 PHOTOVOLTAIC SYSTEM DESIGN 5.1 Introduction So far in the development of this research, the focus has been to estimate the available insolation at a particular location on the earth s surface

More information

Principles of Adjustable Frequency Drives

Principles of Adjustable Frequency Drives What is an Adjustable Frequency Drive? An adjustable frequency drive is a system for controlling the speed of an AC motor by controlling the frequency of the power supplied to the motor. A basic adjustable

More information

Chapter 11. Inductors ISU EE. C.Y. Lee

Chapter 11. Inductors ISU EE. C.Y. Lee Chapter 11 Inductors Objectives Describe the basic structure and characteristics of an inductor Discuss various types of inductors Analyze series inductors Analyze parallel inductors Analyze inductive

More information

CONTINUOUS AUTOMATED FLUX MONITORING FOR TURBINE GENERATOR ROTOR CONDITION ASSESSMENT

CONTINUOUS AUTOMATED FLUX MONITORING FOR TURBINE GENERATOR ROTOR CONDITION ASSESSMENT CONTINUOUS AUTOMATED FLUX MONITORING FOR TURBINE GENERATOR ROTOR CONDITION ASSESSMENT Abstract J. Kapler, S. Campbell, M. Credland Iris Power Engineering Inc. Toronto, Canada Flux monitoring via permanently

More information

3) What is the difference between "Insulating", "Isolating", and "Shielded Winding" transformers?

3) What is the difference between Insulating, Isolating, and Shielded Winding transformers? Tyco Electronics Corporation Crompton Instruments 1610 Cobb International Parkway, Unit #4 Kennesaw, GA 30152 Tel. 770-425-8903 Fax. 770-423-7194 1) What is a transformer and how does it work? A transformer

More information

USE OF ARNO CONVERTER AND MOTOR-GENERATOR SET TO CONVERT A SINGLE-PHASE AC SUPPLY TO A THREE-PHASE AC FOR CONTROLLING THE SPEED OF A THREE-PHASE INDUCTION MOTOR BY USING A THREE-PHASE TO THREE-PHASE CYCLOCONVERTER

USE OF ARNO CONVERTER AND MOTOR-GENERATOR SET TO CONVERT A SINGLE-PHASE AC SUPPLY TO A THREE-PHASE AC FOR CONTROLLING THE SPEED OF A THREE-PHASE INDUCTION MOTOR BY USING A THREE-PHASE TO THREE-PHASE CYCLOCONVERTER International Journal of Electrical Engineering & Technology (IJEET) Volume 7, Issue 2, March-April, 2016, pp.19-28, Article ID: IJEET_07_02_003 Available online at http:// http://www.iaeme.com/ijeet/issues.asp?jtype=ijeet&vtype=7&itype=2

More information

Equipment: Power Supply, DAI, Wound rotor induction motor (8231), Electrodynamometer (8960), timing belt.

Equipment: Power Supply, DAI, Wound rotor induction motor (8231), Electrodynamometer (8960), timing belt. Lab 13: Wound rotor induction motor. Objective: to examine the construction of a 3-phase wound rotor induction motor; to understand exciting current, synchronous speed and slip in this motor; to determine

More information

EDEXCEL NATIONAL CERTIFICATE/DIPLOMA UNIT 5 - ELECTRICAL AND ELECTRONIC PRINCIPLES NQF LEVEL 3 OUTCOME 4 - ALTERNATING CURRENT

EDEXCEL NATIONAL CERTIFICATE/DIPLOMA UNIT 5 - ELECTRICAL AND ELECTRONIC PRINCIPLES NQF LEVEL 3 OUTCOME 4 - ALTERNATING CURRENT EDEXCEL NATIONAL CERTIFICATE/DIPLOMA UNIT 5 - ELECTRICAL AND ELECTRONIC PRINCIPLES NQF LEVEL 3 OUTCOME 4 - ALTERNATING CURRENT 4 Understand single-phase alternating current (ac) theory Single phase AC

More information

Exploring the Necessity of the Hot Hipot Test

Exploring the Necessity of the Hot Hipot Test Exploring the Necessity of the Hot Hipot Test Introduction In an industry comprised of workers with varying electronics knowledge, a Hipot test can seem a daunting task for some. Indeed, many test operators

More information

Power Supplies. 1.0 Power Supply Basics. www.learnabout-electronics.org. Module

Power Supplies. 1.0 Power Supply Basics. www.learnabout-electronics.org. Module Module 1 www.learnabout-electronics.org Power Supplies 1.0 Power Supply Basics What you ll learn in Module 1 Section 1.0 Power Supply Basics. Basic functions of a power supply. Safety aspects of working

More information

Unit 33 Three-Phase Motors

Unit 33 Three-Phase Motors Unit 33 Three-Phase Motors Objectives: Discuss the operation of wound rotor motors. Discuss the operation of selsyn motors. Discuss the operation of synchronous motors. Determine the direction of rotation

More information

SAMPLE OF THE STUDY MATERIAL PART OF CHAPTER 3. Symmetrical Components & Faults Calculations

SAMPLE OF THE STUDY MATERIAL PART OF CHAPTER 3. Symmetrical Components & Faults Calculations SAMPLE OF THE STUDY MATERIAL PART OF CHAPTER 3 3.0 Introduction Fortescue's work proves that an unbalanced system of 'n' related phasors can be resolved into 'n' systems of balanced phasors called the

More information

Specifying a Variable Frequency Drive s

Specifying a Variable Frequency Drive s Specifying a Variable Frequency Drive s Put on by Bruce Reeves and Jeremy Gonzales Dykman Electrical Covering the Western US For all of your VFD and Soft Start and Motor Needs How To Specify a Variable

More information

13 common causes of motor failure

13 common causes of motor failure 13 common causes of motor failure Application Note What to look for and how to improve asset uptime Motors are used everywhere in industrial environments and they are becoming increasingly complex and

More information

AC Induction Motor Slip What It Is And How To Minimize It

AC Induction Motor Slip What It Is And How To Minimize It AC Induction Motor Slip What It Is And How To Minimize It Mauri Peltola, ABB Oy, Helsinki, Finland The alternating current (AC) induction motor is often referred to as the workhorse of the industry because

More information

POWER SYSTEM HARMONICS. A Reference Guide to Causes, Effects and Corrective Measures AN ALLEN-BRADLEY SERIES OF ISSUES AND ANSWERS

POWER SYSTEM HARMONICS. A Reference Guide to Causes, Effects and Corrective Measures AN ALLEN-BRADLEY SERIES OF ISSUES AND ANSWERS A Reference Guide to Causes, Effects and Corrective Measures AN ALLEN-BRADLEY SERIES OF ISSUES AND ANSWERS By: Robert G. Ellis, P. Eng., Rockwell Automation Medium Voltage Business CONTENTS INTRODUCTION...

More information

Impedance Matching and Matching Networks. Valentin Todorow, December, 2009

Impedance Matching and Matching Networks. Valentin Todorow, December, 2009 Impedance Matching and Matching Networks Valentin Todorow, December, 2009 RF for Plasma Processing - Definition of RF What is RF? The IEEE Standard Dictionary of Electrical and Electronics Terms defines

More information

AC Generators. Basic Generator

AC Generators. Basic Generator AC Generators Basic Generator A basic generator consists of a magnetic field, an armature, slip rings, brushes and a resistive load. The magnetic field is usually an electromagnet. An armature is any number

More information

Welcome to Linear Controls Quarterly Training

Welcome to Linear Controls Quarterly Training Welcome to Linear Controls Quarterly Training Introduction to Power Generation Objectives Supply attendees with basic knowledge of power generators and voltage regulators and provide the fundamentals of

More information

CAT AVR V2.3. Instruction Manual. Voltage regulator for generators. March 2008

CAT AVR V2.3. Instruction Manual. Voltage regulator for generators. March 2008 CAT AVR V2.3 Voltage regulator for generators March 2008 Instruction Manual Warnings WARNING The system should not be installed, operated, serviced or modified except by qualified personnel who understand

More information

WIRE AND CABLE ENGINEERING GUIDE

WIRE AND CABLE ENGINEERING GUIDE Excerpt From Prysmian s WIRE AND CABLE ENGINEERING GUIDE Page 1 of 8 CABLE TESTING Testing represents an integral part in the life of a cable. A cable will be subjected to multiple tests in its lifetime

More information

The following table shows approximate percentage wise the

The following table shows approximate percentage wise the SHORT-CIRCUIT CALCULATION INTRODUCTION Designing an electrical system is easy and simple, if only the normal operation of the network is taken into consideration. However, abnormal conditions which are

More information

MIT510/2, MIT520/2 and MIT1020/2

MIT510/2, MIT520/2 and MIT1020/2 99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com MIT510/2, MIT520/2 and MIT1020/2 Line supply or battery operated Digital/analog

More information

The DC Motor/Generator Commutation Mystery. Commutation and Brushes. DC Machine Basics

The DC Motor/Generator Commutation Mystery. Commutation and Brushes. DC Machine Basics The DC Motor/Generator Commutation Mystery One small, yet vital piece of the DC electric motor puzzle is the carbon brush. Using the correct carbon brush is a key component for outstanding motor life,

More information

The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies

The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies DATE: November 17, 1999 REVISION: AUTHOR: John Merrell Introduction In some short circuit studies, the X/R ratio is ignored when comparing

More information

Cable Discharge Event

Cable Discharge Event Cable Discharge Event 1.0 Introduction The widespread use of electronic equipment in various environments exposes semiconductor devices to potentially destructive Electro Static Discharge (ESD). Semiconductor

More information

AC generator theory. Resources and methods for learning about these subjects (list a few here, in preparation for your research):

AC generator theory. Resources and methods for learning about these subjects (list a few here, in preparation for your research): AC generator theory This worksheet and all related files are licensed under the Creative Commons Attribution License, version 1.0. To view a copy of this license, visit http://creativecommons.org/licenses/by/1.0/,

More information

UNIT 3 AUTOMOBILE ELECTRICAL SYSTEMS

UNIT 3 AUTOMOBILE ELECTRICAL SYSTEMS UNIT 3 AUTOMOBILE ELECTRICAL SYSTEMS Automobile Electrical Structure 3.1 Introduction Objectives 3.2 Ignition System 3.3 Requirement of an Ignition System 3.4 Types of Ignition 3.4.1 Battery or Coil Ignition

More information

INSTALLATION AND MAINTENANCE INSTRUCTIONS FOR THREE PHASE INDUCTION MOTORS

INSTALLATION AND MAINTENANCE INSTRUCTIONS FOR THREE PHASE INDUCTION MOTORS INSTALLATION AND MAINTENANCE INSTRUCTIONS FOR THREE PHASE INDUCTION MOTORS Frames 143T - 449TZ 5100 North IH 35 Round Rock, Texas 78681 Phone: 800-451-8798 512-255-4141 Fax: 512-244-5512 RECEIVING 1. Check

More information

SALVAGING FLOOD DAMAGED ELECTRICAL EQUIPMENT

SALVAGING FLOOD DAMAGED ELECTRICAL EQUIPMENT SALVAGING FLOOD DAMAGED ELECTRICAL EQUIPMENT Overview In all drying out of electrical windings, the regulation of temperature should be controlled carefully. Maximum drying temperatures on windings should

More information

PS-6.2 Explain the factors that determine potential and kinetic energy and the transformation of one to the other.

PS-6.2 Explain the factors that determine potential and kinetic energy and the transformation of one to the other. PS-6.1 Explain how the law of conservation of energy applies to the transformation of various forms of energy (including mechanical energy, electrical energy, chemical energy, light energy, sound energy,

More information

BSNL TTA Question Paper-Instruments and Measurement Specialization 2007

BSNL TTA Question Paper-Instruments and Measurement Specialization 2007 BSNL TTA Question Paper-Instruments and Measurement Specialization 2007 (1) Instrument is a device for determining (a) the magnitude of a quantity (b) the physics of a variable (c) either of the above

More information

Induction Motor Theory

Induction Motor Theory PDHonline Course E176 (3 PDH) Induction Motor Theory Instructor: Jerry R. Bednarczyk, P.E. 2012 PDH Online PDH Center 5272 Meadow Estates Drive Fairfax, VA 22030-6658 Phone & Fax: 703-988-0088 www.pdhonline.org

More information

Introduction. Upon completion of Basics of AC Motors you should be able to:

Introduction. Upon completion of Basics of AC Motors you should be able to: Table of Contents Introduction...2 AC Motors...4 Force and Motion...6 AC Motor Construction... 12 Magnetism... 17 Electromagnetism... 19 Developing a Rotating Magnetic Field...24 Rotor Rotation...29 Motor

More information

Lesson 3 DIRECT AND ALTERNATING CURRENTS. Task. The skills and knowledge taught in this lesson are common to all missile repairer tasks.

Lesson 3 DIRECT AND ALTERNATING CURRENTS. Task. The skills and knowledge taught in this lesson are common to all missile repairer tasks. Lesson 3 DIRECT AND ALTERNATING CURRENTS Task. The skills and knowledge taught in this lesson are common to all missile repairer tasks. Objectives. When you have completed this lesson, you should be able

More information

Motor Protection Voltage Unbalance and Single-Phasing

Motor Protection Voltage Unbalance and Single-Phasing Motor Protection Voltage Unbalance and Single-Phasing Cooper Bussmann contributes the following information, which is an excerpt from their 190-page handbook SPD Selecting Protective Devices Based on the

More information

WHAT IS INFRARED (IR) THERMOGRAPHY

WHAT IS INFRARED (IR) THERMOGRAPHY WHAT IS INFRARED (IR) THERMOGRAPHY IR Thermography is the technique of producing pictures called from the invisible thermal radiation that objects emit. This is a non-contact means of identifying electrical

More information

100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center. 598 N. Buth Rd 3215 Arrowhead Rd

100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center. 598 N. Buth Rd 3215 Arrowhead Rd 100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center Introduction Roger Hedding Steven Schoenherr, P.E. ABB Inc. Minnesota Power 598 N. Buth Rd 3215 Arrowhead Rd Dousman,

More information

How To Understand And Understand The Theory Of Electricity

How To Understand And Understand The Theory Of Electricity DIRECT CURRENT AND ALTERNATING CURRENT SYSTEMS N. Rajkumar, Research Fellow, Energy Systems Group, City University Northampton Square, London EC1V 0HB, UK Keywords: Electrical energy, direct current, alternating

More information

Simple Analysis for Brushless DC Motors Case Study: Razor Scooter Wheel Motor

Simple Analysis for Brushless DC Motors Case Study: Razor Scooter Wheel Motor Simple Analysis for Brushless DC Motors Case Study: Razor Scooter Wheel Motor At first glance, a brushless direct-current (BLDC) motor might seem more complicated than a permanent magnet brushed DC motor,

More information

Evaluating Induction Motor Rotor Bars with Electrical Signature Analysis

Evaluating Induction Motor Rotor Bars with Electrical Signature Analysis Evaluating Induction Motor Rotor Bars with Electrical Signature Analysis Howard W Penrose, Ph.D., CMRP SUCCESS by DESIGN Reliability Services Hello and welcome to our presentation on Evaluating Induction

More information

Voltage Unbalance and Motors

Voltage Unbalance and Motors Voltage Unbalance and Motors Background Voltage unbalance occurs when the RMS line voltages on a poly-phase system are unequal. Voltages are seldom perfectly balanced between phases, but when this unbalance

More information

Rotary Phase Converters

Rotary Phase Converters FACTS from Ronk Electrical Industries, Inc. Bulletin 11981 Rotary Phase Converters ROTOVERTER Pat. No. 3,670,238 ROTO-CON Pat. No. 4,158,225 What are the ROTO-CON and ROTOVERTER power converters? The ROTO-CON

More information

Current and Temperature Ratings

Current and Temperature Ratings Document 361-1 Current and Temperature Ratings Introduction This application note describes: How to interpret Coilcraft inductor current and temperature ratings Our current ratings measurement method and

More information

Application Note AN- 1095

Application Note AN- 1095 Application Note AN- 1095 Design of the Inverter Output Filter for Motor Drives with IRAMS Power Modules Cesare Bocchiola Table of Contents Page Section 1: Introduction...2 Section 2 : Output Filter Design

More information

Mylar polyester film. Electrical Properties. Product Information. Dielectric Strength. Electrode Size. Film Thickness

Mylar polyester film. Electrical Properties. Product Information. Dielectric Strength. Electrode Size. Film Thickness Product Information Mylar polyester film Electrical Properties Mylar offers unique design capabilities to the electrical industry due to the excellent balance of its electrical properties with its chemical,

More information

Enhance Power Equipment Reliability with Predictive Maintenance Technologies

Enhance Power Equipment Reliability with Predictive Maintenance Technologies Enhance Power Equipment Reliability with Predictive Maintenance Technologies November 2012/1910DB1208 by S. Frank Waterer, Electrical Engineerinig, Fellow Schneider Electric USA, Inc. Make the most of

More information

26 3213.13 Diesel Engine Driven Generators Page 1 of 6

26 3213.13 Diesel Engine Driven Generators Page 1 of 6 Last Update: December 8, 2014 A. Description of System Consultant s Handbook Page 1 of 6 1. Provide a diesel engine driven electric generating unit, factory assembled, tested and certified to operate at

More information

8 Speed control of Induction Machines

8 Speed control of Induction Machines 8 Speed control of Induction Machines We have seen the speed torque characteristic of the machine. In the stable region of operation in the motoring mode, the curve is rather steep and goes from zero torque

More information