RELT. Reduced Energy Let Thru. Rick Schlobohm, P.E. Senior Specification Engineer, GE Energy Management
|
|
|
- Audra Maxwell
- 9 years ago
- Views:
Transcription
1 RELT Reduced Energy Let Thru Rick Schlobohm, P.E Senior Specification Engineer, Energy Management There is an increasing concern in the electrical industry about arc flash energy levels and the associated dangers when working on energized equipment. This concern is not limited to the design of new systems, but also the retrofitting of existing systems to incorporate features to limit the arc flash energy exposure of technicians working on energized equipment. The intent of this paper is to explain what RELT (Reduced Energy Let-thru) accomplishes, how it benefits electrical equipment users and how the system is implemented. The methods used in the calculations of the incident energy levels are based on the guidelines of IEE 1584 and NFPA 70E The concept behind RELT is to provide a method to lower the arc flash incident energy levels while working on or near energized equipment. Electricians and electrical maintenance personnel are becoming increasingly familiar with arc flash hazards. These personnel are also aware of the different arc flash hazard levels and the need for the proper PPE (personal protective equipment) associated with each hazard level. The RELT system when activated helps to mitigate the arc flash hazard by limiting the duration of the fault current to the fault through the use of a user selectable and settable secondary instantaneous pickup setting. There have been many excellent articles written on the calculations associated with evaluating arc flash energy levels and it is assumed that the reader has a fundamental knowledge of this subject so this paper will not re-iterate that topic in detail. The thing to remember with the arc flash energy levels is two key components, which are the magnitude of the arcing fault current available and the length of time this fault current is available before the overcurrent protective device operates to clear the fault. The RELT system is an alternative user selectable instantaneous pickup setting for the electronic trip unit. By selecting a lower pickup point for the instantaneous trip function of the breaker, the time factor in the calculations is reduced, thus lowering the arc flash energy which can be experienced by the user. A lower pick-up point is selected because arcing fault currents in LV systems are about 50% of the bolted fault current
2 and the instantaneous pick-up point selected for the system coordination may be higher than the arcing current. An important factor to consider when performing coordination studies is that for any point that the instantaneous setting is above the available arcing current, the trip unit will not provide any arc flash energy reduction. To analyze how this system will benefit the user, a comprehensive fault current, device coordination and arc flash hazard study including incident energy analysis must be performed on the system while operating in its normal state. The appropriate arc flash hazard labels would then be installed on the equipment so the user knows what the hazard risk is when approaching and working on this equipment. To determine the alternate instantaneous setting while in the RELT mode, a second coordination study and arc flash hazard study must be performed. By reducing the instantaneous setting of the overcurrent device while in the RELT mode, downstream coordination with other devices will be impacted and an evaluation must be done by the engineer doing the study with the equipment user to maximize the safety of the system while minimizing the impact to the system coordination. Since RELT is an alternative setting for the instantaneous trip pickup level at the trip unit, the user must be able to activate this alternative setting and have positive feedback that the system is activated. Activation can be accomplished by a 24Vdc signal which can be initiated through a switch mounted on the electrical equipment, or through the same switch which can be located outside of the arc flash boundary for that piece of equipment. Additionally, if the electronic trip unit is equipped with communication capabilities, the command can be activated via serial communications utilizing either Modbus or Profibus. The serial communication activation would be advantageous to a facility that employed a comprehensive SCADA or Power Monitoring system. As part of the work procedures, the activation of the RELT would be through the overall monitoring and control system. Once the system is activated, the user will require positive feedback that the RELT has been activated. When a hardwired system is utilized, the trip unit can provide a contact closure that illuminates a lamp to indicate to the user that the system is activated. This light can be in the form of an illuminated switch (utilizing the same switch that activates the system) or a separate indicating lamp. If the system is activated through serial communications, the feedback that the system is activated would be to the remote HMI through the serial communications. After the RELT functioned is activated, the user can commence the maintenance procedure, but he also needs to know that without proper work procedures which are enforced or without direct control over the RELT feature, the system could be put back into its normal position which could expose the worker to an incident energy level for which he is not prepared. To illustrate how RELT can lower the incident energy, a simple substation one-line is used for illustration with three scenarios. All three scenarios utilize a 2500 kva substation with a primary current limiting fuse, a secondary main 3000A ANSI rated breaker and then a 1600A
3 and 800A feeder breaker. The three scenarios involve the settings for the secondary main breaker. Scenario 1 utilizes only long time and short time trip functions (LS) for the secondary main breaker which would be typical for an instantaneous selectively coordinated system (.01 sec). Scenario 2 utilizes long time, short time and Instantaneous trip functions (LSI) for the secondary main which would be typical for a non-instantaneous selectively coordinated system (0.1 sec). The third scenario shows the same main breaker but with the instantaneous pickup in the RELT mode which would be used to limit the incident energy for downstream maintenance. The following is a depiction of the one-line analyzed. Note that the one-lines are identical except for the settings of the 3000A secondary main breaker.
4
5 To understand the effect of the instantaneous setting of a main breaker on the incident energy on the switchgear bus, you must look at the point between the 3000A main breaker and the feeder breakers noted above as SWGR Bus. For the one-line labeled LS, the data block indicates that at the switchgear bus the Arc Flash incident energy is 8.95 Cal/cm2. Adding the instantaneous trip function to the 3000A main breaker as shown on one-line LSI, does not reduce the incident energy. One would expect that the incident energy would be reduced with the addition of the instantaneous trip function. However in this scenario, the instantaneous trip setting is selected at 7X for coordination purposes with the downstream devices. This setting though, is above the available calculated arcing fault current level, thus it does not provide any reduction in the arc flash energy available on the switchgear bus. In this scenario, if the instantaneous trip level was reduced even.5x to 6.5X, the incident energy would be reduced significantly to 3.02 cal.cm2. The design and power systems engineer should always consider the impact of the settings selected for coordination and the impact they have on the arc flash energy downstream of the device. The third one-line above labeled LSI-RELT utilizes the secondary setting in the RELT mode for maintenance. In this case it was set at 1.5X which reduces the incident energy on the switchgear bus to 2.6 Cal/cm2. This is a significant reduction in the available arc flash energy and as you can see the alternate RELT setting will reduce the incident energy to a point where protection to the worker is well within the Everyday Work Clothing level as defined in NFPAA 70E. While the benefits of the RELT maintenance mode for personnel protection are clear, there are a number of scenarios for the implementation of RELT and there are possible limitations to its use. RELT applied to the main device in a lineup as described above has the capability to lower the incident energy on the bus in the switchgear, but it also can be applied to a feeder breakers to lower the incident energy for equipment connected to the load side of the feeder breaker. There are several issues which the design engineer must consider when selecting RELT functionality and determining the secondary instantaneous settings which will be activated with RELT. The first and foremost is the possible loss of selective coordination. If the instantaneous trip function could be set low enough to achieve an acceptable level of incident energy reduction while maintaining selective coordination, then the breaker should be set at that level. However, in most instances, the instantaneous trip function is set at a high enough level for downstream devices to clear a fault before the upstream device will trip, thus maintaining selective coordination. The design engineer should be aware of any restrictions with local codes, owners or other authorities for even a temporary compromise of selective coordination within the system with the implementation of RELT. Hospitals, data centers and other
6 industries where selective coordination is either mandated or desired may not be the best types of projects to implement a RELT scheme just to lower the incident energy level for maintenance personnel to work on energized equipment. The time current coordination (TCC) plots shown below illustrate the levels of selective coordination available with the scenarios previously described.
7 TIME IN SECONDS CURRENT IN AMPERES A Main LS0 WPH-32 Trip A Plug A 100 LTPU/LTD (0.5-1 x RP) 1.00X (3000A); C-6 STPU (1.5-9 x LTPU) 5.5X (16500A) STD (ST01 - ST11) ST06-Min (I^2t Out) Primary Fuse2 9F62 EJ0-1, 5.5kV EJO-1 Trip A 450 Amps A Feeder2 WPH-16 Trip A Plug A LTPU/LTD (0.5-1 x RP) 1.00X (1600A); C-8 STPU (1.5-9 x LTPU) 7X (11200A) INST w/st=on(2-15 x RP) 10X (16000A) A Feeder4 WPX-08 Trip A Plug A LTPU/LTD (0.5-1 x RP) 1.00X (800A); C-8 STPU (1.5-9 x LTPU) 9X (7200A) INST w/st=on(2-15 x RP) 10X (8000A) K 10K LS(b).tcc Ref. Voltage: 480V Current in Amps x 10 The above scenario shows instantaneous selective coordination for all times above.01 sec between the main and the feeder breakers in the switchgear.
8 TIME IN SECONDS CURRENT IN AMPERES A Main LS5 WPH-32 Trip A Plug A LTPU/LTD (0.5-1 x RP) 1.00X (3000A); C-6 STPU (1.5-9 x LTPU) 5.5X (16500A) STD (ST01 - ST11) ST06-Min (I^2t Out) INST w/st=on(2-13 x RP) 7X (21000A) 1600A Feeder3 Primary Fuse3 9F62 EJ0-1, 5.5kV EJO-1 Trip A 450 Amps 10 WPH-16 Trip A Plug A LTPU/LTD (0.5-1 x RP) 1.00X (1600A); C-8 STPU (1.5-9 x LTPU) 7X (11200A) INST w/st=on(2-15 x RP) 10X (16000A) 1 800A Feeder WPX-08 Trip A Plug A LTPU/LTD (0.5-1 x RP) 1.00X (800A); C-8 STPU (1.5-9 x LTPU) 9X (7200A) INST w/st=on(2-15 x RP) 10X (8000A) K 10K LSI(b).tcc Ref. Voltage: 480V Current in Amps x 10 LSI(b).drw This second TCC illustrates the main with instantaneous trip function and selective coordination for time levels exceeding 0.1 sec which is applicable in many jurisdictions.
9 TIME IN SECONDS CURRENT IN AMPERES A Main LS4 WPH-32 Trip A Plug A LTPU/LTD (0.5-1 x RP) 1.00X (3000A); C-6 STPU (1.5-9 x LTPU) 5.5X (16500A) STD (ST01 - ST11) ST06-Min (I^2t Out) RELT ( x RP) 1.50 (4500A) 1600A Feeder5 Primary Fuse5 9F62 EJ0-1, 5.5kV EJO-1 Trip A 450 Amps 10 WPH-16 Trip A Plug A LTPU/LTD (0.5-1 x RP) 1.00X (1600A); C-8 STPU (1.5-9 x LTPU) 7X (11200A) INST w/st=on(2-15 x RP) 10X (16000A) 1 800A Feeder WPX-08 Trip A Plug A LTPU/LTD (0.5-1 x RP) 1.00X (800A); C-8 STPU (1.5-9 x LTPU) 9X (7200A) INST w/st=on(2-15 x RP) 10X (8000A) K 10K LSI-RELT (b).tcc Ref. Voltage: 480V Current in Amps x 10 This third TCC shows the main breaker with the RELT mode activated for downstream personnel protection. Note that all levels of selective coordination have been compromised up
10 to the 10 sec time frame. As mentioned previously, the incident energy level to which the maintenance personnel are exposed to has been reduced, but the level of selective coordination has been severely impacted. The design engineer should be well aware of this impact and use prudence when applying this scheme for certain distribution systems. Another scenario which is often overlooked and of which the design engineer should be aware of is the style of equipment in which the RELT is implemented. If RELT is applied to a main breaker in a switchboard, the design engineer and end user should be aware that the incoming point of connection to that main breaker still has the high incident energy level. This can be seen on the previous one-lines at the point noted as XFMR secondary. For every scenario, the secondary main does not have any effect for the incident energy at this point and for this scenario it is Cal/cm2 which is an extremely dangerous level. If there is no barrier between the main breaker compartment and the distribution sections that is suitable and tested as an arc flash barrier, this high level of incident energy is present in the open space of the distribution equipment. Even though the RELT applied to the main circuit breaker might reduce the incident energy level at any point on the load side of that breaker, the equipment will still indicate the available incident energy level available at the primary of the main breaker. End users and maintenance personnel would typically then be required to adhere to the dangerous label and would not be able to work on the live equipment. The design engineer can overcome this scenario by utilizing switchgear which as a suitable barrier between the main and the feeder breakers or can simply design a system which will separate the main from the feeder sections. For the scenario discussed in this paper, the main could be close coupled to the transformer secondary and then cable or bus connected to the distribution breakers. Activating the RELT function for the main would then effectively lower the incident energy level for the feeder sections without the danger of the high energy levels being present in the equipment while in the RELT mode. While this paper is focused on the RELT function for a specific scenario, there are alternative design scenarios which can be implemented to circumvent this condition. Schemes involving the interlocking of the secondary main with a primary circuit breaker has been designed which effectively reduce the incident energy level at the primary terminals of the secondary main. Other schemes involving zone interlocking and more importantly instantaneous zone interlocking utilizing waveform recognition could also be used to add protection to the equipment and the maintenance personnel. In conclusion, Reduced Energy Let Thru (RELT) is a valuable feature which can be effectively specified and implemented to reduce incident energy levels at electrical equipment. However the electrical design professional should be aware of how the system functions, effective
11 schemes to implement it and the potential drawbacks which can occur when implemented for certain systems. The design engineer should also become familiar with NFPA 70E, Standard for Electrical Safety in the Workplace -2012, to become thoroughly familiar with all of the terms associated with arc flash hazards. There have been numerous changes from previous editions of the standards and the reader should understand the requirements from the latest standards.
Part 1 System Modeling & Studies for Existing Systems
Part 1 System Modeling & Studies for Existing Systems Operation Technology, Inc. Copyright 2009 Result of rapid release of energy due to an arcing fault between two conductors. Bus voltages > 208V Temperatures
Low Voltage Switchgear
Arc Resistant Switchgear n Insulated and isolated bus n Separation barriers and top venting n Breaker shutters 12 SWITCHGEAR Arc resistant metal-enclosed low voltage switchgear is an optional product offering
misconceptions about arc-flash hazard assessments
misconceptions about arc-flash hazard assessments There are some common misconceptions about Arc-Flash Hazard Assessments which reduce the effectiveness of the Assessments and can increase electrical hazards.
A Guide to Performing An Arc Flash Hazard Assessment Using Power Analysis Software
A Guide to Performing An Arc Flash Hazard Assessment Using Power Analysis Software Abstract: The nature of explosive equipment failures, and the rate of serious burn injuries in the electrical industry
Arc Flash Mitigation & Selective Co-ordination
Arc Flash Mitigation & Selective Co-ordination Michael Hodder March 2015 Overview This seminar will provide information on: Mitigating arc flash hazards Selective Coordination What can we do to make these
RISK MITIGATION for ELECTRICAL WORK. Feb 2013 San Diego CA
RISK MITIGATION for ELECTRICAL WORK Feb 2013 San Diego CA Agenda I. RISK Define the Risks Arc Flash Review II. MITIGATION 3 Easy Steps New Designs Vs. Existing Systems III. DUKE UNIVERSITY EXAMPLE I. Risk
Arc Flash Energy Mitigation Techniques
Arc Flash Energy Mitigation Techniques When short circuits occur on an electrical distribution system, an arc flash event usually forms. These arc flash events can cause dangerous and potentially fatal
Choosing the Best Solution for Reducing Arc Energy
CONVENTION SESSION HANDOUT Choosing the Best Solution for Reducing Arc Energy Terry L. Schiazza, Business Development Manager Square D / Schneider Electric SESSION #11 Independent Electrical Contractors
Arc Flash Mitigation. Remote Racking and Switching for Arc Flash danger mitigation in distribution class switchgear.
Arc Flash Mitigation Remote Racking and Switching for Arc Flash danger mitigation in distribution class switchgear. Distance is Safety We will discuss through examples of actual occurrences and possible
ARC FLASH CALCULATIONS & LABELING REQUIREMENTS
ARC FLASH CALCULATIONS & LABELING REQUIREMENTS Presented by: Edmund Elizalde EYP Mission Critical Facilities, Inc. Slides by: Lonnie Lindell SKM Systems Analysis, Inc. 1 Agenda NEC 110.16 NFPA 70E IEEE
Understanding Arc Flash
Understanding Arc Flash Presented by Eddie F. Jones, PE 1 2 3 4 5 Five to 10 arc flash explosions occur in electric equipment every day in the United States. This number does not include cases in which
How to reduce exposure to arc flash hazards
GE Energy Industrial Solutions How to reduce exposure to arc flash hazards Multiple solutions for new and existing facilities imagination at work Multiple Issues Today s power system engineer must not
Arc Flash Hazards. Electrical Hazards. Dan Neeser Field Application Engineer [email protected]. Electrical Hazards 2/18/2015. Shock.
Arc Flash Hazards Dan Neeser Field Application Engineer [email protected] Electrical Hazards Electrical Hazards Shock Arc Flash Arc Blast 2 1 Arcing Fault Basics 35,000 F Radiant Heat & UV Speed of
Technical Guide. SKM Arc Flash Line Side vs. Load Side
SKM Arc Flash Line vs. Load The option of choosing the line-side or the load-side arc flash incident energy for arc flash labels is an important decision when performing an arc flash hazard analysis. When
Primary and Secondary Electrical Distribution Systems
Primary and Secondary Electrical Distribution Systems Critical Facilities Round Table 12th Quarterly Membership Meeting June 2, 2006 David D. Roybal. P.E. Eaton Electrical Cutler-Hammer Products Utility
Safety By Design. Strategies for Electrical Contractors
Safety By Design Strategies for Electrical Contractors Introduction Engineering and system design significantly impact worker safety System design provides opportunity to eliminate/minimize workers exposure
Arc Flash Mitigation. Executive summary. by Antony Parsons, Ph.D., P.E.
by Antony Parsons, Ph.D., P.E. Executive summary Arc flash events can result in significant injury to workers, including severe burn injuries. The most effective arc flash safety programs are not those
What Are the Qualifications to Conduct Arc Flash Studies? Where Do You Begin?
What Are the Qualifications to Conduct Arc Flash Studies? Where Do You Begin? Comparing apples-to-apples bids Plant Services Special Report A shock hazard analysis should be included as part of an arc
A USERS GUIDE TO ARC RESISTANT LOW VOLTAGE SWITCHGEAR & MOTOR CONTROL ANALYTICAL COMPARISON VS ARC FLASH TEST RESULTS
A USERS GUIDE TO ARC RESISTANT LOW VOLTAGE SWITCHGEAR & MOTOR CONTROL ANALYTICAL COMPARISON VS ARC FLASH TEST RESULTS By: Gabriel Arce, ABB, San Luis Potosi, Mexico Casey McCollum, ABB, Houston, TX John
ARC FLASH HAZARD MITIGATION. Industrial Tests, Inc. [indtests.com]
ARC FLASH HAZARD MITIGATION ARC FLASH HAZARD MITIGATION NWHA TECHNICAL SEMINAR May 17, 2012 Richard D Reese Power Systems Manager Industrial Tests, Inc. Rocklin, California [[email protected]; 916-660-2837]
Roadmap to Compliance with NFPA 70E Arc Flash Requirements
Roadmap to Compliance with NFPA 70E Arc Flash Requirements TAHFM Interlink 2015 March 30, 2015 Antony Parsons, Ph.D., P.E. Schneider Electric Engineering Services 1 2 How do we get to Reliable Power? >
BRANDON AND CLARK INC. // SCOTT W. CLARK, P.E. ELECTRICAL CONTINUING EDUCATION ARC FLASH - NFPA 70E
BRANDON AND CLARK INC. // SCOTT W. CLARK, P.E. ELECTRICAL CONTINUING EDUCATION ARC FLASH - NFPA 70E Training is not a substitute for following corporate safety guidelines. Always refer to the latest safety
Short-circuit, Protective Device Coordination & Arc Flash Analysis. By Albert Marroquin Operation Technology, Inc.
Short-circuit, Protective Device Coordination & Arc Flash Analysis By Albert Marroquin Operation Technology, Inc. Agenda Short-circuit Calculations for Arc Flash Analysis Protection and Coordination Principles
NFPA 70E 2012 Rolls Out New Electrical Safety Requirements Affecting Data Centers
NFPA 70E 2012 Rolls Out New Electrical Safety Requirements Affecting Data Centers A market position paper from the experts in Business-Critical Continuity TM Executive Summary Electrocutions are the fourth
Implementation of arc flash mitigating solutions at industrial manufacturing facilities
Thought leadership White paper Implementation of arc flash mitigating solutions at industrial manufacturing facilities David B. Durocher Senior Member, IEEE Global Industry Manager Eaton 26850 SW Kinsman
ELECTRICAL SAFETY RISK ASSESSMENT
ELECTRICAL SAFETY RISK ASSESSMENT The intent of this procedure is to perform a risk assessment, which includes a review of the electrical hazards, the associated foreseeable tasks, and the protective measures
FFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid
Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars Presented By: Greg Pelster & Robert Schmid FFI Ferrie, Franzmann Industries LOW VOLTAGE SWITCHGEAR & LOW VOLTAGE
ETAP Arc Flash Analysis
ETAP Arc Flash Analysis The purpose of this tutorial is to introduce the Arc Flash Analysis module of ETAP and provide instructions on how to setup Arc Flash (AF) calculations. For this section of the
Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services
Circuit Breakers and Switchgear Thomas Greer Director of Engineering TLG Services Presentation Outline Switchgear Definition Overcurrent Protection Devices Circuit Breaker Trip Curves and Coordination
UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation
Basis of Design This section applies to the design relating to low voltage switchboards. Design Criteria UW Class N1 facilities main switchboards shall be rear accessible. The main, tie and feeder breakers
! WARNING Arc Flash and Shock Hazard Appropriate PPE Required
Arc Flash Hazard Labeling Do s and Don ts! WARNING Arc Flash and Shock Hazard Appropriate PPE Required 11' - 3" Flash Hazard Boundary 9 cal/cm2 Flash Hazard at 18 inches #3 PPE Level Cotton underwear plus
Secondary Unit Substations
14 SWITCHGEAR Secondary Unit Substations Overview Siemens offers a wide variety of unit substation designs to meet customer requirements. A unit substation consists of one or more transformers mechanically
Spending too much to maintain aging switchgear? Circuit breaker solutions from Square D Services.
Spending too much to maintain aging switchgear? Circuit breaker solutions from Square D Services. Spending too much time and money on equipment maintenance? Square D Services: Your source for circuit breaker
STANDARDS AND RATINGS FOR THE APPLICATION OF MOLDED CASE, INSULATED CASE, AND POWER CIRCUIT BREAKERS
STANDARDS AND RATINGS FOR THE APPLICATION OF MOLDED CASE, INSULATED CASE, AND POWER CIRCUIT BREAKERS David D. Roybal, P.E. Senior Member, IEEE Cutler-Hammer, Inc. 3697 Mount Diablo Boulevard Lafayette,
Arc Terminator Active Arc-Resistant Switchgear
Arc Terminator Active Arc-Resistant Switchgear Increasing safety and productivity by extinguishing internal arcing faults within the switchgear. The Square D Arc Terminator from Schneider Electric offers
ZONE SELECTIVE INTERLOCKING (ZSI) APPLICATION AND TESTING GUIDE SIEMENS WL UL489 AND UL1066 AIR CIRCUIT BREAKERS
Definition: Zone Selective Interlocking (ZSI) - A method which allows two or more ground fault breakers to communicate with each other so that a short circuit or ground fault will be cleared by the breaker
Electrical Distribution Services for Mining and Metals Industries
Electrical Distribution Services for Mining and Metals Industries Solutions to help maximize plant reliability and ensure personnel safety Make the most of your energy SM Electrical Systems are Serious
Mitigation of Arc-Flash Hazards and Reduction of Costs by Selective Arc-Flash Protection
Mitigation of Arc-Flash Hazards and Reduction of Costs by Selective Arc-Flash Protection L. Kumpulainen, S. Dahl J. Ma Vamp Ltd, Finland Vamp Ltd, China 1 ABSTRACT This paper describes causes and characteristics
ARC FLASH HAZARD OVERVIEW. Presented August 13, 2015 WWOA Lake Michigan District by Mead & Hunt, Inc.
ARC FLASH HAZARD OVERVIEW Presented August 13, 2015 WWOA Lake Michigan District by Mead & Hunt, Inc. ARC FLASH EXPERIENCE Christopher J. DeWaal, MS, MEM, PE, LEED AP, HACCP How did I get involved? A client
4160: THE GREEN 480 MEDIUM VOLTAGE ELECTRICAL SYSTEMS
4160: THE GREEN 480 MEDIUM VOLTAGE ELECTRICAL SYSTEMS for DATA CENTERS Michael Mosman, PE Chief Technical Officer CCG Facilities Integration Incorporated FACILITIES INTEGRATION INCORPORATED MEDIUM VOLTAGE
Paralleling Switchgear
Paralleling Switchgear By Maurice D Mello, P.Eng. Systems Engineer, GE Consumer & Industrial, Canada What is Paralleling? Paralleling is the operation in which multiple power sources, usually two or more
What s up with Arc Flash?
What s up with Arc Flash? Presented by Mark Haskins, CSP Practical Safety Solutions, LLC CONN OSHA Breakfast Roundtable February 18, 2014 2014 Practical Safety Solutions, LLC What is Arc Flash? Definition
IMPLEMENTING THE NEW ELECTRICAL SAFETY REQUIREMENTS
IMPLEMENTING THE NEW ELECTRICAL SAFETY REQUIREMENTS Paul A Zoubek, CSP, CIH Occupational Services, Inc. San Diego, CA 619-861 861-0612 [email protected] OCCUPATIONAL SERVICES, INC. BACKGROUND Update Update
Common Electrical Hazards in the Workplace Including Arc Flash. Presented by Ken Cohen, PhD, PE & CIH (Ret.)
Common Electrical Hazards in the Workplace Including Arc Flash Presented by Ken Cohen, PhD, PE & CIH (Ret.) 1 What s New In February 1972, OSHA incorporated the 1971 edition of the National Fire Protection
Protection Considerations to Mitigate Arc-Flash Hazards
1 Protection Considerations to Mitigate Arc-Flash Hazards echnical Report to the Substation Subcommittee of the Power Systems Relaying Committee Working Group: Chair: K. Zimmerman, Vice Chair: R.A. Hedding,
Management Systems 10 Electrical Safety Audit 14 PPE 20 Arc Mitigation 22 Hazard Assessment 26
Management Systems 10 Electrical Safety Audit 14 PPE 20 Arc Mitigation 22 Hazard Assessment 26 Assessing The Hazards Of High and Low Voltage Single-Phase Arc-Flash By Albert Marroquin One common question
MEDIUM VOLTAGE. Michael Mosman, PE. CCG Facilities Integration Incorporated FACILITIES INTEGRATION INCORPORATED
MEDIUM VOLTAGE ELECTRICAL SYSTEMS for DATA CENTERS Michael Mosman, PE Chief Technical Officer CCG Facilities Integration Incorporated FACILITIES INTEGRATION INCORPORATED CCG Facilities Integration Incorporated
NFPA 70E Updates Affect Your Most Valuable Assets
NFPA 70E Updates Affect Your Most Valuable Assets EXECUTIVE SUMMARY Electrocution is a well-known hazard associated with direct contact with electrical energy. According to the U.S. Department of Labor,
CIRCUIT BREAKER INTERRUPTING CAPACITY AND SHORT-TIME CURRENT RATINGS
CIRCUIT BREAKER INTERRUPTING CAPACITY AND SHORT-TIME CURRENT RATINGS David D. Roybal, P.E. Senior Member, IEEE Eaton Electrical 3697 Mount Diablo Boulevard Lafayette, CA 94549 Abstract Low-voltage circuit
OSHA & ARC FLASH HAZARD ANALYSIS
OSHA & ARC FLASH HAZARD ANALYSIS Impact of Revisions to the OSHA Electrical Safety Regulations Presented by: John J. Kolak, MS, CSP Introduction Important Definitions Understanding OSHA Applicable standards
SPECIAL TOPICS ON GROUND FAULT PROTECTION AND PROTECTION COORDINATION IN INDUSTRIAL AND COMMERCIAL POWER SYSTEMS
SPECIAL TOPICS ON GROUND FAULT PROTECTION AND PROTECTION COORDINATION IN INDUSTRIAL AND COMMERCIAL POWER SYSTEMS Claudio S. Mardegan [email protected] www.engepower.com Phone: 55 3579-8777
Arc Flash Safety in 400V Data Centers
Arc Flash Safety in 400V Data Centers Strategies for protecting employees from underappreciated yet potentially deadly hazards By Dave G. Loucks PCM Solution Manager Eaton Corporation Executive summary
Low Voltage Transformer Through-Fault Protection: A System Approach
Data Bulletin 7400DB1001 Nashville, TN USA Low Voltage Transformer Through-Fault Protection: A System Approach Introduction Low Voltage Transformer Protection Criteria NEC Article 450 Transformers and
Fault Characteristics in Electrical Equipment
1. Introduction Proper design and installation of electrical equipment minimizes the chance of electrical faults. Faults occur when the insulation system is compromised and current is allowed to flow through
Bypass transfer switch mechanisms
Power topic #6013 Technical information from Cummins Power Generation transfer switch mechanisms > White paper By Gary Olson, Director, Power Systems Development This paper describes the configuration
Arc Flash Avoidance and its Application to Overhead Traveling Cranes
Arc Flash Avoidance and its Application to Overhead Traveling Cranes Whitepaper August 2012 Jason Wellnitz, Controls Product Manager Material Handling Numerous technical papers, bulletins, magazine articles
Extend the Life of Existing Switchgear
Extend the Life of Existing Switchgear January 2011/1910DB1002 by Hal Theobald, Product Manager Schneider Electric USA, Inc. Make the most of your energy SM Summary Introduction... p 3 Maintenance Requirements...
Data Bulletin. Circuit Breaker Characteristic Trip Curves and Coordination Class 0600 TRIP CURVES AND COORDINATION CIRCUIT BREAKER TRIP CURVES
Data Bulletin Bulletin No. 000DB0 August 0 Cedar Rapids, IA, USA Class 000 TRIP CURVES AND COORDINATION CIRCUIT BREAKER TRIP CURVES Thermal Tripping Characteristics agnetic Tripping Characteristics A coordination
2004 TRANSMISSION SYSTEMS SEMINAR MEDIUM VOLTAGE, METAL-CLAD ARC RESISTANT SWITCHGEAR: ENHANCING WORKPLACE SAFETY
2004 TRANSMISSION SYSTEMS SEMINAR MEDIUM VOLTAGE, METAL-CLAD ARC RESISTANT SWITCHGEAR: ENHANCING WORKPLACE SAFETY Thomas P. McNamara, P.E. Manager, Development Engineering ABB Inc. Power Technologies Medium
Permissible ambient temperature Operation Storage, transport
The Sitras PRO combined DC protective unit and controller is used in the power supply for DC railways in mass transit and main-line systems up 3,000 V DC. It protects DC switch gear and contact line systems
Alternate Methods to Short Circuit Breaker Coordination
Alternate Methods to Short Circuit Breaker Coordination Nguyen Perez, PE Senior Electrical Engineer 2600 Douglas Road, Suite 301 Coral Gables, Florida 305.529.1515 (p) www.brplusa.com Importance in Healthcare
HAZARDS, INCLUDING SHOCK, ARC FLASH AND FIRE
Appendix B-2 - Electrical Safety In Design Final Report TECHNOLOGIES THAT REDUCE LIKELIHOOD OF INJURY FROM ELECTRICAL HAZARDS, INCLUDING SHOCK, ARC FLASH AND FIRE The following are technologies that reduce
Proper Application of 415V Systems in North American Data Centers. A White Paper from the Experts in Business-Critical Continuity
Proper Application of 415V Systems in North American Data Centers A White Paper from the Experts in Business-Critical Continuity Introduction Increasing pressure to reduce operating expenses and be more
Fortune Oregon Data Center Increases Reliability with a High Resistance Grounding System
Fortune Oregon Data Center Increases Reliability with a High Resistance Grounding System Cory David Smith, Project Manager, ECOM Engineering Inc., and David Lawrence Smith, Principal, ECOM Engineering
Understanding 2015 Changes to NFPA 70E Safety-related work practices and maintenance requirements mandate more robust electrical safety programs for
Understanding 2015 Changes to NFPA 70E Safety-related work practices and maintenance requirements mandate more robust electrical safety programs for data centers Executive Summary Every three years, the
Engineering innovation
Eaton's Electrical Engineering Services & Systems Solutions Focus Seamless Solutions for Reliable, Efficient and Safe Power Systems Engineering innovation Progressive solutions for today s power systems
Integrating SPDs in Switchgear & Switchboards Causes More Problems than it Solves
Integrating SPDs in Switchgear & Switchboards Causes More Problems than it Solves White Paper July 2010 Integrating surge protective devices (SPD) into distribution equipment (i.e. switchgear, switchboards,
Short Circuit Current Calculations
Introduction Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective devices based on these sections mandate that
Electronic Trip Circuit Breaker Basics Circuit Breaker Application Guide Class 0600
Electronic Trip Circuit Breaker Basics Circuit Breaker Application Guide Class 0600 Data Bulletin 0600DB1104 03/2012 Retain for future use. Electronic Trip Circuit Breaker Basics 0600DB1104 Table of Contents
Switchgear Capabilities. NexGear is a Division of PowerSecure NASDAQ: POWR
Switchgear Capabilities NexGear is a Division of PowerSecure NASDAQ: POWR Discussion Points Introducing PowerSecure Introducing NexGear Solutions Offered Scope of Services Examples of Work Q & A NexGear,
2008 Eaton Corporation. All rights reserved.
FlashGard TM Motor Control Center Electrical Safety Hazards Design Philosophy The Product 2008 Eaton Corporation. All rights reserved. Research studies say. Five to 10 arc flash explosions occur in electrical
Analyzing Electrical Hazards in the Workplace
Analyzing Electrical Hazards in the Workplace By Dennis K. Neitzel, CPE AVO Training Institute, Inc. The need for analyzing electrical hazards in the workplace has been recognized by a small segment of
Medium voltage VCP-W MR2 (integral racking)
Supersedes March 2013 Contents Description Page Notices and warnings...................... 2 Introduction.............................. 3 Breaker pan configurations.................. 3 Inspection/maintenance.....................
New standardized approach to arc flash protection
New standardized approach to arc flash protection Samuel Dahl Juha Arvola Tero Virtala Arcteq Relays Ltd Arcteq Relays Ltd Arcteq Relays Ltd Wolffintie 36 F 11 Wolffintie 36 F 11 Wolffintie 36 F11 65200
Submit shop drawings for equipment provided under this section Shop drawings shall indicate:
Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,
The following components are common to most cubicles; this example is an ABB HK cubicle.
4.0 CIRCUIT BREAKER CUBICLE Learning Objectives The circuit breaker cubicle is the component of the switchgear that holds the circuit breaker, and the controls and cabling for the distribution system.
Demystifying arc flash hazard management
Demystifying arc flash hazard management Presented by Matt Brazier Senior Electrical Engineer Gove Operations November 2013 Standard NFPA 70E IEEE 1584 AS/NZS 4836 TERMINOLOGY Arc arc flash hazard analysis
Fusible Disconnect Switch
Circuit Breakers Circuit breakers are used in panelboards and switchboards to provide circuit protection and provide a means of energizing and de-energizing a circuit. Siemens Sentron molded case circuit
Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer
Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer A Short Circuit analysis is used to determine the magnitude of short
Mission Critical Data Center Systems
Mission Critical Systems Mission Critical/ Electrical Distribution Systems Data center electrical distribution designs are rapidly evolving, driven by needs such as increasing power densities, energy efficiency,
How To Choose A Transformer
Consider open loop MV network as an example source 1 source 2 NC NC NC or NO main MV switchboard A B Detail design of substation NC NC NC NO NC NC switchboard 1 switchboard 2 switchboard 3 MV MV MV LV
Eaton s Electrical Services & Systems. Technical Training Safety Training
Eaton s Electrical Services & Systems Technical Training Safety Training 2 EATON CORPORATION Eaton s Electrical Services & Systems Technical Training Safety Training Eaton conducts technical training and
Marcelo Valdes, PE, Steve Hansen, and Dr. Peter Sutherland, PE. Ferraz Shawmut, LLC 374 Merrimac Street Newburyport, MA 01950-1998 USA
Optimizing Circuit Breaker nstantaneous Trip Settings for Selectivity and Arc Flash Performance Simultaneously Copyright Material EEE Paper No. ESW2010-20 Marcelo Valdes, PE, Steve Hansen, and Dr. Peter
Houston Service Center Medium Voltage Service and Aftermarket Solutions
Houston Service Center Medium Voltage Service and Aftermarket Solutions Table of contents Introduction...3 Breaker refurbishment...4 Protective relay & control service and support...5 Power Service and
Instruction Bulletin. MCS025 Sync-Check Module Installation Sheet
Instruction Bulletin 63230-216-244B1 LaVergne, TN, USA MCS025 Sync-Check Module Installation Sheet Retain for future use. DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Only qualified electrical
MEDIUM VOLTAGE SUBSTATION PRACTICES Medium Voltage (MV) is defined as: 1000V< MV 44kV
MEDIUM VOLTAGE SUBSTATION PRACTICES MEDIUM VOLTAGE SUBSTATION PRACTICES Medium Voltage (MV) is defined as: 1000V< MV 44kV MEDIUM VOLTAGE SUBSTATION PRACTICES This presentation covers some safety aspects
Low Voltage Circuit Breakers. Arc flash hazards
Low Voltage Circuit Breakers Arc flash hazards Index Low voltage selectivity with ABB circuit breakers Introduction... 2 Definitions, acronyms and terms used... 3 Electrical arcs and their dangerous effects
Typical Data Requirements Data Required for Power System Evaluation
Summary 66 Carey Road Queensbury, NY 12804 Ph: (518) 792-4776 Fax: (518) 792-5767 www.nepsi.com [email protected] Harmonic Filter & Power Capacitor Bank Application Studies This document describes NEPSI
Arc Protection Relay REA 101. Operator s Manual
Arc Protection Relay 1MRS751003-MUM Issued: 08.04.1998 Version: F/23.06.2005 Arc Protection Relay 1. About this manual...5 1.1. Copyrights...5 1.2. Trademarks...5 1.3. Guarantee...5 1.4. General...5 1.5.
INTRODUCTION ARC FLASH PROTECTION AND SAFETY MEASURES. September 2010
ARC FLASH PROTECTION AND SAFETY MEASURES September 2010 Introduction Hazards of Electrical Energy Electrical Safety Program Safety-Related Work Practices Electrical Safety Procedures Presented By: Ken
Electrical Safety in the Marine Environment
January 3, 2001 TEHNIAL BULLETIN 010 Electrical Safety in the Marine Environment Approach Boundaries Electrical Safety in the Marine Environment presented by adick orporation 1 Overview Electrical power